This is a Fire Alarm Systems Inspection Certificate for the Humboldt Bay Wildlife Refuge - Bunk House located at 1020 Ranch Road, Loleta, CA 95551. The inspection was conducted on January 6, 2026, by Advanced Security Systems, Inc., with inspector Brian Kenny (California Department of Industrial Relations certification number KennB8439). The facility is served by a First Alert fa 1600c control panel installed on December 11, 2014, with cellular monitoring provided by Advanced Security Systems through an SPS TG7 FS communicator. The system was tested to NFPA 72 Standards.
The inspection results indicate that 21 total items were serviced with a 95.24% pass rate. Of the items inspected, 20 passed across all categories (7 control devices, 4 indicating devices, and 9 initiating devices), while 1 failed—an Alarm Pressure Switch located outside the NW Shed requiring time and materials repair authorization. All batteries tested passed, including sealed lead acid units rated at 7Ah/12V with manufacturing dates from June 2025, August 2023, and December 2024. The power supply charging circuit also passed testing with a 13.5V charging voltage. Six smoke detectors, three strobes, two pull stations, one heat detector, and one horn all tested successfully. The facility's communicator and annunciator (LCD display installed December 11, 2015) also passed inspection. The monitoring company account information and specific cost details for the required pressure switch repair were not populated in the report.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Humboldt Bay Wildlife Refuge - Bunk House 1020 Ranch Road Loleta, CA 95551
(707) 733-5406
Building Contact: CASHELL VILLA Title: PROJECT LEADER
Company: Advanced Security Systems, Inc.
Contact: Brian Kenny Title: Life Safety Tech
Fire Alarm Systems
INSPECTION
CERTIFICATE
Jan 6, 2026Inspection Date:
Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 13 Executive Summary
Advanced Security Systems, Inc. Download Date: 02/27/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information Humboldt Bay Wildlife Refuge - Bunk House 1020 Ranch Road Loleta, CA 95551 United States of America
Contact: CASHELL VILLA
Phone: (707)733-5406
Fax:
Mobile:
Email: cashell_villa@fws.gov
Inspection Performed By Advanced Security Systems, Inc.
1336 4th Street Eureka, California 95501 United States of America
Inspector: Brian Kenny
Phone: (707) 497-9192
Fax:
Mobile: (707) 497-9192
Email: briankenney@advancedsecurity.us
System Control Unit Manufacturer: First Alert Inspection Date: 01/06/2026 IDC Style:
Model Number: fa 1600c Install Date: 12/11/2014 SLC Style:
Software Version: Version Date: 12/11/2014 NAC Style:
Location: Ground kitchen Disconnect Location: Disconnect Type:
Current Protection:
Monitoring Company: ADVANCED SECURITY
SYSTEMS
Phone: (707) 443-6366 Account #:
Central Station Signal Verification Type: Cellular Mfg: SPS Model #: TG7 FS
Test Time/Date: 1/6/26 11:41:07 AM Restore Time: Note:
Page of 3 13 Executive Summary
Advanced Security Systems, Inc. Download Date: 02/27/2026
Building: Humboldt Bay Wildlife Refuge - Bunk House Contact: CASHELL VILLA
Company: Advanced Security Systems, Inc.
Inspector: Brian Kenny
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty %
Control 7 33.33% 7 100.00% 7 100.00% 0 0.00%
Indicating 4 19.05% 4 100.00% 4 100.00% 0 0.00%
Initiating 10 47.62% 10 100.00% 9 90.00% 1 10.00%
Totals 21 100% 21 100.00% 20 95.24% 1 4.76%
Certification
Brian Kenny Certifications Certification Type Number
California Department of Industrial Relations KennB8439
Page of 4 13 Discrepancy Report
Advanced Security Systems, Inc. Download Date: 02/27/2026
Control Panel: 2Building: Humboldt Bay Wildlife Refuge - Bunk House
DISCREPANCY REPORT
Deficiency, Impairment, and Observation
Generated by: BuildingReports.com
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Building: Humboldt Bay Wildlife Refuge - Bunk House
Items listed for Recall or Replacement/Upgrade Device Type Manufacturer Model Number Date Qty
No recalled items found during this inspection.
Discrepancies ScanID Location Problem Address Reference
INITIATING
Alarm Pressure Switch
95517652 Outside NW Shed 2
Page of 5 13 Proposed Solutions Report
Advanced Security Systems, Inc. Download Date: 02/27/2026
Control Panel: 2Building: Humboldt Bay Wildlife Refuge - Bunk House
PROPOSED SOLUTIONS REPORT
Generated by: BuildingReports.com
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost
Auth orize d Fixed Date
INITIATING
Alarm Pressure Switch
95517652 Outside NW Shed T/M ☐
Customer WO/PO #:
(none)
Internal WO/PO #:
(none)
Total: T/M
Page of 6 13 Inspection & Testing
Advanced Security Systems, Inc. Download Date: 02/27/2026
Control Panel: 2Building: Humboldt Bay Wildlife Refuge - Bunk House
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Battery Ground kitchen Tested 11:44:55 AM 01/06/2026
Battery Ground kitchen Communicator Tested 11:48:15 AM 01/06/2026
Communicator Ground kitchen Communicator Tested 11:41:07 AM 01/06/2026
Power Supply Ground FACP charging circuit Tested 11:44:50 AM 01/06/2026
Indicating
Horn Ground Back exit To the left as you go out the back exit.
Tested 12:30:17 PM 01/06/2026
Strobe Ground Bathroom Tested 12:16:46 PM 01/06/2026
Strobe Ground Bathroom 2 Tested 12:21:17 PM 01/06/2026
Strobe Ground Living Room Tested 12:18:27 PM 01/06/2026
Initiating
Heat Detector Ground kitchen Tested 12:28:45 PM 01/06/2026
Pull Station Ground Entrance Tested 12:36:27 PM 01/06/2026
Pull Station Ground Living Room Tested 12:33:28 PM 01/06/2026
Smoke Detector Ground Living Room Tested/Cleaned 12:17:50 PM 01/06/2026
Smoke Detector Ground Room 1 Tested/Cleaned 12:08:31 PM 01/06/2026
Smoke Detector Ground Room 2 Tested/Cleaned 12:15:55 PM 01/06/2026
Smoke Detector Ground Room 3 Tested/Cleaned 12:23:37 PM 01/06/2026
Smoke Detector Ground Room 4 Tested/Cleaned 12:22:37 PM 01/06/2026
Page of 7 13 Inspection & Testing
Advanced Security Systems, Inc. Download Date: 02/27/2026
Control Panel: 1 - First Alert fa 1600cBuilding: Humboldt Bay Wildlife Refuge - Bunk House
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector Ground Room 5 Tested/Cleaned 12:25:06 PM 01/06/2026
FAILED/OTHER
Initiating
Alarm Pressure Switch Outside NW Shed Tested 12:52:31 PM 01/06/2026
Device Type Location Service Time Date
PASSED
Control
Annunciator by exit Tested 11:39:39 AM 01/06/2026
Battery Ground kitchen Tested 11:44:57 AM 01/06/2026
Control Panel Ground kitchen Tested 11:40:59 AM 01/06/2026
Page of 8 13 Service Summary
Advanced Security Systems, Inc. Download Date: 02/27/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: Humboldt Bay Wildlife Refuge - Bunk House
Device Type Service Quantity
PASSED
Annunciator Tested 1
Battery Tested 3
Communicator Tested 1
Control Panel Tested 1
Heat Detector Tested 1
Horn Tested 1
Power Supply Tested 1
Pull Station Tested 2
Smoke Detector Tested/Cleaned 6
Strobe Tested 3
Total 20
FAILED/OTHER
Alarm Pressure Switch Tested 1
Total 1
Grand Total 21
Page of 9 13 Sound and Visual Testing
Advanced Security Systems, Inc. Download Date: 02/27/2026
SOUND AND VISUAL TESTING
Generated by: BuildingReports.com
The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.
Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility requirements. The STI or Sound Transmission Index is shown if recorded.
Building: Humboldt Bay Wildlife Refuge - Bunk House
Audible/Visual Appliances Location Comment Ambient Alarm Synched ScanID
PASSED
Strobe
Ground Bathroom Passed ☐ 32387303
Ground Bathroom 2 Passed ☐ 32387307
Ground Living Room Passed ☐ 32387369
Page of 10 13 Battery & Power Supply Testing
Advanced Security Systems, Inc. Download Date: 02/27/2026
Control Panel: 2Building: Humboldt Bay Wildlife Refuge - Bunk House
Control Panel: 1 - First Alert fa 1600cBuilding: Humboldt Bay Wildlife Refuge - Bunk House
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location Rated
Ah Rated Volts
Pre Test
Post Test
Min Ah
Teste d Ah
MFG
Date
PASSED
Sealed Lead Acid Ground kitchen 7 12 (N) 12.9V
06/22 /2025
Battery
Type Location Rated
Ah Rated Volts
Pre Test
Post Test
Min Ah
Teste d Ah
MFG
Date
PASSED
Sealed Lead Acid Ground kitchen 7 12 (N) 12.9V
06/22 /2025
Sealed Lead Acid Ground kitchen Communicator 7 12 13.8V 08/03 /2023
Power Supply
Protection Type Location Rated Ah Rated Volts Charging
Voltage MFG Date
PASSED
Ground FACP charging circuit 12 13.5 12/30/2019
Page of 11 13 Inventory & Warranty Report
Advanced Security Systems, Inc. Download Date: 02/27/2026
Control Panel: 1 - First Alert fa 1600cBuilding: Humboldt Bay Wildlife Refuge - Bunk House
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Building: Humboldt Bay Wildlife Refuge - Bunk House
Device or Type Category % of Inventory Quantity
Alarm Pressure Switch Initiating 4.76% 1
Annunciator Control 4.76% 1
Battery Control 14.29% 3
Communicator Control 4.76% 1
Control Panel Control 4.76% 1
Heat Detector Initiating 4.76% 1
Horn Indicating 4.76% 1
Power Supply Control 4.76% 1
Pull Station Initiating 9.52% 2
Smoke Detector Initiating 28.57% 6
Strobe Indicating 14.29% 3
Type Qty Model # Description Install Date
NEW (UNDER 90 DAYS)
Casil
Battery 1 CA1270 Sealed Lead Acid 01/06/2026
IN SERVICE - 10 YEARS TO 15 YEARS
First Alert
Annunciator 1 LCD Display 12/11/2015
Page of 12 13 Inventory & Warranty Report
Advanced Security Systems, Inc. Download Date: 02/27/2026
Control Panel: 2Building: Humboldt Bay Wildlife Refuge - Bunk House
Type Qty Model # Description Install Date
IN SERVICE - 10 YEARS TO 15 YEARS (continued)
First Alert (continued)
Control Panel 1 fa 1600c 12/11/2014
Type Qty Model # Description Install Date
NEW (UNDER 90 DAYS)
Casil
Battery 1 CA1270 Sealed Lead Acid 01/06/2026
IN SERVICE - 1 YEAR TO 2 YEARS
Casil
Battery 1 CA1270 Sealed Lead Acid 12/11/2024
IN SERVICE - 10 YEARS TO 15 YEARS
Chemetron
Heat Detector 1 Rate-of-Rise 12/11/2014
Fire-Lite
Pull Station 2 BG-12 Single Action 12/11/2014
First Alert
Power Supply 1 1600C 12/11/2014
SPS
Communicator 1 TG7 FS Cellular 12/11/2014
System Sensor
Smoke Detector 6 2WB Photoelectric 12/11/2014
Wendland Manufacture Corp.
Alarm Pressure Switch
1 12/11/2014
(manufacturer not specified)
Horn 1 12/11/2014
Strobe 3 12/11/2014
Page of 13 13 Zone Address Report
Advanced Security Systems, Inc. Download Date: 02/27/2026
Control Panel: 2Building: Humboldt Bay Wildlife Refuge - Bunk House
Control Panel: 1 - First Alert fa 1600cBuilding: Humboldt Bay Wildlife Refuge - Bunk House
ZONE ADDRESS REPORT
Generated by: BuildingReports.com
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
ZONE/CIRCUIT:
left Battery Ground kitchen Sealed Lead Acid 32387366
Address Device Type Location Type ScanID
ZONE/CIRCUIT:
right Battery Ground kitchen Sealed Lead Acid 32387367
| Cover Page |
| Executive Summary |
| Discrepancy Report |
| Proposed Solutions Report |
| Inspection & Testing |
| Service Summary |
| Sound and Visual Testing |
| Battery & Power Supply Testing |
| Inventory & Warranty Report |
| Zone Address Report |
File details come from the government source that posted it. Updated .