36C24418Q9698-001.doc
DOC document 33 KB Posted
- Solicitation number
- 36C24418Q9698
About this file
36C24418Q9698 Attach 01 SOW--Fuel Cleaning Underground Tanks.doc
View the file
Other files
| File | Type | Posted |
|---|---|---|
| -15354.docx | DOCX document | |
| 36C24418Q9698-0001000.docx | DOCX document | |
| 36C24418Q9698-004.pdf | ||
| 36C24418Q9698-000.docx | DOCX document | |
| 36C24418Q9698-003.pdf | ||
| 36C24418Q9698-002.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK FOR
FUEL CLEANING UNDERGROUND TANK SERVICES AT
LEBANON VA MEDICAL CENTER
1700 SOUTH LINCOLN AVENUE
LEBANON, PA
17042-7529
A. GENERAL GUIDANCE
1. Title of Project: Fuel Cleaning Underground Tanks
2. Scope of Work: IN ACCORDANCE WITH THE FOLLOWING SPECIFICATIONS:
2.1 Provide all labor, materials, equipment, supervision, and quality assurance necessary to perform a service contract for fuel maintenance on the following underground storage tanks (UST), in accordance with the following specifications:
2.1.1 Diesel tank number 13, which has a capacity of 1,500 gallons IAW SOW Para. A
2.1.2 Diesel tank number 16, which has a capacity of 1,500 gallons IAW SOW Para. A
2.1.3 Diesel tank number 17, which has a capacity of 1,500 gallons IAW SOW Para. A
2.1.4 Diesel tank number 18, which has a capacity of 3,000 gallons IAW SOW Para. A
2.1.5 Diesel tank number 20, which has a capacity of 2,000 gallons IAW SOW Para. A
2.1.6 Number 2 fuel oil tank numbers 21, which has a capacity of 25,000 gallons IAW SOW Para. A
2.1.7 Number 2 fuel oil tank numbers 22, which has a capacity of 25,000 gallons IAW SOW Para. A
2.1.8 Number 2 fuel oil tank numbers 23, which has a capacity of 25,000 gallons IAW SOW Para. A
2.1.9 Diesel tank number 24, which has a capacity of 10,000 gallons IAW SOW Para. A
2.1.10 Diesel tank number 25, which has a capacity of 13,000 gallons IAW SOW Para. A
2.1.11 Seven – 150 gallon Day Tanks. Tanks are located at Buildings 1/ 2ea, 2, 10, 18, 19, 104
2.2 Maintenance required on each of the above listed UST:
2.2.1 Remove / dispose of properly, all built up contamination, which can include but is not limited to the following: water, sediment, gums, microbes, and oxidized fuel.
2.2.2 Perform tank bottom cleaning via a high velocity recirculation system.
2.2.3 Install treatment of biocide to kill bacteria and microorganisms.
2.2.4 Provide testing before and after cleaning to document the fuel cleaning. Fuel undissolved solids maximum limit is 24 mg/kg (Test Methods – ASTM D6217, EN 12662) and maximum water content is 200 mg/kg (Test Methods – ASTM D6304, EN ISO 12937).
2.2.5 Provide a written report of all findings to below noted contact prior to invoicing.
2.2.6 Perform above services in accordance with any applicable National Fire Protection Association (NFPA) regulations, and any other applicable regulations.
2.2.7 Coordinate above services with the Contracting Officer Representative.
3. Performance Period is one (1) Base Year and four (4) Option Years
File details come from the government source that posted it.