This is a Special Notice of Intent to Award a sole-source contract for the replacement of an uninterruptible power supply (UPS) system at the West Haven VA Medical Center in Connecticut. The Department of Veterans Affairs Network Contracting Office, located in Bedford, Massachusetts, is seeking to procure one 150kVA TMEiC uninterruptible power supply to replace the existing unit for the Canon Aquilion One PRISM CT system. The solicitation number is 36C24126Q0674, with a response deadline of August 3, 2026, at 4:30 PM Eastern Time. This is a firm-fixed-price sole-source contract, and the Government intends to award based on this notice unless responses demonstrate clear and convincing evidence that competition would be advantageous.
The UPS system must meet specific technical requirements including 480 VAC input and output at 60Hz with three-phase, three-wire plus ground configuration, a minimum DC voltage of 400 VDC, reflected current THD of 3% at full load, a transient recovery time of 20 milliseconds, and overload capacities ranging from 105% to 150% load depending on duration. The equipment must not exceed 860 pounds and specific dimensional constraints: 81 inches height plus 19.7 inches clearance, 33 inches depth plus 40 inches service clearance, and 28 inches width. The contractor must provide complete documentation including installation, operation, and service manuals within three business days of award, perform removal and disposal of the existing UPS, deliver and install the new system, and complete all work within 180 days of contract award during normal business hours (7 AM–5 PM, Monday–Friday, excluding Federal Holidays). The place of performance is VA Connecticut Healthcare System Radiology Department at 950 Campbell Avenue, West Haven, Connecticut 06516. The point of contact is Contracting Officer Manases Cabrera at manases.cabrera@va.gov or 781-687-4418.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Special Notice Special Notice
| SUBJECT* |
| UPS Replacement for Canon CT |
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 01730 |
| SOLICITATION NUMBER* |
| 36C24126Q0674 |
| RESPONSE DATE/TIME/ZONE |
| 08-03-2026 4:30PM EASTERN TIME, NEW YORK, USA |
| ARCHIVE |
| 60 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
| PRODUCT SERVICE CODE* |
| 6130 |
| NAICS CODE* |
| 335999 |
| CONTRACTING OFFICE ADDRESS |
| Department of Veterans Affairs |
Network Contracting Office 1
200 Springs Road Bedford MA 01730
POINT OF CONTACT*
Contracting Officer Manasés Cabrera manases.cabrera@va.gov 781-687-4418
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
| AGENCY CONTACT’S EMAIL ADDRESS |
| manases.cabrera@va.gov |
| EMAIL DESCRIPTION |
| POC EMail |
DESCRIPTION
This notice is being published in accordance with the Federal Acquisition Regulation (FAR) Part 5, requiring the dissemination of information on proposed contract actions. This is a notice of intent to award a sole-source contract pursuant to 10 U.S.C 2304 (C)(1), as implemented by FAR 6, only one responsible source, and no other supplies or services will satisfy agency requirements, and brand-name descriptions.
The Department of Veterans Affairs Medical Center located at 950 Campbell Ave, West Haven CT 06516 has a requirement for the replacement of the one (1) uninterruptible power supply for the Canon Aquilion One PRISM CT system.
The Government intends to award a firm-fixed-price sole source contract.
A determination by the Government not to compete with this proposed contract based upon responses to this notice is solely within the discretion of the Government. This notice of intent is not a request for competitive proposals. This is a written notice to inform the public of the Government's intent to award on a sole source basis.
Interested parties may identify their interest and capability to respond to the requirement. Any response to this notice must show clear and convincing evidence that competition will be advantageous to the Government.
Please contact Manasés Cabrera, Contracting Specialist, with the responses or questions regarding this requirement at manases.cabrera@va.gov.
This notice will close on August 3, 2026, at 4:30 PM Eastern Standard Time (EST)
STATEMENT OF WORK FOR THE REPLACEMENT OF THE UNINTERRUPTIBLE POWER SUPPLY FOR THE CANON CT SYSTEM
BACKGROUND
West Haven VA Medical Center requires the replacement of the one (1) uninterruptible power supply for the Canon Aquilion One PRISM CT system.
OBJECTIVES
Deliver one (1) 150Kva TMEiC uninterruptible power supply (UPS) to the West Haven VA Medical Center. The contractor shall electronically provide all documentation required for installation, operation, and maintenance immediately upon award. Contractors shall provide breakdowns, make the existing UPS safe, removal and disposal of the existing UPS and delivery and installation of the new UPS including the reconnection, configuration, testing and start-up by go-live of system.
SCOPE
Deliver one (1) 150kVA TMEiC uninterruptible power supply (UPS) to the West Haven VA Medical Center. Provide documentation required for deinstallation, installation, operation and maintenance upon award. Perform breakdown, removal/disposal of existing UPS and delivery/installation of new UPS.
UPS REQUIREMENTS
Provide and install one 150kVA TMEiC UPS system meeting the following minimum requirements:
· Quantity: One (1) TMEiC Uninterruptible Power Supply
· 480 VAC Input, 60Hz
· 480 VAC Output, 60Hz
· 3 phase 3-wire plus ground
· Reflected Current THD:
· 3% typical at 100% load
· 5% typical at 50% load
· Minimum DC Voltage of 400 VDC
· Transient recovery time of 20ms
· Overload capacity:
· 105% to 100% load for 1 hour
· 111% load for 2 minutes
· 120% to 150% load for 1 minute
· Must have a force air cooling method
· The system must not exceed 860 pounds
· Shall not exceed the following dimensions:
· Height: 81” max equipment height
· Plus 19.7” max clearance requirement above equipment
· Depth: 33” max equipment depth
· Plus 40” max service clearance requirement in front of equipment
· Width: 28”
· Provide UPS documentation including installation, operation, and service manuals, electrical schematics, site preparation requirements, environmental requirements, and dimensional drawings of the UPS
TASKS
Provide documentation to the COR electronically, within 3 business days of award, including installation manual, operation manual, service manual, electrical schematics, site preparation requirements, environmental requirements, and dimensional drawings of the UPS.
Deliver one (1) 150kVA TMEiC Uninterruptible Power Supply, which meet the UPS requirements defined in this statement of work, to the West Haven VA Medical Center.
Provide services that include breakdown, removal/disposal of existing UPS, delivery/installation of new UPS and testing/configuration of the new UPS
DELIVERABLES
Complete the replacement of the one (1) 150kVA TMEiC uninterruptible power supply for the Canon Aquilion One PRISM CT system.
PERIOD OF PERFORMANCE
Deliverables shall be performed within 180 days of contract award. All work shall occur during normal business hours 7 AM-5 PM, Monday-Friday, excluding Federal Holidays.
PLACE OF PERFORMANCE
VA Connecticut Healthcare System Radiology Department, Building 1, Room G187F 950 Campbell Ave.
West Haven, CT 06516
NARA Records Management Requirements
The following standard items relate to records generated in executing this contract:
1. Citations to pertinent laws, codes and regulations such as 44 U.S.C. Chapter 21, 29, 31, and 33; Freedom of Information Act (5 U.S.C. 552); Privacy Act (5 U.S.C. 552a); 36 CFR Part 1222 and Part 1228.
1. Contractor shall treat all deliverables under the contract as the property of the U.S. Government for which the Government Agency shall have unlimited rights to use, dispose of, or disclose such data contained therein as it determines to be in the public interest.
1. Contractor shall not create or maintain any records that are not specifically tied to or authorized by the contract using Government ‘IT’ equipment and/or Government records.
1. Contractor shall not retain, use, sell, or disseminate copies of any deliverable that contains information covered by the Privacy Act of 1974 or that which is generally protected by the Freedom of Information Act.
1. The Contractor shall not create or maintain any records containing any Government Agency records that are not specifically tied to or authorized by the contract.
1. The Government Agency owns the rights to all data/records produced as part of this contract.
1. The Government Agency owns the rights to all electronic information (electronic data, electronic information systems, electronic databases, etc.) and all supporting documentation created as part of this contract. The Contractor must deliver sufficient technical documentation with all data deliverables to permit the agency to use the data.
1. The Contractor agrees to comply with Federal and Agency records management policies, including those policies associated with the safeguarding of records covered by the Privacy Act of 1974. These policies include the preservation of all records created or received regardless of format [paper, electronic, etc.] or mode of transmission [e-mail, fax, etc.] or state of completion [draft, final, etc.].
1. No disposition of documents will be allowed without the prior written consent of the Contracting Officer. The Agency and its contractors are responsible for preventing the alienation or unauthorized destruction of records, including all forms of mutilation. Willful and unlawful destruction, damage, or alienation of Federal records is subject to the fines and penalties imposed by 18 U.S.C. 2701. Records may not be removed from the legal custody of the Agency or destroyed without regard to the provisions of the agency records schedules.
1. The Contractor is required to obtain the Contracting Officer’s approval prior to engaging in any contractual relationship (sub-contractor) in support of this contract requiring the disclosure of information, documentary material and/or records generated under or relating to this contract. The Contractor (and any sub-contractor) is required to abide by Government and Agency guidance for protecting sensitive and proprietary information.
| *= Required Field |
| Special Notice |
Special Notice
File details come from the government source that posted it. Updated .