36C10E19R0009-0002000.docx
DOCX document 32 KB Posted
- Solicitation number
- 36C10E19R0009
About this file
36C10E19R0009 0002 36C10E19R0009 0002.docx
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C10E19R0009-0003000.docx | DOCX document | |
| 36C10E19R0009-0001000.docx | DOCX document | |
| 36C10E19R0009-0001001.pdf | ||
| 36C10E19R0009-0001002.pdf | ||
| 36C10E19R0009-002.pdf | ||
| 36C10E19R0009-007.pdf | ||
| 36C10E19R0009-003.pdf | ||
| 36C10E19R0009-006.pdf | ||
| 36C10E19R0009-004.pdf | ||
| 36C10E19R0009-005.pdf | ||
| 36C10E19R0009-008.pdf | ||
| 36C10E19R0009-001.docx | DOCX document | |
| 36C10E19R0009-000.docx | DOCX document |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION
OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR
ACKNOWLEDGMENT TO BE RECEIVED AT
THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO:
Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADM
INISTRATIVE CHANGES
SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and d ate specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 3
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO
MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer)
VA
3176-000059 00101 Department of Veterans Affairs Veterans Benefits Administration Office of Acquisition 1800 G. Street N.W.
Washington DC 20006 00101 Department of Veterans Affairs Veterans Benefits Administration Office of Acquisition 1800 G. Street N.W.
Washington DC 20006 To all Offerors/Bidders
36C10E19R0009 08-20-2019
X X
X
The purpose of this amendment is to publish the questions and answers that were submitted concerning this project.
All other terms and conditions remain unchanged.
Jeffrey Reed
1. Is the existing chilled water piping to the existing AHU copper or steel?
a. Steel
2. Can grooved fittings be used for the new piping to be installed?
a. Yes
3. What are the pipe sizes to each AHU?
a. 4”, however contractor needs to verify all field measurements
4. Please confirm that the piping only needs to be take back far enough to install new AHU's and Control Valves.
a. Yes
5. Does any of the insulation on the existing duct work or piping contain hazardous materials such as asbestos?
a. No
6. Where will the Lay down area be located? How many sq feet will the lay down area be?
a. North gravel parking lot
7. Where can a dumpster be placed?
a. TBD Upon award
8. If the designated lay down area is not large enough to fit 6 or 7 20ft storage connexs, is there another location where connexs or dumpsters can be place? (example: in the back of the parking lots; the gravel parking lot)
a. North gravel parking lot
9. Please explain badging process for contractors.
a. Refer to SOW section 4.1 for additional information and contractor will be issued badges and keys
10. Will contractor's employees need to go through security every day?
a. No, the requirement calls for after hours and weekend work
11. Will someone from the VA be onsite to let us in mechanical rooms over the weekends?
a. Yes
12. Will temporary air be needed on the weekends while an AHU is down?
a. Yes
13. Will the prime contractor be given keys to mechanical room doors?
a. Yes
14. What type of access to the building will the contractor receive if an employee needs to leave the building to go to the laydown area for material on the weekends?
a. Contractors will have badged access in and out of buildings
15. Are there any infectious control requirements?
a. No
16. Can other controls vendors besides Johnson Controls be used?
a. No, all controls will be Johnson control compatible
17. Please provide as built duct plans for the systems being cleaned.
a. All specs will be made available upon request in the form of a CD. If you want a copy, please notify the Contracting Officer at Jeffrey.reed@va.gov
18. Can units besides JCI AHU’s be utilized?
a. Yes, as long as it is compatible with Metasys
19. Are test and balance pre-demo readings required?
a. No
20. Is test and balance of all the areas served by the units required after the units are running or just the units themselves?
a. All areas served by the unit
21. Is sound and vibration testing required?
a. Yes
22. Staffing- No staffing requirements are found anywhere in solicitation and specifications weren't given at all. Please provide these
a. This question is unclear, what staffing requirements are you talking about? Please send questions to Jeffrey.reed@va.gov
23. Please provide specifications on all divisions related to this project. We do not see any.
a. This question is unclear, what divisions are you talking about? Please send questions to Jeffrey.reed@va.gov
24. When the reference specifications are released, we request you allow an additional 14 business days to the proposal due and allow questions for an additional 7 business days. The additional days for questions will allow our subcontractors sufficient time to review their requirements in the specifications and ask questions which will ensure we provide you with your required product. The additional days for the submission date will allow us to prepare the most responsive, cost-effective proposal, based on the new specification requirements.
a. The due date for the proposals will be changed from 9/2/19 to 9/10/19.
25. Please provide ductwork and mechanical pipe insulation specifications.
a. On CD per request
26. Please provide chilled water and heating hot water coil AHU connection details.
a. On CD per request
27. Will the chilled and hot water coil connection piping, insulation, and associated accessories be removed and replaced under this project?
a. Yes, please refer to the SOW 1.1 scope
28. Please provide mechanical piping specifications.
a. On CD per request
29. Please provide ductwork specifications.
a. On CD per request
30. Does the VA have a complete AHU specification that can be distributed to the contractor?
a. No
31. Any work hour restrictions at the facility? What are the facility’s normal business hours?
a. Refer to SOW 2.5 Location and Hours of work
32. Will crane and rigging work be restricted to weekends only?
a. No
33. Scope of work requires new supply and return automated electric valves and supply and return flow meters at each AHU connected to the Metasys system. This not typical per AHU. Existing conditions only have 1 control valve with existing hand isolation valves. Please confirm requirements?
a. Refer to SOW 3.2.3 Install new valves on chiller lines
34. Based on equipment lead times, the 180 period of performance will not suffice. We request this be adjusted to 270 days.
a. POP will be adjusted to 270 days.
35. We assume that the existing manual isolation valves are in proper working order. If not, whose responsibility is it to fix or replace Manual Valves inclusive of requirements to drain the system?
a. Wet tap up stream of valves prior to removal
36. During the walkthrough there was discussion about an additional Air Handling Unit added to the scope of work by a forthcoming amendment. Please confirm?
a. The removal and replacement of the dehumidification unit in the ground floor mechanical room
37. Are we responsible for moving and reinstallation of existing walls, cubicles, etc. to accommodate installation of AHUs?
a. Yes
38. For Air Handling Units to be provided like-for-like, Units should have double wall, 2” R-13 insulated panels for walls, roof and floor. In order to meet the stainless-steel construction requirements, we recommend stainless steel interior liners. Please confirm?
a. Stainless is acceptable
39. Exterior skin to be painted galvanized sheet metal. Painted unit will exceed 500-hour salt spray test, with (5%) solution, without any sign of red rest when tested in accordance with ASTM B-117.
a. This question is unclear, please clarify what you are looking for? Please send questions to Jeffrey.reed@va.gov
40. All Interior casing panels shall be made of stainless steel
a. This question is unclear, please clarify what you are looking for? Please send questions to Jeffrey.reed@va.gov
41. Are there any environmental hazards that the contractor needs to be made aware of such as asbestos, lead, silica, etc.?
a. No
42. Please provide mechanical as-builts for the mechanical and electrical system.
a. On CD per request
43. Where will the contractor laydown yard be located?
a. North gravel parking lot
44. The completion period of 225 days for this project is too short considering the magnitude of work in both the design and construction. The site investigations, shop drawing drafting, controls engineering, AHU layout, AHU submittal, and submittal approvals will take approximately 90 days. Furthermore, the AHU lead time is approximately 100 days. Considering the above durations, the contractor will be left with only 35 days to install 12 AHUs which isn’t possible. Please consider lengthening the contract duration or issuing an administrative NTP and construction NTP or delay the NTP until the commencement of site construction. Lastly, it has been our experience that these projects require intense phasing which only increases the contractor time on-site.
a. POP will be extended to 270 days.
45. Will the contract be allowed to remove and replace more than one AHU at a time?
a. Yes, as long as they are fully operational at 0600 on Monday mornings
46. What are the temporary air requirements? Will 10-20 stand up units in the affected areas suffice? Please advise.
a. Temporary air handler unit on roof or ground ducted into existing duct work.
47. Please provide paint and epoxy paint specifications.
a. Refer to SOW 3.2.6 paint mechanical room walls
48. Please provide as built floor plans as well as overall site plans for the facility.
a. On CD per request
49. Please provide the name and contact for the site HVAC DDC contractor.
a. Johnson Controls
50. Please provide as-built ductwork plans.
a. On CD per request
51. Is the duct cleaning scope of work for the entire facility or just the duct work serviced by the 12 AHUS?
a. Duct work serviced by the AHUS see attachment 7 of the solicitation for linear ft
52. Reference SF 1442 and solicitation pages 15 of 42, 28 of 42, & 35 of 42: These references variously refer to the NAICS code for this solicitation as 236220, 238220, & 236118. Given the nature of the work, we believe the correct NAICS code is 238220. Can you confirm?
a. NAICS code is 238220.
53. Reference Section L – Instructions, Conditions, and Notices to Offerors: This section provides no instructions regarding our required submission items. We are given limited guidance in Section M – Evaluation Criteria, but not to the extent needed. For example (not necessarily all inclusive):
a. The required submissions are 3 parts;
i. Technical Proposal
ii. Price Proposal
iii. Relevant Past Performance information
54. Do you have a required font and font size?
a. Arial 12pt
55. Are we to provide an email with a single electronic file or are we to provide one electronic file for a Technical Proposal and another electronic file for a Price Proposal?
a. One technical and one price
56. Are we to provide Section K – Representations & Certifications?
a. Yes
57. Are we required/permitted to submit our CVE SDVOSB certification?
a. Yes
58. There is an assumption that we are to provide the SF 1442 and the Bid Schedule (Section B), but we are not told to do so anywhere.
a. Please submit the SF 1442 and the Bid Schedule with submissions.
59. Are we required to submit project experience and, if so, what are the required data elements?
a. Yes, projects of similar size and scope that were performed within the last five years.
60. Reference solicitation: Do you have on-site staffing requirements for offeror personnel? E.g., site superintendent, safety manager, & quality control manager. If you require all three, are there qualification requirements for them? May we combine any of the roles? For example, can the QC manager fill the safety manager role, if qualified? May the superintendent fulfill all three roles, if qualified?
a. Refer to the SOW & OK for super to fill various rolls
61. Reference Evaluation Criteria, page 2, Past Performance Confidence Rating Overview: This paragraph states, in part: “…as defined as relevant in the above Proposal Content section C(2)(b).” We cannot locate the referenced paragraph C(2)(b) in any of our documents. Can you please clarify?
a. Please disregard the reference to paragraph C(2)(b). Relevant past performance is defined as projects in similar scope and size within the last five years.
62. Reference Evaluation Criteria, Evaluation Factor #2 – Past Performance: If we are already aware that there are no evaluations for our firm in PPIRS, may we provide you with copies of past performance questionnaires that have been previously submitted for other proposals?
a. Yes