3-Drawings -Riverside ES Roof Replacement - Drawings Issued For Construction.pdf

PDF 12 MB Posted

Attached to
Riverside Elementary School Roof Replacement
Solicitation number
Bid #030326A
Issued by
Olmsted County, Minnesota

About this file

This is a construction drawing set for the Riverside Elementary School Roof Replacement project in Rochester, Minnesota, prepared by CRW Architecture + Design Group in coordination with Dunham Engineering for mechanical design. The project involves the complete removal and replacement of approximately 23,000 square feet of existing low-slope ballasted EPDM membrane roof systems down to the metal deck and installation of new fully-adhered EPDM membrane roofing systems. The scope of work includes demolition of existing ballast, EPDM membrane, cover board, rigid polyisocyanurate insulation, metal trim and coping, roof drains, and miscellaneous roof penetrations. New construction work comprises installation of fully-adhered EPDM roofing membrane, new polyisocyanurate insulation (average 4-inch thickness providing R-24 value), cover board, new aluminum metal trim and coping, prefinished metal overflow scuppers, roof drains with new collar clamps and strainers, EPDM roof walkway pads, masonry flashing with counter-flashing, vapor barrier, and related roof penetration flashings. All existing roof-mounted mechanical equipment, including exhaust fans, intake hoods, relief hoods, condensing units, and flues, must be temporarily removed during roof work and reinstalled upon completion. The construction documents are issued for bidding dated February 10, 2026, and are based on the 2018 International Building Code, 2020 Minnesota State Building Code, and 2020 Minnesota Accessibility Code.

The project is classified as Type II-B construction with full sprinkler protection and Group A3 occupancy (assembly). While the existing roof system provides only R-24 insulation through 4-inch polyisocyanurate insulation, which does not meet current 2024 Minnesota Energy Code requirements for R-30 minimum, the retrofit is not feasible due to existing parapet heights, through-wall flashing heights, and equipment heights. The general contractor is responsible for obtaining all required permits, coordinating with utility companies 72 hours prior to construction, performing all temporary shoring and scaffolding, managing demolition debris removal, and ensuring compliance with OSHA safety requirements. Contractors must verify existing conditions and dimensions on-site prior to bidding and immediately report any discrepancies, code violations, or hazardous materials discoveries to the architect. The construction documents include detailed architectural, mechanical, and electrical drawings with demolition plans, roof plans, technical details, and photo references to support the bidding process.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OWNER

ARCHITECT

MECHANICAL DESIGN

ROCHESTER PUBLIC SCHOOLS

CONSTRUCTION SERVICES DEPARTMENT

393935 HIGHWAY 14 EAST

ROCHESTER, MINNESOTA 55904

CONTACT: BILL BURT

PHONE NUMBER: (507) 328-4505

EMAIL: wiburt@rochesterschools.org

CRW ARCHITECTURE + DESIGN GROUP

211 ELEVETH AVENUE NORTHWEST

ROCHESTER, MINNESOTA 55901

CONTACT: TROY DOKKEN

PHONE NUMBER: (507) 206-6201

EMAIL: tdokken@crwarchitecture.com

DUNHAM ENGINEERING

421 FIRST AVENUE SW - SUITE 201W

ROCHESTER, MINNESOTA 55902

CONTACT: MIKE SZUBERSKI

PHONE NUMBER: (507) 424-6868

EMAIL: mike.szuberski@dunhameng.com

N O

R T

H

SITE

6TH ST SE6TH ST SE

5T H

A V

E S

E

6T H

A V

E S

E

5T H

A V

E S

E

SCHEDULE OF REQUIRED PERMITS

DESCRIPTION OF PERMIT TYPE

PERMIT ARRANGED FOR AND

PAID FOR BY:

= NOT APPLICABLE= BY OWNER= BY CONTRACTOR

12. SIGNAGE PERMIT

11. FOOTING & FOUNDATION PERMIT

(IF PHASED PERMIT REQUESTED)

10. ZONING & BUILDING REVIEW & PERMIT

9. SITE GRADING PERMIT

8. SEWER & WATER CONNECTION PERMIT

7. TELEPHONE PERMIT

6. CABLE TELEVISION PERMIT

5. GAS UTILITY PERMIT

4. ELECTRICAL UTILITY PERMIT

3. DRIVEWAY APPROACH PERMIT

2. SIDEWALK PERMIT (IF APPLICABLE)

1. DEMOLITION PERMIT

A

B

C

D

E

F

P

O

N

M

L

K

J

H

G

R

S

T

U

V

W I

STANDARD ABBREVIATIONS

W/O.

W.C.

WD.

WDW.

WT.

W.W.F.

W.W.M.

VAR.

V.C.T.

U.L.

UNFIN.

U.N.O.

T.&G.

TEMP.

THK.

T.O.

T.V.

TYP.

SCHD.

SECT.

S.F.

SHT.

SHTG.

SIM.

SIM.REV.

SPEC.

STD.

STL.

STOR.

STRUCT.

SUSP.

SYM.

R.D.

REBAR

REF.

REINF.

REQ.

REV.

RM.

R.O.

PC.

PERF.

P.LAM.

PLYW.

O.C.

OF.D.

O.H.D.

OPNG.

OPP.

O.S.B.

N.I.C.

NO. / #

NOM.

N.T.S.

MAINT.

MATL.

MAX.

MECH.

MEMB.

MEZZ.

MFR.

MIN.

MIR.

MISC.

M.O.

MTD.

MTL.

LAM.

LAV.

L.F.

KIT.

JAN.

I.D.

IN.

INFO.

INSUL.

INT.

H.C.

HCP.

HDR.

HDWD

HDWR.

H.M.

HORIZ

HR.

HT./HGT.

GA

GALV.

G.C.

GYP. BD.

F.D.

FDN.

F.E.

F.E.CAB.

F.F.E.

FLR.

F.O.

F.R.P.

FT.

FTG.

FURN.

F.V.

DBL.

DEPT.

DET.

D.F.

DIA./ Ø

DIAG.

DIM.

DISP.

DN.

DR.

DS.

DWG.

C.I.P.

C.J.

C/L / ℄

CLG.

CLR.

C.M.U.

COL.

COMP.

CONC.

CONST.

CONT.

COORD.

CORR.

CPT.

CT.

BD.

BLDG.

BM.

B.O

BRG.

ACC.

A.C.T.

ADD.

ADJ.

A.F.F.

ALT.

APPROX.

ARCH.

AVG.

EA.

E.I.F.S.

E.J.

ELEC.

ELEV.

ENTR.

EQ.

EQUIP.

EXP.

EXIST.

ACCORDING/ACCORDION

ACOUSTICAL CEILING TILE

ADDENDUM

ADJUSTABLE/ADJACENT

ABOVE FINISHED FLOOR

ALTERNATE/ALTERATION

APPROXIMATE

ARCHITECT/ARCHITECTURAL

AVERAGE

BOARD

BUILDING

BEAM

BOTTOM OF

BEARING

DOUBLE

DEPARTMENT

DETAIL

DRINKING FOUNTAIN

DIAMETER

DIAGONAL

DIMENSION

DISPOSAL

DOWN

DOOR

DOWNSPOUT

DRAWING

EACH

EXTERIOR INSUL. FINISH SYSTEM

EXPANSION JOINT

ELECTRICAL

ELEVATOR / ELEVATION

ENTRANCE

EQUAL

EQUIPMENT

EXPANSION

EXISTING

CAST IRON PIPE/CAST IN PLACE

CONTROL JOINT

CENTER-LINE

CEILING

CLEAR

CONCRETE MASONRY UNITS

COLUMN

COMPOSITE/COMPOSITION

CONCRETE

CONSTRUCTION

CONTINUOUS

COORDINATE

CORRIDOR

CARPET

CERAMIC TILE

FLOOR DRAIN

FOUNDATION

FIRE EXTINGUISHER

FIRE EXTINGUISHER CABINET

FINISH FLOOR ELEVATION

FLOOR

FACE OF

FIBERGLASS REINFORCED PANEL

FOOT OR FEET

FOOTING

FURNACE/FURNISH

FIELD VERIFY

GAUGE

GALVANIZED

GENERAL CONTRACTOR

GYPSUM BOARD

HOLLOW CORE

HANDICAP

HEADER

HARDWOOD

HARDWARE

HOLLOW METAL

HORIZONTAL

HOUR

HEIGHT

INSIDE DIMENSION

INCHES

INFORMATION

INSULATION

INTERIOR

LAMINATED

LAVATORY

LINEAL FOOT

KITCHEN

JANITOR

MAINTENANCE/MAINTAIN

MATERIAL

MAXIMUM

MECHANICAL

MEMBRANE

MEZZANINE

MANUFACTURER

MINIMUM/MINUTE

MIRROR

MISCELLANEOUS

MASONRY OPENING

MOUNTED

METAL

NOT IN CONTRACT

NUMBER

NOMINAL

NOT TO SCALE

ON CENTER

OVERFLOW DRAIN

OVERHEAD DOOR

OPENING

OPPOSITE

ORIENTED STRAND BOARD

PRECAST

PERFORATED

PLASTIC LAMINATE

PLYWOOD

ROOF DRAIN

REINFORCING BAR

REFERENCE/REFRIGERATOR

REINFORCED

REQUIRED

REVISION/REVERSE

ROOM

ROUGH OPENING

SCHEDULE

SECTION

SQUARE FEET

SHEET

SHEATHING

SIMILAR

SIMILAR REVERSE

SPECIFICATION

STANDARD

STEEL

STORAGE

STRUCTURE/STRUCTURAL

SUSPENDED

SYMBOL

TONGUE AND GROOVE

TEMPERED/TEMPORARY/TEMPERATURE

THICK

TOP OF

TELEVISION

TYPICAL

UNDERWRITERS LABORATORIES, INC.

UNFINISHED

UNLESS NOTED OTHERWISE

VARIES

VINYL-COMPOSITION TILE

WITHOUT

WATER CLOSET

WOOD

WINDOW

WEIGHT

WELDED WIRE FABRIC

WELDED WIRE MESH

O.F.C.I. OWNER FURNISHED

CONTRACTOR INSTALLED

GRAPHIC SYMBOLS

100A

ROOM TAG

Room Name

DOOR TAG

WINDOW TAG1t

WALL PARTITION TYPE

FIRE EXTINGUISHER CABINET

A101

SIM

F.E.C

F.E

ELEVATION NUMBER

SHEET NUMBER

BUILDING SECTION NUMBER

SHEET NUMBER

FIRE EXTINGUISHER CABINET

INTERIOR ELEVATION MARK

ELEVATION MARKER

A1.100

Ref

Ref

R e fR e f

XX

2h

A101

Ref

1Ref 1 Ref

Ref

Name Elevation

4 5

6 8

SHEET NUMBER

ISSUE/REVISION HISTORY

CHECKED BY

DRAWN BY

DATE

PROJECT

NUMBER

NUMBER DATE

OF SHEETS

I HEREBY CERTIFY THAT THIS PLAN,

SPECIFICATION, OR REPORT WAS

PREPARED BY ME OR UNDER MY

DIRECT SUPERVISION AND THAT I

AM A DULY LICENSED ARCHITECT

UNDER THE LAWS OF THE STATE OF

MINNESOTA.

© 2026 CRW architecture + design group

CONSTRUCTION DOCUMENT SET

No. ISSUED FOR DATE

211 11th ave nw rochester, mn 55901

p. 507.206.6201

f. 507.206.46.21 www.crwarchitecture.com

CLIENT

CD SET 02/10/26

A u to d e s k D o c s /R

P S

R iv e rs id e E

S R o o f R e p la c e m e n t/

-0

R

P S

R iv e rs id e

E S

R o o f R e p la c e m e n t (R rv t

/1

/2

:5

:4

P

M

G0.00

JASON WOODHOUSE

44421 02/10/2026

COVER SHEET

R O

C H

E S

T E

R

M

IN

N E

S O

T A

R P

S R

IV

E

R S

ID

E

E S

R O

O F

R E

P

LA

C E

M E

N T

26-004

02/10/2026

TmD,LG

JW

RPS RIVERSIDE ES ROOF

REPLACEMENTROCHESTER, MINNESOTA

PLANS ISSUED:02/10/2026

1-GENERAL INFORMATION

G0.00 COVER SHEET

2-ARCHITECTURAL DEMO

AD1.00 ROOF DEMO PLAN

3-ARCHITECTURAL

A1.00 ROOF PLAN

A4.10 DETAILS

A4.11 PARTIAL EXISTING PHOTO REFERENCE

A4.12 PARTIAL EXISTING PHOTO REFERENCE

4-MECHANICAL

M0.0 MECHANICAL SYMBOLS AND ABBREVIATIONS

MD1.00 ROOF MECHANICAL DEMOLITION PLAN

M1.00 ROOF MECHANICAL PLAN

5-ELECTRICAL

E0.00 ELECTRICAL TITLE SHEET

ED1.00 ROOF ELECTRICAL DEMOLITION PLAN

E1.00 ROOF ELECTRICAL PLAN

CODE INFORMATION: SHEET INDEXSITE LOCATION MAP

BUILDING LEGEND

NOT TO SCALE

2018 INTERNATIONAL BUILDING CODE

2020 MINNESOTA STATE BUILDING CODE

2020 MINNESOTA ACCESSIBILITY CODE

PROPOSED PROJECT SUMMARY:

THE PROJECTS CONSIST OF REPLACING THE EXISTING BALLASTED EPDM ROOFS, COVER

BOARD, ROOF INSULATION, COPINGS AND TRIM REQUIRED FOR RE-ROOFING TO A FULLY

ADHERED EPDM ROOF SYSTEM. WORK INCLUDES GENERAL MECHANICAL, ELECTRICAL AND

ARCHITECTURAL ROOFING SCOPE.

(NO ADDITIONAL BUILDING SQUARE FOOTAGE ADDED, CHANGE IN EXISTING BUILDING

SEPARATIONS AND MODIFICATIONS MADE TO EXISTING PARTITION RATINGS WITHIN THIS

PROJECT SCOPE)

OCCUPANCY CLASSIFICATION (CHAPTER 3):

GROUP A3 - ASSEMBLY (UNCHANGED)

TYPE OF CONSTRUCTION (CHAPTER 6):

TYPE II-B CONSTRUCTION, FULL SPRINKLERED (UNCHANGED)

2024 MINNESOTA ENERGY CODE

TABLE 5.5-6 BUILDING ENVELOPE REQUIREMENTS FOR CLIMATE ZONE 6

ROOF - INSULATION ENTIRELY ABOVE DECK:

NON-RESIDENTIAL, INSULATION MIN. R-VALUE: R-30 C.I.

THE PROJECT CONSISTS OF THE REPLACEMENT OF AN EXISTING LOW-SLOPE BALLASTED

MEMBRANE ROOF SYSTEM WITH A NEW FULLY ADHERED MEMBRANE ROOF SYSTEM. DUE TO

EXISTING CONDITIONS, THE NEW ROOF SYSTEM WILL BE INSTALLED WITH THE SAME

THICKNESS OF RIGID INSULATION AS THE EXISTING ROOF SYSTEM, WHICH PROVIDES AN

AVERAGE INSULATION THICKNESS OF 4 INCHES. THE NEW SYSTEM WILL UTILIZE

POLYISOCYANURATE INSULATION PROVIDING AN AVERAGE R-VALUE OF R-24. THIS DOES NOT

MEET CURRENT ENERGY CODES BUT WAS COMPLIANT WHEN ORIGINALLY CONSTRUCTED.

DUE TO EXISTING PARAPET HEIGHTS, THRU-WALL FLASHING HEIGHTS AND EQUIPMENT

HEIGHTS, IT IS NOT FEASIBLE TO INCREASE THE R-VALUE AS PART OF THE ROOF

REPLACEMENT PROJECT.

1. UNLESS SPECIFICALLY NOTED OTHERWISE, ALL DETAILS, SECTIONS, NOTES, ETC. ARE

TO BE CONSIDERED AS BEING TYPICAL AT ALL SIMILAR LOCATIONS OR CONDITIONS. IN

THESE DOCUMENTS, DETAILS, NOTES, ETC. ARE NOT INDICATED OR REFERENCED AT

ALL POSSIBLE APPLICABLE LOCATIONS.

2. THE SPECIFICATIONS AS PREPARED BY CRW ARCHITECTURE + DESIGN GROUP SHALL

BE CONSIDERED A PART OF THESE DOCUMENTS AS IF BOUND HEREIN.

3. THE CONTRACTOR SHALL NOTIFY ALL APPROPRIATE ENGINEERING DEPARTMENTS AND

UTILITY COMPANIES 72 HOURS PRIOR TO CONSTRUCTION. ALL NECESSARY

PRECAUTIONS SHALL BE TAKEN TO AVOID DAMAGE TO ANY EXISTING UTILITY.

4. BEFORE BIDDING, FABRICATION OR BEGINNING WORK, CONTRACTOR SHALL VISIT

PROJECT SITE, REVIEW ALL CONSTRUCTION DOCUMENTS AND UNDERSTAND THEM IN

THEIR ENTIRETY. THE CONSTRUCTION DOCUMENTS MUST BE VIEWED IN THEIR

ENTIRETY AS COMPLETE SETS.

5. BEFORE BIDDING, FABRICATION OR BEGINNING WORK, CONTRACTOR SHALL VISIT

PROJECT SITE AND FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, ETC.

6. CONTRACTOR SHALL IMMEDIATELY REPORT ANY DISCREPANCIES, CONTRADICTIONS OR

QUESTIONS REGARDING THE CONTRACT DOCUMENTS OR EXISTING CONDITIONS TO

THE ARCHITECT IMMEDIATELY FOR RESOLUTION.

7. CONTRACTOR SHALL IMMEDIATELY REPORT ANY CODE VIOLATIONS IN THE CONTRACT

DOCUMENTS TO THE ARCHITECT FOR RESOLUTION.

8. DO NOT SCALE DRAWINGS. IN ALL CASES STATED DIMENSIONS TAKE PRECEDENCE.

CONTACT ARCHITECT IMMEDIATELY FOR ADDITIONAL REQUIRED DIMENSIONS. GENERAL

CONTRACTOR SHALL VERIFY ALL DIMENSIONS, VERIFY AND COORDINATE WITH EXISTING

CONDITIONS AND COORDINATE THE WORK, TIMING AND PHASING OF ALL TRADES.

9. ALL DEMOLITION, NEW CONSTRUCTION, SITE WORK AT INTERIOR AND EXTERIOR OF

BUILDING SHALL BE IN CONFORMANCE WITH ALL APPLICABLE CODE REQUIREMENTS,

INCLUDING BUT NOT LIMITED TO, CURRENT BUILDING CODE

10. ALL FINISH MATERIALS SHALL CONFORM TO APPLICABLE FLAME SPREAD AND SMOKE

GENERATED REQUIREMENTS.

11. ALL FIRE RATED WALLS SHALL BE CONSTRUCTED PER APPROVED U.L. OR OTHER

ACCEPTABLE TESTING AGENCY REQUIREMENTS TO MEET OR EXCEED STATED FIRE

RATINGS. ALL PENETRATIONS OF FIRE RATED BUILDING ELEMENTS SHALL BE SIMILARLY

CONSTRUCTED PER LOCAL BUILDING CODE TO MAINTAIN REQUIRED FIRE RATINGS.

12. IF AT ANY TIME THE CONTRACTOR ENCOUNTERS OR UNCOVERS ASBESTOS

CONTAINING BUILDING MATERIALS OR OTHER POSSIBLE HAZARDOUS OR TOXIC

MATERIALS, IT'S PRESENCE SHALL BE IMMEDIATELY REPORTED TO ARCHITECT AND

BUILDING OWNER.

13. CONTRACTOR SHALL FOLLOW OSHA AND OTHER APPLICABLE SAFETY REQUIREMENTS

DURING ALL WORK INCLUDING BUT NOT LIMITED TO DEMOLITION, REPAIR AND

CONSTRUCTION.

14. ALL EXISTING MATERIALS TO REMAIN WHICH ARE DISTURBED OR DAMAGED AND ALL

OTHER CUTTING SHALL BE PATCHED BACK AS REQUIRED TO LIKE NEW CONDITION, TO

MATCH ADJACENT SURFACES AND TO MAKE SUCH REPAIR IMPERCEPTIBLE.

15. BEFORE DEMOLITION, FABRICATION OR CONSTRUCTION, CONTRACTOR SHALL VERIFY

THAT NO CONFLICTS EXIST IN LOCATIONS OR CLEARANCE REQUIREMENTS OF

STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING, TELECOMMUNICATIONS,

TELEPHONE, DATA OR FIRE PROTECTION SYSTEMS AND THEIR ELEMENTS.

16. FIREBLOCKING, FIRESTOPS, DRAFTSTOPPING SHALL BE INSTALLED AS REQUIRED BY

CURRENT LOCAL BUILDING CODE REQUIREMENTS. TYPICAL AS REQUIRED AT

PARTITIONS, CONCEALED COMBUSTIBLE SPACES, CONCEALED COMBUSTIBLE ATTIC

SPACES, FLOOR PENETRATIONS, PENETRATIONS THROUGH FIRE RATED PARTITIONS OR

OTHER STRUCTURES AS REQUIRED BY CURRENT CODE.

17. CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL TEMPORARY SHORING OR BRACING

AND FOR THE DESIGN, CONSTRUCTION, STABILITY AND SAFETY OF ALL TEMPORARY

STRUCTURES, ENCLOSURES AND SCAFFOLDING.

18. CONTRACTOR SHALL COORDINATE THE TIMING, PHASING AND EXECUTION OF ALL

CUTTING AND PATCHING FOR THE EFFICIENT AND TIMELY COMPLETION OF WORK.

19. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR TEMPORARY PROTECTION AT ANY

OPENINGS IN FLOORS, ROOFS, WALLS, ETC.

20. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR DETERMINING ERECTION

PROCEDURE AND CONSTRUCTION SEQUENCE IN ORDER TO ENSURE THE SAFETY OF

THE BUILDING, WORKMEN AND VISITORS.

21. CONTRACTOR SHALL SAFELY AND LEGALLY REMOVE AND DISPOSE OF ALL MATERIALS

NOT SCHEDULED TO BE SALVAGED OR RE-INSTALLED.

22. CONTRACTOR SHALL MAINTAIN A STAMPED, APPROVED SET OF CONSTRUCTION

DOCUMENTS WITH APPROVAL LETTER AND CURRENT SHOP DRAWINGS. DOCUMENTS

ON SITE SHALL BE KEPT UP TO DATE.

23. MATERIAL OR PRODUCT SUBSTITUTIONS SHALL FOLLOW THE SUBSTITUTION

REQUIREMENTS OF DIVISION 01 OF THE PROJECT SPECIFICATIONS DOCUMENT.

24. SHOP DRAWINGS OR OTHER SUBMITTALS SHALL FOLLOW THE SUBMITTAL

REQUIREMENTS OF DIVISION 01 OF THE PROJECT SPECIFICATIONS DOCUMENT.

25. VERIFY MINIMUM SLOPES TO DRAIN AS INDICATED ON THE DRAWINGS PRIOR TO THE

START OF CONSTRUCTION. NOTIFY THE ARCHITECT IMMEDIATELY UPON DISCOVERY OF

ANY DISCREPANCIES.

26. REPAIR EXISTING PUBLICLY OWNED FACILITIES OR STRUCTURES DAMAGED OR

ALTERED DURING DEMOLITION OR CONSTRUCTION TO THE SATISFACTION OF THE

LOCAL MUNICIPALITY.

27. EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE, CONTRACTOR SHALL ENSURE THAT

ALL FINISH MATERIALS SHALL BE APPLIED TO BE FLUSH WITH ADJACENT SURFACES AND

JOINTS.

28. CONTRACTOR TO PROVIDE AND INSTALL BLOCKING, DOUBLE STUDS, AND/OR ANCHOR

PLATES AS NECESSARY TO SUPPORT EQUIPMENT, PLUMBING FIXTURES, CASEWORK,

CABINETS, GRAB BARS, TOILET ROOM ACCESSORIES, SIGNAGE, HANDRAILS, ETC.

29. CONTRACTOR SHALL VERIFY ALL EQUIPMENT LOCATIONS, DIMENSIONS, AND ALL

REQUIRED CLEARANCES OF ALL EQUIPMENT. COORDINATE WITH DRAWINGS,

SPECIFICATIONS, EQUIPMENT MANUALS AND CUT SHEETS. VERIFY THAT STRUCTURAL

LOADS ARE ACCEPTABLE.

GENERAL NOTES

N O

R T

H

NO. REVISIONS DATE

7 7

EXISTING STANDING SEAM METAL ROOF

EXISTING STANDING SEAM METAL ROOF

EXISTING STANDING

SEAM METAL ROOF

EXISTING STANDING

SEAM METAL ROOF

EXISTING CANOPY BALLAST ROOF

EXISTING CANOPY BALLAST ROOF

EXISTING CANOPY BALLAST ROOF

EXISTING CANOPY BALLAST ROOF

EXISTING CANOPY BALLAST ROOF

R.D.

R.D.

O.D.

R.D.

O.D.

R.D.

EXISTING

OVERFLOW

SCUPPER

EXISTING

OVERFLOW

SCUPPER

R.D.

EXISTING

OVERFLOW

SCUPPER

R.D.

EXISTING

OVERFLOW

SCUPPER

R.D.

EXISTING

OVERFLOW

SCUPPER

R.D.

O.D. R.D.R.D. O.D.

O.D.

EXISTING

OVERFLOW

SCUPPER

R.D.

EXISTING

SCUPPER / D.S.

EXISTING

SCUPPER / D.S.

EXISTING

PRIMARY

SCUPPER

E X

IS

T

IN

G

P

R

IM

A

Y

S C

U P

P E

R

E X

IS

T

IM

A

U P

P E

R

DN

D N

D N

D N

DN

D N

DN

D N

DN

D N

DN

D N

DN

D N

D N

DN

D N

D N

D N

D N

DN

S L O

P E

D

C K

D N

D N

SLOPED

DECK DN

D N

D N

D N

D N

DN

D N

DN

D N

DN

S L O

P

C K

D N

S L O

P

C K

D N

S L O

P

C K

D N

SLOPE DN SLOPE DN

S

LO

P E

D N

S

LO

P E

D N

SLOPE DN

SLOPE DN

S

LO

P E

D N

S

LO

P E

D N

SLOPE DNSLOPE DN

S

LO

P E

D N

EXISTING

VERT. LADDER

DEMOLITION NOTES:

GENERAL DEMOLITION NOTES:

1. DASHED LINES REPRESENT EXISTING ITEMS TO BE REMOVED, U.N.O.

2. PROVIDE ALL WORK TO COMPLETE DEMOLITION AS MAY BE REQUIRED

TO ACCOMPLISH WORK AS SHOWN ON THE DRAWINGS UNLESS NOTED

OTHERWISE. ALL AS INDICATED OR REQUIRED RELATING TO THE

EXISTING BUILDING AND NOT OTHERWISE ASSIGNED IS INCLUDED

UNDER THE RESPONSIBILITY OF THE CONTRACTOR.

3. CONTRACTOR TO VERIFY EXISTING ELECTRICAL & PLUMBING

LOCATIONS PRIOR TO DEMOLITION. EXISTING PLUMBING AND

ELECTRICAL MAY REQUIRE MODIFICATION TO ACCOMPLISH THE NEW

DESIGN AS SHOWN ON THESE PLANS.

4. MECHANICAL, ELECTRICAL AND PLUMBING CONTRACTORS SHALL

TERMINATE ALL APPROPRIATE SERVICES TO EXISTING CONSTRUCTION

WHICH ARE TO BE PERMANENTLY DISCONNECTED. THEY SHALL

FURTHER MAKE ALL TEMPORARY SERVICE TERMINATIONS INDICATED

OR REQUIRED TO ACCOMPLISH THE DEMOLITION AND/OR NEW REVISED

OR REPLACED SERVICES AS PART OF WORK UNDER ALL CONTRACTS.

ALL PERMANENT TERMINATIONS SHALL BE REMOVED BACK TO THE

SOURCE. NO VACANT SERVICES SHALL BE LEFT IN PLACE.

5. CONTRACTORS ARE TO BE RESPONSIBLE FOR REMOVING AND HAULING

OF ALL DEMOLITION DEBRIS.

6. AT CONCLUSION OF DEMOLITION, ALL SURFACES SHALL BE READY TO

RECEIVE NEW FINISHES.

7. THIS ROOF PLAN IS FOR REFERENCE ONLY – FINAL ROOF DESIGN TO BE

BY ROOFING SUPPLIER AND TO BE INSTALLED ACCORDING PER

MANUFACTURER’S WARRANTY REQUIREMENTS. ALL FLASHING AND

ROOF PENETRATIONS PER MANUFACTURER’S DETAILS.

8. EXISTING MECHANICAL / ELECTRICAL EQUIPMENT / CURBS /

PENETRATIONS / OPENINGS ARE SHOWN AT APPROXIMATE LOCATIONS,

SEE MECHANICAL FOR MORE INFORMATION.

9. ENSURE OR ADJUST SECONDARY ROOF DRAINAGE SYSTEM, HEIGHT OF

OVERFLOW DRAIN TO BE 2” MAX. ABOVE PRIMARY ROOF DRAIN.

10. REMOVE ALL EXISTING PREFINISHED METAL WALL OVERFLOW

SCUPPERS.

1 REMOVE EXISTING BALLAST AND EPDM ROOFING MEMBRANE,

COVER BOARD, RIGID INSULATION (DOWN TO EXISTING METAL

DECK) AND ANY FASTENERS IN THEIR ENTIRETY.

(NOT ALL DEMOLITION NOTES APPEAR ON EVERY SHEET)

2 REMOVE EXISTING METAL TRIM / PARAPET COPING IN ITS

ENTIRETY AND ANY DAMAGED / UNUSABLE BLOCKING AND

DISPOSE OF PROPERLY.

3 REMOVE ANY ABANDONED MECHANICAL SUPPORT CURBS AND

FRAMING DOWN TO EXISTING ROOF DECK.

4 REMOVE ROOFTOP HATCH AND / OR PERIMETER FLASHING

NEEDED FOR INSTALLATION OF NEW ROOF.

5 REMOVE ALL ROOF DRAIN AND OVERFLOW DRAIN DOME

STRAINERS WITH COLLAR CLAMPS.

6 REMOVE CONCRETE WALKWAY PADS AND SUPPORTS AND

DISPOSE OF PROPERLY.

7 REMOVE EXISTING MECHANICAL HOODS, PIPE BOOTS AND OTHER

MECHANICAL NEEDED FOR INSTALLATION OF NEW ROOFING - SEE

MECH/ELEC.

8 REMOVE MASONRY FLASHING AND PLASTIC CELL VENTS ALONG

MASONRY WALL AT EPDM ROOFING.

9 CUT AND REMOVE APPROX. 1'-0" OF EXISTING STANDING SEAM

ROOFING TO REMOVE EXISTING DAMAGED AREAS AND GAIN

ACCESS UNDER ROOFING FOR TIE-IN ROOFING, PER

MANUFACTURERS RECOMMENDATIONS.

10 REMOVE EXISTING STANDING SEAM CAP TO ACCESS ROOF TIE-IN

FLASHING.

11 REMOVE EXISTING SATELLITE AND SUPPORTS AND DISPOSE OF

PROPERLY.

SHEET NUMBER

ISSUE/REVISION HISTORY

CHECKED BY

DRAWN BY

DATE

PROJECT

NUMBER

NUMBER DATE

OF SHEETS

I HEREBY CERTIFY THAT THIS PLAN,

SPECIFICATION, OR REPORT WAS

PREPARED BY ME OR UNDER MY

DIRECT SUPERVISION AND THAT I

AM A DULY LICENSED ARCHITECT

UNDER THE LAWS OF THE STATE OF

MINNESOTA.

© 2026 CRW architecture + design group

No. ISSUED FOR DATE

211 11th ave nw rochester, mn 55901

p. 507.206.6201

f. 507.206.46.21 www.crwarchitecture.com

CLIENT

CD SET 02/10/26

A u to d e s k D o c s /R

P S

R iv e rs id e E

S R o o f R e p la c e m e n t/

-0

R

P S

R iv e rs id e

E S

R o o f R e p la c e m e n t (R rv t

/1

/2

:5

:4

P

M

AD1.00

JASON WOODHOUSE

44421 02/10/2026

ROOF DEMO PLAN

R O

C H

E S

T E

R

M

IN

N E

S O

T A

R P

S R

IV

E

R S

ID

E

E S

R O

O F

R E

P

LA

C E

M E

N T

26-004

02/10/2026

TmD,LG

JW

3/32" = 1'-0"

DEMO ROOF PLAN

NORTH

A4.10

A4.10

A4.10

A4.10

A4.10

A4.10

A4.10

A4.10

A4.10

EXISTING STANDING SEAM METAL ROOF

EXISTING STANDING SEAM METAL ROOF

EXISTING STANDING

SEAM METAL ROOF

EXISTING STANDING

SEAM METAL ROOF

R.D.

R.D.

O.D.

R.D.

O.D.

R.D.

EXISTING

OVERFLOW

SCUPPER

EXISTING

OVERFLOW

SCUPPER

R.D.

EXISTING

OVERFLOW

SCUPPER

R.D.

EXISTING

OVERFLOW

SCUPPER

R.D.

EXISTING

OVERFLOW

SCUPPER

R.D.

O.D. R.D.R.D. O.D.

O.D.

EXISTING

OVERFLOW

SCUPPER

R.D.

EXISTING

SCUPPER / D.S.

EXISTING

SCUPPER / D.S.

EXISTING

PRIMARY

SCUPPER

E X

IS

T

IM

A

U P

P E

R

E X

IS

T

IM

A

U P

P E

R

DN

D N

D N

D N

DN

D N

DN

D N

DN

D N

DN

D N

DN

D N

D N

DN

D N

D N

D N

D N

DN

S L O

P

C K

D N

D N

SLOPED

DECK DN

D N

D N

D N

D N

DN

D N

DN

D N

DN

S L O

P

C K

D N

S L O

P

C K

D N

S L O

P

C K

D N

3 3

7 7

A4.10

A4.10

A4.10

A4.10

SLOPE DN SLOPE DN

S

LO

P E

D N

S

LO

P E

D N

SLOPE DN

SLOPE DN

S

LO

P E

D N

S

LO

P E

D N

SLOPE DNSLOPE DN

S

LO

P E

D N

2 2

EXISTING

VERT. LADDER

11 11

2 1 2

1 2

2 2

DETAIL 12/A4.10

GENERAL ROOF PLAN NOTES:

1. ALL WORK SHALL BE PERFORMED IN COMPLIANCE WITH ALL

REQUIREMENTS OF THE OWNER. EACH TRADE CONTRACTOR SHALL BE

RESPONSIBLE FOR INITIATING, MAINTAINING AND SUPERVISING ALL

SAFETY PROCEDURES, PRECAUTIONS AND PROGRAMS IN CONNECTION

WITH THEIR WORK.

2. THE GENERAL CONTRACTOR SHALL FILE FOR AND OBTAIN ALL REQUIRED

PERMITS, LETTERS OF SATISFACTORY COMPLETION AND CERTIFICATES

OF OCCUPANCY FROM THE LOCAL BUILDING OFFICIALS.

3. ALL EQUIPMENT SHOWN AS DASHED IS BY THE OWNER. ELECTRICAL

CONTRACTOR TO VERIFY POWER REQUIREMENTS FOR OWNER'S

EQUIPMENT. MECHANICAL CONTRACTOR TO VERIFY PLUMBING AND

HVAC REQUIREMENTS OF OWNER'S EQUIP.

4. REFER TO THE STRUCTURAL, MECHANICAL, AND ELECTRICAL

DRAWINGS FOR ADDITIONAL WORK REQUIRED UNDER THIS CONTRACT.

5. THE GENERAL CONTRACTOR AND/OR MECHANICAL CONTRACTOR SHALL

COORDINATE ALL MECHANICAL WORK WITH THE OWNER'S

REPRESENTATIVE AND ALL OTHER TRADES.

6. THE GENERAL CONTRACTOR AND/OR ELECTRICAL CONTRACTOR SHALL

COORDINATE ALL ELECTRICAL WORK WITH THE OWNER'S

REPRESENTATIVE AND ALL OTHER TRADES.

7. THIS ROOF PLAN IS FOR REFERENCE ONLY – FINAL ROOF DESIGN TO BE

BY ROOFING SUPPLIER AND TO BE INSTALLED ACCORDING PER

MANUFACTURER’S WARRANTY REQUIREMENTS. ALL FLASHING AND

ROOF PENETRATIONS PER MANUFACTURER’S DETAILS.

8. EXISTING MECHANICAL / ELECTRICAL EQUIPMENT / CURBS /

PENETRATIONS / OPENINGS ARE SHOWN AT APPROXIMATE LOCATIONS,

SEE MECHANICAL FOR MORE INFORMATION.

9. ENSURE OR ADJUST SECONDARY ROOF DRAINAGE SYSTEM, HEIGHT OF

OVERFLOW DRAIN TO BE 2” MAX. ABOVE PRIMARY ROOF DRAIN.

10. PROVIDE TAPERED ROOF INSULATION CRICKETS AT MECHANICAL

EQUIPMENT, SLOPE ½” PER 12”.

11. PROVIDE TAPERED ROOF INSULATION CRICKETS BETWEEN DRAINS,

SLOPE ¼” PER 12”.

12. PROVIDE MINIMUM OF 3” THICKNESS OF TAPERED POLYISOCYRANURATE

INSULATION TO BE USED AT ALL LOCATIONS.

13. PROVIDE AND INSTALL ALL NEW PREFINISHED METAL WALL OVERFLOW

SCUPPERS - COLOR TO MATCH COPING.

ROOF PLAN NOTES:

1 INSTALL NEW FULLY ADHERED EPDM ROOFING SYSTEM

INCLUDING COVER BOARD, BASE AND TAPERED

POLYISOCYANURATE INSULATION. INSULATION THICKNESS

AND SLOPES TO MATCH EXISTING CONDITION, U.N.O.

2 INSTALL NEW PREFINISHED ALUMINUM TRIM / COPING SYSTEM

MATCHING THE DEMOLISHED COPING DIMENSIONS AND

COLOR

3 REINSTALL EXISTING MECHANICAL HOODS AND MECHANICAL

EQUIPMENT REMOVED DURING DEMOLITION, SEE 2/A4.10

4 REINSTALL ROOF HATCH AND NEW PERIMETER FLASHINGS -

SEE 7/A4.10

5 INSTALL ALL NEW ROOF DRAIN AND OVERFLOW COLLAR

CLAMPS WITH DOMED STRAINERS - SEE 6/A4.10

6 INSTALL NEW ADHERED EPDM ROOF WALKWAY PADS

COMPATIBLE WITH ROOFING SYSTEM TO MATCH EXISTING

WALKWAY ROUTES.

7 INSTALL NEW EPDM MANUFACTURED ROOF BOOT WITH

STAINLESS STEEL CLAMP, SEE PLUMB. FOR OTHER

LOCATIONS - SEE 3/A4.10 AND 4/A4.10

8 INSTALL NEW MASONRY FLASHING AND COUNTER FLASHING

WITH NEW PLASTIC CELL VENTS ALONG MASONRY WALL AT

EPDM ROOFING, COLORS TO MATCH EXISTING - SEE 8/A4.10

9 INSTALL NEW VAPOR BARRIER ON EXISTING METAL ROOF

DECK AND EXTEND VERTICALLY ALONG PERIMETER OF ROOF

INSULATION.

10 INSTALL NEW RAIL / GATE SYSTEM AND ROOF HATCH.

11 NEW GALVANIZED BALLASTED GUARDRAIL BY ROOFING

CONTRACTOR. SHEET NUMBER

ISSUE/REVISION HISTORY

CHECKED BY

DRAWN BY

DATE

PROJECT

NUMBER

NUMBER DATE

OF SHEETS

I HEREBY CERTIFY THAT THIS PLAN,

SPECIFICATION, OR REPORT WAS

PREPARED BY ME OR UNDER MY

DIRECT SUPERVISION AND THAT I

AM A DULY LICENSED ARCHITECT

UNDER THE LAWS OF THE STATE OF

MINNESOTA.

© 2026 CRW architecture + design group

No. ISSUED FOR DATE

211 11th ave nw rochester, mn 55901

p. 507.206.6201

f. 507.206.46.21 www.crwarchitecture.com

CLIENT

CD SET 02/10/26

A u to d e s k D o c s /R

P S

R iv e rs id e E

S R o o f R e p la c e m e n t/

-0

R

P S

R iv e rs id e

E S

R o o f R e p la c e m e n t (R rv t

/1

/2

:5

:4

P

M

A1.00

JASON WOODHOUSE

44421 02/10/2026

ROOF PLAN

R O

C H

E S

T E

R

M

IN

N E

S O

T A

R P

S R

IV

E

R S

ID

E

E S

R O

O F

R E

P

LA

C E

M E

N T

26-004

02/10/2026

TmD,LG

JW

3/32" = 1'-0"

ROOF PLAN

NORTH

RTU

WOOD NAILER

INSULATED

METAL CURB

USE APPROPRIATE

ELEVATE BONDING

ADHESIVE

METAL COUNTER-FLASHING

EPDM MEMBRANE

ROOF INSULATION AND

COVER BOARD

METAL ROOF DECK

CONT. BEAD EXTERIOR

SEALANT

CONTINUOUS BEAD

EXTERIOR SEALANT

PRE-MOLDED

MANUFACTURER

STEP FLASHING

CONTINUOUS BEAD

OF LAP SEALANT

ROOF FLASHING

CONTINUOUS BEAD OF

LAP SEALANT

STAINLESS STEEL

CLAMPING RING

FIELD FABRICATED

METAL HOOD

ROOF INSULATION

AND COVER BOARD

METAL ROOF DECK

PIPE CONDUIT-SEE

PLUMBING PLANS FOR

LOCATION AND SIZE OF

PENETRATIONS

CONTINUOUS SEALANT AS

REQUIRED

FLASHING AND COUNTER

FLASHING W/ ADHESIVES AS

REQUIRED

NOTE:

THESE DETAILS ILLUSTRATE INFORMATION REGARDING ROOFING

MEMBRANE INSTALLATION ONLY. REFER TO MANUFACTURER'S

DETAILS AND INSTALLATION REQUIREMENTS FOR SPECIFIC AND

COMPLETE INFORMATION TO INSURE WARRANTY COMPLIANCE.

EPDM MEMBRANE

ROOFING SYSTEM

ROOF INSULATION

AND COVER BOARD

ROOF HATCH

METAL COUNTER-FLASHING

USE APPROPRIATE BONDING

ADHESIVE

FULLY ADHERED EPDM

MEMBRANE ROOFING SYSTEM

ROOF INSULATION AND

COVER BOARD

METAL ROOF DECK

NEW STRAINER

NEW CLAMPING RING

ELECTROMETRIC MASTIC

UNDER ROOFING MEMBRANE

FULLY ADHERED EPDM

MEMBRANE ROOFING SYSTEM

DECK CLAMP

ROOF DRAIN

(EXISTING DISTANCE TO R.D.)

NEW PREFINISHED ALUM. METAL COPING -

COLOR TO MATCH EXISTING

EXTEND EPDM ROOFING MEMBRANE OVER PARAPET

EXISTING PARAPET

CONTIN. SEALANT

NEW PREFINISHED ALUM. THRU WALL SCUPPER

AND TRIM - COLOR TO MATCH EXISTING

FULLY ADHERED EPDM ROOF MEMBRANE SYSTEM

NEW ROOF INSULATION AND COVER BOARD

EXISITNG METAL ROOF DECK

EPDM ROOF FLASHING

NEW CONTINUOUS BEAD OF WATER BLOCK

EXISTING STEEL STANDING SEAM ROOF PANEL

EXISTING METAL PANEL UNDERLAYMENT

NEW EPDM MEMBRANE SYSTEM

FASTENER AND 2" METAL PLATE

REINF. PERIMETER FASTENING STRIP

REMOVE APPROX. 1'-0" OF EXISTING STEEL STANDING SEAM ROOF

PANELS TO REMOVE DAMAGED PORTIONS OF PANELS AND PROVIDE

ACCESS FOR NEW ROOF TIE-IN

NEW PREFINISHED STEEL TRIM MATCHING ROOF PANELS

OVERLAP NEW EPDM AND SECURE TO ROOF DECK

ROOF INSULATION

AND COVER BOARD

METAL ROOF DECK

NEW METAL COPING

METAL COUNTER-FLASHING

USE APPROPRIATE BONDING ADHESIVE

FULLY ADHERED EPDM MEMBRANE

ROOFING SYSTEM

ROOF INSULATION AND

COVER BOARD

METAL ROOF DECK

SEE DETAIL 11/A4.10 FOR

FLASHING DETAIL

USE APPROPRIATE BONDING

ADHESIVE

FULL ADHERED EPDM

MEMBRANE ROOFING SYSTEM

ROOF INSULATION AND

COVER BOARD

METAL ROOF DECK

URETHANE ROD

1 PART POLYURETHANE SEALANT

FASTEN IN HEAD OR BEAD

OF MORTAR JOINT

NEW OR EXISTING REGLET

METAL RECEIVER AND COUNTER FLASHING

ADHERE MEMBRANE UP WALL AND

FASTEN TOP WITH ALUMINUM

COMPRESSION BAR 1/2" O.C.

INSTALL WATER STOP SEALANT BEHIND EPDM

REINFORCED PERIMETER SECUREMENT STRIP

WITH FASTENER PLATES 12" O.C.

EPDM MEMBRANE

INSULATION AS SPECIFIED

EXISTING DECK

MECHANICAL FASTENER AND/OR ADHESIVE

POURABLE SEALER

CUT PVC PIPE

QUICKSEAM PENETRATION

POCKET FASTENING STRIP

APPROPRIATE PRIMER

MEMBRANE ADHESIVE

EPDM MEMBRANE

ROOF INSULATION AND

COVER BOARD NON-SHRINKING GROUT

EXISTING SUBSTRATE

6" M

IN

APPROX. 1

/2" G

AP

SHEET METAL JOINT COVER

SET IN SEALANT ON EACH SIDE

PREFINISHED ALUMINUM COPING

COPING WITH COVER PLATE

NOTE:

1. CONTINUOUS CLEAT NOT SHOWN FOR CLARITY.

2. COPING JOINERY IS SIMILAR ON BOTH SIDES.

3. REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.

SHEET NUMBER

ISSUE/REVISION HISTORY

CHECKED BY

DRAWN BY

DATE

PROJECT

NUMBER

NUMBER DATE

OF SHEETS

I HEREBY CERTIFY THAT THIS PLAN,

SPECIFICATION, OR REPORT WAS

PREPARED BY ME OR UNDER MY

DIRECT SUPERVISION AND THAT I

AM A DULY LICENSED ARCHITECT

UNDER THE LAWS OF THE STATE OF

MINNESOTA.

© 2026 CRW architecture + design group

No. ISSUED FOR DATE

211 11th ave nw rochester, mn 55901

p. 507.206.6201

f. 507.206.46.21 www.crwarchitecture.com

CLIENT

CD SET 02/10/26

A u to d e s k D o c s /R

P S

R iv e rs id e E

S R o o f R e p la c e m e n t/

-0

R

P S

R iv e rs id e

E S

R o o f R e p la c e m e n t (R rv t

/1

/2

:5

:5

P

M

A4.10

JASON WOODHOUSE

44421 02/10/2026

DETAILS

R O

C H

E S

T E

R

M

IN

N E

S O

T A

R P

S R

IV

E

R S

ID

E

E S

R O

O F

R E

P

LA

C E

M E

N T

26-004

02/10/2026

TmD,LG

JW

3" = 1'-0"

MECHANICAL CURB

3" = 1'-0"

PIPE PENETRATION WITH PIPE FLASHING

3" = 1'-0"

TYPICAL PIPE FLASHING

1 1/2" = 1'-0"

EXISTING ROOF HATCH

1 1/2" = 1'-0"

TYPICAL ROOF DRAIN

1 1/2" = 1'-0"

OVERFLOW SCUPPER AND ROOF DRAIN TYP.

1 1/2" = 1'-0"

EXISTING SLOPED ROOF TO FLAT ROOF

1 1/2" = 1'-0"

EXISTING SLOPED ROOF AT PEAK

1 1/2" = 1'-0"

EXISTING LOW ROOF TO WALL

1 1/2" = 1'-0"

ROOF TO BRICK WALL DETAIL

3" = 1'-0"

MULTIPLE PIPE PENETRATION

3" = 1'-0"

COPING SLICE DETAIL WITH EXPOSED COVER PLATES

1 2

7 8

17 18

SHEET NUMBER

ISSUE/REVISION HISTORY

CHECKED BY

DRAWN BY

DATE

PROJECT

NUMBER

NUMBER DATE

OF SHEETS

I HEREBY CERTIFY THAT THIS PLAN,

SPECIFICATION, OR REPORT WAS

PREPARED BY ME OR UNDER MY

DIRECT SUPERVISION AND THAT I

AM A DULY LICENSED ARCHITECT

UNDER THE LAWS OF THE STATE OF

MINNESOTA.

© 2026 CRW architecture + design group

No. ISSUED FOR DATE

211 11th ave nw rochester, mn 55901

p. 507.206.6201

f. 507.206.46.21 www.crwarchitecture.com

CLIENT

CD SET 02/10/26

A u to d e s k D o c s /R

P S

R iv e rs id e E

S R o o f R e p la c e m e n t/

-0

R

P S

R iv e rs id e

E S

R o o f R e p la c e m e n t (R rv t

/1

/2

:5

:0

P

M

A4.11

JASON WOODHOUSE

44421 02/10/2026

PARTIAL EXISTING PHOTO

REFERENCE

R O

C H

E S

T E

R

M

IN

N E

S O

T A

R P

S R

IV

E

R S

ID

E

E S

R O

O F

R E

P

LA

C E

M E

N T

26-004

02/10/2026

TmD,LG

JW

1 2 3 4 5

7 8 9 10

12 13 14 15

17 18 19

1" = 30'-0"

EXISITING ROOF PLAN

1 2

7 8

17 18

SHEET NUMBER

ISSUE/REVISION HISTORY

CHECKED BY

DRAWN BY

DATE

PROJECT

NUMBER

NUMBER DATE

OF SHEETS

I HEREBY CERTIFY THAT THIS PLAN,

SPECIFICATION, OR REPORT WAS

PREPARED BY ME OR UNDER MY

DIRECT SUPERVISION AND THAT I

AM A DULY LICENSED ARCHITECT

UNDER THE LAWS OF THE STATE OF

MINNESOTA.

© 2026 CRW architecture + design group

No. ISSUED FOR DATE

211 11th ave nw rochester, mn 55901

p. 507.206.6201

f. 507.206.46.21 www.crwarchitecture.com

CLIENT

CD SET 02/10/26

A u to d e s k D o c s /R

P S

R iv e rs id e E

S R o o f R e p la c e m e n t/

-0

R

P S

R iv e rs id e

E S

R o o f R e p la c e m e n t (R rv t

/1

/2

:5

:0

P

M

A4.12

JASON WOODHOUSE

44421 02/10/2026

PARTIAL EXISTING PHOTO

REFERENCE

R O

C H

E S

T E

R

M

IN

N E

S O

T A

R P

S R

IV

E

R S

ID

E

E S

R O

O F

R E

P

LA

C E

M E

N T

26-004

02/10/2026

TmD,LG

JW

1" = 30'-0"

PHOTO REFERENCE

23 24 25 26 27 28

MECHANICAL SYMBOLS LEGEND

DESIGNATIONSSYMBOLDESIGNATIONSSYMBOLDESIGNATIONSSYMBOL DESIGNATIONSSYMBOL

PLUMBING

ACID VENT

ACID WASTE

DEIONIZED WATER SUPPLY

FILTERED WATER

DOMESTIC HOT WATER

DOMESTIC HOT WATER (TEMP. INDICATED)

DOMESTIC RECIRC. HOT WATER

HARD COLD WATER

OVERFLOW STORM DRAIN

REVERSE OSMOSIS WATER

SANITARY VENT

SANITARY WASTE

SOIL DRAINAGE TILE

SOFTENED COLD WATER

SOFTENED HOT WATER

TEMPERED WATER

STORM DRAIN

WELL WATER

AV

AW

DIS

HARD

SDT

RO

V

W

SOFT

SHW

TW

OSD

SD

WW

NPCW NON-POTABLE COLD WATER

NPHW NON-POTABLE HOT WATER

FW

HW

RHW

GW GREASE WASTE

DOMESTIC COLD WATERCW

CLEAR WATER VENTCWV

CLEAR WATER WASTECWW

DOM. RECIRC. HOT WATER (TEMP. INDICATED)140 RHW

PUMPED ACID WASTEPAW

PUMPED STORMPSD

PUMPED WASTEPW

COMPRESSED AIR (PSI INDICATED)10#A

MECHANICAL PIPING

BOILER FEED

CHILLED WATER SUPPLY

CHILLED WATER RETURN

CONDENSATE DRAIN

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

FUEL OIL SUPPLY

FUEL OIL RETURN

FUEL OIL VENT

FUEL OIL FILL

GLYCOL SUPPLY

GLYCOL RETURN

HEAT RECOVERY SUPPLY

HEAT RECOVERY RETURN

HEATING WATER SUPPLY

HEATING WATER RETURN

LIQUIFIED PETROLEUM GAS

NATURAL GAS (PSI INDICATED)

PUMPED CONDENSATE

RADIATION WATER SUPPLY

RADIATION WATER RETURN

REFRIGERANT LIQUID

BF

CWS

CWR

CD

FOS

GS

GR

HRS

HRR

HWR

HWS

LPG

2#G

FOF

PC

RADS

CS

CR

FOR

FOV

RADR

RL

REFRIGERANT SUCTION

REFRIGERANT HOT GAS BYPASS

REHEAT WATER SUPPLY

REHEAT WATER RETURN

REMOTE RADIATOR SUPPLY

REMOTE RADIATOR RETURN

SECONDARY HEATING WATER SUPPLY

SECONDARY HEATING WATER RETURN

SNOW MELT SUPPLY

SNOW MELT RETURN

STEAM SUPPLY (PSI INDICATED)

STEAM CONDENSATE (PSI INDICATED)

RRS

RS

RHG

RHR

RHS

RRR

SHWS

SHWR

SMS

SMR

10#STM

10#SC

PIPE FITTINGS

ELBOW DOWN

PIPE CAP

ELBOW UP

TEE, OUTLET UP

TEE, OUTLET DOWN

CONNECTION, TOP

ECCENTRIC REDUCER

CONCENTRIC REDUCER

MEDICAL GAS

MEDICAL VACUUM

WASTE ANESTHETIC GAS DISPOSAL

CARBON DIOXIDE

OXYGEN

NITROGEN

NITROUS OXIDE

MEDICAL AIR

WAGD

CO2

O

N

MV

N2O

MA

PIPE UNION

PIPE FLANGE

ELBOW

TEE

FIRE PROTECTION

DFP

F FIRE PROTECTION

FIRE PROTECTION (DRY SYSTEM)

POST INDICATOR VALVE (PIV)

RECESSED FIRE DEPT CABINET

SURFACE MOUNTED FIRE DEPT CABINET

FIRE PROTECTION RISER

UPRIGHT SPRINKLER HEAD W/GUARD

PENDANT SPRINKLER HEAD

UPRIGHT SPRINKLER HEAD

SIDEWALL SPRINKLER HEAD

BUTTERFLY VALVE W/TAMPER SWITCH

DETECTOR CHECK W/BYPASS METER

GRADE FIRE DEPT CONNECTION

FLUSH FIRE DEPT CONNECTION

FIRE DEPT VALVE W/CAP AND CHAIN

O.S. & Y. VALVE W/TAMPER SWITCH

DRY PIPE VALVE

PREACTION VALVE

TS

FDVC

FDVC

FDV

TS

ANNOTATION

(4)A-12"ø

GRILLE, REGISTER, &

DIFFUSER IDENTIFICATION

QUANTITY

CFM

TYPE

SIZE

X X

X X

X X

X X

DETAIL NUMBER

SHEET NUMBER

SECTION NUMBER

SHEET NUMBER

EQUIP DESIGNATION

EQUIP NUMBER

POINT OF CONNECTION, NEW TO EXISTING

POINT OF DISCONNECTION

FTR/RP 01

6'-5"

0.5

HYDRONIC FINNED TUBE

RADIATION & RADIANT

PANEL IDENTIFICATION

TYPE ACTIVE

ELEMENT

LENGTHGPM

EBR 01

6'-5"

ELECTRIC BASEBOARD

RADIATION

IDENTIFICATION

ACTIVE

ELEMENT

LENGTH

ZONE VALVE BOXZVB

AREA ALARM PANELAAP

COMBINATION AREA/MASTER ALARM

PANEL

CAP

TYPE

INTERRUPTIBLE GASIG

PROCESS AND LABORATORY

LABORATORY AIR

LABORATORY VACUUM

ARGON

PROCESS WASTE

NITROGEN

HOUSE VACUUM

LV

AR

PRW

LA

N

HV

PROCESS VACUUMPV

INSTRUMENT AIRIA

ATMOSPHERIC STEAM SUPPLY

ATMOSPHERIC STEAM CONDENSATE

ATM STM

ATM SC

CONNECTION, BOTTOM

DARK DASHED LINE WEIGHT INDICATES

EXISTING ITEM TO BE DEMOLISHED.

GENERAL

LIGHT SOLID LINE WEIGHT INDICATES

EXISTING ITEM TO REMAIN.

DARK SOLID LINE WEIGHT INDICATES

NEW ITEM OR NEW LOCATION.

ROUND

12x12

12ø 12/12

RECTANGULAR (WxH)

FLAT-OVAL (W/H)

DUCT

DIMENSIONS

LIQUID NITROGENLN

MASTER ALARM PANELMAP

XXXX #-## EXISTING EQUIP NUMBER

EXISTING EQUIP DESIGNATION

MECHANICAL ABBREVIATIONS

AD AREA DRAIN

A.F.F. ABOVE FINISHED FLOOR

AFMS AIR FLOW MEASURING STATION

AHU AIR HANDLING UNIT

ANB ACID NEUTRALIZING BASIN

AP ACCESS PANEL

ARCH ARCHITECT

AS AIR SEPARATOR

BD BUTTERFLY DAMPER

B/G BELOW GRADE

BTU BRITISH THERMAL UNIT

BWV BACKWATER VALVE

CCF HUNDRED CUBIC FEET

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CL CENTER LINE

CLG CEILING

CO CLEAN OUT

CONTR CONTRACTOR

CONV CONVECTOR

CUH CABINET UNIT HEATER

CW COLD WATER

DB DECIBEL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIFF DIFFUSER

DISCH DISCHARGE

DMPR DAMPER

DN DOWN

DR DRAIN

DSN DOWNSPOUT NOZZLE

DWG DRAWING

EAT ENTERING AIR TEMPERATURE

EDR EQUIVALENT DIRECT RADIATION

EP ELECTRIC-PNEUMATIC

EWC ELECTRIC WATER COOLER

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

EXP EXPANSION

F FAHRENHEIT

FC FAN COIL

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FHC FIRE HOSE CABINET

FHR FIRE HOSE RACK

FLR FLOOR

FLEX FLEXIBLE

FM FIRE MAIN

FPM FEET PER MINUTE

FPS FEET PER SECOND

FT FEET OR FOOT

F&T FLOAT AND THERMOSTATIC

FTG FOOTING

FTR FINNED TUBE RADIATION

FV FACE VELOCITY

GA GAUGE

GAL GALLON

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

HB HOSE BIBB

HD HEAD

HOA HANDS-OFF-AUTOMATIC

HTG HEATING

HTR HEATER

HVAC HEATING, VENTILATION,

AND AIR CONDITIONING

HYD HYDRANT

HW HOT WATER

GCO GRADE CLEANOUT

INSUL INSULATION

KW KILOWATT

LAT LEAVING AIR TEMPERATURE

LAV LAVATORY

LWT LEAVING WATER TEMPERATURE

MBH BTU PER HOUR (THOUSANDS)

MCF THOUSAND CUBIC FEET

MH MANHOLE

NC

NOISE CRITERIA OR

NORMALLY CLOSED

NEG NEGATIVE

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OA OUTSIDE AIR

OBD OPPOSED BLADE DAMPER

ORD OVERFLOW ROOF DRAIN

PD PRESSURE DROP OR DIFFERENCE

PE PNEUMATIC-ELECTRIC

PLBG PLUMBING

PRV

PRESSURE REDUCING VALVE

OR POWER ROOF VENTILATOR

PSIA POUNDS/SQ INCH ABSOLUTE

PSIG POUNDS/SQ INCH GAUGE

PVC POLY VINYL CHLORIDE

RA RETURN AIR

RCP REINFORCED CONCRETE PIPE

RD ROOF DRAIN

RECIRC RECIRCULATING

REG REGISTER

RET RETURN

RH RELATIVE HUMIDITY

RHT REHEAT

RHC REHEAT COIL

RHW RECIRCULATED HOT WATER

RM ROOM

RPM REVOLUTIONS PER MINUTE

RPZ

REDUCED ZONE BACKFLOW

PREVENTER

SA SUPPLY AIR

SAN SANITARY

SCFM CFM, STANDARD CONDITIONS

SD SMOKE DAMPER

SP STATIC PRESSURE

SPECS SPECIFICATIONS

SUP SUPPLY

SQ SQUARE

STM STEAM

TD TEMPERATURE DIFFERENCE

TEMP TEMPERATURE

TONS TONS OF REFRIGERATION

T-STAT THERMOSTAT

TYP TYPICAL

UB UP-BLAST

UG UNDERGROUND

UH UNIT HEATER

UR URINAL

V SANITARY VENT

VD VOLUME DAMPER

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W SANITARY WASTE

W/ WITH

WC WATER CLOSET

WCO WALL CLEANOUT

WH WALL HYDRANT

W/O WITHOUT

WTR WATER

GR GRILLE

VAV VARIABLE AIR VOLUME

VTR VENT THROUGH ROOF

INV INVERT

RLF RELIEF

ISO ISOLATION EXHAUST

GEXH GREASE EXHAUST

RH ROOF HYDRANT

YCO YARD CLEANOUT

ZDL ZERO DEADLEG VALVE

AUTOMATIC AIR VENT

AUTOMATIC CONTROL VALVE, 2-WAY

AUTOMATIC CONTROL VALVE, 3-WAY

STRAINER W/BLOWDOWN

CAP AND VALVE

PIPE SPECIALTIES

FLEXIBLE CONNECTION

PIPE ANCHOR

ALIGNMENT GUIDE

STRAINER

PRESSURE REDUCING VALVE

(SETTING AS NOTED, PSI)

EXPANSION JOINT

MANUAL AIR VENT

PRESSURE RELIEF/SAFETY

VALVES(SETTING AS NOTED, PSI)

DRAIN VALVE

REDUCED PRESSURE ZONE BACK

FLOW PREVENTER

DIAPHRAGM

REFRIGERANT SIGHT GLASS

GAS PRESSURE REGULATOR VALVE

BACKWATER VALVE

REFRIGERANT DRYER

FLOW DIRECTION

FLOW DIRECTION W/PITCH

DUPLEX STRAINER

PUMP

THERMOMETER

PRESSURE/TEMPERATURE TEST PORT

STEAM TRAP (TYPE INDICATED)

FLOW SWITCH

PRESSURE GAUGE W/PIGTAIL &

PETCOCK

PRESSURE SWITCH

FLOOR DRAIN

DRAIN ABOVE

FLOOR SINK

WALL HYDRANT

HOSE BIBB

WALL CLEANOUT

ROOF DRAIN

MANHOLE

HB

A

M

FS

PS

GAS COCK VALVE

WH

DEIONIZED WATER RETURNDIR

CLEAN DRY AIRCDA

REVERSE OSMOSISRO

CONTROLS

AQUA STAT

TAMPERPROOF THERMOSTAT

HUMIDISTAT OR R.H. SENSOR

REFRIGERANT SENSOR

SMOKE DETECTOR

SPACE TEMPERATURE SENSOR

STATIC PRESSURE SENSOR

ROOM PRESSURE MONITOR

THERMOSTAT

THERMOSTAT W/GUARD

CARBON MONOXIDE SENSOR

CARBON DIOXIDE SENSOR

DIFFERENTIAL PRESSURE SENSOR

TEMPERATURE SENSOR

A

CO2

CO

H

R

P

SD

TS

SP

PS

T

T

T

DP

TS

P

DUCTWORK

SUPPLY AIR OR OUTDOOR AIR

RETURN AIR

EXHAUST AIR

STANDARD BRANCH, NO SPLITTER -

SUPPLY FLOW TO RIGHT -

RETURN/EXHAUST FLOW TO LEFT

BELLMOUTH WITH BALANCING

DAMPER

FLEXIBLE DUCT

TURNING VANES

FLEXIBLE CONNECTION

MANUAL VOLUME DAMPER

MOTORIZED DAMPER

TYPE:

FD = FIRE DAMPER

SD = SMOKE DAMPER

FSD = COMBINATION FIRE/SMOKE

DAMPER

CRD = CEILING RADIATION DAMPER

ORIENTATION:

SUPPLY GRILLE OR REGISTER

RETURN DUCT UP, NEGATIVE

PRESSURE

SUPPLY DIFFUSER/REGISTER

BLANKOFF INDICATED

RETURN OR EXHAUST GRILLE OR

REGISTER

SUPPLY DUCT UP, POSITIVE

PRESSURE

EXHAUST DUCT UP, NEGATIVE

PRESSURE

RETURN GRILLE/REGISTER

EXHAUST GRILLE/REGISTER

LINEAR DIFFUSER

CONCENTRIC DUCT TRANSITION

ECCENTRIC DUCT TRANSITION

RECTANGULAR-TO-ROUND DUCT

TRANSITION

VAV BOX

REHEAT COIL

VAV BOX W/ REHEAT COIL

DUCT OFFSETS

DUCT CUTLINE

M

XXX

RETURN DUCT DN, NEGATIVE

PRESSURE

SUPPLY DUCT DN, POSITIVE

PRESSURE

EXHAUST DUCT DN, NEGATIVE

PRESSURE

DROPRISE

VERTICAL

XXX

XXX

XXX

ACTUATOR (AS

APPLICABLE)

HORIZONTAL

BLADE/CURTAIN

FIRE, SMOKE, AND

COMBINATION

FIRE/SMOKE DAMPERS

TYPE

ORIENTATION

AIRFLOW MEASURING STATIONAFMS

VAV BOX W/ DUCT SILENCER

VENTURI TYPE AIR VALVE

VAV BOX W/ DUCT SILENCER

& REHEAT COIL

VAV BOX W/ ELECTRIC REHEAT

ENERGY METER

FLOW METER

GPM

EM

WATER HAMMER ARRESTOR

CATCH BASIN

BALANCE VALVE

GENERAL DUTY VALVES

CHECK VALVE

SHUTOFF VALVE

PLUG VALVE

BALL VALVE

BUTTERFLY VALVE

GLOBE ANGLE VALVE

O. S. & Y. VALVE

SOLENOID VALVE

FLOW LIMITING VALVE

GLOBE VALVE

S

OR

OR

OR

OR

OR

GATE VALVE

NITROGEN OXIDE SENSORNOX

SHEET NUMBER

ISSUE/REVISION HISTORY

CHECKED BY

DRAWN BY

DATE

PROJECT

NUMBER

NUMBER DATE

OF SHEETS

© 2025 CRW architecture + design group

No. ISSUED FOR DATE

CLIENT

CD ISSUE 02/10/26

I HEREBY CERTIFY THAT THIS

PLAN, SPECIFICATION, OR REPORT

WAS PREPARED BY ME OR UNDER

MY DIRECT SUPERVISION AND

THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER

THE LAWS OF THE STATE OF

MINNESOTA.

Steven C Harmon

23501

A u to d e s k D o c s /R

P S

R iv e rs id e

E S

R o o f R e p la c e m e n t/ M

E P

R P

S R iv e rs id e R o o f R e p la c e m e n t.

rv t

/1

/2

:2

:2

P

M

M0.0

02/10/2026

MECHANICAL SYMBOLS AND

ABBREVIATIONS

R O

C H

E S

T

M

N E

S O

T A

R P

S R

IV

E

R S

ID

E

E S

R O

O F

R E

P L

A C

E M

E N

T

1226035-000-00

02/10/2026

MJS

SCH

MECHANICAL SHEET LIST

SHEET

NUMBER SHEET NAME

M0.0 MECHANICAL SYMBOLS AND ABBREVIATIONS

MD1.00 ROOF MECHANICAL DEMOLITION PLAN

M1.00 ROOF MECHANICAL PLAN

SHEET TOTAL: 3

KEY NOTES:

EF-3

EF-1

EF-2

EF-10EF-11

EF-5

EF-7

EF-9

EF-6

2"VTR

2"VTR

2"VTR

RELIEF

HOOD

INTAKE

HOOD

INTAKE

HOOD

RELIEF

HOOD

4"RD

4"ORD

4"RD4"ORD

2"VTR

RELIEF

HOOD

INTAKE

HOOD

INTAKE

HOOD

RELIEF

HOOD

2"VTR4"VTR

4"ORD4"RD

2"VTR

6"RD

5"RD

RELIEF

HOOD

RELIEF

HOOD

RELIEF

HOOD

2"VTR

EF-12

EF-4

4"RD

6"RD

6"ORD

5"ORD

5"RD

4"RD

2"VTR

INTAKE

HOOD

INTAKE

HOOD

RELIEF

HOOD

4" FLUE

EF-13

2"VTR

INTAKE

HOOD

2"VTR

2"VTR 2"VTR 2"VTR

4"RD

6"RD

2"VTR

CONDENSING

UNIT

REFRIGERANT

PIPING

ROOF HATCH

ROOF HATCH

ROOF HATCH

1 1

2 2 3

3 3

7 7 7 7

7 7

OVERFLOW

SCUPPER

OVERFLOW

SCUPPER

OVERFLOW

SCUPPER

OVERFLOW

SCUPPER

OVERFLOW

SCUPPER

OVERFLOW

SCUPPER

1 REMOVE EXHAUST FAN. CURB TO REMAIN. SAVE EXHAUST FAN FOR

REINSTALLATION.

REMOVE INTAKE HOOD. CURB TO REMAIN. SAVE INTAKE HOOD FOR

REINSTALLATION.

REMOVE RELIEF HOOD. CURB TO REMAIN. SAVE RELIEF HOOD FOR

REINSTALLATION.

RECOVER REFRIGERANT. DISCONNECT REFRIGERATION PIPING FROM

CONDENSING UNIT. REMOVE CONDENSING UNIT. SAVE CONDENSING

UNIT FOR REINSTALLATION.

DISCONNECT REFRIGERATION PIPING FOR INSTALLATION OF NEW

ROOFING. SAVE PIPING AND ROOF PIPE SUPPORTS FOR

REINSTALLATION.

REMOVE FLUES TO ALLOW FOR INSTALLATION OF NEW ROOFING.

SAVE FLUES FOR REINSTALLATION.

REMOVE ROOF DRAIN STRAINER FOR INSTALLATION OF NEW ROOF

MEMBRANE. SAVE ROOF DRAIN STRAINER FOR REINSTALLATION.

SHEET NUMBER

ISSUE/REVISION HISTORY

CHECKED BY

DRAWN BY

DATE

PROJECT

NUMBER

NUMBER DATE

OF SHEETS

© 2025 CRW architecture + design group

No. ISSUED FOR DATE

CLIENT

CD ISSUE 02/10/26

I HEREBY CERTIFY THAT THIS

PLAN, SPECIFICATION, OR REPORT

WAS PREPARED BY ME OR UNDER

MY DIRECT SUPERVISION AND

THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER

THE LAWS OF THE STATE OF

MINNESOTA.

Steven C Harmon

23501

A u to d e s k D o c s /R

P S

R iv e rs id e

E S

R o o f R e p la c e m e n t/ M

E P

R P

S R iv e rs id e R o o f R e p la c e m e n t.

rv t

/1

/2

:2

:2

P

M

MD1.00

02/10/2026

ROOF MECHANICAL

DEMOLITION PLAN

R O

C H

E S

T

N E

S O

T A

R P

S R

IV

E

R S

ID

E

E S

R O

O F

R E

P L

A C

E M

E N

T

1226035-000-00

02/10/2026

MJS

SCH

3/32" = 1'-0"

ROOF MECHANICAL DEMOLITION PLAN

2"VTR

2"VTR

2"VTR

4"RD

4"ORD

4"RD4"ORD

2"VTR

2"VTR4"VTR

4"ORD4"RD

2"VTR

6"RD

5"RD

2"VTR

4"RD

6"RD

6"ORD

5"ORD

5"RD

4"RD

2"VTR

4" FLUE

2"VTR

2"VTR

2"VTR 2"VTR 2"VTR

4"RD

6"RD

2"VTR

REFRIGERANT

PIPING

EF-7

RELIEF

HOOD

INTAKE

HOOD

INTAKE

HOOD

RELIEF

HOOD

EF-6

EF-5

EF-3

EF-1

EF-9

RELIEF

HOOD

INTAKE

HOOD

INTAKE

HOOD

RELIEF

HOOD

ROOF HATCH

ROOF HATCH

ROOF HATCH

EF-13

EF-2

INTAKE

HOOD

RELIEF

HOODEF-12

EF-4

RELIEF

HOOD

INTAKE

HOOD

INTAKE

HOOD

EF-11 EF-10

RELIEF

HOOD

RELIEF

HOOD

1 1

2 2 3

3 3

CONDENSING

UNIT

7 7 7 7

7 7

OVERFLOW

SCUPPER

OVERFLOW

SCUPPER

OVERFLOW

SCUPPER

OVERFLOW

SCUPPER

OVERFLOW

SCUPPER

OVERFLOW

SCUPPER

1 REINSTALL EXISTING EXHAUST FAN ON EXISTING CURB.

REINSTALL EXISTING INTAKE HOOD ON EXISTING CURB.

REINSTALL EXISTING RELIEF HOOD ON EXISTING CURB.

REINSTALL EXISTING CONDENSING UNIT.

REINSTALL EXISTING REFRIGERATION PIPING AND ROOF PIPE

SUPPORTS. PROVIDE NEW ARMAFLEX INSULATION ON ALL PIPING.

REINSTALL EXISTING REFRIGERANT.

REINSTALL EXISTING FLUES.

REINSTALL EXISTING ROOF DRAIN STRAINER AFTER NEW ROOF

MEMBRANE IS INSTALLED.

SHEET NUMBER

ISSUE/REVISION HISTORY

CHECKED BY

DRAWN BY

DATE

PROJECT

NUMBER

NUMBER DATE

OF SHEETS

© 2025 CRW architecture + design group

No. ISSUED FOR DATE

CLIENT

CD ISSUE 02/10/26

I HEREBY CERTIFY THAT THIS

PLAN, SPECIFICATION, OR REPORT

WAS PREPARED BY ME OR UNDER

MY DIRECT SUPERVISION AND

THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER

THE LAWS OF THE STATE OF

MINNESOTA.

Steven C Harmon

23501

A u to d e s k D o c s /R

P S

R iv e rs id e

E S

R o o f R e p la c e m e n t/ M

E P

R P

S R iv e rs id e R o o f R e p la c e m e n t.

rv t

/1

/2

:2

:2

P

M

M1.00

02/10/2026

ROOF MECHANICAL PLAN

R O

C H

E S

T

N E

S O

T A

R P

S R

IV

E

R S

ID

E

E S

R O

O F

R E

P L

A C

E M

E N

T

1226035-000-00

02/10/2026

MJS

SCH

3/32" = 1'-0"

ROOF MECHANICAL PLAN

DESIGNATIONSSYMBOL

MTG

HT

SYMBOL SCHEDULE NOTES

THESE SYMBOLS COMPRISE A STANDARD LIST, NOT ALL SYMBOLS MAY

APPEAR ON THESE DRAWINGS.

MOUNTING HEIGHTS INDICATED ARE STANDARD. DIMENSIONAL NUMBERS

INDICATED AT DEVICES SHALL OVERRIDE THESE STANDARDS. MOUNTED

HEIGHTS ARE TO THE CENTER OF THE DEVICE, UNLESS NOTED OTHERWISE.

MOUNTING HEIGHTS INDICATED ARE FOR STUD WALL CONSTRUCTION.

WHEN BLOCK OR BRICK CONSTRUCTION IS USED, ADJUST MOUNTING

HEIGHTS TO ALIGN DEVICE PLATES WITH RUNNING JOINT.

REFER TO SPECIFICATIONS FOR FURTHER INFORMATION.

GENERAL

DARK DASHED LINE WEIGHT INDICATES

EXISTING ITEM TO BE REMOVED.

LIGHT SOLID LINE WEIGHT INDICATES EXISTING

ITEM TO REMAIN.

DARK SOLID LINE WEIGHT INDICATES NEW ITEM

OR NEW LOCATION.

REMOVE EXISTING ITEM

REMOVE EXISTING ITEM AND RELOCATE AS INDICATED

NL

EXISTING ITEM TO REMAIN

NEW LOCATION FOR RELOCATED ITEM

NOTES & TAGS

EQUIPMENT IDENTIFICATION TAG - SEE EQUIPMENT SCHEDULES

FEEDER SIZE TAG - SEE POWER RISER SCHEDULE

ELEC EQUIP CONNECTION TAG - SEE EQUIP SCHEDULE

KEYNOTE

MISCELLANEOUS NOTE

#/C

XX

LIGHTING CONTROL SEQUENCE - SEE SCHEDULE

LC

XXX-X

RACEWAYS

CONDUIT CONCEALED IN CEILING OR WALLS

CONDUIT CONCEALED IN THE FLOOR OR BELOW

CONDUIT EXPOSED ON THE CEILING OR WALLS

CONDUIT BURIED UNDERGROUND (# = DEPTH)

CONDUIT WITH BEND DOWN

CONDUIT WITH BEND UP

CONDUIT WITH BUSHED END

CONDUIT WITH BREAK OR CONTINUATION

UG

CIRCUIT HOME RUN

- L1 INDICATES PANEL

- NUMBER

L1 1,3,5

JUNCTION BOX - WALL/CEILING MOUNT

WIREWAY, DUCT BANK, OR FLOOR DUCT AS NOTED

CABLE TRAY, TYPE/SIZE AS INDICATED

J J

X

R

RL

ELECTRICAL ABBREVIATIONS

AMPERES

ABOVE

ADDENDUM

AVAILABLE FAULT CURRENT

ABOVE FINISHED FLOOR

AIR HANDLING UNIT

ALUMINUM

ANTENNA

A, AMP

ABV

ADD

AFC

AFF

AHU

AL

ANT

ABOVE COUNTERAC

ARC FAULT CIRCUIT INTERRUPTERAFCI

BELOW FINISHED CEILING

BOLTED PRESSURE SWITCH

BFC

BPS

AUTOMATIC TRANSFER SWITCHATS

BUILDING AUTOMATION SYSTEMBAS

COPPER

DISTRIBUTED ANTENNA SYSTEM

ELECTRICAL CONTRACTOR

ELECTRIC OR ELECTRICAL

EMERGENCY

ELECTRICAL METALLIC TUBING

ENCLOSURE

ELECTRIC PNEUMATIC

EMERGENCY POWER OFF

CU

DAS

EC

ELEC

EM

EMT

ENCL

EP

EPO

CONDUIT OR CONTROLLED RECEPT

CIRCUIT BREAKER

CLOSED CIRCUIT TV

CIRCUIT

CABINET

C

CAB

CB

CCTV

CKT

ELECTRIC WATER COOLER

FUSE OR FUSED

FIRE ALARM

FLOOR BOX

FIRE-SMOKE DAMPER

GROUND

GROUND FAULT CIRCUIT INTERRUPTER

ISOLATED GROUND

JUNCTION BOX

KILOVOLT

KILOVOLT-AMP

KILOWATT

KILOWATT-HOUR

FILM VIEWER

EWC

F

FA

FB

FSD

FV

G, GND

GFI, GFCI

IG

JBOX

KV

KVA

KW

KWH

MAIN CIRCUIT BREAKER

MOMENTARY CONTACT OR

NATIONAL ELECTRICAL CODE

NOT IN CONTRACT

NOT TO SCALE

ON CENTER

PULL BOX OR PUSHBUTTON

NORMALLY OPEN

NORMALLY CLOSED

MAIN SWITCHBOARD

MC

MCB

MSB

NC

NEC

NIC

NO

NTS

OC

PB

MAIN LUG ONLYMLO

MOTOR RATED SWITCHMR

EMPTYMT

PNEUMATIC ELECTRIC

POWER FACTOR

PHASE

PRIMARY

PANEL

REFRIGERATOR

SECONDARY

SWITCH

SWITCHBOARD

SPEAKER

ROOF TOP UNIT

RECEPTACLE

TELEPHONE

PE

PF

PH

PNL

PRI

RECEPT

REFG

RTU

SEC

SW

SWBD

SPKR

TEL

TAMPER RESISTANTTR

THERMOSTAT

TYPICAL

UNDER COUNTER

UNDER GROUND

UNLESS NOTED OTHERWISE

VOLT OR VOLTAGE

VOLT-AMP

VOLTS ALTERNATING CURRENT

UNIT HEATER

VOLTS DIRECT CURRENT

WATT, WIRE OR WALL PHONE

WEATHERPROOF

EXISTING

TSTAT

TYP

UC

UG

UH

UNO

V

VA

VAC

VDC

W

WP

X

UNIVERSAL SERIAL BUSUSB

18"

18"

18"

18"

18"

18"

18"

VERIFY

VERIFY

VERIFY

VERIFY

VERIFY

VERIFY

VERIFY

VERIFY

VERIFY

18"

18"

18"

18"

BRANCH CIRCUIT PANEL

EQUIPMENT CABINET

TS=TRANSFER SWITCH

MOTOR OR MOTOR CONNECTION

MOTOR CONTROLLER, STARTER OR VFD

COMBINATION STARTER & DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

MOTOR RATED TOGGLE

MANUAL MOTOR STARTER SWITCH WITH THERMAL

OVERLOAD

DUPLEX RECEPTACLE - WALL/CEILING MOUNT

EMERGENCY DUPLEX RECEPTACLE - WALL/CEILING

MOUNT

QUADPLEX RECEPTACLE - WALL/CEILING MOUNT

GFI RECEPTACLE, DUPLEX/QUADPLEX - WALL MOUNT

SPECIAL PURPOSE RECEPTACLE - WALL/CEILING

MOUNT

POKE-THRU - DEVICES AS INDICATED

POWER POLE - DEVICES AS INDICATED

EMERGENCY SPECIAL PURPOSE RECEPTACLE -

WALL/CEILING MOUNT

MR

MMS

G G

P

GFI DEAD FRONT DEVICE, NORMAL/EMERGENCY -

WALL MOUNT

C

SPLIT DUPLEX RECEPTACLE - WALL/CEILING MOUNT

SIMPLEX RECEPTACLE - WALL/CEILING MOUNT

EMERGENCY SIMPLEX RECEPTACLE - WALL/CEILING

MOUNT

DUPLEX RECEPTACLE - CONTROLLED - WALL/CEILING

MOUNT

EMERGENCY QUADPLEX RECEPTACLE - WALL/CEILING

MOUNT

GROUND REFERENCE BUS - AS NOTED - WALL/CEILING

MOUNT

VERIFY

EMERGENCY SPLIT DUPLEX RECEPTACLE -

WALL/CEILING MOUNT

LIGHT FIXTURE ID - REFER TO LIGHT FIXTURE SCHEDULE

(SCHEDULE OVERRIDES SYMBOL ABBREVIATION)

A - INDICATES LIGHT FIXTURE TYPE

# - INDICATES CIRCUIT NUMBER

b - INDICATES SWITCHING

LIGHT FIXTURE CIRCUIT TYPE

- NO HATCH INDICATES NORMAL CIRCUIT

- ANGLED HATCH INDICATES CRITICAL CIRCUIT

- SOLID HATCH INDICATES LIFE SAFETY CIRCUIT

TROFFER TYPE LIGHT FIXTURE, SIZE AS INDICATED -

CEILING MOUNT

CHANNEL OR INDUSTRIAL, LENGTH AS INDICATED

ROUND DOWNLIGHT, RECESSED OR SURFACE MOUNT

CEILING WALL WASH FIXTURE OR TRACK HEAD

WALL MOUNT FIXTURE OR SCONCE

LINEAR RECESSED, LENGTH AS INDICATED

UNDER CABINET FIXTURE, LENGTH AS INDICATED

TRACK FIXTURE, NUMBER OF HEADS AS INDICATED

EMERGENCY BATTERY LIGHT - WALL/CEILING MOUNT

EXIT LIGHT, FILLED QUADRANT INDICATES FACES -

WALL/CEILING MOUNT

VERIFY

SITE LIGHTING ROUND OR SQUARE BOLLARD

SITE LIGHTING POLE FIXTURE, ROUND/RECTANGLE

HEAD - NUMBER OF HEADS INDICATED

b

A

LINEAR SUSPENDED , LENGTH AS INDICATED VERIFY

VERIFY

SQUARE DOWNLIGHT, RECESSED OR SURFACE MOUNT

CHANNEL OR INDUSTRIAL WALL MOUNT, LENGTH AS

INDICATED

ROUND OR SQUARE PENDANT

TAPE OR ROPE LIGHT

VANITY FIXTURE

WALL PACK

FLAG OR FLOOD LIGHT

VERIFY

VERIFY

SINGLE POLE TOGGLE SWITCH

DOUBLE POLE TOGGLE SWITCH

THREE WAY TOGGLE SWITCH

FOUR WAY TOGGLE SWITCH

TOGGLE SWITCH - "a" INDICATES SWITCHING a

48"

PILOT LIGHT TOGGLE SWITCH

ILLUMINATED TOGGLE - TOGGLE SWITCH

KEYED SWITCH

MOMENTARY CONTACT TOGGLE SWITCH

TIMER SWITCH

DIMMER SWITCH

OCCUPANCY SENSOR - CLG MOUNT

OCCUPANCY SENSOR WALL SWITCH

PHOTO ELECTRIC CELL

TIME CLOCK

CONTACTOR

RELAY

IL

K

MC

TS

OS

PUSH BUTTON STATION - BUTTONS AS INDICATED

48"

48"

48"

48"

48"

48"

48"

48"

48"

48"

48"

48"

60"

60"

PC

TC

C

R

D

MULTI SWITCH, MULTI GANG BOX 48"

VERIFY

VERIFY

PUSH BUTTON SWITCHB 48"

SIGNAL AND COMMUNICATIONS

DATA OUTLET - WALL/CEILING MOUNT

(# = WIRE COUNTS)

VOICE/DATA OUTLET - WALL/CEILING MOUNT

FLOOR OUTLET (# = WIRE COUNTS)

WALL PHONE - HIGH WALL MOUNT

WIRELESS ACCESS POINT - WALL/CEILING MOUNT

18"

SPEAKER - WALL/CEILING MOUNT

HORN SPEAKER - WALL MOUNT

VOLUME SWITCH - WALL MOUNT

AUDIO JACK (M=MICROPHONE, A=AUXILIARY)

BUZZER - WALL/CEILING MOUNT

BELL - WALL/CEILING MOUNT

CHIME - WALL/CEILING MOUNT

CLOCK - WALL/CEILING MOUNT (# = DIAMETER)

PROJECTOR/VIDEO CAMERA/DOCUMENT

CAMERA - WALL/CEILING MOUNT

TV SYSTEM OUTLET - WALL/CEILING MOUNT

ANNUNCIATOR PANEL - WALL MOUNT TYPICAL

60"

96"

48"

18"

96"

VERIFY

18"

WALL INTERCOM STATION (M=MASTER, R=REMOTE) 48"

96"

96"

96"

18"

96"

W

PRJ

AUDIO VIDEO SYSTEM OUTLET - WALL/CEILING MOUNT 18"

A/V SYSTEMS CONTROLLER - WALL MOUNT 18"

S

S S

C C

ICM

AM

V

VID

SECURITY

SECURITY - WALL MOUNT - TYPICAL

ES

EL

DC

GB

48"

SECURITY PANEL - WALL MOUNT - TYPICAL VERIFY

S

S

SECURITY CAMERA - WALL/CEILING MOUNT

VERIFY

CR

EP

SECURITY - CEILING MOUNT - TYPICAL

SWITCHES AND CONTROLS

LIGHTING

POWER

A.

B.

C.

D.

TRANSFORMERXFMR

ABOVE GRADEAG

AUDIBLE ALARMAA

CEILING CLG

DOWNDN

DEDICATEDDED

COMMUNICATIONSCOMM

CONTROL CTRL

FIRE ALARM ANNUNCIATOR PANELFAAP

FIRE ALARM CONTROL PANELFACP

FIBER OPTICFO

SINGLE MODE FIBER OPTICSMFO

MULTI MODE FIBER OPTICMMFO

GROUND FAULT EQUIPMENT PROTECTIONGFEP

GENERAL CONTRACTORGC

CURRENT TRANSFORMERCT

ABOVE COUNTER HEIGHTACH

AUDIO VISUALAV

AMERICAN WIRE GUAGEAWG

MOTOR CONTROL CENTERMCC

METER M

MAN HOLEMH

NEUTRALN

HAND HOLEHH

HAND OFF AUTOHOA

POTENTIAL TRANSFORMERPT

MECHANICAL CONTRACTOR

RACEWAYR

UNDER FLOORUF

WIRELESS ACCESS POINTWAP

SHIELDED TWISTED PAIRSTP

SUBSTATIONSUB

UNSHIELDED TWISTED PAIRUTP

ELECTRICAL GROUND BAREGB

SERVICE GROUND BARSGB

TELECOMMUNICATIONSTELCOM

TELECOMMUNICATIONS MAIN GROUND BARTMGB

TELECOMMUNICATIONS GROUND BARTGB

DESIGNATIONSSYMBOL

MTG

HT

DESIGNATIONSSYMBOL

MTG

HT

ELECTRICAL SYMBOLS LEGEND

VERIFY

VERIFY

C

18"

A/V MONITOR - WALL MOUNT 18"MT

CX

AV

TV

AV

TV

X" H

X" W

X' - X" AFF

CABLE TRAY TAG

X" W - WIDTH OF CABLE TRAY

X" H - HEIGHT OF CABLE TRAY

X' - X" AFF - MOUNTING HEIGHT OF CABLE TRAY (FROM FINISH

FLOOR TO BOTTOM OF TRAY)

GFI RECEPTACLE, DUPLEX/QUADPLEX - CEILING MOUNT

18"

DESIGNATIONSSYMBOL

MTG

HT

MOTORMTR

VERIFYDISCONNECT SWITCH

GFI RECEPTACLE, DUPLEX/QUADPLEX - CONTROLLED -

CEILING MOUNT

CC

SEC - SECURITY

IDS - INTRUSION DETECTION SYSTEM

CA - CARD ACCESS

CR/KP

DS

ANN

TWO-POST RACK

FLOOR

FOUR-POST RACK

FLOOR

DATA CABINET

FLOOR

FIRE ALARM

FIRE ALARM - WALL MOUNTED - TYPICAL

DUCT MOUNTED PHOTOELECTRIC DETECTOR

FIREMAN'S STATION - WALL MOUNT

STROBE - WALL/CEILING MOUNT (# = CANDELA)

BELL - WALL/CEILING MOUNT

BELL/STROBE - WALL/CEILING MOUNT (# = CANDELA)

CHIME - WALL/CEILING MOUNT

CHIME/STROBE - WALL/CEILING MOUNT (# = CANDELA)

HORN - WALL/CEILING MOUNT

HORN/STROBE - WALL/CEILING MOUNT (# = CANDELA)

SPEAKER - WALL/CEILING MOUNT

SPEAKER/STROBE - WALL/CEILING MOUNT

(# = CANDELA)

NOTED

48"

82"

82"

82"

82"

82"

82"

82"

82"

82"

FIRE ALARM PANEL - WALL MOUNT

F

F

F F

F F

F F

F F

F F

F F

F F S S

SS

FS

FIRE ALARM/ALERT NOTIFICATION:

SPEAKER/STROBE - WALL/CEILING MOUNT

(# = CANDELA)

82"F A

S SA F

F F

F F C C

CC

VERIFY

FACP

FAAP

VESDA

NAC

AMP

MANUAL PULL STATION (48")

REMOTE STATION (72")

DOOR HOLD

REMOTE INDICATOR LAMP (72")

FIRE ALARM - CEILING MOUNTED - TYPICALF

HEAT DETECTOR

(FIXED TEMP [°F] )

HEAT DETECTOR

(RATE OF RISE [°F] PER MINUTE)

SMOKE DETECTOR

(PHOTO ELEC)

BEAM DETECTOR

(TRANSMITTER)

BEAM DETECTOR

(RECEIVER)

COMBINATION SMOKE

DETECTOR AND ALARM

SMOKE DUCT/DAMPER

CONNECTION

FLOW SWITCH

TAMPER SWITCH

MONITOR MODULE

CONTROL MODULE

AIR SAMPLING

CEILING PROTECTION

FLOOR PROTECTIONCLG

CURRENT LIMITER VERIFYCL _A

ATS=AUTOMATIC TRANSFER SWITCH

T=TRANSFORMER

UPS=UNITERUPTABLE POWER SUPPLY

CEILING FAN

FLOOR BOX - DEVICES AS INDICATED

COMBINATION DUCT MOUNTED PHOTOELECTRIC

DETECTOR/SMOKE DAMPER CONNECTION

FSD

CH

DB

DA

DZ

DO

IC

IR

REQUEST TO EXIT

ELECTRIC STRIKE

ELECTRIC LOCK

MAGNETIC LOCK

POWER TRANSFER HINGE

DOOR CONTACT

OVERHEAD DOOR CONTACT

MONITOR STRIKE

MOTION DETECTOR

GLASS BREAKER DETECTOR

CARD READER

KEYPAD

EXIT PUSHBUTTON

MASTER INTERCOM &

DIRECTORY UNIT

KEY SWITCH

PUSH BUTTON

CARD READER W/ KEY PAD

DURESS SYSTEM

DOOR CHIME

DOOR BELL

DOOR ALARM

DOOR BUZZER

ELECTRIC DOOR OPENER

INTERCOM UNIT

INFRA-RED DETECTOR

MASTER STATION

KP

KS

ML

MI

M

MS

MD

PB

MICROWAVEMW

ODC

PANIC BARP

RX

TH

SECURITY ANTENNAS

ULTRASONIC DETECTORUD

MP

RS

R

B-T

B-R

FS

TS

AS

CP

FP

DH

RI

P

I

MM

CM

SA

SD

SMOKE DETECTOR

(IONIZATION)

FIRE ALARM CONTROL PANEL

AMPLIFIER

ASPIRATING SMOKE

DETECTION

FIRE ALARM ANNUNCIATOR PANEL

NOTIFICATION APPLIANCE CIRCUIT

W W

FIRE ALARM/ALERT NOTIFICATION:

HORN/STROBE - WALL/CEILING MOUNT

(# = CANDELA)

82"F A

A F

FIRE ALARM/MASS NOTIFICATION

F=FIRE ALARM / A=ALERT

R [RED] = HAZARD, W [WHITE] = FIRE ALARM,

B…

This is the start of the file's text. The full file is on GovTribe.