This document contains a Medical Gas Zone Inspection & Performance Verification report for the White River Junction VA Medical Center. The report details comprehensive testing of medical gas systems across multiple floors and zones, including oxygen, medical air, vacuum, nitrous oxide, WAGD (Waste Anesthetic Gas Disposal), nitrogen, and carbon dioxide gas services. The inspections were conducted on Building 31, covering inpatient wards on floors 1 and G (ground), with specific focus on rooms ranging from 101-129, 132-137, and G-71 to G-86.

The documentation systematically verifies each zone's gas outlet and inlet performance, including static pressure, flow rates, dynamic pressure, and assay percentages. Each zone uses a Beacon Medaes Total Alert Infinity monitoring system, with area alarms and zone valves checked for compliance with NFPA 99 standards. The reports consistently show that all tested outlets and inlets met the required performance metrics, with no significant issues identified. The inspection dates range from 1/2/25 to 4/30/24, indicating a proactive approach to medical gas system maintenance and verification at the VA medical facility.

View the file

Other files

File Type Posted
Attachment 1.pdf PDF
36C24126Q0061 0001.docx DOCX document
Questions and Answers.pdf PDF
36C24126Q0061.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

31 1

31 1

31 1

31 1

31 1

31 1

General Notes:

1-6 Ceiling

Overhead Nurses Station

Future Tie In Main Pipelines To ICU Service X X X

1-5 Rest Room

Adjacent to Nurses Station Inpatient

Ward Future Zone Service X X X Yes

1-4 Medication Room 164 Main Pipelines Service X

Inspection & Performance Verification Critical Control Valve

10/17/24

1-2 Ceiling

Overhead Adjacent to

Future Zone Service X X X Yes

1-3

X X

Designation

Date:

Building: Floor: Room / Area: Carbon Dioxide

Valve Identification / Location Meets

NFPA 99:

YesX X X

YesFuture Tie In Main Pipelines Service

Ceiling Overhead

Adjacent to Future Zone Future

Yes

Yes

Location: White River VA Medical Center

Ceiling Overhead Room 137

Med Air Vacuum N2O WAGD Nitrogen Area of Control: Valve

Type:

Gas Service

Valve ID: Oxygen

1-1 X X X

Attachment 2

D W

D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W

Note 1

Note 2

Symbol Key: N/T = Not Tested, N/A = Not Applicable, N/V = Not Verified, Y = Yes, N = No, W = Wall, B = Boom/Column, C = Ceiling, P = Pedestal, O = Other, D = DISS, Q = Quick Connect, C = Chemetron, G = Geo

Findings:

General Notes:

These outlets were checked for proper static pressure, performance, and/or concentration levels only.

49 20.9% Yes 124 Inpatient Ward O None 51 100 50 124 Inpatient Ward A None 50 100

99.8% Yes

124 Inpatient Ward V N/A 20 85 18 N/A Yes 123 Inpatient Ward O None 51 100 50 99.8% Yes

18 N/A Yes 123 Inpatient Ward A None 50 100 49 123 Inpatient Ward V N/A 20 85

20.9% Yes

122 Inpatient Ward O None 51 100 50 99.8% Yes 122 Inpatient Ward A None 50 100 49 20.9% Yes

50 99.8% Yes 122 Inpatient Ward V N/A 20 85 18 121 Inpatient Ward O None 51 100

N/A Yes

121 Inpatient Ward A None 50 100 49 20.9% Yes 121 Inpatient Ward V N/A 20 85 18 N/A Yes

49 20.9% Yes 120 Inpatient Ward O None 51 100 50 120 Inpatient Ward A None 50 100

99.8% Yes

120 Inpatient Ward V N/A 20 85 18 N/A Yes 119 Inpatient Ward O None 51 100 50 99.8% Yes

18 N/A Yes 119 Inpatient Ward A None 50 100 49 119 Inpatient Ward V N/A 20 85

20.9% Yes

118 Inpatient Ward O None 51 100 50 99.8% Yes 118 Inpatient Ward A None 50 100 49 20.9% Yes

50 99.8% Yes 118 Inpatient Ward V N/A 20 85 18 117 Inpatient Ward O None 51 100

N/A Yes

117 Inpatient Ward A None 50 100 49 20.9% Yes 117 Inpatient Ward V N/A 20 85 18 N/A Yes

49 20.9% Yes 116 Inpatient Ward O None 51 100 50 116 Inpatient Ward A None 50 100

99.8% Yes

La tc h

La tc h

FG

I T ab le

2.

1-

Le ak s in

Us e Le ak s

No t

In U se Tr an si en t

Fl ow

Odor Test

(None or

OD)

Room Number: Room Information: Gas

Service

C on ne ct io n

Ty pe

Lo ca tio n of

O ut le t /

In le t

A rt ic ul at in g A ss em bl ie s

116 Inpatient Ward V N/A 20 85 18 N/A Yes

Static Pressure Flow Dynamic

Pressure Assay Meets

NFPA

99:(psi or inHg) (LPM) (psi or inHg) (%)

Notes:

Station Outlets & Inlets Notes: Notes: Notes:

Meets

NFPA 99:

Meets

NFPA 99:

Notes: Notes: Notes:

Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Meets NFPA 99: Yes Meets

NFPA 99: Yes Meets NFPA 99: Yes

Notes:

60 40 60 40 12 50 50 20

Manufacturer: Beacon Medaes Model / Type: Total Alert Infinity Gas Service, Alarm Set Points & Area Alarm Pressure (psi or inHg)

Oxygen Med Air Vacuum Nitrous Oxide WAGD Nitrogen Carbon Dioxide Other

Notes:

Area Alarms Alarm ID: 1-1

Area Monitored: Inpatient Ward 116-129 Location: Adjacent to Room 129

Notes: Notes: Notes:Notes: Notes: Notes: Notes:

Meets

NFPA 99:

Meets NFPA 99: Yes Meets

NFPA 99: Yes Meets NFPA 99: Yes Meets

NFPA 99:

50 50 20 Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Zone Valves Zone ID: 1-1

Area of Control: Inpatient Ward 116-129 Location: Adjacent to room 129

Gas Service & Zone Valve Gauge Pressure (psi or inHg) Oxygen Med Air Vacuum Nitrous Oxide WAGD Nitrogen Carbon Dioxide Other

Medical Gas Zone Inspection & Performance Verification

Location: White River Junction VA Building: 31 Floor: 1 Department: Inpatient Ward Date: 1/2/25

D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W

Note 1

Note 2

Symbol Key: N/T = Not Tested, N/A = Not Applicable, N/V = Not Verified, Y = Yes, N = No, W = Wall, B = Boom/Column, C = Ceiling, P = Pedestal, O = Other, D = DISS, Q = Quick Connect, C = Chemetron, G = Geo

Findings:

General Notes:

These outlets were checked for proper static pressure, performance, and/or concentration levels only.

Yes 129 Inpatient Ward O None 51 100 50 99.8% Yes

N/A Yes 129 Inpatient Ward A None 50 100 49 20.9%

50 99.8% Yes 129 Inpatient Ward V N/A 20 85 18 128 Inpatient Ward O None 51 100

Yes 128 Inpatient Ward A None 50 100 49 20.9% Yes

99.8% Yes 128 Inpatient Ward V N/A 20 85 18 N/A

49 20.9% Yes 127 Inpatient Ward O None 51 100 50 127 Inpatient Ward A None 50 100

Yes 127 Inpatient Ward V N/A 20 85 18 N/A Yes

20.9% Yes 127 Inpatient Ward O None 51 100 50 99.8%

18 N/A Yes 127 Inpatient Ward A None 50 100 49 127 Inpatient Ward V N/A 20 85

Yes 126 Inpatient Ward O None 51 100 50 99.8% Yes

N/A Yes 126 Inpatient Ward A None 50 100 49 20.9%

50 99.8% Yes 126 Inpatient Ward V N/A 20 85 18 126 Inpatient Ward O None 51 100

Yes 126 Inpatient Ward A None 50 100 49 20.9% Yes

99.8% Yes 126 Inpatient Ward V N/A 20 85 18 N/A

49 20.9% Yes 125 Inpatient Ward O None 51 100 50 125 Inpatient Ward A None 50 100 125 Inpatient Ward V N/A 20 85 18 N/A Yes

Static Pressure Flow Dynamic

Pressure Assay Meets

NFPA

99:(psi or inHg) (LPM) (psi or inHg) (%)

La tc h

La tc h

FG

I T

Le ak

Le ak s

No t

In U se Tr an si en t

Fl ow

Odor Test

(None or

OD)

Room Number: Room Information: Gas

Service

C on ne ct io n

Ty pe

Lo ca tio le t /

In le t

A rt ic ul at in g A ss em bl ie s

Notes: Notes:

Station Outlets & Inlets Notes: Notes: Notes:

Meets

NFPA 99:

Meets

NFPA 99:

Notes: Notes: Notes:

Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Meets NFPA 99: Yes Meets

NFPA 99: Yes Meets NFPA 99: Yes

50 50 20

Nitrogen Carbon Dioxide Other 60 40 60 40 12

Manufacturer: Beacon Medaes Model / Type: Total Alert Infinity Gas Service, Alarm Set Points & Area Alarm Pressure (psi or inHg)

Oxygen Med Air Vacuum Nitrous Oxide WAGD

Notes:

Area Alarms Alarm ID: 1-1

Area Monitored: Inpatient Ward 116-129 Location: Adjacent to Room 129

Notes: Notes: Notes:

Meets

NFPA 99:

Notes: Notes: Notes: Notes:

Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Meets NFPA 99: Yes Meets

NFPA 99: Yes Meets NFPA 99: Yes Meets

NFPA 99:

50 50 20

Gas Service & Zone Valve Gauge Pressure (psi or inHg) Oxygen Med Air Vacuum Nitrous Oxide WAGD Nitrogen Carbon Dioxide Other

Inpatient Ward Date: 1/2/25

Zone Valves Zone ID: 1-1

Area of Control: Inpatient Ward 116-129 Location: Adjacent to room 129

Medical Gas Zone Inspection & Performance Verification

Location: White River Junction VA Building: 31 Floor: 1 Department:

D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W

Note 1

Note 2

135 Inpatient O N/A 51 100 50 99.8% Yes

Yes 135 Inpatient A None 50 100 49 20.9% Yes

Symbol Key: N/T = Not Tested, N/A = Not Applicable, N/V = Not Verified, Y = Yes, N = No, W = Wall, B = Boom/Column, C = Ceiling, P = Pedestal, O = Other, D = DISS, Q = Quick Connect, C = Chemetron, G = Geo

Findings:

General Notes:

These outlets were checked for proper static pressure, performance, and/or concentration levels only.

Zone Valves Zone ID: 1-2

Area of Control: Inpatient Ward 132-137 Location: Adjacent to Room 135

Medical Gas Zone Inspection & Performance Verification

1/2/25Date:Inpatient Ward Department:1Floor:31Building:Location: White River Junction VA

Gas Service & Zone Valve Gauge Pressure (psi or inHg) Oxygen Med Air Vacuum Nitrous Oxide WAGD Nitrogen Carbon Dioxide Other

Meets

NFPA 99:

Meets NFPA 99: Yes Meets

NFPA 99: Yes Meets NFPA 99: Yes Meets

NFPA 99:

51 50 20 Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Area Alarms Alarm ID: 1-2

Area Monitored: Inpatient Ward Rooms 132-137 Location: Adjacent to Nurse Station

Notes: Notes: Notes: Notes:Notes: Notes: Notes: Notes:

40 60 40

Manufacturer: Beacon Medaes Model / Type: Total Alert Infinity Gas Service, Alarm Set Points & Area Alarm Pressure (psi or inHg)

Oxygen Med Air Vacuum Nitrous Oxide WAGD Nitrogen Carbon Dioxide Other

50 50 19

Notes: Notes: Notes: Notes:

Yes Meets NFPA 99: Yes Meets

NFPA 99: Yes Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Notes: Notes: Notes:Notes:

(psi or inHg) (%)

Meets

NFPA

99:

Station Outlets & Inlets AssayDynamic

PressureFlowStatic Pressure

Odor Test

(LPM)(None or

OD)

(psi or inHg)

V

99.8% Yes

20.9% Yes 133 Inpatient N/A 20 85 18 N/A Yes

132 Inpatient A None 50 100 49

133 Inpatient O None

Room Number:

Tr an si en t Fl ow

Le ak s No t In

U se

La tc h

La tc h

A rt ic ul at in g A ss em bl ie s

50100None

Room Information:

Inpatient

Lo ca tio le t /

In le t

Le ak

FG

I T

C on ne ct io n

Ty pe

Gas Service

O

134 Inpatient None 50 100 49 20.9% Yes 99.8% YesO134 Inpatient None 51 100 50

135 Inpatient None 20 85 18 N/A Yes

134 Inpatient N/A 20 85 18 N/A Yes 135 Inpatient V None 20 85 18 N/A

135 Inpatient N/A 51 100 50 99.8% Yes 135 Inpatient None 50 100 49 20.9% Yes

136 Inpatient None 50 100 49 20.9% Yes

137 Inpatient None 51 100 50 99.8% Yes 136 Inpatient N/A 20 85 18 N/A Yes

137 Inpatient N/A 20 85 18 N/A Yes 137 Inpatient None 50 100 49 20.9% Yes

100 50 133 Inpatient None 50 100 49A

20.9% Yes 132 Inpatient V N/A 20 85 18 N/A Yes

99.8% Yes

A V

V A O

136 Inpatient O None 51 100 50 99.8% Yes A V O A V

D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W111 Inpatient V N/A 20 85 18 N/A Yes

111 Inpatient A None 50 100 49 20.9% Yes 111 Inpatient O None 51 100 50 99.8% Yes 109 Inpatient V N/A 20 85 18 N/A Yes 109 Inpatient A None 50 100 49 20.9% Yes 109 Inpatient O None 51 100 50 99.8% Yes

99.8% Yes

A V

V A O

107 Inpatient O None 51 100 50 99.8% Yes A V O A V

20.9% Yes 101 Inpatient Bed 1 V N/A 20 85 18 N/A Yes

100 50 103 Inpatient None 50 100 49A

107 Inpatient N/A 20 85 18 N/A Yes

108 Inpatient N/A 20 85 18 N/A Yes 108 Inpatient None 50 100 49 20.9% Yes

107 Inpatient None 50 100 49 20.9% Yes

108 Inpatient None 51 100 50 99.8% Yes

106 Inpatient N/A 51 100 50 99.8% Yes 106 Inpatient None 50 100 49 20.9% Yes 106 Inpatient None 20 85 18 N/A Yes

104 Inpatient N/A 20 85 18 N/A Yes 105 Inpatient V None 20 85 18 N/A

104 Inpatient None 50 100 49 20.9% Yes 99.8% YesO104 Inpatient None 51 100 50

Room Number:

Tr an si en t Fl ow

Le ak s No t In

U se

La tc h

La tc h

A rt ic ul at in g A ss em bl ie s

50100None

Room Information:

Inpatient Bed 1

Lo ca tio le t /

In le t

Le ak

FG

I T

C on ne ct io n

Ty pe

Gas Service

O

V

99.8% Yes

20.9% Yes 103 Inpatient N/A 20 85 18 N/A Yes

101 Inpatient Bed 1 A None 50 100 49

103 Inpatient O None

Notes: Notes: Notes:Notes:

(psi or inHg) (%)

Meets

NFPA

99:

Station Outlets & Inlets AssayDynamic

PressureFlowStatic Pressure

Odor Test

(LPM)(None or

OD)

(psi or inHg)

Notes: Notes: Notes: Notes:

Yes Meets NFPA 99: Yes Meets

NFPA 99: Yes Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

50 50 19 40 60 40

Manufacturer: Beacon Medaes Model / Type: Total Alert Infinity Gas Service, Alarm Set Points & Area Alarm Pressure (psi or inHg)

Oxygen Med Air Vacuum Nitrous Oxide WAGD Nitrogen Carbon Dioxide Other

Area Alarms Alarm ID: 1-2

Area Monitored: Inpatient Ward Rooms 101 - 114 & 143 Location: Fall Nurses Station

Notes: Notes: Notes: Notes:Notes: Notes: Notes: Notes:

Meets

NFPA 99:

Meets NFPA 99: Yes Meets

NFPA 99: Yes Meets NFPA 99: Yes Meets

NFPA 99:

51 50 20 Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Gas Service & Zone Valve Gauge Pressure (psi or inHg) Oxygen Med Air Vacuum Nitrous Oxide WAGD Nitrogen Carbon Dioxide Other

Zone Valves Zone ID: 1-2

Area of Control: Inpatient Ward Rooms 101 - 114 & 143 Location: Adjacent to Room 101

Medical Gas Zone Inspection & Performance Verification

9/24/25Date:Inpatient Fall Ward Department:1Floor:31Building:Location: White River Junction VA

Yes 105 Inpatient A None 50 100 49 20.9% Yes 105 Inpatient O N/A 51 100 50 99.8% Yes

101 Inpatient Bed 2 O None 51 100 50 99.8% Yes 101 Inpatient Bed 2 A None 50 100 49 20.9% Yes 101 Inpatient Bed 2 V N/A 20 85 18 N/A Yes

Room Number:

Tr an si en t Fl ow

Le ak s No t In

U se

La tc h

La tc h

A rt ic ul at in g A ss em bl ie s

Room Information:

Lo ca tio le t /

In le t

Le ak

FG

I T

C on ne ct io n

Ty pe

Gas Service (psi or inHg) (%)

Meets

NFPA

99:

Station Outlets & Inlets AssayDynamic

PressureFlowStatic Pressure

Odor Test

(LPM)(None or

OD)

(psi or inHg)

D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W

Note 1

Note 2

112 Inpatient Bed 1 V N/A 20 85 18 N/A Yes 112 Inpatient Bed 1 A None 50 100 49 20.9% Yes 112 Inpatient Bed 1 O None 51 100 50 99.8% Yes

O A

143 Inpatient Bed 1 N/A 20 85 18 N/A YesV 143 Inpatient Bed 1 None 50 100 49 20.9% YesA 143 Inpatient Bed 1 None 51 100 50 99.8% YesO

114 Inpatient None 51 100 50 99.8% YesO 114 Inpatient None 50 100 49 20.9% YesA 114 Inpatient None 51 100 50 99.8% YesO

113 Inpatient Bed 1 N/A 20 85 18 N/A YesV 113 Inpatient Bed 1 None 50 100 49 20.9% Yes 113 Inpatient Bed 1 None 51 100 50 99.8% Yes

Symbol Key: N/T = Not Tested, N/A = Not Applicable, N/V = Not Verified, Y = Yes, N = No, W = Wall, B = Boom/Column, C = Ceiling, P = Pedestal, O = Other, D = DISS, Q = Quick Connect, C = Chemetron, G = Geo

Findings:

General Notes:

These outlets were checked for proper static pressure, performance, and/or concentration levels only.

112 Inpatient Bed 2 O None 51 100 50 99.8% Yes 112 Inpatient Bed 2 A None 50 100 49 20.9% Yes 112 Inpatient Bed 2 V N/A 20 85 18 N/A Yes

113 Inpatient Bed 2 O None 51 100 50 99.8% Yes 113 Inpatient Bed 2 A None 50 100 49 20.9% Yes 113 Inpatient Bed 2 V N/A 20 85 18 N/A Yes

114 Inpatient A None 50 100 49 20.9% Yes

143 Inpatient Bed 2 O None 51 100 50 99.8% Yes 143 Inpatient Bed 2 A None 50 100 49 20.9% Yes 143 Inpatient Bed 2 V N/A 20 85 18 N/A Yes

D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W

Note 1

Note 2

Symbol Key: N/T = Not Tested, N/A = Not Applicable, N/V = Not Verified, Y = Yes, N = No, W = Wall, B = Boom/Column, C = Ceiling, P = Pedestal, O = Other, D = DISS, Q = Quick Connect, C = Chemetron, G = Geo

Findings:

General Notes:

These outlets were checked for proper static pressure, performance, and/or concentration levels only.

Zone Valves Zone ID: G-1

Area of Control: Inpatient Ward Rooms G71, 78, 83, 84, 85, 86 Location: Across from G-72 Reception B

Medical Gas Zone Inspection & Performance Verification

4/30/24Date:Inpatient Ward Department:G Floor:31Building:Location: White River Junction VA

Gas Service & Zone Valve Gauge Pressure (psi or inHg) Oxygen Med Air Vacuum Nitrous Oxide WAGD Nitrogen Carbon Dioxide Other

Meets

NFPA 99:

Meets NFPA 99: Yes Meets

NFPA 99: Yes Meets NFPA 99: Yes Meets

NFPA 99:

50 50 19 Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Area Alarms Alarm ID: G-1

Area Monitored: Inpatient Ward Rooms G71, 78, 83, 84, 85, 86 Location: Nurse Station Inpatient Ward

Notes: Notes: Notes: Notes:Notes: Notes: Notes: Notes:

40 60 40

Manufacturer: BeaconMedaes Model / Type: TotalAlert Infinity Gas Service, Alarm Set Points & Area Alarm Pressure (psi or inHg)

Oxygen Med Air Vacuum Nitrous Oxide WAGD Nitrogen Carbon Dioxide Other

50 50 19

Notes: Notes: Notes: Notes:

Yes Meets NFPA 99: Yes Meets

NFPA 99: Yes Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Notes: Notes: Notes:Notes:

(psi or inHg) (%)

Meets

NFPA

99:

Station Outlets & Inlets AssayDynamic

PressureFlowStatic Pressure

Odor Test

(LPM)(None or

OD)

(psi or inHg)

V

99.8% Yes

20.9% Yes G-78 Patient Isolation N/A 19 85 16 N/A Yes

G-71 Patient Isolation A None 50 100 48

G-78 Patient Isolation O None

Room Number:

G-71

Tr an si en t Fl ow

Le ak s No t In

U se

La tc h

A rt ic ul at in g A ss em bl ie s

49100None

Room Information:

Patient Isolation

Lo ca tio le t /

In le t

Le ak

La be l

C on ne ct io n

Ty pe

Gas Service

O

G-83 Patient Room None 50 100 48 20.9% Yes 99.8% YesOG-83 Patient Room None 50 100 49

G-83 Patient Room None 50 100 49 99.8% Yes G-83 Patient Room N/A 19 85 16 N/A Yes

G-83 Patient Room None

19 85 16 N/A Yes G-83 Patient Room 50 100 48 20.9% Yes

N/A

G-83 Patient Room None 50 100 48 20.9% Yes

G-84 Patient Room None 50 100 49 99.8% Yes G-83 Patient Room N/A 19 85 16 N/A Yes

G-84 Patient Room N/A 19 85 16 N/A Yes G-84 Patient Room None 50 100 48 20.9% Yes

G-84 Patient Room None 50 100 48 20.9% Yes G-84 Patient Room None 50 100 49 99.8% Yes

G-84 Patient Room N/A 19 85 16 N/A YesV G-84 Patient Room None 50 100 49 99.8% YesO G-84 Patient Room None 50 100 48 20.9% YesA G-84 Patient Room N/A 19 85 16 N/A YesV

100 49 G-78 Patient Isolation None 50 100 48A

20.9% Yes G-71 Patient Isolation V N/A 19 85 16 N/A Yes

99.8% Yes

A V O A V

G-83 Patient Room O None 50 100 49 99.8% Yes A V O A V O A

D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W D W

Note 1

Note 2

G-85 Patient Room A None 50 100 48 20.9% Yes G-85 Patient Room O None 50 100 49 99.8% Yes G-85 Patient Room V N/A 19 85 16 N/A Yes G-85 Patient Room A None 50 100 48 20.9% Yes G-85 Patient Room O None 50 100 49 99.8% Yes

Medical Gas Zone Inspection & Performance Verification

Location: White River Junction VA Building: 31 Floor: G Department: Inpatient Ward Date: 4/30/24

Zone Valves Zone ID: G-1

Area of Control: Inpatient Ward Rooms G71, 78, 83, 84, 85, 86 Location: Across from G-72 Reception B

Gas Service & Zone Valve Gauge Pressure (psi or inHg) Oxygen Med Air Vacuum Nitrous Oxide WAGD Nitrogen Carbon Dioxide Other

Meets

NFPA 99:

Meets NFPA 99: Yes Meets

NFPA 99: Yes Meets NFPA 99: Yes Meets

NFPA 99:

50 50 19 Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Notes:

Area Alarms Alarm ID: G-1

Area Monitored: Inpatient Ward Rooms G71, 78, 83, 84, 85, 86 Location: Nurse Station Inpatient Ward

Notes: Notes: Notes:Notes: Notes: Notes: Notes:

Manufacturer: BeaconMedaes Model / Type: TotalAlert Infinity Gas Service, Alarm Set Points & Area Alarm Pressure (psi or inHg)

Oxygen Med Air Vacuum Nitrous Oxide WAGD Nitrogen Carbon Dioxide Other 60 40 60 40 12

50 50 19 Meets

NFPA 99:

Meets

NFPA 99:

Notes: Notes: Notes:

Meets

NFPA 99:

Meets

NFPA 99:

Meets

NFPA 99:

Meets NFPA 99: Yes Meets

NFPA 99: Yes Meets NFPA 99: Yes

Notes: Notes:

Station Outlets & Inlets Notes: Notes: Notes:

Static Pressure Flow Dynamic

Pressure Assay Meets

NFPA

99:(psi or inHg) (LPM) (psi or inHg) (%)

G-85 Patient Room V N/A 19 85 16 N/A Yes

La tc h

La be l

Le ak

Le ak s

No t

In U se Tr an si en t

Fl ow

Odor Test

(None or

OD)

Room Number: Room Information: Gas

Service

C on ne ct io n

Ty pe

Lo ca tio le t /

In le t

A rt ic ul at in g A ss em bl ie s

49 99.8% Yes G-85 Patient Room A None 50 100 48 G-85 Patient Room O None 50 100

20.9% Yes G-85 Patient Room V N/A 19 85 16 N/A Yes G-86 Patient Room O None 50 100 49 99.8% Yes

48 20.9% Yes G-86 Patient Room V N/A 19 85 16 G-86 Patient Room A None 50 100

N/A Yes G-86 Patient Room O None 50 100 49 99.8% Yes G-86 Patient Room A None 50 100 48 20.9% Yes

16 N/A Yes G-86 Patient Room O None 50 100 49 G-86 Patient Room V N/A 19 85

99.8% Yes G-86 Patient Room A None 50 100 48 20.9% Yes G-86 Patient Room V N/A 19 85 16 N/A Yes

Symbol Key: N/T = Not Tested, N/A = Not Applicable, N/V = Not Verified, Y = Yes, N = No, W = Wall, B = Boom/Column, C = Ceiling, P = Pedestal, O = Other, D = DISS, Q = Quick Connect, C = Chemetron, G = Geo

Findings:

General Notes:

These outlets were checked for proper static pressure, performance, and/or concentration levels only.