3-Drawings -Riverside ES Roof Replacement - Drawings Issued For Construction.pdf
PDF 12 MB Posted
- Attached to
- Riverside Elementary School Roof Replacement
- Solicitation number
- Bid #030326A
- Issued by
- Olmsted County, Minnesota
About this file
This is a construction drawing set for the Riverside Elementary School Roof Replacement project in Rochester, Minnesota, prepared by CRW Architecture + Design Group in coordination with Dunham Engineering for mechanical design. The project involves the complete removal and replacement of approximately 23,000 square feet of existing low-slope ballasted EPDM membrane roof systems down to the metal deck and installation of new fully-adhered EPDM membrane roofing systems. The scope of work includes demolition of existing ballast, EPDM membrane, cover board, rigid polyisocyanurate insulation, metal trim and coping, roof drains, and miscellaneous roof penetrations. New construction work comprises installation of fully-adhered EPDM roofing membrane, new polyisocyanurate insulation (average 4-inch thickness providing R-24 value), cover board, new aluminum metal trim and coping, prefinished metal overflow scuppers, roof drains with new collar clamps and strainers, EPDM roof walkway pads, masonry flashing with counter-flashing, vapor barrier, and related roof penetration flashings. All existing roof-mounted mechanical equipment, including exhaust fans, intake hoods, relief hoods, condensing units, and flues, must be temporarily removed during roof work and reinstalled upon completion. The construction documents are issued for bidding dated February 10, 2026, and are based on the 2018 International Building Code, 2020 Minnesota State Building Code, and 2020 Minnesota Accessibility Code.
The project is classified as Type II-B construction with full sprinkler protection and Group A3 occupancy (assembly). While the existing roof system provides only R-24 insulation through 4-inch polyisocyanurate insulation, which does not meet current 2024 Minnesota Energy Code requirements for R-30 minimum, the retrofit is not feasible due to existing parapet heights, through-wall flashing heights, and equipment heights. The general contractor is responsible for obtaining all required permits, coordinating with utility companies 72 hours prior to construction, performing all temporary shoring and scaffolding, managing demolition debris removal, and ensuring compliance with OSHA safety requirements. Contractors must verify existing conditions and dimensions on-site prior to bidding and immediately report any discrepancies, code violations, or hazardous materials discoveries to the architect. The construction documents include detailed architectural, mechanical, and electrical drawings with demolition plans, roof plans, technical details, and photo references to support the bidding process.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OWNER
ARCHITECT
MECHANICAL DESIGN
ROCHESTER PUBLIC SCHOOLS
CONSTRUCTION SERVICES DEPARTMENT
393935 HIGHWAY 14 EAST
ROCHESTER, MINNESOTA 55904
CONTACT: BILL BURT
PHONE NUMBER: (507) 328-4505
EMAIL: wiburt@rochesterschools.org
CRW ARCHITECTURE + DESIGN GROUP
211 ELEVETH AVENUE NORTHWEST
ROCHESTER, MINNESOTA 55901
CONTACT: TROY DOKKEN
PHONE NUMBER: (507) 206-6201
EMAIL: tdokken@crwarchitecture.com
DUNHAM ENGINEERING
421 FIRST AVENUE SW - SUITE 201W
ROCHESTER, MINNESOTA 55902
CONTACT: MIKE SZUBERSKI
PHONE NUMBER: (507) 424-6868
EMAIL: mike.szuberski@dunhameng.com
N O
R T
H
SITE
6TH ST SE6TH ST SE
5T H
A V
E S
E
6T H
A V
E S
E
5T H
A V
E S
E
SCHEDULE OF REQUIRED PERMITS
DESCRIPTION OF PERMIT TYPE
PERMIT ARRANGED FOR AND
PAID FOR BY:
= NOT APPLICABLE= BY OWNER= BY CONTRACTOR
12. SIGNAGE PERMIT
11. FOOTING & FOUNDATION PERMIT
(IF PHASED PERMIT REQUESTED)
10. ZONING & BUILDING REVIEW & PERMIT
9. SITE GRADING PERMIT
8. SEWER & WATER CONNECTION PERMIT
7. TELEPHONE PERMIT
6. CABLE TELEVISION PERMIT
5. GAS UTILITY PERMIT
4. ELECTRICAL UTILITY PERMIT
3. DRIVEWAY APPROACH PERMIT
2. SIDEWALK PERMIT (IF APPLICABLE)
1. DEMOLITION PERMIT
A
B
C
D
E
F
P
O
N
M
L
K
J
H
G
R
S
T
U
V
W I
STANDARD ABBREVIATIONS
W/O.
W.C.
WD.
WDW.
WT.
W.W.F.
W.W.M.
VAR.
V.C.T.
U.L.
UNFIN.
U.N.O.
T.&G.
TEMP.
THK.
T.O.
T.V.
TYP.
SCHD.
SECT.
S.F.
SHT.
SHTG.
SIM.
SIM.REV.
SPEC.
STD.
STL.
STOR.
STRUCT.
SUSP.
SYM.
R.D.
REBAR
REF.
REINF.
REQ.
REV.
RM.
R.O.
PC.
PERF.
P.LAM.
PLYW.
O.C.
OF.D.
O.H.D.
OPNG.
OPP.
O.S.B.
N.I.C.
NO. / #
NOM.
N.T.S.
MAINT.
MATL.
MAX.
MECH.
MEMB.
MEZZ.
MFR.
MIN.
MIR.
MISC.
M.O.
MTD.
MTL.
LAM.
LAV.
L.F.
KIT.
JAN.
I.D.
IN.
INFO.
INSUL.
INT.
H.C.
HCP.
HDR.
HDWD
HDWR.
H.M.
HORIZ
HR.
HT./HGT.
GA
GALV.
G.C.
GYP. BD.
F.D.
FDN.
F.E.
F.E.CAB.
F.F.E.
FLR.
F.O.
F.R.P.
FT.
FTG.
FURN.
F.V.
DBL.
DEPT.
DET.
D.F.
DIA./ Ø
DIAG.
DIM.
DISP.
DN.
DR.
DS.
DWG.
C.I.P.
C.J.
C/L / ℄
CLG.
CLR.
C.M.U.
COL.
COMP.
CONC.
CONST.
CONT.
COORD.
CORR.
CPT.
CT.
BD.
BLDG.
BM.
B.O
BRG.
ACC.
A.C.T.
ADD.
ADJ.
A.F.F.
ALT.
APPROX.
ARCH.
AVG.
EA.
E.I.F.S.
E.J.
ELEC.
ELEV.
ENTR.
EQ.
EQUIP.
EXP.
EXIST.
ACCORDING/ACCORDION
ACOUSTICAL CEILING TILE
ADDENDUM
ADJUSTABLE/ADJACENT
ABOVE FINISHED FLOOR
ALTERNATE/ALTERATION
APPROXIMATE
ARCHITECT/ARCHITECTURAL
AVERAGE
BOARD
BUILDING
BEAM
BOTTOM OF
BEARING
DOUBLE
DEPARTMENT
DETAIL
DRINKING FOUNTAIN
DIAMETER
DIAGONAL
DIMENSION
DISPOSAL
DOWN
DOOR
DOWNSPOUT
DRAWING
EACH
EXTERIOR INSUL. FINISH SYSTEM
EXPANSION JOINT
ELECTRICAL
ELEVATOR / ELEVATION
ENTRANCE
EQUAL
EQUIPMENT
EXPANSION
EXISTING
CAST IRON PIPE/CAST IN PLACE
CONTROL JOINT
CENTER-LINE
CEILING
CLEAR
CONCRETE MASONRY UNITS
COLUMN
COMPOSITE/COMPOSITION
CONCRETE
CONSTRUCTION
CONTINUOUS
COORDINATE
CORRIDOR
CARPET
CERAMIC TILE
FLOOR DRAIN
FOUNDATION
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FINISH FLOOR ELEVATION
FLOOR
FACE OF
FIBERGLASS REINFORCED PANEL
FOOT OR FEET
FOOTING
FURNACE/FURNISH
FIELD VERIFY
GAUGE
GALVANIZED
GENERAL CONTRACTOR
GYPSUM BOARD
HOLLOW CORE
HANDICAP
HEADER
HARDWOOD
HARDWARE
HOLLOW METAL
HORIZONTAL
HOUR
HEIGHT
INSIDE DIMENSION
INCHES
INFORMATION
INSULATION
INTERIOR
LAMINATED
LAVATORY
LINEAL FOOT
KITCHEN
JANITOR
MAINTENANCE/MAINTAIN
MATERIAL
MAXIMUM
MECHANICAL
MEMBRANE
MEZZANINE
MANUFACTURER
MINIMUM/MINUTE
MIRROR
MISCELLANEOUS
MASONRY OPENING
MOUNTED
METAL
NOT IN CONTRACT
NUMBER
NOMINAL
NOT TO SCALE
ON CENTER
OVERFLOW DRAIN
OVERHEAD DOOR
OPENING
OPPOSITE
ORIENTED STRAND BOARD
PRECAST
PERFORATED
PLASTIC LAMINATE
PLYWOOD
ROOF DRAIN
REINFORCING BAR
REFERENCE/REFRIGERATOR
REINFORCED
REQUIRED
REVISION/REVERSE
ROOM
ROUGH OPENING
SCHEDULE
SECTION
SQUARE FEET
SHEET
SHEATHING
SIMILAR
SIMILAR REVERSE
SPECIFICATION
STANDARD
STEEL
STORAGE
STRUCTURE/STRUCTURAL
SUSPENDED
SYMBOL
TONGUE AND GROOVE
TEMPERED/TEMPORARY/TEMPERATURE
THICK
TOP OF
TELEVISION
TYPICAL
UNDERWRITERS LABORATORIES, INC.
UNFINISHED
UNLESS NOTED OTHERWISE
VARIES
VINYL-COMPOSITION TILE
WITHOUT
WATER CLOSET
WOOD
WINDOW
WEIGHT
WELDED WIRE FABRIC
WELDED WIRE MESH
O.F.C.I. OWNER FURNISHED
CONTRACTOR INSTALLED
GRAPHIC SYMBOLS
100A
ROOM TAG
Room Name
DOOR TAG
WINDOW TAG1t
WALL PARTITION TYPE
FIRE EXTINGUISHER CABINET
A101
SIM
F.E.C
F.E
ELEVATION NUMBER
SHEET NUMBER
BUILDING SECTION NUMBER
SHEET NUMBER
FIRE EXTINGUISHER CABINET
INTERIOR ELEVATION MARK
ELEVATION MARKER
A1.100
Ref
Ref
R e fR e f
XX
2h
A101
Ref
1Ref 1 Ref
Ref
Name Elevation
4 5
6 8
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
CONSTRUCTION DOCUMENT SET
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.46.21 www.crwarchitecture.com
CLIENT
CD SET 02/10/26
A u to d e s k D o c s /R
P S
R iv e rs id e E
S R o o f R e p la c e m e n t/
-0
R
P S
R iv e rs id e
E S
R o o f R e p la c e m e n t (R rv t
/1
/2
:5
:4
P
M
G0.00
JASON WOODHOUSE
44421 02/10/2026
COVER SHEET
R O
C H
E S
T E
R
M
IN
N E
S O
T A
R P
S R
IV
E
R S
ID
E
E S
R O
O F
R E
P
LA
C E
M E
N T
26-004
02/10/2026
TmD,LG
JW
RPS RIVERSIDE ES ROOF
REPLACEMENTROCHESTER, MINNESOTA
PLANS ISSUED:02/10/2026
1-GENERAL INFORMATION
G0.00 COVER SHEET
2-ARCHITECTURAL DEMO
AD1.00 ROOF DEMO PLAN
3-ARCHITECTURAL
A1.00 ROOF PLAN
A4.10 DETAILS
A4.11 PARTIAL EXISTING PHOTO REFERENCE
A4.12 PARTIAL EXISTING PHOTO REFERENCE
4-MECHANICAL
M0.0 MECHANICAL SYMBOLS AND ABBREVIATIONS
MD1.00 ROOF MECHANICAL DEMOLITION PLAN
M1.00 ROOF MECHANICAL PLAN
5-ELECTRICAL
E0.00 ELECTRICAL TITLE SHEET
ED1.00 ROOF ELECTRICAL DEMOLITION PLAN
E1.00 ROOF ELECTRICAL PLAN
CODE INFORMATION: SHEET INDEXSITE LOCATION MAP
BUILDING LEGEND
NOT TO SCALE
2018 INTERNATIONAL BUILDING CODE
2020 MINNESOTA STATE BUILDING CODE
2020 MINNESOTA ACCESSIBILITY CODE
PROPOSED PROJECT SUMMARY:
THE PROJECTS CONSIST OF REPLACING THE EXISTING BALLASTED EPDM ROOFS, COVER
BOARD, ROOF INSULATION, COPINGS AND TRIM REQUIRED FOR RE-ROOFING TO A FULLY
ADHERED EPDM ROOF SYSTEM. WORK INCLUDES GENERAL MECHANICAL, ELECTRICAL AND
ARCHITECTURAL ROOFING SCOPE.
(NO ADDITIONAL BUILDING SQUARE FOOTAGE ADDED, CHANGE IN EXISTING BUILDING
SEPARATIONS AND MODIFICATIONS MADE TO EXISTING PARTITION RATINGS WITHIN THIS
PROJECT SCOPE)
OCCUPANCY CLASSIFICATION (CHAPTER 3):
GROUP A3 - ASSEMBLY (UNCHANGED)
TYPE OF CONSTRUCTION (CHAPTER 6):
TYPE II-B CONSTRUCTION, FULL SPRINKLERED (UNCHANGED)
2024 MINNESOTA ENERGY CODE
TABLE 5.5-6 BUILDING ENVELOPE REQUIREMENTS FOR CLIMATE ZONE 6
ROOF - INSULATION ENTIRELY ABOVE DECK:
NON-RESIDENTIAL, INSULATION MIN. R-VALUE: R-30 C.I.
THE PROJECT CONSISTS OF THE REPLACEMENT OF AN EXISTING LOW-SLOPE BALLASTED
MEMBRANE ROOF SYSTEM WITH A NEW FULLY ADHERED MEMBRANE ROOF SYSTEM. DUE TO
EXISTING CONDITIONS, THE NEW ROOF SYSTEM WILL BE INSTALLED WITH THE SAME
THICKNESS OF RIGID INSULATION AS THE EXISTING ROOF SYSTEM, WHICH PROVIDES AN
AVERAGE INSULATION THICKNESS OF 4 INCHES. THE NEW SYSTEM WILL UTILIZE
POLYISOCYANURATE INSULATION PROVIDING AN AVERAGE R-VALUE OF R-24. THIS DOES NOT
MEET CURRENT ENERGY CODES BUT WAS COMPLIANT WHEN ORIGINALLY CONSTRUCTED.
DUE TO EXISTING PARAPET HEIGHTS, THRU-WALL FLASHING HEIGHTS AND EQUIPMENT
HEIGHTS, IT IS NOT FEASIBLE TO INCREASE THE R-VALUE AS PART OF THE ROOF
REPLACEMENT PROJECT.
1. UNLESS SPECIFICALLY NOTED OTHERWISE, ALL DETAILS, SECTIONS, NOTES, ETC. ARE
TO BE CONSIDERED AS BEING TYPICAL AT ALL SIMILAR LOCATIONS OR CONDITIONS. IN
THESE DOCUMENTS, DETAILS, NOTES, ETC. ARE NOT INDICATED OR REFERENCED AT
ALL POSSIBLE APPLICABLE LOCATIONS.
2. THE SPECIFICATIONS AS PREPARED BY CRW ARCHITECTURE + DESIGN GROUP SHALL
BE CONSIDERED A PART OF THESE DOCUMENTS AS IF BOUND HEREIN.
3. THE CONTRACTOR SHALL NOTIFY ALL APPROPRIATE ENGINEERING DEPARTMENTS AND
UTILITY COMPANIES 72 HOURS PRIOR TO CONSTRUCTION. ALL NECESSARY
PRECAUTIONS SHALL BE TAKEN TO AVOID DAMAGE TO ANY EXISTING UTILITY.
4. BEFORE BIDDING, FABRICATION OR BEGINNING WORK, CONTRACTOR SHALL VISIT
PROJECT SITE, REVIEW ALL CONSTRUCTION DOCUMENTS AND UNDERSTAND THEM IN
THEIR ENTIRETY. THE CONSTRUCTION DOCUMENTS MUST BE VIEWED IN THEIR
ENTIRETY AS COMPLETE SETS.
5. BEFORE BIDDING, FABRICATION OR BEGINNING WORK, CONTRACTOR SHALL VISIT
PROJECT SITE AND FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, ETC.
6. CONTRACTOR SHALL IMMEDIATELY REPORT ANY DISCREPANCIES, CONTRADICTIONS OR
QUESTIONS REGARDING THE CONTRACT DOCUMENTS OR EXISTING CONDITIONS TO
THE ARCHITECT IMMEDIATELY FOR RESOLUTION.
7. CONTRACTOR SHALL IMMEDIATELY REPORT ANY CODE VIOLATIONS IN THE CONTRACT
DOCUMENTS TO THE ARCHITECT FOR RESOLUTION.
8. DO NOT SCALE DRAWINGS. IN ALL CASES STATED DIMENSIONS TAKE PRECEDENCE.
CONTACT ARCHITECT IMMEDIATELY FOR ADDITIONAL REQUIRED DIMENSIONS. GENERAL
CONTRACTOR SHALL VERIFY ALL DIMENSIONS, VERIFY AND COORDINATE WITH EXISTING
CONDITIONS AND COORDINATE THE WORK, TIMING AND PHASING OF ALL TRADES.
9. ALL DEMOLITION, NEW CONSTRUCTION, SITE WORK AT INTERIOR AND EXTERIOR OF
BUILDING SHALL BE IN CONFORMANCE WITH ALL APPLICABLE CODE REQUIREMENTS,
INCLUDING BUT NOT LIMITED TO, CURRENT BUILDING CODE
10. ALL FINISH MATERIALS SHALL CONFORM TO APPLICABLE FLAME SPREAD AND SMOKE
GENERATED REQUIREMENTS.
11. ALL FIRE RATED WALLS SHALL BE CONSTRUCTED PER APPROVED U.L. OR OTHER
ACCEPTABLE TESTING AGENCY REQUIREMENTS TO MEET OR EXCEED STATED FIRE
RATINGS. ALL PENETRATIONS OF FIRE RATED BUILDING ELEMENTS SHALL BE SIMILARLY
CONSTRUCTED PER LOCAL BUILDING CODE TO MAINTAIN REQUIRED FIRE RATINGS.
12. IF AT ANY TIME THE CONTRACTOR ENCOUNTERS OR UNCOVERS ASBESTOS
CONTAINING BUILDING MATERIALS OR OTHER POSSIBLE HAZARDOUS OR TOXIC
MATERIALS, IT'S PRESENCE SHALL BE IMMEDIATELY REPORTED TO ARCHITECT AND
BUILDING OWNER.
13. CONTRACTOR SHALL FOLLOW OSHA AND OTHER APPLICABLE SAFETY REQUIREMENTS
DURING ALL WORK INCLUDING BUT NOT LIMITED TO DEMOLITION, REPAIR AND
CONSTRUCTION.
14. ALL EXISTING MATERIALS TO REMAIN WHICH ARE DISTURBED OR DAMAGED AND ALL
OTHER CUTTING SHALL BE PATCHED BACK AS REQUIRED TO LIKE NEW CONDITION, TO
MATCH ADJACENT SURFACES AND TO MAKE SUCH REPAIR IMPERCEPTIBLE.
15. BEFORE DEMOLITION, FABRICATION OR CONSTRUCTION, CONTRACTOR SHALL VERIFY
THAT NO CONFLICTS EXIST IN LOCATIONS OR CLEARANCE REQUIREMENTS OF
STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING, TELECOMMUNICATIONS,
TELEPHONE, DATA OR FIRE PROTECTION SYSTEMS AND THEIR ELEMENTS.
16. FIREBLOCKING, FIRESTOPS, DRAFTSTOPPING SHALL BE INSTALLED AS REQUIRED BY
CURRENT LOCAL BUILDING CODE REQUIREMENTS. TYPICAL AS REQUIRED AT
PARTITIONS, CONCEALED COMBUSTIBLE SPACES, CONCEALED COMBUSTIBLE ATTIC
SPACES, FLOOR PENETRATIONS, PENETRATIONS THROUGH FIRE RATED PARTITIONS OR
OTHER STRUCTURES AS REQUIRED BY CURRENT CODE.
17. CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL TEMPORARY SHORING OR BRACING
AND FOR THE DESIGN, CONSTRUCTION, STABILITY AND SAFETY OF ALL TEMPORARY
STRUCTURES, ENCLOSURES AND SCAFFOLDING.
18. CONTRACTOR SHALL COORDINATE THE TIMING, PHASING AND EXECUTION OF ALL
CUTTING AND PATCHING FOR THE EFFICIENT AND TIMELY COMPLETION OF WORK.
19. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR TEMPORARY PROTECTION AT ANY
OPENINGS IN FLOORS, ROOFS, WALLS, ETC.
20. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR DETERMINING ERECTION
PROCEDURE AND CONSTRUCTION SEQUENCE IN ORDER TO ENSURE THE SAFETY OF
THE BUILDING, WORKMEN AND VISITORS.
21. CONTRACTOR SHALL SAFELY AND LEGALLY REMOVE AND DISPOSE OF ALL MATERIALS
NOT SCHEDULED TO BE SALVAGED OR RE-INSTALLED.
22. CONTRACTOR SHALL MAINTAIN A STAMPED, APPROVED SET OF CONSTRUCTION
DOCUMENTS WITH APPROVAL LETTER AND CURRENT SHOP DRAWINGS. DOCUMENTS
ON SITE SHALL BE KEPT UP TO DATE.
23. MATERIAL OR PRODUCT SUBSTITUTIONS SHALL FOLLOW THE SUBSTITUTION
REQUIREMENTS OF DIVISION 01 OF THE PROJECT SPECIFICATIONS DOCUMENT.
24. SHOP DRAWINGS OR OTHER SUBMITTALS SHALL FOLLOW THE SUBMITTAL
REQUIREMENTS OF DIVISION 01 OF THE PROJECT SPECIFICATIONS DOCUMENT.
25. VERIFY MINIMUM SLOPES TO DRAIN AS INDICATED ON THE DRAWINGS PRIOR TO THE
START OF CONSTRUCTION. NOTIFY THE ARCHITECT IMMEDIATELY UPON DISCOVERY OF
ANY DISCREPANCIES.
26. REPAIR EXISTING PUBLICLY OWNED FACILITIES OR STRUCTURES DAMAGED OR
ALTERED DURING DEMOLITION OR CONSTRUCTION TO THE SATISFACTION OF THE
LOCAL MUNICIPALITY.
27. EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE, CONTRACTOR SHALL ENSURE THAT
ALL FINISH MATERIALS SHALL BE APPLIED TO BE FLUSH WITH ADJACENT SURFACES AND
JOINTS.
28. CONTRACTOR TO PROVIDE AND INSTALL BLOCKING, DOUBLE STUDS, AND/OR ANCHOR
PLATES AS NECESSARY TO SUPPORT EQUIPMENT, PLUMBING FIXTURES, CASEWORK,
CABINETS, GRAB BARS, TOILET ROOM ACCESSORIES, SIGNAGE, HANDRAILS, ETC.
29. CONTRACTOR SHALL VERIFY ALL EQUIPMENT LOCATIONS, DIMENSIONS, AND ALL
REQUIRED CLEARANCES OF ALL EQUIPMENT. COORDINATE WITH DRAWINGS,
SPECIFICATIONS, EQUIPMENT MANUALS AND CUT SHEETS. VERIFY THAT STRUCTURAL
LOADS ARE ACCEPTABLE.
GENERAL NOTES
N O
R T
H
NO. REVISIONS DATE
7 7
EXISTING STANDING SEAM METAL ROOF
EXISTING STANDING SEAM METAL ROOF
EXISTING STANDING
SEAM METAL ROOF
EXISTING STANDING
SEAM METAL ROOF
EXISTING CANOPY BALLAST ROOF
EXISTING CANOPY BALLAST ROOF
EXISTING CANOPY BALLAST ROOF
EXISTING CANOPY BALLAST ROOF
EXISTING CANOPY BALLAST ROOF
R.D.
R.D.
O.D.
R.D.
O.D.
R.D.
EXISTING
OVERFLOW
SCUPPER
EXISTING
OVERFLOW
SCUPPER
R.D.
EXISTING
OVERFLOW
SCUPPER
R.D.
EXISTING
OVERFLOW
SCUPPER
R.D.
EXISTING
OVERFLOW
SCUPPER
R.D.
O.D. R.D.R.D. O.D.
O.D.
EXISTING
OVERFLOW
SCUPPER
R.D.
EXISTING
SCUPPER / D.S.
EXISTING
SCUPPER / D.S.
EXISTING
PRIMARY
SCUPPER
E X
IS
T
IN
G
P
R
IM
A
Y
S C
U P
P E
R
E X
IS
T
IM
A
U P
P E
R
DN
D N
D N
D N
DN
D N
DN
D N
DN
D N
DN
D N
DN
D N
D N
DN
D N
D N
D N
D N
DN
S L O
P E
D
C K
D N
D N
SLOPED
DECK DN
D N
D N
D N
D N
DN
D N
DN
D N
DN
S L O
P
C K
D N
S L O
P
C K
D N
S L O
P
C K
D N
SLOPE DN SLOPE DN
S
LO
P E
D N
S
LO
P E
D N
SLOPE DN
SLOPE DN
S
LO
P E
D N
S
LO
P E
D N
SLOPE DNSLOPE DN
S
LO
P E
D N
EXISTING
VERT. LADDER
DEMOLITION NOTES:
GENERAL DEMOLITION NOTES:
1. DASHED LINES REPRESENT EXISTING ITEMS TO BE REMOVED, U.N.O.
2. PROVIDE ALL WORK TO COMPLETE DEMOLITION AS MAY BE REQUIRED
TO ACCOMPLISH WORK AS SHOWN ON THE DRAWINGS UNLESS NOTED
OTHERWISE. ALL AS INDICATED OR REQUIRED RELATING TO THE
EXISTING BUILDING AND NOT OTHERWISE ASSIGNED IS INCLUDED
UNDER THE RESPONSIBILITY OF THE CONTRACTOR.
3. CONTRACTOR TO VERIFY EXISTING ELECTRICAL & PLUMBING
LOCATIONS PRIOR TO DEMOLITION. EXISTING PLUMBING AND
ELECTRICAL MAY REQUIRE MODIFICATION TO ACCOMPLISH THE NEW
DESIGN AS SHOWN ON THESE PLANS.
4. MECHANICAL, ELECTRICAL AND PLUMBING CONTRACTORS SHALL
TERMINATE ALL APPROPRIATE SERVICES TO EXISTING CONSTRUCTION
WHICH ARE TO BE PERMANENTLY DISCONNECTED. THEY SHALL
FURTHER MAKE ALL TEMPORARY SERVICE TERMINATIONS INDICATED
OR REQUIRED TO ACCOMPLISH THE DEMOLITION AND/OR NEW REVISED
OR REPLACED SERVICES AS PART OF WORK UNDER ALL CONTRACTS.
ALL PERMANENT TERMINATIONS SHALL BE REMOVED BACK TO THE
SOURCE. NO VACANT SERVICES SHALL BE LEFT IN PLACE.
5. CONTRACTORS ARE TO BE RESPONSIBLE FOR REMOVING AND HAULING
OF ALL DEMOLITION DEBRIS.
6. AT CONCLUSION OF DEMOLITION, ALL SURFACES SHALL BE READY TO
RECEIVE NEW FINISHES.
7. THIS ROOF PLAN IS FOR REFERENCE ONLY – FINAL ROOF DESIGN TO BE
BY ROOFING SUPPLIER AND TO BE INSTALLED ACCORDING PER
MANUFACTURER’S WARRANTY REQUIREMENTS. ALL FLASHING AND
ROOF PENETRATIONS PER MANUFACTURER’S DETAILS.
8. EXISTING MECHANICAL / ELECTRICAL EQUIPMENT / CURBS /
PENETRATIONS / OPENINGS ARE SHOWN AT APPROXIMATE LOCATIONS,
SEE MECHANICAL FOR MORE INFORMATION.
9. ENSURE OR ADJUST SECONDARY ROOF DRAINAGE SYSTEM, HEIGHT OF
OVERFLOW DRAIN TO BE 2” MAX. ABOVE PRIMARY ROOF DRAIN.
10. REMOVE ALL EXISTING PREFINISHED METAL WALL OVERFLOW
SCUPPERS.
1 REMOVE EXISTING BALLAST AND EPDM ROOFING MEMBRANE,
COVER BOARD, RIGID INSULATION (DOWN TO EXISTING METAL
DECK) AND ANY FASTENERS IN THEIR ENTIRETY.
(NOT ALL DEMOLITION NOTES APPEAR ON EVERY SHEET)
2 REMOVE EXISTING METAL TRIM / PARAPET COPING IN ITS
ENTIRETY AND ANY DAMAGED / UNUSABLE BLOCKING AND
DISPOSE OF PROPERLY.
3 REMOVE ANY ABANDONED MECHANICAL SUPPORT CURBS AND
FRAMING DOWN TO EXISTING ROOF DECK.
4 REMOVE ROOFTOP HATCH AND / OR PERIMETER FLASHING
NEEDED FOR INSTALLATION OF NEW ROOF.
5 REMOVE ALL ROOF DRAIN AND OVERFLOW DRAIN DOME
STRAINERS WITH COLLAR CLAMPS.
6 REMOVE CONCRETE WALKWAY PADS AND SUPPORTS AND
DISPOSE OF PROPERLY.
7 REMOVE EXISTING MECHANICAL HOODS, PIPE BOOTS AND OTHER
MECHANICAL NEEDED FOR INSTALLATION OF NEW ROOFING - SEE
MECH/ELEC.
8 REMOVE MASONRY FLASHING AND PLASTIC CELL VENTS ALONG
MASONRY WALL AT EPDM ROOFING.
9 CUT AND REMOVE APPROX. 1'-0" OF EXISTING STANDING SEAM
ROOFING TO REMOVE EXISTING DAMAGED AREAS AND GAIN
ACCESS UNDER ROOFING FOR TIE-IN ROOFING, PER
MANUFACTURERS RECOMMENDATIONS.
10 REMOVE EXISTING STANDING SEAM CAP TO ACCESS ROOF TIE-IN
FLASHING.
11 REMOVE EXISTING SATELLITE AND SUPPORTS AND DISPOSE OF
PROPERLY.
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.46.21 www.crwarchitecture.com
CLIENT
CD SET 02/10/26
A u to d e s k D o c s /R
P S
R iv e rs id e E
S R o o f R e p la c e m e n t/
-0
R
P S
R iv e rs id e
E S
R o o f R e p la c e m e n t (R rv t
/1
/2
:5
:4
P
M
AD1.00
JASON WOODHOUSE
44421 02/10/2026
ROOF DEMO PLAN
R O
C H
E S
T E
R
M
IN
N E
S O
T A
R P
S R
IV
E
R S
ID
E
E S
R O
O F
R E
P
LA
C E
M E
N T
26-004
02/10/2026
TmD,LG
JW
3/32" = 1'-0"
DEMO ROOF PLAN
NORTH
A4.10
A4.10
A4.10
A4.10
A4.10
A4.10
A4.10
A4.10
A4.10
EXISTING STANDING SEAM METAL ROOF
EXISTING STANDING SEAM METAL ROOF
EXISTING STANDING
SEAM METAL ROOF
EXISTING STANDING
SEAM METAL ROOF
R.D.
R.D.
O.D.
R.D.
O.D.
R.D.
EXISTING
OVERFLOW
SCUPPER
EXISTING
OVERFLOW
SCUPPER
R.D.
EXISTING
OVERFLOW
SCUPPER
R.D.
EXISTING
OVERFLOW
SCUPPER
R.D.
EXISTING
OVERFLOW
SCUPPER
R.D.
O.D. R.D.R.D. O.D.
O.D.
EXISTING
OVERFLOW
SCUPPER
R.D.
EXISTING
SCUPPER / D.S.
EXISTING
SCUPPER / D.S.
EXISTING
PRIMARY
SCUPPER
E X
IS
T
IM
A
U P
P E
R
E X
IS
T
IM
A
U P
P E
R
DN
D N
D N
D N
DN
D N
DN
D N
DN
D N
DN
D N
DN
D N
D N
DN
D N
D N
D N
D N
DN
S L O
P
C K
D N
D N
SLOPED
DECK DN
D N
D N
D N
D N
DN
D N
DN
D N
DN
S L O
P
C K
D N
S L O
P
C K
D N
S L O
P
C K
D N
3 3
7 7
A4.10
A4.10
A4.10
A4.10
SLOPE DN SLOPE DN
S
LO
P E
D N
S
LO
P E
D N
SLOPE DN
SLOPE DN
S
LO
P E
D N
S
LO
P E
D N
SLOPE DNSLOPE DN
S
LO
P E
D N
2 2
EXISTING
VERT. LADDER
11 11
2 1 2
1 2
2 2
DETAIL 12/A4.10
GENERAL ROOF PLAN NOTES:
1. ALL WORK SHALL BE PERFORMED IN COMPLIANCE WITH ALL
REQUIREMENTS OF THE OWNER. EACH TRADE CONTRACTOR SHALL BE
RESPONSIBLE FOR INITIATING, MAINTAINING AND SUPERVISING ALL
SAFETY PROCEDURES, PRECAUTIONS AND PROGRAMS IN CONNECTION
WITH THEIR WORK.
2. THE GENERAL CONTRACTOR SHALL FILE FOR AND OBTAIN ALL REQUIRED
PERMITS, LETTERS OF SATISFACTORY COMPLETION AND CERTIFICATES
OF OCCUPANCY FROM THE LOCAL BUILDING OFFICIALS.
3. ALL EQUIPMENT SHOWN AS DASHED IS BY THE OWNER. ELECTRICAL
CONTRACTOR TO VERIFY POWER REQUIREMENTS FOR OWNER'S
EQUIPMENT. MECHANICAL CONTRACTOR TO VERIFY PLUMBING AND
HVAC REQUIREMENTS OF OWNER'S EQUIP.
4. REFER TO THE STRUCTURAL, MECHANICAL, AND ELECTRICAL
DRAWINGS FOR ADDITIONAL WORK REQUIRED UNDER THIS CONTRACT.
5. THE GENERAL CONTRACTOR AND/OR MECHANICAL CONTRACTOR SHALL
COORDINATE ALL MECHANICAL WORK WITH THE OWNER'S
REPRESENTATIVE AND ALL OTHER TRADES.
6. THE GENERAL CONTRACTOR AND/OR ELECTRICAL CONTRACTOR SHALL
COORDINATE ALL ELECTRICAL WORK WITH THE OWNER'S
REPRESENTATIVE AND ALL OTHER TRADES.
7. THIS ROOF PLAN IS FOR REFERENCE ONLY – FINAL ROOF DESIGN TO BE
BY ROOFING SUPPLIER AND TO BE INSTALLED ACCORDING PER
MANUFACTURER’S WARRANTY REQUIREMENTS. ALL FLASHING AND
ROOF PENETRATIONS PER MANUFACTURER’S DETAILS.
8. EXISTING MECHANICAL / ELECTRICAL EQUIPMENT / CURBS /
PENETRATIONS / OPENINGS ARE SHOWN AT APPROXIMATE LOCATIONS,
SEE MECHANICAL FOR MORE INFORMATION.
9. ENSURE OR ADJUST SECONDARY ROOF DRAINAGE SYSTEM, HEIGHT OF
OVERFLOW DRAIN TO BE 2” MAX. ABOVE PRIMARY ROOF DRAIN.
10. PROVIDE TAPERED ROOF INSULATION CRICKETS AT MECHANICAL
EQUIPMENT, SLOPE ½” PER 12”.
11. PROVIDE TAPERED ROOF INSULATION CRICKETS BETWEEN DRAINS,
SLOPE ¼” PER 12”.
12. PROVIDE MINIMUM OF 3” THICKNESS OF TAPERED POLYISOCYRANURATE
INSULATION TO BE USED AT ALL LOCATIONS.
13. PROVIDE AND INSTALL ALL NEW PREFINISHED METAL WALL OVERFLOW
SCUPPERS - COLOR TO MATCH COPING.
ROOF PLAN NOTES:
1 INSTALL NEW FULLY ADHERED EPDM ROOFING SYSTEM
INCLUDING COVER BOARD, BASE AND TAPERED
POLYISOCYANURATE INSULATION. INSULATION THICKNESS
AND SLOPES TO MATCH EXISTING CONDITION, U.N.O.
2 INSTALL NEW PREFINISHED ALUMINUM TRIM / COPING SYSTEM
MATCHING THE DEMOLISHED COPING DIMENSIONS AND
COLOR
3 REINSTALL EXISTING MECHANICAL HOODS AND MECHANICAL
EQUIPMENT REMOVED DURING DEMOLITION, SEE 2/A4.10
4 REINSTALL ROOF HATCH AND NEW PERIMETER FLASHINGS -
SEE 7/A4.10
5 INSTALL ALL NEW ROOF DRAIN AND OVERFLOW COLLAR
CLAMPS WITH DOMED STRAINERS - SEE 6/A4.10
6 INSTALL NEW ADHERED EPDM ROOF WALKWAY PADS
COMPATIBLE WITH ROOFING SYSTEM TO MATCH EXISTING
WALKWAY ROUTES.
7 INSTALL NEW EPDM MANUFACTURED ROOF BOOT WITH
STAINLESS STEEL CLAMP, SEE PLUMB. FOR OTHER
LOCATIONS - SEE 3/A4.10 AND 4/A4.10
8 INSTALL NEW MASONRY FLASHING AND COUNTER FLASHING
WITH NEW PLASTIC CELL VENTS ALONG MASONRY WALL AT
EPDM ROOFING, COLORS TO MATCH EXISTING - SEE 8/A4.10
9 INSTALL NEW VAPOR BARRIER ON EXISTING METAL ROOF
DECK AND EXTEND VERTICALLY ALONG PERIMETER OF ROOF
INSULATION.
10 INSTALL NEW RAIL / GATE SYSTEM AND ROOF HATCH.
11 NEW GALVANIZED BALLASTED GUARDRAIL BY ROOFING
CONTRACTOR. SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.46.21 www.crwarchitecture.com
CLIENT
CD SET 02/10/26
A u to d e s k D o c s /R
P S
R iv e rs id e E
S R o o f R e p la c e m e n t/
-0
R
P S
R iv e rs id e
E S
R o o f R e p la c e m e n t (R rv t
/1
/2
:5
:4
P
M
A1.00
JASON WOODHOUSE
44421 02/10/2026
ROOF PLAN
R O
C H
E S
T E
R
M
IN
N E
S O
T A
R P
S R
IV
E
R S
ID
E
E S
R O
O F
R E
P
LA
C E
M E
N T
26-004
02/10/2026
TmD,LG
JW
3/32" = 1'-0"
ROOF PLAN
NORTH
RTU
WOOD NAILER
INSULATED
METAL CURB
USE APPROPRIATE
ELEVATE BONDING
ADHESIVE
METAL COUNTER-FLASHING
EPDM MEMBRANE
ROOF INSULATION AND
COVER BOARD
METAL ROOF DECK
CONT. BEAD EXTERIOR
SEALANT
CONTINUOUS BEAD
EXTERIOR SEALANT
PRE-MOLDED
MANUFACTURER
STEP FLASHING
CONTINUOUS BEAD
OF LAP SEALANT
ROOF FLASHING
CONTINUOUS BEAD OF
LAP SEALANT
STAINLESS STEEL
CLAMPING RING
FIELD FABRICATED
METAL HOOD
ROOF INSULATION
AND COVER BOARD
METAL ROOF DECK
PIPE CONDUIT-SEE
PLUMBING PLANS FOR
LOCATION AND SIZE OF
PENETRATIONS
CONTINUOUS SEALANT AS
REQUIRED
FLASHING AND COUNTER
FLASHING W/ ADHESIVES AS
REQUIRED
NOTE:
THESE DETAILS ILLUSTRATE INFORMATION REGARDING ROOFING
MEMBRANE INSTALLATION ONLY. REFER TO MANUFACTURER'S
DETAILS AND INSTALLATION REQUIREMENTS FOR SPECIFIC AND
COMPLETE INFORMATION TO INSURE WARRANTY COMPLIANCE.
EPDM MEMBRANE
ROOFING SYSTEM
ROOF INSULATION
AND COVER BOARD
ROOF HATCH
METAL COUNTER-FLASHING
USE APPROPRIATE BONDING
ADHESIVE
FULLY ADHERED EPDM
MEMBRANE ROOFING SYSTEM
ROOF INSULATION AND
COVER BOARD
METAL ROOF DECK
NEW STRAINER
NEW CLAMPING RING
ELECTROMETRIC MASTIC
UNDER ROOFING MEMBRANE
FULLY ADHERED EPDM
MEMBRANE ROOFING SYSTEM
DECK CLAMP
ROOF DRAIN
(EXISTING DISTANCE TO R.D.)
NEW PREFINISHED ALUM. METAL COPING -
COLOR TO MATCH EXISTING
EXTEND EPDM ROOFING MEMBRANE OVER PARAPET
EXISTING PARAPET
CONTIN. SEALANT
NEW PREFINISHED ALUM. THRU WALL SCUPPER
AND TRIM - COLOR TO MATCH EXISTING
FULLY ADHERED EPDM ROOF MEMBRANE SYSTEM
NEW ROOF INSULATION AND COVER BOARD
EXISITNG METAL ROOF DECK
EPDM ROOF FLASHING
NEW CONTINUOUS BEAD OF WATER BLOCK
EXISTING STEEL STANDING SEAM ROOF PANEL
EXISTING METAL PANEL UNDERLAYMENT
NEW EPDM MEMBRANE SYSTEM
FASTENER AND 2" METAL PLATE
REINF. PERIMETER FASTENING STRIP
REMOVE APPROX. 1'-0" OF EXISTING STEEL STANDING SEAM ROOF
PANELS TO REMOVE DAMAGED PORTIONS OF PANELS AND PROVIDE
ACCESS FOR NEW ROOF TIE-IN
NEW PREFINISHED STEEL TRIM MATCHING ROOF PANELS
OVERLAP NEW EPDM AND SECURE TO ROOF DECK
ROOF INSULATION
AND COVER BOARD
METAL ROOF DECK
NEW METAL COPING
METAL COUNTER-FLASHING
USE APPROPRIATE BONDING ADHESIVE
FULLY ADHERED EPDM MEMBRANE
ROOFING SYSTEM
ROOF INSULATION AND
COVER BOARD
METAL ROOF DECK
SEE DETAIL 11/A4.10 FOR
FLASHING DETAIL
USE APPROPRIATE BONDING
ADHESIVE
FULL ADHERED EPDM
MEMBRANE ROOFING SYSTEM
ROOF INSULATION AND
COVER BOARD
METAL ROOF DECK
URETHANE ROD
1 PART POLYURETHANE SEALANT
FASTEN IN HEAD OR BEAD
OF MORTAR JOINT
NEW OR EXISTING REGLET
METAL RECEIVER AND COUNTER FLASHING
ADHERE MEMBRANE UP WALL AND
FASTEN TOP WITH ALUMINUM
COMPRESSION BAR 1/2" O.C.
INSTALL WATER STOP SEALANT BEHIND EPDM
REINFORCED PERIMETER SECUREMENT STRIP
WITH FASTENER PLATES 12" O.C.
EPDM MEMBRANE
INSULATION AS SPECIFIED
EXISTING DECK
MECHANICAL FASTENER AND/OR ADHESIVE
POURABLE SEALER
CUT PVC PIPE
QUICKSEAM PENETRATION
POCKET FASTENING STRIP
APPROPRIATE PRIMER
MEMBRANE ADHESIVE
EPDM MEMBRANE
ROOF INSULATION AND
COVER BOARD NON-SHRINKING GROUT
EXISTING SUBSTRATE
6" M
IN
APPROX. 1
/2" G
AP
SHEET METAL JOINT COVER
SET IN SEALANT ON EACH SIDE
PREFINISHED ALUMINUM COPING
COPING WITH COVER PLATE
NOTE:
1. CONTINUOUS CLEAT NOT SHOWN FOR CLARITY.
2. COPING JOINERY IS SIMILAR ON BOTH SIDES.
3. REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.46.21 www.crwarchitecture.com
CLIENT
CD SET 02/10/26
A u to d e s k D o c s /R
P S
R iv e rs id e E
S R o o f R e p la c e m e n t/
-0
R
P S
R iv e rs id e
E S
R o o f R e p la c e m e n t (R rv t
/1
/2
:5
:5
P
M
A4.10
JASON WOODHOUSE
44421 02/10/2026
DETAILS
R O
C H
E S
T E
R
M
IN
N E
S O
T A
R P
S R
IV
E
R S
ID
E
E S
R O
O F
R E
P
LA
C E
M E
N T
26-004
02/10/2026
TmD,LG
JW
3" = 1'-0"
MECHANICAL CURB
3" = 1'-0"
PIPE PENETRATION WITH PIPE FLASHING
3" = 1'-0"
TYPICAL PIPE FLASHING
1 1/2" = 1'-0"
EXISTING ROOF HATCH
1 1/2" = 1'-0"
TYPICAL ROOF DRAIN
1 1/2" = 1'-0"
OVERFLOW SCUPPER AND ROOF DRAIN TYP.
1 1/2" = 1'-0"
EXISTING SLOPED ROOF TO FLAT ROOF
1 1/2" = 1'-0"
EXISTING SLOPED ROOF AT PEAK
1 1/2" = 1'-0"
EXISTING LOW ROOF TO WALL
1 1/2" = 1'-0"
ROOF TO BRICK WALL DETAIL
3" = 1'-0"
MULTIPLE PIPE PENETRATION
3" = 1'-0"
COPING SLICE DETAIL WITH EXPOSED COVER PLATES
1 2
7 8
17 18
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.46.21 www.crwarchitecture.com
CLIENT
CD SET 02/10/26
A u to d e s k D o c s /R
P S
R iv e rs id e E
S R o o f R e p la c e m e n t/
-0
R
P S
R iv e rs id e
E S
R o o f R e p la c e m e n t (R rv t
/1
/2
:5
:0
P
M
A4.11
JASON WOODHOUSE
44421 02/10/2026
PARTIAL EXISTING PHOTO
REFERENCE
R O
C H
E S
T E
R
M
IN
N E
S O
T A
R P
S R
IV
E
R S
ID
E
E S
R O
O F
R E
P
LA
C E
M E
N T
26-004
02/10/2026
TmD,LG
JW
1 2 3 4 5
7 8 9 10
12 13 14 15
17 18 19
1" = 30'-0"
EXISITING ROOF PLAN
1 2
7 8
17 18
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.46.21 www.crwarchitecture.com
CLIENT
CD SET 02/10/26
A u to d e s k D o c s /R
P S
R iv e rs id e E
S R o o f R e p la c e m e n t/
-0
R
P S
R iv e rs id e
E S
R o o f R e p la c e m e n t (R rv t
/1
/2
:5
:0
P
M
A4.12
JASON WOODHOUSE
44421 02/10/2026
PARTIAL EXISTING PHOTO
REFERENCE
R O
C H
E S
T E
R
M
IN
N E
S O
T A
R P
S R
IV
E
R S
ID
E
E S
R O
O F
R E
P
LA
C E
M E
N T
26-004
02/10/2026
TmD,LG
JW
1" = 30'-0"
PHOTO REFERENCE
23 24 25 26 27 28
MECHANICAL SYMBOLS LEGEND
DESIGNATIONSSYMBOLDESIGNATIONSSYMBOLDESIGNATIONSSYMBOL DESIGNATIONSSYMBOL
PLUMBING
ACID VENT
ACID WASTE
DEIONIZED WATER SUPPLY
FILTERED WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER (TEMP. INDICATED)
DOMESTIC RECIRC. HOT WATER
HARD COLD WATER
OVERFLOW STORM DRAIN
REVERSE OSMOSIS WATER
SANITARY VENT
SANITARY WASTE
SOIL DRAINAGE TILE
SOFTENED COLD WATER
SOFTENED HOT WATER
TEMPERED WATER
STORM DRAIN
WELL WATER
AV
AW
DIS
HARD
SDT
RO
V
W
SOFT
SHW
TW
OSD
SD
WW
NPCW NON-POTABLE COLD WATER
NPHW NON-POTABLE HOT WATER
FW
HW
RHW
GW GREASE WASTE
DOMESTIC COLD WATERCW
CLEAR WATER VENTCWV
CLEAR WATER WASTECWW
DOM. RECIRC. HOT WATER (TEMP. INDICATED)140 RHW
PUMPED ACID WASTEPAW
PUMPED STORMPSD
PUMPED WASTEPW
COMPRESSED AIR (PSI INDICATED)10#A
MECHANICAL PIPING
BOILER FEED
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
FUEL OIL SUPPLY
FUEL OIL RETURN
FUEL OIL VENT
FUEL OIL FILL
GLYCOL SUPPLY
GLYCOL RETURN
HEAT RECOVERY SUPPLY
HEAT RECOVERY RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
LIQUIFIED PETROLEUM GAS
NATURAL GAS (PSI INDICATED)
PUMPED CONDENSATE
RADIATION WATER SUPPLY
RADIATION WATER RETURN
REFRIGERANT LIQUID
BF
CWS
CWR
CD
FOS
GS
GR
HRS
HRR
HWR
HWS
LPG
2#G
FOF
PC
RADS
CS
CR
FOR
FOV
RADR
RL
REFRIGERANT SUCTION
REFRIGERANT HOT GAS BYPASS
REHEAT WATER SUPPLY
REHEAT WATER RETURN
REMOTE RADIATOR SUPPLY
REMOTE RADIATOR RETURN
SECONDARY HEATING WATER SUPPLY
SECONDARY HEATING WATER RETURN
SNOW MELT SUPPLY
SNOW MELT RETURN
STEAM SUPPLY (PSI INDICATED)
STEAM CONDENSATE (PSI INDICATED)
RRS
RS
RHG
RHR
RHS
RRR
SHWS
SHWR
SMS
SMR
10#STM
10#SC
PIPE FITTINGS
ELBOW DOWN
PIPE CAP
ELBOW UP
TEE, OUTLET UP
TEE, OUTLET DOWN
CONNECTION, TOP
ECCENTRIC REDUCER
CONCENTRIC REDUCER
MEDICAL GAS
MEDICAL VACUUM
WASTE ANESTHETIC GAS DISPOSAL
CARBON DIOXIDE
OXYGEN
NITROGEN
NITROUS OXIDE
MEDICAL AIR
WAGD
CO2
O
N
MV
N2O
MA
PIPE UNION
PIPE FLANGE
ELBOW
TEE
FIRE PROTECTION
DFP
F FIRE PROTECTION
FIRE PROTECTION (DRY SYSTEM)
POST INDICATOR VALVE (PIV)
RECESSED FIRE DEPT CABINET
SURFACE MOUNTED FIRE DEPT CABINET
FIRE PROTECTION RISER
UPRIGHT SPRINKLER HEAD W/GUARD
PENDANT SPRINKLER HEAD
UPRIGHT SPRINKLER HEAD
SIDEWALL SPRINKLER HEAD
BUTTERFLY VALVE W/TAMPER SWITCH
DETECTOR CHECK W/BYPASS METER
GRADE FIRE DEPT CONNECTION
FLUSH FIRE DEPT CONNECTION
FIRE DEPT VALVE W/CAP AND CHAIN
O.S. & Y. VALVE W/TAMPER SWITCH
DRY PIPE VALVE
PREACTION VALVE
TS
FDVC
FDVC
FDV
TS
ANNOTATION
(4)A-12"ø
GRILLE, REGISTER, &
DIFFUSER IDENTIFICATION
QUANTITY
CFM
TYPE
SIZE
X X
X X
X X
X X
DETAIL NUMBER
SHEET NUMBER
SECTION NUMBER
SHEET NUMBER
EQUIP DESIGNATION
EQUIP NUMBER
POINT OF CONNECTION, NEW TO EXISTING
POINT OF DISCONNECTION
FTR/RP 01
6'-5"
0.5
HYDRONIC FINNED TUBE
RADIATION & RADIANT
PANEL IDENTIFICATION
TYPE ACTIVE
ELEMENT
LENGTHGPM
EBR 01
6'-5"
ELECTRIC BASEBOARD
RADIATION
IDENTIFICATION
ACTIVE
ELEMENT
LENGTH
ZONE VALVE BOXZVB
AREA ALARM PANELAAP
COMBINATION AREA/MASTER ALARM
PANEL
CAP
TYPE
INTERRUPTIBLE GASIG
PROCESS AND LABORATORY
LABORATORY AIR
LABORATORY VACUUM
ARGON
PROCESS WASTE
NITROGEN
HOUSE VACUUM
LV
AR
PRW
LA
N
HV
PROCESS VACUUMPV
INSTRUMENT AIRIA
ATMOSPHERIC STEAM SUPPLY
ATMOSPHERIC STEAM CONDENSATE
ATM STM
ATM SC
CONNECTION, BOTTOM
DARK DASHED LINE WEIGHT INDICATES
EXISTING ITEM TO BE DEMOLISHED.
GENERAL
LIGHT SOLID LINE WEIGHT INDICATES
EXISTING ITEM TO REMAIN.
DARK SOLID LINE WEIGHT INDICATES
NEW ITEM OR NEW LOCATION.
ROUND
12x12
12ø 12/12
RECTANGULAR (WxH)
FLAT-OVAL (W/H)
DUCT
DIMENSIONS
LIQUID NITROGENLN
MASTER ALARM PANELMAP
XXXX #-## EXISTING EQUIP NUMBER
EXISTING EQUIP DESIGNATION
MECHANICAL ABBREVIATIONS
AD AREA DRAIN
A.F.F. ABOVE FINISHED FLOOR
AFMS AIR FLOW MEASURING STATION
AHU AIR HANDLING UNIT
ANB ACID NEUTRALIZING BASIN
AP ACCESS PANEL
ARCH ARCHITECT
AS AIR SEPARATOR
BD BUTTERFLY DAMPER
B/G BELOW GRADE
BTU BRITISH THERMAL UNIT
BWV BACKWATER VALVE
CCF HUNDRED CUBIC FEET
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CL CENTER LINE
CLG CEILING
CO CLEAN OUT
CONTR CONTRACTOR
CONV CONVECTOR
CUH CABINET UNIT HEATER
CW COLD WATER
DB DECIBEL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIFF DIFFUSER
DISCH DISCHARGE
DMPR DAMPER
DN DOWN
DR DRAIN
DSN DOWNSPOUT NOZZLE
DWG DRAWING
EAT ENTERING AIR TEMPERATURE
EDR EQUIVALENT DIRECT RADIATION
EP ELECTRIC-PNEUMATIC
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXP EXPANSION
F FAHRENHEIT
FC FAN COIL
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FHC FIRE HOSE CABINET
FHR FIRE HOSE RACK
FLR FLOOR
FLEX FLEXIBLE
FM FIRE MAIN
FPM FEET PER MINUTE
FPS FEET PER SECOND
FT FEET OR FOOT
F&T FLOAT AND THERMOSTATIC
FTG FOOTING
FTR FINNED TUBE RADIATION
FV FACE VELOCITY
GA GAUGE
GAL GALLON
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HB HOSE BIBB
HD HEAD
HOA HANDS-OFF-AUTOMATIC
HTG HEATING
HTR HEATER
HVAC HEATING, VENTILATION,
AND AIR CONDITIONING
HYD HYDRANT
HW HOT WATER
GCO GRADE CLEANOUT
INSUL INSULATION
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
LAV LAVATORY
LWT LEAVING WATER TEMPERATURE
MBH BTU PER HOUR (THOUSANDS)
MCF THOUSAND CUBIC FEET
MH MANHOLE
NC
NOISE CRITERIA OR
NORMALLY CLOSED
NEG NEGATIVE
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP OR DIFFERENCE
PE PNEUMATIC-ELECTRIC
PLBG PLUMBING
PRV
PRESSURE REDUCING VALVE
OR POWER ROOF VENTILATOR
PSIA POUNDS/SQ INCH ABSOLUTE
PSIG POUNDS/SQ INCH GAUGE
PVC POLY VINYL CHLORIDE
RA RETURN AIR
RCP REINFORCED CONCRETE PIPE
RD ROOF DRAIN
RECIRC RECIRCULATING
REG REGISTER
RET RETURN
RH RELATIVE HUMIDITY
RHT REHEAT
RHC REHEAT COIL
RHW RECIRCULATED HOT WATER
RM ROOM
RPM REVOLUTIONS PER MINUTE
RPZ
REDUCED ZONE BACKFLOW
PREVENTER
SA SUPPLY AIR
SAN SANITARY
SCFM CFM, STANDARD CONDITIONS
SD SMOKE DAMPER
SP STATIC PRESSURE
SPECS SPECIFICATIONS
SUP SUPPLY
SQ SQUARE
STM STEAM
TD TEMPERATURE DIFFERENCE
TEMP TEMPERATURE
TONS TONS OF REFRIGERATION
T-STAT THERMOSTAT
TYP TYPICAL
UB UP-BLAST
UG UNDERGROUND
UH UNIT HEATER
UR URINAL
V SANITARY VENT
VD VOLUME DAMPER
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W SANITARY WASTE
W/ WITH
WC WATER CLOSET
WCO WALL CLEANOUT
WH WALL HYDRANT
W/O WITHOUT
WTR WATER
GR GRILLE
VAV VARIABLE AIR VOLUME
VTR VENT THROUGH ROOF
INV INVERT
RLF RELIEF
ISO ISOLATION EXHAUST
GEXH GREASE EXHAUST
RH ROOF HYDRANT
YCO YARD CLEANOUT
ZDL ZERO DEADLEG VALVE
AUTOMATIC AIR VENT
AUTOMATIC CONTROL VALVE, 2-WAY
AUTOMATIC CONTROL VALVE, 3-WAY
STRAINER W/BLOWDOWN
CAP AND VALVE
PIPE SPECIALTIES
FLEXIBLE CONNECTION
PIPE ANCHOR
ALIGNMENT GUIDE
STRAINER
PRESSURE REDUCING VALVE
(SETTING AS NOTED, PSI)
EXPANSION JOINT
MANUAL AIR VENT
PRESSURE RELIEF/SAFETY
VALVES(SETTING AS NOTED, PSI)
DRAIN VALVE
REDUCED PRESSURE ZONE BACK
FLOW PREVENTER
DIAPHRAGM
REFRIGERANT SIGHT GLASS
GAS PRESSURE REGULATOR VALVE
BACKWATER VALVE
REFRIGERANT DRYER
FLOW DIRECTION
FLOW DIRECTION W/PITCH
DUPLEX STRAINER
PUMP
THERMOMETER
PRESSURE/TEMPERATURE TEST PORT
STEAM TRAP (TYPE INDICATED)
FLOW SWITCH
PRESSURE GAUGE W/PIGTAIL &
PETCOCK
PRESSURE SWITCH
FLOOR DRAIN
DRAIN ABOVE
FLOOR SINK
WALL HYDRANT
HOSE BIBB
WALL CLEANOUT
ROOF DRAIN
MANHOLE
HB
A
M
FS
PS
GAS COCK VALVE
WH
DEIONIZED WATER RETURNDIR
CLEAN DRY AIRCDA
REVERSE OSMOSISRO
CONTROLS
AQUA STAT
TAMPERPROOF THERMOSTAT
HUMIDISTAT OR R.H. SENSOR
REFRIGERANT SENSOR
SMOKE DETECTOR
SPACE TEMPERATURE SENSOR
STATIC PRESSURE SENSOR
ROOM PRESSURE MONITOR
THERMOSTAT
THERMOSTAT W/GUARD
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
DIFFERENTIAL PRESSURE SENSOR
TEMPERATURE SENSOR
A
CO2
CO
H
R
P
SD
TS
SP
PS
T
T
T
DP
TS
P
DUCTWORK
SUPPLY AIR OR OUTDOOR AIR
RETURN AIR
EXHAUST AIR
STANDARD BRANCH, NO SPLITTER -
SUPPLY FLOW TO RIGHT -
RETURN/EXHAUST FLOW TO LEFT
BELLMOUTH WITH BALANCING
DAMPER
FLEXIBLE DUCT
TURNING VANES
FLEXIBLE CONNECTION
MANUAL VOLUME DAMPER
MOTORIZED DAMPER
TYPE:
FD = FIRE DAMPER
SD = SMOKE DAMPER
FSD = COMBINATION FIRE/SMOKE
DAMPER
CRD = CEILING RADIATION DAMPER
ORIENTATION:
SUPPLY GRILLE OR REGISTER
RETURN DUCT UP, NEGATIVE
PRESSURE
SUPPLY DIFFUSER/REGISTER
BLANKOFF INDICATED
RETURN OR EXHAUST GRILLE OR
REGISTER
SUPPLY DUCT UP, POSITIVE
PRESSURE
EXHAUST DUCT UP, NEGATIVE
PRESSURE
RETURN GRILLE/REGISTER
EXHAUST GRILLE/REGISTER
LINEAR DIFFUSER
CONCENTRIC DUCT TRANSITION
ECCENTRIC DUCT TRANSITION
RECTANGULAR-TO-ROUND DUCT
TRANSITION
VAV BOX
REHEAT COIL
VAV BOX W/ REHEAT COIL
DUCT OFFSETS
DUCT CUTLINE
M
XXX
RETURN DUCT DN, NEGATIVE
PRESSURE
SUPPLY DUCT DN, POSITIVE
PRESSURE
EXHAUST DUCT DN, NEGATIVE
PRESSURE
DROPRISE
VERTICAL
XXX
XXX
XXX
ACTUATOR (AS
APPLICABLE)
HORIZONTAL
BLADE/CURTAIN
FIRE, SMOKE, AND
COMBINATION
FIRE/SMOKE DAMPERS
TYPE
ORIENTATION
AIRFLOW MEASURING STATIONAFMS
VAV BOX W/ DUCT SILENCER
VENTURI TYPE AIR VALVE
VAV BOX W/ DUCT SILENCER
& REHEAT COIL
VAV BOX W/ ELECTRIC REHEAT
ENERGY METER
FLOW METER
GPM
EM
WATER HAMMER ARRESTOR
CATCH BASIN
BALANCE VALVE
GENERAL DUTY VALVES
CHECK VALVE
SHUTOFF VALVE
PLUG VALVE
BALL VALVE
BUTTERFLY VALVE
GLOBE ANGLE VALVE
O. S. & Y. VALVE
SOLENOID VALVE
FLOW LIMITING VALVE
GLOBE VALVE
S
OR
OR
OR
OR
OR
GATE VALVE
NITROGEN OXIDE SENSORNOX
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
© 2025 CRW architecture + design group
No. ISSUED FOR DATE
CLIENT
CD ISSUE 02/10/26
I HEREBY CERTIFY THAT THIS
PLAN, SPECIFICATION, OR REPORT
WAS PREPARED BY ME OR UNDER
MY DIRECT SUPERVISION AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER
THE LAWS OF THE STATE OF
MINNESOTA.
Steven C Harmon
23501
A u to d e s k D o c s /R
P S
R iv e rs id e
E S
R o o f R e p la c e m e n t/ M
E P
R P
S R iv e rs id e R o o f R e p la c e m e n t.
rv t
/1
/2
:2
:2
P
M
M0.0
02/10/2026
MECHANICAL SYMBOLS AND
ABBREVIATIONS
R O
C H
E S
T
M
N E
S O
T A
R P
S R
IV
E
R S
ID
E
E S
R O
O F
R E
P L
A C
E M
E N
T
1226035-000-00
02/10/2026
MJS
SCH
MECHANICAL SHEET LIST
SHEET
NUMBER SHEET NAME
M0.0 MECHANICAL SYMBOLS AND ABBREVIATIONS
MD1.00 ROOF MECHANICAL DEMOLITION PLAN
M1.00 ROOF MECHANICAL PLAN
SHEET TOTAL: 3
KEY NOTES:
EF-3
EF-1
EF-2
EF-10EF-11
EF-5
EF-7
EF-9
EF-6
2"VTR
2"VTR
2"VTR
RELIEF
HOOD
INTAKE
HOOD
INTAKE
HOOD
RELIEF
HOOD
4"RD
4"ORD
4"RD4"ORD
2"VTR
RELIEF
HOOD
INTAKE
HOOD
INTAKE
HOOD
RELIEF
HOOD
2"VTR4"VTR
4"ORD4"RD
2"VTR
6"RD
5"RD
RELIEF
HOOD
RELIEF
HOOD
RELIEF
HOOD
2"VTR
EF-12
EF-4
4"RD
6"RD
6"ORD
5"ORD
5"RD
4"RD
2"VTR
INTAKE
HOOD
INTAKE
HOOD
RELIEF
HOOD
4" FLUE
EF-13
2"VTR
INTAKE
HOOD
2"VTR
2"VTR 2"VTR 2"VTR
4"RD
6"RD
2"VTR
CONDENSING
UNIT
REFRIGERANT
PIPING
ROOF HATCH
ROOF HATCH
ROOF HATCH
1 1
2 2 3
3 3
7 7 7 7
7 7
OVERFLOW
SCUPPER
OVERFLOW
SCUPPER
OVERFLOW
SCUPPER
OVERFLOW
SCUPPER
OVERFLOW
SCUPPER
OVERFLOW
SCUPPER
1 REMOVE EXHAUST FAN. CURB TO REMAIN. SAVE EXHAUST FAN FOR
REINSTALLATION.
REMOVE INTAKE HOOD. CURB TO REMAIN. SAVE INTAKE HOOD FOR
REINSTALLATION.
REMOVE RELIEF HOOD. CURB TO REMAIN. SAVE RELIEF HOOD FOR
REINSTALLATION.
RECOVER REFRIGERANT. DISCONNECT REFRIGERATION PIPING FROM
CONDENSING UNIT. REMOVE CONDENSING UNIT. SAVE CONDENSING
UNIT FOR REINSTALLATION.
DISCONNECT REFRIGERATION PIPING FOR INSTALLATION OF NEW
ROOFING. SAVE PIPING AND ROOF PIPE SUPPORTS FOR
REINSTALLATION.
REMOVE FLUES TO ALLOW FOR INSTALLATION OF NEW ROOFING.
SAVE FLUES FOR REINSTALLATION.
REMOVE ROOF DRAIN STRAINER FOR INSTALLATION OF NEW ROOF
MEMBRANE. SAVE ROOF DRAIN STRAINER FOR REINSTALLATION.
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
© 2025 CRW architecture + design group
No. ISSUED FOR DATE
CLIENT
CD ISSUE 02/10/26
I HEREBY CERTIFY THAT THIS
PLAN, SPECIFICATION, OR REPORT
WAS PREPARED BY ME OR UNDER
MY DIRECT SUPERVISION AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER
THE LAWS OF THE STATE OF
MINNESOTA.
Steven C Harmon
23501
A u to d e s k D o c s /R
P S
R iv e rs id e
E S
R o o f R e p la c e m e n t/ M
E P
R P
S R iv e rs id e R o o f R e p la c e m e n t.
rv t
/1
/2
:2
:2
P
M
MD1.00
02/10/2026
ROOF MECHANICAL
DEMOLITION PLAN
R O
C H
E S
T
N E
S O
T A
R P
S R
IV
E
R S
ID
E
E S
R O
O F
R E
P L
A C
E M
E N
T
1226035-000-00
02/10/2026
MJS
SCH
3/32" = 1'-0"
ROOF MECHANICAL DEMOLITION PLAN
2"VTR
2"VTR
2"VTR
4"RD
4"ORD
4"RD4"ORD
2"VTR
2"VTR4"VTR
4"ORD4"RD
2"VTR
6"RD
5"RD
2"VTR
4"RD
6"RD
6"ORD
5"ORD
5"RD
4"RD
2"VTR
4" FLUE
2"VTR
2"VTR
2"VTR 2"VTR 2"VTR
4"RD
6"RD
2"VTR
REFRIGERANT
PIPING
EF-7
RELIEF
HOOD
INTAKE
HOOD
INTAKE
HOOD
RELIEF
HOOD
EF-6
EF-5
EF-3
EF-1
EF-9
RELIEF
HOOD
INTAKE
HOOD
INTAKE
HOOD
RELIEF
HOOD
ROOF HATCH
ROOF HATCH
ROOF HATCH
EF-13
EF-2
INTAKE
HOOD
RELIEF
HOODEF-12
EF-4
RELIEF
HOOD
INTAKE
HOOD
INTAKE
HOOD
EF-11 EF-10
RELIEF
HOOD
RELIEF
HOOD
1 1
2 2 3
3 3
CONDENSING
UNIT
7 7 7 7
7 7
OVERFLOW
SCUPPER
OVERFLOW
SCUPPER
OVERFLOW
SCUPPER
OVERFLOW
SCUPPER
OVERFLOW
SCUPPER
OVERFLOW
SCUPPER
1 REINSTALL EXISTING EXHAUST FAN ON EXISTING CURB.
REINSTALL EXISTING INTAKE HOOD ON EXISTING CURB.
REINSTALL EXISTING RELIEF HOOD ON EXISTING CURB.
REINSTALL EXISTING CONDENSING UNIT.
REINSTALL EXISTING REFRIGERATION PIPING AND ROOF PIPE
SUPPORTS. PROVIDE NEW ARMAFLEX INSULATION ON ALL PIPING.
REINSTALL EXISTING REFRIGERANT.
REINSTALL EXISTING FLUES.
REINSTALL EXISTING ROOF DRAIN STRAINER AFTER NEW ROOF
MEMBRANE IS INSTALLED.
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
© 2025 CRW architecture + design group
No. ISSUED FOR DATE
CLIENT
CD ISSUE 02/10/26
I HEREBY CERTIFY THAT THIS
PLAN, SPECIFICATION, OR REPORT
WAS PREPARED BY ME OR UNDER
MY DIRECT SUPERVISION AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER
THE LAWS OF THE STATE OF
MINNESOTA.
Steven C Harmon
23501
A u to d e s k D o c s /R
P S
R iv e rs id e
E S
R o o f R e p la c e m e n t/ M
E P
R P
S R iv e rs id e R o o f R e p la c e m e n t.
rv t
/1
/2
:2
:2
P
M
M1.00
02/10/2026
ROOF MECHANICAL PLAN
R O
C H
E S
T
N E
S O
T A
R P
S R
IV
E
R S
ID
E
E S
R O
O F
R E
P L
A C
E M
E N
T
1226035-000-00
02/10/2026
MJS
SCH
3/32" = 1'-0"
ROOF MECHANICAL PLAN
DESIGNATIONSSYMBOL
MTG
HT
SYMBOL SCHEDULE NOTES
THESE SYMBOLS COMPRISE A STANDARD LIST, NOT ALL SYMBOLS MAY
APPEAR ON THESE DRAWINGS.
MOUNTING HEIGHTS INDICATED ARE STANDARD. DIMENSIONAL NUMBERS
INDICATED AT DEVICES SHALL OVERRIDE THESE STANDARDS. MOUNTED
HEIGHTS ARE TO THE CENTER OF THE DEVICE, UNLESS NOTED OTHERWISE.
MOUNTING HEIGHTS INDICATED ARE FOR STUD WALL CONSTRUCTION.
WHEN BLOCK OR BRICK CONSTRUCTION IS USED, ADJUST MOUNTING
HEIGHTS TO ALIGN DEVICE PLATES WITH RUNNING JOINT.
REFER TO SPECIFICATIONS FOR FURTHER INFORMATION.
GENERAL
DARK DASHED LINE WEIGHT INDICATES
EXISTING ITEM TO BE REMOVED.
LIGHT SOLID LINE WEIGHT INDICATES EXISTING
ITEM TO REMAIN.
DARK SOLID LINE WEIGHT INDICATES NEW ITEM
OR NEW LOCATION.
REMOVE EXISTING ITEM
REMOVE EXISTING ITEM AND RELOCATE AS INDICATED
NL
EXISTING ITEM TO REMAIN
NEW LOCATION FOR RELOCATED ITEM
NOTES & TAGS
EQUIPMENT IDENTIFICATION TAG - SEE EQUIPMENT SCHEDULES
FEEDER SIZE TAG - SEE POWER RISER SCHEDULE
ELEC EQUIP CONNECTION TAG - SEE EQUIP SCHEDULE
KEYNOTE
MISCELLANEOUS NOTE
#/C
XX
LIGHTING CONTROL SEQUENCE - SEE SCHEDULE
LC
XXX-X
RACEWAYS
CONDUIT CONCEALED IN CEILING OR WALLS
CONDUIT CONCEALED IN THE FLOOR OR BELOW
CONDUIT EXPOSED ON THE CEILING OR WALLS
CONDUIT BURIED UNDERGROUND (# = DEPTH)
CONDUIT WITH BEND DOWN
CONDUIT WITH BEND UP
CONDUIT WITH BUSHED END
CONDUIT WITH BREAK OR CONTINUATION
UG
CIRCUIT HOME RUN
- L1 INDICATES PANEL
- NUMBER
L1 1,3,5
JUNCTION BOX - WALL/CEILING MOUNT
WIREWAY, DUCT BANK, OR FLOOR DUCT AS NOTED
CABLE TRAY, TYPE/SIZE AS INDICATED
J J
X
R
RL
ELECTRICAL ABBREVIATIONS
AMPERES
ABOVE
ADDENDUM
AVAILABLE FAULT CURRENT
ABOVE FINISHED FLOOR
AIR HANDLING UNIT
ALUMINUM
ANTENNA
A, AMP
ABV
ADD
AFC
AFF
AHU
AL
ANT
ABOVE COUNTERAC
ARC FAULT CIRCUIT INTERRUPTERAFCI
BELOW FINISHED CEILING
BOLTED PRESSURE SWITCH
BFC
BPS
AUTOMATIC TRANSFER SWITCHATS
BUILDING AUTOMATION SYSTEMBAS
COPPER
DISTRIBUTED ANTENNA SYSTEM
ELECTRICAL CONTRACTOR
ELECTRIC OR ELECTRICAL
EMERGENCY
ELECTRICAL METALLIC TUBING
ENCLOSURE
ELECTRIC PNEUMATIC
EMERGENCY POWER OFF
CU
DAS
EC
ELEC
EM
EMT
ENCL
EP
EPO
CONDUIT OR CONTROLLED RECEPT
CIRCUIT BREAKER
CLOSED CIRCUIT TV
CIRCUIT
CABINET
C
CAB
CB
CCTV
CKT
ELECTRIC WATER COOLER
FUSE OR FUSED
FIRE ALARM
FLOOR BOX
FIRE-SMOKE DAMPER
GROUND
GROUND FAULT CIRCUIT INTERRUPTER
ISOLATED GROUND
JUNCTION BOX
KILOVOLT
KILOVOLT-AMP
KILOWATT
KILOWATT-HOUR
FILM VIEWER
EWC
F
FA
FB
FSD
FV
G, GND
GFI, GFCI
IG
JBOX
KV
KVA
KW
KWH
MAIN CIRCUIT BREAKER
MOMENTARY CONTACT OR
NATIONAL ELECTRICAL CODE
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
PULL BOX OR PUSHBUTTON
NORMALLY OPEN
NORMALLY CLOSED
MAIN SWITCHBOARD
MC
MCB
MSB
NC
NEC
NIC
NO
NTS
OC
PB
MAIN LUG ONLYMLO
MOTOR RATED SWITCHMR
EMPTYMT
PNEUMATIC ELECTRIC
POWER FACTOR
PHASE
PRIMARY
PANEL
REFRIGERATOR
SECONDARY
SWITCH
SWITCHBOARD
SPEAKER
ROOF TOP UNIT
RECEPTACLE
TELEPHONE
PE
PF
PH
PNL
PRI
RECEPT
REFG
RTU
SEC
SW
SWBD
SPKR
TEL
TAMPER RESISTANTTR
THERMOSTAT
TYPICAL
UNDER COUNTER
UNDER GROUND
UNLESS NOTED OTHERWISE
VOLT OR VOLTAGE
VOLT-AMP
VOLTS ALTERNATING CURRENT
UNIT HEATER
VOLTS DIRECT CURRENT
WATT, WIRE OR WALL PHONE
WEATHERPROOF
EXISTING
TSTAT
TYP
UC
UG
UH
UNO
V
VA
VAC
VDC
W
WP
X
UNIVERSAL SERIAL BUSUSB
18"
18"
18"
18"
18"
18"
18"
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
18"
18"
18"
18"
BRANCH CIRCUIT PANEL
EQUIPMENT CABINET
TS=TRANSFER SWITCH
MOTOR OR MOTOR CONNECTION
MOTOR CONTROLLER, STARTER OR VFD
COMBINATION STARTER & DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
MOTOR RATED TOGGLE
MANUAL MOTOR STARTER SWITCH WITH THERMAL
OVERLOAD
DUPLEX RECEPTACLE - WALL/CEILING MOUNT
EMERGENCY DUPLEX RECEPTACLE - WALL/CEILING
MOUNT
QUADPLEX RECEPTACLE - WALL/CEILING MOUNT
GFI RECEPTACLE, DUPLEX/QUADPLEX - WALL MOUNT
SPECIAL PURPOSE RECEPTACLE - WALL/CEILING
MOUNT
POKE-THRU - DEVICES AS INDICATED
POWER POLE - DEVICES AS INDICATED
EMERGENCY SPECIAL PURPOSE RECEPTACLE -
WALL/CEILING MOUNT
MR
MMS
G G
P
GFI DEAD FRONT DEVICE, NORMAL/EMERGENCY -
WALL MOUNT
C
SPLIT DUPLEX RECEPTACLE - WALL/CEILING MOUNT
SIMPLEX RECEPTACLE - WALL/CEILING MOUNT
EMERGENCY SIMPLEX RECEPTACLE - WALL/CEILING
MOUNT
DUPLEX RECEPTACLE - CONTROLLED - WALL/CEILING
MOUNT
EMERGENCY QUADPLEX RECEPTACLE - WALL/CEILING
MOUNT
GROUND REFERENCE BUS - AS NOTED - WALL/CEILING
MOUNT
VERIFY
EMERGENCY SPLIT DUPLEX RECEPTACLE -
WALL/CEILING MOUNT
LIGHT FIXTURE ID - REFER TO LIGHT FIXTURE SCHEDULE
(SCHEDULE OVERRIDES SYMBOL ABBREVIATION)
A - INDICATES LIGHT FIXTURE TYPE
# - INDICATES CIRCUIT NUMBER
b - INDICATES SWITCHING
LIGHT FIXTURE CIRCUIT TYPE
- NO HATCH INDICATES NORMAL CIRCUIT
- ANGLED HATCH INDICATES CRITICAL CIRCUIT
- SOLID HATCH INDICATES LIFE SAFETY CIRCUIT
TROFFER TYPE LIGHT FIXTURE, SIZE AS INDICATED -
CEILING MOUNT
CHANNEL OR INDUSTRIAL, LENGTH AS INDICATED
ROUND DOWNLIGHT, RECESSED OR SURFACE MOUNT
CEILING WALL WASH FIXTURE OR TRACK HEAD
WALL MOUNT FIXTURE OR SCONCE
LINEAR RECESSED, LENGTH AS INDICATED
UNDER CABINET FIXTURE, LENGTH AS INDICATED
TRACK FIXTURE, NUMBER OF HEADS AS INDICATED
EMERGENCY BATTERY LIGHT - WALL/CEILING MOUNT
EXIT LIGHT, FILLED QUADRANT INDICATES FACES -
WALL/CEILING MOUNT
VERIFY
SITE LIGHTING ROUND OR SQUARE BOLLARD
SITE LIGHTING POLE FIXTURE, ROUND/RECTANGLE
HEAD - NUMBER OF HEADS INDICATED
b
A
LINEAR SUSPENDED , LENGTH AS INDICATED VERIFY
VERIFY
SQUARE DOWNLIGHT, RECESSED OR SURFACE MOUNT
CHANNEL OR INDUSTRIAL WALL MOUNT, LENGTH AS
INDICATED
ROUND OR SQUARE PENDANT
TAPE OR ROPE LIGHT
VANITY FIXTURE
WALL PACK
FLAG OR FLOOD LIGHT
VERIFY
VERIFY
SINGLE POLE TOGGLE SWITCH
DOUBLE POLE TOGGLE SWITCH
THREE WAY TOGGLE SWITCH
FOUR WAY TOGGLE SWITCH
TOGGLE SWITCH - "a" INDICATES SWITCHING a
48"
PILOT LIGHT TOGGLE SWITCH
ILLUMINATED TOGGLE - TOGGLE SWITCH
KEYED SWITCH
MOMENTARY CONTACT TOGGLE SWITCH
TIMER SWITCH
DIMMER SWITCH
OCCUPANCY SENSOR - CLG MOUNT
OCCUPANCY SENSOR WALL SWITCH
PHOTO ELECTRIC CELL
TIME CLOCK
CONTACTOR
RELAY
IL
K
MC
TS
OS
PUSH BUTTON STATION - BUTTONS AS INDICATED
48"
48"
48"
48"
48"
48"
48"
48"
48"
48"
48"
48"
60"
60"
PC
TC
C
R
D
MULTI SWITCH, MULTI GANG BOX 48"
VERIFY
VERIFY
PUSH BUTTON SWITCHB 48"
SIGNAL AND COMMUNICATIONS
DATA OUTLET - WALL/CEILING MOUNT
(# = WIRE COUNTS)
VOICE/DATA OUTLET - WALL/CEILING MOUNT
FLOOR OUTLET (# = WIRE COUNTS)
WALL PHONE - HIGH WALL MOUNT
WIRELESS ACCESS POINT - WALL/CEILING MOUNT
18"
SPEAKER - WALL/CEILING MOUNT
HORN SPEAKER - WALL MOUNT
VOLUME SWITCH - WALL MOUNT
AUDIO JACK (M=MICROPHONE, A=AUXILIARY)
BUZZER - WALL/CEILING MOUNT
BELL - WALL/CEILING MOUNT
CHIME - WALL/CEILING MOUNT
CLOCK - WALL/CEILING MOUNT (# = DIAMETER)
PROJECTOR/VIDEO CAMERA/DOCUMENT
CAMERA - WALL/CEILING MOUNT
TV SYSTEM OUTLET - WALL/CEILING MOUNT
ANNUNCIATOR PANEL - WALL MOUNT TYPICAL
60"
96"
48"
18"
96"
VERIFY
18"
WALL INTERCOM STATION (M=MASTER, R=REMOTE) 48"
96"
96"
96"
18"
96"
W
PRJ
AUDIO VIDEO SYSTEM OUTLET - WALL/CEILING MOUNT 18"
A/V SYSTEMS CONTROLLER - WALL MOUNT 18"
S
S S
C C
ICM
AM
V
VID
SECURITY
SECURITY - WALL MOUNT - TYPICAL
ES
EL
DC
GB
48"
SECURITY PANEL - WALL MOUNT - TYPICAL VERIFY
S
S
SECURITY CAMERA - WALL/CEILING MOUNT
VERIFY
CR
EP
SECURITY - CEILING MOUNT - TYPICAL
SWITCHES AND CONTROLS
LIGHTING
POWER
A.
B.
C.
D.
TRANSFORMERXFMR
ABOVE GRADEAG
AUDIBLE ALARMAA
CEILING CLG
DOWNDN
DEDICATEDDED
COMMUNICATIONSCOMM
CONTROL CTRL
FIRE ALARM ANNUNCIATOR PANELFAAP
FIRE ALARM CONTROL PANELFACP
FIBER OPTICFO
SINGLE MODE FIBER OPTICSMFO
MULTI MODE FIBER OPTICMMFO
GROUND FAULT EQUIPMENT PROTECTIONGFEP
GENERAL CONTRACTORGC
CURRENT TRANSFORMERCT
ABOVE COUNTER HEIGHTACH
AUDIO VISUALAV
AMERICAN WIRE GUAGEAWG
MOTOR CONTROL CENTERMCC
METER M
MAN HOLEMH
NEUTRALN
HAND HOLEHH
HAND OFF AUTOHOA
POTENTIAL TRANSFORMERPT
MECHANICAL CONTRACTOR
RACEWAYR
UNDER FLOORUF
WIRELESS ACCESS POINTWAP
SHIELDED TWISTED PAIRSTP
SUBSTATIONSUB
UNSHIELDED TWISTED PAIRUTP
ELECTRICAL GROUND BAREGB
SERVICE GROUND BARSGB
TELECOMMUNICATIONSTELCOM
TELECOMMUNICATIONS MAIN GROUND BARTMGB
TELECOMMUNICATIONS GROUND BARTGB
DESIGNATIONSSYMBOL
MTG
HT
DESIGNATIONSSYMBOL
MTG
HT
ELECTRICAL SYMBOLS LEGEND
VERIFY
VERIFY
C
18"
A/V MONITOR - WALL MOUNT 18"MT
CX
AV
TV
AV
TV
X" H
X" W
X' - X" AFF
CABLE TRAY TAG
X" W - WIDTH OF CABLE TRAY
X" H - HEIGHT OF CABLE TRAY
X' - X" AFF - MOUNTING HEIGHT OF CABLE TRAY (FROM FINISH
FLOOR TO BOTTOM OF TRAY)
GFI RECEPTACLE, DUPLEX/QUADPLEX - CEILING MOUNT
18"
DESIGNATIONSSYMBOL
MTG
HT
MOTORMTR
VERIFYDISCONNECT SWITCH
GFI RECEPTACLE, DUPLEX/QUADPLEX - CONTROLLED -
CEILING MOUNT
CC
SEC - SECURITY
IDS - INTRUSION DETECTION SYSTEM
CA - CARD ACCESS
CR/KP
DS
ANN
TWO-POST RACK
FLOOR
FOUR-POST RACK
FLOOR
DATA CABINET
FLOOR
FIRE ALARM
FIRE ALARM - WALL MOUNTED - TYPICAL
DUCT MOUNTED PHOTOELECTRIC DETECTOR
FIREMAN'S STATION - WALL MOUNT
STROBE - WALL/CEILING MOUNT (# = CANDELA)
BELL - WALL/CEILING MOUNT
BELL/STROBE - WALL/CEILING MOUNT (# = CANDELA)
CHIME - WALL/CEILING MOUNT
CHIME/STROBE - WALL/CEILING MOUNT (# = CANDELA)
HORN - WALL/CEILING MOUNT
HORN/STROBE - WALL/CEILING MOUNT (# = CANDELA)
SPEAKER - WALL/CEILING MOUNT
SPEAKER/STROBE - WALL/CEILING MOUNT
(# = CANDELA)
NOTED
48"
82"
82"
82"
82"
82"
82"
82"
82"
82"
FIRE ALARM PANEL - WALL MOUNT
F
F
F F
F F
F F
F F
F F
F F
F F S S
SS
FS
FIRE ALARM/ALERT NOTIFICATION:
SPEAKER/STROBE - WALL/CEILING MOUNT
(# = CANDELA)
82"F A
S SA F
F F
F F C C
CC
VERIFY
FACP
FAAP
VESDA
NAC
AMP
MANUAL PULL STATION (48")
REMOTE STATION (72")
DOOR HOLD
REMOTE INDICATOR LAMP (72")
FIRE ALARM - CEILING MOUNTED - TYPICALF
HEAT DETECTOR
(FIXED TEMP [°F] )
HEAT DETECTOR
(RATE OF RISE [°F] PER MINUTE)
SMOKE DETECTOR
(PHOTO ELEC)
BEAM DETECTOR
(TRANSMITTER)
BEAM DETECTOR
(RECEIVER)
COMBINATION SMOKE
DETECTOR AND ALARM
SMOKE DUCT/DAMPER
CONNECTION
FLOW SWITCH
TAMPER SWITCH
MONITOR MODULE
CONTROL MODULE
AIR SAMPLING
CEILING PROTECTION
FLOOR PROTECTIONCLG
CURRENT LIMITER VERIFYCL _A
ATS=AUTOMATIC TRANSFER SWITCH
T=TRANSFORMER
UPS=UNITERUPTABLE POWER SUPPLY
CEILING FAN
FLOOR BOX - DEVICES AS INDICATED
COMBINATION DUCT MOUNTED PHOTOELECTRIC
DETECTOR/SMOKE DAMPER CONNECTION
FSD
CH
DB
DA
DZ
DO
IC
IR
REQUEST TO EXIT
ELECTRIC STRIKE
ELECTRIC LOCK
MAGNETIC LOCK
POWER TRANSFER HINGE
DOOR CONTACT
OVERHEAD DOOR CONTACT
MONITOR STRIKE
MOTION DETECTOR
GLASS BREAKER DETECTOR
CARD READER
KEYPAD
EXIT PUSHBUTTON
MASTER INTERCOM &
DIRECTORY UNIT
KEY SWITCH
PUSH BUTTON
CARD READER W/ KEY PAD
DURESS SYSTEM
DOOR CHIME
DOOR BELL
DOOR ALARM
DOOR BUZZER
ELECTRIC DOOR OPENER
INTERCOM UNIT
INFRA-RED DETECTOR
MASTER STATION
KP
KS
ML
MI
M
MS
MD
PB
MICROWAVEMW
ODC
PANIC BARP
RX
TH
SECURITY ANTENNAS
ULTRASONIC DETECTORUD
MP
RS
R
B-T
B-R
FS
TS
AS
CP
FP
DH
RI
P
I
MM
CM
SA
SD
SMOKE DETECTOR
(IONIZATION)
FIRE ALARM CONTROL PANEL
AMPLIFIER
ASPIRATING SMOKE
DETECTION
FIRE ALARM ANNUNCIATOR PANEL
NOTIFICATION APPLIANCE CIRCUIT
W W
FIRE ALARM/ALERT NOTIFICATION:
HORN/STROBE - WALL/CEILING MOUNT
(# = CANDELA)
82"F A
A F
FIRE ALARM/MASS NOTIFICATION
F=FIRE ALARM / A=ALERT
R [RED] = HAZARD, W [WHITE] = FIRE ALARM,
B…