36C24221Q0367 0003.docx
DOCX document 17 KB Posted
- Attached to
- J059--Uninterrupted power source questions and answers Additional Questions and Answers Federal contract opportunity
- Solicitation number
- 36C24221Q0367
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24221Q0367 0004.docx | DOCX document | |
| 36C24221Q0367 0001_1.docx | DOCX document | |
| 36C24221Q0367 0001.docx | DOCX document | |
| 36C24221Q0367.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Contract Opportunity Amendment to a Previous Combined Solicitation
PRODUCT SERVICE CODE
SUBJECT
CONTRACTING OFFICE'S
ZIP-CODE
SOLICITATION NUMBER
BASE NOTICE TYPE
RESPONSE DATE/TIME/ZONE
ARCHIVE
DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
SET-ASIDE
NAICS CODE
CONTRACTING OFFICE
ADDRESS
POINT OF CONTACT
(POC Information Automatically Filled from User Profile Unless Entered)
DESCRIPTION
See Attachment
AGENCY'S URL
URL DESCRIPTION
AGENCY CONTACT'S EMAIL
ADDRESS
EMAIL DESCRIPTION
ADDRESS
POSTAL CODE
COUNTRY
ADDITIONAL INFORMATION
GENERAL INFORMATION
PLACE OF PERFORMANCE
* = Required Field Contract Opportunity Amendment to a Previous Combined Solicitation J059 Uninterrupted power source
ADDITIONAL QUESTIONS AND ANSWERS
12203 36C24221Q0367 02-26-2021
10:00 AM
EASTERN TIME, NEW YORK, USA
N
SDVOSBC
811219 Department of Veterans Affairs
NCO 2
20 MADISON AVE EXT
Albany NY 12203
CONTRACT SPECIALIST
MARIANGIE RIVERA
MARIANGIE.RIVERA@VA.GOV
NJ HEALTHCARE SYSTEM
LYONS
EAST ORANGE
NJ
USA
MARIANGIE.RIVERA@VA.GOV
QUESTIONS & ANSWERS
***Please note questions will not be accepted after 02/19/2021 10:00AM EASTERN***
ADDITIONAL QUESTIONS 02/17/2021
Questions: We need some additional information in order to bid on this contract:
1. Please provide the serial number for the Lyons Campus Eaton 9390
1. Please provide the Quantity, Model Numbers, and Serial Numbers for the PDU, PDR, and RPP.
Answers: 1. EA412CBA07 - Serial Number
2. There is one RRP Easton Pow-R-Line C Model PRL4 Panelboard - Volts 208/120 V – Box Cal. BX2473. No serial number on the unit.
PDU and PDR are one in the same and provides power from the power source to the communications unit. This is for the IT personnel to determine not FMS. I was able to count 18 racks with various manufactures names on them. Corning, Compax and HP.
In addition, these are never serviced and have no moveable parts. If you need more information, then IRM will have to provide the exact Models and Serial Numbers of these units.
Question: Is this a new or follow-on requirement? If a follow-on, who is the incumbent and what is the contract number?
Answer: This is a new requirement. Further information on prior contract will not be released.
Original Questions and Answers posted 02/12/2021
Question: The model and make for both campuses regarding UPS?
Answer: These are the 2 East Orange UPS’S
Each UPS has 80 batteries
Make: Eaton Model: 9390-80 SN: EB283CBA03 (UPSA)
Make: Eaton Model: 9390-80 SN: EB311CBA07 (UPSB)
Answer: For the Lyons campus: EATON – MODEL - POWERWARE 9390
Questions:
1. Regarding the “hours” block in the cost matrix. Is this a request for a generalized normal business hours repair rate?
2. Regarding the parts listed in section A. GENERAL REQUIREMENTS - OPERATIONAL INSPECTIONS, Is this what you want looked at on a PM?
3. Can you tell us the number and type of battery for each unit?
4. Are you looking to have your equipment covered in a full-service contract or is this for PM’s only?
Answer: The hours are of normal business hours. PMI only annually, this should include GENERAL REQUIREMENTS along with OPERATIONAL INSPECTIONS. We have one unit at the Lyons Campus, there are 40 batteries total, dry type, sealed type.
Lyons
1. Power Module Question: What are these and are they part of the UPS?
Answer: Power Module – The Power Ware 9390 UPS consists of a rectifier, battery converter, inverter, monitoring/operation control panel, integrated communication server and digital signal processor (DSP) logic.
2. Ancillary devices Question: What are these?
Answers: Ancillary Devices – Single Module Reverse Transfer (RT) operates independently to support an applied load from the inverter. Single Module RT Modes supports a critical load in three different modes of operations. The standard operation modes are:
1. Normal mode – critical load is supplied by the inverter, which derives it power from rectified utility AC power. The battery charger provides charging current for the battery, if needed.
1. Battery mode – the battery provides DC power, which maintains inverter operation. The battery mode, the battery provides DC power, which maintains inverter operation. The battery supports the critical load.
1. Bypass mode – the critical load is directly supported by utility power.
3. PDU/PDR/RPP/STS
Question: Need more detail and quantities?
Answers: PDU are distribution cabinets consisting of power strips for power to the racked I.T. equipment, which is located in the same room as the UPS.
b. PDR are power distribution racks for multipower cords for the PDUs.
c. RPP is a Remote Power Panel which provides power to the existing panels located in the computer room for maximum output.
d. STS is a Static Transfer Switch utilizes a static electronic component (SCR) which permits a transfer in less than four milliseconds.
4. Sealed Battery System and Non-Eaton equipment (MVS) Question: What are these supporting and how many are there?
Answers: Sealed Battery System and Non-Easton Equipment
1. There are 80 sealed batteries and they are feeding the entire PDUs from the distribution cabinets, in turn providing power to the PDRs for the I.T. equipment in the computer room.
1. Model UPS Powerware – 9390-80/80 Module rated 80Kva/72Kw.
5. Eaton UPS Question: What is the Model and KVA of this unit and how many batteries associated?
Answer: Eaton DC – 480 volts – D.C.
6. Eaton DC Question: What is the Model and Amperage of this unit and how many batteries associated?
Answer: answered above
7. Eaton PDU/PDR/RPP/STS and Non Eaton Equipment (MVS) Question: What are these supporting and how many are there?
Answer: answered above