This is a product specification document for a Getinge LRG 4800 RO Water Treatment System along with related technical drawings and specifications. The system is designed to supply high-quality water for medical equipment like steam generators, washer-disinfectors, cart washers, lab glassware washers, and cage & rack washers.

The LRG 4800 system has a capacity of 4800 gallons per day (18,170 LPD) with a 185-gallon float tank. Key features include a 115V single-phase controller, 208V 3-phase processor and pump, KDF/GAC filter tank, integrated pre-treatment, stainless steel membrane housing, and the ability to eliminate up to 99% of total dissolved solids. The system includes detailed utility requirements such as plumbing connections (3/4" CTS with 30-80 psig pressure range), electrical requirements (115V and 208V connections), and specific installation parameters. An auto-bypass model (LRG 4800-AB) is also available. The system meets ETL and CSA safety standards and includes options for post-treatment with polyphosphate. Installation requires specific door access of at least 3' wide by 7'-6" high, with detailed mounting and anchoring specifications provided.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DZ--SPS Auto flush install, newest first.
File Type Posted
S06 Solicitation 36C24225R0028 Amendment 0002.docx DOCX document
S02 RFI QUESTIONS AND ANSWERS - SPS AUTO FLUSH INSTALL.pdf PDF
S04 SITE VISIT SPS AUTO FLUSH 1-2-2025.pdf PDF
S02 SOW SPS auto-flush Revised 1-2-2025.docx DOCX document
36C24225R0028_3.docx DOCX document
Solicitation 36C24225R0028 Amendment 0001.pdf PDF
36C24225R0028_2.docx DOCX document
S02 Buy American Certificate blank.pdf PDF
S02 Bronx Wage Rate 12-6-24.pdf PDF
S02 Limitation on subcontracting blank.docx DOCX document
36C24225R0028_1.docx DOCX document
S03 Solicitation 36C24225R0028 SPS Auto Flush Install.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1/4

Customer Reference

LRG 4800

RO Water Treatment Systems

Product Specification

Municipal water treatment facilities primarily treat water to remove microbiological contaminants to provide safe drinking water but do little to remove organic and inorganic content that adversely affects the performance of water dependent medical and research reprocessing equipment.

Getinge water treatment systems are designed to supply high quality water for point-of-use steam generators; medical washer-disinfectors; cart washer disinfectors; lab glassware washers;

and cage & rack washers. When used as instructed, the Getinge

RO systems eliminate up to 99% of total dissolved solids (TDS);

volatile organic compounds; water hardness (CaCO ); and chlo-rine additives.

Quality Statement Confidence in the Getinge group is the most important quality criteria. This is the hallmark of all our external and internal commitments, activities and products. Products and services supplied by Getinge conform to the agreed terms and expectations. The achievement of these quality goals is the basis for continued competitive and successful enterprise.

Application The Getinge LRG 4800 Series are complete water treatment systems that includes an RO processor, a KDF/GAC filter tank, an atmospheric float tank for storage and delivery, and a microprocessor controller.

Not intended to be used for drinking water.

06/16/2021 64 of 82

06/16/2021 65 of 82

06/16/2021 66 of 82

Benefits • Extends equipment life

• Reduces or eliminates boiler scale

• Increases heater element life

• 115V, 50/60Hz, 1-Phase controller

• 208V, 3-phase processor and pump

• Floor mounted processor

• HW & CW mixing valve

• Atmospheric float tank with delivery pump

• Tank pressure gauge

• Stainless steel membrane housing

• KDF/GAC filter tank

• Integrated pre-treatment

• Pre- and post-filter pressure gauges

• Permeate TDS/Conductivity meter

• Processor pump

• 55 dB A sound pressure level

Equipment Features

• ETL Listed to IEC/UL Standard 61010-1

• Certified to CAN/CSA C22.2 No. 61010-1 Codes

Ordering Information Mark your selections:

= Selected option

Models LRG 4800: 4800 Gallon-Per-Day (18170 LPD) System with 185-Gallon (700 L) Float Tank

Options Post-Treatment - Polyphosphate is used to increase conductivity for level sensing devices and to neutralize the effects of the slightly acidic nature of RO water.

Getinge USA, Inc.

1777 E. Henrietta Road

Rochester NY 14623

Phone: 800.475.9040 info.northamerica@getinge.com

Getinge Canada, Ltd.

6685 Millcreek Drive, Unit 3

Mississauga, ON L5N 5M5

Phone: 800.387.3341 info.northamerica@getinge.com

Getinge Group is a leading global provider of products and systems that contribute to quality enhancement and cost efficiency within healthcare and life sciences. We operate under the three brands of ArjoHuntleigh, Getinge and

Maquet. ArjoHuntleigh focuses on patient mobility and wound management solutions. Getinge provides solutions for infection control within healthcare and contamination prevention within life sciences. Maquet specializes in solutions, therapies and products for surgical interventions, interventional cardiology and intensive care.

ROWater_PS_LRG4800_0115_RevA © 2015 Getinge USA, Inc. Printed in U.S.A. ArjoHuntleigh, Getinge, and MAQUET are registered trademarks. We reserve the right to make changes to specifications and product information.

LRG 4800-AB: 4800 Gallon-Per-Day (18170 LPD) System with 185-Gallon (700 L) Float Tank with Auto Bypass operation

06/16/2021 67 of 82

Item 4.000 6910729834

06/16/2021 68 of 82

06/16/2021 69 of 82

File details come from the government source that posted it. Updated .