This Addendum 1 to RFP #2613 provides clarifications and revisions to the Kenosha County Pre-Trial Facility HVAC Improvements Phase 1 project, a construction services procurement issued by Kenosha County, Wisconsin. The addendum addresses contractor questions regarding piping insulation specifications, joint types, construction scheduling, and ductwork finish requirements through a Questions and Answers section. Key clarifications include confirmation that refrigerant piping insulation specifications have been re-issued, press copper joints are not permitted, the two-week AHU changeout window remains firm, temporary airflow provisions during AHU downtime are required, and exposed ductwork in mechanical rooms must be finished with aluminum jacket rather than board insulation with foil facing. The addendum incorporates multiple drawing revisions across mechanical, electrical, and specification sections, including updates to diffuser locations, control panel placement, roof drain addressing, cooling coil specifications, and new glycol solution requirements. A comprehensive new specification section 230700 for HVAC Insulation has been added, establishing detailed requirements for pipe and ductwork insulation materials, thermal characteristics, vapor barriers, jackets, and installation procedures. The addendum was issued on April 15, 2026, and reflects the second revision to the original bid documents issued March 11, 2026.
The addendum contains no information regarding pricing, set-asides, incumbent contractors, or funding sources, as these elements were established in the original RFP documents. All cost and contract terms remain as specified in the base bid solicitation. The HVAC Insulation specification establishes performance standards requiring maximum flame spread index of 25 and smoke development index not exceeding 50 per ASTM E84 testing, with pipe insulation types ranging from molded glass fiber to closed-cell elastomeric materials rated for operating temperatures from minus 70 to 850 degrees Fahrenheit depending on application. Ductwork insulation specifications similarly detail thermal conductivity requirements, density specifications, and finishing requirements with aluminum jackets for exposed applications in mechanical rooms and finished spaces. Installation requirements mandate that all piping systems conveying fluids below ambient temperature be fully insulated including fittings, valves, unions, and expansion joints, with vapor retarder jackets and specified thickness schedules for heating water and refrigerant piping ranging from 1.5 to 2.0 inches depending on pipe diameter and service application.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2613 Specifications.pdf | ||
| Vendor Responsibility Form Construction.pdf | ||
| 2613 Bid Documents.pdf | ||
| Background Check Form.docx | DOCX document | |
| 2613 Drawings.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFP #2613 Addendum One Page 1 of 2
Yes.
Questions and Answers:
Q. The Piping insulation specification does not indicate any refrigeration piping.
Please confirm what insulation is.
A. Spec has been re-issued regarding refrigerant piping insulation.
Q. Are press copper joints allowed?
A. No.
Q. A two week window for the AHU changeout was mentioned at the walkthrough.
Can you please confirm? That duration is pretty tight and may require overtime costs to get it done in time.
A. 2-week window will remain as originally planned.
Q. Temporary airflow when the AHU was down was mentioned in the walkthrough .
Can you please confirm?
A. Yes.
Q. Insulation spec 23 07 00 3.3 calls for "Ductwork exposed in mechanical equipment rooms or finished space below 8feet above finished floor: finish with aluminum jacket" The existing ductwork does not have this treatment. Can the exposed duct in the mechanical room be insulated with Board insulated with foil facing?
A. We will stay with the aluminum jacket as referenced in spec section.
Revisions & Attachments:
Drawings:
M1.03
• Existing diffusers revised to be removed.
M1.09
• Sheet added to note that the existing AHU-2 is to be removed off the existing control panels in the north mechanical room.
KENOSHA COUNTY
RFP #2613 ADDENDUM ONE DATED 4/15/2026
Kenosha County Pre-Trial Facility HVAC Improvements Phase 1
RFP #2613 Addendum One Page 2 of 2
M2.02
• New diffusers added.
M2.04
• Note added addressing roof drain.
M3.04
• New control panel moved to south mechanical room.
M5.01
• New diffusers added to schedule.
• Cooling coil typo fixed to DX cooling coil.
• Note added for verifying split section in AHU to fit through door.
• ERV unit exhaust fan static pressure fixed to 1”.
E0.00
• Lighting Protection general notes added.
E2.02
• New control panel and feed added.
E4.01
• New control panel added to schedule.
SPECS:
232116
• Section 2.11 Glycol solution: Change “propylene glycol” to ethylene glycol.
230700
• New spec section provided.
End Addendum 1
TS
TS
TS
T S
T S
TS
T S
T S
TS TS
TS
TS
T S
ELEV. S.P.
FACILITY ADMIN
CONF.
CL.
115A
STORAGE
CONFERENCE
OFFICE
OFFICE
OFFICE
OFFICE
LOBBY
T.
J.C.
CLERICAL
CL.
104A
CORR.
RECORDS STORAGE
ELEC. RM.
116A
W.
M.
CORR.
(SA)
(SA)
(S A
(S
A
MATCHLINE
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(RA)
(E A
(TYP.)
4 5 6
(TYP.)
6 6
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:3
:3 P
M
M1.03
F
IR
S T
F L
O O
R S
O U
T H
V E
N T
IL
A
T
IO
N D
E M
O L
IT
IO
N P
L A
N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
FIRST FLOOR SOUTH VENTILATION DEMOLITION PLAN
DEMOLITION KEYNOTES
1. REMOVE EXISTING VAV BOX WITH HW REHEAT AND ASSOCIATED
CONTROLS. DISCONNECT TRANSITION FITTINGS ON BOTH SIDES OF
BOX.
2. REMOVE EXISTING SA DUCT AND ASSOCIATED SA DIFFUSERS. SEE
M2.02 FOR NEW WORK.
3. REMOVE EXISTING VAV BOX WITH HW REHEAT AND ASSOCIATED
CONTROLS. DISCONNECT TRANSITION FITTINGS ON BOTH SIDES OF
BOX. REMOVE EXISTING GYPSUM BOARD CEILING.
4. REMOVE TEMPERTAURE SENSOR AND ASSOCIATED WIRING.
REPLACE WITH NEW.
5. REMOVE EXISTING TEMPERATURE CONTROLS SERVING HOT WATER
CABINET HEATER. EXISTING CABINET HEATER TO REMAIN. REMOVE
EXISTING TEMPERATURE SENSOR.
6. REMOVE EXISTING TEMPERATURE CONTROLS SERVING HOT WATER
UNIT HEATER. EXISTING UNIT HEATER TO REMAIN.
7. REMOVE IN-UNIT THERMOSTAT.
KEYPLAN_________
N.T.S.
GENERAL NOTES
1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND
REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO
INSTALL THEIR WORK.
2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE
DAMAGED DURING WORK.
3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW
DEMOLITION OF EXISTING DUCTWORK AND INSTALLATION OF
DUCTWORK.
4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
5. EXISTING TRANSFER OPENINGS THROUGHOUT TO REMAIN.
KEYNOTES (THIS SHEET)
1. EXISTING EXHAUST GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
2. EXISTING RETURN GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
3. EXISTING SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK TO
REMAIN.
4. EXISTING EXHAUST DUCT UP TO FLOOR ABOVE TO REMAIN.
5. EXISTING RETURN DUCT UP TO FLOOR ABOVE TO REMAIN.
6. EXISTING SUPPLY DUCT UP TO FLOOR ABOVE TO REMAIN.
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
2 04/15/26 ADDENDUM #1
NORTH MECH.
PENTHOUSE
NORTH STORAGE
ELEV. EQUIP.
MATCHLINE
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:3
:5 P
M
M1.09
T H
IR
D
F L O
O R
N O
R T
H H
E A
T
IN
G D
E M
O L
IT
IO
N
P L
A N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
2 04/15/26 ADDENDUM #1
8' 16'4'0
THIRD FLOOR NORTH HEATING DEMOLITION PLAN
DEMOLITION KEYNOTES
1. DISCONNECT AHU-2 FROM EXISTING TEMPERATURE CONTROL
PANELS.
KEYNOTES (THIS SHEET)
1. EXISTING TEMPERATURE CONTROL PANELS TO REMAIN.
KEYPLAN_________
N.T.S.
CO
CO
M
TS
TS
TS
T S
T S
TS
T S
T S
TS TS
TS
TS
T S
M
ELEV. S.P.
FACILITY ADMIN
CONF.
114 CL.
115A
STORAGE
CONFERENCE
OFFICE
OFFICE
OFFICE
OFFICE
LOBBY
101 T.
J.C.
CLERICAL
CL.
104A
CORR.
RECORDS STORAGE
ELEC. RM.
116A
W.
M.
CORR.
VC03-1
VC03-3
VC03-2
VC03-4
VC03-5
VC03-6
VC03-7
VC03-8
VC03-9
VC03-10
VC03-11
S 500
S 300
S 300
S 150
S 150
S 100
S 400
S 150
S 400
S 500
S 300 S 300
S 200
S 175 S 175
E 70
E 70
R 360
R 300
R 300
R 400
R 400
R 500
R 600
R 350
R 200
E 50
E 150 E 100
R 100
E 200
R 1300
R 300
20"/14" SA
16"/12" SA
14"ø SA
(SA)
(SA)
(S A
(RA)
(10"/10" SA)
(8"/6" SA)
(10"/8" SA)
(12"ø SA)
(10"ø SA)
(8"/8" SA)
(10"ø SA)
(10"/10" SA)
(8"/8" SA)
(10"ø SA)
(E A
NO2
(TYP.)
E-1 1600
EF-4
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
MATCHLINE
NO2
A1 500
A1 500
A1 500
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:3
:5 P
M
M2.02
F
IR
S T
F L O
O R
S O
U T
H V
E N
T
IL
A T
IO
N
N E
W W
O R
K P
L A
N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
FIRST FLOOR SOUTH VENTILATION NEW WORK PLAN
KEYNOTES (THIS SHEET)
1. PROVIDE NEW VAV BOX AND COIL. SEE SCHEDULE. PROVIDE NEW
TRANSITION FITTINGS ON BOTH ENDS, CONNECT TO EXISTING
DUCTWORK.
2. PROVIDE NEW SA DUCTWORK.
3. PROVIDE 14" ROUND DUCT AND CONNECT TO NEW GRILLES.
REPLACE EXISTING CEILING.
4. PROVIDE NEW VAV BOX AND COIL. SEE SCHEDULE. PROVIDE NEW
TRANSITION FITTINGS ON BOTH ENDS, CONNECT TO EXISTING
DUCTWORK. PROVIDE 24”X24” ACCESS DOOR AND PATCH AND PAINT
TO MATCH ADJACENT SURFACES.
5. PROVIDE NEW TEMPERATURE SENSOR AND ASSOCIATED WIRING.
6. PROVIDE NEW CO/NO2 SENSORS FOR EXHAUST FANS. SEE
TEMPERATURE CONTROL SCHEMATICS.
7. PROVIDE NEW INTAKE LOUVER AT EXISTING WALL. OFFSET 12”
HORIZONTALLY FROM OVERHEAD DOOR. PROVIDE MOTORIZED
DAMPER FOR LOUVER, SEE SCHEDULE AND DETAIL.
8. PROVIDE CEILING HUNG EXHAUST FAN AND PLENUM TO EXHAUST
LOUVER. SEE SCHEDULE AND DETAIL.
9. PROVIDE NEW WALL EXHAUST LOUVER AND MOTORIZED DAMPER.
OFFSET 12" HORIZONTALLY FROM OVERHEAD DOOR AND VERTICAL
JOINT.
10. PROVIDE DUCT EXHAUST GRILLE 1' AFF. SEE SCHEDULE.
11. EXISTING EXHAUST GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
12. EXISTING RETURN GRILLE AND ASSOCIATED DUCTWORK TO
REMAIN.
13. EXISTING SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK TO
REMAIN.
14. EXISTING EXHAUST DUCT UP TO FLOOR ABOVE TO REMAIN.
15. EXISTING RETURN DUCT UP TO FLOOR ABOVE TO REMAIN.
16. EXISTING SUPPLY DUCT UP TO FLOOR ABOVE TO REMAIN.
17. PROVIDE NEW TEMPERATURE SENSOR MOUNTED ON UNIT.
18. PROVIDE NEW CO/NO2 SENSORS FOR EXHAUST FANS. SEE
TEMPERATURE CONTROL SCHEMATICS.
KEYPLAN_________
N.T.S.
GENERAL NOTES
EL-1
IL-1
MD-2
MD-1
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
2 04/15/26 ADDENDUM #1
1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND
REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO
INSTALL THEIR WORK.
2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE
DAMAGED DURING WORK.
3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW
DEMOLITION OF EXISTING DUCTWORK AND INSTALLATION OF
DUCTWORK.
4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
5. EXISTING TRANSFER OPENINGS THROUGHOUT TO REMAIN.
6. REBALANCE ALL EXISTING SUPPLY DIFFUSERS, RETURN AND
EXHAUST GRILLES TO AIR FLOW RATES SHOWN.
7. CONTRACTOR IS RESPONSIBLE FOR REMOVING AND REPLACING
DRYWALL CEILING AS REQUIRED TO COMPLETE THEIR WORK.
REPLACEMENT OF CEILING SHALL MATCH EXISTING CONDITIONS AND
CONSTRUCTION TYPE. PATCH AND PAINT TO MATCH ADJACENT
SURFACES.
M
M
T S
TS
SOUTH MECH.
PENTHOUSE
SOUTH STORAGE
MATCHLINE
AHU-2
30"/34" SA
34"/30" EA
20"/20" OA
24"/30" RA
ERV-2
MD-3
M4.01
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:3
:0 P
M
M2.04
T H
IR
D
F L
O O
R S
O U
T H
V E
N T
IL
A
T
IO
N N
E W
W O
R K
P L A
N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
THIRD FLOOR SOUTH VENTILATION NEW WORK PLAN
KEYPLAN_________
N.T.S.
GENERAL NOTES
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
2 04/15/26 ADDENDUM #1
1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND
REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO
INSTALL THEIR WORK.
2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE
DAMAGED DURING WORK.
3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW
DEMOLITION OF EXISTING DUCTWORK AND INSTALLATION OF
DUCTWORK.
4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
5. EXISTING TRANSFER OPENINGS THROUGHOUT TO REMAIN.
6. REBALANCE ALL EXISTING SUPPLY DIFFUSERS, RETURN AND
EXHAUST GRILLES TO AIR FLOW RATES SHOWN.
7. CONTRACTOR IS RESPONSIBLE FOR REMOVING AND REPLACING
DRYWALL CEILING AS REQUIRED TO COMPLETE THEIR WORK.
REPLACEMENT OF CEILING SHALL MATCH EXISTING CONDITIONS AND
CONSTRUCTION TYPE. PATCH AND PAINT TO MATCH ADJACENT
SURFACES.
KEYNOTES (THIS SHEET)
1. PROVIDE NEW DUCT CONNECTION TO NEW ERV UNIT ON ROOF.
PATCH EXISTING ROOF AROUND DUCT IN ACCORDANCE WITH
ROOFING MANUFACTURER'S (DOWSIL) REQUIREMENTS. PROVIDE
STANDARD PATCHING WARRANTY. COORDINATE ERV MOUNTING
AROUND EXISTING ROOF DRAINS.
2. EXISTING EXHAUST DUCT DOWN TO FLOOR BELOW TO REMAIN.
3. EXISTING RETURN DUCT DOWN TO FLOOR BELOW TO REMAIN.
4. PROVIDE NEW 34X30 SA DUCT WITH CONNECTION TO EXISTING
SUPPLY DUCT AT FLOOR LEVEL.
5. NEW AIR HANDLING UNIT.
6. EXISTING LOUVERS AND MOTORIZED DAMPERS TO REMAIN.
7. PROVIDE TEMPERATURE SENSOR MOUNTED TO UNIT.
8. CONNET NEW EXHAUST DUCT TO EXISTING LOUVER.
9. MAKE NEW RA CONNECTION TO EXISTING VERTICAL DUCT.
10. NEW 34X30 EA DUCT DOWN. MAKE TRANSITION TO UNIT AS
NECESSARY.
11. NEW OA DUCT UP. TRANSITION TO 30X30 AFTER CONNECTION FROM
SA DUCT COMING FROM ERV.
12. NEW OA DUCT FROM ERV. MAKE CONNECTION TO FLAT VERTICAL
DUCT WORK.
13. NEW 30X30 OA DUCT UP TO EXISTING ROOF HOOD. MAKE
TRANSITION TO ROOF HOOD AS NECCESSARY. PROVIDE NEW
MOTORIZED DAMPER IN DUCT
14. NEW OA DUCT UP TO ROOF MOUNTED ERV.
15. RELOCATE EXISTING ROOF DRAIN FOR NEW DUCTWORK AND ERV
UNIT. RECONNECT TO EXISTING STORM DRAIN PIPING.
T S
TS
SOUTH MECH.
PENTHOUSE
SOUTH STORAGE
(H W
S
(H W
R
(HWS)
(HWR)
REF-S
REF-L
MATCHLINE
(UH07-4)
(UH07-6)
CU-2
AHU-2
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:3
:1 P
M
M3.04
T H
IR
D
F L O
O R
S O
U T
H H
E A
T
IN
G N
E W
W O
R K
P L
A N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
THIRD FLOOR SOUTH HEATING NEW WORK PLAN
KEYNOTES (THIS SHEET)
1. PROVIDE NEW HWR CONTROL VALVES AND CONNECTION TO NEW
HEATING COIL.
2. PROVIDE NEW CONTROLS FOR EXISTING HOT WATER UNIT HEATER.
PROVIDE NEW 3 WAY-CONTROL VALVE. RECONNECT TO EXISTING
PIPING. SEE DETAIL AND CONTROL SCHEMATICS.
3. PROVIDE NEW REFRIGERANT PIPING CONNECTION TO NEW
COOLING COIL.
5. PROVIDE NEW SUCTION AND LIQUID REFRIGERANT PIPING. PROVIDE
NEW PIPING SUPPORTS.
7. PROVIDE NEW AIR-COOLED CONDENSING UNIT.INSTALL NEW ROOF
RAILS. SEE DETAIL 3/M5.02. PATCH EXISTING ROOF AROUND NEW
RAILS IN ACCORDANCE WITH ROOFING MANUFACTURER'S (DOWSIL)
REQUIREMENTS. PROVIDE STANDARD PATCHING WARRANTY.
8. PROVIDE NEW ISOLATION BALL VALVES ON EXISTING HWS/R PIPING.
9. PROVIDE NEW TEMPERATURE SENSOR AND ASSOCIATED WIRING
FOR HW UNIT HEATER.
10. SEAL WALL PENETRATION WEATHER TIGHT.
11. NEW AIR HANDLING UNIT. PROVIDE CONCRETE EQUIPMENT PAD.
SEE SCHEDULE.
12. HWS/R PIPING DOWN TO FLOOR BELOW TO REMAIN.
13. HWS/R PIPING ABOVE CEILING TO REMAIN.
14. NEW TEMPERATURE CONTROL PANEL. INSTALL NEW PANEL ON
EXISTING WALL. COORDINATE EXACT LOCATION WITH OTHER
EXISTING UTILITIES. PROVIDE NEW DATA CONNECTION TO EXISTING
KENOSHA COUNTY NETWORK. CONTRACTOR SHALL BE
RESPONSIBLE FOR COORDINATING NEW DATA LOCATION,
ASSOCIATED CABLING/CONDUIT. CONNECT TO EXISTING KENOSHA
COUNTY NETWORK PANEL.
KEYPLAN_________
N.T.S.
GENERAL NOTES
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
2 04/15/26 ADDENDUM #1
1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND
REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO
INSTALL THEIR WORK.
2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE
DAMAGED DURING WORK.
3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW
DEMOLITION OF EXISTING DUCTWORK AND INSTALLATION OF
DUCTWORK.
4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY
REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING
LIGHT FIXTURES WHEN WORK IS COMPLETE.
5. EXISTING TRANSFER OPENINGS THROUGHOUT TO REMAIN.
6. CONTRACTOR IS RESPONSIBLE FOR REMOVING AND REPLACING
DRYWALL CEILING AS REQUIRED TO COMPLETE THEIR WORK.
REPLACEMENT OF CEILING SHALL MATCH EXISTING CONDITIONS AND
CONSTRUCTION TYPE. PATCH AND PAINT TO MATCH ADJACENT
SURFACES.
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:1
:5
A
M
M5.01
H V
A C
S C
H E
D U
L E
S K
E N
O S
H A
C O
U N
T Y
P R
E -T
R
IA
L F
A C
IL
IT
Y H
V A
C
IM
P R
O V
E M
E N
T S
K0450190
DESIGNED BY: JAW
DRAWN BY: JAW
CHECKED BY: NTP
DATE CHECKED: 02/20/26
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o s h a W
I th
S tr e e t, th F lo o r
VARIABLE AIR VOLUME TERMINAL UNIT (NO REHEAT)...
TAG LOCATION SERVICE
PRIMARY AIRFLOW
INLET SIZE
(DIA. IN.) SP (IN WC) NOTES
MAX
(CFM)
MIN
(CFM)
V05-1 204 204 560 450 8" 0.25
AIR COOLED CONDENSING UNIT
TAG
LOCATION
TYPE
NOMINAL
COOLING
CAP (TON)
FAN COMPRESSOR
SUMMER
AMBIENT
DBT (°F) EER
VOLT
(V) PH NOTESNAME
MOTOR
TYPE
REFRIGERANT
QTY
POWER
(HP) ECM TYPE
CU-2 SOUTH ROOF COOLING 40 6 7.30 No SCROLL
R-454-B OR
R-32 95.0 11.6 460 3
EXHAUST FAN SCHEDULE
TAG
LOCATION
TYPE ARRANGEMENT
FAN
VOLT
(V) PH NOTES MANUFACTURER MODELNAME NO.
DESIGN
AIRFLOW (CFM) ESP (IN W.G) RPM
DRIVE
TYPE
MOTOR
POWER (HP)
EF-4
VEHICLE SALLY
PORT
VEHICLE SALLY
PORT
INLINE HORIZONTAL 1600 0.53 1140 DIRECT 0.33 115 1 GREENHECK SQ-140
LOUVER SCHEDULE
TAG
LOCATION
SERVES QTY MATERIAL FINISH TYPE
DESIGN
AIRFLOW
(CFM)
FREE
AREA
FREE AREA
VELOCITY
DIMENSIONS
NOTES MANUFACTURER MODELNAME WIDTH HEIGHT
EL-1
VEHICLE SALLY
PORT
VEHICLE
SALLY PORT
1 ALUMINUM ENAMEL
DRAINABLE
HORIZONTAL
BLADE WALL
LOUVER
1600 1.6 SF 1000 FPM 1' - 0" 3' - 0" GREENHECK ESD-635
IL-1
VEHICLE SALLY
PORT
VEHICLE
SALLY PORT
1 ALUMINUM ENAMEL
DRAINABLE
HORIZONTAL
BLADE WALL
LOUVER
1600 3.2 SF 500 FPM 2' - 0" 3' - 0" GREENHECK ESD-635
GRILLES, REGISTERS AND DIFFUSERS SCHEDULE
TAG DESCRIPTION SYSTEM FACE SIZE
NECK BLADE DESIGN
MOUNTING MATERIAL
MAX N.C.
LEVEL NOTES MANUFACTURER MODELHEIGHT WIDTH
DEFLECTION
ANGLE
SINGLE DOUBLE
A1
SQUARE PLAQUE CEILING
DIFFUSER
SUPPLY 24X24 CEILING ALUMINUM 30 PRICE SPD
E1
LOUVERED SINGLE DEFLECTION
GRILLE
EXHAUST 14X28 28" 14" 45.0° DUCT ALUMINUM 35 PRICE 610Z
MOTORIZED DAMPER SCHEDULE
TAG
LOCATION
WIDTH HEIGHT
BLADE
CONFIGURATI
ON MOUNTING TYPENAME
MD-1
VEHICLE SALLY
PORT
12" 36" PARALLEL IN-SLEEVE TWO-POSITION
MD-2
VEHICLE SALLY
PORT
24" 36" PARALLEL IN-SLEEVE MODULATING
MD-3
SOUTH MECH.
ROOM
30" 30" PARALLEL IN-SLEEVE MODULATING
NOTES:
1. HEATING WATER SYSTEM WITH WITH 30% ETHYLENE GLYCOL.
2. PROVIDE WITH MANUFACTURER'S VFD ON BOTH FANS.
3. LARGEST SECTION MUST NOT EXCEED 36" TO FIT THROUGH 36" WIDE DOOR.
NOTES:
1. PROVIDE WITH MANUFACTURER'S VARIABLE SPEED SCROLL COMPRESSOR.
NOTES:
1. PROVIDE WITH MANUFACTURER'S VFD.
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
2 04/15/26 ADDENDUM #1
AIR HANDLING UNIT SCHEDULE
TAG
LOCATION SUPPLY FAN RETURN/EXHAUST FAN DX COOLING COIL HEATING PLANT HOT WATER HEATING COIL FILTER
VOLT
(V) PH NOTESNAME NO.
DESIGN
AIRFLOW
(CFM) ESP (IN W.G) RPM
DRIVE
TYPE
MOTOR DESIGN
AIRFLOW
(CFM) ESP (IN W.G) RPM
DRIVE
TYPE
MOTOR CAP AIRSIDE GLYCOL
CAP (BTU/H)
AIRSIDE
TYPEQTY POWER (HP) QTY
POWER
(HP)
TOTAL
(BTU/H)
SENSIBLE
(BTU/H)
EAT, DB
(°F)
EAT, WB
(°F) LAT DB (°F)
LAT, WB
(°F) TYPE % EWT, DB (°F)
LWT, DB
(°F)
AHU-2
SOUTH MECH.
ROOM
303 11745 2.00 2084 DIRECT 2 7.50 11745 2.00 2312 DIRECT 2 5.00 435000 368500 83.6 68.3 55.0 53.1 EG 30 590000 140.0 120.0 MERV-8 480 3
VARIABLE AIR VOLUME TERMINAL UNIT SCHEDULE
TAG LOCATION SERVICE
MAX AIR
VOL (CFM)
MIN AIR
VOL
(CFM)
HEATING
AIR VOL (
CFM)
NECK
SIZE (DIA.
IN.)
HEATING COIL
NOTES
CAP
(BTU/H)
AIRSIDE WATERSIDE
EAT, DB (°F) LAT, DB (°F) PD (IN W.G)
FLOW
(GPM)
EWT
(°F)
LWT
(°F)
PD
(FTH2O)
VC01-1 002 002, 003, 004, 005 400 400 400 8" 16090 55.0 92.0 0.20 3.3 140 129 0.3
VC01-2 008 008 500 500 500 10" 22500 55.0 96.5 0.14 1.6 140 125 3.1
VC01-3 012 013, 014, 015 270 270 270 6" 8800 55.0 85.0 0.22 0.8 140 116 0.2
VC01-4 011 011 450 450 450 8" 14700 55.0 85.1 0.24 2.3 140 125 0.2
VC01-5 012 006, 009, 012 430 270 270 8" 7200 55.0 85.2 0.15 0.5 140 101 4.8
VC01-6 016 016 210 210 210 6" 7060 55.0 86.0 0.12 0.6 140 115 0.2
VC01-7 017 017, 020, 021 610 550 550 12" 18600 55.0 85.1 0.19 1.7 140 116 0.3
VC03-1 104 101, 105 800 400 400 12" 14000 55.0 87.0 0.08 1.9 140 124 0.2
VC03-2 106 106 300 220 300 8" 14300 55.0 99.0 0.13 3.5 140 131 3.3
VC03-3 104 104 300 300 300 8" 9800 55.0 85.0 0.13 1.3 140 124 0.4
VC03-4 107 107 400 200 330 10" 19500 55.0 109.5 0.10 5.6 140 132 0.5
VC03-5 109 108, 109 400 200 225 8" 9800 55.0 95.2 0.20 1.7 140 127 0.1
VC03-6 113 113 400 200 330 10" 19500 55.0 109.5 0.10 5.6 140 132 0.1
VC03-7 112 112 350 300 300 8" 11400 55.0 90.0 0.16 1.8 140 126 0.7
VC03-8 114 114 500 250 400 10" 17000 55.0 94.2 0.14 1.9 140 120 0.5
VC03-9 115 115 600 300 410 10" 17800 55.0 95.0 0.18 2.0 140 121 0.6
VC03-10 116 117 230 230 230 6" 10000 55.0 95.0 0.13 1.3 140 123 0.5
VC03-11 117 117 1500 1500 1500 14" 48800 55.0 85.0 0.25 5.3 140 120 4.7
VC05-1 204 201, 202 900 900 900 12" 39000 55.0 95.0 0.20 7.7 140 129 1.3
VC05-2 204 205 450 225 225 8" 5000 55.0 78.0 0.13 0.5 140 115 0.7
VC05-3 204 206 400 200 200 10" 4840 55.0 86.0 0.05 0.5 140 110 0.7
VC05-4 204 207 400 200 200 10" 4840 55.0 86.0 0.05 0.5 140 110 0.7
VC05-5 210 209, 210 750 750 750 12" 29550 55.0 91.3 0.15 3.9 140 123 1.4
VC05-6 211 212 100 100 100 4" 3620 55.0 89.0 0.03 0.5 140 124 0.5
VC05-7 211 211 1000 1000 1000 12" 28100 55.0 80.0 0.23 2.8 140 118 0.4
ENERGY RECOVERY VENTILATOR SCHEDULE
TAG
LOCATION
TYPE
SUPPLY FAN EXHAUST FAN SUMMER DESIGN ENERGY RECOVERY
WINTER DESIGN ENERGY
RECOVERY
OA
FILTER
EFF
EXHAUS
T FILTER
EFF
UNIT
WEIGHT
(LB)
VOLT
(V) PH NOTES MANUFACTURER MODELNAME
DESIGN
AIRFLOW
(CFM) ESP (IN W.G)
MOTOR
DESIGN
AIRFLOW (CFM) ESP (IN W.G)
MOTOR OUTSIDE AIR OUTSIDE AIR
QTY POWER (HP) QTY POWER (HP) EAT, DB (°F) EAT, WB (°F) LAT, DB (°F) LAT, WB (°F) EAT, DB (°F) LAT, DB (°F)
ERV-2
PENTHOUSE
ROOF
OUTDOOR 5035 0.30 2 1.50 5035 1.00 2 2.00 92.0 77.9 82.4 72.1 -4.0 34.0 MERV-8 MERV-8 935 480 3 GREENHECK ECV-40-P-H
NOTES:
1. PROVIDE WITH MANUFACTURER'S VFDS.
2. PROVIDE ERV WITH BACNET CARD.
3. PROVIDE UNIT WITH MANUFACTURER'S FROST PROTECTION.
14⌀ 14⌀ 4-WAY
J
K
OS
T
TD
D
J
R
TC
F
F
F
F
D
F P
FR
CLNG
J
CLNG
F S
D
V
M
ES
ML
DC
CL
CR
MD
E
B
D
S
P
N
TV
N
XX-1
P
P
XX-1
XX-1
1P 1 POLE (2P, 3P, 4P, ETC.)
A AMPERE
AC ABOVE COUNTER
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
AMPL AMPLIFIER
ANNUN ANNUNCIATOR
APPROX APPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BD BOARD
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT
CAB CABINET
CAT CATALOG
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
COMB COMBINATION
CMPR COMPRESSOR
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
CONV CONVECTOR
CP CIRCULATING PUMP
CRT CATHODE-RAY TUBE
CT CURRENT TRANSFORMER
CTR CENTER
CU COPPER
DCP DOMESTIC WATER CIRCULATING
PUMP
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DPR DAMPER
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
ELU EMERGENCY LIGHTING UNIT
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXH EXHAUST
EXP EXPLOSION PROOF
FA FIRE ALARM
FABP FIRE ALARM BOOSTER POWER
SUPPLY PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT
SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT
INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HOA HANDS-OFF-AUTOMATIC SWITCH
HORIZ HORIZONTAL
HP HORSEPOWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
I/W INTERLOCK WITH
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LOC LOCATE OR LOCATION
LT LIGHT
ELECTRICAL ABBREVIATIONS
ELECTRICAL SYMBOL NOTES
EXIT LIGHTS. STEM INDICATES WALL MOUNTING. NO STEM INDICATES
CEILING MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S).
ARROW INDICATES DIRECTIONAL ARROW ON ILLUMINATED FACE(S). THE
CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. EXAMPLE: THE WALL
MOUNTED EXIT LIGHT TYPE "E1" WITH SINGLE FACE AND DIRECTIONAL
ARROW IS CONNECTED TO CIRCUIT 1.
DEVICES. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. THE SWITCH
DESIGNATION IS INDICATED BY A LOWER CASE LETTER. EXAMPLE: SPLIT
DUPLEX RECEPTACLE IS CONNECTED TO CIRCUIT 1 AND ONE RECEPTACLE
OUTLET IS CONTROLLED BY SWITCH "d".
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE
LETTER. EXAMPLE: SINGLE POLE SWITCH "d" TO CONTROL LIGHTING FIXTURES INDICATED BY "d".
WALL BOX DIMMER WITH SIZE AS INDICATED AT DEVICE. EXAMPLE: 600
WATT WALL BOX DIMMER TO CONTROL LIGHTING FIXTURES INDICATED
BY "e". SEE SPECIFICATIONS FOR WATTAGE IF NOT INDICATED.
SPECIAL CONNECTIONS. THE EQUIPMENT IS INDICATED BY A NUMBER IN A
CIRCLE. SEE THE MOTOR AND EQUIPMENT SCHEDULE FOR THE LOAD
DESCRIPTION AND TYPE OF CONNECTION. THE CIRCUIT DESIGNATION IS
INDICATED BY NUMBER(S) ADJACENT TO THE SYMBOL. EXAMPLE: EQUIPMENT
NO. ELEC-1; 1 PHASE CONNECTION TO CIRCUITS 2, 4.
MOTOR CONNECTIONS. THE MOTOR IS INDICATED BY A NUMBER
WITHIN OR CHARACTERS ADJACENT TO THE MOTOR SYMBOL.
SEE THE MOTOR AND EQUIPMENT SCHEDULE FOR THE MOTOR
DESCRIPTION AND ELECTRICAL REQUIREMENTS.
TRANSFORMERS. THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER "T". SEE THE TRANSFORMER
SCHEDULE OR THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER
DESCRIPTION AND REQUIREMENTS. EXAMPLE: TRANSFORMER TYPE "T1".
PANELBOARDS. PANELBOARD DOORS MAY BE SHOWN TO
INDICATE OPENING SIDE OF RECESSED PANELBOARDS. SEE
PANELBOARD IDENTIFICATION FOR DESIGNATION CODES.
CONDUIT SHOWN WITHOUT SLASH MARKS SHALL CONTAIN 1 # 12 CONDUCTOR
PER PHASE, NEUTRAL, AND GROUND IN 1/2" CONDUIT UNLESS SPECIFIC
EQUIPMENT REQUIRES A DIFFERENT SIZE.
CONDUIT SHOWN SHALL CONTAIN 1 # 10 CONDUCTOR PER PHASE IN
ELECTRICAL CODE SIZED MINIMUM CONDUIT UNLESS A CONDUCTOR AND
CONDUIT SIZE IS SHOWN ADJACENT.
HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE PANELBOARD
DESIGNATION IS SHOWN ADJACENT TO THE HOME RUN ARROW AS
A NUMERATOR AND THE CIRCUIT DESIGNATION IS SHOWN AS THE
DENOMINATOR. CIRCUIT BREAKER SIZES (AMPS/NUMBER OF
POLES) ARE SHOWN IN THE PANELBOARD SCHEDULE WITH THE
CORRESPONDING PANELBOARD AND CIRCUIT DESIGNATION.
EXAMPLE: HOME RUN TO PANELBOARD P4N-102; CIRCUITS 1, 3, 5.
ELECTRICAL LEGEND
LIGHTING SYMBOLS
FIRE ALARM HORN W/STROBE
FIRE ALARM BELL
FIRE ALARM BELL W/STROBE
FIRE ALARM CHIME W/STROBE
TIME CONTROL SWITCH
RELAY
SAFETY DISC. SW. (FUSED)
SAFETY DISC. SW. (NON-FUSED)
COMB. MOTOR STARTER (FUSED)
FLOOR JUNCTION BOX
JUNCTION BOX
MULTIOUTLET ASSEMBLY
RECEPT. ON CORD REEL
FLOOR DUPLEX RECEPT.
240V RECEPTACLE
FOURPLEX RECEPT. ON EMERG. CIRCUIT
FOURPLEX RECEPT.
DUPLEX RECEPT. ON EMERG. CIRCUIT
DUPLEX ISOLATED GROUND RECEPT.
SPLIT DUPLEX RECEPT.
DUPLEX RECEPT.
SINGLE RECEPT.
PUSH BUTTON
TIME DELAY SWITCH
TIMER SWITCH
OCCUPANCY SENSOR W/ MANUAL SWITCH
DIMMER SWITCH
SWITCH W/PILOT
KEYED SWITCH
4-WAY SWITCH
3-WAY SWITCH
SINGLE POLE SWITCH
PS - D2
KEYED NOTE (SEE SCHEDULE)
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
ROOM NAME AND NUMBER
ITEM TO BE
REMOVED
AREA NOT IN
CONTRACT
d e
T1
FLOOR CLEARANCE AREA
CONDUIT IN CEILING, FLOOR OR WALL AS REQUIRED BY FIELD CONDITIONS
CONDUIT IN FLOOR
FIRE ALARM PULL STATION
FIRE ALARM DOOR HOLDER
FIRE ALARM DOOR CLOSER
FIRE ALARM SHUT DOWN RELAY
CEILING DATA OUTLET
FLOOR DATA OUTLET
# OF VOICE AND # OF DATA OUTLETS
P4N-102 1, 3, 5
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NEW
GRAPHICAL REPRESENTATION OF PHASING, TYPICAL FOR ALL SYMBOLS.
CEILING DUPLEX RECEPT.
SPECIAL RECEPT.
CEILING JUNCTION BOX
FLOOR TELEPHONE OUTLET
GFI DUPLEX RECEPT. (FEED THROUGH)
GFI WEATHERPROOF RECEPT.
48"
GFI
GFI
WP
CLNG
ELEC-1
Room
FIRE ALARM SPEAKER W/STROBE
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MAG.S MAGNETIC STARTER
M/C MOMENTARY CONTACT
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SW
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MOA MULTIOUTLET ASSEMBLY
MSP MOTOR STARTER PANELBOARD
MSBD MAIN SWITCHBOARD
MT MOUNT
MT.C EMPTY CONDUIT
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
N.O. NORMALLY OPEN
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
OH OVERHEAD
OL OVERLOADS
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PP POWER POLE
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QUAN QUANTITY
RCPT RECEPTACLE
REQD REQUIRED
RM ROOM
RSC RIGID STEEL CONDUIT
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SHT SHEET
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
S/S STOP/START PUSHBUTTONS
STA STATION
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL CABINET
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UV ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WG WIRE GUARD
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
∠ ANGLE
@ AT
▲ DELTA
' FEET
" INCHES
# NUMBER
Ø PHASE
C CENTER LINE
P PLATE
EXIT LIGHT, WALL-MOUNTED,
SHADING AND ARROWS INDICATE
FACES AND DIRECTION
WALL-MOUNTED FIXTURES, TYPICAL
EXW1
LIGHTING FIXTURE TAG DESCRIPTORS:
TOP VALUE: FIXTURE TYPE ID.
BOTTOM VALUE, NUMBER: CIRCUIT NUMBER, REFER TO DRAWINGS FOR
PANEL.
BOTTOM VALUE, LOWERCASE LETTER: SWITCH DESIGNATION.
ABSENCE OF A SWITCH ID INDICATES FIXTURE IS CONTROLLED BY THE ONLY
SWITCH IN THE SPACE.
"x" IN PLACE OF THE SWITCH ID INDICATES NIGHT LIGHT, UNSWITCHED.
S3 1d
ELECTRIC STRIKE
MAGNETIC LOCK
COMBINATION LOCK
DOOR CONTACT
CARD READER
SECURITY KEYPAD
MOTION DETECTOR
NURSE CALL EMERG. STATION
NURSE CALL CODE BLUE STATION
NURSE CALL DUTY STATION
NURSE CALL STAFF STATION
NURSE CALL PATIENT STATION
NURSE CALL DOME LIGHT (1-COLOR)
TELEPHONE OUTLET
VOICE/DATA OUTLET
DOOR BELL
DOOR BUZZER
DOOR CHIME
DOOR SIGNAL
VOLUME CONTROL
MICROPHONE OUTLET
1V2D
CATV OUTLET
TV OUTLET
NURSE CALL DOME LIGHT (2-COLORS)
AUTO DOOR PUSH PAD
EMERGENCY LIGHTING UNIT, WALL-
MOUNTED, REMOTE BATTERY
EMERGENCY LIGHTING UNIT, WALL-
MOUNTED, INTEGRAL BATTERY
EMERGENCY LIGHTING UNIT, CEILING-
MOUNTED, INTEGRAL BATTERY
EMERGENCY LIGHTING UNIT, CEILING-
MOUNTED, REMOTE BATTERY
LIGHTING FIXTURES, TYPICAL,
RECTANGULAR
FILLED CIRCLES INDICATE RECESSED,
OPEN CIRCLES INDICATE SURFACE
DIAGONAL LINE INDICATES LENSED
OUTER DOTS INDICATE SUSPENDED
LIGHTING FIXTURES, TYPICAL, ROUND
CENTER DOT INDICATES PENDANT
DIAGONAL LINE INDICATES LENSED
CHEVRON INDICATES WALL WASH
STRIP FIXTURE
DIRECTIONAL LIGHT, TRACK, FLOOD
EXIT LIGHT, CEILING-MOUNTED,
SHADING AND ARROWS INDICATE
FACES AND DIRECTION
LINEAR LIGHT, TAPE LIGHT
EXIT/ELU COMBO
DIAGONAL HATCH INDICATES
LIGHT ON A CRITICAL CIRCUIT
SOLID HATCH INDICATES LIGHT ON AN
EMERGENCY OR LIFE SAFETY CIRCUIT
POLE/AREA LIGHTS
POST-TOP AREA LIGHT
BOLLARD LIGHT
SPRINKLER FLOW SWITCH
SPRINKLER VALVE TAMPER SWITCH
DUCT SMOKE DETECTOR
CEILING SMOKE DETECTOR
THERMAL DETECTOR
FIRE ALARM SYMBOLS
POWER SYMBOLS
DENOTES MOUNTING HEIGHT
MOTOR
UTILITY SERVICE POWER POLE
STATIC GROUND RECEPTACLE
SURGERY SERVICE COLUMN
POWER POLE (OPEN OFFICE STYLE)
IDENTITY
EXISTING TO REMAIN
TO BE REMOVED
CABLE TAP BOX
TRANSFORMER
BUS DUCT W/ PLUG IN DISCONNECT
T1
SYSTEMS SYMBOLS
PANELBOARD IDENTIFICATION
1. EQUIPMENT DESIGNATION:
L = LIGHTING
P = POWER
D = DISTRIBUTION
S = SWITCHBOARD
M = MOTOR CONTROL
CENTER
R = RELAY PANEL
2. VOLTAGE DESIGNATION:
1 = 120/240V - 1PH
2 = 240V - 3PH
3 = 208Y/120V - 3PH
4 = 480Y/277V - 3PH
5 = 120/208 - 1PH
6 = SPECIAL
3. SYSTEM DESIGNATION:
N = NORMAL
E = EMERGENCY
C = POWER CONDITIONED
U = UNINTERRUPTIBLE POWER
SOURCE
4. FLOOR
DESIGNATION:
B = BASEMENT
G = GROUND
1 = FIRST FLOOR
2 = SECOND FLOOR
ETC.
5. PANEL NO.
DESIGNATION:
01 = PANELBOARD #1
02 = PANELBOARD #2
03 = PANELBOARD #3
ETC.
P4N-102
1d
2, 4
ELECTRICAL GENERAL NOTES
1. CONDUCTORS OPERATING AT 50 VOLTS OR GREATER SHALL BE IN RACEWAY.
RACEWAY WITHIN THE STRUCTURE ABOVE THE FLOOR SLAB SHALL BE METAL.
RACEWAY BELOW THE FLOOR SLAB AND UNDERGROUND RACEWAY OUTSIDE
THE STRUCTURE SHALL BE PVC.
2. LOW VOLTAGE CABLES OR CONDUCTORS OPERATING AT LESS THAN 50 VOLTS
SHALL BE IN METAL RACEWAY WHERE INSTALLED WITHIN WALLS OR
INACCESSIBLE SPACES. LOW VOLTAGE CABLES MAY BE RUN IN CABLE TRAY
WHERE NOTED. LOW VOLTAGE CABLES MAY BE RUN IN CABLE SUPPORT HOOKS
ABOVE ACCESSIBLE CEILINGS WHERE NOTED. LOW VOLTAGE CABLE SHALL BE
PLENUM RATED IN PLENUM SPACES.
3. COORDINATE LOCATIONS OF DEVICES WITH ARCHITECTURAL ELEVATIONS AND
DETAILS. ARCHITECTURAL ELEVATIONS AND DETAILS TAKE PRECEDENCE OVER
LOCATIONS SHOWN ON ELECTRICAL DRAWINGS.
4. PROVIDE CABLE OR CONDUIT AND WIRE AS REQUIRED TO ACHIEVE CIRCUITING
SHOWN. SIZE CONDUCTORS PER NEC AMPACITY AND WIRE FILL CRITERIA.
PROVIDE DEDICATED NEUTRAL AND GROUND CONDUCTORS FOR CIRCUITING
,UNLESS NOTED OTHERWISE. INCREASE BRANCH CIRCUIT AND/OR FEEDER
CONDUCTORS INCLUDING EQUIPMENT GROUNDING CONDUCTORS
PROPORTIONALLY FOR NO MORE THAN 3% VOLTAGE DROP ON BRANCH
CIRCUITS AND 2% ON FEEDERS PER ENERGY CODE.
5. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE INSTALLATION
OF ELECTRICAL SYSTEMS AND THOSE REQUIRING ELECTRICAL CONNECTIONS
TO MAINTAIN NEC REQUIRED CLEARANCES, INCLUDED BY NOT LIMITED TO
AREAS ABOVE ACCESSIBLE CEILINGS.
6. COORDINATE WITH OTHER TRADES FOR PROPER INSTALLATION OF EQUIPMENT.
CONSULT THE DRAWINGS OF OTHER TRADES OR CRAFTS TO AVOID CONFLICTS
WITH EQUIPMENT, ETC. CONFLICTS SHALL BE RESOLVED PRIOR TO ROUGH-IN
AND AT NO ADDITIONAL COST TO THE OWNER.
7. LEAVE THE SITE CLEAN AND READY FOR OCCUPANCY. REMOVE DIRT, DEBRIS,
EMPTY CARTONS, TOOLS, CONDUIT AND WIRE SCRAPS AND MISCELLANEOUS
SPARE EQUIPMENT AND MATERIALS USED IN THIS DIVISION OF THE WORK
DURING CONSTRUCTION. COMPONENTS SHALL BE FREE OF DUST, GRIT AND
FOREIGN MATERIALS AND LEFT AS NEW BEFORE FINAL ACCEPTANCE OF WORK.
8. THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE
USED IN THIS SET OF DRAWINGS.
9. PERFORM WORK TO COMPLY WITH THE STANDARD PRACTICES FOR GOOD
WORKMANSHIP PUBLISHED BY NATIONAL ELECTRICAL CONTRACTORS
ASSOCIATION (NECA). COMPLY WITH THE LATEST ENFORCED EDITION OF THE
NATIONAL ELECTRICAL CODE (NEC), LOCAL CODES, AMENDMENTS, AND
ORDINANCES.
10. FIELD COORDINATE FINAL MECHANICAL AND EQUIPMENT LOCATIONS ALONG
WITH CONNECTION REQUIREMENTS AND CONTROL WIRING PRIOR TO ROUGH-IN.
ADJUST CORRESPONDING CIRCUIT BREAKER RATINGS AND BRANCH CIRCUITING
ACCORDINGLY.
11. ELECTRICAL WORK SHALL BE PERFORMED UNDER THE SUPERVISION OF A
LICENSED MASTER ELECTRICIAN. PROCURE PERMITS AND LICENSES AND PAY
FEES ASSOCIATED WITH THIS WORK.
12. MATERIALS FURNISHED FOR THIS PROJECT SHALL BE NEW, COMMERCIAL
GRADE, FREE OF DEFECTS, AND LISTED BY A NATIONALLY RECOGNIZED TESTING
LABORATORY UNO.
13. PROVIDE COMPLETE OPERATION & MAINTENANCE MANUAL INCLUDING
APPROVED SUBMITTAL DRAWINGS, WARRANTY INFORMATION FOR PRODUCT
SUPPLIED,AND MANUFACTURES OPERATION AND
MAINTENANCE INSTRUCTIONS.
14. THE CONTRACTOR IS RESPONSIBLE FOR MAKING FINAL WIRING TERMINATIONS
TO PRE-INSTALLED RECEPTACLES IN OFFICE FURNITURE. CONTRACTOR IS
RESPONSIBLE FOR WIRING AND INSTALLING VOICE/DATA DEVICES IN OFFICE
FURNITURE. COORDINATE PLACEMENT OF DEVICES WITH FURNITURE LAY-OUT.
15. SECURITY SYSTEM TO BE PROVIDED UNDER SEPARATE CONTRACT. IT IS THE
RESPONSIBILITY OF THIS CONTRACTOR TO PROVIDE CONDUIT PROVISIONS,
BACK BOXES, ROUGH-INS, SLEEVES AND POWER TO HEAD END EQUIPMENT FOR
EXACT REQUIREMENTS PRIOR TO START OF WORK.
16. CONDUIT AND WIRE SHALL NOT BE INSTALLED BELOW FLOOR SLAB UNLESS
INDICATED ON PLAN BY DASHED CONDUIT.
17. CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ELECTRICAL ITEMS SHOWN
ON DRAWINGS EXCEPT FOR ITEMS LISTED IN NOTE 'R' BELOW.
18. TV OUTLETS, VOLUME CONTROLS, NURSE CALL DOME LIGHTS, NURSE CALL
DEVICES, TELEPHONE OUTLETS, DATA OUTLETS, AND FIRE ALARM DEVICES
SHALL CONSIST OF A BACK BOX WTIH CONDUIT STUBBED ABOVE THE
ACCESSIBLE CEILING, SEE STUB UP DETAIL.VERIFY SIZE OF BACK BOX REQUIRED
WITH DEVICE TO BE INSTALLED. LOCATE BACK BOXES 6" FROM ADJACENT
POWER RECEPTACLE INTENDED FOR COMPUTER USE.
19. FURNISH AND INSTALL CONDUIT FROM BACK BOXES FOR THE FOLLOWING
DEVICES INTO THE ACCESSIBLE CEILING SPACE IN THE CORRIDOR, UNLESS
NOTED OTHERWISE:
1 / 2 " C T V O U T L E T S 1 / 2 " C V O L U M E C O N T R O L S
1/2"C DOOR SECURITY DEVICES (CARD READERS, DOOR STRIKES ETC..)
1 / 2 " C N U R S E C A L L D O M E L I G H T S 3 / 4 " C N U R S E C A L L D E V I C E S 3 / 4 " C T E L E P H O N E O U T L E T S
3 / 4 " C I N F O R M AT I O N O U T L E T S
3 / 4 " C F I R E A L A R M D E V I C E S
PR
O
JE
C
T
TI
TL
E
D R
AW
IN
G T
IT
LE
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING
6t h St re et
Ke no sh a, W I 5
C :\U se rs
\jr f\D oc um en ts
\K
Ke n o sh a co
P
TF
H
VA
C Im pr o v em en ts R
_j on .fu lle nk a m p.
rv t
4 /
/2
9:
:1
PM
E0.00
EL
EC
TR
IC
AL
G
EN
ER
AL
N
O
TE
S, LE
G
EN
D , A
N D
A
BB
R
EV
IA
TI
O N
S
KE
N O
SH
A
C O
U N
TY
P
R E-
TR
IA
L
FA
C
IL
IT
Y
H
VA
C
IM
PR
O
VE
M
EN
TS
K0450190
PH
O
N E
: 2
.6
.1 ww w.
cla rk di et z.
co m Ke no sh a, W
I 5 th S tre et
, 6 th
F lo or
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
2 04/15/26 ADDENDUM #1
GENERAL NOTES
1. MODIFY EXISTING LIGHTNING PROTECTION SYSTEM TO ALLOW FOR REMOVAL AND
REINSTALLATION OF ROOF-TOP UNITS AND FANS INDICATED AS BEING REPLACED ON THE
DRAWINGS.
2. THE MODIFIED LIGHTNING PROTECTION SYSTEM SHALL BEAR THE UL MASTER LABEL FOR
PROTECTION OF THE STRUCTURE. SEE SPECIFICATION SECTION 26 41 00 FOR ADDITIONAL
INFORMATION.
3. ALL LIGHTNING PROTECTION SYSTEM WORK SHALL BE COMPLETED BY AN AUTHORIZED
INSTALLER WITH MINIMUM OF THREE YEARS DOCUMENTED EXPERIENCE AND CERTIFIED BY
LIGHTNING PROTECTION INSTITUTE.
4. PERFORM ALL WORK IN ACCORDANCE WITH NFPA 480.
5. PERFORM ALL WORK IN ACCORDANCE WITH UL 96A AND FURNISH MASTER LABEL.
LIGHTNING PROTECTION SYSTEM
SOUTH MECH.
PENTHOUSE
SOUTH STORAGE
1 CU-2
MATCHLINE
5 3EHS
2 AHU-2(S)
3 AHU-2(R)
4 ERV-1
6 3ELS
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:3
:0 P
M
E2.02
T H
IR
D
F L
O O
R S
O U
T H
E L E
C T
R
IC
A L
N E
W W
O R
K P
L A
N
K E
N O
S H
A C
O U
N T
Y P
R E
-T R
IA
L
F A
C
IL
IT
Y
H V
A C
IM
P
R O
V E
M E
N T
S
K0450190
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
8' 16'4'0
THIRD FLOOR SOUTH ELECTRICAL NEW WORK PLAN
KEYNOTES (THIS SHEET)
1. PROVIDE ELECTRICAL CONNECTION TO NEW AIR COOLED CONDENSING UNIT AND
MANUFACTURER PROVIDED DISCONNECT SWITCH. PROVIDE FEEDER CONDUCTORS FROM
EXISTING PANEL 1HS, IN EXISTING CONUIT AS INDICATED ON EQUIPMENT CONNECTION
SCHEDULE (PROVIDE NEW CONDUIT AS REQUIRED).
2. PROVIDE ELECTRICAL CONNECTION TO NEW AIR HANDLING UNIT SUPPLY FANS AND
MANUFACTURER PROVIDED VFD'S. PROVIDE FUSIBLE DISCONNECT SWITCH. PROVIDE
FEEDER CONDUCTORS AND CONDUIT FROM EXISTING PANEL 3EHS AS INDICATED ON
EQUIPMENT CONNECTION SCHEDULE.
3. PROVIDE ELECTRICAL CONNECTION TO NEW AIR HANDLING UNIT RETURN FANS AND
MANUFACTURER PROVIDED VFD'S. PROVIDE FUSIBLE DISCONNECT SWITCH. PROVIDE
FEEDER CONDUUCTORS AND CONDUIT FROM EXISTING PANEL 3EHS AS INDICATED ON
EQUIPMENT CONNECTION SCHEDULE.
4. PROVIDE ELECTRICAL CONNECTION TO NEW ROOF MOUNTED ENERGY RECOVERY
VENTILATOR AND MANUFACTURER PROVIDED VFD'S. PROVIDE FUSIBLE DISCONNECT
SWITCH NEAR UNIT. PROVIDE FEEDER CONDUCTORS FROM EXISTING PANEL 3EHS, IN
EXISTING CONDUIT AS INDICATED ON EQUIPMENT CONNECTION SCHEDULE (PROVIDE NEW
CONDUIT AS REQUIRED).
5. EXISTING 277/480V PANEL 3EHS.
6. EXISTING 120/208V PANEL 3ELS.
7. PROVIDE ELECTRICAL CONNECTION TO NEW TEMPERATURE CONTROL PANEL. PROVIDE
FEEDER CONDUCTORS AND CONDUIT FROM EXISTING PANEL 3ELS, AS INDICATED ON
EQUIPMENT CONNECTION SCHEDULE. USE SPARE 20A/1P CIRCUIT BREAKER IN EXISTING
PANEL 3ELS.
GENERAL NOTES
1. SEE E0.00 FOR ELECTRICAL GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.
2. MODIFY EXISTING LIGHTNING PROTECTION SYSTEM TO ALLOW FOR REMOVAL AND
REINSTALLATION OF ROOF-TOP UNITS INDICATED AS BEING REPLACED ON THE DRAWINGS.
DISCONNECT LIGHTNING PROTECTION SYSTEM CABLES AND TERMINALS FROM EXISTING
EQUIPMENT FOR REMOVAL OF EQUIPMENT. AFTER NEW EQUIPMENT HAS BEEN INSTALLED
RECONNECT LIGHTNING PROTECTION SYSTEM CABLES AND TERMINALS TO NEW
EQUIPMENT.
KEYPLAN_________
N.T.S.
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
2 04/15/26 ADDENDUM #1
P R
O J E
C T
T
IT
L E
D R
A W
IN
G
T
IT
L E
PROJECT No.
DRAWING No.
NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t
K e n o s h a W
I
C U s e rs
\J W ie d o ff \D o c u m e n ts
\K
K e n o s h a c o P
T F
H V
A C
I m p ro v e m e n ts
R J e ff .W ie d o ff S
D W
.r v t
/1
/2
:3
:0 P
M
E4.01
E L E
C T
R
IC
A L
S C
H E
D U
L E
S K
E N
O S
H A
C O
U N
T Y
P R
E -T
R
IA
L F
A C
IL
IT
Y H
V A
C
IM
P R
O V
E M
E N
T S
K0450190
P H
O N
E
.6
.1 w
.c la rk d ie tz
.c o m
K e n o sh a
W
I th
S tr e e t, th F lo o r
NO. DATE REVISION
1 03/11/26 ISSUED FOR BID
2 04/15/26 ADDENDUM #1
Clark Dietz, Inc. HVAC Insulation
County of Kenosha – Pre-Trial Facility HVAC Improvements 23 07 00 - 1
SECTION 230700
HVAC INSULATION
PART 1 GENERAL
1.1 SUMMARY
A. Section Includes:
1. HVAC piping insulation, jackets and accessories.
2. HVAC ductwork insulation, jackets, and accessories.
1.2 REFERENCES
A. ASTM International:
1. ASTM C450 - Standard Practice for Fabrication of Thermal Insulating Fitting Covers for NPS Piping, and
Vessel Lagging.
2. ASTM C534 - Standard Specification for Preformed Flexible Elastomeric Cellular Thermal Insulation in
Sheet and Tubular Form.
3. ASTM C585 - Standard Practice for Inner and Outer Diameters of Rigid Thermal Insulation for Nominal
Sizes of Pipe and Tubing (NPS System).
4. ASTM C795 - Standard Specification for Thermal Insulation for Use in Contact with Austenitic Stainless
Steel.
5. ASTM C1136 - Standard Specification for Flexible, Low Permeance Vapor Retarders for Thermal
Insulation.
6. ASTM C1290 - Standard Specification for Flexible Fibrous Glass Blanket Insulation Used to Externally
Insulate HVAC Ducts.
7. ASTM D1785 - Standard Specification for Rigid Poly (Vinyl Chloride) (PVC) Compounds and Chlorinated
Poly (Vinyl Chloride) (CPVC) Compounds.
8. ASTM E96/E96M - Standard Test Methods for Water Vapor Transmission of Materials.
9. ASTM E162 - Standard Test Method for Surface Flammability of Materials Using a Radiant Heat Energy
Source.
B. Sheet Metal and Air Conditioning Contractors’:
1. SMACNA - HVAC Duct Construction Standard - Metal and Flexible.
1.3 SUBMITTALS
A. Product Data: Submit product description, thermal characteristics and list of materials and thickness for each service, and location.
B. Manufacturer's Installation Instructions: Submit manufacturers published literature indicating proper installation procedures.
1.4 QUALITY ASSURANCE
A. Test pipe insulation for maximum flame spread index of 25 and maximum smoke developed index of not exceeding 50 in accordance with ASTM E84.
B. Pipe insulation manufactured in accordance with ASTM C585 for inner and outer diameters.
C. Factory fabricated fitting covers manufactured in accordance with ASTM C450.
County of Kenosha – Pre-Trial Facility HVAC Improvements 23 07 00 - 2
D. Duct insulation, Coverings, and Linings: Maximum 25/50 flame spread/smoke developed index, when tested in accordance with ASTM E84, using specimen procedures and mounting procedures of ASTM
E 2231.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Accept materials on site in original factory packaging, labeled with manufacturer's identification, including product density and thickness.
B. Protect insulation from weather and construction traffic, dirt, water, chemical, and damage, by storing in original wrapping.
1.6 ENVIRONMENTAL REQUIREMENTS
A. Install insulation only when ambient temperature and humidity conditions are within range recommended by manufacturer.
B. Maintain temperature before, during, and after installation for minimum period of 24 hours.
PART 2 PRODUCTS
2.1 MANUFACTURER
A. Manufacturers for Glass Fiber and Mineral Fiber Insulation Products:
1. CertainTeed.
2. Knauf.
3. Johns Manville.
4. Owens-Corning.
B. Manufacturers for Closed Cell Elastomeric Insulation Products:
1. Aeroflex. Aerocell.
2. Armacell, LLC. Armaflex.
3. Nomaco. K-flex.
2.2 PIPE INSULATION
A. TYPE P-1: ASTM C547, molded glass fiber pipe insulation.
1. Thermal Conductivity: 0.23 at 75 degrees F.
2. Operating Temperature Range: 0 to 850 degrees F.
3. Vapor Barrier Jacket: ASTM C1136, Type I, factory applied reinforced foil kraft with self-sealing adhesive joints.
4. Jacket Temperature Limit: minus 20 to 150 degrees F.
B. TYPE P-2: ASTM C612; semi-rigid, fibrous glass board noncombustible, end grain adhered to jacket.
Conform to ASTM C795 for application on Austenitic stainless steel.
1. Thermal Conductivity: 0.27 at 75 degrees F.
2. Operating Temperature Range: 0 to 650 degrees F.
3. Vapor Barrier Jacket: ASTM C1136, Type II, factory applied reinforced foil kraft with self-sealing adhesive joints.
4. Jacket Temperature Limit: minus 20 to 150 degrees F.
C. TYPE P-5: ASTM C534; Type I, flexible, closed cell elastomeric insulation, tubular.
County of Kenosha – Pre-Trial Facility HVAC Improvements 23 07 00 - 3
1. Thermal Conductivity: 0.27 at 75 degrees F.
2. Operating Temperature Range: Range: Minus 70 to 180 degrees F.
2.3 PIPE INSULATION JACKETS
A. PVC Plastic Pipe Jacket:
1. Product Description: ASTM D1785, One piece molded type fitting covers and sheet material, off-white color.
2. Thickness: 30 mil.
3. Connections: Brush on welding adhesive.
B. Aluminum Pipe Jacket:
1. ASTM B209.
2. Thickness: 0.016 inch thick sheet.
3. Finish: Smooth.
4. Joining: Longitudinal slip joints and 2 inch laps.
5. Fittings: 0.016 inch thick die shaped fitting covers with factory attached protective liner.
6. Metal Jacket Bands: 3/8 inch wide; 0.015 inch thick aluminum.
2.4 PIPE INSULATION ACCESSORIES
A. Vapor Retarder Lap Adhesive: Compatible with insulation.
B. Covering Adhesive Mastic: Compatible with insulation.
C. Piping 1-1/2 inches diameter and smaller: Galvanized steel insulation protection shield. MSS SP-69, Type
40. Length: Based on pipe size and insulation thickness.
D. Piping 2 inches diameter and larger: Wood insulation saddle, hard maple. Inserts length: not less than 6 inches long, matching thickness and contour of adjoining insulation.
E. Adhesives: Compatible with insulation.
2.5 DUCTWORK INSULATION
A. TYPE D-1: ASTM C1290, flexible glass fiber, commercial grade with factory applied reinforced aluminum foil jacket meeting ASTM C1136, Type II.
1. Thermal Conductivity: 0.27 at 75 degrees F.
2. Maximum Operating Temperature: 250 degrees F.
3. Density: 0.75 pound per cubic foot.
B. TYPE D-2: ASTM C612, Type IA or IB, rigid glass fiber, with factory applied reinforced aluminum foil facing meeting ASTM C1136, Type II.
1. Thermal Conductivity: 0.23 at 75 degrees F.
2. Density: 3.0 pound per cubic foot.
2.6 DUCTWORK INSULATION JACKETS
A. Aluminum Duct Jacket:
1. ASTM B209.
2. Thickness: 0.016 inch thick sheet.
3. Finish: Smooth.
4. Joining: Longitudinal slip joints and 2 inch laps.
County of Kenosha – Pre-Trial Facility HVAC Improvements 23 07 00 - 4
5. Fittings: 0.016 inch thick die shaped fitting covers with factory attached protective liner.
6. Metal Jacket Bands: 3/8 inch wide; 0.015 inch thick aluminum.
B. Aluminum Duct Jacket Systems:
1. Self-adhesive material with aluminum finish surface, color to be selected by owner.
2. Tear strength of 8.5 lbs or greater meeting ASTM D624.
3. Thickness: 6 mils sheet.
4. Finish: Smooth.
5. Non permeable with vapor barrier.
6. Mold resistant.
2.7 DUCTWORK INSULATION ACCESSORIES
A. Vapor Retarder Tape:
1. Kraft paper reinforced with glass fiber yarn and bonded to aluminized film, with pressure sensitive rubber based adhesive.
B. Vapor Retarder Lap Adhesive: Compatible with insulation.
C. Adhesive: Waterproof, ASTM E162 fire-retardant type.
D. Liner Fasteners: Galvanized steel, self-adhesive pad head.
E. Tie Wire: 0.048 inch stainless steel with twisted ends on maximum 12 inch centers.
F. Lagging Adhesive: Fire retardant type with maximum 25/450 flame spread/smoke developed index when tested in accordance with ASTM E84.
G. Impale Anchors: Galvanized steel, 12 gage self-adhesive pad.
H. Adhesives: Compatible with insulation.
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify piping, equipment and ductwork has been tested before applying insulation materials.
B. Verify surfaces are clean and dry, with foreign material removed.
3.2 INSTALLATION - PIPING SYSTEMS
A. Piping Exposed to View in Finished Spaces: Locate insulation and cover seams in least visible locations.
B. Continue insulation through penetrations of building assemblies or portions of assemblies having fire resistance rating of one hour or less. Provide intumescent firestopping when continuing insulation through assembly. Finish at supports, protrusions, and interruptions. Piping Systems Conveying Fluids Below
Ambient Temperature:
1. Insulate entire system including fittings, valves, unions, flanges, strainers, flexible connections, pump bodies, and expansion joints.
County of Kenosha – Pre-Trial Facility HVAC Improvements 23 07 00 - 5
2. Furnish factory-applied or field-applied vapor retarder jackets. Secure factory-applied jackets with pressure sensitive adhesive self-sealing longitudinal laps and butt strips. Secure field-applied jackets with outward clinch expanding staples and seal staple penetrations with vapor retarder mastic.
3. Insulate fittings, joints, and valves with molded insulation of like material and thickness as adjacent pipe. Finish with glass cloth and vapor retarder adhesive or PVC fitting covers.
C. Glass Fiber Board Insulation:
1. Apply insulation close to equipment by grooving, scoring, and beveling insulation. Fasten insulation to equipment with studs, pins, clips, adhesive, wires, or bands.
2. Fill joints, cracks, seams, and depressions with bedding compound to form smooth surface. On cold equipment, use vapor retarder cement.
3. Cover wire mesh or bands with cement to a thickness to remove surface irregularities.
D. Inserts and Shields:
1. Piping 1-1/2 inches Diameter and Smaller: Install galvanized steel shield between pipe hanger and insulation.
2. Piping 2 inches Diameter and Larger: Install insert between support shield and piping and under finish jacket.
a. Insert Configuration: Minimum 6 inches long, of thickness and contour matching adjoining insulation; may be factory fabricated.
b. Insert Material: Compression resistant insulating material suitable for planned temperature range and service.
3. Piping Supported by Roller Type Pipe Hangers: Install galvanized steel shield between roller and inserts.
E. Insulation Terminating Points:
1. Coil Branch Piping 1 inch and Smaller: Terminate hot water piping at union upstream of the coil control valve.
2. Hot Water Coil Branch Piping: Insulate hot water piping and associated components up to coil connection.
3. Condensate Piping: Insulate entire piping system…