2613 Drawings.pdf
PDF 6 MB Posted
- Solicitation number
- 2613
- Issued by
- Kenosha County, Kellnersville Village, Wisconsin
About this file
File Summary
This is a comprehensive set of construction drawings for HVAC improvements at the Kenosha County Pre-Trial Facility located at 927 54th Street, Kenosha, Wisconsin. The project, identified as BID #2613 and project number K0450190, involves selective demolition and replacement of existing HVAC equipment across multiple floors of the facility. The scope of work includes removal and installation of VAV (Variable Air Volume) boxes with heating and cooling coils, replacement of rooftop air handling units and condensing equipment, installation of new ductwork and piping systems, and integration of temperature control systems with existing building management infrastructure. The drawings encompass basement, first floor, second floor, and third floor south sections of the facility, with work organized into phased implementation to maintain operational continuity of the pre-trial detention facility. The project was issued for bid on March 11, 2026, with comprehensive documentation including demolition plans, new work installation plans, equipment schedules, piping and ductwork details, and control system schematics.
The drawings specify equipment requirements including new variable frequency drive-equipped air handling units with heating and cooling capabilities, an energy recovery ventilator unit, air-cooled condensing units for cooling, exhaust fans with motorized dampers, and multiple VAV terminal units with individual zone control. All heating systems utilize hot water from existing building infrastructure with new three-way control valves for zone-level temperature management. New temperature sensors, CO and NO2 monitoring equipment for vehicle areas, and complete integration with building automation systems are required. The electrical work involves connections to existing 277/480V and 120/208V panels with new feeders, disconnect switches, and variable frequency drives for all fan motors. Contractor responsibilities include system draining and refilling during phased work, coordination with facility staff for after-hours access where needed, and restoration of all finishes and ceilings to match existing conditions. The work maintains strict adherence to fire and smoke damper requirements at all wall and floor penetrations, with all ductwork routed to remain concealed above ceilings or within walls where possible.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2613 Specifications.pdf | ||
| Vendor Responsibility Form Construction.pdf | ||
| 2613 Bid Documents.pdf | ||
| Background Check Form.docx | DOCX document | |
| 2613 Addendum 1.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT
LOCATION
PROJECT
LOCATION
PROJECT
LOCATION
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:1 P
M
G0.01
T
IT
L E
S H
E E
T K
E N
O S
H A
C O
U N
T Y
P R
E -T
R
IA
L F
A C
IL
IT
Y H
V A
C
IM
P R
O V
E M
E N
T S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
SHEET LIST
NUMBER SHEET NAME
G0.01 TITLE SHEET
G1.01 BASEMENT PHASING PLAN
G1.02 FIRST FLOOR SOUTH PHASING PLAN
G1.03 SECOND FLOOR SOUTH PHASING PLAN
G1.04 THIRD FLOOR SOUTH PHASING PLAN
M0.00 HVAC GENERAL NOTES, LEGEND, AND ABBREVIATIONS
M1.01 BASEMENT VENTILATION DEMOLITION PLAN
M1.02 BASEMENT HEATING DEMOLITION PLAN
M1.03 FIRST FLOOR SOUTH VENTILATION DEMOLITION PLAN
M1.04 FIRST FLOOR SOUTH HEATING DEMOLITION PLAN
M1.05 SECOND FLOOR SOUTH VENTILATION DEMOLITION PLAN
M1.06 SECOND FLOOR SOUTH HEATING DEMOLITION PLAN
M1.07 THIRD FLOOR SOUTH VENTILATION DEMOLITION PLAN
M1.08 THIRD FLOOR SOUTH HEATING DEMOLITION PLAN
M2.01 BASEMENT VENTILATION NEW WORK PLAN
M2.02 FIRST FLOOR SOUTH VENTILATION NEW WORK PLAN
M2.03 SECOND FLOOR SOUTH VENTILATION NEW WORK PLAN
M2.04 THIRD FLOOR SOUTH VENTILATION NEW WORK PLAN
M3.01 BASEMENT HEATING NEW WORK PLAN
M3.02 FIRST FLOOR SOUTH HEATING NEW WORK PLAN
M3.03 SECOND FLOOR SOUTH HEATING NEW WORK PLAN
M3.04 THIRD FLOOR SOUTH HEATING NEW WORK PLAN
M4.01 HVAC SECTIONS
M5.01 HVAC SCHEDULES
M5.02 HVAC DETAILS
M5.03 HVAC DETAILS
M5.04 HVAC CONTROL SCHEMATICS
M5.05 HVAC CONTROL SCHEMATICS
M5.06 HVAC CONTROL SCHEMATICS
E0.00 ELECTRICAL GENERAL NOTES, LEGEND, AND ABBREVIATIONS
E1.01 FIRST FLOOR SOUTH ELECTRICAL DEMOLITION PLAN
E1.02 THIRD FLOOR SOUTH ELECTRICAL DEMOLITION PLAN
E2.01 FIRST FLOOR SOUTH ELECTRICAL NEW WORK PLAN
E2.02 THIRD FLOOR SOUTH ELECTRICAL NEW WORK PLAN
E4.01 ELECTRICAL SCHEDULES
NOT TO SCALE1
STATE MAP
NOT TO SCALE3
PROJECT LOCATION MAP
NOT TO SCALE2
PROJECT AREA MAP
COUNTY OF KENOSHA PRE-TRIAL
FACILITY HVAC IMPROVEMENTS PH 1
927 54TH ST, KENOSHA, WI 53140
MARCH 11, 2026
ISSUED FOR BID
BID# 2613
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
HOLDING
HOLDING
HOLDING
HOLDING
GROUP HOLDING
JUVENILE HOLDING
JUVENILE HOLDING
SUMP ROOM
ELEV. EQUIP.
H.C. HOLDING
S.T.
S.P.
GROUP HOLDING
A/C
A/C
A/C
SALLY PORT
S.P.
ELEV S.P.
H.C. TLT.
T.
CONVEYANCE OFFICER
J.C.
0.S.
CORR.
VC01-7
VC01-6
VC01-5
VC01-4 VC01-3
VC01-2
VC01-1
ZONE 1
ZONE 1
MATCHLINE
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:1 P
M
G1.01
B A
S E
M E
N T
P H
A S
IN
G
P L A
N K
E N
O S
H A
C O
U N
T Y
P R
E -T
R
IA
L F
A C
IL
IT
Y H
V A
C
IM
P R
O V
E M
E N
T S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
BASEMENT PHASING PLAN
KEYNOTES (THIS SHEET)
1. UNOCCUPIED AREA, WORK TO BE DONE ON REGULAR SHIFT HOURS.
GENERAL NOTES
KEYPLAN_________
N.T.S.
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
1. CONTRACTOR IS RESPONSIBLE FOR DRAINING AND REFILLING THE
SYSTEM AS REQUIRED TO COMPLETE EACH PHASE AND ENSURE THE
AREA IS OPERATIONAL ONCE THE WORK IN THAT AREA IS COMPLETE.
IF ACCESS TO COMPLETED AREA IS REQUIRED, THIS MUST BE
COORDINATED WITH KENOSHA COUNTY STAFF AND WORK MAY NEED
TO BE PERFORMED AFTER HOURS. CONTRACTOR MUST INCLUDE
THIS COORDINATION IN THEIR BID, NO ADDITIONAL COMPENSATION
WILL BE PROVIDED.
2. CONTRACTOR IS RESPONSIBLE FOR COMPLETING ALL ELECTRICAL
AND TEMPERATURE CONTROLS WORK INCLUDING CONDUIT AND
WIRING INSTALLATION IN EACH PHASE AND ENSURE THE AREA IS
OPERATIONAL ONCE THE WORK IN THAT AREA IS COMPLETE. IF
ACCESS TO COMPLETED AREA IS REQUIRED, THIS MUST BE
COORDINATED WITH KENOSHA COUNTY STAFF AND WORK MAY NEED
TO BE PERFORMED AFTER HOURS. CONTRACTOR MUST INCLUDE
THIS COORDINATION IN THEIR BID, NO ADDITIONAL COMPENSATION
WILL BE PROVIDED.
CO
TS TS
ELEV. S.P.
FACILITY ADMIN
CONF.
CL.
115A
STORAGE
CONFERENCE
OFFICE
OFFICE
OFFICE
OFFICE
LOBBY
T.
J.C.
CLERICAL
CL.
104A
CORR.
RECORDS STORAGE
ELEC. RM.
116A
W.
M.
CORR.
VC03-1
VC03-2
VC03-3
VC03-4
VC03-5
VC03-6
VC03-7
VC03-8
VC03-9
VC03-10
VC03-11
(CUH03-5)
(CUH03-6)
ZONE 2
MATCHLINE
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:1 P
M
G1.02
F
IR
S T
F L
O O
R S
O U
T H
P H
A S
IN
G
P L A
N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
FIRST FLOOR SOUTH HEATING NEW WORK PLAN
KEYNOTES (THIS SHEET)
1. UNOCCUPIED AREA, WORK TO BE DONE ON REGULAR SHIFT HOURS.
2. PROVIDE TEMPORARY FULL PARTITION FOR WORK DONE IN SALLY
PORT. SEE M2.02.
KEYPLAN_________
N.T.S.
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
GENERAL NOTES
1. CONTRACTOR IS RESPONSIBLE FOR DRAINING AND REFILLING THE
SYSTEM AS REQUIRED TO COMPLETE EACH PHASE AND ENSURE THE
AREA IS OPERATIONAL ONCE THE WORK IN THAT AREA IS COMPLETE.
IF ACCESS TO COMPLETED AREA IS REQUIRED, THIS MUST BE
COORDINATED WITH KENOSHA COUNTY STAFF AND WORK MAY NEED
TO BE PERFORMED AFTER HOURS. CONTRACTOR MUST INCLUDE
THIS COORDINATION IN THEIR BID, NO ADDITIONAL COMPENSATION
WILL BE PROVIDED.
2. CONTRACTOR IS RESPONSIBLE FOR COMPLETING ALL ELECTRICAL
AND TEMPERATURE CONTROLS WORK INCLUDING CONDUIT AND
WIRING INSTALLATION IN EACH PHASE AND ENSURE THE AREA IS
OPERATIONAL ONCE THE WORK IN THAT AREA IS COMPLETE. IF
ACCESS TO COMPLETED AREA IS REQUIRED, THIS MUST BE
COORDINATED WITH KENOSHA COUNTY STAFF AND WORK MAY NEED
TO BE PERFORMED AFTER HOURS. CONTRACTOR MUST INCLUDE
WOMEN'S LOCKER
ROOM
TLT.
ELEV. S.P.
STORAGE
204B
OFFICE
OFFICE
OFFICE
CUSTODY STAFF
ASSEMBLY
CORR.
J.C.
STOR.
204A
VEST.
TLT.
MEN'S LOCKER ROOM
VC05-1
VC05-2
VC05-3
VC05-4
VC05-5 VC05-6
VC05-7
MATCHLINE
ZONE 3
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:1 P
M
G1.03
S E
C O
N D
F L
O O
R S
O U
T H
P H
A S
IN
G
P L
A N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
SECOND FLOOR SOUTH HEATING NEW WORK PLAN
KEYNOTES (THIS SHEET)
1. UNOCCUPIED AREA, WORK TO BE DONE ON REGULAR SHIFT HOURS.
KEYPLAN_________
N.T.S.
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
GENERAL NOTES
1. CONTRACTOR IS RESPONSIBLE FOR DRAINING AND REFILLING THE
SYSTEM AS REQUIRED TO COMPLETE EACH PHASE AND ENSURE THE
AREA IS OPERATIONAL ONCE THE WORK IN THAT AREA IS COMPLETE.
IF ACCESS TO COMPLETED AREA IS REQUIRED, THIS MUST BE
COORDINATED WITH KENOSHA COUNTY STAFF AND WORK MAY NEED
TO BE PERFORMED AFTER HOURS. CONTRACTOR MUST INCLUDE
THIS COORDINATION IN THEIR BID, NO ADDITIONAL COMPENSATION
WILL BE PROVIDED.
2. CONTRACTOR IS RESPONSIBLE FOR COMPLETING ALL ELECTRICAL
AND TEMPERATURE CONTROLS WORK INCLUDING CONDUIT AND
WIRING INSTALLATION IN EACH PHASE AND ENSURE THE AREA IS
OPERATIONAL ONCE THE WORK IN THAT AREA IS COMPLETE. IF
ACCESS TO COMPLETED AREA IS REQUIRED, THIS MUST BE
COORDINATED WITH KENOSHA COUNTY STAFF AND WORK MAY NEED
TO BE PERFORMED AFTER HOURS. CONTRACTOR MUST INCLUDE
T S
TS
SOUTH MECH.
PENTHOUSE
SOUTH STORAGE
MATCHLINE
(UH07-4)
(UH07-6)
CU-2
ZONE 4
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:1 P
M
G1.04
T H
IR
D
F L O
O R
S O
U T
H P
H A
S
IN
G P
L A
N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
THIRD FLOOR SOUTH HEATING NEW WORK PLAN
KEYNOTES (THIS SHEET)
1. UNOCCUPIED AREA. WORK DONE ON AHU WILL REQUIRE BUILDING
SHUT DOWN. COORDINATE THIS WORK WITH KENOSHA COUNTY.
ENSURE ALL WORK IS COMPLETED WITH-IN THE ALLOCATED SHUT
DOWN PERIOD.
KEYPLAN_________
N.T.S.
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
GENERAL NOTES
1. CONTRACTOR IS RESPONSIBLE FOR DRAINING AND REFILLING THE
SYSTEM AS REQUIRED TO COMPLETE EACH PHASE AND ENSURE THE
AREA IS OPERATIONAL ONCE THE WORK IN THAT AREA IS COMPLETE.
IF ACCESS TO COMPLETED AREA IS REQUIRED, THIS MUST BE
COORDINATED WITH KENOSHA COUNTY STAFF AND WORK MAY NEED
TO BE PERFORMED AFTER HOURS. CONTRACTOR MUST INCLUDE
THIS COORDINATION IN THEIR BID, NO ADDITIONAL COMPENSATION
WILL BE PROVIDED.
2. CONTRACTOR IS RESPONSIBLE FOR COMPLETING ALL ELECTRICAL
AND TEMPERATURE CONTROLS WORK INCLUDING CONDUIT AND
WIRING INSTALLATION IN EACH PHASE AND ENSURE THE AREA IS
OPERATIONAL ONCE THE WORK IN THAT AREA IS COMPLETE. IF
ACCESS TO COMPLETED AREA IS REQUIRED, THIS MUST BE
COORDINATED WITH KENOSHA COUNTY STAFF AND WORK MAY NEED
TO BE PERFORMED AFTER HOURS. CONTRACTOR MUST INCLUDE
M
M
M D
Ƨ Ƨ
C3H3
CH4
CO2
CO
H2
H2S
HZG
NO2
HS
TS
TH
TS
T
H
O2
TS
TS
CD
HWR
HWS
CONDENSATE DRAINAGE
HEATING WATER RETURN
HEATING WATER SUPPLY
REF-L
REF-S
REFRIGERANT-LIQUID
REFRIGERANT-SUCTION
REF-HG REFRIGERANT-HOT GAS
HEATING SYMBOLS
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL PLAN SYMBOLS
ROOM NAME AND NUMBER
NEW CONNECTION TO EXISTING
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
* NOTE *
ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL
OTHER DRAWINGS IN THIS SET.THE SYMBOLS AND ABBREVIATIONS SHOWN
ON THIS SHEET MAY OR MAY NOT BE USED IN THIS SET OF DRAWINGS.
Room
18"/12"
18"/12"ø
(18"ø
18"ø
EXHAUST AIR
OUTSIDE AIR
RETURN AIR
SUPPLY AIR
TRANSFER AIR
EXISTING DUCT
OVAL DUCT (WIDTH / HEIGHT)
RECTANGULAR DUCT (WIDTH x HEIGHT)
ROUND DUCT (DIAMETER)
DUCT TO BE REMOVED
Ø ROUND
ABV ABOVE
AC AIR CONDITIONING
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CW COLD WATER
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FD FLOOR DRAIN
FL FLOOR
FPM FEET PER MINUTE
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
HP HORSE POWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MU/A MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NTS NOT TO SCALE
O/A OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
R/A RETURN AIR
RD ROOF DRAIN
REC RECESSED
RED REDUCER
RM ROOM
RPM REVOLUTIONS PER MINUTE
SF SQUARE FOOT
S/A SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
SD SMOKE DAMPER
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TDR TRENCH DRAIN
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
WB WET BULB
AC AIR CONDITIONING UNIT
ACCU AIR COOLING CONDENSING UNIT
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
CUH CABINET UNIT HEATER
DC DUCT MOUNTED COIL
EF EXHAUST FAN
EDC ELECTRIC DUCT COIL
ET EXPANSION TANK
FCU FAN COIL UNIT
GRV GRAVITY ROOF VENTILATOR
HWP HEATING WATER PUMP
RE RETURN/EXHAUST FAN
UH UNIT HEATER
EQUIPMENT ABBREVIATIONS
18"/18" SA
18"/18" OA
18"/18" RA
18"/18" TA
18"/18" EA
PIPING ACCESSORY SYMBOLS
BALANCING VALVE
CIRCUIT SETTER
GATE VALVE
STRAINER
ELEC. CONTROL
BALL VALVE
SOLENOID VALVE
CHECK VALVE
PRESS REGULATORBUTTERFLY VALVE
3-WAY ELEC. CONTROL
HVAC ABBREVIATIONS
CPD CONDENSATE PUMP DISCHARGE
VENTILATION SYMBOLS
HVAC LEGEND
SUPPLY DUCT UP OR TOWARD
SUPPLY DUCT DOWN OR AWAY
RETURN DUCT UP OR TOWARD
EXHAUST DUCT UP OR TOWARD
RETURN DUCT DOWN OR AWAY
EXHAUST DUCT DOWN OR AWAY
FLEXIBLE DUCT
SUPPLY DIFFUSER (WITH HARD DUCT)
SUPPLY DIFFUSER (WITH FLEX DUCT)
RETURN GRILLE OR REGISTER (WITH HARD DUCT)
RETURN GRILLE OR REGISTER (WITH FLEX DUCT)
EXHAUST GRILLE OR REGISTER (WITH HARD DUCT)
EXHAUST GRILLE OR REGISTER (WITH FLEX DUCT)
LAY-IN GRILLE / REGISTER / DIFFUSER
DUCT MOUNTED SUPPLY GRILLES
DUCT MOUNTED RETURN/EXHAUST GRILLES
DUCTWORK (DIRECTION OF AIRFLOW)
90° ELBOW RADIUS AND MITERED W/ TURNING VANES
BRANCH DUCT TAP
BEVELED (RECTANGULAR BRANCH)
CONICAL (ROUND BRANCH)
CONICAL W/ VOLUME DAMPER (ROUND BRANCH)
SIZE TRANSITION
A1 125
AIRFLOW (CFM)
TYPE MARK
LINEAR SLOT DIFFUSERS
ELBOW DOWN OR AWAY
ELBOW UP OR TOWARD
TEE DOWN OR AWAY
TEE UP OR TOWARD
RISE OR DROP
90° ELBOW
PIPE TEE
PIPE TAKEOFF (FROM BOTTOM OF MAIN)
PIPE TAKEOFF (FROM TOP OF MAIN)
45° ELBOW
45° BRANCH
CAP
DIRECTION OF FLOW
DUCT ACCESSORY SYMBOLS
MOTORIZED DAMPER
BACKDRAFT DAMPER
MANUAL BALANCING DAMPERCOMB. FIRE/SMOKE DAMPER
FIRE DAMPER
SMOKE DAMPER
HVAC CONTROL PANEL
C3H3 DETECTOR
CH4 DETECTOR
CO2 DETECTOR
CO DETECTOR
H2 DETECTOR
H2S DETECTOR
HAZARDOUS GAS DETECTOR
NO2 DETECTOR
HUMIDITY SENSOR
TEMPERATURE SENSOR
TEMPERATURE & HUMIDITY SENSOR
TEMPERATURE SENSOR
THERMOSTAT
HUMIDISTAT
O2 DETECTOR
HVAC CONTROL SYMBOLS
CONTROL WIRING
HVAC EQUIPMENT SYMBOLS
VAV-XX
(VAV-XX)
NEW EQUIPMENT
EXISTING EQUIPMENT TO REMAIN
EQUIPMENT TO BE REMOVED
EQUIPMENT BY OTHER DISCIPLINES
ROOM ABBREVIATIONS
CL CLOSET
COM COMMUNICATIONS
CORR CORRIDOR
JC JANITOR'S CLOSET
M. MEN'S RESTROOM
SP SALLY PORT
TLT TOILET
W. WOMEN'S RESTROOM
S EXISTING SUPPLY DIFFUSER
R EXISTING RETURN REGISTER
E EXISTING EXHAUST REGISTER
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:2 P
M
M0.00
H V
A C
G E
N E
R A
L N
O T
E S
L
E G
E N
D
A N
D A
B B
R E
V
IA
T
IO
N S
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
HEATING GENERAL NOTES
1. PIPING IS SHOWN IN SCHEMATIC FORM ONLY, CHANGES IN ELEVATION ARE NOT NECESSARILY SHOWN.
ROUTE PIPING IN AN ORDERLY MANNER AS REQUIRED FOR CLEARANCE WITH STRUCTURAL CONDITIONS.
COORDINATE LOCATION OF PIPING WITH OTHER TRADES PRIOR TO INSTALLATION. WHERE POSSIBLE, RACK
PIPING HORIZONTALLY OR VERTICALLY.
2. COORDINATE LOCATIONS AND SIZES OF PIPING CONNECTIONS TO EQUIPMENT BEING PROVIDED BY OTHERS.
3. PROVIDE AND INSTALL ISOLATION VALVES IN ALL BRANCH PIPING.
4. CONNECTIONS TO EQUIPMENT SHALL BE PROVIDED WITH ISOLATION VALVES AND UNIONS TO FACILITATE
EQUIPMENT REMOVAL.
5. LOCATE ALL ISOLATION VALVES IN AN ACCESSIBLE LOCATION. WHERE VALVES ARE NOT ACCESSIBLE
PROVIDE 12X12 ACCESS DOOR.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ADEQUATE SUPPORTING SYSTEMS AND DEVICES FOR
ALL HEATING PIPING, EQUIPMENT, AND ACCESSORIES.
7. SEE HEATING DETAILS FOR EXACT PIPING CONNECTIONS TO EQUIPMENT, INCLUDING VALVES, TRAPS, AND
SYSTEM ACCESSORIES.
8. BALANCING VALVES SHALL BE, AT A MINIMUM, ONE PIPE SIZE SMALLER THAN THE PIPING IN WHICH THEY ARE INSTALLED. CONTRACTOR SHALL VERIFY THAT VALVE CAN BE ADJUSTED TO MEET FLOW REQUIREMENTS
WITHOUT THE PRODUCTION OF UNACCEPTABLE NOISE.
9. LOCATE AND INSTALL ALL HEATING EQUIPMENT TO PROVIDE MANUFACTURER'S MINIMUM SERVICE
CLEARANCES.
11. THE LOCATIONS AND SIZES OF EXISTING PIPING AND EQUIPMENT HAS BEEN TAKEN FROM "AS-BUILT" DRAWINGS AND INFORMATION PROVIDED BY THE OWNER. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS PRIOR TO START OF WORK.
12. ALL CONNECTIONS TO, OR SHUTDOWNS OF, EXISTING SYSTEMS SHALL BE COORDINATED WITH THE OWNER TO PROVIDE MINIMUM INTERFERENCE WITH THEIR OPERATION AND DOWNTIME OF THE SYSTEM. PROVIDE PROPOSED PHASING PLAN FOR CONNECTIONS TO EXISTING SERVICES TO OWNER FOR APPROVAL PRIOR TO
STARTING OF WORK.
13. SUPPLY AND RETURN PIPING TO COILS ARE THE SAME SIZE.
16. CONDENSATE DRAINS SHALL BE SUPPLIED FOR ALL COOLING EQUIPMENT. CONTRACTOR SHALL ENSURE PROPER INSTALLATION AND DRAINAGE AS REQUIRED BY FEDERAL, STATE, AND LOCAL CODES. CONDENSATE
PIPING SHALL BE TYPE "L" COPPER.
18. COORDINATE THE EXACT LOCATION OF ALL CEILING DIFFUSERS, REGISTERS, AND GRILLES WITH NEW AND
EXISTING LIGHTING.
19. PROVIDE DIFFUSERS AND REGISTERS WITH 4-WAY BLOW PATTERN UNLESS OTHERWISE NOTED.
20. PROVIDE A 4" HOUSEKEEPING PAD FOR EACH PIECE OF MECHANICAL EQUIPMENT. COORDINATE SIZES WITH
MECHANICAL EQUIPMENT SELECTED.
HEATING DEMOLITION GENERAL NOTES
1. VERIFY EXACT SIZE AND LOCATION OF EXISTING UTILITIES PRIOR TO START OF DEMOLITION.
2. DISCONNECT ALL HEATING PIPING CONNECTIONS TO EQUIPMENT BEING REMOVED.
3. UNLESS OTHERWISE NOTED, REMOVAL OF PIPING AND/OR EQUIPMENT SHALL INCLUDE ALL INSULATION, VALVES, HANGERS, SUPPORTS, EQUIPMENT PADS, FLASHING, CONTROLS, AND ASSOCIATED ACCESSORIES.
4. UNLESS OTHERWISE NOTED, REMOVAL OF PIPING SHALL BE BACK TO THE MAIN OR LAST ACTIVE SERVICE.
5. ALL OPENINGS OR HOLES LEFT IN EXISTING WALLS, FLOORS, AND CEILINGS TO REMAIN, INCLUDING CHASES, SHALL BE PATCHED TO MATCH EXISTING CONDITIONS BY THE CONTRACTOR WHOSE WORK HAS CREATED THE OPENING OR HOLE. PATCHING SHALL BE IN ACCORDANCE WITH THE APPROPRIATE DIVISION OF THE
SPECIFICATIONS.
VENTILATION GENERAL NOTES
1. DUCTWORK IS SHOWN IN SCHEMATIC FORM ONLY, OFFSETS AND CHANGES IN ELEVATIONS ARE NOT
NECESSARILY SHOWN. ROUTE DUCTWORK IN AN ORDERLY MANNER AS REQUIRED FOR CLEARANCE WITH
STRUCTURAL CONDITIONS. COORDINATE LOCATION OF DUCTWORK PRIOR TO INSTALLATION.
2. COORDINATE LOCATIONS AND SIZES OF CONNECTIONS TO EQUIPMENT BEING PROVIDED BY OTHERS.
3. PROVIDE AND INSTALL MANUAL BALANCING DAMPERS IN ALL BRANCH DUCTWORK AND AT EACH AIR INLET
AND OUTLET.
4. LOCATE ALL MANUAL BALANCING DAMPERS IN AN ACCESSIBLE LOCATION. WHERE DAMPERS ARE NOT ACCESSIBLE PROVIDE MINIMUM 18x18 ACCESS DOOR.
5. UNLESS OTHERWISE NOTED, CONCEAL ALL DUCTWORK ABOVE CEILINGS, IN WALLS, OR INSIDE CHASES.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ADEQUATE SUPPORTING SYSTEMS AND DEVICES FOR
ALL DUCTWORK, VENTILATION EQUIPMENT, AND ACCESSORIES.
7. PROVIDE AND INSTALL SLEEVES FOR ALL DUCTWORK PASSING THROUGH WALLS AND FLOORS.
8. PROVIDE FIRE AND/OR SMOKE DAMPERS AT ALL PENETRATIONS OF FIRE AND/OR SMOKE RATED WALLS, CEILINGS, AND FLOORS. SEE ARCHITECTURAL PLANS FOR LOCATIONS OF FIRE AND/OR SMOKE RATED WALLS, CEILINGS, AND FLOORS. PROVIDE ACCESS DOOR(S) TO FACILITATE RESETTING OF DAMPERS.
9. PROVIDE RIGID METAL DUCT, WITH NO EXCEPTION, WHERE FIRE AND/OR SMOKE RATED WALLS, CEILINGS, AND FLOORS ARE PENETRATED.
10. FOR DUCT CONNECTIONS TO TERMINAL DEVICES, FANS, AND OTHER EQUIPMENT SEE VENTILATION DETAILS.
11. COORDINATE LOCATIONS OF ALL DIFFUSERS, GRILLES, AND REGISTERS WITH ARCHITECTURAL REFLECTED
CEILING PLANS.
12. LOCATE AND INSTALL ALL VENTILATION EQUIPMENT TO PROVIDE MANUFACTURER'S MINIMUM SERVICE
CLEARANCES.
13. THE LOCATIONS AND SIZES OF EXISTING DUCTWORK AND EQUIPMENT HAS BEEN TAKEN FROM "AS-BUILT" DRAWINGS AND INFORMATION PROVIDED BY THE OWNER. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS PRIOR TO START OF WORK.
14. ALL CONNECTIONS TO, OR SHUTDOWNS OF, EXISTING SYSTEMS SHALL BE COORDINATED WITH THE OWNER TO PROVIDE MINIMUM INTERFERENCE WITH THEIR OPERATION AND DOWNTIME OF THE SYSTEM. PROVIDE PROPOSED PHASING PLAN FOR CONNECTIONS TO EXISTING SERVICES TO OWNER FOR APPROVAL PRIOR TO
STARTING WORK.
VENTILATION DEMOLITION GENERAL NOTES
1. VERIFY EXACT SIZE AND LOCATION OF EXISTING UTILITIES PRIOR TO START OF DEMOLITION.
2. DISCONNECT ALL DUCTWORK CONNECTIONS TO EQUIPMENT BEING REMOVED.
3. ALL OPENINGS OR HOLES LEFT IN EXISTING WALLS, FLOORS, AND CEILINGS TO REMAIN, INCLUDING CHASES, SHALL BE PATCHED TO MATCH EXISTING CONDITIONS BY THE CONTRACTOR WHOSE WORK HAS CREATED THE OPENING OR HOLE. PATCHING SHALL BE IN ACCORDANCE WITH THE APPROPRIATE DIVISION OF THE
SPECIFICATIONS.
TEMPERATURE CONTROL GENERAL NOTES
1 COORDINATE EXACT LOCATIONS OF EQUIPMENT.
2 WALL THERMOSTATS AND/OR TEMPERATURE SENSORS SHALL BE INSTALLED AT 48" TO 54" ABOVE FLOOR ADJACENT TO OR ABOVE LIGHT CONTROL DEVICE. DO NOT INSTALL THERMOSTATS AND/OR TEMPERATURE
SENSORS ON EXTERIOR WALLS.
3 UNLESS OTHERWISE NOTED, TEMPERATURE CONTROL WIRING/PIPING SHALL BE CONCEALED ABOVE
CEILINGS, IN WALLS, OR INSIDE CHASES.
4 CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ADEQUATE SUPPORTING SYSTEMS FOR
TEMPERATURE CONTROL WIRING/PIPING, EQUIPMENT, AND ACCESSORIES.
5 SEE SPECIFICATION FOR CONTROLS & INSTRUMENTATION REQUIREMENTS AND THE SEQUENCE OF
OPERATION FOR EQUIPMENT.
6 TEMPERATURE CONTROLS CABLING SHALL BE PLENUM RATED.
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
TEMPERATURE CONTROL DEMOLITION NOTES
1. CONTRACTOR SHALL DISCONNECT EXISTING TEMPERATURE CONTROL COMPONENTS, ASSOCIATED
TUBING, AND DEVICES. REMOVE PNEUMATIC TUBING/PIPING BACK TO MAIN AND CAP. UNLESS OTHERWISE NOTED, INSTALL NEW DEVICES ON EXISTING LOCATIONS. MATCH ANY OPENINGS OR PATCHES TO
ADJACENT SURFACES TO OWNER'S SATISFACTION.
2. THE CONTRACTOR SHALL DISCONNECT EXISTING BUILDING TEMPERATURE CONTROL SYSTEM FROM THE
NETWORK AND PROVIDE ALL WORK ASSOCIATED WITH DEMOLITION.
3. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED WORK TO MAINTAIN THE CONTINUITY OF THE EXISTING
NETWORK UNTIL THE NEW NETWORK HAS BEEN ESTABLIISHED.
SITE/PROJECT SPECIFIC REQUIREMENTS
1. EXISTING FINISHES - CONTRACTOR SHALL PROTECT ALL EXISTING FINISHED SURFACES (FLOORS, WALLS, CEILINGS, STEPS, RAILING, FURNISHINGS, ETC.) FROM DAMAGE DURING THE PROJECT. CONTRACTOR IS RESPONSIBLE TO REPAIR OR REPLACE COMPONENTS DAMAGED AS A RESULT OF WORK DONE FOR
THE PROJECT.
2. TEMPORARY REMOVAL OF COMPONENTS - CONTRACTOR MAY TEMPORARILY REMOVE EXISTING DOORS, RAILINGS, FURNISHINGS, ETC. WHILE LOADING AND UNLOADING EQUIPMENT. CONTRACTOR SHALL PROMPTLY REINSTALL OR REPLACE ANY REMOVED COMPONENTS ONCE ADDITIONAL CLEARANCE IS NOT
NEEDED.
3. CONTRACTOR SHALL MAINTAIN MANUFACTURER REQUIRED EQUIPMENT CLEARANCES DURING
EQUIPMENT INSTALLATION.
TS
TS
T S
TS
TS
T S
HOLDING
HOLDING
GROUP HOLDING
JUVENILE HOLDING
JUVENILE HOLDING
SUMP ROOM
ELEV. EQUIP.
H.C. HOLDING
S.T.
S.P.
GROUP HOLDING
A/C
A/C
A/C
SALLY PORT
S.P.
ELEV S.P.
H.C. TLT.
T.
CONVEYANCE OFFICER
J.C.
0.S.
CORR.
(S A
(S A
(S A
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(RA)
(EA)
(TYP.)
(TYP.)
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:2 P
M
M1.01
B A
S E
M E
N T
V E
N T
IL
A
T
IO
N D
E M
O L
IT
IO
N
P L
A N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
BASEMENT VENTILATION DEMOLITION PLAN
DEMOLITION KEYNOTES
1. REMOVE EXISTING VAV BOX WITH HW REHEAT AND ASSOCIATED
CONTROLS. DISCONNECT TRANSITION FITTINGS ON BOTH SIDES OF
BOX. REMOVE EXISTING GYPSUM BOARD CEILING.
2. REMOVE EXISTING VAV BOX WITH HW REHEAT AND ASSOCIATED
CONTROLS. DISCONNECT TRANSITION FITTINGS ON BOTH SIDES OF
BOX.
3. REMOVE TEMPERTAURE SENSOR AND ASSOCIATED WIRING.
REPLACE WITH NEW.
KEYPLAN________
N.T.S.
GENERAL NOTES
1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND
REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO
INSTALL THEIR WORK.
2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE
DAMAGED DURING WORK.
3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW
DEMOLITION OF EXISTING DUCTWORK AND INSTALLATION OF
DUCTWORK.
4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
5. EXISTING TRANSFER OPENINGS THROUGHOUT TO REMAIN.
KEYNOTES (THIS SHEET)
1. EXISTING EXHAUST GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
2. EXISTING RETURN GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
3. EXISTING SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK TO
REMAIN.
4. EXISTING EXHAUST DUCT UP TO FLOOR ABOVE TO REMAIN.
5. EXISTING RETURN DUCT UP TO FLOOR ABOVE TO REMAIN.
6. EXISTING SUPPLY DUCT UP TO FLOOR ABOVE TO REMAIN.
7. UNEXCAVATED SITE. NO WORK.
10. EXISTING SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK TO
REMAIN.
HOLDING
GROUP HOLDING
JUVENILE HOLDING
JUVENILE HOLDING
SUMP ROOM
ELEV. EQUIP.
H.C. HOLDING
S.T.
S.P.
GROUP HOLDING
A/C
A/C
A/C
SALLY PORT
S.P.
ELEV S.P.
H.C. TLT.
T.
CONVEYANCE OFFICER
J.C.
0.S.
CORR.
3/4"
3/4"
1"
(H W
R
(H W
S
(H W
R
(H W
S
1 1/4"
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:3 P
M
M1.02
B A
S E
M E
N T
H E
A T
IN
G
D E
M O
L
IT
IO
N
P L A
N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
BASEMENT HEATING DEMOLITION PLAN
DEMOLITION KEYNOTES
1. DISCONNECT PIPING AND REMOVE EXISTING VAV BOX AND COIL.
REMOVE EXISTING GYPSUM BOARD CEILING.
2. DISCONNECT PIPING AND REMOVE EXISTING VAV BOX AND COIL.
3. REMOVE EXISTING HWS/R PIPING. REMOVE GYPSUM BOARD
CEILING.
4. DISCONNECT HWS/R PIPING FOR NEW VALVES. SEE M3.01. REMOVE
GYPSUM BOARD CEILING.
5. REMOVE EXISTING PIPING FROM VAV BACK TO VALVES.
KEYPLAN_________
N.T.S.
GENERAL NOTES
1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND
REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO
INSTALL THEIR WORK.
2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE
DAMAGED DURING WORK.
3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW
DEMOLITION OF EXISTING PIPING AND INSTALLATION OF
PIPING.
4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
KEYNOTES (THIS SHEET)
1. HWS/R PIPING ABOVE CEILING TO REMAIN.
2. HWS/R PIPING UP TO FLOOR ABOVE TO REMAIN.
3. UNEXCAVATED SITE. NO WORK.
TS
TS
T S
T S
TS
T S
T S
TS TS
TS
TS
T S
ELEV. S.P.
FACILITY ADMIN
CONF.
CL.
115A
STORAGE
CONFERENCE
OFFICE
OFFICE
OFFICE
OFFICE
LOBBY
T.
J.C.
CLERICAL
CL.
104A
CORR.
RECORDS STORAGE
ELEC. RM.
116A
W.
M.
CORR.
(SA)
(SA)
(S A
(S
A
MATCHLINE
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(RA)
(E A
(TYP.)
4 5 6
(TYP.)
6 6
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:3 P
M
M1.03
F
IR
S T
F L
O O
R S
O U
T H
V E
N T
IL
A
T
IO
N D
E M
O L
IT
IO
N P
L A
N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
FIRST FLOOR SOUTH VENTILATION DEMOLITION PLAN
DEMOLITION KEYNOTES
1. REMOVE EXISTING VAV BOX WITH HW REHEAT AND ASSOCIATED
CONTROLS. DISCONNECT TRANSITION FITTINGS ON BOTH SIDES OF
BOX.
2. REMOVE EXISTING SA DUCT. ASSOCIATED SA DIFFUSERS TO
REMAIN. SEE M2.02 FOR NEW WORK.
3. REMOVE EXISTING VAV BOX WITH HW REHEAT AND ASSOCIATED
CONTROLS. DISCONNECT TRANSITION FITTINGS ON BOTH SIDES OF
BOX. REMOVE EXISTING GYPSUM BOARD CEILING.
4. REMOVE TEMPERTAURE SENSOR AND ASSOCIATED WIRING.
REPLACE WITH NEW.
5. REMOVE EXISTING TEMPERATURE CONTROLS SERVING HOT WATER
CABINET HEATER. EXISTING CABINET HEATER TO REMAIN. REMOVE
EXISTING TEMPERATURE SENSOR.
6. REMOVE EXISTING TEMPERATURE CONTROLS SERVING HOT WATER
UNIT HEATER. EXISTING UNIT HEATER TO REMAIN.
7. REMOVE IN-UNIT THERMOSTAT.
KEYPLAN_________
N.T.S.
GENERAL NOTES
1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND
REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO
INSTALL THEIR WORK.
2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE
DAMAGED DURING WORK.
3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW
DEMOLITION OF EXISTING DUCTWORK AND INSTALLATION OF
DUCTWORK.
4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
5. EXISTING TRANSFER OPENINGS THROUGHOUT TO REMAIN.
KEYNOTES (THIS SHEET)
1. EXISTING EXHAUST GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
2. EXISTING RETURN GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
3. EXISTING SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK TO
REMAIN.
4. EXISTING EXHAUST DUCT UP TO FLOOR ABOVE TO REMAIN.
5. EXISTING RETURN DUCT UP TO FLOOR ABOVE TO REMAIN.
6. EXISTING SUPPLY DUCT UP TO FLOOR ABOVE TO REMAIN.
ELEV. S.P.
FACILITY ADMIN
CONF.
CL.
115A
STORAGE
CONFERENCE
OFFICE
OFFICE
OFFICE
OFFICE
LOBBY
T.
J.C.
CLERICAL
CL.
104A
CORR.
RECORDS STORAGE
ELEC. RM.
116A
W.
M.
110CORR.
(HWS)
(HWR)
(H W
S
(H W
R
(H W
S
(H W
R
MATCHLINE
1 1/2"
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:3 P
M
M1.04
F
IR
S T
F L O
O R
S O
U T
H H
E A
T
IN
G D
E M
O L
IT
IO
N
P L
A N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
FIRST FLOOR SOUTH HEATING DEMOLITION PLAN
DEMOLITION KEYNOTES
1. DISCONNECT PIPING AND REMOVE EXISTING VAV BOX AND COIL.
2. DISCONNECT PIPING AND REMOVE EXISTING VAV BOX AND COIL.
REMOVE EXISTING GYPSUM BOARD CEILING.
3. REMOVE HWS/R PIPING FOR NEW VALVES. SEE M3.02.
4. REMOVE EXISTING HWS/R PIPING. REMOVE GYPSUM BOARD
CEILING.
5. REMOVE EXISTING PIPING FROM VAV BACK TO VALVES.
6. REMOVE EXISTING PIPING FROM CABINET UNIT HEATER BACK TO
VALVES.
7. REMOVE EXISTING PIPING FROM UNIT HEATER BACK TO VALVES.
KEYPLAN_________
N.T.S.
GENERAL NOTES
KEYNOTES (THIS SHEET)
1. EXISTING HOT WATER CABINET HEATER TO REMAIN.
2. HWS/R PIPING ABOVE CEILING TO REMAIN.
3. HWS/R PIPING UP TO FLOOR ABOVE TO REMAIN.
4. EXISTING HOT WATER UNIT HEATER TO REMAIN.
1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND
REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO
INSTALL THEIR WORK.
2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE
DAMAGED DURING WORK.
3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW
DEMOLITION OF EXISTING PIPING AND INSTALLATION OF
PIPING.
4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
S
T S
T S
T S
TS
T S
TS
WOMEN'S LOCKER
ROOM
TLT.
ELEV. S.P.
STORAGE
204B
OFFICE
OFFICE
OFFICE
CUSTODY STAFF
ASSEMBLY
CORR.
J.C.
STOR.
204AVEST.
TLT.
MEN'S LOCKER ROOM
(SA)
(S A
(SA)
MATCHLINE
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(E A
(RA)
(TYP.)
4 5 6
(TYP.)
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:4 P
M
M1.05
S E
C O
N D
F L
O O
R S
O U
T H
V E
N T
IL
A
T
IO
N D
E M
O L
IT
IO
N P
L A
N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
SECOND FLOOR SOUTH VENTILATION DEMOLITION PLAN
DEMOLITION KEYNOTES
1. REMOVE EXISTING VAV BOX AND COIL. DISCONNECT TRANSITION
FITTINGS ON BOTH SIDES OF BOX.
2. REMOVE EXISTING VAV TERMINAL BOX. DISCONNECT TRANSITION
FITTINGS ON BOTH SIDES OF THE BOX.
3. REMOVE EXISTING VAV BOX AND COIL. DISCONNECT TRANSITION
FITTINGS ON BOTH SIDES OF BOX. REMOVE EXISTING GYPSUM
BOARD CEILING.
4. REMOVE TEMPERTAURE SENSOR AND ASSOCIATED WIRING.
REPLACE WITH NEW.
KEYPLAN_________
N.T.S.
GENERAL NOTES
1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND
REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO
INSTALL THEIR WORK.
2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE
DAMAGED DURING WORK.
3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW
DEMOLITION OF EXISTING DUCTWORK AND INSTALLATION OF
DUCTWORK.
4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
5. EXISTING TRANSFER OPENINGS THROUGHOUT TO REMAIN.
KEYNOTES (THIS SHEET)
1. EXISTING EXHAUST GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
2. EXISTING RETURN GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
3. EXISTING SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK TO
REMAIN.
4. EXISTING EXHAUST DUCT UP TO FLOOR ABOVE TO REMAIN.
5. EXISTING RETURN DUCT UP TO FLOOR ABOVE TO REMAIN.
6. EXISTING SUPPLY DUCT UP TO FLOOR ABOVE TO REMAIN.
TLT.
ELEV. S.P.
STORAGE
204B
OFFICE
OFFICE
OFFICE
CUSTODY STAFF
ASSEMBLY
CORR.
J.C.
STOR.
204A
VEST.
TLT.
MEN'S LOCKER ROOM
1"
3/4"
1"
MATCHLINE
1 1/4"
1 1/4"
(H W
S ) (H
W R
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:4 P
M
M1.06
S E
C O
N D
F L
O O
R S
O U
T H
H E
A T
IN
G
D E
M O
L
IT
IO
N
P L A
N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
SECOND FLOOR SOUTH HEATING DEMOLITION PLAN
DEMOLITION KEYNOTES
1. DISCONNECT PIPING AND REMOVE EXISTING VAV BOX AND COIL.
2. DISCONNECT PIPING AND REMOVE EXISTING VAV BOX AND COIL.
REMOVE EXISTING GYPSUM BOARD CEILING.
3. REMOVE EXISTING HWS/R PIPING.
4. DISCONNECT HWS/R PIPING FOR NEW VALVES. SEE M3.03. REMOVE
GYPSUM BOARD CEILING.
5. REMOVE EXISTING HWS/R PIPING. REMOVE GYPSUM BOARD
CEILING.
KEYPLAN_________
N.T.S.
GENERAL NOTES
1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND
REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO
INSTALL THEIR WORK.
2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE
DAMAGED DURING WORK.
3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW
DEMOLITION OF EXISTING PIPING AND INSTALLATION OF
PIPING.
4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
KEYNOTES (THIS SHEET)
1. HWS/R IPING TO OTHER BUILDINGS TO REMAIN.
2. HWS/R PIPING ABOVE CEILING TO REMAIN.
3. HWS/R PIPING UP TO FLOOR ABOVE TO REMAIN.
T S
TS
SOUTH MECH.
PENTHOUSE
SOUTH STORAGE
MATCHLINE
3 9
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:4 P
M
M1.07
T H
IR
D
F L
O O
R S
O U
T H
V E
N T
IL
A
T
IO
N D
E M
O L
IT
IO
N P
L A
N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
THIRD FLOOR SOUTH VENTILATION DEMOLITION PLAN
KEYPLAN_________
N.T.S.
GENERAL NOTES
KEYNOTES (THIS SHEET)
1. EXISTING EXHAUST DUCT DOWN TO FLOOR BELOW TO REMAIN.
2. EXISTING RETURN DUCT DOWN TO FLOOR BELOW TO REMAIN.
3. EXISTING LOUVERS AND MOTORIZED DAMPERS TO REMAIN.
1. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
DEMOLITION KEYNOTES
1. REMOVE EXISTING AIR COOLED CONDENSING UNIT. REMOVE
EXISTING ROOF RAILS. ALLOW FOR INSTALLATION OF NEW ROOF
RAILS.
2. REMOVE EXISTING TEMPERATURE CONTROLS SERVING HOT WATER
UNIT HEATER. EXISTING UNIT HEATER TO REMAIN.
3. REMOVE EXISTING RELIEF AIR DUCTWORK AND CONNECTION TO
LOUVER.
4. DISCONNECT EXISTING EA DUCT UP TO ROOF MOUNTED EXHAUST
FAN. REMOVE EXISTING ROOF MOUNTED EXHAUST FAN.
5. REMOVE EXISTING OA DUCTWORK UP TO ROOF HOOD.
6. REMOVE EXISTING SUPPLY AIR DUCTWORK UNTIL DROPS IN CHASE.
7. REMOVE EXISTING AIR HANDLING UNIT AND CONCRETE EQUIPMENT
PAD.
8. REMOVE EXISTING SUPPLY AIR DUCT DOWN TO FLOOR LEVEL.
SUPPLY AIR DUCT TO SECOND FLOOR TO REMAIN.
9. REMOVE EXISTING RETURN AIR DUCTWORK UNTIL DROPS IN CHASE.
SOUTH MECH.
PENTHOUSE
SOUTH STORAGE
(H W
S
(H W
R
(HWS)
(HWR)
MATCHLINE
6(AHU-2)
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:4 P
M
M1.08
T H
IR
D
F L O
O R
S O
U T
H H
E A
T
IN
G D
E M
O L
IT
IO
N P
L A
N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
THIRD FLOOR SOUTH HEATING DEMOLITION PLAN
DEMOLITION KEYNOTES
1. REMOVE EXISTING HOT WATER 3-WAY CONTROL VALVES. REMOVE
PIPING DOWNSTEAM OF VALVES.
2. REMOVE EXISTING REFRIGERANT SUCTION AND LIQUID PIPING.
3. REMOVE EXISTING AIR COOLED CONDENSING UNIT AND
ASSOCIATED ROOF CURB.
4. REMOVE EXISTING PIPING FROM UNIT HEATER BACK TO VALVES.
5. DISCONNECT HWS/R PIPING FOR NEW VALVES. SEE M3.04.
6. REMOVE EXISTING AIR HANDLING UNIT AND CONCRETE EQUIPMENT
PAD.
KEYPLAN_________
N.T.S.
GENERAL NOTES
KEYNOTES (THIS SHEET)
1. EXISTING HOT WATER UNIT HEATER TO REMAIN.
1. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
2. CONTRACTOR RESPONSIBLE FOR REMOVING COIL SECTIONS AND
VERIFY WITH MANUFACTURER OF NEW HEATING AND COOLING COIL
COMPATIBLITY.
TS
TS
T S
TS
TS
T S
HOLDING
HOLDING
GROUP HOLDING
JUVENILE HOLDING
JUVENILE HOLDING
SUMP ROOM
ELEV. EQUIP.
H.C. HOLDING
S.T.
S.P.
GROUP HOLDING
A/C
A/C
A/C
SALLY PORT
S.P.
ELEV S.P.
H.C. TLT.
T.
CONVEYANCE OFFICER
J.C.
0.S.
CORR.
1 VC01-1
VC01-2
VC01-3
VC01-4
VC01-5
VC01-6VC01-7
S 100
S 100
S 100
S 250
S 250
S 225
S 225
S 110
S 100
S 90
S 90
S 90
S 110
S 110
S 130
S 80
S 130
S 290
S 190
E 550
E 500
E 100
E 100 E 230
E 140
E 50 E 50
E 100
E 100
E 100
E 80
R 100
R 100
R 100
R 80
R 30
R 100
S 100
R 140
E 80
(RA)
(8"/6" SA)
(10"/10" SA)
(10"/8" SA)
(10"/8" SA)
(12"/8" SA)
(12"/8" SA)
(10"/8" SA)
(S A
(EA)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:5 P
M
M2.01
B A
S E
M E
N T
V E
N T
IL
A
T
IO
N N
E W
W O
R K
P L
A N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
BASEMENT VENTILATION NEW WORK PLAN
KEYNOTES (THIS SHEET)
1. PROVIDE NEW VAV BOX AND COIL. SEE SCHEDULE. PROVIDE NEW
TRANSITION FITTINGS ON BOTH ENDS, CONNECT TO EXISTING
DUCTWORK. PROVIDE 24”X24” ACCESS DOOR AND PATCH AND PAINT
TO MATCH ADJACENT SURFACES.
2. PROVIDE NEW VAV BOX AND COIL. SEE SCHEDULE. PROVIDE NEW
TRANSITION FITTINGS ON BOTH ENDS, CONNECT TO EXISTING
DUCTWORK.
3. PROVIDE NEW TEMPERATURE SENSOR AND ASSOCIATED WIRING.
4. EXISTING EXHAUST DUCT UP TO FLOOR ABOVE TO REMAIN.
5. EXISTING RETURN DUCT UP TO FLOOR ABOVE TO REMAIN.
6. EXISTING SUPPLY DUCT UP TO FLOOR ABOVE TO REMAIN.
7. UNEXCAVATED SITE. NO WORK.
8. EXISTING EXHAUST GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
9. EXISTING RETURN GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
10. EXISTING SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK TO
REMAIN.
KEYPLAN_________
N.T.S.
GENERAL NOTES
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND
REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO
INSTALL THEIR WORK.
2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE
DAMAGED DURING WORK.
3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW
DEMOLITION OF EXISTING DUCTWORK AND INSTALLATION OF
DUCTWORK.
4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
5. EXISTING TRANSFER OPENINGS THROUGHOUT TO REMAIN.
6. REBALANCE ALL EXISTING SUPPLY DIFFUSERS, RETURN AND
EXHAUST GRILLES TO AIR FLOW RATES SHOWN.
7. CONTRACTOR IS RESPONSIBLE FOR REMOVING AND REPLACING
DRYWALL CEILING AS REQUIRED TO COMPLETE THEIR WORK.
REPLACEMENT OF CEILING SHALL MATCH EXISTING CONDITIONS AND
CONSTRUCTION TYPE. PATCH AND PAINT TO MATCH ADJACENT
SURFACES.
M
TS
TS
TS
T S
T S
TS
T S
T S
TS TS
TS
TS
T S
M
ELEV. S.P.
FACILITY ADMIN
CONF.
114 CL.
115A
STORAGE
CONFERENCE
OFFICE
OFFICE
OFFICE
OFFICE
LOBBY
101 T.
J.C.
CLERICAL
CL.
104A
CORR.
RECORDS STORAGE
ELEC. RM.
116A
W.
M.
CORR.
VC03-1
VC03-3
VC03-2
VC03-4
VC03-5
VC03-6
VC03-7
VC03-8
VC03-9
VC03-10
VC03-11
S 500
S 300
S 300
S 150
S 150
S 100
S 400
S 500
S 500
S 500
S 150
S 400
S 500
S 300 S 300
S 200
S 175 S 175
E 70
E 70
R 360
R 300
R 300
R 400
R 400
R 500
R 600
R 350
R 200
E 50
E 150 E 100
R 100
E 200
R 1300
R 300
20"/14" SA
16"/12" SA
14"ø SA
(SA)
(SA)
(S A
(RA)
(10"/10" SA)
(8"/6" SA)
(10"/8" SA)
(12"ø SA)
(10"ø SA)
(8"/8" SA)
(10"ø SA)
(10"/10" SA)
(8"/8" SA)
(10"ø SA)
(E A
NO2
(TYP.)
E-1 1600
EF-4
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
MATCHLINE
NO2
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:5 P
M
M2.02
F
IR
S T
F L O
O R
S O
U T
H V
E N
T
IL
A T
IO
N
N E
W W
O R
K P
L A
N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
FIRST FLOOR SOUTH VENTILATION NEW WORK PLAN
KEYNOTES (THIS SHEET)
1. PROVIDE NEW VAV BOX AND COIL. SEE SCHEDULE. PROVIDE NEW
TRANSITION FITTINGS ON BOTH ENDS, CONNECT TO EXISTING
DUCTWORK.
2. PROVIDE NEW SA DUCTWORK.
3. PROVIDE 14" ROUND DUCT AND CONNECT TO EXISTING DIFFUSER
NECK.
4. PROVIDE NEW VAV BOX AND COIL. SEE SCHEDULE. PROVIDE NEW
TRANSITION FITTINGS ON BOTH ENDS, CONNECT TO EXISTING
DUCTWORK. PROVIDE 24”X24” ACCESS DOOR AND PATCH AND PAINT
TO MATCH ADJACENT SURFACES.
5. PROVIDE NEW TEMPERATURE SENSOR AND ASSOCIATED WIRING.
6. PROVIDE NEW CO/NO2 SENSORS FOR EXHAUST FANS. SEE
TEMPERATURE CONTROL SCHEMATICS.
7. PROVIDE NEW INTAKE LOUVER AT EXISTING WALL. OFFSET 12”
HORIZONTALLY FROM OVERHEAD DOOR. PROVIDE MOTORIZED
DAMPER FOR LOUVER, SEE SCHEDULE AND DETAIL.
8. PROVIDE CEILING HUNG EXHAUST FAN AND PLENUM TO EXHAUST
LOUVER. SEE SCHEDULE AND DETAIL.
9. PROVIDE NEW WALL EXHAUST LOUVER AND MOTORIZED DAMPER.
OFFSET 12" HORIZONTALLY FROM OVERHEAD DOOR AND VERTICAL
JOINT.
10. PROVIDE DUCT EXHAUST GRILLE 1' AFF. SEE SCHEDULE.
11. EXISTING EXHAUST GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
12. EXISTING RETURN GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
13. EXISTING SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK TO
REMAIN.
14. EXISTING EXHAUST DUCT UP TO FLOOR ABOVE TO REMAIN.
15. EXISTING RETURN DUCT UP TO FLOOR ABOVE TO REMAIN.
16. EXISTING SUPPLY DUCT UP TO FLOOR ABOVE TO REMAIN.
17. PROVIDE NEW TEMPERATURE SENSOR MOUNTED ON UNIT.
18. PROVIDE NEW CO/NO2 SENSORS FOR EXHAUST FANS. SEE
TEMPERATURE CONTROL SCHEMATICS.
KEYPLAN_________
N.T.S.
GENERAL NOTES
EL-1
IL-1
MD-2
MD-1
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND
REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO
INSTALL THEIR WORK.
2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE
DAMAGED DURING WORK.
3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW
DEMOLITION OF EXISTING DUCTWORK AND INSTALLATION OF
DUCTWORK.
4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
5. EXISTING TRANSFER OPENINGS THROUGHOUT TO REMAIN.
6. REBALANCE ALL EXISTING SUPPLY DIFFUSERS, RETURN AND
EXHAUST GRILLES TO AIR FLOW RATES SHOWN.
7. CONTRACTOR IS RESPONSIBLE FOR REMOVING AND REPLACING
DRYWALL CEILING AS REQUIRED TO COMPLETE THEIR WORK.
REPLACEMENT OF CEILING SHALL MATCH EXISTING CONDITIONS AND
S
T S
T S
T S
TS
T S
TS
WOMEN'S LOCKER
ROOM
TLT.
ELEV. S.P.
STORAGE
204B
OFFICE
OFFICE
OFFICE
CUSTODY STAFF
ASSEMBLY
CORR.
J.C.
STOR.
204AVEST.
TLT.
MEN'S LOCKER ROOM
2 V05-1
VC05-2
VC05-3
VC05-1
VC05-4
VC05-5
VC05-6
VC05-7
S 300
S 300
S 300
S 450
S 400
S 400
S 280
S 280
S 500
S 500
S 100
S 250
S 250
S 250
R 1000
E 500
E 500
E 100 E 100
R 90
R 450
R 400
R 400
E 500
E 400
R 100
(S A
(S A
(RA)
(14"/12" SA)(6"ø SA)
(6"ø SA)
(12"/10" SA)
(6"ø SA)
(14"/10" SA)
(6"ø SA)
(8"/8" SA)
(EA)
(E A
MATCHLINE
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
8 9 1011
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:0 P
M
M2.03
S E
C O
N D
F L
O O
R S
O U
T H
V E
N T
IL
A
T
IO
N N
E W
W O
R K
P L A
N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
SECOND FLOOR SOUTH VENTILATION NEW WORK PLAN
KEYNOTES (THIS SHEET)
1. PROVIDE NEW VAV BOX AND COIL. SEE SCHEDULE. PROVIDE NEW
TRANSITION FITTINGS ON BOTH ENDS, CONNECT TO EXISTING
DUCTWORK.
2. PROVIDE NEW VAV TERMINAL BOX. SEE SCHEDULE. PROVIDE NEW
TRANSITION FITTINGS ON BOTH ENDS, CONNECT TO EXISTING
DUCTWORK.
3. PROVIDE NEW VAV BOX AND COIL. SEE SCHEDULE. PROVIDE NEW
TRANSITION FITTINGS ON BOTH ENDS, CONNECT TO EXISTING
DUCTWORK. PROVIDE 24”X24” ACCESS DOOR AND PATCH AND PAINT
TO MATCH ADJACENT SURFACES.
4. PROVIDE NEW TEMPERATURE SENSOR AND ASSOCIATED WIRING.
5. EXISTING EXHAUST GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
6. EXISTING RETURN GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
7. EXISTING SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK TO
REMAIN.
8. EXISTING EXHAUST DUCT UP TO FLOOR ABOVE TO REMAIN.
9. EXISTING RETURN DUCT UP TO FLOOR ABOVE TO REMAIN.
10. EXISTING SUPPLY DUCT UP TO FLOOR ABOVE TO REMAIN.
11. EXISTING RA PLENUM LOUVER TO REMAIN.
KEYPLAN_________
N.T.S.
GENERAL NOTES
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND
REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO
INSTALL THEIR WORK.
2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE
DAMAGED DURING WORK.
3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW
DEMOLITION OF EXISTING DUCTWORK AND INSTALLATION OF
DUCTWORK.
4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
5. EXISTING TRANSFER OPENINGS THROUGHOUT TO REMAIN.
6. REBALANCE ALL EXISTING SUPPLY DIFFUSERS, RETURN AND
EXHAUST GRILLES TO AIR FLOW RATES SHOWN.
7. CONTRACTOR IS RESPONSIBLE FOR REMOVING AND REPLACING
DRYWALL CEILING AS REQUIRED TO COMPLETE THEIR WORK.
REPLACEMENT OF CEILING SHALL MATCH EXISTING CONDITIONS AND
T S
TS
SOUTH MECH.
PENTHOUSE
SOUTH STORAGE
MATCHLINE
AHU-2
30"/34" SA
34"/30" EA
20"/20" OA
24"/30" RA
ERV-2
MD-3
M4.01
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:0
:0 P
M
M2.04
T H
IR
D
F L
O O
R S
O U
T H
V E
N T
IL
A
T
IO
N N
E W
W O
R K
P L A
N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
THIRD FLOOR SOUTH VENTILATION NEW WORK PLAN
KEYPLAN_________
N.T.S.
GENERAL NOTES
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
KEYNOTES (THIS SHEET)
1. PROVIDE NEW DUCT CONNECTION TO NEW ERV UNIT ON ROOF.
PATCH EXISTING ROOF AROUND DUCT IN ACCORDANCE WITH
ROOFING MANUFACTURER'S (DOWSIL) REQUIREMENTS. PROVIDE
STANDARD PATCHING WARRANTY.
2. EXISTING EXHAUST DUCT DOWN TO FLOOR BELOW TO REMAIN.
3. EXISTING RETURN DUCT DOWN TO FLOOR BELOW TO REMAIN.
4. PROVIDE NEW 34X30 SA DUCT WITH CONNECTION TO EXISTING
SUPPLY DUCT AT FLOOR LEVEL.
5. NEW AIR HANDLING UNIT.
6. EXISTING LOUVERS AND MOTORIZED DAMPERS TO REMAIN.
7. PROVIDE TEMPERATURE SENSOR MOUNTED TO UNIT.
8. CONNET NEW EXHAUST DUCT TO EXISTING LOUVER.
9. MAKE NEW RA CONNECTION TO EXISTING VERTICAL DUCT.
10. NEW 34X30 EA DUCT DOWN. MAKE TRANSITION TO UNIT AS
NECESSARY.
11. NEW OA DUCT UP. TRANSITION TO 30X30 AFTER CONNECTION FROM
SA DUCT COMING FROM ERV.
12. NEW OA DUCT FROM ERV. MAKE CONNECTION TO FLAT VERTICAL
DUCT WORK.
13. NEW 30X30 OA DUCT UP TO EXISTING ROOF HOOD. MAKE
TRANSITION TO ROOF HOOD AS NECCESSARY. PROVIDE NEW
MOTORIZED DAMPER IN DUCT
14. NEW OA DUCT UP TO ROOF MOUNTED ERV.
1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND
REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO
INSTALL THEIR WORK.
2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE
DAMAGED DURING WORK.
3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW
DEMOLITION OF EXISTING DUCTWORK AND INSTALLATION OF
DUCTWORK.
4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
5. EXISTING TRANSFER OPENINGS THROUGHOUT TO REMAIN.
6. REBALANCE ALL EXISTING SUPPLY DIFFUSERS, RETURN AND
EXHAUST GRILLES TO AIR FLOW RATES SHOWN.
7. CONTRACTOR IS RESPONSIBLE FOR REMOVING AND REPLACING
DRYWALL CEILING AS REQUIRED TO COMPLETE THEIR WORK.
REPLACEMENT OF CEILING SHALL MATCH EXISTING CONDITIONS AND
HOLDING
HOLDING
HOLDING
GROUP…