297038_ELEC_DWG (1).pdf

PDF 5 MB Posted

Attached to
Repair Building S-11 NNSC (LCS MATOC Only)
Solicitation number
W90VN824R0039
Issued by

About this file

This document appears to be a set of electrical drawings and specifications for the repair of Building S-11 at the NNSC (Non-Commissioned Officers Senior Club) in Camp Bonifas. The key details include:

The scope of work involves repairing and upgrading the electrical, lighting, fire alarm, mass notification, LAN/telecom, and CATV systems in the building. This includes replacing interior and exterior lighting fixtures, panelboards, receptacles, fire alarm control panel, fire alarm/mass notification devices, telephone/LAN equipment, and CATV equipment and cabling. The drawings provide detailed specifications for the required electrical components and systems. The solicitation number for this repair project is W90VN824R0039, and it is limited to the MATOC (Multiple Award Task Order Contract) contractors. No other details about the contract opportunity such as response dates, award dates, pricing terms, or set-asides are provided in this document.

View the file

Other files

File Type Posted
297038-STRUCTURE_DWG.pdf PDF
297038_MECH_DWG (1).pdf PDF
297038-CIVIL_DWG.pdf PDF
297038-ARCH_DWG.pdf PDF
W90VN824R0039.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

L

L

GENERAL NOTES

1.

2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE

NOTED ON THE DRAWING.

LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE

PANELBOARD SEE SPECIFICATION

SAFETY SWITCH 1524mm TO CENTER OF THE ENCL

RECEPTACLE,TELEPHONE OUTLET 305mm TO CENTER OF THE ENCL

MOTOR CONTROLLER 1524mm TO CENTER OF THE ENCL

1676mm TO CENTER OF THE ENCL

2286mm TO CENTER OF BELL

ON CEILINGDETECTOR

1372mm TO CENTER OF STATIONMANUAL PULL STATION

INDICATEDS 2 #12AWG IN 16C

INDICATEDS 3 #12AWG IN 16C

INDICATEDS 4 #12AWG IN 16C

A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;

1219mm TO CENTER OF THE ENCLWALL SWTICH

F/A &MNS CONTROL

COMBO. SPEAKER & STROBE

SINGLE POLE TOGGLE SWITCH, 15A-125V

L E G E N D

FLEXIBLE CONDUIT W/CONNECTORS

LIGHTING

WIRING

POWER

INTERIOR

S

SYMBOL DESCRIPTION

DESCRIPTION

DESCRIPTION

T

J

THERMOSTAT (UNDER MECH. ITEM)

JUNCTION BOX

SYMBOL

SYMBOL

SAFETY SWITCH

C CONTROL CIRCUIT

AND GOVERNMENT INSTALLED

GOVERNMENT FURNISHED

GFGI

WEATHERPROOFWP

LA LIGHTNING ARRESTER

EXPLOSIONPROOFEP

DISTRIBUTIONDIST

GROUND FAULT PROTECTIONGFP

A AMPERE

AC ALTERNATING CURRENT

AF/AT AMPERE FRAME/AMPERE TRIP

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BLDG BUILDING

BRKR BREAKER

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CONN CONNECTION

CT CURRENT TRANSFORMER

DET(S) DETAIL(S)

DIAG DIAGRAM

DISC DISCONNECT

DWG(S) DRAWING(S)

EA EACH

EM EMERGENCY

ENCL ENCLOSURE

EXST EXISTING

F/A FIRE ALARM

FL FLOOR

FLUOR FLUORESCENT

FXTR FIXTURE

GEN GENERATOR

GND GROUND

HP HORSE POWER

HZ HERTZ

INCAND INCANDESCENT

INSTL INSTALLATION

J-BOX JUNCTION BOX

K KILO

KV KILO VOLT

KVA KILO VOLT AMPERE

LTG LIGHTING

MAG MAGNETIC

MAX MAXIMUM

MIN MINIMUM OR MINUTE

MTG MOUNTING

NO NUMBER

O/H OVER HEAD

PH PHASE

PNLBD PANELBOARD

PRIM PRIMARY

PWR POWER

Q'TY QUANTITY

RCPT RECEPTACLE

REQ'D REQUIRED

SCHED SCHEDULE

SEC SECONDARY

SPEC SPECIFICATION

STD STANDARD

SW SWITCH

TEL TELEPHONE

TYP TYPICAL

U/G UNDERGROUND

V VOLT

VA VOLT AMPERE

W WATT

W/ WITH

XFMR TRANSFORMER

& AND

CABNET TYPE, RATED WATT ON LTG SCHEDULE

LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER

ON LTG SCHEDULE, WET LOCATION

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

HOMERUN CIRCUIT TO PANELBOARD

TYPE OF MTG ON LTG SCHEDULE

EXTERIOR LED LIGHTING FIXTURE, RATED WATT &

TYPE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING

ABBREVIATION

ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG

WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.

FMCP

FTR

ANTENNA

AUXILIARY

DESCRIPTION

F

TELEPHONE OUTLET

SYMBOL

CTC CATV SYSTEM CABINET

CATV OUTLET

ADDRESSABLE FA MANUAL PULL STATION

TTC

FIRE ALARM/MASS NOTIFICATION CONTROL PANEL

MOUNTED TYPE

F/A & MASS NOTIFICATION SPEAKER "WP" WALL

STROBES

WALL MOUNTED SPEAKER /COMBO. (FA+MNS)VISUAL

CONNECTION

BUILDING TRANSMITTER UNIT FOR FIRE ALARM

SYSTEM

F

WIRING FOR TELEPHONE LINET

BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL

WIRING CONCEALED IN THE CEILING AND WALL

F/M

L

WP

TYPE WITH PLUG

SINGLE RECEPTACLE, 3P-4W-30A-125/250V, GROUNDING

TYPE WITH PLUG

SINGLE RECEPTACLE, 3P-4W-50A-125/250V, GROUNDING

W/EMERGENCY UNIT

WIRING TO UPSTAIR OR DOWNSTAIR

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

L

L

CIRCUIT INTERRUPTER TYPE,WEATHER PROOF

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND FAULT

CIRCUIT INTERRUPTER TYPE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND FAULT

EXIT LIGHT, SINGLE FACE, WALL MOUNTED TYPE

(CEILING MOUNTED TYPE W/ARROW)

L

TELEPHONE TERMINAL CABINET

STEEL CONDUIT

FIRE ALARM SYSTEM CIRCUIT, FACTORY PAINTED RED

TYPE

SINGLE RECEPTACLE, 2P-3W-20A-125V, GROUNDING

MAGNETIC MOTOR STARTER

FAN MOTOR (UNDER MECH. ITEM)

M MOTOR (UNDER MECH. ITEM)

UH

S

WHM

MANUAL MOTOR STARTER W/PILOT LAMP

WATTHOUR METER

SAFETY SWITCH

S

TS TAMPER SWITCH (UNDER MECH. ITEM)

FS FLOW SWITCH (UNDER MECH. ITEM)

F

MANUAL MOTOR STARTER W/PILOT LAMP AND

3-POSITION SELECTOR SWITCH(H-O-A)

PANELBOARD OR LOADCENTER

TV

3 & 4-WAY SWITCH, 15A-125V

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

W/EMERGENCY BATTERY UNIT

L

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

W/EMERGENCY BATTERY UNIT

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ELECTRIC UNIT HEATER

L

L

WP

F M

3S 4S

3.THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM

IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE

MECHANICAL DRAWINGS.

4.

CONDUIT UNLESS OTHERWISE INDICATED.

ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C

5.THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR

ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.

6.THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION

SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE

CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.

7.

AND LOCATION OF THE F/A ANTENNA WITH THE CENTRAL FIRE DEPARTMENT

THE CONTRACTOR SHALL SUBMIT THE SHOP DRAWING FOR THE MOUNTING

TO TRANSMIT THE ALARM RADIO SIGNAL WAVE WITHOUT ANY OBSTRUCTION.

DETAIL OF THE F/A ANTENNA, AND COORDINATE THE MOUNTING HEIGHT

F/A EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.

THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING

COORDINATED WITH THE CENTRAL FIRE DEPARTMENT SO THAT

THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING

F/A & MNS EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.

THE MANUFACTURER AND MODEL OF NEW F/A& MNS EQUIPMENT SHALL BE8.

9.

CEILING.

ALL WIRING SHALL BE CONCEALED ABOVE CEILING WHEN THE ROOM HAS

10.

CATV BEFORE CONSTRUCTION.

CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,

11.

FIRE CODE AND SPECIFICATIONS.

OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,

ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS

12.

AND GOVERNMENT ACCEPTANCE.

PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION

CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO

13.

OR RENOVATION.

CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION

THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING

14.

FIXTURE A MINIMUM DISTANCE OF 458mm.

FIRE ALARM DETECTORS SHALL BE LOCATED TO CLEAR ANY LIGHTING

15.

UNITS.

CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER

CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY

THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE

WIDTH OF DUCT EXCAVATION.

AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.

TO THEIR ORIGINAL CONDITION AND OPERATION DURING

ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES

THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING 16.

17.

CONFIRMATION.

THE CONTRACTOR SHALL REMOVE ABANDONED ELECTRIC DEVICES W/ COR

INDICATEDS 6 #12AWG IN 21C

ELECTRICAL

SCOPE OF WORKS

LEGEND, GENERAL NOTES AND

E-1

SCOPE OF WORK

2.

A. REPAIR/MAINTENANCE ( K )

4.

6.

3.

7.

5.

1.

PHOTOCELL, WIRE AND CONDUIT WITH NEW.

LIGHTS, TOGGLE SWITCHES, 3 WAY SWITCHES, LIGHTING CONTACTOR,

REPLACE EXISTING INTERIOR AND EXTRIOR LIGHTING FIXTURES, EXIT

8.

PLATES AND ASSOCIATED WIRING AND CONDUIT WITH NEW.

RACK, TELEPHONE TERMINAL BOARD, LAN/TELEPHONE OUTLETS W/ COVER

REPLACE EXISTING TELECOMMUNICATION SYSTEM INCLUDING EQUIPMENT

9.

CONDUIT AS SHOWN ON THE DRAWINGS.

INCLUDING SECONDARY LINE & ASSOCIATED ACCESSORIES, WIRING AND

REPLACE EXISTING EXTERIOR POWER DISTIBUTION SYSTEM WITH NEW

W/COVER PLATES, ASSOCIATED WIRE & CONDUIT WITH NEW.

REPLACE EXISITNG WATTHOUR METER, PANELBOARDS, RECEPTACLES

MECHANICAL SYSTEM WITH NEW.

JUNCTION BOXES, CONTROL SYSTEM, WIRE AND CONDUIT FOR

REPLACE EXISTING A MAGNETIC MOTOR STARTER, SAFETY SWITCHES,

ASSOCIATED WIRE AND CONDUIT.

DEVICES, BUILDING TRANSMITTER, ANTENNA, LIGHTNING ARRESTER AND

VISUAL SIGNAL STROBES, MICROPHONE, SPEAKERS (WATTAGE AS REQ'D)

PANEL, MANUAL PULL STATIONS, SMOKE DETECTOR & RELAY MODULES,

ADDRESSABLE FIRE ALARM CONTROL AND MASS NOTIFICATION SYSTEM

REPLACE EXISTING FIRE ALARM CONTROL SYSTEM WITH NEW

AND ASSOCIATED WIRE AND CONDUIT WITH NEW.

REPLACE EXISTING CATV CABINET, OUTLETS W/COVER PLATES

LINE AND ACCESSORIES WITH NEW.

REPLACE EXISTING EXTERIOR UNDERGROUND, OVERHEAD TELECOMMUNICATION

NNSC

REPAIR BUILDING S-11

TAK, YS

297038

FROM NEW FIRE PUMP SYSTEM TO BUILDING S-11.

SURGE PROTECTORS, ADRESSABLE MODULES, UNDERGROUND SIGNAL LINES

REPAIR EXISTING FIRE PROTECTION SYSTEM BY INSTALLING FIRE ALARM

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-2

L

L

L

L

S

L L

S

S S

S

3 S3S

L

L L

L

S

S

L

L

L

L

L

L

L

L

L L

L

L

S S

S

S

LL

S

S

S

S

NEW GROUND FLOOR LIGHTING PLAN

L L

L

P-1P-2P-3

P-4

OFFICE

(NIC)

(NIC) (NIC)

REF

KITCHEN

PANTRY

BATH

LINEN

STOR 110

CLOSET

BED ROOM102

LIVING ROOM

(NIC)

(NIC)

(NIC)

RM

COMM

ROOM

ELEC

MECH/

"P"

SCALE : 1/50

NEW GROUND FLOOR LIGHTING PLAN

NOTES SEE SHEET NO. E-1.

FOR ABBREVIATION, LEGEND AND GENERAL 1.

NOTES

L

SEE DETAILS IN DRAWING "E-15"

NEW LIGHTING CONTACTOR "LC" WITH PHOTO CELL

L

NNSC

REPAIR BUILDING S-11

TAK, YS

LLL

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-3 m m

308mm

NS-3a & 3b

WALL OR CEILING SURFACE MOUNTED LIGHT EMITTING

WITH BATTERY CHARGER, SINGLE FACE (NS-3a) OR

(MAX INPUT) OR 7.22W(MAX INPUT), BATTERY BACK-UP

DIODE(LED) EXIT LIGHT FIXTURE, 1PH, 120V, 4.99W

m m

1220m m

0m m

DOUBLE FACE (NS-3b) OR APPROVED EQUAL.

NS-5a & 5b NS-6a & 6b

245mm

ELECTRICAL

LIGHTING FIXTURE DETAILS

NS-11 NS-12

UNDERCABINET LED LIGHT FIXTURE

1PH, 120V, 13W, CONVERTER AND ACCESSORIES,

UL LISTED POWER UNIT

NS-13

222mm m m

FIXTURE, 1PH, 120V, 13W, WITH CONVERTER &

CEILING RECESSED LIGHT EMITTING DIODE (LED)

143.9mm

.3 m m

210mm

UNIT

ACCESSORIES, AS REQUIRED AND UL LISTED POWER

CEILING SURFACE/PENDANT MOUNTED LIGHT EMITTING DIODE (LED)

ACCESSORIES AS REQUIRED, (NS-7a) & SELF TEST/DIAGNOSTIC EM UNIT(NS-7b)

FIXTURE, 1PH, 120V, 45W, UL LISTED, PMMA LIGHT GUIDE WITH CONVERTER AND

NS-7a & 7b

FIXTURE, 1PH, 120V, 13W, WITH CONVERTER & ACCESSORIES,

AS REQUIRED, OR APPROVED EQUAL.

WALL SURFACE MOUNTED LIGHT EMITTING DIODE (LED)

NS-8

254mm

CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED)

OR APPROVED EQUAL.

WET LOCATION SHOWER LIGHT TRIM, AS REQUIRED

FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES,

WALL

TYPE, UL LISTED

AND ACCESSORIES W/BUILT-IN PHOTOCELL, WET LOCATION

WALL OR CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED)

LIGHTING FIXUTURE 1PH, 120V, 22W LED MODULES, WITH CONVERTER

NS-10NS-9

CONVERTER & ACCESSORIES AS REQUIRED, (NS-5a) & WITH SELF TEST/DIAGNOSTIC EM UNIT (NS-5b)

FIXTURE, 1PH, 120V, 45W, UL LISTED, PMMA LIGHT GUIDE PLATE, WITH

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

FIXTURE, 1PH, 120V, 50W, UL LISTED, PMMA LIGHT GUIDE WITH CONVERTER &

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

WET LOCATION TYPE, WITH CONVERTER & ACCESSORIES AS

REQUIRED, UL LISTED POWER UNIT

CEILING SURFACE MOUNTED LED LIGHT FIXTURE, 1PH, 120V, 22W,

ACCESSORIES, (NS-6a) & WITH SELF TEST/DIAGNOSTIC EM UNIT (NS-6b)

NNSC

REPAIR BUILDING S-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-4

REMARKSQ'TY

WATTS

MOUNTING METHOD

TYPE

LAMP

NAMENO

ROOM OCE STD DET 40-06-04

LIGHT FIXTURE SCHEDULE

TYPE

LED

LIGHT FIXTURE SCHEDULE

ELECTRICAL

101 OFFICE NS-6a

NS-6b 50

50 3

3 W/ "EM" UNIT

102 LIVING ROOM NS-6a

NS-6b 50

50 3

CEILING RECESSED

W/ "EM" UNIT

103 KITCHEN NS-5b

NS-12 13

45 1

1 UNDER CABINET

W/ "EM" UNIT

104 PANTRY NS-11 13 1

105 NS-11 13 1COMM RM

BATH ROOM NS-8

NS-9

1 CEILING SURFACE

WALL MOUNTED ABOVE THE MIRROR TOP106

CEILING RECESSED

1NS-7a 45

111 MECH/ELEC ROOM

EXIT SIGN

EXTERIOR LIGHT

EXTERIOR LIGHT

- NS-3

NS-13

10 SEE DRAWING E-15 FOR DETAIL10 BOLLARD TYPE

4.99

CEILING SURFACE

WALL MOUNTED

1EXTERIOR LIGHT- NS-10 22 WALL MOUNTED

CEILING SURFACE

NS-7b 45 1 CEILING SURFACE

107 NS-9 18 1LINEN

108 13 1STOR

109 BED ROOM NS-5a

NS-5b

NS-11 13

45 1

W/ "EM" UNIT

110 NS-11 13 1CLOSET

NS-11 CEILING RECESSED

W/ "EM" UNIT

ABOVE THE DOOR TOP

(LIVING ROOM, OFFICE SIDE)

UNDER THE CANOPY

ABOVE THE DOOR TOP (MECH ROOM SIDE)

NS-5b 45 1 W/ "EM" UNITCEILING RECESSED

NNSC

REPAIR BUILDING S-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-5

HDRA

"WP"

"WP"

NEW GROUND FL POWER PLAN

P-5

P-6

P-7

P-8

P-9

P-11

P-13

P-14

P-15

P-16

P-17

P-18

C-4

C-3

C-1C-2

ROOM

MECH/ELEC

OFFICE

(NIC)

REF

KITCHEN

PANTRY

BATH

LINEN

STOR 110

CLOSET

BED ROOM

LIVING ROOM

(NIC)

"P"

* ADDITIONAL LEGEND(THIS SHEET ONLY)

RA

GROUNDING TYPE) W/PLUG

SINGLE RECEPTACLE (2P-3W-20A-125V

GROUNDING TYPE) W/CORD-SET

FOR RANGE HOOD FAN(1PH-115V-2.0A)

AND LIGHT(1PH-120V-75W)

HD

(MH : +1500mm TO TOP OF RCPT)

CIRCUIT INTERRUPTER TYPE,WEATHER PROOF

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND FAULT

DUPLEX RECEPTACLE

(2P-3W-20A-220VAC, GROUNDING TYPE)

(KOREAN RECEPTACLE)

DUPLEX RECEPTACLE

(KOREAN RECEPTACLE)

"WP"

"WP"

1PH-120/208V-50A

SINGLE RECEPTACLE

GROUNDING TYPE

QUAD RECEPTACLE, 2P-3W-20A-125VAC

DUPLEX RECEPTACLE, 2P-3W-20A-125VAC

GROUNDING TYPE

DUPLEX RECEPTACLE (2P-3W-20A-125VAC)

GROUND FAULT PROTECTED

GROUNDING TYPE

SINGLE RECEPTACLE, 2P-3W-20A-125VAC

(2P-3W-20A-220VAC, GROUNDING TYPE, WEATHER PROOF)

"WP"

SCALE :

NEW GROUND FL POWER PLAN

1/50

"C"

COMM RM

"WP"

P-10 P-12

P-22

NNSC

REPAIR BUILDING S-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-6

FOR MECHANICAL SYSTEM

NEW GROUND FL POWER/CONTROL PLAN

CLOSET

BED ROOM

BATH

LINEN

(NIC)

(NIC)

(NIC)

REF

KITCHEN

COMM RM

PANTRY

STOR

(NIC) (NIC)

(NIC)

(NIC)

(NIC)

FEC

OFFICE

101 LIVING ROOM

T

HPU

HPU

T

HPU

T

EH

SAC

O A

S A

E A

R A

EF

EWH

ROOM

MECH/ELEC

"P"

"C"

"MP"

EH

RH

1 POWER:2.0 AMPS, 120V, 1PH, (MECH ITEM)

RANGE HOOD

SINGLE RECEPTACLE (2P-3W-20A-240VAC,

* ADDITIONAL LEGEND(THIS SHEET ONLY)

GROUNDING TYPE) FOR INDOOR HEAT PUMP UNIT

2KW, 208V, 1PH, (MECH ITEM)

ELEC. UNIT HEATER

HPU

40W, 208V, 1PH (MECH ITEM)

INDOOR SPLIT SYSTEM HEAT PUMP UNIT

HPU

79W, 208V, 1PH (MECH ITEM)

INDOOR SPLIT SYSTEM HEAT PUMP UNIT

HPU

199W, 208V, 1PH (MECH ITEM)

INDOOR SPLIT SYSTEM HEAT PUMP UNIT

ERV

176W, 220V, 1PH, (MECH ITEM)

ENERGY RECOVERY VENTILATION UNIT

SAC

15 AMP MOP 220V, 1PH, (MECH ITEM)

SPLIT AIR CONDITIONING

9KW 208 V, 1 PH,

ELECTRIC HOT WATER HEATER

OHPU OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT

25.4 AMP MCA / 40 AMP MOP 208 VOLTS, 1 PH, (MECH ITEM) 1

EF

0.03 HP, 115V, 1PH (MECH ITEM)

FANS

EF

0.02 HP, 115V, 1PH (MECH ITEM)

FANS

EWH

EUH

OHPU

ERV

EF

1,500W, 12AMP 120V, 1PH, (MECH ITEM)

ELECTRIC WALL HEATER

M D

J

C

B

C

J

AT BATH ROOM

CONNECT TO LIGHT SWITCH

A

MP-4

MP-6

MP-3

A

C

B

MAGNETIC MOTOR STARTER, 2P-120V

NEMA SIZE "00" W/O.L RELAYS,

PILOT LAMP(GREEN), AND 3-POSITION

SELECTOR SWITCH (H-O-A)

NEMA 1 ENCL

NON-FUSIBLE, NEMA 3R ENCL

FOR SAC

SAFETY SWITCH, DPST, 240V, 30A

SAFETY SWITCH, DPST, 240V, 60A

SAFETY SWITCH, DPST, 240V, 30A

FOR ERV-1

NON-FUSIBLE, NEMA 3R ENCL

FOR OHPU

SCALE :

NEW GROUND FL POWER/CONTROL PLAN FOR MECHANICAL SYSTEM

1/50

P-20

P-21

C-6

P-23

J

MP-5

EUH

STRUCTURE SUPPORT

NON-FUSIBLE, NEMA 1 ENCL ABOUT CEILING W/ STEEL

NNSC

REPAIR BUILDING S-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-7

WP

M F

WP

M F

F

SB

F

F T R

F M

C P

* ADDITIONAL LEGEND (THIS SHEET ONLY)

COMBINED ADDRESSABLE FIRE ALARM/

MASS NOTIFICATION CONTROL PANEL,

24VDC, BUILT-IN ADDRESSABLE POINTS

MODULES AS REQ'D, PROGRAMMABLE

MODULE & RELAYS LCD ANNUNCIATOR,

SYNCHRONIZATION CONTROL MODULE,

POWER SUPPLY, DIGITAL VOICE MODULE,

MICROPHONE, BATTERY, BATTERY CHAREGER,

POWER MODULES PANEL(AS REQ'D) AND

DIGITAL VOICE PANEL W/AMPLIFIER & BACK

UP AMPLIFIER (AS REQ'D) & MICROPHONE,

NEMA 1 ENCL

FMCP

ADDRESSABLE MANUAL PULL STATION

SPEAKER (WATTAGE AS REQ'D)

FIRE ALARM/MASS NOTIFICATION

WALL MOUNTED "WP" TYPE,

SHALL BE DE-RATED AS REQUIRED)

(75 CANDELA MINIMUM, AMBER STROBE

W/WORDS "ALERT") VISUAL SIGNAL STROBES

W/WORDS "FIRE" + MNS-AMBER STROBE

AS REQ'D)/COMBO. (FA-CLEAR STROBE

WALL MOUNTED SPEAKER (WATTAGE

SHALL BE DE-RATED AS REQUIRED)

(15 CANDELA MINIMUM, AMBER STROBE

W/WORDS "ALERT") VISUAL SIGNAL STROBES

W/WORDS "FIRE" + MNS-AMBER STROBE

AS REQ'D)/COMBO. (FA-CLEAR STROBE

WALL MOUNTED SPEAKER (WATTAGE

WP

M F

F

ADDRESSABLE SMOKE DETECTOR

ADDRESSABLE SMOKE DETECTOR

W/SOUNDER BASE

TAMPER SWITCH W/ADDRESSABLE

MODULE (UNDER MECH ITEM)

PRESSURE SWITCH W/ADDRESSABLE

MODULE (UNDER MECH ITEM)

SB

TS

PS

FTR BUILDING TRANSMITTER

NEW GROUND FLOOR FIRE ALARM/MASS NOTIFICATION SYSTEM PLAN

SCALE :

"P"

NOTIFICATION SYSTEM PLAN

NEW GROUND FLOOR FIRE ALARM/MASS

P-19

ROOM

MECH/ELEC

OFFICE

(NIC)

(NIC) (NIC)

REF

KITCHEN

PANTRY

COMM RM

BATH

LINEN

STOR 110

CLOSET

BED ROOM

LIVING ROOM

(NIC)

(NIC)

(NIC)

FMCPTO

FMCPTO

F

TSTS

JJ

F/M

F /M

F /M

F/M

F /M

F F

FF

F

F F F

F

F

TS

J

PS

J

1/50

NNSC

REPAIR BUILDING S-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-8

NOTES:

NFPA 72, 2013 EDITION.

PRERECORDED MESSAGES ARE IN ENGLISH AND HANGUL AT

CONTRACTOR SUBMITS SHOP DRAWINGS.

THE VOLTAGE DROP AND POWER SUPPLY CALCULATION

SHALL BE PROVIDED BY THE CONTRACTOR WHEN THE

4.

(3-FEET) FROM HVAC, HOT & COLD WATER PIPING.

ALSO CONDUITS SHALL BE RUN AWAY AT LEAST 900mmTHE FIRE ALARM SYSTEM IS CONCEPTUAL. THE

MANUFACTURER'S EQUIPMENT LISTING.

SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION

MANUFACTURER'S LISTED INSTALLATION

2.

CONTRACTOR SHALL COMPLETE DESIGN AND INSTALL

13.

12.

11.

9.

SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH

AND THE MASS MESSAGE NEEDS TO HAVE PRE ALERT

PATTERN IS REQUIRED FOR FIRE ALARM EVACUATION

VOICE EVACUATION SYSTEM IN LIEU OF TEMPORAL

ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED

ELECTRICAL AND MECHANICAL SYSTEM EQUIPMENT

COORDINATE THE EXACT DEVICE LOCATIONS WITH

SWITCHES AND NON-ADDRESSABLE INITIATION

ALL TAMPER SWITCHES, FLOW SWITCHES, PRESSURE

PROHIBITED FOR ALL IDC, NAC AND SLC.

ALL CLASS "B" EXCEPTIONS IN NFPA 72, 23.4.2.2 ARE8.

7. CLASS "B" RACEWAY OF FA SYSTEM SHALL BE

SEPARATED BY A MINIMUM OF 1220mm HORIZONTAL

10. COAXIAL CABLE SHALL BE ONE PIECE BETWEEN

3.

5.

6. THE POWER CIRCUIT NUMBER DEDICATED TO FIRE

ALARM CIRCUIT AND ROOM LOCATION OF PANEL

LETTER "FIRE ALARM CIRCUIT" ON THE DEDICATED

FIRE ALARM CIRCUIT SHALL BE IDENTIFIED BY A RED

THE FIRE ALARM/MASS NOTIFICATION SYSTEM

CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING

FIRE ALARM INTELLIGIBILITY/AUDIBILITY CALCULATION,

WIRE SIZE, CONDUIT SIZE, NO. OF WIRES FOR THE FIRE

POWER CIRCUIT BREAKER AND/OR DISCONNECT SWITCH.

SHALL BE INDICATED ON THE FIRE ALARM/MASS

BUILDING TRANSMITTER AND ANTENNA.

AND 305mm VERTICALLY.

DEVICES SHALL BE PROVIDED WITH CLASS "B"

THE SYSTEM FOR READY TO USE. THE NUMBER OF

DEVICES SHOWN IS THE MINIMUM REQUIRED AND THE

FINAL QUANTITY SHALL BE IN ACCORDANCE WITH THE

DEVICE LOCATIONS IN ACCORDANCE WITH THE

AND BUILDING ARCHITECTURAL FEATURES.

OR FM APPROVED.

SPECIFICATION SECTION 28.31.76.00.31 (FA) AND

HAVE PRE ALERT TEMPORAL PATTERN MIN 2 CYCLES

PROVIDE ADDITIONAL RELAYS AS REQUIRED.14.

18.

19.

20.

PER UFC 4-021-01.

17. THE MASS NOTIFICATION SYSTEM IS CONCEPTUAL. THE

NUMBER OF DEVICES SHOWN IS THE MINIMUM REQUIRED

AND THE FINAL QUANTITY SHALL BE IN ACCORDANCE

MANUFACTURER'S EQUIPMENT LISTING.

SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION

THE MASS NOTIFICATION SYSTEM SHALL BE ENSURED THAT

LEAST FOR THE FOLLOWING ITEMS.

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES

STROBES FOR MASS NOTIFICATION SHALL BE MARKED

STROBES FOR FIRE ALARM SHALL BE MARKED "FIRE"

"ALERT" IN RED LETTER AND W/AMBER LENS.

SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH

1.

AND W/CLEAR LENS.

15.

CONTINUOUS 3-10 SECOND TONE, NFPA 72, 24.4.1.2.2

& 24.4.1.8.2.

THE MASS SYSTEM ACTIVATION MUST OVERRIDE THE FIRE

ALARM NOTIFICATION APPLIANCES THE MASS SYSTEM

ON THE PANEL BY SWITCH.

THIS SEQUENCE IS REQUIRED FOR BOTH PRE-RECORDED

MASS MESSAGE IS REQUIRED TO BE ANNOUNCED

IMMEDIATELY UNTIL SHUTDOWN MANUALLY.

SPECIFICATION SECTION 28.31.76.00.31 (MNS)

THE CONTRACTOR SHALL PROVIDE THE REQUIRED

TESTING TO ACHIEVE A MINIMUM CIS SCORE 0.8 AS

16.

DEVICE LOCATIONS IN ACCORDANCE WITH THE

MANUFACTURER'S LISTED INSTALLATION

AND NFPA 72, 2013 EDITION.

APPLIANCES UNTIL MASS ALERT IS CANCELED MANUALLY

ACTIVATION MUST OVERRIDE THE FIRE ALARM NOTIFICATION

MESSAGES AND MANUAL MICROPHONE INITIATED MESSAGES.

ARE IDENTICAL TO FIRE ALARM VISUAL APPLIANCES.

23.

MASS VISUAL APPLIANCE LOCATION REQUIREMENTS

AS SHOP DRAWING SUBMITTALS.

CONTRACT DRAWINGS SHALL NOT BE SUBMITTED

ARMY AND AIR FORCE PROJECTS.

WITH ANY FIRE ALARM VISUAL APPLIANCES ON

MASS VISUAL APPLIANCES SHALL NOT BE COMBINED24.

25.

22. FIRE ALARM SYMBOLS FROM NEPA 170 SHALL BE

AND ALL VISUAL APPLIANCES WITHIN THE SAME ROOM

ALL AUDIBLE APPLIANCES WITHIN THE BUILDING21.

SHALL BE SYNCHRONIZED.

VOICE EVACUATION SPEAKERS, NEPA 72.

AUDIBLE APPLIANCES SHALL PROVIDE THE STANDARD

TEMPORAL PATTERN UNLESS NFPA 101 REQUIRES

USED.

26. SHOW WEATHERPROOF EXTERIOR SPEAKERS AT ALL

EXTERIOR DOORS OR EXTERIOR GATHERING AREAS.

SHALL BE UL LISTED OFF-THE-SHELF-EQUIPMENT AND

ALL BACK-UP AMPLIFIERS WIRING AND ARRANGEMENT27.

SHALL BE TESTED TO THE STANDARDS OF UL OR RM AS

REQUIRED BY UFC 4-21-01, PARAGRAPH 4-4.3.

BOTH KOREAN AND ENGLISH.

THE MAN SHALL HAVE PRERECORDED MASSAGES IN28.

APPLICABLE CODE, SPECIFICATIONS AND

REQUIREMENTS AND WIRE COUNT.

ALARM AND DETECTION SYSTEM.

NOTIFICATION CONTROL PANEL COVER.

MODULES.

SYSTEM. VOICE EVACUATION MESSAGE NEEDS TO

REQUIRED.

WITH THE APPLICABLE CODE, SPECIFICATIONS AND

REQUIREMENTS AND WIRE COUNT.

OF 20% SPARE ADDRESSES FOR FUTURE USE.

FIRE ALARM SYSTEM OF EACH SLC TO HAVE A MINIMUM29.

SEE SHEET NO. E-1.

2) INTRUDER/HOSTILE PERSON SIGHTED WITHIN/AROUND THE BUILDING

1) BOMB THREAT OR ACTUAL BOMB WITHIN/AROUND THE BUILDING

3) OCCUPANTS DIRECTED TO TAKE COVER WITHIN THE BUILDING

6) "ALL CLEAR" MESSAGE

TEST8)

THE BUILDING

CARBON MONOXIDE GAS DETECTION MESSAGE WITHIN/AROUND 7)

THE LOCAL AREA

5) EMERGENCY WEATHER CONDITIONS APPROPRIATE FOR

NORMAL MAIN ENTRANCE/EXIT

4) EVACUATION OF THE BUILDING USING EXITS OTHER THAN THE

FIRE ALARM/MASS NOTIFICATION

CONTROL PANEL (FMCP)

SG

G ~

G

CONTROL PANEL & BOOSTER PANEL)

(INSTALLED BESIDE FIRE ALARM

(RATED AS REQ'D) (TYPICAL)

SURGE PROTECTOR

2#12 & 1#12(G) IN 16C

GROUND ROD, COPPER CLAD

GROUNDING SYSTEM #6, "BC" IN 21C

CONN TO BLDG ELECTRODE

STEEL, 19mmdiax3000mmLG

WITH WELDING CONNECTION AND

F

ADDRESSABLE MANUAL

PULL STATION (TYPICAL)

WALL MOUNTED "WP" TYPE,

NOTIFICATION SPEAKER

FIRE ALARM/MASS

(WATTAGE AS REQ'D) (TYPICAL)

NOT TO SCALE

ELECTRICAL

F

TS

J

101 111 102 102

F M

WP

EXT

BATTERY CHARGER, POWER MODULE PANEL(AS REQ'D)

SYNCHRONIZATION CONTROL MODULE, DIGITAL VOICE

FIRE ALARM/MASS NOTIFICATION CONTROL PANEL,

24VDC, BUILT-IN ADDRESSABLE POINTS MODULES

AS REQUIRED, PROGRAMMABLE MODULE & RELAYS,

POWER MODULE AS REQ.D LCD ANNUNCIATOR,

MODULE, POWER SUPPLY, MICROPHONE, BATTERY,

AND AMPLIFIER(AS REQ'D), NEMA 1 ENCL

SEMI FLUSH MOUNTED COMBINED ADDRESSABLE

NEW FIRE ALARM/MASS NOTIFICATION SYSTEM DIAGRAM

SYSTEM DIAGRAM

NEW FIRE ALARM/MASS NOTIFICATION

F M

WP

EXT

TO PANELBOARD P-19

F

12#14 IN 21C(FOR SIGNAL)

2#12 IN 16C(FOR POWER)

(PROGRAM OF D-21 MONACO

BUILDING TRANSMITTER

BT-XM AT LEAST 16 ZONES)

#6 "BC" IN 21C

GROUND CONDUCTOR

COAXIAL CABLE

W/CONNECTORS IN 16C

W/MOUNTING BRACKET

GROUND ROD, COPPER CLAD

WITH WELDING CONNECTION

STEEL, 19mmdia x 3000mmLG

ENCLOSURE

LIGHTNING ARRESTER

W/WEATHER-PROOF

W/BATTERY & BATTERY

CHARGER, NEMA 1 ENCL

OMNI-DIRECTION TYPE

FIRE ALARM ANTENNA

FTR

(15 or 75 CANDELA MINIMUM, AMBER STROBE

W/WORDS "ALERT") VISUAL SIGNAL STROBES

W/WORDS "FIRE" + MNS-AMBER STROBE

WALL MOUNTED SPEAKER (WATTAGE

AS REQ'D)/COMBO. (FA-CLEAR STROBE

SHALL BE DE-RATED AS REQUIRED) (TYPICAL)

SB

ADDRESSABLE SMOKE

DETECTOR

DETECTOR W/ SOUNDER BASE

ADDRESSABLE SMOKE

PS

J

W/ADDRESSABLE MODULE

PRESSURE SWITCH

FOR SPRINKLER SYSTEM

(UNDER MECH ITEM)

TS

J

TS

J

NNSC

REPAIR BUILDING S-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

NEW GROUND FLOOR LAN/TEL PLAN

E-9

LAN

T T B

"C"

* ADDITIONAL LEGEND (THIS SHEET ONLY)

LAN

TTB

NEW EQUIPMENT RACK FOR NIPR NETWORK

NEW TELEPHOE TERMINAL BOARD

SEE TELECOMMUNICATION SYSTEM DIAGRAM

SEE TELECOMMUNICATION SYSTEM DIAGRAM

DUAL MODULAR JACK, CAT-6

NIPR EQUIPMENT RACK

TO BE TERMINATED AT PATCH PANEL IN

2-4PAIR,CAT-6,#24AWG IN 27C

( TYPICAL)

ROOM

MECH/ELEC

OFFICE

(NIC)

(NIC) (NIC)

REF

KITCHEN

PANTRY

BATH

LINEN

STOR 110

CLOSET

BED ROOM

LIVING ROOM

(NIC)

RM

COMM

SCALE : 1/50

NEW GROUND FLOOR LAN/TEL PLAN

NNSC

REPAIR BUILDING S-11

EXOTHERMIC WELDING, LISTED COMPRESSION TWO-

1. THE CONNECTIONS OF THE BONDING CONDUCTOR FOR

TELECOMMUNITIONS TO THE TMGB SHALL UTILIZE

HOLE LUGS, SUITABLE AND EQUIVALENT TWO-HOLE

1#6 "BC" IN 21C

CONN TO MAIN PANELBOARD

NOT TO SCALE

STAMP FACING OUT" TO ENSURE THAT THEY CAN BE

3. TEST RESULTS WILL BE PROVIDED IAW THE MOST RECENT

REVISION OF THE ANSI/TIA/EIA-568.

4. LABEL ALL DROPS IAW TIA/EIA-606-A.

5. LABEL ALL GROUNDS IAW I3A.

LUGS ARE PREFERRED.

FIELD VERIFIED.

TO TELEPHONE PATCH PANEL

TGB

CONN TO TMGB

1#6 "BC" IN 27C

(100mm x 450mmLG x 6.4mmTHK)

GROUND BUS BAR(TGB)

TMGB

G

(TYPICAL)

CABLE SUPPORT

G

110TYPE TERMINAL BLOCK

(TYPICAL)

CROSS CONNECTION CORD AS REQ'D

PLUS 25% SPARES TO BE FURNISHED BY THE

1#6 "BC" IN 16C

G

FOR TELEPHONE

1-48PORT PATCH PANEL

AS REQ'D

PROVIDE PATCH CORDS

HUB(N.I.C)

1-48PORT PATCH PANEL

W/ RACK MOUNTED 6-SINGLE

REAR RECEPTACLE, ON-OFF

SWITCH & CORD, 2P-3W-20A-125V

GROUND BUS BAR(TGB)

TELECOMMUNICATION

TELECOMMUNICATION MAIN

PTB

CONTRACTOR

RECEPTACLES

(1-25PAIR)

ENTRANCE TERMINAL BLOCK

110 TYPE PROTECTED

G

2. "PLYWOOD WILL BE INSTALLED WITH FIRE RATED

NOTE.

SHALL BE COORDINATED WITH BASE SIGNAL COMPANY.

SYSTEM AND WIRING FOR GOVERNMENT APPROVAL. TELECOMMUNCATION WORK

6. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DETAILED TELECOMMUNICATION

1-12CORE, FIBER OPTIC CABLE IN 103C.

PATCH PANEL W/"SC" CONNECTOR

1-24 STRAND FIBER OPTIC

QUAD-PLEX RECEPTACLE

2P-3W-125V-20A GND TYPE

WITH DEDICATED CIRCUIT

(24"(W)x36"(H)x30"(D)

POWER SURGE PROTECTION

COMM RM

1-25PAIR, #24AWG TEL CABLE IN 103C.

TO EACH TEL OUTLET AS REQ'D VIA CABLE TRAY

2,200(W)x2,400(H) FIRE RATED PLYWOOD

TELEPHONE TERMINAL BOARD ("TTB"),

G

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

(100PAIR) FOR TEL

(TYPICAL)

NEW LAN/TEL SYSTEM DIAGRAM

TO EACH DATA OUTLET AS REQ'D VIA CABLE TRAY

G

TO BE TERMINATED AT FIBER OPTIC PATCH PANEL

LENGTH AS REQUIRED

CABLE TRAY 300mm(W)x(150(H)

G

G

G

"MDP" GROUNDING BUS BAR

FOR DATA

(TYPICAL)

NEW LAN/TEL SYSTEM DIAGRAM

TO PNLBD C-1

EQUIPMENT CABINET

TO PNLBD C-1 , C-2

E-10

NNSC

REPAIR BUILDING S-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-11

REF

"C"

T V

T V

TV

T V

TV

TV

CTC

9.

NOTES

1.

ACCEPTANCE INSPECTION.

dbMV LEVELS.

CONTRACTOR PRIOR TO START OF WORK.

UPON BY BASE CATV PERSONNEL, CONTRACTOR, AND ANY QUALITY

MATERIAL AND PASSIVE DEVICES TO BE USED MUST BE AGREED

COORDINATION WITH BASE CATV PERSONNEL ON THE TYPE OF CABLE

THEN, BASE CATV PERSONNEL WILL INSPECT/TEST ALL PROJECTS

ON USFK INSTALLATIONS FOR QUALITY ASSURANCE.

RESULTS WILL BE RECORDED AND AVAILABLE AT THE FINAL

CONTRACTORS WILL COORDINATE WITH BASE CATV PERSONNEL

30 DAYS PRIOR TO PERFORMING FINAL ACCEPTANCE TESTING.

RANGE FROM 5 TO 860MHZ, RETURN PATH 5-42MHZ,

TO INCLUDE ALL ATTENUATION'S TO COMPENSATE FOR

C-COR LINE EXTENDER, DIRECTIONAL COUPLERS, SPLITTERS,

AND TAP-OFF'S ARE TO BE 2WAY AND OPERATE IN THE

COORDINATE LOCATION OF "NODE EQUIPMENT" WITH BASE

BASE CATV PERSONNEL.

TAP UNITS, SPLITTERS, AMPLIFIER, COAXIAL CABLE, etc.

THE SPECIFICATION OF MATERIALS SUCH AS CATV OUTLET

CATV SYSTEM. IT SHALL BE COORDINATED WITH

SHALL BE COMPATIBLE WITH THE EXISTING BASE

2. ALL CATV MATERIAL AND EQUIPMENT MUST HAVE RETURN

PATH(2-WAY) CAPABILITIES.

3. PROVIDE DIAGONAL VENTS ON OPPOSITE SIDE OF CATV PANEL;

ONE VENT HIGH AND ONE VENT LOW.

4.

5.

6.

7. INITIAL TESTING OF CATV SYSTEM SHALL BE PERFORMED BY THE

CONTRACTOR TO MEET THE REQUIREMENT OF CATV dB.

8.

THE LOCATION OF PULL BOX WITH COUPLERS WHICH IS INSTALLED

ABOVE THE CEILING SHALL BE MARKED ON THE CEILING FOR THE

MAINTENANCE.

ASSURANCE BRANCH PERSONNEL DPW,

BASE CATV PERSONNEL PRIOR TO ORDERING.

SCALE :

NEW GROUND FL CATV PLAN

COAXIAL CABLE

RG 6/U IN 16C

(TYPICAL)

T V

NEW GROUND FL CATV PLAN

FEC

ROOM

MECH/ELEC

OFFICE

(NIC)

(NIC) (NIC)

REF

KITCHEN

PANTRY COMM RM

BATH

LINEN

108STOR

CLOSET

BED ROOM

LIVING ROOM

(NIC)

(NIC)

(NIC)

1/50

TV WALL MOUNTED TYPE TV OUTLET

W/"0.0"dB LOSS FACE PLATE & F-81 BARREL TYPE CONNECTOR

* ADDITIONAL LEGEND(THIS SHEET ONLY)

RG 11/U IN 21C

(TYPICAL)

CEILING) (TYPICAL)

(MH:+450mm BELOW

TYPE CONNECTOR

PLATE & F-81 BARREL

W/"0.0"dB LOSS FACE

TV OUTLET

WALL MOUNTED TYPE

COAXIAL CABLE

DEVICES BY COORDINATING WITH BASE CATV COMPANY.

CONNECTION POINT AND PROVIDE CATV CABLE, CONNECTION

CONTRACTOR SHALL VERIFY EXIST EXTERIOR CATV LINE

NEW O/H CATV CABLE, RG-11/U W/ MESSENGER WIRE,

ON CATV CABINET TO ENSURE

NEW CATV DISTRIBUTION CABINET

INCLUDING NEW 2-WAY SPLITTER,

TRUNK BRIDGE AMPLIFIERS W/RETURN PATH

CAPABILITIES, LOCKING DEVICE AND

AIR VENTS SHALL BE INSTALLED

ADEQUATE VENTILATION IN COMM RM

NEMA 1 ENCL

NNSC

REPAIR BUILDING S-11

G

AMP

1st FL

ROOF

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

TV

TV

TV

TVTV

TV

RG 11/U IN 21C

COAXIAL CABLE

(TYPICAL)

NEW GROUND FL CATV DIAGRAM

NOT TO SCALE

NEW GROUND FL CATV DIAGRAM

TV

101 102

E-12

(TYPICAL)

DEVICE IS LOCATED

ROOM NO WHERE

COAXIAL CABLE

RG 6/U IN 16C

(TYPICAL)

W/ 8-WAY TAP-OFF AND LOCKING

PULL BOX (300 x 300 x 200D)

DEVICE ABOVE CORRIDOR CEILING

(5-1000MHZ) (TYPICAL)

(2P-3W-20A-125VAC,

NEW DUPLEX RECEPTACLE

GROUNDING TYPE)

FOR CATV AMPLIFIER

TO PNLBD "C-4"

NEW SINGLE RECEPTACLE

(2P-3W-20A-250VAC,

GROUNDING TYPE)

FOR CATV AMPLIFIER

TO PNLBD "C-3"

ADEQUATE VENTILATION IN COMM RM

ON CATV CABINET TO ENSURE

NEMA 1 ENCL

AIR VENTS SHALL BE INSTALLED

CAPABILITIES, LOCKING DEVICE AND

TRUNK BRIDGE AMPLIFIERS W/RETURN PATH

NEW CATV DISTRIBUTION CABINET

INCLUDING NEW 3-WAY SPLITTER,

NEW GROUNDING WIRE

CABINET AT HIS OWN COST.

INSTALLATION AND PROVIDE APPROPRIATE CATV LINE TO NEW CATV DISTRIBUTION

CONTRACTOR SHALL COORDINATE WITH LG U+ FOR EXTERIOR CATV LINE

NOTES

1.

NEW ENTRANCE CAP

& SECOND RACK

ON EXTERIOR WALL

EXTERIOR

NEW O/H CATV CABLE

C T

V

COAXIAL CABLE

RG 11/U IN 21C

NNSC

REPAIR BUILDING S-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-13

ELECTRICAL

NOT TO SCALE

OUTDOOR

INDOOR

200AT

225AF

100AF

3P

3P

3P 2P

100AF

1P

CONDUCTOR, #3/0(G) IN 21C

NEW GROUNDING

CU BUS, 400A

22,000AIC SYM

G

S/NGND

100AF

321 5

2P

100AF

2P

20AT

100AF

FOR ABBREVIATION, LEGEND, GENERAL NOTES1.

& SCOPE OF WORK,

NOTES

"P"

EXT

SURGE SUPPRESSOR

TRANSIENT VOLTAGE

NEMA 1 ENCL

OHPU

1WAY: SPARE W/PULL WIRE & CAP

PVC CONDUIT

NEW U/G SEC LINE, 2WAY OF 103dia

CT BOX W/CT'S

200/5Ax3EA

NEMA 3R ENCL WHM

W/NEW ADVANCED DIGITAL WATTHOUR

METER, TRANSFORMER TYPE

WITH 15 MINUTES DEMAND REGISTER

FOR 3PH, 4WIRE, 120/208V, 60Hz

NEMA 3R ENCL

REPLACE THE DETERIORATED EXISTING WHM

1P

20AT

100AF

SPARE

1P

20AT

100AF100AF

50AT 60AT 50AT

A

IN 35C

3#6&

1#8

SEE SHEET NO. E-1.

EXIST/NEW POWER ONE-LINE DIAGRAM

"C"

3 100 22000

TOTAL LOAD

LOAD

TOTAL

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

CIRCUIT BREAKER

PHASE LOAD

A B PC AT

SIZE

AF AIC

B CA N G

REMARK

MTD TYPE, NEMA 1 ENCL.

3PHASE ,4WIRE, 120/208V,

SPARE

59716

4500 4500

PANELBOARD "C"

60HZ, SN & GND, SURFACEPANELBOARD "MP" LOAD SCHEDULE

19272 22877 18280

MAIN 3P-225AF-200AT CIRCUIT BREAKER

4#2&1#8(G)

4#2 &

IN 53C

1#8(G)

4#8 &

IN 35C

1#10(G)

TOTAL DEMAND LOAD ; 48060 (VA)

NEW

2#12&1#12(G)

1P

20AT

100AF

1P

20AT

100AF

SPARE

NEW PANELBOARD "MP" LOAD SCHEDULE

EXIST/NEW POWER ONE-LINE DIAGRAM &

1WAY: 4-3/0

26852

9300 3650 3150 2500

48124160

100AT

A

PANELBOARD "P"

ELECTRIC HOT WATER HEATER 9000

2000 1000ELECTRIC UNIT HEATER-1 1000

SPARE

SPARE

SPARE

SPARE11

4#8&1#10(G)

2#8&1#10(G)

4#3/0 & 1#2(G)

4-3/0 & #2(G)IN 103C.

NON-FUSIBLE, NEMA 3R ENCL

SAFETY SWITCH, 3PST, 240V, 60A

TVSS

CONNECT NEW U/G SEC. LINE

ACCESSORIES (SEC. RACKS, ETC.)

TO EXIST SEC. LINE WITH ASSOCIATED

EP1EXIST ELEC POLE /

EP1

FOR OHPU

* ADDITIONAL LEGEND(THIS SHEET ONLY)

9362 9271 8280

SPACE SPACE

SPACE SPACE

SPACE SPACE

10001000

2#12&1#12(G)

100 100WALL EXHAUST FAN-1

20AT

EF

EUH

111111

EWH

DOMESTIC ELECTRIC HOT WATER HEATER

ELEC. RATING : 9KW, 208V, 1PH, 60Hz

0.017HP, 115V, 1PH, 60Hz

ELECTRIC UNIT HEATER

EXISTING MAIN PANELBOARD

WITH NEW MAIN PANELBOARD "MP"

REPLACE THE DETERIORATED

1P

20AT

100AF

SPARE

POWER: 1PH-208V, 25.4 AMP MCA, 40 AMP MOP

OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT

(UNDER MECH ITEM)

EXHAUST FAN

ELEC. RATING : 2KW, 208V, 1PH, 60Hz

EXTERIOR

2#8&1#10(G)

2#12&1#12(G)

"LC"

SW IN NEMA 3R ENCL

120V, COIL HAND-OFF-AUTO SEL.

MECHANICALLY HELD CONTACTS,

W/ 4P,20A,12OV, N.O.

NEW LIGHTING CONTRACTOR "LC"

HEAT PUMP UNIT

OUTDOOR SPLIT SYSTEM

3#6&1#8(G)

NNSC

REPAIR BUILDING S-11

TAK, YS

297038

LIGHTS 10W x10, 22Wx3, 100Wx2

LIGHTING CONTACTOR

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-14

ELECTRICAL

5001000

RCPT FOR CATV EQUIPMENT

TOTAL LOAD 31503650 2500

LOAD

TOTAL

PANELBOARD "C" LOAD SCHEDULE

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

3PHASE ,4WIRE, 120/208V,

60HZ, SN & GND, SURFACE

MTD TYPE, NEMA 1 ENCL.

CIRCUIT BREAKER

1000 1000 1

PHASE LOAD

A B PC

20100 10000

AT

SIZE

AF AIC

B CA N G

REMARK

2#12&1#12(G)

TVSS

11000

COMM RACK

RCPT FOR TTB

RCPT FOR CATV EQUIPMENT

SPARE

MAIN 3P-100AF-50AT CIRCUIT BREAKER

4#10&1#10(G)

SPACESPACE

SPACESPACE

SPACESPACE

SPACE - - - - - - - - -

SPACE - - - - - - - - -

SPACE - - - - - - - - -

SPACE - - - - - - - - -

SPACE - - - - - - - - -

3 30

SPARE 1000 1000

4#8 & 1#10(G)

TOTAL DEMAND LOAD ; 6600(VA)

1 100 10000 2#12&1#12(G)

TOTAL LOAD 26852

LOAD

TOTAL

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

CIRCUIT BREAKER

PHASE LOAD

A B PC AT

SIZE

AF AIC

B CA N G

REMARK

MTD TYPE, NEMA 1 ENCL.

3PHASE ,4WIRE, 120/208V,

129 20

9 10

20 21

RCPTS 180VA x4EA

TOTAL DEMAND LOAD ; 19896 (VA)

60HZ, SN & GND, FLUSH

4#2 & 1#8(G)

RCPTS 180VA x4EA

RCPTS 180VA x4EA

RCPTS 180VA x1EA

MAIN 3P-100AF-100AT CIRCUIT BREAKER

LIGHTS LED 45W x2EA, 13W x3EA

RANGE HOOD

RCPTS 360VA x1EA

RCPTS 360VA x4EA

RCPTS 360VA x4EA

RCPTS 360VA x4EA 720

PANELBOARD "P" LOAD SCHEDULE

2#8&1#10(G)

2#12&1#12(G)

SCHEDULE

NEW PANELBOARD "P" & "C" LOAD

4.99W

4.99W

18Wx4EA, 13Wx1EA LIGHTS LED 45W x4EA, 22Wx1EA, REF, RCPTS 180VA x1EA 740 740

RCPTS 180VA x1EA

MICROWAVE

2325032506500ELEC RANGE

RCPTS 180VA x3EA 540

FIRE ALARM SYSTEM 500 500 DEVICE

LOCKING

HEAT PUMP UNIT

INDOOR SPLIT SYSTEM

VENTILATION UNIT

ENERGY RECOVERY

ELECTRIC WALL HEATER

SPARE

SPARE

180 180

1000 -

180 180

20 20

88 88

2#12&1#12(G)

9362 9271 8280

8SPLIT AIR CONDITIONING 3300 1650

2#12&1#12(G)

SPACE - - - - -

RCPTS 360VA x1EA 360 180 180

LIGHTS LED 50W x6EA, LIGHTS LED 50W x5EA, OUTDOOR BOLLARD

RCPTS 180VA x1EA

RCPTS 360VA x1EA

OUTDOOR BOLLARD

SPARE

29 SPARE 1000 1000

30 SPARE 1000

28 29

30 31

31 SPARE 1000

SPACE SPACE

11000

NNSC

REPAIR BUILDING S-11

LED EXTERIOR LIGHT 2-AWG#8 & 1-10(G) IN 27C.

NEW U/G CONCRETE ENCASED FOR BOLLARD

(NIC)

(NIC)

(NIC)

REF

(NIC)(NIC)

(NIC)

(NIC)

(NIC)

T-11

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-15

G N

C

OFF

AUTO

H

TO EXTERIOR LIGHTS (TYP)

WIRES

CONTROL

#14 AWG

FACING NORTH

2000W, 120V, ORIENTED

PHOTOELECTRIC CELL

SW IN NEMA 3R ENCL

120V, COIL HAND-OFF-AUTO SEL.

MECHANICALLY HELD CONTACTS,

W/ 4P,20A,12OV, N.O.

NEW LIGHTING CONTRACTOR "LC"

1/100SCALE:

NNSC

REPAIR BUILDING S-11

TAK, YS

297038

KS CERTIFIED, YONGKYONG LIGHTING OR APPROVED EQUAL

IP65 RATED, CAST, EXTRUDED ALUMINUM, 150(W)x1000(H)x150(D)

OPERATING TEMP: -20 TO 50 degC.

MIN EFFICIENCY: 110LM/W,

IES TYPE 2, CCT 3000K,

INPUT POWER: FREE VOLTAGE IN 120V TO 277 VAC RANGE

BOLLARD 10W LED EXTERIOR LIGHT, SYSTEM

TREATMENT

SEWAGE

LL

LL

L

L

L

L L

SEE DETAILS IN THIS DRAWING

NEW LIGHTING CONTACTOR "LC" WITH PHOTO CELL

NEW EXTERIOR BOLLARD LIGHT

SEE DETAILS IN THIS DRAWING

(TYPICAL OF 10EA)

G

TOP VIEW

WARRANTY: 10YEARS

MOUNTING ARM AND ACCESSORIES

IP66 RATED DIECAST ALUMINUM HOUSING,

OPERATING TEMP: -20 TO 50 degC.

MIN EFFICIENCY: 110LM/W,

IES TYPE 2, CCT 5700K,

SURGE PROTECTION: 10 KV,

OR 120/208/277 VAC MULTI-TAP.

INPUT POWER: FREE VOLTAGE IN 120V TO 277 VAC RANGE

UL LISTED. COLOR: DARK BRONZE

POLE MOUNTED 100W LED EXTERIOR LIGHT, (TYPE NS-A)

CONDUIT COUPLING

CONDUIT

STEEL WITH WELD

GROUND ROD,

19 diax3000 LG

COPPER CLAD

27 dia PVC

3000 PSI IN 28 DAYS

CONCRETE FOUNDATION

#6 "BC"

GROUT UNDER

CONDUIT

27 dia STEEL

ENTIRE BASE ANCHOR BOLTS, 19dia x 915LG

GL

HANDHOLE (76mmx127mm)

BASE W/COVER

PROJECTION

GROUND WIRE

ANCHOR BOLT

AND #6 "BC"

GROUND LUG

4.8mm THICK

4"X4" SQUARE

ANCHOR BOLT

POLE BASE

BASE COVER, 244dia

(DARK BRONZE)

ALUMINUM SQUARE STRAIGHT POLE

L L

L

MP8

M P -8

NEW U/G SEC LINE

NEW POLE MOUNTED LIGHT

SEE DETAILS IN THIS DRAWING

(TYPICAL OF 2EA)

NEW 2#8 & 1#10(G) IN 27dia C.

EXIST/NEW EXTERIOR LIGHTING PLAN

EXIST/NEW EXTERIOR LIGHTING PLAN

(KOREAN RECEPTACLE)

CIRCUIT INTERRUPTER TYPE,WEATHER PROOF

2P-3W-20A-220VAC, GROUND FAULT

OUTDOOR BOLLARD FOR DUPLEX RECEPTACLE,

"WP"

"WP"

U/G

U/G

CONNECT TO "P-25" IN PANEL BOARD "MP"

2-AWG#10 & 1-12(G) IN 21C. /

OUTDOOR BOLLARD RECEPTACLE

NEW U/G CONCRETE ENCASED FOR

CIRCUIT INTERRUPTER TYPE,WEATHER PROOF

2P-3W-20A-125V, GROUND FAULT

OUTDOOR BOLLARD FOR DUPLEX RECEPTACLE,

CONNECT TO "P-24" IN PANEL BOARD "MP"

2-AWG#10 & 1-12(G) IN 21C. /

OUTDOOR BOLLARD RECEPTACLE

NEW U/G CONCRETE ENCASED FOR

14.45

H S

S

H S

S

H S

S

S C 1

S C 1

S C 1

S C

S C

S C

S C

S C

S C

0 S

C

A 1

A 1

A 1

A 1

A 1

A 1

A 1

N M

S C

A 2 A 2

A 2 A 2

A 2

F L

F L

F L

B D

A

H S

T

H S

T

H S

T

B D 2

B D 2

B D 2

B D 2

B D 2

B D 2

B D 2

B D 2

B D 2

B D 2

N N

E

E

G P 1

G P 1

K

K

K

K

K

K

K

K

K

U

X

S C

S C

S C

T L

T L

T L

K P

N M

V

K

K

K

K

H S

T

H S

T

H S

T

G D 2G

D 2

G D 2

G D 2

J

IB

G D

P O

L

B D 0

P E

N M

V 1 V 1

Y 1

Y 1

Y 1

N M

A 3

A 3

X

X

X

X

X

X

A 4

A 4

U 4

U 4

U 4

U 4

U 4

U 4

V 4

V 4

V 4

V 4

N M

B A

L B

W M

P

IP

E

P

IP

E

P

IP

E

P

IP

E

P U

M P

P

U M

P

B D 3

W P

H S

F S 4

F S 4

CP

CP

S-39

C P

C P

N N

S C

S C

S C

S C

S C

S C

S C

S C

S C

A 1

A 1

A 2

A 2

A 2 A 2

A 2

A 2 A 2

A 2 A 2

A 2 A 2

A 2

A 2

A 2

S C

S C

S C

L

K P

S C

E

E

E

E

X

X

X

X

X

X

N N

N N

G P 1

M J

B D

A

B D

R

B D

R

B D

R

B D

R

N A

N

N A

N

N A

N

N A

N

N A

N

N A

N

N A

N

N A

N

N A

N

G D 2

G D 2

B D 1

B D 1

G D

R

G D 1

G D 1

J

J

R

R

H S

T

H S

T

H S

T

K

N N

N N

O

IL

O

IL

O

IL

O

IL

O

IL

C C 1

G D 0

G D 0

G D 0

G D 0

G D 0

G D 0

J O

J O

J O

N A

N

N A

N

N A

N

N M

B D 0

B D 0

B D 0

B D 0

B D 0

B D 0

B D 0

B D 0

B D 0

S C 0

S C 0 S C 0

S C 0

K P

P

IP

E

X

H S

T

H S

T

H S

T

T L

U 1

U 1

V 1

V 1

U

X

X

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

M B

M B

R

R

R

R

M M 1

M M 1

M M 1

M M 1

M M 1

M M 1

M M 1

M M 1

H S

T

H S

H S

T

U

X

X

U

X

X

U 2

U 2

G D 3

G D 3

G D 3

B D 3

B D 3

B D 3

B D 3

V 3

V 3

N N

T R

T R

T R

T R

T R

T R

T R

T R

T R

U 3

U 3

U 3

R B

D

K

K

K

K

K

R

R

B D 4

B D 4

B D 4

B D 4

B D 4

B D 4

B D 4

B D 4

B D 4

B D 4

B D 4

N A

N

N A

N

N A

N

N A

N

N A

N

G D 4

G D 4

G D 4

S C

S C

S C

F L

F L

F L

J

IB

H S

T

F

B D

Y

N M

B D 5

B D 5

A 5

A 5

A 5

A 5

A 5

A 5

A 5

G D 5

G D 5

G D 5

G D 5

G D 5

H S

T

H S

T

V 7

V 7

V 7

V 7

A 7

A 7

A 7

A 7

A 7

B D 7

B D 7

V

Y 7

Y 7

Y 7

Y 7

Y 7

Y 7

G D 7

G D 7

G D 7

G D 7

C 7

C 7

C 7

N A

N

N A

N

N A

N

N A

N

H S

T

U

A 8

A 8

A 8

A 8

A 8

B D 8

B D 8

B D 8 B

D 8 B

D 8

Y 8 Y 8

Y 8

G D 8

G D 8

G D 8

G D 8

H S

T

N A

N

N A

N

8N A

N

V 8

V 8

E V

B O

N G

A

G O

IL

T A

N K

T

A

G

O

IL

T A

N K

A/

G OI

LT

ANK

T

T

N N

C P

D 2

V 1

D 3

A 1

A 1

F S 1

K P

M B

M B

C 1

Y 2

Y 2

Y 2

S C

S C

S C

S C

S C 2

S C 2

S C 2

S C 2

V 2

V 2

N M

A 2

A

C P

C P

C P

C P

A .C

P

A V

E D

R

O A

D

F F

E

.4

S

A .C

P

A V

E D

R

O A

D

A .C

P

A V

E D

R

O A

D

C O

V E

R E

D

C O

N C

D

IT

C H

S T

O N

E

O

P E

N

C

O N

C

D

IT

C H

B U

N K

E R s

T R

S C

B D 8 B

D 8 B

D 8

B D 8

B D

B D 8

B D

G D 8

G D 8

N A

N

8N A

N

V 8

C 9

G P 9

G P 9

C C

A 1

A 1

A 1

A 1

A 1

A 1

A 1

A 1

A 1A 1

W P

W P

A 2 A 2

A 2

A 2

H S

T

H S

T

H S

T

H S

T

H S

T

H S

T

H S

T

H S

T

T R

N M

N M

N M

N M

V 1

V 1

V 1

V 1

E

E

E

A C

F L

F L

T R

T R

T R

H S

X

X

X

M B

M B

0P

P

V 2

S C

V

S C

V

F S 1

Y 2

Y 2

Y 2

Y 1

N N

N N

N N

V 4

V 4

V 4

V 4

V 4

N N

A 4

A 4

A 4

A 4

A 4

A 4

N M

N M

N M

V Y 3

H T 1

Y

H T

U

U

V Y

N M

N M

N M

S

IL

S

IL

S

IL

0S

IL

U

U

J

IB

T R

5U

V 5

V 5

B D 5

B D 5

B D 5

B D 5

B D 5

B D 5

B D 5

B D 5

B D 5

B D 5

P P

B S

0B S

L

L

L

L

L

G D 5

G D 5

G D 5

G D 5

D U

D U

B D 6

B D 6

B D 6

B D 7

B D 7

G D

G D

B D 8

B D 8

B D 8

N M

N M

B D 9

B D 9

B D 9

B D 9

B D 9

B O

N G

B O

N G

CP

CP

CP

CP

C C

T-7

S

W

C B

EXIST AC PAVEMENT

S

S -3

CP

C B

CP

C O

N

TAIN

ER

BO

X

C O

N

TAIN

ER

BO

X

WP

.4

F N S

H F

L

L

FNSH FL EL 53.65

T-10

ROOM

MECH

W

A 2 A 2

A 2

GENERATOR

C P

C P

T -1

F F

E

.6

C O

N 'C R

ETAIN

IN

G W

ALL

S H

E D

S C

S C

S C

S C

0 S

C

49.713

B D 2

49.486

B D 2

49.269

B D 2

B D 2

B D 2

E

X

S C

S C

S C

49.696

T L

48.589

K P

N M

V

K

K

K

K

P E

N M

.4

V 1 1

CP

S C

S C

A 8

B D 8

B D 8

B D 8

B D 8

G D 8

N A

N

V 8

E V

S T

O N

E

O

P E

N

C

O N

C

D

IT

C H

B D 8

B D 8

G D 8

N A

N

V 1

V 1

E

B D 5

CP

49.51

50.51

50.42

K

P E

S C

A 8

B D 8

B D 8

V 1

F F

E

.8

T

T

F F

E

.9

G A

L T

S

S

M E

C H

B

L D

G S

Y S T

T R

E A T

M E

N

S

W A

.6

.8

.9

.9

.7

DOWN

S

Y S T

E A T

M E

W A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

0 3m 12m

1:300SCALE

EXIST/NEW EXTERIOR ELECTRICAL PLAN

U/G

U/G

U/G

U/G

C

C

C

C

S

U/G

L

ELECTRICAL

U/G

C

E-16

D 0D

D

N

IC

N

IC

N

IC

R E F

N

IC

N

IC

N

IC

N

IC

N

IC

T -1

E P

S Y S T

E A T

M E

W A

6m

WHML

A

N

CP

U /G

U /G

S

T E L E

C O

M M

O /H

O /H

O /H

O /H

O /H

O/ H

O/H

O /H

O /H

O /H

O /H

O /H

O /H

O /H

O /H

O /H

O /H

S

S

S

S

S

S

S

S

S

S

NOTES

EXTERIOR AND INTERIOR TELECOMMUNICATION SYSTEM INCLUDING UNDERGROUND

TELECOMMINCATION LINE DISTRIBUTION PLAN TO MEET SITE CONDITION.

2. CONTRACTOR SHALL BE RESPOSIBLE TO VERIFY EXISTING SITE CONDITION AND

SYSTEM, FIBER OPTIC CABLE AND TELEPHONE CABLE AND PROVID SHOP DRAWING FOR

3. TO INSTALL TELECONNUNICATION LINE, ACTUAL ROUTE OF TELECOMMUNICATION LINE AND

TYPE OF CABLE SPLICE KITS SHALL BE COORDINATED WITH SIGNAL COMPANY THRU COR.

ARE ESTIMATED FOR BIDING PURPOSE ONLY. CONTRACTOR SHALL BE RESPONSIBLE TO

PROVIDE ACTUAL O/H AND U/G CABLING TO MEET SITE CONDITION AT HIS OWN COST.

TELECOMMUNICATION SYSTEM SUCH AS EXISTING TELEPHONE PEDESTAL, TELECOMMUNICATION

1. EXTERIOR TELECOMMUNICATION LINE AND SECONDARY POWER LINE SHOWN ON THIS DRAWING

NEW U/G SEC LINE

NEW 2#8 & 1#10(G) IN 27dia C.

CABLE IN NEW FABRIC INNER DUCT 4x3" IN 103dia C, U/G DUCT FOR UNCMAC NETWORK

NEW U/G 1-12 CORE STRAND SINGLE MODE FIBER OPTIC

NEW O/H SEC LINE

NEW 4#1/0 "WP"

(TYPICAL)

NEW O/H SEC LINE

NEW 4#3/0 "WP"

(TYPICAL)

U ./G

U ./G

U ./G

U ./G

U ./G

U ./G

U ./G

C

C C

C

C

C C

FIRE ALARM SYSTEM AT FIRE PUMP.

TO NEW FIRE ALARM SYSTEM AT S-11 FROM EXIST

MODULES FOR EACH END, TO BE CONNECTED

2-AWG#10 IN 35C, 4SETS OF ADDRESSABLE

NEW U/G SIGNALING LINE CIRCUITS,

NEW O/H SEC LINE

(TYPICAL)

(TYPCIAL)

FIBER OPTIC CABLE/CATV CABLE ETC. WITH MESSENGER WIRE

FOR NEW O/H SEC. LINE AND MOUNTING ACCESSORIES FOR

PROVIDE NEW SEC. RACKS (4 SPOOLS)

EXIST ELECTRIC POLE/

TELEC

O

M M /C

ATV

TELECO

M

M

/CATV

TELEC

O

M M /C

ATV

TELECO

M

M

/CATV

TELECO

M

M

/CATV

TE

LE

COMM/

CAT

V

C A T

V O /H

O /H

CP1

CP2

CP3

CP4

CP5

CP6

NEW 4#1/0 "WP" FROM CP1 TO CP6

CLOSURE 12CORE

NEW FIBER OPICE SLPLICE

(TYPICAL)

CABLE "WP" AND CATV CABLE WITH MESSENGER WIRE

NEW O/H 1-12 CORE STRAND SINGLE MODE FIBER OPTIC

(TYPICAL)

CABLE "WP" AND CATV CABLE WITH MESSENGER WIRE

NEW O/H 1-12 CORE STRAND SINGLE MODE FIBER OPTIC

(TYPICAL)

CABLE "WP" AND CATV CABLE WITH MESSENGER WIRE

NEW O/H 1-12 CORE STRAND SINGLE MODE FIBER OPTIC

(TYPCIAL)

FIBER OPTIC CABLE/CATV CABLE ETC. WITH MESSENGER WIRE

FOR NEW O/H SEC. LINE AND MOUNTING ACCESSORIES FOR

PROVIDE NEW SEC. RACKS (4 SPOOLS)

NEW CONCRETE ELECTRIC POLE/

EXIST/NEW EXTERIOR ELECTRICAL PLAN

NNSC

REPAIR BUILDING S-11

297038

TAK, YS

4. CONTRACTOR SHALL RESPONSIBLE TO RESTORE EXISTING COMMERCIAL NETWORK LINE AND

OTHER TELECOMMUNICATION LINE WITH REQUIRED ACCESSORIES TO BE OPERATIONAL AT HIS

OWN COST BY COORDINATING WITH USER THRU COR.

NEW O/H CCTV LINE

CONNECT TO CTC WITH BUILIDNG ATTACHMENT.

P

U /G

T

TELEPHONE CABLE

PROVIDE NEW SPLICE KIT FOR 25PAIR

RELOCATE EXIST TELEPHONE PEDESTAL,

NEW U/G 1-25PAIR TELEPHONE

CABLE IN 103C TO BE TERMINATED

AT TTB

NOT TO SCALE

15.

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES

10.

14.

ADDITIONAL RELAY IS PROVIDED AS REQUIRED.

SYNCHRONIZED. AUDIBLE APPLIANCES SHALL PROVIDE THE

SPECIFICATION SECTION 28.31.64.00.31(FA) AND NFPA 72.

APPROVED.

ARCHITECTURAL FEATURES.

LOCATIONS IN ACCORDANCE WITH THE MANUFACTURER'S

IN ACCORDANCE WITH THE APPLICABLE CODE, SPECIFICATIONS

THE MINIMUM REQUIRED AND THE FINAL QUANTITY SHALL BE

AND READY TO USE. THE NUMBER OF DEVICES SHOWN IS

BE PROVIDED WITH CLASS "A" MODULES

HORIZONTAL AND 305mm VERTICALLY.

TRANSMITTER AND ANTENNA.

PANEL COVER.

BREAKER AND/OR DISCONNECT SWITCH.

FOR THE FIRE ALARM AND DETECTION SYSTEM.

AUDIBILITY CALCULATION, WIRE SIZE, NO. OF WIRES

NOTES:

SHALL BE RESPONSIBLE FOR PROVIDING FIRE ALARM

FIRE ALARM CIRCUIT SHALL BE IDENTIFIED BY A RED LETTER

"FIRE ALARM CIRCUIT" ON THE DEDICATED POWER CIRCUIT

CIRCUIT SHALL BE INDICATED ON THE FIRE ALARM CONTROL

THE POWER CIRCUIT NUMBER DEDICATED TO FIRE ALARM

COAXIAL CABLE SHALL BE ONE PIECE BETWEEN BUILDING

SYSTEM SHALL BE SEPARATED BY A MINIMUM OF 1220mm

INCOMING AND OUTGOING CLASS "A" RACEWAY OF FA

7. ALL CLASS "A" EXCEPTIONS IN NFPA 72, 6.4.2.2.2 ARE

PROHIBITED FOR ALL IDC, NAC AND SLC.

ALL TAMPER SWITCHES, FLOW SWITCHES, PRESSURE

SWITCHES AND NON-ADDRESSABLE INITIATION DEVICES SHALL

COORDINATE THE EXACT DEVICE LOCATIONS WITH ELECTRICAL

AND MECHANICAL SYSTEM EQUIPMENT AND BUILDING

ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED OR FM

ALL AUDIBLE APPLIANCES WITHIN THE BUILDING AND ALL

VISUAL APPLIANCES WITHIN THE SAME ROOM SHALL BE

STANDARD TEMPORAL PATTERN, NFPA 72.

SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH

9.

11.

12.

13.

SHALL COMPLETE THE DESIGN AND INSTALL THE SYSTEM

8.

LISTED INSTALLATION REQUIREMENTS AND WIRE COUNT.

SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION DEVICE

AND MANUFACTURER'S EQUIPMENT LISTING.

THE FIRE ALARM SYSTEM IS CONCEPTUAL. THE CONTRACTOR

ALSO CONDUITS SHALL BE RUN AWAY AT LEAST 900mm

(3-FEET) FROM HVAC, HOT & COLD WATER PIPING.

FA SYSTEM SHALL OVERRIDE THE MASS NOTIFICATION SYSTEM.

SEE SHEET NO E-1.

J JJ

F

WP

F

M

EXT

1.

4.

3.

2.

5.

6.

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

J JJ JJ J JJ J

(WATTAGE AS REQ'D)

(TYPICAL)

F/A SPEAKER

/ FIRE ALARM VISUAL STROBES

(CANDELA AS REQ'D)

THE FIRE ALARM SYSTEM CONTRACTOR

SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH SPECIFICATION

AND NFPA 72.

NEW "WP" WALL MOUNTED TYPE

NEW WALL MOUNTED SPEAKER (WATTAGE AS REQ'D)

AIMAIMAIMAIMAIMAIMAIMAIMAIMAIMAIMAIM

NEW ADDRESSABLE RELAY

CONTROL PANEL (FACP)

EXIST ADDRESSABLE FIRE ALARM

AT BUILDING S-10

J J JJ

AIMAIMAIMAIM

CONTROL PANEL (FACP)

EXIST ADDRESSABLE FIRE ALARM

AT BUILDING S-25

J J JJ

AIMAIMAIMAIM

MODULE (TYPICAL OF 16)

CONNECT TO FIRE PUMP CONTROL PANEL

(TYPICAL)

NEW HOUSE PACKAGED TYPE FIRE PUMP SYSTEM

SGSGSGSGSGSGSGSG

SGSGSGSG

SG

SG SGSG

SG SGSG SG

(TYPICAL)

SURGE ARRESTER (DC VOLTAGE)

J

AIM

J

AIM

J

AIM

J

AIM

J

AIM

J

AIM

J

AIM

J

AIM

MODULE (TYPICAL OF 16)

FACPTO

FACPTO

FACPTO

FACPTO

(TYPICAL)

OF BUILDING S-25

FIR…