Structural Modifications to 911 Emergency Operations Center
This is a structural design document prepared for the City of Hampton, Virginia, detailing required modifications to reinforce the existing 911 Emergency Operations Center located at 100 Exploration Way, Hampton, VA 23666. The project involves structural reinforcement of the existing building to meet Risk Category IV classification standards in accordance with the 2021 International Building Code and Virginia Uniform Statewide Building Code effective January 18, 2024. The primary work consists of reinforcing fourteen existing HSS8x8 diagonal braces throughout the structure using steel plates welded to all four sides of each brace. The building features three floors plus a roof level, with finished first floor elevation at 0'-0", second floor steel at 13'-6", third floor steel at 26'-10", and roof steel at 41'-9". The scope of work includes field verification of vertical brace lengths, installation of 1/4-inch thick continuous steel reinforcing plates, and complete joint penetration welds between plate sections. All structural steel must comply with AISC 360-16 specifications and be fabricated from new ASTM A36 steel, with welding performed to AWS D1.1 standards using E70XX electrodes. Third-party visual inspection by a testing agency hired by the owner is required for all steel plate installations and welds.
The design incorporates specific load criteria including a ground snow load of 10 PSF with a resulting flat roof snow load of 15.6 PSF, ultimate wind speed of 131 MPH (nominal 101.5 MPH) for Risk Category IV exposure, and seismic design parameters with importance factor of 1.5 and design base shear of 0.070W using ordinary concentrically braced frames with a response modification factor of 3.25. The contractor bears full responsibility for field measurements, shop drawing submissions, dimensional verification, job site safety, and protection of existing building elements. Prior to commencing work, the general contractor must become familiar with existing building construction and coordinate with the owner regarding removal of finishes, partitions, and building systems necessary to access members for reinforcement. Upon completion of reinforcement and inspection, the contractor is responsible for reconstruction and repair of all removed building elements. The document establishes that contractors must submit shop drawings for approval before fabrication and accept complete responsibility for the accuracy and correctness of all dimensional work in accordance with generally accepted construction practices.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ITB 27-16TM Exploration Way.pdf | ||
| ITB 27-16TM Addendum 1.pdf | ||
| Mandatory Pre0Bid ITB 27-16TM.pdf | ||
| Statement and Schedule of Special Inspections.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 3 4 5 6 7 8 9 10
A
B
C
D
A
S201
B
S201
C
S201
C
S201
A
S201
B
S201
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
33 3
(TYP)(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)(TYP)(TYP)(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(-0'-8")(-0'-8")(-4'-8")(-0'-8")(-0'-8")
(-0'-8")
(-0'-8")
(-4'-8") (-0'-8") (-0'-8")
(-2'-0")(-2'-0")(-2'-0")(-2'-0")
± 20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0"
A. DATUM FOR ALL ELEVATIONS GIVEN ON THIS PLAN IS
EXISTING FINISHED FIRST FLOOR ELEVATION = 0’-0”.
B. TOP OF EXISTING FIRST FLOOR IS AT +0’-0”.
C. TOP OF EXISTING FOOTING ELEVATIONS ARE -1'-4"
BELOW FINISHED FIRST FLOOR UNLESS NOTED THUS
(-____) ON PLAN PER ORIGINAL DRAWINGS DATED
JUNE 1, 2004.
D. THE EXISTING FIRST FLOOR IS A 4" SLAB-ON-GRADE
REINFORCED WITH WELDED-WIRE-FABRIC PER THE
ORIGINAL BUILDING DRAWINGS.
E. FOR GENERAL NOTES REFER TO THIS SHEET.
FACE OF EXISTING BUILDING.
EXISTING 10" WIDE FLANGE COLUMN.
EXISTING WALL FOOTING.
EXISTING COLUMN FOOTING.
EXISTING GRADE BEAM.
LOCATION OF VERTICALLY BRACED BAY. FOR
DETAILS AND MEMBERS TO BE REINFORCED
REFER TO FRAMING ELEVATIONS ON SHEET S201.
14 TOTAL DIAGONAL BRACES TO BE REINFORCED.
DRAWN BY:
DESIGNED BY:
CHECKED BY:
DATE:
JOB NUMBER:
5/28/2026
S101
E X
IS
T
IN
G
F O
U N
D A
T
IO
N P
L A
N
S T
R U
C T
U R
A L M
O D
IF
IC
A T
IO
N
S T
O
E M
E R
G E
N C
Y O
P E
R A
T
IO
N S
C E
N T
E R
DFS
DFS
05/28/2026
26.030
KBF
E
X P
L O
R A
T
IO
N W
A Y
H
A M
P T
O N
V
A
1/8" = 1'-0"
EXISTING FOUNDATION PLAN
N
4'0 8' 16'
SCALE: 1/8"=1'-0"
SHEET NOTES:
SHEET KEYNOTES:
GENERAL:
1. ALL WORK MUST COMPLY WITH THE CODES LISTED BELOW AND IN THE
SPECIFICATIONS.
2. THE NEW WORK SHOWN ON THESE PLANS ILLUSTRATE THE
REQUIREMENTS TO REINFORCE THE EXISTING STRUCTURE TO A RISK
CATEGORY IV STRUCTURE IN ACCORDANCE WITH THE PROVISIONS OF
THE INTERNATIONAL BUILDING CODE, 2021 EDITION, AS ADOPTED BY THE
VIRGINIA UNIFORM STATEWIDE BUILDING CODE, 2021 EDITION,
EFFECTIVE JANUARY 18, 2024.
3. THE CONTRACTOR IS RESPONSIBLE FOR DIMENSIONS, ELEVATIONS,
ETC., NECESSARY FOR THE PROPER CONSTRUCTION AND ALIGNMENT OF
THE NEW STRUCTURAL ELEMENTS TO THE EXISTING STRUCTURE. MAKE
ALL MEASUREMENTS NECESSARY PRIOR TO THE FABRICATION AND
ERECTION OF STRUCTURAL MEMBERS.
4. BEFORE PROCEEDING WITH ANY WORK WITHIN THE EXISTING
STRUCTURE, BECOME FAMILIAR WITH STRUCTURAL CONDITIONS OF THE
EXISTING STRUCTURE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO
PROVIDE ALL NECESSARY SAFEGUARDS, TO MAINTAIN ALL PARTS OF
THE STRUCTURE IN A SAFE CONDITION AT ALL TIMES DURING THE
PROCESS OF CONSTRUCTION AND TO PROTECT FROM DAMAGE THOSE
PORTIONS OF THE EXISTING BUILDING WHICH ARE TO REMAIN.
GENERAL (CONT'D):
5. SUBMIT SHOP DRAWINGS FOR APPROVAL BEFORE PROCEEDING WITH THE
WORK. THE CONTRACTOR MUST CHECK ALL DIMENSIONS AND ACCEPT FULL
RESPONSIBILITY FOR DIMENSIONAL CORRECTNESS.
6. UNDER NO CIRCUMSTANCES CAN THE REPRODUCTION OF CONTRACT
DRAWINGS BE USED AS SHOP DRAWINGS.
7. IN ACCORDANCE WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES,
CONTRACTOR WILL BE SOLELY AND COMPLETELY RESPONSIBLE FOR
CONDITION OF JOB SITE INCLUDING SAFETY OF ALL PERSONS AND PROPERTY
DURING PERFORMANCE OF THE WORK.
8. TYPICAL DETAILS AND GENERAL NOTES APPLY TO ALL PARTS OF THE JOB
EXCEPT WHERE SPECIFICALLY DETAILED OR NOTED OTHERWISE.
9. INFORM THE PROFESSIONAL OF RECORD IN WRITING OF ANY DEVIATION
FROM THE CONTRACT DOCUMENTS. THE CONTRACTOR IS NOT RELIEVED OF
THE RESPONSIBILITY OF SUCH DEVIATION BY THE PROFESSIONAL OF RECORD
REVIEW OF SHOP DRAWINGS, PRODUCT DATA, ETC. UNLESS THE
CONTRACTOR HAS SPECIFICALLY INFORMED THE PROFESSIONAL OF RECORD
OF SUCH DEVIATION AT THE TIME OF SUBMISSION, AND THE PROFESSIONAL
OF RECORD HAS GIVEN WRITTEN APPROVAL TO THE SPECIFIC DEVIATION.
DESIGN CRITERIA:
1. ROOF SNOW LOADS:
GROUND SNOW LOAD Pg = 10 PSF (PER FIGURE 1608.2 OF VCC) SNOW EXPOSURE FACTOR Ce = 0.9
SNOW LOAD IMPORTANCE FACTOR I =1.0
THERMAL FACTOR Ct=1.025 FLAT ROOF SNOW LOAD: Pf = 15.6 PSF
RAIN ON SNOW SURCHARGE LOAD= 0 PSF
2. WIND LOADS:
RISK CATEGORY = IV
ULTIMATE WIND SPEED = 131 MPH
NOMINAL WIND SPEED (ASD) = 101.5 MPH
EXPOSURE CATEGORY (MAIN WINDFORCE-RESISTING SYSTEM): C
EXPOSURE CATEGORY (COMPONENTS AND CLADDING): C
INTERNAL PRESSURE COEFFICIENT: +/- 0.18 (ENCLOSED)
DESIGN CRITERIA (CONT'D):
3. SEISMIC LOADS:
RISK CATEGORY IV
IMPORTANCE FACTOR I = 1.5
Ss = .10g S1 = .04g
SOIL SITE CLASS E
Sds = 0.152 Sd1 = 0.114
SEISMIC DESIGN CATEGORY: C
BASIC SEISMIC FORCE RESISTING SYSTEM:
STEEL ORDINARY CONCENTRICALLY BRACED FRAMES
RESPONSE MODIFICATION FACTOR, R=3.25
SEISMIC RESPONSE COEFFICIENT, Cs = 0.070
DESIGN BASE SHEAR: 0.070W
ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL FORCE
STRUCTURAL STEEL:
1. STRUCTURAL STEEL MUST COMPLY WITH
THE AMERICAN INSTITUTE OF STEEL
CONSTRUCTION (AISC 360-16)
“SPECIFICATION FOR STRUCTURAL STEEL
BUILDINGS”.
2. STRUCTURAL STEEL MUST BE NEW,
CLEAN, AND STRAIGHT, AND CONFORM
TO THE FOLLOWING:
A. STEEL PLATES - ASTM A36, UNLESS
OTHERWISE NOTED
3. WELDING MUST COMPLY WITH THE
"STRUCTURAL WELDING CODE - STEEL"
(AWS D1.1). WELD ELECTRODES MUST BE
E70XX.UNLESS OTHERWISE NOTED,
MINIMUM WELD SIZE MUST BE 3/16"
CONTINUOUS FILLET WELDS.
4. STEEL PLATE INSTALLATION AND WELDS
MUST BE VISUALLY INSPECTED BY THIRD
PARTY TESTING AGENCY, HIRED BY
OWNER.
GENERAL NOTES
NOTE:
PRIOR TO ANY WORK, GENERAL CONTRACTOR WILL
BECOME FAMILIAR WITH THE EXISTING BUILDINGS
CONSTRUCTION AND FINISHES, PARTITIONS, AND
OTHER SYSTEMS THAT MUST BE REMOVED TO
ACCESS THE MEMBERS IN ORDER TO REINFORCE
THE MEMBERS AS SHOWN ON THESE PLANS. THE
OWNER WILL PROVIDE DIRECTION TO THE GENERAL
CONTRACTOR FOR REMOVAL OF EXISTING
FINISHES, PARTITIONS AND SYSTEMS. ONCE THE
REINFORCING OF THE MEMBERS IS COMPLETE AND
INSPECTED; THE GENERAL CONTRACTOR WILL
RECONSTRUCT/REPAIR THE BUILDING ELEMENTS
THAT WERE REMOVED PER THE OWNERS
DIRECTION.
REVISIONS
NO. DATE COMMENTS
FINISHED
EXISTING FIRST
FLOOR
0' - 0"
TOP OF STEEL AT
SECOND FLOOR
13' - 6"
TOP OF STEEL AT
THIRD FLOOR
26' - 10"
3 4
TOP OF STEEL AT
ROOF
41' - 9"
S201
S201
S201
EXISTING 3" CONCRETE
ON 3" METAL DECK
COMPOSITE SLAB, TYP
AT SECOND AND THIRD
FLOOR
4" SLAB-ON-GRADE,
(TYP)
GUSSET PLATE,
TYP EACH END OF
VERTICAL BRACE
±21'-0
±20'-0
±21'-0
REINFORCE EXISTING
HSS8x8 BRACE WITH STEEL
PLATES PER SECTION
1/S201
REINFORCE EXISTING HSS8x8
BRACE WITH STEEL PLATES
PER SECTION 1/S201
20' - 0"
CONTRACTOR TO FIELD VERIFY
LENGTH OF EACH VERTICAL
BRACE AND PROVIDE STEEL
REINFORCING PLATE BETWEEN
GUSSET PLATES, TYP
EXISTING WIDE
FLANGE BEAMS,
TYP
FINISHED
EXISTING FIRST
FLOOR
0' - 0"
TOP OF STEEL AT
SECOND FLOOR
13' - 6"
TOP OF STEEL AT
THIRD FLOOR
26' - 10"
BC
TOP OF STEEL AT
ROOF
41' - 9"
S201
±28'-0
±27'-0"
±29'-0"
CONTRACTOR TO FIELD VERIFY
LENGTH OF EACH VERTICAL
BRACE AND PROVIDE STEEL
REINFORCING PLATE BETWEEN
GUSSET PLATES, TYP
EXISTING WIDE
FLANGE BEAMS,
TYP
REINFORCE EXISTING HSS8x8
BRACE WITH STEEL PLATES
PER SECTION 1/S201
EXISTING 3" CONCRETE
ON 3" METAL DECK
COMPOSITE SLAB, TYP
AT SECOND AND THIRD
FLOOR
30' - 0"
4" SLAB-ON-GRADE,
(TYP)
EXISTING HSS8x8
BRACE, DO NOT
REINFORCE
GUSSET PLATE,
TYP EACH END OF
VERTICAL BRACE
FINISHED
EXISTING FIRST
FLOOR
0' - 0"
TOP OF STEEL AT
SECOND FLOOR
13' - 6"
TOP OF STEEL AT
THIRD FLOOR
26' - 10"
TOP OF STEEL AT
ROOF
41' - 9"
S201
S201
S201
±21'-0"
±20'-0"
±21'-0"
CONTRACTOR TO FIELD VERIFY
LENGTH OF EACH VERTICAL
BRACE AND PROVIDE STEEL
REINFORCING PLATE BETWEEN
GUSSET PLATES, TYP
EXISTING WIDE
FLANGE BEAMS,
TYP
REINFORCE EXISTING
HSS8x8 BRACE WITH STEEL
PLATES PER SECTION 1/S201
REINFORCE EXISTING
HSS8x8 BRACE WITH STEEL
PLATES PER SECTION
1/S201
EXISTING 3" CONCRETE
ON 3" METAL DECK
COMPOSITE SLAB, TYP
AT SECOND AND THIRD
FLOOR
20' - 0"
4" SLAB-ON-GRADE,
(TYP)
GUSSET PLATE,
TYP EACH END OF
VERTICAL BRACE
EXISTING HSS8x8x1/4
BRACE
1/4" THICK x 7" WIDE CONTINUOUS STEEL
PLATE (TYP) WELDED TO ALL 4 SIDES OF
EXISTING BRACE. PLATE CAN BE SEPARATE
SECTIONS WITH A COMPLETE JOINT
PENETRATION (CJP) WELD BETWEEN
SECTIONS TO BE CONTINUOUS. PLATES MUST
EXTEND FROM GUSSET PLATE TO GUSSET
PLATE.
3/16 2"
EVERY 8",
TYP AT EACH
PLATE
E Q
E Q
EQ EQ
CENTERLINE
OF HSS
DRAWN BY:
DESIGNED BY:
CHECKED BY:
DATE:
JOB NUMBER:
5/28/2026
S201
E L E
V A
T
IO
N S
S T
R U
C T
U R
A L M
O D
IF
IC
A T
IO
N
S T
O
E M
E R
G E
N C
Y O
P E
R A
T
IO
N S
C E
N T
E R
DFS
DFS
05/28/2026
26.030
KBF
E
X P
L O
R A
T
IO
N W
A Y
H
A M
P T
O N
V
A
1/4" = 1'-0"S101
A ELEVATION
1/4" = 1'-0"S101
B ELEVATION
1/4" = 1'-0"S101
C ELEVATION
1 1/2" = 1'-0"S201
1 SECTION
0 1' 2'
SCALE: 1-1/2"=1'-0"
0 2' 4' 8'
SCALE: 1/4"=1'-0"
7 6 6 7
REVISIONS
NO. DATE COMMENTS
| Sheets |
| S101 - EXISTING FOUNDATION PLAN |
| S201 - ELEVATIONS |
File details come from the government source that posted it. Updated .