This document appears to be a set of mechanical drawings and specifications for the repair of Building S-11 at the NNSC (Neutral Nations Supervisory Commission) facility located at Camp Bonifas. The drawings and specifications detail the work required, which includes repairing the HVAC, plumbing, fire protection, and electrical systems for the building. Key details include the installation of new heat pump units, ductwork, domestic water heater, sprinkler system, and associated controls and accessories. The document also includes mechanical equipment schedules, control diagrams, and installation details. This appears to be a solicitation for this repair work under the Army's LCS (Local Contracting Support) MATOC (Multiple Award Task Order Contract) program, with a solicitation number of W90VN824R0039.

View the file

Other files

File Type Posted
297038-STRUCTURE_DWG.pdf PDF
297038-CIVIL_DWG.pdf PDF
297038-ARCH_DWG.pdf PDF
W90VN824R0039.pdf PDF
297038_ELEC_DWG (1).pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M-1

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

MECHANICAL MATERIAL INDICATIONS &

M E C H A N I C A L M A T E R I A L I N D I C A T I O N S & S Y M B O L S

NTS

PD

Pa

OS&Y

OXY

OD

OAIL

OA

QT

PRV

PPM

POL

POC

PLMB

PH

PG

RT

RPM

RH

RDTR

RA

R12, R22

QTY

A B B R E V I A T I O N S

SBM

SAN

SA

SCH

FLOWMETER, ORIFICEBUTTERFLY

REFRIGERANT LIQUID

CHILLED WATER SUPPLY

CHILLED WATER RETURN

AIR COOLED CONDENSING UNIT

AIR CONDITION UNIT (S)

APPARATUS DEW POINT

AIR CONDITION (-ING,-ED)

CHILLED/HOT WATER RETURN

AMERICAN WIRE GAUGE

PRESSURE, BAROMETRIC

CUBIC METER PER HOUR

CHILLED/HOT WATER SUPPLY

CAPACITYCAP

CONNECTION

CONTINUE

COMPRESSOR

CUBIC METER

CPRSR

CONN

CONT

CU M

CHILLED WATER

CAST IRON PIPE

CIRCUIT

CLASSIFICATION

COOLING LOAD

COEFFICIENT

COUNTER CLOCKWISE

CLASS

CLG LOAD

COEF

CMH

CIP

CCW

CHW

CKT

ACV ALARM CHECK VALVE

AVERAGEAVG

BOILING POINT

CENTIGRADE

BAROMETER(-TRIC)

BRAKE HORSEPOWER

BP

BHP

C

BARO PR

AWG

BARO

ALUMINUM

ALTITUDE

AMBIENT

AIR HANDLING UNIT

AMPERE(AMP, AMPS)

APPROXIMATEAPPROX

ALT

AMB

AMP

AIR COND

ADP

AL

AHU

AIR COOLED

ACCU

ACLD

ACU

CHR

C/HWR

C/HWS

CHS

RL

D DRAIN

DIAMETER, INSIDE

ISOMETRIC

IRON PIPE SIZE

JOULE

THERMAL CONDUCTIVITY

KILOGRAM

KILOGRAM PER SQ. CENTIMETER (GAUGE)

KILOGRAM PER SQ. CENTIMETER

KILOGRAM PER SQ. CENTIMETER (ABSOLUTE)

KILOCALORIE PER HOUR

EXPANSION JOINT

EXPLOSION PROOF

FIRE HOSE CABINET

FULL LOAD AMPERES

ENTERING WATER TEMP

EVAPORAT (-E,-ING,-ED,-OR)

EXTERNAL STATIC PRESSURE

FACE AREA OR FRESH AIRFA

FHC

FHY

FLA

FIRE HYDRANT

ESP

EXPJT

EWT

EVAP

EP

EQPT

ENT

EFF

EQUIPMENT

ENTERING

EFFICIENCY

KG/SQ CM

KG/SQ CM A

KG/SQ CM G

KG

KCAL/HR

J

K

ID

ISO

IPS

NO

N.O.

NIC

NPT

MPS

NC

N/A

N.C.

MAX

MIN

MPH

MM

NOT IN CONTRACT

NATIONAL TAPER PIPE (THREAD)

NUMBER

NORMALLY OPEN

MINIMUM OR MINUTE

METERS PER HOUR

METERS PER SECOND

NORMALLY CLOSED

NOISE CRITERIA

NOT APPLICABLE

MAXIMUM

MILLIMETER R

FEMALE PIPE THREAD

FUEL OIL

GALVANIZED STEEL

GAGE OR GAUGE

FIXTURE

FEED WATER PUMP

FACE VELOCITY

FLUSH VALVE

FREQUENCY

FIBERGLASS REINFORCED PLASTIC

HORIZONTAL

HOT WATER HEATER

HOT WATER

HOUR(S)

HORSEPOWER

MERCURY

HEAD

HOSE BIBB

HERTZ

GRAMS

FRPCWP CIRCULATING WATER PUMP

DIRECT EXPANSION

DRY PIPE VALVE

EQUIVALENT DIRECT RADIATION

ENTERING AIR TEMPERATURE

DOUBLE POLE DOUBLE THROW

DEWPOINT TEMPERATURE

DRY BULB TEMPERATURE

DECIBEL OR DRY BULB

DIESEL OILDO

ECON

ECC

EAT

EDR

DX

DPV

DPDT

DPT

ECONOMIZER

ECCENTRIC

o

DEG or °

DIFF

DIAG

DIA or

DIV

DBT

DB

DIFFERENCE

DIAGRAM

DIAMETER

DIVISION

DEGREE

HR

HORIZ

HWH

HW

HZ

HP

HG

HD

HB

GALVS

GA

GR

FXTR

FWP

FVEL

FV

CUBIC MILLIMETER

CLOCKWISE OR COLD WATER

COEFFICIENT, VALVE FLOWCv

CU MM

CW

PLUG VALVE

THREE WAY

FPT

FO

FREQ

GATE, ANGLE

GATE, GLOBE

GLOBE

GATE

CONTROL

KJ KILOJOULE

LH

LT

LWT

LPS

M

LL

LPD

LPH

LM

LAV

LAT

LBS

LG

KW

KWH

L

LATENT HEAT

LEAVING WATER TEMPERATURE

LITERS PER HOUR

LITERS PER SECOND

LAUNDRY TRAY

METERS

LIQUID LINE

LITERS PER DAY

LINEAR METER

LEAVING AIR TEMPERATURE

LAVATORY

POUNDS

LENGTH

KILOWATT

KILOWATT HOUR

LITERS

P

FLOWMETER, VENTURI

FLOW SWITCH

PRESSURE SWITCH

PRESSURE GAUGE AND COCK

PUMP (INDICATE USE)

STRAINER

STRAINER, BLOW OFF

KG/SM

KG/SM A

KG/SM G

PS

P

OFM

FS

VFM

KILOGRAM PER SQ. METER

KILOGRAM PER SQ. METER (ABSOLUTE)

KILOGRAM PER SQ. METER (GAUGE)

JACKET WATER RETURN

MEDIUM PRESSURE STEAM

MEDIUM PRESSURE CONDENSATE

LOW PRESSURE STEAM

LOW PRESSURE CONDENSATE

BOILER BLOW DOWN

PUMPED CONDENSATE

JACKET WATER SUPPLY

VACUUM PUMP DISCHARGE

FUEL OIL TANK VENT

CONDENSATE WATER SUPPLY

CONDENSATE WATER RETURN

MEDIUM TEMPERATURE HOT WATER SUPPLY

MEDIUM TEMPERATURE HOT WATER RETURN

LOW TEMPERATURE HOT WATER SUPPLY

LOW TEMPERATURE HOT WATER RETURN

PIPE TO BE REMOVED

REFRIGERANT DISCHARGE

REFRIGERANT SUCTION

LPS

CONTROL AIR MAIN

air conditioning and refrigeration

RD

RS

(NAME)E

(NAME)

M

EXISTING PIPE

COMPRESSED AIR

VACUUM (AIR)

HWR

VAC

A

MTWS

MTWR

HWS

FOD FUEL OIL DRAIN

FOR

CS

CR

FOV

FOG

FOS FUEL OIL SUPPLY

FUEL OIL RETURN

FUEL OIL GAUGE

PC

VPD

MU

LPC

BBD

MAKE UP WATER

MPS

MPC

JWR

JWS

heating

PIPING

CHECK, SWINGSANITARY DRAIN

PITCH OR PIPE, UP(U), DOWN(D)

FLOOR SINK (200mm x 200mm)

PIPE SLEEVE WITH FIRE STOPPING

VENT THRU ROOF

BFP

60°C

82°C valves : (for selective actuators)

PLAN

HOT WATER (82°C)

HOSE BIBB

AIR LINEA

BALL

ELEV.

HOT WATER (60°C)

BACKFLOW PREVENTER

PIPE SLEEVE

(NAME)

ACID

200mm x 200mm

SURFACE CLEANOUT

FLOOR CLEANOUT

FLOOR DRAIN

CHEMICAL SUPPLY PIPES

FUNNEL DRAIN, OPEN

FCO

FD

SCO

FLOOR OR GRADE

FLOOR OR GRADE

CONDENSATE DRAIN BELOW

CONDENSATE DRAIN ABOVE

ACID WASTE

GASG

CD

CD

AIR VENT, MANUAL

AIR VENT, AUTOMATIC

W/ MEASURING TAP

EXPANSION LOOP

EXPANSION JOINT

BALL JOINT

ANCHOR, MAIN

ANCHOR, INTERMEDIATE

ALIGNMENT GUIDE

AIR SEPARATOR

FLEXIBLE CONNECTOR

SQUARE HEAD BALANCING COCK

EJ

S

MV

AVV

CHECK, NON-SLAM

CONTROL, ELECTRIC-PNEUMATIC

CONTROL, PNEUMATIC-ELECTRIC

QUICK OPENING

PRESSURE REDUCING

NEEDLE

LOCK SHIELD

HOSE END DRAIN

SAFETY

RELIEF

SQUARE HEAD BALANCING COCK

QUICK CLOSING, FUSIBLE LINK

R

S

PE

EP

plumbing

COLD WATER

HOT WATER RETURN

HOT WATER SUPPLY

VENT

MOTOR ELECTRIC

DIAPHRAGM

valves, special duty :

SOLENOIDS

valve actuators

M

FDAD

SUCTIONQUANTITY SUCT

TONS OF REFRIGERATION

TEMPERATURE DIFFERENCE

HEAT TRANSFER COEFFICIENT

SANITARY

SUBMERSIBLE

SUPPLY AIR

SCHEDULE

RADIATOR

REFRIGERATION TON

REVOLUTIONS PER MINUTE

RELATIVE HUMIDITY

RETURN AIR

THERMAL RESISTANCE

REFRIGERANT (12, 22, ETC)

TYPICALTYP

URINAL

UNIT HEATER

UR

UH

U

THERMOSTAT

THICKNESS

THERMOMETER

TEMPERATURE

SYMBOL

TSTAT

TONS

THERM

THK

TEMP

TD

SYM

SINGLE POLE DOUBLE THROW

LPH, STANDARD CONDITIONS

LPS, STANDARD CONDITIONS

LPD, STANDARD CONDITIONS

SAYBOLT SECONDS UNIVERSAL

SAYBOLT SECONDS FUROL

SENSIBLE HEATOUTSIDE AIR INTAKE LOUVER SH

PRESSURE DROP OR DIFFERENCE

PRESSURE REDUCING VALVE

PHASE (ELECTRIC)

PERCENT

PARTS PER MILLION

POINT OF CONNECTION

PLUMBING

PETROLEUM, OIL AND LUBRICANTS

QUART

OUTSIDE SCREW & YOKE

DIAMETER, OUTSIDE

PRESSURE GAGE

POLE

PASCAL

OXYGEN

SPRINKLERSPR

STEEL

STANDARD

STEAM

SQUARE

STAINLESS STEEL

STORAGESTOR

STL

STD

ST

SSU

SST

SSF

SQ

SENSIBLE LOAD

STATIC PRESSURE

SQUARE METER

SPECIFICATION

SPDT

SPEC

SM

SP

SLPH

SLPS

SLPD

SL

ALARM CHECK VALVE

SIDEWALL SPRINKLER

PENDENT SPRINKLER

UPRIGHT SPRINKLER

FIRE DEPARTMENT CONNECTION

PRE-ACTION VALVE

NOT TO SCALE

OUTSIDE AIR

(2-WAY SHOWN)

DRY-PIPE VALVE

SECOND

SAFETY FACTOR

SPECIFIC GRAVITYSG

SF

SEC

VARIABLE AIR VOLUMEVAV

VENTILATION

PRESSURE, DYNAMIC(VELOCITY)

WATER-COOLED

WATER CLOSET

WATTHOUR OR WATER HEATER

WET BULB TEMPERATURE

WATERPROOF

WSHR

WCLD

WTRPRF

WH

WT

W/

WD

WC

WBT

WEIGHT

WITH

WASHER

WIDTH

VP

VOL

WB

W

VISC

VERT

VENT

VEL

VOLUME

WET BULB

WATT

VISCOSITY

VERTICAL

VELOCITY

MANUAL VOLUME DAMPER

SMOKE DAMPER (PROVIDE ACCESS DOOR)

PNEUMATIC OPERATED DAMPER

VLV

V

VAC

M

VALVE

VOLT

VACUUM

SPLITTER DAMPER

SD

AD

VD

grilles, registers and diffusers :

SG

SR

600/300

300x150

200mm NCD

FIGURE IS ON TOP

810mm x 400mm dampers

ELBOW, TURNED DOWN

REDUCER, CONCENTRIC

REDUCER, ECCENTRIC (STRAIGHT, INVERT)

REDUCER, ECCENTRIC (STRAIGHT, DOWN)

TEE, OUTLET DOWN

TEE, SINGLE SWEEP

sprinkler

UNION, SCREWED

UNION, FLANGED

TEE, OUTLET UP

TEE

LATERAL

CONNECTION, BOTTOM

CONNECTION, TOP

ELBOW, TURNED UP

BUSHING

ELBOW, 45°

ELBOW, 90°

CAP

WELDED

FLANGED

SOLDERED

SCREWED BELL AND SPIGOT

SOLVENT CEMENT

SOUND ATTENUATOR

DETECTORS, FIRE AND/OR SMOKE

ELECTRIC MOTOR OPERATED DAMPER

FIRE DAMPER (PROVIDE ACCESS DOOR)

BACKDRAFT DAMPER

BDD

S

TRANSITION

TURNING VANES

SF

CHANGE OF ELEVATION, RISE(R), DOWN(D)

DUCT SECTION, NEGATIVE PRESS., FIRST

ACCESS DOOR, VERTICAL OR HORIZONTAL

COWL, (GOOSENECK) AND FLASHING

ACOUSTICAL LINING

FLEXIBLE DUCT

FLEXIBLE CONNECTIONFC

FIGURE IS ON TOP

R

AD

47.2

TG

94.4

UC 13mm

DG

500/300L

DUCT WORK

810mm x 400mm

810mm x 400mm

THERMOSTAT, ELECTRIC

TRAP, ELECTRIC (INDICATE TYPE)

fitting :

R

THERMOMETER

EXHAUST AIR GRILLE OR REGISTER, CEILING

DUCT SECTION, POSITIVE PRESS., FIRST

DIRECTION OF FLOW

SR

DIFFUSER, LINEAR

RETURN AIR GRILLE OR REGISTER, CEILING

CEILING DIFFUSER, SQUARE TYPE

CEILING DIFFUSER, ROUND TYPE (200mm

(600mm x 300mmH, 472 LPS)

UNDERCUT DOOR (13mm, 47.2 LPS)

DOOR GRILLE (300mmx150mmH)

NECK DIAMETER)

TRANSFER GRILLE ASSEMBLY

LOUVER, DOOR OR WALL

(500mmWx300mmH, 94.4 LPS)

RG

RR

SUPPLY AIR GRILLE OR REGISTER, SIDEWALL

EXHAUST AIR GRILLE OR REGISTER, CEILING

SUPPLY AIR GRILLE OR REGISTER, CEILING

ER

SG

EG

EXISTING WORK TO BE REMOVED.

POINT OF CONNECTION NEW TO EXISTING

OR END OF DEMOLITION WORK

EXISTING WORK TO REMAIN.(E)

REMOVE EXIST WORK.(R)

1 5

SYMBOLS AND ABBREVIATIONS

REPAIR BUILDING S-11

NNSCCHONG, ST

297038

M-2

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

MECHANICAL GENERAL NOTES

EQUIPMENT PAD SIZE, INSTALLATION LOCATIONS, AND ADDITIONAL ITEMS.

10. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE CLEARANCE, COMMENCING ANY CONSTRUCTION OR RENOVATION.

9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITION AND DIMENSIONS PRIOR TO

8. ALL VALVES ON WET PIPE SYSTEM SHALL MEET NFPA 13 REQUIREMENT.

7. INSATLL SYSTEM TEST CONNECTION ON WET PIPE SYSTEM AND SHALL BE LOCATED AT THE MOST REMOTE BRANCH LINE.

6. SPRINKLERS WITH O-RINGS ARE NOT PERMITTED. PLUG TYPE TAMPER SWITCH SHALL NOT BE USED.

TO ALL RISER AND TRIM, SECTIONAL VALVES, INSPECTIORS TEST VALVES AND DRAINS.

5. PROVIDE LABEL TAG INDICATING "NORMALLY OPEN" OR "NORMALLY CLOSED" ON ALL VALVES INCLUDING AND NOT LIMITED

FLEXIBLE COUPLINGS, CLEARANCES, AND SEPARATION ASSEMBLES.

PIPING AGAINST DAMAGE WHERE SUBJECT TO EARTHQUAKES". INCLUDING, BUT NOT LIMITED TO, SWAY BRACINGS,

4. PROVIDE ALL SEISMIC PROTECTION MEASURES FOR THE FIRE PROTECTION SYSTEM IAW NFPA 13 FOR "PROTECTION OF

PIPES LESS THAN 50MM (2 INCHES) IN NOMINAL.

OF FLUID CARRIED AND DIRECTION OF FLOW. LABELS ARE NOT REQUIRED ON SPRINKLER SYSTEM BRANCH LINES AND

CONFORMING TO ASME/ANSI A13,1-1996 "SCHEME FOR IDENTIFICATION OF PIPING SYSTEMS", INDICATING THE TYPE

3. MARK ALL EXPOSED INTERIOR PIPING AT 8 METER(26 FT) INTERVALS, WITH PLASTIC WRAPAROUND TYPE PIPE LABLES

2. THE CLEARANCES AROUND PIPE PENETRATION AT FIRE RATED WALLS AND/OR FLOOR SHALL BE PROPERLY SEALED

WITH APPROVED FIRE STOPPING MATERIAL IAW SPECIFICATION 07 84 00.

11. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO EXISTING AREAS CAUSED

NO ADDITIONAL COST TO THE GOVERNMENT, INCLUDING, BUT NOT NECESSARILY LIMITED TO ITEMS SUCH AS WALLS, CEILLING, ROOF, PIPE, DUCT, EQUIPMENT AND ELECTRICAL ITEMS.

12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND REINSTALLATION OF ALL OBSTRUCTIONS AS NECESSARY

TO NECESSARY TO ALLOW FOR INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE PROTECTION SYSTEM AT

19. PROVIDE ACCESS PANELS TO ALL CONCEALED VALVES, DAMPERS, AND EQUIPMENT. PROVIDE ACCESS DOORS

IN DUCTS AT ALL AUTOMATIC CONTROL DAMPERS, FIRE DAMPERS, FIRE/SMOKE DAMPERS, DUCT SMOKE DETECTOR, BACKDRAFT DAMPERS AND FOR ANY ITEM INDISE DUCTS REQUIRING SERVICING OR INSPECTION 12"X12" ACCESS

PANELS FOR TWO VALVES. COORDINATE THE LOCATION OF ACCESS PANEL TO INSURE THAT THE EQUIPMENT

CAN BE MAINTAINED ADEQUATELY. PROVIDE REMOTELY ACTUATED DAMPERS IN AREA WITH GYPBOARD OR

CONCEALED CEILINGS.

20. INSTALL CONDENSATE DRAINS AT A MINIMUM SLOPE OF 1 / 4INCH PER 1FOOT. INSULATE ALL SEWER PIPING

RECEIVING AIR CONDITIONING CONDENSATE DRAINS, OR ANY OTHER COLD LIQUID WHICH MAY CREATE

CONDENSATION, FROM SINK BODIES EXPOSED TO AIR BELOW THE FLOOR.

21. PROVIDE TURNING VANES IN ALL ELBOWS THAT CHANGE AIR DIRECTION MORE THAN 30 DEGREES OR

USE RADIUS ELBOWS. PROVIDE AIR SPLITTER DAMPERS AT ALL BRANCH TAKE-OFFS FROM THE MAIN DUCT.

PROVIDE SPIN-IN TYPE FITTINGS AT ALL ROUND DUCT TAKE-OFFS FROM SQUARE OR RECTANGULAR MAINS.

22. PIPING SYSTEM SHALL BE FLUSHED, PURGED & CLEANED PER SPECS REQUIREMENTS AND FLUSHED UNTIL

ALL WATER BEING FLUSHED IS CLEAR AS TAP WATER.

23. ALL CONDENSATE DRAINS FROM COOLING UNIT (AS NOTED ON THE DRAWINGS) SHALL BE PROVIDED WITH

SHUT-OFF VALVE WITHIN 1M OF THE UNIT.

24. DISPOSAL OF CONSTRUCTION DEBRIS, WASTE MATERIALS, MATERIALS RESULTING FROM DEMOLITION ACTIVITIES,

1. THE EQUIPMENT SHOWN ON THE PLAN ARE SUGGESTED LOCATIONS. FINAL LAUOUT SHALL BE VERIFIED AND

IN ACCORDANCE WITH APPLICABLE CODES, MANUFACTURER'S RECOMMENDATIONS, AND EQUIPMENT LISTINGS.

THE CONTRACTOR SHALL COORDINATE SPRINKLER HEADS LOCATIONS WITH, LIGHTING FIXTURES, AND HVAC DEVICES.

ALL EQUIPMENT SHALL BE UL LISTED AND/OR FM APPROVED IN ACCORDANCE WITH NFPA 13, NFPA 20 AND THE PROJECT

SPECIFICATION.

BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS AT HIS OWN COST.

13. CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE ANY EXISTING EQUIPMENT

DUCT WORK, PIPING ETC. DAMAGED DUE TO THE WORK PERFORMED UNDER THIS CONTRACT SHALL

BE REPAIRED OR REPLACED BY THIS CONTRACTOR AT HIS OWN COST.

14. CONTRACTOR SHALL SUBMIT MANUFACTURERS INSTALLATION SHOP DRAWINGS FOR APPROVAL BY THE

CONTRACTING OFFICER.

AND THE LIKE SHALL BE DONE BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE GOVERNMENT.

15. FOR O & MA PROJECTS, KOREA, OCTOBER 1, 2003 DEPARTMENT OF THE ARMY FORM AS A PART OF THIS PROJECT.

THE DETAILS SHALL BE UTILIZED WHILE PERFORMING THE MECHANICAL SCOPE OF WORK.

16. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT FIELD CONDITIONS. SUCH DETAILS

SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS AND

SUBMITTED TO THE CONTRACTING OFFICER FOR APPROVAL.

17. ALL MECHANICAL SYSTEMS SHALL BE TESTED, ADJUSTED AND BALANCED BY THE CONTRACTOR IN STRICT

ACCORDANCE WITH APPLICABLE SECTIONS OF DIVISION 22 & 23 - MECHANICAL, O & MA STANDARD TECHNICAL

SPECIFICATIONS FOR MISCELLANEOUS PROJECTS, KOREA. THE HVAC TESTING, ADJUSTING AND BALANCING (TAB)

REPORT SHALL BE SUBMITTED TO THE PROJECT COR FOR GOVERNMENT REVIEW AND APPROVAL.

18. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING TO SMACNA STATIC

PRESSURE CALSS 500PA AND DUCTWORK SHALL MEET THE REQUIREMENTS OF SEAL CLASS C.

SCOPE OF WORK

WORK CLASS "K" (REPAIR / MAINTENANCE WORK)

BY A LICENSED OR CERTIFIED INSTALLER.

8. INSTALLATION OF THE HVAC SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S SPECIFICATION

7. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED PER SPEC.

CONDUITS AND ALL NECESSARY ACCESSORIES FOR H.V.A.C CONTROLS.

6. THE MECHANICAL/CONTROLS CONTRACTOR SHALL PROVIDE ALL THE WIRINGS, RELAYS, CONTROLLERS, PROVIDE REMOTELY ACTUATED DAMPERS IN AREAS WITH GYPBOARD OR CONCEALED CEILINGS.

5. PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE DRAWINGS OR NOT.

UL LISTED.

DAMPER RATINGS SHALL BE COMPATIBLE WITH THE FIRE WALL OR FLOOR. FIRE DAMPERS SHALL BE

4. PROVIDE FIRE DAMPERS AT ALL DUCT PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS. FIRE

TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES.

3. PROVIDE DIFFUSERS AND GRILLE FRAMES COMPATIBLE WITH ARCHITECTURAL CEILING TYPES. REFER

THE CONTRACTING OFFICER.

2. THE CONTRACTOR SHALL SUBMIT MECHANICAL SYSTEM INSTALLATION SHOP DRAWINGS FOR APPROVAL BY

CLEARANCE, INSTALLATION LOCATIONS, AND ADDITIONAL ITEMS.

1. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE

NOTE :

AND NOTE

GENERAL NOTES, SCOPE OF WORK

REPAIR BUILDING S-11

TEST SHALL BE PERFORMED BY THE FPE(FIRE PROTECTION PROFESSINONAL ENGINEER)

6. THE CONTRACTOR SHALL INSPECT AND TEST THE FIRE PROTECTION SYSTEM. THE WORK INSPECTOPN AND

SPARE SPRINKLER HEAD CABINET WITH SPARE SPRINKLER HEAD AS SHOWN ON DRAWINGS.

5. REPAIR THE SPRINKLER SYSTEM BY INSTALLING NEW AUTOMATIC FIRE PROTECTION WET SPRINKLER SYSTEM, AND ALL ASSOCIATED ACCESSORIES AS SHOWN ON DRAWINGS.

HOT WATER HEATER, VALVES, WATER HAMMER ARRESTERS, CONC PAD, CONTROL, ACCESS DOORS, INSULATION, SEWER AND VENT PIPING SYSTEM INCLUDING PLUMBING FIXTURES, ELECTRIC DOMESTIC

4. REPAIR THE PLUMBING SYSTEM BY INSTALLING NEW DOMESTIC COLD AND HOT WATER PIPING SYSTEM, CONSTRUCTION TO VERIFY THAT THE HVAC SYSTEM WORKS PROPERLY.

3. PERFORM DALT(DUCT AIR LEAKAGE TEST) AND T.A.B(TESTING, ADJUSTING, AND BALANCING) AFTER

AND ALL ASSOCIATED ACCESSORIES FOR VENTILATION SYSTEM AS SHOWN ON DRAWINGS

INSULATIONS, HVAC EMERGENCY SHUTDOWM SWITCH, ACCESS DOORS, EQUIPMENT SUPPORT,

EXHAUST FANS, RANGE HOODS, CONTROLS, DIFFUSERS, GRILLES, LOUVERS, DAMPERS, DUCTS,

2. REPAIR THE VENTILATION SYSTEM BY INSTALLING NEW ENERGY RECOVERY VENTILATION UNIT, ALL ASSOCIATED ACCESSORIES FOR HVAC SYSTEM AS SHOWN ON DRAWINGS.

AIR INTAKE LOUVED DAMPER, ACCESS DOORS, EQUIPMENT SUPPORT (CONC. PAD) AND

ELEC. UNIT HEATER, VALVES, INSULATIONS, CONTROLS, MOTORIZED OUTSIDE

SPLIT AIR CONDITIONING, HVAC PIPING(COPPER), ELEC. WALL HEATER, CONC PAD

1. REPAIR THE HEATING AND COOLING SYSTEM BY INSTALLING NEW HEAT PUMP UNIT SYSTEM, M-3

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

M E C H A N I C A L E Q U I P M E N T S C H E D U L E - 1

MECHANICAL EQUIPMENT SCHEDULE - 1

MECHANICAL

3 SIMILAR TO LG MULTI V S MODEL ARUN060GSS4 OR APPROVED EQUAL.

64,00060,000

REFRIGERANT

TYPE

R-410A

HEATING CAPACITY SHALL BE BASED ON 8 DEG C

HEAT PUMP UNIT MULTI V S HEAT PUMP1

T Y P EITEM NO SERVICE

HEATING CAP.

(BTU/H)

QTY.

OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT

OHPU

ALL HEAT PUMP UNITS REFRIGERANT PIPING SHALL BE INSTALLED AS PER MANUFACTURER RECOMMENDATIONS. COOLING CAPACITY SHALL BE BASED ON 35 DEG C21NOTES :

(BTU/H)

COOLING CAP. COMPRESSOR

HERMETICALLY SCROLL

TYPE

ELECTRICAL

MOP(A) MCA(A)

40 25.4

QTY

FAN

TYPE

AXIAL FLOW

QTY

VOLT/PH/HZ

208/ 1/ 60

AS PER MANUFACTURER RECOMMENDATIONS.

TYPE

REFRIGERANT

HEATING CAPACITY SHALL BE BASED ON 8 DEG C

COOLING CAP.

(BTU/H)

NOTES : 1 2 COOLING CAPACITY SHALL BE BASED ON 35 DEG CALL HEAT PUMP UNITS REFRIGERANT PIPING SHALL BE INSTALLED

HPU

INDOOR SPLIT SYSTEM HEAT PUMP UNIT

QTY. REMARKS

POWER INPUT

(W)

VOLT/PH/HZ

(BTU/H)

HEATING CAP. CFM

SERVICEITEM NO T Y P E

1 2

(H/M/L)

10,9009,600 40 208/ 1/ 60325/304/290 R-410A1-WAY CEILING CASSETTE TYPE

3 SIMILAR TO LG MULTIV MODEL ARNU093TUD4 OR APPROVED EQUAL.

BED ROOM

3YESRS WARRENTY

ELECTRICAL DATA

MCA MOP

0.23 15

31 2 4

3YESRS WARRENTY

HPU

21,50019,100 79 208/ 1/ 60735/653/556 R-410A4-WAY CEILING CASSETTE TYPE1 LIVING ROOM 2.09 15

5 SIMILAR TO LG MULTIV MODEL ARNU243TAA4 OR APPROVED EQUAL.

41 2 6

FACTORY

CHARGE(lbs)

7.7

HPU

4 SIMILAR TO LG MULTIV MODEL ARNU183TAA4 OR APPROVED EQUAL.

INDOORUNIT CONDENSATION PREVENTION KIT6

5127,30024,200 199 208/ 1/ 60813/742/670 R-410A4-WAY CEILING CASSETTE TYPEOFFICE 2.09 15 2 6 7

SPLIT AIR CONDITIONING

ITEM NO

SAC

QTY. SERVICE

NOTES : CAPACITY SHALL BE BASED ON 35DEG C

ALL AC UNIT REFRIGERANT PIPING SHALL BE INSTALLED PERMANUFACTURER RECOMMENDATIONS.3

T Y P E

PACKAGED SPLIT AIR CONDITIONING TYPE

WALL MOUNTED

COOLING CAP

(W)

3,000 960

(W)

POWER INPUT VOLT/PH/HZ

220/1/60 15A

(A)

MOP REFRIGERANT

TYPE

R-410A 1 2 3 4

REMARKS

WALL MOUNTED DUCT FREE SPLIT COOLING SYSTEM WITH REMOTE ELECTRONIC CONTROLLER.

LG ELECTRINICES MODEL "NO. SW07BAJWAS OR APPROVED EQUAL.4

ERV

T Y P EQTY.ITEM NO

ENERGY RECOVERY VENTILATION UNIT

HORIZONTAL

CAPACITY

(CFM)

POWER INPUT

(W)

SOUND

PRESSURE

dB(A)

ELECTRIC RATING REMARKS

REFERED TO "LG"MODEL NO. LZ-H354GBS OR APPROVED EQUAL206/206/123 176/168/81 36/31/27 220V/60Hz/1PH

COMM RM(105)1

REPAIR BUILDING S-11

M-4

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

M E C H A N I C A L E Q U I P M E N T S C H E D U L E - 2

MECHANICAL EQUIPMENT SCHEDULE - 2

MECHANICAL

ITEM NO Q'TY

FANS

SERVICE TYPE

AIR CAP

(CFM)

ESP

RPM

FAN MOTOR

VOLT/PH/HZ

R E M A R K S

1 321

BIRD SCREEN3W/BACKDRAFT DAMPER W/DISCONNECT SWITCH21 CEILING GRILLE4

FOR MECH RM. 115/1/60

WALL MOUNTED TYPE,

DIRECT DRIVEN, CENTRIFUGAL FAN1

EF

BHP

0.17

ELEC. UNIT HEATER

Q'TYITEM NO TYPESERVICE

HEATING ELEMENT CAP

POWER(KW) VOLT/PH/HZ AIR CAP.(LPS)

FAN CAPACITY

RPM HP VOLT/PH/HZ

REMARKS

AND UNIT MTD. THERMOSTAT.

PROVIDE UNIT MOUNTED DISCONNECT SWITCH208/1/601/1001,600165.2208/1/602

DISCHARGE TYPE

HORIZONTAL1 MECH/ELEC RM(111)

120/1/60

LIGHTING(75W)WASHABLE FILTER1 2 BUILT-IN CONTROL SWITCH3

RANGE HOOD

Q'TYITEM NO

FAN MOTORFAN

CAPACITY

(CFM)

TYPESERVICE

2.0AMPS 1

VOLT/PH/HZPOWER

HOOD SIZE

32 & 4

REMARKS

EUH

RH

(MM)

750Lx440WKITCHEN(103)

1 321FOR BATH RM. 115/1/60

EF

0.031,400

CEILING MOUNTED TYPE,

DIRECT DRIVEN 164

62Pa

62Pa 4

PROVIDE UNIT MTD. DISCONNECT

(AMPS)

WALL MTD TYPE

12.5

AMPERAGE

(WATTS)

REMARKS

VOLT/PH/HZ

TOTAL

1,500 120/ 1/ 60

ELEMENT CAPACITY

HEAVY DUTY, RECESSED

T Y P ESERVICEQTYITEM NO

ELECTRIC WALL HEATER

SWITCH.

EH

BATH RM (106)

ELECTRIC TYPEWATER SYSTEM

DOMESTIC HOT

ELEMENT CAPACITY

REMARKSTYPEITEM NO SERVICE

Q'TY VOLT/PH/HZ

4.5 208/1/60 43.3

ELECTRIC HOT WATER HEATER

CAPACITY TEMP. (DEG C)

SUPPLY WATER

(GALS)

STORAGE

CAPACITY

EWH

STAINLESS STEEL

HOOD VENTED TYPE

W/BACKDRAFT DAMPER

RECOVERY

UPPER

(KW)

4.5

LOWER

(KW)

(GPH)

350 987

REPAIR BUILDING S-11

M-5

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

EXISTING AND REMOVAL MECHANICAL PLAN

- M5

1 EXISTING AND REMOVAL MECHANICAL PLAN

NOT TO SCALE

INSULATIONS, CONTROL WORK, EQUIPMENT SUPPORT AND ALL ASSOCIATED ACCESSORIES.

AND HOT WATER PIPING SYSTEM, SEWER AND VENT PIPING SYSTEM, PLUMBING FIXTURES,

VALVES, DAMPERS, RANGE HOODS, ELECTRIC DOMESTIC HOT WATER HEATER, DOMESTIC COLD

PUMPS, EXHAUST FANS, AIR CONDITIONING UNIT, CONC. PAD, LOUVERS, DIFFUSERS, GRILLES, REMOVE EXISTING DETERIORATEDWATER WARM AIR FURANCE, DUCT, HVAC PIPING, REPAIR BUILDING S-11

NNSCCHONG, ST

TURN-IN TO SUPPLY DIV. TURN-IN TO SUPPLY DIV.

M-6

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

1.

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION

2.

M6- SCALE : 1 / 50

OF HVAC PIPING IN FIELD(TYP)

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HVAC PIPING SYSTEM.

1.

SPECIFIC NOTE:

ALL HVAC PIPE LINES SHALL BE COPPER TUBE.

NOTE ON INSTALLATION OF PIPE INSULATION :

THE PIPE INSULATION IS COMPLETED.

FOR QUALITY INSPECTION WHEN THE INSTALLATION OF

4. THE CONTRACTOR SHALL INVITE THE MECH. ENGINEER

ASTM E84.

INDEX OF 50 WHEN TESTED IN ACCORDANCE WITH

SPREAD INDEX OF 25 AND A MAXIMUM SMOKE DEVELOPED

FIRERESISTANT AND SHALL HAVE A MAXIMUM FLAME

3. LAGGING ADHESIVES SHALL BE NONFLAMMABLE AND

LISTED IN FM APP GUIDE.

2. INSULATION MATERIALS RECOGNIZED UNDER UL94 AND

C534/C534M, GRADE 1, TYPE I OR II.

OMA SPEC 23 07 00, AND SHALL COMPLY WITH ASTM

1. INSULATION MATERIALS SHALL CONFORM TO TABLE1 OF

BED ROOM

REF

ROOM

MECH/ELEC

FEC

T

HPU

HPU

T

(TYP)

THERMOSTAT COVER

HPU

T

NEW CONC. PAD

OHPU

METAL PIPE TRAY(TYP)

PIPE CHASE(TYP.)

NEW HVAC PIPING PLAN

EUH

EH

SAC

INSULATION, NOTES AND SPECIFIC NOTE

NOTE ON INSTALLATION OF PIPE

NEW HVAC PIPING FLOOR PLAN,

BED ROOM

BATH

LINEN

REF

KITCHEN

COMM RM

PANTRY

STOR

ROOM

MECH/ELEC

OFFICE

FEC

110 111

CLOSET-2CLOSET-1

LIVING ROOM

CONC. PAD

NEW

REPAIR BUILDING S-11

M-7

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

M7- SCALE : 1 / 50

HORIZONTAL FACE BARS.

DOUBLE DEFLECTION REGISTER WITH

421STEELSUPPLY REGISTERS-1

REMARKS

ACCESSORIESFINISH

AIR DEVICE SCHEDULE

MATERIAL

21STEEL

FUNCTION TYPEUNIT NO.

R-1 RETURN

WHITE ENAMEL 1

OPPOSED BLADE DAMPER

45 DEG. DEFLECTION.

3 FIXED 3/4" HORIZONTAL BARS,

REGISTER

TYPE

1.

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION

2.

(NIC)

REF

(NIC) (NIC)

(NIC)

FEC 13.8 LPS

13.8 LPS

ERV

BIRD SCREEN(TYP OF 2)

HOODED WALL CAP W/STS METAL

STAINLESS STEEL SQUARE SHAPE

O.AE.A

MD

MOTOR DAMPER

BACKDRAFT DAMPER

BDD

VD

VD

VD

VD

VD

O150

O150

O150

34.7LPS x 2 S-1:O150

34.7LPS x 2 E-1:O150

VD

O

O

O

O

O100

O100

13.8LPS

E-1:O100

13.8LPS

S-1:O100

M D

W/MOTORIZED DAMPER

300 X 300 OUTSIDE AIR OPENING

EF

200O1

RH

BIRDSCREEN FOR RANGE HOOD

HOODED WALL CAP W/

EF

BIRDSCREEN

HOODED WALL CAP W/

200O

O A

S A

E A

R A

NEW HVAC DUCT PLAN

OF HVAC DUCT IN FIELD(TYP)

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HVAC DUCT SYSTEM.

NOTES

AIR DEVICE SCHEDULE AND

NEW HVAC DUCT FLOOR PLAN

4.185

.3

8 (NIC) (NIC)

(NIC)

BED ROOM

LINEN

REF

KITCHEN

PANTRY

STOR

OFFICE

104 107

110 111

CLOSET-2CLOSET-1

LIVING ROOM

BATH

COMM RM

ROOM

MECH/ELEC

"EMERGENCY HVAC SHUT-OFF SWITCH"

W/ CLEAR FLIP-COVER LABELLED AS

HVAC EMERGENCY SHUT-OFF SWITCH

T

REPAIR BUILDING S-11

M-8

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

M8- SCALE : 1 / 50

REF

FEC

HB

REF

(NIC)

B

C

A

REMARKS

RATING

FU

QTY

SYMBOL

P.D.I

1-11

12-32 20

33-60 25

WATER HAMMER ARRESTER SCHEDULE

CONN.

PIPE

INSTRUCTIONS.

PER PDI-WH 201 AND MANUFACTURER'S

2. SIZE AND LOCATE WATER HAMMER ARRESTORS

COMPRESSION CHAMBER W/EXPANSION BELLOWS.

1. COPPER CONSTRUCTION PRESSURIZED

PLUMBING FIXTURES SCHEDULE

PLUMBING FIXTURES QTY

COLD HOT TRAP VENT

REMARKS

1515LAVATORY

-15

50 32

SYMBOL

408015SHOWER

P-1

P-4

P-5 MAX.0.5 GPM @60 PSI

WATER CLOSET (F.T) 100

LOCAL PIPE CONNECTION

1515 80 32P-7 1KITCHEN SINK

3.8 LITERS/FLUSH

NOTE :

NOTE ON INSTALLATION OF PIPE INSULATION :

COMPLETED.

INSPECTION WHEN THE INSTALLATION OF THE PIPE INSULATION IS

4. THE CONTRACTOR SHALL INVITE THE MECHANICAL ENGINEER FOR QUALITY

E84.

SMOKE DEVELOPED INDEX OF 50 WHEN TESTED IN ACCORDANCE WITH ASTM

SHALL HAVE A MAXIMUM FLAME SPREAD INDEX OF 25 AND A MAXIMUM

3. LAGGING ADHESIVES SHALL BE NON-FLAMMABLE AND FIRE RESISTANT AND

APP GUIDE.

2. INSULATION MATERIALS RECOGNIZED UNDER UL 94 AND LISTED IN FM

TYPE I OR II AND SHALL CONFORM TO TABLE 1 OF OMA SPEC 23 07 00.

1. INSULATION MATERIALS SHALL COMPLY WITH ASTM C534/C534M, GRADE 1,

BACK-FLOW PREVENTER

TRAP PRIMER

A

ARRESTER(TYP.)

WATERHAMMER

A

ARRESTER(TYP.)

WATERHAMMER

P-1P-5 P-4

P-7 P-7

P-4P-1P-5

EWH

32 25

3-WAY MIXING VALVE

THERMOSTATIC

SEE CIVIL DWG FOR CONT

100 80 V.T.R

80SD

100FCO100FCO

100FCO

50FD

32 50 50 40

CW & HW PIPING SEWER & VENT PIPING

CONDUITS, AND ALL NECESSARY ACCESSORIES.

4. THE CONTRACTOR SHALL PROVIDE ALL THE SWITCHES, RELAYS, WIRING,

WATER HAMMER ARRESTORS.

3. PROVIDE CEILING/WALL ACCESS PANEL FOR ISOLATION VALVES AND

PIPING INSTALLATION.

& COLD WATER PIPING, SEWER AND VENT PIPING) PRIOR TO PLUMBING

2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING PIPING (HOT

1. ALL WATER PIPE LINES SHALL BE COPPER TUBE.

WATER HAMMER ARRESTER SCH. AND NOTES

INSULATION, PLUMBING FIXTURES SCH.,

NOTE ON INSTALLATION PIPE

NEW PLUMBING PIPING PLAN,

SEE CIVIL DWG FOR CONT

(NIC) (NIC)

(NIC)

BED ROOM

LINEN

REF

LIVING ROOM

KITCHEN

COMM RM

PANTRY

STOR

OFFICE

101 102

105 107

FEC

110 111

CLOSET-2CLOSET-1

(NIC) (NIC)

(NIC)

BED ROOM

BATH

LINEN

REF

LIVING ROOM

KITCHEN

COMM RM

PANTRY

STOR

OFFICE

101 102

FEC

110 111

CLOSET-2CLOSET-1

ROOM

MECH/ELEC

ROOM

MECH/ELEC

BATH

REPAIR BUILDING S-11

M-9

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

DOMESTIC WATER HEATER SECTION

EA

NOT TO SCALE

OFF

C

OL

120 VAC

M

M

MD

DAMPER

MOTORIZED

OL

120 VAC

AUTO

HAND

C

MD

OFF

TF

C

NOTE :

LADDER DIAGRAM

TF T

OFF

120 VAC

T

C

OL

ON

FAN

EXHAUST

FAN MOTOR

UNIT HEATER

LADDER DIAGRAM

LADDER DIAGRAM

THE ROOM TEMPERATURE AT 10°C FOR FREEZING PROTECTION.

SUPPLY FAN OPERATION IN AN "ON-OFF" SEQUENCE TO MAINTAIN

2. UNIT MOUNTED THERMOSTAT T CONTROLS THE UNIT HEATER

HEATER SUPPLY FAN CONTINUOUSLY UNTIL MANUALLY STOPPED.

1. "ON/OFF" SELECTOR SWITCH TO "ON" POSITION RUNS THE UNIT

ELECTRIC UNIT HEATER

NOT TO SCALE

EUH

UNIT HEATER

ELECTRIC

INTERRUPTION

CLOSED ON POWER

WITH SPRING RETURN,

MOTORIZED LOUVER

OUTSIDE AIR

WF

1 EXHAUST FAN

WALL TYPE

EXHAUST FAN CONTROL

NOT TO SCALE

WHEN THE EXHAUST FAN IS TURNED-OFF.

EXHAUST FAN IS OPERATING AND SHALL RETURN TO FULLY CLOSED

4. THE OUTSIDE AIR MOTORIZED LOUVER SHALL OPEN WHEN THE

FAN WHEN THE ROOM TEMPERATURE DROPS TO 26°C.

TEMPERATURE REACHES 29°C OR HIGHER AND STOPS THE EXHAUST

3. ROOM THERMOSTAT TF RUNS THE EXHAUST FAN WHEN THE ROOM

ENERGIZES THE EXHAUST FAN.

2. "HAND-OFF-AUTO" SELECTOR SWITCH TO "AUTO" POSITION

THE EXHAUST FAN CONTINUOUSLY UNTIL MANUALLY STOPPED.

1. "HAND-OFF-AUTO" SELECTOR SWITCH TO "HAND" POSITION RUNS

VENTILATION.

RUN 24 HOURS A DAY 7-DAYS A WEEK FOR BROMINE AND OZONE

2. EXHAUST FAN SHALL HAVE INDIVIDUAL ON/OFF SWITH AND SHALL

1. NO MOTORIZED DAMPER INTERLOCK FOR EXHAUST FAN.

LADDER DIAGRAM

TO INSTALL THE CONTROLS SYSTEM.

RELAYS, WIRING, CONDUITS, AND ALL NECESSARY ACCESSORIES

THE CONTROLS CONTRACTOR SHALL PROVIDE ALL THE SWITCHES,

EXHAUST FAN CONTROL

NOT TO SCALE

CF

EXHAUST FAN

ENERGIZES THE EXHAUST FAN.

2. "HAND-OFF-AUTO" SELECTOR SWITCH TO "AUTO" POSITION

THE EXHAUST FAN CONTINUOUSLY UNTIL MANUALLY STOPPED.

1. "HAND-OFF-AUTO" SELECTOR SWITCH TO "HAND" POSITION RUNS

EXHAUST FAN

HAND

AUTO

AQUASTAT

3-WAY MIXING VALVE

THERMOSTATIC

PRIMARY

CONTROL

A

120 VAC

A AQUASTAT

SYMBOL D E S C R I P T I O N

COMPLETE WITH WELL ADAPTER AND TUBE OF HEAT CONDUCTIVE COMPOUND AND MANUAL RESET.

IMMERSION TYPE, SENSING ELEMENT ACTUATES ENCLOSED SNAP ACTING SWITCH BREAKS ON TEMPERATURE RISE, SET-POINT

TEMPERATURE RANGE

INPUT VOLTAGE

: 93.30°C (200°F)

: 43.30°C-143.30°C (110°F-290°F)

: 120 VAC

A

DHWS 43°C

C

DWH

HOT WATER HEATER

ELECTRIC DOMESTIC

TO PLUMBING FIXTURES

CW MAKE-UP WATER LINE

HOT WATER HEATER

DOMESTIC

3. 3-WAY MIXING VALVE MODULATES TO MAINTAIN HOT WATER SUPPLY TEMPERATURE TO THE FIXTURES AT 43°C.

HOT WATER SUPPLY TEMPERATURE AT 60°C.

2. WHEN ENERGIZED, AQUASTAT A CONTROLS THE BURNER OPERATION IN AN "ON-OFF" SEQUENCE TO MAINTAIN THE DOMESTIC

1. "ON-OFF" SWITCH TO "ON" POSITION ENERGIZES THE BURNER OF THE DOMESTIC WATER HEATER.

DOMESTIC HOT WATER HEATER

MECH CONTROLS

REPAIR BUILDING S-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

M-10

SP

D

FIRE PROTECTION LEGEND & ABBREVIATION

SPRINKLER

MAIN SUPPLY SPRINKLER

PENDENT SPRINKLER(K=5.6)

UPRIGHT SPRINKLER(K=5.6)

CUTTING POINT

CAP

FIRE DEPARTMENT CONNECTION

(2-WAY SHOWN)

VALVES

CHECK VALVE

FITTING

WALL MOUNTED TEST HEADER

CONNECTION, TOP

ELBOW, 90

ELBOW, TURNED UP

ELBOW, TURNED DOWN

TEE

TEE, OUTLET UP

TEE, OUTLET DOWN

CONNECTION, BOTTOM

RISER

TEST VALVE

DRAIN VALVE

TYPICALTYP.

NO

EXST EXISTING

ABBREVIATIONS

MAX MAXIMUM

MIN MINIMUM

DRAIN PIPE

NUMBER

DRAWINGDWG

CONN

CONT CONTINUE/CONTINUATION

CONNECTION

RM ROOM

W/ WITH

W/O WITHOUT

SCH SCHEDULE

RESIDENTIAL PENDENT SPRINKLER(K=4.9)

UPRIGHT SPRINKLER(K=8.0)

9. ELEVATOR FIRE SPRINKLER SHALL BE IN ACCORDANCE WITH UFC 3-600-01

AUTOMATIC FIRE SUPPRESSION(S) GENERAL NOTES:

1. THE CONTRACTOR SHALL PROVIDE AND INSTALL AN AUTOMATIC WET PIPE SPRINKLER SYSTEM

TO FULLY PROTECT THIS FACILITY. THE FIRE SPRINKLER SYSTEM SHOWN THESE DRAWING IS

PERFORMANCE BASED WHICH MEANS CONCEPTUAL REQUIREMENT ONLY. THE SPRINKLER

CONTRACTOR SHALL SUBMIT A COMPLETE FIRE SPRINKLER SYSTEM SHOPDRAWINGS BASED ON

NFPA 13 AND SPECIFICATION REQUIREMENTS AND SUBMIT FOR APPROVAL PRIOR TO

INSTALLATION. THE EQUIPMENT SHOWN ARE SUGGESTED LOCATIONS HOWEVER FINAL LAYOUT

SHALL BE IN ACCORDANCE WITH APPLICABLE CODES, MANUFACTURER'S RECOMMENDATIONS, AND

EQUIPMENT LISTINGS. CONTRACTOR SHALL COORDINATE SPRINKLER HEADS LOCATIONS WITH,

CEILING PANELS, LIGHTING FIXTURES, AND HVAC AIR DEVICES. ALL EQUIPMENT SHALL BE UL

LISTED AND FM APPROVED IN ACCORDANCE WITH NFPA 13 AND THE PROJECT SPECIFICATION.

2. THE CONTRACTOR SHALL CONDUCT WATER SUPPLY HYDRANT TEST FOR THIS PROJECT BASED

ON NFPA 291 REQUIREMENTS AND UTILIZE THIS DATA TO DESIGN THE SPRINKLER SYSTEM.

THE HYDRANT LOCATIONS, FLOW TESTS, AND DATE SHALL BE INDICATED ON THE

SHOPDRAWINGS. AUTOMATIC SPRINKLER PROTECTION SYSTEM IS REQUIRED TO PROTECT THIS

ENTIRE FACILITY. A MINIMUM 10% SAFETY FACTOR IS REQUIRED BETWEEN THE AVAILABLE

WATER SUPPLY AND THE SPRINKLER SYSTEM DEMAND.

INSTALLED IN THE HORIZONTAL POSITION.

7. ALL AUTOMATIC SPRINKLER DRAIN VALVES FOR FIRE DEPARTMENT CONNECTIONS SHALL BE

BE INSTALLED ON THE EXTERIOR.

DRAINS, BUT MUST TERMINATE TO THE BUILDING EXTERIOR. SPRINKLER RISERS SHALL NOT

AND MAINTENANCE. TEST DRAINS ARE NOT TO BE TERMINATED AT WALL SINKS OR FLOOR

6. PROVIDE MINIMUM 1M X 2M SPACE FOR EACH FIRE SPRINKLER RISER FOR INSTALLATION

AS-BUILT DRAWINGS FOR THIS PROJECT.

CONTRACTOR SHALL CONFORM TO THE SYMBOLS INDICATED IN NFPA 170 TO DEVELOP THE

22-"PLANS AND CALCULATIONS" PRIOR TO SPRINKLER PIPING INSTALLATION. THE

5. CONTRACTOR SHALL SUBMIT HYDRAULIC CALCULATIONS AS REQUIRED BY NFPA 13 CHAPTER

4. FIRE PROTECTION PLANS SHOWN ARE USED FOR COST ESTIMATE PURPOSE ONLY.

WITH O-RINGS ARE NOT PERMITTED.

BRACING CALCULATION IN ACCORDANCE WITH NFPA 13 REQUIREMENTS; SPRINKLERS

3. PROVIDE EARTHQUAKE PROTECTION (SWAY BRACING), END OF BRANCH LINE AND SEISMIC

8. FLEXIBLE COUPLINGS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 13

10. ALL PIPING, SANITARY, VENT, WASTE, PLUMBING, OTHER PIPING, POWER OR CONTROL CIRCUTS, OR DUCT SHALL PENETRATE ANY STAIR OR EXIT PASSAGEWAY ENCLOSURE UNLESS IT SERVES

AN APPLIANCE WITHIN THE ENCLOSURE AND DEAD ENDS IN THE ENCLOSURE.

DRY SIDEWALL SPRINKLER(K=5.6)

OS&Y GATE VALVE(N.O.)

W/TAMPER SWITCH

OS&Y GATE VALVE(N.C.)

W/TAMPER SWITCH

FIRE PROTECTION LEGEND & ABBREVIATION

AUROMATIC FIRE SUPPRESSION GENERAL

NOTES, SPRINKLER Q'TY LIST AND NOTE

SPRINKLER Q'TY LIST

SPRINKLER HEAD TYPE

US/(METRIC)

"K" FACTOR

SIZE

A R E ASYMBOL

LIVING ROOM, BED ROOM, BATH, KITCHEN, CLOSET, PANTRY, LINEN

THREAD

SPRINKLER Q'TY LIST

RESIDENTIAL PENDENT TYPE SPRINKLER HEAD 4.9/(68)1/2" NPT

TOTAL

MECH/ELEC ROOM, COMM RMQUICK RESPONSE UPRIGHT TYPE SPRINKLER HEAD 8.0/(115)3/4" NPT

75.6/(80)1/2" NPTQUICK RESPONSE PENDENT TYPE SPRINKLER HEAD

TOTAL NUMBER OF SPRINKLER OF SYSTEM 33

OFFICE

VERIFYING ACTUAL QUANTITIES BASED ON THE CONTRACT DOCUMENT REQUIRMENTS.

1. QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY, THE CONTRACTOR SHALL BE RESPONSIBLE FOR

NOTE

STORAGEQUICK RESPONSE PENDENT TYPE SPRINKLER HEAD 8.0/(115)3/4" NPT 6

REPAIR BUILDING S-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

M-11

M11-

REF

FEC

0 25

25 32 40

25324050 25 32 40

20mm QUICK RESPONSE

UPRIGHT TYPE SPRINKLER HEAD

FIRE DEPARTMENT SIAMESE CONNECTION

65mm X 65mm W/20mm BALL DRIP VALVE

15mm QUICK RESPONSE

PENDENT TYPE SPRINKLER HEAD

PENDENT TYPE SPRINKLER HEAD

15mm RESIDENTIAL CONCEALED

PENDENT TYPE SPRINKLER HEAD

20mm QUICK RESPONSE

FIRE PROTECTION PIPING PLAN

SCALE = 1:50

FIRE PROTECTION PIPING PLAN

BED ROOM

LINEN

REF

KITCHEN

PANTRY

STOR

OFFICE

104 107

FEC

110 111

CLOSET-2CLOSET-1

ROOM

MECH/ELEC

LIVING ROOM

COMM RM

BATH

REPAIR BUILDING S-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

M-12

REQUIREMENTS

PARTIAL PLAN AND FIRE PROTECTION

SPRINKLER RM FIRE PROTECTION PIPING

SCALE = 1:25

MECH/ELEC ROOM FIRE PROTECTION PIPING PARTIAL PLAN1

WET SPRINKLER

4.1 LPM/SM (0.10 GPM/SF)

RESIDENTIAL

950 LPM (250 GPM)

MAX. 4.9 M (16 FT)

MAX. 4 HEADS

MIN. 2.4 M (8 FT)

60 MIN.

ORDINARY TEMPERATURE RATING

TYPE OF SYSTEM

SPRINKLER

SPRINKLER TYPE

MAX. COVERAGE PER

BETWEEN SPRINKLERS

MAX. & MIN. SPACE OF

RATING*

SPRINKLER TEMPERATURE

DESCRIPTION

HAZARD

FIRE PROTECTION REQUIREMENTS

DESIGN DENSITY

DURATION OF SUPPLY

HOSE STREAM

DESIGN AREA

APPLICATION AREA

WET SPRINKLER

8.2 LPM/SM (0.20 GPM/SF)

QUICK RESPONSE

12.07 SM (130 SF)

950 LPM (250 GPM)

MAX. 4.6 M (15 FT)

230 SM (2500 SF)

MIN. 1.8 M (6 FT)

60 MIN.

INTERMEDIATE TEMPERATURE RATING

ORDINARY TEMPERATURE RATING

RESIDENTIAL

OCCUPANCY

ORDINARY HAZARD

OCCUPANCY

STOR, COMM RM

SPRINKLER NOZZLE

K-FACTOR OF

(8.0)

(4.9)

ORDINARY TEMPERATURE RATING

REFER TO PARA 9-7.3, UFC 3-600-01(28. NOV. 2016, CHANGE 1)*

WET SPRINKLER

4.1 LPM/SM (0.10 GPM/SF)

QUICK RESPONSE

20.90 SM (225 SF)

950 LPM (250 GPM)

MAX. 4.6 M (15 FT)

140 SM (1500 SF)

MIN. 1.8 M (6 FT)

60 MIN.

ORDINARY TEMPERATURE RATINGORDINARY TEMPERATURE RATING

LIGHT HAZARD

OCCUPANCY

(5.6)

4.9M X 4.9M

(16FT X 16FT)

OFFICE

LIVING ROOM, BED ROOM, BATH

KITCHEN, CLOSET, PANTRY, LINEN

MECH/ELEC ROOM,

TS N.O.

N.O.

TS

N.O.

TS

ROOM

MECH/ELEC

80mm X 1-65mm TEST HOSE HEADER W/1-65mm HOSE VALVE

W/20mm BALL DRIP VALVE

FOR BACKFLOW PREVENTER FLOW TEST

80mm OS & Y GATE VALVE

W/TAMPER SWITCH

80mm BACKFLOW PREVENTER

UL/FM APPROVED ASSEMBLY

M12-

80mm ALARM CHECK VALVETEST AND DRAIN VALVE

SEE CIVIL DWG FOR CONT

REPAIR BUILDING S-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

M-13

MAIN RISER CONNECTION(TYPICAL)

AND SPIGOT PIECE

DUCTILE IRON FLANGE

AND SPIGOT PIIPE

RODS NOT LESS

THAN 20Ø

DUCTILE IRON BELL

SERVICE

FROM FIRE

MAIN

G.L

GENERAL NOTE :

OR LEAVING THE SUBJECT BUILDINGS.

THIS DETAIL SHALL BE UTILIZED WHERE

.FIRE MAIN SERVICE LINES ARE ENTERINE

STEEL PIPE

THRUST BLOCK

CONC.

FL

BITUMASTIC COATED

BITUMASTIC COATED

SPRINKLER ALARM CHECK VALVE & MAIN RISER

W/TAMPER SWITCH

GATE VALVE

OS & Y

FIRST

PIPE SUPPORT

1 3

SEE

M10

FIRE DEPT CONNECTION

VALVE

BALL DROP

2 TAMPER SWITCH

BACKFLOW PREVENTER

TEST VALVE HEADER

TEST VALVE

OS & Y GATE VALVE

DESCRIPTION

ITEM

SPRINKLER MAIN RISER

FIRE DEPT SIAMESE CONNECTION

PER NFPA 13

FLEXIBLE COUPLING

FOR EARTH QUAKE

(WITH TAMPER SWITCH)

SUPERVISORY VALVE

WATER MOTOR ALARM DRAIN

PRESSURE SWITCH

PIPE SUPPORT

RISER TO SPRINKLER SYSTEM

FIRST SUPPORT W/CROSS BRACING

RETARDING CHAMBER

WATER MOTOR ALARM GONG

MAIN DRAIN AND TEST VALVE

SWAY BRACING PER NFPA 13 FOR

FLEXIBLE COUPLERS PER NFPA 13

DESCRIPTION

ALARM CHECK VALVE

(2-REQUIRED)

PRESSURE GAGE

ZONE 1 EARTHQUAKE

ITEM

FOR EARTH QUAKE

SEE

M10

VALVE

BALL DROP

PIPE

O N

I C T

E N

AU

O

F

IR

E

DEPT C

TOSPK

N

R

CONNECTION

FIRE DEPT

CLAPPER

SWIVEL

2-1/2" NS OR BS

EASE - OFF

HOSE COUPLING

PLUG

THREAD

MAIN DRAIN

SYSTEM TEST CONNECTION

PIPE EXTENDS THROUGH WALL TO OUTSIDE.

2. THE TEST VALVE SHOULD BE LOCATED AT AN

ACCESSIBLE POINT AND PREFERABLY NOT

OVER 7FT (2.1M) ABOVE THE FLOOR.

PIPE IN WARM ROOM BEYOND VALVE WHERE

1. NOT LESS THAN 4FT (1.2M) OF EXPOSED TEST

NOTES :

ACCESSIBLE LOCATION

TEST VALVE IN READILY

SEE NOTE

BRANCH LINE

P.G.

SWAY BRACING

CONC

SLAB

SWAY BRACE FITTINGS

SCHEDULE 40 PIPE

PIPE CLAMP

SPRINKLER

CROSSMAIN

EXPANSION BOLT (TYP)

CONC

SLAB

SWAY BRACE FITTINGS

SCHEDULE 40 PIPE

SPRINKLER

CROSS MAIN

EXPANSION BOLT

PIPE CLAMP

* PIPE SIZE SHALL BE DETERMINED BY CALCULATIONS

ON WET PIPE SYSTEM

PRESSURE RELIEF VALVE13

DETAILS - 1

1 2 3

4 5 6

REPAIR BUILDING S-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

M-14

DETAILS-2

REMOTE CONTROL

FULL BOX

ELECTRICAL CONC. BOX

CEILING

ROOM

(CEILING CASETTE 4-WAY TYPE)

INDOOR HEAT PUMP

ROOM

R.L/R.G

DRAIN PIPE

CEILING

PUMP

HEAT

(TYP)

HANGERMIN 300

FOR SERVICE

ACCESS DOOR

600x600 CEILING

CABLE

POWER

CEILING

R.L/R.G

DRAIN PIPE

DRRAIN HOSE

(CEILING CASETTE 4-WAY TYPE)

INDOOR HEAT PUMP

MAX.700

(TYP.)

HANGER

SLOPE

1/50-1/100

SEE

LIQUID PIPE 6.35A/ 9.52A

TAPE

Y-JOINT

INLET

INSULATION REFRIGERANT LIQUID/ GAS PIPE

COVER

OUTLET

GAS PIPE 12.7/ 15.88

PIPE INSULATION:19T

EPDM

VCTF-SB1.25x2C

CABLE LINE

FIN. GRADE

150 150

SECTION

PLAN

N F S M

150150ACTUAL EQUIPMENT SIZE

AT EXPOSED EDGES

20mm CHAMFERS#4 @300 O.C.

50 CLR

CONC. PAD

150 150 150150ACTUAL EQUIPMENT SIZE

A C

T U

A L

E

Q U

IP

M E

N T

S

IZ

E

EQUIPMENT UNIT

GRAVEL BASE

150mm THK.

1 INDOOR HEAT PUMP UNIT INSTALLATION DETAIL

SECTION ENLARGED SECTION

Y JOINT DETAIL

SECTION

CONCRETE PAD DETAIL

WITH MANUFACTURER.

FINAL PAD SIZE SHALL BE CORDINATED

6" (150mm) LARGER THAN UNIT SIZE AND

ALL EQUIPMENT CONC PAD SIZE SHALL BE

FILTER DRIER

LIQUID LINE

CONDENSATE DRAIN

DRAIN PUMP

CONDENSATE

THERMOSTAT

SWITCH

DISCONNECT

FUSED

VAPOR LINE

(OUTDOOR UNIT)

DUCT-FREE HEAT PUMP

(INDOOR UNIT)

DUCT-FREE HEAT PUMP

SWITCH

FUSED DISCONNECT

WEATHERPROOF

ISOLATORS

SPRING

HANGER ROD

HANGER PLATE

VENTILATOR

ENERGY RECOVERY

E.R.V EQUIPMENT INSTALLATION

TYPICAL REFRIGERANT PIPING DIAGRAM3

REPAIR BUILDING S-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

M-15

DETAILS-3

EXTERIOR INTERIOR

MASONRY WALL

CONCRETE OR

INSULATION

PIPE WITHOUT

ALL AROUND

MIN. 7 CLEARANCE

METAL JACKET

INSULATION

SEALANT #10

PIPE SLEEVE

BACK UP MATERIAL

INSULATION

PIPE WITH

ANCHOR

RUBBER OR PLASTIC)

FLEXIBLE FOAM

(CLOSED CELL

BACK UP MATERIAL

SEALANT #2

MEMBRANE

WATERPROOFING

CLAMPING FLANGE

WATERPROOFING

METAL JACKET

SLEEVE

INSULATION

INSULATION

PIPE WITHOUT

SEALANT #2

ALL AROUND

7 MIN CLEARANCE

INSULATION

PIPE WITH

BACK UP MATERIAL

50SEALANT #2

(TYP)

METAL BAND

SLEEVE

CEILING

MASONRY WALL

CONCRETE OR

RUBBER OR PLASTIC)

FLEXIBLE FOAM

(CLOSED CELL

BACK UP MATERIAL

INSTRUCTIONS.

IN ACCORDANCE WITH MANUFACTURER'S LISTED INSTALLATION

2. FIRESTOPPING SHALL BE PROVIDED AND SHALL BE INSTALLED

EQUIPMENT ROOMS.

FLOORS OR CEILINGS, EXCEPT IN BOILER, UTILITY OR

WHERE EXPOSED PIPING, BARE OR INSULATED PASSES THROUGH

1. ESCUTCHEONS SHALL BE PROVIDED AT ALL FINISHED SURFACES

PIPE WITH INSULATIONPIPE WITHOUT INSULATION

METAL JACKET

SLEEVE

PLASTIC)

RUBBER OR

FLEXIBLE FOAM

(CLOSED CELL

BACK UP MATERIAL

7 MIN CLEARANCE

INSULATION

METAL BAND (TYP)

SEALANT #2

MATERIAL

BACK UP

FIN FLOOR

CEMENT

CLIP TYPE

SPRING

ESCUTCHEON

SLEEVE

PIPE WITHOUT INSULATION PIPE WITH INSULATION

INSULATION

FLOOR

METAL JACKET

METAL BAND

WATERPROOFING

PLASTIC)

RUBBER OR

FLEXIBLE FOAM

(CLOSED CELL

MATERIAL

BACK UP

OR 450 GMS COPPER

20 KG/SQ. METER

FLASHING

SEALANT #2

STAINLESS STEEL FLUSH TYPE ACCESS COVER PLATE.

2. CHROMIUM-PLATED BRONZE, NICKEL BRONZE, NICKEL BRASS OR

1. WATERPROOF MEMBRANE ARE NOT REQUIRED IN SLAB ON GRADE.

PACKING

TARRED JUTE

WHEN NOT THRU RUN

PLUG Y-BRANCH

3mm BEND

GASKET

NEOPRENESCORIATED COVER, SEE NOTE 2

ADJUSTABLE HOUSING

TWO PIECE THREADED

WATERPROOF MEMBRANE

Y-BRANCH

PIPE

CAST IRON

FFL

REDUCING TEE

UNION

13 FEMALE ADAPTER

WATER METER

PRESSURE GAUGE

MALE ADAPTER

GATE VALVE

MALE ADAPTER

20 HOSE BIBB

G.L

CIVIL DRAWING

ELEVATION SEE

FOR INVERT

MASTIC

WATERPROOF

REDUCING TEE

INSTALLATION

VERTICAL

SUITABLE FOR

STRAINER

FOR LOCATION AND SIZE

20mm OR 25mm SEE DWGS

DISPLACEMENT CUSHION

PRESSURE PNEMATIC

DISPLACEMENT FLUID

HYDRAULIC

ORIFICE

FLOW CONTROL

BRANCH SUPPLY

FROM

LAST FIXTURE

TO

CW

STRAINER

GLOBE VALVE

TO SYSTEM

REDUCER

COCK (TYP. OF 2)

6 SHUT-OFF

PRESSURE REDUCING VALVE

(TYP. OF 2)

PRESSURE GAGE

REDUCING TEE (TYP.)

UNION (TYP.)

(TYP. OF 3)

GATE VALVE

TYPE BACK-FLOW PREVENTER

REDUCED PRESSURE PRINCIPLE

SERVICE LINE

COLD WATER

SUPPLY LINE

HOT WATER

VACUUM BREAKER

ADAPTER (TYP)

DRAIN

TO NEAREST

RELIEF DRAIN

1 PIPE SLEEVE-THRU FOOTING 2 PIPE SLEEVE-THRU INTERIOR WALL 3 PIPE SLEEVE-THRU FLOOR

NOTES

PIPE SLEEVE-THRU FLOOR WITH WATERPROOFING

FLOOR CLEANOUT

NOTES

WATER SERVICE

SEE DETAIL ON THIS SHEET

PIPE SLEEVE-THRU FOOTING

ON THIS SHEET

FLOOR SEE DETAIL

PIPE SLEEVE-THRU

8 WATER HAMMER ARRESTOR6

H E

IG

H T

COPPER SHELL

THREADED PLUG

DIAMETER

COPPER ADAPTOR

BELLOWS

ELECTRIC WATER HEATER 11 BACK FLOW PREVENTER & PRESSURE REDUCING STATION

GATE VALVE

PRESSURE GAUGE

COMPOUND

50mm DIAL

CONNECTION

UNION TYPE

PRESSURE GAUGE

DISCHARGE

50mm DIAL

GATE VALVE

8mm SHUT-OFF COCK

(TYP)

REDUCING TEE

MOTOR

NIPPLE (TYP)

FROM SYSTEM

BALANCE VALVE

10 IN-LINE PUMP CONNECTION

CHECK VALVE

MOUNTED

HORIZONTAL

SHUT-OFF COCK

8mm

PUMP

CIRCULATION

HEATER

HOT WATER

TO DOMESTIC

HEATER

WATER

ELECTRIC

CLEARANCE FROM THE FLOOR (OR PAD)

HEATER SHALL BE DROPPED UP MIN.ƒ"

2" NIPPLE

MAXIMUM

1/2" HOSE BIBB

RELIEF VALVE

AND PRESSURE

TEMPERATURE

COMBINATION

PIPE

(I N

C L U

D

IN

G

IN

S U

L A T

IO

N

P

IP

E

D

IA

m m

PIPE

P

E

P

E

TYPE

D

C

B

A

HEIGHT DIAMETER

DIMENSION SHALL BE

VARIED DEPEND UPON

MFR

CAPACITY(FU)

61-113

33-60

12-32

1-11

FIXTURE UNIT

CONN.SIZE

REPAIR BUILDING S-11

NNSCCHONG, ST

297038

FILL/BED

CEMENT

SLAB

STRUCTURAL

SEE NOTE 2

SEE NOTE 1

MEMBRANE

WATERPROOF

FLOOR

FINISH/TILE

A

P-TRAP

ADAPTOR

WASTE LINE

CLEANOUT PLUG

FLOOR DRAIN

297038_REPAIR BUILDING S-11-NNSC_MECH_M1
297038_REPAIR BUILDING S-11-NNSC_MECH_M2
297038_REPAIR BUILDING S-11-NNSC_MECH_M3
297038_REPAIR BUILDING S-11-NNSC_MECH_M4
297038_REPAIR BUILDING S-11-NNSC_MECH_M5
297038_REPAIR BUILDING S-11-NNSC_MECH_M6
297038_REPAIR BUILDING S-11-NNSC_MECH_M7
297038_REPAIR BUILDING S-11-NNSC_MECH_M8
297038_REPAIR BUILDING S-11-NNSC_MECH_M9
297038_REPAIR BUILDING S-11-NNSC_MECH_M10
297038_REPAIR BUILDING S-11-NNSC_MECH_M11
297038_REPAIR BUILDING S-11-NNSC_MECH_M12
297038_REPAIR BUILDING S-11-NNSC_MECH_M13
297038_REPAIR BUILDING S-11-NNSC_MECH_M14
297038_REPAIR BUILDING S-11-NNSC_MECH_M15