2613 Addendum 1.pdf

PDF 5 MB Posted

Attached to
Kenosha County Pre-Trial Facility HVAC Improvements Phase 1
Solicitation number
2613
Issued by
Kenosha County, Kellnersville Village, Wisconsin

About this file

This Addendum 1 to RFP #2613 provides clarifications and revisions to the Kenosha County Pre-Trial Facility HVAC Improvements Phase 1 project, a construction services procurement issued by Kenosha County, Wisconsin. The addendum addresses contractor questions regarding piping insulation specifications, joint types, construction scheduling, and ductwork finish requirements through a Questions and Answers section. Key clarifications include confirmation that refrigerant piping insulation specifications have been re-issued, press copper joints are not permitted, the two-week AHU changeout window remains firm, temporary airflow provisions during AHU downtime are required, and exposed ductwork in mechanical rooms must be finished with aluminum jacket rather than board insulation with foil facing. The addendum incorporates multiple drawing revisions across mechanical, electrical, and specification sections, including updates to diffuser locations, control panel placement, roof drain addressing, cooling coil specifications, and new glycol solution requirements. A comprehensive new specification section 230700 for HVAC Insulation has been added, establishing detailed requirements for pipe and ductwork insulation materials, thermal characteristics, vapor barriers, jackets, and installation procedures. The addendum was issued on April 15, 2026, and reflects the second revision to the original bid documents issued March 11, 2026.

The addendum contains no information regarding pricing, set-asides, incumbent contractors, or funding sources, as these elements were established in the original RFP documents. All cost and contract terms remain as specified in the base bid solicitation. The HVAC Insulation specification establishes performance standards requiring maximum flame spread index of 25 and smoke development index not exceeding 50 per ASTM E84 testing, with pipe insulation types ranging from molded glass fiber to closed-cell elastomeric materials rated for operating temperatures from minus 70 to 850 degrees Fahrenheit depending on application. Ductwork insulation specifications similarly detail thermal conductivity requirements, density specifications, and finishing requirements with aluminum jackets for exposed applications in mechanical rooms and finished spaces. Installation requirements mandate that all piping systems conveying fluids below ambient temperature be fully insulated including fittings, valves, unions, and expansion joints, with vapor retarder jackets and specified thickness schedules for heating water and refrigerant piping ranging from 1.5 to 2.0 inches depending on pipe diameter and service application.

View the file

Other files

File Type Posted
2613 Specifications.pdf PDF
Vendor Responsibility Form Construction.pdf PDF
2613 Bid Documents.pdf PDF
Background Check Form.docx DOCX document
2613 Drawings.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFP #2613 Addendum One Page 1 of 2

Yes.

Questions and Answers:

Q. The Piping insulation specification does not indicate any refrigeration piping.

Please confirm what insulation is.

A. Spec has been re-issued regarding refrigerant piping insulation.

Q. Are press copper joints allowed?

A. No.

Q. A two week window for the AHU changeout was mentioned at the walkthrough.

Can you please confirm? That duration is pretty tight and may require overtime costs to get it done in time.

A. 2-week window will remain as originally planned.

Q. Temporary airflow when the AHU was down was mentioned in the walkthrough .

Can you please confirm?

A. Yes.

Q. Insulation spec 23 07 00 3.3 calls for "Ductwork exposed in mechanical equipment rooms or finished space below 8feet above finished floor: finish with aluminum jacket" The existing ductwork does not have this treatment. Can the exposed duct in the mechanical room be insulated with Board insulated with foil facing?

A. We will stay with the aluminum jacket as referenced in spec section.

Revisions & Attachments:

Drawings:

M1.03

• Existing diffusers revised to be removed.

M1.09

• Sheet added to note that the existing AHU-2 is to be removed off the existing control panels in the north mechanical room.

KENOSHA COUNTY

RFP #2613 ADDENDUM ONE DATED 4/15/2026

Kenosha County Pre-Trial Facility HVAC Improvements Phase 1

RFP #2613 Addendum One Page 2 of 2

M2.02

• New diffusers added.

M2.04

• Note added addressing roof drain.

M3.04

• New control panel moved to south mechanical room.

M5.01

• New diffusers added to schedule.

• Cooling coil typo fixed to DX cooling coil.

• Note added for verifying split section in AHU to fit through door.

• ERV unit exhaust fan static pressure fixed to 1”.

E0.00

• Lighting Protection general notes added.

E2.02

• New control panel and feed added.

E4.01

• New control panel added to schedule.

SPECS:

232116

• Section 2.11 Glycol solution: Change “propylene glycol” to ethylene glycol.

230700

• New spec section provided.

End Addendum 1

TS

TS

TS

T S

T S

TS

T S

T S

TS TS

TS

TS

T S

ELEV. S.P.

FACILITY ADMIN

CONF.

CL.

115A

STORAGE

CONFERENCE

OFFICE

OFFICE

OFFICE

OFFICE

LOBBY

T.

J.C.

CLERICAL

CL.

104A

CORR.

RECORDS STORAGE

ELEC. RM.

116A

W.

M.

CORR.

(SA)

(SA)

(S A

(S

A

MATCHLINE

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(RA)

(E A

(TYP.)

4 5 6

(TYP.)

6 6

P R

O J E

C T

T

IT

L E

D R

A W

IN

G

T

IT

L E

PROJECT No.

DRAWING No.

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t

K e n o s h a W

I

C U s e rs

\J W ie d o ff \D o c u m e n ts

\K

K e n o s h a c o P

T F

H V

A C

I m p ro v e m e n ts

R J e ff .W ie d o ff S

D W

.r v t

/1

/2

:3

:3 P

M

M1.03

F

IR

S T

F L

O O

R S

O U

T H

V E

N T

IL

A

T

IO

N D

E M

O L

IT

IO

N P

L A

N

K E

N O

S H

A C

O U

N T

Y P

R E

-T R

IA

L

F A

C

IL

IT

Y

H V

A C

IM

P

R O

V E

M E

N T

S

K0450190

DESIGNED BY: JAW

DRAWN BY: JAW

CHECKED BY: NTP

DATE CHECKED: 02/20/26

P H

O N

E

.6

.1 w w

.c la rk d ie tz

.c o m

K e n o sh a

W

I th

S tr e e t, th F lo o r

8' 16'4'0

FIRST FLOOR SOUTH VENTILATION DEMOLITION PLAN

DEMOLITION KEYNOTES

1. REMOVE EXISTING VAV BOX WITH HW REHEAT AND ASSOCIATED

CONTROLS. DISCONNECT TRANSITION FITTINGS ON BOTH SIDES OF

BOX.

2. REMOVE EXISTING SA DUCT AND ASSOCIATED SA DIFFUSERS. SEE

M2.02 FOR NEW WORK.

3. REMOVE EXISTING VAV BOX WITH HW REHEAT AND ASSOCIATED

CONTROLS. DISCONNECT TRANSITION FITTINGS ON BOTH SIDES OF

BOX. REMOVE EXISTING GYPSUM BOARD CEILING.

4. REMOVE TEMPERTAURE SENSOR AND ASSOCIATED WIRING.

REPLACE WITH NEW.

5. REMOVE EXISTING TEMPERATURE CONTROLS SERVING HOT WATER

CABINET HEATER. EXISTING CABINET HEATER TO REMAIN. REMOVE

EXISTING TEMPERATURE SENSOR.

6. REMOVE EXISTING TEMPERATURE CONTROLS SERVING HOT WATER

UNIT HEATER. EXISTING UNIT HEATER TO REMAIN.

7. REMOVE IN-UNIT THERMOSTAT.

KEYPLAN_________

N.T.S.

GENERAL NOTES

1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND

REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO

INSTALL THEIR WORK.

2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE

DAMAGED DURING WORK.

3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW

DEMOLITION OF EXISTING DUCTWORK AND INSTALLATION OF

DUCTWORK.

4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY

REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING

LIGHT FIXTURES WHEN WORK IS COMPLETE.

5. EXISTING TRANSFER OPENINGS THROUGHOUT TO REMAIN.

KEYNOTES (THIS SHEET)

1. EXISTING EXHAUST GRILLE AND ASSOCIATED DUCTWORK TO

REMAIN.

2. EXISTING RETURN GRILLE AND ASSOCIATED DUCTWORK TO

REMAIN.

3. EXISTING SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK TO

REMAIN.

4. EXISTING EXHAUST DUCT UP TO FLOOR ABOVE TO REMAIN.

5. EXISTING RETURN DUCT UP TO FLOOR ABOVE TO REMAIN.

6. EXISTING SUPPLY DUCT UP TO FLOOR ABOVE TO REMAIN.

NO. DATE REVISION

1 03/11/26 ISSUED FOR BID

2 04/15/26 ADDENDUM #1

NORTH MECH.

PENTHOUSE

NORTH STORAGE

ELEV. EQUIP.

MATCHLINE

P R

O J E

C T

T

IT

L E

D R

A W

IN

G

T

IT

L E

PROJECT No.

DRAWING No.

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t

K e n o s h a W

I

C U s e rs

\J W ie d o ff \D o c u m e n ts

\K

K e n o s h a c o P

T F

H V

A C

I m p ro v e m e n ts

R J e ff .W ie d o ff S

D W

.r v t

/1

/2

:3

:5 P

M

M1.09

T H

IR

D

F L O

O R

N O

R T

H H

E A

T

IN

G D

E M

O L

IT

IO

N

P L

A N

K E

N O

S H

A C

O U

N T

Y P

R E

-T R

IA

L

F A

C

IL

IT

Y

H V

A C

IM

P

R O

V E

M E

N T

S

K0450190

DESIGNED BY: JAW

DRAWN BY: JAW

CHECKED BY: NTP

DATE CHECKED: 02/20/26

P H

O N

E

.6

.1 w

.c la rk d ie tz

.c o m

K e n o sh a

W

I th

S tr e e t, th F lo o r

NO. DATE REVISION

1 03/11/26 ISSUED FOR BID

2 04/15/26 ADDENDUM #1

8' 16'4'0

THIRD FLOOR NORTH HEATING DEMOLITION PLAN

DEMOLITION KEYNOTES

1. DISCONNECT AHU-2 FROM EXISTING TEMPERATURE CONTROL

PANELS.

KEYNOTES (THIS SHEET)

1. EXISTING TEMPERATURE CONTROL PANELS TO REMAIN.

KEYPLAN_________

N.T.S.

CO

CO

M

TS

TS

TS

T S

T S

TS

T S

T S

TS TS

TS

TS

T S

M

ELEV. S.P.

FACILITY ADMIN

CONF.

114 CL.

115A

STORAGE

CONFERENCE

OFFICE

OFFICE

OFFICE

OFFICE

LOBBY

101 T.

J.C.

CLERICAL

CL.

104A

CORR.

RECORDS STORAGE

ELEC. RM.

116A

W.

M.

CORR.

VC03-1

VC03-3

VC03-2

VC03-4

VC03-5

VC03-6

VC03-7

VC03-8

VC03-9

VC03-10

VC03-11

S 500

S 300

S 300

S 150

S 150

S 100

S 400

S 150

S 400

S 500

S 300 S 300

S 200

S 175 S 175

E 70

E 70

R 360

R 300

R 300

R 400

R 400

R 500

R 600

R 350

R 200

E 50

E 150 E 100

R 100

E 200

R 1300

R 300

20"/14" SA

16"/12" SA

14"ø SA

(SA)

(SA)

(S A

(RA)

(10"/10" SA)

(8"/6" SA)

(10"/8" SA)

(12"ø SA)

(10"ø SA)

(8"/8" SA)

(10"ø SA)

(10"/10" SA)

(8"/8" SA)

(10"ø SA)

(E A

NO2

(TYP.)

E-1 1600

EF-4

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

MATCHLINE

NO2

A1 500

A1 500

A1 500

P R

O J E

C T

T

IT

L E

D R

A W

IN

G

T

IT

L E

PROJECT No.

DRAWING No.

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t

K e n o s h a W

I

C U s e rs

\J W ie d o ff \D o c u m e n ts

\K

K e n o s h a c o P

T F

H V

A C

I m p ro v e m e n ts

R J e ff .W ie d o ff S

D W

.r v t

/1

/2

:3

:5 P

M

M2.02

F

IR

S T

F L O

O R

S O

U T

H V

E N

T

IL

A T

IO

N

N E

W W

O R

K P

L A

N

K E

N O

S H

A C

O U

N T

Y P

R E

-T R

IA

L

F A

C

IL

IT

Y

H V

A C

IM

P

R O

V E

M E

N T

S

K0450190

DESIGNED BY: JAW

DRAWN BY: JAW

CHECKED BY: NTP

DATE CHECKED: 02/20/26

P H

O N

E

.6

.1 w

.c la rk d ie tz

.c o m

K e n o sh a

W

I th

S tr e e t, th F lo o r

8' 16'4'0

FIRST FLOOR SOUTH VENTILATION NEW WORK PLAN

KEYNOTES (THIS SHEET)

1. PROVIDE NEW VAV BOX AND COIL. SEE SCHEDULE. PROVIDE NEW

TRANSITION FITTINGS ON BOTH ENDS, CONNECT TO EXISTING

DUCTWORK.

2. PROVIDE NEW SA DUCTWORK.

3. PROVIDE 14" ROUND DUCT AND CONNECT TO NEW GRILLES.

REPLACE EXISTING CEILING.

4. PROVIDE NEW VAV BOX AND COIL. SEE SCHEDULE. PROVIDE NEW

TRANSITION FITTINGS ON BOTH ENDS, CONNECT TO EXISTING

DUCTWORK. PROVIDE 24”X24” ACCESS DOOR AND PATCH AND PAINT

TO MATCH ADJACENT SURFACES.

5. PROVIDE NEW TEMPERATURE SENSOR AND ASSOCIATED WIRING.

6. PROVIDE NEW CO/NO2 SENSORS FOR EXHAUST FANS. SEE

TEMPERATURE CONTROL SCHEMATICS.

7. PROVIDE NEW INTAKE LOUVER AT EXISTING WALL. OFFSET 12”

HORIZONTALLY FROM OVERHEAD DOOR. PROVIDE MOTORIZED

DAMPER FOR LOUVER, SEE SCHEDULE AND DETAIL.

8. PROVIDE CEILING HUNG EXHAUST FAN AND PLENUM TO EXHAUST

LOUVER. SEE SCHEDULE AND DETAIL.

9. PROVIDE NEW WALL EXHAUST LOUVER AND MOTORIZED DAMPER.

OFFSET 12" HORIZONTALLY FROM OVERHEAD DOOR AND VERTICAL

JOINT.

10. PROVIDE DUCT EXHAUST GRILLE 1' AFF. SEE SCHEDULE.

11. EXISTING EXHAUST GRILLE AND ASSOCIATED DUCTWORK TO

REMAIN.

12. EXISTING RETURN GRILLE AND ASSOCIATED DUCTWORK TO

REMAIN.

13. EXISTING SUPPLY DIFFUSER AND ASSOCIATED DUCTWORK TO

REMAIN.

14. EXISTING EXHAUST DUCT UP TO FLOOR ABOVE TO REMAIN.

15. EXISTING RETURN DUCT UP TO FLOOR ABOVE TO REMAIN.

16. EXISTING SUPPLY DUCT UP TO FLOOR ABOVE TO REMAIN.

17. PROVIDE NEW TEMPERATURE SENSOR MOUNTED ON UNIT.

18. PROVIDE NEW CO/NO2 SENSORS FOR EXHAUST FANS. SEE

TEMPERATURE CONTROL SCHEMATICS.

KEYPLAN_________

N.T.S.

GENERAL NOTES

EL-1

IL-1

MD-2

MD-1

NO. DATE REVISION

1 03/11/26 ISSUED FOR BID

2 04/15/26 ADDENDUM #1

1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND

REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO

INSTALL THEIR WORK.

2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE

DAMAGED DURING WORK.

3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW

DEMOLITION OF EXISTING DUCTWORK AND INSTALLATION OF

DUCTWORK.

4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY

REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING

LIGHT FIXTURES WHEN WORK IS COMPLETE.

5. EXISTING TRANSFER OPENINGS THROUGHOUT TO REMAIN.

6. REBALANCE ALL EXISTING SUPPLY DIFFUSERS, RETURN AND

EXHAUST GRILLES TO AIR FLOW RATES SHOWN.

7. CONTRACTOR IS RESPONSIBLE FOR REMOVING AND REPLACING

DRYWALL CEILING AS REQUIRED TO COMPLETE THEIR WORK.

REPLACEMENT OF CEILING SHALL MATCH EXISTING CONDITIONS AND

CONSTRUCTION TYPE. PATCH AND PAINT TO MATCH ADJACENT

SURFACES.

M

M

T S

TS

SOUTH MECH.

PENTHOUSE

SOUTH STORAGE

MATCHLINE

AHU-2

30"/34" SA

34"/30" EA

20"/20" OA

24"/30" RA

ERV-2

MD-3

M4.01

P R

O J E

C T

T

IT

L E

D R

A W

IN

G

T

IT

L E

PROJECT No.

DRAWING No.

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t

K e n o s h a W

I

C U s e rs

\J W ie d o ff \D o c u m e n ts

\K

K e n o s h a c o P

T F

H V

A C

I m p ro v e m e n ts

R J e ff .W ie d o ff S

D W

.r v t

/1

/2

:3

:0 P

M

M2.04

T H

IR

D

F L

O O

R S

O U

T H

V E

N T

IL

A

T

IO

N N

E W

W O

R K

P L A

N

K E

N O

S H

A C

O U

N T

Y P

R E

-T R

IA

L

F A

C

IL

IT

Y

H V

A C

IM

P

R O

V E

M E

N T

S

K0450190

DESIGNED BY: JAW

DRAWN BY: JAW

CHECKED BY: NTP

DATE CHECKED: 02/20/26

P H

O N

E

.6

.1 w

.c la rk d ie tz

.c o m

K e n o sh a

W

I th

S tr e e t, th F lo o r

8' 16'4'0

THIRD FLOOR SOUTH VENTILATION NEW WORK PLAN

KEYPLAN_________

N.T.S.

GENERAL NOTES

NO. DATE REVISION

1 03/11/26 ISSUED FOR BID

2 04/15/26 ADDENDUM #1

1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND

REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO

INSTALL THEIR WORK.

2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE

DAMAGED DURING WORK.

3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW

DEMOLITION OF EXISTING DUCTWORK AND INSTALLATION OF

DUCTWORK.

4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY

REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING

LIGHT FIXTURES WHEN WORK IS COMPLETE.

5. EXISTING TRANSFER OPENINGS THROUGHOUT TO REMAIN.

6. REBALANCE ALL EXISTING SUPPLY DIFFUSERS, RETURN AND

EXHAUST GRILLES TO AIR FLOW RATES SHOWN.

7. CONTRACTOR IS RESPONSIBLE FOR REMOVING AND REPLACING

DRYWALL CEILING AS REQUIRED TO COMPLETE THEIR WORK.

REPLACEMENT OF CEILING SHALL MATCH EXISTING CONDITIONS AND

CONSTRUCTION TYPE. PATCH AND PAINT TO MATCH ADJACENT

SURFACES.

KEYNOTES (THIS SHEET)

1. PROVIDE NEW DUCT CONNECTION TO NEW ERV UNIT ON ROOF.

PATCH EXISTING ROOF AROUND DUCT IN ACCORDANCE WITH

ROOFING MANUFACTURER'S (DOWSIL) REQUIREMENTS. PROVIDE

STANDARD PATCHING WARRANTY. COORDINATE ERV MOUNTING

AROUND EXISTING ROOF DRAINS.

2. EXISTING EXHAUST DUCT DOWN TO FLOOR BELOW TO REMAIN.

3. EXISTING RETURN DUCT DOWN TO FLOOR BELOW TO REMAIN.

4. PROVIDE NEW 34X30 SA DUCT WITH CONNECTION TO EXISTING

SUPPLY DUCT AT FLOOR LEVEL.

5. NEW AIR HANDLING UNIT.

6. EXISTING LOUVERS AND MOTORIZED DAMPERS TO REMAIN.

7. PROVIDE TEMPERATURE SENSOR MOUNTED TO UNIT.

8. CONNET NEW EXHAUST DUCT TO EXISTING LOUVER.

9. MAKE NEW RA CONNECTION TO EXISTING VERTICAL DUCT.

10. NEW 34X30 EA DUCT DOWN. MAKE TRANSITION TO UNIT AS

NECESSARY.

11. NEW OA DUCT UP. TRANSITION TO 30X30 AFTER CONNECTION FROM

SA DUCT COMING FROM ERV.

12. NEW OA DUCT FROM ERV. MAKE CONNECTION TO FLAT VERTICAL

DUCT WORK.

13. NEW 30X30 OA DUCT UP TO EXISTING ROOF HOOD. MAKE

TRANSITION TO ROOF HOOD AS NECCESSARY. PROVIDE NEW

MOTORIZED DAMPER IN DUCT

14. NEW OA DUCT UP TO ROOF MOUNTED ERV.

15. RELOCATE EXISTING ROOF DRAIN FOR NEW DUCTWORK AND ERV

UNIT. RECONNECT TO EXISTING STORM DRAIN PIPING.

T S

TS

SOUTH MECH.

PENTHOUSE

SOUTH STORAGE

(H W

S

(H W

R

(HWS)

(HWR)

REF-S

REF-L

MATCHLINE

(UH07-4)

(UH07-6)

CU-2

AHU-2

P R

O J E

C T

T

IT

L E

D R

A W

IN

G

T

IT

L E

PROJECT No.

DRAWING No.

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t

K e n o s h a W

I

C U s e rs

\J W ie d o ff \D o c u m e n ts

\K

K e n o s h a c o P

T F

H V

A C

I m p ro v e m e n ts

R J e ff .W ie d o ff S

D W

.r v t

/1

/2

:3

:1 P

M

M3.04

T H

IR

D

F L O

O R

S O

U T

H H

E A

T

IN

G N

E W

W O

R K

P L

A N

K E

N O

S H

A C

O U

N T

Y P

R E

-T R

IA

L

F A

C

IL

IT

Y

H V

A C

IM

P

R O

V E

M E

N T

S

K0450190

DESIGNED BY: JAW

DRAWN BY: JAW

CHECKED BY: NTP

DATE CHECKED: 02/20/26

P H

O N

E

.6

.1 w

.c la rk d ie tz

.c o m

K e n o sh a

W

I th

S tr e e t, th F lo o r

8' 16'4'0

THIRD FLOOR SOUTH HEATING NEW WORK PLAN

KEYNOTES (THIS SHEET)

1. PROVIDE NEW HWR CONTROL VALVES AND CONNECTION TO NEW

HEATING COIL.

2. PROVIDE NEW CONTROLS FOR EXISTING HOT WATER UNIT HEATER.

PROVIDE NEW 3 WAY-CONTROL VALVE. RECONNECT TO EXISTING

PIPING. SEE DETAIL AND CONTROL SCHEMATICS.

3. PROVIDE NEW REFRIGERANT PIPING CONNECTION TO NEW

COOLING COIL.

5. PROVIDE NEW SUCTION AND LIQUID REFRIGERANT PIPING. PROVIDE

NEW PIPING SUPPORTS.

7. PROVIDE NEW AIR-COOLED CONDENSING UNIT.INSTALL NEW ROOF

RAILS. SEE DETAIL 3/M5.02. PATCH EXISTING ROOF AROUND NEW

RAILS IN ACCORDANCE WITH ROOFING MANUFACTURER'S (DOWSIL)

REQUIREMENTS. PROVIDE STANDARD PATCHING WARRANTY.

8. PROVIDE NEW ISOLATION BALL VALVES ON EXISTING HWS/R PIPING.

9. PROVIDE NEW TEMPERATURE SENSOR AND ASSOCIATED WIRING

FOR HW UNIT HEATER.

10. SEAL WALL PENETRATION WEATHER TIGHT.

11. NEW AIR HANDLING UNIT. PROVIDE CONCRETE EQUIPMENT PAD.

SEE SCHEDULE.

12. HWS/R PIPING DOWN TO FLOOR BELOW TO REMAIN.

13. HWS/R PIPING ABOVE CEILING TO REMAIN.

14. NEW TEMPERATURE CONTROL PANEL. INSTALL NEW PANEL ON

EXISTING WALL. COORDINATE EXACT LOCATION WITH OTHER

EXISTING UTILITIES. PROVIDE NEW DATA CONNECTION TO EXISTING

KENOSHA COUNTY NETWORK. CONTRACTOR SHALL BE

RESPONSIBLE FOR COORDINATING NEW DATA LOCATION,

ASSOCIATED CABLING/CONDUIT. CONNECT TO EXISTING KENOSHA

COUNTY NETWORK PANEL.

KEYPLAN_________

N.T.S.

GENERAL NOTES

NO. DATE REVISION

1 03/11/26 ISSUED FOR BID

2 04/15/26 ADDENDUM #1

1. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND

REPLACING ALL CEILING TILES REQUIRED FOR DEMOLITION AND TO

INSTALL THEIR WORK.

2. PROVIDE NEW CEILING TILES WHERE EXISTING CEILING TILES ARE

DAMAGED DURING WORK.

3. PROVIDE NEW CEILING GRID WHERE REQUIRED TO ALLOW

DEMOLITION OF EXISTING DUCTWORK AND INSTALLATION OF

DUCTWORK.

4. CONTRACTORS SHALL BE RESPONBILE FOR TEMPORARILY

REMOVING LIGHT FIXTURES TO FACILITATE WORK AND REPLACING

LIGHT FIXTURES WHEN WORK IS COMPLETE.

5. EXISTING TRANSFER OPENINGS THROUGHOUT TO REMAIN.

6. CONTRACTOR IS RESPONSIBLE FOR REMOVING AND REPLACING

DRYWALL CEILING AS REQUIRED TO COMPLETE THEIR WORK.

REPLACEMENT OF CEILING SHALL MATCH EXISTING CONDITIONS AND

CONSTRUCTION TYPE. PATCH AND PAINT TO MATCH ADJACENT

SURFACES.

P R

O J E

C T

T

IT

L E

D R

A W

IN

G

T

IT

L E

PROJECT No.

DRAWING No.

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t

K e n o s h a W

I

C U s e rs

\J W ie d o ff \D o c u m e n ts

\K

K e n o s h a c o P

T F

H V

A C

I m p ro v e m e n ts

R J e ff .W ie d o ff S

D W

.r v t

/1

/2

:1

:5

A

M

M5.01

H V

A C

S C

H E

D U

L E

S K

E N

O S

H A

C O

U N

T Y

P R

E -T

R

IA

L F

A C

IL

IT

Y H

V A

C

IM

P R

O V

E M

E N

T S

K0450190

DESIGNED BY: JAW

DRAWN BY: JAW

CHECKED BY: NTP

DATE CHECKED: 02/20/26

P H

O N

E

.6

.1 w

.c la rk d ie tz

.c o m

K e n o s h a W

I th

S tr e e t, th F lo o r

VARIABLE AIR VOLUME TERMINAL UNIT (NO REHEAT)...

TAG LOCATION SERVICE

PRIMARY AIRFLOW

INLET SIZE

(DIA. IN.) SP (IN WC) NOTES

MAX

(CFM)

MIN

(CFM)

V05-1 204 204 560 450 8" 0.25

AIR COOLED CONDENSING UNIT

TAG

LOCATION

TYPE

NOMINAL

COOLING

CAP (TON)

FAN COMPRESSOR

SUMMER

AMBIENT

DBT (°F) EER

VOLT

(V) PH NOTESNAME

MOTOR

TYPE

REFRIGERANT

QTY

POWER

(HP) ECM TYPE

CU-2 SOUTH ROOF COOLING 40 6 7.30 No SCROLL

R-454-B OR

R-32 95.0 11.6 460 3

EXHAUST FAN SCHEDULE

TAG

LOCATION

TYPE ARRANGEMENT

FAN

VOLT

(V) PH NOTES MANUFACTURER MODELNAME NO.

DESIGN

AIRFLOW (CFM) ESP (IN W.G) RPM

DRIVE

TYPE

MOTOR

POWER (HP)

EF-4

VEHICLE SALLY

PORT

VEHICLE SALLY

PORT

INLINE HORIZONTAL 1600 0.53 1140 DIRECT 0.33 115 1 GREENHECK SQ-140

LOUVER SCHEDULE

TAG

LOCATION

SERVES QTY MATERIAL FINISH TYPE

DESIGN

AIRFLOW

(CFM)

FREE

AREA

FREE AREA

VELOCITY

DIMENSIONS

NOTES MANUFACTURER MODELNAME WIDTH HEIGHT

EL-1

VEHICLE SALLY

PORT

VEHICLE

SALLY PORT

1 ALUMINUM ENAMEL

DRAINABLE

HORIZONTAL

BLADE WALL

LOUVER

1600 1.6 SF 1000 FPM 1' - 0" 3' - 0" GREENHECK ESD-635

IL-1

VEHICLE SALLY

PORT

VEHICLE

SALLY PORT

1 ALUMINUM ENAMEL

DRAINABLE

HORIZONTAL

BLADE WALL

LOUVER

1600 3.2 SF 500 FPM 2' - 0" 3' - 0" GREENHECK ESD-635

GRILLES, REGISTERS AND DIFFUSERS SCHEDULE

TAG DESCRIPTION SYSTEM FACE SIZE

NECK BLADE DESIGN

MOUNTING MATERIAL

MAX N.C.

LEVEL NOTES MANUFACTURER MODELHEIGHT WIDTH

DEFLECTION

ANGLE

SINGLE DOUBLE

A1

SQUARE PLAQUE CEILING

DIFFUSER

SUPPLY 24X24 CEILING ALUMINUM 30 PRICE SPD

E1

LOUVERED SINGLE DEFLECTION

GRILLE

EXHAUST 14X28 28" 14" 45.0° DUCT ALUMINUM 35 PRICE 610Z

MOTORIZED DAMPER SCHEDULE

TAG

LOCATION

WIDTH HEIGHT

BLADE

CONFIGURATI

ON MOUNTING TYPENAME

MD-1

VEHICLE SALLY

PORT

12" 36" PARALLEL IN-SLEEVE TWO-POSITION

MD-2

VEHICLE SALLY

PORT

24" 36" PARALLEL IN-SLEEVE MODULATING

MD-3

SOUTH MECH.

ROOM

30" 30" PARALLEL IN-SLEEVE MODULATING

NOTES:

1. HEATING WATER SYSTEM WITH WITH 30% ETHYLENE GLYCOL.

2. PROVIDE WITH MANUFACTURER'S VFD ON BOTH FANS.

3. LARGEST SECTION MUST NOT EXCEED 36" TO FIT THROUGH 36" WIDE DOOR.

NOTES:

1. PROVIDE WITH MANUFACTURER'S VARIABLE SPEED SCROLL COMPRESSOR.

NOTES:

1. PROVIDE WITH MANUFACTURER'S VFD.

NO. DATE REVISION

1 03/11/26 ISSUED FOR BID

2 04/15/26 ADDENDUM #1

AIR HANDLING UNIT SCHEDULE

TAG

LOCATION SUPPLY FAN RETURN/EXHAUST FAN DX COOLING COIL HEATING PLANT HOT WATER HEATING COIL FILTER

VOLT

(V) PH NOTESNAME NO.

DESIGN

AIRFLOW

(CFM) ESP (IN W.G) RPM

DRIVE

TYPE

MOTOR DESIGN

AIRFLOW

(CFM) ESP (IN W.G) RPM

DRIVE

TYPE

MOTOR CAP AIRSIDE GLYCOL

CAP (BTU/H)

AIRSIDE

TYPEQTY POWER (HP) QTY

POWER

(HP)

TOTAL

(BTU/H)

SENSIBLE

(BTU/H)

EAT, DB

(°F)

EAT, WB

(°F) LAT DB (°F)

LAT, WB

(°F) TYPE % EWT, DB (°F)

LWT, DB

(°F)

AHU-2

SOUTH MECH.

ROOM

303 11745 2.00 2084 DIRECT 2 7.50 11745 2.00 2312 DIRECT 2 5.00 435000 368500 83.6 68.3 55.0 53.1 EG 30 590000 140.0 120.0 MERV-8 480 3

VARIABLE AIR VOLUME TERMINAL UNIT SCHEDULE

TAG LOCATION SERVICE

MAX AIR

VOL (CFM)

MIN AIR

VOL

(CFM)

HEATING

AIR VOL (

CFM)

NECK

SIZE (DIA.

IN.)

HEATING COIL

NOTES

CAP

(BTU/H)

AIRSIDE WATERSIDE

EAT, DB (°F) LAT, DB (°F) PD (IN W.G)

FLOW

(GPM)

EWT

(°F)

LWT

(°F)

PD

(FTH2O)

VC01-1 002 002, 003, 004, 005 400 400 400 8" 16090 55.0 92.0 0.20 3.3 140 129 0.3

VC01-2 008 008 500 500 500 10" 22500 55.0 96.5 0.14 1.6 140 125 3.1

VC01-3 012 013, 014, 015 270 270 270 6" 8800 55.0 85.0 0.22 0.8 140 116 0.2

VC01-4 011 011 450 450 450 8" 14700 55.0 85.1 0.24 2.3 140 125 0.2

VC01-5 012 006, 009, 012 430 270 270 8" 7200 55.0 85.2 0.15 0.5 140 101 4.8

VC01-6 016 016 210 210 210 6" 7060 55.0 86.0 0.12 0.6 140 115 0.2

VC01-7 017 017, 020, 021 610 550 550 12" 18600 55.0 85.1 0.19 1.7 140 116 0.3

VC03-1 104 101, 105 800 400 400 12" 14000 55.0 87.0 0.08 1.9 140 124 0.2

VC03-2 106 106 300 220 300 8" 14300 55.0 99.0 0.13 3.5 140 131 3.3

VC03-3 104 104 300 300 300 8" 9800 55.0 85.0 0.13 1.3 140 124 0.4

VC03-4 107 107 400 200 330 10" 19500 55.0 109.5 0.10 5.6 140 132 0.5

VC03-5 109 108, 109 400 200 225 8" 9800 55.0 95.2 0.20 1.7 140 127 0.1

VC03-6 113 113 400 200 330 10" 19500 55.0 109.5 0.10 5.6 140 132 0.1

VC03-7 112 112 350 300 300 8" 11400 55.0 90.0 0.16 1.8 140 126 0.7

VC03-8 114 114 500 250 400 10" 17000 55.0 94.2 0.14 1.9 140 120 0.5

VC03-9 115 115 600 300 410 10" 17800 55.0 95.0 0.18 2.0 140 121 0.6

VC03-10 116 117 230 230 230 6" 10000 55.0 95.0 0.13 1.3 140 123 0.5

VC03-11 117 117 1500 1500 1500 14" 48800 55.0 85.0 0.25 5.3 140 120 4.7

VC05-1 204 201, 202 900 900 900 12" 39000 55.0 95.0 0.20 7.7 140 129 1.3

VC05-2 204 205 450 225 225 8" 5000 55.0 78.0 0.13 0.5 140 115 0.7

VC05-3 204 206 400 200 200 10" 4840 55.0 86.0 0.05 0.5 140 110 0.7

VC05-4 204 207 400 200 200 10" 4840 55.0 86.0 0.05 0.5 140 110 0.7

VC05-5 210 209, 210 750 750 750 12" 29550 55.0 91.3 0.15 3.9 140 123 1.4

VC05-6 211 212 100 100 100 4" 3620 55.0 89.0 0.03 0.5 140 124 0.5

VC05-7 211 211 1000 1000 1000 12" 28100 55.0 80.0 0.23 2.8 140 118 0.4

ENERGY RECOVERY VENTILATOR SCHEDULE

TAG

LOCATION

TYPE

SUPPLY FAN EXHAUST FAN SUMMER DESIGN ENERGY RECOVERY

WINTER DESIGN ENERGY

RECOVERY

OA

FILTER

EFF

EXHAUS

T FILTER

EFF

UNIT

WEIGHT

(LB)

VOLT

(V) PH NOTES MANUFACTURER MODELNAME

DESIGN

AIRFLOW

(CFM) ESP (IN W.G)

MOTOR

DESIGN

AIRFLOW (CFM) ESP (IN W.G)

MOTOR OUTSIDE AIR OUTSIDE AIR

QTY POWER (HP) QTY POWER (HP) EAT, DB (°F) EAT, WB (°F) LAT, DB (°F) LAT, WB (°F) EAT, DB (°F) LAT, DB (°F)

ERV-2

PENTHOUSE

ROOF

OUTDOOR 5035 0.30 2 1.50 5035 1.00 2 2.00 92.0 77.9 82.4 72.1 -4.0 34.0 MERV-8 MERV-8 935 480 3 GREENHECK ECV-40-P-H

NOTES:

1. PROVIDE WITH MANUFACTURER'S VFDS.

2. PROVIDE ERV WITH BACNET CARD.

3. PROVIDE UNIT WITH MANUFACTURER'S FROST PROTECTION.

14⌀ 14⌀ 4-WAY

J

K

OS

T

TD

D

J

R

TC

F

F

F

F

D

F P

FR

CLNG

J

CLNG

F S

D

V

M

ES

ML

DC

CL

CR

MD

E

B

D

S

P

N

TV

N

XX-1

P

P

XX-1

XX-1

1P 1 POLE (2P, 3P, 4P, ETC.)

A AMPERE

AC ABOVE COUNTER

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

AF AMP FRAME

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHU AIR HANDLING UNIT

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

AMPL AMPLIFIER

ANNUN ANNUNCIATOR

APPROX APPROXIMATELY

AQ-STAT AQUASTAT

ARCH ARCHITECT, ARCHITECTURAL

AS AMP SWITCH

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BATT BATTERY

BD BOARD

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

C CONDUIT

CAB CABINET

CAT CATALOG

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

COMB COMBINATION

CMPR COMPRESSOR

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

CONV CONVECTOR

CP CIRCULATING PUMP

CRT CATHODE-RAY TUBE

CT CURRENT TRANSFORMER

CTR CENTER

CU COPPER

DCP DOMESTIC WATER CIRCULATING

PUMP

DEPT DEPARTMENT

DET DETAIL

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DPR DAMPER

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

ELU EMERGENCY LIGHTING UNIT

EM EMERGENCY

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EP ELECTRIC PNEUMATIC

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXH EXHAUST

EXP EXPLOSION PROOF

FA FIRE ALARM

FABP FIRE ALARM BOOSTER POWER

SUPPLY PANEL

FACP FIRE ALARM CONTROL PANEL

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FU FUSE

FUDS FUSED SAFETY DISCONNECT

SWITCH

GA GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT

INTERRUPTER

GFP GROUND FAULT PROTECTOR

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BD GYPSUM BOARD

HOA HANDS-OFF-AUTOMATIC SWITCH

HORIZ HORIZONTAL

HP HORSEPOWER

HPF HIGH POWER FACTOR

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

I/W INTERLOCK WITH

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LOC LOCATE OR LOCATION

LT LIGHT

ELECTRICAL ABBREVIATIONS

ELECTRICAL SYMBOL NOTES

EXIT LIGHTS. STEM INDICATES WALL MOUNTING. NO STEM INDICATES

CEILING MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S).

ARROW INDICATES DIRECTIONAL ARROW ON ILLUMINATED FACE(S). THE

CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. EXAMPLE: THE WALL

MOUNTED EXIT LIGHT TYPE "E1" WITH SINGLE FACE AND DIRECTIONAL

ARROW IS CONNECTED TO CIRCUIT 1.

DEVICES. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. THE SWITCH

DESIGNATION IS INDICATED BY A LOWER CASE LETTER. EXAMPLE: SPLIT

DUPLEX RECEPTACLE IS CONNECTED TO CIRCUIT 1 AND ONE RECEPTACLE

OUTLET IS CONTROLLED BY SWITCH "d".

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE

LETTER. EXAMPLE: SINGLE POLE SWITCH "d" TO CONTROL LIGHTING FIXTURES INDICATED BY "d".

WALL BOX DIMMER WITH SIZE AS INDICATED AT DEVICE. EXAMPLE: 600

WATT WALL BOX DIMMER TO CONTROL LIGHTING FIXTURES INDICATED

BY "e". SEE SPECIFICATIONS FOR WATTAGE IF NOT INDICATED.

SPECIAL CONNECTIONS. THE EQUIPMENT IS INDICATED BY A NUMBER IN A

CIRCLE. SEE THE MOTOR AND EQUIPMENT SCHEDULE FOR THE LOAD

DESCRIPTION AND TYPE OF CONNECTION. THE CIRCUIT DESIGNATION IS

INDICATED BY NUMBER(S) ADJACENT TO THE SYMBOL. EXAMPLE: EQUIPMENT

NO. ELEC-1; 1 PHASE CONNECTION TO CIRCUITS 2, 4.

MOTOR CONNECTIONS. THE MOTOR IS INDICATED BY A NUMBER

WITHIN OR CHARACTERS ADJACENT TO THE MOTOR SYMBOL.

SEE THE MOTOR AND EQUIPMENT SCHEDULE FOR THE MOTOR

DESCRIPTION AND ELECTRICAL REQUIREMENTS.

TRANSFORMERS. THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER "T". SEE THE TRANSFORMER

SCHEDULE OR THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER

DESCRIPTION AND REQUIREMENTS. EXAMPLE: TRANSFORMER TYPE "T1".

PANELBOARDS. PANELBOARD DOORS MAY BE SHOWN TO

INDICATE OPENING SIDE OF RECESSED PANELBOARDS. SEE

PANELBOARD IDENTIFICATION FOR DESIGNATION CODES.

CONDUIT SHOWN WITHOUT SLASH MARKS SHALL CONTAIN 1 # 12 CONDUCTOR

PER PHASE, NEUTRAL, AND GROUND IN 1/2" CONDUIT UNLESS SPECIFIC

EQUIPMENT REQUIRES A DIFFERENT SIZE.

CONDUIT SHOWN SHALL CONTAIN 1 # 10 CONDUCTOR PER PHASE IN

ELECTRICAL CODE SIZED MINIMUM CONDUIT UNLESS A CONDUCTOR AND

CONDUIT SIZE IS SHOWN ADJACENT.

HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE PANELBOARD

DESIGNATION IS SHOWN ADJACENT TO THE HOME RUN ARROW AS

A NUMERATOR AND THE CIRCUIT DESIGNATION IS SHOWN AS THE

DENOMINATOR. CIRCUIT BREAKER SIZES (AMPS/NUMBER OF

POLES) ARE SHOWN IN THE PANELBOARD SCHEDULE WITH THE

CORRESPONDING PANELBOARD AND CIRCUIT DESIGNATION.

EXAMPLE: HOME RUN TO PANELBOARD P4N-102; CIRCUITS 1, 3, 5.

ELECTRICAL LEGEND

LIGHTING SYMBOLS

FIRE ALARM HORN W/STROBE

FIRE ALARM BELL

FIRE ALARM BELL W/STROBE

FIRE ALARM CHIME W/STROBE

TIME CONTROL SWITCH

RELAY

SAFETY DISC. SW. (FUSED)

SAFETY DISC. SW. (NON-FUSED)

COMB. MOTOR STARTER (FUSED)

FLOOR JUNCTION BOX

JUNCTION BOX

MULTIOUTLET ASSEMBLY

RECEPT. ON CORD REEL

FLOOR DUPLEX RECEPT.

240V RECEPTACLE

FOURPLEX RECEPT. ON EMERG. CIRCUIT

FOURPLEX RECEPT.

DUPLEX RECEPT. ON EMERG. CIRCUIT

DUPLEX ISOLATED GROUND RECEPT.

SPLIT DUPLEX RECEPT.

DUPLEX RECEPT.

SINGLE RECEPT.

PUSH BUTTON

TIME DELAY SWITCH

TIMER SWITCH

OCCUPANCY SENSOR W/ MANUAL SWITCH

DIMMER SWITCH

SWITCH W/PILOT

KEYED SWITCH

4-WAY SWITCH

3-WAY SWITCH

SINGLE POLE SWITCH

PS - D2

KEYED NOTE (SEE SCHEDULE)

NUMBER OF SHEET WHERE DETAIL APPEARS

NUMBER OF DETAIL ON SHEET

REVISION NUMBER - SHOWN ON PLANS

ROOM NAME AND NUMBER

ITEM TO BE

REMOVED

AREA NOT IN

CONTRACT

d e

T1

FLOOR CLEARANCE AREA

CONDUIT IN CEILING, FLOOR OR WALL AS REQUIRED BY FIELD CONDITIONS

CONDUIT IN FLOOR

FIRE ALARM PULL STATION

FIRE ALARM DOOR HOLDER

FIRE ALARM DOOR CLOSER

FIRE ALARM SHUT DOWN RELAY

CEILING DATA OUTLET

FLOOR DATA OUTLET

# OF VOICE AND # OF DATA OUTLETS

P4N-102 1, 3, 5

EXISTING TO REMAIN

EXISTING TO BE REMOVED

NEW

GRAPHICAL REPRESENTATION OF PHASING, TYPICAL FOR ALL SYMBOLS.

CEILING DUPLEX RECEPT.

SPECIAL RECEPT.

CEILING JUNCTION BOX

FLOOR TELEPHONE OUTLET

GFI DUPLEX RECEPT. (FEED THROUGH)

GFI WEATHERPROOF RECEPT.

48"

GFI

GFI

WP

CLNG

ELEC-1

Room

FIRE ALARM SPEAKER W/STROBE

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MAX MAXIMUM

MAG.S MAGNETIC STARTER

M/C MOMENTARY CONTACT

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDC MAIN DISTRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SW

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOA MULTIOUTLET ASSEMBLY

MSP MOTOR STARTER PANELBOARD

MSBD MAIN SWITCHBOARD

MT MOUNT

MT.C EMPTY CONDUIT

MTS MANUAL TRANSFER SWITCH

MTR MOTOR, MOTORIZED

N.C. NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

N.O. NORMALLY OPEN

NPF NORMAL POWER FACTOR

NTS NOT TO SCALE

OH OVERHEAD

OL OVERLOADS

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PE PNEUMATIC ELECTRIC

PED PEDESTAL

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

PP POWER POLE

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QUAN QUANTITY

RCPT RECEPTACLE

REQD REQUIRED

RM ROOM

RSC RIGID STEEL CONDUIT

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SHT SHEET

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

S/S STOP/START PUSHBUTTONS

STA STATION

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TL TWIST LOCK

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TVTC TELEVISION TERMINAL CABINET

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UV ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VDT VIDEO DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WG WIRE GUARD

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

∠ ANGLE

@ AT

▲ DELTA

' FEET

" INCHES

# NUMBER

Ø PHASE

C CENTER LINE

P PLATE

EXIT LIGHT, WALL-MOUNTED,

SHADING AND ARROWS INDICATE

FACES AND DIRECTION

WALL-MOUNTED FIXTURES, TYPICAL

EXW1

LIGHTING FIXTURE TAG DESCRIPTORS:

TOP VALUE: FIXTURE TYPE ID.

BOTTOM VALUE, NUMBER: CIRCUIT NUMBER, REFER TO DRAWINGS FOR

PANEL.

BOTTOM VALUE, LOWERCASE LETTER: SWITCH DESIGNATION.

ABSENCE OF A SWITCH ID INDICATES FIXTURE IS CONTROLLED BY THE ONLY

SWITCH IN THE SPACE.

"x" IN PLACE OF THE SWITCH ID INDICATES NIGHT LIGHT, UNSWITCHED.

S3 1d

ELECTRIC STRIKE

MAGNETIC LOCK

COMBINATION LOCK

DOOR CONTACT

CARD READER

SECURITY KEYPAD

MOTION DETECTOR

NURSE CALL EMERG. STATION

NURSE CALL CODE BLUE STATION

NURSE CALL DUTY STATION

NURSE CALL STAFF STATION

NURSE CALL PATIENT STATION

NURSE CALL DOME LIGHT (1-COLOR)

TELEPHONE OUTLET

VOICE/DATA OUTLET

DOOR BELL

DOOR BUZZER

DOOR CHIME

DOOR SIGNAL

VOLUME CONTROL

MICROPHONE OUTLET

1V2D

CATV OUTLET

TV OUTLET

NURSE CALL DOME LIGHT (2-COLORS)

AUTO DOOR PUSH PAD

EMERGENCY LIGHTING UNIT, WALL-

MOUNTED, REMOTE BATTERY

EMERGENCY LIGHTING UNIT, WALL-

MOUNTED, INTEGRAL BATTERY

EMERGENCY LIGHTING UNIT, CEILING-

MOUNTED, INTEGRAL BATTERY

EMERGENCY LIGHTING UNIT, CEILING-

MOUNTED, REMOTE BATTERY

LIGHTING FIXTURES, TYPICAL,

RECTANGULAR

FILLED CIRCLES INDICATE RECESSED,

OPEN CIRCLES INDICATE SURFACE

DIAGONAL LINE INDICATES LENSED

OUTER DOTS INDICATE SUSPENDED

LIGHTING FIXTURES, TYPICAL, ROUND

CENTER DOT INDICATES PENDANT

DIAGONAL LINE INDICATES LENSED

CHEVRON INDICATES WALL WASH

STRIP FIXTURE

DIRECTIONAL LIGHT, TRACK, FLOOD

EXIT LIGHT, CEILING-MOUNTED,

SHADING AND ARROWS INDICATE

FACES AND DIRECTION

LINEAR LIGHT, TAPE LIGHT

EXIT/ELU COMBO

DIAGONAL HATCH INDICATES

LIGHT ON A CRITICAL CIRCUIT

SOLID HATCH INDICATES LIGHT ON AN

EMERGENCY OR LIFE SAFETY CIRCUIT

POLE/AREA LIGHTS

POST-TOP AREA LIGHT

BOLLARD LIGHT

SPRINKLER FLOW SWITCH

SPRINKLER VALVE TAMPER SWITCH

DUCT SMOKE DETECTOR

CEILING SMOKE DETECTOR

THERMAL DETECTOR

FIRE ALARM SYMBOLS

POWER SYMBOLS

DENOTES MOUNTING HEIGHT

MOTOR

UTILITY SERVICE POWER POLE

STATIC GROUND RECEPTACLE

SURGERY SERVICE COLUMN

POWER POLE (OPEN OFFICE STYLE)

IDENTITY

EXISTING TO REMAIN

TO BE REMOVED

CABLE TAP BOX

TRANSFORMER

BUS DUCT W/ PLUG IN DISCONNECT

T1

SYSTEMS SYMBOLS

PANELBOARD IDENTIFICATION

1. EQUIPMENT DESIGNATION:

L = LIGHTING

P = POWER

D = DISTRIBUTION

S = SWITCHBOARD

M = MOTOR CONTROL

CENTER

R = RELAY PANEL

2. VOLTAGE DESIGNATION:

1 = 120/240V - 1PH

2 = 240V - 3PH

3 = 208Y/120V - 3PH

4 = 480Y/277V - 3PH

5 = 120/208 - 1PH

6 = SPECIAL

3. SYSTEM DESIGNATION:

N = NORMAL

E = EMERGENCY

C = POWER CONDITIONED

U = UNINTERRUPTIBLE POWER

SOURCE

4. FLOOR

DESIGNATION:

B = BASEMENT

G = GROUND

1 = FIRST FLOOR

2 = SECOND FLOOR

ETC.

5. PANEL NO.

DESIGNATION:

01 = PANELBOARD #1

02 = PANELBOARD #2

03 = PANELBOARD #3

ETC.

P4N-102

1d

2, 4

ELECTRICAL GENERAL NOTES

1. CONDUCTORS OPERATING AT 50 VOLTS OR GREATER SHALL BE IN RACEWAY.

RACEWAY WITHIN THE STRUCTURE ABOVE THE FLOOR SLAB SHALL BE METAL.

RACEWAY BELOW THE FLOOR SLAB AND UNDERGROUND RACEWAY OUTSIDE

THE STRUCTURE SHALL BE PVC.

2. LOW VOLTAGE CABLES OR CONDUCTORS OPERATING AT LESS THAN 50 VOLTS

SHALL BE IN METAL RACEWAY WHERE INSTALLED WITHIN WALLS OR

INACCESSIBLE SPACES. LOW VOLTAGE CABLES MAY BE RUN IN CABLE TRAY

WHERE NOTED. LOW VOLTAGE CABLES MAY BE RUN IN CABLE SUPPORT HOOKS

ABOVE ACCESSIBLE CEILINGS WHERE NOTED. LOW VOLTAGE CABLE SHALL BE

PLENUM RATED IN PLENUM SPACES.

3. COORDINATE LOCATIONS OF DEVICES WITH ARCHITECTURAL ELEVATIONS AND

DETAILS. ARCHITECTURAL ELEVATIONS AND DETAILS TAKE PRECEDENCE OVER

LOCATIONS SHOWN ON ELECTRICAL DRAWINGS.

4. PROVIDE CABLE OR CONDUIT AND WIRE AS REQUIRED TO ACHIEVE CIRCUITING

SHOWN. SIZE CONDUCTORS PER NEC AMPACITY AND WIRE FILL CRITERIA.

PROVIDE DEDICATED NEUTRAL AND GROUND CONDUCTORS FOR CIRCUITING

,UNLESS NOTED OTHERWISE. INCREASE BRANCH CIRCUIT AND/OR FEEDER

CONDUCTORS INCLUDING EQUIPMENT GROUNDING CONDUCTORS

PROPORTIONALLY FOR NO MORE THAN 3% VOLTAGE DROP ON BRANCH

CIRCUITS AND 2% ON FEEDERS PER ENERGY CODE.

5. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO COORDINATE INSTALLATION

OF ELECTRICAL SYSTEMS AND THOSE REQUIRING ELECTRICAL CONNECTIONS

TO MAINTAIN NEC REQUIRED CLEARANCES, INCLUDED BY NOT LIMITED TO

AREAS ABOVE ACCESSIBLE CEILINGS.

6. COORDINATE WITH OTHER TRADES FOR PROPER INSTALLATION OF EQUIPMENT.

CONSULT THE DRAWINGS OF OTHER TRADES OR CRAFTS TO AVOID CONFLICTS

WITH EQUIPMENT, ETC. CONFLICTS SHALL BE RESOLVED PRIOR TO ROUGH-IN

AND AT NO ADDITIONAL COST TO THE OWNER.

7. LEAVE THE SITE CLEAN AND READY FOR OCCUPANCY. REMOVE DIRT, DEBRIS,

EMPTY CARTONS, TOOLS, CONDUIT AND WIRE SCRAPS AND MISCELLANEOUS

SPARE EQUIPMENT AND MATERIALS USED IN THIS DIVISION OF THE WORK

DURING CONSTRUCTION. COMPONENTS SHALL BE FREE OF DUST, GRIT AND

FOREIGN MATERIALS AND LEFT AS NEW BEFORE FINAL ACCEPTANCE OF WORK.

8. THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE

USED IN THIS SET OF DRAWINGS.

9. PERFORM WORK TO COMPLY WITH THE STANDARD PRACTICES FOR GOOD

WORKMANSHIP PUBLISHED BY NATIONAL ELECTRICAL CONTRACTORS

ASSOCIATION (NECA). COMPLY WITH THE LATEST ENFORCED EDITION OF THE

NATIONAL ELECTRICAL CODE (NEC), LOCAL CODES, AMENDMENTS, AND

ORDINANCES.

10. FIELD COORDINATE FINAL MECHANICAL AND EQUIPMENT LOCATIONS ALONG

WITH CONNECTION REQUIREMENTS AND CONTROL WIRING PRIOR TO ROUGH-IN.

ADJUST CORRESPONDING CIRCUIT BREAKER RATINGS AND BRANCH CIRCUITING

ACCORDINGLY.

11. ELECTRICAL WORK SHALL BE PERFORMED UNDER THE SUPERVISION OF A

LICENSED MASTER ELECTRICIAN. PROCURE PERMITS AND LICENSES AND PAY

FEES ASSOCIATED WITH THIS WORK.

12. MATERIALS FURNISHED FOR THIS PROJECT SHALL BE NEW, COMMERCIAL

GRADE, FREE OF DEFECTS, AND LISTED BY A NATIONALLY RECOGNIZED TESTING

LABORATORY UNO.

13. PROVIDE COMPLETE OPERATION & MAINTENANCE MANUAL INCLUDING

APPROVED SUBMITTAL DRAWINGS, WARRANTY INFORMATION FOR PRODUCT

SUPPLIED,AND MANUFACTURES OPERATION AND

MAINTENANCE INSTRUCTIONS.

14. THE CONTRACTOR IS RESPONSIBLE FOR MAKING FINAL WIRING TERMINATIONS

TO PRE-INSTALLED RECEPTACLES IN OFFICE FURNITURE. CONTRACTOR IS

RESPONSIBLE FOR WIRING AND INSTALLING VOICE/DATA DEVICES IN OFFICE

FURNITURE. COORDINATE PLACEMENT OF DEVICES WITH FURNITURE LAY-OUT.

15. SECURITY SYSTEM TO BE PROVIDED UNDER SEPARATE CONTRACT. IT IS THE

RESPONSIBILITY OF THIS CONTRACTOR TO PROVIDE CONDUIT PROVISIONS,

BACK BOXES, ROUGH-INS, SLEEVES AND POWER TO HEAD END EQUIPMENT FOR

EXACT REQUIREMENTS PRIOR TO START OF WORK.

16. CONDUIT AND WIRE SHALL NOT BE INSTALLED BELOW FLOOR SLAB UNLESS

INDICATED ON PLAN BY DASHED CONDUIT.

17. CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ELECTRICAL ITEMS SHOWN

ON DRAWINGS EXCEPT FOR ITEMS LISTED IN NOTE 'R' BELOW.

18. TV OUTLETS, VOLUME CONTROLS, NURSE CALL DOME LIGHTS, NURSE CALL

DEVICES, TELEPHONE OUTLETS, DATA OUTLETS, AND FIRE ALARM DEVICES

SHALL CONSIST OF A BACK BOX WTIH CONDUIT STUBBED ABOVE THE

ACCESSIBLE CEILING, SEE STUB UP DETAIL.VERIFY SIZE OF BACK BOX REQUIRED

WITH DEVICE TO BE INSTALLED. LOCATE BACK BOXES 6" FROM ADJACENT

POWER RECEPTACLE INTENDED FOR COMPUTER USE.

19. FURNISH AND INSTALL CONDUIT FROM BACK BOXES FOR THE FOLLOWING

DEVICES INTO THE ACCESSIBLE CEILING SPACE IN THE CORRIDOR, UNLESS

NOTED OTHERWISE:

1 / 2 " C T V O U T L E T S 1 / 2 " C V O L U M E C O N T R O L S

1/2"C DOOR SECURITY DEVICES (CARD READERS, DOOR STRIKES ETC..)

1 / 2 " C N U R S E C A L L D O M E L I G H T S 3 / 4 " C N U R S E C A L L D E V I C E S 3 / 4 " C T E L E P H O N E O U T L E T S

3 / 4 " C I N F O R M AT I O N O U T L E T S

3 / 4 " C F I R E A L A R M D E V I C E S

PR

O

JE

C

T

TI

TL

E

D R

AW

IN

G T

IT

LE

PROJECT No.

DRAWING No.

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING

6t h St re et

Ke no sh a, W I 5

C :\U se rs

\jr f\D oc um en ts

\K

Ke n o sh a co

P

TF

H

VA

C Im pr o v em en ts R

_j on .fu lle nk a m p.

rv t

4 /

/2

9:

:1

PM

E0.00

EL

EC

TR

IC

AL

G

EN

ER

AL

N

O

TE

S, LE

G

EN

D , A

N D

A

BB

R

EV

IA

TI

O N

S

KE

N O

SH

A

C O

U N

TY

P

R E-

TR

IA

L

FA

C

IL

IT

Y

H

VA

C

IM

PR

O

VE

M

EN

TS

K0450190

PH

O

N E

: 2

.6

.1 ww w.

cla rk di et z.

co m Ke no sh a, W

I 5 th S tre et

, 6 th

F lo or

NO. DATE REVISION

1 03/11/26 ISSUED FOR BID

2 04/15/26 ADDENDUM #1

GENERAL NOTES

1. MODIFY EXISTING LIGHTNING PROTECTION SYSTEM TO ALLOW FOR REMOVAL AND

REINSTALLATION OF ROOF-TOP UNITS AND FANS INDICATED AS BEING REPLACED ON THE

DRAWINGS.

2. THE MODIFIED LIGHTNING PROTECTION SYSTEM SHALL BEAR THE UL MASTER LABEL FOR

PROTECTION OF THE STRUCTURE. SEE SPECIFICATION SECTION 26 41 00 FOR ADDITIONAL

INFORMATION.

3. ALL LIGHTNING PROTECTION SYSTEM WORK SHALL BE COMPLETED BY AN AUTHORIZED

INSTALLER WITH MINIMUM OF THREE YEARS DOCUMENTED EXPERIENCE AND CERTIFIED BY

LIGHTNING PROTECTION INSTITUTE.

4. PERFORM ALL WORK IN ACCORDANCE WITH NFPA 480.

5. PERFORM ALL WORK IN ACCORDANCE WITH UL 96A AND FURNISH MASTER LABEL.

LIGHTNING PROTECTION SYSTEM

SOUTH MECH.

PENTHOUSE

SOUTH STORAGE

1 CU-2

MATCHLINE

5 3EHS

2 AHU-2(S)

3 AHU-2(R)

4 ERV-1

6 3ELS

P R

O J E

C T

T

IT

L E

D R

A W

IN

G

T

IT

L E

PROJECT No.

DRAWING No.

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t

K e n o s h a W

I

C U s e rs

\J W ie d o ff \D o c u m e n ts

\K

K e n o s h a c o P

T F

H V

A C

I m p ro v e m e n ts

R J e ff .W ie d o ff S

D W

.r v t

/1

/2

:3

:0 P

M

E2.02

T H

IR

D

F L

O O

R S

O U

T H

E L E

C T

R

IC

A L

N E

W W

O R

K P

L A

N

K E

N O

S H

A C

O U

N T

Y P

R E

-T R

IA

L

F A

C

IL

IT

Y

H V

A C

IM

P

R O

V E

M E

N T

S

K0450190

P H

O N

E

.6

.1 w

.c la rk d ie tz

.c o m

K e n o sh a

W

I th

S tr e e t, th F lo o r

8' 16'4'0

THIRD FLOOR SOUTH ELECTRICAL NEW WORK PLAN

KEYNOTES (THIS SHEET)

1. PROVIDE ELECTRICAL CONNECTION TO NEW AIR COOLED CONDENSING UNIT AND

MANUFACTURER PROVIDED DISCONNECT SWITCH. PROVIDE FEEDER CONDUCTORS FROM

EXISTING PANEL 1HS, IN EXISTING CONUIT AS INDICATED ON EQUIPMENT CONNECTION

SCHEDULE (PROVIDE NEW CONDUIT AS REQUIRED).

2. PROVIDE ELECTRICAL CONNECTION TO NEW AIR HANDLING UNIT SUPPLY FANS AND

MANUFACTURER PROVIDED VFD'S. PROVIDE FUSIBLE DISCONNECT SWITCH. PROVIDE

FEEDER CONDUCTORS AND CONDUIT FROM EXISTING PANEL 3EHS AS INDICATED ON

EQUIPMENT CONNECTION SCHEDULE.

3. PROVIDE ELECTRICAL CONNECTION TO NEW AIR HANDLING UNIT RETURN FANS AND

MANUFACTURER PROVIDED VFD'S. PROVIDE FUSIBLE DISCONNECT SWITCH. PROVIDE

FEEDER CONDUUCTORS AND CONDUIT FROM EXISTING PANEL 3EHS AS INDICATED ON

EQUIPMENT CONNECTION SCHEDULE.

4. PROVIDE ELECTRICAL CONNECTION TO NEW ROOF MOUNTED ENERGY RECOVERY

VENTILATOR AND MANUFACTURER PROVIDED VFD'S. PROVIDE FUSIBLE DISCONNECT

SWITCH NEAR UNIT. PROVIDE FEEDER CONDUCTORS FROM EXISTING PANEL 3EHS, IN

EXISTING CONDUIT AS INDICATED ON EQUIPMENT CONNECTION SCHEDULE (PROVIDE NEW

CONDUIT AS REQUIRED).

5. EXISTING 277/480V PANEL 3EHS.

6. EXISTING 120/208V PANEL 3ELS.

7. PROVIDE ELECTRICAL CONNECTION TO NEW TEMPERATURE CONTROL PANEL. PROVIDE

FEEDER CONDUCTORS AND CONDUIT FROM EXISTING PANEL 3ELS, AS INDICATED ON

EQUIPMENT CONNECTION SCHEDULE. USE SPARE 20A/1P CIRCUIT BREAKER IN EXISTING

PANEL 3ELS.

GENERAL NOTES

1. SEE E0.00 FOR ELECTRICAL GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. MODIFY EXISTING LIGHTNING PROTECTION SYSTEM TO ALLOW FOR REMOVAL AND

REINSTALLATION OF ROOF-TOP UNITS INDICATED AS BEING REPLACED ON THE DRAWINGS.

DISCONNECT LIGHTNING PROTECTION SYSTEM CABLES AND TERMINALS FROM EXISTING

EQUIPMENT FOR REMOVAL OF EQUIPMENT. AFTER NEW EQUIPMENT HAS BEEN INSTALLED

RECONNECT LIGHTNING PROTECTION SYSTEM CABLES AND TERMINALS TO NEW

EQUIPMENT.

KEYPLAN_________

N.T.S.

NO. DATE REVISION

1 03/11/26 ISSUED FOR BID

2 04/15/26 ADDENDUM #1

P R

O J E

C T

T

IT

L E

D R

A W

IN

G

T

IT

L E

PROJECT No.

DRAWING No.

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING th S tr e e t

K e n o s h a W

I

C U s e rs

\J W ie d o ff \D o c u m e n ts

\K

K e n o s h a c o P

T F

H V

A C

I m p ro v e m e n ts

R J e ff .W ie d o ff S

D W

.r v t

/1

/2

:3

:0 P

M

E4.01

E L E

C T

R

IC

A L

S C

H E

D U

L E

S K

E N

O S

H A

C O

U N

T Y

P R

E -T

R

IA

L F

A C

IL

IT

Y H

V A

C

IM

P R

O V

E M

E N

T S

K0450190

P H

O N

E

.6

.1 w

.c la rk d ie tz

.c o m

K e n o sh a

W

I th

S tr e e t, th F lo o r

NO. DATE REVISION

1 03/11/26 ISSUED FOR BID

2 04/15/26 ADDENDUM #1

Clark Dietz, Inc. HVAC Insulation

County of Kenosha – Pre-Trial Facility HVAC Improvements 23 07 00 - 1

SECTION 230700

HVAC INSULATION

PART 1 GENERAL

1.1 SUMMARY

A. Section Includes:

1. HVAC piping insulation, jackets and accessories.

2. HVAC ductwork insulation, jackets, and accessories.

1.2 REFERENCES

A. ASTM International:

1. ASTM C450 - Standard Practice for Fabrication of Thermal Insulating Fitting Covers for NPS Piping, and

Vessel Lagging.

2. ASTM C534 - Standard Specification for Preformed Flexible Elastomeric Cellular Thermal Insulation in

Sheet and Tubular Form.

3. ASTM C585 - Standard Practice for Inner and Outer Diameters of Rigid Thermal Insulation for Nominal

Sizes of Pipe and Tubing (NPS System).

4. ASTM C795 - Standard Specification for Thermal Insulation for Use in Contact with Austenitic Stainless

Steel.

5. ASTM C1136 - Standard Specification for Flexible, Low Permeance Vapor Retarders for Thermal

Insulation.

6. ASTM C1290 - Standard Specification for Flexible Fibrous Glass Blanket Insulation Used to Externally

Insulate HVAC Ducts.

7. ASTM D1785 - Standard Specification for Rigid Poly (Vinyl Chloride) (PVC) Compounds and Chlorinated

Poly (Vinyl Chloride) (CPVC) Compounds.

8. ASTM E96/E96M - Standard Test Methods for Water Vapor Transmission of Materials.

9. ASTM E162 - Standard Test Method for Surface Flammability of Materials Using a Radiant Heat Energy

Source.

B. Sheet Metal and Air Conditioning Contractors’:

1. SMACNA - HVAC Duct Construction Standard - Metal and Flexible.

1.3 SUBMITTALS

A. Product Data: Submit product description, thermal characteristics and list of materials and thickness for each service, and location.

B. Manufacturer's Installation Instructions: Submit manufacturers published literature indicating proper installation procedures.

1.4 QUALITY ASSURANCE

A. Test pipe insulation for maximum flame spread index of 25 and maximum smoke developed index of not exceeding 50 in accordance with ASTM E84.

B. Pipe insulation manufactured in accordance with ASTM C585 for inner and outer diameters.

C. Factory fabricated fitting covers manufactured in accordance with ASTM C450.

County of Kenosha – Pre-Trial Facility HVAC Improvements 23 07 00 - 2

D. Duct insulation, Coverings, and Linings: Maximum 25/50 flame spread/smoke developed index, when tested in accordance with ASTM E84, using specimen procedures and mounting procedures of ASTM

E 2231.

1.5 DELIVERY, STORAGE, AND HANDLING

A. Accept materials on site in original factory packaging, labeled with manufacturer's identification, including product density and thickness.

B. Protect insulation from weather and construction traffic, dirt, water, chemical, and damage, by storing in original wrapping.

1.6 ENVIRONMENTAL REQUIREMENTS

A. Install insulation only when ambient temperature and humidity conditions are within range recommended by manufacturer.

B. Maintain temperature before, during, and after installation for minimum period of 24 hours.

PART 2 PRODUCTS

2.1 MANUFACTURER

A. Manufacturers for Glass Fiber and Mineral Fiber Insulation Products:

1. CertainTeed.

2. Knauf.

3. Johns Manville.

4. Owens-Corning.

B. Manufacturers for Closed Cell Elastomeric Insulation Products:

1. Aeroflex. Aerocell.

2. Armacell, LLC. Armaflex.

3. Nomaco. K-flex.

2.2 PIPE INSULATION

A. TYPE P-1: ASTM C547, molded glass fiber pipe insulation.

1. Thermal Conductivity: 0.23 at 75 degrees F.

2. Operating Temperature Range: 0 to 850 degrees F.

3. Vapor Barrier Jacket: ASTM C1136, Type I, factory applied reinforced foil kraft with self-sealing adhesive joints.

4. Jacket Temperature Limit: minus 20 to 150 degrees F.

B. TYPE P-2: ASTM C612; semi-rigid, fibrous glass board noncombustible, end grain adhered to jacket.

Conform to ASTM C795 for application on Austenitic stainless steel.

1. Thermal Conductivity: 0.27 at 75 degrees F.

2. Operating Temperature Range: 0 to 650 degrees F.

3. Vapor Barrier Jacket: ASTM C1136, Type II, factory applied reinforced foil kraft with self-sealing adhesive joints.

4. Jacket Temperature Limit: minus 20 to 150 degrees F.

C. TYPE P-5: ASTM C534; Type I, flexible, closed cell elastomeric insulation, tubular.

County of Kenosha – Pre-Trial Facility HVAC Improvements 23 07 00 - 3

1. Thermal Conductivity: 0.27 at 75 degrees F.

2. Operating Temperature Range: Range: Minus 70 to 180 degrees F.

2.3 PIPE INSULATION JACKETS

A. PVC Plastic Pipe Jacket:

1. Product Description: ASTM D1785, One piece molded type fitting covers and sheet material, off-white color.

2. Thickness: 30 mil.

3. Connections: Brush on welding adhesive.

B. Aluminum Pipe Jacket:

1. ASTM B209.

2. Thickness: 0.016 inch thick sheet.

3. Finish: Smooth.

4. Joining: Longitudinal slip joints and 2 inch laps.

5. Fittings: 0.016 inch thick die shaped fitting covers with factory attached protective liner.

6. Metal Jacket Bands: 3/8 inch wide; 0.015 inch thick aluminum.

2.4 PIPE INSULATION ACCESSORIES

A. Vapor Retarder Lap Adhesive: Compatible with insulation.

B. Covering Adhesive Mastic: Compatible with insulation.

C. Piping 1-1/2 inches diameter and smaller: Galvanized steel insulation protection shield. MSS SP-69, Type

40. Length: Based on pipe size and insulation thickness.

D. Piping 2 inches diameter and larger: Wood insulation saddle, hard maple. Inserts length: not less than 6 inches long, matching thickness and contour of adjoining insulation.

E. Adhesives: Compatible with insulation.

2.5 DUCTWORK INSULATION

A. TYPE D-1: ASTM C1290, flexible glass fiber, commercial grade with factory applied reinforced aluminum foil jacket meeting ASTM C1136, Type II.

1. Thermal Conductivity: 0.27 at 75 degrees F.

2. Maximum Operating Temperature: 250 degrees F.

3. Density: 0.75 pound per cubic foot.

B. TYPE D-2: ASTM C612, Type IA or IB, rigid glass fiber, with factory applied reinforced aluminum foil facing meeting ASTM C1136, Type II.

1. Thermal Conductivity: 0.23 at 75 degrees F.

2. Density: 3.0 pound per cubic foot.

2.6 DUCTWORK INSULATION JACKETS

A. Aluminum Duct Jacket:

1. ASTM B209.

2. Thickness: 0.016 inch thick sheet.

3. Finish: Smooth.

4. Joining: Longitudinal slip joints and 2 inch laps.

County of Kenosha – Pre-Trial Facility HVAC Improvements 23 07 00 - 4

5. Fittings: 0.016 inch thick die shaped fitting covers with factory attached protective liner.

6. Metal Jacket Bands: 3/8 inch wide; 0.015 inch thick aluminum.

B. Aluminum Duct Jacket Systems:

1. Self-adhesive material with aluminum finish surface, color to be selected by owner.

2. Tear strength of 8.5 lbs or greater meeting ASTM D624.

3. Thickness: 6 mils sheet.

4. Finish: Smooth.

5. Non permeable with vapor barrier.

6. Mold resistant.

2.7 DUCTWORK INSULATION ACCESSORIES

A. Vapor Retarder Tape:

1. Kraft paper reinforced with glass fiber yarn and bonded to aluminized film, with pressure sensitive rubber based adhesive.

B. Vapor Retarder Lap Adhesive: Compatible with insulation.

C. Adhesive: Waterproof, ASTM E162 fire-retardant type.

D. Liner Fasteners: Galvanized steel, self-adhesive pad head.

E. Tie Wire: 0.048 inch stainless steel with twisted ends on maximum 12 inch centers.

F. Lagging Adhesive: Fire retardant type with maximum 25/450 flame spread/smoke developed index when tested in accordance with ASTM E84.

G. Impale Anchors: Galvanized steel, 12 gage self-adhesive pad.

H. Adhesives: Compatible with insulation.

PART 3 EXECUTION

3.1 EXAMINATION

A. Verify piping, equipment and ductwork has been tested before applying insulation materials.

B. Verify surfaces are clean and dry, with foreign material removed.

3.2 INSTALLATION - PIPING SYSTEMS

A. Piping Exposed to View in Finished Spaces: Locate insulation and cover seams in least visible locations.

B. Continue insulation through penetrations of building assemblies or portions of assemblies having fire resistance rating of one hour or less. Provide intumescent firestopping when continuing insulation through assembly. Finish at supports, protrusions, and interruptions. Piping Systems Conveying Fluids Below

Ambient Temperature:

1. Insulate entire system including fittings, valves, unions, flanges, strainers, flexible connections, pump bodies, and expansion joints.

County of Kenosha – Pre-Trial Facility HVAC Improvements 23 07 00 - 5

2. Furnish factory-applied or field-applied vapor retarder jackets. Secure factory-applied jackets with pressure sensitive adhesive self-sealing longitudinal laps and butt strips. Secure field-applied jackets with outward clinch expanding staples and seal staple penetrations with vapor retarder mastic.

3. Insulate fittings, joints, and valves with molded insulation of like material and thickness as adjacent pipe. Finish with glass cloth and vapor retarder adhesive or PVC fitting covers.

C. Glass Fiber Board Insulation:

1. Apply insulation close to equipment by grooving, scoring, and beveling insulation. Fasten insulation to equipment with studs, pins, clips, adhesive, wires, or bands.

2. Fill joints, cracks, seams, and depressions with bedding compound to form smooth surface. On cold equipment, use vapor retarder cement.

3. Cover wire mesh or bands with cement to a thickness to remove surface irregularities.

D. Inserts and Shields:

1. Piping 1-1/2 inches Diameter and Smaller: Install galvanized steel shield between pipe hanger and insulation.

2. Piping 2 inches Diameter and Larger: Install insert between support shield and piping and under finish jacket.

a. Insert Configuration: Minimum 6 inches long, of thickness and contour matching adjoining insulation; may be factory fabricated.

b. Insert Material: Compression resistant insulating material suitable for planned temperature range and service.

3. Piping Supported by Roller Type Pipe Hangers: Install galvanized steel shield between roller and inserts.

E. Insulation Terminating Points:

1. Coil Branch Piping 1 inch and Smaller: Terminate hot water piping at union upstream of the coil control valve.

2. Hot Water Coil Branch Piping: Insulate hot water piping and associated components up to coil connection.

3. Condensate Piping: Insulate entire piping system…