33 77 23 DS - 1200A~1.xlsx

XLSX spreadsheet 179 KB Posted

Attached to
CRCBC-06 15kV Power Circuit Breakers
Solicitation number
69CRC-S3446
Issued by
Clark County, Nevada

About this file

This document is a technical data sheet for a vacuum medium voltage circuit breaker, specifically for the Boulder City Substation #3 project. The procurement involves four (4) 12.5kV 1200A circuit breakers designated as feeder breakers, with a quote date of 7/16/25 and project number 185915. The circuit breakers are intended for a substation application with no field services required.

The electrical specifications indicate the breakers will operate at a maximum voltage of 15.5 kV, with a rated continuous current of 1200A and a short-circuit current rating of 25 kA. The breakers are designed for an effectively grounded system with an X/R ratio of 5.66, and are classified as S2 circuit breakers. Environmental service conditions specify an ambient temperature range of -30°C to +40°C for normal climates. The quote appears to be in preparation for equipment procurement, with the supplier expected to provide specific capacitor current switching ratings and complete certain technical parameters.

View the file

Other files

File Type Posted
CRCBC-06 15kV Circuit Breaker_Bid Contract_WORD.docx DOCX document
Quote Instructions.pdf PDF
33 77 23 - Vacuum Medium Voltage Circuit Breakers.pdf PDF
33 77 23 DS - 2000A~1.xlsx XLSX spreadsheet

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Data Sheet ERROR:#VALUE! 33 77 23 Vacuum Medium Voltage Circuit Breaker Data Sheet Equipment Tag & Description Supplier Name:

Contract:[XXX][XXX]
By:F. Oxler12.5kV 1200A Circuit BreakerQuote Number:
Project Name:Boulder City Substation #3Chk:C. Ma[XXX]
Project Number:185915Rev:1Quote Date:
Date:7/16/25[XXX]
PARAMETERUNITNOTESSPECIFIED DATASUPPLIER PROVIDED
GENERAL:
Substation Name:-Boulder City Sub #3
Quantity Of Circuit Breakers:QTY4
Application:-Feeder Breaker
Field Services-Not Required
ELECTRICAL REQUIREMENTS:
Rated Maximum VoltagekV, RMS15.5
Basic Impulse Lightning Level (BIL)kV, Peak110
Basic Switching Level (BSL)kV, PeakN/A
Rated Continuous CurrentA1200
Rated Short-Circuit Current:kA25
Rated Interrupting Time:m-sec50 (3 cycle)
System Neutral-Effectively grounded
System X/R Ratio-5.66
Power-Frequency 1 Minute Dry Withstand Voltage:kV50
Lightning Impulse Full Wave Withstand Voltage:kV110
Lightning Impulse Chopped Wave Withstand Voltage (if applicable):kV142
Switching Impulse Terminal-Ground Withstand (Breaker Closed):kVN/A
Switching Impulse Terminal-Terminal Withstand (On One Phase, Breaker Open):kVN/A
Capacitor current switching rating: (C0/C1/C2)-Supplier to Specify
Circuit Breaker Classification: (S1/S2/NA)-S2
First Pole to Clear Factor (Kpp)-1.5
TRV Envelope Parameters:-Supplier to provide
SERVICE CONDITIONS:
Ambient Temperature Range°C−30 °C to +40 °C for normal climates
Maximum Solar Radiation IntensityWatts/meter2<1044
AltitudeMeters<1000
Maximum Ambient Pollution-Heavy
Ice Coatingmm20
Maximum Wind Speedm/sec50
Seismic Qualification Level:-Moderate
MECHANICAL REQUIREMENTS:
Independent Pole Operation Required?-NO
Operating Duty:-O-0.3sec-CO-15sec-CO
Mechanical Endurance (Operations): (M1/M2)-Supplier to Specify
CIRCUIT BREAKER CONSTRUCTION:
Heaters Required In The Tank For Low Temperature:-Supplier to Specify
Temperature Below Which Heater Operation Is Required ( °C)°CSupplier to Specify
Type of Circuit Breaker Operating Mechanism System.-Spring/Hydraulic/Pneumatic/OtherMagnetic
Design Pressure Of Main Circuit Breaker TankKpaSupplier to Specify
Design Pressure Of Compressed Gas/Fluid Stored Energy System (If Applicable)KpaSupplier to Specify
Circuit Breaker Exterior Coating Color:-Supplier to Specify
Circuit Breaker Interior Coating Color:-Supplier to Specify
Bushing Terminal Pad:Supplier to SpecifyProvide the NEMA type and material
CIRCUIT BREAKER BUSHINGS:
Bushing Construction:-Manufacturer to Specify
Minimum Withstand Cantilever Load Level:-Level 1
Bushing Creepage-Supplier to Specify
Bushing Color:-Supplier to Specify
CURRENT TRANSFORMERS:
1Z,3Z,5Z Winding-Not Required
CT Ratio--
TerminationsAccuracy/Burden--
|||TRF--
ZZZ1Y,3Y,5Y Winding-Not Required
|||CT Ratio--
YYYAccuracy/Burden--
|||TRF--
XXX1X,3X,5X Winding-Required
|||CT Ratio-1200:5 MR
135Accuracy/Burden-C800
Breaker Bushing OrientationTRF-2
2461X,3X,5X Winding-Required
|||CT Ratio-1200:5 MR
XXXAccuracy/Burden-C800
|||TRF-2
YYY1Y,3Y,5Y Winding-Not Required
|||CT Ratio--
ZZZAccuracy/Burden--
|||TRF--
Terminations1Z,3Z,5Z Winding-Not Required
CT Ratio--
Accuracy/Burden--
TRF--
CIRCUIT BREAKER LOW VOLTAGE/ANCILLARY DEVICE REQUIREMENTS:
Spare Auxiliary Contact:QTY8 Normal Close, 8 Normal Open
Terminal Blocks Type:-Rated 600V and 30A
CT Shorting Terminal Blocks-Shorting Type with Shorting Bars and Screws
Control Enclosure NEMA Rating:-3R
Station Low Voltage AC Power Supply-1 phase, 240 V ac
Charging Motor Power Supply DC or AC (if applicable)1 phase, 240 V ac
Station Low Voltage DC Supply-125 V dc
BPS Separation Required?-Not Required
ANNUNCIATOR/DATA CONCENTRATOR REQUIREMENTS:
Device Model:-
Points To Be Monitored:-
Low SF6 Gas Pressure Alarm-NO
Low SF6 Gas Pressure Trip and Block Close-NO
Pole Disagreement (for independent pole breakers)-NO
Failure of Operating Mechanism to Re-Charge-NO
DC Motor undervoltage alarm-NO
AC motor undervoltage alarm-YES
Breaker Maintenance Switch Status-YES
Low Hydraulic Pressure or Low Spring Charge Alarm-YES
Excessive mechanism run-time alarm-NO
CLOSING RESISTORS:
Closing Resistor Required:-Not Required
Closing Resistor Value (Hot)ohms-
Closing Resistor Value (Cold)ohms-
Insertion Time-
SYNCHRONOUS SWITCHING CONTROL:
Synchronous Switching Control Required:-Not Required-
Description Of Controlled Switching System, Including Operation, Manufacturer/Model.--
GRADING CAPACITOR :
Grading Capacitor :-Supplier to Specify
ADDITIONAL REQUIREMENTS:
GPS triaxial impact and environmental recorders:-Not Required
List Replacement Parts (Not Already Included In Part 2.10):-Supplier's Recommendation
List Maintenance Equipment Required (Not Already Included In Part 2.10)-Supplier's Recommendation
Spare SF6 Refill Tank Required?-Not Required
IEC 61850 Compliance Required?-Not Required
END OF DATA SHEET

Drop Down Menus Field Choices

ChoiceRequired
Manufacturer to Specify (if needed)
Choice w/ Optional PricingRequired
Manufacturer to Specify (if needed)
Price as Optional
ApplicationLine Switching
Transformer Switching
Cap Bank Switching
Interrupting Time33 (2 cycle)
50 (3 cycle)
System NeutralEffectively grounded
Non-grounded
Resistor grounded
Pollution LevelLight
Medium
Heavy
Very Heavy
Seismic QualificationLow
Moderate
High
Choice 2Required
Not Required
Choice 3Yes
No
Capacitor Current Switch RatingClass C0
Class C1
Class C2
Mechanical EnduranceM1
M2
AC1 phase, 120 V ac
3 phase, 208Y/120 V ac
1 phase, 240 V ac
3 phase, 240 V ac
Other - specify
DC48 V DC
125 V DC
250 V DC
ApplicableApplicable
Not Required
Bushing Construction:Composite
Porcelain
Manufacturer to Specify
Cantilever Load Level:Level 1
Level 2
AC/DC ProtectionFused Disconnect
Breaker
SynchronousCapacitor
Reactor
Transformer Remnant Flux
Not Required
NEMA3R
4
4X
CT Ratios600:5 MR
1200:5 MR
2000:5 MR
3000:5 MR
4000:5 MR
5000:5 MR
CT Accuracy ClassC100
C200
C400
C800
TRF1.0
1.33
1.5
2.0
3.0
4.0
Supply Value
Manufacturer to Specify
System NeutralEffectively grounded
Non-grounded
Resistor grounded
Pollution LevelLight
Medium
Heavy
Very Heavy
Choice 4Required
Not Required
Manufacturer to Specify
Yes
No
Kpp1.3
1.5
Ambient air temperature−50 °C to +40 °C for extremely cold climates
−40 °C to +40 °C for very cold climates
−30 °C to +40 °C for normal climates
−5 °C and +55 °C for very hot climates
−15 °C and +55 °C for hot and dry desert regions
Reclosing dutyO-0.3sec-CO-15sec-CO
O-0.3sec-CO-3min-CO
O-15sec-CO-3min-CO

IEEE Tables image2.png