26-8683_Exhibit_M1_-_General_Plans.pdf
PDF 7 MB Posted
- Attached to
- SCRWTP Lime Softening Improvements - Blend Tank
- Solicitation number
- 26-8683
- Issued by
- Collier County, Florida
About this file
This file contains general construction plans and technical drawings for the South County Regional Water Treatment Plant (SCRWTP) Lime Softening Improvements – Blend Tank project in Collier County, Florida. The project, identified as Bid No. 26-8683 and Project No. 204170, involves the construction of lime softening improvements with a focus on blend tank installation and related mechanical, structural, and electrical systems. The bid documents were advertised on June 1, 2026, with sealed bids due no later than July 1, 2026 at 3:00 PM local time. A non-mandatory pre-bid meeting is scheduled for June 9, 2026 at 11:00 AM at the SCRWTP facility located at 3851 City Gate Drive, Naples, FL 34117. The project location is in District 5 of Collier County. Prospective bidders must register on the OpenGov procurement portal at https://procurement.opengov.com/portal/collier-county-fl to access the complete bid documents, which include demolition plans, site plans, structural details, mechanical systems, electrical components, and instrumentation specifications.
The bid documents establish comprehensive requirements for the contractor, including responsibility for all labor, equipment, materials, and services necessary to complete the work in accordance with the plans and specifications. The contractor must obtain all applicable permits, provide erosion and sediment control measures, verify existing utilities and site conditions prior to construction, and ensure protection of existing structures and utilities throughout the project duration. All material and construction methods must conform to the Collier County Land Development Code, Collier County Water-Sewer District Utilities Standards Manual, and all applicable federal, state, and local regulations. The contractor is responsible for identifying and managing underground utilities, with no reimbursement allowed for utility or pipe repair or replacement due to contractor negligence. Trench excavation must comply with OSHA requirements and the Trench Safety Act. A Collier County Utility Inspector must be present for all connections to existing utility mains.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
203954 h v o
204170B_00G01.dgn
P lo t
D a te
-M
A Y -2
:0
:2
P
M U s e r:
s v c P
W
M o d e l:
L a y o u t1
C lo rT a b le g s h a d e .c tb
D e s ig n S c ri p t:
a ro ll o S td
P e n v .p n lo tS c a le :1
PROJECT NO. FILE NAME:
204170
DRAWING NO.
JOB NO.
SHEET NO.
OF 391
00G01
10 11 12 135 6 7 8 91 2 3 4
A
B
C
D
E
F
G
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
G
L A
S T S
A V
E D B
Y
CONSTRUCTION OF
LIME SOFTENING IMPROVEMENTS - BLEND TANK
SOUTH COUNTY REGIONAL WATER TREATMENT PLANT
CAROLLO PROJECT NO. 204170
PROJECT NO. 70283.2
COLLIER COUNTY
PROJECT LOCATION
BID DOCUMENTS - APRIL 2026
DISTRICT 5 - WILLIAM L. MCDANIEL, JR.
DISTRICT 4 - DAN KOWAL
DISTRICT 3 - BURT L. SAUNDERS
DISTRICT 2 - CHRIS HALL
DISTRICT 1 - RICK LOCASTRO
THE BOARD OF COLLIER COUNTY COMMISSIONERS
NAPLES, FL 34117
3851 CITY GATE DRIVE
SOUTH COUNTY REGIONAL WTP
MAGNOLIA POND DRIVE
C O
L L
IE
R B
O U
L E
V A
R D
DRIVE
CITY GATE
PROJECT LOCATION MAP
NO SCALE
CA 00008571
PHONE: (941) 371-9832
SARASOTA, FL. 34232
301 NORTH CATTLEMEN ROAD SUITE 302
No 93091
ANY ELECTRONIC COPIES.
THE SIGNATURE MUST BE VERIFIED ON
THE DATE ADJACENT TO THE SEAL.
AND SEALED BY ANTHONY HORVAT ON
THIS ITEM HAS BEEN DIGITALLY SIGNED
TYPICAL DETAILS00TN0139
BLEND TANK P&ID00N0138
ABBREVIATIONS AND SYMBOLS - 200GN0237
ABBREVIATIONS AND SYMBOLS - 100GN0136
(N) - INSTRUMENTATION
DETAILS SHEET NO. 200TE0235
DETAILS SHEET NO. 100TE0134
BLEND TANK PLAN00E0533
SCHEDULES00E0432
CONTROL RISER00E0331
POWER RISER00E0230
SITE PLAN00E0129
NOTES00GE0228
LEGEND00GE0127
(E) - ELECTRICAL
MECHANICAL TYPICAL DETAILS 300TM0326
MECHANICAL TYPICAL DETAILS 200TM0225
MECHANICAL TYPICAL DETAILS 100TM0124
BLEND TANK SITE SECTIONS 200M0423
BLEND TANK SITE SECTIONS 100M0322
YARD PIPING PLAN00M0221
BLEND TANK SITE PLAN00M0120
GENERAL NOTES, LEGENDS AND SYMBOLS00GM0119
(M) - MECHANICAL
TYPICAL DETAILS 600TS0618
TYPICAL DETAILS 500TS0517
TYPICAL DETAILS 400TS0416
TYPICAL DETAILS 300TS0315
TYPICAL DETAILS 200TS0214
TYPICAL DETAILS 100TS0113
BLEND TANK ELEVATIONS00S0312
BLEND TANK SECTIONS00S0211
BLEND TANK PLANS00S0110
GENERAL NOTES00GS019
(S) - STRUCTURAL
BLEND TANK DEMOLITION PHOTOS00D048
BLEND TANK DEMOLITION SECTIONS00D037
BLEND TANK DEMOLITION PLAN 00D026
BLEND TANK DEMOLITION SITE PLAN00D015
(D) - DEMOLITION
FACILITY INDEX00G044
NOTES, LEGEND AND SYMBOLS00G033
SHEET INDEX00G022
COVER SHEET00G011
(G) - GENERAL
h v
GENERAL
00G02
204170-100000
AH
HV
SHEET INDEX
204170B_00G02.dgn
DATEREV BY DESCRIPTION
DATE
CHECKED
DRAWN
DESIGNED
204170
JOB NO.
DRAWING NO.
SHEET NO.
SCALES ACCORDINGLY
VERIFY SCALES
THIS SHEET, ADJUST
IF NOT ONE INCH ON
BAR IS ONE INCH ON
ORIGINAL DRAWING
0 1"
OFAPRIL 2026
COLLIER COUNTY
SCRWTP LIME SOFTENING IMPROVEMENTS
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
G G
CA 00008571
PHONE: (941) 371-9832 FAX: (941) 371-9873
SARASOTA, FL. 343232
301 NORTH CATTLEMEN ROAD, SUITE 302
BID DOCUMENTS
ELECTRONIC COPIES.
VERIFIED ON ANY
THE SIGNATURE MUST BE
ADJACENT TO THE SEAL.
HORVAT ON THE DATE
SEALED BY ANTHONY
DIGITALLY SIGNED AND
THIS ITEM HAS BEEN
P lo t
D a
A Y -2
:0
:2
P
M U s e r:
s v c d e l:
L a y o lo rT a b le g s h a d e s ig n S c ri ro ll o S td
P e n v .p tS c a le :1
L A
S T S
A V
E D B
Y
PROJECT NO. FILE NAME:
NO.
SHEET
NO.
DRAWING
DESCRIPTION
v o AH
HV
00G03
NOTES, LEGEND, AND SYMBOLS
204170B_00G03.dgn
30°
DATEREV BY DESCRIPTION
DATE
CHECKED
DRAWN
DESIGNED
204170
JOB NO.
DRAWING NO.
SHEET NO.
SCALES ACCORDINGLY
VERIFY SCALES
THIS SHEET, ADJUST
IF NOT ONE INCH ON
BAR IS ONE INCH ON
ORIGINAL DRAWING
0 1"
OFAPRIL 2026
COLLIER COUNTY
SCRWTP LIME SOFTENING IMPROVEMENTS
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
G G
CA 00008571
PHONE: (941) 371-9832 FAX: (941) 371-9873
SARASOTA, FL. 343232
301 NORTH CATTLEMEN ROAD, SUITE 302
THE SIGNATURE MUST BE
ADJACENT TO THE SEAL.
HORVAT ON THE DATE
SEALED BY ANTHONY
DIGITALLY SIGNED AND
THIS ITEM HAS BEEN
P lo t
D a
A Y -2
:0
:4
P
M U s e r:
s v c d e l:
L a y o lo rT a b le g s h a d e s ig n S c ri ro ll o S td
P e n v .p tS c a le :1
L A
S T S
A V
E D B
Y
PROJECT NO. FILE NAME:
A
##X##
VIEW
REVISION DELTA
SCALE FENCE
GUARDRAIL
CENTER LINE
REMOVE AND/OR ABANDON
GATE
EXISTINGNEW
DETAIL REFERENCES HATCH PATTERNS
VIEW
DRAWING CUT ORIGINATION
TYPICAL DETAIL #
TYP
FILE:
SCALE:
FILE:
100'0 50' 200'
SECTION CUT
REFERENCE
TYPICAL DETAIL
(EXIST)
VIEWS
EXTERIOR ELEVATION
PHOTO LOCATION
KEY NOTE
TAG AND NUMBER
EQUIPMENT/DEVICE
AGRID BUBBLE
PIPE TAG
BREAK LINE
T R
U E
N O
R T
H P
L A
N T
N O
R T
H
NORTH ARROW/PLANT NORTH
SPECIFIC)
(STATE/REGION
WARNING
OVERHEAD
UNDERGROUND/
SYMBOLS
GENERAL NOTES
MATCH LINE
HIDDEN LINE
MATCH LINE SEE DWG ##X##
VIEW
ELEVATION
TOC XXXX.XX
EXISTING ELEVATION
PLAN VIEW
PIPE BREAK
CROSS SECTION
PIPE BREAK
CONSTRUCTION
FUTURE CONSTRUCTION
(SINGLE LINE)
PIPE CONTINUATION
BRACKET
EF-EQUIP = FUTURE EQUIPMENT
EX-EQUIP = EXISTING EQUIPMENT
EQUIPMENT
EF-SIZE FLOW STREAM = FUTURE
EX-SIZE FLOW STREAM = EXISTING
SIZE FLOW STREAM
PLAN/TITLE
TITLE W/ REFERENCE
SECTION OR DETAIL
NUMERIC = DETAIL
ALPHA = SECTION
(ENLARGED)
DETAIL CALL-OUT
POINT OF VIEW
ARROW INDICATES
##X## = SEE INDICATED DRAWING
- = SHOWN ON SAME DRAWING
DRAWING REFERENCE ##X##
DISCIPLINE DESIGNATOR
DRAWING
SEE INDICATED
DETAIL
SHEETS IN
TYPICAL DETAIL NUMBER
TYPICAL DETAIL TITLE
(WHEN APPLICABLE)
AREA DESIGNATOR
SHEET NUMBER
CONSECUTIVE
(REVISED)
DATE CREATED
PLAN NOT REFERENCED
GENERAL NOTES (CONT'D)
N = NOTE TO TYPICAL DETAIL USER
R = REVISED
J = JOB SPECIFIC
S = STANDARD
MODIFICATION NOTE
T.O.W. XXXX.X±
PIPE SIZE FLOW STREAM
XXX-XX-XXXX
X" XXX
##X##
SHT # OF #MOD
LINE 2
LINE 1
LINE 3
VER DATE
TYP
SECTION/DETAIL TITLEC/1
##X##
FILE
SCALE
C
A FILE
PLAN TITLE
26.
COUNTY IN WRITING.
NO FIELD CHANGES OR DEVIATION FROM DESIGN SHALL BE MADE WITHOUT PRIOR APPROVAL OF THE 25.
TO THE PLANS AND SPECIFICATIONS AND ALL STATE AND LOCAL REQUIREMENTS.
ENSURE ADEQUATE EROSION AND SEDIMENT CONTROL MEASURES. THESE MEASURES SHALL CONFORM
CONTRACTOR SHALL PROVIDE ALL LABOR, EQUIPMENT, TOOLS, MATERIALS AND SERVICES NEEDED TO 24.
DISTURBED BY THE CONSTRUCTION.
CONTRACTOR SHALL BE RESPONSIBLE FOR REGRADING AND REPLANTING VEGETATION IN ALL AREAS 23.
BETTER UNLESS OTHERWISE NOTED.
ALL DISTURBED AREAS SHALL BE RESTORED, INCLUDING REGRADING, TO THEIR ORIGINAL CONDITION OR 22.
GOVERNING ENTITIES.
CULVERTS, FENCES, AND LANDSCAPING AS REQUIRED BY OWNER, ENGINEER OF RECORD, AND/OR OTHER
DAMAGED ITEMS INCLUDING, BUT NOT LIMITED TO, DRIVEWAYS, SIDEWALKS, BOLLARDS, SIGNS, STORM
CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING, DISPOSE, REPAIRING, OR REPLACING ANY 21.
WORK.
CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL APPLICABLE PERMITS BEFORE COMMENCING20.
PROTECT THE HEALTH, SAFETY AND WELFARE OF THOSE PERSONS HAVING ACCESS TO THE WORK SITE.
SERVICE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR TAKING SUCH MEASURES AS NECESSARY TO
FOR THE PROTECTION OF EXISTING AND NEWLY INSTALLED UTILITIES FROM DAMAGE OR DISRUPTION OF
THE CONTRACTOR SHALL BE RESPONSIBLE AT ALL TIMES THROUGH THE DURATION OF CONSTRUCTION19.
AND ALL FEDERAL STATE, AND LOCAL REGULATIONS.
DISTRICT UTILITIES STANDARDS MANUAL. THE APPROVED TECHNICAL STANDARDS AND SPECIFICATIONS, CONFORM WITH THE COLLIER COUNTY LAND DEVELOPMENT CODE, THE COLLIER COUNTY WATER-SEWER
ALL MATERIAL AND CONSTRUCTION METHODS USED FOR THE PROPOSED IMPROVEMENTS SHALL18.
PROVIDE ALL SHEETING/SHORING REQUIRED TO PROTECT EXISTING STRUCTURES, PIPES AND FACILITIES. 17.
OWNER OF THE ELECTRIC LINES.
LINES. CONTRACTOR SHALL ABIDE BY THE NATIONAL ELECTRIC CODE AND ANY REQUIREMENT BY THE
THE CONTRACTOR SHALL TAKE SPECIAL PRECAUTIONS IN THE VICINITY OF ANY OVERHEAD ELECTRIC 16.
DOWNTIME SHALL BE A MAXIMUM OF 8 HOURS, UNLESS SPECIFIED OR SHOWN OTHERWISE.
THE EXISTING PIPE SHALL REMAIN IN SERVICE UNTIL NEW PIPING IS READY TO BE PLACED INTO SERVICE.
CONTRACTOR SHALL REROUTE THE EXISTING PIPING IF REQUIRED TO MISS THE PROPOSED STRUCTURES. 15.
TO MAINTAIN SERVICE BY THE PLANT.
PHASES OF WORK, AND IT CONFLICTS WITH NEW PIPING, TEMPORARILY RELOCATE PIPING AS REQUIRED
WHERE PIPING IS TO BE ABANDONED AND MUST REMAIN IN SERVICE UNTIL COMPLETION OF OTHER
ALL EXISTING PIPES THAT ARE TO BE ABANDONED IN PLACE OR REMOVED MAY NOT BE SHOWN. 14.
THE PLANT.
IS NO LONGER IN SERVICE. LINES IN SERVICE SHALL BE MAINTAINED UNTIL NO LONGER REQUIRED BY
CONTRACTOR SHALL VERIFY THAT PIPING SHOWN TO BE ABANDONED OR AS ABANDONED PREVIOUSLY 13.
COORDINATE LOCATION OF UNDERGROUND UTILITIES.
THE CONTRACTOR SHALL CONTACT SUNSHINE STATE ONE CALL OF FL, INC. (SUNSHINE 811) TO12.
GRADE AND VAULTS SHALL BE SIX INCHES ABOVE FINISHED GRADE.
WISE SHOWN OR DIRECTED. MANHOLES IN OPEN FIELDS SHALL BE SET TWELVE INCHES ABOVE FINISHED
ADJUST ALL VALVE BOXES, VAULTS, PULL BOXES, AND MANHOLES TO FINISHED GRADE UNLESS OTHER-11.
PROVIDE ALL RESTRAINTS REQUIRED FOR A RIGIDLY SUPPORTED COMPLETE AND WORKING SYSTEM.
SHALL PROVIDE ALL FITTINGS, ADAPTERS, AND APPURTENANCES REQUIRED TO MAKE THE CONNECTIONS.
CONTRACTOR SHALL MAKE CONNECTIONS TO EXISTING PIPE, EQUIPMENT, ETC. AS REQUIRED AND 10.
WITHOUT ADDITIONAL COMPENSATION.
OR RECONSTRUCTED TO THE ORIGINAL OR BETTER CONDITION AT THE CONTRACTOR'S EXPENSE
ALL FACILITIES DAMAGED BY THE CONTRACTOR'S OPERATIONS SHALL BE EXPEDITIOUSLY REPAIRED
DAMAGE EXISTING FACILITIES AND UTILITIES SHOWN OR NOT SHOWN THAT ARE TO REMAIN IN PLACE.
THE CONTRACTOR SHALL TAKE ALL PRECAUTIONARY MEASURES NECESSARY TO PROTECT FROM 9.
SHOWN AROUND OR NEAR AREAS OF NEW CONSTRUCTION PRIOR TO START OF CONSTRUCTION.
THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS, SIZES, MATERIAL TYPES, AND ELEVATIONS
RESPONSIBILITY FOR FACILITIES AND UTILITIES NOT SHOWN OR NOT IN THE LOCATION SHOWN.
AVAILABLE RECORDS OR ELECTRONIC FILES. NEITHER THE OWNER NOR ENGINEER ASSUMES ANY
EXISTING FACILITY AND UTILITY INFORMATION SHOWN ON THE DRAWINGS WAS OBTAINED FROM 8.
ADDITIONAL COST TO THE OWNER. CONTRACTOR SHALL INCLUDE COST FOR THIS IN THE BID.
FOR FURNISHING ALL FITTINGS AND ADAPTERS REQUIRED TO MAKE THE ROUTING CHANGES AT NO
ARE NECESSARY TO MISS EXISTING PIPES, STRUCTURES, ETC. CONTRACTOR SHALL BE RESPONSIBLE
INDICATED ON THE DRAWINGS. PIPES SHALL BE ROUTED AS SHOWN UNLESS MINOR REVISIONS
ALL PIPELINES SHALL HAVE A MINIMUM COVER OF 36" UNLESS THE COVER DEPTH IS SPECIFICALLY 7.
OWNER.
AND REINSTALL THEM AS REQUIRED TO ELIMINATE THE CONFLICT AT NO ADDITIONAL COST TO THE
SHALL TEMPORARILY RELOCATE CONFLICTING EXISTING UTILITIES AT TIE-IN/CONNECTION LOCATIONS
LOCATION OF ALL EXISTING PIPING AND UTILITIES IN THE CONSTRUCTION AREA. THE CONTRACTOR
AND/OR OTHER PROPOSED UTILITIES, CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE
PRIOR TO EXCAVATION FOR NEW STRUCTURES, ELECTRICAL CONDUIT, FABRICATION OF NEW PIPING 6.
AND REQUIREMENTS.
CONTRACTOR SHALL COMPLY WITH LOCAL CONSTRUCTION STORM WATER DISCHARGE REGULATIONS 5.
IN THE SAME AS FOR OTHER SIMILAR WORK.
WHERE NO CONSTRUCTION DETAILS ARE SHOWN OR NOTED FOR ANY PART OF WORK. DETAILS SHALL BE 4.
EVEN THOUGH NOT REFERENCED AT SPECIFIC LOCATIONS ON DRAWINGS.
AS INDICATED IN THE APPLICABLE TYPICAL DETAILS AND GENERAL NOTES. TYPICAL DETAILS SHALL APPLY
UNLESS DETAILED, SPECIFIED, OR OTHERWISE INDICATED ON THE DRAWINGS, CONSTRUCTION SHALL BE 3.
THE ENGINEER OF ANY DISCREPANCIES.
CONTRACTOR SHALL VERIFY ALL DIMENSIONS BEFORE STARTING WORK AND SHALL IMMEDIATELY NOTIFY 2.
THEY WERE WRITTEN IN THEIR ENTIRETY ON EACH SHEET.
FOLLOWING NOTES ARE GENERAL AND APPLY TO ALL SHEETS OF THESE CONTRACT DOCUMENTS AS IF 1.
(NAVD) OF 1988 UNLESS NOTED OTHERWISE IN THE DRAWINGS.
ALL NEW, OR PROPOSED, ELEVATIONS SHOWN ARE BASED ON THE NORTH AMERICAN VERTICAL DATUM
GEODETIC VERTICAL DATUM 1929). THE CONVERSION FACTOR FROM NGVD29 TO NAVD88 IS -1.28 FEET
ALL ELEVATIONS SHOWN ON ALL HISTORICAL RECORD DRAWINGS ARE BASED ON NGVD 29 (NATIONAL
BETWEEN THE CONTRACT DOCUMENTS AND EXISTING CONSTRUCTION BEFORE PROCEEDING WITH WORK.
CONTRACTOR SHALL NOTIFY ENGINEER IF THERE IS A CONFLICT SITE FEATURES AFFECTING THE WORK.
ELEVATIONS, AND CONFIGURATION OF EXISTING STRUCTURES, EQUIPMENT, PIPING, UTILITIES, AND OTHER
CONDITIONS PRIOR TO CONSTRUCTION, INCLUDING, BUT NOT LIMITED TO, THE LOCATION, DIMENSIONS, CONTRACTOR SHALL VERIFY IN THE FIELD ALL EXISTING
TREAD PLATE
LANDSCAPING
GRATING
STEEL
LINE WORK
COURSE (ABC)
AGGREGATE BASE
BEDROCK
CLSM
(ALL CLASSES)
CONCRETE
DRAIN ROCK
OR BACKFILL
STRUCTURAL FILL
STAGING AREA
SPAN
ASPHALT PAVING
GRAVEL
UNDISTURBED SOIL
EXISTING/
Know what's below.
Callbefore you dig.
KEY TAG X
DISPOSE
DEMOLISH AND
SALVAGE
DEMOLISH AND
RIPRAP(WITH AERIAL)
OR
OTHERWISE.
ALL DEBRIS FROM DEMOLITION TO BE DISPOSED OF PROPERLY OFFSITE, EXCEPT WHEN NOTED35.
ACCORDANCE WITH THE CONTRACT DOCUMENTS.
PHOTOGRAPHS SHOWN FOR CLARITY, CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLETING ALL WORK IN34.
CONSISTENT WITH SURROUNDINGS.
AND STABILIZING WITH GRANULAR MATERIALS OR SOD AS NEEDED SO THAT SURFACES APPEAR
AFTER DEMOLITION, RESTORE EXISTING SURFACES AT DEMOLITION SITE BY REMOVING IRREGULARITIES,33.
WORKING CONDITIONS.
THAT ARE TO REMAIN. ALL DAMAGES MUST BE REPAIRED IMMEDIATELY AND RESTORED TO ORIGINAL
DEMOLITION WORK SHALL BE PERFORMED SO AS NOT TO DISTURB ANY STRUCTURES, PIPING, AND UTILITIES32.
NOTIFY THE ENGINEER OF ANY DISCREPANCIES.
CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR TO DEMOLITION AND CONSTRUCTION AND31.
DIGGING TO MINIMIZE DAMAGE TO EXISTING FEATURES.
ON THE BEST AVAILABLE INFORMATION TO UTILITIES MAY REQUIRE MINOR FIELD ADJUSTMENTS OR HAND
AWARE THAT THIS IS AN EXISTING WATER TREATMENT PLANT SITE. NEW WORK HAS BEEN DESIGNED BASED
REIMBURSEMENT WILL BE ALLOWED FOR UTILITY/ PIPE REPAIR OR REPLACEMENT. CONTRACTOR SHALL BE
ALL REPAIR WORK SHALL MEET THE APPROVAL OF THE OWNER OF THE DAMAGED UTILITY. NO
UNDERGROUND PIPELINES ON OR OFF THE PROPERTY SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
AND UNDERGROUND PIPELINES IN CONSTRUCTION AREA. ANY DAMAGES TO EXISTING UTILITIES OR
CONTRACTORS SHALL BE RESPONSIBLE FOR THE LOCATION AND IDENTIFICATION OF ALL EXISTING UTILITIES30.
TRENCH SAFETY STANDARDS.
PROVIDE WRITTEN ASSURANCE THAT THE TRENCH EXCAVATION WILL COMPLY WITH THE APPLICABLE
SET FOR IN THE TRENCH SAFETY ACT THROUGHOUT THE DURATION OF THE PROJECT. CONTRACTOR SHALL
EXCAVATION MUST MEET OSHA REQUIREMENTS AND CONTRACTOR SHALL CONFORM TO THE GUIDELINES29.
CONTRACTOR SHALL CONFIRM LIMITS OF STAGING AREA WITH PLANT MANAGER OR PLANT STAFF.28.
OR STRUCTURE WITHOUT THE PRESENCE OF A COLLIER COUNTY UTILITY INSPECTOR.
NO CONNECTIONS TO, OR ANY OTHER CONSTRUCTION SHALL BE PERFORMED ON AN EXISTING UTILITY MAIN27.
(800) 432-4770 v o AH
HV
00G04
FACILITY INDEX
204170B_00G04.dgn
DATEREV BY DESCRIPTION
DATE
CHECKED
DRAWN
DESIGNED
204170
JOB NO.
DRAWING NO.
SHEET NO.
SCALES ACCORDINGLY
VERIFY SCALES
THIS SHEET, ADJUST
IF NOT ONE INCH ON
BAR IS ONE INCH ON
ORIGINAL DRAWING
0 1"
OFAPRIL 2026
COLLIER COUNTY
SCRWTP LIME SOFTENING IMPROVEMENTS
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
G G
CA 00008571
PHONE: (941) 371-9832 FAX: (941) 371-9873
SARASOTA, FL. 343232
301 NORTH CATTLEMEN ROAD, SUITE 302
THE SIGNATURE MUST BE
ADJACENT TO THE SEAL.
HORVAT ON THE DATE
SEALED BY ANTHONY
DIGITALLY SIGNED AND
THIS ITEM HAS BEEN
P lo t
D a
A Y -2
:0
:4
P
M U s e r:
s v c d e l:
L a y o lo rT a b le g s h a d e s ig n S c ri ro ll o S td
P e n v .p tS c a le :1
L A
S T S
A V
E D B
Y
PROJECT NO. FILE NAME:
AREA CODE
FACILITY
FACILITY NAME
EXISTING BLEND TANK AREA
RESERVOIR
WATER STORAGE
EX. FINISHED
AREA
INHIBITOR FEED
CORROSION
EX. CAUSTIC /
PUMPS
TRANSFER
EX.
TANK NO. 4
REACTOR
EX.
TANK NO. 3
REACTOR
EX.
TANK NO. 2
REACTOR
EX.
TANK NO. 1
REACTOR
EX.
BUILDING
ELECTRICAL
NO. 2
STATION
PUMP
SERVICE
HIGH
AREA
FILTER
EFFLUENT
L.S.
STATION NO. 1
HIGH SERVICE PUMP
AREA
L.S. RECARBONATION
BUILDING
HANDLING
EX. SLUDGE
BUILDING
CHEMICAL
EX.
CONTROL
ODER
OSMOSIS
REVERSE
EX.
CONTROL
ODOR
EX. L.S.
CONTRACTOR LAYDOWN, STAGING AND STORAGE AREA06
REVERSE OSMOSIS BUILDING
EX. OPERATIONS AND
BLEND TANK AREA
SEE SHEET M01 FOR CONTINUATION
| 204170B_00G01 |
| 204170B_00G01 |
| 204170B_00G02 |
| 204170B_00G02 |
| 204170B_00G03 |
| 204170B_00G03 |
| 204170B_00G04 |
| 204170B_00G04 |
| Carollo Engineers, Inc. | |
| 2026-05-11T14:29:57-0400 | |
| Anthony Ryan Horvat | |
| I am approving this document |
File details come from the government source that posted it. Updated .