26-8683_Exhibit_P_–_Pipe_Schedule.pdf
PDF 476 KB Posted
- Attached to
- SCRWTP Lime Softening Improvements - Blend Tank
- Solicitation number
- 26-8683
- Issued by
- Collier County, Florida
About this file
This is a Pipe Schedule exhibit prepared by Carollo Engineers, Inc. for Collier County's South County Regional Water Treatment Plant (SCRWTP) Lime Softening Improvements - Blend Tank project (Bid No. 26-8683). The document specifies materials, dimensions, pressure ratings, testing methods, and installation requirements for all piping systems associated with the blend tank construction. Piping materials include polyvinyl chloride (PVC) for drain lines ranging from 0.5 to 12 inches, chlorinated polyvinyl chloride (CPVC) Schedule 80 for chemical injection systems (chlorine solution, ammonia, sodium hydroxide, and corrosion inhibitor) in sizes from 0.5 to 4 inches, and ductile iron pipe (DIP) rated at 150 pounds per square inch for process water lines including 42-inch blended finished water and 36-inch filter effluent lines. All chemical injection piping requires double-wall containment with leak detection. Joints and fittings specifications vary by application, with solvent-welded connections for plastic piping and restrained mechanical joints for ductile iron piping. Test pressures range from gravity method testing for drain systems to high-head testing at 125 pounds per square inch for pressurized water lines. The schedule includes coating and lining requirements, with cement mortar lining and polyethylene encasement specified for ductile iron piping carrying blended finished water and filter effluent to ensure water quality protection and corrosion resistance.
The document was digitally signed and sealed on June 29, 2026, by Anthony Ryan Horvat, P.E., and serves as Addendum 4 to the specification set for the blend tank construction. This pipe schedule is referenced in Section 40_05_00.01 (Common Work Results for General Piping) and cross-references detailed specifications in Section 40_05_31.01 for plastic piping and Section 40_05_19.01 for ductile iron piping. The schedule establishes standards for underground and aboveground piping installations, differentiating between process water, chemical injection, and drain systems to ensure compliance with applicable codes and the project's operational requirements while maintaining the facility's function as the county's sole drinking water source during construction.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
301 NORTH CATTLEMEN ROAD, SUITE 302 SARASOTA, FLORIDA 34232 P 941-371-9832
pw://Carollo/Documents/FL/Collier County/204170-100000/04 Design/04 Specs/Carollo/Blend Tank/00_01_02_Addendum4.docx
COLLIER COUNTY
SOUTH COUNTY REGIONAL WATER TREATMENT PLANT
LIME SOFTENING IMPROVEMENTS - BLEND TANK
CLIENT PROJECT NO. 70283.2
ADDENDUM 4 ATTACHMENT
JUNE 2026
This item has been digitally signed and sealed by Anthony Ryan Horvat on the date adjacent to the seal.
The signature must be verified on any electronic copies.
Carollo Engineers, Inc.
301 North Cattlemen Road Suite 302 Sarasota, Florida 941-371-9832 (Ph)
Common Work Results for General Piping 40_05_00.01-13 204170-10 June 2026 – Addendum No. 4 pw://Carollo/Documents/FL/Collier County/204170-100000/04 Design/04 Specs/Carollo/Blend Tank/40_05_00.01 (Bid Set)
ATTACHMENT A - PIPE SCHEDULE
40_05_00.01-14 204170-10 June 2026 – Addendum No. 4 pw://Carollo/Documents/FL/Collier County/204170-100000/04 Design/04 Specs/Carollo/Blend Tank/40_05_00.01 (Bid Set)
PIPE SCHEDULE
Process Abbrev. Service
Nominal Diameter (inches) Material
Pressure Class Special
Thickness Class
Schedule Wall Thickness
Pipe Spec.
Section
Joints/ Fittings
Test Pressure/ Method Lining Coating
Service Conditions Comments
D Drain
Underground 1 - 12 PVC SCH 80 40_05_31.01 - Plastic Piping and Tubing
SW 15 feet/GR None None
Aboveground 0.5 - 6 PVC SCH 80 40_05_31.01 - Plastic Piping and Tubing
SW 15 feet/GR None None
Groundwater Dewatering
6 - 8 PVC SCH 40
40_05_31.01 - Plastic Piping and Tubing
SW 20 feet/GR None None
BFW
Blended
Finished Water
Post Blend
Tank (Underground)
42 DIP 150
40_05_19.01 - Ductile Iron
Pipe:
AWWA C151
RSMJ
125 psig/H
H
CM PEE
BTV
Blend Tank Vent Piping
Vent
12 DIP 150
40_05_19.01 - Ductile Iron
Pipe:
AWWA C151
FL N/A CM
EPP (EPU-
M-1;
Exposed)
Vent
12 DIP 150
40_05_19.01 - Ductile Iron
Pipe:
AWWA C151
FL N/A CM
EPP (EPX-
M-1-PWS;
Submerged)
LS
Lime Softened
Water
40_05_00.01-15 204170-10 June 2026 – Addendum No. 4 pw://Carollo/Documents/FL/Collier County/204170-100000/04 Design/04 Specs/Carollo/Blend Tank/40_05_00.01 (Bid Set)
Abbrev. Service
Nominal Diameter (inches) Material
Pressure Class Special
Thickness Class
Schedule Wall Thickness
Pipe Spec.
Section
Joints/ Fittings
Test Pressure/ Method Lining Coating
Service Conditions Comments
Filter Effluent
(Underground)
36 DIP 150
40_05_19.01 - Ductile Iron
Pipe:
AWWA C151
RSMJ
125 psig/H
H
CM PEE
ROP
Reverse Osmosis Permeate
RO Permeate from Degasifiers
42 DIP 150
40_05_19.01 - Ductile Iron
Pipe:
AWWA C151
RSMJ
125 psig/H
H
CM PEE
SHC
Chlorine Solution
(Chemical Piping)
SHC-1
& 2
Underground 2- 4 CPVC SCH 80 40_05_31.01 - Plastic Piping and Tubing
SW
1.5x Working
Pressure /
HH
None None Double
Containme nt
Provide 2”
– 4” carrier piping
SHC-1
& 2
Aboveground 2 - 4 CPVC SCH 80 40_05_31.01 - Plastic Piping and Tubing
SW
1.5x Working
Pressure /
HH
None None
Drain- To-
Waste Piping
Drain-To- Waste Piping
Underground 1/2 - 2 CPVC SCH 80 40_05_31.01 - Plastic Piping and Tubing
SW GR None None
40_05_00.01-16 204170-10 June 2026 – Addendum No. 4 pw://Carollo/Documents/FL/Collier County/204170-100000/04 Design/04 Specs/Carollo/Blend Tank/40_05_00.01 (Bid Set)
Nominal Diameter (inches) Material
Pressure Class Special
Thickness Class
Schedule Wall Thickness
Pipe Spec.
Section
Joints/ Fittings
Test Pressure/ Method Lining Coating
Service Conditions Comments
Aboveground 1/2 - 2 CPVC SCH 80 40_05_31.01 - Plastic Piping and Tubing
SW GR None None
AMS
Ammonia System
Underground 1 - 2 CPVC SCH 80
Plastic Piping and Tubing
SW
1.5x Working
Pressure /
HH
None None Double
Containme nt
Provide 2” carrier piping
Aboveground 1 CPVC SCH 80 40_05_31.01 - Plastic Piping and Tubing
SW
1.5x Working
Pressure /
HH
None None
CS
Sodium Hydroxide
Underground 1/2 - 2 CPVC SCH 80
Plastic Piping and Tubing
SW
1.5x Working
Pressure /
HH
None None Double
Containme nt
Provide 2” carrier piping
Aboveground 1/2 CPVC SCH 80 40_05_31.01 - Plastic Piping and Tubing
SW
1.5x Working
Pressure /
HH
None None
CRI
Corrosion Inhibitor
40_05_00.01-17 204170-10 June 2026 – Addendum No. 4 pw://Carollo/Documents/FL/Collier County/204170-100000/04 Design/04 Specs/Carollo/Blend Tank/40_05_00.01 (Bid Set)
Nominal Diameter (inches) Material
Pressure Class Special
Thickness Class
Schedule Wall Thickness
Pipe Spec.
Section
Joints/ Fittings
Test Pressure/ Method Lining Coating
Service Conditions Comments
Underground 1.5 - 4 CPVC SCH 80 40_05_31.01 - Plastic Piping and Tubing
SW
1.5x Working
Pressure /
HH
None None Double
Containme nt
Provide 4” carrier piping
Aboveground 1.5 CPVC SCH 80 40_05_31.01 - Plastic Piping and Tubing
SW
1.5x Working
Pressure /
HH
None None
Abbreviations:
1. The following abbreviations used in the column of test method refer to the respective methods as specified in Section 40_05_00.09 - Piping Systems Testing.
AM Air method GR Gravity method HH High head method LH Low head method SC Special case
2. Abbreviations to designate piping include the following:
AMS Ammonium Solution B&SP Bell and spigot BSP Black Steel Pipe CS Caustic Soda – Sodium Hydroxide CE Ceramic epoxy lining CI Cast iron CISP Cast iron soil pipe CL Class, followed by the designation CM Cement mortar CRI Corrosion Inhibitor CTP Coal tar pitch DIP Ductile iron piping EPP Epoxy polyurethane coating FL Flange
GA Gauge, preceded by the designation GE Grooved end joint GL Glass lined GSP Galvanized steel pipe MJ Mechanical joint MWA Mechanical wedge action NPS Nominal pipe size, followed by the number in inches psi pounds per square inch psig pounds per square inch gauge PE Polyethylene PEE Polyethylene encasement PTW Polyethylene tape wrap PVC Polyvinyl Chloride RPO Restrained push-on RSMJ Restrained Mechanical Joint SCH Schedule, followed by the designation SCRD Screwed-on SHC Sodium Hypochlorite SST Stainless steel SW Solvent welded VCP Vitrified clay piping WLD Weld
40_05_00.01-18 204170-10 June 2026 – Addendum No. 4 pw://Carollo/Documents/FL/Collier County/204170-100000/04 Design/04 Specs/Carollo/Blend Tank/40_05_00.01 (Bid Set)
| Carollo Engineers, Inc. | |
| 2026-06-29T18:32:13-0400 | |
| Anthony Ryan Horvat | |
| I am approving this document |