3-26-054-R - Drawings.pdf
PDF 489 KB Posted
- Solicitation number
- 26-054-R
- Issued by
- Winnebago County, Wisconsin
About this file
This is a technical drawing specification document for Walworth County Department of Public Works in Elkhorn, Wisconsin, detailing a motor-operated rolling door system for a salt shed facility. The project involves the furnishing and installation of a NEMA 4X motor-operated rolling door with integrated safety and control features. The door specifications include a 30'-6" opening width, 33'-2" overall height, and 19'-9" door opening height, constructed of galvanized steel with GalvaNex coating in gray finish. The motor system includes a totally enclosed non-ventilated (TENV) motor, reversing magnetic controller, spur gear box, electric brake, auxiliary chain operator, and a transformer with 24-volt control secondary. Control components specified include two push button stations (one NEMA 1 and one NEMA 4X), a wireless sensing edge kit, an electric sensing edge, a UL325 light curtain, and associated safety monitoring modules. The drawing, dated May 12, 2026, with revisions through June 5, 2025, was prepared by John K with drawing number E 02188112 001 B.
The structure supporting the door system must be designed to accommodate a 4,304-pound static load, with materials specified as hot-dip galvanized structural steel per ASTM A 123. Assembly fasteners include Grade 8 hex head cap screws, hex head nuts, hardened flat washers, and hex head lag screws, with critical spacing requirements to maintain factory-set guide gaps essential for proper door operation and wind load resistance. Installation requires a minimum 16-inch clearance in front of the motor for control access, and electrical current specifications must be verified in writing before manufacturing begins. The door's coil is mounted on the exterior side of the building and may be exposed to weather conditions.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL EQUIPMENT LIST:MOTOR SPECIFICATIONS:
LRG_STDR
SPRING
ADJUSTOR
ELEVATION (COIL SIDE) AND SECTION VIEW
See drawing # for guide detail.
MATERIAL & FINISH:
QUANTITY & MARK:
Hood -
Plain Steel -
Curtain -
Guides -
Bottom Bar -
O
PE
N
IN
G H
EI
G
H T
O
VE
R
AL
L D
O O
R H
EI
G
H T
D O
O R
O
PE
N
IN
G H
EI
G
H T
# GA. INTERLOCKING SLATS
ROLLING DOOR
DISTANCE BETWEEN GUIDES
OPENING WIDTH
MECH COVER
"SUPPORT TO RUN TO TOP OF COIL"
MOTOR COVER
EXTERIOR SLOPED
HOOD
3"
SOLID WALL CONSTRUCTION REQ'D
FOR PROVIDED HOOD SUPPORT(S)
BETWEEN EACH HOOD SECTION
(2) SECTION
1-1/2" TOP HOOD BEAD
FLARED FOR CAULKING
REVISION DATE BY
ORIGINAL DRAWING
JOB:
MODEL # : JOB #:
DEALER*:
CONTRACTOR:
ARCHITECT:
PRODUCT CODE:
â
* "Dealer" refers to any purchaser, customer, or reseller of CornellCookson products, and not necessarily an authorized CornellCookson dealer.
SGH NEMA 4X MOTOR
OPERATED ROLLING DOOR
STOPPERS
HP motor to include a totally enclosed non-ventilated (TENV) motor removable without resetting of limit switches, reversing magnetic controller in NEMA 4X enclosure, spur gear box for drive reduction, electric brake and an auxiliary chain operator. Includes magnetic contactors, UL listed thermal overload protection, rotary limit switches, safety edge circuit and transformer with 24 volt control secondary, delay on reverse, and a door closing warning signal. Pre-wired to a terminal block using color coding of the wires to facilitate troubleshooting. A minimum clearance of 16” in front of motor is required for control access.
CURRENT CHARACTERISTICS:
HZV PH
Electrical current must be verified in writing before job is released for manufacture; current verified and found correct.
Operator bracket bracing required, unless operator is wall mounted.
Signed:
FLA
BOTTOM BAR LOCKING:
None
NOTE: COIL IS MOUNTED ON THE EXTERIOR SIDE OF THE
BUILDING AND MAY BE EXPOSED TO WEATHER1/2"1/2"
WIRELESS
TRANSMITTER
(FIELD MOUNTED)
WIRELESS RECEIVER
(FIELD MOUNTED)
SENSING EDGE
AUXILIARY
HAND CHAIN
2"
14 3/8"±
03-17-2026
'-6
3.9460
MFO 5F 20GP
05/12/26 JOHNK
E 2188112 001 B
ELKHORN, WI
WALWORTH COUNTY DPW SALT SHED
(001)
Galvanized steel with GalvaNex™ coating system.
Finish color: Gray
CORNELLCOOKSON A.D.S.
Structural steel, hot dip galvanized per ASTM A 123
Galvanized steel with GalvaNex™ coating system.
Finish color: Gray
MK:001
Hot dip galvanized per ASTM A 123
Structural steel, hot dip galvanized per ASTM A
ESD10
(**Ultra Powder Coat Slats**)
E 02188112 001 A
6 3/4"
7 3/4"±
19'-10"
19'-9"
9 3/4"±
6 3/4"
23 3/4"
'-6
9"
'-2
1 - Three button push button station `OPEN-CLOSE-STOP` in NEMA 1 enclosure, surface mounted.
1 - Three button push button station `OPEN-CLOSE-STOP` in NEMA 4X enclosure, MMTC 3B4X, flush mounted.
1 - Module GW40-05-1(Reqd w/ (2) monitored entrapment devices) 1 - Y Connector wiring harness #ADA-DA111-WH001.
1 - Telco UL325 light curtain.
1 - Electric sensing edge.
1 - Smartsync wireless, failsafe sensing edge kit.
COIL SIDE
EXTERIOR
MTR.AMP
GID.SCLR.LT
SIDE.CLR.ADJ
SL.GA
DBG
PROPEN
SIDE.CLR.OPR
GID.SCLR.RT
HOD.TOP.DIM
COL.SZ
COH
UPS
OAH
Joseph Latocha Cross-Out
G224A - 4 1/4"
PLAN OF OPENING
SERVICE DOOR GUIDE ASSEMBLY
4-1/4" PACKOFF
SD1_425
AT ON CENTER
ASSEMBLY FASTENERS:
G224A - 4 1/4"
AT ON CENTER
ASSEMBLY FASTENERS:
DISTANCE BETWEEN GUIDES
OPENING WIDTH
1/4" STEEL BRACKET PLATE ABOVE
2 5/8" 1 1/4"
1 5/8"
4 1/4"
1/2"
1 1/8"
3" x 2" x 3/16"
3" x 3 1/2" x 1/4"
6 1/4"
7 1/4"
2 1/2"
1/2"
6 1/4"
7 1/4"
2 1/2"
2 5/8" 1 1/4"
1 5/8"
4 1/4"1 1/8"
3" x 2" x 3/16"
WALL FASTENERS: WALL FASTENERS:
AT ON CENTER AT ON CENTER
INSTALLERS NOTE:
MAINTAINING FACTORY SET GUIDE GAPS IS CRITICAL
TO THE PROPER OPERATION OF THE DOOR AND IT'S
ABILITY TO WITHSTAND THE DESIGNED WINDLOAD!
ENDLOCK DETAIL
NOTE: Wall construction detail shown is for illustrative purposes only, does not imply compliance with building requirements, and must meet architectural specifications to properly support product. Products designed with wind load requirements must be properly fastened to structural members as specified in order to avoid catastrophic failure. Wall construction and closure installation shall be in accordance with the local authority having jurisdiction requirements.
3 1/2" x 3 1/2" x 1/4"3 1/2" x 3 1/2" x 1/4"
REVISION DATE BY
ORIGINAL DRAWING
JOB:
MODEL # : JOB #:
DEALER*:
CONTRACTOR:
ARCHITECT:
PRODUCT CODE:
â
* "Dealer" refers to any purchaser, customer, or reseller of CornellCookson products, and not necessarily an authorized CornellCookson dealer.
- Ø3/8-16 x 1-1/2"- Ø3/8-16 x 1-1/2" - Ø3/8"- Ø3/8" HEX HEAD CAP SCREW, GR. 8
- HEX HEAD NUT, GR. 8
- HARDENED FLAT WASHERS
HEX HEAD CAP SCREW, GR. 8
- HEX HEAD NUT, GR. 8
- HARDENED FLAT WASHERS
- HEX HEAD LAG SCREW- HEX HEAD LAG SCREW
x 2" x 2"
3/4" 2 5/8"
CP0020
EXTERIOR
COIL
SENSING
EDGE
2" 2"
BOTTOM BAR / SLAT DETAIL
CP1443 MOLDED NYLON ENDLOCK
ON ALTERNATING SLATS WITH
2 x 1/4" RIVETS
CP1443
1 1/2" (TYP.)
LIGHT CURTAIN
(TYP.)
06-05-2025
STRUCTURE MUST BE
DESIGNED TO SUPPORT
4304 LBS STATIC LOAD
MFO 5F 20GP
05/12/26 JOHNK
MK:001
ELKHORN, WI
WALWORTH COUNTY DPW SALT SHED
CORNELLCOOKSON A.D.S.
ESD10 E 2188112 001 B
24" 24"
19'-10"
19'-9"
24" 24"
WLFSTSPCNGMAXL
ASYFSTSPCNGMAXL
DBG
PROPEN
WLFSTSPCNGMAXR
ASYFSTSPCNGMAXR