260819_19A Mott Street_Permit Set.pdf
PDF 981 KB Posted
- Attached to
- 19A Mott Street General Contractor Bid Form
- Solicitation number
- 2138330
- Issued by
- New York County, Nissequogue Village, New York
About this file
This is a permit set and project documentation file for a general contractor bid opportunity in New York involving renovation work at 19A Mott Street. The project requires submission of a Guaranteed Maximum Price (GMP) as the Base Bid Sum, with a mandatory site walkthrough scheduled for August 25, 2026, and a proposal submission deadline of September 10, 2026. Questions from bidders must be submitted by September 4, 2026, via email to the Architect, with responses distributed to all bidders. No identical or substantially similar contracts have been awarded within the past five years.
The contract will utilize a modified AIA Document A102-2007 Standard Form of Agreement Between Owner and Contractor structured as Cost of Work Plus a Fee with a Guaranteed Maximum Price. Minority and Women Business Enterprise (MWBE) contracting goals have been established at 15.00% for Minority Business Enterprises (MBE) and 15.00% for Women Business Enterprises (WBE). The permit set documentation provides the detailed technical specifications, drawings, and requirements necessary for bidders to develop accurate pricing and project scope understanding.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 260819_19A Mott Street_Bid Form_Project Manual.pdf | ||
| 260819_19A Mott Street_Bid Set.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A/E
AB
ACOUS
ACS, PNL, AP
AESS
AFF
ADDL
ADJ
ALT
ALUM
ARCH
BLDG
BLKG
BOS
BOD
B.O.
B/S
BTWN
BYND
C
CAB
CB
CG
CEM
CER
CHAN
CJ
CLG
CLR
CMPST
CMU
COL
CONC
CONT
CORR
CSMT
CT
CTR
DBL
DEG
DEMO
DEPT
DET
DF
DIA
DAMP
DN
DWG
E
EA
EFS
EG
EL
ELEC
ELEV
EMER
ENCL
ENGR
ENTR
EOS
EPDM
EQ
EQUIP
EXT
FA
FD
FEC
FE
FHC
FIN
FLR
FLUOR
FOC
FOF
FOM
FOS
FSTP
FT
FTG
FURN
FURR
GAVL
GEN
GL
GWB
GYP
HCD
HDWD
HGT
HM
HORIZ
HR
HTR
HVAC
IN
INSUL
INT
JAN
JT
L
LAM
LAV
LD
Architect/Engineer Anchor Bolt Acoustical Access Panel Architecturally Exposed Structural Steel Above Finish Floor Additional Adjustable, Adjacent, Adjoining Alternate, Altitude Aluminum Architect
Building Blocking Bottom of Steel Basis of Design Bottom of Both Sides Between Beyond
Course(s) Cabinet Chilled Beam Corner Guard Cement Ceramic Channel Construction Joint Ceiling Clear Composite Concrete Masonry Unit Column Concrete Continuous Corridor Casement Ceramic Tile Center, Contour
Double Degree Demolition Department Detail Drinking Fountain Diameter Damproofing Down Drawing
East Each Exterior Finish System Exhaust Grille Elevation Electric Elevator Emergency Enclosure Engineer Entrance Edge of Slab Ethylene Proplene Diene Monomer Equal Equipment Exterior
Fire Alarm Floor Drain Fire Extinguisher Cabinet Fire Extinguisher Fire Hose Cabinet Finished Floor or Flooring Fluorescent Face of Concrete Face of Finish
Face of Masonry Face of Stud Firestopping Foot or Feet Footing Furniture Furring
Galvanized Generator Glass Gypsum Wall Board Gypsum
Handicapped Door Operator Hardwood Height Hollow Metal Horizontal Hour Heater Heating, Ventilation, Air Conditioning
Inch or Inches Insulation Interior
Janitor Joint
Left Lamination Lavatory Linear Diffuser
LF
LG
LH
LHR
LT
LTG
LVT
MATL
MAX
MECH
MEP
MIN
MISC
MO
MTD
MTL
N
NA
NIC
NO
NOM
NTS
OC
OFCI
OFF
OPNG
OPP
PART
PC
PERF
PGWB
PL
PLAM
PLAS
PLYWD
PNL
PNT
PTD
PR
PRCST
PREFAB
QTY
R
RAD
RB
RCP
RD
REC
REF
REG
REINF
REQ
RH
RHR
RM
RO
RV
S
SAF
SC
SCHED
SECT
SGL
SIM
SP
SP_EX
SPEC
SS
STD
STL
STOR
STRUC
SUSP
T
TOB
TOC
TEL
TEMP
TOF
TOFF
THRESH
THRU
TOL
TOS
TYP
UNEX
UNFIN
UON
UNO
VB
VCT
VERT
VEST
VIF
VNR
VR
W W/ W/O
WD
WT
WP
Linear Foot Linear Grille Left Hand Left Hand Reverse Light Lighting Luxury Vinyl Tile
Material Maximum Mechanical Mechanical, Electrical, Plumbing Minimum Miscellaneous Masonry Opening Mounted Metal
North Not Applicable Not in Contract Number Nominal Not to Scale
On Center Owner Furnished, GC Installed Office Opening Opposite
Particle or Partial Precast Perforated Pointed Gypsum Wall Board Plate Plastic Laminate Plaster Plywood Panel Paint Painted Pair Precast Prefabricated
Quantity
Riser Radius Rubber Base Reflected Ceiling Plan Roof Drain Recessed Reference Register Reinforce or Reinforcing Required Right Hand Right Hand Reverse Room Rough Opening Roof Vent
South Sound Absorptive Finish Solid Core Schedule or Scheduled Section Single Similar Speaker Exterior Speaker Specification Stainless Steel Standard Steel Storage Structural Suspended
Tread Top of Beam Top of Concrete Telephone Temporary Top of Footing Top of Finishd Floor Threshold Through Tolerance Top of Slab or Top of Steel Typical
Unexcavated Unfinished Unless Otherwise Noted Unless Noted Otherwise
Vinyl Base Vinyl Composite Tile Vertical Vestibule Verify in Field Veneer Vapor Retarder
West With Without Wood Weight Waterproofing
85.83' 26.08'
26.50'
MOSCO ST
M O
TT ST
WORK UNDER THIS
APPLICATION TO BE
PERFORMED IN THIS AREA
OF THE BUILDING ONLY
X
AX.XX
X
AX.XX
ROOM
AX.XX
P0
0' - 00"
SLOPE
BUILDING SECTION
PLAN/SECTION DETAIL
ROOM NUMBER
DOOR NUMBER
INTERIOR ELEVATION
PARTITION TYPE
CEILING HEIGHT
INDICATED SLOPED
SURFACE
REVISION MARKER
REVISION CLOUD
ALIGN
ALIGN
CENTEREDCL
CONSULTANT
CERTIFICATION
SHEET TITLE:
PROJECT #:
DATE:
SCALE:
REVISION HISTORY
s p a c e d a g e n c y
© Spaced Agency PLLC a r c h i t e c t u r e
867 BOYLSTON ST, 5TH FL #1183
BOSTON, MA 02116
TEL: 646-580-2256
SHEET #:
DRAWN BY: TK
PERMIT DRAWINGS
As indicated
A M
O T
S
R E
E T
N ew
Y or k, N
Y
T-010.00
COVER SHEET
19A MOTT ST.
PERMIT SET
DATE ISSUED: AUGUST 19, 2026
N
NTS
BLOCK: 164
LOT: 46
ZONE: C6-1
MAP: 12D
CONSTRUCTION CLASS: 3 NON-FIREPROOF
HEIGHT: FIVE STORIES
EXISTING OCCUPANCY: STORES
PROPOSED OCCUPANCY: STORES
WORK UNDER: 1968 BUILDING CODE
LANDMARK STAUS: -
CHINATOWN AND LITTLE ITALY HISTORIC DISTRICT
DOB JOB #: M01442993-I1
CLIENT
WELCOME TO CHINATOWN INC.
115 BOWERY, GROUND FL
NEW YORK, NY 10002
ARCHITECT
SPACED AGENCY PLLC
D/B/A SPACED AGENCY ARCHITECTURE
867 BOYLSTON ST, 5TH FL #1183
BOSTON, MA 02116
TEL: 646-580-2256
CODE CONSULTANT + EXPEDITOR
J. CALLAHAN CONSULTING
299 BROADWAY, SUITE 1420
NEW YORK, NY 10007
TEL: 212-766-2115
NEW YORK, NY 10013
S Y M B O L SA B B R E V I A T I O N S
P L O T P L A N
P R O J E C T
D R A W I N G I N D E X
G E N E R A L N O T E S
P R O J E C T T E A M
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
SCOPE OF WORK: WORK TO INCLUDE RENOVATION OF EXISTING STOREFRONT AND INTERIOR
COMMERCIAL SPACE ON THE 001 FLOOR, STORE UNIT A. NO CHANGE IN USE, OCCUPANCY, OR EGRESS
UNDER THIS APPLICATION.
ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE NEW YORK CITY BUILDING CODE, FIRE DEPARTMENT REGULATIONS, UTILITY COMPANY REQUIREMENTS, AND THE BEST TRADE POLICIES.
BEFORE COMMENCING WORK, THE CONTRACTOR SHALL FILE ALL REQUIRED CERTIFICATES OF INSURANCE WITH THE DEPARTMENT OF BUILDINGS, OBTAIN ALL REQUIRED PERMITS, AND PAY ALL FEES REQUIRED BY
GOVERNING NEW YORK CITY AGENCIES.
THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS IN THE FIELD PRIOR TO COMMENCING WORK, AND SHALL REPORT ANY DISREPANCIES BETWEEN DRAWING AND FIELD CONDITIONS TO THE ARCHITECT.
CONSULTANT DRAWINGS ARE SUPPLEMENTAL TO THE ARCHITECTURAL DRAWINGS. IT IS THE
RESPONSIBILITY OF THE GENERAL CONTRACTOR TO CROSS CHECK WITH ARCHITECTURAL DRAWINGS PRIOR TO THE ORDERING AND INSTALLATION OF ANY STRUCTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL WORK. ANY DISCREPANCIES BETWEEN THE ARCHITECTURAL AND CONSULTING ENGINEERS' DRAWINGS SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION FOR IMMEDIATE CLARIFICATION.
ALL MANUFACTURED ARTICLES, MATERIALS, AND EQUIPMENT SHALL BE APPLIED, INSTALLED, CONNECTED, ERECTED, USED, CLEANED, AND CONDITIONED IN ACCORDANCE WITH THE MANUFACTURERS' WRITTEN
SPECIFICATIONS OR INSTRUCTIONS.
MINOR DETAILS NOT USUALLY SHOWN OR SPECIFIED, BUT NECESSARY FOR PROPER CONSTRUCTION OF ANY PART OF THE WORK SHALL BE INCLUDED AS IF THEY WERE INDICATED IN THE DRAWINGS.
THE CONTRACTOR SHALL COORDINATE ALL WORK PROCEDURES WITH REQUIREMENTS OF LOCAL
AUTHORITIES AND BUILDING MANAGEMENT.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF ALL CONDITIONS AND MATERIALS WITHIN THE PROPOSED CONSTRUCTION AREA. THE CONTRACTOR SHALL DESIGN AND INSTALL ADEQUATE SHORING AND BRACING FOR ALL STRUCTURAL OR REMOVAL TASKS. THE CONTRACTOR SHALL HAVE THE SOLE RESPONSIBILITY FOR ANY DAMAGE OR INJURIES CAUSED BY OR DURING THE EXECUTION OF THE
WORK.
THE CONTRACTOR SHALL LAY OUT THEIR OWN WORK, AND SHALL PROVIDE ALL DIMENSIONS REQUIRED
FOR OTHER TRADES (PLUMBING, ELECTRICAL, ETC.).
PLUMBING AND ELECTRICAL WORK SHALL BE PERFORMED BY PERSONS LICENSED IN THEIR TRADES, WHO
SHALL ARRANGE FOR AND OBTAIN INSPECTIONS AND REQUIRED SIGN-OFFS.
THE CONTRACTOR SHALL DO ALL CUTTING, PATCHING, REPAIRING AS REQUIRED TO PERFORM ALL OF THE WORK INDICATED ON THE DRAWINGS, AND ALL OTHER WORK THAT MAY BE REQUIRED TO COMPLETE THE
JOB.
ALL PIPING AND WIRING SHALL BE REMOVED TO A POINT OF CONCEALMENT AND SHALL BE PROPERLY
CAPPED OR PLUGGED.
THE CONTRACTOR, UPON COMPLETION OF THE WORK, SHALL ARRANGE FOR DEPARTMENT OF BUILDINGS
INSPECTIONS AND SIGNOFFS AS REQUIRED.
SMOKE DETECTORS AND CARBON MONOXIDE DETECTORS TO BE INSTALLED TO MEET CODE
REQUIREMENTS.
THIS PROJECT IS NOT LOCATED IN A SPECIAL FLOOD HAZARD AREA (SFHA).
1.
2.
3.
4.
5.
6.
7.
8.
9.
CONTRACTOR SHALL PERFORM ALL OPERATIONS OF DEMOLITION AND REMOVAL INDICATED ON THE DRAWINGS AND AS MAY BE REQUIRED BY THE WORK. ALL WORK SHALL BE DONE CAREFULLY AND
NEATLY, IN A SYSTEMATIC MANNER.
ALL EXISTING SURFACES AND EQUIPMENT TO REMAIN SHALL BE FULLY PROTECTED FROM DAMAGE. THE CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR DAMAGE AND SHALL MAKE REPAIRS REQUIRED
WITHOUT ADDITIONAL COST TO THE OWNER.
NO DEBRIS SHALL BE ALLOWED TO ACCUMULATE ON THE SITE. DEBRIS SHALL BE REMOVED BY THE CONTRACTOR AS THE JOB PROCEEDS. THE SITE SHALL BE LEFT BROOM CLEAN AT THE COMPLETION OF
DEMOLITION.
NO STRUCTURAL ELEMENTS SHALL BE REMOVED UNLESS PORTIONS AFFECTED ARE ADEQUATELY
SUPPORTED BY EITHER TEMPORARY SHORING OR NEW STRUCTURAL ELEMENTS AS REQUIRED TO
PROTECT THE STABILITY AND INTEGRITY OF THE EXISTING STRUCTURE.
ALL ADJOINING PROPERTY AFFECTED BY ANY OPERATIONS OF DEMOLITION SHALL BE PROTECTED PER
THE REQUIREMENTS OF ARTICLE 19 OF THE NYC BUILDING CODE.
REMOVE OR RELOCATE ALL WIRING, PLUMBING, AND MECHANICAL EQUPMENT AFFECTED BY REMOVAL OF PARTITIONS. REMOVED PIPES AND/OR LINES SHALL BE CUT TO A POINT OF CONCEALMENT BEHIND OR
BELOW FINISH SURFACES, AND SHALL BE PROPERLY CAPPED OR PLUGGED.
THE CONTRACTOR SHALL PROVIDE, ERECT AND MAINTAIN ALL TEMPORARY BARRIER AND GUARDS, AND ALL TEMPORARY SHORING AND BRACING AS REQUIRED BY DEPARTMENT OF BUILDING RULES AND
REGULATIONS.
THE CONTRACTOR SHALL PROVIDE ADEQUATE WEATHER PROTECTION FOR THE BUILDING AND ITS CONTENTS DURING THE COURSE OF THE WORK. ALL OPENINGS IN ANY WALL OR ROOF SHALL BE
PROTECTED FROM ALL FORMS OF WEATHER OR WATER PENETRATION.
THE CONTRACTOR SHALL FILE ALL NECESSARY CERTIFICATES OF INSURANCE WITH THE DEPARTMENT OF BUILDINGS, PAY ALL FEES, OBTAIN ALL PERMITS AND PROVIDE ANY AND ALL BONDS REQUIRED BY ANY
CITY AGENCY IN ORDER TO DO THE WORK HEREIN DESCRIBED.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
ALL AREAS SHALL BE DESIGNED AND CONSTRUCTED TO BE ACCESSIBLE IN ACCORDANCE WITH THE 2022
NYC BUILDING CODE, CHAPTER 11, AND ICC/ANSI A117.1-2009.
ALL WALKWAYS, HALLS, CORRIDORS, AISLES AND OTHER SPACES THAT ARE PART OF AN ACCESSIBLE ROUTE SHALL COMPLY WITH NYC BC CHAPTER 11 (ACCESSIBLE ROUTES) AND ICC/ANSI A117.1, CHAPTER 4
(ACCESSIBLE ROUTES).
SPACE ALLOWANCES AND REACH RANGES AT ALL ROOMS AND SPACES SHALL COMPLY WITH ICC/ANSI
A117.1 CHAPTER 3.
GROUND AND FLOOR SURFACES ALONG ACCESSIBLE ROUTES AND IN ROOMS AND SPACES INCLUDING FLOORS, WALKWAYS, RAMPS, CORRIDORS, STAIRS, AND CURB RAMPS SHALL BE STABLE, FIRMAND SLIP
RESISTANT AND COMPLY WITH ICC/ANSI A117.1 SECTION 302 AND 303.
ALL THRESHOLDS AT DOORWAYS SHALL NOT EXCEED 1/4 IN. AND SHALL COMPLY WITH ICC/ANSI A117.1
CHAPTER 3.
ALL DOORS/DOORWAYS REQUIRED TO BE ACCESSIBLE SHALL COMPLY WITH ICC/ANSI A117.1 SECTION 404.
HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERATING DEVICES SHALL COMPLY WITH ICC/ANSI
A117.1 SECTION 309 AND THE APPLICABLE DOOR HARDWARE PROVISIONS OF SECTION 404.
ALL ACCESSIBLE STORAGE FACILITIES, SUCH AS CABINETS AND CLOSETS, SHALL COMPLY WITH ICC/ANSI
A117.1 SECTION 905.
ALL CONTROLS AND OPERATING MECHANISMS FOR LIGHTSWITCHES AND ALARMS SHALL BE ACCESSIBLE
AND SHALL COMPLY WITH ICC/ANSI A117.1 SECTION 309.
ALL EMERGENCY WARNING SYSTEMS SHALL COMPLY WITH ICC/ANSI A117.1 SECTION 702.
ACCESSIBILITY SIGNAGE SHALL COMPLY WITH ICC/ANSI A117.1 SECTION 703, INCLUDING TACTILE AND
BRAILLE REQUIREMENTS WHERE REQUIRED.
D E M O L I T I O N N O T E S
A C C E S S I B I L I T Y N O T E S
L I S T O F I N S P E C T I O N S
SPECIAL INSPECTION:
FIRE RESISTANT PENETRATIONS AND JOINTS BC 1705.17
TENANT PROTECTION PLAN COMPLIANCE BC 3303.10
PROGRESS INSPECTION:
FINAL INSPECTIONS
ENERGY CODE COMPLIANCE INSPECTIONS BC 110.3.5
FENESTRATION AND DOOR U-FACTOR AND PRODUCT RATING RCNY 5000-01 IIA3
FENESTRATION AIR LEAKAGE RCNY 5000-01 IIA4
T-010.00 COVER SHEET
A-100.00 ACCESSIBILITY DIAGRAMS AND PARTITION TYPES
DM-200.00 EXISTING AND DEMOLITION DRAWINGS
A-200.00 PROPOSED PLAN, RCP AND ELEVATION
EN-100.00 HISTORIC BUILDING REPORT
EN-200.00 ENERGY ANALYSIS
DOB JOB NUMBER: M01442993-I1
T E N A N T P R O T E C T I O N P L A N
1. TENANT PROTECTION PLAN WILL BE SUBMITTED IN ACCORDANCE WITH THE REQUIREMENTS OF ARTICLE 120 OF TITLE 28 OF THE ADMINISTRATIVE CODE PRIOR TO THE ISSUANCE OF A PERMIT. LOCAL
LAW 106 OF 2019.
DOOR SCHEDULE ON A-200.00
NO DESCRIPTION DATE
08/19/2026
A C C E S S I B L E D O O R C L E A R A N C E S
" M
IN
18" MIN.
FRONT APPROACH,
PULL SIDE
" M
IN
FRONT APPROACH,
PUSH SIDE
X
NOTE: X=12"
IF THE DOOR HAS
BOTH A CLOSER
AND A LATCH
" M
IN
Y
HINGE SIDE APPROACH,
PUSH SIDE NOTE: Y=48" MIN
IF DOOR HAS BOTH
LATCH AND CLOSER
54" MIN.
" M
IN
YLATCH SIDE APPROACH,
PUSH SIDE
NOTE: Y=48" MIN
IF DOOR HAS A
CLOSER
24" MIN.
X
Y
X
HINGE SIDE APPROACH,
PULL SIDE
NOTE:
X=36" MIN. IF Y=60" MIN.;
X=42" MIN. IF Y=54" MIN.
" M
IN
Y
24" MIN.
LATCH SIDE APPROACH,
PULL SIDE
NOTE:
Y=54" MIN. IF DOOR
HAS CLOSER
" M
IN
24" MAX 48" MIN 24" MAX
" M
IN
.00
32" MIN.
SINGLE WHEELCHAIR SPACE
36" MIN
" M
IN
CLEAR WIDTH OF ACCESSIBLE ROUTE
CLEAR WIDTH AT DOORS
8" MIN
" M
IN
MIN
11"
9"
KNEE AND TOE SPACE AT LAVATORIES AND SINKS
MAX
6"
17" MIN
" M
IN
25" MAX
A C C E S S I B L E C L E A R A N C E S A N D R E A C H
" M
IN
4" MAX
" M
IN
X
IF
0" <X
<2 4"
, 4
" M
AX
IF
X
<1 0"
, 4 8"
M
AX
" M
AX
" M
IN
" M
AX
" M
AX
" M
IN
MAX
10"
UNOBSTRUCTED FORWARD REACH
X
IF
0" <X
<2 5"
, 4 4"
M
AX
IF
X
<2 0"
, 4 8"
M
AX
UNOBSTRUCTED HIGH FORWARD REACH
UNOBSTRUCTED SIDE REACH
UNOBSTRUCTED HIGH SIDE REACH
LIMITS OF PROTRUDING OBJECTS
LEVEL CHANGES
THRESHOLD
1/ 4"
M
AX
DOOR AS
SCHEDULE
D
THRESHOLD
2% MAX. SLOPE
1/ 2"
M
AX
1/ 2"
M
AX
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
PARTITION TYPE DESIGNATIONS ARE SHOWN ON FLOOR PLANS. WHERE PLANS ARE ENLARGED, DESIGNATIONS ARE FOUND ONLY ON THE ENLARGED PLANS.
UNLESS NOTED OTHERWISE, ALL METAL STUDS ARE 25 GA. UNLESS PROJECT CONDITIONS REQUIRE HEAVIER MATERIAL DUE TO VERTICAL SPAN. BASIS OF DESIGN IS THE LIMITING HEIGHT TABLES FROM UNITED STATES GYPSUM CO., AND INCLUDE AN ALLOWANCE OF 5 P.S.F. HORIZONTAL LOAD. REFER TO STRUC.
DWG FOR ALL BEARING WALL REQUIREMENTS.
THE LIMITS OF DEFLECTION FOR ALL PARTITIONS IS L/240 WITH 25GA. 3 5/8" METAL STUDS FOR STANDARD HEIGHT INTERIOR PARTITIONS, L/360 WITH 25GA. 3 5/8" METAL STUDS FOR STANDARD HEIGHT INTERIOR PARTITIONS WITH RIGID FINISHES SUCH AS TILE OR STONE, AND L/240 WITH 20 GA. 6" METAL STUDS FOR
EXTENDED HEIGHT PARTITIONS.
ALL GYPSUM BOARD IS 5/8" TYPE X WITH A MINIMUM OF 2.2 PSF PER LAYER. WHERE TILE, STONE AND SIMILAR RIGID MATERIALS ARE USED AS FINISH
MATERIALS, USE 1/2" CEMENT FIBER BACKER BOARD IN LIEU OF GYPSUM BOARD.
THE MAXIMUM SPACING OF METAL STUDS IS 16 INCHES O.C. REFER TO PARTITION TYPES FOR STUD TYPE.
ALL METAL STUDS ARE CONTINUOUS FOR THE FULL HEIGHT OF THE PARTITION. STUD SPLICING IS NOT PERMITTED UNLESS NOTED OTHERWISE OR REQUIRED
AS PART OF AN APPROVED ASSEMBLY BY THE STRUCTURAL ENGINEER.
TAPE AND FLOAT ALL JOINTS FOR THE FULL HEIGHT OF PARTITIONS.
FULL-HEIGHT PARTITIONS EXTEND FROM THE TOP OF STRUCTURAL CONCRETE FLOORS TO THE UNDERSIDE OF STRUCTURE OF THE FLOOR OR ROOF ABOVE, AND ARE CONSIDERED UNBRACED FOR THEIR FULL HEIGHT.
PARTITIONS ARE DRAWN AT THEIR ACTUAL THICKNESS AND DO NOT INCLUDE APPLIED FINISHES.
SEE REFLECTED CEILING PLANS FOR CEILING HEIGHTS.
PROVIDE VERTICAL CONTROL JOINTS IN ACCORDANCE WITH GA-216 IN ALL PARTITIONS, AND WHERE OTHERWISE INDICATED FOR AESTHETIC REASONS.
CONTROL JOINTS IN FIRE-RESISTANCE-RATED PARTITIONS SHALL BE CONSTRUCTED TO MAINTAIN THE INTEGRITY OF THE LISTED FIRE-RESISTANCE-RATED
ASSEMBLY.
CONSTRUCTION OF FIRE-RESISTANCE-RATED PARTITIONS SHALL BE IN ACCORDANCE WITH THE LISTED ASSEMBLY TO ACHIEVE THE REQUIRED RATING
CLASSIFICATION.
AT ALL LOCATIONS WHERE A FIRE-RESISTANCE-RATED PARTITION ASSEMBLY ABUTS OR ATTACHES TO A PROTECTED STRUCTURAL MEMBER, MAINTAIN THE RATING OF BOTH THE PARTITION AND THE STRUCTRUAL MEMBER IN A MANNER THAT IS ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.
WHERE ITEMS ARE RECESSED INTO A FIRE-RESISTANCE-RATED ASSEMBLY, PROVIDE CONSTRUCTION THAT MAINTAINS THE INTEGRITY OF THE FIRE- RESISTANCE-RATED ASSEMBLY IN A MANNER THAT IS ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.
ALL PENETRATIONS INTO SOUND ISOLATING PARTITIONS SHALL BE FULLY SEALED.
P A R T I T I O N N O T E S
P A R T I T I O N / W A L L T Y P E S
STOREFRONT GLASS PARTITION WALL
1" CLEAR DOUBLE LAMINATED TEMPERED GLASS
EXISTING HORIZONTAL
STRUCTURE ABOVE
2" x 4 1/2" ANODIZED
ALUMINUM FRAME,
CENTERED ON DEMOLISHED
STOREFRONT FRAME
LOCATION WITH ACOUSTIC
SEALANT ON BOTH SIDES
FINISH FLOOR PER SCHEDULE
TOP OF FLOOR SLAB
1" CLEAR DOUBLE LAMINATED
INSULATING GLASS, TEMPERED
2" x 4 1/2" ANODIZED ALUMINUM
FRAME, CENTERED ON
DEMOLISHED STOREFRONT
FRAME LOCATION WITH ACOUSTIC
SEALANT ON BOTH SIDES
BASE
HEAD
G1
MAXIMUM U-0.30 AT FIXED FENESTRATION
MAXIMUM SHGC = 0.33
MAXIMUM AIR LEAKAGE = 0.06 CFM/FT2 AT STOREFRONT
MAXIMUM AIR LEAKAGE = 0.20 CFM/FT2 AT WINDOW
CONSULTANT
CERTIFICATION
SHEET TITLE:
PROJECT #:
DATE:
SCALE:
REVISION HISTORY
s p a c e d a g e n c y
© Spaced Agency PLLC a r c h i t e c t u r e
867 BOYLSTON ST, 5TH FL #1183
BOSTON, MA 02116
TEL: 646-580-2256
SHEET #:
DRAWN BY: TK
PERMIT DRAWINGS
As indicated
A M
O
R E
E T
N ew
Y or k, N
Y
A-100.00
ACCESSIBILITY
DIAGRAMS AND
PARTITION TYPES
DOB JOB NUMBER: M01442993-I1
DEMOLISH EXISTING
STOREFRONT AND DOOR
DEMOLISH EXISTING
DISPLAY CASE
EXISTING STEP AND
LANDING TO REMAIN
OFFICE
WC
STORE
REMOVE
EXISTING
STOREFRONT
REMOVE
EXISTING
DOOR
REMOVE EXISTING
AWNING BOX
REMOVE EXISTING
SCONCE
8"
EXISTING METAL
ROLL-UP GATE,
HOOD AND MOTOR
BOX TO REMAIN
DEMOLISH
DISPLAY CASE
EXISTING LANDING
AND STEP TO REMAIN
PROTECT EXISTING WALLS
PROTECT
EXISTING WALLS
NORTH
D E M O L I T I O N L E G E N D
EXISTING WALL TO BE DEMOLISHED
D E M O L I T I O N G E N E R A L N O T E S
EXISTING WALL
1.
2.
3.
4.
COMPLY WITH APPLICABLE LOCAL, STATE, AND
FEDERAL CODES AND REGULATIONS PERTAINING
TO SAFETY OF PERSON, PROPERTY AND
ENVIRONMENT PROTECTION.
PRIOR TO ANY DEMOLITION WORK, CONTRACTOR
TO CONDUCT ALL APPROPRIATE TESTING FOR
HAZARDOUS MATERIALS.
MANAGE AND DISPOSE OF HAZARDOUS BUILDING
MATERIALS ENCOUNTERED DURING
RENOVATION, IF ANY, IN ACCORDANCE WITH
APPLICABLE ENVIRONMENTAL, HEALTH, AND
SAFETY REGULATIONS AND STANDARDS.
REMOVE MISCELLANEOUS CONDUIT, ETC. ON
EXTERIOR WALLS IF NO LONGER REQUIRED FOR
INTERIOR CONSTRUCTION.
NO WORK DONE UNDER THIS APPLICATION
EXISTING DOOR TO BE DEMOLISHED
9'
7"
9'
23' - 8"3' - 3"18' - 10"6"13' - 11"5"12' - 6"
OFFICE
WC
STORE
6'
3'
0" 3'
0"
3'
0"
6' - 5"
2' - 11"
10' - 3"
73' - 1"
5'
5" 3'
6"
CONSULTANT
CERTIFICATION
SHEET TITLE:
PROJECT #:
DATE:
SCALE:
REVISION HISTORY
s p a c e d a g e n c y
© Spaced Agency PLLC a r c h i t e c t u r e
867 BOYLSTON ST, 5TH FL #1183
BOSTON, MA 02116
TEL: 646-580-2256
SHEET #:
DRAWN BY: TK
PERMIT DRAWINGS
As indicated
A M
O
R E
E T
N ew
Y or k, N
Y
DM-200.00
EXISTING AND
DEMOLITION
DRAWINGS
1/4" = 1'-0"2 DEMOLITION PLAN
1/2" = 1'-0"3 DEMOLITION EXTERIOR ELEVATION
DOB JOB NUMBER: M01442993-I1
1/4" = 1'-0"1 EXISTING PLAN
C O N S T R U C T I O N G E N E R A L N O T E S
NORTH
1.
2.
3.
4.
ALL DIMENSIONS TO BE VERIFIED IN THE FIELD (VIF).
NOTIFY ARCHITECT IF THERE IS A DISCREPANCY
GREATER THAN 1/2".
NOTIFY ARCHITECT IMMEDIATELY OF ANY
INCONSISTENCIES OR DISCREPANCIES WITH PLANS IN
RELATION TO EXISTING FIELD CONDITIONS.
WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALE
ON THE CONSTRUCTION DOCUMENTS. DO NOT SCALE
DRAWING DIRECTLY.
UNLESS NOTED OTHERWISE, ALL DIMENSIONS ARE TO
THE FINISH FACE.
NEW WALL
EXISTING WALL
NO WORK DONE UNDER THIS APPLICATION
C O N S T R U C T I O N L E G E N D
NEW WALL
EXISTING WALL
NO WORK DONE UNDER THIS APPLICATION
R C P L E G E N D
GYPSUM CEILING BOARD
NORTH
L I G H T I N G F I X T U R E S C H E D U L E
RECESSED CEILING MOUNTED FIXTURE
WALL SCONCE
TRACK LIGHTING
L I G H T I N G S Y M B O L S
X
X
X
NOTE: REF. TO ELECTRICAL DWG FOR SWITCHING
LIGHT SWITCH, + 48" AFF UNO
3 = 3-WAY
D = DIMMER
OC = WITH OCCUPANCY SENSOR
X
CONTROLS NARRATIVE
PROVIDE WALL SWITCH WITH OCCUPANCY AT OFFICE AND WC.
SENSOR SHALL AUTOMATICALLY TURN LIGHTS OFF WITHIN 30
MINUTES.
PROVIDE TIME-SWITCH CONTROLS AT STORE FOR AUTOMATIC ON
AND OFF CONTROL OF LIGHTING DURING STORE OPERATING
HOURS. EMERGENCY FIXTURES SHALL REMAIN ILLUMINATED 24
HOURS A DAY.
PROVIDED PHOTO-SENSOR AT ALL EXTERIOR LIGHTS TO ALLOW
LIGHTS TO TURN ON ONLY WHEN SUNLIGHT IS NOT PRESENT. A
TIMER SWITCH SHALL ALSO BE PROVIDED FOR LIGHTING BUILDING
FACADE. TIME CLOCK SHALL SHUT OFF LIGHTING FROM 12
MIDNIGHT OR WITHIN ONE HOUR OF THE END OF OPERATIONS AS
PER OWNER'S PROJECT REQUIREMENTS.
D O O R S C H E D U L E
CEILING / WALL MOUNTED EMERGENCY LIGHT
WALL MOUNTED EMERGENCY LED EXIT SIGN
WITH DIRECTIONAL ARROWS
ILLUMINATED SURFACE
F I R E S A F E T Y S Y M B O L S
ES-1
EL-1
NEW STOREFRONT AND
ENTRY DOOR AT EXISTING
LOCATION
EXISTING ENTRY STEP
TO REMAIN
A-200.00
EXISTING BOX TO REMAIN
STORE
A-200.00
CL
EA
R
" M
IN
WALL-MOUNTED DISPLAY
WITH CABINET DOORS, TYP.
C
LE
AR
" M
IN
48" MIN.
OFFICE
WC
G1G1
9' - 0"
7' - 6" 7' - 6" 8' - 6"
7' - 7"
EXISTING METAL ROLL-
UP GATE TO REMAIN
ES-1 RR-5
EL-1EL-1WS-1
FL-1
RR-2RR-2
OC
TL-2
D3D
EL-1
D3
TL-4TL-4TL-4TL-4TL-4 TL-4TL-4TL-4TL-4TL-4TL-4TL-4
D3D3
OC
RR-2 RR-2 RR-2 RR-2RR-2
LIGHTED
BULLETIN
BOARD
8"
EXISTING METAL ROLL-UP
GATE AND GATE MOTOR
BOX TO REMAIN
EXISTING LANDING AND
STEP TO REMAIN
CLEAN, REPAIR AND REPOINT
EXISTING BRICK FACADE
BEHIND DEMOLISHED SIGN
BOX AS REQ.
G1
NEW EXTERIOR TILES OVER
EXISTING OPAQUE WALLS, TYP.
NEW EXTERIOR TILES OVER
EXISTING OPAQUE WALLS, TYP.
6' - 5 1/2" VIF
6'
" V
IF
7'
" V
IF
3' - 4"
NEW STOREFRONT
MATCHING EXISTING
STOREFRONT
LOCATION AND AREA
G1
2' - 11" VIF
6'
" V
IF
8"
1/
2"
FINISH FLOOR
CONSULTANT
CERTIFICATION
SHEET TITLE:
PROJECT #:
DATE:
SCALE:
REVISION HISTORY
s p a c e d a g e n c y
© Spaced Agency PLLC a r c h i t e c t u r e
867 BOYLSTON ST, 5TH FL #1183
BOSTON, MA 02116
TEL: 646-580-2256
SHEET #:
DRAWN BY: TK
PERMIT DRAWINGS
As indicated
A M
O
R E
E T
N ew
Y or k, N
Y
A-200.00
PROPOSED PLAN,
RCP AND
ELEVATION
1/4" = 1'-0"1 PROPOSED PLAN
1/4" = 1'-0"2 PROPOSED RCP
1/2" = 1'-0"3 EXTERIOR ELEVATION (MOTT STREET)
MARK WIDTH HEIGHT NOTE
100 3' - 0" 7' - 9" PROVIDE HOLD-OPEN DEVICE AND
WEATHERSTRIPPING. MAX U-FACTOR =
U-0.63, MAX SHGC = 0.33, MAX AIR
LEAKAGE = 1 CFM/SQFT
DOB JOB NUMBER: M01442993-I1
1/2" = 1'-0"4 STOREFRONT SIDE ELEVATION
NO DESCRIPTION DATE
08/19/2026
TRACK LIGHT (TL-2 = 2' LENGTH, TL-4 = 4' LENGTH)
TYPE
TL-2, TL-4
DESCRIPTION
RECESSED DOWNLIGHT FIXTURERR-2
FAN LIGHT COMBOFL-1
LIGHTED MIRRORWS-1
EXTERIOR - CEILING SURFACE MOUNTRR-5
CONSULTANT
CERTIFICATION
SHEET TITLE:
PROJECT #:
DATE:
SCALE:
REVISION HISTORY
s p a c e d a g e n c y
© Spaced Agency PLLC a r c h i t e c t u r e
867 BOYLSTON ST, 5TH FL #1183
BOSTON, MA 02116
TEL: 646-580-2256
SHEET #:
DRAWN BY: TK
PERMIT DRAWINGS
A M
O
R E
E T
N ew
Y or k, N
Y
EN-100.00
HISTORIC BUILDING
REPORT
THIS BUILDING IS LISTED AS A
NATIONAL HISTORIC LANDMARK
(USN#: 06101.013330) AND
CONTAINS CHARACTER-
DEFINING FEATURES THAT MAY
CLAIM EXEMPTION FROM
COMPLIANCE WITH THE 2025
NYCECC
DOB JOB NUMBER: M01442993-I1
PART 1: PROOF THE BUILDING IS LISTED
PART 2: CHARACTER-DEFINING FEATURES PART 3: JUSTIFICATION FOR EXEMPTIONS
CHARACTER-DEFINING FEATURE
N/A
SOURCE
N/A
CLAIMING EXEMPTION
NO
EXPLANATION
N/A
EXEMPTION STATUS
NO EXEMPTION IS CLAIMED AS PART OF THIS APPLICATION
N/A
CONSULTANT
CERTIFICATION
SHEET TITLE:
PROJECT #:
DATE:
SCALE:
REVISION HISTORY
s p a c e d a g e n c y
© Spaced Agency PLLC a r c h i t e c t u r e
867 BOYLSTON ST, 5TH FL #1183
BOSTON, MA 02116
TEL: 646-580-2256
SHEET #:
DRAWN BY: TK
PERMIT DRAWINGS
A M
O
R E
E T
N ew
Y or k, N
Y
EN-200.00
ENERGY ANALYSIS
U = 0.63 MAX
SHGC = 0.33 MAX
AIR LEAKAGE = 1.00 CFM/FT2 MAX
ITEM DESCRIPTION
DOOR 101
REPLACEMENT OF EXISTING
ENTRY DOOR
ENERGY ANALYSIS
CODE PRESCRIPTIVE VALUE AND CITATION
MAXIMUM U-FACTOR = U-0.63
NYCECC C402.5
MAXIMUM SHGC = 0.33
NYCECC 402.5
MAXIMUM AIR LEAKAGE = 1.00 CFM/FT2
NYCECC C402.6.3
PROPOSED DESIGN VALUE
OCCUPANCY: COMMERCIAL
SCOPE OF WORK: REPLACEMENT OF EXISTING STOREFRONT AND ENTRY DOOR. ALL OTHER SCOPE IS LIMTED TO INTERIOR ALTERATIONS.
CLIMATE ZONE: 4
STANDARD USED: CHAPTER 5 OR ASHRAE 90.1
A-200.00 (DOOR SCHEDULE)
SUPPORTING DOCUMENTS
ENERGY CODE TABULAR ANALYSIS - STOREFRONT AT COMMERCIAL BUILDING
U = 0.30 MAX
SHGC = 0.33 MAX
AIR LEAKAGE = 0.06 CFM/FT2 MAX
EXAMPLE GUARDIAN SUNGUARD SNX 62/67:
U = 0.28
SHGC = 0.27
AIR LEAKAGE = 0.06 CFM/FT2 MAX
REPLACEMENT OF EXISTING
STOREFRONT WITH NEW
ALUMINUM FRAMED
STOREFRONT
MAXIMUM U-FACTOR = U-0.30 AT FIXED FENESTRATION
NYCECC C402.5
MAXIMUM SHGC = 0.33
NYCECC 402.5
MAXIMUM AIR LEAKAGE = 0.06 CFM/FT2 AT STOREFRONT GLAZING
MAXIMUM AIR LEAKAGE = 0.20 CFM/FT2 AT WINDOW
NYCECC C402.6.3
A-100.00 (PARTITION TYPE)
DOB JOB NUMBER: M01442993-I1
NO DESCRIPTION DATE
08/19/2026
PER TABLE C405.3.2(2):
- SALES AREA: 513 SQFT X 0.85 W/FT2 = 436.05 WATTS
- OFFICE: 63 SQFT X 0.73 W/FT2 = 45.99 WATTS
- RESTROOM: 40 SQFT X 0.74 W/FT2 = 29.6 WATTS
TOTAL ALLOWABLE = 511.64 WATTS
TOTAL PROVIDED = 507.60 WATTS = COMPLIANT
TOTAL CONNECTED LOAD
OF PROPOSED INTERIOR
LIGHTING
MAXIMUM LIGHTING POWER DENSITY USING SPACE-BY-SPACE METHOD:
= 0.85 W/FT2 FOR SALES AREA
= 0.73 W/FT2 FOR OFFICE
= 0.74 W/FT2 FOR RESTROOM
NYCECC C405.3.2
PER TABLE C405.5.2
- TOTAL ALLOWABLE = 19.6 W/LT X 3 = 58.8 WATTS
TOTAL PROVIDED = 9 WATTS = COMPLIANT
TOTAL CONNECTED LOAD
OF PROPOSED EXTERIOR
LIGHTING
LIGHTING POWER ALLOWANCES FOR BUILDING EXTERIORS (ZONE 4)
= 19.6 W/LIINEAR FOOT OF OPENING AT ENTRANCES
NYCECC C405.5.2
OCCUPANT SENSORS HAVE BEEN PROVIDED
IN RESTROOM AND ENCLOSED OFFICE
OCCUPANCY SENSOR
CONTROLS
RESTROOMS AND OTHER SPACES 300 SQFT OR LESS THAT ARE ENCLOSED BY FLOOR-TO-CEILING
HEIGHT PARTITIONS ARE TO HAVE OCCUPANT SENSORS CONTROLLING LIGHTS.
NYCECC C405.2.1., C405.2.1.1, C405.2.1.2
ALL AREAS OF THE SPACE NOT PROVIDED
WITH OCCUPANCY SENSORS ARE
PROVIDED WITH TIME SWITCHES
TIME SWITCH CONTROLS
PROVIDED AT EACH ROOM
NOT CONTROLLED BY
OCCUPANCY SENSOR
EACH AREA OF THE BUILDING THAT IS NOT PROVIDED WITH OCCUPANT SENSOR CONTROLS
COMPLYING WITH SECTION C405.2.1.1 SHALL BE PROVIDED WITH TIME SWITCH CONTROLS
COMPLYING WITH SECTION NYCECC C405.2.2, C405.2.2.1
INTERIOR LIGHTING CONTROLS HAVE
BEEN PROVIDED
MANUAL CONTROLS
PROVIDED AT EACH ROOM
EACH SPACE PROVIDED WITH TIME-SWITCH CONTROLS SHALL ALSO BE PROVIDED WITH A MANUAL
CONTROL FOR LIGHT REDUCTION IN ACCORDANCE WITH SECTION C405.2.2.1. TIME-SWITCH
CONTROLS SHALL INCLUDE AN OVERRIDE SWITCHING DEVICE THAT COMPLIES WITH THE
FOLLOWING: 1. HAVE A MINIMUM 7-DAY CLOCK. 2. BE CAPABLE OF BEING SET FOR SEVEN
DIFFERENT DAY TYPES PER WEEK. 3. INCORPORATE AN AUTOMATIC HOLIDAY "SHUTOFF" FEATURE, WHICH TURNS OFF ALL CONTROLLED LIGHTING LOADS FOR AT LEAST 24 HOURS AND THEN
RESUMES NORMALLY SCHEDULED OPERATIONS. 4. HAVE PROGRAM BACKUP CAPABILITIES, WHICH
PREVENT THE LOSS OF PROGRAM AND TIME SETTINGS FOR AT LEAST 10 HOURS, IF POWER IS
INTERRUPTED. 5. INCLUDE AN OVERRIDE SWITCH THAT COMPLIES WITH THE FOLLOWING: 5.1. THE OVERRIDE SWITCH WILL BE A MANUAL CONTROL. 5.2. THE OVERRIDE SWITCH, WHEN INITIATED, SHALL PERMIT THE CONTROLLED LIGHTING TO REMAIN ON FOR NOT MORE THAN 2 HOURS. 5.3. ANY INDIVIDUAL OVERRIDE SWITCH SHALL CONTROL THE LIGHTING FOR AN AREA NOT LARGER THAN
5,000 SQUARE FEET (465M^2). EXCEPTIONS AS PER THIS CODE SECTION.
NYCECC C405.2.2.1
DIMMING CONTROLS HAVE BEEN PROVIDED
AT THE OFFICE AND EACH ROOM WITH
MANUAL CONTROLS CONTROLS.
LIGHT REDUCTION
CONTROLS PROVIDED AT
EACH ROOM WITH MANUAL
CONTROLS
EACH SPACE NOT PROVIDED WITH OCCUPANT SENSOR CONTROLS COMPLYING WITH SECTION
C405.2.1.1 AND OFFICES SHALL BE PROVIDED WITH DIMMING CONTROLS THAT ALLOW LIGHTS TO BE
DIMMED FROM FULL OUTPUT TO 10% OF FULL POWER, AS WELL AS TURNING OFF LIGHTS.
NYCECC C405.2.3, C405.2.3.1
DAYLIGHT RESPONSIVE CONTROLS ARE
NOT PROVIDED
DAYLIGHT RESPONSIVE
CONTROLS WITHIN
DAYLIGHT ZONES
DAYLIGHT RESPONSIVE CONTROLS ARE NOT REQUIRED AT SIDELIT DAYLIGHT ZONES ON THE FIRST
FLOOR ABOVE GRADE IN GROUP M OCCUPANY AND NOT REQUIRED IN ENCLOSED OFFICE SPACES
LESS THAN 250 SQFT.
NYCECC C405.2.4
MANUAL CONTROLS HAVE BEEN
PROVIDED
MANUAL CONTROLS MANUAL CONTROLS SHALL BE IN A LOCATION WITH READY ACCESS TO OCCUPANTS AND LOCATED
WHERE THE CONTROLLED LIGHTS OR VISIBLE OR SHALL IDENTIFY THE AREA SERVED BY THE
LIGHTS AND INDICATE THEIR STATUS
NYCECC C405.2.6
EXTERIOR LIGHTING CONTROLS HAVE
BEEN PROVIDED
EXTERIOR LIGHTING
CONTROLS
EXTERIOR LIGHTING SYSTEM SHALL BE PROVIDED WITH CONTROLS THAT CONTROL LIGHTING
SUCH THAT LIGHTS SHALL BE AUTOMATICALLY TURNED OFF WHEN DAYLIGHT IS PRESENT AND
SATISFIES THE LIGHTING NEEDS. NYCECC C405.2.7.1
EXTERIOR DECORATIVE LIGHTING
CONTROLS HAVE BEEN PROVIDED
EXTERIOR DECORATIVE
LIGHTING CONTROLS
BUILDING FACADE LIGHTING AND LANDSCAPE LIGHTING SHALL SHUT OFF NOT LATER THAN 1
HOUR AFTER BUSINESS CLOSING TO NOT EARLIER THAN 1 HOUR BEFORE BUSINESS OPENING OR
SHALL BE CONTROLLED SO THE TOTAL WATTAGE IS REDUCED BY NOT LESS THAN 50% BY
SHUTTING OFF THE LIGHTING OR DIMMING LUMINAIRES
NYCECC C405.2.7.2
ENERGY CODE TABULAR ANALYSIS - COMMERCIAL BUILDING ELECTRICAL POWER AND LIGHTING SYSTEMS
ITEM DESCRIPTION CODE PRESCRIPTIVE VALUE AND CITATIONPROPOSED DESIGN VALUE
1.
2.
3.
CONTROLS NARRATIVE
ENCLOSED OFFICE AND RESTROOM (WC) SHALL BE PROVIDED WITH AN OCCUPANCY SENSOR AND WALL SWITCH. SENSOR SHALL AUTOMATICALLY TURN LIGHTS OFF
WITHIN 30 MINUTES.
STORE AREA SHALL BE PROVIDED WITH TIME-SWITCH CONTROLS FOR AUTOMATIC ON AND OFF CONTROL OF LIGHTING DURING STORE OPERATING HOURS.
EMERGENCY FIXTURES SHALL REMAIN ILLUMINATED 24 HOURS A DAY.
ALL EXTERIOR LIGHTING SHALL BE PROVIDED WITH A PHOTO-SENSOR TO ALLOW LIGHTS TO TURN ON ONLY WHEN SUNLIGHT IS NOT PRESENT. A TIMER SWITCH SHALL ALSO BE PROVIDED FOR LIGHTING BUILDING FACADE AND/OR LANDSCAPING. TIME CLOCK SHALL SHUT OFF LIGHTING FROM 12 MIDNIGHT OR WITHIN ONE HOUR OF THE
END OF OPERATIONS AS PER OWNER'S PROJECT REQUIREMENTS.
1.
2.
3.
4.
FUNCTIONAL TESTING PROCEDURES FOR LIGHTING
CONFIRM THAT THE PLACEMENT, SENSITIVITY AND TIME-OUT ADJUSTMENTS FOR OCCUPANT SENSORS YIELD ACCEPTABLE PERFORMANCE.
CONFIRM THAT THE TIME SWITCHES AND PROGRAMMABLE SCHEDULE CONTROLS ARE PROGRAMMED TO TURN THE LIGHTS OFF.
CONFIRM THAT THE PLACEMENT AND SENSITIVITY ADJUSTMENTS FOR PHOTO-SENSOR CONTROLS REDUCE ELECTRIC LIGHT BASED ON THE AMOUNT OF USABLE DAYLIGHT
IN THE SPACE AS SPECIFIED (IF APPLICABLE).
TESTING SHALL BE IN COMPLIANCE WITH SECTION C408.3: LIGHTING SYSTEM FUNCTION TESTING PROCEDURES OF THE 2025 NYC ECC.
CEILING SURFACE MOUNT
FIXTURE TYPE
RR-5
WATTAGE
9 W
DESCRIPTION
9 W
TOTAL WATTS
EXTERIOR LIGHTING FIXTURE SCHEDULE
QUANTITY
TOTAL PROPOSED EXTERIOR WATTS: 9 W
ALLOWED: 58.8 W | COMPLIANT
TRACK LIGHTING
FIXTURE TYPE
TL-2, TL-4
WATTAGE
8 W/LF
DESCRIPTION
400 W
TOTAL WATTS
INTERIOR LIGHTING FIXTURE SCHEDULE
QUANTITY
50 FT
TOTAL PROPOSED INTERIOR WATTS: 507.60 W
ALLOWED: 511.64 W | COMPLIANT
RECESSED DOWNLIGHT FIXTURERR-2 9.8 W 19.6 W2
FAN LIGHT COMBOFL-1 11 W 11 W1
LIGHTED MIRRORWS-1 28 W 15 W1
| T-010.00 - COVER SHEET |
| A-100.00 - ACCESSIBILITY DIAGRAMS AND PARTITION TYPES |
| DM-200.00 - EXISTING AND DEMOLITION DRAWINGS |
| A-200.00 - PROPOSED PLAN, RCP AND ELEVATION |
| EN-100.00 - HISTORIC BUILDING REPORT |
| EN-200.00 - ENERGY ANALYSIS |
File details come from the government source that posted it. Updated .