This document provides details for two upcoming single award task order contracts for construction services at Veterans Affairs medical centers in Bedford, Massachusetts and Providence, Rhode Island. The contracts will be set aside for service-disabled veteran-owned or veteran-owned small businesses. Work will involve repairs, renovations, and minor alterations to existing facilities and infrastructure with task order values between $25,000 to $75,000 and a ceiling of $500,000 per contract. The NAICS code is 236220 and the small business size standard is $36.5 million. One contract will be awarded for each location. Contractors must have a local office and bonding capacity up to $500,000. The base period of performance is one five-year term.
36C24119R0045 A0002 RFI Response 8.27.19.docx
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24119D0032-000.docx | DOCX document | |
| 36C24119D0031-000.docx | DOCX document | |
| 36C24119R0045-A0002000.docx | DOCX document | |
| 36C24119R0045-A0002003.pdf | ||
| 36C24119R0045-A0002002.pdf | ||
| 36C24119R0045-A0002004.pdf | ||
| 36C24119R0045-A0001000.docx | DOCX document | |
| 36C24119R0045-008.zip | ZIP file | |
| 36C24119R0045-009.zip | ZIP file | |
| 36C24119R0045-005.docx | DOCX document | |
| 36C24119R0045-006.xlsx | XLSX spreadsheet | |
| 36C24119R0045-007.docx | DOCX document | |
| 36C24119R0045.docx | DOCX document |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Bedford - 518-18-060 Female Bathroom
1. Is the Bedford Seed Project intended to be Design-Build?
0. No. Project has already been designed. See Final Drawings.
1. The Statement of Work for the Bedford Seed Project, Item C.3. HVAC Commissioning indicates that the contractor shall include cost for the zone where the new Female Shower is being installed. This section also indicates that “the system’s complete commissioning shall be included” AFTER the VA’s CxA completes a “thorough holistic exploration of the building’s system” and identifies its deficiencies. How are we to include cost for the complete commissioning without any information about the existing system from the VA and its CxA?
1. Commissioning is no longer required. HVAC commissioning can be descoped from the SOW.
1. The Statement of Work for the Bedford Seed Project, C.5. Demolition, Item iii. states that “the structure above will be assessed…” At the site visit we were told that the VA has conducted a structural assessment for support of the patient lift. Please confirm.
2. See page 7 of ‘Final Set with Stamped Structural’ for structural assessment of patient lift and proposed installation method.
1. The Statement of Work for the Bedford Seed Project, C.5. Demolition, Item iv. Indicates partial removal of the existing slab will be required. Is the intent to alter the existing slab (grind & core at drain locations then pitch mortar to drain) or to remove the slab and form and pour a new slab pitched to drain?
3. Contractor is to alter existing slab. Refer to structural drawings S0-2.0 – the First Floor Plan and Detail 1 indicate the cutting required to install the linear floor drain. The drawing indicates that the core drain will be located so it is drilled between beams. Contractor will have to coordinate with representative from Simpson Gumpertz & Heger to ensure the structure is not compromised. Leveling material will have to be used to create pitch for drain.
Providence - 650-19-123 Bldg. 8 Haz Mat Exterior Improvements
1. Please confirm if taxes should be carried in proposals?
a. Taxes should not be carried. The VA is exempt from all Federal, State, and Local taxes. See attached.
2. Please confirm if any state, local, and/or Federal permits will be required on this project?
a. No permits are required for this project.
3. Please confirm if there are any known hazardous materials?
a. No hazardous materials are known to exist at this site.
4. Can the government confirm the thickness of the binder and top coat required? As well as the size binder and top to use?
| a. 2-1/2 inches of RI STD CLASS 12.5 HMA TOP COAT |
| 2-1/2 inches of RI STD CLASS 12.5 HMA BINDER |
5. Please confirm what type of signage is required and how many of them are required?
a. Twenty-one (21) Type R7-8 Handicap Parking signs with posts. see attached for details.