3__Attachment_2_-_Fire_Alarm_Test.pdf

PDF 726 KB Posted

Attached to
CA-Humboldt Bay NWR - Bunkhouse Safety Repairs
Solicitation number
140FC326Q0019
Issued by

About this file

This is a Fire Alarm Systems Inspection Certificate for the Humboldt Bay Wildlife Refuge - Bunk House located at 1020 Ranch Road, Loleta, CA 95551. The inspection was conducted on January 6, 2026, by Advanced Security Systems, Inc., with inspector Brian Kenny (California Department of Industrial Relations certification number KennB8439). The facility is served by a First Alert fa 1600c control panel installed on December 11, 2014, with cellular monitoring provided by Advanced Security Systems through an SPS TG7 FS communicator. The system was tested to NFPA 72 Standards.

The inspection results indicate that 21 total items were serviced with a 95.24% pass rate. Of the items inspected, 20 passed across all categories (7 control devices, 4 indicating devices, and 9 initiating devices), while 1 failed—an Alarm Pressure Switch located outside the NW Shed requiring time and materials repair authorization. All batteries tested passed, including sealed lead acid units rated at 7Ah/12V with manufacturing dates from June 2025, August 2023, and December 2024. The power supply charging circuit also passed testing with a 13.5V charging voltage. Six smoke detectors, three strobes, two pull stations, one heat detector, and one horn all tested successfully. The facility's communicator and annunciator (LCD display installed December 11, 2015) also passed inspection. The monitoring company account information and specific cost details for the required pressure switch repair were not populated in the report.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Humboldt Bay Wildlife Refuge - Bunk House 1020 Ranch Road Loleta, CA 95551

(707) 733-5406

Building Contact: CASHELL VILLA Title: PROJECT LEADER

Company: Advanced Security Systems, Inc.

Contact: Brian Kenny Title: Life Safety Tech

Fire Alarm Systems

INSPECTION

CERTIFICATE

Jan 6, 2026Inspection Date:

Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Page of 2 13 Executive Summary

Advanced Security Systems, Inc. Download Date: 02/27/2026

EXECUTIVE SUMMARY

Generated by: BuildingReports.com

Building Information Humboldt Bay Wildlife Refuge - Bunk House 1020 Ranch Road Loleta, CA 95551 United States of America

Contact: CASHELL VILLA

Phone: (707)733-5406

Fax:

Mobile:

Email: cashell_villa@fws.gov

Inspection Performed By Advanced Security Systems, Inc.

1336 4th Street Eureka, California 95501 United States of America

Inspector: Brian Kenny

Phone: (707) 497-9192

Fax:

Mobile: (707) 497-9192

Email: briankenney@advancedsecurity.us

System Control Unit Manufacturer: First Alert Inspection Date: 01/06/2026 IDC Style:

Model Number: fa 1600c Install Date: 12/11/2014 SLC Style:

Software Version: Version Date: 12/11/2014 NAC Style:

Location: Ground kitchen Disconnect Location: Disconnect Type:

Current Protection:

Monitoring Company: ADVANCED SECURITY

SYSTEMS

Phone: (707) 443-6366 Account #:

Central Station Signal Verification Type: Cellular Mfg: SPS Model #: TG7 FS

Test Time/Date: 1/6/26 11:41:07 AM Restore Time: Note:

Page of 3 13 Executive Summary

Advanced Security Systems, Inc. Download Date: 02/27/2026

Building: Humboldt Bay Wildlife Refuge - Bunk House Contact: CASHELL VILLA

Company: Advanced Security Systems, Inc.

Inspector: Brian Kenny

Inspection Summary

Category

Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty %

Control 7 33.33% 7 100.00% 7 100.00% 0 0.00%

Indicating 4 19.05% 4 100.00% 4 100.00% 0 0.00%

Initiating 10 47.62% 10 100.00% 9 90.00% 1 10.00%

Totals 21 100% 21 100.00% 20 95.24% 1 4.76%

Certification

Brian Kenny Certifications Certification Type Number

California Department of Industrial Relations KennB8439

Page of 4 13 Discrepancy Report

Advanced Security Systems, Inc. Download Date: 02/27/2026

Control Panel: 2Building: Humboldt Bay Wildlife Refuge - Bunk House

DISCREPANCY REPORT

Deficiency, Impairment, and Observation

Generated by: BuildingReports.com

The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.

Building: Humboldt Bay Wildlife Refuge - Bunk House

Items listed for Recall or Replacement/Upgrade Device Type Manufacturer Model Number Date Qty

No recalled items found during this inspection.

Discrepancies ScanID Location Problem Address Reference

INITIATING

Alarm Pressure Switch

95517652 Outside NW Shed 2

Page of 5 13 Proposed Solutions Report

Advanced Security Systems, Inc. Download Date: 02/27/2026

Control Panel: 2Building: Humboldt Bay Wildlife Refuge - Bunk House

PROPOSED SOLUTIONS REPORT

Generated by: BuildingReports.com

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost

Auth orize d Fixed Date

INITIATING

Alarm Pressure Switch

95517652 Outside NW Shed T/M ☐

Customer WO/PO #:

(none)

Internal WO/PO #:

(none)

Total: T/M

Page of 6 13 Inspection & Testing

Advanced Security Systems, Inc. Download Date: 02/27/2026

Control Panel: 2Building: Humboldt Bay Wildlife Refuge - Bunk House

INSPECTION & TESTING

Generated by: BuildingReports.com

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .

Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

PASSED

Control

Battery Ground kitchen Tested 11:44:55 AM 01/06/2026

Battery Ground kitchen Communicator Tested 11:48:15 AM 01/06/2026

Communicator Ground kitchen Communicator Tested 11:41:07 AM 01/06/2026

Power Supply Ground FACP charging circuit Tested 11:44:50 AM 01/06/2026

Indicating

Horn Ground Back exit To the left as you go out the back exit.

Tested 12:30:17 PM 01/06/2026

Strobe Ground Bathroom Tested 12:16:46 PM 01/06/2026

Strobe Ground Bathroom 2 Tested 12:21:17 PM 01/06/2026

Strobe Ground Living Room Tested 12:18:27 PM 01/06/2026

Initiating

Heat Detector Ground kitchen Tested 12:28:45 PM 01/06/2026

Pull Station Ground Entrance Tested 12:36:27 PM 01/06/2026

Pull Station Ground Living Room Tested 12:33:28 PM 01/06/2026

Smoke Detector Ground Living Room Tested/Cleaned 12:17:50 PM 01/06/2026

Smoke Detector Ground Room 1 Tested/Cleaned 12:08:31 PM 01/06/2026

Smoke Detector Ground Room 2 Tested/Cleaned 12:15:55 PM 01/06/2026

Smoke Detector Ground Room 3 Tested/Cleaned 12:23:37 PM 01/06/2026

Smoke Detector Ground Room 4 Tested/Cleaned 12:22:37 PM 01/06/2026

Page of 7 13 Inspection & Testing

Advanced Security Systems, Inc. Download Date: 02/27/2026

Control Panel: 1 - First Alert fa 1600cBuilding: Humboldt Bay Wildlife Refuge - Bunk House

Device Type Location Service Time Date

PASSED (continued)

Initiating (continued)

Smoke Detector Ground Room 5 Tested/Cleaned 12:25:06 PM 01/06/2026

FAILED/OTHER

Initiating

Alarm Pressure Switch Outside NW Shed Tested 12:52:31 PM 01/06/2026

Device Type Location Service Time Date

PASSED

Control

Annunciator by exit Tested 11:39:39 AM 01/06/2026

Battery Ground kitchen Tested 11:44:57 AM 01/06/2026

Control Panel Ground kitchen Tested 11:40:59 AM 01/06/2026

Page of 8 13 Service Summary

Advanced Security Systems, Inc. Download Date: 02/27/2026

SERVICE SUMMARY

Generated by: BuildingReports.com

The Service Summary section provides an overview of the services performed in this report.

Building: Humboldt Bay Wildlife Refuge - Bunk House

Device Type Service Quantity

PASSED

Annunciator Tested 1

Battery Tested 3

Communicator Tested 1

Control Panel Tested 1

Heat Detector Tested 1

Horn Tested 1

Power Supply Tested 1

Pull Station Tested 2

Smoke Detector Tested/Cleaned 6

Strobe Tested 3

Total 20

FAILED/OTHER

Alarm Pressure Switch Tested 1

Total 1

Grand Total 21

Page of 9 13 Sound and Visual Testing

Advanced Security Systems, Inc. Download Date: 02/27/2026

SOUND AND VISUAL TESTING

Generated by: BuildingReports.com

The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.

Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility requirements. The STI or Sound Transmission Index is shown if recorded.

Building: Humboldt Bay Wildlife Refuge - Bunk House

Audible/Visual Appliances Location Comment Ambient Alarm Synched ScanID

PASSED

Strobe

Ground Bathroom Passed ☐ 32387303

Ground Bathroom 2 Passed ☐ 32387307

Ground Living Room Passed ☐ 32387369

Page of 10 13 Battery & Power Supply Testing

Advanced Security Systems, Inc. Download Date: 02/27/2026

Control Panel: 2Building: Humboldt Bay Wildlife Refuge - Bunk House

Control Panel: 1 - First Alert fa 1600cBuilding: Humboldt Bay Wildlife Refuge - Bunk House

BATTERY & POWER SUPPLY TESTING

Generated by: BuildingReports.com

The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Battery

Type Location Rated

Ah Rated Volts

Pre Test

Post Test

Min Ah

Teste d Ah

MFG

Date

PASSED

Sealed Lead Acid Ground kitchen 7 12 (N) 12.9V

06/22 /2025

Battery

Type Location Rated

Ah Rated Volts

Pre Test

Post Test

Min Ah

Teste d Ah

MFG

Date

PASSED

Sealed Lead Acid Ground kitchen 7 12 (N) 12.9V

06/22 /2025

Sealed Lead Acid Ground kitchen Communicator 7 12 13.8V 08/03 /2023

Power Supply

Protection Type Location Rated Ah Rated Volts Charging

Voltage MFG Date

PASSED

Ground FACP charging circuit 12 13.5 12/30/2019

Page of 11 13 Inventory & Warranty Report

Advanced Security Systems, Inc. Download Date: 02/27/2026

Control Panel: 1 - First Alert fa 1600cBuilding: Humboldt Bay Wildlife Refuge - Bunk House

INVENTORY & WARRANTY REPORT

Generated by: BuildingReports.com

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Building: Humboldt Bay Wildlife Refuge - Bunk House

Device or Type Category % of Inventory Quantity

Alarm Pressure Switch Initiating 4.76% 1

Annunciator Control 4.76% 1

Battery Control 14.29% 3

Communicator Control 4.76% 1

Control Panel Control 4.76% 1

Heat Detector Initiating 4.76% 1

Horn Indicating 4.76% 1

Power Supply Control 4.76% 1

Pull Station Initiating 9.52% 2

Smoke Detector Initiating 28.57% 6

Strobe Indicating 14.29% 3

Type Qty Model # Description Install Date

NEW (UNDER 90 DAYS)

Casil

Battery 1 CA1270 Sealed Lead Acid 01/06/2026

IN SERVICE - 10 YEARS TO 15 YEARS

First Alert

Annunciator 1 LCD Display 12/11/2015

Page of 12 13 Inventory & Warranty Report

Advanced Security Systems, Inc. Download Date: 02/27/2026

Control Panel: 2Building: Humboldt Bay Wildlife Refuge - Bunk House

Type Qty Model # Description Install Date

IN SERVICE - 10 YEARS TO 15 YEARS (continued)

First Alert (continued)

Control Panel 1 fa 1600c 12/11/2014

Type Qty Model # Description Install Date

NEW (UNDER 90 DAYS)

Casil

Battery 1 CA1270 Sealed Lead Acid 01/06/2026

IN SERVICE - 1 YEAR TO 2 YEARS

Casil

Battery 1 CA1270 Sealed Lead Acid 12/11/2024

IN SERVICE - 10 YEARS TO 15 YEARS

Chemetron

Heat Detector 1 Rate-of-Rise 12/11/2014

Fire-Lite

Pull Station 2 BG-12 Single Action 12/11/2014

First Alert

Power Supply 1 1600C 12/11/2014

SPS

Communicator 1 TG7 FS Cellular 12/11/2014

System Sensor

Smoke Detector 6 2WB Photoelectric 12/11/2014

Wendland Manufacture Corp.

Alarm Pressure Switch

1 12/11/2014

(manufacturer not specified)

Horn 1 12/11/2014

Strobe 3 12/11/2014

Page of 13 13 Zone Address Report

Advanced Security Systems, Inc. Download Date: 02/27/2026

Control Panel: 2Building: Humboldt Bay Wildlife Refuge - Bunk House

Control Panel: 1 - First Alert fa 1600cBuilding: Humboldt Bay Wildlife Refuge - Bunk House

ZONE ADDRESS REPORT

Generated by: BuildingReports.com

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID

ZONE/CIRCUIT:

left Battery Ground kitchen Sealed Lead Acid 32387366

Address Device Type Location Type ScanID

ZONE/CIRCUIT:

right Battery Ground kitchen Sealed Lead Acid 32387367

Cover Page
Executive Summary
Discrepancy Report
Proposed Solutions Report
Inspection & Testing
Service Summary
Sound and Visual Testing
Battery & Power Supply Testing
Inventory & Warranty Report
Zone Address Report