36C10D24Q0172 0001.pdf
PDF 940 KB Posted
- Attached to
- CHEYENNE HVAC REPAIR
- Solicitation number
- 36C10D24Q0172
- Issued by
-
Department of Veterans Affairs
About this file
This document appears to be a contract amendment (Standard Form 30) for a federal solicitation. The amendment is to add a plan sheet showing the location where the units will be placed and additional technical information. The solicitation number is 36C10D24Q0172 for the CHEYENNE HVAC REPAIR project, issued by the Department of Veterans Affairs. Proposals are due on June 14th at 2:00PM EST, and all other terms and conditions of the solicitation remain unchanged. The amendment provides details on the refrigerant piping, condensing unit, electrical work, and wall-mounted units to be installed. It also specifies that the work must be completed in accordance with VA ICRA requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Wage Determination.pdf | ||
| 36C10D24Q0172.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE 7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO. 1. CONTRACT ID CODE
FACILITY CODE CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30 PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243
(Type or print) (Type or print)
(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code)
(If other than Item 6)
(Specify type of modification and authority)
(such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer)
VA
VB3092
00101
Department of Veterans Affairs Veterans Benefits Administration Acquisition Directorate 1800 G Street NW Washington DC 20006
00101
Department of Veterans Affairs Veterans Benefits Administration Acquisition Directorate 1800 G Street NW Washington DC 20006
To all Offerors/Bidders
36C10D24Q0172
X x x x
This Amendment is to add a plan sheet showing the location where the units will be placed and additional technical information. Please see attached Plans.
Proposals are due June 14th at 2:00PM EST.
All other terms and conditions of this solicitation remain unchanged.
293.41 SF
35.41 SF
159.14 SF 124.35 SF
88.79 SF
38.76 SF
187 SF
152 SF
108 SF247 SF
96 SF
143 SF
174 SF
129 SF
128 SF
124 SF
313 SF
377 SF
483 SF
25 SF
32 SF
85.50 SF
195 SF 135 SF
436.19 SF
161.29 SF
289.65 SF
141.38 SF
76.02 SF
146.48 SF131 SF
82 SF
81.34 SF
81.34 SF
289.83 SF
S F
.0
S F
.0
S F
.0
S F
315 SF
289.83 SF
641 SF
S F
SF
SF
SF
S F
S F
S F
S F
SF
SF
SF
SF
SF
SF
SF
150 SF
SF
SF
SF
S F
S F
S F
677 SF
S F
S F
240 SF
S F
SCALE: 116" = 1'-0"
0 4'-0" 8'-0" 16'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
Revisions: Date:
G
H
Local I.D.AS-BUILT BY:
Project Director
(SOUTH) DOUGLAS FIR / (NORTH) RRTP
VBA / RRTP
FIRST FLOOR
45 / RRTP
A-110
RE:
MATCHLINE
A-108
RE:
MATCHLINE
A-111
SCHEMATIC CONDENSING UNIT/HEAT PUMP
LOCATION, FIELD COORDINATE. PROVIDE
THE FOLLOWING ACCESSORIES: LOW
AMBIENT KIT, STAND, POURED CONCRETE
PAD, DRAIN PAN HEATER, WIND BAFFLES.
SCHEMATIC ROUTING OF REFRIGERANT
LINESET(S)/ PIPING. REFRIGERANT PIPING
SHALL BE SIZED, SELECTED, AND DESIGNED
BY THE CONTRACTOR IN STRICT
ACCORDANCE WITH THE MANUFACTURER’S
PUBLISHED INSTRUCTIONS. PROVIDE ALL
ACCESSORIES SUCH AS, STOP VALVES, LEVEL
INDICATORS, LIQUID RECEIVERS, OIL
SEPARATOR, GAUGES, THERMOSTATIC
EXPANSION VALVES, SOLENOID VALVES,
MOISTURE SEPARATORS AND DRIERS TO
MAKE A COMPLETE AND WORKING
INSTALLATION. INSULATE PER CODE.
REFRIGERANT PIPING AT WALL UNITS SHALL
BE CONCEALED IN THE WALL WHERE
POSSIBLE OR CONCEALED IN LINE HIDE (OR
EQUAL) WHERE NOT.
COORDINATE ROUTING OF COMMON
CONDENSATE DRAIN (1" MIN. OR AS
SUGGESTED BY MANUFACTURER) TO
HOUSEKEEPING HAC D1-64 AND TERMINATE
IN MOP-SINK. PROVIDE CONDENSATE LIFT
PUMPS IF GRAVITY DRAINAGE CANNOT BE
ACCOMPLISHED IN THE PLENUM. DRAIN
PIPING MAY BE COPPER OR SCHEDULE 80
FLAME RETARDANT POLYPROPYLENE
PLASTIC.
INSTALL SLIMDUCT (OR EQUAL) TO
CONCEAL REFRIGERANT PIPING RUNS UP
THE SIDE OF THE BUILDING. SLIMDUCT TO
BE BROWN/ BRONZE IN COLOR.
PROPERLY SEAL ALL PENETRATIONS.
INSTALL THE THREE WALL MOUNTED UNITS
IN D1-87, D1-92, AND D1-91. LOCATIONS
SHOWN ARE SCHEMATIC, FIELD
COORDINATE WITH EXISTING CONDITIONS
IN EACH SPACE. PROVIDE HARD-WIRED
THERMOSTAT FOR EACH. WORK TO BE
COMPLETED IN ACCORDANCE WITH VA
ICRA REQUIREMENTS.
COLOR MATCH PAINT EXPOSED EXTERIOR
RATED CONDUIT TO EFIS SIDING.
CHEYENNE HVAC REPAIR
(VBA MINI-SPLITS)
36C10D24Q0172
SCHEMATIC ROUTE FOR ELECTRICAL
CONDUIT IN PLENUM, FIELD COORDINATE.
WORK TO BE COMPLETED IN ACCORDANCE
WITH VA ICRA REQUIREMENTS IN A
CONTAINMENT CART FOR ACTIVE DUST
CONTROL. CONTRACTOR SHALL PROVIDE
SINGLE CONDUIT CONTAINING POWER FEEDS
FOR BOTH THE EXTERIOR CONDENSING UNIT
AND EXTERIOR RECEPTACLE. PROVIDE 1"C
W/ 5#10 & 2#10G. CONDENSING UNIT
MANUFACTURER CUTSHEET DOES NOT
SPECIFY WHETHER NEUTRAL IS REQUIRED
OR NOT. IF NEUTRAL NOT REQUIRED,
CONTRACTOR SHALL CAP NEUTRAL AT
PANEL AND DISCONNECT.
CONTRACTOR SHALL PROVIDE 30A DISCONNECT WITH
25A FUSES FOR CONDENSING UNIT. PROVIDE
ENGRAVED NAMEPLATE INDICATING EQUIPMENT
DESIGNATION AND CIRCUITRY.
CONDENSING UNIT RECEPTACLE SHALL BE LISTED AS
WEATHER RESISTANT (WR) AND PROVIDED WITH A
CAST METAL COVER WITH "IN-USE" CABLE OPENINGS AT
BOTTOM OF COVER.
PENETRATION THROUGH 2HR
FIREWALL FOR RACEWAY SHALL BE
SEALED WITH SYSTEM SPECIFICALLY
U.L. APPROVED FOR THE APPLICATION.
TIE INTO PANEL LPN1. PROVIDE 20A/1P
BREAKER IN EXISTING SPACE 53 FOR
NEW EXTERIOR RECEPTACLE. PROVIDE
30A/2P BREAKER IN EXISTING SPACES
55/57 FOR NEW CONDENSING UNIT.
CONTRACTOR SHALL PROVIDE
UPDATED, TYPED, PANEL SCHEDULE
DIRECTORY.
T
T
T
../PDF/Overall plan.pdf ../PDF/Overall plan.pdf ../PDF/Overall plan.pdf ../PDF/Overall plan.pdf
File details come from the government source that posted it. Updated .