33 75 19 DS~1.xlsx
XLSX spreadsheet 176 KB Posted
- Attached to
- CRCBC-05 69kV Circuit Breakers
- Solicitation number
- 69CRC-S3445
- Issued by
- Clark County, Nevada
About this file
This document is a detailed equipment data sheet for a high voltage circuit breaker procurement for Boulder City Substation #3, likely involving a municipal or utility agency. The project involves purchasing two 69kV 2000A circuit breakers with specific electrical requirements, including a rated maximum voltage of 72.5 kV, basic impulse lightning level of 350 kV peak, and a rated short-circuit current of 40 kA. The circuit breakers are intended for transformer switching, with no field services required. The quote is dated 6/26/25, with a project number of 185915 and revision 0.
The equipment specifications indicate operational parameters for standard utility infrastructure, with an ambient temperature range of -30°C to +40°C and compliance with specific technical standards. The circuit breakers are classified as S2 with a first pole to clear factor of 1.5, designed for an effectively grounded system with a system X/R ratio of 17. While pricing details are not explicitly provided in the document, the comprehensive technical specifications suggest a precise procurement process for critical electrical infrastructure components, likely through a competitive bidding or proposal process typical of municipal utility projects.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 33 75 19 - Gas High Voltage Circuit Breakers.pdf | ||
| CRCBC-05 69kV Circuit Breaker_Bid Contract_WORD.docx | DOCX document | |
| Quote Instructions.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Data Sheet ERROR:#VALUE! 33 75 19 Gas High Voltage Circuit Breaker Data Sheet Equipment Tag & Description Supplier Name:
| Contract: | [XXX] | [XXX] | |||
| By: | F. Oxler | 69kV 2000A Circuit Breaker | Quote Number: | ||
| Project Name: | Boulder City Substation #3 | Chk: | C. Ma | [XXX] | |
| Project Number: | 185915 | Rev: | 0 | Quote Date: | |
| Date: | 6/26/25 | [XXX] |
| PARAMETER | UNIT | NOTES | SPECIFIED DATA | SUPPLIER PROVIDED | |||
| GENERAL: | |||||||
| Substation Name: | - | Boulder City Sub #3 | |||||
| Quantity Of Circuit Breakers: | QTY | 2 | |||||
| Application: | - | Transformer Switching | |||||
| Field Services | - | Not Required | |||||
| ELECTRICAL REQUIREMENTS: | |||||||
| Rated Maximum Voltage | kV, RMS | 72.5 | |||||
| Basic Impulse Lightning Level (BIL) | kV, Peak | 350 | |||||
| Basic Switching Level (BSL) | kV, Peak | N/A | |||||
| Rated Continuous Current | A | 2000 | |||||
| Rated Short-Circuit Current: | kA | 40 | |||||
| Rated Interrupting Time: | m-sec | 50 (3 cycle) | |||||
| System Neutral | - | Effectively grounded | |||||
| System X/R Ratio | - | 17 | |||||
| Power-Frequency 1 Minute Dry Withstand Voltage: | kV | 160 | |||||
| Lightning Impulse Full Wave Withstand Voltage: | kV | 350 | |||||
| Lightning Impulse Chopped Wave Withstand Voltage (if applicable): | kV | 452 | |||||
| Switching Impulse Terminal-Ground Withstand (Breaker Closed): | kV | N/A | |||||
| Switching Impulse Terminal-Terminal Withstand (On One Phase, Breaker Open): | kV | N/A | |||||
| Capacitor current switching rating: (C0/C1/C2) | - | Supplier to Specify | |||||
| Circuit Breaker Classification: (S1/S2/NA) | - | S2 | |||||
| First Pole to Clear Factor (Kpp) | - | 1.5 | |||||
| TRV Envelope Parameters: | - | C37.06.1 Compliance | |||||
| SERVICE CONDITIONS: | |||||||
| Ambient Temperature Range | °C | −30 °C to +40 °C for normal climates | |||||
| Maximum Solar Radiation Intensity | Watts/meter2 | <1044 | |||||
| Altitude | Meters | <1000 | |||||
| Maximum Ambient Pollution | - | Heavy | |||||
| Ice Coating | mm | 20 | |||||
| Maximum Wind Speed | m/sec | 50 | |||||
| Seismic Qualification Level: | - | Moderate | |||||
| MECHANICAL REQUIREMENTS: | |||||||
| Independent Pole Operation Required? | - | NO | |||||
| Operating Duty: | - | O-0.3sec-CO-15sec-CO | |||||
| Mechanical Endurance (Operations): (M1/M2) | - | M1 | |||||
| CIRCUIT BREAKER CONSTRUCTION: | |||||||
| Heaters Required In The Tank For Low Temperature: | - | Supplier to Specify | |||||
| Temperature Below Which Heater Operation Is Required ( °C) | °C | Supplier to Specify | |||||
| Type of Circuit Breaker Operating Mechanism System. | - | Spring/Hydraulic/Pneumatic/Other | Supplier to Specify | ||||
| Design Pressure Of Main Circuit Breaker Tank | Kpa | Supplier to Specify | |||||
| Design Pressure Of Compressed Gas/Fluid Stored Energy System (If Applicable) | Kpa | Supplier to Specify | |||||
| Circuit Breaker Exterior Coating Color: | - | Supplier to Specify | |||||
| Circuit Breaker Interior Coating Color: | - | Supplier to Specify | |||||
| Bushing Terminal Pad: | Supplier to Specify | Provide the NEMA type and material | |||||
| CIRCUIT BREAKER BUSHINGS: | |||||||
| Bushing Construction: | - | Manufacturer to Specify | |||||
| Minimum Withstand Cantilever Load Level: | - | Level 1 | |||||
| Bushing Creepage | - | Supplier to Specify | |||||
| Bushing Color: | - | Supplier to Specify | |||||
| CURRENT TRANSFORMERS: | |||||||
| 1Z,3Z,5Z Winding | - | Not Required | |||||
| CT Ratio | - | - | |||||
| Terminations | Accuracy/Burden | - | - | ||||
| | | | | | | TRF | - | - | ||
| Z | Z | Z | 1Y,3Y,5Y Winding | - | Required | ||
| | | | | | | CT Ratio | - | 1200:5 MR | ||
| Y | Y | Y | Accuracy/Burden | - | C800 | ||
| | | | | | | TRF | - | 2 | ||
| X | X | X | 1X,3X,5X Winding | - | Required | ||
| | | | | | | CT Ratio | - | 1200:5 MR | ||
| 1 | 3 | 5 | Accuracy/Burden | - | C800 | ||
| Breaker Bushing Orientation | TRF | - | 2 | ||||
| 2 | 4 | 6 | 1X,3X,5X Winding | - | Required | ||
| | | | | | | CT Ratio | - | 1200:5 MR | ||
| X | X | X | Accuracy/Burden | - | C800 | ||
| | | | | | | TRF | - | 2 | ||
| Y | Y | Y | 1Y,3Y,5Y Winding | - | Required | ||
| | | | | | | CT Ratio | - | 1200:5 MR | ||
| Z | Z | Z | Accuracy/Burden | - | C800 | ||
| | | | | | | TRF | - | 2 | ||
| Terminations | 1Z,3Z,5Z Winding | - | Not Required | ||||
| CT Ratio | - | - | |||||
| Accuracy/Burden | - | - | |||||
| TRF | - | - | |||||
| CIRCUIT BREAKER LOW VOLTAGE/ANCILLARY DEVICE REQUIREMENTS: | |||||||
| Spare Auxiliary Contact: | QTY | 8 Normal Close, 8 Normal Open | |||||
| Terminal Blocks Type: | - | Rated 600V and 30A | |||||
| CT Shorting Terminal Blocks | - | Shorting Type with Shorting Bars and Screws | |||||
| Control Enclosure NEMA Rating: | - | 3R | |||||
| Station Low Voltage AC Power Supply | - | 1 phase, 240 V ac | |||||
| Charging Motor Power Supply DC or AC (if applicable) | 1 phase, 240 V ac | ||||||
| Station Low Voltage DC Supply | - | 125 V dc | |||||
| BPS Separation Required? | - | Not Required | |||||
| ANNUNCIATOR/DATA CONCENTRATOR REQUIREMENTS: | |||||||
| Device Model: | - | ||||||
| Points To Be Monitored: | - | ||||||
| Low SF6 Gas Pressure Alarm | - | YES | |||||
| Low SF6 Gas Pressure Trip and Block Close | - | YES | |||||
| Pole Disagreement (for independent pole breakers) | - | NO | |||||
| Failure of Operating Mechanism to Re-Charge | - | NO | |||||
| DC Motor undervoltage alarm | - | NO | |||||
| AC motor undervoltage alarm | - | YES | |||||
| Breaker Maintenance Switch Status | - | YES | |||||
| Low Hydraulic Pressure or Low Spring Charge Alarm | - | YES | |||||
| Excessive mechanism run-time alarm | - | NO | |||||
| CLOSING RESISTORS: | |||||||
| Closing Resistor Required: | - | Not Required | |||||
| Closing Resistor Value (Hot) | ohms | - | |||||
| Closing Resistor Value (Cold) | ohms | - | |||||
| Insertion Time | - | ||||||
| SYNCHRONOUS SWITCHING CONTROL: | |||||||
| Synchronous Switching Control Required: | - | Not Required | - | ||||
| Description Of Controlled Switching System, Including Operation, Manufacturer/Model. | - | - | |||||
| GRADING CAPACITOR : | |||||||
| Grading Capacitor : | - | Supplier to Specify | |||||
| ADDITIONAL REQUIREMENTS: | |||||||
| GPS triaxial impact and environmental recorders: | - | Not Required | |||||
| List Replacement Parts (Not Already Included In Part 2.10): | - | Supplier's Recommendation | |||||
| List Maintenance Equipment Required (Not Already Included In Part 2.10) | - | Supplier's Recommendation | |||||
| Spare SF6 Refill Tank Required? | - | Not Required | |||||
| IEC 61850 Compliance Required? | - | Not Required | |||||
| END OF DATA SHEET |
Drop Down Menus Field Choices
| Choice | Required |
| Manufacturer to Specify (if needed) | |
| Choice w/ Optional Pricing | Required |
| Manufacturer to Specify (if needed) | |
| Price as Optional | |
| Application | Line Switching |
| Transformer Switching | |
| Cap Bank Switching | |
| Interrupting Time | 33 (2 cycle) |
| 50 (3 cycle) | |
| System Neutral | Effectively grounded |
| Non-grounded | |
| Resistor grounded | |
| Pollution Level | Light |
| Medium | |
| Heavy | |
| Very Heavy | |
| Seismic Qualification | Low |
| Moderate | |
| High | |
| Choice 2 | Required |
| Not Required | |
| Choice 3 | Yes |
| No | |
| Capacitor Current Switch Rating | Class C0 |
| Class C1 | |
| Class C2 | |
| Mechanical Endurance | M1 |
| M2 | |
| AC | 1 phase, 120 V ac |
| 3 phase, 208Y/120 V ac | |
| 1 phase, 240 V ac | |
| 3 phase, 240 V ac | |
| Other - specify | |
| DC | 48 V DC |
| 125 V DC | |
| 250 V DC | |
| Applicable | Applicable |
| Not Required | |
| Bushing Construction: | Composite |
| Porcelain | |
| Manufacturer to Specify |
| Cantilever Load Level: | Level 1 |
| Level 2 | |
| AC/DC Protection | Fused Disconnect |
| Breaker | |
| Synchronous | Capacitor |
| Reactor | |
| Transformer Remnant Flux | |
| Not Required | |
| NEMA | 3R |
| 4 | |
| 4X | |
| CT Ratios | 600:5 MR |
| 1200:5 MR | |
| 2000:5 MR | |
| 3000:5 MR | |
| 4000:5 MR | |
| 5000:5 MR | |
| CT Accuracy Class | C100 |
| C200 | |
| C400 | |
| C800 | |
| TRF | 1.0 |
| 1.33 | |
| 1.5 | |
| 2.0 | |
| 3.0 | |
| 4.0 | |
| Supply Value | |
| Manufacturer to Specify | |
| System Neutral | Effectively grounded |
| Non-grounded | |
| Resistor grounded | |
| Pollution Level | Light |
| Medium | |
| Heavy | |
| Very Heavy | |
| Choice 4 | Required |
| Not Required | |
| Manufacturer to Specify | |
| Yes | |
| No | |
| Kpp | 1.3 |
| 1.5 | |
| Ambient air temperature | −50 °C to +40 °C for extremely cold climates |
| −40 °C to +40 °C for very cold climates | |
| −30 °C to +40 °C for normal climates | |
| −5 °C and +55 °C for very hot climates | |
| −15 °C and +55 °C for hot and dry desert regions | |
| Reclosing duty | O-0.3sec-CO-15sec-CO |
| O-0.3sec-CO-3min-CO | |
| O-15sec-CO-3min-CO |
IEEE Tables image2.png