EP-25---Door-Assemblies-Fire-Doors-Inspection-Report.pdf

PDF 6 MB Posted

Attached to
J042--Door Inspections and Repair Service Contract
Solicitation number
36C24126Q0497
Issued by

About this file

This is an Initial Annual Fire & Smoke Door Inspection Report prepared by DH Pace Inc. for Faletti Construction LLC at the Manchester VA Medical Center, 718 Smyth Road, Manchester, NH 03104. The comprehensive inspection was conducted between August 26 and September 18, 2024, under Inspection No. SLS484561, based on NFPA 80-2010 standards for healthcare facilities. The inspection covered 107 total door openings across multiple buildings (DVA-1, DVA-1 EAST, DVA-15, DVA-18, and DVA-1E) and multiple floors, evaluating fire and smoke door assemblies including frames, hardware, glazing, gasketing, and labeling. Initial results showed 55 doors passing inspection and 52 failing; after repairs, 87 doors passed and 20 remained failed. The report identifies 20 failed openings categorized by priority: 6 critical deficiencies requiring urgent corrective action, 12 immediate deficiencies requiring corrective action without delay, and 1 essential deficiency requiring corrective action. Common deficiencies include missing or broken hardware parts (FC4), field modifications voiding labels (FC10), non-operational self-closing devices (FC6), non-functioning latching hardware (FC8), door clearance violations (FC5), missing door labels (FC13.D and FC13.F), open holes in door or frame surfaces (FC1), and louver/transfer grill installations in fire/smoke barrier doors (FC15). The report was prepared by Certified Fire Door Assembly Inspector (CFDAI) Ivan Albert and reviewed on September 18, 2024, with DH Pace recommending the owner remove excess signage and verify ratings of protective devices, electric strikes, power transfer cords, sensors, and sealing components.

View the file

Other files

File Type Posted
5.10_Rpt14_April23_30583.pdf PDF
36C24126Q0497_1.docx DOCX document
36C24126Q0497.docx DOCX document
36C24126Q0497.docx DOCX document
Wage Determination 2015-4019 rev 33.pdf PDF
Attachment 3 852.219-75 Limitation on Subcontracting.pdf PDF
Attachment 1 FAR 52.212-1.pdf PDF
ADDENDUM to 52.212-2 EVALUATION -Deviation Aug 2025.pdf PDF
QASP_Campus_Wide_Doors.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Initial Annual Fire & Smoke Door Inspection

Faletti Construction LLC

Manchester Va

718 Smyth Road

Manchester, NH 03104

Inspection No.: SLS484561

Code Edition: NFPA 80 - 2010 for Healthcare

Inspection Initiated: August 26 2024

If the report indicates that deficiencies were found (and were not repaired on-site), please refer to corresponding proposal.

This comprehensive FireCheck® inspection report is based on NFPA 80 (fire) and NFPA 105 (smoke) requirements. This report applies only to door list provided by the Customer.

Code Interpretation Disclaimer: All information provided by DH Pace Inc. represents our interpretation regarding the intent of the standard(s) and/or code(s) applicable to the issue being addressed. By law, the Authority Having Jurisdiction (AHJ) is the only entity with the legal standing and discretionary authority to make a definitive ruling on these matters. As such, DH Pace disclaims any consequential damages that may arise from the use of the information provided, recommendation made, or opinions expressed on this matter.

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Inspection No. SLS484561 Printed 9/18/2024 2:20 PM 1 of 127

Initial Annual Fire & Smoke Door Inspection Summary Name Manchester Va Contact Faletti, Alex

Address 718 Smyth Road Contact # (801) 201-8438

City, State Zip Manchester, NH 03104 Inspection Dates 8/26/2024 To 9/18/2024

P/F Initial Repaired Post Repair

Pass 55 32 87

Fail 52 5 20

Total 107 37

Priority of Failed Openings Opening #

Critical 6

Immediate 12

Essential 1

Total Failed 20

Priority Definitions

Critical - Deficiency requires urgent corrective action without delay

Immediate - Deficiency requires corrective action without delay

Essential - Deficiency requires corrective action, safety concern

Owner to remove excess signage.

Owner to verify rating of protection plates, electric strikes, power transfer cords, presence sensors, door position/alarm sensors, steel pick guards, door/frame guards, gasketing/perimeter seal, door viewers, and auto door bottoms/sweeps.

Name: Ivan Albert - CFDAI Signature: Date: 9/18/2024

Ivan Albert DH Pace Compliance Services

3035 Horseshoe Lane, Suite R

Charlotte, NC 28208

(704) 527-5379

Main: (516) 317-9495

Email: Ivan.Albert@dhpace.com

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 2 of 127

Initial Annual Fire & Smoke Door Inspection Criteria Name Manchester Va Code Edition:

Address 718 Smyth Road Manchester, NH 03104 NFPA 80 - 2010 for Healthcare

Inspection Dates 8/26/2024 To 9/18/2024 Inspection No. SLS484561

Criteria Components Description # Failed Openings

FC1 Frame, Door No open holes or breaks exist in surfaces of either the door or frame. 3

FC2 Frame, Door Glazing, vision light frames, and glazing beads are intact and securely fastened in place, if so equipped. Safety glass is the correct size and type.

FC3 Frame, Door, Hardware The door, frame, hinges, hardware and non-combustible threshold are secured, aligned, and in working order with no signs of visible damage.

FC4 Frame, Door, Hardware No parts are missing or broken. 4

FC5 Top, Bottom, Hinge Edge, Strike Edge

Door clearances do not exceed clearances listed in 4.8.4 and 6.3.1.7. WOOD/PLAM EDGES/TOP not > 1/8", WOOD/PLAM BOTTOM not > 3/4", HM-STEEL EDGES/TOP 1/8" + or - 1/16", HM-STEEL BOTTOM not > 3/4"

FC6 Hardware The self-closing device is operational, that is, the active door completely closes when operated from the full open position.

FC7 Hardware If a coordinator is installed, the inactive leaf closes before the active leaf. 0

FC8 Hardware Where latching hardware is required, it operates and secures the door when it is in the closed position (not required for cross-corridor doors 1-hr Smoke Barriers in Healthcare deemed "Substantial Doors" and not 20-min rated/labeled)

FC9 Hardware Auxiliary items that interfere or prohibit operation are not installed on the door or frame. 0

FC10 Frame, Door, Hardware No field modifications to the door assembly have been performed to void the label. 6

FC11 Frame, Door Gasketing and edge seals, where required, are inspected to verify their presence and integrity.

FC12 Size, Mounting Signage is the correct size and mounted properly. 1

FC13.D Door Labels are present and readily visible on the opening door. 2

FC13.F Frame Labels are present and readily visible on the opening frame. 2

FC13.G Glass Labels are present and readily visible on the opening glass. 0

FC13.H Hardware Labels are present and readily visible on the opening hardware. 0

FC13.P Protection Plate Labels are present and readily visible on the protection plate (when plate is mounted above 16" from bottom of door)

FC14 Hardware Doors installed in pressurized applications have gasketing and a bottom seal (note deficient gasketing on FC11)

FC15 Hardware No louvers or transfer grills in door (when door is in combo fire and smoke barrier or just smoke barrier)

Door Type S - Single UP - Unequal Pair P - Pair DE - Double

Egress B - Bank D - Dutch

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 3 of 127

Initial Annual Fire & Smoke Door Inspection Details Name Manchester Va

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1

Floor: 1

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0072 265-410299-001-0072 Passed STAIR E 137 Ivan Albert 9/06/2024

Single Hollow Metal 46" (3'10") x 84"

Hollow Metal Filled 1-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0073 265-410299-001-0073 Passed WAITING RM E129 Ivan Albert 9/06/2024

Pair Wood 44" (3'8") x 84"

Hollow Metal Not Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

0074 265-410299-001-0074 Passed STAIR #1 E111 Kevin Sheehan 9/16/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0075 265-410299-001-0075 Passed ELECTRICAL CL E110 Ivan Albert 8/27/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0077 265-410299-001-0077 Passed ELECTRICAL CL N145 Kevin Sheehan 9/18/2024

Single Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

0077 265-410299-001-0077 Passed ELECTRICAL CL N145 Ivan Albert 8/27/2024

Single Hollow Metal 24" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0078 265-410299-001-0078 Passed CORRIDOR N147A Ivan Albert 8/27/2024

Double Egress Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

0079 265-410299-001-0079 Passed STAIR #4 N126 Kevin Sheehan 9/16/2024

Single Hollow Metal 32" x 84" Hollow Metal Not Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0080 265-410299-001-0080 Passed STAIR #3 W145 Kevin Sheehan 9/16/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 4 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1

Floor: 1

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0081 265-410299-001-0081 Passed SPRINKLER CONTROL Ivan Albert 8/27/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0082 265-410299-001-0082 Passed ELECTRICAL CL W146 Ivan Albert 8/27/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0083 265-410299-001-0083 Failed VESTIBULE NW141 Kevin Sheehan 9/18/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier Critical

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A FC6

0084 265-410299-001-0084 Passed VESTIBULE NW141 Kevin Sheehan 9/16/2024

Pair Wood 46" (3'10") x 90"

Hollow Metal Not Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

0085 265-410299-001-0085 Passed EMER ELECTR SW103 Ivan Albert 8/27/2024

Single Wood 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0086 265-410299-001-0086 Passed ELECTRICAL CL SW102 Ivan Albert 8/27/2024

Single Wood 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0087 265-410299-001-0087 Failed OFFICE NW101 Ivan Albert 9/06/2024

Single Wood 36" x 84" Hollow Metal Not Filled 2-Hour Fire Barrier Immediate

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A FC4

Floor: 2

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0063 265-410299-001-0063 Passed STAIR #1 E209 Kevin Sheehan 9/18/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 5 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1

Floor: 2

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0064 265-410299-001-0064 Passed ELECTIRCAL CL E210 Kevin Sheehan 9/16/2024

Single Hollow Metal 30 x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0065 265-410299-001-0065 Passed STAIR #2 N286 Kevin Sheehan 9/18/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0066 265-410299-001-0066 Passed ELECTRICAL CL N285 Kevin Sheehan 9/18/2024

Single Hollow Metal 30 x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0067 265-410299-001-0067 Passed STAIR #4 N273 Kevin Sheehan 9/18/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0068 265-410299-001-0068 Passed ELECTRICAL CL N 272 Kevin Sheehan 9/16/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0069 265-410299-001-0069 Passed ELECTRICAL CL W255 Kevin Sheehan 9/16/2024

Pair Hollow Metal 24" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

0070 265-410299-001-0070 Passed STAIR #3 W246 Kevin Sheehan 9/18/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0071 265-410299-001-0071 Passed ELECTRICAL CL W247 Kevin Sheehan 9/16/2024

Single Hollow Metal 30" x 80" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0148 265-410299-001-0148 Passed ELECTRICAL W154A Ivan Albert 8/27/2024

Pair Hollow Metal 24" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 6 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1

Floor: 2

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0149 265-410299-001-0149 Passed CHAPEL N267 Ivan Albert 9/06/2024

Single Wood 42" (3'6") x 84"

Hollow Metal Not Filled 1-Hour Smoke Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 20 mins N/A N/A

Floor: 3

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0053 265-410299-001-0053 Passed STAIR #1 E316 Kevin Sheehan 9/18/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0054 265-410299-001-0054 Passed ELECTRICAL CL E315 Ivan Albert 8/26/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0055 265-410299-001-0055 Passed ELECTRICAL CL N389 Ivan Albert 8/26/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0056 265-410299-001-0056 Passed STAIR - N390 Kevin Sheehan 9/18/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 1-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0057 265-410299-001-0057 Passed STAIR #4 N375 Kevin Sheehan 9/16/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0058 265-410299-001-0058 Passed ELECTRICAL CL N376 Ivan Albert 8/26/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0059 265-410299-001-0059 Passed ELECTRICAL C W357A Ivan Albert 8/26/2024

Pair Hollow Metal 24" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 7 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1

Floor: 3

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0061 265-410299-001-0061 Passed STAIR #3 W349 Kevin Sheehan 9/18/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0062 265-410299-001-0062 Passed ELECTRICAL CL W350 Ivan Albert 8/26/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Floor: 4

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0044 265-410299-001-0044 Passed STAIR #1 E415 Kevin Sheehan 9/16/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0045 265-410299-001-0045 Passed ELECTRICAL CL E414 Ivan Albert 8/26/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0046 265-410299-001-0046 Passed STAIR #2 N498 Kevin Sheehan 9/18/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0047 265-410299-001-0047 Passed ELECTRICAL CL N497 Ivan Albert 8/26/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0048 265-410299-001-0048 Passed STAIR #4 N481 Ivan Albert 9/06/2024

Single Hollow Metal 44" (3'8") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0049 265-410299-001-0049 Passed ELECTRICAL CL N480A Ivan Albert 9/06/2024

Single Hollow Metal 24" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 8 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1

Floor: 4

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0050 265-410299-001-0050 Passed ELECTRICAL CL W453 Ivan Albert 8/26/2024

Pair Hollow Metal 24" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

0051 265-410299-001-0051 Passed STAIR #3 W446 Kevin Sheehan 9/16/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0052 265-410299-001-0052 Passed ELECTRICAL CL W447 Kevin Sheehan 9/16/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Floor: 5

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0033 265-410299-001-0033 Passed STAIR #1 E515 Kevin Sheehan 9/16/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0034 265-410299-001-0034 Passed ELECTRICAL CL E514 Ivan Albert 8/26/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0035 265-410299-001-0035 Passed STAIR #2 N578 Kevin Sheehan 9/16/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0036 265-410299-001-0036 Passed ELECTRICAL CL N577 Ivan Albert 8/26/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0037 265-410299-001-0037 Passed STAIR N565 Kevin Sheehan 9/18/2024

Single Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 9 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1

Floor: 5

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0038 265-410299-001-0038 Passed CORRIDOR N569A Ivan Albert 9/06/2024

Single Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0039 265-410299-001-0039 Failed MECHANICAL N566 Kevin Sheehan 9/16/2024

Single Hollow Metal 36" x 84" Hollow Metal Not Filled 2-Hour Fire Barrier Immediate

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A FC13.F

0040 265-410299-001-0040 Passed MECHANICAL N567 Ivan Albert 8/26/2024

Single Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0041 265-410299-001-0041 Passed ELECTRICAL CL W566 Kevin Sheehan 9/16/2024

Pair Hollow Metal 24" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

0042 265-410299-001-0042 Passed ELECTRICAL CL W549 Ivan Albert 8/26/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0043 265-410299-001-0043 Passed STAIR #3 W548 Ivan Albert 9/06/2024

Single Hollow Metal 44" (3'8") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Floor: 6

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0025 265-410299-001-0025 Passed STAIR #1 E614 Kevin Sheehan 9/16/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0026 265-410299-001-0026 Passed ELECTRICAL CL E613 Ivan Albert 8/26/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 10 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1

Floor: 6

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0027 265-410299-001-0027 Passed ELECTRICAL CL N661 Ivan Albert 8/26/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0028 265-410299-001-0028 Passed STAIR #2 N662 Kevin Sheehan 9/16/2024

Single Hollow Metal 44" (3'8") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0029 265-410299-001-0029 Passed STAIR N653 Ivan Albert 8/26/2024

Single Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0030 265-410299-001-0030 Passed ELECTRICAL CL W645 Ivan Albert 9/06/2024

Pair Hollow Metal 24" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

0031 265-410299-001-0031 Failed STAIR #3 W638 Kevin Sheehan 9/18/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier Essential

0031 265-410299-001-0031 Passed STAIR #3 W638 Ivan Albert 9/06/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Floor: 7

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0024 265-410299-001-0024 Passed STAIR #2 E703 Ivan Albert 8/26/2024

Single Hollow Metal 44" (3'8") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Floor: B

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0091 265-410299-001-0091 Passed STAIR #1 E07 Kevin Sheehan 9/16/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 11 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1

Floor: B

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0092 265-410299-001-0092 Passed ELECTRICAL CL E06 Ivan Albert 9/06/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0094 265-410299-001-0094 Failed STAIR #2 N100 Kevin Sheehan 9/16/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier Immediate

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A FC1, FC4, FC5

0095 265-410299-001-0095 Passed ELECTRICAL CL N99 Ivan Albert 8/27/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0096 265-410299-001-0096 Failed STAIR #2 N100 Ivan Albert 9/06/2024

Single Hollow Metal 48" x 84" Hollow Metal Filled 2-Hour Fire Barrier Critical

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A FC1, FC8

0097 265-410299-001-0097 Passed ROOM NE103 Ivan Albert 8/27/2024

Single Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0098 265-410299-001-0098 Passed CORRIDOR N89 Kevin Sheehan 9/18/2024

Double Egress Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

0099 265-410299-001-0099 Passed EXIT PASSAGE N88 Kevin Sheehan 9/16/2024

Pair Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

0100 265-410299-001-0100 Failed EXIT PASSAGE N88 Kevin Sheehan 9/16/2024

Pair Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier Critical

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A FC8

Leaf B 90 mins N/A FC8

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 12 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1

Floor: B

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0101 265-410299-001-0101 Failed STAIR #4 N82 Ivan Albert 9/06/2024

Pair Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier Critical

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A FC8

Leaf B 90 mins N/A FC8

0102 265-410299-001-0102 Passed STAIR #4 N82 Ivan Albert 9/06/2024

Pair Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

0103 265-410299-001-0103 Passed ELECTRICAL CL N83 Ivan Albert 8/27/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0104 265-410299-001-0104 Passed ELECTRICAL N78 Ivan Albert 8/27/2024

Pair Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

0105 265-410299-001-0105 Failed EXIT PASSAGE N88 Ivan Albert 9/06/2024

Single Hollow Metal 44" (3'8") x 84"

Hollow Metal Filled 2-Hour Fire Barrier Immediate

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A FC10

0106 265-410299-001-0106 Failed EXIT PASSAGE N88 Kevin Sheehan 9/18/2024

Pair Hollow Metal 36" x 84" Hollow Metal Not Filled 2-Hour Fire Barrier Critical

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A Label Missing N/A FC5, FC13.D, FC13.F

Leaf B Label Missing N/A FC5, FC13.D, FC13.F

0107 265-410299-001-0107 Passed STAIR #3 W53 Kevin Sheehan 9/18/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0108 265-410299-001-0108 Passed ELECTRICAL CL W54 Ivan Albert 8/27/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Building: DVA-1 EAST

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 13 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 EAST

Floor: 1

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0145 265-410299-001-0145 Passed STAIR 5 SE091A Ivan Albert 8/27/2024

Single Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Floor: B

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0147 265-410299-001-0147 Passed STAIR 5 SE001B Ivan Albert 8/27/2024

Single Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Floor: LL

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0144 265-410299-001-0144 Passed STAIR 6 SE002A Ivan Albert 8/27/2024

Single Hollow Metal 44" (3'8") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Building: DVA-15

Floor: 1

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0007 265-410299-001-0007 Passed STAIR #1 S1A Kevin Sheehan 9/16/2024

Pair Hollow Metal 44" (3'8") x 84"

Hollow Metal Not Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

0008 265-410299-001-0008 Passed ELEV PUMP R D102 Ivan Albert 8/26/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 1-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0009 265-410299-001-0009 Failed CLOSET 104A Ivan Albert 8/27/2024

Single Hollow Metal 36" x 84" Hollow Metal Filled 1-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A Label Missing N/A FC13.D, FC15

0010 265-410299-001-0010 Failed STAIR #2 S2A Kevin Sheehan 9/16/2024

Pair Hollow Metal 36" x 84" Hollow Metal Not Filled 2-Hour Fire Barrier Immediate

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 14 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-15

Floor: 1

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0010 265-410299-001-0010 Passed STAIR #2 S2A Ivan Albert 9/06/2024

Single Hollow Metal 44" (3'8") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0011 265-410299-001-0011 Failed STAIR #3 S3A Ivan Albert 9/06/2024

Pair Hollow Metal 44" (3'8") x 84"

Hollow Metal Filled 2-Hour Fire Barrier Immediate

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A FC10

Leaf B 90 mins N/A FC10

0012 265-410299-001-0012 Passed CORRIDOR C14 Kevin Sheehan 9/16/2024

Pair Hollow Metal 42" (3'6") x 84"

Hollow Metal Not Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

Floor: 2

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0004 265-410299-001-0004 Failed STAIR S2A Kevin Sheehan 9/16/2024

Single Hollow Metal 36" x 84" Hollow Metal Not Filled 2-Hour Fire Barrier Immediate

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A FC5

0005 265-410299-001-0005 Failed ELECTRICAL D251 Ivan Albert 9/06/2024

Single Wood 36" x 84" Hollow Metal Not Filled 1-Hour Fire Barrier Immediate

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 45 mins N/A FC1

0006 265-410299-001-0006 Passed CIRC CORRIDOR C201 Kevin Sheehan 9/16/2024

Double Egress Hollow Metal 48" x 84" Hollow Metal Not Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

Floor: B

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0014 265-410299-001-0014 Passed STAIR #1 S1 Ivan Albert 8/26/2024

Single Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 15 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-15

Floor: B

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0015 265-410299-001-0015 Failed ELECTRICAL D02 Ivan Albert 9/06/2024

Single Hollow Metal 36" x 84" Hollow Metal Filled 1-Hour Fire Barrier Immediate

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A FC10

0016 265-410299-001-0016 Passed ELECTRICAL D02 Kevin Sheehan 9/16/2024

Single Wood 36" x 84" Hollow Metal Not Filled 1-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

0017 265-410299-001-0017 Passed CLOSET D04A Ivan Albert 9/06/2024

Single Hollow Metal 36" x 84" Hollow Metal Filled 1-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 180 mins N/A N/A

0018 265-410299-001-0018 Failed STAIR #2 S2 Ivan Albert 9/06/2024

Single Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier Immediate

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A FC10

0020 265-410299-001-0020 Failed STAIR #3 S3 Ivan Albert 9/06/2024

Pair Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier Immediate

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A FC10

Leaf B 90 mins N/A FC10

0022 265-410299-001-0022 Failed CORRIDOR C 5 Kevin Sheehan 9/16/2024

Double Egress Hollow Metal 42" (3'6") x 84"

Hollow Metal Not Filled 2-Hour Fire Barrier Immediate

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A FC5

Leaf B 90 mins N/A FC5

Building: DVA-18

Floor: 1

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0001 265-410299-001-0001 Passed WAITING RM 103 Kevin Sheehan 9/16/2024

Double Egress Wood 36" x 84" Hollow Metal Not Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Leaf B 90 mins N/A N/A

0002 265-410299-001-0002 Failed CORRIDOR 103A Ivan Albert 9/06/2024

Double Egress Wood 48" x 84" Hollow Metal Not Filled 2-Hour Fire Barrier Critical

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A FC4, FC6, FC8

Leaf B 90 mins N/A FC4, FC6, FC8

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 16 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-18

Floor: 1

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0003 265-410299-001-0003 Passed ELECTRICAL 106A Kevin Sheehan 9/16/2024

Single Hollow Metal 36" x 84" Hollow Metal Not Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Building: DVA-1E

Floor: 1

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0143 265-410299-001-0143 Passed STAIR Kevin Sheehan 9/16/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Not Filled 1-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 90 mins N/A N/A

Floor: B

Opening Door Type

Barcode Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

0146 265-410299-001-0146 Passed STAIR Kevin Sheehan 9/16/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Not Filled 1-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label Failed Fire Criteria

Leaf A 60 mins N/A N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 17 of 127

Initial Annual Fire & Smoke Inspection Door Details

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0072

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265-410299-001-0072 Yes / No Passed STAIR E 137 Ivan Albert 9/06/2024

Single Hollow Metal 46" (3'10") x 84"

Hollow Metal Filled 1-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label

Leaf A 90 mins N/A

Criteria Failed Notes General Notes Components Repaired Compliant Repaired

FC4 Strike plate missing fastener Hardware Yes Yes

FC4 - Repaired Deficiency

Push

Pull

FC4 - Deficiency

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Inspection Rpt. 8/26/2024

Printed 9/18/2024 2:20 PM 18 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0073

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265-410299-001-0073 Yes / No Passed WAITING RM E129 Ivan Albert 9/06/2024

Pair Wood 44" (3'8") x 84"

Hollow Metal Not Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label

Leaf A 90 mins N/A

Leaf B 90 mins N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Printed 9/18/2024 2:20 PM 19 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0074

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265-410299-001-0074 Yes / No Passed STAIR #1 E111 Kevin Sheehan 9/16/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label

Leaf A 90 mins N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Printed 9/18/2024 2:20 PM 20 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0075

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265-410299-001-0075 Yes / No Passed ELECTRICAL CL E110 Ivan Albert 8/27/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Printed 9/18/2024 2:20 PM 21 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0077

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265-410299-001-0077 Yes / No Passed ELECTRICAL CL N145 Kevin Sheehan 9/18/2024

Single Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Printed 9/18/2024 2:20 PM 22 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0077

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Printed 9/18/2024 2:20 PM 23 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0078

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265-410299-001-0078 Yes / No Passed CORRIDOR N147A Ivan Albert 8/27/2024

Double Egress Hollow Metal 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label

Leaf B 90 mins N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Printed 9/18/2024 2:20 PM 24 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0079

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265-410299-001-0079 Yes / No Passed STAIR #4 N126 Kevin Sheehan 9/16/2024

Single Hollow Metal 32" x 84" Hollow Metal Not Filled 2-Hour Fire Barrier N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Printed 9/18/2024 2:20 PM 25 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0080

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265-410299-001-0080 Yes / No Passed STAIR #3 W145 Kevin Sheehan 9/16/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label

Leaf A 90 mins N/A

FC4 Strike plate missing fastener Frame Yes Yes

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Printed 9/18/2024 2:20 PM 26 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0081

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265-410299-001-0081 Yes / No Passed SPRINKLER CONTROL Ivan Albert 8/27/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Printed 9/18/2024 2:20 PM 27 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0082

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265-410299-001-0082 Yes / No Passed ELECTRICAL CL W146 Ivan Albert 8/27/2024

Single Hollow Metal 30" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Printed 9/18/2024 2:20 PM 28 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0083

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265-410299-001-0083 Yes / No Failed VESTIBULE NW141 Kevin Sheehan 9/18/2024

Single Hollow Metal 42" (3'6") x 84"

Hollow Metal Filled 2-Hour Fire Barrier Critical

Leaf Fire Rating Smoke Label

Leaf A 90 mins N/A

Criteria Failed Notes General Notes Components Repaired Compliant Repaired

FC6 Closer leaking fluid Hardware No No

FC6 Closer leaking fluid Hardware No No

FC6 - Deficiency

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Printed 9/18/2024 2:20 PM 29 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0084

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265-410299-001-0084 Yes / No Passed VESTIBULE NW141 Kevin Sheehan 9/16/2024

Pair Wood 46" (3'10") x 90"

Hollow Metal Not Filled 2-Hour Fire Barrier N/A

Leaf Fire Rating Smoke Label

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Printed 9/18/2024 2:20 PM 30 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0085

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265-410299-001-0085 Yes / No Passed EMER ELECTR SW103 Ivan Albert 8/27/2024

Single Wood 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Printed 9/18/2024 2:20 PM 31 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0086

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265-410299-001-0086 Yes / No Passed ELECTRICAL CL SW102 Ivan Albert 8/27/2024

Single Wood 36" x 84" Hollow Metal Filled 2-Hour Fire Barrier N/A

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Printed 9/18/2024 2:20 PM 32 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 1 Opening: 0087

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265-410299-001-0087 Yes / No Failed OFFICE NW101 Ivan Albert 9/06/2024

Single Wood 36" x 84" Hollow Metal Not Filled 2-Hour Fire Barrier Immediate

Leaf Fire Rating Smoke Label

Leaf A 90 mins N/A

FC4 Missing closer Hardware No No

This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.

Printed 9/18/2024 2:20 PM 33 of 127

Address 718 Smyth Road Manchester, NH 03104

Inspection Dates 8/26/2024 To 9/18/2024 Project # 484898 Inspection No. SLS484561

Building: DVA-1 Floor: 2 Opening: 0063

Barcode Door Type

Fire / Smoke Door Material

P/F Door Size

Area Frame Material

Inspector Barrier Type

Date Priority

265…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .