Exhibit B1 - Agency Requirements - 12.10.2024.pdf
PDF 2 MB Posted
- Attached to
- GENERAL SERVICES ADMINISTRATION (GSA) SEEKS TO LEASE SPACE IN IMPERIAL, CA - RLP PACKAGE
- Solicitation number
- 2CA1503
About this file
This is an agency special requirements document (Exhibit B-1) dated 12/10/2024 that details specific building design and technical requirements for a U.S. Citizenship and Immigration Services (USCIS) facility.
The document outlines comprehensive requirements for a USCIS office space, which must be BOMA Class A or B located within a professional office/business park setting and within 1/2 walkable mile to public transportation. Key requirements include: separate public and employee entrances; public spaces (approximately half the total space) must be on the same floor; Level III security requirements; dedicated HVAC systems for specific areas like computer rooms; specialized rooms including HSDN/TALON rooms, interview rooms, and secure file storage; comprehensive electronic security systems including HSPD-12 compliant access control; and specific technical requirements for electrical, data, and telecommunications infrastructure. The document provides detailed specifications for flooring, walls, ceilings, lighting, and other building components, as well as requirements for documentation, warranties, and post-occupancy maintenance. The facility must achieve Energy Star rating and obtain Green Globes Certification for tenant interiors.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Special Requirements
USCIS Facilities Management Division Version 4.1 – January 2022
Exhibit B-1 Agency Special Requirements
DATED 12/10/2024
Gov ________ / Lessor _______
Version 4.1 – January 2022 Page 2 of 40
Table of Contents
BUILDING DESIGN 3
BRANDING 4
SIGNAGE 4
EXTERIOR SIGNAGE 4
INTERIOR SIGNAGE 4
COLOR PALETTES 5
BUILDING HOURS OF OPERATION 5
REGULAR BUSINESS HOURS 5
AFTER HOURS HVAC 5
24/7 HVAC 5
APPENDICES 5
SPACE REQUIREMENTS 6
OFFICE DIRECTOR AREA 6
IMMIGRATION SERVICES 7
IMMIGRATION SERVICES SUPPORT DIVISION 8
SUPPORT 9
FRAUD DETECTION AND NATIONAL SECURITY SPACES 10
JOINT USE AND OFFICE SUPPORT SPACES 11
DESIGN 12
GENERAL NOTES 12
ENVIRONMENTAL CONSIDERATIONS 15
FINISH PERFORMANCE 16
TYPICAL DESIGN LAYOUTS 20
HSDN/TALON ROOM CONFIGURATION 20
SHOWERS 20
CHECK-IN | DECISION COUNTERS 21
LACTATION ROOM 22
WALL PARTITION TYPES 22
SCHEDULES 23
CEILINGS 23
DOORS 24
ELECTRICAL - POWER AND DATA 25
FLOORING 28
HVAC - MECHANICAL 28
LIGHTING 29
MISCELLANEOUS 30
SECURITY 32
WALLS 33
SUMMARY OF REQUIREMENTS &
MAINTENANCE 34
DELIVERABLES 35
EQUIPMENT LISTS 36
WARRANTY 36
POST WARRANTY PREVENTATIVE MAINTENANCE 36
DRAWING REQUIREMENTS 37
TEST-FIT SUBMISSION 38
DESIGN INTENT DOCUMENT (DID) SUBMISSION 38
CONSTRUCTION DOCUMENT (CD) SUBMISSION 39
AS-BUILT SUBMISSION 40
FINAL RECORD DRAWING SUBMISSION 40
Version 4.1 – January 2022 Page 3 of 40
Building Design
The U.S. Citizenship and Immigration Services (USCIS) maintains a strong tradition of public building design that reflects the highly respected stature of the U.S. Government. All USCIS facilities should embrace and illustrate this principle and present a building or office environment that exhibits fiscal prudence and efficiency of the public’s money, as well as contribute to the vitality of the surrounding area.
USCIS space shall be in an office, research, technology, or business park that is modern in design with a campus-like atmosphere; and be in a modern office building that is professional and prestigious in appearance with the surrounding development well maintained and in consonance with a professional image. The space shall be within an appropriately zoned district, i.e., Central Business District, Business Park, Commercial, or Office. Buildings located within any type of Manufacturing, Industrial, Warehouse, Retail or similar zones will not be accepted. Space shall be BOMA Class “A” or Class “B” Office space with no exceptions (See General Notes for definitions). USCIS space shall be located within a ½ walkable mile to public transportation with one or more bus stops or combination of bus and train stops. Adequate eating facilities shall be located within the immediate vicinity. Other services such as retail shops, cleaners, banks, etc. shall also be located within the immediate vicinity.
USCIS space can be located on more than one floor. However, the public spaces (which consist of approximately half of the space) should remain on the same floor serving most public functions. The remaining USCIS required space will be planned accordingly to include proper and separate access (including elevators) for the public and for employees.
The separation of the Public and Employee space will be an important aspect of this facility. All visitors shall enter through a single, well-defined, secure entrance. The entrance sequence will include a public entry that provides for protection from the weather while waiting for the security screening. USCIS employs an online appointment scheduling system, so visitors will come in a consistent stream throughout the day. The employees will enter through a separate entrance.
The proposed site, building and premises must comply with the security requirements for up to a Level III facility. Refer to Appendices 1 thru 4.
Version 4.1 – January 2022 Page 4 of 40
Branding Branding is incorporated throughout USCIS spaces and includes Lady Liberty, interior signage, and exterior signage. Branding is further emphasized using color palettes.
Signage All signage shall meet ADA and local codes. The Lessor’s Architect shall coordinate with the USCIS PM for government approval of the signage numbering scheme and location for incorporation into the design intent drawing submissions. During the Construction Administration Process, the lessor team shall submit a comprehensive signage package for government approval inclusive of sign type, size, color, material, message, mounting type and location. USCIS shall ensure correct spellings, punctuation and capitalization during the submittal approval process.
The lessor team shall design, procure and install the following signage annotated in the chart and sections below:
Exterior Signage Signage must be provided on the exterior of the building or in the entrance area to the USCIS space (such as multi-tenant Central Business District buildings). Additionally, USCIS may include a freestanding monument sign. The proposed sign location should be located on the site plan or building elevation plans. Based on the Lessor’s building location, additional exterior directional signage may be required for campus or professional park environments. (Dimensions utilized in the following layout are for scaling purposes only.
Lady Liberty The Lady Liberty image should be provided on the exterior perimeter of the building near the public entry or within the public lobby space. Sizing, color, and material application will be determined during the design.
Interior Signage USCIS has agency specific interior signage requirements for consistency throughout USCIS spaces. Refer to the USCIS Sign Standards Design Guidelines for interior signage specifications, locations and size requirements.
USCIS SIGNAGE REQUIREMENTS
Signage Types Lessor Procure Lessor Install Lessor Maintain USCIS Maintain Exterior Signage and Lady Liberty X X X
Building and Tenant Wayfinding/Circulation /Directional Signage
X X X
TI USCIS Identity Signs X X X TI Informational/Freestanding Signage X X X
TI Office Signage X X X TI Workstation/Desk Signage X X X
TI Regulatory Signage X X X
Version 4.1 – January 2022 Page 5 of 40
Color Palettes USCIS color palettes will be incorporated into the space. The Lessor’s architect will work with the USCIS PM to establish the color palette during design.
USCIS COLOR PALETTES
DARK ACCENT MEDIUM ACCENT LIGHT ACCENT WHITE BASE
Benjamin Moore Benjamin Moore Benjamin Moore Benjamin Moore
Orange Tone Masada (AF-220 Classic Caramel (1118) Putnam (HC-39) Elephant Tusk (OC-8)
Blue Tone Blue Danube (2062-30) Philadelphia Cream (HC-30) Yellow Freeze (2020-70) Ocean Air (2123-50)
Red Tone Apache Red (1295) Secret (AF-170) Stonington Gray (HC-170) White Dove (OC-17)
Green Tone Guilford Green (HC-116) Chambourd (AF-645) Lancaster Whitewash (HC-174) White Dove (OC-17)
Violet Tone Mint Violet (1252) Stardust (2108-40) Tapestry (975) White Dove (OC-17)
Tan/Blue Tone
Quincy Tan (HC-25) Montpeliar (AF-555) Stonington Gray (HC-170 Sea pearl (OC-19)
Building Hours of Operation
Regular Business Hours The entire building is considered operational from 7:00am to 6:00pm five days per week (except for Federal Holidays).
After Hours HVAC USCIS recognizes that all utility costs (excluding 24/7) in excess of regular business hours per day Monday through Friday will be paid for as overtime utilities through either a Reimbursable Work Authorization, purchase card (PCard) or lease amendment. 24/7 HVAC spaces annotated below shall not be included as a separate overtime utility cost to the government.
24/7 HVAC
All USCIS space must be capable of having HVAC services on 24/7. HVAC shall be zoned accordingly to avoid unoccupiable areas (such as plenum, crawl spaces etc.) from being heated or cooled.
Appendices Note: Documents below are subject to change. Any and all updates will be provided as necessary.
1. Facility Security Specific Requirements (FSSR) - For FSL Level IV
2. RLP USCIS FSL Attachment – For FSL Level II & III
3. Physical Security Construction Standard (PSCS) and annexes
4. 3rd Edition ISC Appendix B (password protected)
5. USICS Structured Cable Plant Standards V2.3
6. USCIS Computer and Telephone Room Standards
7. USCIS Computer and Telephone Room Appendix A
8. USCIS Audiovisual Standards
9. USCIS Sign Standard Design Guidelines
10. USCIS BIM Requirements
11. USCIS M3 BIM Matrix
The following rooms and/or rooms housing the equipment identified below, shall not be included as a separate overtime utility cost to the government.
Security Equipment (ESS) Lan Rooms Phone Switch Rooms/ Telecommunications Room Main Point of Entry (MPOE) or Demarcation Computer Room Remote Wiring Closets Tenant Uninterrupted Power Source (UPS)
Version 4.1 – January 2022 Page 6 of 40
Space Requirements The design solution shall combine all Public and Interview Space on a single floor. Multi-floor solutions will be considered if all Public Spaces and Interview Spaces cannot be accommodated on the same floor.
The legend is a color-coded adjacency chart for separation of public, interview and non-public spaces. The legend is applicable to each Asylum Requirement (room, area, division, or staffing) annotated on the subsequent pages under this heading.
General Note: Check-in | SIT | Decision Counters are required to separate USCIS Public Space and Interview Space. These counters should be welcoming and open while maintaining the security and privacy to both customers and USCIS employees. The public entry shall include a weather vestibule (if the entry is at an exterior door) and a security screening area. The security screening area, where guards will be posted, will include tenant provided walk-through metal detectors, x-ray machines and an area to conduct Biometrics.
Office Director Area The Office Director is the individual responsible for overseeing the operations of the USCIS Office location. This office shall occupy a prominent area within the facility. The Office Director’s Area consists of private offices planned with open office workstations including a reception area, conference room (typically adjacent to the Office Director’s office), copy area, storage, and circulation space.
ROOM (STAFFING) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Director F1 W1 D3 C1 L1 H1 E1 S4
Deputy Director F1 W1 D1 C1 L1 H1 E1
Section Chief F1 W1 D1 C1 L1 H1 E2
Chief of Staff F1 W1 D1 C1 L1 H1 E2
Community Relations Officer F1 W1 D1 C1 L1 H1 E2
Supervisory ISA F1 W1 D1 C1 L1 H1 E2
Supervisory OSS F1 W1 D1 C1 L1 H1 E2
Congressional Liaison F1 W1 D1 C1 L1 H1 E2
ROOM (SUPPORT) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Mgmt VTC Conference Room F1 W1 D2 C1 L2 H2 E3 M1
Copier Room - Management F1 W2 N/A C1 L3 H1 E5 M2
OPEN OFFICE (STAFFING) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Mission Support Specialist F1 N/A N/A C1 L1 H1 E4
Mission Support Analyst F1 N/A N/A C1 L1 H1 E4
Immigration Services Analyst F1 N/A N/A C1 L1 H1 E4
Operations Support Specialist F1 N/A N/A C1 L1 H1 E4
Mgmt and Program Analyst F1 N/A N/A C1 L1 H1 E4
Special Assistant F1 N/A N/A C1 L1 H1 E4
Training Officer F1 N/A N/A C1 L1 H1 E4
Teleworker F1 N/A N/A C1 L1 H1 E4
OPEN OFFICE (SUPPORT) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Copier Area F1 W2 N/A C1 L3 H1 E5 M2
Reception / Open Office Space / Circulation
F1 W2 D3 C1 L1 H1 E4 S5
Legend
Public Space (must be located within a contiguous block of space on the same floor) shown in green shaded cells
Interview Space | Public Escorted at All Times (must be located within a contiguous block of space on the same floor as Public Spaces above) shown in yellow shaded cells
Non-Public Space | No Public Allowed (may be on a different contiguous floor depending on the function) shown in white cells
Version 4.1 – January 2022 Page 7 of 40
Immigration Services
Immigration Services is responsible for conducting interviews to determine eligibility to receive citizenship in the United States of America. The design of this area should reflect the importance of the process and provide a space that is comfortable for both the customer and employee.
ROOM (STAFFING) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Supervisory ISO F1 W1 D2 C1 L1 H1 E2 M3 | M4 | M7
Immigration Services Officer F1 W1 D2 C1 L1 H1 E2 M3 | M4 | M7
Customer Service ISO F1 W1 D2 C1 L1 H1 E2 M3 | M4 | M7
Asylum Circuit Rider F1 W1 D2 C1 L1 H1 E2 M3 | M4
Branch Chief F1 W1 D2 C1 L1 H1 E2 M3 | M4
ROOM (SUPPORT) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Special Needs Office F1 W1 D1 C1 L1 H1 E2 M3
HUB Room F1 | F3 W3 D4 C1 L3 H1 E6 M4
FDNS Duty Office F1 W1 D1 C1 L1 H1 E2 M3
Team / Collaboration Room (VTC | Video Teleconference)
F1 W1 D2 C1 L2 H2 E3 M1
Team / Collaboration Room (Non-VTC)
F1 W1 D2 C1 L2 H2 E3 M1 | M9
NATZ Room F1 W1 D1 C2 L2 H3 E3
Naturalization Certificate Prep Room
F1 W3 D1 C1 L1 H1 E2
NATZ Room Storage F1 W3 D1 C1 L1 H1 E2
Cashier/Form Storage F1 W5 D8 C7 L2 H2 E3 M1
Information Counters F4 W4 D1 C2 L4 H3 E10 M6 S4
Adjudications Interview/Infopass Waiting Rooms
F4 W4 D3 C2 L4 H3 E8 M5 S4
OPEN OFFICE (SUPPORT) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Copier Area (Non-Public Space)
F1 W2 N/A C1 L3 H1 E5 M2
Open Office Space/Circulation/Corridors
(Non-Public Space)
F1 W2 D3 C1 L1 H1 E4
Immigration Services Analyst F1 NA NA C1 L1 H1 E4
Teleworker F1 NA NA C1 L1 H1 E4
Copier Area (Interview Space)
F1 W2 N/A C1 L3 H1 E5 M2
Open Office Space/Circulation/Corridors
(Interview Space)
F1 W2 D3 C1 L1 H1 E4 S5
Version 4.1 – January 2022 Page 8 of 40
Immigration Services Support Division
The Immigration Services Support Division maintains all files and records regarding applicants. This division’s open office spaces may be combined with the other open office spaces in other divisions.
ROOMS (STAFFING) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Records Manager F1 W1 D1 C1 L1 H1 E2
ROOMS (SUPPORT) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
A-File Room F1 | F3 D4 C7 L1 H1 E6 M17
Secure File Room F1 | F3 W3 D4 C7 L1 H1 E6 M4
OPEN OFFICE (STAFFING) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Immigration Services Assistant F1 - - C1 L1 H1 E4
Government Clerical F1 - - C1 L1 H1 E4
Contractor Management Staff F1 - - C1 L1 H1 E4
Records Clerk F1 - - C1 L1 H1 E4
Contractor Clerical Staff F1 - - C1 L1 H1 E4
Immigration Services Clerk F1 - - C1 L1 H1 E4
Office Automation Assistant F1 - - C1 L1 H1 E4
Teleworker F1 - - C1 L1 H1 E4
OPEN OFFICE (SUPPORT) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Open Office Space F1 W2 D3 C1 L1 H1 E4
Copier Area (Non-Public Space)
F2 - - C1 L3 H1 E5 M2
Version 4.1 – January 2022 Page 9 of 40
Support Support open office spaces may be combined with the other open office spaces in other divisions.
ROOMS (STAFFING) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Field Security Manager F1 W1 D1 C1 L1 H1 E2
Attorney F1 W1 D1 C1 L1 H1 E2
Supervisory Attorney F1 W1 D1 C1 L1 H1 E2
Communications Officer F1 W1 D1 C1 L1 H1 E2
ROOMS (SUPPORT) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Computer Setup and Storage (includes IT Contractor and
IT Specialist positions) F6 W3 D3 C1 L3 H1 E16
OSI Interview Room F1 W1 D2 C1 L2 H2 E3 M1 | M7
Remote Wiring Closet F6 W6 D3 C4 L3 H9 E20 M11
LAN Room/Security Equipment/Switch Room
F6 W6 D3 C4 L3 H7 E17 M10 S6
OPEN OFFICE (STAFFING) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Mission Support Assistant F1 - - C1 L1 H1 E4
OIT Government F1 - - C1 L1 H1 E4
OIT Contractor F1 - - C1 L1 H1 E4
OSI Government F1 - - C1 L1 H1 E4
Teleworker F1 - - C1 L1 H1 E4
Paralegal F1 - - C1 L1 H1 E4
Legal Assistant F1 - - C1 L1 H1 E4
Verification Government F1 - - C1 L1 H1 E4
Verification Contractor F1 - - C1 L1 H1 E4
OPEN OFFICE (SUPPORT) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Copier Area (Non-Public Space)
F2 - - C1 L3 H1 E5 M2
Open Office Space/Circulation
(Non-Public Space)
F1 W2 D3 C1 L1 H1 E4
Version 4.1 – January 2022 Page 10 of 40
Fraud Detection and National Security Spaces Fraud Detection and National Security (FDNS) reviews applications. These spaces may be combined with other divisions.
ROOMS (STAFFING) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Supervisory FDNS Immigration Officer
F1 W1 D1 C1 L1 H1 E2
ROOMS (SUPPORT) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
FDNS Interview Room F1 W1 D2 C1 L1 H1 E2
FDNS File Room F1 | F3 W3 D4 C1 L3 H1 E6
HSDN/TALON Room F1 W5 D8 C7 L1 H5 E12
OPEN OFFICE (STAFFING) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
FDNS Immigration Officer F1 N/A N/A C1 L1 H1 E4
FDNS Assistant F1 N/A N/A C1 L1 H1 E4
FDNS Clerk F1 N/A N/A C1 L1 H1 E4
OPEN OFFICE (SUPPORT) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Open Office Space/Circulation (Non-Public Space)
F1 W2 D3 C1 L1 H1 E4 S5
Copier Area (Non-Public Space)
F2 W2 N/A C1 L3 H1 E5 M2
Version 4.1 – January 2022 Page 11 of 40
Joint Use and Office Support Spaces The Joint Use and Office Support Spaces include areas that are shared by all divisions within the office.
The public entry will include a security screening area. The security screening area, where guards will be posted, will include a walk-through metal detector and an x-ray machine.
The Break Room may be incorporated into the open office area for the USCIS divisions within the building.
A Mail Room, located near the loading dock/receiving area, will require a dedicated exhaust system, and will also include an additional x-ray machine for the screening of packages.
Remote wiring closet(s) will only be required if USCIS occupies more than one floor (one per floor that does not have LAN / Security Equipment / Phone Switch Room). Additional wiring closets are required if cabling lengths exceed 295 ft total length.
ROOMS (SUPPORT) FLOOR WALL DOOR CEILING LIGHTING HVAC EDV MISC SEC
Break Room F5 W1 D2 C1 L1 H6 E15 M7 | M8
Mail Room – Incoming / Outgoing F2 W8 D9 C1 L3 H8 E18 M12 S7 | S8
Union Office F1 W1 D1 C1 L1 H1 E2
Bulk Storage F3 W3 D9 C5 L5 H1 E9
Supply Room F1 | F3 W3 D1 C1 L3 H1 E9
Multipurpose / Training Room F1 W1 D1 C3 L2 H3 E14 M1 | M7 | M9
Chair, Table & A/V Storage F1 W2 D7 C1 L1 H1 E13
Computer Training F1 W1 D1 C3 L2 H3
Asylum Interview / Waiting Room F4 W4 D3 | D5
C2 L1 H3 E8 M5 S1
Employee Restroom (Men) F7 W7 D10 C6 L6 H1 E22 M15
Employee Restroom (Women) F7 W7 D10 C6 L6 H1 E22 M15
Employee Showers (Men and Women)
F7 W7 D10 C6 L6 H1 E22 M13
Lactation Room F1 W2 D11 C1 L1 H1 E19 M19
Family Restroom F7 W7 D10 C6 L6 H1 E22 M16
Visitor Restroom (Men) F7 W7 D10 C6 L6 H1 E22 M16
Visitor Restroom (Women) F7 W7 D10 C6 L6 H1 E22 M16
Guard Room / PIV Issuing Room F1 W2 D3 C1 L1 H1 E6
Security Queuing Space F8 W3 D3/D5 C2 L1 H3 E21 M14 S1 | S2
Security Screening Stations F8 W3 D3/D5 C2 L1 H3 E21 M14 S1 | S2
Weather Vestibule F8 W3 D3/D5 C2 L1 H3 E21 M14 S1 | S2
LAN / Security Equipment / Phone Switch Room
F6 W6 D4 C4 L3 H7 E17 M10 S6
Remote Wiring Closet F6 W6 D4 C4 L3 H9 E20 M11
Version 4.1 – January 2022 Page 12 of 40
Design General Notes
In the event a conflict exists between the GSA Request for Lease Proposal (RLP) and the USCIS Asylum Special Requirements, the more stringent shall prevail.
1. Building Classification – USCIS requires all buildings to be Class A or B, no exceptions.
Class A Definition: Most prestigious buildings competing for premier office users with rents above average for the area. Buildings have high quality standard finishes, state of the art systems, exceptional accessibility, and a definite market presence.
Class B Definition: Buildings competing for a wide range of users with rents in the average range for the area. Building finishes are fair to good for the area. Building finishes are fair to good for the area and systems are adequate, but the building does not compete with Class A at the same price.
2. Building Entrance – There shall be two separate entrances to USCIS space. One entrance for employees and one entrance for the public.
3. Direct/Indirect Light Fixtures – Light fixtures shall be LED direct/indirect and be capable of providing 30-foot candles (unless otherwise noted) of light at work surface height (30"AFF). Corridors shall be capable of providing minimum 25-foot candles. Lamp color shall be maintained at 3500K and the CRI (Color Rendition Index) must be maintained at a minimum of 80 for the term of the lease unless an alternative light color is approved by the USCIS Facilities Division (FAC).
Pricing requirements: The Lessor shall ensure that the cost of the shell lighting specified in the RLP is subtracted from the total lighting cost in the Tenant Improvement pricing.
4. Door/Frame/Sidelight A ssemblies – Typical sidelight assemblies (as required) shall be integral with the door frame. If transoms and additional glazing adjacent to the door frame are specified for daylighting, they should also be integral to the door frame and approved by (FAC) prior to being included in the project design.
Pricing requirements: Provide three pricing options to USCIS FAC for approval. Option 1: No sidelight; Option 2: Integral door frame with sidelight, Option 3: Integral door frame with sidelight and Transom.
5. Tenant Uninterrupted Power Supply (UPS) – A Tenant UPS is required and must be located prior to the building’s main distribution panel (or at least before the panels/service serving the Government's leased space). The Lessor shall be responsible for replacement of modules when a failure occurs, and the system indicates the module is defective. The Tenant UPS shall be monitored and connected to the building’s BAS system for automatic indicators for reporting and replacement. The Lessor shall be responsible for providing, installing, and maintaining this system throughout the term of the lease (including all service repairs, parts replacement, and maintenance). The UPS Shall provide minimum 4-hour battery backup for HVAC, lighting and power supporting 24/7 spaces and security equipment. Note: Intrusion Detection Systems (IDS) shall have minimum 4-hour backup in stand-by (non-alarm) and then five minutes in alarm, no exceptions. Power distribution points and emergency sources shall be separated to eliminate single point vulnerabilities.
Pricing requirements: Provide three pricing options to USCIS for approval. Option 1: 4-hour battery backup; Option 2: 2-hour battery backup, Option 3: 1-hour battery backup. Note: Intrusion Detection Systems (IDS) shall have minimum (Option 1 only) 4-hour backup in stand-by (non-alarm) and then five minutes in alarm, no exceptions. In areas where frequent and prolonged power outages occur, more time may be necessary.
6. Electronic Security System (ESS) – The Lessor shall furnish and install an operational ESS. The Lessor will maintain the systems during the one-year warranty listed to the installer which commences on the date USCIS Security accepts and signs of on Security System Testing/ Certification and Activation Completion Documentation. The Lessor shall provide testing and certification documentation certifying all ESS components are fully operational and have been tested (including transmission/connection to and from the Mega-Center). USCIS Security will sign off commencing security acceptance. The Government will own and maintain all installed equipment upon expiration of the one-year warranty. The lessor shall provide documentation annotating the latest software/firmware updates are uploaded and configured within the system no more than 30 calendar days prior to the one-year warranty turnover to the government. The ESS will comprise of an HSPD-12 Compliant Access Control System (ACS), Intrusion Detection System (IDS), and Internet Protocol Video Surveillance System (IPVSS) that will be capable of operating on an integrated standalone platform which can provide USCIS with the ability to access, monitor, administer and control of all three systems through a single client. The costs of the ESS shall be paid by the Government through the BSAC. The complete requirements for the electronic security systems are provided in the attached USCIS Facility Security Specific Requirements (FSSR) for Electronic Security Systems and the ISC Countermeasures.
Refer to paragraph 8a. below and section E17 for POTs line requirements.
7. Tenant Provided Magnetometer and X-ray Machine(s) – USCIS will provide security equipment to be located within lobby security screening and mailroom areas. The Lessor shall provide, install and the coordinate the power and data required for the tenant provided equipment.
Version 4.1 – January 2022 Page 13 of 40
8. Building Services – Demarcation (Voice/Data Requirements) – For new facilities, the lessor shall provide and install (3) – 4” inch conduits (PVC – Schedule 80 outside) with pull strings in the Main building demarcation(s) within the facility. These conduits shall connect Service Provider Utilities for copper, fiber optic, CATV, etc. at telephone pole, enclosure, etc. on the exterior building directly to the building demarcation conduits. The lessor shall coordinate with local Service Providers to identify all new locations.
For new/existing buildings: The lessor shall provide and install minimum (3) - 4” inch EMT conduits with pull string for building services to connect from the Main Building demarcations(s) extending directly to the USCIS Computer room/ LAN / Security Equipment / Phone Switch Room. Separate conduit raceways shall be utilized for copper, fiber optic, and CATV service into the facility based on circuit requests/orders submitted by USCIS. Refer to USCIS Structured Cable Plant Standard document: CMP plenum-rated or CMR riser-rated 50-pair Category 3, copper backbone cable, terminated on 110 stand-off blocks (110FT) on each end for extension of voice, data, and security circuits or analog (POTS) lines will be specified.
a. Voice circuit - copper requirement – The voice lines and circuit requirements shall meet the staffing criteria, which shall utilize copper to deliver service to the Building Demarcation on new, existing/ upgraded infrastructure for implementation that includes approximately 6-12 analog line(s) and Primary Rate Interface (PRI’s) for voice applications. Leased construction build-out per lease will require the coordination by the lessor with the local service provider to install the copper cable requirement to support the facility for USCIS voice requirement installation. NOTE: The lessor shall be responsible for shell cost for providing the required amount of analog lines which will connect to the Federal Protective Service Mega Center, USCIS LAN / Security Equipment / Phone Switch Room Environmental Alarm, the local fire alarm, life safety, and any other systems along with the monthly re-occurring costs included in the lease agreement. See Reference E17.
b. Data circuit – copper requirement – The data circuit requirement shall utilize copper to deliver service to the Facility Demarcation on new, existing, or upgraded infrastructure for implementation of one analog line, Public Switched Telephone Network (PSTN), for monitoring network. Leased construction build-out will require the coordination by the lessor with the local service provider to install the copper cable requirement to support USCIS network deployment per lease the agreement.
Two separate phone service providers (Verizon, AT&T, Comcast or other) may be required for redundancy.
c. Data circuit - fiber optic requirement – For office and staffing requirements, the data circuit type shall support bandwidth demands from 100 Megabits per second (Mbps) up to 10 Gigabit speeds or DS3, which requires that the existing fiber optic cable in the facility shall be utilized to support the network. If fiber cable does not exist within the facility or meet needed circuit requirement, coordination is required by the Lessor and the local service provider to install accordingly or upgraded infrastructure included per lease agreement for implementation with the site upgrades to support the USCIS network deployment. Note with existing buildings – The location within the facility where the building demarcation resides (telephone room, electrical closet, etc.) may require site upgrades that may include, but not limited to, the installation of electrical outlets (typically two (2) dedicated L5-15R's or requested equivalent), plywood backing, grounding to the Main Electrical Service, busbar, etc., as part of the shell requirement.
9. Cable Management: The Lessor’s IT Vendor shall be responsible for providing and installing cabling. Each cabling component type shall be separately included in a material list with pricing. Quantities shall be provided for each type. Cabling work (materials and labor) shall be warranted for the full term of the lease. Cable trays (basket and ladder) shall be installed per manufacturer’s instruction and be coordinated with mechanical ducts, sprinklers, plumbing, etc. to ensure a 12” clearance above the tray from any obstructions. The Lessor shall be responsible for providing 19” x 19” x 84”H standalone equipment racks with 10” double-sided vertical managers and patch panels for phone and data punch downs along with wire management, shelves, PDU’s, and 18”-24” ladder runway above racks in the LAN / Security Equipment / Phone Switch Room as highlighted in the USCIS Structured Cabling Plant Standard
a. Data/Voice
i. Unclassified (A-LAN)- refer to the USCIS Structured Cabling Plant Standards attached with the RLP. Each drop location shall consist of two data Category 6 white (2D) plenum cables for each office, workstation or other location indicated during the design phase to support network and voice applications. A wall phone location shall consist of one voice Category 6 white (1V) plenum cable. s. A combination of cable basket trays and J-hooks shall be used to distribute the data/voice cabling throughout the building. If quantity exceeds 100 cables, basket trays shall be identified during the design intent drawing plan review to determine pricing impact. The cost of this work shall be paid by the Government through the Tenant Improvement Allowance. Upon final cost reconciliation of the project, and itemized list of costs of the data and voice cabling shall be provided to the Government.
ii. Classified (B-LAN) is required for all HSDN/Room locations in addition to A-LAN. B-LAN shall be armored fiber optic cables which MUST be routed separately throughout the basket tray and j-hook assemblies and maintain a 5” separation from A-LAN fiber and Cat 6 cabling with no exceptions. All armored plenum fiber optic backbone cables supporting the B-LAN shall be routed through ceiling space in wire mesh, basket style tray to the designated HSDN(s) throughout the facility and will be supported by J-hooks staggered approximately within four feet (4’) on center (max. distance of 5’ spacing) upon exiting the tray system along with the 5” separation noted above.
b. Audio Visual – Lessor’s IT Vendor shall be responsible for procuring, installing, and certifying cabling.
c. Security - Lessor’s IT Vendor shall be responsible for procuring, installing, and certifying cabling.
10. Wireless & Overhead Paging Application – The lessor shall provide and install all Wireless & Overhead Paging Application infrastructure throughout the facility. Wireless and overhead paging drop locations shall be indicated on design intent documentation to ensure there is adequate coverage throughout the facility without overlapping signals and dead spots. Each location shall consist of two data Category 6 white (2D) plenum cables. Other infrastructure requirements include plenum cabling, surface boxes, ceiling or wall mounted components, patch panels, wire management, conductivity/termination hardware, patch cables, etc.
Version 4.1 – January 2022 Page 14 of 40
Pricing Requirements: Include all components, quantities, and labor costs as separate line items during design intent document phase.
Drawings and pricing will be reviewed by USCIS for compliance during the design development phase for inclusion into Construction Documents. All Wireless Access Point (WAPs) devices and Overhead Paging speakers will be provided and installed by the Government following final acceptance of the building and are NOT included as part of Tenant Improvement.
11. Electrical Circuits – Dedicated circuits will be required in copier areas, HSDN (TALON) Room, security screening lobby and in the break room. Dedicated outlets shall be a different color than the building standard. Provide dedicated outlet color options for USCIS approval during the submittal process. Further information and locations will be provided during design.
12. Standard Duplex Electrical/Data Drop Installations – Electrical outlets and data drops heights and distances between shall be installed per the industry standard unless otherwise noted.
13. Corner Guards – USCIS requires corner guards to be installed throughout the facility. Corner guards should be at least 4’-0” high and placement will be determined during design intent documents. At a minimum, they will be placed in high traffic areas. The corner guards should be stainless steel or interchangeable high-impact vinyl with aluminum retainer. Manufacturer to be InPro, Koroguard or other approved equal. Pricing requirements: Option 1 – Cost per item for stainless steel; Option 2 – Cost per item for interchangeable high impact vinyl with aluminum retainer; Option 3 – Cost per item for other recommendations by the AE. All cost options shall include labor costs.
14. Systems Furniture Electrical Circuit Configuration – USCIS utilizes systems furniture workstations in open office space. The USCIS systems furniture vendor will provide the electrical circuit configuration during the design phase. The furniture vendor will provide the necessary electrical whips, but it will be the responsibility of the Lessor’s electrical contractor to install the power/data connections. A single circuit must not serve more than 4 workstations. The lessor’s contractor shall provide a line item within the construction schedule identifying when furniture whips are required to be onsite. The design shall include the following Pricing Requirements:
a. Option 1: 8-wire feed consisting of 3 general purpose 120v circuits with 1 neutral and 1 ground wire, and one 120v isolated-ground circuit with 1 neutral and 1 isolated ground wire
b. Option 2: 8-wire feed consisting of 2 general purpose 120v circuits with 1 neutral and 1 ground wire, and two 120v isolated-ground circuit with 1 neutral and 1 isolated ground wire.
15. Architectural Wall Electrical Circuit Configuration – USCIS may consider using architectural walls (provided by a USCIS contracted vendor). The USCIS architectural wall vendor will provide the electrical circuit configuration during the design phase. If used, the lessor’s contractors shall coordinate power/data connections, lighting controls, HVAC, lighting, sprinklers, and other building systems with the USCIS architectural vendor on design intent document.
16. E-Verify – The Offeror's contractors, subcontractors, cleaning staff and other employees having access to the facility both before and post occupancy must comply with Federal Acquisition Regulation 52.222-54 Employment Eligibility Verification. Only those individuals legally authorized to work in the United States are permitted to be employed either directly or indirectly by the Offeror. Information on registration for the use of the E-Verify program can be obtained via the internet at the Department of homeland Security Web site:
http//www.usics.gov/e-verify.
17. Security Clearances –HSPD12 Compliant Access Control Systems are required in all USCIS Facilities. PIV Access will be required by all contract staff to include the lessor contract staff and his/her designees, lessor’s maintenance team and custodian/janitorial staff.
Once USCIS has taken occupancy of the space, it is required that all contractors, janitorial and lessor staff requiring routine access to the USCIS space will have completed the required NACI security background check as mandated by HSPD12 for unescorted access during normal working hours. The Government will facilitate, monitor compliance, and pay for all required NACI security backgrounds checks for the duration of the lease.
18. COVID Requirements: Lessor employees and contractors shall be in compliance with Executive Order 14042 ensuring adequate COVID safety protocols for Federal Contractors.
19. Door Hardware and Keying Control – USCIS has specific requirements for all door hardware, keying, lockset cores and the control of such. The Lessor shall review and comply with the requirements listed in this document as well as the USCIS Facility Security Specific Requirements and Annex B. The design of the keying plan and Master Key System/ hierarchy will be developed during design. The implementation and execution of the final plan will be the Lessor’s responsibility. The Lessor shall provide a minimum of (3) copies of each lockset key type. USCIS will control all keys. The Lessor is responsible for providing and installing a securable key storage box within the USCIS space for the storage and/or control of all keys. The key box shall be able to hold all USCIS required keys for the facility. USCIS shall maintain all copies of keys to the key box as well as all USCIS Facility keys. Cores shall be delivered directly to USCIS. USCIS shall install all cores onsite and include defective or malfunctioning cores to the lessor as a punch item. Key control shall be finalized as part of security acceptance. Refer to Physical Security Construction Standards for Key requirements.
20. Fire Alarm System (FAS) – The Lessor shall provide, install, and maintain a compliant FAS for any building(s) occupied by USCIS.
The FAS shall be complaint with the space’s intended use and meet all applicable NFPA while also meeting all requirements of the local authority having jurisdiction (AHJ). If the GSA lease requirements and/or the local building codes require a complaint system as part of the building shell, those costs will be included with the shell rent. In this case USCIS will only focus on what is needed for the tenant improvement (TI) fit out and its integration with the shell FAS.
21. Mass Notification System (MNS) – As part of the tenant improvements, USCIS will require the design, installation, and maintenance of a mass notification system for any space occupied by USCIS. The system and its components will be integrated with the installed
Version 4.1 – January 2022 Page 15 of 40
FAS. The system and its components shall be installed to comply with NFPA codes and all requirements of the local authority having jurisdiction. The lay-out and placement for all components will be detailed during the design development phase. At a minimum the MNS shall include eight (8) pre-recorded messages, two (2) activation panels with manual voice override and the ability to accept recorded .WAV files at a later date.
22. Cell Phone Repeaters - The Lessor shall be responsible for the installation of cell phone repeaters, also known as signal boosters, in the building(s). The repeater shall boost cell signal for any major cell phone company (AT&T, Verizon, Sprint/ T-Mobile, Motorola). The cell signal should be clear and uninterrupted to all parts of the building including basement/garage levels (if applicable). The lessor shall coordinate with local Service Providers to ensure all Major Cell Phone Company Services are included within the building.
23. Building Information Management (BIM): USCIS must consistently and accurately measure, classify, and assign its space in order to fulfill facilities throughout the country. For that reason, USCIS requires the Lessor’s A/Es to validate their own spatial program against USCIS’s program of requirements (POR) prior to the start of Design Intent Documentation. The Lessor, at its sole cost and expense, shall provide a Model using Building Information Modeling (“BIM”) supplemented with Computer Aided Design (“CAD”) content (if necessary) to produce a complete set of design and construction drawings. Refer to USCIS BIM Requirements and M3 BIM Matrix.
Environmental Considerations
The U.S. Citizenship and Immigration Services make a strong commitment to environmental stewardship. The Offeror shall comply with the following requirements which can also be found within the GSA RLP.
1. Green Globes Certification for Tenant Interiors - The Offeror shall obtain Green Globes Certification.
2. Compliances – The Offeror shall comply to the extent feasible with the Resource Conservation and Recovery Act (RCRA), Section 6002, 1976. The Offeror shall use recycled content products as indicated in the lease and as designated by the U.S. Environmental Protection Agency (EPA) in the Comprehensive Procurement Guidelines (CPG), 40 CFR Part 247, and its accompanying Recovered Materials Advisory Notice (RMAN).
3. Preferable Products – The use of environmentally preferable products and materials is encouraged in addition to the consideration of the lifecycle analysis of the product to the initial cost. Some examples may include janitorial cleaning products packaged ecologically, products and equipment considered environmentally beneficial, recycled products that are phosphate free; non-corrosive; non-flammable; fully biodegradable and paper products with recycled content conforming to EPA’s CPG.
4. Construction W aste – Prior to construction commencement, the Offeror shall submit a proposed Construction Waste Management plan following industry standard to recycle construction waste. The plan shall quantify material diversion goals and maximize the materials to be recycled and/or salvaged (at least 50 percent) from construction, demolition, and packaging debris.
5. Building Management Recycling – For leased space greater than 10,000 square feet with a term longer than six months, the Lessor shall establish a recycling program for (at a minimum) paper, corrugated cardboard, glass, plastics, and metals where local markets for recovered materials exist. An appropriately sized recycling area (2 SF per 1,000 SF of gross area) should be designed for collection and storage of recycling materials. Telecom rooms are not acceptable as recycling space.
Recycling area(s) within the building shall be included as part of the DID and CD submissions. The Government, upon request, may request additional information concerning the recycling programs.
6. Energy Star – The Lessor shall achieve Energy Star rating for new construction. USCIS shall provide Energy star information to the lessor.
7. Renewable Energy – The Lessor is encouraged to purchase at least 50 percent of the Government tenant’s electricity from renewable sources.
8. Landscaping – As required, the Lessor must provide landscape management practices which avoids or minimizes the use of fertilizer and pesticides; prohibits the use of the 2,4-Dichlorophenoxyacetic Acid (2,4-D) herbicide and organophosphates;
composted/recycled all yard waste; utilizing landscaping products with recycled content as required by EPA’s CPG for landscaping products; and for new construction, where conditions permit, the site shall be landscaped for low maintenance and water conservation with plants that are either native or well-adapted to the local growing conditions.
9. Plumbing – The Lessor must provide plumbing fixtures that conform to EPA WaterSense or fixtures with equivalent flush volumes/flow rates. The lessor shall provide, install and maintain water bottle filling stations (high efficiency refrigerated filtered electric water coolers with integrated water bottle filing station. Water bottle filling stations shall be located at the following locations:
a. (1) per each floor USCIS occupies (employee use only)
b. (1) for public use space (public use only)
Version 4.1 – January 2022 Page 16 of 40
10. Flagpoles: A ground-mounted flagpole, located preferably at the left of the entrance (facing the building), must be provided for new federal buildings. If ground-mounted poles are not feasible, a roof-mounted pole is permissible; or, if roof mounting is not suitable, an outrigger pole may be used. Only one flagpole is needed for a complex of buildings on a common site. The flag must be illuminated, and the light controlled with a seasonally adjustable time clock, photocell, or the BAS system. Flag poles shall be located far enough away to eliminate the possibility of the flag touching the building. Flag poles shall be grounded. Below are approved flagpole heights and the corresponding flag sizes.
Flagpole Height Flag Dimensions 20 ft. 3 ½ by 6 2/3 ft.
30 ft. 5 by 9 ½ ft.
40 ft. 5 by 9 ½ ft.
50 ft. 8 2/3 by 17 ft.
60 ft. 8 2/3 by 17 ft.
Finish Performance o Solid Core Wood Doors
Construction: Bonded structural composite core; AWI Premium Grade; 5-ply; Factory finish Durability: Lifetime Warranty; Manufacturer’s Warranty (Document Warranty Period) Hardware: Grade 1; Heavy duty mortise locks; solid stainless steel. Gasketing shall be provided for all sound rated door requirements Frame: Welded hollow metal, Level 3; 0.053” (1.3 mm); galvanized Security: Time Rated o Hollow Metal Doors Construction: Level 3; 0.053” (1.3mm)/untreated; Shop applied paint Durability: Extra Heavy Duty, Document Warranty period Hardware: Grade 1; Heavy duty mortise locks; solid stainless steel. Gasketing shall be provided for all sound rated door requirements Frame: Welded hollow metal, Level 3; 0.053” (1.3 mm); galvanized Security: Time Rated o Glazed Aluminum Doors Construction: 1/8” (3mm) extruded aluminum; Class I anodic or fluoropolymer paint finish Durability: Standard Manufacturer’s Warranty. Document warranty period Hardware: Center pivots, BMHA Grade 1 Frame: Welded hollow metal, Level 3; 0.053” (1.3 mm); galvanized Glazing: 1” (25mm) clear insulating laminated glass Security: Lock Set Only (at locations without security equipment). Electronically Controlled Access shall be used at all security device locations.
o All Glass Entrances
Construction: All glass with stainless steel or chrome plated top and bottom rails or patches.
Durability: 3-year Manufacturer’s Warranty. Document warranty period Hardware: Grade 1 top and bottom pivots. Concealed floor or overhead closer.
Glazing: Clear safety or decorative glass, ½” (13mm) thick.
Security: Electronically Controlled Access o Metal Stud Partitions Construction: 3-5/8” x min. 16 ga. Light gage metal framing studs @ 16” o.c., 2 layers 5/8” gypsum board, with
Greengard Gold certification, Durability: High Impact Resistance Security: Document Security Requirement Environmental: Gypsum board shall be certified as meeting the minimum performance level specified in UL 100, Standard for Sustainability for Gypsum Boards and Panels. GREENGUARD Gold certification.
o Operable Partitions
Construction: 3 Steel or MDF/vinyl, fabric, veneer, or marker board/3” (75mm) thick. Gasketed at top, bottom, and panel joints.
Operation: Continuously hinged panels, motorized o Millwork and Cabinets
Construction: Particle Board with Wood Veneer on exposed to view surfaces.
Durability: Extended Life Quality: AWI Premium grade, shop fabricated by millworker to custom sizes and configurations. Grade 1 hardware, solid stainless steel, brass, or bronze. Provide AWI QCP Labels/Certificates o Countertops
Construction: Exterior Grade Plywood with Solid Surface and Edge Durability: Extended Life Quality: AWI Premium grade o Broadloom/Carpet Tile Construction: Refer to CRI Model Specification for TARR Recommendation.
Durability (Fiber Life): Type 6 or Type 6,6 Nylon Fiber
Version 4.1 – January 2022 Page 17 of 40
Service Life: 10 Year Commercial Warranty or better. Provide copy of manufacturer’s published warranty.
Document Warranty period
Environmental: Comply with IgCC-2018 Section 901.4.1.4.3 (9.4.1.4.3) Third-Party Multi-attribute Certification – NSF/ANSI 140 for carpet. NSF 140 Gold or Cradle to Cradle Silver o Vinyl Composite Tile (VCT) Durability: VCT – ASTM F1066; Document Product Size and Thickness based on Application. Basis of Design shall describe type of backing when used, installation (glue down or loose lay), and identify required wear layer for application.
Static Load: ASTM F970 compliance, depression less than 5 mil after 24 hours. Method cites 250 psi max.
Document static load in PSI.
Maintenance: Factory Finish + Wax/Polish Applied. Document frequency and type of cleaning and disinfection.
Identify maintenance requirements as determined by Owner Project Requirements (OPR). Provide product manufacturer recommendations. Verify cleaning and disinfection chemical compatibility and efficacy.
Service Life: 5-year Warranty. Document warranty period.
Environmental: NSF/ANSI-332 Platinum and GREENGUARD Gold o Sheet Vinyl Durability: VCT – Heterogeneous Sheet Vinyl – ASTM F1303. Document product thickness and sheet width based on application Static Load: ASTM F970 compliance, depression less than 5 mil after 24 hours. Method cites 250 psi max.
Document static load in PSI.
Maintenance: Factory Finish – No Wax. Document frequency and type of cleaning and disinfection. Identify maintenance requirements as determined by Owner Project Requirements (OPR). Provide product manufacturer recommendations. Verify cleaning and disinfection chemical compatibility and efficacy.
Service Life: 5-year Warranty. Document warranty period.
Environmental: Comply with IgCC-2018 Section 901.4.1.4.3 (9.4.1.4.3) Third-Party Multi-attribute Certification.
NSF-332 Platinum and GREENGUARD Gold o Rubber Tile
Durability: VCT – Class II Laminated A&B (A=Solid Color Wear Layer; B=Mottled Wear Layer) Static Load: ASTM F970 compliance, depression less than 5 mil after 24 hours. Method cites 250 psi max.
Document static load in PSI.
Maintenance: Optional Polyurethane Layer. Document frequency and type of cleaning and disinfection. Identify maintenance requirements as determined by Owner Project Requirements (OPR). Provide product manufacturer recommendations. Verify cleaning and disinfection chemical compatibility and efficacy.
Service Life: 1) 5 Year Warranty or 2) Determined by the Owner Project Requirements (OPR) or 3) Determined by EPD (LCA) Cradle to Grave. Document number of years and warranty period.
Environmental: Comply with IgCC-2018 Section 901.4.1.4.3 (9.4.1.4.3) Third-Party Multi-attribute…
This is the start of the file's text. The full file is on GovTribe.