36C24418Q9505-010.pdf
PDF 11 MB Posted
- Solicitation number
- 36C24418Q9505
About this file
36C24418Q9505 Attachment 010 Altoona complete test reports.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| -15293.docx | DOCX document | |
| 36C24418Q9505-0003000.docx | DOCX document | |
| 36C24418Q9505-0002000.docx | DOCX document | |
| 36C24418Q9505-0001000.docx | DOCX document | |
| 36C24418Q9505-001.doc | DOC document | |
| 36C24418Q9505-006.zip | ZIP file | |
| 36C24418Q9505-002.docx | DOCX document | |
| 36C24418Q9505-007.zip | ZIP file | |
| 36C24418Q9505-000.docx | DOCX document | |
| 36C24418Q9505-005.zip | ZIP file | |
| 36C24418Q9505-008.zip | ZIP file | |
| 36C24418Q9505-004.zip | ZIP file | |
| 36C24418Q9505-003.pdf | ||
| 36C24418Q9505-009.zip | ZIP file |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL TESTING
AND
MAINTENANCE
For
Altoona, PA Solicitation Number VA-244-13-R-0065
Testing and Inspection of Electrical Switchgear James E. Vanzandt VA Medical Center
Completed by
Great Lakes Power Services, Inc.
P.O. Box 97 - 330 N. Huron Road
Linwood MI 48634 Phone (989) 697-3023 Fax (989) 697-3050
Email: glpower@att.net
3/14/2013 1
Great Lakes Power Services, Inc.
P.O. Box 97 - 330 N. Huron Road
Linwood MI 48634 Phone (989) 697-3023 Fax (989) 697-3050
Email: glpower@att.net
EXECUTIVE SUMMARY
for James E. Vanzandt VA Medical Center
Altoona, PA Solicitation Number VA-244-13-R-0065
Testing and Inspection of Electrical Switchgear
OVERVIEW
This Executive Summary was prepared by Jim DiGiovanni, President of Great Lakes Power.
Electrical maintenance and testing is performed at periodic intervals in order to reduce or prevent equipment failure resulting in an interruption of electrical service. Electrical maintenance will help minimize hazards to one’s life and to equipment resulting from failure of equipment when it is not properly maintained.
Electrical maintenance has been performed at the James E. Vanzandt VA Medical Center performed over February and March, 2013
Maintenance, testing, and infrared scanning of electrical equipment has been performed for the entire facility. The three main incoming circuit breakers for the facility were meggered, ductored, Hi-potted and inspected. The associated protective relays for the facility were tested and calibrated in accordance of manufacturers recommendations. All main circuit breakers for the facility were secondary current injected on all three phases, meggered, ductored, tested, and visually inspected. All other feeder circuit breakers on switchboards for the facility were meggered, ductored, and visually inspected. Motor Control Centers for the facility were megger tested. Infrared scanning was also performed on all panels for the facility.
SUMMARY
• Electrical Maintenance – No Problems were found in the mechanical or electrical operation of any of the equipment tested
• Results of the infra-red testing revealed that the highest temperature was 105.5o F and is an indication of only a nearly fully loaded circuit breaker. The hard copy for this report is shown below. This panel, along with 264 images were taken, reviewed and are available
3/14/2013 2 in electronic form. These images are in .jpg format and can be viewed with any computer. They are also included in the .pdf copy and located within this report. In addition, software has also been provided that will allow for further review of images.
This software will allow the user to manipulate the image and determine the temperature anywhere on it.
• Oil sample reports-Transformer oil analysis is a process in which transformer oil is analyzed in a lab. The presences of different chemicals are indications of possible trouble within the transformer itself. As this is an excellent diagnostic tool and relatively inexpensive, it is recommended to test all transformers on an annual basis. Upon completion of the samples taken, the following conditions are present within the oil transformers.
o Bldg 4 shows a significant level of acetylene in the sample. Acetylene is a byproduct of arcing occurring within the transform itself. It is recommended that this transformer opened and internal connections checked. However, it would be more cost effective to simply replace this transformer. It is only a 10 kva and located in a small room in the back of the garage. Therefore, it could be replaced with a dry type transformer which would be a cost reduction vs. an oil filled transformer of the same rating.
o Bldg 7 also shows some acetylene as well, but at a much lower level. This sample should be retaken in 3 months to insure that the level of acetylene does not increase; an indication of ongoing arcing issues within the transformer itself.
3/14/2013 3 o Transformer feeding rehab shows a slight elevation of moisture present within the oil. At this time it is of no concern, but should be compared to the next oil sample taken to be sure of no increase.
o Gas analysis shows the presence of carbon monoxide and carbon dioxide within transformers for TR-AC, TR-1, TR-2, BLDG 4, and BLDG 7. Carbon monoxide and Carbon dioxide are byproducts of cellulose insulation (paper) beginning to break down due to overheating. All these transformers show a level 2 condition with the worse level to a level 4. This result is pretty normal with transformers that have load on them, increasing over time. It is recommended to re-test in 3 months to determine the rate at which these chemicals are increasing.
COMPLIANCE WITH NFPA 70E 2012 – ELECTRICAL SAFETY
Federal OSHA has announced that inspectors in all ten OSHA regions have received training in the 2012 version of the NFPA 70E Standard. Section 110.3 Electrical Safety Program, outlines the key elements of an overall electrical safety program. Specifically, Section 110.3(H) is a new section for 2012 that requires employers to have their electrical safety programs audited by a qualified professional at intervals not exceeding three years. This section reads as follows:
NFPA 70E 2012, 110.3(H) Electrical Safety Auditing.
(1) Electrical Safety Program. The electrical safety program shall be audited to verify the principles and procedures of the electrical safety program are in compliance with this standard. The frequency of the audit shall not exceed 3 years.
(2) Field Work. Field work shall be audited to verify the requirements contained in the procedures of the electrical safety program are being followed. When the auditing determines that the principles and procedures of the electrical safety program are not being followed, the appropriate revisions to the training program or revisions to the procedures shall be made.
(3) Documentation. The audit shall be documented.
Dated March 15, 2013
James J. DiGiovanni
President of Great Lakes Power
3/14/2013 4
PRIMARY SWITCHOUSE
3/14/2013 5
564 S HURON Great Lakes Power Services
LINWOOD, MI 48634 MED VOLTAGE CIRCUIT BREAKER TEST REPORT PH. 989-697-3023
CUSTOMER: Altoona VA DATE: 3-2-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 62935 Sub# Primary DESIGNATION:
MFG Square D TYPE: DSE-65 RATED AMPS: 1200 RATED VOLTS: 15kv
(REMOVED) CUBMAIN (RETURNED) CUB. MAIN TECH: TMB
OPERATOR TYPE COUNTER 271 SOLONOID STORED ENERGY X
REBUILD TEST ONLY X REPAIR
INSPECTION AND MAINTENANCE
BREAKER PART GOOD FAIR POOR COMMENTS
ARC CHUTE X
BUSHINGS X
FINGER CLUSTER X
ARCING CONTACTS X
MAIN CONTACTS X
CONTACT WIPE X
CONTACT SEQUENCE X
CONTACT ALIGNMENT X
CONTROL WIRING X
OPERATING MECH. X
CUBICLE CLEANED XX LUBRICATION XX
CUBICLE HEATERS XX HARDWARE TIGHTENED XX
ELECTRICAL CHECKS
INSULATION RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+
HI-POTENTIAL TEST TESTED @ 30 KV
LEAKAGE IN MICRO-AMPS
BREAKER CLOSED A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
LEAKAGE 0.03 0.03 0.03 0.03 0.02 0.02
BREAKER OPEN A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
LEAKAGE (FRONT/TOP) 0.02 0.02 0.02
LEAKAGE (BACK/BOTTOM)
CONTACT RESISTANCE (MICRO-OHMS)
A B C
AS LEFT 38 48 44
ELECTRICAL OPERATION TEST AND CONTROL VOLTAGES
CLOSING COIL OK CHARGING MOTOR XX
TRIP COIL OK AUXILARY SWITCHES XX
CLOSING SOLONOID N/A RELAEY TRIP CIRCUIT N/A
Other comments:
3/14/2013 6
CUSTOMER: Altoona VA DATE: 3-2-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 62934 Sub# Primary DESIGNATION:
MFG Square D TYPE: DSE-65 RATED AMPS: 1200 RATED VOLTS: 15kv
(REMOVED) CUBF1 (RETURNED) CUB. F1 TECH: TMB
OPERATOR TYPE COUNTER 316 SOLONOID STORED ENERGY X
REBUILD TEST ONLY X REPAIR
INSPECTION AND MAINTENANCE
BREAKER PART GOOD FAIR POOR COMMENTS
ARC CHUTE X
BUSHINGS X
FINGER CLUSTER X
ARCING CONTACTS X
MAIN CONTACTS X
CONTACT WIPE X
CONTACT SEQUENCE X
CONTACT ALIGNMENT X
CONTROL WIRING X
OPERATING MECH. X
CUBICLE CLEANED XX LUBRICATION XX
CUBICLE HEATERS XX HARDWARE TIGHTENED XX
ELECTRICAL CHECKS
INSULATION RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+
HI-POTENTIAL TEST TESTED @ 30 KV
LEAKAGE IN MICRO-AMPS
BREAKER CLOSED A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
LEAKAGE 0.02 0.02 0.02 0.02 0.03 0.03
BREAKER OPEN A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
LEAKAGE (FRONT/TOP) 0.04 0.04 0.04
LEAKAGE (BACK/BOTTOM)
CONTACT RESISTANCE (MICRO-OHMS)
A B C
AS LEFT 36 38 39
ELECTRICAL OPERATION TEST AND CONTROL VOLTAGES
CLOSING COIL OK CHARGING MOTOR XX
TRIP COIL OK AUXILARY SWITCHES XX
CLOSING SOLONOID N/A RELAEY TRIP CIRCUIT N/A
3/14/2013 7
CUSTOMER: Altoona VA DATE: 3-2-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 63034 Sub# Primary DESIGNATION:
MFG Square D TYPE: DSE-65 RATED AMPS: 1200 RATED VOLTS: 15kv
(REMOVED) CUBF2 (RETURNED) CUB. F2 TECH: TMB
OPERATOR TYPE COUNTER 294 SOLONOID STORED ENERGY X
REBUILD TEST ONLY X REPAIR
INSPECTION AND MAINTENANCE
BREAKER PART GOOD FAIR POOR COMMENTS
ARC CHUTE X
BUSHINGS X
FINGER CLUSTER X
ARCING CONTACTS X
MAIN CONTACTS X
CONTACT WIPE X
CONTACT SEQUENCE X
CONTACT ALIGNMENT X
CONTROL WIRING X
OPERATING MECH. X
CUBICLE CLEANED XX LUBRICATION XX
CUBICLE HEATERS XX HARDWARE TIGHTENED XX
ELECTRICAL CHECKS
INSULATION RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+ 5k+
HI-POTENTIAL TEST TESTED @ 30 KV
LEAKAGE IN MICRO-AMPS
BREAKER CLOSED A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
LEAKAGE 0.02 0.02 0.02 0.02 0.02 0.02
BREAKER OPEN A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
LEAKAGE (FRONT/TOP) 0.03 0.03 0.03
LEAKAGE (BACK/BOTTOM)
CONTACT RESISTANCE (MICRO-OHMS)
A B C
AS LEFT 52 49 52
ELECTRICAL OPERATION TEST AND CONTROL VOLTAGES
CLOSING COIL OK CHARGING MOTOR XX
TRIP COIL OK AUXILARY SWITCHES XX
CLOSING SOLONOID N/A RELAEY TRIP CIRCUIT N/A
3/14/2013 8
300 N. HURON Great Lakes Power Services
LINWOOD, MI 48634 OVERCURRENT RELAY TEST REPORT PH. 989-697-3023
CUSTOMER: VA ALTOONA DATE: 3/2/13 GLP ID#: JOB #:
LOCATION: ALTOONA SERIAL NO: SUB #: 13800 VOLT DESIGNATION FEEDER F1
MFG BBC TYPE: 223T3242 51E EXT INVERSE RATED AMPS: RATED VOLTS:
GND/NEUT RELAY MF BBC GND/NEUT RELAY TYP22353242 51E EXT INVERSE TECH: JD
PHASE CT RATIO 250/5 GROUND CT RATIO 250/5 RELAYS TESTED AS FOUND: YES
PHASE PT RATIO GROUND PT RATIO COORDINATION STUDY PROVIDED: NO
RELAY SETTINGS & TEST INFORMATION
ICS INST TAP SETTING TIME DIAL
A B C G A B C G A B C G A B C G
SPECIFIED
AS FOUND
AS LEFT
TEST OPERATIONS- AS FOUND
TIMING ELEMENT INST ELEMENT ICS
TIME IN CYCLES CURRENT ELEMENT COMMENTS
PICK UP TIMING TCC TIME @ (CY) PICK DROP PICK DROP
AMPS 2X 3X 2X 3X UP OUT UP OUT
A-PHASE 5.0 3.24 1.18 3.2 1.15 N/A 1.5
B-PHASE 5.0 3.26 1.18 3.2 1.15 N/A 1.7
C-PHASE 5.0 3.19 1.16 3.2 1.15 N/A 1.7
GROUND 1.5 7.13 2.34 7.0 2.3 N/A
TEST OPERATIONS- AS LEFT
TIMING ELEMENT INST ELEMENT ICS
TIME IN CYCLES CURRENT ELEMENT COMMENTS
PICK UP TIMING TCC TIME @ (CY) PICK DROP PICK DROP
AMPS 2X 3X 2X 3X UP OUT UP OUT
A-PHASE
B-PHASE
C-PHASE
GROUND
COMMENTS INST CONNECTIONS NOT MADE AT RELAY CASE FOR GROUND OR PHASE RELAYS
N/A N/A N/A N/A 16 16 2 2 2 4
16 16
16 16 5 5 5 1.5
2 2 216 16 5 5 5 1.5
3/14/2013 9
CUSTOMER: VA ALTOONA DATE: 3/2/13 GLP ID#: JOB #:
LOCATION: ALTOONA SERIAL NO: SUB #: 13800 VOLT DESIGNATION FEEDER F2
MFG BBC TYPE: 223T3242 51E EXT INVERSE RATED AMPS: RATED VOLTS:
GND/NEUT RELAY MF BBC GND/NEUT RELAY TYP22353242 51E EXT INVERSE TECH: JD
PHASE CT RATIO 250/5 GROUND CT RATIO 250/5 RELAYS TESTED AS FOUND: YES
PHASE PT RATIO GROUND PT RATIO COORDINATION STUDY PROVIDED: NO
RELAY SETTINGS & TEST INFORMATION
ICS INST TAP SETTING TIME DIAL
A B C G A B C G A B C G A B C G
SPECIFIED
AS FOUND
AS LEFT
TEST OPERATIONS- AS FOUND
TIMING ELEMENT INST ELEMENT ICS
TIME IN CYCLES CURRENT ELEMENT COMMENTS
PICK UP TIMING TCC TIME @ (CY) PICK DROP PICK DROP
AMPS 2X 3X 2X 3X UP OUT UP OUT
A-PHASE 5.0 3.25 1.14 3.2 1.15 N/A
B-PHASE 5.0 3.24 1.18 3.2 1.15 N/A
C-PHASE 5.0 3.27 1.17 3.2 1.15 N/A
GROUND 1.5 7.09 2.29 7.0 2.3 N/A
TEST OPERATIONS- AS LEFT
TIMING ELEMENT INST ELEMENT ICS
TIME IN CYCLES CURRENT ELEMENT COMMENTS
PICK UP TIMING TCC TIME @ (CY) PICK DROP PICK DROP
AMPS 2X 3X 2X 3X UP OUT UP OUT
A-PHASE
B-PHASE
C-PHASE
GROUND
COMMENTS INST CONNECTIONS NOT MADE AT RELAY CASE FOR GROUND OR PHASE RELAYS
N/A N/A N/A N/A 16 16 2 2 2 4
16 16
16 16 5 5 5 1.5
2 2 216 16 5 5 5 1.5
3/14/2013 10
CUSTOMER: VA ALTOONA DATE: 3/2/13 GLP ID#: JOB #:
LOCATION: ALTOONA SERIAL NO: SUB #: 13800 VOLT DESIGNATION MAIN
MFG BBC TYPE: 223T3242 51E EXT INVERSE RATED AMPS: RATED VOLTS:
GND/NEUT RELAY MF BBC GND/NEUT RELAY TYP22353242 51E EXT INVERSE TECH: JD
PHASE CT RATIO 300/5 GROUND CT RATIO 300/5 RELAYS TESTED AS FOUND: YES
PHASE PT RATIO GROUND PT RATIO COORDINATION STUDY PROVIDED: NO
RELAY SETTINGS & TEST INFORMATION
ICS INST TAP SETTING TIME DIAL
A B C G A B C G A B C G A B C G
SPECIFIED
AS FOUND
AS LEFT
TEST OPERATIONS- AS FOUND
TIMING ELEMENT INST ELEMENT ICS
TIME IN CYCLES CURRENT ELEMENT COMMENTS
PICK UP TIMING TCC TIME @ (CY) PICK DROP PICK DROP
AMPS 2X 3X 2X 3X UP OUT UP OUT
A-PHASE 6.0 11.59 3.70 11.5 3.5 N/A
B-PHASE 6.0 11.62 3.65 11.5 3.5 N/A
C-PHASE 6.0 11.55 3.75 11.5 3.5 N/A
GROUND 2.0 17.41 .55 17.5 5.5 N/A
TEST OPERATIONS- AS LEFT
TIMING ELEMENT INST ELEMENT ICS
TIME IN CYCLES CURRENT ELEMENT COMMENTS
PICK UP TIMING TCC TIME @ (CY) PICK DROP PICK DROP
AMPS 2X 3X 2X 3X UP OUT UP OUT
A-PHASE
B-PHASE
C-PHASE
GROUND
COMMENTS INST CONNECTIONS NOT MADE AT RELAY CASE FOR GROUND OR PHASE RELAYS
N/A N/A N/A N/A 16 16 6 6 6 9
16 16
16 16 6 6 6 2
6 6 6 916 16 6 6 6 2
3/14/2013 11
Great Lakes Power Services
330 N. HURON OVERCURRENT RELAY TEST REPORT
LINWOOD, MI 48634 PH. 989-697-3023
MISC RELAY TEST REPORT
CUSTOMER: Altoona VA DATE: 3/2/2013
SUBSTATION NO: PRIMARY CUSTOMER DESIGNATION: 52-M MAIN
COORDINATION STUDY PROVIDED: NO RELAYS TESTED AS FOUND: YES
RELAY DEVICE INFORMATION
PHASE RELAY GROUND/NEUTRAL RELAY
MFG: ABB CIRCUIT SHIELD MFG:
TYPE: 27 STYLE 411R1175 TYPE:
APPLICATION: UNDERVOLTAGE APPLICATION:
C.T. RATIO: P.T. RATIO: C.T. RATIO: P.T. RATIO:
TEST SETTINGS AND INFORMATION-- A PHASE
AS FOUND SETTINGS
TAP @ 110 VOLTS
AS FOUND TIMING
TIMING @ 40% (44 VOLTS) - 16.75 SECONDS
TIMING @ 20% (22 VOLTS)- 13.96 SECONDS
TEST SETTINGS AND INFORMATION-- B PHASE
AS FOUND SETTINGS
TAP @ 110 VOLTS
AS FOUND TIMING
TIMING @ 40% (44 VOLTS) - 16.62 SECONDS
TIMING @ 20% (22 VOLTS)- 13.81 SECONDS
TEST SETTINGS AND INFORMATION-- C PHASE
AS FOUND SETTINGS
TAP @ 110 VOLTS
AS FOUND TIMING
TIMING @ 40% (44 VOLTS) - 16.84 SECONDS
TIMING @ 20% (22 VOLTS)- 13.98 SECONDS
3/14/2013 12
BLDG 1
MDS1 & MDS2
3/14/2013 13
330 N. HURON ROAD Great Lakes Power Services
LINWOOD, MI 48634 LOW VOLTAGE CIRCUIT BREAKER TEST REPORT PH. 989-697-3023
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301117003 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-3 (RETURNED) CUB. FDR-1 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 36 44 37 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
OTHER COMMENTS
3/14/2013 14
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116009 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600 (REMOVED) CUB: FDR-6 Spare (RETURNED) CUB. FDR-2 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 300 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 26 28 29 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 15
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116021 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600 (REMOVED) CUB: FDR-27-Spare (RETURNED) CUB. FDR-3 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 30 27 32 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 16
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116036 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-5 (RETURNED) CUB. FDR-4 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 31 33 35 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 17
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301115027 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600 (REMOVED) CUB: FDR-13-Spare (RETURNED) CUB. FDR-5 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 25 28 30 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 18
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 400130111601 SUB #: Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600 (REMOVED) CUB: FDR-15 (RETURNED) CUB. FDR-6 Spare TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x LTD 2 sec 2 sec
STPU 6x 1.5x STD 0.1 in 0.1 out INST max 1.5x GFPU A = 100Amp A = 100Amp GFD 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 48 38 36 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 19
CUSTOMER: Altoona VA DATE: 2-27-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116039 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-4 (RETURNED) CUB. FDR-7 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 26 34 37 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 20
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116020 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-14 (RETURNED) CUB. FDR-8 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 28 32 34 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 21
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301115028 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-1 (RETURNED) CUB. FDR-9 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 22 24 25 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 22
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116034 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-16 (RETURNED) CUB. FDR-10 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 300 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1.0x 1.0x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 39 28 37 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 23
CUSTOMER: Altoona VA DATE: 2-27-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116022 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-7 (RETURNED) CUB. FDR-11 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 300 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 26 28 33 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 24
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116037 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600 (REMOVED) CUB: FDR-25-Spare (RETURNED) CUB. FDR-12 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 300 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1.0x 1x LTD 2 sec 2 sec
STPU 6x 1.5x STD 0.1 in 0.1 out INST max 1.5x GFPU A = 100Amp A = 100Amp GFD 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 33 30 34 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 25
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301115042SUB #: Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600 (REMOVED) CUB: FDR-23 (RETURNED) CUB. FDR-13 Spare TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x LTD 2 sec 2 sec
STPU 6x 1.5x STD 0.1 out 0.1 out INST max 1.5x GFPU A = 100Amp A = 100Amp GFD 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD PRIMARY INJECTION
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE 100 100
B PHASE 100 100
C PHASE 100 100
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD 1200 8 12 8.79 8.63 8.66
STD 1200 0.07 0.18 0.10 0.10 0.10
INST 1200 0.01 0.05 0.05 0.05 0.05
GFD 400 0.07 0.18 0.11 0.11 0.11
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 78 80 82 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 26
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116033 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-2 (RETURNED) CUB. FDR-14 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 300 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 29 30 34 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 27
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301117002 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-22 (RETURNED) CUB. FDR-15 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1.0x 1.0x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU B=300Amp B=300Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 29 23 26 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 28
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116005 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-12 (RETURNED) CUB. FDR-12 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 300 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1.0x 1x LTD 2 sec 2 sec
STPU 6x 1.5x STD 0.1 in 0.1 out INST max 1.5x GFPU A = 100Amp A = 100Amp GFD 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 38 42 43 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 29
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301117001 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-17 (RETURNED) CUB. FDR-19 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 600 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU B B A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 26 30 29 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 30
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301117000 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-8 (RETURNED) CUB. FDR-18 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 26 30 27 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 31
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116038 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-17 (RETURNED) CUB. FDR-19 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 600 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 14 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 out 0.1 out INST max 12 1.5x GFPU B B A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 26 40 30 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 32
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301117007 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-9 (RETURNED) CUB. FDR-20 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 35 26 40 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 33
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116031 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-21 (RETURNED) CUB. FDR-17 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 300 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 6x STD 0.1 in 0.1 in 0.1 in INST max max max
GFPU B B B
GFD 0.2 out 0.2 out 0.2 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 57 66 69 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 34
CUSTOMER: Altoona VA DATE: 2-26-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116011 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-10 (RETURNED) CUB. FDR-22 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1.0x 1.0x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 32 31 33 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF BREAKER GOOD X FAIR POOR
CORRECTIVE ACTION NECESSARY REPAIR REBUILD RETROFIT
3/14/2013 35
CUSTOMER: Altoona VA DATE: 2-27-13 GLP ID#: N/A JOB #: 4041 LOCATION: Penn. SERIAL NO: 4001301116024 Sub# Room 19 DESIGNATION:
MFG Siemans TYPE: WLL2A308 RATED AMPS: 800 RATED VOLTS: 600
(REMOVED) CUB: FDR-11 (RETURNED) CUB. FDR-22 TECH: TMB
STORED ENERGY X MANUAL X ELECTRICAL
REBUILD RETROFIT REPAIR TEST ONLY X
TRIP DEVICE INFORMATION
TYPE: ETU745 RATING PLUG: 400 TARGETS: Yes
ELECTRO-MECH. SIZE: N/A CT TAPS AVAIL.: N/A
SETTINGS AS FOUND AS LEFT AS TESTED
LTPU 1x 1x 1x LTD 2 sec 2 sec 2 sec
STPU 6x 6x 1.5x STD 0.1 in 0.1 in 0.1 out INST max max 1.5x GFPU A = 100Amp A = 100Amp A = 100Amp GFD 0.2 out 0.2 out 0.1 out
BREAKER PERFORMANCE
TIME DELAY TESTED @ 300% TESTING METHOD Secondary Injection
PICK-UP LTPU STPU INST GFPU
VALUES FOUND LEFT FOUND LEFT FOUND LEFT FOUND LEFT
A PHASE
B PHASE
C PHASE
SETTINGS CURRENT MIN TIME MAX TIME A PHASE B PHASE C PHASE
LTD Sec. N/A N/A OK OK OK STD Sec. N/A N/A OK OK OK INST Sec. N/A N/A OK OK OK GFD Sec. N/A N/A OK OK OK
INSUL. RESISTANCE BREAKER CLOSED BREAKER OPEN
(MΩ) (GΩ) A-GND B-GND C-GND A-B A-C B-C A-A B-B C-C
AS LEFT 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+ 5K+
CONTACT RESISTANCE (MICRO-OHMS) FUSE RESISTANCE (MICRO OHMS)
A B C A B C
AS LEFT 35 25 32 AS LEFT
INSPECTION AND MAINTENANCE
ARC CHUTES X TRIP COIL N/A LUBRICATION X CONTACT WIPE X
ARCING CONTACTS X CLOSING COIL N/A TRIP BAR X AUX SWITCHES N/A
MAIN CONTACTS X SOLONOID N/A CONTROL WIRING N/A CONTACT ALN. X
RECOMMENDATIONS
TRIPS WITHIN SPECIFIED PARAMETERS YES X NO
GENERAL CONDITION OF…