3-PLAN 2 DCF-26-72-UTIL-6638 Sketch Package SK-1.pdf
PDF 562 KB Posted
- Attached to
- Pajarito Well #1 Eletrical Service Upgrade
- Solicitation number
- IFB27-35
- Issued by
- Los Alamos County, New Mexico
About this file
This file is a meter installation detail sketch package for the Pajarito Well #1 electrical service upgrade project in Los Alamos, New Mexico, prepared by design and engineering personnel for the Los Alamos County. The sketch (SK-1) provides technical specifications for a new service entrance metering system, including detailed installation requirements for current transformer cabinets, meter enclosures, and associated electrical components. The document specifies that Los Alamos National Laboratory (LANL) will own and install current transformers and associated metering within equipment provided and owned by Los Alamos County (LAC). Key equipment requirements include an Erickson Model CT07A 283-2 current transformer cabinet (24" width, 48" height, 8" depth) for three-phase, four-wire service rated at 65kA, and a Hoffman metal meter enclosure (20" width, 24" height, 10" depth, Model A24H2010SSLP) with swing-out panel mounted 60 inches off ground. The document was issued for design review and procurement purposes on April 22, 2026, with verification and approval signatures completed through April 23, 2026.
This is a design review document for procurement only and does not to scale. The sketch establishes that LAC will provide and own specified equipment components including the current transformer cabinet, service entrance rated disconnect, and meter enclosure. The installation details specify conduit routing requirements, 1-1/4" EMT minimum spacing between the CT enclosure and meter enclosure, and field-determined connection points to the existing service entrance disconnect and cell modem on the building. No pricing information, set-asides, contract terms, funding sources, or other commercial terms are included in this technical drawing package.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
METER INSTALLATION DETAIL
GENERAL NOTES:
KEYED NOTES:
1. LANL WILL OWN AND INSTALL CTS AND ASSOCIATED METERING WITHIN
LAC OWNED EQUIPMENT.
2. CONDUIT IS SHOWN FOR CONNECTION PURPOSES ONLY. FIELD ROUTE AS
NECESSARY.
3. FOR PROCUREMENT ONLY
4. NOT DRAWN TO SCALE.
INCOMING CONDUCTOR FROM NEW TRANSFORMER BANK THROUGH
WEATHERHEAD.
CURRENT TRANSFORMER CABINET. ERICKSON MODEL CT07A 283-2. 3Ø
4W 65kA WITH PROVISIONS FOR SUPPORTING CTS. WIDTH 24", HEIGHT
48", AND DEPTH 8" PROVIDED AND OWNED BY LAC.
SERVICE ENTRANCE RATED DISCONNECT, PROVIDED AND OWNED BY
LAC.
DC
D
C
B
A
1 3 42 65
Los Alamos, New Mexico 87545 PO Box 1663
APPCHKDDWN DSGN
DRAWN
CLASS
REV
DESCRIPTION SUB
OF
REV
CHECKED
DESIGN
DATE
TA-
SHEET
REVIEWER:
FDAR APPROVED
DRAWING NO
DATENO
BLDG
SUBMITTED
D.C.:
PROJECT ID
DATE:
INITIAL ISSUE FOR [DCF-26-72-UTIL-6638]0
REVISIONS PER [DCF] [DRN] [FCR]
TA-72 PAJARITO WELL 1
NEW SERVICE ENTRANCE METERING
METER INSTALLATION DETAIL
72 PW 1
J. TATE
J. TATE
N. RIVERA
2026-04-22
N/A K. D'DONNELL
[CLASSIFICATION] [REVIEWER]
SK-1
SHT TTL
XXXXXX DCF-26-72-UTIL-6638-SK-1 0
METER ENCLOSURE 20" W X 24" H X 10" D, MODEL A24H2010SSLP NVENT
HOFFMAN, METAL ENCLOSURE. WITH A24P20 NVENT SWING OUT PANEL.
CENTER OF ENCLOSURE TO BE BETWEEN 60 (±5") INCHES OFF GROUND.
PROVIDED AND OWNED BY LAC.
5 1-1/4" EMT MINIMUM BETWEEN CT ENCLOSURE AND METER ENCLOSURE.
ENTER SERVICE ENTRANCE DISCONNECT AT LOCATION DETERMINED BY
FIELD CONDITIONS.
FIELD ROUTE TO EXISTING CELL MODEM ON BUILDING.
SCALE: NONE
0%
D
ESIG
N R
EVIE
W
FO
R P
R O C U R E M
E N T O
N
LY
DRAWN:
VERIFIED:
FDAR:
DC:
| 2026-04-22T15:46:30-0600 | |
| JAMES TATE |
| 2026-04-23T08:10:48-0600 | |
| NICOLE RIVERA (Affiliate) |
| 2026-04-23T10:59:55-0600 | |
| Kevin O'Donnell |
| 2026-04-23T13:15:47-0600 | |
| Harold Salazar |