This document is a series of Questions and Responses (RFI) related to a Photovoltaic (PV) Carport Solar System Repair project at the Northport, NY Veterans Affairs facility. The responses address technical details about electrical wiring, conduit replacement, underground conductor repairs, and system components. Key points include replacing damaged PV string circuits, reusing existing underground conduits with minor modifications, installing new electrical vaults, and replacing two damaged PV panels. The VA will provide two replacement panels, and the contractor must test and install them, providing a unit cost for additional panel replacements as an add alternate.
The project involves electrical work for both West and South parking lot solar arrays, with specific requirements for wiring installation, conduit routing, and system testing. The contractor must follow existing installation methods, route new wiring through existing RMC conduits, and provide free-air wiring that is neatly supported and protected. New combiner boxes must be rated for 600VDC with 400A disconnecting means, surge protection, and 15A fusing per input. The system last functioned in January 2021, and the contractor is responsible for a full inspection, testing, and startup of the entire solar system, including existing and new installations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions Responses
For areas on the racking system but below the solar panels, and where it says to replace wire and use existing conduit. There is no conduit. Are we to install the new wiring the same way, not in conduit for those areas?
Means and methods for new PV string wiring shall match existing installation. New PV sting wiring under the solar carport is to be routed through existing RMC conduits stubbed-up at the top of the structure. Sections of wiring exiting conduit raceways shall be routed free air and shall be neatly tied and supported from the structure, and protected from damage. Provide separation and protection between free air conductors and strucutral steel sharp edges.
On page E-101 you reference the wires under the panels and the duct back using the same note #3. So, for under the panels we are just replacing the wires and for areas you have a note 3 that shows the duct bank, just replacing those wires??
Electrical PV source circuts conductors (A-01 throught A-08 and B-01 through B-08)shall be replaced entirely between each combiner box and inveter unit. Existing PV string circuits (overhead wiring below panels) under the panels shall remain and be protected during the installation, unless otherwise noted on design documentation, i.e. string circuitry associated with CB-B-06.
On page E 201, E-202 note 4 you reference the wires under the panels as a duct bank. Please clarify.
In note 4 on E-201 and E-202, 'existing electrical ductbank' references existing underground concrete encased conduits to be reused for installation of new PV source circuits (between each combiner box and inverter units).
Please clarify if wires being replaced under the panels but on the racks if we are to install conduit and if so, what type of conduit
Means and methods for new PV string wiring shall match existing installation. New PV sting wiring under the solar carport is to be routed through existing RMC conduits stubbed-up at the top of the structure. Sections of wiring exiting conduit raceways shall be routed free air and shall be neatly tied and supported from the structure, and protected from damage. Provide separation and protection between free air conductors and strucutral steel sharp edges.
On page E202, we are to extend the existing duct bank after we install the new vaults but do not mention how much of the existing vault we are to demo in order to install the new vats.
Should we demo the existing bank only what is necessary to install the new vaults.
Correct, contractor shall reuse existing electrical conduit as much as possible. The extent of removal and installation of new electrical concrete encased raceways shall be confirmed per location of manholes and field conditions, after all required field survey, utility mark out, etc. is completed.
On page E202 you mention reuse existing conduit. Is there existing conduit in this area?
On E-202, for PV source circuits (between each combiner box and inverter units) there is an existing underground and overhead conduit system that will be reused with minor modification. As noted on drawings, PV string circuitry shall be replaced under the carport near CB-B-6 combiner box, and that circuitry shall be isntalled in new 1.25"C RMC conduits.
Please clarify circuits A-01, A-02, A-03, A-04, A-05, A-08, B-01, B- 02, B-04, and B-06 from provided drawings. Does the contractor need to install (2) new 3” conduits with one parallel set of phase conductors and one grounding conductor in each?
For each of these circuits contractor shall provide (2) sets of specified electrical conductors in (2) 3" conduits, one set per conduit. Each conduit is to be provided with equipment ground conductor. i.e. A-01 PV source circuit shall be installed in two (2) 3" conduits, each conduit provided with 2#500kcmil and 1#3 ground conductors.
What caused the underground conductors to need to be replaced? Is there potential electrical damage in the combiners, inverters, or AC disconnects?
Existing underground PV source circuit conductors were damaged due to imporperly made underground splices in the underground boxes. There is no damage witnessed anywhere else in the system but contractor shall be responsible for full inspection, testing and startup of the entire system.
More than two modules should be replaced to remove all char and damage from the fire, (6) modules have signs of fire damage.
Does the government have more than two spare modules?
Based on VA investigation, only (2) PV panels are damaged and in non-operational condition. VA is able to furnish only (2) PV panels for contractors use. If more than (2) PV panels are determined to be damaged, then contractor is to inform the VA COR immediately who will make the final decision on how to proceed. Contractor to provide in their Fee Proposal Unit cost (labor and material) per panel (exact replacement) as an add alternate.
Does the government know the cause of the PV fire? The bundle of homeruns is close to or making contact with the underside of the module which can cause the wires to overheat and catch fire.
This appears to be the same throughout the other arrays.
Based on VA investigation, insulation on improperly supported PV string circuits was damaged on the metal structure. PV string wiring is rated for 90˚C which would be unlikely to overheat outdoors.
Does the racking need to be repaired at the burn location? Existing steel structure to remain. Refer to RFI #1 and #9 responses for means and methods for new cabling installation and support.
12 When was the last time the system was functional? January 2021, even though it was turned on in 2023 for testing.
Do any existing CTs need to be replaced? (Also Energy monitoring)
Existing CTs and energy monitoring shall remain but shall be inspected and tested by the contractor. Monitoring was functional in 2023.
Please clarify the required minimum compressive strength of the concrete for the manholes and concrete-encased duct bank.
Manholes shall be precast and suitable for vehicular traffic per HS-20 standards. Precast manholes concrete strength is typically 5,000 psi. Electrical concrete-encased duct bank shall be of min. 3,000 psi strength. Upon manhole material selection, contractor shall provide calculations by licensed structural engineer for VA's review to confirm the adherence to the HS-20 standard.
Please clarify the requirements (conductor and conduit sizes) for the communications cables shown on E-201 and E-202 of the provided drawings. Will these cables be routed through the new manholes? If so, please provide drawing details.
Communications cabling shall be routed throug manhole is same manner as electrical conductors. Same details shall apply. Provide two (2) 24AWG, 1-pair, shielded, 600V insulation, tinned copper wire, RS-485 cables.
Would the VA like a full inspection of the entire system when the system is turned back on to avoid any of these issues in the future or are they looking just for the testing and commissioning of the one array that we are working on?
Contractor shall be responsible for full inspection, testing and startup of the entire system, including existing and new installation. This pertains to both West and South PV Solar Systems.
Per #9 on the SOW - does the VA want all the undamaged DC cables underground connecting to the other arrays but in the same combiner box pulled out and replaced as well? (See wires in the photos attached all the way to the left in the box.)
PV String circuits routed to other arrays shall be maintained.
Contractor shall disconnect existing circuitry, replace and extend wiring as required to make necessary terminations in the new combiner box.
In the photo attached, we noted that there are lighting cables in this combiner box that are not to code and would need to be taken out of the box, should that be part of the SOW?
Photograph attached by the contractor represents a splice box, not a combiner box. Based on VA review there are no code restrictions for lighting branch circuit to be routed through the same splice box as DC circuitry.
Is the VA able to provide the original string chart for the solar system, as we will need that for wiring the project.
Original PV string circuitry chart is not available. As noted on design documentation each string circuit shall consist of 11 PV panels in series.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
REPAIR PHOTOVOLTAIC
CARPORT SYSTEM
79 Middleville Rd, Northport, NY 11768
632-24-130
N/A
AUGUST 23, 2024 KNRevisions: Date:
1. BID DOCUMENTS 08/23/2024
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
REPAIR PHOTOVOLTAIC
CARPORT SYSTEM
79 Middleville Rd, Northport, NY 11768
632-24-130
N/A
AUGUST 23, 2024 KNRevisions: Date:
1. BID DOCUMENTS 08/23/2024 E-001
ELECTRICAL SYMBOLS,
ABBREVIATIONS AND NOTES
MR
GENERAL PROJECT NOTES:
A. INSTALLATION SHALL COMPLY WITH ALL APPLICABLE ANSI, ASTM, IBC, IESNA, IEEE,
ISO, JCAHO, NFPA, NEMA AND UL CODES AND STANDARDS.
B. ALL CONDUCTORS, TRANSFORMER WIDINGS, AND BUSSING IN ELECTRICAL POWER
DISTRIBUTION SYSTEM COMPONENTS SHALL BE COPPER.
C. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE
OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.
D. LIGHTING FIXTURES WITH MORE THAN TWO LAMPS SHALL HAVE TWO OUTER LAMPS
CONTROLLED WITH ONE SWITCH AND INNER LAMP(S) CONTROLLED BY A SECOND
SWITCH.
E. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS.
EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED
EQUIPMENT GROUNDING CONDUCTOR.
F. NEUTRAL SHARING FOR MULTI-WIRE BRANCH CIRCUITS SHALL NOT BE ALLOWED.
G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY
AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.
H. ALL WIRING DEVICES SHALL BE PROVIDED WITH PERMANENT ADHESIVE LABEL
LISTING PANEL AND CIRCUIT SUPPLYING THE WIRING DEVICE.
I. CONTRACTOR SHALL BE RESPONSIBLE FOR FULL INSPECTION, TESTING, AND
STARTUP OF THE ENTIRE SYSTEM, INCLUDING EXISTING AND NEW INSTALLATION.
J. FOR WORK ASSOCIATED WITH UNDERGROUND CONCRETE PRE-CAST ELECTRICAL
MANHOLE AND CONCRETE ENCASED ELECTRICAL DUCTBANKS, CONTRACTOR SHALL
OBTAIN SERVICES OF LICENSED STRUCTURAL ENGINEER TO PROVIDE CALCULATIONS
FOR VA REVIEW AND APPROVAL. CONCRETE PRECAST ELECTRICAL MANHOLE
CONCRETE SHALL BE OF MIN. 5000 P.S.I. @ 28 DAYS STRENGTH, AND CONCRETE FOR
UNDERGROUND ELECTRICAL DUCTBANK SHALL BE OF MIN. 3000 P.S.I. @ 28 DAYS
STRENGTH. CALCULATIONS SHALL CONFIRM ADHERENCE TO HS-20 LOADING
STANDARDS AND SUITABILITY FOR VEHICULAR TRAFFIC.
GENERAL NOTES - DEMOLITION:
A. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES,
CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP
CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE
WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND
REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.
B. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT
PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.
C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS
PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS. ALL
CIRCUITS SERVICE AREAS ADJACENT TO THE CONSTRUCTION AREA THAT ARE
MODIFIED, AS PART OF THE CONSTRUCTION PROJECT, SHALL BE RE-CIRCUITED AS
PART OF THE CONSTRUCTION PROJECT.
D. PROVIDE TEMPORARY AND/OR MODIFY EXISTING LIGHTING AND POWER, AND
RELATED SERVICES AS REQUIRED FOR CONSTRUCTION-PERIOD'S INTERIM LIFE
SAFETY MEASURES.
E. PRIOR TO REMOVAL OF EXISTING ELECTRICAL COMPONENTS, CONTRACTOR SHALL
COORDINATE WITH COR AND HOUSE ELECTRICIAN IF ANY EQUIPMENT SHALL BE
RETAINED BY THE GOVERNMENT. COORDINATION ITEMS SHALL INCLUDE BUT NOT BE
LIMITED TO ANY CONDUCTORS REMOVED FROM EXISTING RACEWAYS, DISCONNECTS
OF 100A OR LARGER, FIRE ALARM DEVICES, PANELBOARDS AND CIRCUIT BREAKERS,
SPECIAL LIGHTING FIXTURES, SPECIAL RECEPTACLES, TRANSFORMERS, POWER
COMPONENTS TO PROVIDE TEMPORARY CONSTRUCTION ELECTRICAL SERVICES (IF
NOT THE PROPERTY OF THE CONTRACTOR). ANY EQUIPMENT NOT REQUESTED TO BE
RETAINED SHALL BE REMOVED IN ACCORDANCE WITH CONTRACT REQUIREMENTS.
INDICATES EQUIPMENT TO BE DEMOLISHED, UON.
ELECTRICAL ABBREVIATIONS
ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION
1P SINGLE POLE FA FIRE ALARM PEND PENDANT
2/C TWO-CONDUCTOR FAAP FIRE ALARM ANNUNCIATOR PANEL PF POWER FACTOR
3/C THREE-CONDUCTOR FACP FIRE ALARM CONTROL PANEL PH PHASE
3PH THREE-PHASE FC FOOT CANDLE PNL PANEL
4/C FOUR-CONDUCTOR FIXT FIXTURE PT POTENTIAL TRANSFORMER
4W FOUR WIRE FLA FULL LOAD AMPS PVC POLYVINYL CHLORIDE (PLASTIC)
A/C UNIT AIR CONDITIONING UNIT FP FIRE PROTECTION PWR POWER
A/E ARCHITECT / ENGINEER FT FEET OR FOOT RCP REFLECTED CEILING PLAN
AAP ALARM ANNUNCIATOR PANEL FU SW FUSED SWITCH REC RECESSED
AC ALTERNATING CURRENT OR ARMORED CABLE G ELECTRICAL GROUND RECPT RECEPTACLE
ACC ACCESSIBLE GFCI GROUND FAULT CIRCUIT INTERRUPTER RM ROOM
ADDL ADDITIONAL HOA HAND-OFF-AUTO RMS ROOT MEAN SQUARE
ADJ ADJACENT, ADJOINING HP HORSEPOWER REQD REQUIRED
AF AMPERE FRAME OR AMP FUSE HT HEIGHT SCC SHORT CIRCUIT CURRENT
AFF ABOVE FINISHED FLOOR HZ HERTZ SD SMOKE DETECTOR
AFG ABOVE FINISHED GRADE IMC INTERMEDIATE METAL CONDUIT SF SQUARE FOOT (FEET)
AHJ AUTHORITY HAVING JURISDICTION IR INFRARED SHT SHEET
AIC AMPERE INTERRUPTING CAPACITY J-BOX JUNCTION BOX SI INTERNATIONAL SYSTEM OF UNITS
ALT ALTERNATE kV KILOVOLT SPEC SPECIFICATION
AMP AMPERE kVA KILOVOLT AMPERE SPST SINGLE POLE SINGLE THROW
AT AMPERE TRIP kVAh KILOVOLT AMPERE PER HOUR SURF SURFACE
AUTO AUTOMATIC kVAR KILOVOLT AMPERE REACTIVE SW SWITCH
BLDG BUILDING kW KILOWATT SWBD SWITCHBOARD
BRKR BREAKER kWh KILOWATT HOUR SWGR SWITCHGEAR
C CONDUIT kWhM KILOWATT HOUR METER TEL TELEPHONE
CAB CABINET LED LIGHT EMITTING DIODE TYP TYPICAL
CALC CALCULATE LF LINEAR FEET (FOOT) UGND UNDERGROUND
CAP CAPACITY LRA LOCKED ROTOR AMPS UL UNDERWRITERS LABORATORY
CAT CATALOG LT LIGHT UON UNLESS OTHERWISE NOTED
cd CANDELA LTG LIGHTING UPS UNINTERRUPTIBLE POWER SUPPLY
CD CONSTRUCTION DOCUMENTS LTG PNL LIGHTING PANEL UTIL UTILITY
CF CONTRACTOR FURNISHED LTNG LIGHTNING V VOLT
CKT CIRCUIT LV LOW VOLTAGE VA VOLT AMPERE
CKT BRKR OR C/B CIRCUIT BREAKER MAX MAXIMUM VAR VOLT AMPERE REACTIVE
CLF CURRENT LIMITING FUSE MC METAL-CLAD VFD VARIABLE FREQUENCY DRIVE
CLG CEILING MCA MINIMUM CIRCUIT AMPACITY VOLT VOLTAGE
COMPT COMPARTMENT MCB MAIN CIRCUIT BREAKER W WATT
CONT CONTINUE MCC MOTOR CONTROL CENTER WH WATER HEATER
CONTR CONTRACTOR MECH MECHANICAL WP WEATHERPROOF
CRI COLOR RENDERING INDEX MH MANHOLE XFMR TRANSFORMER
CT CURRENT TRANSFORMER MIN MINIMUM
CU COPPER MOCP MAXIMUM OVERCURRENT PROTECTION
dB DECIBEL MLO MAIN LUGS ONLY
DC DIRECT CURRENT MT MOUNT
DEG C DEGREES CELCIUS MTD MOUNTED
DEG F DEGREES FAHRENHEIT MTG MOUNTING
DEMO DEMOLITION MTS MANUAL TRANSFER SWITCH
DIAG DIAGRAM MV MEDIUM VOLTAGE
DISC DISCONNECT MVA MEGAVOLT-AMPERE
DISTR PNL DISTRIBUTION PANEL MW MEGAWATT
DMR SW DIMMER SWITCH NA NOT APPLICABLE
DPDT DOUBLE POLE DOUBLE THROW NC NORMALLY OPEN
DPST DOUBLE POLE SINGLE THROW NEC NATIONAL ELECTRICAL CODE
DS DISCONNECT SWITCH NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
DWG DRAWING NEUT OR N NEUTRAL
EL ELEVATION NFPA NATIONAL FIRE PROTECTION ASSOCIATION
ELEC ELECTRIC OR ELECTRICAL NIC NOT IN CONTRACT
ELEV ELEVATOR NL NIGHT LIGHT
EMER EMERGENCY NO NORMALLY OPEN
EMT ELECTRICAL METAL TUBING NTS NOT TO SCALE
ENCL ENCLOSURE OD OUTSIDE DIAMETER
EPO EMERGENCY POWER OFF OL OVERLOAD
EWC ELECTRIC WATER COOLER P POLE
EWH ELECTRIC WATER HEATER PB PULL BOX
EXIST OR (E) EXISTING PEC PHOTOLELECTRIC CELL
AUTOMATIC TRANSFER SWITCH
- INDICATES EXISTING CABLES TO BE REMOVED FROM DUCT.
- INDICATES EXISTING FEEDER TO BE ENTIRELY REMOVED.
- INDICATES FEEDER INSTALLED IN EXISTING DUCT.
- INDICATES FEEDER INSTALLED IN CONDUIT.
- INDICATES EMPTY SPARE CONDUIT. PROVIDE MUELTAPE
AND TAG BOTH ENDS OF CONDUIT RUN WITH ENGRAVED
TAGS INDICATING POINT AT OTHER END OF MULETAPE.
A
PPEQ1
PANELBOARD WITH MAIN CIRCUIT BREAKER.
KD
SWITCH, SINGLE BREAK
FUSE WITH RATING
CIRCUIT BREAKER
DRAWOUT AIR CIRCUIT BREAKER
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
DELTA CONNECTION
TRANSFORMER
WYE CONNECTION
EARTH GROUND
JUNCTION BOX
PULL BOX
TRANSFORMER, PLAN
DISTRIBUTION PANEL
PANELBOARD, FLUSH MOUNTED
PANELBOARD, SURFACE MOUNTED
RECEPTACLE, DUPLEX
RECEPTACLE, DUPLEX ON EMERGENCY POWER
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER
RECEPTACLE, QUADRAPLEX
RECEPTACLE, SINGLE
RECEPTACLE, SPECIAL PURPOSE
A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.
B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.
C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.
D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.
E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.
F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.
G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.
H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.
SWITCH
F = FUSED SWITCH K = KEY OPERATED
L = LOCK LM= LOW VOLTAGE MASTER
M = MANUAL MOTOR STARTING MC= MOMENTARY CONTACT
MP= MOTOR SNAP WITH PILOT LIGHT P = WITH PILOT LIGHT
(THERMAL TYPE)
PB= PUSH BUTTON STATION RC= REMOTE CONTROL
WP= WEATHER PROOF X = EXPLOSION PROOF
BRANCH CIRCUIT HOMERUN. ONE SEPARATE GREEN GROUNDING
CONDUCTOR SHALL BE PROVIDED FOR EACH HOMERUN
/ / / INDICATES EQUIPMENT TO BE DEMOLISHED, UON.
DISCONNECT SWITCH, FUSED. '30AS' DENOTES SWITCH RATING.
'30AF' DENOTES FUSE SIZE. '3P' DENOTES NUMBER OF POLES.
DISCONNECT SWITCH, FUSED. '30AS' DENOTES SWITCH RATING.
'3P' DENOTES NUMBER OF POLES.
STARTER, COMBINATION WITH DISCONNECT SWITCH. '30AS'
DENOTES SWITCH RATING. '1' DENOTES NEMA STARTER SIZE.
SYMBOL DESCRIPTION
ELECTRICAL SYMBOLS
CONDUIT/CABLE CUT/INTERCEPTION POINT:
- WHERE "1" IS SHOWN CONTRACTOR SHALL REMOVE CONDUIT
AND CABLE IN DIRECTION OF ARROW SHOWN.
- WHERE "2" IS SHOWN CONTRACTOR SHALL REMOVE CABLE
ONLY IN THE DIRECTION OF ARROW, CONDUIT SHALL BE CUT AND
PROTECTED FROM THIS POINT FOR FOR SPLICING INTO NEW
FEEDERS.
- WHERE "X" IS SHOWN IT INDICATES END OF CONDUIT REMOVAL
- WHERE "3" IS SHOWN CONTRACTOR SHALL INTERCEPT AND
EXTEND CONDUIT AS SHOWN.
- WHERE "4" IS SHOWN IT INDICATES PVC SCHEDULE 40 CONDUITS
ENCASED IN MINIMUM 2" CONCRETE.
- WHERE "5" IS SHOWN IT INDICATES END OF CONDUIT CONCRETE
ENCASEMENT.
SYMBOL DESCRIPTION
DUCT BANK SECTION (2x2 CONDUIT BANK/DUCT BANK INDICATED)
STARTER OR MOTOR CONTROLLER. '1' DENOTES
NEMA STARTER SIZE.
PANELBOARD WITH MAIN LUGS ONLY.
KEY INTERLOCK.
DRAWOUT DEVICE, 3 POLE U.O.N.
2. ADDENDUM #1 04/18/20251
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text J
AutoCAD SHX Text
PB
AutoCAD SHX Text T
AutoCAD SHX Text
AutoCAD SHX Text
30AS
AutoCAD SHX Text 3P
AutoCAD SHX Text
30AS
AutoCAD SHX Text 3P
AutoCAD SHX Text
30AF
AutoCAD SHX Text
30AS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
GFI
AutoCAD SHX Text
DP#____
AutoCAD SHX Text
AutoCAD SHX Text
KI
AutoCAD SHX Text 4-4"
CB-A-01 &
J-BOX-A1
CB-A-06
CB-A-07
CB-A-08
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
'MH-PV-A1'
ELECTRICAL
VAULT.
(14)3"C
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
CB-A-02 &
J-BOX-A2
CB-A-03 &
J-BOX-A3
J-BOX
CB-A-04 &
J-BOX-A4
CB-A-05 &
J-BOX-A5
(2)3"C
(4)3"C
(6)3"C
(6)3"C
(8)3"C
(10)3"C
(11)3"C
J-BOX
(2)3"C
(2)3"C
WATER
TANK
INVERTER 'A'
TRANSFORMER
'TX-PV-A1'
(8)3"C
(1)3"C
'ACD-A1'
SERVICE RATED SWITCH
TO BUILDING 11
UG
UG
UG
UG
UG
UG
UG
(3)3"C
(6)4"C
'MH-PV-A2'
ELECTRICAL
VAULT.
UG
UG
(6)3"C
OFFICES
BUILDING #09
LIBRARY MEDIA
BUILDING #12
HOSPITAL / AMBULATORY CARE
BUILDING #200
OFFICES
BUILDING #10
GENERATOR
BUILDING 218
BUILDING #11
PARKING 'F'
PARKING 'E'
M
EDICAL CIRCLE
MEDICAL CIRCLE
UG
UG
UG
UG
UG
UG
UG
UG
UGUG
UG
(2)3"C SIDEWALK
SIDEWALK
(1)3"C
(14)3"C
(11)3"C
UG
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
REPAIR PHOTOVOLTAIC
CARPORT SYSTEM
79 Middleville Rd, Northport, NY 11768
632-24-130
N/A
AUGUST 23, 2024 KNRevisions: Date:
1. BID DOCUMENTS 08/23/2024
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
REPAIR PHOTOVOLTAIC
CARPORT SYSTEM
79 Middleville Rd, Northport, NY 11768
632-24-130
N/A
AUGUST 23, 2024 KNRevisions: Date:
1. BID DOCUMENTS 08/23/2024 E-201
ELECTRICAL NEW WORK SITE PLAN
- WEST PARKING LOT
MR
ELECTRICAL NEW WORK SITE PLAN - WEST PARKING LOT
1"= 30'-0"
NOTES:
1. PROVIDE NEW ELECTRICAL VAULT AS SHOWN. REFER TO ELECTRICAL DETAIL
DRAWING E-502 FOR ADDITIONAL INFORMATION AND CONDUCTOR ROUTING
DETAILS.
2. EXTEND EXISTING CONDUIT BANKS TO NEW ELECTRICAL VAULTS. NEW
DUCTBANK EXTENSIONS SHALL BE PVC SCHEDULE 40 AND CONCRETE
ENCASED.
3. NEW DUCTBANK FROM MH-PV-A1 TO INVERTER A SHALL BE ROUTED TO
TERMINATE ON THE SIDE PANEL OF THE INVERTER IN DESIGNATED CONDUIT
ENTRY AREA. REFER TO PART PLANS ON DRAWING E-301.
4. EXISTING DUCTBANKS TO BE USED FOR NEW ELECTRICAL CONDUCTORS.
CLEAN AND MANDREL CONDUITS BEFORE PULLING NEW WIRING.
5. PRIOR TO ANY SITE EXCAVATION WORK CONTRACTOR SHALL PERFORM SITE
UTILITY SURVEY AS REQUIRED IN SPECIFICATIONS SECTION 02 21 13 AND
THROUGHOUT.
6. CONTRACTOR SHALL TEST CONDITION OF EXISTING DUCTBANKS AND ENSURE
SUITABILITY FOR REUSE. CONTRACTOR SHALL SUBMIT THE REPORT WITH
FINDING TO COR FOR REVIEW AND APPROVAL. ALL CONDUITS SHALL BE
CLEANED USING MANDRELS PRIOR TO INSTALLATION OF NEW CONDUCTORS IN
DUCTBANKS.
7. INSTALL NEW COMMUNICATIONS CABLING AND SITE LIGHTING WIRING FROM
INVERTER 'A' SYSTEM TO ELECTRICAL VAULT 'MH-PV-A2'. SITE LIGHTING
CIRCUITRY SHALL BE SPLICED USING WEATHERPROOF SPLICE KITS.
COMMUNICATIONS CABLING SHALL BE A NEW CONTINUOUS RUN FROM
INVERTER 'A' TO SOLAR PANEL SYSTEM WEATHER STATION LOCATED ON THE
SOLAR ARRAY. COMMUNICATIONS CABLING SHALL BE (2) 24AWG, 1-PAIR,
SHIELDED, 600V INSULATION, TINNED COPPER, RS-485 WIRE. EXACT
TERMINATION POINTS SHALL BE COORDINATED WITH COR PRIOR TO
COMMENCEMENT.
8. EXTEND EXISTING CONCRETE PAD, FENCING, AND ROOF AT THE LOCATION OF
EXISTING INVERTER UNIT. ANY EXISTING APPURTENANCES SHALL BE
REMOVED AND RELOCATED TO NEW FENCE/ROOF AS REQUIRED. REFER TO
PART PLANS ON DRAWING E-301 FOR ADDITIONAL REQUIREMENTS.
2. ADDENDUM #1 04/18/20251
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text A-01
AutoCAD SHX Text A-01
AutoCAD SHX Text A-02
AutoCAD SHX Text A-01
AutoCAD SHX Text A-02
AutoCAD SHX Text A-01
AutoCAD SHX Text A-02
AutoCAD SHX Text A-01
AutoCAD SHX Text A-02
AutoCAD SHX Text A-01
AutoCAD SHX Text A-02
AutoCAD SHX Text A-01
AutoCAD SHX Text A-02
AutoCAD SHX Text A-03
AutoCAD SHX Text A-03
AutoCAD SHX Text A-03
AutoCAD SHX Text A-04
AutoCAD SHX Text A-03
AutoCAD SHX Text A-04
AutoCAD SHX Text A-05
AutoCAD SHX Text A-04
AutoCAD SHX Text A-05
AutoCAD SHX Text A-03
AutoCAD SHX Text A-07
AutoCAD SHX Text A-08
AutoCAD SHX Text A-08
AutoCAD SHX Text A-01
AutoCAD SHX Text A-02
AutoCAD SHX Text A-05
AutoCAD SHX Text A-06
AutoCAD SHX Text A-03
AutoCAD SHX Text A-04
AutoCAD SHX Text A-07
AutoCAD SHX Text A-08
AutoCAD SHX Text A-01
AutoCAD SHX Text A-02
AutoCAD SHX Text A-05
AutoCAD SHX Text A-06
AutoCAD SHX Text A-03
AutoCAD SHX Text A-04
AutoCAD SHX Text A-07
AutoCAD SHX Text A-08
AutoCAD SHX Text A-08
AutoCAD SHX Text A-07
AutoCAD SHX Text A-01
AutoCAD SHX Text A-02
AutoCAD SHX Text A-05
AutoCAD SHX Text A-06
AutoCAD SHX Text A-03
AutoCAD SHX Text A-04
AutoCAD SHX Text A-07
AutoCAD SHX Text A-08
AutoCAD SHX Text A-01
AutoCAD SHX Text A-02
AutoCAD SHX Text A-04
AutoCAD SHX Text A-05
A-03
INVERTER 'B'
TRANSFORMER
'TX-PV-B1'
CB-B-02 &
J-BOX-B2
CB-B-01 &
J-BOX-B1
CB-B-03 &
J-BOX-B3
CB-B-04 &
J-BOX-B4
CB-B-05 &
J-BOX-B5
CB-B-06 &
J-BOX-B6
CB-B-07 &
J-BOX-B7
CB-B-08 &
J-BOX-B8
J-BOX
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG
UG UG
UG
UG
(2)3"C
(4)3"C
(1)3"C
(5)3"C
(7)3"C
(8)3"C
(2)3"C
(2)3"C
(1)3"C
(13)3"C
(8)3"C
UG
'SS-PV-S'
SERVICE RATED SWITCH
TO BUILDING 92
(6)4"C
(3)3"C
'MH-PV-B1'
ELECTRICAL
VAULT.
'MH-PV-B2'
ELECTRICAL
VAULT.
UG
UG
(4)3"C
UG
UG
NURSING HOME
BUILDING #08
OFFICES
BUILDING #07
BUILDING #216
GYM / POOL
BUILDING #88
UG
UG
UG
MEDICAL CIRCLE
PARKING 'I'
PARKING 'I'
MEDICAL CIRCLE
BUILDING 92
TUNNEL
SI
DE
W
AL
K
RE
CO
VE
RY
R D
60'S BLVD
(2)3"C
(8)3"C
(13)3"C
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
REPAIR PHOTOVOLTAIC
CARPORT SYSTEM
79 Middleville Rd, Northport, NY 11768
632-24-130
N/A
AUGUST 23, 2024 KNRevisions: Date:
1. BID DOCUMENTS 08/23/2024
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
REPAIR PHOTOVOLTAIC
CARPORT SYSTEM
79 Middleville Rd, Northport, NY 11768
632-24-130
N/A
AUGUST 23, 2024 KNRevisions: Date:
1. BID DOCUMENTS 08/23/2024 E-202
ELECTRICAL NEW WORK SITE PLAN
- SOUTH PARKING LOT
MR
ELECTRICAL NEW WORK SITE PLAN - SOUTH PARKING LOT
1"= 30'-0"
NOTES:
1. PROVIDE NEW ELECTRICAL VAULT AS SHOWN. REFER TO ELECTRICAL DETAIL
DRAWING E-502 FOR ADDITIONAL INFORMATION AND CONDUCTOR ROUTING DETAILS.
2. EXTEND EXISTING CONDUIT BANKS TO NEW ELECTRICAL VAULTS. NEW DUCTBANK
EXTENSIONS SHALL BE PVC SCHEDULE 40 AND CONCRETE ENCASED.
3. NEW DUCTBANK FROM MH-PV-A1 TO INVERTER A SHALL BE ROUTED TO TERMINATE
ON THE SIDE PANEL OF THE INVERTER IN DESIGNATED CONDUIT ENTRY AREA.
4. EXISTING DUCTBANKS TO BE USED FOR NEW ELECTRICAL CONDUCTORS.
5. PRIOR TO ANY SITE EXCAVATION WORK CONTRACTOR SHALL PERFORM SITE UTILITY
SURVEY AS REQUIRED IN SPECIFICATIONS SECTION 02 21 13 AND THROUGHOUT.
6. PROVIDE NEW PV ARRAY STRING WIRING. REFER TO PART PLAN ON DRAWING E-301.
7. INSTALL (2) PV PANELS FURNISHED BY VA. CONTRACTOR SHALL TEST OWNER
FURNISHED PANELS.
8. PROVIDE NEW COMBINER BOX TO REPLACE EXISTING. REFER TO PART PLAN ON
DRAWING E-301.
9. EXISTING OVERHEAD CONDUITS TO REMAIN AND BE REUSED FOR INSTALLATION OF
NEW CONDUCTORS.
10. CONTRACTOR SHALL TEST CONDITION OF EXISTING DUCTBANKS AND ENSURE
SUITABILITY FOR REUSE. CONTRACTOR SHALL SUBMIT THE REPORT WITH FINDING
TO COR FOR REVIEW AND APPROVAL. ALL CONDUITS SHALL BE CLEANED USING
MANDRELS PRIOR TO INSTALLATION OF NEW CONDUCTORS IN DUCTBANKS.
11. INSTALL NEW COMMUNICATIONS CABLING AND SITE LIGHTING WIRING FROM
INVERTER 'B' SYSTEM TO ELECTRICAL VAULT 'MH-PV-B2'. SITE LIGHTING CIRCUITRY
SHALL BE SPLICED USING WEATHERPROOF SPLICE KITS. COMMUNICATIONS CABLING
SHALL BE A NEW CONTINUOUS RUN FROM INVERTER 'B' TO SOLAR PANEL SYSTEM
WEATHER STATION LOCATED ON THE SOLAR ARRAY. COMMUNICATIONS CABLING
SHALL BE (2) 24AWG, 1-PAIR, SHIELDED, 600V INSULATION, TINNED COPPER, RS-485
WIRE. EXACT TERMINATION POINTS SHALL BE COORDINATED WITH COR PRIOR TO
COMMENCEMENT.
12. EXTEND EXISTING CONCRETE PAD, FENCING, AND ROOF AT THE LOCATION OF
EXISTING INVERTER UNIT. ANY EXISTING APPURTENANCES SHALL BE REMOVED AND
RELOCATED TO NEW FENCE/ROOF AS REQUIRED. REFER TO PART PLANS ON
DRAWING E-301 FOR ADDITIONAL REQUIREMENTS.
2. ADDENDUM #1 04/18/20251
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text B-01
AutoCAD SHX Text B-01
AutoCAD SHX Text B-02
AutoCAD SHX Text B-03
AutoCAD SHX Text B-01
AutoCAD SHX Text B-02
AutoCAD SHX Text B-03
AutoCAD SHX Text B-03
AutoCAD SHX Text B-04
AutoCAD SHX Text B-01
AutoCAD SHX Text B-02
AutoCAD SHX Text B-05
AutoCAD SHX Text B-03
AutoCAD SHX Text B-04
AutoCAD SHX Text B-06
AutoCAD SHX Text B-07
AutoCAD SHX Text B-08
AutoCAD SHX Text B-08
AutoCAD SHX Text B-01
AutoCAD SHX Text B-02
AutoCAD SHX Text B-05
AutoCAD SHX Text B-06
AutoCAD SHX Text B-03
AutoCAD SHX Text B-04
AutoCAD SHX Text B-07
AutoCAD SHX Text B-08
AutoCAD SHX Text B-01
AutoCAD SHX Text B-02
AutoCAD SHX Text B-05
AutoCAD SHX Text B-06
AutoCAD SHX Text B-03
AutoCAD SHX Text B-04
AutoCAD SHX Text B-07
AutoCAD SHX Text B-08
AutoCAD SHX Text B-01
AutoCAD SHX Text B-02
AutoCAD SHX Text B-07
AutoCAD SHX Text B-08
AutoCAD SHX Text B-01
AutoCAD SHX Text B-02
AutoCAD SHX Text B-05
AutoCAD SHX Text B-03
AutoCAD SHX Text B-04
AutoCAD SHX Text B-01
AutoCAD SHX Text B-02
AutoCAD SHX Text B-05
AutoCAD SHX Text B-06
AutoCAD SHX Text B-03
AutoCAD SHX Text B-04
AutoCAD SHX Text B-07
B-08
NEW COMBINER
BOX 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
TO 'CB-B-06'
XXXX
CHAIN LINK ENCLOSURE
X X X X
X
XX
X X
X
X
TRANSFORMER
X
X
EX. CONCRETE
EQUIPMENT PAD
EX. SOLECTRIA SGI 500
INVERTER
EXTEND FENCE OVER NEW
CONCRETE PAD AS REQUIRED.
EXISTING (8) 3" CONDUITS TO
HANDHOLE TO BE REUSED.
EX. TRANSFORMER
X
NEW PULLBOX
24"x24"x24"
NEW (6) 3" CONDUITS TO
NEW ELECTRICAL VAULT.
EXISTING CONCRETE
PAD SHALL BE
EXTENDED BY 24" MIN.
EX. SOLECTRIA
SGI 500
INVERTER
EXISTING ANTENNA TO BE
RELOCATED TO NEW FENCE
POST. PROVIDE ADDITIONAL
WIRING AND RE-POSITION
ANTENNA AS REQUIRED.
EXISTING WEATHER STATION TO
BE RELOCATED TO NEW POST.
EXISTING (2) 1" CONDUITS FOR SITE
LIGHTING AND COMMUNICATIONS
TO BE REUSED.
XXXX
X X X X
X
XX
X X
X
X
EX. CONCRETE
EQUIPMENT PAD
EX. SOLECTRIA SGI 500
INVERTER
EXISTING FENCE AND GATE
TO BE DISASSEMBLED.
EXISTING (8) 3" CONDUITS TO
HANDHOLE TO BE REUSED.
EX. TRANSFORMER
EXISTING ANTENNA TO
BE RELOCATED TO
NEW FENCE POST.
EX. SOLECTRIA
SGI 500
INVERTER
EXISTING WEATHER STATION TO
BE RELOCATED TO NEW POST.
EXISTING (2) 1" CONDUITS FOR SITE
LIGHTING AND COMMUNICATIONS
TO BE REUSED.
SOLECTRIA SGI 500 INVERTER
NEW PULLBOX
24"x24"x24"
NEW (6) 3" CONDUITS TO
NEW ELECTRICAL VAULT.
EXTEND METAL ROOF
OVER CONCRETE
PAD ADDITION
EXTEND FENCE OVER
NEW CONCRETE PAD
AS REQUIRED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
REPAIR PHOTOVOLTAIC
CARPORT SYSTEM
79 Middleville Rd, Northport, NY 11768
632-24-130
N/A
AUGUST 23, 2024 KNRevisions: Date:
1. BID DOCUMENTS 08/23/2024
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
REPAIR PHOTOVOLTAIC
CARPORT SYSTEM
79 Middleville Rd, Northport, NY 11768
632-24-130
N/A
AUGUST 23, 2024 KNRevisions: Date:
1. BID DOCUMENTS 08/23/2024 E-301
ELECTRICAL PART PLANS
MR
ELECTRICAL NEW WORK SITE PLAN - SOUTH PARKING LOT
1"= 30'-0"
NOTES:
1. PROVIDE NEW PV ARRAY STRING WIRING. PROVIDE NEW 2#10AWG.
2. INSTALL (2) PV PANELS FURNISHED BY VA. PV PANELS SHALL BE TESTED BY
CONTRACTOR PRIOR TO INSTALLATION.
3. ALL NEW DC PV STRING CIRCUITRY WIRING INSTALLATION SHALL MATCH
EXISTING MEANS AND METHODS. WHERE PERMITTED, CONTRACTOR SHALL
ROUTE NEW WIRING FREE AIR AND THROUGH EXISTING RMC CONDUIT FROM
COMBINER BOX STUBBED UP TO THE TOP OF THE STRUCTURE. ANY SECTIONS
OF CABLING THAT IS TO BE INSTALLED FREE AIR SHALL BE NEATLY TIED AND
SUPPORTED FROM THE STRUCTURE, AND PROTECTED FROM DAMAGE.
PROVIDE SEPARATION BETWEEN FREE AIR CONDUCTORS AND STRUCTURAL
STEEL SHARP EDGES. REFER TO ONE-LINE DIAGRAMS AND SPECIFICATIONS
FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
4. PROVIDE NEW COMBINER BOX TO REPLACE EXISTING DAMAGED UNIT. NEW
COMBINER BOX SHALL BE RATED FOR 600VDC MIN., BE PROVIDED WITH 400A
INTEGRAL DISCONNECTING MEANS, SURGE PROTECTION, 15A FUSING PER
INPUT, AND MIN. 30 INPUTS TO ACCOMMODATE NEW ARRAY STRING WIRING.
BASIS OF DESIGN: CROUSE-HINDS CCBF-30-F15-DS400-SP-DCM, OR APPROVED
EQUAL.
5. IN THEIR FEE PROPOSAL CONTRACTOR SHALL PROVIDE UNIT COST (LABOR
AND MATERIAL) PER PANEL (REPLACEMENT WITH SAME CHARACTERISTICS) AS
AN ADD ALTERNATE.
ELECTRICAL PART PLAN - TYPICAL INVERTER DEMOLITION
1/4" = 1'-0"
1 ELECTRICAL PART PLAN - TYPICAL INVERTER NEW WORK
1/4" = 1'-0"
2 ELECTRICAL PART PLAN - TYPICAL INVERTER ELEVATION
1/4" = 1'-0"
2. ADDENDUM #1 04/18/2025
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
REPAIR PHOTOVOLTAIC
CARPORT SYSTEM
79 Middleville Rd, Northport, NY 11768
632-24-130
N/A
AUGUST 23, 2024 KNRevisions: Date:
1. BID DOCUMENTS 08/23/2024
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
REPAIR PHOTOVOLTAIC
CARPORT SYSTEM
79 Middleville Rd, Northport, NY 11768
632-24-130
N/A
AUGUST 23, 2024 KNRevisions: Date:
1. BID DOCUMENTS 08/23/2024 E-501
ELECTRICAL DETAILS (1 OF 3)
MR
2. ADDENDUM #1 04/18/20251
AutoCAD SHX Text (8")
AutoCAD SHX Text
%%USECTION "A-A"
AutoCAD SHX Text
%%USECTION "B-B"
AutoCAD SHX Text
SLOPE
AutoCAD SHX Text
SLOPE
AutoCAD SHX Text
SLOPE
AutoCAD SHX Text
VARIES
AutoCAD SHX Text (5'-0")
AutoCAD SHX Text 1930mm
AutoCAD SHX Text (6'-4")
AutoCAD SHX Text (8")
AutoCAD SHX Text 1524mm
AutoCAD SHX Text SUMP 305x305mm (12"x12")
AutoCAD SHX Text 203mm
AutoCAD SHX Text 203mm
AutoCAD SHX Text (6")
AutoCAD SHX Text
(12") MIN.
AutoCAD SHX Text (8")
AutoCAD SHX Text 1524mm
AutoCAD SHX Text (5'-0")
AutoCAD SHX Text 203mm
AutoCAD SHX Text (8")
AutoCAD SHX Text 2235mm
AutoCAD SHX Text (7'-4")
AutoCAD SHX Text (3")
AutoCAD SHX Text 76mm
AutoCAD SHX Text (8'-0")
AutoCAD SHX Text (8")
AutoCAD SHX Text 203mm
AutoCAD SHX Text (9'-4")
AutoCAD SHX Text (8")
AutoCAD SHX Text 203mm
AutoCAD SHX Text 2438mm
AutoCAD SHX Text 2845mm
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text
PULLING IRON
AutoCAD SHX Text
CONC. ENVELOPE
AutoCAD SHX Text
GROUND ROD SLEEVE
AutoCAD SHX Text
PULLING IRON
AutoCAD SHX Text
CABLE STANCHION PER SECTION 26 05 41.
AutoCAD SHX Text SUMP 305mm (12")
AutoCAD SHX Text
SUMP FRAME & COVER
AutoCAD SHX Text (3'-0")
AutoCAD SHX Text 915mm
AutoCAD SHX Text 915mm
AutoCAD SHX Text (3'-0")
AutoCAD SHX Text GENERAL NOTE: 1. INCLUDE ALUMINUM LADDER (NOT SHOWN FOR CLARITY). INCLUDE ALUMINUM LADDER (NOT SHOWN FOR CLARITY). 2. MANHOLE SHALL BE COMPLIANT WITH HS-20 LOADING STANDARD. MANHOLE SHALL BE COMPLIANT WITH HS-20 LOADING STANDARD. 3. CONCRETE SHALL BE MIN. 5000 P.S.I. @ 28 DAYS, OR AS SPECIFIEDCONCRETE SHALL BE MIN. 5000 P.S.I. @ 28 DAYS, OR AS SPECIFIED
AutoCAD SHX Text
%%UTOP VIEW
AutoCAD SHX Text
POWER
AutoCAD SHX Text 965mm
AutoCAD SHX Text 965mm
AutoCAD SHX Text (3'-2")
AutoCAD SHX Text 1930mm
AutoCAD SHX Text (6'-4")
AutoCAD SHX Text (3'-2")
AutoCAD SHX Text (5'-6")
AutoCAD SHX Text (3'-10")
AutoCAD SHX Text (9'-4")
AutoCAD SHX Text 1676mm
AutoCAD SHX Text 1168mm
AutoCAD SHX Text 2845mm
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
GROUND ROD PER SECTION 26 05 26.
AutoCAD SHX Text GRAVEL SUMP 0.764 CUBIC METERS (1 CUBIC YARD) 19mm (3/4")
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
GRADE RINGS AS REQ'D TO MATCH CIVIL FINISHED GRADE ELEVATION.
AutoCAD SHX Text
CABLE STANCHION
AutoCAD SHX Text 152mm
AutoCAD SHX Text 305mm
AutoCAD SHX Text 203mm
AutoCAD SHX Text
AutoCAD SHX Text
POWER MANHOLE DETAILS
AutoCAD SHX Text
NTS
AutoCAD SHX Text
PLASTIC SPACER
AutoCAD SHX Text
INNERDUCT, SEE NOTE 5
AutoCAD SHX Text
DUCT [SIZE AS INDICATED ON DWGS.]
AutoCAD SHX Text (3")
AutoCAD SHX Text (3")
AutoCAD SHX Text 76mm
AutoCAD SHX Text 76mm
AutoCAD SHX Text 76mm
AutoCAD SHX Text (3")
AutoCAD SHX Text 76mm
AutoCAD SHX Text (3")
AutoCAD SHX Text 76mm
AutoCAD SHX Text (3")
AutoCAD SHX Text (3")
AutoCAD SHX Text 76mm
AutoCAD SHX Text 152mm
AutoCAD SHX Text
TIE WIRE
AutoCAD SHX Text
(6")(SEE NOTE 4)
AutoCAD SHX Text (3")
AutoCAD SHX Text
6-WAY DUCT LINE
AutoCAD SHX Text
4-WAY DUCT LINE
AutoCAD SHX Text
2-WAY DUCT LINE
AutoCAD SHX Text
GENERAL NOTES: 1. 2. 3. 4. 5.
AutoCAD SHX Text CONCRETE SHALL BE MIN. 3000 P.S.I. @ 28 DAYS, OR AS SPECIFIED. PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS WHEN CROSSING OR PLACED IN ROADWAYS. MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (36") OR AS OTHERWISE SPECIFIED IN SECTION 26 05 41. PROVIDE MINIMUM 152mm (6") SPACE BETWEEN POWER AND TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED. INNERDUCT QUANTITY AND SIZE AS INDICATED ON PLANS.
AutoCAD SHX Text (3")
AutoCAD SHX Text 76mm
AutoCAD SHX Text (3")
AutoCAD SHX Text 76mm
AutoCAD SHX Text (3")
AutoCAD SHX Text 76mm
AutoCAD SHX Text 76mm
AutoCAD SHX Text (3")
AutoCAD SHX Text 76mm
AutoCAD SHX Text (3")
AutoCAD SHX Text 76mm
AutoCAD SHX Text (3")
AutoCAD SHX Text 76mm
AutoCAD SHX Text (3")
AutoCAD SHX Text 76mm
AutoCAD SHX Text (3")
AutoCAD SHX Text (3")
AutoCAD SHX Text 76mm
AutoCAD SHX Text (3")
AutoCAD SHX Text 76mm
AutoCAD SHX Text 76mm
AutoCAD SHX Text
AutoCAD SHX Text
DUCT BANK DETAILS
AutoCAD SHX Text
NTS
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
EQUIPMENT GROUND CONDUCTOR
AutoCAD SHX Text
MANHOLE COVER FRAME GROUND CONNECTION
AutoCAD SHX Text
#6 STRANDED BARE CU CABLE (TYP)
AutoCAD SHX Text
DUCT BANK
AutoCAD SHX Text
CABLE PULLING IRONS
AutoCAD SHX Text
#3/0 STRANDED BARE CU COMPLETE RING.
AutoCAD SHX Text
EXOTHERMIC WELD CONNECTION
AutoCAD SHX Text
GROUND ROD PER SECTION 26 05 26
AutoCAD SHX Text
SUMP FRAME
AutoCAD SHX Text
EMBED CHANNEL OR CABLE RACK (TYP)
AutoCAD SHX Text
EXOTHERMIC WELD CONNECTION (TYP)
AutoCAD SHX Text
CABLE CLIP (TYP)
AutoCAD SHX Text
DRILL AND TAP GROUND CONNECTION
AutoCAD SHX Text
CABLE SPLICES
AutoCAD SHX Text
BRAIDED SHIELD DRAIN WIRES (TYP)
AutoCAD SHX Text
AutoCAD SHX Text
MANHOLE GROUNDING DETAIL
AutoCAD SHX Text
NTS
AutoCAD SHX Text
CADWELD "GY"
AutoCAD SHX Text
MIN
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text 24"
AutoCAD SHX Text
MIN
AutoCAD SHX Text 30"
AutoCAD SHX Text
CABLE TO CABLE TAP
AutoCAD SHX Text
CADWELD "TA"
AutoCAD SHX Text
3/4" DIA. X 10'-0" LONG COPPER CLAD GROUND ROD
AutoCAD SHX Text
CADWELD "GR"
AutoCAD SHX Text
"C" FOR COMMUNICATIONS "E" FOR ELECTRIC
AutoCAD SHX Text DRILL AND TAP 1/2"-13 HOLE FOR LIFTING RINGS AND SUPPLY THREADED BOLTS TO PLUG HOLES
AutoCAD SHX Text
NAME PLATE
AutoCAD SHX Text
NON-PENETRATING PICKHOLE
AutoCAD SHX Text WHERE REQUIRED, PROVIDE TWO McGRAD INTIMIDATOR MAN-LOCKS WITH 1/2"-13 BOLTS AND PROTECTIVE NON-CORROSIVE CAPS. PROVIDE (2) SPARE BOLTS AND CAPS
AutoCAD SHX Text
1/3"-13 BOLTS (TYP. 4 PLACES)
AutoCAD SHX Text
3-INCH DIAM.
AutoCAD SHX Text
BEARING SURFACE OF FRAME AND COVER SHALL BE MACHINED
AutoCAD SHX Text 3"x5/8"x1/4" LETTERS
AutoCAD SHX Text
DRILL FOR 10-24 SCREWS. USE BRASS SCREWS
AutoCAD SHX Text MANHOLE DESIGNATION (TYPICAL) ENGRAVED 1/32" DEEP. NOT LESS THAN 1/32" WIDE. FOR REQUIRED DESIGNATION SEE PLANS
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
(BRASS-1/8" THICK)
AutoCAD SHX Text
%%UNAME PLATE
AutoCAD SHX Text 2 1/8"
AutoCAD SHX Text 2 1/2"
AutoCAD SHX Text E
AutoCAD SHX Text 10 1/2"
AutoCAD SHX Text A
AutoCAD SHX Text P
AutoCAD SHX Text 3"
AutoCAD SHX Text
%%USECTION A-A
AutoCAD SHX Text 3/16"
AutoCAD SHX Text
SYMMETRICAL ABOUT
AutoCAD SHX Text L
AutoCAD SHX Text C
AutoCAD SHX Text
MANHOLE CEILING
AutoCAD SHX Text
1/2" STAINLESS STEEL ANCHOR SLEEVE AND BOLT (TYPICAL)
AutoCAD SHX Text LINE MATERIAL TYPE NO8-LOC OR APPROVED EQUAL HOT DIPPED GALVANIZED CLENIS AND PIN TYPE HEAVY CABLE RACK (TYPICAL)
AutoCAD SHX Text LINE MATERIAL OR APPROVED EQUAL CLENIS AND PIN SUPPORT TYPE A, 3-GROOVE (TYPICAL)
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL CONNECTIONS GROUND ROD AND GROUND LOOP
AutoCAD SHX Text
NTS
AutoCAD SHX Text
AutoCAD SHX Text
MANHOLE CABLE RACK MOUNTING DETAIL
AutoCAD SHX Text
NTS
AutoCAD SHX Text
AutoCAD SHX Text
MANHOLE FRAME AND COVER DETAIL
NTS
| Sheet1 |
| 632-24-130 - Repair PV Carport System - Addendum1_04182025.pdf |
| E-001-ELECTRICAL SYMBOLS-E-001 |
| Sheets and Views |
| E-001 |
| E-201 - NEW WORK WEST-E-201 |
| Sheets and Views |
| E-201 |
| E-202 - NEW WORK SOUTH-E-202 |
| Sheets and Views |
| E-202 |
| E-301 - ELECTRICAL PART PLANS-E-301 |
| Sheets and Views |
| E-301 |
| E-501-ELECTRICAL DETAILS-E-501 |
| Sheets and Views |
| E-501 |
File details come from the government source that posted it. Updated .