26.09.01 Repair and Replace Cathodic Protection Drawings.pdf

PDF 2 MB Posted

Attached to
VR25047 Cathodic Protection Repair
Solicitation number
2140502
Issued by
Chautauqua County, New York

About this file

This file contains repair and replacement drawings for cathodic protection systems related to an RFQ issued by OPWDD's Broome DDSO for cathodic protection repair work on the heating water system at Valley Ridge CIT in Norwich, New York. The project involves repair or replacement of cathodic protection components, with a mandatory site visit scheduled for November 9, 2026 at 9:00 AM at 276 County Road 46, Norwich, NY. Quotes must be submitted using the Official Bid Form to brm.bids@opwdd.ny.gov no later than 5:00 PM on November 16, 2026. The contract term is 60 days from the date of award, with the location situated in Chenango County.

This is a Public Works Project requiring prevailing wage compliance. All vendors and sub-contractors must be registered with the New York State Department of Labor and provide a copy of their registration certificate with their quote. The Broome DDSO intends to award the contract to the most responsible and responsive vendor offering the lowest cost while meeting all scope of work requirements. The awarded vendor must provide certificates of Liability Insurance and Worker's Compensation Insurance, as well as completed Lobbying Law Forms and signed Appendix A documentation. The Broome DDSO reserves the right to reject all quotes and will make no concessions for vendor misunderstandings regarding project specifications or requirements.

View the file

Other files

File Type Posted
Cathodic Protection Scope.docx DOCX document
BRM RFQ Form 25-27.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

4500 STATE ROUTE 434

APALACHIN, NY 13732

TEL: 607-223-4334

"UNAUTHORIZED ALTERATION OR ADDITION TO PLANS BEARING

A LICENSED ENGINEER'S OR ARCHITECTS SEAL, IS A VIOLATION

OF SECTION 7209 OF THE NEW YORK STATE EDUCATION LAW"

PROJECT NO:

DATE:

SCALE:

DRAWN BY:

DESIGNED BY:

CHECKED BY:

OP-26002

09/01/2026

LAC

JWE

JWE

REVISIONS

MARK DATE DESCRIPTION

C

AT

H O

D

IC

P R

O

TE

C

TI

O N

NTS

VA

LL

EY

R

ID

G

E C

IT

D

C

B

A

1 2 3 4

1 2 3 4

D

C

B

A

T-100

ISSUED FOR

100% BID

TITLE SHEET

REPAIR AND REPLACE

CATHODIC PROTECTION

276 COUNTRY ROAD 46

NORWICH, NY 13815

PROJECT DATA DRAWING INDEX

AREA MAP LOCATION MAP

PROJECT ADDRESS:

276 COUNTRY ROAD 46 NORWICH, NY 13815

PROJECT SCOPE:

REPAIR AND REPLACEMENT OF SACRIFICAL MAGNESIUM CATHODIC PROTECTION ANODES

THAT HAVE SURPASSED THEIR LIFESPAN. EXISTING ANODES PROTECT PRE-FABRICATED

PERMA-PIPE SERVICE PIPES THAT RUN FROM THE MAIN FACILITY TO EACH HOUSING UNIT AND

BACK INTO THE MAIN FACILITY. THESE ANODES HAVE BEEN TESTED AND IDENTIFIED AS NO

LONGER CAPABLE OF PROVIDING SUFFICIENT PROTECTION AND NEED TO BE REPLACED.

SHEET NUMBER SHEET NAME

T-100 TITLE SHEET

E-001 CATHODIC PROTECTION GENERAL NOTES

E-101 ELECTRICAL NEW WORK

E-102 ELECTRICAL NEW WORK

E-501 ELECTRICAL DETAILS

1 07/23/2026 100% CD

09/01/2026 Issued for Bid2

Date: 09/01/2026

4500 STATE ROUTE 434

APALACHIN, NY 13732

TEL: 607-223-4334

"UNAUTHORIZED ALTERATION OR ADDITION TO PLANS BEARING

A LICENSED ENGINEER'S OR ARCHITECTS SEAL, IS A VIOLATION

OF SECTION 7209 OF THE NEW YORK STATE EDUCATION LAW"

PROJECT NO:

DATE:

SCALE:

DRAWN BY:

DESIGNED BY:

CHECKED BY:

OP-26002

09/01/2026

LAC

JWE

JWE

REVISIONS

MARK DATE DESCRIPTION

C

AT

H O

D

IC

P R

O

TE

C

TI

O N

NTS

VA

LL

EY

R

ID

G

E C

IT

D

C

B

A

1 2 3 4

1 2 3 4

D

C

B

A

E-001

CATHODIC

PROTECTION

GENERAL

NOTES

CATHODIC PROTECTION GENERAL NOTES

1. SYSTEM DESIGN

1.1. THE CATHODIC PROTECTION SYSTEM WAS DESIGNED AS A SACRIFICIAL ANODE CATHODIC PROTECTION SYSTEM.

1.2. THIS PROJECT PRESERVES THE ORIGINAL DESIGN INTENT OF THE PIPE MANUFACTURER. THE PURPOSE OF THIS

PROJECT IS TO REPLACE THE ANODE SYSTEM WHICH IS BEYOND ITS USABLE LIFE.

1.3. THE SYSTEM IS DESIGNED AS A HEADER SYSTEM. THE ANODES ARE CONNECTED TO A COMMON ANODE HEADER WIRE.

THE HEADER WIRE IS CONNECTED TO THE CONDUIT/CONTAINMENT THROUGH THE TEST STATION(S).

1.4. THE DESIGN OF THE CATHODIC PROTECTION SYSTEM IS BASED ON A MINIMUM 20 YEAR ANODE LIFE AND AN ASSUMED SOIL RESISTIVITY OF 10,000 OHM-CM (MILDLY TO SLIGHTLY CORROSIVE). SOIL RESISTIVITY VALUES SHOULD BE

VERIFIED BY FIELD MEASUREMENTS OR SOIL SAMPLES.

2. ELECTRICAL ISOLATION

2.1. CATHODIC PROTECTION SYSTEM WARNING - AN ELECTRICAL SHORT TO ANOTHER METALLIC PIPING SYSTEM OR STRUCTURE IS THE PRIMARY CAUSE OF A CATHODIC PROTECTION SYSTEM NOT MEETING DESIGN REQUIREMENTS.

EXTREME CARE IS REQUIRED TO COMPLETELY ELECTRICALLY ISOLATE THE NEW CATHODICALLY PROTECTED SYSTEM

FROM OTHER PIPING SYSTEMS AND METALLIC STRUCTURES TO AVOID ELECTRICAL SHORTING.

2.2. USE EXTREME CARE TO PREVENT ANODES FROM CONTACTING ANY UNDERGROUND STRUCTURES.

3. INSTALLATION

3.1. INSTALLATION OF THE CATHODIC PROTECTION SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS OF THESE

DRAWINGS IS THE RESPONSIBILITY OF THE INSTALLER.

3.2. A CATHODIC PROTECTION TECHNICIAN CERTIFIED AT CP-2 OR HIGHER IS REQUIRED TO OVERSEE CATHODIC PROTECTION INSTALLATION AND PERFORM THE ACCEPTANCE TESTING OF THE INSTALLATION IN ORDER TO ENSURE

PROPER PERFORMANCE OF THE SYSTEM IS ACHIEVED.

3.3. ANODE INSTALLATION

3.3.1. ANODES MUST BE PROPERLY LOCATED AND CONNECTED TO THE CONDUIT/CONTAINMENT SYSTEM AT THE

LOCATIONS SHOWN ON THESE DRAWINGS.

3.3.2. ANODES MAY BE SHIPPED IN A CLOTH BAG OR CARDBOARD BOX CONFIGURATION. FOLLOW MANUFACTURER

INSTRUCTIONS DURING INSTALLATION.

3.3.2.1. IF USING CLOTH BAG ANODES, THE SHIPPING BAG MUST BE REMOVED PRIOR TO INSTALLATION. THE CLOTH

BAG CONTAINING THE ANODE AND BACKFILL MUST BE LEFT INTACT.

3.3.2.2. IF USING CARDBOARD BOX ANODES, THE ENTIRE ASSEMBLY, INCLUDING CARDBOARD BOX, MUST BE LEFT

INTACT.

3.3.3. DO NOT HANDLE ANODES BY THE LEAD WIRE. DO NOT DROP THE ANODE OR ATTEMPT TO LOWER THE ANODE BY

THE LEAD WIRE.

3.3.4. ANODES MUST BE INSTALLED:

- A MINIMUM OF 3' BELOW GRADE.

- WITH THE TOP OF THE ANODE AT OR BELOW THE CENTERLINE OF THE CONDUIT/CONTAINMENT.

- A MINIMUM OF 3' TO THE SIDE OF THE CONDUIT/CONTAINMENT.

- IN A VERTICAL OR HORIZONTAL POSITION.

- CLEAR OF ANY UNDERGROUND STRUCTURE.

3.3.5. ANODES SHALL BE SPACED AT EQUAL DISTANCES ALONG THE RUN OF CONDUIT/CONTAINMENT.

3.3.6. ANODES SHALL BE SOAKED WITH WATER PRIOR TO BACKFILLING. FIRMLY PACKED NATIVE SOIL SHALL BE

SCREENED AND USED FOR ANODE BACKFILLING. DO NOT USE SAND BACKFILL AROUND ANODES.

3.3.7. UNDERGROUND UTILITY LOCATIONS SHOWN ARE APPROXIMATE ONLY AND REQUIRE FIELD VERIFICATION BY THE CONTRACTOR. THE CONTRACTOR SHALL LOCATE UTILITIES WITHIN THE PROJECT CORRIDOR PRIOR TO COMMENCING CONSTRUCTION. DAMAGE TO UNDERGROUND UTILITIES FROM CONSTRUCTION ACTIVITIES SHALL BE

REPAIRED AT NO ADDITIONAL COST TO THE OWNER.

3.4. WIRING INSTALLATION

3.4.1. LEAVE SLACK IN ALL ANODE LEAD WIRES AND ANODE HEADER WIRES TO ALLOW FOR MOVEMENT AND SETTLING

OF THE CONDUIT/CONTAINMENT AND SOIL DURING BACKFILL AND OVER TIME.

3.4.2. AT TEST STATIONS, ALLOW 6" MINIMUM SLACK FOR ALL WIRES.

3.4.3. ALL UNDERGROUND WIRE SPLICES MUST BE WATER AND MOISTURE PROOF.

3.4.4. PHYSICAL DAMAGE TO WIRE INSULATION MUST BE AVOIDED. ALL WIRING MUST BE WATER AND MOISTURE PROOF.

IF DAMAGE DOES OCCUR TO WIRE INSULATION, REPAIR BY WRAPPING THE DAMAGED AREA WITH 2 LAYERS OF

RUBBER INSULATING TAPE THEN 1 LAYER OF PLASTIC ELECTRICAL TAPE.

3.5. TESTING

3.5.1. A NEGATIVE (CATHODIC) STRUCTURE-TO-ELECTROLYTE POTENTIAL OF AT LEAST -0.850 V OR MORE NEGATIVE MUST BE TESTED AND CONFIRMED AFTER INSTALLATION OF ALL CATHODIC PROTECTION ANODES.

3.5.2. A MINIMUM NEGATIVE (CATHODIC) POLARIZATION VOLTAGE SHIFT OF 100 mV MUST BE MEASURED BETWEEN THE

STRUCTURE SURFACE AND A STABLE REFERENCE ELECTRODE CONTACTING THE ELECTROLYTE.

3.5.3. REFER TO CORRTECH REPORT 17754-LTR-01-1 FOR TEST RESULTS REGARDING THE EXISTING SACRIFICAL ANODES

AND ISOLATION JOINTS ALONG THE PIPING NETWORK.

1 07/23/2026 100% CD

09/01/2026 Issued for Bid2

ISSUED FOR

100% BID

INV 1282.75

INV 1281.83

INV 1282.16

INV 1282.75

"B" HOUSE

"A" HOUSE

PROGRAM

BUILDING

TS #1

TS #2

TS #3

TS #4

4' 2'

2'

40'

5'-4" 4'7'-4"

4' 40'

40'

40'

40' 37'

40' 3'

11'

4'

5'

3'-9 3 16"

11'

3'-2 1 16"

2'-0"

20'-10" 3'-6"

15'

2' 2' 8'

20'-13 4"

2'-93 4"

17'

2'

2'

4' 19'-4"

21'-4"

A

A

A A

4500 STATE ROUTE 434

APALACHIN, NY 13732

TEL: 607-223-4334

"UNAUTHORIZED ALTERATION OR ADDITION TO PLANS BEARING

A LICENSED ENGINEER'S OR ARCHITECTS SEAL, IS A VIOLATION

OF SECTION 7209 OF THE NEW YORK STATE EDUCATION LAW"

PROJECT NO:

DATE:

SCALE:

DRAWN BY:

DESIGNED BY:

CHECKED BY:

OP-26002

09/01/2026

LAC

JWE

JWE

REVISIONS

MARK DATE DESCRIPTION

C

AT

H O

D

IC

P R

O

TE

C

TI

O N

NTS

VA

LL

EY

R

ID

G

E C

IT

D

C

B

A

1 2 3 4

1 2 3 4

D

C

B

A

E-101

ELECTRICAL

NEW WORK

1 ELECTRICAL NEW WORK PLAN - PROGRAM BLDG TO BLDG B

SCALE: 1/8" = 1'

KEYED NOTES:

EXISTING #17 ANODES TO BE ABANDONED IN PLACE AND

DISCONNECTED FROM TEST STATIONS. NEW ANODES WILL BE

INSTALLED AND CONNECTED TO THE EXISTING TEST STATIONS.

GENERAL ELECTRICAL NEW WORK NOTES:

1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO BEGINNING WORK.

2. ALL AREAS OF THE BUILDING AFFECTED BY ELECTRICAL DEMOLITION WORK SHALL BE PATCHED AND REPAIRED TO MATCH ADJACENT FINAL FINISHES. THE REPAIR WORK SHALL BE DONE TO THE

CONTRACTING OFFICER'S SATISFACTION.

3. WORK REPLACED SHALL MATCH SIMILAR EXISTING WORK. STRUCTURAL MEMBERS OF

CONCRETE OR STRUCTURAL STEEL SHALL NOT BE CUT OR ALTERED, EXCEPT AS SHOWN,

WITHOUT AUTHORIZATION OF THE ENGINEER. WORK REMAINING IN PLACE DAMAGED OR

DEFACED DURING THIS CONTRACT SHALL BE RESTORED TO THE CONDITION AT TIME OF AWARD

OF CONTRACT. CUT, ALTER, REMOVE, OR TEMPORARILY REMOVE AND REPLACE EXISTING WORK

FOR INSTALLATION OF ELECTRICAL WORK.

CONDUIT PIPE SCHEDULE

SECTION SERVICE PIPE

INSULATION

THICKNESS

CONDUIT OUTSIDE

DIAMETER SERVICE

A 4" SCH. 40 HHWS&R2" 12-3/4"

B 3" SCH. 40 HHWS&R2" 10-3/4"

C 2-1/2" SCH. 40 HHWS&R2" 10-3/4"

CATHODIC PROTECTION SYMBOLS

#17 ANODES

TEST STATION

4", 150LB RATED ISOLATION FLANGE

KIT

3", 150LB RATED ISOLATION FLANGE

KIT

2-1/2", 150LB RATED ISOLATION

FLANGE KIT

COPPER/COPPER SULFATE

REFERENCE ELECTRODE

END SEAL ASSEMBLY

ANCHOR ASSEMBLY

FIELD JOINT ASSEMBLY

OVAL SUPPORTS

1 07/23/2026 100% CD

09/01/2026 Issued for Bid2

ISSUED FOR

INV 1280.75

INV 1281.16

"B" HOUSE

"C" HOUSE

TS #6

TS #5

22'

3'-10"

5'-10"

3'

3'

2'-83 4"

3'

3'-10"

4'-

3 4

A A

INV 1278.06

INV 1277.75

"D" HOUSE

"C" HOUSE

TS #10

TS #9

24'-10"

22'-10"

4'

4'

'-8

3 4"

3'-6 3 4 "

2'-10"

22'

22'

B B

INV 1279.16

INV 1278.75

"E" HOUSE

"D" HOUSE

TS #7

TS #8

24'-1 3 4 "

24'-10" 3'-33 4"

3'-6"

16'

15'

2' 2'

2' 2'7'

4' 20'-10"

19'-4"

C C

4500 STATE ROUTE 434

APALACHIN, NY 13732

TEL: 607-223-4334

"UNAUTHORIZED ALTERATION OR ADDITION TO PLANS BEARING

A LICENSED ENGINEER'S OR ARCHITECTS SEAL, IS A VIOLATION

OF SECTION 7209 OF THE NEW YORK STATE EDUCATION LAW"

PROJECT NO:

DATE:

SCALE:

DRAWN BY:

DESIGNED BY:

CHECKED BY:

OP-26002

08/03/2026

LAC

JWE

JWE

REVISIONS

MARK DATE DESCRIPTION

C

AT

H O

D

IC

P R

O

TE

C

TI

O N

NTS

VA

LL

EY

R

ID

G

E C

IT

D

C

B

A

1 2 3 4

1 2 3 4

D

C

B

A

E-102

ELECTRICAL

NEW WORK

1 ELECTRICAL NEW WORK PLAN - BLDG B TO BLDG C

SCALE: 1/8" = 1'

2 ELECTRICAL NEW WORK PLAN - BLDG C TO BLDG D

SCALE: 1/8" = 1'

3 ELECTRICAL NEW WORK PLAN - BLDG D TO BLDG E

SCALE: 1/8" = 1'

1 1

KEYED NOTES:

EXISTING #17 ANODES TO BE ABANDONED IN PLACE AND

DISCONNECTED FROM TEST STATIONS. NEW ANODES WILL BE

INSTALLED AND CONNECTED TO THE EXISTING TEST STATIONS.

EXISTING ELECTRICALLY SHORTED ISOLATION FLANGE KIT TO BE

REMOVED AND REPLACED WITH NEW.

GENERAL ELECTRICAL NEW WORK NOTES:

1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO BEGINNING WORK.

2. ALL AREAS OF THE BUILDING AFFECTED BY ELECTRICAL DEMOLITION WORK SHALL BE PATCHED AND REPAIRED TO MATCH ADJACENT FINAL FINISHES. THE REPAIR WORK SHALL BE DONE TO THE

CONTRACTING OFFICER'S SATISFACTION.

3. WORK REPLACED SHALL MATCH SIMILAR EXISTING WORK. STRUCTURAL MEMBERS OF

CONCRETE OR STRUCTURAL STEEL SHALL NOT BE CUT OR ALTERED, EXCEPT AS SHOWN,

WITHOUT AUTHORIZATION OF THE ENGINEER. WORK REMAINING IN PLACE DAMAGED OR

DEFACED DURING THIS CONTRACT SHALL BE RESTORED TO THE CONDITION AT TIME OF AWARD

OF CONTRACT. CUT, ALTER, REMOVE, OR TEMPORARILY REMOVE AND REPLACE EXISTING WORK

FOR INSTALLATION OF ELECTRICAL WORK.

CONDUIT PIPE SCHEDULE

SECTION SERVICE PIPE

INSULATION

THICKNESS

CONDUIT OUTSIDE

DIAMETER SERVICE

A 4" SCH. 40 HHWS&R2" 12-3/4"

B 3" SCH. 40 HHWS&R2" 10-3/4"

C 2-1/2" SCH. 40 HHWS&R2" 10-3/4"

CATHODIC PROTECTION SYMBOLS

#17 ANODES

TEST STATION

4", 150LB RATED ISOLATION FLANGE

KIT

3", 150LB RATED ISOLATION FLANGE

KIT

2-1/2", 150LB RATED ISOLATION

FLANGE KIT

COPPER/COPPER SULFATE

REFERENCE ELECTRODE

END SEAL ASSEMBLY

ANCHOR ASSEMBLY

FIELD JOINT ASSEMBLY

OVAL SUPPORTS

1 07/23/2026 100% CD

09/01/2026 Issued for Bid2

ISSUED FOR

10'-10"

TYP

3'-0"

MIN.

GRADE EXISTING 3" x 12" x 12"

CONCRETE SLAB TO

REMAIN FLUSH TEST STATION WITH

REMOVABLE COVER

TOP OF ANODES MUST

BE AT OR BELOW

CENTERLINE OF PIPE .

#12 TEST LEAD

WIRE

THERMITE WELD

CABLE SPLICE

TO TEST

STATION

ANODE COLLECTOR CABLE

HIGH POTENTIAL

MAGNESIUM ANODE

#12 STRUCTURE

LEAD WIRE

3" MIN.

NOTE: ANODE IS INDICATED AS INSTALLED IN THE VERTICAL POSITION FOR

CLARITY. ANODE MAY BE INSTALLED IN THE VERTICAL OR HORIZONTAL POSITION.

3'

0" M

IN

CATHODICALLY PROTECTED

UNDERGROUND PIPE

ANODE BACKFILL (A MIXTURE OF HYDRATED

GYPSUM, POWDERED BENTONITE, AND SODIUM

SULFATE PREPACKAGED INSIDE OF THE ANODE)

COTTON SACK OR

CARDBOARD BOX

GALVANIZED STEEL

STRAP CORE

HEAT SHRINK PE TUBE

COVERED

THERMIT WELDING

PVC TAPE WRAPPING

1C-#12 THWN

2'-11

2"

6"

2'-6"

A

A

SECTION A-A

2"

3"

3"

SPECIFICATION OF MAGNESIUM ANODE

SIZE: 3" x 3" x 25.5"

WEIGHT: 17LB

WRAP CONNECTOR WITH TAPE.

THEN POSITION IN CENTER OF

PAD.

FIG. 1 FIG. 2

FOLD BOTTOM LEFT CORNER OF

PAD OVER CONNECTOR. STRETCH

PAD AROUND CABLE.

FIG. 3

FOLD OTHER CORNER OVER

CONNECTOR AS SHOWN. STRETCH

PAD AROUND CABLE.

FIG. 4

FOLD TOP OF PAD DOWN OVER

CONNECTOR.

FIG. 5

FOLD AROUND CONNECTOR AS

SHOWN. STRETCH AROUND CABLE.

FIG. 6

NOTES:

1. MAKE ELECTRICAL WIRE SPLICE CONNECTION AS REQUIRED.

2. VIGOROUSLY SAND HEADER & ANODE WIRE INSULATION

APPROXIMATELY 2 INCHES BACK FROM THE CONNECTION.

3. IF RE-ENTRY MAY BE REQUIRED, TAPE THE CONNECTION

FIRST WITH ONE LAYER OF VINYL TAPE.

4. ENFOLD THE CONNECTION USING THE SQUARE MASTIC

SPLICING PATCH, KNEADING THE MASTIC SEALANT SO THAT IT

COVERS THE ENTIRE SPLICE AND BONDS COMPLETELY TO

ITSELF.

5. COVER THE SPLICE PATCH MASTIC MATERIAL WITH ONE

LAYER OF RUBBER TAPE.

6. COVER RUBBER TAPE WITH TWO LAYERS OF VINYL TAPE.

UNDERGROUND SPICE IS COMPLETE.

STUDS

1/8" THICK STEEL WASHER

NOMEX ISOLATION SLEEVE

NUTISOLATION WASHER

NEMA GRADE 7

SERVICE PIPE FLANGES

FULL FACE PTFE ISOLATION

GASKET

NOTES:

1. USE ONLY HIGH TENSILE STUDS AND HEAVY

SERIES NUTS. STUDS MUST BE 1/2" MINIMUM

LONGER THAN STANDARD TO ACCOMMODATE

ISOLATION WASHERS

2. PROPERLY ALIGN FLANGE FACES TO AVOID

DAMAGE TO FLANGE ISOLATION KIT

MATERIALS.

3. ISOLATION FLANGES MUST BE INSTALLED

SUCH THAT THE FORCES CREATED BY THE

PIPE ON THE FLANGES CAUSE COMPRESSION

OF THE ISOLATION GASKET.

4500 STATE ROUTE 434

APALACHIN, NY 13732

TEL: 607-223-4334

"UNAUTHORIZED ALTERATION OR ADDITION TO PLANS BEARING

A LICENSED ENGINEER'S OR ARCHITECTS SEAL, IS A VIOLATION

OF SECTION 7209 OF THE NEW YORK STATE EDUCATION LAW"

PROJECT NO:

DATE:

SCALE:

DRAWN BY:

DESIGNED BY:

CHECKED BY:

OP-26002

09/01/2026

LAC

JWE

JWE

REVISIONS

MARK DATE DESCRIPTION

C

AT

H O

D

IC

P R

O

TE

C

TI

O N

NTS

VA

LL

EY

R

ID

G

E C

IT

D

C

B

A

1 2 3 4

1 2 3 4

D

C

B

A

E-501

1 07/23/2026 100% CD

ELECTRICAL

DETAILS

1 ANODE TEST STATION DETAIL

SCALE: NTS

2 #17 ANODE DETAIL

SCALE: NTS

3 TYPE S SPLICE KIT INSTALLATION DETAIL (TYP.)

SCALE: NTS

4 CATHODIC PROTECTION FLANGE ISOLATION KIT

SCALE: NTS

09/01/2026 Issued for Bid2

ISSUED FOR

Cathodic Protection Drawings-T-100
Sheets and Views
T-100
Cathodic Protection Drawings-E-001
Sheets and Views
E-001
Cathodic Protection Drawings-E-101
Sheets and Views
E-101
Cathodic Protection Drawings-E-102
Sheets and Views
E-102
Cathodic Protection Drawings-E-501
Sheets and Views
E-501

File details come from the government source that posted it. Updated .