33 77 23 DS - 1200A~1.xlsx
XLSX spreadsheet 179 KB Posted
- Attached to
- CRCBC-06 15kV Power Circuit Breakers
- Solicitation number
- 69CRC-S3446
- Issued by
- Clark County, Nevada
About this file
This document is a technical data sheet for a vacuum medium voltage circuit breaker, specifically for the Boulder City Substation #3 project. The procurement involves four (4) 12.5kV 1200A circuit breakers designated as feeder breakers, with a quote date of 7/16/25 and project number 185915. The circuit breakers are intended for a substation application with no field services required.
The electrical specifications indicate the breakers will operate at a maximum voltage of 15.5 kV, with a rated continuous current of 1200A and a short-circuit current rating of 25 kA. The breakers are designed for an effectively grounded system with an X/R ratio of 5.66, and are classified as S2 circuit breakers. Environmental service conditions specify an ambient temperature range of -30°C to +40°C for normal climates. The quote appears to be in preparation for equipment procurement, with the supplier expected to provide specific capacitor current switching ratings and complete certain technical parameters.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| CRCBC-06 15kV Circuit Breaker_Bid Contract_WORD.docx | DOCX document | |
| Quote Instructions.pdf | ||
| 33 77 23 - Vacuum Medium Voltage Circuit Breakers.pdf | ||
| 33 77 23 DS - 2000A~1.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Data Sheet ERROR:#VALUE! 33 77 23 Vacuum Medium Voltage Circuit Breaker Data Sheet Equipment Tag & Description Supplier Name:
| Contract: | [XXX] | [XXX] | |||
| By: | F. Oxler | 12.5kV 1200A Circuit Breaker | Quote Number: | ||
| Project Name: | Boulder City Substation #3 | Chk: | C. Ma | [XXX] | |
| Project Number: | 185915 | Rev: | 1 | Quote Date: | |
| Date: | 7/16/25 | [XXX] |
| PARAMETER | UNIT | NOTES | SPECIFIED DATA | SUPPLIER PROVIDED | |||
| GENERAL: | |||||||
| Substation Name: | - | Boulder City Sub #3 | |||||
| Quantity Of Circuit Breakers: | QTY | 4 | |||||
| Application: | - | Feeder Breaker | |||||
| Field Services | - | Not Required | |||||
| ELECTRICAL REQUIREMENTS: | |||||||
| Rated Maximum Voltage | kV, RMS | 15.5 | |||||
| Basic Impulse Lightning Level (BIL) | kV, Peak | 110 | |||||
| Basic Switching Level (BSL) | kV, Peak | N/A | |||||
| Rated Continuous Current | A | 1200 | |||||
| Rated Short-Circuit Current: | kA | 25 | |||||
| Rated Interrupting Time: | m-sec | 50 (3 cycle) | |||||
| System Neutral | - | Effectively grounded | |||||
| System X/R Ratio | - | 5.66 | |||||
| Power-Frequency 1 Minute Dry Withstand Voltage: | kV | 50 | |||||
| Lightning Impulse Full Wave Withstand Voltage: | kV | 110 | |||||
| Lightning Impulse Chopped Wave Withstand Voltage (if applicable): | kV | 142 | |||||
| Switching Impulse Terminal-Ground Withstand (Breaker Closed): | kV | N/A | |||||
| Switching Impulse Terminal-Terminal Withstand (On One Phase, Breaker Open): | kV | N/A | |||||
| Capacitor current switching rating: (C0/C1/C2) | - | Supplier to Specify | |||||
| Circuit Breaker Classification: (S1/S2/NA) | - | S2 | |||||
| First Pole to Clear Factor (Kpp) | - | 1.5 | |||||
| TRV Envelope Parameters: | - | Supplier to provide | |||||
| SERVICE CONDITIONS: | |||||||
| Ambient Temperature Range | °C | −30 °C to +40 °C for normal climates | |||||
| Maximum Solar Radiation Intensity | Watts/meter2 | <1044 | |||||
| Altitude | Meters | <1000 | |||||
| Maximum Ambient Pollution | - | Heavy | |||||
| Ice Coating | mm | 20 | |||||
| Maximum Wind Speed | m/sec | 50 | |||||
| Seismic Qualification Level: | - | Moderate | |||||
| MECHANICAL REQUIREMENTS: | |||||||
| Independent Pole Operation Required? | - | NO | |||||
| Operating Duty: | - | O-0.3sec-CO-15sec-CO | |||||
| Mechanical Endurance (Operations): (M1/M2) | - | Supplier to Specify | |||||
| CIRCUIT BREAKER CONSTRUCTION: | |||||||
| Heaters Required In The Tank For Low Temperature: | - | Supplier to Specify | |||||
| Temperature Below Which Heater Operation Is Required ( °C) | °C | Supplier to Specify | |||||
| Type of Circuit Breaker Operating Mechanism System. | - | Spring/Hydraulic/Pneumatic/Other | Magnetic | ||||
| Design Pressure Of Main Circuit Breaker Tank | Kpa | Supplier to Specify | |||||
| Design Pressure Of Compressed Gas/Fluid Stored Energy System (If Applicable) | Kpa | Supplier to Specify | |||||
| Circuit Breaker Exterior Coating Color: | - | Supplier to Specify | |||||
| Circuit Breaker Interior Coating Color: | - | Supplier to Specify | |||||
| Bushing Terminal Pad: | Supplier to Specify | Provide the NEMA type and material | |||||
| CIRCUIT BREAKER BUSHINGS: | |||||||
| Bushing Construction: | - | Manufacturer to Specify | |||||
| Minimum Withstand Cantilever Load Level: | - | Level 1 | |||||
| Bushing Creepage | - | Supplier to Specify | |||||
| Bushing Color: | - | Supplier to Specify | |||||
| CURRENT TRANSFORMERS: | |||||||
| 1Z,3Z,5Z Winding | - | Not Required | |||||
| CT Ratio | - | - | |||||
| Terminations | Accuracy/Burden | - | - | ||||
| | | | | | | TRF | - | - | ||
| Z | Z | Z | 1Y,3Y,5Y Winding | - | Not Required | ||
| | | | | | | CT Ratio | - | - | ||
| Y | Y | Y | Accuracy/Burden | - | - | ||
| | | | | | | TRF | - | - | ||
| X | X | X | 1X,3X,5X Winding | - | Required | ||
| | | | | | | CT Ratio | - | 1200:5 MR | ||
| 1 | 3 | 5 | Accuracy/Burden | - | C800 | ||
| Breaker Bushing Orientation | TRF | - | 2 | ||||
| 2 | 4 | 6 | 1X,3X,5X Winding | - | Required | ||
| | | | | | | CT Ratio | - | 1200:5 MR | ||
| X | X | X | Accuracy/Burden | - | C800 | ||
| | | | | | | TRF | - | 2 | ||
| Y | Y | Y | 1Y,3Y,5Y Winding | - | Not Required | ||
| | | | | | | CT Ratio | - | - | ||
| Z | Z | Z | Accuracy/Burden | - | - | ||
| | | | | | | TRF | - | - | ||
| Terminations | 1Z,3Z,5Z Winding | - | Not Required | ||||
| CT Ratio | - | - | |||||
| Accuracy/Burden | - | - | |||||
| TRF | - | - | |||||
| CIRCUIT BREAKER LOW VOLTAGE/ANCILLARY DEVICE REQUIREMENTS: | |||||||
| Spare Auxiliary Contact: | QTY | 8 Normal Close, 8 Normal Open | |||||
| Terminal Blocks Type: | - | Rated 600V and 30A | |||||
| CT Shorting Terminal Blocks | - | Shorting Type with Shorting Bars and Screws | |||||
| Control Enclosure NEMA Rating: | - | 3R | |||||
| Station Low Voltage AC Power Supply | - | 1 phase, 240 V ac | |||||
| Charging Motor Power Supply DC or AC (if applicable) | 1 phase, 240 V ac | ||||||
| Station Low Voltage DC Supply | - | 125 V dc | |||||
| BPS Separation Required? | - | Not Required | |||||
| ANNUNCIATOR/DATA CONCENTRATOR REQUIREMENTS: | |||||||
| Device Model: | - | ||||||
| Points To Be Monitored: | - | ||||||
| Low SF6 Gas Pressure Alarm | - | NO | |||||
| Low SF6 Gas Pressure Trip and Block Close | - | NO | |||||
| Pole Disagreement (for independent pole breakers) | - | NO | |||||
| Failure of Operating Mechanism to Re-Charge | - | NO | |||||
| DC Motor undervoltage alarm | - | NO | |||||
| AC motor undervoltage alarm | - | YES | |||||
| Breaker Maintenance Switch Status | - | YES | |||||
| Low Hydraulic Pressure or Low Spring Charge Alarm | - | YES | |||||
| Excessive mechanism run-time alarm | - | NO | |||||
| CLOSING RESISTORS: | |||||||
| Closing Resistor Required: | - | Not Required | |||||
| Closing Resistor Value (Hot) | ohms | - | |||||
| Closing Resistor Value (Cold) | ohms | - | |||||
| Insertion Time | - | ||||||
| SYNCHRONOUS SWITCHING CONTROL: | |||||||
| Synchronous Switching Control Required: | - | Not Required | - | ||||
| Description Of Controlled Switching System, Including Operation, Manufacturer/Model. | - | - | |||||
| GRADING CAPACITOR : | |||||||
| Grading Capacitor : | - | Supplier to Specify | |||||
| ADDITIONAL REQUIREMENTS: | |||||||
| GPS triaxial impact and environmental recorders: | - | Not Required | |||||
| List Replacement Parts (Not Already Included In Part 2.10): | - | Supplier's Recommendation | |||||
| List Maintenance Equipment Required (Not Already Included In Part 2.10) | - | Supplier's Recommendation | |||||
| Spare SF6 Refill Tank Required? | - | Not Required | |||||
| IEC 61850 Compliance Required? | - | Not Required | |||||
| END OF DATA SHEET |
Drop Down Menus Field Choices
| Choice | Required |
| Manufacturer to Specify (if needed) | |
| Choice w/ Optional Pricing | Required |
| Manufacturer to Specify (if needed) | |
| Price as Optional | |
| Application | Line Switching |
| Transformer Switching | |
| Cap Bank Switching | |
| Interrupting Time | 33 (2 cycle) |
| 50 (3 cycle) | |
| System Neutral | Effectively grounded |
| Non-grounded | |
| Resistor grounded | |
| Pollution Level | Light |
| Medium | |
| Heavy | |
| Very Heavy | |
| Seismic Qualification | Low |
| Moderate | |
| High | |
| Choice 2 | Required |
| Not Required | |
| Choice 3 | Yes |
| No | |
| Capacitor Current Switch Rating | Class C0 |
| Class C1 | |
| Class C2 | |
| Mechanical Endurance | M1 |
| M2 | |
| AC | 1 phase, 120 V ac |
| 3 phase, 208Y/120 V ac | |
| 1 phase, 240 V ac | |
| 3 phase, 240 V ac | |
| Other - specify | |
| DC | 48 V DC |
| 125 V DC | |
| 250 V DC | |
| Applicable | Applicable |
| Not Required | |
| Bushing Construction: | Composite |
| Porcelain | |
| Manufacturer to Specify |
| Cantilever Load Level: | Level 1 |
| Level 2 | |
| AC/DC Protection | Fused Disconnect |
| Breaker | |
| Synchronous | Capacitor |
| Reactor | |
| Transformer Remnant Flux | |
| Not Required | |
| NEMA | 3R |
| 4 | |
| 4X | |
| CT Ratios | 600:5 MR |
| 1200:5 MR | |
| 2000:5 MR | |
| 3000:5 MR | |
| 4000:5 MR | |
| 5000:5 MR | |
| CT Accuracy Class | C100 |
| C200 | |
| C400 | |
| C800 | |
| TRF | 1.0 |
| 1.33 | |
| 1.5 | |
| 2.0 | |
| 3.0 | |
| 4.0 | |
| Supply Value | |
| Manufacturer to Specify | |
| System Neutral | Effectively grounded |
| Non-grounded | |
| Resistor grounded | |
| Pollution Level | Light |
| Medium | |
| Heavy | |
| Very Heavy | |
| Choice 4 | Required |
| Not Required | |
| Manufacturer to Specify | |
| Yes | |
| No | |
| Kpp | 1.3 |
| 1.5 | |
| Ambient air temperature | −50 °C to +40 °C for extremely cold climates |
| −40 °C to +40 °C for very cold climates | |
| −30 °C to +40 °C for normal climates | |
| −5 °C and +55 °C for very hot climates | |
| −15 °C and +55 °C for hot and dry desert regions | |
| Reclosing duty | O-0.3sec-CO-15sec-CO |
| O-0.3sec-CO-3min-CO | |
| O-15sec-CO-3min-CO |
IEEE Tables image2.png
File details come from the government source that posted it. Updated .