34-0007_-_COG_-_RTS_EBF_-_MEP_100%_Const_Docs_Combined.pdf
PDF 6 MB Posted
- Solicitation number
- RTSX-260049-DS
- Issued by
- Alachua County, Graceville City, Florida
About this file
This document comprises the 100% construction drawings for the Eastside Bus Transfer Facility, a transit facility project in Gainesville, Florida located at the intersection of S.E. Hawthorne Road and S.E. 21st Street. The facility includes mechanical, electrical, and plumbing systems designed to support bus operations and public transit functions. The mechanical systems feature three split-system heat pumps (3-ton, 5-ton configurations) with supplemental heating, a dedicated outdoor air system (DOAS) with cooling and electric heating, ductless split cooling systems, multiple exhaust fans, and gravity ventilators for relief and intake functions. The electrical systems include a 208-volt, three-phase main service with two distribution panels (400-amp and 225-amp capacity), comprehensive lighting throughout interior and exterior spaces with occupancy sensors and dimming controls, emergency lighting with central inverter backup, multiple receptacle configurations with GFCI protection, and provisions for future electric vehicle chargers. The plumbing and HVAC designs comply with the Florida Building Code 2023, ASHRAE standards, NFPA codes, and other applicable regulations. Construction documents indicate coordination requirements among mechanical, electrical, telecommunications, audio-visual, security, and fire alarm contractors, with specific responsibilities outlined in responsibility matrices for each system category.
The design phase documentation, prepared by H2Engineering (Project No. 24024) and dated April 1, 2026, establishes comprehensive installation, maintenance, and operational standards for all building systems. Key requirements include field verification of dimensions and conditions prior to work commencement, contractor responsibility for code compliance without additional owner cost, furnishing of as-built record documents upon completion, and a one-year warranty from the date of final acceptance. The project mandates specialized inspections and testing including duct pressure testing coordinated with local mechanical inspectors, test and balance reporting, and permanent link testing for electrical systems. Critical coordination notes require contractors to verify equipment connections, maintain fire and smoke wall assembly integrity, provide UL-approved drawings for fire-rated penetrations, obtain all necessary permits and connection fees, and maintain a clean construction site. The construction documents serve as binding instruments of service prepared by the design professional and retain all copyright and reserved rights.
View the file
Other files
Show all 45
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MD
1. TRAP AIR CONDITIONING CONDENSATE AND RUN TO SAFEWASTE AT LOCATION SHOWN ON PLANS.
2. INSTALL DUCTWORK, PIPING, ETC. AS HIGH AS POSSIBLE ABOVE CEILING WHILE MAINTAINING
ACCESSIBILITY FOR EQUIPMENT AND DEVICES AS APPROPRIATE.
3. COORDINATE LOCATION OF ALL EQUIPMENT, DUCTWORK AND PIPING INSTALLATIONS WITH ELECTRICAL
TO PROVIDE THE REQUIRED CLEARANCES AROUND ALL ELECTRICAL PANELS, SWITCHGEAR, ETC.
4. INSTALLATION OF EQUIPMENT, DUCTWORK AND PIPING SHALL PROVIDE CONVENIENT ACCESS FOR
REMOVAL OF FILTERS AND FOR MAINTENANCE.
5. DUCT SIZES GIVEN ARE SHEET METAL SIZES.
6. COORDINATE EXACT LOCATIONS OF AIR DISTRIBUTION EQUIPMENT WITH THE CEILING AND THE LIGHTING
LAYOUT.
7. THE CEILING DIFFUSERS SHALL BE 4-WAY THROW UNLESS OTHERWISE NOTED.
8. PROVIDE NEW AIR FILTERS IN EACH UNIT REQUIRING FILTERS WHEN THE PROJECT IS READY FOR TEST
AND BALANCE. DO NOT OPERATE UNITS WITHOUT FILTERS DURING CONSTRUCTION. REPLACE FILTERS
DURING CONSTRUCTION ACCORDING TO FILTER MANUFACTURER'S RECOMMENDATIONS. SEAL ALL
OPEN ENDS OF DUCT WORK DURING CONSTRUCTION.
9. WHEREVER THE DEPTH OF THE TRUNK DUCT IS LESS THAN THE ROUND RUNOUT DUCT DIAMETER, PROVIDE TRANSITION FITTING OF EQUIVALENT AREA TO THE RUNOUT DUCT.
10. PROVIDE FLEXIBLE DUCT CONNECTIONS AT EACH EQUIPMENT CONNECTION.
11. OUTSIDE AIR INTAKES SHALL NOT BE LOCATED ANY CLOSER THAN 15 FEET FROM ANY CHIMNEY OR
EXHAUST OUTLET OR PLUMBING VENT TERMINAL.
12. PROVIDE FIRE DAMPER AT EVERY DUCT PENETRATION OF FIRE RATED CONSTRUCTION, WHETHER
SHOWN ON THE DRAWINGS OR NOT.
13. INSTALL DUCT MOUNTED SMOKE DETECTOR (FURNISHED BY DIV. 29) IN SUPPLY TRUNK DUCT BEFORE
ANY TAKE-OFFS FOR AIR HANDLING UNITS WITH SUPPLY AIR CAPACITY GREATER THAN 2000 CFM AND
WHERE INDICATED ON PLANS.
14. WHERE FIRE DAMPERS ARE REQUIRED, PROVIDE DUCT ACCESS DOORS TO ALLOW RE-LINKING OF DAMPER FUSIBLE LINKS. PROVIDE CEILING/WALL ACCESS PANELS WHERE INSTALLED IN INACCESSIBLE
LOCATIONS; ACCESS PANELS IN RATED CONSTRUCTION SHALL BEAR UL LABEL.
15. WHERE DUCT MOUNTED SMOKE DETECTORS ARE REQUIRED, PROVIDE DUCT ACCESS DOORS TO ALLOW VIEWING AND SERVICING. PROVIDE CEILING/WALL ACCESS PANELS WHERE INSTALLED IN INACCESSIBLE
LOCATIONS; ACCESS PANELS IN RATED CONSTRUCTION SHALL BEAR UL LABEL.
16. WHERE SMOKE DAMPERS OR COMBINATION FIRE/SMOKE DAMPERS ARE REQUIRED, PROVIDE DUCT ACCESS DOORS TO ALLOW RE-LINKING OF DAMPER FUSIBLE LINKS AND TO ALLOW VIEWING AND REMOVAL OF SMOKE DETECTORS. PROVIDE CEILING/WALL ACCESS PANELS WHERE INSTALLED IN
INACCESSIBLE LOCATIONS; ACCESS PANELS IN RATED CONSTRUCTION SHALL BEAR UL LABEL.
17. IT IS RECOMMENDED THAT DUCTWORK BE FABRICATED FROM FIELD MEASUREMENTS TAKEN AS THE
BUILDING STRUCTURE AND SPACE COMPETING SYSTEMS ARE PROGRESSIVELY INSTALLED. THE
DUCTWORK AS SHOWN ON THE CONSTRUCTION DOCUMENTS IS DIAGRAMMATIC AND DOES NOT
NECESSARILY INCLUDE ALL MODIFICATIONS REQUIRED TO AVOID THESE INTERFERENCES. BEFORE
FABRICATING ANY DUCTWORK, CHECK THE PHYSICAL CONDITIONS AT THE JOB SITE AND MAKE
CHANGES IN CROSS SECTIONS, ROUTING, OFFSETS AND SIMILAR ITEMS WHETHER SPECIFICALLY
INDICATED OR NOT. VERIFY THAT SUFFICIENT CLEARANCES ARE AVAILABLE FOR INSTALLING
DUCTWORK, PIPING, LIGHT FIXTURES, CEILING SYSTEMS AND TO PROVIDE EQUIPMENT SERVICE. COSTS REQUIRED TO CHANGE DUCTWORK TO FIT THE SPACE AVAILABLE AND AVOID INTERFERENCES CAUSED
BY SPACE COMPETING SYSTEMS SHALL BE BORNE BY THE CONTRACTOR. NO ADDITIONAL
REMUNERATION WILL BE PAID BY THE OWNER.
18. APPLY EXTERNAL INSULATION TO SINGLE WALL SUPPLY DUCTS, RETURN DUCTS AND OUTSIDE AIR
DUCTS PER SPECIFICATIONS.
19. PROVIDE VOLUME CONTROL DAMPERS IN SIDE TAKE-OFF FITTINGS TO SUPPLY AIR DIFFUSERS AND EXHAUST AIR AND RETURN AIR GRILLES AND AT EACH DUCT BRANCH SERVING TWO OR MORE AIR
TERMINALS, WHETHER SHOWN ON THE DRAWINGS OR NOT.
20. PROVIDE ACCESS PANEL AT EACH LOCATION WHERE A VALVE, DAMPER OR OTHER DEVICE REQUIRING SERVICE IS LOCATED ABOVE AN INACCESSIBLE CEILING OR INSIDE A WALL. ACCESS PANELS IN RATED CONSTRUCTION SHALL BEAR UL LABEL. COORDINATE ACCESS PANEL LOCATION WITH ARCHITECT PRIOR
TO INSTALLATION.
21. PATCH ALL BREAKS, TEARS AND VOIDS IN EXISTING EXTERNAL DUCT INSULATION WITHIN PROJECT AREA.
SEAL INSULATION USING ALUMINUM DUCT TAPE.
22. BEFORE COMMENCING ANY WORK, MEASURE AND RECORD AIR QUANTITIES OF SUPPLY AIR OUTLETS OF EACH AHU SYSTEM AFFECTED BY THIS WORK. UPON COMPLETION OF WORK, BALANCE EACH SYSTEM TO AIR QUANTITIES SHOWN AND TO PREVIOUSLY RECORDED QUANTITIES OF OTHER OUTLETS ON THAT
SYSTEM. ADJUST AHU SUPPLY FAN ACCORDINGLY.
23. COORDINATE ALL DUCT TEST WITNESSING WITH LOCAL MECHANICAL INSPECTOR.
24. PRIOR TO FINAL INSPECTION, PROVIDE CERTIFIED TEST & BALANCE REPORT AND OPERATIONS &
MAINTENANCE MANUALS TO THE OWNER.
25. PROVIDE DUCT ACCESS DOOR AT EACH FLOW MEASURING STATION.
26. DUCT CONSTRUCTION, INCLUDING SHEET METAL THICKNESS, SEAM AND JOINT CONSTRUCTION, REINFORCEMENTS, AND HANGERS AND SUPPORTS, SHALL COMPLY WITH SMACNA'S "HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE DUCT."
27. LOCATIONS OF EXISTING EQUIPMENT ARE BASED ON REFERENCE MATERIALS PROVIDED TO THE
ENGINEER AND CONCEALED ELEMENTS HAVE NOT BEEN VERIFIED. CONTRACTOR SHALL LOCATE
CONCEALED ELEMENTS AND NOTIFY ENGINEER IF VARIANCES BETWEEN THESE DOCUMENTS AND
ACTUAL FIELD CONDITIONS EXIST AND MAY MATERIALLY AFFECT THE DESIGN INTENT.
HVAC NOTESAPPLICABLE CODES
RECTANGULAR SHEET METAL DUCT
AIR DISTRIBUTION
AxB
PIPING AND FITTINGS
C CONDENSATE DRAIN PIPING FROM COOLING COIL PERFORM WORK IN ACCORDANCE WITH THE FOLLOWING CODES AND ANY APPLICABLE STATUTES, ORDINANCES, CODES, AND REGULATIONS OF GOVERNMENTAL AUTHORITIES HAVING JURISDICTION.
1. ASHRAE
a. STANDARD 55 THERMAL ENVIRONMENTAL CONDITIONS FOR HUMAN OCCUPANCY - 2017
b. STANDARD 62.1 VENTILATION STANDARD FOR ACCEPTABLE INDOOR AIR QUALITY - 2019
c. STANDARD 90.1 ENERGY STANDARD FOR BUILDINGS EXCEPT LOW RISE RESIDENTIAL
BUILDINGS - 2019
2. OCCUPATIONAL SAFETY AND HEALTH REGULATIONS (OSHA).
3. NATIONAL FIRE CODES
a. NFPA 1 UNIFORM FIRE CODE - 2021 (FLORIDA EDITION)
b. NFPA 70 NATIONAL ELECTRICAL CODE - 2020
c. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE - 2019
d. NFPA 90A STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATION
SYSTEMS - 2021
e. NFPA 90B STANDARD FOR THE INSTALLATION OF WARM AIR HEATING AND AIR
CONDITIONING SYSTEMS - 2024
f. NFPA 101 LIFE SAFETY CODE - 2021 (FLORIDA EDITION)
4. FLORIDA BUILDING CODE, 2023 EDITION
a. BUILDING CODE
b. ENERGY CONSERVATION CODE
c. MECHANICAL CODE
d. PLUMBING CODE
e. ACCESSIBILITY CODE
5. FLORIDA STATUTES
a. CHAPTER 471 ENGINEERING
b. CHAPTER 533.80 BUILDING CONSTRUCTION STANDARDS; FLORIDA BUILDING CODE -
ENFORCEMENT
6. FLORIDA ADMINISTRATIVE CODE
a. CHAPTER 61G15-34 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE
DESIGN OF MECHANICAL SYSTEMS
b. CHAPTER 69A-3 FIRE PREVENTION - GENERAL PROVISIONS
c. CHAPTER 69A-60 THE FLORIDA FIRE PREVENTION CODE
RESOLVE, IN WRITING, ANY CODE VIOLATION DISCOVERED IN CONTRACT DOCUMENTS WITH THE ENGINEER PRIOR TO BIDDING. AFTER AWARD OF THE CONTRACT, MAKE ANY CORRECTION OR ADDITION NECESSARY
FOR COMPLIANCE WITH APPLICABLE CODES AT NO ADDITIONAL COST TO OWNER.
THE CONTRACTOR SHALL INCLUDE IN THE WORK, WITHOUT EXTRA COST TO THE OWNER, ANY LABOR, MATERIALS, SERVICES, APPARATUS, AND DRAWINGS REQUIRED TO COMPLY WITH ALL APPLICABLE LAWS, ORDINANCES, RULES, AND REGULATIONS.
WHERE THERE IS CONFLICT BETWEEN THE CONTRACT DOCUMENTS AND THE APPLICABLE CODES, THE CODES SHALL GOVERN, EXCEPT WHERE THE REQUIREMENTS OF THE CONTRACT DOCUMENTS ARE MORE
STRINGENT.
REF REFRIGERANT PIPING (ONE LINE REPRESENTS BOTH LIQUID AND GAS LINES)
UNION
FLEXIBLE PIPE CONNECTION
NEW PIPE
BALL VALVE (WITH QUARTER TURN HANDLE)
VALVES
BUTTERFLY VALVE (WITH QUARTER TURN HANDLE)
N.O. N.C.
N.C.N.O.
QUARTER TURN LEVER
HANDWHEEL
VALVE ACTUATORS:
M ELECTRIC MOTOR
FLEXIBLE RUNOUT DUCT
ROUND OR RECTANGULAR TAKE-OFF FITTING WITH
BALANCING DAMPER - SEE DETAIL D/M501
SUPPLY AIR DUCTWORK SECTION
RETURN AIR DUCTWORK SECTION
AIR BALANCING DAMPER (MANUAL)
CONTROL DAMPER (MOTORIZED)
EXHAUST AIR DUCTWORK SECTION
DUCTWORK FLEXIBLE CONNECTION
DUCT ELBOW WITH SINGLE THICKNESS TURNING VANES
SIDEWALL REGISTER AND AIR FLOW (CFM)(SEE SCHEDULE
FOR SIZES UNLESS NOTED OTHERWISE)
SQUARE CEILING SA DIFFUSER AND AIR FLOW (CFM)(SEE SCHEDULE FOR SIZES
UNLESS NOTED OTHERWISE) SHADED REGION INDICATED SECTORIZING BAFFLE(S)
RECTANGULAR CEILING RA REGISTER AND AIR FLOW (CFM)(SEE SCHEDULE FOR
SIZES UNLESS NOTED OTHERWISE) WHERE CFM IS NOT INDICATED, PROVIDE
STANDARD SIZE FOR CEILING TYPE INDICATED IN SCHEDULE. SEE DETAIL E/M501
RECTANGULAR CEILING EA REGISTER AND AIR FLOW (CFM)(SEE SCHEDULE FOR
SIZES UNLESS NOTED OTHERWISE) SEE DETAIL E/M501
CFM
CFM
CFM
ACCESS PANEL IN INACCESSIBLE CEILING (24x24, UNO) SEE DETAIL J/M502AP
NEW DUCT
DUCT MOUNTED SMOKE DETECTOR (PROVIDED AND INSTALLED BY FIRE ALARM
CONTRACTOR)
DOOR UNDERCUT (3/4", UNO)
U C
LENGTH OF DIFFUSER (FEET)
NUMBER OF SLOTS
SLOT WIDTH (2 = 1/2", 3 = 3/4", 4 = 1", 6 = 1 1/2")
INLET SIZE (INCHES)
AIR FLOW (CFM)
4-4-4-12
SA SLOT DIFFUSER WITH PLENUM / BOOT (FLOW DIRECTION INDICATED)
LENGTH OF DIFFUSER (FEET)
NUMBER OF SLOTS
SLOT WIDTH (2 = 1/2", 3 = 3/4", 4 = 1", 6 = 1 1/2")
INLET SIZE (INCHES)
AIR FLOW (CFM)
4-4-4-12
RA SLOT DIFFUSER WITH PLENUM / BOOT (TO MATCH SA DIFFUSER IN SAME
ROOM)
AC ABOVE CEILING
AFF ABOVE FINISHED FLOOR
AHAP AS HIGH AS POSSIBLE
AHU AIR HANDLING UNIT
BDD BACKDRAFT DAMPER
BHP BRAKE HORSEPOWER
BOD BOTTOM OF DUCT
BTUH BRITISH THERMAL UNITS PER HOUR
C CONDENSATE
CC COOLING COIL
CFM CUBIC FEET PER MINUTE
CU CONDENSING UNIT
DDC DIRECT DIGITAL CONTROL PANEL
DN DOWN
EA EXHAUST AIR
EAG EXHAUST AIR GRILLE
EF EXHAUST FAN
ER EXHAUST REGISTER
F FEET
°Fdb DEGREES FAHRENHEIT DRY BULB °Fwb DEGREES FAHRENHEIT WET BULB
FPM FEET PER MINUTE
GPH GALLONS PER HOUR
HC HEATING COIL
HP HORSEPOWER
IN INCHES
MCA MINIMUM CIRCUIT AMPACITY
MOCP MAXIMUM OVERLOAD PROTECTION
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
OA OUTSIDE AIR
RA RETURN AIR
RAG RETURN AIR GRILLE
RAR RETURN AIR REGISTER
REF REFRIGERANT
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SAR SUPPLY AIR REGISTER
SF SUPPLY FAN
SMS SHEET METAL SIZE
SQ FT SQUARE FEET
TOD TOP OF DUCT
TOP TOP OF PIPE
TYP TYPICAL
UC DOOR UNDERCUT (3/4", UNO)
UNO UNLESS NOTED OTHERWISE
V VALVE
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
WG WATER GAUGE
ABBREVIATIONS
DRAWING INDEX
THERMOSTAT/TEMPERATURE SENSORT
MEASUREMENTS AND CONTROLS
SYMBOL
CEILING SUPPLY DIFFUSERS
CFM NECK SIZE
MINIMUM - MAXIMUM
1/2 SPACING
FACE DIMENSION
HARD
CEILING
LAY-IN
CEILING
40-80
85-180
185-340
345-500
505-600
6"Ø
8"Ø
10"Ø
12"Ø
14"Ø
4' - 5'
4' - 8'
8' - 10'
9' - 10'
10' - 12'
12x12
12x12
24x24
24x24
24x24
24x24
24x24
24x24
24x24
24x24
NOTE:
1. RUNOUT DUCTS TO DIFFUSERS SHALL BE THE SAME SIZE AS THE INDICATED NECK SIZE.
SYMBOL
CEILING RETURN OR EXHAUST REGISTERS & GRILLES
CFM
0-95
100-195
200-295
300-595
600-695
18x18 (NOTE 1)
22x22 (NOTE 1)
GRILLE SIZE
700-795
6x6
8x8
10x8
12x12
12x12
RUNOUT DUCT (NOTE 2)
14x12
800-1500 18x14
OR
NOTES:
1. USE 22x22 GRILLE SIZE FOR ALL LAY-IN CEILING APPLICATIONS. USE SIZE INDICATED FOR HARD CEILING
APPLICATIONS.
2. WHERE DUCT CONNECTION IS SHOWN, RUNOUT DUCT SHALL BE SIZE SHOWN IN SCHEDULE U.N.O.
3. USE 18x18 GRILLE SIZE AND 12x12 RUNOUT DUCT FOR HARD CEILING APPLICATIONS WHERE SIZE OR
AIRFLOW IS NOT INDICATED.
4. USE 12x12 RUN OUT DUCT FOR LAY-IN CEILING APPLICATIONS WHERE AIRFLOW IS NOT INDICATED.
24x24 (NOTE 1)
48x24 (NOTE 1)
8x8 (NOTE 1)
10x10 (NOTE 1)
12x12 (NOTE 1)
ROUND SHEET METAL DUCTCØ
GENERAL NOTES
1. INSTALL ALL WORK IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 2023, THE FLORIDA FIRE PREVENTION CODE, THE NATIONAL ELECTRICAL CODE 2020 EDITION, AND ALL CODES, ORDINANCES, RULES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION AT THIS SITE. WHERE CONFLICTS
OCCUR BETWEEN CODES AND THE CONSTRUCTION DOCUMENTS, THE MOST RESTRICTIVE
REQUIREMENTS SHALL GOVERN.
2. DRAWINGS ARE DIAGRAMMATIC, INDICATIVE OF WORK TO BE FURNISHED AND INSTALLED UNDER THIS
CONTRACT. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR ALL DIMENSIONS.
3. FIELD VERIFY DIMENSIONS AND CONDITIONS. IF THE CONTRACTOR IS UNABLE TO INTERPRET THE CONTRACT DOCUMENTS, CONTRACTOR IS RESPONSIBLE TO REQUEST CLARIFICATION IN WRITING TO THE ARCHITECT. IF CONTRACTOR PROCEEDS WITH ANY WORK BEFORE OBTAINING CLARIFICATION, CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ALL DEFICIENCIES ASSOCIATED THEREWITH.
4. BEFORE SUBMITTING FOR THE WORK, EACH BIDDER WILL BE RESPONSIBLE TO EXAMINE THE PREMISES AND SATISFY HIMSELF AS TO THE EXISTING CONDITIONS UNDER WHICH CONTRACTOR WILL BE OBLIGED
TO OPERATE AND COMPLETE THE WORK UNDER THIS CONTRACT. NO ALLOWANCE WILL
SUBSEQUENTLY BE MADE IN THIS CONNECTION ON BEHALF OF THE CONTRACTOR FOR ANY ERROR OR
OMISSION ON CONTRACTOR'S PART.
5. THE CONTRACTOR SHALL PAY FOR ALL INSPECTION PERMITS, CERTIFICATES, CONNECTION FEES, SYSTEM DEMAND CHARGES AND LICENSE FEES IN CONNECTION WITH CONTRACTOR'S WORK.
6. CONSTRUCTION MANAGER OR GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR SEQUENCING AND
COORDINATING WORK OF SUBCONTRACTORS TO AVOID INTERFERENCES.
7. WORK SHALL COMPLY WITH APPLICABLE O.S.H.A. AND E.P.A. REGULATIONS AND GUIDELINES.
8. ERECT AND MAINTAIN ALL REASONABLE PRECAUTIONS FOR SAFETY AND HEALTH INCLUDING POSTING
DANGER SIGNS AND OTHER WARNINGS AGAINST HAZARDS INCLUDING PROMULGATING SAFETY
REGULATIONS. PROVIDE SAFETY PRECAUTIONS AND BARRICADES FOR PEDESTRIANS AT
CONSTRUCTION VEHICLE ACCESS AND EGRESS LOCATIONS.
9. THE CONTRACTOR SHALL PROVIDE MANPOWER AND EQUIPMENT NECESSARY TO MAINTAIN THE
PROJECT SCHEDULE.
10. THE CONTRACTOR SHALL BE RESTRICTED TO AREAS DESIGNATED BY THE OWNER FOR ON-SITE STORAGE OF CONSTRUCTION MATERIALS AND IS RESPONSIBLE FOR THE PROTECTION AND SECURITY
OF ALL EQUIPMENT AND MATERIALS.
11. THE CONTRACTOR SHALL MAINTAIN A CLEAN WORK ENVIRONMENT AND SHALL CLEAN CONSTRUCTION
SITE OF ALL DEBRIS AT COMPLETION OF THE JOB AND BEFORE FINAL PAYMENT IS MADE.
12. THE CONTRACTOR SHALL FURNISH "AS-BUILT" RECORD DOCUMENTS TO THE OWNER AT COMPLETION
OF CONSTRUCTION.
13. CONTRACTOR SHALL GUARANTEE THE WORK AND MATERIALS FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE. THIS GUARANTEE SHALL BE IN ADDITION TO THE WARRANTIES PROVIDED BY
MATERIAL SUPPLIERS AND MANUFACTURERS.
14. CONTRACTOR'S APPROVAL STAMP ON SUBMITTALS AND SHOP DRAWINGS CERTIFIES THAT THE CONTRACTOR HAS REVIEWED THE DOCUMENTS AND THAT THE CONTRACT DOCUMENT REQUIREMENTS
HAVE BEEN ADHERED TO.
15. THE CONTRACTOR SHALL NOT BE RELIEVED OF RESPONSIBILITY FOR DEVIATIONS FROM
REQUIREMENTS OF THE CONTRACT DOCUMENTS BY THE ARCHITECT/ENGINEER'S APPROVAL OF SHOP
DRAWINGS, PRODUCT DATA, SAMPLES OR SIMILAR SUBMITTALS UNLESS THE CONTRACTOR HAS
SPECIFICALLY INFORMED THE ARCHITECT/ENGINEER IN WRITING OF SUCH DEVIATION AT THE TIME OF
SUBMITTAL AND THE ARCHITECT/ENGINEER HAS GIVEN WRITTEN APPROVAL TO THE SPECIFIC
DEVIATION. THE CONTRACTOR SHALL NOT BE RELIEVED OF RESPONSIBILITY FOR ERRORS OR
OMISSIONS IN SHOP DRAWINGS, PRODUCT DATA, SAMPLES OR SIMILAR SUBMITTALS BY THE
ARCHITECT/ENGINEER'S APPROVAL THEREOF.
16. PRIOR TO INSTALLATION, COORDINATE AND ADJUST THE FINAL LOCATION OF ALL WALL MOUNTED DEVICES AND EQUIPMENT WITH ALL CASEWORK, SHELVING, MARKER BOARDS, BULLETIN BOARDS OR
OTHER WALL MOUNTED FURNISHINGS.
17. ENTRY AND/OR REMOVAL OF EQUIPMENT FROM THE BUILDING SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR. DISMANTLE AND REASSEMBLE EQUIPMENT AS NECESSARY FOR ENTRY INTO THE
BUILDING AND/OR EQUIPMENT ROOMS. CONTRACTOR SHALL PATCH AND REPAIR ANY DAMAGED
MATERIALS TO MATCH THE ADJACENT UNDAMAGED SURFACES.
18. PROTECT THE ROOF FROM DAMAGE WHENEVER ANY WORK ON THE ROOF IS REQUIRED.
19. SUPPORTS AND HANGERS SHALL PRESENT A NEAT, ORDERLY APPEARANCE.
20. CONTRACTOR SHALL MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE WALL ASSEMBLIES AND
ACOUSTICAL WALLS.
21. BEAM AND FLOOR PENETRATIONS SHALL BE APPROVED BY THE STRUCTURAL ENGINEER. BEAM
SLEEVES AND BEAM REINFORCING APPROVED BY STRUCTURAL ENGINEER SHALL BE FURNISHED AND
INSTALLED BY THIS CONTRACTOR.
22. CONTRACTOR SHALL FURNISH U.L. APPROVED DRAWINGS FOR EACH TYPE OF FIRE RATED ASSEMBLY PENETRATION BY DUCTS, PIPES OR CONDUITS. THESE DRAWINGS SHALL BE DISPLAYED ON THE JOB
SITE AT ALL TIMES DURING CONSTRUCTION. SEE SPECIFICATIONS.
A L
L R
E P
O R
T S
P
LA
N
S
S P
E C
IF
IC
A T
IO
N
S
C O
M P
U T
E R
F
IL
E S
F
IE
LD
D A
T A
N
O T
E S
O
T H
E R
D O
C U
M E
N T
S
IN
S
T R
U M
E N
T S
P R
E P
A R
E D
B Y
T H
E D
E S
IG
N
P R
O F
E S
S
IO
N A
L A
S
IN
S T
R U
M E
N T
S O
F S
E R
V
IC
E S
H A
LL
R
E M
A
IN
T H
E P
R O
P E
R T
Y O
F T
H E
D E
S
IG
N P
R O
F E
S S
IO
N
A L.
T H
E D
E S
IG
N
P R
O F
E S
S
IO
N A
L S
H A
LL
R
E T
A
IN
A
LL
C O
M M
O N
L A
W
S T
A T
U T
O R
Y
O T
H E
R R
E S
E R
V E
D R
IG
H
T S
IN
C
LU
D
IN
G T
H E
C O
P Y
R
IG
H T
T H
E R
E T
O
U S
E O
F T
H E
S E
D O
C U
M E
N T
S F
O R
A N
Y P
U R
P O
S E
O R
P R
O
JE
C T
O T
H E
R T
H A
N T
H E
P R
O
JE
C T
W H
IC
H
I S
S U
B
JE
C T
O F
T H
E A
G R
E E
M E
N T
IS
U
N L
A W
F U
L.
Florida Registry #2485
SEAL
Matthew R. Thoele, P.E #75448
DESIGN PHASE:
114 EAST 5TH AVENUE TALLAHASSEE, FL
32303 PHONE 850.224.7922
www.H2Engineering.com
H2E PROJECT No. 24024
THIS DOCUMENT IS THE PROPERTY OF H2Engineering
AND IS PREPARED AS AN INSTRUMENT OF SERVICE. ITS
USE, REUSE OR REPRODUCTION, EXCEPT BY WRITTEN
AGREEMENT WITH H2Engineering, IS PROHIBITED.
/1
/2
:2 :4
P
M A u to d e s k D o c s:
-0
G a in e s v ill e R
T S
E a s ts id e B u s F a c ili ty /2
-0
G a in e sv ill e R
T S
E a st s id e B u s
F a ci lit y M
E P
R
.r v t
Project Number: 34-0007
Date: 4/1/2026
Drawn By: KWW
Checked By: MRT
GENERAL NOTES & LEGENDS
LOT 3, INTERSECTION OF S.E.
HAWTHORNE ROAD & S.E. 21ST
STREET
M001
EASTSIDE BUS
TRANSFER FACILITY
100% CONSTRUCTION DOCUMENTS
CITY OF GAINESVILLE DEPARTMENT
OF TRANSPORTATION
M001 GENERAL NOTES & LEGENDS
M002 SCHEDULES
M101 FLOOR PLAN - HVAC
M501 DETAILS
M502 DETAILS
REVISIONS
DUCTLESS SPLIT SYSTEM TYPES
TYPE DSSI-1/DSSO-1
DESCRIPTION COOLING ONLY
PERFORMANCE - (NOTES 1 & 2)
NOMINAL CAPACITY TONS 1 1/2
TOTAL COOLING CAPACITY BTUH 18,000
SENSIBLE COOLING CAPACITY BTUH 13,700
HEATING CAPACITY @ 47 °F BTUH N/A
HEATING CAPACITY @ 17 °F BTUH N/A
AIR FLOW RATE (HIGH - LOW) CFM 500 - 400
SEER2 BTU / W-HR 16.9
HSPF2 BTU / W-HR N/A
INDOOR UNIT DATA
FILTERS 1" WASHABLE
CONDENSATE DRAIN SIZE IN. 3/4
ELECTRICAL CHARACTERISTICS V / PH 208 / 1
MINIMUM CIRCUIT AMPACITY AMPS 0.5
MAXIMUM OVERLOAD PROTECTION AMPS 15
WEIGHT LBS. 31
OUTDOOR UNIT DATA
COMPRESSOR TYPE INVERTER
ELECTRICAL CHARACTERISTICS V / PH 208 / 1
MINIMUM CIRCUIT AMPACITY AMPS 16.5
MAXIMUM OVERLOAD PROTECTION AMPS 20
WEIGHT LBS. 172
MAX REFRIGERANT LINE LENGTH FT 164
REFRIGERANT TYPE R410A
MANUFACTURER DAIKIN
MODEL NUMBER (INDOOR UNIT) FAQ18TAVJU
MODEL NUMBER (OUTDOOR UNIT) RZR18TBVJU
DETAIL REFERENCE A/M502 F/M502
NOTES:
1 COOLING CAPACITY RATED @ 95 °F AMBIENT, 80°Fdb / 67°Fwb ENTERING AIR TEMPERATURE.
2 HEATING CAPACITY RATED @ 47 °Fdb / 43°Fwb AMBIENT, 70°Fdb ENTERING AIR TEMPERATURE.
3 UNIT SHALL BE CAPABLE OF OPERATION FOR AMBIENT TEMPERATURES DOWN TO 14°F
4 REFRIGERANT PIPING SHALL BE SIZED BY MANUFACTURER.
5 PROVIDE INTEGRAL CONDENSATE SENSOR TO SHUT UNIT OFF IF HIGH CONDENSATE LEVELS ARE DETECTED IN THE DRAIN PAN.
DESIGN CONDITIONS
OUTDOOR CONDITIONS - DESIGN DAY (GAINESVILLE, FLORIDA)
COOLING (0.4% ANNUAL) °Fdb - °Fwb 95.0 - 80.0
HEATING (99.6% ANNUAL) °Fdb 30.0
INDOOR CONDITIONS - SUMMER
ALL AREAS °Fdb - %RH 74 - 55
INDOOR CONDITIONS - WINTER
ALL AREAS °Fdb - %RH 70 - 30
SPLIT SYSTEM TYPES (1 - 5 TONS)
TYPE
DESCRIPTION HEAT PUMP HEAT PUMP
PERFORMANCE - (NOTES 1 & 2)
NOMINAL CAPACITY TONS 3 5
TOTAL COOLING CAPACITY BTUH 36,700 57,700
SENSIBLE COOLING CAPACITY BTUH 27,100 44,400
HEATING CAPACITY @ 47°F BTUH 20,500 38,500
AIR FLOW RATE CFM 1,215 1,975
SEER2 BTU / W-HR 16.0 14.7
INDOOR UNIT DATA
NOMINAL CAPACITY TONS 3 5
FAN DRIVE TYPE DIRECT DIRECT
FAN MOTOR HORSEPOWER HP 1/2 1
EXTERNAL STATIC PRESSURE IN. WG 0.8 0.7
AUXILIARY HEATING CAPACITY (NOTE 3) kW - # 8.0 15
AUXILIARY HEAT TEMPERATURE RISE °F 15.6 18.0
ELECTRICAL CHARACTERISTICS V / PH 208 / 1 208/3
MINIMUM CIRCUIT AMPACITY (NOTE 4) AMPS 41 49
MAXIMUM OVERLOAD PROTECTION (NOTE 4) AMPS 45 50
FILTERS 1" THICK PLEATED 1" THICK PLEATED
CONDENSATE DRAIN SIZE IN. 3/4 1
WEIGHT LBS. 150 200
OUTDOOR UNIT DATA
NOMINAL CAPACITY TONS 3 5
NUMBER OF COMPRESSORS OR STAGES # 2 2
ELECTRICAL CHARACTERISTICS V / PH 208 / 1 208/3
MINIMUM CIRCUIT AMPACITY AMPS 19 23
MAXIMUM OVERLOAD PROTECTION AMPS 30 40
WEIGHT LBS. 188 246
REFRIGERANT TYPE R-454B R-454B
MANUFACTURER LENNOX LENNOX
MODEL NUMBER (INDOOR UNIT) CBK47UJET-036 CBK47UHET-060
MODEL NUMBER (OUTDOOR UNIT) ML17KC2-036-230 ML17KC2-060-233
DETAIL REFERENCE H/M501 H/M501
NOTES:
1 COOLING CAPACITY RATED @ 95°F AMBIENT, 80°Fdb / 67°Fwb ENTERING AIR TEMPERATURE.
2 HEATING CAPACITY RATED @ 47°Fdb / 43°Fwb AMBIENT, 70°Fdb ENTERING AIR TEMPERATURE.
3 AUXILIARY HEATING RATED @ 240 V
4 REFRIGERANT PIPING SHALL BE SIZED BY MANUFACTURER.
AIR BALANCE SCHEDULE
OFFICE SPACE COMMUNITY CENTER
OUTSIDE AIR EXHAUST AIR OUTSIDE AIR EXHAUST AIR
SOURCE CFM SOURCE CFM SOURCE CFM SOURCE CFM
AHU-1 90 AHU-4 600 RELIEF 500
TOTAL 90 TOTAL 0 TOTAL 600 TOTAL 500
BALANCE 90 CFM/SF 0.08 BALANCE 100 CFM/SF 0.05
AIR BALANCE SCHEDULE
PUBLIC SPACES (FANS ON) PUBLIC SPACES (FANS OFF)
OUTSIDE AIR EXHAUST AIR OUTSIDE AIR EXHAUST AIR
SOURCE CFM SOURCE CFM SOURCE CFM SOURCE CFM
AHU-2 140 EF-1 70 AHU-2 140 EF-1 70
EF-2 70 EF-2 70
EF-3 70 EF-3 70
TOTAL 140 TOTAL 210 TOTAL 140 TOTAL 0
BALANCE -70 CFM/SF -0.06 BALANCE 140 CFM/SF 0.11
MAKEUP AIR UNIT - SPLIT SYSTEM
INDOOR UNIT DESIGNATION AHU-4
OUTDOOR UNIT DESIGNATION CU-4
AIR FLOW RATES
TOTAL SUPPLY AIR CFM 600
OUTSIDE AIR CFM 600
FILTER SECTION
DAMPERS NONE
FILTER ORIENTATION FLAT
TYPE OF FILTER 2" THICK PLEATED
COOLING DATA
TOTAL COOLING CAPACITY MBTUH 60.3
SENSIBLE COOLING CAPACITY MBTUH 28.1
AIR ENTERING COOLING COIL °Fdb - °Fwb 95.0 – 80.0
AIR LEAVING COOLING COIL °Fdb - °Fwb 51.6 – 51.6
EER / IEER BTU / W-HR 16.0 / 11.3
CONDENSATE DRAIN SIZE IN. 1
HOT GAS REHEAT DATA
TYPE MODULATING
HEATING CAPACITY MBTUH 6.9
AIR ENTERING HOT GAS REHEAT COIL °F 51.6
AIR LEAVING HOT GAS REHEAT COIL °F 86.2
HEATING DATA - ELECTRIC
HEATING CAPACITY - # OF STAGES kW - # 8 – SCR
AIR ENTERING HEATING COIL °F 30
AIR LEAVING HEATING COIL °F 69.5
SUPPLY FAN SECTION
FAN TYPE AIRFOIL
DRIVE TYPE DIRECT
FAN QUANTITY # 1
EXTERNAL STATIC PRESSURE IN. WG 0.3
MAXIMUM TOTAL STATIC PRESSURE (INCLUDING DIRTY FILTER) IN. WG 1
DIRTY FILTER ALLOWANCE IN. WG 0.7
FAN MOTOR HORSEPOWER (PER FAN) HP - BHP 1 – 0.2
VARIABLE FREQUENCY DRIVE 1 PER UNIT
INDOOR UNIT DATA
WEIGHT LBS 815
ELECTRICAL CHARACTERISTICS V / PH 208 / 3
MCA / MOCP AMPS 32 / 35
OUTDOOR UNIT DATA
COMPRESSOR QUANTITY # 1
WEIGHT LBS 635
REFRIGERANT TYPE R410A
ELECTRICAL CHARACTERISTICS V / PH 208 / 3
MCA / MOCP AMPS 24 / 40
MANUFACTURER ADDISON
MODEL NUMBER (INDOOR UNIT) SCOA0048
MODEL NUMBER (OUTDOOR UNIT) SAOA0048
DETAIL REFERENCE
NOTES:
1 REFRIGERANT PIPING SHALL BE SIZED BY THE MANUFACTURER OF THE SUPPLIED SYSTEM.
2 PROVIDE ONE (1) VARIABLE CAPACITY COMPRESSOR.
3 PROVIDE SUPPLY AIR TEMPERATURE SENSOR.
4 PROVIDE OUTSIDE AIR TEMPERATURE AND HUMIDITY SENSORS.
5 PROVIDE SUCTION PRESSURE TRANSDUCER.
6 PROVIDE EBTRON GOLD SERIES AIRFLOW MEASURING STATION.
7 PROVIDE DISCONNECT SWITCH BY DIV 26.
8 PROVIDE NEUTRAL AIR CONTROL.
GRAVITY VENTILATOR SCHEDULE
DESIGNATION GV-1 OA-1 OA-2
SERVICE RELIEF INTAKE INTAKE
AIRFLOW CFM 500 230 600
THROAT SIZE IN. 14 14 14
HOOD DIAMETER IN. 29 29 29
CURB CAP IN. x IN. 22x22 22x22 22x22
WEIGHT LBS. 13 13 13
MANUFACTURER GREENHECK GREENHECK GREENHECK
MODEL NUMBER GRSR-15 GRSI-15 GRSI-15
DETAIL REFERENCE C/M502 C/M502 C/M502
NOTES:
1 PROVIDE PREFABRICATED ROOF CURB WITH WELDED CAP CORNERS AND DAMPER TRAY.
2 PROVIDE BACKDRAFT DAMPER.
3 PROVIDE ALUMINUM BIRD SCREEN.
FANS
DESIGNATION EF-1 EF-2 EF-3 EF-4
SERVICE
CLASS 1 OR 2
EXHAUST
CLASS 1 OR 2
EXHAUST
CLASS 1 OR 2
EXHAUST
CLASS 1 OR 2
EXHAUST
MOUNTING METHOD CEILING CEILING CEILING SUSPENDED
FAN TYPE
CENTRIFUGAL
CABINET
CENTRIFUGAL
CABINET
CENTRIFUGAL
CABINET
CENTRIFUGAL
SQUARE IN-LINE
AIR FLOW CFM 70 70 70 150
STATIC PRESSURE IN. 0.30 0.30 0.30 0.30
AIRSTREAM TEMPERATURE DEG F 70 70 70 70
FAN SPEED RPM 900 900 900 1,474
FAN DRIVE DIRECT DIRECT DIRECT DIRECT
MOTOR POWER HP or W 15 W 15 W 15 W 15 W
ELECTRICAL CHARACTERISTICS V / PH 120 / 1 120 / 1 120 / 1 120 / 1
WEIGHT LBS. 12 12 12 12
NOISE LEVEL (RADIATED) SONES or LwA 0.5 SONES 0.5 SONES 0.5 SONES 3.4 SONES
MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK
MODEL NUMBER SP-A90 SP-A90 SP-A90 SQ-70-VG
DETAIL REFERENCE D/M502 D/M502 D/M502 B/M501
NOTES:
1 PROVIDE PRE-WIRED DISCONNECT SWITCH, FACTORY MOUNTED FOR SINGLE PHASE MOTORS (3/4 HP AND SMALLER).
2 PROVIDE BACKDRAFT DAMPER.
3 PROVIDE WHITE, ALUMINUM INLET GRILLE.
4 PROVIDE TIME DELAY SWITCH, INSTANT ON WITH LIGHTS AND 10-MINUTE TIME DELAY OFF. WIRED BY DIV 26 CONTRACTOR.
5 PROVIDE SPEED CONTROLLER.
SPLIT SYSTEM SCHEDULE (1 - 5 TONS)
INDOOR UNIT DESIGNATION AHU-1 AHU-2 AHU-3
OUTDOOR UNIT DESIGNATION CU-1 CU-2 CU-3
SCHEDULED TYPE D D F
DESCRIPTION HEAT PUMP HEAT PUMP HEAT PUMP
SUPPLY AIR FLOW CFM 950 1,200 2,000
OUTSIDE AIR FLOW CFM 90 140 0
NOTES 1 1 1
NOTES:
1 PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT/HUMIDISTAT WITH C02 MONITOR
D F
A L
L R
E P
O R
T S
P
LA
N
S
S P
E C
IF
IC
A T
IO
N
S
C O
M P
U T
E R
F
IL
E S
F
IE
LD
D A
T A
N
O T
E S
O
T H
E R
D O
C U
M E
N T
S
IN
S
T R
U M
E N
T S
P R
E P
A R
E D
B Y
T H
E D
E S
IG
N
P R
O F
E S
S
IO
N A
L A
S
IN
S T
R U
M E
N T
S O
F S
E R
V
IC
E S
H A
LL
R
E M
A
IN
T H
E P
R O
P E
R T
Y O
F T
H E
D E
S
IG
N P
R O
F E
S S
IO
N
A L.
T H
E D
E S
IG
N
P R
O F
E S
S
IO
N A
L S
H A
LL
R
E T
A
IN
A
LL
C O
M M
O N
L A
W
S T
A T
U T
O R
Y
O T
H E
R R
E S
E R
V E
D R
IG
H
T S
IN
C
LU
D
IN
G T
H E
C O
P Y
R
IG
H T
T H
E R
E T
O
U S
E O
F T
H E
S E
D O
C U
M E
N T
S F
O R
A N
Y P
U R
P O
S E
O R
P R
O
JE
C T
O T
H E
R T
H A
N T
H E
P R
O
JE
C T
W H
IC
H
I S
S U
B
JE
C T
O F
T H
E A
G R
E E
M E
N T
IS
U
N L
A W
F U
L.
Florida Registry #2485
SEAL
Matthew R. Thoele, P.E #75448
DESIGN PHASE:
114 EAST 5TH AVENUE TALLAHASSEE, FL
32303 PHONE 850.224.7922
www.H2Engineering.com
H2E PROJECT No. 24024
THIS DOCUMENT IS THE PROPERTY OF H2Engineering
AND IS PREPARED AS AN INSTRUMENT OF SERVICE. ITS
USE, REUSE OR REPRODUCTION, EXCEPT BY WRITTEN
AGREEMENT WITH H2Engineering, IS PROHIBITED.
/1
/2
:2 :4
P
M A u to d e s k D o c s:
-0
G a in e s v ill e R
T S
E a s ts id e B u s F a c ili ty /2
-0
G a in e sv ill e R
T S
E a st s id e B u s
F a ci lit y M
E P
R
.r v t
Project Number: 34-0007
Date: 4/1/2026
Drawn By: KWW
Checked By: MRT
SCHEDULES
LOT 3, INTERSECTION OF S.E.
HAWTHORNE ROAD & S.E. 21ST
STREET
M002
EASTSIDE BUS
TRANSFER FACILITY
100% CONSTRUCTION DOCUMENTS
CITY OF GAINESVILLE DEPARTMENT
OF TRANSPORTATION
T
T
T
T
COMMUNITY MEETING ROOM
OFFICE
BREAK ROOM
MECHANICAL
MECHANICAL CLOSET
JANITOR
TICKETING
RESTROOM
TRAINING
LOBBY
JANITOR
RESTROOM
RESTROOM
OFFICE
TELECOM
RESTROOM
OFFICE CORRIDOR
R.R HALLWAY
STORAGE 1
EF-2
EF-1
EF-3
x8 x1
UC
UC
22x18 x1
16x8
16x8
200 200 200 200 200
6" VTR
6" VTR
UC
NOZZLE DIFFUSER
PRICE ND8 (TYP)
6x8 x8
AP
6x8
4-1-4-12
TYP(4)
AHU-1
AHU-2
R E
F
R E
F
CU-1
CU-2
M101 x1
DSSI-1
DSSO-1
ROUTE CONDENSATE TO EXTERIOR.
DISCHARGE TO SPLASHBLOCK.
REF
C
ROUTE CONDENSATE
LINES OUTSIDE OF
BUILDING.
DISCHARGE TO
SPLASH BLOCK
C
C
ROUTE CONDENSATE TO
EXTERIOR. DISCHARGE
TO SPLASHBLOCK.
RETURN PLENUM
BEHIND WALL
AP
6" VTR
PRICE 18X14
730-RAS LOUVERED
GRILLES (TYP. 3)
CU-3
CU-4
(DOAS)
AHU-4
(DOAS)
AHU-3
REF
x1 x8
M101
OA-2
OA-1
GV-1 -
BAROMETRIC DAMPER
ON ROOF
12x12
6x
12x12
UNIT MOUNTED AT 6'
HEIGHT ON WALL. ADHERE
TO MANUFACTURER'S
WALL CLEARANCE.
C
ROUTE CONDENSATE
LINES OUTSIDE OF
BUILDING. DISCHARGE
TO SPLASH BLOCK
REF
EHV-901D
EXTERIOR LOUVER
12X6 EXHAUST
LOUVER INTO
DUCTING TO EF-5
12X6 EXHAUST
LOUVER INTO
DUCTING TO EF-5
EF-4
x6 x6
10x10
GV-1
x1
FIRST FLOOR
0"
T.O.W. LOWER
10' - 0"
AHU-4
(DOAS)
AHU-3
18x22 SA
OA-2
x1 x1
FIRST FLOOR
0"
T.O.W. LOWER
10' - 0"
AHU-1AHU-2
x8
R A x8
S A x1
O
A
REF
C
ROUTE
CONDENSATE
TO EXTERIOR
OA-1
x1
TRUE
A L
L R
E P
O R
T S
P
LA
N
S
S P
E C
IF
IC
A T
IO
N
S
C O
M P
U T
E R
F
IL
E S
F
IE
LD
D A
T A
N
O T
E S
O
T H
E R
D O
C U
M E
N T
S
IN
S
T R
U M
E N
T S
P R
E P
A R
E D
B Y
T H
E D
E S
IG
N
P R
O F
E S
S
IO
N A
L A
S
IN
S T
R U
M E
N T
S O
F S
E R
V
IC
E S
H A
LL
R
E M
A
IN
T H
E P
R O
P E
R T
Y O
F T
H E
D E
S
IG
N P
R O
F E
S S
IO
N
A L.
T H
E D
E S
IG
N
P R
O F
E S
S
IO
N A
L S
H A
LL
R
E T
A
IN
A
LL
C O
M M
O N
L A
W
S T
A T
U T
O R
Y
O T
H E
R R
E S
E R
V E
D R
IG
H
T S
IN
C
LU
D
IN
G T
H E
C O
P Y
R
IG
H T
T H
E R
E T
O
U S
E O
F T
H E
S E
D O
C U
M E
N T
S F
O R
A N
Y P
U R
P O
S E
O R
P R
O
JE
C T
O T
H E
R T
H A
N T
H E
P R
O
JE
C T
W H
IC
H
I S
S U
B
JE
C T
O F
T H
E A
G R
E E
M E
N T
IS
U
N L
A W
F U
L.
Florida Registry #2485
SEAL
Matthew R. Thoele, P.E #75448
DESIGN PHASE:
114 EAST 5TH AVENUE TALLAHASSEE, FL
32303 PHONE 850.224.7922
www.H2Engineering.com
H2E PROJECT No. 24024
THIS DOCUMENT IS THE PROPERTY OF H2Engineering
AND IS PREPARED AS AN INSTRUMENT OF SERVICE. ITS
USE, REUSE OR REPRODUCTION, EXCEPT BY WRITTEN
AGREEMENT WITH H2Engineering, IS PROHIBITED.
/1
/2
:2 :5
P
M A u to d e s k D o c s:
-0
G a in e s v ill e R
T S
E a s ts id e B u s F a c ili ty /2
-0
G a in e sv ill e R
T S
E a st s id e B u s
F a ci lit y M
E P
R
.r v t
Project Number: 34-0007
Date: 4/1/2026
Drawn By: KWW
Checked By: MRT
FLOOR PLAN - HVAC
LOT 3, INTERSECTION OF S.E.
HAWTHORNE ROAD & S.E. 21ST
STREET
M101
EASTSIDE BUS
TRANSFER FACILITY
100% CONSTRUCTION DOCUMENTS
CITY OF GAINESVILLE DEPARTMENT
OF TRANSPORTATION
FLOOR PLAN - HVAC
SCALE: 3/16" = 1'-0"M101
1/4" = 1'-0"M101
2 MECHANICAL CLOSET
1/4" = 1'-0"M101
3 MECHANICAL ROOM
GENERAL NOTES
1. PLENUM RETURN DETAIL. SEE DETAIL C/M502
90° MIN
SECURE FLEXIBLE DUCT SUPPORT
ELBOW TO FLEXIBLE DUCT WITH
NYLON CABLE TIES ON BOTH ENDS
DRAW BAND WITH CABLE SUPPORT
ATTACHED TO STRUCTURE (NOTE 1)
STAINLESS STEEL DRAW BAND
(1/2" MIN. WIDTH). FORM AIRTIGHT
SEAL WITH FABRIC AND MASTIC
SEALANT. (NOTES 3 & 4)
INSULATION (NOTE 2)
CEILING TILE
CEILING GRID
SUPPLY DIFFUSER
PROVIDE FLEXIBLE DUCT
ELBOW SUPPORT TO FORM 90°
DEGREE ELBOW (NOTE 5)
BALANCING DAMPER - LOCATE
AT BRANCH TAKE-OFF
STAINLESS STEEL DRAW BAND
(1/2" MIN. WIDTH). FORM AIRTIGHT
SEAL WITH FABRIC AND MASTIC
SEALANT.
FLEXIBLE DUCT (SAME AS DIFFUSER NECK
SIZE). MIN LENGTH 3'-0" / MAX LENGTH = 5'-0"
FLEXIBLE DUCT CONNECTION TO SUPPLY DIFFUSERG
R
NOTES:
1. FLEXIBLE DUCT SHALL NOT HAVE MORE THAN 1/2" SAG PER FOOT.
2. PROVIDE INSULATION ON BACK OF DIFFUSERS (SEE SPECIFICATIONS). SEAL VAPOR TIGHT WITH FABRIC AND MASTIC.
3. PULL INNER LINER OF FLEXIBLE DUCT OVER DIFFUSER COLLAR AND SECURE WITH DRAW BAND.
4. SECURE FLEXIBLE DUCT INSULATION AND OUTER JACKET WITH DRAW BAND.
5. MAINTAIN MINIMUM RADIUS (R) OF 1.5 TIMES THE DUCT DIAMETER.
AIR FLOW
!M245
REF
REF
C
VERTICAL AHU ON RA STAND/PLENUM
DUCT SMOKE DETECTOR (TYPICAL FOR ALL
AIR HANDLING UNITS OF 2000 CFM OR
GREATER AND WHEN INDICATED ON PLANS)
SUPPLY AIR DUCT
RETURN AIR DUCT
OUTSIDE AIR DUCT
MANUAL BALANCING DAMPER
FLEX. DUCT CONNECTION (TYP.)
REFRIGERANT PIPING.
PRIMARY CONDENSATE DRAIN.
FILTER (DO NOT BLOCK ACCESS)
PROVIDE CONTINUOUS STRIP OF 1/4" THICK
NEOPRENE BEARING PAD (MASON INDUSTRIES
BBP OR APPROVED EQUAL) BETWEEN FLANGE
OF PLENUM AND AIR HANDLING UNIT.
SHEET METAL RA PLENUM WITH EXTERNAL
DUCTBOARD INSULATION (SIDES AND
BOTTOM), SAME SIZE AS OPENING ON UNIT.
1 1/2" X 1 1/2" X 3/16" GALV. STEEL ANGLE
STAND (ALL WELDED CONSTRUCTION).
HEIGHT OF PLENUM - 24" OR AS REQUIRED
AUXILIARY DRAIN PAN
4"x4"x1" THICK NEOPRENE/CORK PAD
SECURE TO ANGLE FRAME (TYP.)
AIR HANDLING UNIT
MANUAL BALANCING DAMPER
NOTE:
1. PROVIDE A FLOAT SWITCH IN THE AUXILIARY DRAIN PAN INTERLOCKED WITH AHU FAN.
!M227.5
RECTANGULAR DUCT
TYPICAL DUCT TAKE-OFF FITTINGSD
L 45
C
12 x 6
12 x 6
16 x 6.75
D
8.5
8.5
10 9.5
18 x 8.5
20 x 9.5
24 x 12
10.5
10.5
DIMENSIONS BASED ON CROWN PRODUCTS CO., INC.
NO FIRE
DAMPER
NOTE 4
NOTE 3
NOTE 2
ROUND DUCT
WALL TO
STRUCTURE
D
(DIAMETER)
NOTE 1
W x H
(W=WIDTH, H=HEIGHT)
A x B TRUNK DUCT
(A=WIDTH, B=HEIGHT) E
(NOTE 5)
WxH
(NOTE 5)
TRUNK DUCT
HEIGHT (B MIN.) WITH FIRE
DAMPER
L = W/4 (4"MIN.)
H = B-2 (MAX.)
C = L+4 (WITH FIRE DAMPER)
C = L+2 (WITHOUT FIRE DAMPER)
NOTES:
1. 45° ENTRY.
2. 1" WIDE FLANGE WITH GASKET SEAL AROUND ENTIRE PERIMETER.
3. PROVIDE MANUAL BALANCING DAMPER. OPERATOR SHALL PENETRATE INSULATION.
4. USE ROUND TYPE TAKE-OFF FOR SUPPLY AIR TO NOT MORE THAN ONE TERMINAL.
5. USE ROUND TYPE TAKE-OFF FOR SUPPLY AIR TO NOT MORE THAN ONE TERMINAL.
DIAMETER, PROVIDE TRANSITION FITTING OF EQUIVALENT AREA TO THE RUNOUT DUCT.
WALL TO
STRUCTURE
C
M
IN
E
(W=WIDTH, H=HEIGHT)
C
M
IN
NOTE 1
W x H
NOTE 2
NOTE 3
!M182
!M170.3
RETURN OR EXHAUST
GRILLE. SEE SCHEDULE OR
PLAN FOR REQUIRED SIZE.
CEILING
TOP ENTRY
6" 1"
PLENUM FULL SIZE
OF GRILLE
RETURN OR EXHAUST
GRILLE. SEE SCHEDULE OR
PLAN FOR REQUIRED SIZE.
CEILING
SIDE ENTRY
DUCT
PLENUM FULL SIZE OF GRILLE
DUCT
NOTES:
1. INSTALL BLADES OF GRILLE SO
SIGHT LINE INTO PLENUM IS
OBSCURED FROM ROOM.
2. PROVIDE APPROPRIATE MOUNTING
HARDWARE FOR GRILLE TO
ACCOMMODATE CEILING TYPE.
1-INCH 1.5 PCF DUCT LINER
1-INCH 1.5 PCF DUCT LINER
8"
2"
PLENUM FULL
SIZE OF GRILLE
RETURN OR EXHAUST
GRILLE. SEE SCHEDULE OR
PLAN FOR REQUIRED SIZE.
CEILING
PLENUM RETURN GRILLES
1-INCH 1.5 PCF DUCT LINER
OPENING: 10" MIN.
x WIDTH OF GRILLE
1"
H
ELECTRIC HEAT SECTION
(WHERE INDICATED IN SCHEDULE)
DUCT SIZE + 25%
METAL SCREEN FRAME
ANGLE IRON REINFORCING
SCREEN
BOLTS
STANDARD DUCT CONSTRUCTION
SEAMS WATERTIGHT
PROVIDE ANGLE
IRON SUPPORT LEGS
WHERE REQUIRED
BACKDRAFT
DAMPER
CURB
SPECIFIED
DUCT SIZE
FLASHING
ROOFING
18" MINIMUM
1/2" SCREEN
ANGLE RIVETED OR SPOT
WELDED AS REQUIRED
CANT
!M164
AIR
FLOW
FAN
STRUCTURE
BACKDRAFT DAMPER
DUCTWORK
NOTES:
1. INSTALL TO ALLOW ACCESS FOR MAINTENANCE.
2. PROVIDE DIRECT DRIVE FAN WHERE SCHEDULED.
SPRING TYPE VIBRATION
ISOLATING HANGER (TYP.)
FLEXIBLE CONNECTION (TYP.)
HOOD WITH PITCHED ROOF
PROVIDE BIRD SCREEN
APPLY FOAM RUBBER
GASKET TO UNDERSIDE
OF CURB CAP.
PRE-FABRICATED ROOF
CURB.
NOTES:
1. SECURE HOOD TO ROOF CURB WITH SHEET
METAL SCREWS @ 12" O.C. ALL AROUND.
2. SECURE CURB TO ROOF WITH SHEET METAL
SCREWS, LAG BOLTS OR OTHER METHOD
CONSISTENT WITH ROOF CONSTRUCTION.
3. FOLLOW MANUFACTURERS INSTALLATION
REQUIREMENTS.
FINISHED ROOF
P.T. WOOD NAILER
AIR OUTLET
FRONT GRILLE
FRONT PANEL
C R
E F
CEILING
SHUTOFF VALVES
ROUTE CONDENSATE TO LOCATION
SHOWN ON PLANS
CEILING
W A
LL
3 1/2" MIN.
2" MIN.
4 3/4" MIN.
1 1/4" MIN.
CLEARANCE
R E
F
PIPE CONNECTION HOLE
CONDENSATE DRAIN, LIQUID
AND GAS REFRIGERANT
GALVANIZED STEEL DRYWALL
TAPING BEAD FLANGE
DRYWALL
METAL STUD
NOTES:
1. ACCESS DOOR SHALL BE NOMINAL 24"x24" UNLESS NOTED OTHERWISE.
2. LOCATE DOOR IN CEILING OR WALL TO ALLOW UNOBSTRUCTED ACCESS
TO EQUIPMENT, DAMPERS, ETC. AND NOT IN CONFLICT WITH LIGHTS,
DIFFUSERS, SPRINKLERS, ETC.
3. ATTACH FRAME OF ACCESS PANEL TO CEILING OR WALL FRAMED
OPENING ACCORDING TO MANUFACTURER'S RECOMMENDATIONS.
PROVIDE:
1. CONCEALED HINGE WITH REMOVABLE DOOR PANEL.
2. EXTRUDED ALUMINUM DOOR AND FRAME CONSTRUCTION.
3. REVERSIBLE DOOR PANEL ACCOMMODATES EITHER 5/8" OR 1/2" DRYWALL
4. SAFETY CHAIN FOR SIZES OVER 12"x12".
5. SCREWDRIVER OPERATED CAM LATCH.
CONCEALED HINGE SUPPLIED WITH 5/8"
DRYWALL INSTALLED
IN DOOR PANEL.
SCREWDRIVER OPERATED CAM
LATCHES
WALL OR CEILING OPENING
NOMINAL SIZE + 0.20"
RECESSED EQUIPMENT ACCESS PANEL - DRYWALL FACE
!M78.2 !M72.3
J
RETURN OR EXHAUST CEILING GRILLEE
DUCTLESS - WALL MOUNTED INDOOR UNITF
RECTANGULAR GOOSENECKA
IN-LINE FANB
GRAVITY ROOF VENTILATORC
!M121.3
!M103.1
A L
L R
E P
O R
T S
P
LA
N
S
S P
E C
IF
IC
A T
IO
N
S
C O
M P
U T
E R
F
IL
E S
F
IE
LD
D A
T A
N
O T
E S
O
T H
E R
D O
C U
M E
N T
S
IN
S
T R
U M
E N
T S
P R
E P
A R
E D
B Y
T H
E D
E S
IG
N
P R
O F
E S
S
IO
N A
L A
S
IN
S T
R U
M E
N T
S O
F S
E R
V
IC
E S
H A
LL
R
E M
A
IN
T H
E P
R O
P E
R T
Y O
F T
H E
D E
S
IG
N P
R O
F E
S S
IO
N
A L.
T H
E D
E S
IG
N
P R
O F
E S
S
IO
N A
L S
H A
LL
R
E T
A
IN
A
LL
C O
M M
O N
L A
W
S T
A T
U T
O R
Y
O T
H E
R R
E S
E R
V E
D R
IG
H
T S
IN
C
LU
D
IN
G T
H E
C O
P Y
R
IG
H T
T H
E R
E T
O
U S
E O
F T
H E
S E
D O
C U
M E
N T
S F
O R
A N
Y P
U R
P O
S E
O R
P R
O
JE
C T
O T
H E
R T
H A
N T
H E
P R
O
JE
C T
W H
IC
H
I S
S U
B
JE
C T
O F
T H
E A
G R
E E
M E
N T
IS
U
N L
A W
F U
L.
Florida Registry #2485
SEAL
Matthew R. Thoele, P.E #75448
DESIGN PHASE:
114 EAST 5TH AVENUE TALLAHASSEE, FL
32303 PHONE 850.224.7922
www.H2Engineering.com
H2E PROJECT No. 24024
THIS DOCUMENT IS THE PROPERTY OF H2Engineering
AND IS PREPARED AS AN INSTRUMENT OF SERVICE. ITS
USE, REUSE OR REPRODUCTION, EXCEPT BY WRITTEN
AGREEMENT WITH H2Engineering, IS PROHIBITED.
/1
/2
:2 :5
P
M A u to d e s k D o c s:
-0
G a in e s v ill e R
T S
E a s ts id e B u s F a c ili ty /2
-0
G a in e sv ill e R
T S
E a st s id e B u s
F a ci lit y M
E P
R
.r v t
Project Number: 34-0007
Date: 4/1/2026
Drawn By: KWW
Checked By: MRT
DETAILS
LOT 3, INTERSECTION OF S.E.
HAWTHORNE ROAD & S.E. 21ST
STREET
M501
EASTSIDE BUS
TRANSFER FACILITY
100% CONSTRUCTION DOCUMENTS
CITY OF GAINESVILLE DEPARTMENT
2"
4"
NEOPRENE RUBBER
WAFFLE IS
OLATION PAD
EQUIPMENT
LIFTING HOLE6" M
IN.
(TYPICAL ALL
SIDES)
CONCRETE SLAB
EQUIPMENT TIE-DOWN AND ISOLATION
CONCRETE SLAB -
DIMENSIONS AS REQUIRED
(3000 PSI @ 28 DAYS)
GRADEGRADE
#4 @ 12"
EACH WAY
SLAB WITHOUT FOOTING
!M45
9" M
IN
4"
NOTES:
1. USE WHERE OBSTRUCTION PREVENTS NORMAL
FLEX DUCT CONNECTION TO CEILING DIFFUSER.
2. INSULATE ALL DUCTWORK AS SPECIFIED.
OBSTRUCTING DUCT
CEILING
RECT./ROUND
TRANSITION
4" OVERHANG, 3 SIDES
CEILING DIFFUSER
MAX. 10"∅
NECK
FLEX DUCT
PLENUM
!M29
CONCRETE EQUIPMENT SLAB AND TIE-DOWNB
CEILING RETURN PLENUMC
CEILING EXHAUST FAND
FLEXIBLE CONNECTOR
EXHAUST DUCT
BACKDRAFT DAMPER
CEILING EXHAUST FAN
MOUNTING BRACKET (NOTE 1)
FRAMED OPENING IN STUDS
GYP. BOARD CEILING
REMOVABLE ALUMINUM GRILLE
NOTES:
1. SUPPORT CEILING FAN LOCATED ABOVE LAY-IN CEILING FROM
THE BUILDING STRUCTURE, INDEPENDENT OF CEILING.
FRONT VIEW SIDE VIEW
CEILING EXHAUST FAN
DUCTLESS SPLIT SYSTEM
CONDENSING UNIT
POWDER COATED WALL MOUNT BRACKET
RATED FOR 500 LBS. AIRTEC MODEL
WBB500 OR APPROVED EQUAL.
PROVIDE MANUFACTURER'S
MINIMUM CLEARANCE
AIR FLOW
S E
E P
LA
N
S F
O R
M
O U
N T
IN
G
H E
IG
H
T
REFRIGERANT PIPING
DUCTLESS SPLIT SYSTEM - CONDENSING UNITA
!M72.2
A L
L R
E P
O R
T S
P
LA
N
S
S P
E C
IF
IC
A T
IO
N
S
C O
M P
U T
E R
F
IL
E S
F
IE
LD
D A
T A
N
O T
E S
O
T H
E R
D O
C U
M E
N T
S
IN
S
T R
U M
E N
T S
P R
E P
A R
E D
B Y
T H
E D
E S
IG
N
P R
O F
E S
S
IO
N A
L A
S
IN
S T
R U
M E
N T
S O
F S
E R
V
IC
E S
H A
LL
R
E M
A
IN
T H
E P
R O
P E
R T
Y O
F T
H E
D E
S
IG
N P
R O
F E
S S
IO
N
A L.
T H
E D
E S
IG
N
P R
O F
E S
S
IO
N A
L S
H A
LL
R
E T
A
IN
A
LL
C O
M M
O N
L A
W
S T
A T
U T
O R
Y
O T
H E
R R
E S
E R
V E
D R
IG
H
T S
IN
C
LU
D
IN
G T
H E
C O
P Y
R
IG
H T
T H
E R
E T
O
U S
E O
F T
H E
S E
D O
C U
M E
N T
S F
O R
A N
Y P
U R
P O
S E
O R
P R
O
JE
C T
O T
H E
R T
H A
N T
H E
P R
O
JE
C T
W H
IC
H
I S
S U
B
JE
C T
O F
T H
E A
G R
E E
M E
N T
IS
U
N L
A W
F U
L.
Florida Registry #2485
SEAL
Matthew R. Thoele, P.E #75448
DESIGN PHASE:
114 EAST 5TH AVENUE TALLAHASSEE, FL
32303 PHONE 850.224.7922
www.H2Engineering.com
H2E PROJECT No. 24024
THIS DOCUMENT IS THE PROPERTY OF H2Engineering
AND IS PREPARED AS AN INSTRUMENT OF SERVICE. ITS
USE, REUSE OR REPRODUCTION, EXCEPT BY WRITTEN
AGREEMENT WITH H2Engineering, IS PROHIBITED.
/1
/2
:2 :5
P
M A u to d e s k D o c s:
-0
G a in e s v ill e R
T S
E a s ts id e B u s F a c ili ty /2
-0
G a in e sv ill e R
T S
E a st s id e B u s
F a ci lit y M
E P
R
.r v t
Project Number: 34-0007
Date: 4/1/2026
Drawn By: KWW
Checked By: MRT
DETAILS
LOT 3, INTERSECTION OF S.E.
HAWTHORNE ROAD & S.E. 21ST
STREET
M502
EASTSIDE BUS
TRANSFER FACILITY
100% CONSTRUCTION DOCUMENTS
CITY OF GAINESVILLE DEPARTMENT
LIGHTING FIXTURE SCHEDULE
GENERAL NOTES:
1.) CONTRACTOR SHALL COORDINATE FIXTURE TYPE WITH ARCHITECTURAL FINISH SCHEDULE(S). ARCHITECT SHALL CONFIRM TRIMS AND FINISHES FOR ALL FIXTURES.
2.) LIGHT FIXTURES DEEMED EQUAL TO THOSE SPECIFIED SHALL BE SUBMITTED FOR APPROVAL IN ACCORDANCE WITH SPECIFICATIONS.
3.) PROVIDE MOUNTING TRIM REQUIRED FOR CEILING TYPE INSTALLED.
TYPE CATALOG NUMBER
LAMP
VOLTAGE DESCRIPTION
MANUFACTURER (OR
EQUAL) POWER TYPE
LUMEN
OUTPUT CRI
COLOR
TEMPERATURE
LF-1 ELITE LIGHTING HH4-LED-3000L-DIM10-120-VWD-40K-90 32W LED 3000 90 4000K 120V 4" ARCHITECTURAL LED DOWNLIGHT WITH VERY WIDE DISTRIBUTION. 0-10V
DIMMING. UGR < 19
LF-2 ELITE LIGHTING HH4-LED-3000L-DIM10-120-VWD-40K-90-HH4-4501 32W LED 3000 90 4000K 120V 4" ARCHITECTURAL HIGH LUMEN LED DOWNLIGHT WITH VERY WIDE
DISTRIBUTION. 0-10V DIMMING. WET LOCATION LISTED. UGR < 19
LF-3 ELITE LIGHTING HH6-LED-2000L-DIM10-120-VWD-40K-90-HH6-6501 20W LED 2000 90 4000K 120V 6" ARCHITECTURAL HIGH LUMEN LED DOWNLIGHT WITH VERY WIDE
DISTRIBUTION. 0-10V DIMMING. WET LOCATION LISTED. UGR < 19
LF-4 ELITE LIGHTING 11.7 W/FT LED 1000 LM/FT 90 4000K 120V
LF-5 KLUS LIGHTING B-FC-40-1275/2-24-8FT-SUSPENDED-CABLE36 8.78 W/FT LED 893 LM/FT 90 4000K 120V 1" W X 8'L SUSPENDED LINEAR FIXTURE WITH FROSTED ACRYLIC LENS AND
BLACK FINISH. COORDINATE WITH ARCHITECTURAL CEILING PLAN FOR EXACT
HEIGHT OF SUSPENDED FIXTURE.
LF-6 ELITE LIGHTING 4-OC1-LED-5000L-DIM10-MVOLT-40K-85-V3 31W LED 5000 90 4000K 120V 4' ARCHITECTURAL SURFACE/SUSPENDED STRIP FIXTURE. SURFACE
MOUNTED OR SUSPENDED. WHERE SUSPENDED MOUNT 10' AFF.
LF-7 ELITE LIGHTING 22-EDGE-LED-2000L-DIM10-120-40K-85 23W LED 2000 90 4000K 120-277V 2' x 2' ARCHITECTURAL VOLUMETRIC RECESSED LED TROFFER. UGR < 17
LF-8 ELITE LIGHTING OVLS-LED-30-1900L-DIMTR-120V-4000K-90 27W LED 1900 90 4000K 120V 30" INTERIOR SQUARE LENS LINEAR VANITY LIGHT WITH ACRYLIC DIFFUSER.
LF-9 ORACLE LIGHTING OFL-R-102-LED-4500L-DIM10-MVOLT-40K-FL-BZ-LED-STAKE 30W LED 4500 80 4000K 120V EXTERIOR FLOOD LIGHT
LF-10 CGF DESIGN E804-LED36-CT4-UNV-BK-0-10D1 36W LED 3700 80 4000K 120-277V 4' LED LINEAR LED FIXTURE, IK10 RATED. WET LOCATION RATED.
LF-11 ELITE LIGHTING OWP-FC-209-LED-6000L-DIM10-120-347V-40K-BZ 44W LED 6000 80 4000K 120-347V LED FULL CUT OFF LARGE WALL PACK WITH POLYCARBONATE DIFFUSER.
0-10V DIMMING. WET LOCATION LISTED.
LF-12 BLE-G-BSL-100-G15-NA-LED23-4000K-NA-FST-277 23W LED 2000 80 4000K 120-277V BULLET GOOSENECK LED SIGN LIGHT. 0-10V DIMMING. WET LOCATION LISTED.
LF-13 HE WILLIAMS 1SF-3-L18/840-AF12125-DIM-UNV 16W LED 1800 80 4000K 120-277V 3' SURFACE MOUNT UNDERCABINET LED FIXTURE. DIE FORMED HOUSING.
0-10V DIMMING.
E ELITE LIGHTING ELX-LED-618-G/R-1-CL-W LED CLEAR, EDGE LIT LED EXIT SIGN WITH GREEN LETTERING
RESPONSIBILITY MATRIX FOR TELECOMMUNICATIONS
AREA OF WORK / CATEGORY OF EQUIPMENT FURNISHED BY INSTALLED BY
NOTE:
THIS MATRIX IS INTENDED TO INDICATE A GENERAL LISTING OF THE WORK AND MATERIALS TO BE
FURNISHED AND INSTALLED BY THE VARIOUS TRADES FOR COORDINATION PURPOSES ONLY. IT IS NOT INTENDED TO TO BE ALL INCLUSIVE. EACH TRADE IS RESPONSIBLE FOR FURNISHING AND
INSTALLING THEIR RESPECTIVE COMPLETE AND WORKING SYSTEM. REFER TO DRAWINGS AND
SPECIFICATIONS FOR THE EXTENT OF WORK
INVOLVED.
O W
N E
R
E
LE
C T
R
IC
A L
C O
N T
R A
C T
O R
T E
LE
C
O M
C O
N T
R A
C T
O R
A /V
C O
N T
R A
C T
O R
S E
C U
R
IT
Y C
O N
T R
A C
T O
R
F
IR
E A
LA
R
M C
O N
T R
A C
T O
R
O W
N E
R
E
LE
C T
R
IC
A L
C O
N T
R A
C T
O R
T E
LE
C
O M
C O
N T
R A
C T
O R
A /V
C O
N T
R A
C T
O R
S E
C U
R
IT
Y C
O N
T R
A C
T O
R
F
IR
E A
LA
R
M C
O N
T R
A C
T O
R
COMMENTS
TELECOMMUNICATIONS
CROSS CONNECTIONS AT THE DEMARCATION POINT X X
DIAL TONE SERVICES AND ASSOCIATED RACKS AND EQUIPMENT X X
NETWORK ROUTER X X
NETWORK ACCESS & DISTRIBUTION SWITCHES X X
NETWORK SERVERS, OPERATING SYSTEM SOFTWARE X X
WORKSTATION COMPUTERS, OPERATING SYSTEM SOFTWARE, APPLICATION SOFTWARE, PRINTERS, COPIERS, CUSTOMER PREMISE EQUIPMENT
X X
COPPER PATCH CORDS AT WORKSTATION OUTLETS X X
WIRELESS ACCESS POINTS X X
COPPER PATCH CORDS AT PATCH PANELS TO ACCESS SWITCHES X X
ABOVEGROUND AND UNDERGROUND RACEWAY SYSTEM; INCLUDING HAND HOLES, PULL BOXES, CONDUITS, CABLE TRAYS, BACK BOXES, SLEEVES THRU WALLS AND FLOORS
X X
FLOOR BOXES, WALL BOXES AND SERVICE FITTINGS INCLUDING ELECTRICAL DEVICES AND EMPTY PLATES TO
ACCEPT TELECOMMUNICATION MODULES.
X X
COMMUNICATION BACKBOARDS X X
GROUNDING BUSBARS AND BOND TO BUILDING GROUND X X
RACEWAY SYSTEM GROUNDING; TO ASSURE CONTINUOUS GROUND THROUGHOUT X X
EQUIPMENT RACKS AND RACK MOUNTED POWER DISTRIBUTION UNITS (PDU) X X COORDINATE PDU WITH UPS TYPE(S)
RACK MOUNTED UNINTERRUPTABLE POWER SUPPLIES (UPS) X X
POPULATED FIBER AND COPPER PATCH PANELS X X
LADDER RACK IN TELECOMMUNICATION ROOMS X X
J-HOOKS PATHWAY FROM WORKSTATION STUB-UP ABOVE CEILING TO CABLE TRAY, TELECOMMUNICATION
ROOM, OR CONDUIT PATHWAY PROVIDED BY ELECTRICAL CONTRACTOR
X X
BONDING OF RACKS, CABINETS, LADDER RACK AND OTHER TELECOM CONTRACTOR PROVIDED EQUIPMENT TO
TELECOM GROUND BUS BAR
X X
WORKSTATION OUTLET FACEPLATES AND MODULAR PLUGS X X
HORIZONTAL CABLE BETWEEN WORKSTATION MODULAR PLUG AND PATCH PANEL INCLUDING TERMINATIONS X X
BACKBONE CABLE AND/OR PATCH CORDS BETWEEN EQUIPMENT ROOM DISTRIBUTION SWITCHES OR PATCH
PANELS INCLUDING TERMINATIONS
X X
BACKBONE CABLE BETWEEN SERVICE PROVIDER DEMARC AND DISTRIBUTION SWITCHES OR PATCH PANELS
INCLUDING TERMINATIONS
X X
SURGE PROTECTION DEVICES FOR COPPER CABLING TO EXTERIOR DEVICES X X CAMERAS ONLY
MEDIA FIBER TO COPPER CONVERTERS X X
FIRESTOPPING OF SLEEVES AFTER NETWORK CABLES ARE PULLED X X
IDENTIFICATION AND LABELING X X
PERMANENT LINK TESTING AND DOCUMENTATION AFTER INSTALLATION X X
RESPONSIBILITY MATRIX FOR AUDIO VISUAL SYSTEMS
AREA OF WORK / CATEGORY OF EQUIPMENT FURNISHED BY INSTALLED BY
NOTE:
THIS MATRIX IS INTENDED TO INDICATE A GENERAL LISTING OF THE WORK AND MATERIALS TO BE FURNISHED AND INSTALLED BY THE VARIOUS TRADES FOR COORDINATION PURPOSES ONLY. IT IS
NOT INTENDED TO TO BE ALL INCLUSIVE. EACH TRADE IS RESPONSIBLE FOR FURNISHING AND
INSTALLING THEIR RESPECTIVE COMPLETE AND WORKING SYSTEM. REFER TO DRAWINGS AND
SPECIFICATIONS FOR THE EXTENT OF WORK INVOLVED. GENERAL CONTRACTOR IS RESPONSIBLE
FOR CONFIRMING OWNER RESPONSIBILITIES WITH THE OWNER'S IT
DEPARTMENT.
O W
N E
R
E
LE
C T
R
IC
A L
C O
N T
R A
C T
O R
T E
LE
C
O M
C O
N T
R A
C T
O R
O W
N E
R H
IR
E
D A
/V C
O N
T R
A C
T O
R
S E
C U
R
IT
Y C
O N
T R
A C
T O
R
G E
N E
R A
L C
O N
T R
A C
T O
R
O W
N E
R
E
LE
C T
R
IC
A L
C O
N T
R A
C T
O R
T E
LE
C
O M
C O
N T
R A
C T
O R
O W
N E
R H
IR
E
D A
/V C
O N
T R
A C
T O
R
S E
C U
R
IT
Y C
O N
T R
A C
T O
R
G E
N E
R A
L C
O N
T R
A C
T O
R
COMMENTS
AUDIO / VISUAL SYSTEM
RACEWAY SYSTEM; INCLUDING PULL BOXES, CONDUITS, CABLE TRAYS, BACK BOXES, SLEEVES THRU WALLS
AND FLOORS
X X
FLOOR BOXES, WALL BOXES & POKE THROUGHS INCLUDING ELECTRICAL DEVICES AND EMPTY SPACE TO
ACCEPT AUDIO/VISUAL MODULES.
X X
AUDIO / VISUAL SYSTEM INTEGRATION HARDWARE AND SOFTWARE X X
FLAT PANEL DISPLAYS, PROJECTORS, PROJECTOR SCREENS AND MOUNTS X X
AUDIO SYSTEMS ASSOCIATED WITH A/V SYSTEM X X
CAMERAS ASSOCIATED WITH A/V SYSTEM X X
WIRELESS AND WIRED MICROPHONES ASSOCIATED WITH A/V SYSTEM X X
A/V RELATED CABLES AND TERMINATIONS (CAT6, HDMI, COAX, XLR, ETC.) X X
A/V MODULES, FACEPLATES AND JACKS X X
FIRESTOPPING OF SLEEVES AFTER A/V CABLES ARE PULLED X X
IDENTIFICATION AND LABELING X X
PERMANENT LINK TESTING AND DOCUMENTATION AFTER INSTALLATION X X
RESPONSIBILITY MATRIX FOR ELECTRONIC SAFETY AND SECURITY
AREA OF WORK / CATEGORY OF EQUIPMENT FURNISHED BY INSTALLED BY
NOTE:
THIS MATRIX IS INTENDED TO INDICATE A GENERAL LISTING OF THE WORK AND MATERIALS TO BE FURNISHED AND INSTALLED BY THE VARIOUS TRADES FOR COORDINATION PURPOSES ONLY. IT IS
NOT INTENDED TO TO BE ALL INCLUSIVE. EACH TRADE IS RESPONSIBLE FOR FURNISHING AND
INSTALLING THEIR RESPECTIVE COMPLETE AND WORKING SYSTEM. REFER TO DRAWINGS AND
SPECIFICATIONS FOR THE EXTENT OF WORK INVOLVED. GENERAL CONTRACTOR IS RESPONSIBLE
FOR CONFIRMING OWNER RESPONSIBILITIES WITH THE OWNER'S IT
DEPARTMENT.
O W
N E
R
E
LE
C T
R
IC
A L
C O
N T
R A
C T
O R
T E
LE
C
O M
C O
N T
R A
C T
O R
A /V
C O
N T
R A
C T
O R
O W
N E
R H
IR
E
D S
E C
U R
IT
Y
C O
N T
R A
C T
O R
F
IR
E A
LA
R
M C
O N
T R
A C
T O
R
O W
N E
R
E
LE
C T
R
IC
A L
C O
N T
R A
C T
O R
T E
LE
C
O M
C O
N T
R A
C T
O R
A /V
C O
N T
R A
C T
O R
O W
N E
R H
IR
E
D S
E C
U R
IT
Y
C O
N T
R A
C T
O R
F
IR
E A
LA
R
M C
O N
T R
A C
T O
R
COMMENTS
SECURITY SYSTEMS
ACCESS CONTROL SYSTEM INTEGRATION HARDWARE AND SOFTWARE X X
ACCESS CONTROL DEVICES (EXCLUDING DOOR HARDWARE) X X
POWER SUPPLIES FOR ACCESS CONTROL DEVICES X X
VIDEO SURVEILLANCE CAMERAS, NVR, INTEGRATION HARDWARE AND SOFTWARE X X
ABOVEGROUND AND UNDERGROUND RACEWAY SYSTEM; INCLUDING HAND HOLES, PULL BOXES, CONDUITS, CABLE TRAYS, BACK BOXES, SLEEVES THRU WALLS AND FLOORS
X X
SECURITY SYSTEM NETWORK CABLES AND PATCH CORDS X X INCLUDING UPLINK TO SWITCH
MEDIA FIBER TO COPPER CONVERTERS X X
SURGE PROTECTION DEVICES FOR COPPER CABLES TO EXTERIOR MOUNTED SECURITY DEVICES X X
FIRESTOPPING OF SLEEVES AFTER SECURITY CABLES (NON-NETWORK CABLES) ARE PULLED X X
IDENTIFICATION AND LABELING X X
PERMANENT LINK TESTING AND DOCUMENTATION AFTER INSTALLATION X X
RESPONSIBILITY MATRIX FOR FIRE SAFETY AND EMERGENCY COMMUNICATIONS
AREA OF WORK / CATEGORY OF EQUIPMENT FURNISHED BY INSTALLED BY
NOTE:
THIS MATRIX IS INTENDED TO INDICATE A GENERAL LISTING OF THE WORK AND MATERIALS TO BE
FURNISHED AND INSTALLED BY THE VARIOUS TRADES FOR COORDINATION PURPOSES ONLY. IT IS NOT INTENDED TO TO BE ALL INCLUSIVE. EACH TRADE IS RESPONSIBLE FOR FURNISHING AND
INSTALLING THEIR RESPECTIVE COMPLETE AND WORKING SYSTEM. REFER TO DRAWINGS AND
SPECIFICATIONS FOR THE EXTENT OF WORK INVOLVED. GENERAL CONTRACTOR IS RESPONSIBLE
FOR CONFIRMING OWNER RESPONSIBILITIES WITH THE OWNER'S IT
DEPARTMENT. O
W N
E R
E
LE
C T
R
IC
A L
C O
N T
R A
C T
O R
T E
LE
C
O M
C O
N T
R A
C T
O R
A /V
C O
N T
R A
C T
O R
S E
C U
R
IT
Y C
O N
T R
A C
T O
R
F
IR
E A
LA
R
M C
O N
T R
A C
T O
R
O W
N E
R
E
LE
C T
R
IC
A L
C O
N T
R A
C T
O R
T E
LE
C
O M
C O
N T
R A
C T
O R
A /V
C O
N T
R A
C T
O R
S E
C U
R
IT
Y C
O N
T R
A C
T O
R
F
IR
E A
LA
R
M C
O N
T R
A C
T O
R
COMMENTS
FIRE ALARM SYSTEM
FIRE ALARM CONTROL PANELS, ANNUNCIATORS, INITIATING DEVICES, NOTIFICATION APPLIANCES X X
UNDERGROUND CONDUITS, BACKBOXES, HAND HOLES, PULL BOXES X X
ABOVEGROUND CONDUITS, CABLE TRAYS, BACK BOXES, SLEEVES THRU WALLS AND FLOORS X X
SURGE PROTECTION DEVICES FOR EXTERIOR COPPER CABLES X X
FIRE STOPPING OF CONDUITS AND SLEEVES X X
IDENTIFICATION AND LABELING X X
PERMANENT LINK TESTING AND DOCUMENTATION AFTER INSTALLATION X X
ELECTRICAL GENERAL NOTES
1. WIRING SHALL BE COPPER, TYPE THHN/THWN-2 IN RACEWAY UNLESS NOTED OTHERWISE. RIGID
ELECTRICAL NON-METALLIC SCHEDULE 40 PVC SHALL BE USED IN SLABS AND BELOW GRADE ; RIGID STEEL CONDUIT (RSC) SHALL BE USED WHERE EXPOSED TO PHYSICAL DAMAGE; ELECTRICAL METALLIC TUBING (EMT) MAY BE USED ELSEWHERE WHERE APPROVED BY N.E.C. AND LOCAL CODES. FLEXIBLE METAL CONDUIT (FMC) SHALL BE STEEL AND SHALL BE USED TO CONNECT MOVEABLE EQUIPMENT AND/OR SUBJECT TO VIBRATION; LIQUID-TIGHT FLEXIBLE METALLIC CONDUIT (LFMC) SHALL BE USED
OUTDOORS OR WHERE SUBJECT TO MOISTURE.
2. CONDUIT SHALL BE STRAPPED IN ACCORDANCE WITH REQUIREMENTS OF N.E.C.
3. CONTRACTOR SHALL BOND AND GROUND SYSTEMS AND EQUIPMENT PER ARTICLE 250 OF N.E.C.
PROVIDE A GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH ARTICLE 250-122 N.E.C. ON ALL
RECEPTACLES AND POWER BRANCH CIRCUITS.
4. LIGHTING FIXTURES SHALL BE SECURELY FASTENED AND SUPPORTED PER N.E.C.
5. THE CONTRACTOR SHALL COORDINATE THE CIRCUIT REQUIREMENTS WITH THE MANUFACTURER OF THE
ACTUAL EQUIPMENT FURNISHED UNDER OTHER DIVISIONS OF WORK. THE CIRCUIT BREAKER, WIRE AND
CONDUIT SHALL BE SIZED AS RECOMMENDED BY THE EQUIPMENT MANUFACTURER.
6. CIRCUIT BREAKERS SHALL BE BOLT-IN TYPE.
7. PROVIDE A LAMINATED PLASTIC NAMEPLATE IDENTIFYING EACH NEW PANELBOARD, MOTOR STARTER
AND DISCONNECT SWITCH. LETTERING SHALL BE 1/2" MINIMUM AND SHALL IDENTIFY EQUIPMENT
SERVED, FEEDER ORIGINATION AND CIRCUIT NUMBER. SECURE NAMEPLATE WITH SCREWS TO
EQUIPMENT TO BE IDENTIFIED. PLASTIC TAPE IS NOT APPROVED.
8. ELECTRICAL CONNECTIONS AND ASSOCIATED ROUGH-IN FOR EQUIPMENT FURNISHED BY OWNER OR
OTHER TRADE CONTRACTORS SHALL BE CONSTRUCTED BY ELECTRICAL CONTRACTOR. VERIFY
CONNECTION SIZE, RATING, AND LOCATION WITH EQUIPMENT PROVIDER PRIOR TO ROUGH-IN.
9. A 120V/20A GFI RECEPTACLE SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND WITHIN 25 FT OF THE HEATING, AIR-CONDITIONING, AND REFRIGERATION
EQUIPMENT. THE OUTLET SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT
DISCONNECTING MEANS.
10. DEVICE MOUNTING HEIGHTS INDICATED SHALL BE TO DEVICE CENTER LINE.
11. EXTERIOR DEVICES SHALL BE WEATHER PROOF ENCLOSURES AND GFI RATED IN ACCORDANCE WITH
N.E.C. INSTALLER REQUIRED TO VERIFY PRIOR TO ORDERING MATERIALS.
12. EACH FEEDER, UNGROUNDED CONDUCTOR, AND GROUNDED CONDUCTOR SHALL BE IDENTIFIED BY
PHASE OR LINE AND SYSTEM AT ALL TERMINATION, CONNECTION, AND SPLICE POINTS.
DUPLEX RECEPTACLE - 120 VOLT, 20 AMP, 3 POLE GROUNDING TYPE, MOUNT
18" AFF WITH GROUND PRONG UP UNLESS NOTED OTHERWISE.
DUPLEX…