297038_ELEC_DWG (1).pdf
PDF 5 MB Posted
- Attached to
- Repair Building S-11 NNSC (LCS MATOC Only)
- Solicitation number
- W90VN824R0039
About this file
This document appears to be a set of electrical drawings and specifications for the repair of Building S-11 at the NNSC (Non-Commissioned Officers Senior Club) in Camp Bonifas. The key details include:
The scope of work involves repairing and upgrading the electrical, lighting, fire alarm, mass notification, LAN/telecom, and CATV systems in the building. This includes replacing interior and exterior lighting fixtures, panelboards, receptacles, fire alarm control panel, fire alarm/mass notification devices, telephone/LAN equipment, and CATV equipment and cabling. The drawings provide detailed specifications for the required electrical components and systems. The solicitation number for this repair project is W90VN824R0039, and it is limited to the MATOC (Multiple Award Task Order Contract) contractors. No other details about the contract opportunity such as response dates, award dates, pricing terms, or set-asides are provided in this document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 297038-STRUCTURE_DWG.pdf | ||
| 297038_MECH_DWG (1).pdf | ||
| 297038-CIVIL_DWG.pdf | ||
| 297038-ARCH_DWG.pdf | ||
| W90VN824R0039.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
L
L
GENERAL NOTES
1.
2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE
NOTED ON THE DRAWING.
LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE
PANELBOARD SEE SPECIFICATION
SAFETY SWITCH 1524mm TO CENTER OF THE ENCL
RECEPTACLE,TELEPHONE OUTLET 305mm TO CENTER OF THE ENCL
MOTOR CONTROLLER 1524mm TO CENTER OF THE ENCL
1676mm TO CENTER OF THE ENCL
2286mm TO CENTER OF BELL
ON CEILINGDETECTOR
1372mm TO CENTER OF STATIONMANUAL PULL STATION
INDICATEDS 2 #12AWG IN 16C
INDICATEDS 3 #12AWG IN 16C
INDICATEDS 4 #12AWG IN 16C
A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;
1219mm TO CENTER OF THE ENCLWALL SWTICH
F/A &MNS CONTROL
COMBO. SPEAKER & STROBE
SINGLE POLE TOGGLE SWITCH, 15A-125V
L E G E N D
FLEXIBLE CONDUIT W/CONNECTORS
LIGHTING
WIRING
POWER
INTERIOR
S
SYMBOL DESCRIPTION
DESCRIPTION
DESCRIPTION
T
J
THERMOSTAT (UNDER MECH. ITEM)
JUNCTION BOX
SYMBOL
SYMBOL
SAFETY SWITCH
C CONTROL CIRCUIT
AND GOVERNMENT INSTALLED
GOVERNMENT FURNISHED
GFGI
WEATHERPROOFWP
LA LIGHTNING ARRESTER
EXPLOSIONPROOFEP
DISTRIBUTIONDIST
GROUND FAULT PROTECTIONGFP
A AMPERE
AC ALTERNATING CURRENT
AF/AT AMPERE FRAME/AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CONN CONNECTION
CT CURRENT TRANSFORMER
DET(S) DETAIL(S)
DIAG DIAGRAM
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
EM EMERGENCY
ENCL ENCLOSURE
EXST EXISTING
F/A FIRE ALARM
FL FLOOR
FLUOR FLUORESCENT
FXTR FIXTURE
GEN GENERATOR
GND GROUND
HP HORSE POWER
HZ HERTZ
INCAND INCANDESCENT
INSTL INSTALLATION
J-BOX JUNCTION BOX
K KILO
KV KILO VOLT
KVA KILO VOLT AMPERE
LTG LIGHTING
MAG MAGNETIC
MAX MAXIMUM
MIN MINIMUM OR MINUTE
MTG MOUNTING
NO NUMBER
O/H OVER HEAD
PH PHASE
PNLBD PANELBOARD
PRIM PRIMARY
PWR POWER
Q'TY QUANTITY
RCPT RECEPTACLE
REQ'D REQUIRED
SCHED SCHEDULE
SEC SECONDARY
SPEC SPECIFICATION
STD STANDARD
SW SWITCH
TEL TELEPHONE
TYP TYPICAL
U/G UNDERGROUND
V VOLT
VA VOLT AMPERE
W WATT
W/ WITH
XFMR TRANSFORMER
& AND
CABNET TYPE, RATED WATT ON LTG SCHEDULE
LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER
ON LTG SCHEDULE, WET LOCATION
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
HOMERUN CIRCUIT TO PANELBOARD
TYPE OF MTG ON LTG SCHEDULE
EXTERIOR LED LIGHTING FIXTURE, RATED WATT &
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ABBREVIATION
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG
WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.
FMCP
FTR
ANTENNA
AUXILIARY
DESCRIPTION
F
TELEPHONE OUTLET
SYMBOL
CTC CATV SYSTEM CABINET
CATV OUTLET
ADDRESSABLE FA MANUAL PULL STATION
TTC
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL
MOUNTED TYPE
F/A & MASS NOTIFICATION SPEAKER "WP" WALL
STROBES
WALL MOUNTED SPEAKER /COMBO. (FA+MNS)VISUAL
CONNECTION
BUILDING TRANSMITTER UNIT FOR FIRE ALARM
SYSTEM
F
WIRING FOR TELEPHONE LINET
BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL
WIRING CONCEALED IN THE CEILING AND WALL
F/M
L
WP
TYPE WITH PLUG
SINGLE RECEPTACLE, 3P-4W-30A-125/250V, GROUNDING
TYPE WITH PLUG
SINGLE RECEPTACLE, 3P-4W-50A-125/250V, GROUNDING
W/EMERGENCY UNIT
WIRING TO UPSTAIR OR DOWNSTAIR
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
L
L
CIRCUIT INTERRUPTER TYPE,WEATHER PROOF
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND FAULT
CIRCUIT INTERRUPTER TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND FAULT
EXIT LIGHT, SINGLE FACE, WALL MOUNTED TYPE
(CEILING MOUNTED TYPE W/ARROW)
L
TELEPHONE TERMINAL CABINET
STEEL CONDUIT
FIRE ALARM SYSTEM CIRCUIT, FACTORY PAINTED RED
TYPE
SINGLE RECEPTACLE, 2P-3W-20A-125V, GROUNDING
MAGNETIC MOTOR STARTER
FAN MOTOR (UNDER MECH. ITEM)
M MOTOR (UNDER MECH. ITEM)
UH
S
WHM
MANUAL MOTOR STARTER W/PILOT LAMP
WATTHOUR METER
SAFETY SWITCH
S
TS TAMPER SWITCH (UNDER MECH. ITEM)
FS FLOW SWITCH (UNDER MECH. ITEM)
F
MANUAL MOTOR STARTER W/PILOT LAMP AND
3-POSITION SELECTOR SWITCH(H-O-A)
PANELBOARD OR LOADCENTER
TV
3 & 4-WAY SWITCH, 15A-125V
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
W/EMERGENCY BATTERY UNIT
L
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
W/EMERGENCY BATTERY UNIT
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ELECTRIC UNIT HEATER
L
L
WP
F M
3S 4S
3.THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM
IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE
MECHANICAL DRAWINGS.
4.
CONDUIT UNLESS OTHERWISE INDICATED.
ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C
5.THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
6.THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION
SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE
CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.
7.
AND LOCATION OF THE F/A ANTENNA WITH THE CENTRAL FIRE DEPARTMENT
THE CONTRACTOR SHALL SUBMIT THE SHOP DRAWING FOR THE MOUNTING
TO TRANSMIT THE ALARM RADIO SIGNAL WAVE WITHOUT ANY OBSTRUCTION.
DETAIL OF THE F/A ANTENNA, AND COORDINATE THE MOUNTING HEIGHT
F/A EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.
THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING
COORDINATED WITH THE CENTRAL FIRE DEPARTMENT SO THAT
THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING
F/A & MNS EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.
THE MANUFACTURER AND MODEL OF NEW F/A& MNS EQUIPMENT SHALL BE8.
9.
CEILING.
ALL WIRING SHALL BE CONCEALED ABOVE CEILING WHEN THE ROOM HAS
10.
CATV BEFORE CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,
11.
FIRE CODE AND SPECIFICATIONS.
OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS
12.
AND GOVERNMENT ACCEPTANCE.
PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION
CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO
13.
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING
14.
FIXTURE A MINIMUM DISTANCE OF 458mm.
FIRE ALARM DETECTORS SHALL BE LOCATED TO CLEAR ANY LIGHTING
15.
UNITS.
CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY
THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE
WIDTH OF DUCT EXCAVATION.
AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
TO THEIR ORIGINAL CONDITION AND OPERATION DURING
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING 16.
17.
CONFIRMATION.
THE CONTRACTOR SHALL REMOVE ABANDONED ELECTRIC DEVICES W/ COR
INDICATEDS 6 #12AWG IN 21C
ELECTRICAL
SCOPE OF WORKS
LEGEND, GENERAL NOTES AND
E-1
SCOPE OF WORK
2.
A. REPAIR/MAINTENANCE ( K )
4.
6.
3.
7.
5.
1.
PHOTOCELL, WIRE AND CONDUIT WITH NEW.
LIGHTS, TOGGLE SWITCHES, 3 WAY SWITCHES, LIGHTING CONTACTOR,
REPLACE EXISTING INTERIOR AND EXTRIOR LIGHTING FIXTURES, EXIT
8.
PLATES AND ASSOCIATED WIRING AND CONDUIT WITH NEW.
RACK, TELEPHONE TERMINAL BOARD, LAN/TELEPHONE OUTLETS W/ COVER
REPLACE EXISTING TELECOMMUNICATION SYSTEM INCLUDING EQUIPMENT
9.
CONDUIT AS SHOWN ON THE DRAWINGS.
INCLUDING SECONDARY LINE & ASSOCIATED ACCESSORIES, WIRING AND
REPLACE EXISTING EXTERIOR POWER DISTIBUTION SYSTEM WITH NEW
W/COVER PLATES, ASSOCIATED WIRE & CONDUIT WITH NEW.
REPLACE EXISITNG WATTHOUR METER, PANELBOARDS, RECEPTACLES
MECHANICAL SYSTEM WITH NEW.
JUNCTION BOXES, CONTROL SYSTEM, WIRE AND CONDUIT FOR
REPLACE EXISTING A MAGNETIC MOTOR STARTER, SAFETY SWITCHES,
ASSOCIATED WIRE AND CONDUIT.
DEVICES, BUILDING TRANSMITTER, ANTENNA, LIGHTNING ARRESTER AND
VISUAL SIGNAL STROBES, MICROPHONE, SPEAKERS (WATTAGE AS REQ'D)
PANEL, MANUAL PULL STATIONS, SMOKE DETECTOR & RELAY MODULES,
ADDRESSABLE FIRE ALARM CONTROL AND MASS NOTIFICATION SYSTEM
REPLACE EXISTING FIRE ALARM CONTROL SYSTEM WITH NEW
AND ASSOCIATED WIRE AND CONDUIT WITH NEW.
REPLACE EXISTING CATV CABINET, OUTLETS W/COVER PLATES
LINE AND ACCESSORIES WITH NEW.
REPLACE EXISTING EXTERIOR UNDERGROUND, OVERHEAD TELECOMMUNICATION
NNSC
REPAIR BUILDING S-11
TAK, YS
297038
FROM NEW FIRE PUMP SYSTEM TO BUILDING S-11.
SURGE PROTECTORS, ADRESSABLE MODULES, UNDERGROUND SIGNAL LINES
REPAIR EXISTING FIRE PROTECTION SYSTEM BY INSTALLING FIRE ALARM
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-2
L
L
L
L
S
L L
S
S S
S
3 S3S
L
L L
L
S
S
L
L
L
L
L
L
L
L
L L
L
L
S S
S
S
LL
S
S
S
S
NEW GROUND FLOOR LIGHTING PLAN
L L
L
P-1P-2P-3
P-4
OFFICE
(NIC)
(NIC) (NIC)
REF
KITCHEN
PANTRY
BATH
LINEN
STOR 110
CLOSET
BED ROOM102
LIVING ROOM
(NIC)
(NIC)
(NIC)
RM
COMM
ROOM
ELEC
MECH/
"P"
SCALE : 1/50
NEW GROUND FLOOR LIGHTING PLAN
NOTES SEE SHEET NO. E-1.
FOR ABBREVIATION, LEGEND AND GENERAL 1.
NOTES
L
SEE DETAILS IN DRAWING "E-15"
NEW LIGHTING CONTACTOR "LC" WITH PHOTO CELL
L
NNSC
REPAIR BUILDING S-11
TAK, YS
LLL
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-3 m m
308mm
NS-3a & 3b
WALL OR CEILING SURFACE MOUNTED LIGHT EMITTING
WITH BATTERY CHARGER, SINGLE FACE (NS-3a) OR
(MAX INPUT) OR 7.22W(MAX INPUT), BATTERY BACK-UP
DIODE(LED) EXIT LIGHT FIXTURE, 1PH, 120V, 4.99W
m m
1220m m
0m m
DOUBLE FACE (NS-3b) OR APPROVED EQUAL.
NS-5a & 5b NS-6a & 6b
245mm
ELECTRICAL
LIGHTING FIXTURE DETAILS
NS-11 NS-12
UNDERCABINET LED LIGHT FIXTURE
1PH, 120V, 13W, CONVERTER AND ACCESSORIES,
UL LISTED POWER UNIT
NS-13
222mm m m
FIXTURE, 1PH, 120V, 13W, WITH CONVERTER &
CEILING RECESSED LIGHT EMITTING DIODE (LED)
143.9mm
.3 m m
210mm
UNIT
ACCESSORIES, AS REQUIRED AND UL LISTED POWER
CEILING SURFACE/PENDANT MOUNTED LIGHT EMITTING DIODE (LED)
ACCESSORIES AS REQUIRED, (NS-7a) & SELF TEST/DIAGNOSTIC EM UNIT(NS-7b)
FIXTURE, 1PH, 120V, 45W, UL LISTED, PMMA LIGHT GUIDE WITH CONVERTER AND
NS-7a & 7b
FIXTURE, 1PH, 120V, 13W, WITH CONVERTER & ACCESSORIES,
AS REQUIRED, OR APPROVED EQUAL.
WALL SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
NS-8
254mm
CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
OR APPROVED EQUAL.
WET LOCATION SHOWER LIGHT TRIM, AS REQUIRED
FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES,
WALL
TYPE, UL LISTED
AND ACCESSORIES W/BUILT-IN PHOTOCELL, WET LOCATION
WALL OR CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
LIGHTING FIXUTURE 1PH, 120V, 22W LED MODULES, WITH CONVERTER
NS-10NS-9
CONVERTER & ACCESSORIES AS REQUIRED, (NS-5a) & WITH SELF TEST/DIAGNOSTIC EM UNIT (NS-5b)
FIXTURE, 1PH, 120V, 45W, UL LISTED, PMMA LIGHT GUIDE PLATE, WITH
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
FIXTURE, 1PH, 120V, 50W, UL LISTED, PMMA LIGHT GUIDE WITH CONVERTER &
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
WET LOCATION TYPE, WITH CONVERTER & ACCESSORIES AS
REQUIRED, UL LISTED POWER UNIT
CEILING SURFACE MOUNTED LED LIGHT FIXTURE, 1PH, 120V, 22W,
ACCESSORIES, (NS-6a) & WITH SELF TEST/DIAGNOSTIC EM UNIT (NS-6b)
NNSC
REPAIR BUILDING S-11
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-4
REMARKSQ'TY
WATTS
MOUNTING METHOD
TYPE
LAMP
NAMENO
ROOM OCE STD DET 40-06-04
LIGHT FIXTURE SCHEDULE
TYPE
LED
LIGHT FIXTURE SCHEDULE
ELECTRICAL
101 OFFICE NS-6a
NS-6b 50
50 3
3 W/ "EM" UNIT
102 LIVING ROOM NS-6a
NS-6b 50
50 3
CEILING RECESSED
W/ "EM" UNIT
103 KITCHEN NS-5b
NS-12 13
45 1
1 UNDER CABINET
W/ "EM" UNIT
104 PANTRY NS-11 13 1
105 NS-11 13 1COMM RM
BATH ROOM NS-8
NS-9
1 CEILING SURFACE
WALL MOUNTED ABOVE THE MIRROR TOP106
CEILING RECESSED
1NS-7a 45
111 MECH/ELEC ROOM
EXIT SIGN
EXTERIOR LIGHT
EXTERIOR LIGHT
- NS-3
NS-13
10 SEE DRAWING E-15 FOR DETAIL10 BOLLARD TYPE
4.99
CEILING SURFACE
WALL MOUNTED
1EXTERIOR LIGHT- NS-10 22 WALL MOUNTED
CEILING SURFACE
NS-7b 45 1 CEILING SURFACE
107 NS-9 18 1LINEN
108 13 1STOR
109 BED ROOM NS-5a
NS-5b
NS-11 13
45 1
W/ "EM" UNIT
110 NS-11 13 1CLOSET
NS-11 CEILING RECESSED
W/ "EM" UNIT
ABOVE THE DOOR TOP
(LIVING ROOM, OFFICE SIDE)
UNDER THE CANOPY
ABOVE THE DOOR TOP (MECH ROOM SIDE)
NS-5b 45 1 W/ "EM" UNITCEILING RECESSED
NNSC
REPAIR BUILDING S-11
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-5
HDRA
"WP"
"WP"
NEW GROUND FL POWER PLAN
P-5
P-6
P-7
P-8
P-9
P-11
P-13
P-14
P-15
P-16
P-17
P-18
C-4
C-3
C-1C-2
ROOM
MECH/ELEC
OFFICE
(NIC)
REF
KITCHEN
PANTRY
BATH
LINEN
STOR 110
CLOSET
BED ROOM
LIVING ROOM
(NIC)
"P"
* ADDITIONAL LEGEND(THIS SHEET ONLY)
RA
GROUNDING TYPE) W/PLUG
SINGLE RECEPTACLE (2P-3W-20A-125V
GROUNDING TYPE) W/CORD-SET
FOR RANGE HOOD FAN(1PH-115V-2.0A)
AND LIGHT(1PH-120V-75W)
HD
(MH : +1500mm TO TOP OF RCPT)
CIRCUIT INTERRUPTER TYPE,WEATHER PROOF
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND FAULT
DUPLEX RECEPTACLE
(2P-3W-20A-220VAC, GROUNDING TYPE)
(KOREAN RECEPTACLE)
DUPLEX RECEPTACLE
(KOREAN RECEPTACLE)
"WP"
"WP"
1PH-120/208V-50A
SINGLE RECEPTACLE
GROUNDING TYPE
QUAD RECEPTACLE, 2P-3W-20A-125VAC
DUPLEX RECEPTACLE, 2P-3W-20A-125VAC
GROUNDING TYPE
DUPLEX RECEPTACLE (2P-3W-20A-125VAC)
GROUND FAULT PROTECTED
GROUNDING TYPE
SINGLE RECEPTACLE, 2P-3W-20A-125VAC
(2P-3W-20A-220VAC, GROUNDING TYPE, WEATHER PROOF)
"WP"
SCALE :
NEW GROUND FL POWER PLAN
1/50
"C"
COMM RM
"WP"
P-10 P-12
P-22
NNSC
REPAIR BUILDING S-11
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-6
FOR MECHANICAL SYSTEM
NEW GROUND FL POWER/CONTROL PLAN
CLOSET
BED ROOM
BATH
LINEN
(NIC)
(NIC)
(NIC)
REF
KITCHEN
COMM RM
PANTRY
STOR
(NIC) (NIC)
(NIC)
(NIC)
(NIC)
FEC
OFFICE
101 LIVING ROOM
T
HPU
HPU
T
HPU
T
EH
SAC
O A
S A
E A
R A
EF
EWH
ROOM
MECH/ELEC
"P"
"C"
"MP"
EH
RH
1 POWER:2.0 AMPS, 120V, 1PH, (MECH ITEM)
RANGE HOOD
SINGLE RECEPTACLE (2P-3W-20A-240VAC,
* ADDITIONAL LEGEND(THIS SHEET ONLY)
GROUNDING TYPE) FOR INDOOR HEAT PUMP UNIT
2KW, 208V, 1PH, (MECH ITEM)
ELEC. UNIT HEATER
HPU
40W, 208V, 1PH (MECH ITEM)
INDOOR SPLIT SYSTEM HEAT PUMP UNIT
HPU
79W, 208V, 1PH (MECH ITEM)
INDOOR SPLIT SYSTEM HEAT PUMP UNIT
HPU
199W, 208V, 1PH (MECH ITEM)
INDOOR SPLIT SYSTEM HEAT PUMP UNIT
ERV
176W, 220V, 1PH, (MECH ITEM)
ENERGY RECOVERY VENTILATION UNIT
SAC
15 AMP MOP 220V, 1PH, (MECH ITEM)
SPLIT AIR CONDITIONING
9KW 208 V, 1 PH,
ELECTRIC HOT WATER HEATER
OHPU OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT
25.4 AMP MCA / 40 AMP MOP 208 VOLTS, 1 PH, (MECH ITEM) 1
EF
0.03 HP, 115V, 1PH (MECH ITEM)
FANS
EF
0.02 HP, 115V, 1PH (MECH ITEM)
FANS
EWH
EUH
OHPU
ERV
EF
1,500W, 12AMP 120V, 1PH, (MECH ITEM)
ELECTRIC WALL HEATER
M D
J
C
B
C
J
AT BATH ROOM
CONNECT TO LIGHT SWITCH
A
MP-4
MP-6
MP-3
A
C
B
MAGNETIC MOTOR STARTER, 2P-120V
NEMA SIZE "00" W/O.L RELAYS,
PILOT LAMP(GREEN), AND 3-POSITION
SELECTOR SWITCH (H-O-A)
NEMA 1 ENCL
NON-FUSIBLE, NEMA 3R ENCL
FOR SAC
SAFETY SWITCH, DPST, 240V, 30A
SAFETY SWITCH, DPST, 240V, 60A
SAFETY SWITCH, DPST, 240V, 30A
FOR ERV-1
NON-FUSIBLE, NEMA 3R ENCL
FOR OHPU
SCALE :
NEW GROUND FL POWER/CONTROL PLAN FOR MECHANICAL SYSTEM
1/50
P-20
P-21
C-6
P-23
J
MP-5
EUH
STRUCTURE SUPPORT
NON-FUSIBLE, NEMA 1 ENCL ABOUT CEILING W/ STEEL
NNSC
REPAIR BUILDING S-11
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-7
WP
M F
WP
M F
F
SB
F
F T R
F M
C P
* ADDITIONAL LEGEND (THIS SHEET ONLY)
COMBINED ADDRESSABLE FIRE ALARM/
MASS NOTIFICATION CONTROL PANEL,
24VDC, BUILT-IN ADDRESSABLE POINTS
MODULES AS REQ'D, PROGRAMMABLE
MODULE & RELAYS LCD ANNUNCIATOR,
SYNCHRONIZATION CONTROL MODULE,
POWER SUPPLY, DIGITAL VOICE MODULE,
MICROPHONE, BATTERY, BATTERY CHAREGER,
POWER MODULES PANEL(AS REQ'D) AND
DIGITAL VOICE PANEL W/AMPLIFIER & BACK
UP AMPLIFIER (AS REQ'D) & MICROPHONE,
NEMA 1 ENCL
FMCP
ADDRESSABLE MANUAL PULL STATION
SPEAKER (WATTAGE AS REQ'D)
FIRE ALARM/MASS NOTIFICATION
WALL MOUNTED "WP" TYPE,
SHALL BE DE-RATED AS REQUIRED)
(75 CANDELA MINIMUM, AMBER STROBE
W/WORDS "ALERT") VISUAL SIGNAL STROBES
W/WORDS "FIRE" + MNS-AMBER STROBE
AS REQ'D)/COMBO. (FA-CLEAR STROBE
WALL MOUNTED SPEAKER (WATTAGE
SHALL BE DE-RATED AS REQUIRED)
(15 CANDELA MINIMUM, AMBER STROBE
W/WORDS "ALERT") VISUAL SIGNAL STROBES
W/WORDS "FIRE" + MNS-AMBER STROBE
AS REQ'D)/COMBO. (FA-CLEAR STROBE
WALL MOUNTED SPEAKER (WATTAGE
WP
M F
F
ADDRESSABLE SMOKE DETECTOR
ADDRESSABLE SMOKE DETECTOR
W/SOUNDER BASE
TAMPER SWITCH W/ADDRESSABLE
MODULE (UNDER MECH ITEM)
PRESSURE SWITCH W/ADDRESSABLE
MODULE (UNDER MECH ITEM)
SB
TS
PS
FTR BUILDING TRANSMITTER
NEW GROUND FLOOR FIRE ALARM/MASS NOTIFICATION SYSTEM PLAN
SCALE :
"P"
NOTIFICATION SYSTEM PLAN
NEW GROUND FLOOR FIRE ALARM/MASS
P-19
ROOM
MECH/ELEC
OFFICE
(NIC)
(NIC) (NIC)
REF
KITCHEN
PANTRY
COMM RM
BATH
LINEN
STOR 110
CLOSET
BED ROOM
LIVING ROOM
(NIC)
(NIC)
(NIC)
FMCPTO
FMCPTO
F
TSTS
JJ
F/M
F /M
F /M
F/M
F /M
F F
FF
F
F F F
F
F
TS
J
PS
J
1/50
NNSC
REPAIR BUILDING S-11
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-8
NOTES:
NFPA 72, 2013 EDITION.
PRERECORDED MESSAGES ARE IN ENGLISH AND HANGUL AT
CONTRACTOR SUBMITS SHOP DRAWINGS.
THE VOLTAGE DROP AND POWER SUPPLY CALCULATION
SHALL BE PROVIDED BY THE CONTRACTOR WHEN THE
4.
(3-FEET) FROM HVAC, HOT & COLD WATER PIPING.
ALSO CONDUITS SHALL BE RUN AWAY AT LEAST 900mmTHE FIRE ALARM SYSTEM IS CONCEPTUAL. THE
MANUFACTURER'S EQUIPMENT LISTING.
SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION
MANUFACTURER'S LISTED INSTALLATION
2.
CONTRACTOR SHALL COMPLETE DESIGN AND INSTALL
13.
12.
11.
9.
SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH
AND THE MASS MESSAGE NEEDS TO HAVE PRE ALERT
PATTERN IS REQUIRED FOR FIRE ALARM EVACUATION
VOICE EVACUATION SYSTEM IN LIEU OF TEMPORAL
ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED
ELECTRICAL AND MECHANICAL SYSTEM EQUIPMENT
COORDINATE THE EXACT DEVICE LOCATIONS WITH
SWITCHES AND NON-ADDRESSABLE INITIATION
ALL TAMPER SWITCHES, FLOW SWITCHES, PRESSURE
PROHIBITED FOR ALL IDC, NAC AND SLC.
ALL CLASS "B" EXCEPTIONS IN NFPA 72, 23.4.2.2 ARE8.
7. CLASS "B" RACEWAY OF FA SYSTEM SHALL BE
SEPARATED BY A MINIMUM OF 1220mm HORIZONTAL
10. COAXIAL CABLE SHALL BE ONE PIECE BETWEEN
3.
5.
6. THE POWER CIRCUIT NUMBER DEDICATED TO FIRE
ALARM CIRCUIT AND ROOM LOCATION OF PANEL
LETTER "FIRE ALARM CIRCUIT" ON THE DEDICATED
FIRE ALARM CIRCUIT SHALL BE IDENTIFIED BY A RED
THE FIRE ALARM/MASS NOTIFICATION SYSTEM
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
FIRE ALARM INTELLIGIBILITY/AUDIBILITY CALCULATION,
WIRE SIZE, CONDUIT SIZE, NO. OF WIRES FOR THE FIRE
POWER CIRCUIT BREAKER AND/OR DISCONNECT SWITCH.
SHALL BE INDICATED ON THE FIRE ALARM/MASS
BUILDING TRANSMITTER AND ANTENNA.
AND 305mm VERTICALLY.
DEVICES SHALL BE PROVIDED WITH CLASS "B"
THE SYSTEM FOR READY TO USE. THE NUMBER OF
DEVICES SHOWN IS THE MINIMUM REQUIRED AND THE
FINAL QUANTITY SHALL BE IN ACCORDANCE WITH THE
DEVICE LOCATIONS IN ACCORDANCE WITH THE
AND BUILDING ARCHITECTURAL FEATURES.
OR FM APPROVED.
SPECIFICATION SECTION 28.31.76.00.31 (FA) AND
HAVE PRE ALERT TEMPORAL PATTERN MIN 2 CYCLES
PROVIDE ADDITIONAL RELAYS AS REQUIRED.14.
18.
19.
20.
PER UFC 4-021-01.
17. THE MASS NOTIFICATION SYSTEM IS CONCEPTUAL. THE
NUMBER OF DEVICES SHOWN IS THE MINIMUM REQUIRED
AND THE FINAL QUANTITY SHALL BE IN ACCORDANCE
MANUFACTURER'S EQUIPMENT LISTING.
SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION
THE MASS NOTIFICATION SYSTEM SHALL BE ENSURED THAT
LEAST FOR THE FOLLOWING ITEMS.
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES
STROBES FOR MASS NOTIFICATION SHALL BE MARKED
STROBES FOR FIRE ALARM SHALL BE MARKED "FIRE"
"ALERT" IN RED LETTER AND W/AMBER LENS.
SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH
1.
AND W/CLEAR LENS.
15.
CONTINUOUS 3-10 SECOND TONE, NFPA 72, 24.4.1.2.2
& 24.4.1.8.2.
THE MASS SYSTEM ACTIVATION MUST OVERRIDE THE FIRE
ALARM NOTIFICATION APPLIANCES THE MASS SYSTEM
ON THE PANEL BY SWITCH.
THIS SEQUENCE IS REQUIRED FOR BOTH PRE-RECORDED
MASS MESSAGE IS REQUIRED TO BE ANNOUNCED
IMMEDIATELY UNTIL SHUTDOWN MANUALLY.
SPECIFICATION SECTION 28.31.76.00.31 (MNS)
THE CONTRACTOR SHALL PROVIDE THE REQUIRED
TESTING TO ACHIEVE A MINIMUM CIS SCORE 0.8 AS
16.
DEVICE LOCATIONS IN ACCORDANCE WITH THE
MANUFACTURER'S LISTED INSTALLATION
AND NFPA 72, 2013 EDITION.
APPLIANCES UNTIL MASS ALERT IS CANCELED MANUALLY
ACTIVATION MUST OVERRIDE THE FIRE ALARM NOTIFICATION
MESSAGES AND MANUAL MICROPHONE INITIATED MESSAGES.
ARE IDENTICAL TO FIRE ALARM VISUAL APPLIANCES.
23.
MASS VISUAL APPLIANCE LOCATION REQUIREMENTS
AS SHOP DRAWING SUBMITTALS.
CONTRACT DRAWINGS SHALL NOT BE SUBMITTED
ARMY AND AIR FORCE PROJECTS.
WITH ANY FIRE ALARM VISUAL APPLIANCES ON
MASS VISUAL APPLIANCES SHALL NOT BE COMBINED24.
25.
22. FIRE ALARM SYMBOLS FROM NEPA 170 SHALL BE
AND ALL VISUAL APPLIANCES WITHIN THE SAME ROOM
ALL AUDIBLE APPLIANCES WITHIN THE BUILDING21.
SHALL BE SYNCHRONIZED.
VOICE EVACUATION SPEAKERS, NEPA 72.
AUDIBLE APPLIANCES SHALL PROVIDE THE STANDARD
TEMPORAL PATTERN UNLESS NFPA 101 REQUIRES
USED.
26. SHOW WEATHERPROOF EXTERIOR SPEAKERS AT ALL
EXTERIOR DOORS OR EXTERIOR GATHERING AREAS.
SHALL BE UL LISTED OFF-THE-SHELF-EQUIPMENT AND
ALL BACK-UP AMPLIFIERS WIRING AND ARRANGEMENT27.
SHALL BE TESTED TO THE STANDARDS OF UL OR RM AS
REQUIRED BY UFC 4-21-01, PARAGRAPH 4-4.3.
BOTH KOREAN AND ENGLISH.
THE MAN SHALL HAVE PRERECORDED MASSAGES IN28.
APPLICABLE CODE, SPECIFICATIONS AND
REQUIREMENTS AND WIRE COUNT.
ALARM AND DETECTION SYSTEM.
NOTIFICATION CONTROL PANEL COVER.
MODULES.
SYSTEM. VOICE EVACUATION MESSAGE NEEDS TO
REQUIRED.
WITH THE APPLICABLE CODE, SPECIFICATIONS AND
REQUIREMENTS AND WIRE COUNT.
OF 20% SPARE ADDRESSES FOR FUTURE USE.
FIRE ALARM SYSTEM OF EACH SLC TO HAVE A MINIMUM29.
SEE SHEET NO. E-1.
2) INTRUDER/HOSTILE PERSON SIGHTED WITHIN/AROUND THE BUILDING
1) BOMB THREAT OR ACTUAL BOMB WITHIN/AROUND THE BUILDING
3) OCCUPANTS DIRECTED TO TAKE COVER WITHIN THE BUILDING
6) "ALL CLEAR" MESSAGE
TEST8)
THE BUILDING
CARBON MONOXIDE GAS DETECTION MESSAGE WITHIN/AROUND 7)
THE LOCAL AREA
5) EMERGENCY WEATHER CONDITIONS APPROPRIATE FOR
NORMAL MAIN ENTRANCE/EXIT
4) EVACUATION OF THE BUILDING USING EXITS OTHER THAN THE
FIRE ALARM/MASS NOTIFICATION
CONTROL PANEL (FMCP)
SG
G ~
G
CONTROL PANEL & BOOSTER PANEL)
(INSTALLED BESIDE FIRE ALARM
(RATED AS REQ'D) (TYPICAL)
SURGE PROTECTOR
2#12 & 1#12(G) IN 16C
GROUND ROD, COPPER CLAD
GROUNDING SYSTEM #6, "BC" IN 21C
CONN TO BLDG ELECTRODE
STEEL, 19mmdiax3000mmLG
WITH WELDING CONNECTION AND
F
ADDRESSABLE MANUAL
PULL STATION (TYPICAL)
WALL MOUNTED "WP" TYPE,
NOTIFICATION SPEAKER
FIRE ALARM/MASS
(WATTAGE AS REQ'D) (TYPICAL)
NOT TO SCALE
ELECTRICAL
F
TS
J
101 111 102 102
F M
WP
EXT
BATTERY CHARGER, POWER MODULE PANEL(AS REQ'D)
SYNCHRONIZATION CONTROL MODULE, DIGITAL VOICE
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL,
24VDC, BUILT-IN ADDRESSABLE POINTS MODULES
AS REQUIRED, PROGRAMMABLE MODULE & RELAYS,
POWER MODULE AS REQ.D LCD ANNUNCIATOR,
MODULE, POWER SUPPLY, MICROPHONE, BATTERY,
AND AMPLIFIER(AS REQ'D), NEMA 1 ENCL
SEMI FLUSH MOUNTED COMBINED ADDRESSABLE
NEW FIRE ALARM/MASS NOTIFICATION SYSTEM DIAGRAM
SYSTEM DIAGRAM
NEW FIRE ALARM/MASS NOTIFICATION
F M
WP
EXT
TO PANELBOARD P-19
F
12#14 IN 21C(FOR SIGNAL)
2#12 IN 16C(FOR POWER)
(PROGRAM OF D-21 MONACO
BUILDING TRANSMITTER
BT-XM AT LEAST 16 ZONES)
#6 "BC" IN 21C
GROUND CONDUCTOR
COAXIAL CABLE
W/CONNECTORS IN 16C
W/MOUNTING BRACKET
GROUND ROD, COPPER CLAD
WITH WELDING CONNECTION
STEEL, 19mmdia x 3000mmLG
ENCLOSURE
LIGHTNING ARRESTER
W/WEATHER-PROOF
W/BATTERY & BATTERY
CHARGER, NEMA 1 ENCL
OMNI-DIRECTION TYPE
FIRE ALARM ANTENNA
FTR
(15 or 75 CANDELA MINIMUM, AMBER STROBE
W/WORDS "ALERT") VISUAL SIGNAL STROBES
W/WORDS "FIRE" + MNS-AMBER STROBE
WALL MOUNTED SPEAKER (WATTAGE
AS REQ'D)/COMBO. (FA-CLEAR STROBE
SHALL BE DE-RATED AS REQUIRED) (TYPICAL)
SB
ADDRESSABLE SMOKE
DETECTOR
DETECTOR W/ SOUNDER BASE
ADDRESSABLE SMOKE
PS
J
W/ADDRESSABLE MODULE
PRESSURE SWITCH
FOR SPRINKLER SYSTEM
(UNDER MECH ITEM)
TS
J
TS
J
NNSC
REPAIR BUILDING S-11
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
NEW GROUND FLOOR LAN/TEL PLAN
E-9
LAN
T T B
"C"
* ADDITIONAL LEGEND (THIS SHEET ONLY)
LAN
TTB
NEW EQUIPMENT RACK FOR NIPR NETWORK
NEW TELEPHOE TERMINAL BOARD
SEE TELECOMMUNICATION SYSTEM DIAGRAM
SEE TELECOMMUNICATION SYSTEM DIAGRAM
DUAL MODULAR JACK, CAT-6
NIPR EQUIPMENT RACK
TO BE TERMINATED AT PATCH PANEL IN
2-4PAIR,CAT-6,#24AWG IN 27C
( TYPICAL)
ROOM
MECH/ELEC
OFFICE
(NIC)
(NIC) (NIC)
REF
KITCHEN
PANTRY
BATH
LINEN
STOR 110
CLOSET
BED ROOM
LIVING ROOM
(NIC)
RM
COMM
SCALE : 1/50
NEW GROUND FLOOR LAN/TEL PLAN
NNSC
REPAIR BUILDING S-11
EXOTHERMIC WELDING, LISTED COMPRESSION TWO-
1. THE CONNECTIONS OF THE BONDING CONDUCTOR FOR
TELECOMMUNITIONS TO THE TMGB SHALL UTILIZE
HOLE LUGS, SUITABLE AND EQUIVALENT TWO-HOLE
1#6 "BC" IN 21C
CONN TO MAIN PANELBOARD
NOT TO SCALE
STAMP FACING OUT" TO ENSURE THAT THEY CAN BE
3. TEST RESULTS WILL BE PROVIDED IAW THE MOST RECENT
REVISION OF THE ANSI/TIA/EIA-568.
4. LABEL ALL DROPS IAW TIA/EIA-606-A.
5. LABEL ALL GROUNDS IAW I3A.
LUGS ARE PREFERRED.
FIELD VERIFIED.
TO TELEPHONE PATCH PANEL
TGB
CONN TO TMGB
1#6 "BC" IN 27C
(100mm x 450mmLG x 6.4mmTHK)
GROUND BUS BAR(TGB)
TMGB
G
(TYPICAL)
CABLE SUPPORT
G
110TYPE TERMINAL BLOCK
(TYPICAL)
CROSS CONNECTION CORD AS REQ'D
PLUS 25% SPARES TO BE FURNISHED BY THE
1#6 "BC" IN 16C
G
FOR TELEPHONE
1-48PORT PATCH PANEL
AS REQ'D
PROVIDE PATCH CORDS
HUB(N.I.C)
1-48PORT PATCH PANEL
W/ RACK MOUNTED 6-SINGLE
REAR RECEPTACLE, ON-OFF
SWITCH & CORD, 2P-3W-20A-125V
GROUND BUS BAR(TGB)
TELECOMMUNICATION
TELECOMMUNICATION MAIN
PTB
CONTRACTOR
RECEPTACLES
(1-25PAIR)
ENTRANCE TERMINAL BLOCK
110 TYPE PROTECTED
G
2. "PLYWOOD WILL BE INSTALLED WITH FIRE RATED
NOTE.
SHALL BE COORDINATED WITH BASE SIGNAL COMPANY.
SYSTEM AND WIRING FOR GOVERNMENT APPROVAL. TELECOMMUNCATION WORK
6. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DETAILED TELECOMMUNICATION
1-12CORE, FIBER OPTIC CABLE IN 103C.
PATCH PANEL W/"SC" CONNECTOR
1-24 STRAND FIBER OPTIC
QUAD-PLEX RECEPTACLE
2P-3W-125V-20A GND TYPE
WITH DEDICATED CIRCUIT
(24"(W)x36"(H)x30"(D)
POWER SURGE PROTECTION
COMM RM
1-25PAIR, #24AWG TEL CABLE IN 103C.
TO EACH TEL OUTLET AS REQ'D VIA CABLE TRAY
2,200(W)x2,400(H) FIRE RATED PLYWOOD
TELEPHONE TERMINAL BOARD ("TTB"),
G
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
(100PAIR) FOR TEL
(TYPICAL)
NEW LAN/TEL SYSTEM DIAGRAM
TO EACH DATA OUTLET AS REQ'D VIA CABLE TRAY
G
TO BE TERMINATED AT FIBER OPTIC PATCH PANEL
LENGTH AS REQUIRED
CABLE TRAY 300mm(W)x(150(H)
G
G
G
"MDP" GROUNDING BUS BAR
FOR DATA
(TYPICAL)
NEW LAN/TEL SYSTEM DIAGRAM
TO PNLBD C-1
EQUIPMENT CABINET
TO PNLBD C-1 , C-2
E-10
NNSC
REPAIR BUILDING S-11
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-11
REF
"C"
T V
T V
TV
T V
TV
TV
CTC
9.
NOTES
1.
ACCEPTANCE INSPECTION.
dbMV LEVELS.
CONTRACTOR PRIOR TO START OF WORK.
UPON BY BASE CATV PERSONNEL, CONTRACTOR, AND ANY QUALITY
MATERIAL AND PASSIVE DEVICES TO BE USED MUST BE AGREED
COORDINATION WITH BASE CATV PERSONNEL ON THE TYPE OF CABLE
THEN, BASE CATV PERSONNEL WILL INSPECT/TEST ALL PROJECTS
ON USFK INSTALLATIONS FOR QUALITY ASSURANCE.
RESULTS WILL BE RECORDED AND AVAILABLE AT THE FINAL
CONTRACTORS WILL COORDINATE WITH BASE CATV PERSONNEL
30 DAYS PRIOR TO PERFORMING FINAL ACCEPTANCE TESTING.
RANGE FROM 5 TO 860MHZ, RETURN PATH 5-42MHZ,
TO INCLUDE ALL ATTENUATION'S TO COMPENSATE FOR
C-COR LINE EXTENDER, DIRECTIONAL COUPLERS, SPLITTERS,
AND TAP-OFF'S ARE TO BE 2WAY AND OPERATE IN THE
COORDINATE LOCATION OF "NODE EQUIPMENT" WITH BASE
BASE CATV PERSONNEL.
TAP UNITS, SPLITTERS, AMPLIFIER, COAXIAL CABLE, etc.
THE SPECIFICATION OF MATERIALS SUCH AS CATV OUTLET
CATV SYSTEM. IT SHALL BE COORDINATED WITH
SHALL BE COMPATIBLE WITH THE EXISTING BASE
2. ALL CATV MATERIAL AND EQUIPMENT MUST HAVE RETURN
PATH(2-WAY) CAPABILITIES.
3. PROVIDE DIAGONAL VENTS ON OPPOSITE SIDE OF CATV PANEL;
ONE VENT HIGH AND ONE VENT LOW.
4.
5.
6.
7. INITIAL TESTING OF CATV SYSTEM SHALL BE PERFORMED BY THE
CONTRACTOR TO MEET THE REQUIREMENT OF CATV dB.
8.
THE LOCATION OF PULL BOX WITH COUPLERS WHICH IS INSTALLED
ABOVE THE CEILING SHALL BE MARKED ON THE CEILING FOR THE
MAINTENANCE.
ASSURANCE BRANCH PERSONNEL DPW,
BASE CATV PERSONNEL PRIOR TO ORDERING.
SCALE :
NEW GROUND FL CATV PLAN
COAXIAL CABLE
RG 6/U IN 16C
(TYPICAL)
T V
NEW GROUND FL CATV PLAN
FEC
ROOM
MECH/ELEC
OFFICE
(NIC)
(NIC) (NIC)
REF
KITCHEN
PANTRY COMM RM
BATH
LINEN
108STOR
CLOSET
BED ROOM
LIVING ROOM
(NIC)
(NIC)
(NIC)
1/50
TV WALL MOUNTED TYPE TV OUTLET
W/"0.0"dB LOSS FACE PLATE & F-81 BARREL TYPE CONNECTOR
* ADDITIONAL LEGEND(THIS SHEET ONLY)
RG 11/U IN 21C
(TYPICAL)
CEILING) (TYPICAL)
(MH:+450mm BELOW
TYPE CONNECTOR
PLATE & F-81 BARREL
W/"0.0"dB LOSS FACE
TV OUTLET
WALL MOUNTED TYPE
COAXIAL CABLE
DEVICES BY COORDINATING WITH BASE CATV COMPANY.
CONNECTION POINT AND PROVIDE CATV CABLE, CONNECTION
CONTRACTOR SHALL VERIFY EXIST EXTERIOR CATV LINE
NEW O/H CATV CABLE, RG-11/U W/ MESSENGER WIRE,
ON CATV CABINET TO ENSURE
NEW CATV DISTRIBUTION CABINET
INCLUDING NEW 2-WAY SPLITTER,
TRUNK BRIDGE AMPLIFIERS W/RETURN PATH
CAPABILITIES, LOCKING DEVICE AND
AIR VENTS SHALL BE INSTALLED
ADEQUATE VENTILATION IN COMM RM
NEMA 1 ENCL
NNSC
REPAIR BUILDING S-11
G
AMP
1st FL
ROOF
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
TV
TV
TV
TVTV
TV
RG 11/U IN 21C
COAXIAL CABLE
(TYPICAL)
NEW GROUND FL CATV DIAGRAM
NOT TO SCALE
NEW GROUND FL CATV DIAGRAM
TV
101 102
E-12
(TYPICAL)
DEVICE IS LOCATED
ROOM NO WHERE
COAXIAL CABLE
RG 6/U IN 16C
(TYPICAL)
W/ 8-WAY TAP-OFF AND LOCKING
PULL BOX (300 x 300 x 200D)
DEVICE ABOVE CORRIDOR CEILING
(5-1000MHZ) (TYPICAL)
(2P-3W-20A-125VAC,
NEW DUPLEX RECEPTACLE
GROUNDING TYPE)
FOR CATV AMPLIFIER
TO PNLBD "C-4"
NEW SINGLE RECEPTACLE
(2P-3W-20A-250VAC,
GROUNDING TYPE)
FOR CATV AMPLIFIER
TO PNLBD "C-3"
ADEQUATE VENTILATION IN COMM RM
ON CATV CABINET TO ENSURE
NEMA 1 ENCL
AIR VENTS SHALL BE INSTALLED
CAPABILITIES, LOCKING DEVICE AND
TRUNK BRIDGE AMPLIFIERS W/RETURN PATH
NEW CATV DISTRIBUTION CABINET
INCLUDING NEW 3-WAY SPLITTER,
NEW GROUNDING WIRE
CABINET AT HIS OWN COST.
INSTALLATION AND PROVIDE APPROPRIATE CATV LINE TO NEW CATV DISTRIBUTION
CONTRACTOR SHALL COORDINATE WITH LG U+ FOR EXTERIOR CATV LINE
NOTES
1.
NEW ENTRANCE CAP
& SECOND RACK
ON EXTERIOR WALL
EXTERIOR
NEW O/H CATV CABLE
C T
V
COAXIAL CABLE
RG 11/U IN 21C
NNSC
REPAIR BUILDING S-11
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-13
ELECTRICAL
NOT TO SCALE
OUTDOOR
INDOOR
200AT
225AF
100AF
3P
3P
3P 2P
100AF
1P
CONDUCTOR, #3/0(G) IN 21C
NEW GROUNDING
CU BUS, 400A
22,000AIC SYM
G
S/NGND
100AF
321 5
2P
100AF
2P
20AT
100AF
FOR ABBREVIATION, LEGEND, GENERAL NOTES1.
& SCOPE OF WORK,
NOTES
"P"
EXT
SURGE SUPPRESSOR
TRANSIENT VOLTAGE
NEMA 1 ENCL
OHPU
1WAY: SPARE W/PULL WIRE & CAP
PVC CONDUIT
NEW U/G SEC LINE, 2WAY OF 103dia
CT BOX W/CT'S
200/5Ax3EA
NEMA 3R ENCL WHM
W/NEW ADVANCED DIGITAL WATTHOUR
METER, TRANSFORMER TYPE
WITH 15 MINUTES DEMAND REGISTER
FOR 3PH, 4WIRE, 120/208V, 60Hz
NEMA 3R ENCL
REPLACE THE DETERIORATED EXISTING WHM
1P
20AT
100AF
SPARE
1P
20AT
100AF100AF
50AT 60AT 50AT
A
IN 35C
3#6&
1#8
SEE SHEET NO. E-1.
EXIST/NEW POWER ONE-LINE DIAGRAM
"C"
3 100 22000
TOTAL LOAD
LOAD
TOTAL
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
MTD TYPE, NEMA 1 ENCL.
3PHASE ,4WIRE, 120/208V,
SPARE
59716
4500 4500
PANELBOARD "C"
60HZ, SN & GND, SURFACEPANELBOARD "MP" LOAD SCHEDULE
19272 22877 18280
MAIN 3P-225AF-200AT CIRCUIT BREAKER
4#2&1#8(G)
4#2 &
IN 53C
1#8(G)
4#8 &
IN 35C
1#10(G)
TOTAL DEMAND LOAD ; 48060 (VA)
NEW
2#12&1#12(G)
1P
20AT
100AF
1P
20AT
100AF
SPARE
NEW PANELBOARD "MP" LOAD SCHEDULE
EXIST/NEW POWER ONE-LINE DIAGRAM &
1WAY: 4-3/0
26852
9300 3650 3150 2500
48124160
100AT
A
PANELBOARD "P"
ELECTRIC HOT WATER HEATER 9000
2000 1000ELECTRIC UNIT HEATER-1 1000
SPARE
SPARE
SPARE
SPARE11
4#8&1#10(G)
2#8&1#10(G)
4#3/0 & 1#2(G)
4-3/0 & #2(G)IN 103C.
NON-FUSIBLE, NEMA 3R ENCL
SAFETY SWITCH, 3PST, 240V, 60A
TVSS
CONNECT NEW U/G SEC. LINE
ACCESSORIES (SEC. RACKS, ETC.)
TO EXIST SEC. LINE WITH ASSOCIATED
EP1EXIST ELEC POLE /
EP1
FOR OHPU
* ADDITIONAL LEGEND(THIS SHEET ONLY)
9362 9271 8280
SPACE SPACE
SPACE SPACE
SPACE SPACE
10001000
2#12&1#12(G)
100 100WALL EXHAUST FAN-1
20AT
EF
EUH
111111
EWH
DOMESTIC ELECTRIC HOT WATER HEATER
ELEC. RATING : 9KW, 208V, 1PH, 60Hz
0.017HP, 115V, 1PH, 60Hz
ELECTRIC UNIT HEATER
EXISTING MAIN PANELBOARD
WITH NEW MAIN PANELBOARD "MP"
REPLACE THE DETERIORATED
1P
20AT
100AF
SPARE
POWER: 1PH-208V, 25.4 AMP MCA, 40 AMP MOP
OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT
(UNDER MECH ITEM)
EXHAUST FAN
ELEC. RATING : 2KW, 208V, 1PH, 60Hz
EXTERIOR
2#8&1#10(G)
2#12&1#12(G)
"LC"
SW IN NEMA 3R ENCL
120V, COIL HAND-OFF-AUTO SEL.
MECHANICALLY HELD CONTACTS,
W/ 4P,20A,12OV, N.O.
NEW LIGHTING CONTRACTOR "LC"
HEAT PUMP UNIT
OUTDOOR SPLIT SYSTEM
3#6&1#8(G)
NNSC
REPAIR BUILDING S-11
TAK, YS
297038
LIGHTS 10W x10, 22Wx3, 100Wx2
LIGHTING CONTACTOR
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-14
ELECTRICAL
5001000
RCPT FOR CATV EQUIPMENT
TOTAL LOAD 31503650 2500
LOAD
TOTAL
PANELBOARD "C" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
3PHASE ,4WIRE, 120/208V,
60HZ, SN & GND, SURFACE
MTD TYPE, NEMA 1 ENCL.
CIRCUIT BREAKER
1000 1000 1
PHASE LOAD
A B PC
20100 10000
AT
SIZE
AF AIC
B CA N G
REMARK
2#12&1#12(G)
TVSS
11000
COMM RACK
RCPT FOR TTB
RCPT FOR CATV EQUIPMENT
SPARE
MAIN 3P-100AF-50AT CIRCUIT BREAKER
4#10&1#10(G)
SPACESPACE
SPACESPACE
SPACESPACE
SPACE - - - - - - - - -
SPACE - - - - - - - - -
SPACE - - - - - - - - -
SPACE - - - - - - - - -
SPACE - - - - - - - - -
3 30
SPARE 1000 1000
4#8 & 1#10(G)
TOTAL DEMAND LOAD ; 6600(VA)
1 100 10000 2#12&1#12(G)
TOTAL LOAD 26852
LOAD
TOTAL
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
MTD TYPE, NEMA 1 ENCL.
3PHASE ,4WIRE, 120/208V,
129 20
9 10
20 21
RCPTS 180VA x4EA
TOTAL DEMAND LOAD ; 19896 (VA)
60HZ, SN & GND, FLUSH
4#2 & 1#8(G)
RCPTS 180VA x4EA
RCPTS 180VA x4EA
RCPTS 180VA x1EA
MAIN 3P-100AF-100AT CIRCUIT BREAKER
LIGHTS LED 45W x2EA, 13W x3EA
RANGE HOOD
RCPTS 360VA x1EA
RCPTS 360VA x4EA
RCPTS 360VA x4EA
RCPTS 360VA x4EA 720
PANELBOARD "P" LOAD SCHEDULE
2#8&1#10(G)
2#12&1#12(G)
SCHEDULE
NEW PANELBOARD "P" & "C" LOAD
4.99W
4.99W
18Wx4EA, 13Wx1EA LIGHTS LED 45W x4EA, 22Wx1EA, REF, RCPTS 180VA x1EA 740 740
RCPTS 180VA x1EA
MICROWAVE
2325032506500ELEC RANGE
RCPTS 180VA x3EA 540
FIRE ALARM SYSTEM 500 500 DEVICE
LOCKING
HEAT PUMP UNIT
INDOOR SPLIT SYSTEM
VENTILATION UNIT
ENERGY RECOVERY
ELECTRIC WALL HEATER
SPARE
SPARE
180 180
1000 -
180 180
20 20
88 88
2#12&1#12(G)
9362 9271 8280
8SPLIT AIR CONDITIONING 3300 1650
2#12&1#12(G)
SPACE - - - - -
RCPTS 360VA x1EA 360 180 180
LIGHTS LED 50W x6EA, LIGHTS LED 50W x5EA, OUTDOOR BOLLARD
RCPTS 180VA x1EA
RCPTS 360VA x1EA
OUTDOOR BOLLARD
SPARE
29 SPARE 1000 1000
30 SPARE 1000
28 29
30 31
31 SPARE 1000
SPACE SPACE
11000
NNSC
REPAIR BUILDING S-11
LED EXTERIOR LIGHT 2-AWG#8 & 1-10(G) IN 27C.
NEW U/G CONCRETE ENCASED FOR BOLLARD
(NIC)
(NIC)
(NIC)
REF
(NIC)(NIC)
(NIC)
(NIC)
(NIC)
T-11
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-15
G N
C
OFF
AUTO
H
TO EXTERIOR LIGHTS (TYP)
WIRES
CONTROL
#14 AWG
FACING NORTH
2000W, 120V, ORIENTED
PHOTOELECTRIC CELL
SW IN NEMA 3R ENCL
120V, COIL HAND-OFF-AUTO SEL.
MECHANICALLY HELD CONTACTS,
W/ 4P,20A,12OV, N.O.
NEW LIGHTING CONTRACTOR "LC"
1/100SCALE:
NNSC
REPAIR BUILDING S-11
TAK, YS
297038
KS CERTIFIED, YONGKYONG LIGHTING OR APPROVED EQUAL
IP65 RATED, CAST, EXTRUDED ALUMINUM, 150(W)x1000(H)x150(D)
OPERATING TEMP: -20 TO 50 degC.
MIN EFFICIENCY: 110LM/W,
IES TYPE 2, CCT 3000K,
INPUT POWER: FREE VOLTAGE IN 120V TO 277 VAC RANGE
BOLLARD 10W LED EXTERIOR LIGHT, SYSTEM
TREATMENT
SEWAGE
LL
LL
L
L
L
L L
SEE DETAILS IN THIS DRAWING
NEW LIGHTING CONTACTOR "LC" WITH PHOTO CELL
NEW EXTERIOR BOLLARD LIGHT
SEE DETAILS IN THIS DRAWING
(TYPICAL OF 10EA)
G
TOP VIEW
WARRANTY: 10YEARS
MOUNTING ARM AND ACCESSORIES
IP66 RATED DIECAST ALUMINUM HOUSING,
OPERATING TEMP: -20 TO 50 degC.
MIN EFFICIENCY: 110LM/W,
IES TYPE 2, CCT 5700K,
SURGE PROTECTION: 10 KV,
OR 120/208/277 VAC MULTI-TAP.
INPUT POWER: FREE VOLTAGE IN 120V TO 277 VAC RANGE
UL LISTED. COLOR: DARK BRONZE
POLE MOUNTED 100W LED EXTERIOR LIGHT, (TYPE NS-A)
CONDUIT COUPLING
CONDUIT
STEEL WITH WELD
GROUND ROD,
19 diax3000 LG
COPPER CLAD
27 dia PVC
3000 PSI IN 28 DAYS
CONCRETE FOUNDATION
#6 "BC"
GROUT UNDER
CONDUIT
27 dia STEEL
ENTIRE BASE ANCHOR BOLTS, 19dia x 915LG
GL
HANDHOLE (76mmx127mm)
BASE W/COVER
PROJECTION
GROUND WIRE
ANCHOR BOLT
AND #6 "BC"
GROUND LUG
4.8mm THICK
4"X4" SQUARE
ANCHOR BOLT
POLE BASE
BASE COVER, 244dia
(DARK BRONZE)
ALUMINUM SQUARE STRAIGHT POLE
L L
L
MP8
M P -8
NEW U/G SEC LINE
NEW POLE MOUNTED LIGHT
SEE DETAILS IN THIS DRAWING
(TYPICAL OF 2EA)
NEW 2#8 & 1#10(G) IN 27dia C.
EXIST/NEW EXTERIOR LIGHTING PLAN
EXIST/NEW EXTERIOR LIGHTING PLAN
(KOREAN RECEPTACLE)
CIRCUIT INTERRUPTER TYPE,WEATHER PROOF
2P-3W-20A-220VAC, GROUND FAULT
OUTDOOR BOLLARD FOR DUPLEX RECEPTACLE,
"WP"
"WP"
U/G
U/G
CONNECT TO "P-25" IN PANEL BOARD "MP"
2-AWG#10 & 1-12(G) IN 21C. /
OUTDOOR BOLLARD RECEPTACLE
NEW U/G CONCRETE ENCASED FOR
CIRCUIT INTERRUPTER TYPE,WEATHER PROOF
2P-3W-20A-125V, GROUND FAULT
OUTDOOR BOLLARD FOR DUPLEX RECEPTACLE,
CONNECT TO "P-24" IN PANEL BOARD "MP"
2-AWG#10 & 1-12(G) IN 21C. /
OUTDOOR BOLLARD RECEPTACLE
NEW U/G CONCRETE ENCASED FOR
14.45
H S
S
H S
S
H S
S
S C 1
S C 1
S C 1
S C
S C
S C
S C
S C
S C
0 S
C
A 1
A 1
A 1
A 1
A 1
A 1
A 1
N M
S C
A 2 A 2
A 2 A 2
A 2
F L
F L
F L
B D
A
H S
T
H S
T
H S
T
B D 2
B D 2
B D 2
B D 2
B D 2
B D 2
B D 2
B D 2
B D 2
B D 2
N N
E
E
G P 1
G P 1
K
K
K
K
K
K
K
K
K
U
X
S C
S C
S C
T L
T L
T L
K P
N M
V
K
K
K
K
H S
T
H S
T
H S
T
G D 2G
D 2
G D 2
G D 2
J
IB
G D
P O
L
B D 0
P E
N M
V 1 V 1
Y 1
Y 1
Y 1
N M
A 3
A 3
X
X
X
X
X
X
A 4
A 4
U 4
U 4
U 4
U 4
U 4
U 4
V 4
V 4
V 4
V 4
N M
B A
L B
W M
P
IP
E
P
IP
E
P
IP
E
P
IP
E
P U
M P
P
U M
P
B D 3
W P
H S
F S 4
F S 4
CP
CP
S-39
C P
C P
N N
S C
S C
S C
S C
S C
S C
S C
S C
S C
A 1
A 1
A 2
A 2
A 2 A 2
A 2
A 2 A 2
A 2 A 2
A 2 A 2
A 2
A 2
A 2
S C
S C
S C
L
K P
S C
E
E
E
E
X
X
X
X
X
X
N N
N N
G P 1
M J
B D
A
B D
R
B D
R
B D
R
B D
R
N A
N
N A
N
N A
N
N A
N
N A
N
N A
N
N A
N
N A
N
N A
N
G D 2
G D 2
B D 1
B D 1
G D
R
G D 1
G D 1
J
J
R
R
H S
T
H S
T
H S
T
K
N N
N N
O
IL
O
IL
O
IL
O
IL
O
IL
C C 1
G D 0
G D 0
G D 0
G D 0
G D 0
G D 0
J O
J O
J O
N A
N
N A
N
N A
N
N M
B D 0
B D 0
B D 0
B D 0
B D 0
B D 0
B D 0
B D 0
B D 0
S C 0
S C 0 S C 0
S C 0
K P
P
IP
E
X
H S
T
H S
T
H S
T
T L
U 1
U 1
V 1
V 1
U
X
X
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
M B
M B
R
R
R
R
M M 1
M M 1
M M 1
M M 1
M M 1
M M 1
M M 1
M M 1
H S
T
H S
H S
T
U
X
X
U
X
X
U 2
U 2
G D 3
G D 3
G D 3
B D 3
B D 3
B D 3
B D 3
V 3
V 3
N N
T R
T R
T R
T R
T R
T R
T R
T R
T R
U 3
U 3
U 3
R B
D
K
K
K
K
K
R
R
B D 4
B D 4
B D 4
B D 4
B D 4
B D 4
B D 4
B D 4
B D 4
B D 4
B D 4
N A
N
N A
N
N A
N
N A
N
N A
N
G D 4
G D 4
G D 4
S C
S C
S C
F L
F L
F L
J
IB
H S
T
F
B D
Y
N M
B D 5
B D 5
A 5
A 5
A 5
A 5
A 5
A 5
A 5
G D 5
G D 5
G D 5
G D 5
G D 5
H S
T
H S
T
V 7
V 7
V 7
V 7
A 7
A 7
A 7
A 7
A 7
B D 7
B D 7
V
Y 7
Y 7
Y 7
Y 7
Y 7
Y 7
G D 7
G D 7
G D 7
G D 7
C 7
C 7
C 7
N A
N
N A
N
N A
N
N A
N
H S
T
U
A 8
A 8
A 8
A 8
A 8
B D 8
B D 8
B D 8 B
D 8 B
D 8
Y 8 Y 8
Y 8
G D 8
G D 8
G D 8
G D 8
H S
T
N A
N
N A
N
8N A
N
V 8
V 8
E V
B O
N G
A
G O
IL
T A
N K
T
A
G
O
IL
T A
N K
A/
G OI
LT
ANK
T
T
N N
C P
D 2
V 1
D 3
A 1
A 1
F S 1
K P
M B
M B
C 1
Y 2
Y 2
Y 2
S C
S C
S C
S C
S C 2
S C 2
S C 2
S C 2
V 2
V 2
N M
A 2
A
C P
C P
C P
C P
A .C
P
A V
E D
R
O A
D
F F
E
.4
S
A .C
P
A V
E D
R
O A
D
A .C
P
A V
E D
R
O A
D
C O
V E
R E
D
C O
N C
D
IT
C H
S T
O N
E
O
P E
N
C
O N
C
D
IT
C H
B U
N K
E R s
T R
S C
B D 8 B
D 8 B
D 8
B D 8
B D
B D 8
B D
G D 8
G D 8
N A
N
8N A
N
V 8
C 9
G P 9
G P 9
C C
A 1
A 1
A 1
A 1
A 1
A 1
A 1
A 1
A 1A 1
W P
W P
A 2 A 2
A 2
A 2
H S
T
H S
T
H S
T
H S
T
H S
T
H S
T
H S
T
H S
T
T R
N M
N M
N M
N M
V 1
V 1
V 1
V 1
E
E
E
A C
F L
F L
T R
T R
T R
H S
X
X
X
M B
M B
0P
P
V 2
S C
V
S C
V
F S 1
Y 2
Y 2
Y 2
Y 1
N N
N N
N N
V 4
V 4
V 4
V 4
V 4
N N
A 4
A 4
A 4
A 4
A 4
A 4
N M
N M
N M
V Y 3
H T 1
Y
H T
U
U
V Y
N M
N M
N M
S
IL
S
IL
S
IL
0S
IL
U
U
J
IB
T R
5U
V 5
V 5
B D 5
B D 5
B D 5
B D 5
B D 5
B D 5
B D 5
B D 5
B D 5
B D 5
P P
B S
0B S
L
L
L
L
L
G D 5
G D 5
G D 5
G D 5
D U
D U
B D 6
B D 6
B D 6
B D 7
B D 7
G D
G D
B D 8
B D 8
B D 8
N M
N M
B D 9
B D 9
B D 9
B D 9
B D 9
B O
N G
B O
N G
CP
CP
CP
CP
C C
T-7
S
W
C B
EXIST AC PAVEMENT
S
S -3
CP
C B
CP
C O
N
TAIN
ER
BO
X
C O
N
TAIN
ER
BO
X
WP
.4
F N S
H F
L
L
FNSH FL EL 53.65
T-10
ROOM
MECH
W
A 2 A 2
A 2
GENERATOR
C P
C P
T -1
F F
E
.6
C O
N 'C R
ETAIN
IN
G W
ALL
S H
E D
S C
S C
S C
S C
0 S
C
49.713
B D 2
49.486
B D 2
49.269
B D 2
B D 2
B D 2
E
X
S C
S C
S C
49.696
T L
48.589
K P
N M
V
K
K
K
K
P E
N M
.4
V 1 1
CP
S C
S C
A 8
B D 8
B D 8
B D 8
B D 8
G D 8
N A
N
V 8
E V
S T
O N
E
O
P E
N
C
O N
C
D
IT
C H
B D 8
B D 8
G D 8
N A
N
V 1
V 1
E
B D 5
CP
49.51
50.51
50.42
K
P E
S C
A 8
B D 8
B D 8
V 1
F F
E
.8
T
T
F F
E
.9
G A
L T
S
S
M E
C H
B
L D
G S
Y S T
T R
E A T
M E
N
S
W A
.6
.8
.9
.9
.7
DOWN
S
Y S T
E A T
M E
W A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
0 3m 12m
1:300SCALE
EXIST/NEW EXTERIOR ELECTRICAL PLAN
U/G
U/G
U/G
U/G
C
C
C
C
S
U/G
L
ELECTRICAL
U/G
C
E-16
D 0D
D
N
IC
N
IC
N
IC
R E F
N
IC
N
IC
N
IC
N
IC
N
IC
T -1
E P
S Y S T
E A T
M E
W A
6m
WHML
A
N
CP
U /G
U /G
S
T E L E
C O
M M
O /H
O /H
O /H
O /H
O /H
O/ H
O/H
O /H
O /H
O /H
O /H
O /H
O /H
O /H
O /H
O /H
O /H
S
S
S
S
S
S
S
S
S
S
NOTES
EXTERIOR AND INTERIOR TELECOMMUNICATION SYSTEM INCLUDING UNDERGROUND
TELECOMMINCATION LINE DISTRIBUTION PLAN TO MEET SITE CONDITION.
2. CONTRACTOR SHALL BE RESPOSIBLE TO VERIFY EXISTING SITE CONDITION AND
SYSTEM, FIBER OPTIC CABLE AND TELEPHONE CABLE AND PROVID SHOP DRAWING FOR
3. TO INSTALL TELECONNUNICATION LINE, ACTUAL ROUTE OF TELECOMMUNICATION LINE AND
TYPE OF CABLE SPLICE KITS SHALL BE COORDINATED WITH SIGNAL COMPANY THRU COR.
ARE ESTIMATED FOR BIDING PURPOSE ONLY. CONTRACTOR SHALL BE RESPONSIBLE TO
PROVIDE ACTUAL O/H AND U/G CABLING TO MEET SITE CONDITION AT HIS OWN COST.
TELECOMMUNICATION SYSTEM SUCH AS EXISTING TELEPHONE PEDESTAL, TELECOMMUNICATION
1. EXTERIOR TELECOMMUNICATION LINE AND SECONDARY POWER LINE SHOWN ON THIS DRAWING
NEW U/G SEC LINE
NEW 2#8 & 1#10(G) IN 27dia C.
CABLE IN NEW FABRIC INNER DUCT 4x3" IN 103dia C, U/G DUCT FOR UNCMAC NETWORK
NEW U/G 1-12 CORE STRAND SINGLE MODE FIBER OPTIC
NEW O/H SEC LINE
NEW 4#1/0 "WP"
(TYPICAL)
NEW O/H SEC LINE
NEW 4#3/0 "WP"
(TYPICAL)
U ./G
U ./G
U ./G
U ./G
U ./G
U ./G
U ./G
C
C C
C
C
C C
FIRE ALARM SYSTEM AT FIRE PUMP.
TO NEW FIRE ALARM SYSTEM AT S-11 FROM EXIST
MODULES FOR EACH END, TO BE CONNECTED
2-AWG#10 IN 35C, 4SETS OF ADDRESSABLE
NEW U/G SIGNALING LINE CIRCUITS,
NEW O/H SEC LINE
(TYPICAL)
(TYPCIAL)
FIBER OPTIC CABLE/CATV CABLE ETC. WITH MESSENGER WIRE
FOR NEW O/H SEC. LINE AND MOUNTING ACCESSORIES FOR
PROVIDE NEW SEC. RACKS (4 SPOOLS)
EXIST ELECTRIC POLE/
TELEC
O
M M /C
ATV
TELECO
M
M
/CATV
TELEC
O
M M /C
ATV
TELECO
M
M
/CATV
TELECO
M
M
/CATV
TE
LE
COMM/
CAT
V
C A T
V O /H
O /H
CP1
CP2
CP3
CP4
CP5
CP6
NEW 4#1/0 "WP" FROM CP1 TO CP6
CLOSURE 12CORE
NEW FIBER OPICE SLPLICE
(TYPICAL)
CABLE "WP" AND CATV CABLE WITH MESSENGER WIRE
NEW O/H 1-12 CORE STRAND SINGLE MODE FIBER OPTIC
(TYPICAL)
CABLE "WP" AND CATV CABLE WITH MESSENGER WIRE
NEW O/H 1-12 CORE STRAND SINGLE MODE FIBER OPTIC
(TYPICAL)
CABLE "WP" AND CATV CABLE WITH MESSENGER WIRE
NEW O/H 1-12 CORE STRAND SINGLE MODE FIBER OPTIC
(TYPCIAL)
FIBER OPTIC CABLE/CATV CABLE ETC. WITH MESSENGER WIRE
FOR NEW O/H SEC. LINE AND MOUNTING ACCESSORIES FOR
PROVIDE NEW SEC. RACKS (4 SPOOLS)
NEW CONCRETE ELECTRIC POLE/
EXIST/NEW EXTERIOR ELECTRICAL PLAN
NNSC
REPAIR BUILDING S-11
297038
TAK, YS
4. CONTRACTOR SHALL RESPONSIBLE TO RESTORE EXISTING COMMERCIAL NETWORK LINE AND
OTHER TELECOMMUNICATION LINE WITH REQUIRED ACCESSORIES TO BE OPERATIONAL AT HIS
OWN COST BY COORDINATING WITH USER THRU COR.
NEW O/H CCTV LINE
CONNECT TO CTC WITH BUILIDNG ATTACHMENT.
P
U /G
T
TELEPHONE CABLE
PROVIDE NEW SPLICE KIT FOR 25PAIR
RELOCATE EXIST TELEPHONE PEDESTAL,
NEW U/G 1-25PAIR TELEPHONE
CABLE IN 103C TO BE TERMINATED
AT TTB
NOT TO SCALE
15.
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES
10.
14.
ADDITIONAL RELAY IS PROVIDED AS REQUIRED.
SYNCHRONIZED. AUDIBLE APPLIANCES SHALL PROVIDE THE
SPECIFICATION SECTION 28.31.64.00.31(FA) AND NFPA 72.
APPROVED.
ARCHITECTURAL FEATURES.
LOCATIONS IN ACCORDANCE WITH THE MANUFACTURER'S
IN ACCORDANCE WITH THE APPLICABLE CODE, SPECIFICATIONS
THE MINIMUM REQUIRED AND THE FINAL QUANTITY SHALL BE
AND READY TO USE. THE NUMBER OF DEVICES SHOWN IS
BE PROVIDED WITH CLASS "A" MODULES
HORIZONTAL AND 305mm VERTICALLY.
TRANSMITTER AND ANTENNA.
PANEL COVER.
BREAKER AND/OR DISCONNECT SWITCH.
FOR THE FIRE ALARM AND DETECTION SYSTEM.
AUDIBILITY CALCULATION, WIRE SIZE, NO. OF WIRES
NOTES:
SHALL BE RESPONSIBLE FOR PROVIDING FIRE ALARM
FIRE ALARM CIRCUIT SHALL BE IDENTIFIED BY A RED LETTER
"FIRE ALARM CIRCUIT" ON THE DEDICATED POWER CIRCUIT
CIRCUIT SHALL BE INDICATED ON THE FIRE ALARM CONTROL
THE POWER CIRCUIT NUMBER DEDICATED TO FIRE ALARM
COAXIAL CABLE SHALL BE ONE PIECE BETWEEN BUILDING
SYSTEM SHALL BE SEPARATED BY A MINIMUM OF 1220mm
INCOMING AND OUTGOING CLASS "A" RACEWAY OF FA
7. ALL CLASS "A" EXCEPTIONS IN NFPA 72, 6.4.2.2.2 ARE
PROHIBITED FOR ALL IDC, NAC AND SLC.
ALL TAMPER SWITCHES, FLOW SWITCHES, PRESSURE
SWITCHES AND NON-ADDRESSABLE INITIATION DEVICES SHALL
COORDINATE THE EXACT DEVICE LOCATIONS WITH ELECTRICAL
AND MECHANICAL SYSTEM EQUIPMENT AND BUILDING
ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED OR FM
ALL AUDIBLE APPLIANCES WITHIN THE BUILDING AND ALL
VISUAL APPLIANCES WITHIN THE SAME ROOM SHALL BE
STANDARD TEMPORAL PATTERN, NFPA 72.
SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH
9.
11.
12.
13.
SHALL COMPLETE THE DESIGN AND INSTALL THE SYSTEM
8.
LISTED INSTALLATION REQUIREMENTS AND WIRE COUNT.
SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION DEVICE
AND MANUFACTURER'S EQUIPMENT LISTING.
THE FIRE ALARM SYSTEM IS CONCEPTUAL. THE CONTRACTOR
ALSO CONDUITS SHALL BE RUN AWAY AT LEAST 900mm
(3-FEET) FROM HVAC, HOT & COLD WATER PIPING.
FA SYSTEM SHALL OVERRIDE THE MASS NOTIFICATION SYSTEM.
SEE SHEET NO E-1.
J JJ
F
WP
F
M
EXT
1.
4.
3.
2.
5.
6.
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
J JJ JJ J JJ J
(WATTAGE AS REQ'D)
(TYPICAL)
F/A SPEAKER
/ FIRE ALARM VISUAL STROBES
(CANDELA AS REQ'D)
THE FIRE ALARM SYSTEM CONTRACTOR
SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH SPECIFICATION
AND NFPA 72.
NEW "WP" WALL MOUNTED TYPE
NEW WALL MOUNTED SPEAKER (WATTAGE AS REQ'D)
AIMAIMAIMAIMAIMAIMAIMAIMAIMAIMAIMAIM
NEW ADDRESSABLE RELAY
CONTROL PANEL (FACP)
EXIST ADDRESSABLE FIRE ALARM
AT BUILDING S-10
J J JJ
AIMAIMAIMAIM
CONTROL PANEL (FACP)
EXIST ADDRESSABLE FIRE ALARM
AT BUILDING S-25
J J JJ
AIMAIMAIMAIM
MODULE (TYPICAL OF 16)
CONNECT TO FIRE PUMP CONTROL PANEL
(TYPICAL)
NEW HOUSE PACKAGED TYPE FIRE PUMP SYSTEM
SGSGSGSGSGSGSGSG
SGSGSGSG
SG
SG SGSG
SG SGSG SG
(TYPICAL)
SURGE ARRESTER (DC VOLTAGE)
J
AIM
J
AIM
J
AIM
J
AIM
J
AIM
J
AIM
J
AIM
J
AIM
MODULE (TYPICAL OF 16)
FACPTO
FACPTO
FACPTO
FACPTO
(TYPICAL)
OF BUILDING S-25
FIR…