26-8683_Exhibit_M3_-_Structural_Plans.pdf
PDF 3 MB Posted
- Attached to
- SCRWTP Lime Softening Improvements - Blend Tank
- Solicitation number
- 26-8683
- Issued by
- Collier County, Florida
About this file
This is a set of structural plans and design specifications for the Collier County South County Regional Water Treatment Plant (SCRWTP) Lime Softening Improvements Blend Tank project, prepared by Carollo Engineers, Inc. The bid documents contain comprehensive structural engineering drawings and details for the construction of a reinforced concrete blend tank facility. The project is located at the SCRWTP in Naples, Florida, with sealed bids due no later than July 1, 2026 at 3:00 PM local time. A non-mandatory pre-bid meeting is scheduled for June 9, 2026 at 11:00 AM at the facility located at 3851 City Gate Drive, Naples, FL 34117. The structural plans include general notes, blend tank plans, sections, elevations, and typical construction details for concrete reinforcement, joints, equipment installation, stairs, guardrails, ladders, and grating systems. The design incorporates three 42" x 42" water-tight Bilco J-5AL hatches cast into the deck concrete, stainless steel access ladders, aluminum guardrails, and multiple access points for operation and maintenance.
The structural design is based on the 2023 Florida Building Code with ASCE 7-22 standards, with a Structure Risk Category III designation. Key design parameters include a base flood elevation of 11.00 feet, ultimate design wind speed of 174 mph, and groundwater elevation at 5.00 feet, with a net allowable bearing pressure of 1,500 psf. The concrete specifications call for minimum compressive strength of 4,500 psi for structural elements and 2,500 psi for fill and thrust blocks, with reinforcing steel conforming to ASTM A615 Grade 60. The project utilizes reinforced concrete construction with extensive specifications for waterstop placement, construction joint details, anchor bolt installations, and equipment grouting requirements. Structural materials include aluminum for guardrails, grating, and ladder systems with Type 316 stainless steel fasteners, and stainless steel construction details at specified locations. The document was digitally signed and sealed by Vanessa Negron-Vieira on April 2026.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATEREV BY DESCRIPTION
DATE
CHECKED
DRAWN
DESIGNED
204170
JOB NO.
DRAWING NO.
SHEET NO.
SCALES ACCORDINGLY
VERIFY SCALES
THIS SHEET, ADJUST
IF NOT ONE INCH ON
BAR IS ONE INCH ON
ORIGINAL DRAWING
0 1"
OFAPRIL 2026
COLLIER COUNTY
SCRWTP LIME SOFTENING IMPROVEMENTS
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
G G
301 NORTH CATTLEMEN ROAD, SUITE 302
SARASOTA, FL. 343232
PHONE: (941) 371-9832 FAX: (941) 371-9873
CA 00008571 39
BID DOCUMENTS
THIS ITEM HAS BEEN
DIGITALLY SIGNED AND
SEALED BY VANESSA
NEGRON-VIEIRA ON THE
DATE ADJACENT TO THE
SEAL.
THE SIGNATURE MUST BE
VERIFIED ON ANY
ELECTRONIC COPIES.
PROJECT NO.
LA
ST
S
AV
ED
B
Y:
FILE NAME:
CE
CE
00GS01STRUCTURAL
GENERAL NOTES
204170_00GS01.dwg hv o
GEOTECHNICAL REPORT / FOUNDATION DESIGN CRITERIA:
TYPICAL STRUCTURAL MATERIALS:
CONSTRUCTION:
STRUCTURAL SYMBOLS:
STRUCTURAL ABBREVIATIONS:
DEFERRED DESIGN SUBMITTALS
STRUCTURAL DESIGN CRITERIA - GENERAL:
GENERAL NOTES:
1. USE STRUCTURAL DRAWINGS IN CONJUNCTION WITH PROJECT DRAWINGS BY OTHER
DISCIPLINES AND WITH THE SPECIFICATIONS.
2. UNLESS DETAILED. SPECIFIED OR INDICATED OTHERWISE, CONSTRUCTION SHALL BE
AS INDICATED IN THE GENERAL NOTES AND TYPICAL DETAILS.
3. PRESENTATION CONVENTIONS FOR STRUCTURAL DRAWINGS:
A. SCREENED LINE WORK INDICATES EXISTING CONDITIONS.
B.WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED SIZES.
C.PLANS ARE TREATED AS HORIZONTAL SECTIONS. (I.E.: "PLAN AT ELEVATION 110''
SHOWS CONSTRUCTION AT END BELOW ELEVATION 110.)
4. VERIFY DIMENSIONS AND CONDITIONS BEFORE BEGINNING WORK. ADVISE ENGINEER
IMMEDIATELY OF DISCREPANCIES BETWEEN EXISTING CONDITIONS AND DIMENSIONS,
AND INFORMATION SHOWN ON THESE DRAWINGS. CONFIRM THE FOLLOWING BEFORE
PREPARATION AND SUBMITTAL OF SHOP DRAWINGS:
A. DIMENSIONS AND WEIGHTS FOR EQUIPMENT SELECTED.
B. SIZES AND LOCATIONS OF EQUIPMENT PADS FOR EQUIPMENT SELECTED.
5. TYPICAL DETAILS ARE INCLUDED ON THE "TS" DRAWINGS.
A. TYPICAL DETAILS ARE INTENDED TO APPLY AT LOCATIONS DESCRIBED BY THEIR
TITLES, EVEN WHEN NOT SPECIFICALLY REFERENCED ON THE DRAWINGS.
B. IN STRUCTURAL TYPICAL DETAILS, ORIENTATION OF BARS IN EACH MAT OF
REINFORCEMENT (WHETHER "LINES" OR "DOTS" ARE CLOSER TO THE FACE OF THE
CONCRETE) IS GENERALLY ARBITRARY. SEE DRAWINGS OF EACH STRUCTURE FOR
ORIENTATION REQUIRED AT THAT STRUCTURE.
6. SEE CIVIL DRAWINGS FOR STRUCTURE COORDINATES. POINTS ON THE STRUCTURES
TO WHICH SITE COORDINATES REFER ARE SHOWN ON THE STRUCTURAL PLANS.
7. DRAWINGS PREPARED BY OTHER DISCIPLINES INCLUDE OPENINGS, ANCHORS, PIPES,
CONDUITS, AND OTHER ITEMS THAT EMBEDDED INTO OR PASS THROUGH
STRUCTURES.
A. CONFIRM SIZE AND LOCATIONS OF OPENINGS, PENETRATIONS AND EMBEDMENT
FOR ITEMS AND EQUIPMENT FURNISHED.
B. IN GENERAL, OPENINGS, EMBEDMENTS, AND PENETRATIONS LESS THAN 12
INCHES IN DIAMETER ARE NOT SHOWN ON THE STRUCTURAL DRAWINGS.
C. SEE MECHANICAL DRAWINGS FOR DETAILS OF PIPE PENETRATION, PIPE
SUPPORTS AND ASSOCIATED STRUCTURAL REQUIREMENTS.
D. SEE MECHANICAL DRAWINGS FOR EQUIPMENT PADS AND PIPE SUPPORTS.
SEE DRAWINGS OF INDIVIDUAL STRUCTURES FOR SPECIFIC DESIGN CRITERIA BASED ON
THESE OVERALL CRITERIA FOR THE SITE.
1. BUILDING CODE:
A. 2023 FLORIDA BUILDING CODE, EIGHTH EDITION W/ ASCE 7-22
2. STRUCTURE RISK CATEGORY: III
3. DEAD LOADS: CALCULATED FOR STRUCTURE SELF-WEIGHT.
4. LIVE LOADS: (REDUCTIONS NOT USED)
A. FLOOR LIVE LOAD: 100 PSF
B. GRATING, PLATFORM AND STAIRS: 100 PSF (UNO).
C. EQUIPMENT LOADS: SEE PLANS.
5. FLUID PRESSURE LOADS: 63 PSF/FT (UNO).
6. SNOW LOAD DATA: N/A
7. WIND DESIGN DATA:
A. ULTIMATE DESIGN WIND SPEED, VULT (3-SECOND GUST): 174 MPH
B. NOMINAL DESIGN WIND SPEED, VASD: 135 MPH
C. TORNADO SPEED, VT: 50 MPH
D. EFFECTIVE PLAN AREA, AE: 1,000 SF
E. WIND EXPOSURE: C
F. SPECIAL WIND REGION: YES - HURRICANE
G. WIND-BORNE DEBRIS REGION: YES
8. EARTHQUAKE DESIGN DATA:
A. SITE CLASS: D (ASSUMED) 0.2 SECOND *1.0 SECOND
B. MAPPED SPECTRAL RESPONSE ACCELERATIONS: Ss = 0.075 g S1 = 0.032 g C. DESIGN SPECTRAL RESPONSE ACCELERATIONS:* Sds = 0.066 g Sd1= 0.046 g
(*5% DAMPED)
9. FLOOD LOADS:
A. REFERENCE MAP ("FIRM"): 12021C0416J
B. COASTAL HAZARD ZONE: AH
C. BASE FLOOD ELEVATION: 11.00
10. RAIN LOADS:
A. DESIGN RAINFALL INTENSITY: i = 10 INCHES/ HOUR. (200 YEAR/1 HOUR EVENT)
11. ICE LOADS: N/A
1. MATERIALS SHALL CONFORM TO THE FOLLOWING REQUIREMENTS UNLESS
OTHERWISE INDICATED ON THE DRAWINGS.
2. SEE PROJECT SPECIFICATIONS AND NOTES ON THE DRAWINGS OF SPECIFIC
STRUCTURES FOR DETAILED AND LOCATION-SPECIFIC REQUIREMENTS.
REINFORCING STEEL (FOR CONCRETE):
1. DEFORMED BARS:
A. TYPICAL: ASTM A615, GRADE 60.
B. WHERE INDICATED ON THE DRAWINGS: ASTM A706.
2. WELDED WIRE FABRIC: ASTM A064.
CONCRETE:
1. NORMAL DENSITY.
2. MINIMUM SPECIFIED CONCRETE COMPRESSIVE STRENGTH, f'c (AT 28 DAYS UNO).
A. STRUCTURES: "CLASS A" OR "CLASS A-NA" f'c = 4500 PSI.
B. FILL AND THRUST BLOCKS: "CLASS C" f'c = 2500 PSI.
C. PIPE ENCASEMENT: "CLASS A-NA" f'c = 4000 PSI.
D. ELECTRICAL DUCT ENCASEMENT: "CLASS CE" f'c = 3000 PSI.
CONFORM TO THE FOLLOWING REQUIREMENTS UNLESS OTHERWISE INDICATED ON THE
DRAWINGS.
EXCAVATION AND BACKFILLING:
1. EXPOSE AND PREPARE SUBGRADE AS SHOWN ON THE DRAWINGS AND SPECIFIED.
OBTAIN ENGINEER'S OBSERVATION OF SUBGRADE SURFACES, AS EXPOSED AND AS
PREPARED, BEFORE PROCEEDING WITH FOUNDATION CONSTRUCTION.
2. DO NOT PLACE BACKFILL AGAINST WALLS UNTIL STRUCTURES SUPPORTING THE TOP
OF THE WALL ARE IN PLACE, ARE COMPLETE, AND (IN THE CASE OF CONCRETE) HAVE
CURED TO THEIR MINIMUM SPECIFIED 28-DAY COMPRESSIVE STRENGTH.
3. WHERE BACKFILL MUST BE PLACED AGAINST WALLS BEFORE STRUCTURES ABOVE
ARE COMPLETE, PROVIDE BRACING FOR WALLS. KEEP BRACING IN PLACE UNTIL THE
STRUCTURE ABOVE IS COMPLETE AND (IN THE CASE OF CONCRETE) HAS CURED TO
ITS MINIMUM SPECIFIED 28- COMPRESSIVE STRENGTH.
CONCRETE:
1. SEE SC001/TYP FOR CONCRETE NOTES, INCLUDING CLEAR COVER AND LAP SPLICE
LENGTH REQUIREMENTS FOR REINFORCING.
2. SUBMIT LOCATIONS OF CONSTRUCTION JOINTS NOT SHOWN ON THE DRAWINGS
FOR ACCEPTANCE BY THE ENGINEER BEFORE FORM LAYOUT.
3. PROVIDE CHAMFER AT EXPOSED EDGES OF CAST-IN-PLACE CONCRETE. SEE
SPECIFICATIONS (03_11_07) FOR CHAMFERS.
4. PROVIDE REINFORCING:
A. AT CORNERS AND JUNCTIONS- AS INDICATED IN SC310/TYP, SUPPLEMENT WITH
ADDED BARS WHERE INDICATED ON THE DRAWINGS.
B. AT OPENINGS- AS INDICATED IN SC012/TYP.
5. WELDING OF REINFORCING IS NOT PERMITTED UNLESS DETAILED ON THE
DRAWINGS OR ACCEPTED IN ADVANCE BY THE ENGINEER.
6. MAINTAIN MINIMUM 3 INCHES CLEAR CONCRETE COVER BETWEEN REINFORCING
AND EMBEDMENTS.
7. FINISH CONCRETE AS SPECIFIED IN SECTION (03_35_29)
1. SEE DRAWING_____FOR KEY TO DRAWING TITLES AND SECTION CUTS, AND FOR
DEFINITION OF MATERIALS SHADING PATTERNS.
2. WELDING: SYMBOLS: IN ACCORDANCE WITH THE AMERICAN WELDING SOCIETY
(AWS) A2.4.
1. SEE DRAWING 00G03 FOR GENERAL LIST OF ABBREVIATIONS USED ON
DRAWINGS.
2. ABBREVIATIONS FOR NAMES OF TECHNICAL GROUPS MAY BE FOUND IN THE
PROJECT SPECIFICATIONS.
3. STRUCTURAL MEMBERS:
A. STEEL: ABBREVIATIONS AND DESIGNATIONS ARE IN ACCORDANCE WITH THE
AMERICAN INSTITUTE OF STEEL CONSTRUCTION'S STEEL CONSTRUCTION
MANUAL, CURRENT EDITION.
B. ALUMINUM: ABBREVIATIONS AND DESIGNATIONS ARE IN ACCORDANCE WITH
THE ALUMINUM ASSOCIATION'S ALUMINUM DESIGN MANUAL, CURRENT
EDITION.
AS DEFINED IN THE BUILDING CODE, DEFERRED DESIGN SUBMITTALS ARE PORTIONS
OF THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF PERMIT APPLICATION, AND
THAT ARE SUBSEQUENTLY SUBMITTED TO THE BUILDING OFFICIAL.
DEFERRED DESIGN SUBMITTALS FOR THE PROJECT INCLUDE:
1. DIVISION 3(03) CONCRETE.
A. 03_30_00 CONCRETE MIX
2. DIVISION 5(05) METALS.
A. (05_50_00) HANDRAILS AND GUARDRAILS.
(05_50_00) GRATING.
3. LIFTING EYES: SUBMIT DETAILS WITH CALCULATIONS DEMONSTRATING THE
SPECIFIED LOAD CAPACITY TO ENGINEER. DELIVER REMOVABLE EYES TO OWNER
AFTER INSTALLATION OF REMOVABLE PANELS.
METAL FABRICATIONS:
1. HANDRAILS AND GUARDRAILS:
A. ALUMINUM, EXCEPT WHERE OTHER MATERIALS ARE NOTED.
2. GRATING:
A. ALUMINUM WITH TYPE 316 STAINLESS STEEL FASTENERS, UNLESS OTHERWISE
NOTED.
B. GRATING AND ITS SEATS OR SUPPORTS SHALL BE THE SAME MATERIAL.
3. COVER PLATES:
A. ALUMINUM WITH TYPE 316 STAINLESS STEEL FASTENERS, UNLESS OTHERWISE
NOTED.
B. COVER PLATE AND ITS SEATS OR SUPPORTS SHALL BE THE SAME MATERIAL.
STRUCTURAL ALUMINUM:
1. SECTIONS:
A. SHAPES: ASTM B308, ALLOY 6061-T6
B. SHEET AND PLATE: ASTM B209,ALLOY 6061-T6
2. BOLTED CONNECTION-BOLTS AND ANCHOR BOLTS:
A. STAINLESS STEEL-TYPE 316, ASTM F593, GRADE B8M, CLASS 1, HEAVY HEX.
3. WELDED CONNECTIONS:
A. GAS METAL ARC (MIG) OR GAS TUNGSTEN ARC (TIG) PROCESS USING FILLER
ALLOY 4043 ELECTRODES.
STEEL, STAINLESS STEEL, AND ALUMINUM-CONNECTIONS:
1. BOLTED:
A. MADE USING 3/4 -INCH DIAMETER BOLTS.
B. HAVING A MINIMUM OF 2 BOLTS, SPACED NOT CLOSER THAN 3 INCHES ON
CENTER.
C. WITH A DISTANCE OF AT LEAST 1 1/2 INCHES FROM CENTER OF BOLT TO ANY
EDGE OF A PLATE OR STRUCTURAL ELEMENT.
2. WELDED:
A. FILLET WELDS: PER AWS CODE BASED ON THE THICKNESS OF THE MATERIALS
BEING JOINED, AND FULL LENGTH OF THE JOINT.
3. INTERFACE BETWEEN MATERIALS:
A. AT BOLTED CONNECTIONS THAT INCLUDE DIFFERENT METALS (E.G.:STEEL AND
STAINLESS STEEL. OR ALUMINUM AND STEEL) PROVIDE ISOLATING SLEEVES
AND WASHERS AS SPECIFIED IN SECTION (05_05_24).
B. WHERE ALUMINUM IS IN CONTACT WITH MASONRY OR CONCRETE, COAT
ALUMINUM SURFACES AS SPECIFIED IN SECTION (09_96_01).
4. POST-INSTALLED ANCHORS IN CONCRETE:
A. INSTALL IN FULL COMPLIANCE WITH ACCEPTED BUILDING CODE EVALUATION
REPORT AND MANUFACTURER'S INSTRUCTIONS.
B. DO NOT CUT, DAMAGE, OR INTERRUPT EXISTING REINFORCEMENT TO
INSTALL ANCHORS. USE NON-DESTRUCTIVE TESTING EQUIPMENT TO IDENTIFY
LOCATIONS OF REINFORCEMENT IN MEMBERS BEFORE DRILLING-HOLES
FOR ANCHORS.
STRUCTURAL STEEL:
1. SECTIONS
A. SHAPES W, WT: ASTM A 992 (Fy = 50 KSI) B. SHAPES S, ST, M, MT, HP, C, MC, L: ASTM A 36 (Fy = 36 KSI) C. PLATES AND BARS: ASTM A 36 (Fy = 36 KSI) D. PIPES: ASTM A 53, GRADE B (Fy = 35 KSI)
E. HOLLOW STRUCTURAL SECTION:
ROUND: ASTM A 500, GRADE C (Fy = 46 KSI)
SQUARE AND RECTANGULAR: ASTM A 500, GRADE C (Fy = 50 KSI)
2. CONNECTIONS:
A. BOLTS- STEEL TO-STEEL:
ASTM F 3125 GRADE A325 HIGH-STRENGTH BOLTS, WITH LOAD INDICATOR
WASHERS.
B. BOLTS- STEEL TO CONCRETE:
ANCHOR BOLTS WITH HEX FORGED HEAD.
ASTM F 593, STAINLESS TYPE 316 (304)
ASTM F 1554, GRADE 36 GALVANIZED.
C. WELDS- SHIELDED METAL ARC PROCESS USING E70-XX ELECTRODES.
STAINLESS STEEL:
1. ANSI TYPE 316/316L EXCEPT WHERE TYPE 304/304L IS INDICATED ON THE DRAWINGS.
2. SECTIONS: SHAPES AND BARS: ASTM A276
3. BOLTED CONNECTIONS- BOLTS AND ANCHOR BOLTS:
A. MATCH ALLOW OF THE STRUCTURAL MEMBERS CONNECTED.
B. TYPE 316/316L: ASTM F593, GRADE B8M, CLASS 1, HEAVY HEX.
C. TYPE 304/304L: ASTM F593, GRADE B8, CLASS 1, HEAVY HEX.
4. WELDED CONNECTIONS:
A. TYPE 316L: E316L- 15 ELECTRODES
B. TYPE 304L: E304L- 15 ELECTRODES.
12. CONSTRUCTION LOADS:
STRUCTURES HAVE BEEN DESIGNED FOR OPERATION LOADS ON COMPLETED
FACILITIES. UNTIL CONSTRUCTION IS COMPLETE AND MEMBERS HAVE ACHIEVED
THEIR DESIGN STRENGTH, PROTECT STRUCTURES AS REQUIRED BY SHORING,
BRACING AND BALANCING.
1. GEOTECHNICAL INVESTIGATION REPORT:
TITLE: PROPOSED SCRWTP REACTOR TANK 4
PREPARED BY: ARDAMAN & ASSOCIATES, INC.
REPORT NO: 19-33-4539 DATED: JUNE 2, 2019
2. FOUNDATION DESIGNS ARE BASED ON RECOMMENDATIONS IN THE
GEOTECHNICAL INVESTIGATION REPORT.
A. NET ALLOWABLE BEARING PRESSURE SEE PLANS: 1,500 PSF
B. GROUNDWATER EL 5.00
PROJECT NO.
LA
ST
S
AV
ED
B
Y:
FILE NAME:
MPJ
CHK
00S01
STRUCTURAL
BLEND TANK PLANS
204170_00S01.dwg
N D ia z
204170
DATEREV BY DESCRIPTION
DATE
CHECKED
DRAWN
DESIGNED
204170
JOB NO.
DRAWING NO.
SHEET NO.
SCALES ACCORDINGLY
VERIFY SCALES
THIS SHEET, ADJUST
IF NOT ONE INCH ON
BAR IS ONE INCH ON
ORIGINAL DRAWING
0 1"
OFAPRIL 2026
COLLIER COUNTY
SCRWTP LIME SOFTENING IMPROVEMENTS
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
G G
301 NORTH CATTLEMEN ROAD, SUITE 302
SARASOTA, FL. 343232
PHONE: (941) 371-9832 FAX: (941) 371-9873
SEALED BY VANESSA
NEGRON-VIEIRA ON THE
DATE ADJACENT TO THE
SEAL.
THE SIGNATURE MUST BE
VERIFIED ON ANY
ELECTRONIC COPIES.
GENERAL NOTES:
KEY NOTES:
1. SEE SHEET 00GS01 FOR STRUCTURAL GENERAL NOTES.
2. FOR PIPE SIZES AND LOCATIONS SEE MECHANICAL DRAWINGS.
3. SCJ = SLAB CONSTRUCTION JOINT PER TYPICAL DETAIL SD102/TYP
WCJ = WALL CONSTRUCTION JOINT PER TYPICAL DETAIL SD102/TYP.
4. NOT ALL STRUCTURAL PENETRATIONS ARE SHOWN OR
DIMENSIONED. COORDINATE PENETRATIONS WITH MECHANICAL
AND ELECTRICAL DRAWINGS. REINFORCE PENETRATIONS AT
CONCRETE PER DETAIL SC012/TYP UNLESS OTHERWISE NOTED.
1. PROVIDE (3) 42"X42" BILCO J-5AL WATER TIGHT HATCHES CAST
INTO THE DECK CONCRETE. DRAIN PIPES SHALL BE ROUTED TO
THROUGH THE EXTERIOR WALLS PER 08_31_14.
2. (2) #5X5'-0" AT RE-ENTRANT CORNERS (TYP).
3. 12"WX20" DP CONCRETE BEAM.
4. SAFETY GRAB BARS FOR HATCH ENTRY (TYP AT ALL ACCESS
HATCHES)
SCALE:
PLAN
1/8" = 1'-0"B
UPPER SLAB
SCALE:
PLAN
1/8" = 1'-0"A
LOWER SLAB
HPT 6.30
SUMP AREA
TOC 5.38
LPT 5.63
STAINLESS STEEL
LADDER (TYP OF 3)
SUMP AREA
TOC 5.38
HPT 6.30 HPT 6.30
SUMP AREA
TOC 5.38
(TYP)
C 00S02
SCW/WCJ
E 00S02
LPT 5.63
G 00S03
F 00S03
TYP
SC012
ALUMINUM
GUARDRAIL TYP
SR401
TYP
SR416
TYP
SR450
TYP
SR226
TOG 18.00
TYP
SR214
3 3
G 00S03
F 00S03
E 00S02
LPT 18.00 LPT 18.00
HPT 18.25
SCW/WCJ
45'-6"
1'-2" 21'-0"
1'-2"
21'-0" 1'-2"
2' (TYP)
1'-6"1'-6"
6'
(TYP)
2'-0" (TYP)
6' -0
(T
YP
9"
2' -0
" S Q
(T
YP
1 2
A
B
1' -6
'-0
1' -2
'-0
1' -2
'-4
'-6
1'
-6
10'-0"
1'-0"
10'-0"
1'-2"
10'-0" 10'-0"
9" (TYP) 9"
(T
YP
2' -0
TY
P)
'-0
SL
O
PE
SL
O
PE
SL
O
PE
SL
O
PE
TYP
SD602
(TYP)
1'-2" (TYP) 21'-7" 21'-7"
45'-6"
16'-6"
19'-0"
(TYP)
9"
9"
'-0
'-0
1'
-2
TY
P)
'-4
2'-0" (TYP)
A
B
1 2
1% SLOPE1% SLOPE
4'
(1 0)
T
1"
'-2
(1 1)
E Q
R
1'
2'-0" (TYP) 6'-0"
(TYP)
2'-0" (TYP)
2' -0
TY
P) 6'
-0
(T
YP
2' -0
TY
P)
2' -0
1'-0"
4'
(TYP)
(TYP)
1' -0
D 00S02
SLO
PE SLOPE D
00S02
FOR COORDINATES, SEE
MECHANICAL DRAWINGS
FOR COORDINATES, SEE
MECHANICAL DRAWINGS
4 (TYP)
(TYP)
(TYP)
(1 0)
T
1"
'-2
(1 1)
E Q
R
1' -0
4' -0
" 4'-0"
TOG 18.00
ST
S
AV
ED
B
Y:
FILE NAME:
DES
MPJ
CHK
00S02
STRUCTURAL
BLEND TANK SECTIONS
204170_00S02.dwg
N D ia z
DATEREV BY DESCRIPTION
DATE
CHECKED
DRAWN
DESIGNED
204170
JOB NO.
DRAWING NO.
SHEET NO.
SCALES ACCORDINGLY
VERIFY SCALES
THIS SHEET, ADJUST
IF NOT ONE INCH ON
BAR IS ONE INCH ON
ORIGINAL DRAWING
0 1"
OFAPRIL 2026
COLLIER COUNTY
SCRWTP LIME SOFTENING IMPROVEMENTS
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
G G
301 NORTH CATTLEMEN ROAD, SUITE 302
SARASOTA, FL. 343232
PHONE: (941) 371-9832 FAX: (941) 371-9873
SEALED BY VANESSA
NEGRON-VIEIRA ON THE
DATE ADJACENT TO THE
SEAL.
THE SIGNATURE MUST BE
VERIFIED ON ANY
ELECTRONIC COPIES.
GENERAL NOTES:
KEY NOTES:
1. SEE SHEET 00GS01 FOR STRUCTURAL GENERAL NOTES.
1. PROVIDE (3) 42"X42" BILCO J-5AL WATER TIGHT
HATCHES CAST INTO THE DECK CONCRETE. DRAIN
PIPES SHALL BE ROUTED TO THROUGH THE EXTERIOR
WALLS PER 08_31_14.
SCALE:
SECTION
3/8" = 1'-0"00S01
C
SCALE:
SECTION
3/8" = 1'-0"00S01
E
ALUMINUM
GUARDRAIL
(TYP)
TYP
SR401
TYP
SR416
TYP
SR450
LPT 18.00
(TYP)
FF GRADE, SEE
CIVIL
TOC 5.45 (TYP)
ALUMINUM
GUARDRAIL TYP
SR401
TYP
SR416
TYP
SR450
#5@8" EW
T&B (TYP)
#6@6" EW EF
TYP EXT WALLS
#6@6" EW EF
#5@8" EW EF
TYP INT WALLS
U.O.N.
HPT18.25
SLOPE GROUT
TOPPING (TYP)
TYP
SD130 (TYP)
12" WX20" DP CONCRETE
BEAM W/ (3)#6 T&B AND #3
STIRRUPS @ 12" O.C. (TYP)
(TYP OF 3)
TYP
SD150
TYP
SR214
#7@12" EW
T&B (TYP)
ALUMINUM
GUARDRAIL
TYP
SV103
#5@8" EW
T&B (TYP)
#6@6" EW EF
TYP EXT WALLS
STAINLESS
STEEL LADDER
SLOPE GROUT
TOPPING (TYP)
TOC VARIES
FF GRADE, SEE CIVIL
TOC 5.45
TOC 18.00
FF GRADE, SEE CIVIL
TOC 5.45
TYP
SC102(TYP)
1 2
1'-2"1'-0" (TYP)
1'-6" (TYP)
1'-2" (TYP)
1' -6
TOC 13.70
6'-0" (TYP)
1' -6
1'
-0 " M
IN
A
1' -6
LAP (TYP)
1" M
IN
TOC 11.45
TYP
SC102
LPT 5.63 (TYP)
TOC 5.38 (TYP)
2'-0"
(TYP)
2'-0"
(TYP)
EL 9.45
EL 11.45 (TYP)
12" WX20" DP CONCRETE
BEAM W/ (3)#6 T&B AND #3
STIRRUPS @ 12" O.C. (TYP)
(TYP OF 3)
TYP
SD150
SCALE:
SECTION
3/8" = 1'-0"00S01
D
TOC 9.45
#5@8" EW EF
TYP INT WALLS
U.O.N.
EL 16.33
TYP
SV103
9" (TYP)
1 (TYP)
TYP
SD602#7@12" EW
T&B (TYP)
#5@8" EW
T&B (TYP)
TYP
SD130 (TYP)
TYP
SD602(TYP)
TOC 5.38
STAINLESS STEEL
LADDER (TYP)
1' -0
" M
IN
7" (TYP)
SUMP AREA (TYP)
ST
S
AV
ED
B
Y:
FILE NAME:
DES
MPJ
CHK
00S03
STRUCTURAL
BLEND TANK ELEVATIONS
204170_00S03.dwg
N D ia z
DATEREV BY DESCRIPTION
DATE
CHECKED
DRAWN
DESIGNED
204170
JOB NO.
DRAWING NO.
SHEET NO.
SCALES ACCORDINGLY
VERIFY SCALES
THIS SHEET, ADJUST
IF NOT ONE INCH ON
BAR IS ONE INCH ON
ORIGINAL DRAWING
0 1"
OFAPRIL 2026
COLLIER COUNTY
SCRWTP LIME SOFTENING IMPROVEMENTS
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
G G
301 NORTH CATTLEMEN ROAD, SUITE 302
SARASOTA, FL. 343232
PHONE: (941) 371-9832 FAX: (941) 371-9873
SEALED BY VANESSA
NEGRON-VIEIRA ON THE
DATE ADJACENT TO THE
SEAL.
THE SIGNATURE MUST BE
VERIFIED ON ANY
ELECTRONIC COPIES.
GENERAL NOTES:
KEY NOTES:
1. SEE SHEET 00GS01 FOR STRUCTURAL GENERAL NOTES.
1. PROVIDE (3) 42"X42" BILCO J-5AL WATER TIGHT
HATCHES CAST INTO THE DECK CONCRETE. DRAIN
PIPES SHALL BE ROUTED TO THROUGH THE EXTERIOR
WALLS PER 08_31_14.
SCALE:
ELEVATION
3/8" = 1'-0"00S01
F
SCALE:
ELEVATION
3/8" = 1'-0"00S01
G
ALUMINUM
GUARDRAIL
(TYP)
TYP
SR401
TYP
SR416
TYP
SR450
LPT 18.00 (TYP)
ALUMINUM
GUARDRAIL TYP
SR401
TYP
SR416
TYP
SR450
TOC 5.45 (TYP)
TOC 13.70 (TYP)
TOC 18.00
FF GRADE, SEE CIVIL
TOC 5.45
B
TOC 13.70
1' -6
1' -6
19'-0"
(TYP)
1' -0
TY
P)
TYP
SC102
8"
12'-0" 2'-0"
FF GRADE, SEE CIVIL
2'-0 1/8"
(TYP)
8" (T
YP
SC001 REINFORCED CONCRETE - NOTES
TYP
SHEET 1 OF 3 12/18/2023
FORMED CONCRETE SURFACES FOR DRY CONDITIONS:
FORMED CONCRETE SURFACES EXPOSED TO WEATHER,
STIRRUPS AND TIES................................................2"
FORMED CONCRETE SURFACES EXPOSED TO WEATHER,
FORMED CONCRETE SURFACES FOR DRY CONDITIONS:
C. WALLS:
B. BEAMS AND COLUMNS:
FORMED CONCRETE SURFACES AND UNFORMED TOP SURFACES
7.
6.
5.
EXPOSED TO WEATHER, IN CONTACT WITH SOIL OR FLUIDS,
3.
2.
1.
A. SLABS AND JOISTS:
#7 BARS AND SMALLER..........................................1"
#8 BARS AND LARGER............................................1 1/2"
#8 BARS AND LARGER............................................1 1/2"
#7 BARS AND SMALLER..........................................1"
PRINCIPAL REINFORCEMENT................................2 1/2"
PRINCIPAL REINFORCEMENT................................2"
STIRRUPS, SPIRALS, AND TIES..............................1 1/2"
SEE DIVISION 03 SPECIFICATION FOR REQUIREMENTS FOR CONCRETE CONSTRUCTION.
WALL REINFORCEMENT AT CORNERS OR JUNCTIONS OF WALLS SHALL BE CONTINUOUS,
OR LOCATED OVER FLUIDS..........................................2"
IN CONTACT WITH SOIL OR FLUIDS, OR IN BEAMS LOCATED
OVER FLUIDS:
OR IN CONTACT WITH SOIL OR FLUIDS.......................2"
SLAB, BEAM AND COLUMN REINFORCING BARS SHALL HAVE A MINIMUM EXTENSION OR
ANCHORAGE INTO SUPPORTS IN ACCORDANCE WITH ACI 318 AND ACI 350.
DISPLACEMENT AS REQUIRED.
UNLESS OTHERWISE INDICATED ON THE DRAWINGS, CONCRETE COVER OVER #11 AND
SMALLER REINFORCING BARS SHALL BE AS FOLLOWS:
FORMED CONCRETE SURFACES AND UNFORMED TOP SURFACES FOR DRY CONDITIONS
UNLESS OTHERWISE INDICATED ON THE DRAWINGS, MINIMUM REINFORCEMENT OF
CONCRETE WALLS OR SLABS SHALL BE AS FOLLOWS. CONTACT ENGINEER FOR
LOCATIONS INSIDE CONCRETE.
MORE THAN 10" THICK: ..........................................#5 @ 12" EACH WAY, EACH FACE.
PROVIDE STIRRUP SUPPORT BARS SHALL BE TO SECURE TOP BARS AGAINST
10" THICK OR LESS: ................................................#5 @ 12" EACH WAY.
4. UNLESS OTHERWISE INDICATED ON THE DRAWINGS, DOWELS BETWEEN ADJACENT CONCRETE
PLACEMENTS SHALL BE THE SAME SIZE AND SPACING AS THE REINFORCEMENT WHICH IS
SPLICED TO THE DOWELS.
LAP SPLICED, OR TERMINATED IN AN ACI STANDARD 90 DEGREE HOOK. SEE DETAIL SC310/TYP.
SC001 REINFORCED CONCRETE - NOTES
TYP
SHEET 2 OF 3 12/18/2023
SPLICE SHALL BE IN CONTACT WITH EACH OTHER.
WHEN MULTIPLE BARS ARE SPLICED AT THE SAME SECTION, THE "CLEAR
D.
C.
B.
FORMED VERTICAL CONCRETE SURFACES.............................2"
11. LAP SPLICES:
D. FOOTINGS AND SLABS ON GRADE:
OR CONCRETE WORK MATS.......................................................3"
AT UNFORMED CONCRETE SURFACES CAST AGAINST SOIL, ROCK,
TOP SURFACE OF FOOTINGS AND SLABS................................SAME AS SLABS
8. WATERSTOPS:
A SLAB WITHOUT WATERSTOPS, CONTINUE WATERSTOP TO WALL/SLAB JOINT. WHERE
B. END WATERSTOPS 3" BELOW TOP OF WALLS. WHERE TOP OF WALL IS COVERED BY
TOP OF WALL IS COVERED BY A SLAB WITH WATERSTOPS, MAKE WATERSTOPS
ADEQUATE SYSTEMS TO PROVIDE WATER CURING WHERE REQUIRED.
10. DO NOT PLACE BACKFILL AGAINST WALLS UNTIL:
HAS REACHED THE MINIMUM SPECIFIED COMPRESSIVE STRENGTH (f'c).
BAR SPACING" IS DEFINED AS THE MINIMUM CLEAR DISTANCE BETWEEN THE BARS
OUTSIDE THE SPLICE LENGTH MINUS ONE BAR DIAMETER.
"TOP BARS" ARE HORIZONTAL REINFORCEMENT AT LOCATIONS WHERE MORE
9. CURE CONCRETE IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. WHERE WATER
CURING IS SPECIFIED, MEMBRANE CURING IS NOT ALLOWED.
A. THE CONTRACTOR IS WARNED THAT WATER CURING IS DIFFICULT AT TIMES DUE TO
WIND AND DRY CONDITIONS. STUDY SPECIFICATION REQUIREMENTS AND FURNISH
B. KEEP WATER CURED SURFACES VISIBLY MOIST AT ALL TIMES. FLOOD TOPS OF WALLS
NOT LESS THEN 3 TIMES DAILY.
ELEMENTS HAS REACHED THE MINIMUM SPECIFIED COMPRESSIVE STRENGTH (f'c).
B. CONNECTING SLABS AND BEAMS HAVE BEEN CAST AND CONCRETE IN THOSE
12. FORM EXPOSED CONCRETE CORNERS AND EDGES WITH 3/4" CHAMFER UNLESS
A. PROVIDE WATERSTOPS AT JOINTS IN SLABS AND WALLS OF LIQUID-CONTAINING
CONTINUOUS, SPLICING WATERSTOPS IN WALLS WITH WATERSTOPS IN SLAB.
A. WALLS HAVE BEEN CAST TO FULL HEIGHT OF STRUCTURE AND CONCRETE
UNLESS OTHERWISE INDICATED ON THE DRAWINGS, BARS AT A LAP
THAN 12 INCHES OF FRESH CONCRETE IS CAST IN THE MEMBER BELOW THE BAR.
OTHERWISE INDICATED ON THE DRAWINGS.
STRUCTURES, AND PORTIONS OF STRUCTURES BELOW THE DESIGN GROUNDWATER
LEVEL. MAKE WATERSTOPS CONTINUOUS THROUGH STRUCTURE, SPLICING
A.
WATERSTOPS IN SLABS WITH WATERSTOPS IN WALLS.
SEE TABLE 1 OF THIS DETAIL FOR LAP SPLICE LENGTHS.
SC001 REINFORCED CONCRETE - NOTES
TYP
SHEET 3 OF 3 12/18/2023
MORE THAN 2#4
MORE THAN 2
#11
MORE THAN 2
MORE THAN 2
#10
#9
MORE THAN 2
MORE THAN 2
#8
#7
MORE THAN 2
MORE THAN 4
#6
#5
MORE THAN 1
MORE THAN 2
MORE THAN 1
MORE THAN 2
MORE THAN 1
MORE THAN 2
MORE THAN 1
MORE THAN 2
MORE THAN 1
MORE THAN 2
MORE THAN 1
MORE THAN 1
MORE THAN 1
MORE THAN 4
MORE THAN 4
MORE THAN 4
MORE THAN 4
MORE THAN 4
MORE THAN 4
MORE THAN 2
MORE THAN 4 5469MORE THAN 2
MORE THAN 2
MORE THAN 2
* *88114
104*
*32
BAR
SIZE
LAP SPLICE LENGTH (INCHES)
TOP BARS OTHER BARS
MINIMUM CLEAR
BAR SPACING
(BAR DIA)
MINIMUM
COVER
(BAR DIA)
TABLE 1: REINFORCING BAR LAP SPLICES: f'c = 4000 PSI, Fy = 60,000 PSI
REINFORCING BAR LAP SPLICE TABLE NOTES:
1. TABULATED SPLICE LENGTHS ARE APPLICABLE ONLY WHEN BOTH REQUIREMENTS FOR
MINIMUM COVER AND FOR MINIMUM CLEAR BAR SPACING ARE SATISFIED.
2. = IF THE CLEAR BAR SPACING IS LESS THAN OR EQUAL TO TWO BAR DIAMETERS, OR THE
COVER IS LESS THAN OR EQUAL TO ONE BAR DIAMETER, THE LAP SPLICE LENGTH SHALL BE
INCREASED BY 50 PERCENT.
SC012 CONCRETE - REINFORCEMENT - ADDITIONAL
REINF AT OPENINGS - SLABS AND WALLSTYP
N 12/18/2023
"S" (TYP)
"S"/2 (TYP)
IN
TE
R R
U
PT
ED
(T
YP
(TYP)
"X"/2 (TYP)
"X" (TYP)
ADD BARS ON EACH
SIDE OF OPENING (TYP)
BARS AS INDICATED
ON THE DRAWINGS
BA
R
S (T
YP
INTERRUPTED
BARS (TYP)
C
IR
C U
LA
R
O
PE
N
IN
G R
EC
TA
N G
U
LA
R O
PE
N
IN
G
NOTES:
NOTE 6
(TYP)
NOTE 6
(TYP)
ADD 4 - #5 x 5'-0" DIAGONAL CORNER BARS.
PROVIDE 1 SET OF DIAGONAL BARS FOR WALLS
AND SLABS 12" THICK OR LESS. PROVIDE 1 SET
EACH FACE FOR WALLS AND SLABS GREATER
THAN 12" THICK.
1. AREA OF ADD BARS AT EACH EDGE OF OPENING IN EACH DIRECTION SHALL BE EQUAL TO OR
GREATER THAN 1/2 THE CROSS SECTIONAL AREA OF THE INTERRUPTED BARS.
2. PROVIDE STANDARD ACI HOOKS ON BARS IF STRAIGHT EXTENSION PAST THE OPENING, CANNOT
BE ACHIEVED.
3. PLACE ADD BARS IN SAME PLANES AS INTERRUPTED REINFORCING.
4. PLACE #5 DIAGONAL BARS ON INSIDE OF INTERRUPTED REINFORCING.
5. DIMENSION EQUALS OPENING DIMENSION MEASURED PERPENDICULAR TO ADD BARS PLUS LAP
SPLICE LENGTH.
6. 2" CLEAR TO CONCRETE OPENINGS OR OUTSIDE FACE OF PIPES AND PIPE SLEEVES. DO NOT
OVERCUT REINFORCEMENT FOR EASIER PLACEMENT OF WEEP RINGS AND FLANGES.
7. ADD BARS ARE NOT REQUIRED AT SIDES OF OPENINGS PARALLEL TO AND WITHIN 6" OF A WALL
OR BEAM.
SC040 CONCRETE REINFORCEMENT - ADHESIVE-BONDED
BARS AND ALL-THREAD RODSTYP
N 03/17/2025
REINFORCING BARS
ALL-THREAD RODS
EX
IS
TI
N
G C
O N
C R
ET
E
EXISTING CONCRETENEW CONCRETE
NOTE:
1. INSTALLATION OF REINFORCING BARS AND ALL THREAD RODS AS INDICATED IN THE
SPECIFICATIONS.
ADHESIVE (EPOXY UNO)
ADHESIVE (EPOXY UNO)
LAP SPLICE, UNLESS
OTHERWISE INDICATED
ON THE DRAWINGS
SEE DRAWINGS FOR
EMBEDMENT LENGTH
SEE DRAWINGS FOR
REINFORCING BAR
SIZE AND SPACING
ROUGHEN CONCRETE TO 1/4"
AMPLITUDE AND COAT WITH
EPOXY RESIN/PORTLAND
CEMENT BONDING AGENT
SEE DRAWINGS FOR ALL
THREAD ROD SIZE AND SPACING
SEE DRAWINGS FOR
EMBEDMENT LENGTH
SC310 CONCRETE - REINFORCEMENT - WALL CORNERS
AND INTERSECTIONSTYP
SHEET 1 OF 2 12/18/2023
ALTERNATE
DIRECTION
OF HOOKS
0"
0"
0" LA
P
SP
LI
C E
LA
P
SP
LI
C E
A
0"
STD 90°
HOOK
DETAIL - CORNER:
DOUBLE MAT
CHAMFER
CHAMFER
B
DETAIL - CORNER:
SINGLE MAT
0" 0"
NOTE 2
STD 90° HOOK
2" C
LR
C
- DOUBLE MAT
D
- SINGLE MAT
DETAIL - INTERSECTION: DETAIL - INTERSECTION:
NOTE 2
STD 90°
HOOK
NOTE 2
NOTE 4
NOTE 4
NOTE 2
NOTES:
1. BAR SIZE, SPACING, AND ORIENTATION OF BAR LAYERS SHALL BE AS INDICATED ON THE
DRAWINGS.
2. AT INTERSECTION, MAKE BAR SIZE THE LARGER OF BAR SIZES IN CONNECTING WALLS. PLACE
BARS IN SAME LAYERS AS AT CONNECTING WALLS (TYP).
3. BAR TAILS: 12 BAR DIAMETERS PLUS 12".
4. EXTERIOR VERTICAL BARS SHALL BE PROVIDED AT A SPACING THAT DOES NOT EXCEED THE
SPACING SPECIFIED ON THE DRAWINGS REGARDLESS OF THE WALL THICKNESS.
SC066 ANCHOR BOLT - SLEEVE FULL HEIGHT
TYP
N 12/18/2023
1 1/2" NON-SHRINK GROUT
SST LOCK NUT
1/8
DETAIL
1/4" 1/4"
"D" x
"D " M
IN
3"
M
IN
C O
VE
R
A
SST AB WITH 2 TO 4 THREADS EXPOSED.
SEE NOTE 3.
1/8" MIN WALL THICKNESS
SST PIPE SLEEVE.
ID = BOLT DIA + 2" MIN.
FILL SLEEVE WITH POLYURETHANE FOAM.
SEE NOTE 4.
A
SST PL 1/2" x SLEEVE DIA + 2"
SQ FOR BOLTS 1 1/8" DIA AND
SMALLER. PL 3/4" x SLEEVE DIA
+ 2" FOR BOLTS LARGER THAN
1 1/8" DIA.
EQUIPMENT BASE, BASE PLATE,
SOLE PLATE, OR SKID
SYNTHETIC RUBBER SEALING
COMPOUND BEAD CONTINUOUS
ALL AROUND EQUIPMENT BASE,
BASE PLATE, SOLE PLATE, OR SKID
NOTES:
1. "D" = DIAMETER OF ANCHOR BOLT.
2. ANCHOR BOLT DIAMETER AS INDICATED ON THE DRAWINGS. IF NOT INDICATED ON THE
DRAWINGS, THE ANCHOR BOLT SIZE SHALL BE AS RECOMMENDED BY THE EQUIPMENT
MANUFACTURER.
3. DO NOT USE ALL THREAD RODS AS A SUBSTITUTE FOR BOLTS WITH A BOLT HEAD.
4. COMPLETELY REMOVE ANY POLYURETHANE FOAM FROM CONCRETE, EQUIPMENT BASE,
BASE PLATE, SOLE PLATE, OR SKID, AND ANCHOR BOLTS ABOVE TOP OF CONCRETE.
5. DO NOT USE LEVELING NUTS TO SUPPORT AND LEVEL EQUIPMENT BASE, BASE PLATE, SOLE
PLATE, OR SKID.
SC064 ANCHOR BOLT - SLEEVE PLUS EMBED
TYP
N 03/27/2024
SE
E
N O
TE
1/8
SST LOCK NUT
1 1/2" NON-SHRINK GROUT
1/4" SST PLATE
DETAIL
x
"D
1/4" 1/4" x
"D " M
IN
SST AB WITH 2 TO 4 THREADS EXPOSED"D"
FILL SLEEVE WITH POLYURETHANE FOAM.
SEE NOTE 6.
A
A
1/8" MIN WALL THICKNESS
SST PIPE SLEEVE.
ID = BOLT DIA + 2" MIN.
EQUIPMENT BASE, BASE PLATE,
SOLE PLATE OR SKID
SYNTHETIC RUBBER SEALING
COMPOUND BEAD CONTINUOUS
ALL AROUND EQUIPMENT BASE,
BASE PLATE, SOLE PLATE, OR SKID
NOTES:
1. "D" = DIAMETER OF ANCHOR BOLT.
2. ANCHOR BOLT DIAMETER AS INDICATED ON THE DRAWINGS. IF NOT INDICATED ON THE
DRAWINGS, THE ANCHOR BOLT SIZE SHALL BE AS RECOMMENDED BY THE EQUIPMENT
MANUFACTURER.
3. WHERE CONCRETE SLAB OR BEAM THICKNESS WILL NOT ACCOMMODATE THE ANCHOR BOLT,
PROVIDE EXTRA THICKNESS OF SLAB OR BEAM.
4. DO NOT USE ALL THREAD RODS AS A SUBSTITUTE FOR BOLTS WITH A BOLT HEAD. SMOOTH
RODS THREADED AT THE ENDS MAY BE USED IF ACCEPTABLE TO THE ENGINEER. DO NOT
WELD NUTS TO THE THREADED RODS.
5. COMPLETELY REMOVE ANY POLYURETHANE FOAM FROM CONCRETE, EQUIPMENT BASE, BASE
PLATE, SOLE PLATE, OR SKID, AND ANCHOR BOLTS ABOVE TOP OF CONCRETE.
6. DO NOT USE LEVELING NUTS TO SUPPORT AND LEVEL EQUIPMENT BASE, BASE PLATE, SOLE
PLATE, OR SKID.
PROJECT NO.
LA
ST
S
AV
ED
B
Y:
FILE NAME:
CE
CE
CHK
STRUCTURAL
TYPICAL DETAILS 1
204071_00TS01.dwg hv o
DATEREV BY DESCRIPTION
DATE
CHECKED
DRAWN
DESIGNED
204170
JOB NO.
DRAWING NO.
SHEET NO.
SCALES ACCORDINGLY
VERIFY SCALES
THIS SHEET, ADJUST
IF NOT ONE INCH ON
BAR IS ONE INCH ON
ORIGINAL DRAWING
0 1"
OFAPRIL 2026
COLLIER COUNTY
SCRWTP LIME SOFTENING IMPROVEMENTS
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
G G
301 NORTH CATTLEMEN ROAD, SUITE 302
SARASOTA, FL. 343232
PHONE: (941) 371-9832 FAX: (941) 371-9873
SEALED BY VANESSA
NEGRON-VIEIRA ON THE
DATE ADJACENT TO THE
SEAL.
THE SIGNATURE MUST BE
VERIFIED ON ANY
ELECTRONIC COPIES.
00TS01
SC310 CONCRETE - REINFORCEMENT - WALL CORNERS
AND INTERSECTIONSTYP
SHEET 2 OF 2 12/18/2023
0"
G
DETAIL - INTERSECTION:
LAP SPLICE
STD 90° HOOK
CHANGE IN WALL THICKNESS
E
DETAIL - INTERSECTION:
DOUBLE MAT
F
DETAIL - INTERSECTION:
SINGLE MAT
NOTE 3
NOTE 30"
0"
LA
P
SP
LI
C E
1 BAR DIA CLR
2" C
LR
0"
NOTE 3
LA
P
SP
LI
C E
NOTE 2
STD 90° HOOK
0"
BAR AT BEND
SEE NOTE 2
LAP
SPLICE
LENGTH
BAR AT BEND
SEE NOTE 2
NOTE 4
SD130 CONCRETE JOINTS - CONSTRUCTION JOINT -
WALLS - STARTER WALL AT PVC WATERSTOPTYP
N SHEET 2 OF 2 12/18/2023
1. "S" EQUALS TYPICAL BAR SPACING INDICATED ON THE DRAWINGS.
2. PLACE AND ALIGN BARS BEFORE PLACING DOWELS. BAR SIZE TO MATCH SLAB BARS.
3. WATER-BLAST JOINT FACE AND PROJECTING REINFORCEMENT BEFORE PLACING CONCRETE.
4.
5.
6.
7.
8. 6" PVC WATERSTOP CENTERED VERTICALLY ON JOINT. PROVIDE WIRE TIES MAX 2'-0" OC.
HOG RINGS MAY BE USED IN LIEU OF WIRE LOOPS. THOROUGHLY CLEAN WATERSTOP
BEFORE PLACING CONCRETE.
NOTES:
10.
9. STANDARD 90° HOOK UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
DOWELS: SAME SIZE AND SPACING AS VERTICAL WALL BARS, UNLESS OTHERWISE NOTED.
PLACE NEAT CEMENT GROUT OVER JOINT FACE IMMEDIATELY BEFORE PLACING
CONCRETE. (SEE SPECIFICATIONS.)
STANDARD 90° HOOK WHERE INDICATED ON THE DRAWINGS. (ALTERNATE: PROVIDE 180°
HOOK WHERE REQUIRED BY SLAB THICKNESS.)
WHERE DRAWINGS INDICATE "W/ STRIP WSTP" PROVIDE LOW EXPANSION HYDROPHILIC
WATERSTOP AT TOP SURFACE OF JOINT AND CENTERED BETWEEN VERTICAL BARS.
CONSTRUCTION JOINT WHERE INDICATED ON THE DRAWINGS. WHERE WALL SURFACE IS
EXPOSED TO VIEW IN THE FINISHED WORK, PROVIDE V-GROOVE PER DETAIL SD050/TYP.
SD130 CONCRETE JOINTS - CONSTRUCTION JOINT -
WALLS - STARTER WALL AT PVC WATERSTOPTYP
N SHEET 1 OF 2 12/18/2023
2" C
LR
A
B
NOTE 7
NOTES 3 & 4
LA
P
SP
LI
C E
(T
YP
NOTE 5
NOTE 7
NOTES 3 & 4
NOTE 6
SECTION
NOTE 5
NOTES 3 & 4
NOTE 7
NOTE 8
NOTES 3 & 4
NOTE 7
NOTE 6
NOTE 8
2" C
LR
BA
R
S
AT
"S
4" 4"
(T
YP
) BA
R
S
AT
"S
4"
4"LA
P
SP
LI
C
E
0" (TYP AT LAPS)
LA
P
SP
LI
C E
(T
YP
) BA
R
S
AT
"S
4" 4"
0" (TYP AT LAPS)
(T
YP
BA
R
S
AT
"S
4"
4"LA
P
SP
LI
C
E
SECTION - "W/ WSTP"
NOTE 2 NOTE 2
NOTE 9NOTE 9
3"
NOTE 10
WALL AND SLAB REINF
SIZE AND SPACING AS
INDICATED ON THE
DRAWINGS
NOTE 10
SEE DETAIL SD150/TYP
FOR SLABS AT TOP OF
WALLS AND AT
INTERMEDIATE
ELEVATIONS ALONG
WALL HEIGHT
SD102 CONCRETE JOINTS - CONSTRUCTION JOINT -
WALL OR SLABTYP
SHEET 2 OF 2 12/18/2023
LAP SPLICE
LAP SPLICE (TYP)
NOTES:
1.
2.
3.
4.
WATER BEARING SLAB OR WALL
WATER BEARING SLAB LESS THAN 12" THICK
1 1/2 1 1/2
CL CONSTRUCTION JOINT
NOTE 2
NOTE 3
NOTE 4
(T
YP
0"
MIN 9"
EQ
EQ
" U
N O
NOTE 4 NOTE 3
CL CONSTRUCTION JOINT
0" (T
YP
CONTINUE REINF
THROUGH JOINT
"T "/2
"T
JOINT EDGES:
A. FOR WALLS AND BOTTOM OF EXPOSED SLABS: FORM EDGES WITH 1/2" CHAMFER.
B. FOR SLABS: EDGE TOP AND ENDS WITH 1/4" RADIUS.
"S" EQUALS TYPICAL BAR SPACING INDICATED ON THE DRAWINGS.
"T" EQUALS SLAB OR WALL THICKNESS.
MIN 9"
NOTE 2
CONTINUE REINF THROUGH JOINT
5. STOP REINFORCING 2" CLEAR OF JOINT.
WATER-BLAST EXPOSED JOINT FACE AND PROJECTING REINFORCEMENT BEFORE
PLACING CONCRETE.
NOTE 5
NOTE 5
6" WATERSTOP CENTERED ON JOINT - SEE DETAIL SD004/TYP. PROVIDE WIRE TIES MAX 2'-0" OC.
HOG RINGS MAY BE USED IN LIEU OF WIRE LOOPS. THOROUGHLY CLEAN WATERSTOP BEFORE
PLACING CONCRETE IN SECOND POUR.
SD102 CONCRETE JOINTS - CONSTRUCTION JOINT -
WALL OR SLABTYP
SHEET 1 OF 2 12/18/2023
NON-WATER BEARING WALL OR SLAB
SINGLE LAYER REINFORCEMENT
NON-WATER BEARING WALL OR SLAB
DOUBLE LAYER REINFORCEMENT
CL CONSTRUCTION JOINT
CL CONSTRUCTION JOINT
BARS @ "S" 2 1/2" 2 1/2" BARS @ "S"
BARS @ "S" 2 1/2" 2 1/2" BARS @ "S"
CONTINUE REINF
THROUGH JOINT
TYP SPACING OF
REINF WHERE "S" > 8"_
TYP SPACING OF
REINF WHERE "S" < 8"
NOTE 2
0" (T
YP
CONTINUE REINF
THROUGH JOINT
LAP SPLICE
NOTE 2 NOTE 3
0" (T
YP
LAP SPLICE NOTE 3
NOTE 2
TYP FOR ALL
FIGURES
THIS
DETAIL
4" 4"
NOTE 5
NOTE 5
SD050 CONCRETE JOINTS - V-GROOVE
TYP
N 12/18/2023
JOINT
3/ 4"
3/ 4"
3/4"
SD008 CONCRETE JOINTS - PVC WATERSTOPS -
PREFABRICATED JOINTSTYP
10/17/2025
BOND BOND
BOND
BOND
VERTICAL CROSS
EXPANSION JOINT.
EXPANSION JOINT
NOTES:
1. MAKE WELDS AS SPECIFIED AND IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
2. CROSSES AND TEES SHALL BE FACTORY PREFABRICATED BY THE
MANUFACTURER. FIELD WELDS SHALL BE BUTT WELDS ONLY.
CROSS TEE
IN-PLANE JOINTS
CROSS
TEE WALL TO FOOTING AT EXPANSION JOINT
OUT-OF-PLANE JOINTS
VERTICAL / WALL
HORIZONTAL / SLAB
WALL TO FOOTING /
SLAB CONSTRUCTION
JOINT
SD004 CONCRETE JOINTS - PVC WATERSTOPS - SCHEDULE
TYP
12/18/2023
3/8"
3/8"
3/8"1"
3/8" -
1/4"
"D""C""B"TYPE
"E" = NUMBER OF
"F""E"
RIBS PER SIDE
3/8"3/8" 7 9/32"7/8"
7 1/4"2" 3/8" 3/8"
"A"
"B"
"D"
"C"
"F"
9"
"A"
6"
9"
6"
APPLICATION
(MINIMUM)
CONSTRUCTION AND
FOR USE WITH
EXPANSION JOINTS
1" AND NARROWER
EXPANSION JOINTS
TENSION/COMPRESSION
NOTES:
1. SEE SPECIFICATIONS FOR MATERIAL REQUIREMENTS.
2. DIMENSIONS ARE MINIMUM, UNLESS OTHERWISE NOTED.
CONTROL JOINTS
WIDER THAN 1" AND
RING BEAM AT DIGESTERS
DETAIL EM071/TYP ONLY
W/O CENTER BULB
CENTER BULB
CENTER BULB
CENTER BULB
PROJECT NO.
LA
ST
S
AV
ED
B
Y:
FILE NAME:
CE
CE
CHK
STRUCTURAL
TYPICAL DETAILS 2
204071_00TS02.dwg hv o
DATEREV BY DESCRIPTION
DATE
CHECKED
DRAWN
DESIGNED
204170
JOB NO.
DRAWING NO.
SHEET NO.
SCALES ACCORDINGLY
VERIFY SCALES
THIS SHEET, ADJUST
IF NOT ONE INCH ON
BAR IS ONE INCH ON
ORIGINAL DRAWING
0 1"
OFAPRIL 2026
COLLIER COUNTY
SCRWTP LIME SOFTENING IMPROVEMENTS
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
G G
301 NORTH CATTLEMEN ROAD, SUITE 302
SARASOTA, FL. 343232
PHONE: (941) 371-9832 FAX: (941) 371-9873
SEALED BY VANESSA
NEGRON-VIEIRA ON THE
DATE ADJACENT TO THE
SEAL.
THE SIGNATURE MUST BE
VERIFIED ON ANY
00TS02
SD602 CONCRETE - EQUIPMENT - PROCESS -
SLIDE GATE W/ FACE MOUNTED FRAMETYP
S 12/18/2023SHEET 2 OF 2
D
M
IN
AD
D
L R
EI
N
F
AT
O
PN
G
VERT REINF
AT OPNG
WALL
2"CLR
2" C
LR
1/
2"
1/ 2"
GATE FRAME
WALL GASKET
SIDE SEAL
(TYP)
GATE SLIDE
BA
C
K
ED
G E
O F
VE
R
T R
EI
N
F:
1/ 2"
M
AX
GATE ANCHORS.
NOTE 1 & 2.
TYP HORIZ
WALL REINF
PLAN: SIDE - WALL MOUNTED
M
IN
SC
2/
TY
P U
N O
NOTES:
1. CAST-IN ANCHOR BOLTS OR POST-INSTALLED MECHANICAL CONCRETE ANCHORS.
CONFIRM SIZE AND MINIMUM EFFECTIVE EMBEDMENT OF ANCHORS AFTER APPROVAL
OF PROPOSED GATES, AND BEFORE CONSTRUCTION OF CONCRETE WALLS.
2. IF UNSEATING HEAD CONDITIONS REQUIRE SUPPLEMENTARY CONCRETE REINFORCEMENT
FOR ANCHORS AT VERTICAL EDGES OF GATE OPENING, ADVISE ENGINEER BEFORE
SUBMITTAL OF WALL REINFORCEMENT SHOP DRAWINGS. INDICATE REQUIRED
SUPPLEMENTARY REINFORCEMENT SIZE AND SPACING.
3. REINFORCEMENT LOCATION AT ANCHORS: 3 1/2 INCHES MAX (TO PROVIDE 1 INCH BETWEEN
OUTSIDE DIAMETER OF BAR AND CENTERLINE OF ANCHOR).
4. POST-INSTALLED ANCHORS: DRILLING FOR INSTALLATION OF POST-INSTALLED
ANCHORS MUST NOT DAMAGE WALL REINFORCEMENT.
WHERE POST-INSTALLED ANCHORS ARE REQUIRED OR PROPOSE, SUBMIT
PROPOSED METHODS TO CONFIRM THAT LOCATIONS OF REINFORCEMENT
WILL NOT CONFLICT WITH DRILLING LOCATIONS BEFORE PLACING
REINFORCEMENT AND CONCRETE.
SD602 CONCRETE - EQUIPMENT - PROCESS -
SLIDE GATE W/ FACE MOUNTED FRAMETYP
S 12/18/2023SHEET 1 OF 2
1.5 x "T" BLOCKOUT 1.5 x "T"
"T
1/
2"
H
1.5
"T
A
- BOTTOM - FLUSH INVERT
B
M
IN
M
IN
C
2" C
LR
WALL
WALL VERT
REINF
TOP SEAL
TOP OF
GATE
OPNG
BOTTOM - WALL MOUNTED
SECTION: SECTION:
TOP - WALL MOUNTED
WALL
GASKET
BOTTOM
SEAL
WALL
GASKET
GATE
FRAME
WALL
GASKET
GATE SLIDE
BOTTOM
SEAL
NON-SHRINK
CEMENT
GROUT
WALL AS REQ'D FOR ANCHOR
INSTALLATION
(6" MIN/12" MAX)
SL
AB
"T
GROUTED
(TYP)
SECTION:
WALL GATE SLIDE
1/
2" M
AX
SL
AB
SEE DWGS FOR
JOINT DETAILS
GATE ANCHORS.
NOTE 1.
GATE ANCHORS.
NOTE 1.
1/
2"
1/ 2"
M
IN
GATE ANCHORS.
NOTE 1.
M
IN
1/
2"
1/ 2"
M
IN
GATE SLIDE
N O
TE
N O
TE
SD174 CONCRETE JOINTS - CONSTRUCTION JOINT -
BEAM POCKET AT CONCRETE WALLTYP
12/18/2023
"T"
(12" MIN)
A SECTION
T/2
CONC SLAB
BEAM POCKET DEPTH
(WIDTH = BEAM WIDTH)
NOTES:
1. COAT BACK, SIDES & BOTTOM OF BEAM POCKET WITH BOND BREAKER BEFORE PLACING SLAB AND
BEAM.
CONTINUE HORIZONTAL
WALL REINFORCEMENT
THROUGH POCKET
UNO
WALL
REINFORCEMENT
PER DETAIL SD150/TYP
CONSTRUCTION JOINT
SEE DRAWINGS
FOR DETAILS
CONCRETE WALL
BEAM DROP
BEAM
REINFORCEMENT.
SEE DRAWINGS.
NOTE 1
SD150 CONCRETE JOINTS - CONSTRUCTION JOINT -
WALLS AT ELEVATED SLABSTYP
N SHEET 3 OF 3 12/18/2023
1. "S" EQUALS TYPICAL BAR SPACING INDICATED ON THE DRAWINGS.
2.
3. WATER-BLAST JOINT FACE AND PROJECTING REINFORCEMENT BEFORE PLACING CONCRETE.
4.
5.
6.
8. 6" PVC WATERSTOP CENTERED VERTICALLY ON JOINT. PROVIDE WIRE TIES MAX 2'-0" OC.
HOG RINGS MAY BE USED IN LIEU OF WIRE LOOPS. THOROUGHLY CLEAN WATERSTOP
BEFORE PLACING CONCRETE.
9.
AT INTERSECTION, MAKE BAR SIZE THE LARGER OF BAR SIZES IN ADJACENT SLAB OR
WALL. PLACE BARS AT SAME LAYERS AS IN ADJACENT SLAB OR WALL.
NOTES:
PLACE NEAT CEMENT GROUT OVER JOINT FACE IMMEDIATELY BEFORE PLACING CONCRETE.
(SEE SPECIFICATIONS)
1 BAR DIAMETER CLEAR.
STANDARD 90° HOOK UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
WHERE DRAWINGS INDICATE "W/ STRIP WSTP" PROVIDE LOW EXPANSION HYDROPHILIC
WATERSTOP AT TOP SURFACE OF JOINT AND CENTERED BETWEEN VERTICAL BARS.
CONSTRUCTION JOINT WHERE INDICATED ON THE DRAWINGS. WHERE WALL SURFACE IS
EXPOSED TO VIEW IN THE FINISHED WORK, PROVIDE V-GROOVE PER DETAIL SD050/TYP.
10.
7.
STANDARD 180° HOOK WHERE INDICATED ON THE DRAWINGS.11.
STANDARD 180° HOOK (ALTERNATE: 90° HOOK ROTATED OUT OF VERTICAL PLANE IF
APPROVED BY ENGINEER.)
SD150 CONCRETE JOINTS - CONSTRUCTION JOINT -
WALLS AT ELEVATED SLABSTYP
N SHEET 2 OF 3 12/18/2023
B
0"
NOTE 6
(T
YP
) BA
R
S
AT
"S
4" 4"
LA
P
SP
LI
C E
NOTE 6
NOTE 9
T.O. SLAB
NOTE 5
NOTES 3 & 4
LAP
SPLICE
NOTE 5
T.O. SLAB
NOTE 5
NOTES 3 & 4
SLAB AT 1 SIDE SLAB AT 2 SIDES
NOTES 3 & 4(T
YP
LA
P
SP
LI
C
E
BA
R
S
AT
"S
4" 4"
SECTION - "W/ WSTP"
NOTE 8
NOTE 8
NOTE 8
NOTES 3 & 4 NOTE 6
0" (T
YP
)NOTE 2
NOTE 9
NOTE 8
NOTE 8
NOTES 3 & 4
T.O. SLAB
(TYP)
NOTE 2
(TYP)
3"
NOTES 3 & 4
NOTE 2 (TYP)
3"3"
3"
3"
NOTE 2 (TYP)
NOTE 8
NOTE 11
WALL AND SLAB
REINF SIZE AND
SPACING AS
INDICATED ON THE
DRAWINGS
SEE DETAIL
SD130/TYP FOR
SLABS AT BOTTOM
OF WALL
SD150 CONCRETE JOINTS - CONSTRUCTION JOINT -
WALLS AT ELEVATED SLABSTYP
N SHEET 1 OF 3 12/18/2023
NOTE 5
0"
NOTE 6
4" MAX
0" (T
YP
A
SECTION
(T
YP
) BA
R
S
AT
"S
4" 4"
LA
P
SP
LI
C E
NOTE 6
NOTE 9
T.O. SLAB
NOTES 3 & 4
NOTE 2 NOTE 2
NOTE 9
LAP
SPLICE
NOTE 5 T.O. SLAB
NOTES 3 & 4
NOTE 5
NOTES 3 & 4
SLAB AT 1 SIDE SLAB AT 2 SIDES
NOTES 3 & 4
NOTES 3 & 4
(T
YP
LA
P
SP
LI
C
E
BA
R
S
AT
"S
4" 4"
NOTES 3 & 4 NOTE 6
T.O. SLAB
NOTE 10
NOTE 10
NOTE 10
NOTE 10
NOTE 7
NOTE 10
(TYP)(TYP)
NOTE 2 (TYP)
NOTE 2 (TYP)
NOTE 11
WALL AND SLAB
REINF SIZE AND
SPACING AS
INDICATED ON THE
DRAWINGS
SEE DETAIL
SD130/TYP FOR
SLABS AT BOTTOM
OF WALL
SD546 CONCRETE - EQUIPMENT GROUTING
TYP
N 12/18/2023
JACK SCREW
(TYP)
HEAD BOX ON ONE
SIDE OF FORMS
EQUIPMENT
SEE NOTE 5
"T
GROUT
FORMS
CONCRETE
EQUIPMENT
FOUNDATION
POUR GROUT
HERE
NON-SHRINK GROUT.
SEE NOTE 6.
CIRCULAR STEEL WASHER.
EPOXY BOND TO CONCRETE.
SEE NOTE 7
EQUIPMENT BASE,
BASEPLATE,
SOLEPLATE,
OR SKID
SEE NOTE 4
"T"
(TYP)
EQUIPMENT ANCHORS
AS INDICATED ON DRAWINGS
NOTES:
1. "T" = EQUALS GROUT THICKNESS INDICATED ON THE DRAWING. 1" MINIMUM GROUT
THICKNESS.
2. FILL ANCHOR SLEEVES WITH POLYURETHANE FOAM BEFORE GROUTING.
3. DO NOT USE LEVELING NUTS ON EQUIPMENT ANCHORS.
4. PREPARE SURFACE OF EQUIPMENT BASES, BASE PLATES, SOLE PLATES, AND SKIDS IN
CONTACT WITH GROUT AS SPECIFIED IN SECTION 15050 (46_05_10).
5. PREPARE SURFACES OF CONCRETE FOUNDATION IN CONTACT WITH GROUT AS
SPECIFIED IN SECTION 15050 (46_05_10).
6. PLACE NON-SHRINK GROUT AS SPECIFIED IN SECTION 15050 (46_05_10).
7. AFTER GROUT SETS, TRIM GROUT TO 45 DEGREE CHAMFER.
SD512 CONCRETE - EQUIPMENT BASE -
DEEP ANCHORSTYP
N 12/18/2023
1:1 SLOPE (TYP)
LAP SPLICE
CL ANCHOR BOLT
3" CLR FOR SLABS ON GRADE.
2" CLR FOR ALL OTHER SLABS.
H
EI
G H
T
SEE NOTE 2
4" MIN ALL
AROUND
"D"
TYP
SC064
2" CLR (TYP 4 SIDES)
#5 @ 12" H1E (TYP 4 SIDES)
3/4" CHAMFER 2"
C
LR
ROUGHEN CONCRETE TO
1/4" AMPLITUDE AND
COAT WITH EPOXY RESIN/
PORTLAND CEMENT
BONDING AGENT
N O
TE
(OPT)
EQUIPMENT BASE, BASE
PLATE, SOLE PLATE, OR
SKID
#5 @ 12" (TYP 4 SIDES)
NOTE 6
ANCHOR BOLTS
NOTE 5
NOTES:
1. "D" = DIAMETER OF ANCHOR BOLT.
2. THE EDGE DISTANCE ON THE ANCHOR BOLTS SHALL NOT BE LESS THAN 6" OR 8 x "D".
3. PAD DIMENSIONS AND ANCHOR BOLT SIZE SHALL CONFORM TO EQUIPMENT MANUFACTURER'S
REQUIREMENTS.
4. HEIGHT TO SUIT EQUIPMENT FURNISHED OR AS INDICATED ON THE DRAWINGS.
5. WHERE CONCRETE SLAB OR BEAM THICKNESS WILL NOT ACCOMMODATE THE ANCHOR BOLT,
PROVIDE EXTRA THICKNESS FOR SLAB OR BEAM.
6. PROVIDE HOOPS OR CORNERS PER DETAIL SC310/TYP.
1 1/2" NON-SHRINK
GROUT. SEE
DETAIL SD546/TYP
PROJECT NO.
LA
ST
S
AV
ED
B
Y:
FILE NAME:
CE
CE
CHK
STRUCTURAL
TYPICAL DETAILS 3
204071_00TS03.dwg hv o
DATEREV BY DESCRIPTION
DATE
CHECKED
DRAWN
DESIGNED
204170
JOB NO.
DRAWING NO.
SHEET NO.
SCALES ACCORDINGLY
VERIFY SCALES
THIS SHEET, ADJUST
IF NOT ONE INCH ON
BAR IS ONE INCH ON
ORIGINAL DRAWING
0 1"
OFAPRIL 2026
COLLIER COUNTY
SCRWTP LIME SOFTENING IMPROVEMENTS
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
G G
301 NORTH CATTLEMEN ROAD, SUITE 302
SARASOTA, FL. 343232
PHONE: (941) 371-9832 FAX: (941) 371-9873
SEALED BY VANESSA
NEGRON-VIEIRA ON THE
DATE ADJACENT TO THE
SEAL.
THE SIGNATURE MUST BE
VERIFIED ON ANY
00TS03
SR226 STAIR - FLUSH TOP TREAD - ALUMINUM LANDING
N SHEET 1 OF 8 09/11/2024
TYP FLANGES
G
AND WEB
D
G
B
M
C
B
A PLAN - TOP LANDING
SEE DRAWINGS.
9"
DOWN
AL GRATING
AL CS10
T
TOP TREAD
FLUSH WITH
TOP OF
LANDING
TYP
SR605 GRATING SEAT
MIN = MATCH
STAIR WIDTH
CONC STRUCTURE
CONC STRUCTURE
12" MIN
1'-4"
MIN
H (TYP EA CS10 TO
WALL CONNECTION)
ST
AI
R W
ID
TH
SE
E D
R
AW
IN
G
S.
6"
AL CS10 x 6.14 (TYP 3 SIDES
AROUND LANDINGS)
(SIM - L BRACE
ON FAR SIDE
OF PLATE)
ELEVATION - TOP LANDING
AL L 3 x 3 x 3/8
BRACE (TYP BOTH
SIDES OF LANDING)
AL HANDRAIL
AL GUARDRAIL
AL GRATING
AL L 3 x 3 x 3/8 (UNDER TOP
FLANGES OF CS10)
AL GUARDRAIL
T.O. GRATING =
T.O. STRUCTURE
5/8" AL PL
AL L 3 x 3 x 3/8
(TYP)
BRACE (TYP BOTH
SIDES OF LANDING)
L
D
C
D
DETAIL
2"
2"
AL GRATING
SECTION - TOP LANDING
1"
(TYP)
CONC STRUCTURE
TYP
SR605
BED PLATE IN EPOXY
GEL FOR UNIFORM
BEARING
AL L 3 x 3
H
(TYP EA CS10
TO WALL CONN)
3"
NOTES:
1/2"
1. BEFORE DRILLING CONCRETE FOR ANCHORS, LAY OUT ALL ANCHOR PLATES AND HOLES.
FIELD LOCATE REINFORCEMENT WITHIN 6" OF EACH HOLE. ADJUST PLATE LOCATIONS
HORIZONTALLY TO AVOID MAXIMUM NUMBER OF BARS.
2. COAT ALUMINUM SURFACES IN CONTACT WITH CONCRETE, AND INSTALL ISOLATION SLEEVES
AND WASHERS AT DISSIMILAR METALS, AS SPECIFIED.
AL L3x3 BRACE
AL HANDRAIL (TYP
BOTH SIDES)
1/2"
AL GUARDRAIL
(4) 3/4"Ø SST CA
(2) 3/4"Ø SST BOLTS (TYP)
SR226 STAIR - FLUSH TOP TREAD - ALUMINUM LANDING
TYP
N SHEET 2 OF 8 09/11/2024
CONC WALL
(TYP)
AL CS10 x 6.14
CONC WALL
AL L 3 x 3 x 3/8
G
BRACE (TYP BOTH
SIDES OF LANDING)
D
Q
P
F -M
C
F
E
SECTION - INTERMEDIATE LANDING
PLAN - INTERMEDIATE LANDING
6"
AND WEB
TYP FLANGES
DOWN
UP
AL GRATING
AL CS10
TYP
SR605 GRATING SEAT
SIM
TOP TREAD
FLUSH WITH
TOP OF
LANDING
AL GUARDRAIL
U
N
T
9"
SEE DRAWINGS
MIN = MATCH
STAIR WIDTH
ST
AI
R W
ID
TH
SE
E
D R
AW
IN
G S
(TYP 3 SIDES AROUND
LANDING)
AL L 3 x 3 x 3/8
(UNDER TOP
FLANGES OF CS10S)
AL HANDRAIL
AL GUARDRAIL
SR226 STAIR - FLUSH TOP TREAD - ALUMINUM LANDING
TYP
N SHEET 3 OF 8 09/11/2024
4"5/8" AL PL
1/4 1/4
(4) 3/4"Ø SST CA
AL BAR 1/4" x
5/8" AL PL
HEIGHT OF GRATING
J
H
K 5J
G
DETAIL
DETAIL DETAIL
2"
5/8" AL PL
AL L 3 x 3
AL CS10
AL L 3 x 3
AL GRATING
AL CS10
AL GRATING
AL CS10
1/
2"
AL BAR (TYP 3
SIDES AROUND
LANDING)
x CONT (TYP 3 SIDES
AROUND LANDING)
1/
2"
1 1/2"
TO CS10
3"
G
1" 2"
2"
1/2"
TYP BAR
CJP:
1/
2"
BED WALL PLATE
IN EPOXY GEL FOR
UNIFORM BEARING
1"(TYP)
1/ 2"
(2) 3/4"Ø SST
BOLTS (TYP)
(2) 3/4"Ø SST
BOLTS (TYP)
(2) 3/4"Ø SST BOLTS
G
R
AT
IN
G
TH
IC
KN
ES
S
SR226 STAIR - FLUSH TOP TREAD - ALUMINUM LANDING
TYP
N SHEET 4 OF 8 09/11/2024
G
1/4
5/16 5/16
TYP FLANGES
AND WEB
TYP
L
K
M
SECTION
SECTION
DETAIL
1 1/2"1 1/2"
5/8" AL PL
5/16 5/16
1 1/2"1 1/2"
1 1/2"
1 1/2"
5/8" AL PL
AL CS10
AL CS10
8"
8"
1/
2"
4" T.O. CONC
8"
4"
1 1/2"
7"
3"
1/2"
1/2"
1/2"
AL CS10
SEE DRAWINGS.
CONNECTION PER
DETAIL V/8 (TYP)
STAIR STRINGER.
AL L 3 x 3 HORIZ BRACE
(SEE DETAIL D/2 FOR CA'S)
/2
/2
BOLTS
13/16"Ø HOLES
FOR 3/4"Ø
SST CA (TYP 4)
13/16"Ø HOLES
FOR 3/4"Ø
SST CA (TYP 4)
SR226 STAIR - FLUSH TOP TREAD - ALUMINUM LANDING
TYP
N SHEET 5 OF 8 09/11/2024
STRINGER
CUT ANGLE LEG
TO CLEAR STAIR
SLOTTED HOLE
N STAIR STRINGER TO PLATFORM CONNECTION
AL CS10
AL GRATING
AL CS10
AL GRATING
STAIR TREAD
AL STAIR
STRINGER
3/4"Ø SST BOLT. SEE DETAIL U/8
AL L 4 x 3 x 3/8" LLV
AL L 4 x 3 x 3/8" - VERT
SR226 STAIR - FLUSH TOP TREAD - ALUMINUM LANDING
TYP
N SHEET 6 OF 8 09/11/2024
1 1/2" 8" 1 1/2"
1/
2"
1/ 2"
7" 2"
2"
1/4 1/41/4
AL BAR 1/4" x
1/4 1/4
AL 3 x 3
TYP
HEIGHT OF GRATING
S
R
Q DETAIL
P
R
2"
2"
DETAIL
DETAIL
AL L 4 x 3 x 3/8
1"
(TYP)
AL CS10
AL CS10
AL L 3 x 3
5/8" AL PL
AL GRATING
AL CS10
AL CS10
8"
5/16 5/16
S DETAIL
AL L 4 x 3 x 3/8
AL CS10
3" x CONT (TYP 3 SIDES
AROUND LANDING)
1/2"
G
1 1/2" 1" 2"
BED PLATE IN
EPOXY GEL FOR
UNIFORM BEARING
1/4
1/4 1/4
SST BOLTS
(SEE DETAIL P/-)
2" 2"
3"
5/8" AL PL
1/ 2"
CJP:
TYP BAR
TO CS10
13/16"Ø HOLES FOR
3/4"Ø CA (TYP 4)
(2) 3/4"Ø SST BOLTS
(2) 3/4"Ø SST
BOLTS
(4) 3/4"Ø SST CA
SR226 STAIR - FLUSH TOP TREAD - ALUMINUM LANDING
TYP
N SHEET 7 OF 8 09/11/2024
SR220 STAIR - FLUSH TOP TREAD - CONNECTIONS
TYP
N 12/23/2024
= T.O. TREAD
T.O. PLATFORM
1" (TYP)
"T" + 1"
FULL TREAD
= T.O. TREAD
T.O. PLATFORM
1" (TYP)
TYP T&B
EA ANGLE 3/16
3/16
NOTES:
"T" (11" MIN)
(TYP)
BEAM. SEE DRAWINGS
FOR DETAILS
(2) 3/4"Ø
SST BOLTS.
TYP EA
CHANNEL
TO BEAM
A
CONNECTION TO BEAM
1" MAX
"T" + 1"
FULL TREAD
"T" (11" MIN)
(TYP)
1" MAX
B
CONNECTION TO CHANNEL
CHANNEL.
SEE DRAWINGS
FOR DETAILS
(2) 3/4"Ø SST BOLTS.
TYP EA CHANNEL
TO BEAM
1. INSTALL ISOLATION SLEEVES AND DIELECTRIC BREAKS BETWEEN DISSIMILAR METALS.
SEE SPECIFICATIONS.
M
IN3"
3"
3" 3"
M
IN
FITTED ANGLE W/ O.F.
LEG WIDTH T = 1/4" MIN TO
MATCH STRINGER END PLATE.
TYP AT EA CHANNEL
PROJECT NO.
LA
ST
S
AV
ED
B
Y:
FILE NAME:
CE
CE
CHK
STRUCTURAL
TYPICAL DETAILS 4
204071_00TS04.dwg hv o
DATEREV BY DESCRIPTION
DATE
CHECKED
DRAWN
DESIGNED
204170
JOB NO.
DRAWING NO.
SHEET NO.
SCALES ACCORDINGLY
VERIFY SCALES
THIS SHEET, ADJUST
IF NOT ONE INCH ON
BAR IS ONE INCH ON
ORIGINAL DRAWING
0 1"
OFAPRIL 2026
COLLIER COUNTY
SCRWTP LIME SOFTENING IMPROVEMENTS
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
G G
301 NORTH CATTLEMEN ROAD, SUITE 302
SARASOTA, FL. 343232
PHONE: (941) 371-9832 FAX: (941) 371-9873
SEALED BY VANESSA
NEGRON-VIEIRA ON THE
DATE ADJACENT TO THE
SEAL.
THE SIGNATURE MUST BE
VERIFIED ON ANY
00TS04
V SECTION
AL CS10V
T SECTION
1" (TYP)
AL CS10
4" 2"
1"
STAIR STRINGER
3/4"Ø SST BOLT.
U
1" NOSING
AL L 4 x 3 x 3/8
SECTION
TIGHTEN FINGER
TIGHT AND DOUBLE
NUT (TYP)
12" AL
GRATING
BRACE
AL CS10
AL STAIR
STRINGER
AL BAR~
T.O GRATING
1/4
1/4
5/8" AL END
PLATE
AL BAR 1/4" x
HEIGHT GRATING
x CONT (TYP 3 SIDES
AROUND LANDING)
G
G
AL CS STRINGER
AL L 4 x 3 x3/8 LLV
(2) 3/4Ø SST BOLTS
SR226 STAIR - FLUSH TOP TREAD - ALUMINUM LANDING
TYP
N SHEET 8 OF 8 09/11/2024
SR401 GUARDRAILS & HANDRAILS - NOTES
TYP
N 09/25/2024
NOTES:
1. PROVIDE GUARDRAILS AT STAIRS AND AT OPEN SIDED WALKING SURFACES THAT ARE ELEVATED
MORE THAN 30" ABOVE GRADE OR ADJACENT CONSTRUCTION.
2. WHERE EQUIPMENT IS LOCATED LESS THAN 10' FROM EDGE OF ROOF AND ELEVATED MORE THAN
30" ABOVE GRADE OR ADJACENT CONSTRUCTION, PROVIDE 42" HIGH GUARDRAIL FORMING A
PROTECTIVE BARRIER. PARAPET WALL 42" OR MORE IN HEIGHT MAY BE THE GUARDRAIL AT ROOF
LOCATIONS.
3. SEE DRAWINGS AND SPECIFICATIONS FOR GUARDRAIL MATERIAL TYPE(S).
4. PROVIDE HANDRAIL AT BOTH SIDES OF EVERY STAIR HAVING 2 OR MORE RISERS.
5. PROVIDE CONTINUOUS HANDRAIL GRIPPING SURFACES FOR THE FULL LENGTH OF THE STAIR.
6. PROVIDE HANDRAIL EXTENSIONS AT BOTH SIDES OF STAIRS AT TOP AND BOTTOM. HANDRAIL
EXTENSION ON STAIR MOUNTED GUARDRAIL MAY BE OMITTED WHERE IT IS PERPENDICULAR TO
AND IMPEDES EXIT FLOW.
7. MAKE INSIDE HANDRAIL ON SWITCHBACK STAIRS CONTINUOUS.
8. FOR WALL MOUNTED HANDRAILS, PROVIDE SINGLE RAIL WITH TOP OF RAIL AT 2'-10" HEIGHT
ABOVE LANDINGS OR TREAD NOSINGS. PROVIDE MATCHING HANDRAIL ON OPPOSITE SIDE.
9. GUARDRAIL SHALL BE FIXED UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
10. PLACE CENTER OF EMBEDDED POSTS 6" FROM EDGE OF CONCRETE AND 6" FROM FRONT EDGE
OF CONCRETE STAIR NOSINGS UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
11. PLACE GUARDRAIL POSTS OPPOSITE EACH OTHER WHERE RAILINGS ARE PARALLEL.
12. FOR GUARDRAIL POSTS MOUNTED TO BEAM OR STAIR CHANNEL, PROVIDE MANUFACTURERS
REINFORCED CONNECTION FROM POST TO PLATE. PLATE AND REINFORCED INSERTS SHALL BE
ALUMINUM OR STAINLESS STEEL.
13. PROVIDE SLIDING JOINTS AT 24' MAX SPACING FOR EXPANSION OF RAIL AND KICKPLATE. LOCATE
SLIDING JOINTS NEAR FACE OF POST. GAP AT TIME OF INSTALLATION SHALL BE BASED ON
TEMPERATURE OF GUARDRAIL. PROVIDE 1/4" GAP AT 100°F AND 5/8" GAP AT 0°F. INTERPOLATE
GAP FOR OTHER INSTALLATION TEMPERATURES. AT CONCRETE EXPANSION JOINTS, PROVIDE
MINIMUM 1" GAP IN SLIDING JOINTS BUT NOT LESS THAN WIDTH OF CONCRETE EXPANSION JOINT.
MAKE INSERT SLEEVES IN RAILS LONG ENOUGH TO ALLOW FOR THE FULL RANGE OF MOVEMENT.
14. MATERIAL FOR KICKPLATE CHANNEL SLIDING JOINT PLATES, SHALL BE OF THE SAME MATERIAL AS
THE GUARDRAIL.
15. JOINTS FOR WELDED STAINLESS STEEL GUARDRAIL AND HANDRAIL SHALL BE COPED, WELDED, AND GROUND SMOOTH.
16. PROVIDE KICKPLATE AT ALL LOCATIONS EXCEPT AT SLOPING GUARDRAIL ON STAIRS AND WHERE GUARDRAIL IS MOUNTED ON A 4" MIN CURB. KICKPLATE MAY BE EXTRUDED OR BENT PLATE AND SHALL BE ATTACHED WITH SST BOLTS IN 5/16" x 3/4" SLOTTED HOLES. BOLT KICKPLATE TO POST
WITH BOTTOM 1/4" CLEAR ABOVE FLOOR. FOR SIDE MOUNTED GUARDRAIL, PROVIDE STANDARD
SPACER BLOCK BETWEEN POST AND KICKPLATE TO MAINTAIN 1/4" MAX CLEAR SPACING. HAND
TIGHTEN AND CENTER PUNCH BOLT THREADS TO LOCK.
17. COAT ALUMINUM SURFACES IN CONTACT WITH CONCRETE AS SPECIFIED. PROVIDE NEOPRENE
GASKET BETWEEN ALUMINUM AND STEEL.
SR416 GUARDRAIL - 3 RAIL
TYP
N SHEET 1 OF 3 05/29/2025
HANDRAIL
GUARDRAIL
KICKPLATE
4"R (TYP)
GUARDRAIL
HANDRAIL
SLIP JOINT
AT RAILS AND
KICKPLATE
METAL BEAM
WALKING
SURFACE
KICKPLATE
CURB
HEIGHT
PER DWGS
(NOTE 5)
3' -6
" 3' -6
6'-0" MAX
6"
MAX
3' -6
4"
TYP
SR450
TYP
SR450
TYP
SR450
KICKPLATE
NOT SHOWN
FOR CLARITY
KICKPLATE
NOT SHOWN
FOR CLARITY
1'-0 1/2"
1'-0 1/2"
1' -5
1'-2"
1'-2" EA WAY
PAST CORNER
KICK-
PLATE
KICKPLATE
12" (MIN)
GUARDRAIL ELEVATIONA
GUARDRAIL CORNERS & ENDSB
- SEE DRAWINGS FOR POST MOUNTING CONDITIONS
TOP OF STAIR ENDCORNER
BEAM TOP MOUNT
BOTTOM OF STAIR
SIDE MOUNT EMBED MOUNT CURB MOUNT TOP MOUNT
1 1/2"Ø
PIPE (TYP)
1" GAP
4" R
(TYP)
ALUMINUM GUARDRAIL UNLESS OTHERWISE NOTED.
1" GAP
12" (MIN)
12" (MIN) 12" (MIN)STAIR
SR416 GUARDRAIL - 3 RAIL
TYP
N SHEET 2 OF 3 05/29/2025
STAIR GUARDRAIL/HANDRAIL ELEVATION
1 1/2"Ø PIPE (TYP)
KICKPLATE
GUARDRAIL
HANDRAIL
3' -6
3' -6
2' -1
0"
5'-0" MAX
3' -6
2' -1
0"
6" (TYP)
6"
1' -5
3' -6
12" HANDRAIL
EXTENSION
12" HANDRAIL
EXTENSION (MIN)
NOTES:
1. DETAIL IS APPLICABLE AT PRIVATE STAIRS IN F, H, AND S OCCUPANCIES FOR "OPERATOR ONLY"
ACCESS. DETAILS AND INSTALLATION SHALL COMPLY WITH THE BUILDING CODE.
2. SEE SPECIFICATIONS AND DETAIL SR401/TYP FOR ADDITIONAL REQUIREMENTS.
3. VARIOUS POST MOUNTING DETAILS ARE ILLUSTRATED. SEE DRAWINGS AND DETAIL SR450/TYP
FOR SPECIFIC MOUNTING REQUIREMENTS.
4. HANDRAIL EXTENSIONS ARE REQUIRED ON BOTH SIDES OF STAIR, EXCEPT WHERE INSIDE
HANDRAIL IS CONTINUOUS AT SWITCHBACK STAIR.
5. AT CURB, USE EMBEDDED OR TOP MOUNTED POST AS INDICATED ON THE DRAWINGS.
4"
POST BRACKET
GUARDRAIL
SUPPORT POST
GUARDRAIL
MOUNTED HANDRAIL
GUARDRAIL POST
ELEVATION PLAN
1 1/2" CLEAR
4 1/2" MAX
TERMINATION AT POST
MFR DETAIL FOR
CONCEALED FASTENING
MFR POST
BRACKET (TYP)
SECTION
D
E
(SEE DRAWINGS FOR POST MOUNTING CONDITIONS)
C
(TYP)
1' -5
1'
-0
/2
1' -0
/2
SR416 GUARDRAIL - 3 RAIL
TYP
N SHEET 3 OF 3 05/29/2025
GUARDRAIL
1/4" PL GATE STOP.
SLEEVE FULL HEIGHTSELF CLOSING HINGE
HINGE RINGS 4" R (TYP)
3' -6
AS INDICATED ON THE DRAWING
OR TO SUIT EQUIP FURNISHED
(2'-0" MIN/4'-0" MAX)
SST GATE LATCH
TO SUIT HINGE PROVIDED
WITH SST RIVETS
REINFORCE WITH INTERNAL
WELD TO VERTICAL GATE
0.74"Ø SST PIN (TYP)
ELEVATION
PLAN
GATE
1' -5
2'
-1
NYLON WASHER
BEARINGS (TYP)
WALKING SURFACE
1/8 1/2T&B
1 1/4"
2 1/2"
GATE…
This is the start of the file's text. The full file is on GovTribe.