ELECTRICAL TESTING

AND

MAINTENANCE

For

Altoona, PA Solicitation Number VA-244-13-R-0065

Testing and Inspection of Electrical Switchgear James E. Vanzandt VA Medical Center

Completed by

Great Lakes Power Services, Inc.

P.O. Box 97 - 330 N. Huron Road

Linwood MI 48634 Phone (989) 697-3023 Fax (989) 697-3050

Email: glpower@att.net

3/14/2013 1

Great Lakes Power Services, Inc.

P.O. Box 97 - 330 N. Huron Road

Linwood MI 48634 Phone (989) 697-3023 Fax (989) 697-3050

Email: glpower@att.net

EXECUTIVE SUMMARY

for James E. Vanzandt VA Medical Center

Altoona, PA Solicitation Number VA-244-13-R-0065

Testing and Inspection of Electrical Switchgear

OVERVIEW

This Executive Summary was prepared by Jim DiGiovanni, President of Great Lakes Power.

Electrical maintenance and testing is performed at periodic intervals in order to reduce or prevent equipment failure resulting in an interruption of electrical service. Electrical maintenance will help minimize hazards to one’s life and to equipment resulting from failure of equipment when it is not properly maintained.

Electrical maintenance has been performed at the James E. Vanzandt VA Medical Center performed over February and March, 2013

Maintenance, testing, and infrared scanning of electrical equipment has been performed for the entire facility. The three main incoming circuit breakers for the facility were meggered, ductored, Hi-potted and inspected. The associated protective relays for the facility were tested and calibrated in accordance of manufacturers recommendations. All main circuit breakers for the facility were secondary current injected on all three phases, meggered, ductored, tested, and visually inspected. All other feeder circuit breakers on switchboards for the facility were meggered, ductored, and visually inspected. Motor Control Centers for the facility were megger tested. Infrared scanning was also performed on all panels for the facility.

SUMMARY

• Electrical Maintenance – No Problems were found in the mechanical or electrical operation of any of the equipment tested

• Results of the infra-red testing revealed that the highest temperature was 105.5o F and is an indication of only a nearly fully loaded circuit breaker. The hard copy for this report is shown below. This panel, along with 264 images were taken, reviewed and are available

3/14/2013 2 in electronic form. These images are in .jpg format and can be viewed with any computer. They are also included in the .pdf copy and located within this report. In addition, software has also been provided that will allow for further review of images.

This software will allow the user to manipulate the image and determine the temperature anywhere on it.

• Oil sample reports-Transformer oil analysis is a process in which transformer oil is analyzed in a lab. The presences of different chemicals are indications of possible trouble within the transformer itself. As this is an excellent diagnostic tool and relatively inexpensive, it is recommended to test all transformers on an annual basis. Upon completion of the samples taken, the following conditions are present within the oil transformers.

o Bldg 4 shows a significant level of acetylene in the sample. Acetylene is a byproduct of arcing occurring within the transform itself. It is recommended that this transformer opened and internal connections checked. However, it would be more cost effective to simply replace this transformer. It is only a 10 kva and located in a small room in the back of the garage. Therefore, it could be replaced with a dry type transformer which would be a cost reduction vs. an oil filled transformer of the same rating.

o Bldg 7 also shows some acetylene as well, but at a much lower level. This sample should be retaken in 3 months to insure that the level of acetylene does not increase; an indication of ongoing arcing issues within the transformer itself.

3/14/2013 3 o Transformer feeding rehab shows a slight elevation of moisture present within the oil. At this time it is of no concern, but should be compared to the next oil sample taken to be sure of no increase.

o Gas analysis shows the presence of carbon monoxide and carbon dioxide within transformers for TR-AC, TR-1, TR-2, BLDG 4, and BLDG 7. Carbon monoxide and Carbon dioxide are byproducts of cellulose insulation (paper) beginning to break down due to overheating. All these transformers show a level 2 condition with the worse level to a level 4. This result is pretty normal with transformers that have load on them, increasing over time. It is recommended to re-test in 3 months to determine the rate at which these chemicals are increasing.

COMPLIANCE WITH NFPA 70E 2012 – ELECTRICAL SAFETY

Federal OSHA has announced that inspectors in all ten OSHA regions have received training in the 2012 version of the NFPA 70E Standard. Section 110.3 Electrical Safety Program, outlines the key elements of an overall electrical safety program. Specifically, Section 110.3(H) is a new section for 2012 that requires employers to have their electrical safety programs audited by a qualified professional at intervals not exceeding three years. This section reads as follows:

NFPA 70E 2012, 110.3(H) Electrical Safety Auditing.

(1) Electrical Safety Program. The electrical safety program shall be audited to verify the principles and procedures of the electrical safety program are in compliance with this standard. The frequency of the audit shall not exceed 3 years.

(2) Field Work. Field work shall be audited to verify the requirements contained in the procedures of the electrical safety program are being followed. When the auditing determines that the principles and procedures of the electrical safety program are not being followed, the appropriate revisions to the training program or revisions to the procedures shall be made.

(3) Documentation. The audit shall be documented.

Dated March 15, 2013

James J. DiGiovanni

President of Great Lakes Power

3/14/2013 4

PRIMARY SWITCHOUSE

3/14/2013 5

564 S HURON Great Lakes Power Services

LINWOOD, MI 48634 MED VOLTAGE CIRCUIT BREAKER TEST REPORT PH. 989-697-3023

CUSTOMER: Altoona VA DATE: 3-2-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 62935 Sub# Primary DESIGNATION:

MFG Square D TYPE: DSE-65 RATED AMPS: 1200 RATED VOLTS: 15kv

(REMOVED) CUBMAIN (RETURNED) CUB. MAIN TECH: TMB

OPERATOR TYPE COUNTER 271 SOLONOID STORED ENERGY X

REBUILD TEST ONLY X REPAIR

INSPECTION AND MAINTENANCE

BREAKER PART GOOD FAIR POOR COMMENTS

ARC CHUTE X

BUSHINGS X

FINGER CLUSTER X

ARCING CONTACTS X

MAIN CONTACTS X

CONTACT WIPE X

CONTACT SEQUENCE X

CONTACT ALIGNMENT X

CONTROL WIRING X

OPERATING MECH. X

CUBICLE CLEANED XX LUBRICATION XX

CUBICLE HEATERS XX HARDWARE TIGHTENED XX

ELECTRICAL CHECKS

INSULATION RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+

HI-POTENTIAL TEST TESTED @ 30 KV

LEAKAGE IN MICRO-AMPS

BREAKER CLOSED A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

LEAKAGE 0.03 0.03 0.03 0.03 0.02 0.02

BREAKER OPEN A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

LEAKAGE (FRONT/TOP) 0.02 0.02 0.02

LEAKAGE (BACK/BOTTOM)

CONTACT RESISTANCE (MICRO-OHMS)

A B C

AS LEFT 38 48 44

ELECTRICAL OPERATION TEST AND CONTROL VOLTAGES

CLOSING COIL OK CHARGING MOTOR XX

TRIP COIL OK AUXILARY SWITCHES XX

CLOSING SOLONOID N/A RELAEY TRIP CIRCUIT N/A

Other comments:

3/14/2013 6

CUSTOMER: Altoona VA DATE: 3-2-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 62934 Sub# Primary DESIGNATION:

MFG Square D TYPE: DSE-65 RATED AMPS: 1200 RATED VOLTS: 15kv

(REMOVED) CUBF1 (RETURNED) CUB. F1 TECH: TMB

OPERATOR TYPE COUNTER 316 SOLONOID STORED ENERGY X

REBUILD TEST ONLY X REPAIR

INSPECTION AND MAINTENANCE

BREAKER PART GOOD FAIR POOR COMMENTS

ARC CHUTE X

BUSHINGS X

FINGER CLUSTER X

ARCING CONTACTS X

MAIN CONTACTS X

CONTACT WIPE X

CONTACT SEQUENCE X

CONTACT ALIGNMENT X

CONTROL WIRING X

OPERATING MECH. X

CUBICLE CLEANED XX LUBRICATION XX

CUBICLE HEATERS XX HARDWARE TIGHTENED XX

ELECTRICAL CHECKS

INSULATION RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+

HI-POTENTIAL TEST TESTED @ 30 KV

LEAKAGE IN MICRO-AMPS

BREAKER CLOSED A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

LEAKAGE 0.02 0.02 0.02 0.02 0.03 0.03

BREAKER OPEN A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

LEAKAGE (FRONT/TOP) 0.04 0.04 0.04

LEAKAGE (BACK/BOTTOM)

CONTACT RESISTANCE (MICRO-OHMS)

A B C

AS LEFT 36 38 39

ELECTRICAL OPERATION TEST AND CONTROL VOLTAGES

CLOSING COIL OK CHARGING MOTOR XX

TRIP COIL OK AUXILARY SWITCHES XX

CLOSING SOLONOID N/A RELAEY TRIP CIRCUIT N/A

3/14/2013 7

CUSTOMER: Altoona VA DATE: 3-2-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 63034 Sub# Primary DESIGNATION:

MFG Square D TYPE: DSE-65 RATED AMPS: 1200 RATED VOLTS: 15kv

(REMOVED) CUBF2 (RETURNED) CUB. F2 TECH: TMB

OPERATOR TYPE COUNTER 294 SOLONOID STORED ENERGY X

REBUILD TEST ONLY X REPAIR

INSPECTION AND MAINTENANCE

BREAKER PART GOOD FAIR POOR COMMENTS

ARC CHUTE X

BUSHINGS X

FINGER CLUSTER X

ARCING CONTACTS X

MAIN CONTACTS X

CONTACT WIPE X

CONTACT SEQUENCE X

CONTACT ALIGNMENT X

CONTROL WIRING X

OPERATING MECH. X

CUBICLE CLEANED XX LUBRICATION XX

CUBICLE HEATERS XX HARDWARE TIGHTENED XX

ELECTRICAL CHECKS

INSULATION RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+

HI-POTENTIAL TEST TESTED @ 30 KV

LEAKAGE IN MICRO-AMPS

BREAKER CLOSED A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

LEAKAGE 0.02 0.02 0.02 0.02 0.02 0.02

BREAKER OPEN A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

LEAKAGE (FRONT/TOP) 0.03 0.03 0.03

LEAKAGE (BACK/BOTTOM)

CONTACT RESISTANCE (MICRO-OHMS)

A B C

AS LEFT 52 49 52

ELECTRICAL OPERATION TEST AND CONTROL VOLTAGES

CLOSING COIL OK CHARGING MOTOR XX

TRIP COIL OK AUXILARY SWITCHES XX

CLOSING SOLONOID N/A RELAEY TRIP CIRCUIT N/A

3/14/2013 8

300 N. HURON Great Lakes Power Services

LINWOOD, MI 48634 OVERCURRENT RELAY TEST REPORT PH. 989-697-3023

CUSTOMER: VA ALTOONA DATE: 3/2/13 GLP ID#: JOB #:

LOCATION: ALTOONA SERIAL NO: SUB #: 13800 VOLT DESIGNATION FEEDER F1

MFG BBC TYPE: 223T3242 51E EXT INVERSE RATED AMPS: RATED VOLTS:

GND/NEUT RELAY MF BBC GND/NEUT RELAY TYP22353242 51E EXT INVERSE TECH: JD

PHASE CT RATIO 250/5 GROUND CT RATIO 250/5 RELAYS TESTED AS FOUND: YES

PHASE PT RATIO GROUND PT RATIO COORDINATION STUDY PROVIDED: NO

RELAY SETTINGS & TEST INFORMATION

ICS INST TAP SETTING TIME DIAL

A B C G A B C G A B C G A B C G

SPECIFIED

AS FOUND

AS LEFT

TEST OPERATIONS- AS FOUND

TIMING ELEMENT INST ELEMENT ICS

TIME IN CYCLES CURRENT ELEMENT COMMENTS

PICK UP TIMING TCC TIME @ (CY) PICK DROP PICK DROP

AMPS 2X 3X 2X 3X UP OUT UP OUT

A-PHASE 5.0 3.24 1.18 3.2 1.15 N/A 1.5

B-PHASE 5.0 3.26 1.18 3.2 1.15 N/A 1.7

C-PHASE 5.0 3.19 1.16 3.2 1.15 N/A 1.7

GROUND 1.5 7.13 2.34 7.0 2.3 N/A

TEST OPERATIONS- AS LEFT

TIMING ELEMENT INST ELEMENT ICS

TIME IN CYCLES CURRENT ELEMENT COMMENTS

PICK UP TIMING TCC TIME @ (CY) PICK DROP PICK DROP

AMPS 2X 3X 2X 3X UP OUT UP OUT

A-PHASE

B-PHASE

C-PHASE

GROUND

COMMENTS INST CONNECTIONS NOT MADE AT RELAY CASE FOR GROUND OR PHASE RELAYS

N/A N/A N/A N/A 16 16 2 2 2 4

16 16

16 16 5 5 5 1.5

2 2 216 16 5 5 5 1.5

3/14/2013 9

CUSTOMER: VA ALTOONA DATE: 3/2/13 GLP ID#: JOB #:

LOCATION: ALTOONA SERIAL NO: SUB #: 13800 VOLT DESIGNATION FEEDER F2

MFG BBC TYPE: 223T3242 51E EXT INVERSE RATED AMPS: RATED VOLTS:

GND/NEUT RELAY MF BBC GND/NEUT RELAY TYP22353242 51E EXT INVERSE TECH: JD

PHASE CT RATIO 250/5 GROUND CT RATIO 250/5 RELAYS TESTED AS FOUND: YES

PHASE PT RATIO GROUND PT RATIO COORDINATION STUDY PROVIDED: NO

RELAY SETTINGS & TEST INFORMATION

ICS INST TAP SETTING TIME DIAL

A B C G A B C G A B C G A B C G

SPECIFIED

AS FOUND

AS LEFT

TEST OPERATIONS- AS FOUND

TIMING ELEMENT INST ELEMENT ICS

TIME IN CYCLES CURRENT ELEMENT COMMENTS

PICK UP TIMING TCC TIME @ (CY) PICK DROP PICK DROP

AMPS 2X 3X 2X 3X UP OUT UP OUT

A-PHASE 5.0 3.25 1.14 3.2 1.15 N/A

B-PHASE 5.0 3.24 1.18 3.2 1.15 N/A

C-PHASE 5.0 3.27 1.17 3.2 1.15 N/A

GROUND 1.5 7.09 2.29 7.0 2.3 N/A

TEST OPERATIONS- AS LEFT

TIMING ELEMENT INST ELEMENT ICS

TIME IN CYCLES CURRENT ELEMENT COMMENTS

PICK UP TIMING TCC TIME @ (CY) PICK DROP PICK DROP

AMPS 2X 3X 2X 3X UP OUT UP OUT

A-PHASE

B-PHASE

C-PHASE

GROUND

COMMENTS INST CONNECTIONS NOT MADE AT RELAY CASE FOR GROUND OR PHASE RELAYS

N/A N/A N/A N/A 16 16 2 2 2 4

16 16

16 16 5 5 5 1.5

2 2 216 16 5 5 5 1.5

3/14/2013 10

CUSTOMER: VA ALTOONA DATE: 3/2/13 GLP ID#: JOB #:

LOCATION: ALTOONA SERIAL NO: SUB #: 13800 VOLT DESIGNATION MAIN

MFG BBC TYPE: 223T3242 51E EXT INVERSE RATED AMPS: RATED VOLTS:

GND/NEUT RELAY MF BBC GND/NEUT RELAY TYP22353242 51E EXT INVERSE TECH: JD

PHASE CT RATIO 300/5 GROUND CT RATIO 300/5 RELAYS TESTED AS FOUND: YES

PHASE PT RATIO GROUND PT RATIO COORDINATION STUDY PROVIDED: NO

RELAY SETTINGS & TEST INFORMATION

ICS INST TAP SETTING TIME DIAL

A B C G A B C G A B C G A B C G

SPECIFIED

AS FOUND

AS LEFT

TEST OPERATIONS- AS FOUND

TIMING ELEMENT INST ELEMENT ICS

TIME IN CYCLES CURRENT ELEMENT COMMENTS

PICK UP TIMING TCC TIME @ (CY) PICK DROP PICK DROP

AMPS 2X 3X 2X 3X UP OUT UP OUT

A-PHASE 6.0 11.59 3.70 11.5 3.5 N/A

B-PHASE 6.0 11.62 3.65 11.5 3.5 N/A

C-PHASE 6.0 11.55 3.75 11.5 3.5 N/A

GROUND 2.0 17.41 .55 17.5 5.5 N/A

TEST OPERATIONS- AS LEFT

TIMING ELEMENT INST ELEMENT ICS

TIME IN CYCLES CURRENT ELEMENT COMMENTS

PICK UP TIMING TCC TIME @ (CY) PICK DROP PICK DROP

AMPS 2X 3X 2X 3X UP OUT UP OUT

A-PHASE

B-PHASE

C-PHASE

GROUND

COMMENTS INST CONNECTIONS NOT MADE AT RELAY CASE FOR GROUND OR PHASE RELAYS

N/A N/A N/A N/A 16 16 6 6 6 9

16 16

16 16 6 6 6 2

6 6 6 916 16 6 6 6 2

3/14/2013 11

Great Lakes Power Services

330 N. HURON OVERCURRENT RELAY TEST REPORT

LINWOOD, MI 48634 PH. 989-697-3023

MISC RELAY TEST REPORT

CUSTOMER: Altoona VA DATE: 3/2/2013

SUBSTATION NO: PRIMARY CUSTOMER DESIGNATION: 52-M MAIN

COORDINATION STUDY PROVIDED: NO RELAYS TESTED AS FOUND: YES

RELAY DEVICE INFORMATION

PHASE RELAY GROUND/NEUTRAL RELAY

MFG: ABB CIRCUIT SHIELD MFG:

TYPE: 27 STYLE 411R1175 TYPE:

APPLICATION: UNDERVOLTAGE APPLICATION:

C.T. RATIO: P.T. RATIO: C.T. RATIO: P.T. RATIO:

TEST SETTINGS AND INFORMATION-- A PHASE

AS FOUND SETTINGS

TAP @ 110 VOLTS

AS FOUND TIMING

TIMING @ 40% (44 VOLTS) - 16.75 SECONDS

TIMING @ 20% (22 VOLTS)- 13.96 SECONDS

TEST SETTINGS AND INFORMATION-- B PHASE

AS FOUND SETTINGS

TAP @ 110 VOLTS

AS FOUND TIMING

TIMING @ 40% (44 VOLTS) - 16.62 SECONDS

TIMING @ 20% (22 VOLTS)- 13.81 SECONDS

TEST SETTINGS AND INFORMATION-- C PHASE

AS FOUND SETTINGS

TAP @ 110 VOLTS

AS FOUND TIMING

TIMING @ 40% (44 VOLTS) - 16.84 SECONDS

TIMING @ 20% (22 VOLTS)- 13.98 SECONDS

3/14/2013 12

BLDG 1

MDS1 & MDS2

3/14/2013 13

330 N. HURON ROAD Great Lakes Power Services

LINWOOD, MI 48634 LOW VOLTAGE CIRCUIT BREAKER TEST REPORT PH. 989-697-3023

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301117003 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-3 (RETURNED) CUB. FDR-1 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 36 44 37 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

OTHER COMMENTS

3/14/2013 14

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116009 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600 (REMOVED) CUB: FDR-6 Spare (RETURNED) CUB. FDR-2 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 300 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 26 28 29 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 15

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116021 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600 (REMOVED) CUB: FDR-27-Spare (RETURNED) CUB. FDR-3 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 30 27 32 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 16

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116036 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-5 (RETURNED) CUB. FDR-4 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 31 33 35 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 17

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301115027 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600 (REMOVED) CUB: FDR-13-Spare (RETURNED) CUB. FDR-5 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 25 28 30 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 18

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 400130111601 SUB #: Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600 (REMOVED) CUB: FDR-15 (RETURNED) CUB. FDR-6 Spare TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x LTD 2 sec 2 sec

STPU 6x 1.5x STD 0.1 in 0.1 out INST max 1.5x GFPU A = 100Amp A = 100Amp GFD 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 48 38 36 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 19

CUSTOMER: Altoona VA DATE: 2-27-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116039 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-4 (RETURNED) CUB. FDR-7 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 26 34 37 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 20

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116020 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-14 (RETURNED) CUB. FDR-8 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 28 32 34 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 21

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301115028 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-1 (RETURNED) CUB. FDR-9 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 22 24 25 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 22

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116034 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-16 (RETURNED) CUB. FDR-10 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 300 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1.0x 1.0x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 39 28 37 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 23

CUSTOMER: Altoona VA DATE: 2-27-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116022 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-7 (RETURNED) CUB. FDR-11 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 300 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 26 28 33 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 24

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116037 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600 (REMOVED) CUB: FDR-25-Spare (RETURNED) CUB. FDR-12 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 300 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1.0x 1x LTD 2 sec 2 sec

STPU 6x 1.5x STD 0.1 in 0.1 out INST max 1.5x GFPU A = 100Amp A = 100Amp GFD 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 33 30 34 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 25

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301115042SUB #: Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600 (REMOVED) CUB: FDR-23 (RETURNED) CUB. FDR-13 Spare TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x LTD 2 sec 2 sec

STPU 6x 1.5x STD 0.1 out 0.1 out INST max 1.5x GFPU A = 100Amp A = 100Amp GFD 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD PRIMARY INJECTION

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE 100 100

B PHASE 100 100

C PHASE 100 100

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD 1200 8 12 8.79 8.63 8.66

STD 1200 0.07 0.18 0.10 0.10 0.10

INST 1200 0.01 0.05 0.05 0.05 0.05

GFD 400 0.07 0.18 0.11 0.11 0.11

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 78 80 82 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 26

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116033 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-2 (RETURNED) CUB. FDR-14 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 300 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 29 30 34 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 27

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301117002 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-22 (RETURNED) CUB. FDR-15 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1.0x 1.0x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU B=300Amp B=300Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 29 23 26 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 28

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116005 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-12 (RETURNED) CUB. FDR-12 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 300 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1.0x 1x LTD 2 sec 2 sec

STPU 6x 1.5x STD 0.1 in 0.1 out INST max 1.5x GFPU A = 100Amp A = 100Amp GFD 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 38 42 43 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 29

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301117001 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-17 (RETURNED) CUB. FDR-19 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 600 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU B B A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 26 30 29 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 30

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301117000 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-8 (RETURNED) CUB. FDR-18 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 26 30 27 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 31

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116038 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-17 (RETURNED) CUB. FDR-19 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 600 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 14 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 out 0.1 out INST max 12 1.5x GFPU B B A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 26 40 30 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 32

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301117007 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-9 (RETURNED) CUB. FDR-20 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 35 26 40 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 33

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116031 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-21 (RETURNED) CUB. FDR-17 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 300 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 6x STD 0.1 in 0.1 in 0.1 in INST max max max

GFPU B B B

GFD 0.2 out 0.2 out 0.2 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 57 66 69 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 34

CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116011 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-10 (RETURNED) CUB. FDR-22 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1.0x 1.0x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 32 31 33 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF BREAKER GOOD X FAIR POOR

CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT

3/14/2013 35

CUSTOMER: Altoona VA DATE: 2-27-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116024 Sub# Room 19 DESIGNATION:

MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600

(REMOVED) CUB: FDR-11 (RETURNED) CUB. FDR-22 TECH: TMB

STORED ENERGY X MANUAL X ELECTRICAL

REBUILD RETROFIT REPAIR TEST ONLY X

TRIP DEVICE INFORMATION

TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes

ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A

SETTINGS AS FOUND AS LEFT AS TESTED

LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec

STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out

BREAKER PERFORMANCE

TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection

PICK-UP LTPU STPU INST GFPU

VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT

A PHASE

B PHASE

C PHASE

SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE

LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK

INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN

(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C

AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+

CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)

A B C A B C

AS LEFT 35 25 32 AS LEFT

INSPECTION AND MAINTENANCE

ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X

ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A

MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X

RECOMMENDATIONS

TRIPS WITHIN SPECIFIED PARAMETERS YES X NO

GENERAL CONDITION OF…