34-0007_-_COG_-_RTS_EBF_-_MEP_100%_Const_Docs_Combined.pdf

PDF 6 MB Posted

Attached to
Commissioning Agent for Eastside Bus Transfer Facility
Solicitation number
RTSX-260049-DS
Issued by
Alachua County, Graceville City, Florida

About this file

This document comprises the 100% construction drawings for the Eastside Bus Transfer Facility, a transit facility project in Gainesville, Florida located at the intersection of S.E. Hawthorne Road and S.E. 21st Street. The facility includes mechanical, electrical, and plumbing systems designed to support bus operations and public transit functions. The mechanical systems feature three split-system heat pumps (3-ton, 5-ton configurations) with supplemental heating, a dedicated outdoor air system (DOAS) with cooling and electric heating, ductless split cooling systems, multiple exhaust fans, and gravity ventilators for relief and intake functions. The electrical systems include a 208-volt, three-phase main service with two distribution panels (400-amp and 225-amp capacity), comprehensive lighting throughout interior and exterior spaces with occupancy sensors and dimming controls, emergency lighting with central inverter backup, multiple receptacle configurations with GFCI protection, and provisions for future electric vehicle chargers. The plumbing and HVAC designs comply with the Florida Building Code 2023, ASHRAE standards, NFPA codes, and other applicable regulations. Construction documents indicate coordination requirements among mechanical, electrical, telecommunications, audio-visual, security, and fire alarm contractors, with specific responsibilities outlined in responsibility matrices for each system category.

The design phase documentation, prepared by H2Engineering (Project No. 24024) and dated April 1, 2026, establishes comprehensive installation, maintenance, and operational standards for all building systems. Key requirements include field verification of dimensions and conditions prior to work commencement, contractor responsibility for code compliance without additional owner cost, furnishing of as-built record documents upon completion, and a one-year warranty from the date of final acceptance. The project mandates specialized inspections and testing including duct pressure testing coordinated with local mechanical inspectors, test and balance reporting, and permanent link testing for electrical systems. Critical coordination notes require contractors to verify equipment connections, maintain fire and smoke wall assembly integrity, provide UL-approved drawings for fire-rated penetrations, obtain all necessary permits and connection fees, and maintain a clean construction site. The construction documents serve as binding instruments of service prepared by the design professional and retain all copyright and reserved rights.

View the file

Other files

File Type Posted
Commissioning_Agent_for_Eastside_Bus_Transfer_Facility_(Addendum_#1_Revision).pdf PDF
COG_RTS_EASTSIDE_DIVISION_11_EQUIPMENT.pdf PDF
COG_RTS_EASTSIDE_DIVISION_26_ELECTRICAL.pdf PDF
COG_RTS_EASTSIDE_DIVISION_29_FIRE_SAFETY_AND_EMERGENCY_COMMUNICATIONS.pdf PDF
COG_RTS_EASTSIDE_DIVISION_10_SPECIALIST.pdf PDF
COG_RTS_EASTSIDE_DIVISION_12_FURNISHINGS.pdf PDF
COG_RTS_EASTSIDE_DIVISION_23_HEATING,_VENTILATING,_AND_AIR-COND..pdf PDF
COG_RTS_EASTSIDE_DIVISION_27_COMMUNICATIONS.pdf PDF
COG_RTS_EASTSIDE_DIVISION_08_OPENINGS.pdf PDF
COG_RTS_EASTSIDE_DIVISION_09_FINISHES.pdf PDF
34-0007_-_COG_-_RTS_EBF_-_ARCH_100%_Construction_Docs_Combined.pdf PDF
34-0007_-_COG_-_RTS_EBF_-_STRUCTURAL_100%_CONSTR_DOCS_COMBINED.pdf PDF
34-0007_-_COG_-_RTS_Eastside_Bus_Facility_-_CIVIL_Addendum_1_Combined.pdf PDF
COG_RTS_EASTSIDE_DIVISION_07_THERMAL_AND_MOISTURE_PROTECTION.pdf PDF
COG_RTS_EASTSIDE_DIVISION_22_PLUMBING.pdf PDF
COG_RTS_EASTSIDE_DIVISION_28_ELECTRONIC_SAFETY_AND_SECURITY.pdf PDF
COG_RTS_EASTSIDE_DISIVION_00_INTRODUCTORY_INFORMATION.pdf PDF
260401_COG_EBTF_LETTER_OF_TRANSMITTAL_100_CONSTRUCTION_DOCUMENTATION.pdf PDF
34-0007_-_COG_-_RTS_Eastside_Bus_Facility_-_Project_Manual.pdf PDF
COG_RTS_EASTSIDE_DIVISION_06_WOOD,_PLASTICS,_AND_COMPOSITES.pdf PDF
COG_RTS_EASTSIDE_DIVISION_01_GENERAL_REQUIREMENTS.pdf PDF
COG_RTS_EASTSIDE_DIVISION_03_CONCRETE.pdf PDF
COG_RTS_EASTSIDE_DIVISION_04_MASONRY.pdf PDF
COG_RTS_EASTSIDE_DIVISION_05_METALS.pdf PDF
Commissioning_Agent_for_Eastside_Bus_Transfer_Facility.pdf PDF
Respondent_References.pdf PDF
Certification_Regarding_Debarment.pdf PDF
Drug_Free_Workplace.pdf PDF
Consolidated_State_Law_Affidavit_10-22-25.docx DOCX document
Contractor_Responsibility_Certification.pdf PDF
Federal_Tax_Liability_and_Recent_Felony_Conviction.pdf PDF
Drug_Free_Workplace.pdf PDF
Federal_Tax_Liability_and_Recent_Felony_Conviction.pdf PDF
Federally_Funded_Purchase_Questionnaire.pdf PDF
Contractor_Responsibility_Certification.pdf PDF
Prohibition_on_Certain_Telecommunications....pdf PDF
Respondent_References.pdf PDF
Certification_Regarding_Debarment.pdf PDF
Prohibition_on_Certain_Telecommunications....pdf PDF
Consolidated_State_Law_Affidavit_10-22-25.docx DOCX document
Federally_Funded_Purchase_Questionnaire.pdf PDF
Respondent_Verification.pdf PDF
Respondent_Verification.pdf PDF
Draft_Contract.pdf PDF
Draft_Contract.pdf PDF
Show all 45

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MD

1. TRAP AIR CONDITIONING CONDENSATE AND RUN TO SAFEWASTE AT LOCATION SHOWN ON PLANS.

2. INSTALL DUCTWORK, PIPING, ETC. AS HIGH AS POSSIBLE ABOVE CEILING WHILE MAINTAINING

ACCESSIBILITY FOR EQUIPMENT AND DEVICES AS APPROPRIATE.

3. COORDINATE LOCATION OF ALL EQUIPMENT, DUCTWORK AND PIPING INSTALLATIONS WITH ELECTRICAL

TO PROVIDE THE REQUIRED CLEARANCES AROUND ALL ELECTRICAL PANELS, SWITCHGEAR, ETC.

4. INSTALLATION OF EQUIPMENT, DUCTWORK AND PIPING SHALL PROVIDE CONVENIENT ACCESS FOR

REMOVAL OF FILTERS AND FOR MAINTENANCE.

5. DUCT SIZES GIVEN ARE SHEET METAL SIZES.

6. COORDINATE EXACT LOCATIONS OF AIR DISTRIBUTION EQUIPMENT WITH THE CEILING AND THE LIGHTING

LAYOUT.

7. THE CEILING DIFFUSERS SHALL BE 4-WAY THROW UNLESS OTHERWISE NOTED.

8. PROVIDE NEW AIR FILTERS IN EACH UNIT REQUIRING FILTERS WHEN THE PROJECT IS READY FOR TEST

AND BALANCE. DO NOT OPERATE UNITS WITHOUT FILTERS DURING CONSTRUCTION. REPLACE FILTERS

DURING CONSTRUCTION ACCORDING TO FILTER MANUFACTURER'S RECOMMENDATIONS. SEAL ALL

OPEN ENDS OF DUCT WORK DURING CONSTRUCTION.

9. WHEREVER THE DEPTH OF THE TRUNK DUCT IS LESS THAN THE ROUND RUNOUT DUCT DIAMETER, PROVIDE TRANSITION FITTING OF EQUIVALENT AREA TO THE RUNOUT DUCT.

10. PROVIDE FLEXIBLE DUCT CONNECTIONS AT EACH EQUIPMENT CONNECTION.

11. OUTSIDE AIR INTAKES SHALL NOT BE LOCATED ANY CLOSER THAN 15 FEET FROM ANY CHIMNEY OR

EXHAUST OUTLET OR PLUMBING VENT TERMINAL.

12. PROVIDE FIRE DAMPER AT EVERY DUCT PENETRATION OF FIRE RATED CONSTRUCTION, WHETHER

SHOWN ON THE DRAWINGS OR NOT.

13. INSTALL DUCT MOUNTED SMOKE DETECTOR (FURNISHED BY DIV. 29) IN SUPPLY TRUNK DUCT BEFORE

ANY TAKE-OFFS FOR AIR HANDLING UNITS WITH SUPPLY AIR CAPACITY GREATER THAN 2000 CFM AND

WHERE INDICATED ON PLANS.

14. WHERE FIRE DAMPERS ARE REQUIRED, PROVIDE DUCT ACCESS DOORS TO ALLOW RE-LINKING OF DAMPER FUSIBLE LINKS. PROVIDE CEILING/WALL ACCESS PANELS WHERE INSTALLED IN INACCESSIBLE

LOCATIONS; ACCESS PANELS IN RATED CONSTRUCTION SHALL BEAR UL LABEL.

15. WHERE DUCT MOUNTED SMOKE DETECTORS ARE REQUIRED, PROVIDE DUCT ACCESS DOORS TO ALLOW VIEWING AND SERVICING. PROVIDE CEILING/WALL ACCESS PANELS WHERE INSTALLED IN INACCESSIBLE

LOCATIONS; ACCESS PANELS IN RATED CONSTRUCTION SHALL BEAR UL LABEL.

16. WHERE SMOKE DAMPERS OR COMBINATION FIRE/SMOKE DAMPERS ARE REQUIRED, PROVIDE DUCT ACCESS DOORS TO ALLOW RE-LINKING OF DAMPER FUSIBLE LINKS AND TO ALLOW VIEWING AND REMOVAL OF SMOKE DETECTORS. PROVIDE CEILING/WALL ACCESS PANELS WHERE INSTALLED IN

INACCESSIBLE LOCATIONS; ACCESS PANELS IN RATED CONSTRUCTION SHALL BEAR UL LABEL.

17. IT IS RECOMMENDED THAT DUCTWORK BE FABRICATED FROM FIELD MEASUREMENTS TAKEN AS THE

BUILDING STRUCTURE AND SPACE COMPETING SYSTEMS ARE PROGRESSIVELY INSTALLED. THE

DUCTWORK AS SHOWN ON THE CONSTRUCTION DOCUMENTS IS DIAGRAMMATIC AND DOES NOT

NECESSARILY INCLUDE ALL MODIFICATIONS REQUIRED TO AVOID THESE INTERFERENCES. BEFORE

FABRICATING ANY DUCTWORK, CHECK THE PHYSICAL CONDITIONS AT THE JOB SITE AND MAKE

CHANGES IN CROSS SECTIONS, ROUTING, OFFSETS AND SIMILAR ITEMS WHETHER SPECIFICALLY

INDICATED OR NOT. VERIFY THAT SUFFICIENT CLEARANCES ARE AVAILABLE FOR INSTALLING

DUCTWORK, PIPING, LIGHT FIXTURES, CEILING SYSTEMS AND TO PROVIDE EQUIPMENT SERVICE. COSTS REQUIRED TO CHANGE DUCTWORK TO FIT THE SPACE AVAILABLE AND AVOID INTERFERENCES CAUSED

BY SPACE COMPETING SYSTEMS SHALL BE BORNE BY THE CONTRACTOR. NO ADDITIONAL

REMUNERATION WILL BE PAID BY THE OWNER.

18. APPLY EXTERNAL INSULATION TO SINGLE WALL SUPPLY DUCTS, RETURN DUCTS AND OUTSIDE AIR

DUCTS PER SPECIFICATIONS.

19. PROVIDE VOLUME CONTROL DAMPERS IN SIDE TAKE-OFF FITTINGS TO SUPPLY AIR DIFFUSERS AND EXHAUST AIR AND RETURN AIR GRILLES AND AT EACH DUCT BRANCH SERVING TWO OR MORE AIR

TERMINALS, WHETHER SHOWN ON THE DRAWINGS OR NOT.

20. PROVIDE ACCESS PANEL AT EACH LOCATION WHERE A VALVE, DAMPER OR OTHER DEVICE REQUIRING SERVICE IS LOCATED ABOVE AN INACCESSIBLE CEILING OR INSIDE A WALL. ACCESS PANELS IN RATED CONSTRUCTION SHALL BEAR UL LABEL. COORDINATE ACCESS PANEL LOCATION WITH ARCHITECT PRIOR

TO INSTALLATION.

21. PATCH ALL BREAKS, TEARS AND VOIDS IN EXISTING EXTERNAL DUCT INSULATION WITHIN PROJECT AREA.

SEAL INSULATION USING ALUMINUM DUCT TAPE.

22. BEFORE COMMENCING ANY WORK, MEASURE AND RECORD AIR QUANTITIES OF SUPPLY AIR OUTLETS OF EACH AHU SYSTEM AFFECTED BY THIS WORK. UPON COMPLETION OF WORK, BALANCE EACH SYSTEM TO AIR QUANTITIES SHOWN AND TO PREVIOUSLY RECORDED QUANTITIES OF OTHER OUTLETS ON THAT

SYSTEM. ADJUST AHU SUPPLY FAN ACCORDINGLY.

23. COORDINATE ALL DUCT TEST WITNESSING WITH LOCAL MECHANICAL INSPECTOR.

24. PRIOR TO FINAL INSPECTION, PROVIDE CERTIFIED TEST & BALANCE REPORT AND OPERATIONS &

MAINTENANCE MANUALS TO THE OWNER.

25. PROVIDE DUCT ACCESS DOOR AT EACH FLOW MEASURING STATION.

26. DUCT CONSTRUCTION, INCLUDING SHEET METAL THICKNESS, SEAM AND JOINT CONSTRUCTION, REINFORCEMENTS, AND HANGERS AND SUPPORTS, SHALL COMPLY WITH SMACNA'S "HVAC DUCT

CONSTRUCTION STANDARDS - METAL AND FLEXIBLE DUCT."

27. LOCATIONS OF EXISTING EQUIPMENT ARE BASED ON REFERENCE MATERIALS PROVIDED TO THE

ENGINEER AND CONCEALED ELEMENTS HAVE NOT BEEN VERIFIED. CONTRACTOR SHALL LOCATE

CONCEALED ELEMENTS AND NOTIFY ENGINEER IF VARIANCES BETWEEN THESE DOCUMENTS AND

ACTUAL FIELD CONDITIONS EXIST AND MAY MATERIALLY AFFECT THE DESIGN INTENT.

HVAC NOTESAPPLICABLE CODES

RECTANGULAR SHEET METAL DUCT

AIR DISTRIBUTION

AxB

PIPING AND FITTINGS

C CONDENSATE DRAIN PIPING FROM COOLING COIL PERFORM WORK IN ACCORDANCE WITH THE FOLLOWING CODES AND ANY APPLICABLE STATUTES, ORDINANCES, CODES, AND REGULATIONS OF GOVERNMENTAL AUTHORITIES HAVING JURISDICTION.

1. ASHRAE

a. STANDARD 55 THERMAL ENVIRONMENTAL CONDITIONS FOR HUMAN OCCUPANCY - 2017

b. STANDARD 62.1 VENTILATION STANDARD FOR ACCEPTABLE INDOOR AIR QUALITY - 2019

c. STANDARD 90.1 ENERGY STANDARD FOR BUILDINGS EXCEPT LOW RISE RESIDENTIAL

BUILDINGS - 2019

2. OCCUPATIONAL SAFETY AND HEALTH REGULATIONS (OSHA).

3. NATIONAL FIRE CODES

a. NFPA 1 UNIFORM FIRE CODE - 2021 (FLORIDA EDITION)

b. NFPA 70 NATIONAL ELECTRICAL CODE - 2020

c. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE - 2019

d. NFPA 90A STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATION

SYSTEMS - 2021

e. NFPA 90B STANDARD FOR THE INSTALLATION OF WARM AIR HEATING AND AIR

CONDITIONING SYSTEMS - 2024

f. NFPA 101 LIFE SAFETY CODE - 2021 (FLORIDA EDITION)

4. FLORIDA BUILDING CODE, 2023 EDITION

a. BUILDING CODE

b. ENERGY CONSERVATION CODE

c. MECHANICAL CODE

d. PLUMBING CODE

e. ACCESSIBILITY CODE

5. FLORIDA STATUTES

a. CHAPTER 471 ENGINEERING

b. CHAPTER 533.80 BUILDING CONSTRUCTION STANDARDS; FLORIDA BUILDING CODE -

ENFORCEMENT

6. FLORIDA ADMINISTRATIVE CODE

a. CHAPTER 61G15-34 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE

DESIGN OF MECHANICAL SYSTEMS

b. CHAPTER 69A-3 FIRE PREVENTION - GENERAL PROVISIONS

c. CHAPTER 69A-60 THE FLORIDA FIRE PREVENTION CODE

RESOLVE, IN WRITING, ANY CODE VIOLATION DISCOVERED IN CONTRACT DOCUMENTS WITH THE ENGINEER PRIOR TO BIDDING. AFTER AWARD OF THE CONTRACT, MAKE ANY CORRECTION OR ADDITION NECESSARY

FOR COMPLIANCE WITH APPLICABLE CODES AT NO ADDITIONAL COST TO OWNER.

THE CONTRACTOR SHALL INCLUDE IN THE WORK, WITHOUT EXTRA COST TO THE OWNER, ANY LABOR, MATERIALS, SERVICES, APPARATUS, AND DRAWINGS REQUIRED TO COMPLY WITH ALL APPLICABLE LAWS, ORDINANCES, RULES, AND REGULATIONS.

WHERE THERE IS CONFLICT BETWEEN THE CONTRACT DOCUMENTS AND THE APPLICABLE CODES, THE CODES SHALL GOVERN, EXCEPT WHERE THE REQUIREMENTS OF THE CONTRACT DOCUMENTS ARE MORE

STRINGENT.

REF REFRIGERANT PIPING (ONE LINE REPRESENTS BOTH LIQUID AND GAS LINES)

UNION

FLEXIBLE PIPE CONNECTION

NEW PIPE

BALL VALVE (WITH QUARTER TURN HANDLE)

VALVES

BUTTERFLY VALVE (WITH QUARTER TURN HANDLE)

N.O. N.C.

N.C.N.O.

QUARTER TURN LEVER

HANDWHEEL

VALVE ACTUATORS:

M ELECTRIC MOTOR

FLEXIBLE RUNOUT DUCT

ROUND OR RECTANGULAR TAKE-OFF FITTING WITH

BALANCING DAMPER - SEE DETAIL D/M501

SUPPLY AIR DUCTWORK SECTION

RETURN AIR DUCTWORK SECTION

AIR BALANCING DAMPER (MANUAL)

CONTROL DAMPER (MOTORIZED)

EXHAUST AIR DUCTWORK SECTION

DUCTWORK FLEXIBLE CONNECTION

DUCT ELBOW WITH SINGLE THICKNESS TURNING VANES

SIDEWALL REGISTER AND AIR FLOW (CFM)(SEE SCHEDULE

FOR SIZES UNLESS NOTED OTHERWISE)

SQUARE CEILING SA DIFFUSER AND AIR FLOW (CFM)(SEE SCHEDULE FOR SIZES

UNLESS NOTED OTHERWISE) SHADED REGION INDICATED SECTORIZING BAFFLE(S)

RECTANGULAR CEILING RA REGISTER AND AIR FLOW (CFM)(SEE SCHEDULE FOR

SIZES UNLESS NOTED OTHERWISE) WHERE CFM IS NOT INDICATED, PROVIDE

STANDARD SIZE FOR CEILING TYPE INDICATED IN SCHEDULE. SEE DETAIL E/M501

RECTANGULAR CEILING EA REGISTER AND AIR FLOW (CFM)(SEE SCHEDULE FOR

SIZES UNLESS NOTED OTHERWISE) SEE DETAIL E/M501

CFM

CFM

CFM

ACCESS PANEL IN INACCESSIBLE CEILING (24x24, UNO) SEE DETAIL J/M502AP

NEW DUCT

DUCT MOUNTED SMOKE DETECTOR (PROVIDED AND INSTALLED BY FIRE ALARM

CONTRACTOR)

DOOR UNDERCUT (3/4", UNO)

U C

LENGTH OF DIFFUSER (FEET)

NUMBER OF SLOTS

SLOT WIDTH (2 = 1/2", 3 = 3/4", 4 = 1", 6 = 1 1/2")

INLET SIZE (INCHES)

AIR FLOW (CFM)

4-4-4-12

SA SLOT DIFFUSER WITH PLENUM / BOOT (FLOW DIRECTION INDICATED)

LENGTH OF DIFFUSER (FEET)

NUMBER OF SLOTS

SLOT WIDTH (2 = 1/2", 3 = 3/4", 4 = 1", 6 = 1 1/2")

INLET SIZE (INCHES)

AIR FLOW (CFM)

4-4-4-12

RA SLOT DIFFUSER WITH PLENUM / BOOT (TO MATCH SA DIFFUSER IN SAME

ROOM)

AC ABOVE CEILING

AFF ABOVE FINISHED FLOOR

AHAP AS HIGH AS POSSIBLE

AHU AIR HANDLING UNIT

BDD BACKDRAFT DAMPER

BHP BRAKE HORSEPOWER

BOD BOTTOM OF DUCT

BTUH BRITISH THERMAL UNITS PER HOUR

C CONDENSATE

CC COOLING COIL

CFM CUBIC FEET PER MINUTE

CU CONDENSING UNIT

DDC DIRECT DIGITAL CONTROL PANEL

DN DOWN

EA EXHAUST AIR

EAG EXHAUST AIR GRILLE

EF EXHAUST FAN

ER EXHAUST REGISTER

F FEET

°Fdb DEGREES FAHRENHEIT DRY BULB °Fwb DEGREES FAHRENHEIT WET BULB

FPM FEET PER MINUTE

GPH GALLONS PER HOUR

HC HEATING COIL

HP HORSEPOWER

IN INCHES

MCA MINIMUM CIRCUIT AMPACITY

MOCP MAXIMUM OVERLOAD PROTECTION

N.C. NORMALLY CLOSED

N.O. NORMALLY OPEN

OA OUTSIDE AIR

RA RETURN AIR

RAG RETURN AIR GRILLE

RAR RETURN AIR REGISTER

REF REFRIGERANT

RPM REVOLUTIONS PER MINUTE

SA SUPPLY AIR

SAR SUPPLY AIR REGISTER

SF SUPPLY FAN

SMS SHEET METAL SIZE

SQ FT SQUARE FEET

TOD TOP OF DUCT

TOP TOP OF PIPE

TYP TYPICAL

UC DOOR UNDERCUT (3/4", UNO)

UNO UNLESS NOTED OTHERWISE

V VALVE

VAV VARIABLE AIR VOLUME

VFD VARIABLE FREQUENCY DRIVE

WG WATER GAUGE

ABBREVIATIONS

DRAWING INDEX

THERMOSTAT/TEMPERATURE SENSORT

MEASUREMENTS AND CONTROLS

SYMBOL

CEILING SUPPLY DIFFUSERS

CFM NECK SIZE

MINIMUM - MAXIMUM

1/2 SPACING

FACE DIMENSION

HARD

CEILING

LAY-IN

CEILING

40-80

85-180

185-340

345-500

505-600

6"Ø

8"Ø

10"Ø

12"Ø

14"Ø

4' - 5'

4' - 8'

8' - 10'

9' - 10'

10' - 12'

12x12

12x12

24x24

24x24

24x24

24x24

24x24

24x24

24x24

24x24

NOTE:

1. RUNOUT DUCTS TO DIFFUSERS SHALL BE THE SAME SIZE AS THE INDICATED NECK SIZE.

SYMBOL

CEILING RETURN OR EXHAUST REGISTERS & GRILLES

CFM

0-95

100-195

200-295

300-595

600-695

18x18 (NOTE 1)

22x22 (NOTE 1)

GRILLE SIZE

700-795

6x6

8x8

10x8

12x12

12x12

RUNOUT DUCT (NOTE 2)

14x12

800-1500 18x14

OR

NOTES:

1. USE 22x22 GRILLE SIZE FOR ALL LAY-IN CEILING APPLICATIONS. USE SIZE INDICATED FOR HARD CEILING

APPLICATIONS.

2. WHERE DUCT CONNECTION IS SHOWN, RUNOUT DUCT SHALL BE SIZE SHOWN IN SCHEDULE U.N.O.

3. USE 18x18 GRILLE SIZE AND 12x12 RUNOUT DUCT FOR HARD CEILING APPLICATIONS WHERE SIZE OR

AIRFLOW IS NOT INDICATED.

4. USE 12x12 RUN OUT DUCT FOR LAY-IN CEILING APPLICATIONS WHERE AIRFLOW IS NOT INDICATED.

24x24 (NOTE 1)

48x24 (NOTE 1)

8x8 (NOTE 1)

10x10 (NOTE 1)

12x12 (NOTE 1)

ROUND SHEET METAL DUCTCØ

GENERAL NOTES

1. INSTALL ALL WORK IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 2023, THE FLORIDA FIRE PREVENTION CODE, THE NATIONAL ELECTRICAL CODE 2020 EDITION, AND ALL CODES, ORDINANCES, RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION AT THIS SITE. WHERE CONFLICTS

OCCUR BETWEEN CODES AND THE CONSTRUCTION DOCUMENTS, THE MOST RESTRICTIVE

REQUIREMENTS SHALL GOVERN.

2. DRAWINGS ARE DIAGRAMMATIC, INDICATIVE OF WORK TO BE FURNISHED AND INSTALLED UNDER THIS

CONTRACT. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR ALL DIMENSIONS.

3. FIELD VERIFY DIMENSIONS AND CONDITIONS. IF THE CONTRACTOR IS UNABLE TO INTERPRET THE CONTRACT DOCUMENTS, CONTRACTOR IS RESPONSIBLE TO REQUEST CLARIFICATION IN WRITING TO THE ARCHITECT. IF CONTRACTOR PROCEEDS WITH ANY WORK BEFORE OBTAINING CLARIFICATION, CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ALL DEFICIENCIES ASSOCIATED THEREWITH.

4. BEFORE SUBMITTING FOR THE WORK, EACH BIDDER WILL BE RESPONSIBLE TO EXAMINE THE PREMISES AND SATISFY HIMSELF AS TO THE EXISTING CONDITIONS UNDER WHICH CONTRACTOR WILL BE OBLIGED

TO OPERATE AND COMPLETE THE WORK UNDER THIS CONTRACT. NO ALLOWANCE WILL

SUBSEQUENTLY BE MADE IN THIS CONNECTION ON BEHALF OF THE CONTRACTOR FOR ANY ERROR OR

OMISSION ON CONTRACTOR'S PART.

5. THE CONTRACTOR SHALL PAY FOR ALL INSPECTION PERMITS, CERTIFICATES, CONNECTION FEES, SYSTEM DEMAND CHARGES AND LICENSE FEES IN CONNECTION WITH CONTRACTOR'S WORK.

6. CONSTRUCTION MANAGER OR GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR SEQUENCING AND

COORDINATING WORK OF SUBCONTRACTORS TO AVOID INTERFERENCES.

7. WORK SHALL COMPLY WITH APPLICABLE O.S.H.A. AND E.P.A. REGULATIONS AND GUIDELINES.

8. ERECT AND MAINTAIN ALL REASONABLE PRECAUTIONS FOR SAFETY AND HEALTH INCLUDING POSTING

DANGER SIGNS AND OTHER WARNINGS AGAINST HAZARDS INCLUDING PROMULGATING SAFETY

REGULATIONS. PROVIDE SAFETY PRECAUTIONS AND BARRICADES FOR PEDESTRIANS AT

CONSTRUCTION VEHICLE ACCESS AND EGRESS LOCATIONS.

9. THE CONTRACTOR SHALL PROVIDE MANPOWER AND EQUIPMENT NECESSARY TO MAINTAIN THE

PROJECT SCHEDULE.

10. THE CONTRACTOR SHALL BE RESTRICTED TO AREAS DESIGNATED BY THE OWNER FOR ON-SITE STORAGE OF CONSTRUCTION MATERIALS AND IS RESPONSIBLE FOR THE PROTECTION AND SECURITY

OF ALL EQUIPMENT AND MATERIALS.

11. THE CONTRACTOR SHALL MAINTAIN A CLEAN WORK ENVIRONMENT AND SHALL CLEAN CONSTRUCTION

SITE OF ALL DEBRIS AT COMPLETION OF THE JOB AND BEFORE FINAL PAYMENT IS MADE.

12. THE CONTRACTOR SHALL FURNISH "AS-BUILT" RECORD DOCUMENTS TO THE OWNER AT COMPLETION

OF CONSTRUCTION.

13. CONTRACTOR SHALL GUARANTEE THE WORK AND MATERIALS FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE. THIS GUARANTEE SHALL BE IN ADDITION TO THE WARRANTIES PROVIDED BY

MATERIAL SUPPLIERS AND MANUFACTURERS.

14. CONTRACTOR'S APPROVAL STAMP ON SUBMITTALS AND SHOP DRAWINGS CERTIFIES THAT THE CONTRACTOR HAS REVIEWED THE DOCUMENTS AND THAT THE CONTRACT DOCUMENT REQUIREMENTS

HAVE BEEN ADHERED TO.

15. THE CONTRACTOR SHALL NOT BE RELIEVED OF RESPONSIBILITY FOR DEVIATIONS FROM

REQUIREMENTS OF THE CONTRACT DOCUMENTS BY THE ARCHITECT/ENGINEER'S APPROVAL OF SHOP

DRAWINGS, PRODUCT DATA, SAMPLES OR SIMILAR SUBMITTALS UNLESS THE CONTRACTOR HAS

SPECIFICALLY INFORMED THE ARCHITECT/ENGINEER IN WRITING OF SUCH DEVIATION AT THE TIME OF

SUBMITTAL AND THE ARCHITECT/ENGINEER HAS GIVEN WRITTEN APPROVAL TO THE SPECIFIC

DEVIATION. THE CONTRACTOR SHALL NOT BE RELIEVED OF RESPONSIBILITY FOR ERRORS OR

OMISSIONS IN SHOP DRAWINGS, PRODUCT DATA, SAMPLES OR SIMILAR SUBMITTALS BY THE

ARCHITECT/ENGINEER'S APPROVAL THEREOF.

16. PRIOR TO INSTALLATION, COORDINATE AND ADJUST THE FINAL LOCATION OF ALL WALL MOUNTED DEVICES AND EQUIPMENT WITH ALL CASEWORK, SHELVING, MARKER BOARDS, BULLETIN BOARDS OR

OTHER WALL MOUNTED FURNISHINGS.

17. ENTRY AND/OR REMOVAL OF EQUIPMENT FROM THE BUILDING SHALL BE THE RESPONSIBILITY OF THE

CONTRACTOR. DISMANTLE AND REASSEMBLE EQUIPMENT AS NECESSARY FOR ENTRY INTO THE

BUILDING AND/OR EQUIPMENT ROOMS. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGED

MATERIALS TO MATCH THE ADJACENT UNDAMAGED SURFACES.

18. PROTECT THE ROOF FROM DAMAGE WHENEVER ANY WORK ON THE ROOF IS REQUIRED.

19. SUPPORTS AND HANGERS SHALL PRESENT A NEAT, ORDERLY APPEARANCE.

20. CONTRACTOR SHALL MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE WALL ASSEMBLIES AND

ACOUSTICAL WALLS.

21. BEAM AND FLOOR PENETRATIONS SHALL BE APPROVED BY THE STRUCTURAL ENGINEER. BEAM

SLEEVES AND BEAM REINFORCING APPROVED BY STRUCTURAL ENGINEER SHALL BE FURNISHED AND

INSTALLED BY THIS CONTRACTOR.

22. CONTRACTOR SHALL FURNISH U.L. APPROVED DRAWINGS FOR EACH TYPE OF FIRE RATED ASSEMBLY PENETRATION BY DUCTS, PIPES OR CONDUITS. THESE DRAWINGS SHALL BE DISPLAYED ON THE JOB

SITE AT ALL TIMES DURING CONSTRUCTION. SEE SPECIFICATIONS.

A L

L R

E P

O R

T S

P

LA

N

S

S P

E C

IF

IC

A T

IO

N

S

C O

M P

U T

E R

F

IL

E S

F

IE

LD

D A

T A

N

O T

E S

O

T H

E R

D O

C U

M E

N T

S

IN

S

T R

U M

E N

T S

P R

E P

A R

E D

B Y

T H

E D

E S

IG

N

P R

O F

E S

S

IO

N A

L A

S

IN

S T

R U

M E

N T

S O

F S

E R

V

IC

E S

H A

LL

R

E M

A

IN

T H

E P

R O

P E

R T

Y O

F T

H E

D E

S

IG

N P

R O

F E

S S

IO

N

A L.

T H

E D

E S

IG

N

P R

O F

E S

S

IO

N A

L S

H A

LL

R

E T

A

IN

A

LL

C O

M M

O N

L A

W

S T

A T

U T

O R

Y

O T

H E

R R

E S

E R

V E

D R

IG

H

T S

IN

C

LU

D

IN

G T

H E

C O

P Y

R

IG

H T

T H

E R

E T

O

U S

E O

F T

H E

S E

D O

C U

M E

N T

S F

O R

A N

Y P

U R

P O

S E

O R

P R

O

JE

C T

O T

H E

R T

H A

N T

H E

P R

O

JE

C T

W H

IC

H

I S

S U

B

JE

C T

O F

T H

E A

G R

E E

M E

N T

IS

U

N L

A W

F U

L.

Florida Registry #2485

SEAL

Matthew R. Thoele, P.E #75448

DESIGN PHASE:

114 EAST 5TH AVENUE TALLAHASSEE, FL

32303 PHONE 850.224.7922

www.H2Engineering.com

H2E PROJECT No. 24024

THIS DOCUMENT IS THE PROPERTY OF H2Engineering

AND IS PREPARED AS AN INSTRUMENT OF SERVICE. ITS

USE, REUSE OR REPRODUCTION, EXCEPT BY WRITTEN

AGREEMENT WITH H2Engineering, IS PROHIBITED.

/1

/2

:2 :4

P

M A u to d e s k D o c s:

-0

G a in e s v ill e R

T S

E a s ts id e B u s F a c ili ty /2

-0

G a in e sv ill e R

T S

E a st s id e B u s

F a ci lit y M

E P

R

.r v t

Project Number: 34-0007

Date: 4/1/2026

Drawn By: KWW

Checked By: MRT

GENERAL NOTES & LEGENDS

LOT 3, INTERSECTION OF S.E.

HAWTHORNE ROAD & S.E. 21ST

STREET

M001

EASTSIDE BUS

TRANSFER FACILITY

100% CONSTRUCTION DOCUMENTS

CITY OF GAINESVILLE DEPARTMENT

OF TRANSPORTATION

M001 GENERAL NOTES & LEGENDS

M002 SCHEDULES

M101 FLOOR PLAN - HVAC

M501 DETAILS

M502 DETAILS

REVISIONS

DUCTLESS SPLIT SYSTEM TYPES

TYPE DSSI-1/DSSO-1

DESCRIPTION COOLING ONLY

PERFORMANCE - (NOTES 1 & 2)

NOMINAL CAPACITY TONS 1 1/2

TOTAL COOLING CAPACITY BTUH 18,000

SENSIBLE COOLING CAPACITY BTUH 13,700

HEATING CAPACITY @ 47 °F BTUH N/A

HEATING CAPACITY @ 17 °F BTUH N/A

AIR FLOW RATE (HIGH - LOW) CFM 500 - 400

SEER2 BTU / W-HR 16.9

HSPF2 BTU / W-HR N/A

INDOOR UNIT DATA

FILTERS 1" WASHABLE

CONDENSATE DRAIN SIZE IN. 3/4

ELECTRICAL CHARACTERISTICS V / PH 208 / 1

MINIMUM CIRCUIT AMPACITY AMPS 0.5

MAXIMUM OVERLOAD PROTECTION AMPS 15

WEIGHT LBS. 31

OUTDOOR UNIT DATA

COMPRESSOR TYPE INVERTER

ELECTRICAL CHARACTERISTICS V / PH 208 / 1

MINIMUM CIRCUIT AMPACITY AMPS 16.5

MAXIMUM OVERLOAD PROTECTION AMPS 20

WEIGHT LBS. 172

MAX REFRIGERANT LINE LENGTH FT 164

REFRIGERANT TYPE R410A

MANUFACTURER DAIKIN

MODEL NUMBER (INDOOR UNIT) FAQ18TAVJU

MODEL NUMBER (OUTDOOR UNIT) RZR18TBVJU

DETAIL REFERENCE A/M502 F/M502

NOTES:

1 COOLING CAPACITY RATED @ 95 °F AMBIENT, 80°Fdb / 67°Fwb ENTERING AIR TEMPERATURE.

2 HEATING CAPACITY RATED @ 47 °Fdb / 43°Fwb AMBIENT, 70°Fdb ENTERING AIR TEMPERATURE.

3 UNIT SHALL BE CAPABLE OF OPERATION FOR AMBIENT TEMPERATURES DOWN TO 14°F

4 REFRIGERANT PIPING SHALL BE SIZED BY MANUFACTURER.

5 PROVIDE INTEGRAL CONDENSATE SENSOR TO SHUT UNIT OFF IF HIGH CONDENSATE LEVELS ARE DETECTED IN THE DRAIN PAN.

DESIGN CONDITIONS

OUTDOOR CONDITIONS - DESIGN DAY (GAINESVILLE, FLORIDA)

COOLING (0.4% ANNUAL) °Fdb - °Fwb 95.0 - 80.0

HEATING (99.6% ANNUAL) °Fdb 30.0

INDOOR CONDITIONS - SUMMER

ALL AREAS °Fdb - %RH 74 - 55

INDOOR CONDITIONS - WINTER

ALL AREAS °Fdb - %RH 70 - 30

SPLIT SYSTEM TYPES (1 - 5 TONS)

TYPE

DESCRIPTION HEAT PUMP HEAT PUMP

PERFORMANCE - (NOTES 1 & 2)

NOMINAL CAPACITY TONS 3 5

TOTAL COOLING CAPACITY BTUH 36,700 57,700

SENSIBLE COOLING CAPACITY BTUH 27,100 44,400

HEATING CAPACITY @ 47°F BTUH 20,500 38,500

AIR FLOW RATE CFM 1,215 1,975

SEER2 BTU / W-HR 16.0 14.7

INDOOR UNIT DATA

NOMINAL CAPACITY TONS 3 5

FAN DRIVE TYPE DIRECT DIRECT

FAN MOTOR HORSEPOWER HP 1/2 1

EXTERNAL STATIC PRESSURE IN. WG 0.8 0.7

AUXILIARY HEATING CAPACITY (NOTE 3) kW - # 8.0 15

AUXILIARY HEAT TEMPERATURE RISE °F 15.6 18.0

ELECTRICAL CHARACTERISTICS V / PH 208 / 1 208/3

MINIMUM CIRCUIT AMPACITY (NOTE 4) AMPS 41 49

MAXIMUM OVERLOAD PROTECTION (NOTE 4) AMPS 45 50

FILTERS 1" THICK PLEATED 1" THICK PLEATED

CONDENSATE DRAIN SIZE IN. 3/4 1

WEIGHT LBS. 150 200

OUTDOOR UNIT DATA

NOMINAL CAPACITY TONS 3 5

NUMBER OF COMPRESSORS OR STAGES # 2 2

ELECTRICAL CHARACTERISTICS V / PH 208 / 1 208/3

MINIMUM CIRCUIT AMPACITY AMPS 19 23

MAXIMUM OVERLOAD PROTECTION AMPS 30 40

WEIGHT LBS. 188 246

REFRIGERANT TYPE R-454B R-454B

MANUFACTURER LENNOX LENNOX

MODEL NUMBER (INDOOR UNIT) CBK47UJET-036 CBK47UHET-060

MODEL NUMBER (OUTDOOR UNIT) ML17KC2-036-230 ML17KC2-060-233

DETAIL REFERENCE H/M501 H/M501

NOTES:

1 COOLING CAPACITY RATED @ 95°F AMBIENT, 80°Fdb / 67°Fwb ENTERING AIR TEMPERATURE.

2 HEATING CAPACITY RATED @ 47°Fdb / 43°Fwb AMBIENT, 70°Fdb ENTERING AIR TEMPERATURE.

3 AUXILIARY HEATING RATED @ 240 V

4 REFRIGERANT PIPING SHALL BE SIZED BY MANUFACTURER.

AIR BALANCE SCHEDULE

OFFICE SPACE COMMUNITY CENTER

OUTSIDE AIR EXHAUST AIR OUTSIDE AIR EXHAUST AIR

SOURCE CFM SOURCE CFM SOURCE CFM SOURCE CFM

AHU-1 90 AHU-4 600 RELIEF 500

TOTAL 90 TOTAL 0 TOTAL 600 TOTAL 500

BALANCE 90 CFM/SF 0.08 BALANCE 100 CFM/SF 0.05

AIR BALANCE SCHEDULE

PUBLIC SPACES (FANS ON) PUBLIC SPACES (FANS OFF)

OUTSIDE AIR EXHAUST AIR OUTSIDE AIR EXHAUST AIR

SOURCE CFM SOURCE CFM SOURCE CFM SOURCE CFM

AHU-2 140 EF-1 70 AHU-2 140 EF-1 70

EF-2 70 EF-2 70

EF-3 70 EF-3 70

TOTAL 140 TOTAL 210 TOTAL 140 TOTAL 0

BALANCE -70 CFM/SF -0.06 BALANCE 140 CFM/SF 0.11

MAKEUP AIR UNIT - SPLIT SYSTEM

INDOOR UNIT DESIGNATION AHU-4

OUTDOOR UNIT DESIGNATION CU-4

AIR FLOW RATES

TOTAL SUPPLY AIR CFM 600

OUTSIDE AIR CFM 600

FILTER SECTION

DAMPERS NONE

FILTER ORIENTATION FLAT

TYPE OF FILTER 2" THICK PLEATED

COOLING DATA

TOTAL COOLING CAPACITY MBTUH 60.3

SENSIBLE COOLING CAPACITY MBTUH 28.1

AIR ENTERING COOLING COIL °Fdb - °Fwb 95.0 – 80.0

AIR LEAVING COOLING COIL °Fdb - °Fwb 51.6 – 51.6

EER / IEER BTU / W-HR 16.0 / 11.3

CONDENSATE DRAIN SIZE IN. 1

HOT GAS REHEAT DATA

TYPE MODULATING

HEATING CAPACITY MBTUH 6.9

AIR ENTERING HOT GAS REHEAT COIL °F 51.6

AIR LEAVING HOT GAS REHEAT COIL °F 86.2

HEATING DATA - ELECTRIC

HEATING CAPACITY - # OF STAGES kW - # 8 – SCR

AIR ENTERING HEATING COIL °F 30

AIR LEAVING HEATING COIL °F 69.5

SUPPLY FAN SECTION

FAN TYPE AIRFOIL

DRIVE TYPE DIRECT

FAN QUANTITY # 1

EXTERNAL STATIC PRESSURE IN. WG 0.3

MAXIMUM TOTAL STATIC PRESSURE (INCLUDING DIRTY FILTER) IN. WG 1

DIRTY FILTER ALLOWANCE IN. WG 0.7

FAN MOTOR HORSEPOWER (PER FAN) HP - BHP 1 – 0.2

VARIABLE FREQUENCY DRIVE 1 PER UNIT

INDOOR UNIT DATA

WEIGHT LBS 815

ELECTRICAL CHARACTERISTICS V / PH 208 / 3

MCA / MOCP AMPS 32 / 35

OUTDOOR UNIT DATA

COMPRESSOR QUANTITY # 1

WEIGHT LBS 635

REFRIGERANT TYPE R410A

ELECTRICAL CHARACTERISTICS V / PH 208 / 3

MCA / MOCP AMPS 24 / 40

MANUFACTURER ADDISON

MODEL NUMBER (INDOOR UNIT) SCOA0048

MODEL NUMBER (OUTDOOR UNIT) SAOA0048

DETAIL REFERENCE

NOTES:

1 REFRIGERANT PIPING SHALL BE SIZED BY THE MANUFACTURER OF THE SUPPLIED SYSTEM.

2 PROVIDE ONE (1) VARIABLE CAPACITY COMPRESSOR.

3 PROVIDE SUPPLY AIR TEMPERATURE SENSOR.

4 PROVIDE OUTSIDE AIR TEMPERATURE AND HUMIDITY SENSORS.

5 PROVIDE SUCTION PRESSURE TRANSDUCER.

6 PROVIDE EBTRON GOLD SERIES AIRFLOW MEASURING STATION.

7 PROVIDE DISCONNECT SWITCH BY DIV 26.

8 PROVIDE NEUTRAL AIR CONTROL.

GRAVITY VENTILATOR SCHEDULE

DESIGNATION GV-1 OA-1 OA-2

SERVICE RELIEF INTAKE INTAKE

AIRFLOW CFM 500 230 600

THROAT SIZE IN. 14 14 14

HOOD DIAMETER IN. 29 29 29

CURB CAP IN. x IN. 22x22 22x22 22x22

WEIGHT LBS. 13 13 13

MANUFACTURER GREENHECK GREENHECK GREENHECK

MODEL NUMBER GRSR-15 GRSI-15 GRSI-15

DETAIL REFERENCE C/M502 C/M502 C/M502

NOTES:

1 PROVIDE PREFABRICATED ROOF CURB WITH WELDED CAP CORNERS AND DAMPER TRAY.

2 PROVIDE BACKDRAFT DAMPER.

3 PROVIDE ALUMINUM BIRD SCREEN.

FANS

DESIGNATION EF-1 EF-2 EF-3 EF-4

SERVICE

CLASS 1 OR 2

EXHAUST

CLASS 1 OR 2

EXHAUST

CLASS 1 OR 2

EXHAUST

CLASS 1 OR 2

EXHAUST

MOUNTING METHOD CEILING CEILING CEILING SUSPENDED

FAN TYPE

CENTRIFUGAL

CABINET

CENTRIFUGAL

CABINET

CENTRIFUGAL

CABINET

CENTRIFUGAL

SQUARE IN-LINE

AIR FLOW CFM 70 70 70 150

STATIC PRESSURE IN. 0.30 0.30 0.30 0.30

AIRSTREAM TEMPERATURE DEG F 70 70 70 70

FAN SPEED RPM 900 900 900 1,474

FAN DRIVE DIRECT DIRECT DIRECT DIRECT

MOTOR POWER HP or W 15 W 15 W 15 W 15 W

ELECTRICAL CHARACTERISTICS V / PH 120 / 1 120 / 1 120 / 1 120 / 1

WEIGHT LBS. 12 12 12 12

NOISE LEVEL (RADIATED) SONES or LwA 0.5 SONES 0.5 SONES 0.5 SONES 3.4 SONES

MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK

MODEL NUMBER SP-A90 SP-A90 SP-A90 SQ-70-VG

DETAIL REFERENCE D/M502 D/M502 D/M502 B/M501

NOTES:

1 PROVIDE PRE-WIRED DISCONNECT SWITCH, FACTORY MOUNTED FOR SINGLE PHASE MOTORS (3/4 HP AND SMALLER).

2 PROVIDE BACKDRAFT DAMPER.

3 PROVIDE WHITE, ALUMINUM INLET GRILLE.

4 PROVIDE TIME DELAY SWITCH, INSTANT ON WITH LIGHTS AND 10-MINUTE TIME DELAY OFF. WIRED BY DIV 26 CONTRACTOR.

5 PROVIDE SPEED CONTROLLER.

SPLIT SYSTEM SCHEDULE (1 - 5 TONS)

INDOOR UNIT DESIGNATION AHU-1 AHU-2 AHU-3

OUTDOOR UNIT DESIGNATION CU-1 CU-2 CU-3

SCHEDULED TYPE D D F

DESCRIPTION HEAT PUMP HEAT PUMP HEAT PUMP

SUPPLY AIR FLOW CFM 950 1,200 2,000

OUTSIDE AIR FLOW CFM 90 140 0

NOTES 1 1 1

NOTES:

1 PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT/HUMIDISTAT WITH C02 MONITOR

D F

A L

L R

E P

O R

T S

P

LA

N

S

S P

E C

IF

IC

A T

IO

N

S

C O

M P

U T

E R

F

IL

E S

F

IE

LD

D A

T A

N

O T

E S

O

T H

E R

D O

C U

M E

N T

S

IN

S

T R

U M

E N

T S

P R

E P

A R

E D

B Y

T H

E D

E S

IG

N

P R

O F

E S

S

IO

N A

L A

S

IN

S T

R U

M E

N T

S O

F S

E R

V

IC

E S

H A

LL

R

E M

A

IN

T H

E P

R O

P E

R T

Y O

F T

H E

D E

S

IG

N P

R O

F E

S S

IO

N

A L.

T H

E D

E S

IG

N

P R

O F

E S

S

IO

N A

L S

H A

LL

R

E T

A

IN

A

LL

C O

M M

O N

L A

W

S T

A T

U T

O R

Y

O T

H E

R R

E S

E R

V E

D R

IG

H

T S

IN

C

LU

D

IN

G T

H E

C O

P Y

R

IG

H T

T H

E R

E T

O

U S

E O

F T

H E

S E

D O

C U

M E

N T

S F

O R

A N

Y P

U R

P O

S E

O R

P R

O

JE

C T

O T

H E

R T

H A

N T

H E

P R

O

JE

C T

W H

IC

H

I S

S U

B

JE

C T

O F

T H

E A

G R

E E

M E

N T

IS

U

N L

A W

F U

L.

Florida Registry #2485

SEAL

Matthew R. Thoele, P.E #75448

DESIGN PHASE:

114 EAST 5TH AVENUE TALLAHASSEE, FL

32303 PHONE 850.224.7922

www.H2Engineering.com

H2E PROJECT No. 24024

THIS DOCUMENT IS THE PROPERTY OF H2Engineering

AND IS PREPARED AS AN INSTRUMENT OF SERVICE. ITS

USE, REUSE OR REPRODUCTION, EXCEPT BY WRITTEN

AGREEMENT WITH H2Engineering, IS PROHIBITED.

/1

/2

:2 :4

P

M A u to d e s k D o c s:

-0

G a in e s v ill e R

T S

E a s ts id e B u s F a c ili ty /2

-0

G a in e sv ill e R

T S

E a st s id e B u s

F a ci lit y M

E P

R

.r v t

Project Number: 34-0007

Date: 4/1/2026

Drawn By: KWW

Checked By: MRT

SCHEDULES

LOT 3, INTERSECTION OF S.E.

HAWTHORNE ROAD & S.E. 21ST

STREET

M002

EASTSIDE BUS

TRANSFER FACILITY

100% CONSTRUCTION DOCUMENTS

CITY OF GAINESVILLE DEPARTMENT

OF TRANSPORTATION

T

T

T

T

COMMUNITY MEETING ROOM

OFFICE

BREAK ROOM

MECHANICAL

MECHANICAL CLOSET

JANITOR

TICKETING

RESTROOM

TRAINING

LOBBY

JANITOR

RESTROOM

RESTROOM

OFFICE

TELECOM

RESTROOM

OFFICE CORRIDOR

R.R HALLWAY

STORAGE 1

EF-2

EF-1

EF-3

x8 x1

UC

UC

22x18 x1

16x8

16x8

200 200 200 200 200

6" VTR

6" VTR

UC

NOZZLE DIFFUSER

PRICE ND8 (TYP)

6x8 x8

AP

6x8

4-1-4-12

TYP(4)

AHU-1

AHU-2

R E

F

R E

F

CU-1

CU-2

M101 x1

DSSI-1

DSSO-1

ROUTE CONDENSATE TO EXTERIOR.

DISCHARGE TO SPLASHBLOCK.

REF

C

ROUTE CONDENSATE

LINES OUTSIDE OF

BUILDING.

DISCHARGE TO

SPLASH BLOCK

C

C

ROUTE CONDENSATE TO

EXTERIOR. DISCHARGE

TO SPLASHBLOCK.

RETURN PLENUM

BEHIND WALL

AP

6" VTR

PRICE 18X14

730-RAS LOUVERED

GRILLES (TYP. 3)

CU-3

CU-4

(DOAS)

AHU-4

(DOAS)

AHU-3

REF

x1 x8

M101

OA-2

OA-1

GV-1 -

BAROMETRIC DAMPER

ON ROOF

12x12

6x

12x12

UNIT MOUNTED AT 6'

HEIGHT ON WALL. ADHERE

TO MANUFACTURER'S

WALL CLEARANCE.

C

ROUTE CONDENSATE

LINES OUTSIDE OF

BUILDING. DISCHARGE

TO SPLASH BLOCK

REF

EHV-901D

EXTERIOR LOUVER

12X6 EXHAUST

LOUVER INTO

DUCTING TO EF-5

12X6 EXHAUST

LOUVER INTO

DUCTING TO EF-5

EF-4

x6 x6

10x10

GV-1

x1

FIRST FLOOR

0"

T.O.W. LOWER

10' - 0"

AHU-4

(DOAS)

AHU-3

18x22 SA

OA-2

x1 x1

FIRST FLOOR

0"

T.O.W. LOWER

10' - 0"

AHU-1AHU-2

x8

R A x8

S A x1

O

A

REF

C

ROUTE

CONDENSATE

TO EXTERIOR

OA-1

x1

TRUE

A L

L R

E P

O R

T S

P

LA

N

S

S P

E C

IF

IC

A T

IO

N

S

C O

M P

U T

E R

F

IL

E S

F

IE

LD

D A

T A

N

O T

E S

O

T H

E R

D O

C U

M E

N T

S

IN

S

T R

U M

E N

T S

P R

E P

A R

E D

B Y

T H

E D

E S

IG

N

P R

O F

E S

S

IO

N A

L A

S

IN

S T

R U

M E

N T

S O

F S

E R

V

IC

E S

H A

LL

R

E M

A

IN

T H

E P

R O

P E

R T

Y O

F T

H E

D E

S

IG

N P

R O

F E

S S

IO

N

A L.

T H

E D

E S

IG

N

P R

O F

E S

S

IO

N A

L S

H A

LL

R

E T

A

IN

A

LL

C O

M M

O N

L A

W

S T

A T

U T

O R

Y

O T

H E

R R

E S

E R

V E

D R

IG

H

T S

IN

C

LU

D

IN

G T

H E

C O

P Y

R

IG

H T

T H

E R

E T

O

U S

E O

F T

H E

S E

D O

C U

M E

N T

S F

O R

A N

Y P

U R

P O

S E

O R

P R

O

JE

C T

O T

H E

R T

H A

N T

H E

P R

O

JE

C T

W H

IC

H

I S

S U

B

JE

C T

O F

T H

E A

G R

E E

M E

N T

IS

U

N L

A W

F U

L.

Florida Registry #2485

SEAL

Matthew R. Thoele, P.E #75448

DESIGN PHASE:

114 EAST 5TH AVENUE TALLAHASSEE, FL

32303 PHONE 850.224.7922

www.H2Engineering.com

H2E PROJECT No. 24024

THIS DOCUMENT IS THE PROPERTY OF H2Engineering

AND IS PREPARED AS AN INSTRUMENT OF SERVICE. ITS

USE, REUSE OR REPRODUCTION, EXCEPT BY WRITTEN

AGREEMENT WITH H2Engineering, IS PROHIBITED.

/1

/2

:2 :5

P

M A u to d e s k D o c s:

-0

G a in e s v ill e R

T S

E a s ts id e B u s F a c ili ty /2

-0

G a in e sv ill e R

T S

E a st s id e B u s

F a ci lit y M

E P

R

.r v t

Project Number: 34-0007

Date: 4/1/2026

Drawn By: KWW

Checked By: MRT

FLOOR PLAN - HVAC

LOT 3, INTERSECTION OF S.E.

HAWTHORNE ROAD & S.E. 21ST

STREET

M101

EASTSIDE BUS

TRANSFER FACILITY

100% CONSTRUCTION DOCUMENTS

CITY OF GAINESVILLE DEPARTMENT

OF TRANSPORTATION

FLOOR PLAN - HVAC

SCALE: 3/16" = 1'-0"M101

1/4" = 1'-0"M101

2 MECHANICAL CLOSET

1/4" = 1'-0"M101

3 MECHANICAL ROOM

GENERAL NOTES

1. PLENUM RETURN DETAIL. SEE DETAIL C/M502

90° MIN

SECURE FLEXIBLE DUCT SUPPORT

ELBOW TO FLEXIBLE DUCT WITH

NYLON CABLE TIES ON BOTH ENDS

DRAW BAND WITH CABLE SUPPORT

ATTACHED TO STRUCTURE (NOTE 1)

STAINLESS STEEL DRAW BAND

(1/2" MIN. WIDTH). FORM AIRTIGHT

SEAL WITH FABRIC AND MASTIC

SEALANT. (NOTES 3 & 4)

INSULATION (NOTE 2)

CEILING TILE

CEILING GRID

SUPPLY DIFFUSER

PROVIDE FLEXIBLE DUCT

ELBOW SUPPORT TO FORM 90°

DEGREE ELBOW (NOTE 5)

BALANCING DAMPER - LOCATE

AT BRANCH TAKE-OFF

STAINLESS STEEL DRAW BAND

(1/2" MIN. WIDTH). FORM AIRTIGHT

SEAL WITH FABRIC AND MASTIC

SEALANT.

FLEXIBLE DUCT (SAME AS DIFFUSER NECK

SIZE). MIN LENGTH 3'-0" / MAX LENGTH = 5'-0"

FLEXIBLE DUCT CONNECTION TO SUPPLY DIFFUSERG

R

NOTES:

1. FLEXIBLE DUCT SHALL NOT HAVE MORE THAN 1/2" SAG PER FOOT.

2. PROVIDE INSULATION ON BACK OF DIFFUSERS (SEE SPECIFICATIONS). SEAL VAPOR TIGHT WITH FABRIC AND MASTIC.

3. PULL INNER LINER OF FLEXIBLE DUCT OVER DIFFUSER COLLAR AND SECURE WITH DRAW BAND.

4. SECURE FLEXIBLE DUCT INSULATION AND OUTER JACKET WITH DRAW BAND.

5. MAINTAIN MINIMUM RADIUS (R) OF 1.5 TIMES THE DUCT DIAMETER.

AIR FLOW

!M245

REF

REF

C

VERTICAL AHU ON RA STAND/PLENUM

DUCT SMOKE DETECTOR (TYPICAL FOR ALL

AIR HANDLING UNITS OF 2000 CFM OR

GREATER AND WHEN INDICATED ON PLANS)

SUPPLY AIR DUCT

RETURN AIR DUCT

OUTSIDE AIR DUCT

MANUAL BALANCING DAMPER

FLEX. DUCT CONNECTION (TYP.)

REFRIGERANT PIPING.

PRIMARY CONDENSATE DRAIN.

FILTER (DO NOT BLOCK ACCESS)

PROVIDE CONTINUOUS STRIP OF 1/4" THICK

NEOPRENE BEARING PAD (MASON INDUSTRIES

BBP OR APPROVED EQUAL) BETWEEN FLANGE

OF PLENUM AND AIR HANDLING UNIT.

SHEET METAL RA PLENUM WITH EXTERNAL

DUCTBOARD INSULATION (SIDES AND

BOTTOM), SAME SIZE AS OPENING ON UNIT.

1 1/2" X 1 1/2" X 3/16" GALV. STEEL ANGLE

STAND (ALL WELDED CONSTRUCTION).

HEIGHT OF PLENUM - 24" OR AS REQUIRED

AUXILIARY DRAIN PAN

4"x4"x1" THICK NEOPRENE/CORK PAD

SECURE TO ANGLE FRAME (TYP.)

AIR HANDLING UNIT

MANUAL BALANCING DAMPER

NOTE:

1. PROVIDE A FLOAT SWITCH IN THE AUXILIARY DRAIN PAN INTERLOCKED WITH AHU FAN.

!M227.5

RECTANGULAR DUCT

TYPICAL DUCT TAKE-OFF FITTINGSD

L 45

C

12 x 6

12 x 6

16 x 6.75

D

8.5

8.5

10 9.5

18 x 8.5

20 x 9.5

24 x 12

10.5

10.5

DIMENSIONS BASED ON CROWN PRODUCTS CO., INC.

NO FIRE

DAMPER

NOTE 4

NOTE 3

NOTE 2

ROUND DUCT

WALL TO

STRUCTURE

D

(DIAMETER)

NOTE 1

W x H

(W=WIDTH, H=HEIGHT)

A x B TRUNK DUCT

(A=WIDTH, B=HEIGHT) E

(NOTE 5)

WxH

(NOTE 5)

TRUNK DUCT

HEIGHT (B MIN.) WITH FIRE

DAMPER

L = W/4 (4"MIN.)

H = B-2 (MAX.)

C = L+4 (WITH FIRE DAMPER)

C = L+2 (WITHOUT FIRE DAMPER)

NOTES:

1. 45° ENTRY.

2. 1" WIDE FLANGE WITH GASKET SEAL AROUND ENTIRE PERIMETER.

3. PROVIDE MANUAL BALANCING DAMPER. OPERATOR SHALL PENETRATE INSULATION.

4. USE ROUND TYPE TAKE-OFF FOR SUPPLY AIR TO NOT MORE THAN ONE TERMINAL.

5. USE ROUND TYPE TAKE-OFF FOR SUPPLY AIR TO NOT MORE THAN ONE TERMINAL.

DIAMETER, PROVIDE TRANSITION FITTING OF EQUIVALENT AREA TO THE RUNOUT DUCT.

WALL TO

STRUCTURE

C

M

IN

E

(W=WIDTH, H=HEIGHT)

C

M

IN

NOTE 1

W x H

NOTE 2

NOTE 3

!M182

!M170.3

RETURN OR EXHAUST

GRILLE. SEE SCHEDULE OR

PLAN FOR REQUIRED SIZE.

CEILING

TOP ENTRY

6" 1"

PLENUM FULL SIZE

OF GRILLE

RETURN OR EXHAUST

GRILLE. SEE SCHEDULE OR

PLAN FOR REQUIRED SIZE.

CEILING

SIDE ENTRY

DUCT

PLENUM FULL SIZE OF GRILLE

DUCT

NOTES:

1. INSTALL BLADES OF GRILLE SO

SIGHT LINE INTO PLENUM IS

OBSCURED FROM ROOM.

2. PROVIDE APPROPRIATE MOUNTING

HARDWARE FOR GRILLE TO

ACCOMMODATE CEILING TYPE.

1-INCH 1.5 PCF DUCT LINER

1-INCH 1.5 PCF DUCT LINER

8"

2"

PLENUM FULL

SIZE OF GRILLE

RETURN OR EXHAUST

GRILLE. SEE SCHEDULE OR

PLAN FOR REQUIRED SIZE.

CEILING

PLENUM RETURN GRILLES

1-INCH 1.5 PCF DUCT LINER

OPENING: 10" MIN.

x WIDTH OF GRILLE

1"

H

ELECTRIC HEAT SECTION

(WHERE INDICATED IN SCHEDULE)

DUCT SIZE + 25%

METAL SCREEN FRAME

ANGLE IRON REINFORCING

SCREEN

BOLTS

STANDARD DUCT CONSTRUCTION

SEAMS WATERTIGHT

PROVIDE ANGLE

IRON SUPPORT LEGS

WHERE REQUIRED

BACKDRAFT

DAMPER

CURB

SPECIFIED

DUCT SIZE

FLASHING

ROOFING

18" MINIMUM

1/2" SCREEN

ANGLE RIVETED OR SPOT

WELDED AS REQUIRED

CANT

!M164

AIR

FLOW

FAN

STRUCTURE

BACKDRAFT DAMPER

DUCTWORK

NOTES:

1. INSTALL TO ALLOW ACCESS FOR MAINTENANCE.

2. PROVIDE DIRECT DRIVE FAN WHERE SCHEDULED.

SPRING TYPE VIBRATION

ISOLATING HANGER (TYP.)

FLEXIBLE CONNECTION (TYP.)

HOOD WITH PITCHED ROOF

PROVIDE BIRD SCREEN

APPLY FOAM RUBBER

GASKET TO UNDERSIDE

OF CURB CAP.

PRE-FABRICATED ROOF

CURB.

NOTES:

1. SECURE HOOD TO ROOF CURB WITH SHEET

METAL SCREWS @ 12" O.C. ALL AROUND.

2. SECURE CURB TO ROOF WITH SHEET METAL

SCREWS, LAG BOLTS OR OTHER METHOD

CONSISTENT WITH ROOF CONSTRUCTION.

3. FOLLOW MANUFACTURERS INSTALLATION

REQUIREMENTS.

FINISHED ROOF

P.T. WOOD NAILER

AIR OUTLET

FRONT GRILLE

FRONT PANEL

C R

E F

CEILING

SHUTOFF VALVES

ROUTE CONDENSATE TO LOCATION

SHOWN ON PLANS

CEILING

W A

LL

3 1/2" MIN.

2" MIN.

4 3/4" MIN.

1 1/4" MIN.

CLEARANCE

R E

F

PIPE CONNECTION HOLE

CONDENSATE DRAIN, LIQUID

AND GAS REFRIGERANT

GALVANIZED STEEL DRYWALL

TAPING BEAD FLANGE

DRYWALL

METAL STUD

NOTES:

1. ACCESS DOOR SHALL BE NOMINAL 24"x24" UNLESS NOTED OTHERWISE.

2. LOCATE DOOR IN CEILING OR WALL TO ALLOW UNOBSTRUCTED ACCESS

TO EQUIPMENT, DAMPERS, ETC. AND NOT IN CONFLICT WITH LIGHTS,

DIFFUSERS, SPRINKLERS, ETC.

3. ATTACH FRAME OF ACCESS PANEL TO CEILING OR WALL FRAMED

OPENING ACCORDING TO MANUFACTURER'S RECOMMENDATIONS.

PROVIDE:

1. CONCEALED HINGE WITH REMOVABLE DOOR PANEL.

2. EXTRUDED ALUMINUM DOOR AND FRAME CONSTRUCTION.

3. REVERSIBLE DOOR PANEL ACCOMMODATES EITHER 5/8" OR 1/2" DRYWALL

4. SAFETY CHAIN FOR SIZES OVER 12"x12".

5. SCREWDRIVER OPERATED CAM LATCH.

CONCEALED HINGE SUPPLIED WITH 5/8"

DRYWALL INSTALLED

IN DOOR PANEL.

SCREWDRIVER OPERATED CAM

LATCHES

WALL OR CEILING OPENING

NOMINAL SIZE + 0.20"

RECESSED EQUIPMENT ACCESS PANEL - DRYWALL FACE

!M78.2 !M72.3

J

RETURN OR EXHAUST CEILING GRILLEE

DUCTLESS - WALL MOUNTED INDOOR UNITF

RECTANGULAR GOOSENECKA

IN-LINE FANB

GRAVITY ROOF VENTILATORC

!M121.3

!M103.1

A L

L R

E P

O R

T S

P

LA

N

S

S P

E C

IF

IC

A T

IO

N

S

C O

M P

U T

E R

F

IL

E S

F

IE

LD

D A

T A

N

O T

E S

O

T H

E R

D O

C U

M E

N T

S

IN

S

T R

U M

E N

T S

P R

E P

A R

E D

B Y

T H

E D

E S

IG

N

P R

O F

E S

S

IO

N A

L A

S

IN

S T

R U

M E

N T

S O

F S

E R

V

IC

E S

H A

LL

R

E M

A

IN

T H

E P

R O

P E

R T

Y O

F T

H E

D E

S

IG

N P

R O

F E

S S

IO

N

A L.

T H

E D

E S

IG

N

P R

O F

E S

S

IO

N A

L S

H A

LL

R

E T

A

IN

A

LL

C O

M M

O N

L A

W

S T

A T

U T

O R

Y

O T

H E

R R

E S

E R

V E

D R

IG

H

T S

IN

C

LU

D

IN

G T

H E

C O

P Y

R

IG

H T

T H

E R

E T

O

U S

E O

F T

H E

S E

D O

C U

M E

N T

S F

O R

A N

Y P

U R

P O

S E

O R

P R

O

JE

C T

O T

H E

R T

H A

N T

H E

P R

O

JE

C T

W H

IC

H

I S

S U

B

JE

C T

O F

T H

E A

G R

E E

M E

N T

IS

U

N L

A W

F U

L.

Florida Registry #2485

SEAL

Matthew R. Thoele, P.E #75448

DESIGN PHASE:

114 EAST 5TH AVENUE TALLAHASSEE, FL

32303 PHONE 850.224.7922

www.H2Engineering.com

H2E PROJECT No. 24024

THIS DOCUMENT IS THE PROPERTY OF H2Engineering

AND IS PREPARED AS AN INSTRUMENT OF SERVICE. ITS

USE, REUSE OR REPRODUCTION, EXCEPT BY WRITTEN

AGREEMENT WITH H2Engineering, IS PROHIBITED.

/1

/2

:2 :5

P

M A u to d e s k D o c s:

-0

G a in e s v ill e R

T S

E a s ts id e B u s F a c ili ty /2

-0

G a in e sv ill e R

T S

E a st s id e B u s

F a ci lit y M

E P

R

.r v t

Project Number: 34-0007

Date: 4/1/2026

Drawn By: KWW

Checked By: MRT

DETAILS

LOT 3, INTERSECTION OF S.E.

HAWTHORNE ROAD & S.E. 21ST

STREET

M501

EASTSIDE BUS

TRANSFER FACILITY

100% CONSTRUCTION DOCUMENTS

CITY OF GAINESVILLE DEPARTMENT

2"

4"

NEOPRENE RUBBER

WAFFLE IS

OLATION PAD

EQUIPMENT

LIFTING HOLE6" M

IN.

(TYPICAL ALL

SIDES)

CONCRETE SLAB

EQUIPMENT TIE-DOWN AND ISOLATION

CONCRETE SLAB -

DIMENSIONS AS REQUIRED

(3000 PSI @ 28 DAYS)

GRADEGRADE

#4 @ 12"

EACH WAY

SLAB WITHOUT FOOTING

!M45

9" M

IN

4"

NOTES:

1. USE WHERE OBSTRUCTION PREVENTS NORMAL

FLEX DUCT CONNECTION TO CEILING DIFFUSER.

2. INSULATE ALL DUCTWORK AS SPECIFIED.

OBSTRUCTING DUCT

CEILING

RECT./ROUND

TRANSITION

4" OVERHANG, 3 SIDES

CEILING DIFFUSER

MAX. 10"∅

NECK

FLEX DUCT

PLENUM

!M29

CONCRETE EQUIPMENT SLAB AND TIE-DOWNB

CEILING RETURN PLENUMC

CEILING EXHAUST FAND

FLEXIBLE CONNECTOR

EXHAUST DUCT

BACKDRAFT DAMPER

CEILING EXHAUST FAN

MOUNTING BRACKET (NOTE 1)

FRAMED OPENING IN STUDS

GYP. BOARD CEILING

REMOVABLE ALUMINUM GRILLE

NOTES:

1. SUPPORT CEILING FAN LOCATED ABOVE LAY-IN CEILING FROM

THE BUILDING STRUCTURE, INDEPENDENT OF CEILING.

FRONT VIEW SIDE VIEW

CEILING EXHAUST FAN

DUCTLESS SPLIT SYSTEM

CONDENSING UNIT

POWDER COATED WALL MOUNT BRACKET

RATED FOR 500 LBS. AIRTEC MODEL

WBB500 OR APPROVED EQUAL.

PROVIDE MANUFACTURER'S

MINIMUM CLEARANCE

AIR FLOW

S E

E P

LA

N

S F

O R

M

O U

N T

IN

G

H E

IG

H

T

REFRIGERANT PIPING

DUCTLESS SPLIT SYSTEM - CONDENSING UNITA

!M72.2

A L

L R

E P

O R

T S

P

LA

N

S

S P

E C

IF

IC

A T

IO

N

S

C O

M P

U T

E R

F

IL

E S

F

IE

LD

D A

T A

N

O T

E S

O

T H

E R

D O

C U

M E

N T

S

IN

S

T R

U M

E N

T S

P R

E P

A R

E D

B Y

T H

E D

E S

IG

N

P R

O F

E S

S

IO

N A

L A

S

IN

S T

R U

M E

N T

S O

F S

E R

V

IC

E S

H A

LL

R

E M

A

IN

T H

E P

R O

P E

R T

Y O

F T

H E

D E

S

IG

N P

R O

F E

S S

IO

N

A L.

T H

E D

E S

IG

N

P R

O F

E S

S

IO

N A

L S

H A

LL

R

E T

A

IN

A

LL

C O

M M

O N

L A

W

S T

A T

U T

O R

Y

O T

H E

R R

E S

E R

V E

D R

IG

H

T S

IN

C

LU

D

IN

G T

H E

C O

P Y

R

IG

H T

T H

E R

E T

O

U S

E O

F T

H E

S E

D O

C U

M E

N T

S F

O R

A N

Y P

U R

P O

S E

O R

P R

O

JE

C T

O T

H E

R T

H A

N T

H E

P R

O

JE

C T

W H

IC

H

I S

S U

B

JE

C T

O F

T H

E A

G R

E E

M E

N T

IS

U

N L

A W

F U

L.

Florida Registry #2485

SEAL

Matthew R. Thoele, P.E #75448

DESIGN PHASE:

114 EAST 5TH AVENUE TALLAHASSEE, FL

32303 PHONE 850.224.7922

www.H2Engineering.com

H2E PROJECT No. 24024

THIS DOCUMENT IS THE PROPERTY OF H2Engineering

AND IS PREPARED AS AN INSTRUMENT OF SERVICE. ITS

USE, REUSE OR REPRODUCTION, EXCEPT BY WRITTEN

AGREEMENT WITH H2Engineering, IS PROHIBITED.

/1

/2

:2 :5

P

M A u to d e s k D o c s:

-0

G a in e s v ill e R

T S

E a s ts id e B u s F a c ili ty /2

-0

G a in e sv ill e R

T S

E a st s id e B u s

F a ci lit y M

E P

R

.r v t

Project Number: 34-0007

Date: 4/1/2026

Drawn By: KWW

Checked By: MRT

DETAILS

LOT 3, INTERSECTION OF S.E.

HAWTHORNE ROAD & S.E. 21ST

STREET

M502

EASTSIDE BUS

TRANSFER FACILITY

100% CONSTRUCTION DOCUMENTS

CITY OF GAINESVILLE DEPARTMENT

LIGHTING FIXTURE SCHEDULE

GENERAL NOTES:

1.) CONTRACTOR SHALL COORDINATE FIXTURE TYPE WITH ARCHITECTURAL FINISH SCHEDULE(S). ARCHITECT SHALL CONFIRM TRIMS AND FINISHES FOR ALL FIXTURES.

2.) LIGHT FIXTURES DEEMED EQUAL TO THOSE SPECIFIED SHALL BE SUBMITTED FOR APPROVAL IN ACCORDANCE WITH SPECIFICATIONS.

3.) PROVIDE MOUNTING TRIM REQUIRED FOR CEILING TYPE INSTALLED.

TYPE CATALOG NUMBER

LAMP

VOLTAGE DESCRIPTION

MANUFACTURER (OR

EQUAL) POWER TYPE

LUMEN

OUTPUT CRI

COLOR

TEMPERATURE

LF-1 ELITE LIGHTING HH4-LED-3000L-DIM10-120-VWD-40K-90 32W LED 3000 90 4000K 120V 4" ARCHITECTURAL LED DOWNLIGHT WITH VERY WIDE DISTRIBUTION. 0-10V

DIMMING. UGR < 19

LF-2 ELITE LIGHTING HH4-LED-3000L-DIM10-120-VWD-40K-90-HH4-4501 32W LED 3000 90 4000K 120V 4" ARCHITECTURAL HIGH LUMEN LED DOWNLIGHT WITH VERY WIDE

DISTRIBUTION. 0-10V DIMMING. WET LOCATION LISTED. UGR < 19

LF-3 ELITE LIGHTING HH6-LED-2000L-DIM10-120-VWD-40K-90-HH6-6501 20W LED 2000 90 4000K 120V 6" ARCHITECTURAL HIGH LUMEN LED DOWNLIGHT WITH VERY WIDE

DISTRIBUTION. 0-10V DIMMING. WET LOCATION LISTED. UGR < 19

LF-4 ELITE LIGHTING 11.7 W/FT LED 1000 LM/FT 90 4000K 120V

LF-5 KLUS LIGHTING B-FC-40-1275/2-24-8FT-SUSPENDED-CABLE36 8.78 W/FT LED 893 LM/FT 90 4000K 120V 1" W X 8'L SUSPENDED LINEAR FIXTURE WITH FROSTED ACRYLIC LENS AND

BLACK FINISH. COORDINATE WITH ARCHITECTURAL CEILING PLAN FOR EXACT

HEIGHT OF SUSPENDED FIXTURE.

LF-6 ELITE LIGHTING 4-OC1-LED-5000L-DIM10-MVOLT-40K-85-V3 31W LED 5000 90 4000K 120V 4' ARCHITECTURAL SURFACE/SUSPENDED STRIP FIXTURE. SURFACE

MOUNTED OR SUSPENDED. WHERE SUSPENDED MOUNT 10' AFF.

LF-7 ELITE LIGHTING 22-EDGE-LED-2000L-DIM10-120-40K-85 23W LED 2000 90 4000K 120-277V 2' x 2' ARCHITECTURAL VOLUMETRIC RECESSED LED TROFFER. UGR < 17

LF-8 ELITE LIGHTING OVLS-LED-30-1900L-DIMTR-120V-4000K-90 27W LED 1900 90 4000K 120V 30" INTERIOR SQUARE LENS LINEAR VANITY LIGHT WITH ACRYLIC DIFFUSER.

LF-9 ORACLE LIGHTING OFL-R-102-LED-4500L-DIM10-MVOLT-40K-FL-BZ-LED-STAKE 30W LED 4500 80 4000K 120V EXTERIOR FLOOD LIGHT

LF-10 CGF DESIGN E804-LED36-CT4-UNV-BK-0-10D1 36W LED 3700 80 4000K 120-277V 4' LED LINEAR LED FIXTURE, IK10 RATED. WET LOCATION RATED.

LF-11 ELITE LIGHTING OWP-FC-209-LED-6000L-DIM10-120-347V-40K-BZ 44W LED 6000 80 4000K 120-347V LED FULL CUT OFF LARGE WALL PACK WITH POLYCARBONATE DIFFUSER.

0-10V DIMMING. WET LOCATION LISTED.

LF-12 BLE-G-BSL-100-G15-NA-LED23-4000K-NA-FST-277 23W LED 2000 80 4000K 120-277V BULLET GOOSENECK LED SIGN LIGHT. 0-10V DIMMING. WET LOCATION LISTED.

LF-13 HE WILLIAMS 1SF-3-L18/840-AF12125-DIM-UNV 16W LED 1800 80 4000K 120-277V 3' SURFACE MOUNT UNDERCABINET LED FIXTURE. DIE FORMED HOUSING.

0-10V DIMMING.

E ELITE LIGHTING ELX-LED-618-G/R-1-CL-W LED CLEAR, EDGE LIT LED EXIT SIGN WITH GREEN LETTERING

RESPONSIBILITY MATRIX FOR TELECOMMUNICATIONS

AREA OF WORK / CATEGORY OF EQUIPMENT FURNISHED BY INSTALLED BY

NOTE:

THIS MATRIX IS INTENDED TO INDICATE A GENERAL LISTING OF THE WORK AND MATERIALS TO BE

FURNISHED AND INSTALLED BY THE VARIOUS TRADES FOR COORDINATION PURPOSES ONLY. IT IS NOT INTENDED TO TO BE ALL INCLUSIVE. EACH TRADE IS RESPONSIBLE FOR FURNISHING AND

INSTALLING THEIR RESPECTIVE COMPLETE AND WORKING SYSTEM. REFER TO DRAWINGS AND

SPECIFICATIONS FOR THE EXTENT OF WORK

INVOLVED.

O W

N E

R

E

LE

C T

R

IC

A L

C O

N T

R A

C T

O R

T E

LE

C

O M

C O

N T

R A

C T

O R

A /V

C O

N T

R A

C T

O R

S E

C U

R

IT

Y C

O N

T R

A C

T O

R

F

IR

E A

LA

R

M C

O N

T R

A C

T O

R

O W

N E

R

E

LE

C T

R

IC

A L

C O

N T

R A

C T

O R

T E

LE

C

O M

C O

N T

R A

C T

O R

A /V

C O

N T

R A

C T

O R

S E

C U

R

IT

Y C

O N

T R

A C

T O

R

F

IR

E A

LA

R

M C

O N

T R

A C

T O

R

COMMENTS

TELECOMMUNICATIONS

CROSS CONNECTIONS AT THE DEMARCATION POINT X X

DIAL TONE SERVICES AND ASSOCIATED RACKS AND EQUIPMENT X X

NETWORK ROUTER X X

NETWORK ACCESS & DISTRIBUTION SWITCHES X X

NETWORK SERVERS, OPERATING SYSTEM SOFTWARE X X

WORKSTATION COMPUTERS, OPERATING SYSTEM SOFTWARE, APPLICATION SOFTWARE, PRINTERS, COPIERS, CUSTOMER PREMISE EQUIPMENT

X X

COPPER PATCH CORDS AT WORKSTATION OUTLETS X X

WIRELESS ACCESS POINTS X X

COPPER PATCH CORDS AT PATCH PANELS TO ACCESS SWITCHES X X

ABOVEGROUND AND UNDERGROUND RACEWAY SYSTEM; INCLUDING HAND HOLES, PULL BOXES, CONDUITS, CABLE TRAYS, BACK BOXES, SLEEVES THRU WALLS AND FLOORS

X X

FLOOR BOXES, WALL BOXES AND SERVICE FITTINGS INCLUDING ELECTRICAL DEVICES AND EMPTY PLATES TO

ACCEPT TELECOMMUNICATION MODULES.

X X

COMMUNICATION BACKBOARDS X X

GROUNDING BUSBARS AND BOND TO BUILDING GROUND X X

RACEWAY SYSTEM GROUNDING; TO ASSURE CONTINUOUS GROUND THROUGHOUT X X

EQUIPMENT RACKS AND RACK MOUNTED POWER DISTRIBUTION UNITS (PDU) X X COORDINATE PDU WITH UPS TYPE(S)

RACK MOUNTED UNINTERRUPTABLE POWER SUPPLIES (UPS) X X

POPULATED FIBER AND COPPER PATCH PANELS X X

LADDER RACK IN TELECOMMUNICATION ROOMS X X

J-HOOKS PATHWAY FROM WORKSTATION STUB-UP ABOVE CEILING TO CABLE TRAY, TELECOMMUNICATION

ROOM, OR CONDUIT PATHWAY PROVIDED BY ELECTRICAL CONTRACTOR

X X

BONDING OF RACKS, CABINETS, LADDER RACK AND OTHER TELECOM CONTRACTOR PROVIDED EQUIPMENT TO

TELECOM GROUND BUS BAR

X X

WORKSTATION OUTLET FACEPLATES AND MODULAR PLUGS X X

HORIZONTAL CABLE BETWEEN WORKSTATION MODULAR PLUG AND PATCH PANEL INCLUDING TERMINATIONS X X

BACKBONE CABLE AND/OR PATCH CORDS BETWEEN EQUIPMENT ROOM DISTRIBUTION SWITCHES OR PATCH

PANELS INCLUDING TERMINATIONS

X X

BACKBONE CABLE BETWEEN SERVICE PROVIDER DEMARC AND DISTRIBUTION SWITCHES OR PATCH PANELS

INCLUDING TERMINATIONS

X X

SURGE PROTECTION DEVICES FOR COPPER CABLING TO EXTERIOR DEVICES X X CAMERAS ONLY

MEDIA FIBER TO COPPER CONVERTERS X X

FIRESTOPPING OF SLEEVES AFTER NETWORK CABLES ARE PULLED X X

IDENTIFICATION AND LABELING X X

PERMANENT LINK TESTING AND DOCUMENTATION AFTER INSTALLATION X X

RESPONSIBILITY MATRIX FOR AUDIO VISUAL SYSTEMS

AREA OF WORK / CATEGORY OF EQUIPMENT FURNISHED BY INSTALLED BY

NOTE:

THIS MATRIX IS INTENDED TO INDICATE A GENERAL LISTING OF THE WORK AND MATERIALS TO BE FURNISHED AND INSTALLED BY THE VARIOUS TRADES FOR COORDINATION PURPOSES ONLY. IT IS

NOT INTENDED TO TO BE ALL INCLUSIVE. EACH TRADE IS RESPONSIBLE FOR FURNISHING AND

INSTALLING THEIR RESPECTIVE COMPLETE AND WORKING SYSTEM. REFER TO DRAWINGS AND

SPECIFICATIONS FOR THE EXTENT OF WORK INVOLVED. GENERAL CONTRACTOR IS RESPONSIBLE

FOR CONFIRMING OWNER RESPONSIBILITIES WITH THE OWNER'S IT

DEPARTMENT.

O W

N E

R

E

LE

C T

R

IC

A L

C O

N T

R A

C T

O R

T E

LE

C

O M

C O

N T

R A

C T

O R

O W

N E

R H

IR

E

D A

/V C

O N

T R

A C

T O

R

S E

C U

R

IT

Y C

O N

T R

A C

T O

R

G E

N E

R A

L C

O N

T R

A C

T O

R

O W

N E

R

E

LE

C T

R

IC

A L

C O

N T

R A

C T

O R

T E

LE

C

O M

C O

N T

R A

C T

O R

O W

N E

R H

IR

E

D A

/V C

O N

T R

A C

T O

R

S E

C U

R

IT

Y C

O N

T R

A C

T O

R

G E

N E

R A

L C

O N

T R

A C

T O

R

COMMENTS

AUDIO / VISUAL SYSTEM

RACEWAY SYSTEM; INCLUDING PULL BOXES, CONDUITS, CABLE TRAYS, BACK BOXES, SLEEVES THRU WALLS

AND FLOORS

X X

FLOOR BOXES, WALL BOXES & POKE THROUGHS INCLUDING ELECTRICAL DEVICES AND EMPTY SPACE TO

ACCEPT AUDIO/VISUAL MODULES.

X X

AUDIO / VISUAL SYSTEM INTEGRATION HARDWARE AND SOFTWARE X X

FLAT PANEL DISPLAYS, PROJECTORS, PROJECTOR SCREENS AND MOUNTS X X

AUDIO SYSTEMS ASSOCIATED WITH A/V SYSTEM X X

CAMERAS ASSOCIATED WITH A/V SYSTEM X X

WIRELESS AND WIRED MICROPHONES ASSOCIATED WITH A/V SYSTEM X X

A/V RELATED CABLES AND TERMINATIONS (CAT6, HDMI, COAX, XLR, ETC.) X X

A/V MODULES, FACEPLATES AND JACKS X X

FIRESTOPPING OF SLEEVES AFTER A/V CABLES ARE PULLED X X

IDENTIFICATION AND LABELING X X

PERMANENT LINK TESTING AND DOCUMENTATION AFTER INSTALLATION X X

RESPONSIBILITY MATRIX FOR ELECTRONIC SAFETY AND SECURITY

AREA OF WORK / CATEGORY OF EQUIPMENT FURNISHED BY INSTALLED BY

NOTE:

THIS MATRIX IS INTENDED TO INDICATE A GENERAL LISTING OF THE WORK AND MATERIALS TO BE FURNISHED AND INSTALLED BY THE VARIOUS TRADES FOR COORDINATION PURPOSES ONLY. IT IS

NOT INTENDED TO TO BE ALL INCLUSIVE. EACH TRADE IS RESPONSIBLE FOR FURNISHING AND

INSTALLING THEIR RESPECTIVE COMPLETE AND WORKING SYSTEM. REFER TO DRAWINGS AND

SPECIFICATIONS FOR THE EXTENT OF WORK INVOLVED. GENERAL CONTRACTOR IS RESPONSIBLE

FOR CONFIRMING OWNER RESPONSIBILITIES WITH THE OWNER'S IT

DEPARTMENT.

O W

N E

R

E

LE

C T

R

IC

A L

C O

N T

R A

C T

O R

T E

LE

C

O M

C O

N T

R A

C T

O R

A /V

C O

N T

R A

C T

O R

O W

N E

R H

IR

E

D S

E C

U R

IT

Y

C O

N T

R A

C T

O R

F

IR

E A

LA

R

M C

O N

T R

A C

T O

R

O W

N E

R

E

LE

C T

R

IC

A L

C O

N T

R A

C T

O R

T E

LE

C

O M

C O

N T

R A

C T

O R

A /V

C O

N T

R A

C T

O R

O W

N E

R H

IR

E

D S

E C

U R

IT

Y

C O

N T

R A

C T

O R

F

IR

E A

LA

R

M C

O N

T R

A C

T O

R

COMMENTS

SECURITY SYSTEMS

ACCESS CONTROL SYSTEM INTEGRATION HARDWARE AND SOFTWARE X X

ACCESS CONTROL DEVICES (EXCLUDING DOOR HARDWARE) X X

POWER SUPPLIES FOR ACCESS CONTROL DEVICES X X

VIDEO SURVEILLANCE CAMERAS, NVR, INTEGRATION HARDWARE AND SOFTWARE X X

ABOVEGROUND AND UNDERGROUND RACEWAY SYSTEM; INCLUDING HAND HOLES, PULL BOXES, CONDUITS, CABLE TRAYS, BACK BOXES, SLEEVES THRU WALLS AND FLOORS

X X

SECURITY SYSTEM NETWORK CABLES AND PATCH CORDS X X INCLUDING UPLINK TO SWITCH

MEDIA FIBER TO COPPER CONVERTERS X X

SURGE PROTECTION DEVICES FOR COPPER CABLES TO EXTERIOR MOUNTED SECURITY DEVICES X X

FIRESTOPPING OF SLEEVES AFTER SECURITY CABLES (NON-NETWORK CABLES) ARE PULLED X X

IDENTIFICATION AND LABELING X X

PERMANENT LINK TESTING AND DOCUMENTATION AFTER INSTALLATION X X

RESPONSIBILITY MATRIX FOR FIRE SAFETY AND EMERGENCY COMMUNICATIONS

AREA OF WORK / CATEGORY OF EQUIPMENT FURNISHED BY INSTALLED BY

NOTE:

THIS MATRIX IS INTENDED TO INDICATE A GENERAL LISTING OF THE WORK AND MATERIALS TO BE

FURNISHED AND INSTALLED BY THE VARIOUS TRADES FOR COORDINATION PURPOSES ONLY. IT IS NOT INTENDED TO TO BE ALL INCLUSIVE. EACH TRADE IS RESPONSIBLE FOR FURNISHING AND

INSTALLING THEIR RESPECTIVE COMPLETE AND WORKING SYSTEM. REFER TO DRAWINGS AND

SPECIFICATIONS FOR THE EXTENT OF WORK INVOLVED. GENERAL CONTRACTOR IS RESPONSIBLE

FOR CONFIRMING OWNER RESPONSIBILITIES WITH THE OWNER'S IT

DEPARTMENT. O

W N

E R

E

LE

C T

R

IC

A L

C O

N T

R A

C T

O R

T E

LE

C

O M

C O

N T

R A

C T

O R

A /V

C O

N T

R A

C T

O R

S E

C U

R

IT

Y C

O N

T R

A C

T O

R

F

IR

E A

LA

R

M C

O N

T R

A C

T O

R

O W

N E

R

E

LE

C T

R

IC

A L

C O

N T

R A

C T

O R

T E

LE

C

O M

C O

N T

R A

C T

O R

A /V

C O

N T

R A

C T

O R

S E

C U

R

IT

Y C

O N

T R

A C

T O

R

F

IR

E A

LA

R

M C

O N

T R

A C

T O

R

COMMENTS

FIRE ALARM SYSTEM

FIRE ALARM CONTROL PANELS, ANNUNCIATORS, INITIATING DEVICES, NOTIFICATION APPLIANCES X X

UNDERGROUND CONDUITS, BACKBOXES, HAND HOLES, PULL BOXES X X

ABOVEGROUND CONDUITS, CABLE TRAYS, BACK BOXES, SLEEVES THRU WALLS AND FLOORS X X

SURGE PROTECTION DEVICES FOR EXTERIOR COPPER CABLES X X

FIRE STOPPING OF CONDUITS AND SLEEVES X X

IDENTIFICATION AND LABELING X X

PERMANENT LINK TESTING AND DOCUMENTATION AFTER INSTALLATION X X

ELECTRICAL GENERAL NOTES

1. WIRING SHALL BE COPPER, TYPE THHN/THWN-2 IN RACEWAY UNLESS NOTED OTHERWISE. RIGID

ELECTRICAL NON-METALLIC SCHEDULE 40 PVC SHALL BE USED IN SLABS AND BELOW GRADE ; RIGID STEEL CONDUIT (RSC) SHALL BE USED WHERE EXPOSED TO PHYSICAL DAMAGE; ELECTRICAL METALLIC TUBING (EMT) MAY BE USED ELSEWHERE WHERE APPROVED BY N.E.C. AND LOCAL CODES. FLEXIBLE METAL CONDUIT (FMC) SHALL BE STEEL AND SHALL BE USED TO CONNECT MOVEABLE EQUIPMENT AND/OR SUBJECT TO VIBRATION; LIQUID-TIGHT FLEXIBLE METALLIC CONDUIT (LFMC) SHALL BE USED

OUTDOORS OR WHERE SUBJECT TO MOISTURE.

2. CONDUIT SHALL BE STRAPPED IN ACCORDANCE WITH REQUIREMENTS OF N.E.C.

3. CONTRACTOR SHALL BOND AND GROUND SYSTEMS AND EQUIPMENT PER ARTICLE 250 OF N.E.C.

PROVIDE A GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH ARTICLE 250-122 N.E.C. ON ALL

RECEPTACLES AND POWER BRANCH CIRCUITS.

4. LIGHTING FIXTURES SHALL BE SECURELY FASTENED AND SUPPORTED PER N.E.C.

5. THE CONTRACTOR SHALL COORDINATE THE CIRCUIT REQUIREMENTS WITH THE MANUFACTURER OF THE

ACTUAL EQUIPMENT FURNISHED UNDER OTHER DIVISIONS OF WORK. THE CIRCUIT BREAKER, WIRE AND

CONDUIT SHALL BE SIZED AS RECOMMENDED BY THE EQUIPMENT MANUFACTURER.

6. CIRCUIT BREAKERS SHALL BE BOLT-IN TYPE.

7. PROVIDE A LAMINATED PLASTIC NAMEPLATE IDENTIFYING EACH NEW PANELBOARD, MOTOR STARTER

AND DISCONNECT SWITCH. LETTERING SHALL BE 1/2" MINIMUM AND SHALL IDENTIFY EQUIPMENT

SERVED, FEEDER ORIGINATION AND CIRCUIT NUMBER. SECURE NAMEPLATE WITH SCREWS TO

EQUIPMENT TO BE IDENTIFIED. PLASTIC TAPE IS NOT APPROVED.

8. ELECTRICAL CONNECTIONS AND ASSOCIATED ROUGH-IN FOR EQUIPMENT FURNISHED BY OWNER OR

OTHER TRADE CONTRACTORS SHALL BE CONSTRUCTED BY ELECTRICAL CONTRACTOR. VERIFY

CONNECTION SIZE, RATING, AND LOCATION WITH EQUIPMENT PROVIDER PRIOR TO ROUGH-IN.

9. A 120V/20A GFI RECEPTACLE SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND WITHIN 25 FT OF THE HEATING, AIR-CONDITIONING, AND REFRIGERATION

EQUIPMENT. THE OUTLET SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT

DISCONNECTING MEANS.

10. DEVICE MOUNTING HEIGHTS INDICATED SHALL BE TO DEVICE CENTER LINE.

11. EXTERIOR DEVICES SHALL BE WEATHER PROOF ENCLOSURES AND GFI RATED IN ACCORDANCE WITH

N.E.C. INSTALLER REQUIRED TO VERIFY PRIOR TO ORDERING MATERIALS.

12. EACH FEEDER, UNGROUNDED CONDUCTOR, AND GROUNDED CONDUCTOR SHALL BE IDENTIFIED BY

PHASE OR LINE AND SYSTEM AT ALL TERMINATION, CONNECTION, AND SPLICE POINTS.

DUPLEX RECEPTACLE - 120 VOLT, 20 AMP, 3 POLE GROUNDING TYPE, MOUNT

18" AFF WITH GROUND PRONG UP UNLESS NOTED OTHERWISE.

DUPLEX…

This is the start of the file's text. The full file is on GovTribe.