D0904 Dental Lab Workstation wSuction and Electric Handpieces SOW.docx
DOCX document 695 KB Posted
- Attached to
- 6520--Brand Name or Equal DentalEZ / Nevins Lab Workstations with Suction and Electric Handpieces
- Solicitation number
- 36C24224Q0254
About this file
This statement of work outlines requirements for a dental lab workstation with suction and electric handpieces to outfit the dental department at a new VA clinic in Toms River, New Jersey. The VA seeks one two-sided, face-to-face pedestal workstation from Nevin Labs or equal. The workstation must include overhead task lighting, a dust collection system capable of collecting 0.5-micron particles at 750 CFM, electric handpieces with knee control for each user, and at least four drawers per side. Delivery is required between February and March 2024 to the Toms River VA clinic. The contractor must coordinate delivery and installation, which includes assembly, calibration, and waste removal. Training is not included.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24224Q0254.docx | DOCX document | |
| 36C24224Q0254_1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VHA New Jersey Health Care System Initial Outfitting, Transition & Activation Statement of Work Workstation, Pedestal, Dental Lab, Two-Sided, w/Dust Collector, and Electric Handpieces (JSN: D0904)
VHA New Jersey Health Care System Toms River VA Clinic 1051 Hooper Avenue Toms River, NJ 08753 Introduction The VHA New Jersey Health Care System has a requirement to purchase Workstation, Pedestal, Dental Lab, Two-Sided, w/Dust Collector, and Electric Handpieces (JSN: D0904) with an authorized vendor to supply and deliver the item(s) identified in Table 1 below to properly outfit the Dental Lab work area within the Dental Department of the new clinic. See salient characteristics below. This is a Brand Name or Equal Requirement. This requirement is in support of the activation of the New Toms River VA Clinic. Nevin Labs (Dental EZ) is the basis of design.
Table 1 – Package Items Summary
| Item # |
| JSN |
| Item Description |
| Part # (basis of design) |
| QTY |
| 1 |
| D0904 |
| 2 Person, Face to Face Pedestal Workstation w/dust collector, and 2 electric handpieces |
| Nevin Labs Pedestal Workstation |
| 1 |
Additional Item Requirements The vendor will provide service manuals that includes theory of operation, maintenance requirements, repair information, schematics, part lists and troubleshooting information in electronic format for use by the VA HTM Department.
Date of manufacture must not be greater than 2 years before the purchase order date. The equipment must not be used or refurbished and must have the latest manufacturer’s software/hardware updates installed. Any batteries provided with the unit will not be manufactured more than 12 months before the purchase order issue date.
General Conditions Site Address The address of the Toms River VA Clinic is provided below.
1051 Hooper Avenue Toms River, NJ 08753 Delivery Schedule Items shall be delivered no earlier than the estimated delivery start date and no later than the delivery end date listed in Table 2 below.
Table 2 – Anticipated Building Outfitting Schedule
| Building Name |
| Est. Delivery Start Date |
| Est. Delivery End Date |
| Toms River VA Clinic |
| 1 February 2024 |
| 15 March 2024 |
Schedule and Order Management The above delivery schedule is based upon the current construction schedule due to the nature of activation efforts and construction timelines and dates may vary and shift. Delivery dates need to be flexible. The delivery of items for installation are dependent upon the completion of applicable areas within the building. If there is a delay, the Contractor may be required to adjust the delivery date at no cost to the Government. The Contractor will coordinate with the on-site POC’s before delivery.
The awardee’s actual delivery dates will be confirmed by VA upon award.
Post-award, the vendor will coordinate delivery identified in this document with the VA prior to beginning any work (See Section 2.4). Once the dates have been confirmed, modifications to the schedule are subject to written approval by the CO, COR, and the vendor.
Delivery and Receiving Delivery and receipt of the proposed items is anticipated to be directed to the location identified below. Confirmation of delivery location will be provided post-award. To coordinate delivery, contact VA POC, David Stoff at (973) 968-1842, David.Stoff@va.gov; SME-Solutions POC, Heather Arvesen at (619) 504-4869, heather.arvesen@sme-solutions.co, and Robert Stonerook at (706) 304-7194, Robert.stonerook@sme-solutions.co.
☒ Toms River VA Clinic (Direct Delivery to address detailed in paragraph 2.1)
☐ IOT&A Contractor Provided warehouse: Address TBD The vendor is required to define the need for a staging area to accommodate item delivery, if needed. Post-award, this information will be confirmed with the vendor.
The delivery of items identified in this document shall take place during normal loading dock business hours which are defined as: 8:00 AM to 3:30 PM Eastern Standard Time, Monday through Friday, and excluding Federal Holidays.
Delivery trucks will not be permitted to remain in the receiving area. Trucks shall be unloaded, moved from the receiving area, and then brought back to the receiving area if required to haul out any waste, tools, or excess materials.
Labeling of delivered items shall include the VA facilities contract number and VA purchase order number for identification and reference upon receipt of product.
Clean Up and Disposal There are no dumpsters available for vendor use.
The removal of waste and/or excess material shall be conducted through the loading dock area.
Assembly, Installation, and Calibration Required (Yes ☒ No ☐) The vendor is required to manage and coordinate installation at the Toms River VA Clinic with the COR or his representative IOT&A POC.
On-site assembly and installation of items, and performance of services identified in this document shall take place during normal business hours which are defined as: 8:00 AM to 4:00 PM Eastern Standard Time, Monday through Friday, and excluding Federal Holidays.
The proposed installation date will occur after delivery of equipment. The current timeframe of delivery is February 1, 2024 – March 15, 2024.
The vendor is required to define the need for a staging area to accommodate item assembly and installation, if needed. Post-award, this information will be confirmed with the vendor.
The vendor is required to provide tools, labor and materials to complete assembly and installation of the items detailed in this document.
The vendor shall protect all finished spaces and surfaces as required from delivery and installation damage. The vendor shall use covering and protection to the extent necessary to prevent damage to finished spaces. Any damage that occurred during delivery and installation is the responsibility of the vendor. The vendor will be responsible for paying for and repairing any damage or noted deficiencies to finished spaces and surfaces that occur because of the vendor’s (or associated subcontractors) installation.
During the entire duration of assembly and installation, the vendor will have a competent representative on-site as the vendor’s contact, and to serve as the interface between the vendor and the Toms River VA Clinic. The on-site representative can be the installer. All instructions provided by COR to the representative will be binding as if given to the vendor’s main contact. The COR may provide specific instructions, however, only the Contracting Officer may change the terms or conditions of the contract.
Training Required (Yes ☐ No ☒)
2.8 Confidentiality and Non-Disclosure
1.1 This equipment Does Not connect to a VA network. Therefore, in accordance with Appendix A, Handbook 6500.6 Checklist, block 6, the C&A requirements Do Not apply to this requirement, and a Security Accreditation Package is Not required.
Salient Characteristics Workstation, Pedestal, Dental Lab, Two-Sided, w/Dust Collector, and Electric Handpieces (JSN: D0904) Total Quantity: 1 ☐ Network Required if Checked ☒ Manufacturer Certified Installation Required if Checked ☐ BMET Training Required if Checked ☐ End User Training Required if Checked
Basis of Design: Nevin Labs (DentalEZ) Pedestal Workstation w/VARIOstar K50 Knee Control Electric Handpiece
Brand Name or Equal Requirement
Description: Modular technician's workstation for the dental laboratory. The unit contains an overhead task lighting array. The workstation also includes a dust extraction system with filtration, knee activated electric handpieces, a minimum of 4 drawers for storage, per side, and electrical outlets for accessory equipment. The workstation generally has slanted overhead case pan shelves for storing equipment trays. The desktop is made from a fiber/cement mixture or similar material to resist heat, abrasion, and chemical attack. The workstation shall have the following Salient Characteristics:
Salient Characteristics:
· Shall be two-sided, face to face, pedestal design
· Shall be between 44” to 48” in length
· Shall be between 55” to 60” deep (entire face to face pedestal workstation)
· Shall have a work surface depth of 20” to 24”
· Shall have an ADA seating opening of approximately 32” high
· Shall have at least four drawers, per user
· Shall have at least a 35-watt task side, and two slanted overhead case pan shelves per user
· Task light and shelves shall be at least 40” in length and not extend past the outer dimension of the workstation
· Shall have at least two sets of double duplex outlets per user
· Shall have an integrated dust collector
· capable of collecting 0.5 microns
· capable of at least 750 CFM
· blast gates will be approximately 3.5” in diameter and mounted to the rear of the work surface, one per user
· Workstation shall be in Postal Blue color or similar
· Shall have a solid surface countertop in Sanded Grey color or similar
· Shall be 120VAC, 60Hz, 20Amp with hospital grade plug
· Shall have a brushless handpiece with knee control, one per user
· capable of being operated with left or right hand rotation
· up to 50,000 rpm
· capable of sending start-up signal to dust collector
· Shall be 115VAC, 60Hz, with hospital grade plug
Statement of Work Page 1 of 8 image2.png
File details come from the government source that posted it. Updated .