26-8683_Exhibit_M5_-_Electrical_Plans.pdf

PDF 2 MB Posted

Attached to
SCRWTP Lime Softening Improvements - Blend Tank
Solicitation number
26-8683
Issued by
Collier County, Florida

About this file

This electrical plans document pertains to the SCRWTP Lime Softening Improvements project located in Collier County, Florida, a construction project involving electrical system installation and upgrades for the South County Regional Water Treatment Plant. The project scope includes providing all materials and labor to install electrical systems as indicated on the drawings, including power, lighting, instrumentation, lightning protection, fiber optic, and low-voltage systems. The work encompasses the installation of conduit runs, conductors, control panels, grounding systems, lighting fixtures, and related electrical equipment throughout the facility. A non-mandatory pre-bid meeting is scheduled for June 9, 2026 at 11:00 AM at the SCRWTP location (3851 City Gate Drive, Naples, FL 34117), with sealed bids due no later than July 1, 2026 at 3:00 PM local time. Prospective bidders must register on the Collier County procurement portal to obtain the complete bid documents. The contractor must obtain all necessary permits including power, lighting, instrumentation, lightning protection, fiber optic, and low-voltage electrical demolition permits, with all associated fees included in the bid.

All equipment and materials must be new and UL-listed where applicable, with all conductors specified as copper (no aluminum unless specifically indicated). The contractor is responsible for testing all installed or modified systems and must provide a one-year guarantee against defects in material and workmanship from the date of acceptance. Shop drawings must be submitted for all electrical and control equipment, and all control panels must be constructed by a UL 508A-approved vendor bearing a UL 508A label. Installation must comply with the National Electrical Code 2020 (NFPA 70), Electrical Safety in the Workplace (NFPA 70E), Monroe County codes, and the latest Florida Building Code. The grounding system test must not exceed 10 ohms of dry resistance within a 48-hour span, with additional grounding installed at no extra cost to meet this requirement. The contractor must coordinate work with the engineer and owner, visit the site prior to bidding to become familiar with existing conditions, and provide as-built drawings and manuals in accordance with Florida Building Code requirements.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EC- MOUNTED TO EXPOSED CEILING

H- HARSH ENVIRONMENT RATED

EC- MOUNTED TO EXPOSED CEILING

SECURITY CARD READERCR

THERMAL SWITCH

TRANSFORMER

TWISTED SHIELDED PAIR

UNDER VOLTAGE RELAY

VOLTMETER SWITCH

VARIABLE FREQUENCY DRIVE

VOLTMETER, VOLT

WATTHOUR DEMAND METER

WEATHERPROOF

SWITCHBOARD

SOLENOID VALVE

STAINLESS STEEL

VOLTAGE STARTER

SOLID STATE REDUCED

SOLID NEUTRAL

SYMMETRICAL

SWITCHGEAR

TIME DELAY RELAY

TERMINAL BOARD

TERMINAL JUNCTION BOX

THERMOSTAT

RIGID GALVANIZED STEEL

MAIN CIRCUIT BREAKER

RIGID STEEL CONDUIT

REMOTE TELEMETRY UNIT

SPACE HEATER

SUPPLY FAN

SURGE CAPACITOR

MANUFACTURER'S

NORMALLY OPEN

NAMEPLATE

ASSOCIATION

OVERLOAD RELAY

POWER PANEL (480VAC)

PHASE MONITOR, POWER METER

PHOTOCELL

PRESSURE SWITCH

POTENTIAL TRANSFORMER

POLYVINYL CHLORIDE CONDUIT

ROOT MEAN SQUARE

RECEPTACLE

NOT TO SCALE

MOTOR STARTER

MERCURY VAPOR

MOTOR HEATER, MANHOLE

MAIN LUGS ONLY

MINI POWER ZONE

MOTOR CONTROL CENTER

MAIN DISTRIBUTION PANEL

MANUFACTURER SUPPLIED

MOTOR TEMPERATURE

NATIONAL ELECTRIC

NORMALLY CLOSED

DESCRIPTION

CRE-WEATHERPROOFWP- CORROSION

INDICATED OTHERWISE. 4X = NEMA 4X SS

JUNCTION BOX NEMA 12 ENCLOSURE UNLESS

FIRE ALARM HORN/STROBE LIGHT

TELEPHONE/DATA RECEPTACLE MOUNTED FLUSH IN FLOOR

TELEPHONE/DATA RECEPTACLE (OUTLET BOX, 18" AFF)

RECEPTACLE, SPECIAL PURPOSE - AMPERAGE AS INDICATED.

CONVENIENCE RECEPTACLE - 20A DUPLEX UNLESS SPECIFIED

WEATHERPROOF

CONVENIENCE RECEPTACLE - 20A DUPLEX UNLESS SPECIFIED

OTHERWISE. LOCATED ABOVE COUNTER TOP

CONVENIENCE RECEPTACLE - 20A DUPLEX UNLESS SPECIFIED

OTHERWISE. MOUNTED FLUSH IN FLOOR.

CONVENIENCE RECEPTACLE - 20A QUADROPLEX UNLESS SPECIFIED

GFI-GROUND FAULT INTERRUPTER

GFI-GROUND FAULT INTERRUPTER

FIRE ALARM STROBE LIGHT

FIRE ALARM PULL STATION

F

F

F

J

W - WALL MOUNTED, 54" AFF

OTHERWISE

OTHERWISE

TWIST LOCKTL-

WP-

GROUND

MILLIAMPS

MAGNETIC CONTACTOR COIL

LIQUID TIGHT FLEX CONDUIT

LIGHTING PANEL (PANELBOARD)

LIGHTING

(PANELBOARD)

JUNCTION BOX

KIRK KEY INTERLOCK

KEY INTERLOCK

LIMIT SWITCH

LIGHTING CONTACTOR

LOCAL/REMOTE, LATCHING RELAY

LIGHTNING ARRESTER

HEATING, VENTILATING & AIR

HIGH PRESSURE SODIUM

HIGH INTENSITY DISCHARGE

INTERRUPTING CAPACITY

INSTRUMENTATION AND

HAND/OFF/REMOTE

CONTROL

CONDITIONING

INSTRUMENT PANEL

INSTANTANEOUS

HANDHOLE

HAND/OFF/AUTO

OR MOTOR

GROUND FAULT RELAY

GROUND FAULT INTERRUPTER

GENERATOR

GREEN, GROUND

J, J-BOX

MA

M

LP

LT FLEX

LTG

LS

LR

LA

LC

KK

K

CORROSION RESISTANT

RESISTANT

CLOCK HANGER

CRE-

C-

HPS

IP

INST

I & C

IC

HVAC

GND

HOA

HOR

HID

HH

GFI

GFR

GEN

G

TS

W

XFMR

WHD

WP

UVR

VFD

VS

V

TYP

TSP

WATT

TYPICAL

SS

SYM

TJB

TDR

TB

T

SWBD

SWGR

SV

SW SWITCH

SSRVS

SH

S/N

SPD

SC

SF

RTU

SURGE PROTECTION DEVICE

CONDUIT

FLOOD LIGHTS - AIM IN THE DIRECTION SHOWN

CONDUIT, STUBBED AND CAPPED AS SHOWN

GROUND WIRE, 4/O UNLESS OTHERWISE NOTED

DOUBLE POLE

YARD CONDUIT. REFER TO YARD CONDUIT SCHEDULE

* ALL UNMARKED CONDUIT RUNS CONSIST OF

UNDERGROUND CONDUIT AND CONDUCTORS*

LIGHTING FIXTURE POWER AND SWITCHING LEGEND

EXPOSED CONDUIT AND CONDUCTORS*

IF NO Z INDICATED, CONNECT DIRECTLY TO CIRCUIT

HOME RUN - PANEL AND CIRCUIT NUMBER SHOWN

EXIT LIGHTS - SOLID SECTION IS DIRECTION OF FACE

EMERGENCY LIGHT WITH BATTERY PACK

CONDUIT/CONDUCTOR - REFER TO CIRCUIT SCHEDULE

6 FOOT GROUND WIRE PIGTAIL, 4/O UNLESS

WALL MOUNTED LUMINAIRE - NOT

LUMINAIRE AND POLE - NOT

FLUORESCENT LUMINAIRE, SURFACE OR LAY IN TYPE

CEILING MOUNTED DOWNLIGHT LUMINAIRE - NOT

2#12, 1#12G IN 3/4"C.

DIRECT BURIED CONDUIT

WALL SWITCH:

OTHERWISE NOTED

S

YCX

NOTE:

2- 3- 4-

THREE WAY

FOUR WAY

X=FIXTURE TYPE

Y=PANEL-CIRCUIT BRKR

Z=SWITCH

BREAKER.

NOT USED

NOT USED

LPA-2

[B2]

(TYP)X

Z

Y

X

X

NOT USED

TERMINAL JUNCTION BOX

TELEPHONE TERMINAL CABINET

USED

NOT USED

USED

USED

ELECTRICAL EQUIPMENT

X

X

X

X

TTC

X

SYMBOL DESCRIPTION

ABBREVIATIONS

ADJUSTABLE FREQUENCY DRIVE

ELECTRICAL GROUND

ABOVE FINISHED GRADE

CURRENT TRANSFORMER

ELAPSED TIME METER

FULL VOLTAGE NON-REVERSING

STARTER

FLOAT SWITCH, FLOW SWITCH

FLUORESCENT

FLOW METER

FLOW TRANSMITTER

FUTURE

FLOOR

EXISTING

DIRECT CURRENT

EXHAUST FAN

FLOW INDICATOR

FEEDER

FUSE

DIVISION

CONTROL POWER TRANSFORMER

ALTERNATING CURRENT

AUTOMATIC TRANSFER

ABOVE FINISHED FLOOR

COMBINATION MOTOR STARTER

BREAKER

CONTROL RELAY

CONDUIT, CONTACTOR

CIRCUIT BREAKER

BYPASS CONTACTOR

CIRCUIT

SWITCH

AMMETER, AMPERE

AMPERE FRAME

AIR SUPPLY UNIT

AMMETER SWITCH,

AMPERE SENSOR

CR

KEY OPERATED

PILOT LIGHT

DIMMER

P-

D- K-

F, FU

FS

FVNR

FT

FUT

FLUOR

FM

FLR

FI

EXST

FDR

ETM

EG

DC

DIV

EF

CT

ASU

C

CMS

CPT

CB

CKT

BRKR

BC

ATS

AFD

AS

AFG

AFF

AF

AC

A

PANELPNL

PVC

RMS

RGS

RS

RCPT

PR

PS

PT

PP

PAIR

P

PC

PM

PH

PB

NTS

OL

NO

NP

POLE

PHASE

PULL BOX

DESCRIPTION

MS

NEMA

NC

N

MT

MTD

MSC

DETECTOR

NEUTRAL

CABLE

MOUNT

ABBREVIATIONS

MLO

MPZ

MH

MERC

MCB

MDP

MCC

BD

SD

RTU

D

R

FACP

FAAP

SD

HD

ELECTRICAL PLAN/LAYOUT

SYMBOL

FIRE ALARM CONTROL PANEL

FIRE ALARM HEAT DETECTOR

FIRE ALARM SMOKE DETECTOR

FIRE ALARM ANNUNCIATOR PANEL

BEAM DETECTOR, T=TRANSMITTER, R=RECEIVER

ABBREVIATIONS

DUCT SMOKE DETECTOR

REMOTE TELEMETRY UNIT

DESCRIPTION

THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS

OR ABBREVIATIONS MAY APPEAR ON THIS SHEET AND

NOT BE UTILIZED ON PROJECT.

OOX

XOO

1"C,1-25/C 1"C,2#12,1#12G

NORMALLY CLOSED

A - AMBER

B - BLUE

C - CLEAR

SCHEMATIC DIAGRAMS ONLY

INDICATING LIGHT - LETTER INDICATES COLOR

PUSH TO TEST AND CONNECT INDICATING LIGHT

C - CLEAR

REMOTE DEVICE

B - BLUE

A - AMBER

CONTROL TRANSFORMER

PUSH-BUTTON SWITCH, MOMENTARY CONTACT,

PUSH-BUTTON SWITCH, MOMENTARY CONTACT,

NORMALLY OPEN

GROUND FAULT RELAY WITH C.T.

A

A

GFR

120V

R - RED

W - WHITE

G - GREEN

W - WHITE

G - GREEN

R - RED

NOTE:

SYMBOL

H AO

O - OPEN CONTACT

X - CLOSED CONTACT

LINE WEIGHT

NEW

EXISTING

CONTACT POSITION INDICATED, CHART IDENTIFIES

SELECTOR SWITCH: MAINTAINED CONTACT WITH

POSITION

OFF

GENERAL

DESCRIPTION

OPERATION

CKT.

O

HAND

X

O O

AUTO

X O

SYMBOL

ONE LINE DIAGRAMS, RISER DIAGRAMS AND SCHEMATICS

SURGE PROTECTION DEVICE

V - VOLTS

A - AMPS

UTILITY METER

CURRENT TRANSFORMER, NUMBER OF

TRANSFORMER, VOLTAGES, PHASE AND

METER SCALE RANGE SHOWN IF REQUIRED

CAPACITOR OR SURGE CAPACITOR

RATING INDICATED AS APPLICABLE

LIGHTNING ARRESTER

WINDINGS INDICATED

X

CPT

SPD

0-600V

GROUND

FUSE

G

M

GENERATOR

K-4 RATED

480-120 /208V

3Ø

15 KVA,

(3)

PM - PHASE MONITOR

P - POWER METER

NOTC

TDX

CRX

LRX

(L)

CRX

CRX

ETM

4X

4X

DESCRIPTION

M

SYMBOL

4X

LC 30

4X

F 60

4X

PB

4X

S M

NCTC=NORMALLY CLOSED TIMED CLOSED AFTER OPEN

NOTO=NORMALLY OPEN TIMED OPEN AFTER CLOSE

COMBINATION (FUSE OR CIRCUIT BREAKER AS INDICATED).

NEMA 12 ENCLOSURE UNLESS INDICATED OTHERWISE.

MAGNETIC STARTER, NEMA SIZE INDICATED, NEMA 12

CONTROL DIAGRAM. 4X = NEMA 4X 316 STAINLESS STEEL

CONTACT - NORMALLY OPEN WITH COIL INDICATED

CONTACT - NORMALLY CLOSED WITH COIL INDICATED

NCTO=NORMALLY CLOSED TIMED OPEN

NOTC=NORMALLY OPEN TIMED CLOSED

TIME DELAY RELAY, X=SEQUENTIAL NUMBER

CONTROL RELAY, X=SEQUENTIAL NUMBER

L - LATCH, U - UNLATCH

LATCHING RELAY, X=SEQUENTIAL NUMBER

OPENS ON FALLING TEMPERATURE

CLOSES ON RISING TEMPERATURE,

CLOSES ON FALLING TEMPERATURE

OPENS ON RISING TEMPERATURE,

TEMPERATURE

ELECTRIC RESISTANCE HEATER

MAGNETIC STARTER, NEMA SIZE INDICATED,

SEE CONTROL SCHEMATIC DIAGRAM.

ENCLOSURE, UNLESS INDICATED OTHERWISE. SEE

4X = NEMA 4X 316 STAINLESS STEEL

ELAPSED TIME METER

NEMA 12 ENCLOSURE UNLESS INDICATED OTHERWISE.

MANUAL MOTOR STARTER SWITCH, NEMA 4X UNLESS

OTHERWISE NOTED. NUMBER OF POLES AS REQUIRED

PUSH-BUTTON STATION, NEMA 12 ENCLOSURE UNLESS

STEEL ENCLOSURE. SEE CONTROL DIAGRAMS FOR TYPE

INDICATED OTHERWISE. 4X = NEMA 4X 316 STAINLESS

LIGHTING CONTACTOR, CURRENT RATING INDICATED,

SEE CONTROL DIAGRAM FOR NUMBER OF POLES.

4X = NEMA 4X 316 STAINLESS STEEL

NON-FUSED DISCONNECT SWITCH, SIZE INDICATED,

ENCLOSURE, 4X = NEMA 4X 316 STAINLESS STEEL

3 POLE UNLESS INDICATED OTHERWISE, NEMA 12

ENCLOSURE, 4X = NEMA 4X 316 STAINLESS STEEL

3 POLE UNLESS INDICATED OTHERWISE, NEMA 12

(60 = SWITCH RATING: 40 = FUSE RATING)

FUSED DISCONNECT SWITCH, SIZE INDICATED

PUSH BUTTON REQUIRED

DESCRIPTION

DISTRIBUTION PANEL (480V)DP

INSTRUMENTATION MANHOLEIMH

MOTOR PROTECTION RELAYMPR

OPTICAL LINK MODULEOLM

FIBER OPTICFO

UPS UNINTERRUPTIBLE POWER

SUPPLY

CRE CORROSION RESISTANT

GROUND TEST WELL, SEE DETAIL

DEMOLITION TO BE REMOVED OR DELETED

INDICATES RACEWAY AND CIRCUIT

CONDUCTORS. FIRST NUMBER IS RACEWAY

SIZE. THE FOLLOWING NUMBERS ARE THE

CONDUCTOR QUANTITIES, SIZES, AND TYPES.

CONNECTION POINT TO EQUIPMENT SPECIFIED,

FURNISHED AND INSTALLED UNDER OTHER

SECTIONS. RACEWAY, CONDUCTOR AND

CONNECTION IN THIS SECTION.

TYPE 1

PUSH BUTTON SWITCH, MAINTAINED CONTACTS

WITH MECHANICAL INTERLOCK

FUSED SWITCH, SWITCH AND FUSE CURRENT

RATING INDICATED, 3 POLE UNLESS INDICATED

OTHERWISE.

CIRCUIT BREAKER, THERMAL MAGNETIC TRIP

SHOWN, 3 POLE UNLESS INDICATED OTHERWISE.

MOTOR CIRCUIT PROTECTOR, MAGNETIC, 3 POLE

UNLESS INDICATED OTHERWISE.

MAGNETIC STARTER WITH NEMA SIZE INDICATED

OVERLOAD RELAY HEATER

MOTOR, SQUIRREL CAGE INDUCTION UNLESS

OTHERWISE NOTED - HORSEPOWER INDICATED

DRAWOUT FUSED SWITCH, LOW OR MEDIUM

VOLTAGE 600= FRAME RATING, 400=FUSE RATING

DRAWOUT CIRCUIT BREAKER, MEDIUM VOLTAGE

1200= FRAME RATING, 1200=TRIP SETTING

DRAWOUT CIRCUIT BREAKER, LOW VOLTAGE

600= FRAME RATING, 400=TRIP SETTING

SWITCH - CURRENT RATING INDICATED, 3 POLE

UNLESS INDICATED OTHERWISE.

CAM

X

SURVEILLANCE CAMERA

X - 90, 180 OR 360 CAMERA

DS SECURITY SYSTEM

DOOR SWITCH

GROUND ROD - 5/8" x 20' COPPER CLAD UNLESS OTHERWISE NOTED.

COUPLING TWO 10' RODS IS ACCEPTABLE.

DATEREV BY DESCRIPTION

DATE

CHECKED

DRAWN

DESIGNED

204170

JOB NO.

DRAWING NO.

SHEET NO.

SCALES ACCORDINGLY

VERIFY SCALES

THIS SHEET, ADJUST

IF NOT ONE INCH ON

BAR IS ONE INCH ON

ORIGINAL DRAWING

0 1"

OF

COLLIER COUNTY

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G G

00GE01

4701 N FEDERAL HWY, STE 390

POMPANO BEACH, FL 33064

PHONE (561) 210-5715

ADS

SIDZ

MDG

SCRWTP LIME SOFTENING IMPROVEMENTS

301 NORTH CATTLEMEN ROAD, SUITE 302

SARASOTA, FL. 343232

PHONE: (941) 371-9832 FAX: (941) 371-9873

CA 00008571

PROJECT NO.

LA

ST

S

AV

ED

B

Y:

FILE NAME: 00GE01 - ELECTRICAL LEGEND.DWG

AD

S

204170-100000

39APRIL 2026

BID DOCUMENTS

THIS ITEM HAS BEEN

DIGITALLY SIGNED AND

SEALED BY

ALEKSANDAR D.

STOJANOVIC ON THE

DATE ADJACENT TO

THE SEAL.

THE SIGNATURE MUST

BE VERIFIED ON ANY

ELECTRONIC COPIES.

ELECTRICAL

LEGEND

GENERAL NOTES AND SPECIFICATIONS:

1. NOT USED.

2. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS AND LABOR TO INSTALL THE ELECTRICAL SYSTEMS AS INDICATED ON THE DRAWINGS. ITEMS NOT SHOWN

BUT OBVIOUSLY NECESSARY FOR COMPLETION OF THE WORK SHALL BE INCLUDED.

3. THE INSTALLATION SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE 2020 (NFPA 70), ELECTRICAL SAFETY IN THE WORKPLACE (NFPA 70E), ALL

MONROE COUNTY CODES AND LATEST FLORIDA BUILDING CODE.

4. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS TO INCLUDE, BUT ARE NOT LIMITED TO, INSPECTIONS AND APPROVALS AND TO INCLUDE ALL FEES AS PART OF HIS BID IF NOT OTHERWISE NOTED. THE FOLLOWING PERMITS ARE REQUIRED: POWER, LIGHTING, INSTRUMENTATION, LIGHTNING PROTECTION, FIBER OPTIC, LOW VOLTAGE AND ELECTRICAL DEMOLITION.

5. THE CONTRACTOR SHALL COORDINATE HIS WORK WITH THE ENGINEER AND THE OWNER.

6. THE CONTRACTOR SHALL, BEFORE SUBMITTING HIS BID, VISIT THE SITE OF THE PROJECT AND BECOME FAMILIAR WITH THE EXISTING CONDITIONS. NO ALLOWANCE WILL BE MADE FOR EXISTING CONDITIONS OR FAILURE OF THE CONTRACTOR TO OBSERVE THEM.

7. ALL EQUIPMENT AND MATERIAL SHALL BE NEW AND U.L. LISTED WHERE APPLICABLE.

8. THE CONTRACTOR IS RESPONSIBLE TO TEST ALL SYSTEMS INSTALLED OR MODIFIED UNDER THIS PROJECT AND REPAIR OR REPLACE ALL DEFECTIVE WORK TO

THE SATISFACTION OF THE ENGINEER AND OWNER.

9. ALL EQUIPMENT FURNISHED AND INSTALLED BY THE CONTRACTOR SHALL BE GUARANTEED AGAINST DEFECTS IN MATERIAL AND WORKMANSHIP FOR A PERIOD

OF ONE YEAR FROM DATE OF ACCEPTANCE.

10. ALL CONDUCTORS SHALL BE COPPER. NO ALUMINUM ALLOWED UNLESS SPECIFICALLY INDICATED ON DRAWINGS.

11. SHOP DRAWINGS SHALL BE SUBMITTED FOR ALL ELECTRICAL & CONTROL EQUIPMENT AND MATERIAL.

12. ALL CONTROL PANELS SHALL BE CONSTRUCTED BY A UL 508A APPROVED PANEL VENDOR AND SHALL BEAR A UL 508A LABEL ON THE PANEL.

13. THE DRAWINGS ARE NOT INTENDED TO SHOW THE EXACT LOCATION OF CONDUIT RUNS. THESE ARE TO BE COORDINATED WITH THE OTHER TRADES SO THAT

CONFLICTS ARE AVOIDED PRIOR TO INSTALLATIONS.

14. ALL LOCATIONS OF EQUIPMENT, PANELS ETC. ARE SHOWN FOR ILLUSTRATION PURPOSES. CONTRACTOR SHALL VERIFY AND COORDINATE EXACT LOCATION AND SIZE WITH ALL SUBCONTRACTORS AND EQUIPMENT SUPPLIERS PRIOR TO ANY INSTALLATION AND THEN INSTALL AS SUCH WITH CORRESPONDING

CONDUIT STUB-UPS.

15. SEE OTHER DISCIPLINE DRAWINGS FOR COORDINATION OF ALL DRAWINGS. ANY CONFLICTS SHALL BE BROUGHT TO THE ENGINEER'S ATTENTION AND MOVEMENT OF CONDUITS OR OTHER ELECTRICAL EQUIPMENT SHALL BE ACCOMPLISHED WITHOUT ANY ADDITIONAL COST FOR THE OWNER.

16. LOCATIONS OF MANHOLES, HANDHOLES AND PULL BOXES ARE APPROXIMATE. CONTRACTOR SHALL COORDINATE EXACT LOCATION WITH EXISTING AND NEW

PIPING OR CONDUIT AND ADJUST ACCORDINGLY.

17. NOT ALL CONDUITS SHOWN ON RISER AND ONE-LINE DIAGRAMS ARE SHOWN ON BUILDING LAYOUTS. CONTRACTOR SHALL SUPPLY ALL CONDUITS AND CABLES

AS SHOWN ON RISER AND ONE-LINE DIAGRAMS.

18. ALL CIRCUITS SHALL BE IDENTIFIED IN JUNCTION BOXES, PULL BOXES, CONTROL PANELS, PANELBOARDS, LIGHTING POLES, CONTROLLERS AND SERVICE

POINTS. IDENTIFICATION SHALL MATCH PANELBOARD SCHEDULES.

19. EXPOSED RUNS OF CONDUITS SHALL BE INSTALLED WITH RUNS PARALLEL OR PERPENDICULAR TO WALLS, STRUCTURAL MEMBERS OR INTERSECTIONS OF VERTICAL PLANES AND CEILINGS, WITH RIGHT ANGLE TURNS CONSISTING OF SYMMETRICAL BENDS OR PULL BOXES AS INDICATED ON THE DRAWINGS. BENDS

AND OFFSETS SHALL BE AVOIDED WHERE POSSIBLE.

20. INSTRUMENTATION IS LOW VOLTAGE SIGNALS SUCH AS 4-20MA, TELEPHONE COMMUNICATION, FIRE ALARM COMMUNICATION. POWER CONDUIT SHALL ONLY CROSS INSTRUMENTATION CONDUIT PERPENDICULARLY AT RIGHT ANGLES WITH 6" SEPARATION.

21. CONDUCTOR PULLING TENSIONS SHALL NOT EXCEED MANUFACTURER'S RECOMMENDATION. CONTRACTOR SHALL INSTALL PULL BOXES TO MEET

MANUFACTURER'S REQUIREMENTS.

22. MINIMUM DISTANCE ALLOWED BETWEEN POWER CONDUITS AND INSTRUMENTATION CONDUITS SHALL BE:

VOLTAGE DISTANCE

4160V - 15KV TO INST. CONDUIT 3 FT

480V - 600V TO INST CONDUIT 2 FT

120V TO INST. CONDUIT 1 FT

23. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONDUIT AND WIRING INSTALLATION FOR ALL VENDOR PROVIDED EQUIPMENT (PACKAGE SYSTEMS). IF THE SHOP DRAWINGS DIFFER FROM THE DESIGNED FACILITIES, THE CONTRACTOR SHALL REDESIGN THE FACILITIES AND SUBMIT THE REVISED DESIGN FOR THE ENGINEER'S APPROVAL ALONG WITH THE SHOP DRAWINGS. THERE SHALL BE NO ADDITIONAL COST TO THE OWNER FOR THE REDESIGN NOR FOR ANY ADDITIONAL CONDUITS AND WIRING. DURING SUBMITTAL THE CONTRACTOR SHALL VERIFY ALL SUPPLIED BREAKER SIZES FOR ALL PACKAGED SYSTEMS SUCH AS HVAC, EXHAUST FANS, MIXERS, CHEMICAL PUMPS ETC. AND MODIFY ALL BREAKERS IN MCC'S AND PANELBOARDS ACCORDINGLY WITHOUT ANY ADDITIONAL

COST TO THE OWNER.

24. ALL EXCAVATIONS FOR CONDUITS, HANDHOLES, MANHOLES AND PULLBOXES NEAR EXISTING PIPING, CONDUIT AND EQUIPMENT SHALL BE HAND EXCAVATED

AND COORDINATED WITH THE OWNER.

25. MINIMUM DEPTH FROM TOP OF DUCT BANKS OR CONDUITS TO FINISHED GRADE SHALL BE 24" UNLESS OTHERWISE NOTED.

26. COLORED WARNING TAPE 6" WIDE SHALL BE INSTALLED 8" BELOW FINISHED GRADE DIRECTLY ABOVE ALL UNDERGROUND YARD CONDUITS ACCORDING TO THE

FOLLOWING SCHEDULE:

POWER: RED

ALL OTHER CONDUITS: GREEN

27. CONTRACTOR SHALL RESTORE SIDEWALKS, ROADWAYS, SOD AND SPRINKLER SYSTEM PIPING TO MATCH EXISTING, AFTER THE COMPLETION OF THE CONDUIT

AND PULLBOX INSTALLATION.

28. GROUNDING SHALL BE INSTALLED IN ACCORDANCE WITH NEC 2020, ARTICLE 250. THE GROUNDING SYSTEM TEST SHALL NOT EXCEED A 48 HOUR SPAN DRY RESISTANCE OF 10 OHMS. ADDITIONAL GROUNDING TO MEET THIS REQUIREMENT SHALL BE INSTALLED AT NO EXTRA COST. GROUNDING AND BONDING CONNECTIONS SHALL NOT BE PAINTED. ALL GROUNDING CONNECTIONS SHALL BE EXOTHERMIC UNLESS SPECIFICALLY INDICATED OTHERWISE.

29. AN EQUIPMENT GROUND WIRE SIZED PER NEC SHALL BE PULLED IN ALL ELECTRICAL CONDUITS, POWER AND CONTROL, AS SHOWN ON PLANS.

30. ALL ENCLOSURES, TJB, WIREWAY, PULL BOXES (EXCEPT IN-GROUND PULL BOXES AND MANHOLES) ETC. SHALL CONTAIN A GROUNDING BUS. CONNECT ALL RACEWAY BONDS TO THIS BUS VIA GROUNDING BUSHING AND EXTEND BONDING JUMPER FROM THIS BUS TO THE ENCLOSURE.

31. PRIMARY BUILDING GROUNDING SHALL BE AN EMBEDDED GRID OF MINIMUM #4/0 AWG WIRE INSTALLED IN THE FOUNDATION AND AROUND THE BUILDING PERIMETER TO FORM A COMPLETE LOOP. SECONDARY GROUND CONNECTIONS TO ALL METAL EQUIPMENT, HAND RAILS, STRUCTURAL STEEL, CONCRETE PADS, REBAR ETC. SHALL HAVE A MINIMUM #4 STRANDED COPPER CONDUCTOR BONDED USING APPROVED LUGS OR EXOTHERMIC CONNECTIONS. ALL EQUIPMENT GROUNDING CONDUCTORS PENETRATING CONCRETE SLABS OR FINISHED GRADE SHALL HAVE A 72" CONDUCTOR PIGTAIL AT EACH LOCATION FOR

CONNECTION TO EQUIPMENT.

32. ALL CONCRETE ENCASED DUCTBANKS SHALL CARRY A MINIMUM #4/0 AWG BARE COPPER GROUND WIRE, OVER THE ENTIRE LENGTH, WHICH SHALL BE CONNECTED TO THE SITE GROUNDING GRID AND GROUND RODS LOCATED CONNECTING MANHOLES, HANDHOLES OR PULL BOXES.

33. CONTRACTOR SHALL CORE DRILL EXISTING CONCRETE WALLS, FLOORS, MANHOLES, HANDHOLES AND PULL BOXES FOR CONDUIT PENETRATIONS. SEAL PENETRATIONS WITH NON-SHRINK GROUT OR APPROPRIATE FIRE RATED DEVICES WHERE APPLICABLE.

34. ALL CONDUITS PENETRATING RATED FIRE WALLS OR RATED FIRE FLOORS SHALL BE INSTALLED WITH U.L. APPROVED DEVICES TO MAINTAIN THE FIRE RATING

OF THE WALL OR FLOOR PENETRATED.

35. PROVIDE CONDUIT DUCT SEAL AT ALL CONDUIT ENDS.

36. ALL SPARE CONDUITS SHALL BE SEALED WITH A CAP AT BOTH ENDS AND A PULL STRING INSTALLED WITH IDENTIFICATION ON BOTH ENDS.

37. ALL RECEPTACLES SHALL BE INSTALLED 18" AFF UNLESS OTHERWISE NOTED. LIGHT SWITCHES SHALL BE MOUNTED 48" AFF UNLESS OTHERWISE NOTED.

38. ALL RECEPTACLES WITHIN 6' OF A SINK SHALL BE GFI.

39. FLEXIBLE CONDUITS SHALL BE USED TO TERMINATE ALL MOTORS AND OTHER VIBRATING EQUIPMENT AND SHALL BE BETWEEN 18" AND 3' IN LENGTH.

40. TYPEWRITTEN PANEL SCHEDULES SHALL BE INSTALLED IN EACH PANELBOARD, AND TYPEWRITTEN TERMINAL BLOCK SCHEDULES IN EACH CONTROL CABINET.

41. ALL SPD'S SHALL BE INTEGRAL TO THE NEW EQUIPMENT SHOWN AND SUPPLIED AS ONE UNIT AND ONE U.L. ENTITY.

42. ALL MATERIAL IN DESIGNATED CORROSIVE AREAS SHALL BE NEMA 4X STAINLESS STEEL OR NON-METALLIC.

43. ALL OUTDOOR LIGHTING FIXTURES SHALL BE OF COPPER FREE CONSTRUCTION.

44. ALL REFERENCES TO SS OR STAINLESS STEEL SHALL BE 316 STAINLESS STEEL.

45. CONTRACTOR SHALL BALANCE PANELBOARD LOADS AT THE END OF THE PROJECT.

46. ALL YARD CONDUITS SHALL BE CONCRETE ENCASED UNLESS NOTED OTHERWISE. REFER TO DRAWING 00TE01 FOR INSTALLATION DETAILS.

47. ALL CONDUIT CONNECTIONS TO NEMA 4X PANELS/ENCLOSURES SHALL USE MYERS HUBS (OR EQUAL) TO MAINTAIN 4X RATING.

48. PROVIDE VFD RATED CABLE FOR ALL VFD'S FROM VFD TO MOTOR WHERE INDICATED ON DRAWINGS PER SPECIFICATION 26_05_05. INSTALL VFD RATED CABLE

PER MANUFACTURER'S INSTRUCTIONS AND SPECIFICATION 26_05_05.

49. CONTRACTOR SHALL PROVIDE FOR A SATISFACTORY NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) INSPECTION FOR ALTERATIONS TO CONTROL

PANELS, ELECTRICAL EQUIPMENT, OR ASSEMBLIES TO MAINTAIN THE ORIGINAL UL RATING.

50. PROVIDE AS-BUILT DRAWINGS AND MANUALS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 13-413.ABC.2.1 & 13-413.ABC.2.2

51. CONDUCTORS SHALL BE STRANDED COPPER, NO ALUMINUM ALLOWED UNLESS SPECIFICALLY INDICATED ON DRAWINGS. POWER CONDUCTORS SHALL BE XHHW IN WET LOCATIONS OR IN UNDERGROUND RACEWAYS AND SHALL BE THWN/THHN IN DRY LOCATIONS.

52. INSTRUMENTATION AND CONTROL CIRCUITS ORIGINATING FROM CONTROL PANELS CONTAINING A PLC ARE CLASSIFIED AS CLASS 1 POWER-LIMITED CIRCUITS PER NEC ARTICLE 725. CONTROL AND INSTRUMENTATION AND CONTROL CIRCUITS ORIGINATING FROM CONTROL PANELS WITHOUT A PLC OR FROM A MOTOR CONTROL CENTER ARE CLASSIFIED AS CLASS 1 REMOTE CONTROL AND SIGNALING CIRCUITS PER NEC ARTICLE 725.

53. ALL VERTICAL CONDUIT PENETRATIONS FROM CONCRETE SLAB SHALL HAVE A MAINTENANCE PAD TO PREVENT CORROSION.

54. AFFIX NAMEPLATES TO ALL DISCONNECT SWITCHES WITH THE NAME OF THE EQUIPMENT SERVED BY THE DISCONNECT SWITCH IN ACCORDANCE WITH NEC

ARTICLE 110.22. NAMEPLATES SHALL BE AS DESCRIBED IN SPECIFICATION 26_05_04.

55. THERE ARE NO CLASSIFIED AREAS PERTAINING TO NEC ARTICLE 500 IN THIS FACILITY.

56. ALL CONDUITS SHALL BE MEGGER TESTED AFTER INSTALLATION AND INSULATION MUST BE IN COMPLIANCE WITH THE INSULATED POWER CABLE ENGINEERS ASSOCIATION MINIMUM VALUES OF INSULATION RESISTANCE. MEGGER TEST RESULTS SHALL BE SUBMITTED TO ENGINEER FOR APPROVAL.

DATEREV BY DESCRIPTION

DATE

CHECKED

DRAWN

DESIGNED

204170

JOB NO.

DRAWING NO.

SHEET NO.

SCALES ACCORDINGLY

VERIFY SCALES

THIS SHEET, ADJUST

IF NOT ONE INCH ON

BAR IS ONE INCH ON

ORIGINAL DRAWING

0 1"

OF

COLLIER COUNTY

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G G

00GE02

4701 N FEDERAL HWY, STE 390

POMPANO BEACH, FL 33064

PHONE (561) 210-5715

ADS

SIDZ

MDG

SCRWTP LIME SOFTENING IMPROVEMENTS

301 NORTH CATTLEMEN ROAD, SUITE 302

SARASOTA, FL. 343232

PHONE: (941) 371-9832 FAX: (941) 371-9873

CA 00008571

PROJECT NO.

LA

ST

S

AV

ED

B

Y:

FILE NAME: 00GE02 - ELECTRICAL NOTES.DWG

AD

S

204170-100000

39APRIL 2026

BID DOCUMENTS

THIS ITEM HAS BEEN

DIGITALLY SIGNED AND

SEALED BY

ALEKSANDAR D.

STOJANOVIC ON THE

DATE ADJACENT TO

THE SEAL.

THE SIGNATURE MUST

BE VERIFIED ON ANY

ELECTRONIC COPIES.

ELECTRICAL

NOTES

MT42X24

DATEREV BY DESCRIPTION

DATE

CHECKED

DRAWN

DESIGNED

204170

JOB NO.

DRAWING NO.

SHEET NO.

SCALES ACCORDINGLY

VERIFY SCALES

THIS SHEET, ADJUST

IF NOT ONE INCH ON

BAR IS ONE INCH ON

ORIGINAL DRAWING

0 1"

OF

COLLIER COUNTY

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G G

00E01

4701 N FEDERAL HWY, STE 390

POMPANO BEACH, FL 33064

PHONE (561) 210-5715

ADS

SIDZ

MDG

SCRWTP LIME SOFTENING IMPROVEMENTS

301 NORTH CATTLEMEN ROAD, SUITE 302

SARASOTA, FL. 343232

PHONE: (941) 371-9832 FAX: (941) 371-9873

CA 00008571

PROJECT NO.

LA

ST

S

AV

ED

B

Y:

FILE NAME: 00E01 - SITE PLAN.DWG

AD

S

204170-100000

39APRIL 2026

BID DOCUMENTS

THIS ITEM HAS BEEN

DIGITALLY SIGNED AND

SEALED BY

ALEKSANDAR D.

STOJANOVIC ON THE

DATE ADJACENT TO

THE SEAL.

THE SIGNATURE MUST

BE VERIFIED ON ANY

ELECTRONIC COPIES.

ELECTRICAL

NEW PROPOSED

BLEND TANK

ELECTRICAL

EQUIPMENT

BUILDING

0 16' 32' 64'

SCALE: 1/32" = 1'-0"

LEAK DETECTION

VAULT 1

LEAK DETECTION

VAULT 2

1. CONTRACTOR SHALL PROVIDE AND INSTALL NEW LIGHTING

PROTECTION SYSTEM FOR ALL NEW STRUCTURES, BLEND TANK,

AS PER SPECIFICATION 26_41_00.

GROUNDING NOTES

YC07

YC16

YC06

YC15

YC01

YC02

YC03

YC04

YC05

YC08

YC09

YC10

YC11

YC12

YC13

YC14

SAMPLE PANEL 1

SAMPLE PANEL 2

SITE PLAN

SAMPLE

PUMP

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text

CO

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text 12.1

AutoCAD SHX Text 12.1

AutoCAD SHX Text 12.2

AutoCAD SHX Text 12.1

AutoCAD SHX Text 11.8

AutoCAD SHX Text 11.6

AutoCAD SHX Text 11.5

AutoCAD SHX Text 11.5

AutoCAD SHX Text 11.4

AutoCAD SHX Text 11.3

AutoCAD SHX Text 11.3

AutoCAD SHX Text 11.0

AutoCAD SHX Text 11.0

AutoCAD SHX Text 11.1

AutoCAD SHX Text 11.1

AutoCAD SHX Text 11.2

AutoCAD SHX Text 11.5

AutoCAD SHX Text

36" TOP OF PIPE ELEV AT NG = 11.05

AutoCAD SHX Text

36" TOP OF PIPE ELEV = 15.14

AutoCAD SHX Text

36" TOP OF PIPE ELEV = 15.23

AutoCAD SHX Text

36" TOP OF PIPE ELEV AT NG = 11.30

AutoCAD SHX Text 10.5

AutoCAD SHX Text 10.5

AutoCAD SHX Text 11.0

AutoCAD SHX Text 10.8

AutoCAD SHX Text 11.0

AutoCAD SHX Text 11.1

AutoCAD SHX Text 11.2

AutoCAD SHX Text 11.1

AutoCAD SHX Text 11.0

AutoCAD SHX Text 11.0

AutoCAD SHX Text 11.2

AutoCAD SHX Text 11.4

AutoCAD SHX Text 11.3

AutoCAD SHX Text 10.9

AutoCAD SHX Text 10.8

AutoCAD SHX Text 10.7

AutoCAD SHX Text

FLAG POLE

AutoCAD SHX Text 10.78

'EXISTING 4LP1'

POWERED BY: DP-6

LOCATION: BLEND TANK/TRANSFER PUMP ELECTRICAL BUILDING

AIT-410A

BLEND

TANK

pH/TEMP

[B2]

AIT-411A

BLEND

TANK

CL2 FREE

[B2]

LIT-412

BLEND

TANK

LEVEL

[B2]

AIT-410

BLEND

TANK pH

[B2]

AIT-411

BLEND

TANK

CL2 TOTAL

[B2]

LSH410A

VAULT 1

LEAK

DETECTION

ALARM BOX

[B2]

LSH410B

VAULT 2

LEAK

DETECTION

ALARM BOX

[B2]

SAMPLE PUMP

3/4 6.9A

[B2]

[B2]

SM

BLEND TANK

LIGHT POLE 1

[B2]

BLEND TANK

LIGHT POLE 2

[B2]

S4X [B2]

YC06 YC07 YC08 YC09YC05YC04YC03YC02YC01

DATEREV BY DESCRIPTION

DATE

CHECKED

DRAWN

DESIGNED

204170

JOB NO.

DRAWING NO.

SHEET NO.

SCALES ACCORDINGLY

VERIFY SCALES

THIS SHEET, ADJUST

IF NOT ONE INCH ON

BAR IS ONE INCH ON

ORIGINAL DRAWING

0 1"

OF

COLLIER COUNTY

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G G

00E02

4701 N FEDERAL HWY, STE 390

POMPANO BEACH, FL 33064

PHONE (561) 210-5715

ADS

SIDZ

MDG

SCRWTP LIME SOFTENING IMPROVEMENTS

301 NORTH CATTLEMEN ROAD, SUITE 302

SARASOTA, FL. 343232

PHONE: (941) 371-9832 FAX: (941) 371-9873

CA 00008571

PROJECT NO.

LA

ST

S

AV

ED

B

Y:

FILE NAME: 00E02 - POWER RISERS.DWG

AD

S

204170-100000

39APRIL 2026

BID DOCUMENTS

THIS ITEM HAS BEEN

DIGITALLY SIGNED AND

SEALED BY

ALEKSANDAR D.

STOJANOVIC ON THE

DATE ADJACENT TO

THE SEAL.

THE SIGNATURE MUST

BE VERIFIED ON ANY

ELECTRONIC COPIES.

ELECTRICAL

POWER RISER

PLC 2

LOCATION:

EXISTING

BLEND

TANK /

TRANSFER

PUMPS

ELECTRICAL

BUILDING

AIT-410A BLEND TANK pH/TEMP [S1]

[3/4"C, MSC]

AE-410A

AIT-411A BLEND TANK CL2 FREE

[R1]

[3/4"C, MSC]

AE-411A

LIT-412 BLEND TANK LEVEL

[R1]

[3/4"C, MSC]

LE-412

AIT-411 BLEND TANK CL2 TOTAL

[R1]

[3/4"C, MSC]

AE-411

AIT-410 BLEND TANK pH [R1]

[3/4"C, MSC]

AE-410

LEAK

DETECTION

ALARM

BOX

LSH-410A

LEAK DETECTION - CORROSION INHIBITOR

LEAK DETECTION - CAUSTIC SODA (SODIUM HYDROXIDE)

[A1]

[3/4"C, MSC]

[3/4"C, MSC]

LD-CRI

LD-CS

LEAK

DETECTION

ALARM

BOX

LSH-410B

[A1]

[3/4"C, MSC]

[3/4"C, MSC]

LD-SHC-1

LD-AMS

LEAK DETECTION - SODIUM HYPOCHLORITE 1

LEAK DETECTION - SODIUM HYPOCHLORITE 2

LEAK DETECTION - AMMONIA SOLUTION

YC10

YC11

YC12

YC13

YC14

YC15

YC16

SAMPLE PANEL 1

SAMPLE PANEL 2

[3/4"C, MSC]

LD-SHC-2

DATEREV BY DESCRIPTION

DATE

CHECKED

DRAWN

DESIGNED

204170

JOB NO.

DRAWING NO.

SHEET NO.

SCALES ACCORDINGLY

VERIFY SCALES

THIS SHEET, ADJUST

IF NOT ONE INCH ON

BAR IS ONE INCH ON

ORIGINAL DRAWING

0 1"

OF

COLLIER COUNTY

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G G

00E03

4701 N FEDERAL HWY, STE 390

POMPANO BEACH, FL 33064

PHONE (561) 210-5715

ADS

SIDZ

MDG

SCRWTP LIME SOFTENING IMPROVEMENTS

301 NORTH CATTLEMEN ROAD, SUITE 302

SARASOTA, FL. 343232

PHONE: (941) 371-9832 FAX: (941) 371-9873

CA 00008571

PROJECT NO.

LA

ST

S

AV

ED

B

Y:

FILE NAME: 00E03 - CONTROL RISERS.DWG

AD

S

204170-100000

39APRIL 2026

BID DOCUMENTS

THIS ITEM HAS BEEN

DIGITALLY SIGNED AND

SEALED BY

ALEKSANDAR D.

STOJANOVIC ON THE

DATE ADJACENT TO

THE SEAL.

THE SIGNATURE MUST

BE VERIFIED ON ANY

ELECTRONIC COPIES.

ELECTRICAL

CONTROL RISER

CIRCUIT SCHEDULE 3PH, 3W OR 1PH, 3W

CKT I.D. CONDUIT AND CONDUCTOR SIZE

[A3] [3/4 ”C, 3#12, 1#12G] [B3] [3/4 ”C, 3#10, 1#10G] [C3] [1”C, 3#8, 1#10G] [D3] [1”C, 3#6, 1#10G] [E3] [1 1/4 ”C, 3#4, 1#10G] [F3] [1 1/4 ”C, 3#4, 1#8G] [G3] [1 1/4 ”C, 3#3, 1#8G] [H3] [1 1/2 ”C, 3#2, 1#8G] [J3] [1 1/2 ”C, 3#1, 1#8G] [K3] [2 ”C, 3#1/O, 1#6G] [L3] [2”C, 3#2/O, 1#6G] [M3] [2”C, 3#3/O, 1#6G] [N3] [2 1/2 ”C, 3#4/O, 1#4G]

[P3] [2 1/2 ”C, 3-250KCMIL, 1#4G]

[Q3] [3 1/2”C, 3-500KCMIL, 1#3G]

[R3] 2 EA.[2 ”C, 3-3/O, 1#3G]

[S3] 2 EA.[2 1/2 ”C, 3-250KCMIL, 1#2G]

[T3] 2 EA.[3”C, 3-350KCMIL, 1#1G]

[U3] 2 EA.[4”C, 3-500KCMIL, 1#1/OG]

[V3] 2 EA.[4”C, 3-600KCMIL, 1#1/OG]

[W3] 3 EA.[3 1/2”C, 3-500KCMIL, 1#2/OG]

[X3] 4 EA.[3”C, 3-350KCMIL, 1#3/OG]

[Y3] 5 EA.[4”C, 3-500KCMIL, 1#4/OG]

[Z3] 6 EA.[4”C,3-500KCMIL, 1 -250KCMIL G]

[ZA3] 6 EA.[4”C,3-600KCMIL,1 -250KCMIL G]

[ZB3] 8 EA.[4”C,3-600KCMIL, 1 -600KCMIL G]

[ZC3] 8 EA.[4”C,3-600KCMIL, 1 -600KCMIL G/N]

[ZD3] 10 EA.[4”C,3-600KCMIL, 1 -600KCMILG]

CIRCUIT SCHEDULE 3PH, 4W

CKT I.D. CONDUIT AND CONDUCTOR SIZE

[A4] [3/4 ”C, 4#12, 1#12G] [B4] [3/4 ”C, 4#10, 1#10G] [C4] [1”C, 4#8, 1#10G] [D4] [1 1/4”C, 4#6, 1#10G] [E4] [1 1/4 ”C, 4#4, 1#10G] [F4] [1 1/4 ”C, 4#4, 1#8G] [G4] [1 1/2 ”C, 4#3, 1#8G] [H4] [1 1/2”C, 4#2, 1#8G] [J4] [2”C, 4#1, 1#8G] [K4] [2”C, 4#1/O, 1#6G] [L4] [2 1/2”C, 4#2/O, 1#6G] [M4] [2 1/2 ”C, 4#3/O, 1#6G] [N4] [3 ”C, 4#4/O, 1#4G]

[P4] [3”C, 4-250KCMIL, 1#4G]

[Q4] [3 1/2”C, 4-350KCMIL, 1#3G]

[R4] 2 EA.[2 1/2 ”C, 4#3/O, 1#3G]

[S4] 2 EA.[3”C, 4-250KCMIL, 1#2G]

[T4] 2 EA.[4”C, 4-350KCMIL, 1#1G]

[U4] 2 EA.[4”C, 4-500KCMIL, 1#1/O G]

[V4] 3 EA.[4”C, 4-350KCMIL, 1#1/O G]

[W4] 3 EA.[4”C, 4-500KCMIL, 1#2/O G]

[X4] 4 EA.[4”C, 4-350KCMIL, 1#3/O G]

[Y4] 5 EA.[4”C, 4-500KCMIL, 1#4/O G]

[Z4] 6 EA.[4”C, 4-500KCMIL, 1-250KCMIL G]

CIRCUIT SCHEDULE 1PH, 2W

CKT I.D. CONDUIT AND CONDUCTOR SIZE

[A2] [3/4 ”C, 2#12, 1#12G] [B2] [3/4 ”C, 2#12, 1#12G] [C2] [3/4 ”C, 2#10, 1#10G] [D2] [3/4 ”C, 2#8, 1#10G] [E2] [1 ”C, 2#6, 1#10G] [F2] [1”C, 2#4, 1#10G] [G2] [1”C, 2#4, 1#8G] [H2] [1 1/4 ”C, 2#3, 1#8G] [J2] [1 1/4 ”C, 2#2, 1#8G] [K2] [1 1/4 ”C, 2#1, 1#8G] [L2] [1 1/2 ”C, 2#1/O, 1#6G] [M2] [1 1/2 ”C, 2#2/O, 1#6G] [N2] [2”C, 2#3/O, 1#6G] [P2] [2”C, 2#4/O, 1#4G]

[Q2] [2 1/2 ”C, 2-250KCMIL, 1#4G]

[R2] [2 1/2 ”C, 2-350KCMIL, 1#4G]

CIRCUIT SCHEDULE - CONTROL,

INSTRUMENTATION

CKT I.D. CONDUIT AND CONDUCTOR SIZE

[A1] [3/4 ”C, 2#14, 1#14G] [B1] [3/4 ”C, 3#14, 1#14G] [C1] [3/4 ”C, 4#14, 1#14G] [D1] [3/4 ”C, 5#14, 1#14G] [E1] [3/4 ”C, 6#14, 1#14G] [F1] [3/4 ”C, 7#14, 1#14G] [G1] [1 ”C, 9#14, 1#14G] [H1] [1”C, 11#14, 1#14G] [J1] [1 1/2”C, 30#14, 1#14G]

[K1] [1 1/4”C, 7/C TYPE A]

[LI] [1 1/4”C, 12/C TYPE A]

[M1] [1 1/2 ”C, 19/C TYPE A]

[N1] [2”C, 25/C TYPE A]

[P1] [2”C, 37/C TYPE A]

[Q1] [3/4 ”C, 1#16, TW PR]

[R1] [3/4 ”C, 1-TYPE B, TW SHLD PR]

[S1] [1 ”C, 2-TYPE B, TW SHLD PR]

[T1] [1 1/4 ”C, 3-TYPE B, TW SHLD PR]

[U1] [1 1/4 ”C, 4-TYPE B, TW SHLD PR]

[V1] [2 ”C, 8-TYPE B, TW SHLD PR]

[W1] [T’C. 1-BELDEN 3092A CONTROLNET]

[X1] [3 ”C, 100#14, 1#12G] [Y1] [2"C, 20#14, 1#14G]

[Z1] [2”C, 14-TYPE B, TW SHLD PR]

[A] [3/4”C, EMPTY]

[B] [2”C, EMPTY]

[C] [2 1/2”C, EMPTY]

[D] [1 1/4”C, 4#12, 1 #12G]

[E] [1 1/2”C, 3#10, 3#14G ARMORED CABLE]

[F] [1 1/4”C, 3#8, 1 #10G]

[G] [1 1/4”C, 5-TYPE B, TW SHLD PR]

[H] [2 1/2”C, 15-TYPE B, TW SHLD PR]

[I] [1”C, 14#14, 1 #14G]

[J] [2 1/2”C, 3-2/0, 3#6G VFD CABLE]

[K] [1”C, EMPTY]

[L] [4”C, WITH INNERDUCT FOR FO]

[M] [1”C, 4-CAT 6e]

[N] [2”C, FOR FIBER OPTIC CABLES]

[O] [3”C, 3-350KCMIL, 1#3G]

[P] [3"C, 4#300KCMIL, 1#3G]

[Q] 8EA.[4"C, 3-500KCM, 1-350KCMG]

[R] [11/2"C, 40#14, 1#14G] [S] [11/4"C, 20#14, 2#12, 1#12G]

[T] [4"C-3#600KCM, 1#2G]

[U] [1"C, CAT 6]

[V] [1"C, I&C SUPPLIED CABLE, 1#14G]

[W] [2"C, 60#14, 1#14G]

[Y] [3"C, 18-TYPE B, TW SHLD PR]

[Z] [1"C, 1-CAT 6e]

[B6] [1 1/4”C, 3#10, 3#14G ARMORED CABLE]

[C6] [1 1/4”C, 3#8, 3#14G ARMORED CABLE]

[D6] [1 1/2”C, 3#6, 3#12G VFD CABLE]

[E6] [1 1/2"C, 3#4, 3#12G VFD CABLE]

[G6] [2"C, 3#2, 3#10G VFD CABLE]

[H6] [2"C, 3#2, 3#10G VFD CABLE]

[K6] [2 1/2"C, 3#1/0, 3#10G VFD CABLE]

[L6] [3"C, 3#2/0, 3#6G VFD CABLE]

[M6] [2 1/2”C, 3#3/0, 3#4G VFD CABLE]

[N6] [3 1/2"C, 3#4/0, 3#4G VFD CABLE]

[R6] 2 EA.[3”C, 3#3/0, 3#4G VFD CABLE]

[S6] 2 EA.[3”C, 3-250KCMIL, 3#4G VFD CABLE]]

[T6] 2 EA.[3”C, 3-350KCMIL, 3#2G VFD CABLE]]

[Q6] [4"C, 3#500KCM, 3#1G VFD CABLE]

[V6] 2 EA.[4”C, 3-600KCMIL, 3#1/0G VFD CABLE]]

[ZA] [1"C, 6-CAT 6e]

AIT 410A

AIT 411A

1 CONTRACTOR SHALL REUSE EXISTING CIRCUIT

BREAKER PREVIOUSLY USED FOR DEMOLISHED

INSTRUMENT AND RE-PURPOSE FOE NEW

INSTRUMENT INSTALLATION.

CONTRACTOR SHALL USE SPARE BREAKERS IN

EXISTING PLANELOAD FOR NEW INSTRUMENTS.

REPLACE EXISTING BREAKERS WITH 2P, 20A FOR

SAMPLE PUMP.

KEYED NOTES:

1.0 1.0

40.4 30

LSH 410A LEAK DETECTION ALARM BOX

LSH 410B LEAK DETECTION ALARM BOX

SAMPLE PUMP

BLEND TANK TASK LIGHT

1.0 1.0

6.9 6.9

1.4

29.3

LUMINAIRE SCHEDULE

1 120 AREA LIGHT - LED SINGLE LUMINARE, UNIVERSAL

120-277VAC TYPE II, GLARE/HOUSIDE SHIELD LITHONIA LIGHTING EAX1-P3-SWW2-T2-UVOLT-

SRA-DDB LED 82W POLE MOUNT TASK LIGHT.

FURNISH WITH 15' SQUARE POLE.

DATEREV BY DESCRIPTION

DATE

CHECKED

DRAWN

DESIGNED

204170

JOB NO.

DRAWING NO.

SHEET NO.

SCALES ACCORDINGLY

VERIFY SCALES

THIS SHEET, ADJUST

IF NOT ONE INCH ON

BAR IS ONE INCH ON

ORIGINAL DRAWING

0 1"

OF

COLLIER COUNTY

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G G

00E04

4701 N FEDERAL HWY, STE 390

POMPANO BEACH, FL 33064

PHONE (561) 210-5715

ADS

SIDZ

MDG

SCRWTP LIME SOFTENING IMPROVEMENTS

301 NORTH CATTLEMEN ROAD, SUITE 302

SARASOTA, FL. 343232

PHONE: (941) 371-9832 FAX: (941) 371-9873

CA 00008571

PROJECT NO.

LA

ST

S

AV

ED

B

Y:

FILE NAME: 00E04 - SCHEDULES.DWG

AD

S

204170-100000

39APRIL 2026

BID DOCUMENTS

THIS ITEM HAS BEEN

DIGITALLY SIGNED AND

SEALED BY

ALEKSANDAR D.

STOJANOVIC ON THE

DATE ADJACENT TO

THE SEAL.

THE SIGNATURE MUST

BE VERIFIED ON ANY

ELECTRONIC COPIES.

ELECTRICAL

SCHEDULES

DATEREV BY DESCRIPTION

DATE

CHECKED

DRAWN

DESIGNED

204170

JOB NO.

DRAWING NO.

SHEET NO.

SCALES ACCORDINGLY

VERIFY SCALES

THIS SHEET, ADJUST

IF NOT ONE INCH ON

BAR IS ONE INCH ON

ORIGINAL DRAWING

0 1"

OF

COLLIER COUNTY

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G G

00E05

4701 N FEDERAL HWY, STE 390

POMPANO BEACH, FL 33064

PHONE (561) 210-5715

ADS

SIDZ

MDG

SCRWTP LIME SOFTENING IMPROVEMENTS

301 NORTH CATTLEMEN ROAD, SUITE 302

SARASOTA, FL. 343232

PHONE: (941) 371-9832 FAX: (941) 371-9873

CA 00008571

PROJECT NO.

LA

ST

S

AV

ED

B

Y:

FILE NAME: 00E05 - BLEND TANK PLAN.DWG

AD

S

204170-100000

39APRIL 2026

BID DOCUMENTS

THIS ITEM HAS BEEN

DIGITALLY SIGNED AND

SEALED BY

ALEKSANDAR D.

STOJANOVIC ON THE

DATE ADJACENT TO

THE SEAL.

THE SIGNATURE MUST

BE VERIFIED ON ANY

ELECTRONIC COPIES.

1. CONTRACTOR SHALL INSTALL GROUNDING CONDUCTOR

FROM THE GROUNDING GRID TO ALL CONTROL PANELS,

PUMPS, DISCONNECTS, TRANSMITTERS, TANKS, ETC.

2. CONTRACTOR SHALL BOND STEEL COLUMNS AND REBAR

IN FLOOR TO GROUND GRID USING CONNECTIONS PER

SPECIFICATION 26 05 26.

GROUNDING NOTES

20'10'0 5'

SCALE: 1" = 10'

GROUND TEST

WELL (TYP.)

GROUND TRIANGLE

(TYP.)GROUND ROD

(TYP.)

BLEND TANK

LIT

LE

AIT

AE

AIT

AE

AIT

410A

AE

410A

AIT

411A

AE

411A

EXISTING

REACTOR TANK 4

EXISTING

REACTOR TANK 3

EXISTING

REACTOR TANK 2

EXISTING

BLEND

TANK

CORROSION

INHIBITOR

CAUSTIC

SODA

HIGH SERVICE

TRANSFER PUMPS

FILTER BUILDING

LSH

410A

LSH

410B

SAMPLE

PUMP

1 COORDINATE THE EXACT LOCATION ON THE FIELD. MOUNT

MANUAL MOTOR STARTER SWITCH IN THE LINE OF SIGHT OF

THE PUMP.

COORDINATE ON THE FIELD WITH OWNER ON THE EXACT

LOCATION OF THE LEAK DETECTION ALARM BOX AND

PROVIDE WIRES AND CONDUITS ACCORDINGLY.

KEYED NOTES:

SAMPLE PANEL 1

SAMPLE PANEL 2

P-1

4LP1-33

[B2] TYP.

P-2

4LP1-33

[B2] TYP.

S3a

4LP1-33

a a

LD

SHC

LD

SHC

LD

AMS

LD

CS

LD

CRI

BLEND TANK PLAN

ELECTRICAL

S3a a

4LP1-33

ELECTRICAL

EQUIPMENT

BUILDING

EXISTING PLC-2 AT BLEND

TANK / TRANSFER PUMP

ELECTRICAL BUILDING

EXISTING 4LP1 AT BLEND

TANK / TRANSFER PUMP

ELECTRICAL BUILDING

EXISTING

FINISH WATER

STORAGE

RESERVOIR

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

AutoCAD SHX Text AeccDbCogoPoint (AeccLand130)

NOTE:

1. PROVIDE 6" MINIMUM COMPACTED GRAVEL, 3/4"

MINUS,

2. UNDER ALL CONCRETE ENCASED DUCT RUNS.

PROVIDE CLASS CE CONCRETE PER

SPECIFICATION SECTION 03 30 00.

#4@18" OC,

TYP

D

4/0 BARE TINNED

COPPER GROUND

CONDUCTOR, TYP

#4 LONGITUDINAL

BARS

@18" OC

MAXIMUM, WITH

2'-0" LAP

2.5"

MIN

2.5"

MIN

2.

5"

M

IN

2.

5"

M

IN

2.5"

MIN

2.5"

MIN

2.

5"

M

IN

2.

5"

M

IN

4/0 BARE TINNED

COPPER GROUND

CONDUCTOR, TYP

D = 3" FOR 2" AND

LARGER CONDUITS

D = 2" FOR 1 1/2" AND

SMALLER CONDUITS

D

D 2.5"

MIN

2.5"

MIN

2.

5"

M

IN

2.

5"

M

IN

2" CLR,

(TYP TOP AND SIDES)

3" CLR,

(TYP BOT)

D

D D

4/0 BARE TINNED

COPPER

GROUND CONDUCTOR,

TYP

2.5"

MIN

2.5"

MIN

2.

5"

M

IN

2.

5"

M

IN

#4 @ 18"

CTRS, VERT

LEGS 1'-0" MIN

D

D D

FOR LARGER DUCT BANKS,

CONTINUE PATTERN OF REBAR,

CONDUIT SEPARATION AND

CONCRETE COVER.

2.5"

MIN

2.

5"

M

IN

#4 @ 18"

CTRS, VERT

LEGS 1'-6" MIN

CONCRETE ENCASED

DUCTBANK DETAIL SCALE: NTS

ENCLOSURE

STAINLESS STEEL 316

CHANNEL

PIPE CAP

3" DIA GALVANIZED

STEELPIPE FILLED WITH

CONCRETE

12" DIA X 36" DEEP

POURED CONCRETE

BASE

FINISHED

GRADE

AS REQD

AS REQD

24" MIN

2" MIN

NOTE:

PROVIDE CLASS A CONCRETE PER SPECIFICATION SECTION 03300.1.

ENCLOSURE MOUNTING STAND

SCALE: NTS

MULTI-GRIP

PIPE CLAMP,

SS TYP

CROSS SUPPORT CHANNEL,

LENGTH AS REQUIRED, SS

TYP

FOUR HOLE TEE PLATE,

(TYP EACH CROSS MEMBER)

VERTICAL SS SUPPORT

CHANNEL FRAMING

CONDUIT RISER,

TYP

POST BASE ATTACHED TO UNDERSIDE

OF STRUCTURE WITH MINIMUM 1/2"

CONCRETE ANCHORS

CONNECTION TO ALLOW FOR 5/8"

VERTICAL STRUCTURE DEFLECTION

POST BASE ATTACHED TO

FLOOR WITH MINIMUM

1/2" SS CONCRETE ANCHORS

1. LENGTH AS REQUIRED TO LIMIT UNSUPPORTED CONDUIT LENGTH

TO MAXIMUM VALUES ALLOWED BY NEC.

2. ALL MATERIALS AND FASTENING HARDWARE SHALL BE TYPE 316

STAINLESS STEEL (SS).

SE

E

N O

TE

SE

E

N O

TE

NOTES:

VERTICAL CONDUIT SUPPORT

SCALE: NTS

NOTE:

1. ALL MOUNTING HARDWARE SHALL BE STAINLESS STEEL 316. ON

CONCRETE WALLS, USE MALLEABLE IRON INSERTS, MOUNT

ENCLOSURE ON 1/4" SPACERS OF 1/2" RIGID CONDUIT.

ANCHOR TO WALL WITH 1/2" DIA.

X 4" STAINLESS STEEL

CONCRETE ANCHORS, WITH

SUPPORTS AT 5"-0" MAXIMUM.

CHANNEL-GLOBE STRUT,

UNISTRUT OR EQUAL TYPE 316

STAINLESS STEEL

CONDUIT SUPPORT

SCALE: NTS

OZ/GEDNEY RAINTIGHT

SPACE-MAKER HUB

WITH INSULATED

THROAT

1. TYPICAL FOR ALL

CONDUIT ENTRANCES

INTO NEMA 3R, NEMA 4,

OR NEMA 4X

ENCLOSURES.

NEOPRENE "O" RING INSULATED THROAT

BUSHING

CONTROL CABINET

MIN. 12" STRAIGHT

SECTION

CONDUIT HUB

SCALE: NTS

WIRING DEVICE

OR ELECTRICAL

EQUIPMENT SIZE

AS REQD

CONDUIT

PIPE STRAP

FLOOR OR

PLATFORM

FOR CONTROL

STATIONS MOUNT

@ 4'-0" ABOVE

FLOOR

WALL OR COLUMN

NOTE:

WALL OR COLUMN MOUNTED DEVICE

SCALE: NTS

COVER THIS

PORTION WITH

SHRINK TUBING

OUTER JACKET

COVER THIS

PORTION WITH

SHRINK TUBING

CONNECTOR

OUTER JACKET

WRAPPED SHIELD

CRIMPED SPLICE

SHIELD

SHRINK TUBING

OUTER JACKET

WIRE

GREEN INSULATED

SHIELD

SHRINK TUBING

SIGNAL LEADS

LUG, TYP

GROUND LEAD

NOTE:

AT TERMINATION.

SHIELD GROUNDED

TERMINATION OF SHIELDED

CONTROL CABLE

SCALE: NTS

MINIMUM 3" ON ALL EXPOSED

SIDES OR AS REQUIRED BY

ANCHORAGE CALCULATIONS

6" M

AX

3/4" TOOLED EDGE

ON EXPOSED FACES

CONSTRUCTION

JOINT, LEAVE ROUGH

#4 @ 12" CTRS

AROUND PERIMETER

OF PAD

1/

2" M

IN

1/

2" M

IN

#4@12", EW, 1" CLR TOP

1'-8", TYP

TOP & BOTTOM

3" M

AX

CONCRETE PAD SECTION

SCALE: NTS

DATEREV BY DESCRIPTION

DATE

CHECKED

DRAWN

DESIGNED

204170

JOB NO.

DRAWING NO.

SHEET NO.

SCALES ACCORDINGLY

VERIFY SCALES

THIS SHEET, ADJUST

IF NOT ONE INCH ON

BAR IS ONE INCH ON

ORIGINAL DRAWING

0 1"

OF

COLLIER COUNTY

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G G

00TE01

4701 N FEDERAL HWY, STE 390

POMPANO BEACH, FL 33064

PHONE (561) 210-5715

ADS

SIDZ

MDG

SCRWTP LIME SOFTENING IMPROVEMENTS

301 NORTH CATTLEMEN ROAD, SUITE 302

SARASOTA, FL. 343232

PHONE: (941) 371-9832 FAX: (941) 371-9873

CA 00008571

PROJECT NO.

LA

ST

S

AV

ED

B

Y:

FILE NAME: 00TE01 - DETAILS NO.1.DWG

AD

S

204170-100000

39APRIL 2026

BID DOCUMENTS

THIS ITEM HAS BEEN

DIGITALLY SIGNED AND

SEALED BY

ALEKSANDAR D.

STOJANOVIC ON THE

DATE ADJACENT TO

THE SEAL.

THE SIGNATURE MUST

BE VERIFIED ON ANY

ELECTRONIC COPIES.

PROJECT NO.

LA

ST

S

AV

ED

B

Y:

FILE NAME:

ELECTRICAL

DETAILS SHEET NO.1

AD

S

CONNECTION

TYPE "TA" CADWELD

GROUND

COPPER

CABLE

5/8" DIA. X 20'-0"

ROD TYPE CONNECTOR

COPPER CONDUCTOR TAP TO HORIZONTAL REINFORCING BAR

(REBAR) LOCATED NEAR THE BOTTOM OR VERTICALLY, WITHIN THAT

PORTION OF CONCRETE FOUNDATION OR FOOTING. MAXIMUM

CONDUCTOR SIZE IS 4/0 AWG. MINIMUM DIAMETER OF REBAR IS 1/2".

MINIMUM LENGTH OF REBAR IS 20'.

COPPER

GROUND

CABLE

10'-0"

TINNED COPPER

#4/0 AWG, BARE

10'-0" 10'-0"

#4/0 AWG, CU,

BTC GROUNDING

CABLE TO

ELECTRICAL

EQUIPMENT

(BTC)

GROUND TEST WELL

GROUND ROD

(TYP)

9 5/8"

13 1/2"

8"

3 1/4"

1 3/4"

12"

#4/0 BTC GROUND WIRE

7/8"

8 3/4"

GROUND ROD

No. 4/0 AWG STRANDED

BARE TINNED COPPER

2' -6

" BURIAL DEPTH

MINIMUM

5/8 " DIA X 20'-0"

COPPER CLAD

GROUND ROD

(BTC)

TYPE "TA" CADWELD

CONNECTION

CABLE TO ROD CONNECTION

SCALE: NTS

GROUND ROD

GROUND CABLE CONNECTION

SCALE: NTS

GROUND CABLE CADWELDED TO REBAR

SCALE: NTS

GROUND TRIANGLE

SCALE: NTS

GROUND ROD

SCALE: NTS

GROUND WIRE TO FUTURE EQUIPMENT

GROUND LUG, (STRAIGHT, 90 , 45 , OR

AS REQ'D.)

FINISH FLOOR

GROUND CONDUCTOR

FITTING

GROUND CONDUCTOR

NOTE:

1. BOLTS SHALL BE INSERTED IN BOLT HOLES

BEFORE CONNECTOR IS EMBEDDED.

GROUNDING INSERT

SCALE: NTS

NO. 1-RT CAST

IRON TRAFFIC

COVER WT.-12#

NO. 1-RT BODY

WT.-54#

CAST IRON

RING WITH

LIFTING

SOCKETS

FINISH GRADE

GROUND TEST WELL

SCALE: NTS

DIRECT BURIED 6"

#6 AWG & 3/4" DIA.x10'

COPPERCLAD GROUND ROD.

M

IN

IM

U

M

8"

SEE PLAN FOR CONDUIT

IDENTIFICATION TAPE (TYP.)

AND WIRE REQUIREMENTS

FINISH GRADE

ALL UNDERGROUND SPLICES SHALL BE MADE

WITH APPROVED WATERPROOF SPLICE KITS,

POLARIS BLUE OR APPROVED EQUAL.

QUAZITE PULL BOX W/BASE, 17"X30"

I.D. MINIMUM SIZE, CONTRACTOR

SHALL ENLARGE SIZE TO MEET NEC

WHEN NEEDED AT HIS OWN

EXPENSE AND INSTALL PER

MANUFACTURER'S

RECOMMENDATIONS.

QUAZITE HEAVY DUTY, SKID RESISTANT & TRAFFIC

RATED TIER 15 COVER, BOLTED DOWN, MARKED

"ELECTRICAL" "INSTRUMENTATION"

ATTACH SYSTEM GROUND

CONDUCTOR TO #6 AWG. AND SEAL

BOX ACCORDINGLY WITH

APPROVED 3M WATERTIGHT

SEALER.

8" CRUSHED STONE OR

GRAVEL FOR DRAINAGE

QUAZITE PULL BOX DETAIL

SCALE: NTS

SST ANCHOR BOLTS,

NUTS, LOCK WASHERS

AND LEVELING NUTS PER

POLE MANUFACTURERS

REQUIREMENTS

NON-SHRINK

GROUT

ONE-PIECE POLE

ANCHOR BASE FOR LIGHT POLE MOUNTED ON SLAB

NON-SHRINK

GROUT

SST ANCHOR BOLTS,

NUTS, LOCK WASHERS

AND LEVELING NUTS PER

POLE MANUFACTURERS

REQUIREMENTS

HINGED POLE

SCALE: NTS

1. COAT AL SURFACES IN CONTACT WITH CONCRETE PER SPECS.

2. * = LARGER OF OD OF EQUIPMENT SUPPORT / LIGHT POLE BASE + 2", OD OF LIGHT POLE EQUIPMENT SUPPORT BASE COVER + 1", AND 12".

3. CONDUIT. SEE ELECTRICAL DRAWINGS FOR CONDUIT ROUTING. PROVIDE HOLE IN BRACKET TOP PLATE WITH HOLE DIAMETER EQUAL TO

CONDUIT OD + 1/2".

4. EQUIPMENT MOUNTING LOCATION SHALL NOT CREATE A TRIPPING OR MAINTENANCE HAZARD. BRACKET INSTALLATION SHALL BE ON THE

WATER SIDE OF THE BASIN.

5. EQUIPMENT SUPPORT / LIGHT POLE BRACKET INSTALLATION SHALL BE SUITABLE FOR 170 MPH WIND WITH APPROPRIATE GUST FACTOR

PER APPLICABLE ZONE OF INSTALLATION AS DEFINED IN THE FLORIDA BUILDING CODE.

6. ADJUST THE BRACKET DESIGN AND/OR PROVIDE ADDITIONAL POLE SUPPORT AS NECESSARY PER WIND LOAD CALCULATIONS.

CONTRACTOR SHALL INCLUDE WITH THE SHOP DRAWING SUBMITTAL A POLE WIND LOADING CALCULATION SIGNED & SEALED BY A STRUCTURAL ENGINEER REGISTERED IN FLORIDA SHOWING THAT THE PROPOSED INSTALLATIONS WILL MEET THE GIVEN WIND LOADING

REQUIREMENT.

NOTES:

1/4 1/4

3/8

3/4" AL PL

1/2" AL PL

3/8

CONCRETE

TYP

POLE BASE WITH OPENING

CONCRETE ANCHOR BY HILTI

SIZE SST BOLTS AND BOLT

MANUFACTURER'S DWGS

ELEVATION

EQUIPMENT SUPPORT / LIGHT

POLE

FOR CONDUIT

PATTERN PER POLE

BASE COVER

1/2" (TYP)

1 1/2"

1 1/2" (TYP)

1/2"

1/2"

2"2 1/2"

9"

SEE NOTE 3

WITH 10" EMBEDMENT

TOP OF

A

A SECTION

EQUIPMENT

SUPPORT /

LIGHT POLE

BASE

EQUIPMENT SUPPORT / LIGHT POLE BRACKET ON CONCRETE

SCALE: NTS

DATEREV BY DESCRIPTION

DATE

CHECKED

DRAWN

DESIGNED

204170

JOB NO.

DRAWING NO.

SHEET NO.

SCALES ACCORDINGLY

VERIFY SCALES

THIS SHEET, ADJUST

IF NOT ONE INCH ON

BAR IS ONE INCH ON

ORIGINAL DRAWING

0 1"

OF

COLLIER COUNTY

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G G

00TE02

4701 N FEDERAL HWY, STE 390

POMPANO BEACH, FL 33064

PHONE (561) 210-5715

ADS

SIDZ

MDG

SCRWTP LIME SOFTENING IMPROVEMENTS

301 NORTH CATTLEMEN ROAD, SUITE 302

SARASOTA, FL. 343232

PHONE: (941) 371-9832 FAX: (941) 371-9873

CA 00008571

PROJECT NO.

LA

ST

S

AV

ED

B

Y:

FILE NAME: 00TE01 - DETAILS NO.1.DWG

AD

S

204170-100000

39APRIL 2026

BID DOCUMENTS

THIS ITEM HAS BEEN

DIGITALLY SIGNED AND

SEALED BY

ALEKSANDAR D.

STOJANOVIC ON THE

DATE ADJACENT TO

THE SEAL.

THE SIGNATURE MUST

BE VERIFIED ON ANY

ELECTRONIC COPIES.

PROJECT NO.

LA

ST

S

AV

ED

B

Y:

FILE NAME:

ELECTRICAL

DETAILS SHEET NO.2

AD

S

ADS Engineering
2026-05-13T18:33:23-0400
Aleksandar Stojanovic

File details come from the government source that posted it. Updated .