This document is Amendment No. 1 to a Request for Lease Proposals (RLP) for the U.S. Secret Service, specifically modifying Section 6.04 regarding Heating and Air Conditioning (Warehouse) for a facility in Washington, DC and Suburban Maryland. The amendment provides detailed specifications for temperature and humidity control, including maintaining office temperatures between 72-75 degrees Fahrenheit during operational hours, setting non-working hour temperatures to 55 degrees, and requiring 24/7 cooling for a designated server room with temperatures between 69-78 degrees and humidity not exceeding 60%. The lease amendment is dated September 30, 2025, and is associated with RLP No. 2DC0655, issued by GSA Public Buildings Service Region 11, with specific requirements for HVAC system maintenance, balancing, and operation that must be provided by the Lessor as part of the operating rent.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GSA Public Buildings Service Region 11
US General Services Administration
Lessor______ Gov’t______
AMENDMENT NO. 1 to REQUEST FOR LEASE PROPOSALS (RLP)
RLP No. 2DC0655 U.S. Secret Service
Washington, DC & Suburban Maryland September 30, 2025
Request for Lease Proposals (RLP) No. 2DC0655 is amended as follows:
1. Section 6.04 HEATING AND AIR CONDITIONING (WAREHOUSE) (OCT 2024) of RLP Exhibit A – 2.
Warehouse Lease Template L201WH – Washington, DC USSS, shall be deleted in its entirety and replaced with the following:
6.04 HEATING AND AIR CONDITIONING (WAREHOUSE) (OCT 2024)
A. In all office areas, temperatures shall conform to local commercial equivalent temperature levels and operating practices in order to maximize tenant satisfaction. Thermostats shall be set to maintain temperatures of 72 degrees F (+/- 3 degrees) during the heating season and 75 degrees F (+/- 3 degrees) during the cooling season. These temperatures shall be maintained throughout the leased Premises and service areas, regardless of outside temperatures, during the hours of operation specified in the Lease. The Lessor shall perform any necessary systems start-up required to meet the commercially equivalent temperature levels prior to the first hour of each day’s operation. At all times, the dew point shall be maintained below 55 degrees F in occupied spaces, and below 60 degrees F in unoccupied spaces.
B. In all office areas, during non-working hours, heating temperatures shall be set no higher than 55 degrees F, and air conditioning shall not be provided except as necessary to return Space temperatures to a suitable level for the beginning of working hours. Thermostats shall be secured from manual operation by key or locked cage. A key shall be provided to the Government’s designated representative.
C. INTENTIONALLY DELETED
D. The Lessor shall conduct HVAC system balancing after any HVAC system alterations during the term of the Lease and shall make a reasonable attempt to schedule major construction outside of office hours.
E. Normal HVAC systems’ maintenance shall not disrupt tenant operations.
F. 146,679 ABOA SF of the Premises (all of the warehouse space) shall receive cooling at all times (24 hrs. a day, 365 days a year) for purposes of cooling the designated server room. The temperature of this room shall be maintained between 69- and 78- degrees F, with humidity control not to exceed 60% relative humidity, regardless of outside temperature or seasonal changes.
G. INTENTIONALLY DELETED
H. The 24 hour, 365 days a year HVAC service(s) stated above shall be provided by the Lessor as part of the operating rent established under the Lease.
FOR THE LESSOR: FOR THE GOVERNMENT:
Name: Name: Lisa Richmond Title: Title: Contracting Officer Entity: _ Entity: General Services Administration, Public Building Service Date: Date:
6.04 HEATING AND AIR CONDITIONING (WAREHOUSE) (OCT 2024)