3-82700-100-S-23-LSA NCPS Pump Replacement Plans SS.pdf

PDF 11 MB Posted

Attached to
SDCA Naamans Creek Pump Station Upgrades
Solicitation number
US.261380
Issued by
Delaware County, Gibraltar CDP, Pennsylvania

About this file

This file comprises electrical construction plans and specifications for the SDCA Naamans Creek Pump Station Upgrades project located in Lower Chichester, Pennsylvania, prepared for Southern Delaware County Authority. The project involves replacement of pump equipment with new installations requiring comprehensive electrical work including demolition of existing equipment, installation of new Variable Frequency Drives (VFDs), wiring extensions, junction boxes, and coordination with mechanical, plumbing, and HVAC contractors. The work must comply with the 2021 International Building Code, 2021 International Mechanical Code, 2020 National Electrical Code, 2021 International Fire Code, and 2021 International Energy Conservation Code/ASHRAE 90.1-2019. A mandatory pre-bid conference is scheduled for November 19, 2026 at 10:00 AM at the project site (1500 Naamans Creek Road, Garnet Valley, PA 19060), with sealed bids due online via PennBid by 10:00 AM on Monday, December 7, 2026. The project specifications indicate that all materials and equipment must be new unless otherwise noted, with UL listing and ASME/AGA approvals required, and the successful bidder must provide a one-year guarantee from the date of owner acceptance of substantial completion.

The successful bidder will be required to pay PennBid a fee of one-third percent of the contract award value, with a minimum fee of $150.00 and maximum of $6,000.00. A bid bond equal to ten percent of the total bid amount, payable to Southern Delaware County Authority, must accompany each bid submission. The contractor must provide both a performance bond and payment bond for 100 percent of the contract price and a one-year maintenance bond for 10 percent of the contract price. The project is subject to Pennsylvania Prevailing Wage Rates, Public Works Employment Verification requirements, various insurance provisions, equal opportunity requirements, and nondiscrimination/sexual harassment provisions. Funding for this project was provided in part by a grant from the Commonwealth of Pennsylvania Financing Authority. All work must be coordinated with the architect/engineer, with coordination drawings required prior to commencing work, and the contractor bears sole responsibility for construction means, methods, safety procedures, and completion in accordance with all applicable local, state, and federal codes and regulations.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N

SITE

CEA

N

FM FM

FM

FM

CEA

N

GENERAL SPECIFICATIONS ABBREVIATIONS

MUNICIPALITY

USE AND OCC. CLASSIFICATION

APPLICABLE CODES

LOWER CHICHESTER, PA

B (BUSINESS)

CODE SUMMARY

BUILDING CODE: 2021 INTERNATIONAL BUILDING CODE

MECHANICAL CODE: 2021 INTERNATIONAL MECHANICAL CODE

ELECTRICAL CODE: 2020 NATIONAL ELECTRICAL CODE (BY REFERENCE)

FIRE CODE: 2021 INTERNATIONAL FIRE CODE

ENERGY CODE: 2021 INTERNATIONAL ENERGY CONSERVATION CODE/ASHRAE 90.1-2019

1. DRAWINGS AND SPECIFICATIONS FORM COMPLIMENTARY REQUIREMENTS; PROVIDE WORK SPECIFIED AND NOT SHOWN, AND WORK SHOWN BUT NOT SPECIFIED AS THOUGH EXPLICITLY REQUIRED BY BOTH. ALTHOUGH WORK IS NOT SPECIFICALLY SHOWN OR SPECIFIED, PROVIDE SUPPLEMENTARY OR MISCELLANEOUS ITEMS, APPURTENANCES, DEVICES AND MATERIALS

OBVIOUSLY NECESSARY FOR A SOUND, SECURE AND COMPLETE INSTALLATION

2. ANY CONFLICTS BETWEEN THE DRAWINGS, SPECIFICATIONS, AND THE REQUIREMENTS OF THE BUILDING SHALL BE BID USING THE MOST STRINGENT REQUIREMENT, INCLUDING THE GREATER QUANTITY OF WORK AND THE GREATER MATERIAL COST

3. DRAWINGS ARE DIAGRAMMATIC: THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL COMPONENTS NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM. DETERMINE LOCATIONS OF COMPONENTS NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM. DETERMINE LOCATIONS OF SYSTEMS AND COMPONENTS IN FIELD. COORDINATE WITH

ARCHITECTURAL DRAWINGS AND OTHER TRADES.

4. ADDRESS QUESTIONS REGARDING DRAWINGS TO ENGINEER IN WRITING BEFORE AWARD OF CONTRACT. OTHERWISE, ARCHITECT'S INTERPRETATION OF MEANING AND INTENT OF DRAWINGS SHALL BE FINAL

5. THE INTENTION IS FOR INSTALLATION OF COMPLETE AND OPERATING SYSTEMS INSTALLED IN ACCORDANCE WITH THE ASSOCIATED MANUFACTURER'S INSTRUCTIONS. NOT EVERY COMPONENT REQUIRED IS SHOWN. THE CONTRACTOR SHALL INCLUDE ALL COMPONENTS NORMALLY ASSOCIATED WITH THE PARTICULAR SYSTEM AND/OR REQUIRED BY THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE SYSTEM SHALL BE FULLY COMMISSIONED AND SIGNED OFF BY AN

OFFICER OF THE RESPECTIVE CONTRACTOR.

6. PRIOR TO COMMENCING WORK, COORDINATION DRAWINGS MUST BE PREPARED AND SUBMITTED FOR REVIEW AND APPROVAL TO THE ARCHITECT/ENGINEER. EACH TRADE (HVAC, PLUMBING, ELECTRIC, AND FIRE PROTECTION) IS RESPONSIBLE FOR DOCUMENTING THEIR WORK ON THE PLAN ORIGINALLY SUBMITTED AS THE SPRINKLER PIPE FABRICATION DRAWING. LOCATION AND ELEVATION OF THE RESPECTIVE DISCIPLINE'S WORK MUST BE SHOWN ON THE COORDINATION DRAWINGS. SHEETMETAL SHOP DRAWINGS SHALL INCLUDE ALL ELEMENTS OF THE EQUIPMENT, DUCTWORK, AIR DEVICES, AND REFLECTED CEILING PLAN FOR COORDINATION OF CRITICAL DIMENSIONS OF ARCHITECTURAL/STRUCTURAL

COMPONENTS.

7. GIVE NOTICES, FILE PLANS, OBTAIN PERMITS AND LICENSES, PAY FEES AND BACK CHARGES, AND OBTAIN NECESSARY APPROVALS FROM AUTHORITIES THAT HAVE JURISDICTION AS REQUIRED TO PERFORM WORK IN ACCORDANCE WITH ALL

LEGAL REQUIREMENTS AND WITH THE DESIGN DOCUMENTS.

8. MATERIALS AND EQUIPMENT SHALL BE LISTED BY UNDERWRITERS LABORATORIES (UL) AND APPROVED BY ASME AND AGA

FOR INTENDED SERVICE.

9. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES REQUIRED FOR SAFE EXECUTION AND COMPLETION OF WORK, AND FOR INITIATING, MAINTAINING AND

SUPERVISING ALL SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK.

10. ANY INTERFERENCE SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER'S REPRESENTATIVE, AND SHALL BE RESOLVED

PRIOR TO THE INSTALLATION OF THE WORK INVOLVED.

11. ALL MATERIALS, EQUIPMENT AND METHOD OF INSTALLATION SHALL BE ACCORDANCE WITH THE STANDARDS, REGULATIONS, CODES, ORDINANCES, AND LAW OF LOCAL, STATE, AND FEDERAL GOVERNMENTS, AND OTHER AUTHORITIES THAT HAVE

LAWFUL JURISDICTION.

12. IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE HIS WORK WITH THAT OF ALL OTHER TRADES, INCLUDING (BUT NOT LIMITED TO), ELECTRICAL, HVAC, SPRINKLER, PLUMBING, STRUCTURAL AND GENERAL ARCHITECTURE.

OFFSETS IN PIPING AND OFFSETS AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.

13. DEVIATION FROM CONTRACT DOCUMENTS, OR PROPOSED SUBSTITUTION OF MATERIALS OR EQUIPMENT FOR THOSE SPECIFIED, SHALL BE REQUESTED IN SEPARATE LETTER, WHETHER DEVIATIONS ARE DUE TO FIELD CONDITIONS, STANDARD SHOP PRACTICE OR OTHER CAUSE. SUBSTITUTED PRODUCTS SUBMITTED AND APPROVED FOR USE THAT NECESSITATE CHANGES TO THE WORK OF THAT OR ANY OTHER TRADES OF CONTRACT SHALL BE COORDINATED AND ARRANGED BY THE

CONTRACTOR WHO SUBMITTED THE SUBSTITUTION WITHOUT ADDITIONAL COST TO THE OWNER.

14. EACH CONTRACTOR IS RESPONSIBLE FOR ITS CUTTING AND PATCHING REQUIRED FOR THE INSTALLATION OF ITS NEW WORK.

CUTTING AND PATCHING SHALL BE COMPLETED IN A NEAT AND WORKMANLIKE MANNER. PATCHING MATERIALS SHALL MATCH EXISTING MATERIALS TO THE GREATEST EXTENT POSSIBLE. PROVIDE TOUCH-UP TO MATCH EXISTING SURROUNDING AREAS

OF CUTTING AND PATCHING WORK.

15. INTERRUPTIONS TO EXISTING SERVICES AND SYSTEMS SHALL BE MINIMIZED AND AT A TIME AND DURATION APPROVED BY THE OWNER. INCLUDE ALL PREMIUM TIME ASSOCIATED WITH INTERRUPTIONS. INTERRUPTIONS SHALL BE SCHEDULED WITH

OWNER 48 HOURS IN ADVANCE.

16. ANY DEMOLITION SHALL BE COORDINATED WITH OWNER, ARCHITECT, GENERAL CONTRACTOR AND ENGINEER. ALL DEBRIS SHALL BE CLEANED UP AND REMOVED FROM THE SITE BY THE END OF THE DAY. PRIOR TO DISPOSAL OF EQUIPMENT AND MATERIALS, TURN OVER TO THE OWNER ANY REMOVED EQUIPMENT AND MATERIALS PER OWNERS REQUEST.

17. ALL MATERIALS AND EQUIPMENT SHALL BE NEW UNLESS NOTED OTHERWISE.

18. MANUFACTURERS' MODEL NUMBERS ARE SPECIFIED SOLELY TO ESTABLISH STANDARDS OF QUALITY FOR PERFORMANCE

AND MATERIALS.

19. PRODUCT INSTALLATION SHALL ADHERE TO MANUFACTURERS RECOMMENDATIONS.

20. ANY REFERENCE TO ELECTRICAL, PLUMBING AND HVAC CONTRACTORS, NOTED ON THESE DRAWINGS OR STATED IN THE SPECIFICATIONS SHALL NOT BE MISCONSTRUED AS AN INTENTION TO DEFINE SEPARATE CONTRACTORS FOR THE RESPECTIVE WORK. THE GENERAL CONTRACTOR SHALL COORDINATE AND PROVIDE A COMPLETE BUILDING WITH COMPLETE MECHANICAL AND ELECTRICAL SYSTEMS, REGARDLESS OF ANY SPECIFICATION REFERENCES TO OTHER CONTRACTORS.

21. GUARANTEE WORK OF THIS CONTRACTOR IN WRITING FOR ONE YEAR FROM THE DATE OF OWNER'S ACCEPTANCE OF CERTIFICATE OF SUBSTANTIAL COMPLETION. PROMPTLY, REPAIR OR REPLACE DEFECTIVE MATERIALS, EQUIPMENT, WORKMANSHIP AND INSTALLATIONS THAT DEVELOP DEFECTS WITHIN THIS PERIOD. OWNER'S SATISFACTION ANY DAMAGE REPLACEMENTS UNDER GUARANTEED AT NO ADDITIONAL COST TO OWNER. SUBMIT GUARANTEE TO ARCHITECT BEFORE FINAL PAYMENT. STATEMENT OF GUARANTEE REQUIREMENTS SHALL NOT BE INTERRUPTED TO LIMIT OWNER'S RIGHTS

UNDER LAW AND THIS CONTRACT.

A

ABV.

A.F.F.

A.F.G.

A.H.U.

C/B

C.H.

CLG.

CONC.

ELEC.

EM

E.P.O.

EXIST.

FU

GEN.

G.F.I.

GND.

HP

IG

JB

KVA

KW

LTG.

AMPS

ABOVE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLER UNIT

CIRCUIT BREAKER

CABINET HEATER

CEILING

CONCRETE

ELECTRIC

INDICATES LIGHT FIXTURE OR

DEVICE WIRED TO EMERGENCY

CIRCUIT

EMERGENCY POWER-OFF

PUSHBUTTON SWITCH

EXISTING

FUSE (OR FUSED)

GENERAL

GROUND FAULT INTERRUPT

GROUND

HORSE POWER

ISOLATED GROUND

JUNCTION BOX

KILOVOLT-AMPERE

KILOWATT

LIGHTING

L.V.

M.C.

MCB

MECH.

MLO

MOD

MT.

MTD.

MTG.

N.L.

P.C.

PLG

SLD

SP/ST

S/S

SW

T/C

TYP.

U.O.N.

V

WP

XFMR.

(E)

(R)

(RL)

LOW VOLTAGE

MECHANICAL CONTRACTOR

MAIN CIRCUIT BREAKER

MECHANICAL

MAIN LUGS ONLY

MOTOR OPERATED DOOR

MOUNT

MOUNTED

MOUNTING

NIGHT LIGHTING

PLUMBING CONTRACTOR

PLUMBING

SINGLE LINE DIAGRAM

SINGLE POLE/SINGLE THROW

SAFETY SWITCH (DISCONNECT

SWITCH)

SWITCH

TIME CLOCK

TYPICAL

UNLESS OTHERWISE NOTED

VOLTS

WEATHERPROOF

TRANSFORMER

EXISTING TO REMAIN

REMOVE EXISTING

RELOCATED EXISTING

PRICING INSTRUCTIONS - BASE BID

1. BID PRICE SHALL INCLUDE AN ALLOWANCE FOR CONTROL CONNECTIONS FROM

VFD'S TO PLC. ELECTRICAL CONTRACTOR SHALL ALLOW FOR COORDINATION WITH

OWNERSHIP TO FINALIZE THE FULL EXTENT OF THIS SCOPE.

DRAWING NO. DRAWING TITLE

IS

SUE

ISSUED

FO

R PE

RMIT

/27 /20

NAAMAN'S CREEK - DRAWING INDEX

N E

L

TVSS

M

K

E

SURGE PROTECTION DEVICE

POTENTIAL TRANSFORMER

CURRENT TRANSFORMER

AUTOMATIC TRANSFER SWITCH

GROUND CONNECTION

KEY INTERLOCK SWITCH

ELECTRIC INTERLOCK SWITCH

MS

WP

J

PB

GENERAL POWER

P1-3

G

R

SINGLE LINE SYMBOLS

T

AA/FA

SPD

SPD

125V., 20A DUPLEX RECEPTACLE MOUNTED AT 18" AFF UNLESS

OTHERWISE NOTED. "+" INDICATES MOUNTED AT 42" AFF OR 6"

ABOVE COUNTER OR BACKSPLASH.

125V., 20A DUPLEX GFCI RECEPTACLE MOUNTED AT 18" AFF

UNLESS OTHERWISE NOTED. "+" INDICATES MOUNTED AT 42" AFF

OR 6" ABOVE COUNTER OR BACKSPLASH. "WP" INDICATES

WEATHERPROOF ENCLOSURE .

125V., 20A DOUBLE DUPLEX (QUAD) RECEPTACLE, MOUNTED AT

18" AFF UNLESS OTHERWISE NOTED.

JUNCTION BOX, COORDINATE LOCATION, RATING AND SIZE WITH

END DEVICE. PROVIDE FIRE RATED ASSEMBLY WHERE REQUIRED.

COORDINATE JUNCTION BOX TYPE FOR FAN/ PENDANT RATING

WHERE REQUIRED.

PULL BOX. COORDINATE SIZE AS REQUIRED.

MOTOR RATED SWITCH, COORDINATE LOCATION, RATING, AND

SIZE WITH END DEVICE

DISCONNECT SWITCH, COORDINATE LOCATION, RATING AND SIZE

WITH END DEVICE. IF CONCEALED USE GENERAL DUTY, IF

EXPOSED USE HEAVY DUTY.

FUSED DISCONNECT SWITCH, COORDINATE LOCATION, RATING

AND SIZE WITH END DEVICE. IF CONCEALED USE GENERAL DUTY,

IF EXPOSED USE HEAVY DUTY.

COMBINATION MOTOR STARTER AND DISCONNECT; PROVIDED BY

MECHANICAL CONTRACTOR/PLUMBING CONTRACTOR; INSTALLED

BY ELECTRICAL CONTRACTOR

SURGE PROTECTION DEVICE

HOME RUN TO PANEL, "P1" INDICATES PANEL NAME, "3" INDICATES

CIRCUIT BREAKER POSITION.

PANELBOARD, SURFACE MOUNTED.

PANELBOARD, FLUSH MOUNTED.

TRANSFORMER, SIZE, TYPE AND RATING AS INDICATED ON PLAN.

COPPER GROUND BAR, SIZE AS INDICATED ON PLAN.

COPPER GROUND CONDUCTOR, SIZE AS INDICATED ON PLAN.

PLAN NOTE CALLOUT

NEW CONNECTION TO EXISTING

TERMINATION OF DEMOLITION

PANELBOARD; SIZE, TYPE AND RATING AS NOTED

AA = PANEL DESIGNATION;

### = PANEL CAPACITY (AMPERAGE)

MLO = MAIN LUGS ONLY

MCB = MAIN CIRCUIT BREAKER

COORDINATE MFG./TYPE WITH LOCAL UTILITY

METER AND SOCKET. COORDINATE MFG./TYPE WITH LOCAL

UTILITY

TRANSIENT VOLTAGE SURGE SUPPRESSION SYSTEM

PANEL AA

MLO/MCB

MOTOR OR MOTORIZED EQUIPMENT. NUMBER INDICATES

HORSEPOWER (HP)

MOLDED CASE CIRCUIT BREAKER

DRAWOUT CIRCUIT BREAKER

DRAWOUT CIRCUIT BREAKER MEDIUM VOLTAGE

FUSED SWITCH

FUSE

CONTACT

RELAY/CONTACTOR COIL

POWER TRANSFORMER, WITH VOLTAGES AS INDICATED

TRANSFORMER: ### - TRANSFORMER CAPACITY AT

AMBIENT AIR

*** - TRANSFORMER CAPACITY AT FORCED AIR

AA - AMBIENT AIR

FA - FORCED AIR

- Y CONFIGURATION TO GROUND

- DELTA CONFIGURATION

E0.0 ELECTRICAL COVER SHEET

E2.1 ELECTRICAL DEMOLITION AND NEW WORK PLANS

E5.0 ELECTRICAL SINGLE LINE DIAGRAM

5561 Pennell Rd Media, PA 19063 P: 610.361.0700

E0.0

J

J

J

MSB

MSB

MSB

VFD #1

(N)

(BY

OTHERS)

VFD #2

(N)

(BY

OTHERS)

VFD #3

(N)

(BY

OTHERS)

5561 Pennell Rd Media, PA 19063 P: 610.361.0700

CEAE2.0

SCALE - 1/8" = 1'-0"

GROUND LEVEL FLOOR PLAN - NEW WORK

E2.0

SCALE - 1/8" = 1'-0"

GROUND LEVEL FLOOR PLAN - DEMOLITION

PROVIDE NEW WIRING FROM MSB TO VFD, AND FROM VFD TO EACH FLOOR

JUNCTION BOX. FOLLOW SINGLE LINE DIAGRAM FOR WIRING AND CONDUIT SIZING.

ALL CONDUIT TO BE RUN IN RIGID METAL CONDUIT. SPLICE PUMP CONNECTION

WITH JUNCTION BOX IN GROUND FOR CONNECTION TO PUMP MOTOR.

NEW FLOOR MOUNTED CAST IRON FLOOR JUNCTION BOX (NEMA 3R). PUMP

CONDUCTORS TO BE SPLCED WITHIN. SEE SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

NEW WORK NOTES:

DISCONNECT AND REMOVE VFD. COORDINATE PUMP INSTALLATION WITH OTHER

TRADES. LEAVE ALL COMMUNICATION WIRE FOR FUTURE VFD. PROVIDE SPLICE

BOX FOR EXTENSION OF CONTROL WIRE TO NEW VFD LOCATIONS AS SHOWN ON

NEW WORK DRAWINGS.

DEMOLITION NOTES

1. ALL WORK SHALL BE COMPLETED IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE

AND THE LOCAL AUTHORITY HAVING JURISDICTION.

2. COORDINATE OTHER TRADE CONSTRUCTION WITH APPROPRIATE TRADE.

3. CONFIRM ALL DEVICE MOUNTING HEIGHTS AND EXISTING CONDITIONS PRIOR TO

INSTALLATION.

4. NEC 110.26 REQUIRED CLEARANCES SHALL BE MAINTAINED FOR EXISTING AND NEW

ELECTRICAL EQUIPMENT INSTALLED DURING CONSTRUCTION.

5. COORDINATE ALL VFD TO PLC SIGNAL AND CONTROL WIRING INTERCONNECTION

REQUIREMENTS WITH OWNERSHIP PRIOR TO CONSTRUCTION. PLC PROGRAMMING BY

OTHERS. CONTROL AND SIGNAL WIRING BY ELECTRICAL CONTRACTOR

GENERAL NOTES:

E2.1

1. RETAIN EXISTING PUMP BRANCH CIRCUITS AND EXTEND AS REQUIRED TO

CONNECT NEW PUMPS. MATCH CONDUCTOR TYPE AND SIZE.

ALTERNATE

E2.0

SCALE - 1/4" = 1'-0"

ELEVATION

1. ALL WORK SHALL BE COMPLETED IN ACCORDANCE WITH THE NATIONAL

ELECTRIC CODE AND THE LOCAL AUTHORITY HAVING JURISDICTION.

2. CONFIRM ALL DEVICE MOUNTING HEIGHTS AND EXISTING CONDITIONS PRIOR

TO INSTALLATION.

3. NEC 110.26 REQUIRED CLEARANCES SHALL BE MAINTAINED FOR EXISTING

AND NEW ELECTRICAL EQUIPMENT INSTALLED DURING CONSTRUCTION.

4. COORDINATE ALL VFD SIGNAL AND CONTROL WIRING INTERCONNECTION

REQUIREMENTS WITH OWNERSHIP PRIOR TO CONSTRUCTION.

PROGRAMMING BY OTHERS. CONTROL AND SIGNAL WIRING BY E.C.

5. PROVIDE BONDING & GROUNDING PER NEC.

GENERAL NOTES:

DEMOLISH PUMP EQUIPMENT FEEDER BREAKER.1

DEMO SHEET NOTES

NEW VFD OWNER SUPPLIED AND INSTALLED BY E.C. COORDINATE FINAL

CONTROL REQUIREMENTS WITH MECHANICAL CONTRACTOR.

NEW FLOOR MTD CAST IRON FLOOR JUNCTION BOX (NEMA 3R). PUMP

CONDUCTORS TO BE SPLICED WITHIN. SEE SINGLE FOR MORE INFORMATION.

NEW WORK SHEET NOTES

EXISTING CONDUIT AND CONDUCTORS

TO BE EVALUATED FOR REUSE

3 #4/0 & 1 #1/0 GRD CU IN

RIGID STL CONDUIT

3 #4/0 & 1 #1/0 GRD CU IN

RIGID STL CONDUIT

2 2

1 1

3 #4/0 & 1 #1/0 GRD CU IN

LIQUIDTIGHT FLEX MC

5561 Pennell Rd Media, PA 19063 P: 610.361.0700

CEA

E5.0

SCALE - NO SCALE

ELECTRICAL SINGLE LINE - DEMOLITION

E5.0

SCALE - NO SCALE

ELECTRICAL SINGLE LINE - NEW WORK

E5.0

Sheets and Views
E0.0 Cover - E0.0
E2.1 floor plans - E2.1
E5.0 single line - E5.0

File details come from the government source that posted it. Updated .