This is a construction document set consisting of architectural, mechanical, and electrical plans for the renovation of 206 North Union Street in Danville, Virginia, prepared for North Union Properties, LLC. The project involves renovation work to a two-story, 10,755 square-foot building classified as Group B occupancy (Business) with Type-IIIB construction. The scope includes demolition of existing mezzanines and internal partitions, creation of two retail tenant spaces (Tenant A and Tenant B) and a backroom, installation of new mechanical systems consisting of two 3-ton air handlers with heat pump units, new electrical distribution and lighting systems, plumbing fixture upgrades, and life safety improvements including fire-rated wall assemblies and egress modifications. The project requires compliance with Virginia Construction Code (2021), Virginia Energy Conservation Code (2021), and Virginia Statewide Fire Prevention Code (2021). The pre-bid meeting is scheduled for Tuesday, September 29, 2026, at 10:00 AM; the deadline for submitting questions is Wednesday, October 7, 2026, at 5:00 PM; and bids open Thursday, October 15, 2026, at 4:30 PM.
The construction documents specify multiple code compliance requirements including fire-resistance ratings for wall assemblies (minimum 1-hour fire-rated construction utilizing UL Design No. 301), occupant load calculations (24 total occupants across retail and support spaces), and egress capacity standards requiring minimum widths of 32 inches for exits. Mechanical systems are designed for heating loads of 15,800-16,246 BTU/h and cooling loads of 17,807 BTU/h (sensible) with additional latent cooling capacity of 7,832 BTU/h per zone. Electrical work includes installation of new panel boards (Panels A1, A2, and J), LED lighting fixtures with emergency battery backup, GFCI-protected receptacles, and data/communications infrastructure with CAT 6 cabling. The renovation maintains existing EPDM roofing and structural elements while upgrading all mechanical, electrical, and plumbing systems to current code standards. General contractor responsibilities include coordination of all trades, site safety, asbestos floor tile removal, utility connections, and restoration of adjacent areas affected by construction operations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UP
UP
REFERENCE CODES
VIRGINIA CONSTRUCTION CODE (VCC), 2021 ED.
VIRGINIA ENERGY CONSERVATION CODE, 2021 ED.
VIRGINIA STATEWIDE FIRE PREVENTION CODE (SFPC), 2021 ED.
ALL APPLICABLE NFPA FIRE CODES INCLUDING BUT NOT LIMITED TO :
NFPA, 2021 ED.
AMERICAN DISABILITY ACT - ADA ACCESSIBILITY GUIDELINES, 2010 ED.
BUILDING OCCUPANCY AND CLASSIFICATIONS:
THE OCCUPANCY IS CLASSIFIED AS "B" - BUSINESS
BUILDING OCCUPANCY CATEGORY
THIS BUILDING IS TYPE-II OCCUPANCY PER VCC TABLE 1604.5
CONSTRUCTION TYPE
THIS BUILDING IS TYPE-IIIB CONSTRUCTION PER VCC (TABLE 601)
AND TYPE-III (2,0,0) PER NFPA 220.
GENERAL BUILDING LIMITATIONS
ACTUAL BUILDING AREA
BUILDING GROSS AREA: 10,755 SF
ALLOWABLE AREA / HEIGHT FOR B OCCUPANCY
PER TABLE 504.3, THE ALLOWABLE BUILDING HEIGHT OF A NON-
SPRINKLED GROUP B, TYPE-IIIB, BUILDING IS LIMITED TO 55 FEET.
PER TABLE 504.4, THE ALLOWABLE NUMBER OF STORIES OF A NON-
SPRINKLED GROUP B, TYPE-IIIB, BUILDING IS LIMITED TO 3.
PER TABLE 506.2, THE ALLOWABLE AREA OF A NON-SPRINKLED
GROUP B, TYPE-IIIB, BUILDING IS LIMITED TO 19,000 SQUARE
FEET.
BUILDING HEIGHT: TWO STORIES +/- 35'-0"
BUILDING PERIMETER WALLS NOT ISOLATED BY 30'-0" OR GREATER
MUST HAVE A FIRE-RESISTANCE RATING OF 1 HR MIN. (TABLE
602). EXISTING EXTERIOR WALLS CONSIST OF SOLID BRICK
EXCEEDING 6 INCHES IN THICKNESS WHICH EQUATES TO
GREATER THAN 4 HR OF RATED FIRE-RESISTENCE IN
ACCORDANCE WITH VCC TABLE 721.1(2). INFILL WITHIN THESE
WALLS WILL BE BUILT WITH A 2 HR FIRE-RESISTENCE RATING IN
ACCORDANCE WITH UL DESIGN NO. 301.
BUILDING DOES NOT CONTAIN AN AUTOMATIC SPRINKLER SYSTEM
DESIGN OCCUPANCY: TABLE 1004.1.2
BUILDING AREA (B): 2,202 SF / 150 SF PER OCCUPANT = 15
OCCUPANTS
TOTAL CALCULATED OCCUPANT LOAD: 24 (SUM OF ROOM-BY-
ROOM BASIS)
SEE LIFE SAFETY PLAN ON THIS SHEET FOR BREAKDOWN OF
OCCUPANT LOADS PER SPACE. OCCUPANT LOADS SHOWN ON
LIFE SAFETY PLANS AREA CALCULATED BY THE FOLLOWING
CALCULATION:
AREA (SF) / 150 SF PER OCCUPANT = OCCUPANT LOAD
NUMBER OF MEANS OF EGRESS - VCC TABLE 1006.3.2(2)
OCCUPANCY STORY MIN. NO. OF EXITS REQUIRED PROVIDED
BUSINESS FIRST STORY 2 2
EGRESS CAPACITY
EGRESS WIDTH CAPACITY - (VCC SECTION 1005)
LEVEL COMPONENTS AND RAMPS - 0.2 IN/PERSON
STAIRWAYS - 0.3 IN/PERSON
LEVEL COMPONENTS AND RAMPS
24 PEOPLE X 0.2 IN/PERSON = 4.8 IN. REQUIRED
(32 INCH MIN. REQUIRED)
(1 EXIT X 71.5 IN.) + (1 EXIT X 36 IN.) = 107.5 IN. PROVIDED
STAIRWAYS
24 PEOPLE X 0.3 IN/PERSON = 7.3 IN. REQUIRED
(32 INCH MIN. REQUIRED)
1 EXIT X 36 IN. = 36 IN. PROVIDED
DEAD END CORRIDORS (VCC SECTION 1020.4)
BUSINESS OCCUPANCY - MAXIMUM LENGTH = 20 FT.
COMMON PATH OF TRAVEL (VCC SECTION 1006.2.1)
BUSINESS OCCUPANCY - MAXIMUM LENGTH = 75 FT.
TOTAL TRAVEL DISTANCE TO EXITS (VCC TABLE 1017.2)
BUSINESS OCCUPANCY - MAXIMUM LENGTH = 200 FT.
REMOTENESS BETWEEN EXITS - (VCC SECTION 1007.1.1)
THE SEPARATION DISTANCE OF THE EXIT DOORS OR EXIT ACCESS DOORWAYS
SHALL BE PLACED A DISTANCE APART EQUAL TO NOT LESS THAN ONE-HALF THE
LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR AREA
BEING SERVED, MEASURED IN A STRAIGHT LINE BETWEEN THE NEAREST EDGE OF
THE EXIT DOORS OR EXIT ACCESS DOORS.
DIAGONAL DIMENSION OF AREA BEING SERVED = 126 FT.
MINIMUM EXIT SEPARATION REQUIRED = 126 FT. / 2 = 63 FT.
EXIT SEPARATION PROVIDED = VARIES, BUT EXCEEDS MINIMUM REQUIREMENTS
PLUMBING FIXTURES - B OCCUPANCY (TABLE 2902.1)
FIXTURE
WATER CLOSET - UNISEX
LAVATORIES
DRINKING FOUNTAINS
SERVICE SINK
RATIO REQUIRED
1 PER 25 FOR THE FIRST 50
1 PER 50 FOR THE REMAINDER
1 PER 40 FOR THE FIRST 80
1 PER 80 FOR THE REMAINDER
1 PER 100
QTY. REQ.
QTY. PROVIDED
FIRE PROTECTION SYSTEMS
THE ENTIRE BUILDING IS NOT PROTECTED BY AN APPROVED AUTOMATIC WET PIPE
SPRINKLER SYSTEM.
FIRE ALARM AND DETECTION SYSTEMS
FIRE ALARM SYSTEM MODIFICATIONS TO BE A DELEGATED DESIGN ITEM. FIRE ALARM TO BE
INTERCONNECTED WITH EXISTING SYSTEM. RELOCATE EXISTING PULL STATION AND ADD
AN ADDITIONAL PULL STATION. ADD HORN/STROBES AS REQUIRED.
PORTABLE FIRE EXTINGUISHERS/CABINET LOCATIONS
PORTABLE FIRE EXTINGUISHERS SHALL BE ADDED THROUGHOUT THE BUILDING
IN LOCATIONS AS REQUIRED BY NFPA 10, NFPA 101 AND AS SHOWN.
LOCATIONS DESIGNATED AS FEC SHALL BE 1 HR FIRE RATED SEMI-RECESSED CABINETS
WITH BATTERY POWERED ALARMS. NOT TO PROTRUDE MORE THAN 4" FROM WALL.
MAXIMUM TRAVEL DISTANCE TO EXTINGUISHER - 75 FEET
MAXIMUM AREA PER EXTINGUISHER - 11,250 SQUARE FEET
FIRE DEPARTMENT KEY BOX
THE GENERAL CONTRACTOR IS TO COORDINATE ADDING KEYS TO KNOX BOX WITH FIRE
MARSHAL.
FIRE SAFETY PLAN LEGEND
XX
XXA
FE
CALCULATED OCCUPANT LOAD
ACTUAL OCCUPANT LOAD
CAPACITY OF EGRESS COMPONENT
ACTUAL EGRESS
FIRE EXTINGUISHER
EXIT SIGN
APPROXIMATE TRAVEL DISTANCE
VIRGINIA ENERGY CODE
SECTION C402.4.1 - THE VERTICAL FENESTRATION AREA (NOT INCLUDING OPAQUE
DOORS AND OPAQUE SPANDREL PANELS)SHALL NOT EXCEED 30% OF THE GROSS
ABOVE-GRADE WALL AREA
ACTUAL FENESTRATION (INCLUDING OPAQUE DOORS AND SPANDREL PANELS) =
708 SF / 2,799 SF = 25%
TABLE C402.1.3(1) AND 402.1.3(2) - (CLIMATE ZONE 4A PER TABLE C301.1)
OPAQUE THERMAL ENVELOPE REQUIREMENTS
ROOFING
SLAB ON GRADE, UNHEATED
SWINGING OPAQUE DOORS
REQUIRED APPROXIMATE
R-30ci
R-10 FOR 24" BELOW
U-0.61
UNCHANGED
UNCHANGED
UNCHANGED
JOIST/ FRAMING FLOOR R-30 UNCHANGED
TENANT B
A
AP
PR
O X.
T R
AV
EL
D
IS
TA
N C
E
1/ 2"
F T
AP
PR
O X.
T R
TA
N C
E
F
T
FE
C
EXISTING MASONRY
FIRE WALL
TENANT A
AP
PR
O X.
T R
TA
N C
E
/2 " F
T
36024A
1 HR FIRE RATED
UL DESIGN NO. U305.
EXTEND TO DECK
AND SEAL.
FE FE
JOINTS COVERED
WITH PAPER TAPE
AND JOINT
COMPOUND. NAIL
HEADS EXPOSED
OR COVERED WITH
JOINT COMPOUND.
5/8" GPDW
2 X 4 STUDS
3" THICK BATTS AND
BLANKETS OR GLASS
FIBER INSULATION
5/8" GPDW
JOINTS COVERED
WITH PAPER TAPE
AND JOINT
COMPOUND. NAIL
HEADS EXPOSED OR
COVERED WITH JOINT
COMPOUND.
5/8" GPDW
2 X 4 STUDS
5/8" GPDWNON-BEARING WALL
PARTITION INTERSECTION.
TWO NOMINAL 2 X 4 OR
2 X 6 STUDS TO BE FLUSH
WITH STUDS ON BEARING
WALL.
3" THICK BATTS AND
BLANKETS OR GLASS
FIBER INSULATION
MAX
16" O.C.
MAX
16" O.C.
ARCHITECTURAL
REVISIONS
PROJECT NO.
SO
LE
X
AR
C H
IT
EC
TU
R
E, IN
C
M
AI
N S
TR
EE
T D
AN
VI
LL
E, V
IR
G
IN
IA
4.
8.
P H
O N
E
4.
1.
F
AX
MECHANICAL/ELECTRICAL
/PLUMBING
INSPECTION SIGN-OFF
DATE DESCRIPTION INITIAL
RENOVATION TO 206 NORTH UNION ST
N O
R
TH
U N
IO
N
S
TR
EE
T
D
AN
VI
LL
E, V
IR
G
IN
IA
2026.08.17
NORTH UNION PROPERTIES, LLC
20260025
N O
R
TH
U N
IO
N
P R
O
PE
R
TI
ES
, L
LC
R
EN
O
VA
TI
O N
T O
N O
R
TH
U N
IO
N
S T
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
Scale: 1/8" = 1'-0"G-100
FIRST FLOOR LIFE SAFETY PLAN1
DRAWINGS LIST
SHEET NO. SHEET NAME
GENERAL
G-100 TITLE SHEET & LIFE SAFETY PLAN
ARCHITECTURAL
AD-101 EXISTING & DEMO FLOOR PLANS
A-101 PROPOSED LAYOUT
A-103 REFLECTED CEILING PLAN
A-601 DOOR SCHEDULE, ELEVATIONS, AND
DETAILS AND WALL DETAILS
MECHANICAL
M-001 MECHANICAL NOTES
M-101 MECHANICAL PLAN
M-301 MECHANICAL SCHEDULES
ELECTRICAL
E-001 ELECTRICAL NOTES
E-101 DEMO PLANS
E-102 LIGHTING PLAN
E-103 POWER PLAN
E-301 PANEL SCHEDULES
E-302 POWER RISER
Scale: 3/4" = 1'-0"G-100
UL DESIGN # U305 (WALL ASSEMBLY) - 1 HOUR2
NO. DESCRIPTION DATE
UPUP
UP
UP
STORAGE
RR
E100
A102 E105 E104
E106
CLOSET
206A
STAIR
D002
D003
D004
D006
D007
D009
D008
22' - 5 1/2"
/4
/8
REMOVE AND RELOCATE
EXIT SIGN
MEZZ
DN
OPEN
BELOW
A107
D001
D002
D005
D010
7'
1/
2"
/2
9' - 0 3/4" 12' - 7 1/8"
GENERAL DEMO NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
DASHED LINES DENOTE ITEMS TO BE REMOVED.
THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH
ALL HEALTH & OCCUPATIONAL REGULATIONS REGARDING PROTECTION OF
WORKERS DURING CONSTRUCTION AND PROVIDE RECEIPT OF PROPER
DISPOSAL.
DEMOLITION SHALL BE ACCOMPANIED BY ALL SAFETY MEASURES NECESSARY
AND REQUIRED TO PROTECT WORKERS AND VISITORS AT THE SITE.
GENERAL CONTRACTORS, SUBS, SUPPLIERS, ETC. WORKING ON OR
ASSOCIATED IN ANY WAY WITH THIS PROJECT MUST ADHERE TO ALL
APPLICABLE LOCAL, STATE, AND FEDERAL LAWS, CODES, AND REGULATIONS.
THE GENERAL CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR OVERVIEW
COORDINATION WITH ALL TRADES. FAILURE TO COORDINATE WORK OF EACH
TRADE SHALL NOT BE JUSTIFICATION FOR ADDITIONAL COMPENSATION.
THE GENERAL CONTRACTOR IS REQUIRED TO NOTIFY THE A/E OF ANY
CONFLICT OF THE PLANS AND SPECIFICATIONS. FAILURE TO NOTIFY THE A/E
RESULTING IN ADDITIONAL COST SHALL BE THE GENERAL CONTRACTOR'S
EXPENSE.
IN THE EVENT A CONFLICT IS FOUND OR AN INTERPRETATION IS REQUIRED,
THE ARCHITECT SHALL RESPOND BASED ON THE OWNER'S APPROVAL.
MAINTAIN PORTIONS OF EXISTING BUILDING AFFECTED BY CONSTRUCTION
OPERATIONS IN A WEATHERTIGHT CONDITION THROUGHOUT CONSTRUCTION
PERIOD. REPAIR DAMAGE CAUSED BY DEMOLITION OPERATIONS.
NO WORK SHALL BE DONE BY CONTRACTORS THAT WILL REDUCE THE
STRUCTURAL INTEGRITY OF THE BUILDING OR ITS COMPONENTS, REDUCE
THE CURRENT LEVEL OR DEGREE OF FIRE PROTECTION OR LIFE-SAFETY
MEASURES OR CONFLICT WITH ANY APPLICABLE CODES, ORDINANCES,
REGULATIONS, REQUIREMENTS, OR INSTRUCTIONS OF INSPECTING
AUTHORITIES.
GENERAL CONTRACTOR TO MAINTAIN EXISTING EXITS DURING
CONSTRUCTION ACTIVITIES UNLESS OTHERWISE INDICATED.
THE GENERAL CONTRACTOR SHALL FURNISH ALL LABOR AND MATERIALS AS
REQUIRED TO COMPLETE DEMOLITION AND REMOVAL OF ALL ITEMS AS
SHOWN OR NOTED ON DRAWINGS AND THOSE ITEMS REQUIRED TO BE
REMOVED TO FULFILL THE INTENT OF THE CONSTRUCTION DOCUMENTS.
DEMOLITION THAT INVOLVES ITEMS OR ASSEMBLIES WITH MECHANICAL,
PLUMBING, OR ELECTRICAL CONNECTIONS, SHALL HAVE SUCH CONNECTIONS
DISCONNECTED, DEACTIVATED, CAPPED, OR SEALED BY THE APPROPRIATE
CONTRACTOR IN ACCORDANCE WITH THE APPLICABLE CODES, ORDINANCES,
REGULATIONS, REQUIREMENTS, OR INSTRUCTIONS OF INSPECTING
AUTHORITIES.
ALL PLUMBING, MECHANICAL, AND ELECTRICAL INDICATED TO BE REMOVED
SHALL BE DEMOLISHED BACK TO THE SOURCE. CONTRACTOR RESPONSIBLE
FOR IDENTIFYING SOURCE LOCATION PRIOR TO BID.
THE GENERAL CONTRACTOR SHALL PROTECT AND BE RESPONSIBLE FOR THE
EXISTING STRUCTURE, FACILITIES, AND IMPROVEMENTS ADJOINING THE AREA
UNDER THIS CONTRACT. CLEAN ADJACENT STRUCTURES AND
IMPROVEMENTS OF DUST, DIRT, AND DEBRIS CAUSED BY SELECTIVE
DEMOLITION OPERATIONS. RETURN ADJACENT AREAS TO CONDITION
EXISTING BEFORE SELECTIVE DEMOLITION OPERATIONS BEGAN. ANY
DISTURBANCE OR DAMAGE TO ADJOINING PROPERTY RESULTING DIRECTLY
OR INDIRECTLY FROM THE CONTRACTOR'S OPERATIONS SHALL BE PROMPTLY
RESTORED, REPAIRED, OR REPLACED TO THE SATISFACTION OF THE OWNER
AT NO ADDITIONAL COST.
IN CASE OF DAMAGE TO EXISTING FACILITY, CONTRACTOR'S PHOTOGRAPHIC
DOCUMENTATION WILL BE BASIS FOR OWNER'S DECISION. IF CONTRACTOR
CANNOT PROVIDE DOCUMENTATION, OWNER’S DECISION WILL BE FINAL.
DEBRIS SHALL BE REMOVED FROM THE SITE PER ALL APPLICABLE
REGULATIONS. AREA TO BE SWEPT CLEAN AT THE END OF EACH DAY.
E
54321
D
C
B
A
CHECKED BY
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SO
LE
X
AR
C H
IT
EC
TU
R
E, IN
C
M
AI
N S
TR
EE
T D
AN
VI
LL
E, V
IR
G
IN
IA
4.
8.
P H
O N
E
4.
1.
F
AX
SCALE
SHEET NUMBER
SHEET INFORMATION
SHEET NAME
As indicated
AD-101
EXISTING &
DEMO FLOOR
PLANS
JMW
JLB
2026.08.17
20260025
R
EN
O
VA
TI
O
N T
O
N
O R
TH
U
N
IO
N S
T
N O
R
TH
U N
IO
N
P R
O
PE
R
TI
ES
, L
LC
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
N O
R
TH
U N
IO
N
S
TR
EE
T
D
AN
VI
LL
E, V
IR
G
IN
IA
Scale: 1/8" = 1'-0"A-501AD-101
EXISTING/DEMO FIRST FLOOR1
Scale: 1/8" = 1'-0"AD-101
EXISTING/DEMO 206 MEZZANINE2
KEYNOTES PER SHEET
NOTE DESCRIPTION
D001 MEZZANINE TO BE DEMOLISHED. REPAIR ADJACENT
WALLS, CEILING, AND FLOOR AS REQUIRED.
D002 STAIR TO MEZZANINE TO BE DEMOLISHED. REPAIR
ADJACENT WALLS AND FLOOR AS REQUIRED.
D003 PART OF PLATFORM TO BE DEMOLISHED TO MAKE SPACE
FOR NEW VESTIBULE. SEE PROPOSED.
D004 HANGING DOOR ON WALL TO BE DEMOLISHED. REPAIR
WALL AS REQUIRED.
D005 STAIR ABOVE MEZZANINE TO BE DEMOLISHED. REPAIR
ADJACENT WALLS AND CEILING AS REQUIRED.
D006 EXISTING FLOORING TO BE REMOVED ONLY AS NEEDED
FOR NEW WALLS. SAW CUT TILE AS MINIMAL AS POSSIBLE.
D007 EXISTING WALL AND DOOR TO BE DEMOLISHED. REPAIR
ADJACENT WALLS, FLOOR, AND CEILING.
D008 REMOVE ALL EXISTING DUCTWORK AND MECHANICAL
EQUIPMENT. RETURN EQUIPMENT TO OWNER. SEE
MECHANICAL.
D009 REMOVE ALL EXISTING LIGHTS, OUTLETS, AND CONDUIT
AND REINSTALL PER NEW LAYOUT. PATCH/PAINT AS
REQUIRED. SEE ELECTRICAL. RETURN ALL UNUSED
FIXTURES TO OWNER. LIGHTS ABOVE MEZZANINE TO
RECEIVE NEW WIRING AND AIRPLANE CABLES TO MATCH
MOUNTING HEIGHT OF OTHER LIGHTS.
D010 ROUTE ALL NEW REFRIGERANT LINES AND ELECTRICAL
THROUGH UTILITY CLOSET(S) ON SECOND FLOOR. SEAL
ALL PENETRATIONS WITH APPROVED FIRE CAULKING.
FLASH AND SEAL ROOF PENETRATIONS TO MAINTAIN
EXISTING WARRANTY.
UP
UP
FE
C
TENANT A
TENANT B
BACKROOM
VESTIBULE
CORR
103A 103B
A-101 A-101
103C
M
EC
H
FULL HEIGHT STUD WALL
TO CONTINUE ABOVE
STOREFRONT
PLYWOOD PLATFORM
OVER VESTIBULE
9' - 8 1/2"
21' - 10 1/4"
/8
7' - 0 1/2" 2' - 8"12' - 1 3/4"
7'
3/
8"
11' - 7"
6 3/4"
FULL HEIGHT
STUD WALL
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
GENERAL CONTRACTORS, SUBS, SUPPLIERS, ETC. WORKING ON OR ASSOCIATED IN ANY
WAY WITH THIS PROJECT MUST ADHERE TO ALL APPLICABLE LOCAL, STATE, AND
FEDERAL LAWS, CODES, AND REGULATIONS.
THE GENERAL CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR OVERVIEW
COORDINATION WITH ALL TRADES. FAILURE TO COORDINATE WORK OF EACH TRADE
SHALL NOT BE JUSTIFICATION FOR ADDITIONAL COMPENSATION.
THE GENERAL CONTRACTOR IS REQUIRED TO NOTIFY THE A/E OF ANY CONFLICT OF THE
PLANS AND SPECIFICATIONS. FAILURE TO NOTIFY THE A/E RESULTING IN ADDITIONAL
COST SHALL BE THE GENERAL CONTRACTOR'S EXPENSE.
IN THE EVENT A CONFLICT IS FOUND OR AN INTERPRETATION IS REQUIRED, THE
ARCHITECT SHALL RESPOND BASED ON THE OWNER'S APPROVAL.
CONTRACTOR RESPONSIBLE FOR VISITING SITE AS NECESSARY AND BECOMING
FAMILIAR WITH ALL REQUIREMENTS PRIOR TO BID.
CONTRACTOR RESPONSIBLE FOR CONNECTING TO EXISTING UTILITIES AND/OR
REPLACING AS SHOWN ON ENGINEERING DRAWINGS.
THE GENERAL CONTRACTOR SHALL PROTECT AND BE RESPONSIBLE FOR THE EXISTING
STRUCTURE, FACILITIES, AND IMPROVEMENTS ADJOINING THE AREA UNDER THIS
CONTRACT. CLEAN ADJACENT STRUCTURES AND IMPROVEMENTS OF DUST, DIRT, AND
DEBRIS CAUSED BY SELECTIVE DEMOLITION OPERATIONS. RETURN ADJACENT AREAS TO
CONDITION EXISTING BEFORE SELECTIVE DEMOLITION OPERATIONS BEGAN. ANY
DISTURBANCE OR DAMAGE TO ADJOINING PROPERTY RESULTING DIRECTLY OR
INDIRECTLY FROM THE CONTRACTOR'S OPERATIONS SHALL BE PROMPTLY RESTORED,
REPAIRED, OR REPLACED TO THE SATISFACTION OF THE OWNER AT NO ADDITIONAL
COST.
IN CASE OF DAMAGE TO EXISTING FACILITY, CONTRACTOR'S PHOTOGRAPHIC
DOCUMENTATION WILL BE BASIS FOR OWNER'S DECISION. IF CONTRACTOR CANNOT
PROVIDE DOCUMENTATION, OWNER'S DECISION WILL BE FINAL.
PATCH AND REPAIR CEILINGS AND WALLS ASSOCIATED WITH CONSTRUCTION
ACTIVITIES.
CONTRACTOR TO PROVIDE AND INSTALL SMOKE / CARBON MONOXIDE DETECTOR AS
PER ALL APPLICABLE CODES. (SEE ELECTRICAL)
ELEVATIONS SHOWN ON ARCHITECTURAL DRAWINGS ARE RELATIVE.
CONTRACTOR TO PROVIDE KNOX BOX. COORDINATE LOCATION WITH LOCAL FIRE
DEPARTMENT.
CONTRACTOR RESPONSIBLE FOR COORDINATING ALL MECHANICAL AND ELECTRICAL
FIXTURES, EQUIPMENT, SWITCHES, THERMOSTATS, ETC. WITH FURNISHINGS, SHELVING,
ETC.
A-601
A-101
A-601
A-101
0.
BRAKE METAL
CORNER TRIM
STUD WALL TO
CONTINUE ABOVE
NEW HEADER TO
FLOOR ABOVE.
4 1/2"
6' - 8"
3' - 1 3/4"
4 1/2"
6' - 6 7/8"
3' - 3 3/8"
NEW STUDS
AND GPDW
E
54321
D
C
B
A
CHECKED BY
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SO
LE
X
AR
C H
IT
EC
TU
R
E, IN
C
M
AI
N S
TR
EE
T D
AN
VI
LL
E, V
IR
G
IN
IA
4.
8.
P H
O N
E
4.
1.
F
AX
SCALE
SHEET NUMBER
SHEET INFORMATION
SHEET NAME
As indicated
A-101
PROPOSED
LAYOUT
JMW
JLB
2026.08.17
20260025
R
EN
O
VA
TI
O
N T
O
N
O R
TH
U
N
IO
N S
T
N O
R
TH
U N
IO
N
P R
O
PE
R
TI
ES
, L
LC
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
N O
R
TH
U N
IO
N
S
TR
EE
T
D
AN
VI
LL
E, V
IR
G
IN
IA
Scale: 1/8" = 1'-0"A-501A-101
206 PROPOSED FLOOR PLAN1
NOTE: MODIFY FA & MOVE PULL
STATION INTO VESTIBULE
Scale: 1/8" = 1'-0"A-101
206 DIMENSION PLAN2
Scale: 1/2" = 1'-0"A-101A-101
ENLARGED VESTIBULE PLAN4
REROUTE DOWNSPOUT AND REPAIR GUTTER
AS REQUIRED FOR ELECTRICAL WORK
VTR TO BE REMOVED.
VTR TO BE REMOVED
ROOF
HATCH
EXISTING
EPDM ROOF
TO REMAIN
22' - 7"
52' - 1 3/8"
112' - 8 5/8"
10' - 0 1/2"
58' - 4 7/8"
A-301
A-301
LIFT
LIFT SUPPORT COLUMNS
AND RAILS TO BE
REMOVED. CAB AND
PULLEY MECHANISM TO
BE RELOCATED IN 206.
REMOVE METAL FIRE
DOOR AND SECURE
IN OPEN POSITION
REMOVE AND REPLACE
CONCRETE FOR WASTE
LINE. EXACT ROUTING
TO BE DETERMINED.
REMOVE
EXISTING VCT
FLOORING
HATCHED BUILDING IS PART
OF SEPARATE APPLICATION
REMOVE CMU AND
BRICK INFILL. PREP
OPENING TO RECEIVE
NEW WINDOW.
MEZZANINE COLUMNS
TO BE REMOVED
NON-ORIGINAL METAL
FRAMED PARTITION TO
BE REMOVED
REMOVE NON-
ORIGINAL BLOCK
STEPS. PATCH
FLOOR AND WALL
AS REQUIRED.
CONCRETE FLOOR FROM
THIS LINE TO REAR OF
BUILDING. PLYWOOD
AND WOOD JOISTS TO
FRONT OF BUILDING.
SEWER LINE TO CONTINUE
BENEATH WOOD JOISTS
TO THE STREET
REPLACE UPPER PANE OF
STOREFRONT WITH CURVED
GLAZING TO MATCH EXISTING
EXISTING RAISED
STOREFRONT
DISPLAY WOOD
FLOOR TO BE
REFINISHED
REMOVE TRANSOME AND DOORS. PREP
OPENING TO RECEIVE NEW FIRE RATED
WALL AND DOOR. STORE / MOUNT
DOORS TO WALL AS DISPLAY.
REMOVE ASBESTOS
FLOOR TILES
UP
UP
REMOVE AND
SALVAGE DOORS
REMOVE CONCRETE
PLATFORM. PATCH
CONCRETE FLOORING
AS REQUIRED.
SAWCUT CONCRETE FLOOR TO
REMOVE WASTE LINE. INFILL
FLOORING TO MATCH ADJACENT.
REMOVE AND REPLACE
DOOR TO MATCH ADJACENT
HATCHED BUILDING IS PART
OF SEPARATE APPLICATION
REMOVE CMU AND BRICK
INFILL. PREP OPENING TO
RECEIVE NEW WINDOW.
REMOVE CMU AND BRICK
INFILL. EXTEND OPENING
TO NEW FLOOR LEVEL
AND PREP OPENING TO
RECEIVE NEW DOOR.
REMOVE NON-ORIGINAL
WOOD FRAMED OSB
WALLS AND DOOR
EXISTING FIBERBOARD
CEILING TO BE
REMOVED TO EXPOSE
TONGUE AND GROOVE
WOOD CEILING
LOWERED GPDW CEILING
TO BE REMOVED TO
EXPOSE HIGH CEILING
EXISTING LINOLEUM WALL
COVERING TO BE REMOVED
EXISTING FRAMING TO REMAIN.
FIBERBOARD WALL COVERING
TO BE REMOVED.
REMOVE SECURITY BARS
REMOVE AND REPLACE
DOOR TO MATCH EXISTING
UP
UP
LIFT
LIFT SUPPORT
COLUMNS AND RAILS
TO BE REMOVED. CAB
AND PULLEY
MECHANISM TO BE
RELOCATED IN 206.
REAR MEZZANINE
TO BE REMOVED
REMOVE CHASE.
PATCH WALL.
OPEN TO
BELOW
NON-ORIGINAL METAL
FRAMED PARTITION
TO BE REMOVED.
REMOVE CMU AND BRICK
INFILL. PREP OPENING TO
RECEIVE NEW WINDOW.
UP
LIFT
LIFT SUPPORT
COLUMNS AND RAILS
TO BE REMOVED.
CAB AND PULLEY
MECHANISM TO BE
RELOCATED IN 206.
REMOVE AND
SECURE METAL
FIRE DOOR IN
OPEN POSITION
HATCHED BUILDING IS PART
OF SEPARATE APPLICATION
REMOVE CMU AND BRICK
INFILL. PREP OPENING TO
RECEIVE NEW WINDOW.
REMOVE PARTITION,
DOOR, PLUMBING
FIXTURES, AND PIPING
DN
REMOVE AND
SECURE METAL
FIRE DOOR IN
OPEN POSITION HATCHED BUILDING IS PART
OF SEPARATE APPLICATION
REMOVE CMU AND BRICK
INFILL. PREP OPENING TO
RECEIVE NEW WINDOW.
REMOVE WOOD
FRAMING AND
METAL WIRE
STORAGE CAGE
208G
DN
NON-ORIGINAL METAL
SIGN TO BE REMOVED
EXISTING DOORS
TO BE REMOVED
REMOVE EXISTING
WINDOW AC UNIT
& PLYWOOD INFILL
AT TRANSOM
REPLACE ACRYLIC
PANE WITH GLASS.
REMOVE EXISTING
PLYWOOD INFILL
REMOVE EXISTING WINDOW AC UNIT
AND PLYWOOD INFILL AT TRANSOM
REMOVE NON-ORIGINAL HOLLOW
METAL DOOR (OUT OF VIEW)
REMOVE INFILL AT
TRANSOM (OUT OF VIEW)
REMOVE EXISTING
METAL SECURITY BARS
EXISTING DOOR TO
BE REPLACED TO
MATCH EXISTING
REMOVE CORRUGATED
METAL SIDING TO EXPOSE
PAINTED WOOD SIDING
REMOVE CORRUGATED
METAL SIDING TO EXPOSE
PAINTED WOOD SIDING REMOVE CORRUGATED METAL
SIDING TO EXPOSE PAINTED
WOOD SIDING (OUT OF VIEW)
LOCATION OF EXISTING MEZZANINE
FLOOR TO BE REMOVED
CMU / BRICK INFILL
TO BE REMOVED
CMU / BRICK INFILL TO BE REMOVED
CMU / BRICK INFILL TO BE REMOVED
NEW PLAQUE FOR
NATIONAL TRUST
FUNDING
REPLACE UPPER PANE OF
STOREFRONT WITH CURVED
GLAZING TO MATCH EXISTING
NEW GLASS TRANSOM
NEW GLASS DOORS TO
MATCH EXISTING. PAINT
DOORS AND FRAME.
REPAIR EXISTING
WINDOWS. PAINT.
EXISTING PAINTED
BRICK. REPAIR / PAINT.EXISTING PAINTED BRICK.
REPAIR / PAINT.
REPAIR EXISTING
WINDOW. PAINT.
REPAIR EXISTING WOOD
SIDING. PAINT.
REPAIR EXISTING WOOD
SIDING. PAINT.
NEW WOOD
GLASS DOOR TO
MATCH EXISTING
NEW GLASS TRANSOM
NEW GLASS TRANSOM
NEW GLASS TRANSOM
(OUT OF VIEW)
NEW WOOD GLASS
DOOR TO MATCH
EXISTING (OUT OF VIEW)
REPAIR EXTERIOR GYPSUM
CEILING IN RECESSED
ENTRANCE. PAINT.
REPAIR EXISTING WOOD
SIDING. PAINT.
NEW ALUMINUM CLAD
WOOD WINDOWS
EXISTING PAINTED
BRICK. REPAIR / PAINT.
NEW ALUMINUM CLAD
WOOD WINDOWS
NEW ALUMINUM CLAD
WOOD WINDOWS
NEW HOLLOW METAL
EMERGENCY EGRESS
DOOR. PAINT.
EXHISTING PAINTED
BRICK. REPAIR / PAINT.
VTR TO BE REMOVED.
VTR TO BE REMOVED
ROOF
HATCH
EXISTING
EPDM ROOF
TO REMAIN
22' - 7"
52' - 1 3/8"
112' - 8 5/8"
10' - 0 1/2"
58' - 4 7/8"
A-301
A-301
LIFT
LIFT SUPPORT COLUMNS
AND RAILS TO BE
REMOVED. CAB AND
PULLEY MECHANISM TO
BE RELOCATED IN 206.
REMOVE METAL FIRE
DOOR AND SECURE
IN OPEN POSITION
REMOVE AND REPLACE
CONCRETE FOR WASTE
LINE. EXACT ROUTING
TO BE DETERMINED.
REMOVE
EXISTING VCT
FLOORING
HATCHED BUILDING IS PART
OF SEPARATE APPLICATION
REMOVE CMU AND
BRICK INFILL. PREP
OPENING TO RECEIVE
NEW WINDOW.
MEZZANINE COLUMNS
TO BE REMOVED
NON-ORIGINAL METAL
FRAMED PARTITION TO
BE REMOVED
REMOVE NON-
ORIGINAL BLOCK
STEPS. PATCH
FLOOR AND WALL
AS REQUIRED.
CONCRETE FLOOR FROM
THIS LINE TO REAR OF
BUILDING. PLYWOOD
AND WOOD JOISTS TO
FRONT OF BUILDING.
SEWER LINE TO CONTINUE
BENEATH WOOD JOISTS
TO THE STREET
REPLACE UPPER PANE OF
STOREFRONT WITH CURVED
GLAZING TO MATCH EXISTING
EXISTING RAISED
STOREFRONT
DISPLAY WOOD
FLOOR TO BE
REFINISHED
REMOVE TRANSOME AND DOORS. PREP
OPENING TO RECEIVE NEW FIRE RATED
WALL AND DOOR. STORE / MOUNT
DOORS TO WALL AS DISPLAY.
REMOVE ASBESTOS
FLOOR TILES
UP
UP
REMOVE AND
SALVAGE DOORS
REMOVE CONCRETE
PLATFORM. PATCH
CONCRETE FLOORING
AS REQUIRED.
SAWCUT CONCRETE FLOOR TO
REMOVE WASTE LINE. INFILL
FLOORING TO MATCH ADJACENT.
REMOVE AND REPLACE
DOOR TO MATCH ADJACENT
HATCHED BUILDING IS PART
OF SEPARATE APPLICATION
REMOVE CMU AND BRICK
INFILL. PREP OPENING TO
RECEIVE NEW WINDOW.
REMOVE CMU AND BRICK
INFILL. EXTEND OPENING
TO NEW FLOOR LEVEL
AND PREP OPENING TO
RECEIVE NEW DOOR.
REMOVE NON-ORIGINAL
WOOD FRAMED OSB
WALLS AND DOOR
EXISTING FIBERBOARD
CEILING TO BE
REMOVED TO EXPOSE
TONGUE AND GROOVE
WOOD CEILING
LOWERED GPDW CEILING
TO BE REMOVED TO
EXPOSE HIGH CEILING
EXISTING LINOLEUM WALL
COVERING TO BE REMOVED
EXISTING FRAMING TO REMAIN.
FIBERBOARD WALL COVERING
TO BE REMOVED.
REMOVE SECURITY BARS
REMOVE AND REPLACE
DOOR TO MATCH EXISTING
UP
UP
LIFT
LIFT SUPPORT
COLUMNS AND RAILS
TO BE REMOVED. CAB
AND PULLEY
MECHANISM TO BE
RELOCATED IN 206.
REAR MEZZANINE
TO BE REMOVED
REMOVE CHASE.
PATCH WALL.
OPEN TO
BELOW
NON-ORIGINAL METAL
FRAMED PARTITION
TO BE REMOVED.
REMOVE CMU AND BRICK
INFILL. PREP OPENING TO
RECEIVE NEW WINDOW.
UP
LIFT
LIFT SUPPORT
COLUMNS AND RAILS
TO BE REMOVED.
CAB AND PULLEY
MECHANISM TO BE
RELOCATED IN 206.
REMOVE AND
SECURE METAL
FIRE DOOR IN
OPEN POSITION
HATCHED BUILDING IS PART
OF SEPARATE APPLICATION
REMOVE CMU AND BRICK
INFILL. PREP OPENING TO
RECEIVE NEW WINDOW.
REMOVE PARTITION,
DOOR, PLUMBING
FIXTURES, AND PIPING
DN
REMOVE AND
SECURE METAL
FIRE DOOR IN
OPEN POSITION HATCHED BUILDING IS PART
OF SEPARATE APPLICATION
REMOVE CMU AND BRICK
INFILL. PREP OPENING TO
RECEIVE NEW WINDOW.
REMOVE WOOD
FRAMING AND
METAL WIRE
STORAGE CAGE
208G
DN
NON-ORIGINAL METAL
SIGN TO BE REMOVED
EXISTING DOORS
TO BE REMOVED
REMOVE EXISTING
WINDOW AC UNIT
& PLYWOOD INFILL
AT TRANSOM
REPLACE ACRYLIC
PANE WITH GLASS.
REMOVE EXISTING
PLYWOOD INFILL
REMOVE EXISTING WINDOW AC UNIT
AND PLYWOOD INFILL AT TRANSOM
REMOVE NON-ORIGINAL HOLLOW
METAL DOOR (OUT OF VIEW)
REMOVE INFILL AT
TRANSOM (OUT OF VIEW)
REMOVE EXISTING
METAL SECURITY BARS
EXISTING DOOR TO
BE REPLACED TO
MATCH EXISTING
REMOVE CORRUGATED
METAL SIDING TO EXPOSE
PAINTED WOOD SIDING
REMOVE CORRUGATED
METAL SIDING TO EXPOSE
PAINTED WOOD SIDINGREMOVE CORRUGATED METAL
SIDING TO EXPOSE PAINTED
WOOD SIDING (OUT OF VIEW)
LOCATION OF EXISTING MEZZANINE
FLOOR TO BE REMOVED
CMU / BRICK INFILL
TO BE REMOVED
CMU / BRICK INFILL TO BE REMOVED
CMU / BRICK INFILL TO BE REMOVED
NEW PLAQUE FOR
NATIONAL TRUST
FUNDING
REPLACE UPPER PANE OF
STOREFRONT WITH CURVED
GLAZING TO MATCH EXISTING
NEW GLASS TRANSOM
NEW GLASS DOORS TO
MATCH EXISTING. PAINT
DOORS AND FRAME.
REPAIR EXISTING
WINDOWS. PAINT.
EXISTING PAINTED
BRICK. REPAIR / PAINT.EXISTING PAINTED BRICK.
REPAIR / PAINT.
REPAIR EXISTING
WINDOW. PAINT.
REPAIR EXISTING WOOD
SIDING. PAINT.
REPAIR EXISTING WOOD
SIDING. PAINT.
NEW WOOD
GLASS DOOR TO
MATCH EXISTING
NEW GLASS TRANSOM
NEW GLASS TRANSOM
NEW GLASS TRANSOM
(OUT OF VIEW)
NEW WOOD GLASS
DOOR TO MATCH
EXISTING (OUT OF VIEW)
REPAIR EXTERIOR GYPSUM
CEILING IN RECESSED
ENTRANCE. PAINT.
REPAIR EXISTING WOOD
SIDING. PAINT.
NEW ALUMINUM CLAD
WOOD WINDOWS
EXISTING PAINTED
BRICK. REPAIR / PAINT.
NEW ALUMINUM CLAD
WOOD WINDOWS
NEW ALUMINUM CLAD
WOOD WINDOWS
NEW HOLLOW METAL
EMERGENCY EGRESS
DOOR. PAINT.
EXHISTING PAINTED
BRICK. REPAIR / PAINT.
11' - 8 1/2"
11' - 8 1/2"
EXPOSED
CEILING
EXPOSED
CEILING
EXPOSED
CEILING
26' - 11 3/8" 26' - 11 3/8"
T&G
T&G
25' - 10 7/8"
25' - 11 1/2"
EXPOSED
CEILING
ALL EXPOSED DUCT, CONDUIT, ETC.
TO BE PAINTED TO MATCH CEILING
REDISTRIBUTE WHITE
NOISE SPEAKERS
GENERAL CEILING NOTES
1.
2.
3.
4.
5.
6.
CONTRACTOR TO COORDINATE NEW WORK WITH HVAC AND ELECTRICAL.
CONTRACTOR RESPONSIBLE COORDINATING THE INSTALLATION ALL CEILING MOUNTED FIXTURES, DIFFUSERS, ETC.
CONTRACTOR TO PERFORM FINAL SETTING OF ALL CEILING MOUNTED ITEMS. CONTRACTOR RESPONSIBLE FOR FINAL
CLEANING OF ALL CEILING MOUNTED ITEMS.
ALL CEILINGS ARE TO REMAIN AT EXISTING HEIGHTS UNLESS OTHERWISE NOTED.
CONTRACTOR TO COORDINATE ALL ABOVE CEILING TRADES TO AVOID CONFLICT.
CONTRACTOR RESPONSIBLE FOR COORDINATING ALL LAY-IN FIXTURES, DIFFUSERS, ETC.
7. CONTRACTOR RESPONSIBLE FOR PROVIDING AND INSTALLING NEW EXIT SIGNS AND EMERGENCY LIGHTING AS SHOWN.
7' - 6 1/4"
GPDW
A-103
3/4" SHEATHING
2x6 CEILING JOIST @ 16" O.C.
5/8" GPDW
SOUND ATTENUATION
BATTS
TRIM BOARD
(PAINT BLACK)
CAULK
NEW STUD WALL BEYOND
NEW STOREFRONT BEYOND
E
54321
D
C
B
A
CHECKED BY
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SO
LE
X
AR
C H
IT
EC
TU
R
E, IN
C
M
AI
N S
TR
EE
T D
AN
VI
LL
E, V
IR
G
IN
IA
4.
8.
P H
O N
E
4.
1.
F
AX
SCALE
SHEET NUMBER
SHEET INFORMATION
SHEET NAME
As indicated
A-103
REFLECTED
CEILING PLAN
KMW/JMW
JLB
2026.08.17
20260025
R
EN
O
VA
TI
O
N T
O
N
O R
TH
U
N
IO
N S
T
N O
R
TH
U N
IO
N
P R
O
PE
R
TI
ES
, L
LC
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
N O
R
TH
U N
IO
N
S
TR
EE
T
D
AN
VI
LL
E, V
IR
G
IN
IA
Scale: 1/8" = 1'-0"A-501A-103
FIRST FLOOR REFLECTED CEILING PLAN1
EXISTING
HALLWAY
Scale: 1/2" = 1'-0"A-103
VESTIBULE REFLECTED CEILING PLAN2
Scale: 3" = 1'-0"A-103A-103
STOREFRONT CEILING DETAIL3
ALL FRAMES TO BE 2"
WIDE UNLESS NOTED
OTHERWISE.
SOME OF THE FRAME
TYPES SHOWN IN
THIS LEGEND MAY
NOT BE USED IN THIS
PROJECT.
D O
O R
H
EI
G H
T
WIDTH
DOOR
F
H
EI
G H
T
WIDTH
FG
H
EI
G H
T
WIDTH
1'
0" 6"
6"6"
TYPICAL DOOR HEAD AND JAMB DETAILS
SOUND
ATTENUATION
BATTS
5/8" GPDW
CAULK CONT. ON
BOTH SIDES
H.M. FRAME - VERIFY
FRAME DEPTH BASED
ON STUD WALL SIZE
WOOD STUDS
2"
MIN. 3 ANCHORS
PER JAMB
WOOD DOOR
SOUND
ATTENUATION
BATTS
5/8" GPDW
CAULK CONT. ON
BOTH SIDES
H.M. FRAME - VERIFY
FRAME DEPTH BASED ON
STUD WALL SIZE
MIN. 3 ANCHORS
PER JAMB
WOOD STUDS
2"
WOOD DOOR
5/8" GPDW
H1
J1
H2
J2
6 3/4"
4 3/4" OR
ALUMINUM
FRAME
ALUMINUM
DOOR
STOREFRONT
GLAZING
ALUMINUM
FRAME
ALUMINUM
DOOR
STOREFRONT
GLAZING
1/ 8"
1/
2"
4 1/2"
1/8"
T
T T
1'
6"
2" 2"
5'
2"
2"1' - 3 3/4"
2"
1' - 3 3/4"
2"
3' - 0"
8'
5/
8"
/8
2"
T T
4 1/2"
6' - 8"
2"
T
T T
T T
1' - 5 1/2" 1' - 5 1/2" 2"
2" 3' - 0" 2" 2"
2"
5'
2"
2"
1'
6"
2" 7'
2"
ALL GLAZING TO RECEIVE D-H-45
6' - 6 7/8"
J1
H1
TYPICAL STOREFRONT DETAILS
CAULK CONT. ON
BOTH SIDES
SOUND ATTENUATION
BATTS (FULL HEIGHT
OF WALL)
METAL STUD @ 16"O.C.
PROVIDE 2 AT JAMB
CAULK CONT. ON
BOTH SIDES
5/8" GPDW EACH SIDE
UNLESS OTHERWISE
NOTED
2" x 4 1/2" ALUMINUM
STOREFRONT FRAME
2"x 4 1/2" ALUMINUM
STOREFRONT FRAME
5/8" GPDW
(2) 2x6 TOP PLATE
1x6 TRIM BOARD. PAINT.
(2) 2x8 RIM JOIST
5/8" GPDW
3/4" SHEATHING
2x6 CEILING JOIST @ 16" O.C.
S1
EXISTING SUBFLOOR
EXISTING FLOORING
PREFINISHED BRAKE
METAL TRIM
2" x 4 1/2" ALUMINUM
STOREFRONT FRAME
POP RIVET OR
ADHESIVE TAPE
GENERAL STOREFRONT NOTES
NOTE: T SYMBOL INDICATES PANELS OF TEMPERED / SAFETY GLAZING
E
54321
D
C
B
A
CHECKED BY
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SO
LE
X
AR
C H
IT
EC
TU
R
E, IN
C
M
AI
N S
TR
EE
T D
AN
VI
LL
E, V
IR
G
IN
IA
4.
8.
P H
O N
E
4.
1.
F
AX
SCALE
SHEET NUMBER
SHEET INFORMATION
SHEET NAME
As indicated
A-601
DOOR
SCHEDULE,
ELEVATIONS,
AND DETAILS
AND WALL
DETAILS
KMW
JLB
2026.08.17
20260025
R
EN
O
VA
TI
O
N T
O
N
O R
TH
U
N
IO
N S
T
N O
R
TH
U N
IO
N
P R
O
PE
R
TI
ES
, L
LC
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
N O
R
TH
U N
IO
N
S
TR
EE
T
D
AN
VI
LL
E, V
IR
G
IN
IA
Scale: 1/4" = 1'-0"A-601
DOOR FRAME TYPES2
Scale: 1/4" = 1'-0"A-601
DOOR PANEL TYPES1
206 DOOR SCHEDULE
D O
O R
N U
M
BE
R DOOR FRAME DETAILS
FI
R
E
LA
BE
L
H
AR
D W
AR
E
D O
O R
N U
M
BE
R
SIZE
TYPE M
AT
ER
IA
L
G
LA
ZI
N
G
TY
PE
M
AT
ER
IA
L
H
EA
D
JA
M
B
W
ID
TH
H
EI
G H
T
101 3' - 0" 7' - 0" FG AL 01 AL H2 J2 1 101
102 3' - 0" 7' - 0" FG AL D-H-45 01 AL H2 J2 45 MIN. 1 102
103A 3' - 0" 7' - 0" F HM 01 HM H1 J1 45 MIN. 2 103A
103B 3' - 0" 7' - 0" F HM 01 HM H1 J1 45 MIN. 2 103B
103C 3' - 0" 7' - 0" F HM 02 HM H1 J1 3 103C
FINISH LIST
FINISH COMMENTS
FLOOR FINISHES
GROUT (G)
G-1 MAPEI, 47 CHARCOAL, ANTHRACITE, CARBON, 1/8"
TILE (T)
T-2 EXISTING TILE FLOORING
BASE FINISHES
PAINT (PNT)
PNT-2 SHERWIN-WILLIAMS, S7006, EXTRA WHITE, SEMI-GLOSS
WALL FINISHES
PAINT (PNT)
PNT-5 SHERWIN-WILLIAMS, SW7064, PASSIVE, EGGSHELL
FINISH SCHEDULE
ROOM MATERIALS AND FINISHES
NAME NUMBER WALL MATERIAL WALL FINISH BASE MATERIAL BASE FINISH FLOOR MATERIAL FLOOR FINISH CEILING MATERIAL CEILING FINISH
VESTIBULE 100 GPDW, EXIST. PLASTER PNT-5 NEW DIMENSIONAL WOOD PNT-2 T-2, G-1 SEAL EXISTING WOOD ROOF STRUCTURE PNT-2 TENANT A 101 GPDW, EXIST. PLASTER PNT-5 NEW DIMENSIONAL WOOD PNT-2 T-2, G-1 SEAL EXISTING WOOD ROOF STRUCTURE PNT-2 TENANT B 102 GPDW, EXIST. PLASTER PNT-5 NEW DIMENSIONAL WOOD PNT-2 T-2, G-1 SEAL EXISTING WOOD ROOF STRUCTURE PNT-2
BACKROOM 103 GPDW PNT-5 NEW DIMENSIONAL WOOD PNT-2 T-2, G-1 SEAL EXISTING WOOD ROOF STRUCTURE PNT-2 MECH. 104 GPDW PNT-5 NEW DIMENSIONAL WOOD PNT-2 T-2, G-1 SEAL EXISTING WOOD ROOF STRUCTURE PNT-2
Scale: 3/4" = 1'-0"A-101A-601
RETAIL 1 VESTIBULE DOOR3
Scale: 3/4" = 1'-0"A-101A-601
RETAIL 2 VESTIBULE DOOR4
1. PROVIDE WEATHERSTRIPPING, THRESHOLD, CLOSER, PUSH/PULL BAR, AND ENTRY LOCK WITH THUMB LATCH ON INTERIOR.
2. PROVIDE WEATHERSTRIPPING, CLOSER, AND ENTRY LOCKSET.
3. PROVIDE SILENCERS AND STOREROOM LOCKSET.
4. ALL HARDWARE TO MATCH EXISTING FINISH, QUALITY, TYPE, AND KEYWAY. CONFIRM KEYING W/OWNER.
1. ALL PAINT COLORS TO MATCH EXISTING.
2. NEW WOOD BASE AND MOLDING TO MATCH EXISTING.
RECTANGULAR/SQUARE TO ROUND DUCT EQUIVALENT
RECTANGULAR DUCT ROUND DUCT
30"X26" 30"Ø
20"X26" 24"Ø
18"X18" 20"Ø
18"X20" 20"Ø
20"X16" 18"Ø
16"X16" 16"Ø
10"X16" 14"Ø
10"X20" 16"Ø
16"X14" 16"Ø
16"X12" 14"Ø
GENERAL MECHANICAL NOTES:
ADMINISTRATIVE:
1. THE FOLLOWING ABBREVIATIONS SHALL APPLY TO NOTES AND PLANS:
PC - PLUMBING CONTRACTOR,
EC - ELECTRICAL CONTRACTOR,
MC - MECHANICAL CONTRACTOR,
GC - GENERAL CONTRACTOR,
FASC - FIRE ALARM SYSTEM CONTRACTOR,
AHJ - AUTHORITY HAVING JURISDICTION.
SMC - CURRENT STATE MECHANICAL CODE (VIRGINIA MECHANICAL CODE)
SBC - CURRENT STATE BUILDING CODE (VIRGINIA CONSTRUCTION CODE)
SECC- CURRENT STATE ENERGY CONSERVATION CODE (VIRGINIA ENERGY
CONSERVATION CODE)
NFPA - NATIONAL FIRE PROTECTION ASSOCIATION
2. "PROVIDE" MEANS TO FURNISH AND INSTALL. MC SHALL ALSO INSTALL MATERIALS
FURNISHED BY OTHERS AND GENERAL CONTRACTOR AS SHOWN ON THE PLANS OR
NECESSARY FOR A COMPLETE INSTALLATION.
3. THE MC SHALL BE RESPONSIBLE FOR A COMPLETE AND OPERATING SYSTEM AS
DESCRIBED BY THESE PLANS AND SPECIFICATIONS.
4. ALL MATERIALS AND EQUIPMENT SHALL BE DELIVERED TO THE SITE AND UNLOADED
BY THE CONTRACTOR AT AN APPROVED LOCATION. THE MC SHALL PROTECT ALL
MATERIALS AND EQUIPMENT FROM BREAKAGE, THEFT, AND THE ELEMENTS. ALL
MATERIALS AND EQUIPMENT SHALL REMAIN THE PROPERTY OF THE MC UNTIL THE
PROJECT HAS BEEN COMPLETED AND TURNED OVER TO THE OWNER.
5. THE MC SHALL INSTALL ALL MATERIALS AND EQUIPMENT IN ACCORDANCE WITH THE
SMC AND SBC AND ANY APPLICABLE LOCAL CODES. WHERE A CONFLICT EXISTS
BETWEEN THE ABOVE REQUIREMENTS, THE MC SHALL OBTAIN CLARIFICATION FROM
THE ENGINEER OR IN THE EVENT ANY PART OF THESE PLANS CONFLICTS WITH THE
ABOVE REQUIREMENTS.
6. THE MC SHALL OBTAIN AND PAY FOR ALL PERMITS, FEES, AND INSPECTIONS
NECESSARY FOR THE COMPLETION OF THE WORK UNDER THIS CONTRACT.
7. DO NOT SCALE THESE DRAWINGS-REFER TO ARCHITECTURAL SHEETS FOR
DIMENSIONS.
8. THE MC SHALL VISIT THE SITE PRIOR TO BIDDING TO BECOME FAMILIAR WITH
EXISTING CONDITIONS. THE MC SHALL CONTACT THE ENGINEER TO RESOLVE ANY
DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THESE PLANS. THE MC SHALL
COORDINATE WITH OTHER TRADES PRIOR TO THE START OF CONSTRUCTION.
9. ALL MECHANICAL MATERIALS SHALL BE NEW AND FREE OF DEFECT AND LISTED AND
LABELED BY UL OR AN APPROVED THIRD-PARTY AGENCY. ANY MATERIALS FOUND TO
BE DEFECTIVE SHALL BE REPLACED BY THE MC WITHOUT ADDITIONAL COST TO THE
OWNER. WHERE A MANUFACTURER AND MODEL NUMBER IS GIVEN, THE CITED
EXAMPLE IS INTENDED TO ESTABLISH A STANDARD OF QUALITY AND NOT TO LIMIT
PRODUCTS TO A PARTICULAR MANUFACTURER. SUCH EXAMPLES ARE USED TO
CONVEY A GENERAL STYLE, TYPE, CHARACTER, AND QUALITY OF THE PRODUCT
DESIRED; PRODUCTS DETERMINED TO BE EQUAL BY THE ENGINEER WILL BE
ACCEPTED.
10. THESE PLANS ARE DIAGRAMMATIC. THE MC SHALL ADJUST THE LOCATIONS OF
EQUIPMENT, DUCTS, REGISTERS, GRILLES, ETC, TO ACCOMMODATE PLANNED AND
ENCOUNTERED INTERFERENCES. THE DRAWINGS DO NOT SHOW ALL BENDS,
OFFSETS, AND FITTINGS THAT MAY BE REQUIRED FOR A COMPLETE AND
OPERATIONAL SYSTEM. THE MC SHALL MAKE ALLOWANCES FOR SUCH DEVIATIONS
AND CONTINGENCIES IN BID TO IMPLEMENT THEM WITHOUT ADDITIONAL COST TO THE
OWNER.
11. EC SHALL BE RESPONSIBLE FOR ALL POWER CONNECTIONS TO THE MECHANICAL
EQUIPMENT. MC SHALL BE RESPONSIBLE FOR ALL CONTROL WIRING.
12. IT IS THE MC'S RESPONSIBILITY TO VERIFY THAT ITEMS FURNISHED FOR THIS
CONTRACT WILL FIT IN THE SPACE AVAILABLE. THE MC SHALL MAKE FIELD
MEASUREMENTS AS NECESSARY TO DETERMINE SPACE REQUIREMENTS. IF THE MC
MUST ALTER EQUIPMENT DUE TO SPACE CONSIDERATIONS, THE MC SHALL PROVIDE
SIZES AND SHAPES THAT FIT THE INTENT OF THESE DRAWINGS AND SPECIFICATIONS.
13. MC SHALL COORDINATE WITH THE EC REGARDING THE ELECTRICAL REQUIREMENTS
OF ALL EQUIPMENT BEING PROVIDED.
14. MAINTAIN CLEARANCES FOR ALL EQUIPMENT ACCORDING TO MANUFACTURER'S
RECOMMENDATIONS FOR SERVICEABILITY. ALL ROOFTOP EQUIPMENT MUST BE A
MINIMUM OF 10 FEET FROM ROOF EDGE.
15. MC SHALL FURNISH A BOUND SET OF OPERATING AND MAINTENANCE INSTRUCTIONS
FOR ALL EQUIPMENT TO THE OWNER UPON COMPLETION OF THE PROJECT. MC SHALL
PROVIDE ALL DOCUMENTATION TO THE OWNER AS NECESSARY TO SUBMIT FOR
FACTORY WARRANTIES.
16. CONTRACTOR SHALL PROTECT ALL HVAC EQUIPMENT FROM CONSTRUCTION AND
SHEET ROCK DUST DURING CONSTRUCTION. ALL FILTERS SHALL BE REPLACED WITH
NEW AT THE COMPLETION OF THE PROJECT.
17. ALL EQUIPMENT INSTALLED ON ROOF MUST BE WITHIN THE ROOF SCREEN.
18. IF A ROOF PENETRATION IS REQUIRED AND THE ROOF IS UNDER WARRANTY, USE THE
AUTHORIZED ROOFER. PROVIDE DOCUMENTATION.
19. ALL PIPING, WIRING, CONDUIT, INSULATION, EQUIPMENT, SUPPORTS, ETC. SHALL BE
SUITABLE FOR INSTALLATION IN A RETURN PLENUM AS NECESSARY. COORDINATE
WITH OTHER TRADES ON LOCATIONS OF ALL PLENUMS.
20. MC SHALL COORDINATE WITH THE GENERAL CONTRACTOR TO ENSURE ALL
APPLICABLE CONSTRUCTION WASTE IS RECYCLED DURING THE CONSTRUCTION
PHASE OF THE PROJECT.
21. THE MC SHALL VERIFY THE FUNCTIONALITY AND OPERATION OF ALL EXISTING
MECHANICAL EQUIPMENT IN THE AREA OF WORK. REPLACE FILTERS, LEAK TEST AND
RECHARGE REFRIGERANT LINES, REPLACE OR LUBRICATE BEARINGS, CHECK
LINKAGES AND ACTUATORS, AND PERFORM OTHER MAINTENANCE SERVICE AS
NECESSARY TO GET THE EQUIPMENT IN PROPER ORDER.
METHODS:
1. INSULATE DUCTWORK WITH FIBERGLASS DUCT WRAP; INSTALLED R-VALUE SHALL BE
A MINIMUM R-6. COVERINGS AND LININGS, INCLUDING ADHESIVES WHEN USED, SHALL
HAVE A FLAME SPREAD INDEX NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84. ALL NEW
DUCTWORK SHALL RECEIVE INSULATION ON THE OUTSIDE. INSTALL DUCT WRAP
INSULATION WITH FACING OUTSIDE SO THAT TAPE FLAP OVERLAPS INSULATION AND
FACING OF ADJACENT PIECE OF DUCT WRAP. INSULATION SHALL BE TIGHTLY BUTTED.
FOR RECTANGULAR DUCTS, INSTALL SO INSULATION IS NOT EXCESSIVELY
COMPRESSED AT DUCT CORNERS. STAPLE SEAMS APPROXIMATELY 6 INCHES ON
CENTER WITH OUTWARD CLINCHING STAPLES. SEAL SEAMS WITH PRESSURE
SENSITIVE TAPE MATCHING THE FACING. FOR RECTANGULAR DUCTS 24 INCHES IN
WIDTH OR GREATER, SECURE DUCT WRAP TO THE BOTTOM OF THE DUCT WITH
MECHANICAL FASTENERS SPACED 18 INCHES ON CENTER TO PREVENT SAGGING OF
INSULATION. ADJACENT SECTIONS OF DUCT WRAP SHALL BE TIGHTLY BUTTED WITH
THE 2 INCH TAPE FLAP OVERLAPPING. ALL TEARS, PUNCTURES, ETC. OF THE DUCT
WRAP INSULATION SHALL BE SEALED WITH TAPE OR MASTIC TO PROVIDE A VAPOR
TIGHT SYSTEM. INSULATION SHALL BE BY KNAUF INSULATION, OWENS CORNING
CORP, OR CERTAINTEED CORPORATION.
2. VERIFY THAT DUCTS HAVE BEEN TESTED BEFORE APPLYING INSULATION MATERIALS.
VERIFY THAT DUCT SURFACES ARE CLEAN, DRY AND FREE OF FOREIGN MATERIAL
PRIOR TO INSULATING. DUCT COVERINGS SHALL NOT PENETRATE A WALL OR FLOOR
REQUIRED TO HAVE A FIRE-RESISTANCE RATING OR REQUIRED TO BE FIRE BLOCKED.
3. WHERE DUCTS ARE CONNECTED TO EXTERIOR WALL LOUVERS AND DUCT OUTLET IS
SMALLER THAN LOUVER FRAME, PROVIDE BLANK-OUT PANELS SEALING LOUVER AREA
AROUND DUCT. USE SAME MATERIAL AS DUCT, PAINTED BLACK ON EXTERIOR SIDE.
SEAL TO LOUVER FRAME AND DUCT.
4. PROVIDE DUCT ACCESS DOORS FOR INSPECTION AND CLEANING BEFORE AND AFTER
FILTERS, COILS, FANS, AUTOMATIC DAMPERS, AT FIRE DAMPERS, COMBINATION FIRE
AND SMOKE DAMPERS.
5. CONSTRUCT T's, BENDS, AND ELBOWS WITH RADII OF NOT LESS THAN 1-1/2 TIMES THE
WIDTH OF THE DUCT ON CENTERLINE. WHERE NOT POSSIBLE AND WHERE
RECTANGULAR ELBOWS MUST BE USED, PROVIDE TURNING VANES.
6. INCREASE DUCT SIZES GRADUALLY, NOT EXCEEDING 15 DEGREES DIVERGENCE;
MAXIMUM OF 30 DEGREES DIVERGENCE UPSTREAM OF EQUIPMENT AND 45 DEGREES
CONVERGENCE DOWNSTREAM.
7. IT SHALL BE THE RESPONSIBILITY OF THE MC TO SUSPEND AND SUPPORT ALL
EQUIPMENT, DUCTWORK, DIFFUSERS, AND OTHER MATERIALS FOLLOWING
RECOGNIZED ENGINEERING PRACTICES AND USING STANDARD, COMMERCIALLY
ACCEPTED HANGERS AND SUSPENSION EQUIPMENT. ALL HVAC EQUIPMENT SHALL BE
SECURELY MOUNTED TO THE BUILDING STRUCTURE AND SHALL NOT RELY ON
CEILING OR WALL SURFACES FOR SUPPORT. THE SUPPORT ATTACHMENT SHALL
SUPPORT THE WEIGHT OF THE EQUIPMENT PLUS THE WEIGHT OF THE SUPPORT
ATTACHMENT ITSELF. SUPPORT FROM THE TOP CHORD OF THE ROOF JOISTS,
GIRDERS, AND BEAMS. THE BOTTOM CHORD IS NOT TO BE USED FOR EQUIPMENT OR
PIPING SUPPORT. HANGERS SHALL NOT BE ATTACHED TO CORRUGATED STEEL
DECKING.
8. DUCTS SHALL BE SUPPORTED IN ACCORDANCE WITH SMACNA AT INTERVALS NOT
EXCEEDING 10 FEET. DUCTS 36 INCHES OR LARGER SHALL HAVE TRAPEZE TYPE
HANGERS SUSPENDED WITH THREADED ROD. SUPPORT DUCTS FROM BAR JOISTS,
GIRDERS, OR BEAMS.
9. CHECK LOCATIONS OF AIR OUTLETS AND INLETS AND MAKE NECESSARY
ADJUSTMENTS IN POSITION TO CONFORM WITH ARCHITECTURAL FEATURES,
SYMMETRY, AND LIGHTING ARRANGEMENT. COORDINATE WITH SPRINKLER
CONTRACTOR IF APPLICABLE.
10. PROVIDE BALANCING DAMPERS AT POINTS ON SUPPLY WHERE BRANCHES ARE TAKEN
FROM LARGER DUCTS AS REQUIRED FOR AIR BALANCING. INSTALL MINIMUM 2 DUCT
WIDTHS FROM DUCT TAKE-OFF. PROVIDE BALANCING DAMPERS ON DUCT TAKE-OFFS
TO DIFFUSERS AND REGISTERS, REGARDLESS OF WHETHER DAMPERS ARE
SPECIFIED AS PART OF THE DIFFUSER OR REGISTER ASSEMBLY. ADJUST AIR
HANDLING AND DISTRIBUTION SYSTEMS TO PROVIDE DESIGN SUPPLY, RETURN, AND
EXHAUST AIR QUANTITIES AT SITE ALTITUDE.
11. MC SHALL INSTALL PROGRAMMABLE THERMOSTATS AS SHOWN ON THE PLANS.
THERMOSTAT SHALL BE MOUNTED AT 48 INCHES AFF. THERMOSTATS SHALL MEET
THE REQUIREMENTS FOR THERMOSTATIC CONTROLS IN SECTION C403 OF THE SECC.
12. FRESH AIR INTAKES SHALL BE INSTALLED ON ALL UNITS AS SHOWN ON DRAWINGS.
MAINTAIN 10 FEET OF DISTANCE BETWEEN FRESH AIR INTAKES AND ALL EXHAUST
TERMINATIONS AND PLUMBING VENT THRU ROOFS.
13. MC SHALL INSTALL ALL EXHAUST FANS AND VENT TO THE BUILDING'S EXTERIOR. EC
SHALL SWITCH FANS WITH LIGHTS OR ON SEPARATE SWITCH AS SHOWN.
14. P-TRAPS MUST BE INSTALLED ON ALL UNITS. MC SHALL INSTALL AUXILIARY DRAIN
PANS UNDER OVERHEAD AIR HANDLERS AND AN AUTOMATIC CUT-OFF FLOAT SWITCH
FOR EACH. P-TRAPS AND CONDENSATE LINES SHALL BE 1 INCH. P-TRAPS AND
CONDENSATE LINES MAY BE PVC WHERE NOT LOCATED IN PLENUMS; OTHERWISE,
THEY SHALL BE TYPE M COPPER.
15. INSTALL BACKDRAFT DAMPERS ON FRESH AIR AND EXHAUST DUCTS WHERE THEY
PENETRATE THE THERMAL ENVELOPE PER SECC C402.5.7
16. DUCTS CONNECTING TO A FURNACE SHALL HAVE A CLEARANCE TO COMBUSTIBLES IN
ACCORDANCE WITH THE FURNACE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
17. FOR STRUCTURES IN FLOOD HAZARD AREAS, DUCTS SHALL BE LOCATED ABOVE THE
DESIGN FLOOD ELEVATION. DUCT SHALL NOT BE INSTALLED IN OR WITHIN 4 INCHES
OF THE EARTH.
18. MC SHALL INSTALL FIRE DAMPERS AT EACH PENETRATION OF A RATED WALL AS
INDICATED ON THE DRAWINGS OR AS REQUIRED BY THE AUTHORITY HAVING
JURISDICTION. FIRE DAMPERS SHALL BE UL LABELED (UL 555), CURTAIN TYPE, WITH
INTEGRAL FACTORY SLEEVE AND BLADES LOCATED OUTSIDE THE AIR STREAM.
INSTALLATION OF ALL FIRE DAMPERS SHALL BE IN ACCORDANCE WITH THE
MANUFACTURER'S INSTALLATION INSTRUCTIONS AND SECTION 607 OF THE SMC.
PROVIDE ACCESS PANELS FOR TESTING AND SERVICE AS NECESSARY. MC SHALL
PROVIDE RADIATION DAMPERS AND THERMAL BLANKETS FOR ALL PENETRATIONS OF
RATED CEILING ASSEMBLIES. RADIATION DAMPERS SHALL BE UL LABELED (UL 555C)
AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFIC
INSTALLATION INSTRUCTIONS. FIRE DAMPERS, COMBINATION FIRE/SMOKE DAMPERS,
AND CEILING RADIATION DAMPERS SHALL BE BY RUSKIN, NAILOR, OR LLOYD
INDUSTRIES.
19. MC SHALL INSTALL A SMOKE DETECTOR-UL LISTED FOR DUCT INSTALLATION (UL 268A)
IN EACH UNIT'S RETURN UPSTREAM OF ANY FILTERS, OUTSIDE AIR CONNECTIONS, OR
DECONTAMINATION EQUIPMENT. DUCT SMOKE DETECTORS SHALL BE INSTALLED IN
ACCORDANCE WITH NFPA 72. DUCT SMOKE DETECTOR SUPERVISION SHALL COMPLY
WITH 606.4.1 OF THE SMC. IF THE BUILDING IS (TO BE) EQUIPPED WITH A FIRE ALARM
SYSTEM, THE FIRE ALARM SYSTEM CONTRACTOR SHALL FURNISH AND WIRE ALL DUCT
SMOKE DETECTORS. IF THE BUILDING IS NOT PROVIDED WITH A FIRE ALARM SYSTEM,
THE MC SHALL FURNISH AND WIRE THE DUCT SMOKE DETECTORS AND A/V DEVICE. IT
SHALL BE THE RESPONSIBILITY OF THE MC TO INSTALL ALL SMOKE DUCT DETECTORS
PER NFPA AND MFG'S INSTALLATION INSTRUCTIONS REGARDLESS OF WHO
FURNISHES THE DEVICES.
20. UNITS PROVIDED WITH ECONOMIZERS SHALL ALSO BE PROVIDED WITH POWERED
EXHAUST AND COMPARATIVE ENTHALPY CONTROLS.
MATERIALS:
1. THE MC SHALL PROVIDE ALL HEATING AND COOLING EQUIPMENT AS SCHEDULED ON
THE DRAWINGS. ALTERNATES SHALL BE FROM MANUFACTURERS LISTED IN
SCHEDULES. THE MC SHALL PROVIDE FACTORY AND FIELD INSTALLED ACCESSORIES
AS SCHEDULED OR AS NECESSARY FOR A COMPLETE AND OPERATIONAL HVAC
SYSTEM.
2. THE MC SHALL PROVIDE ALL EXHAUST AND SUPPLY FANS AS SCHEDULED OR BY
EQUALS LISTED.
3. DUCTWORK IS SHOWN WITH FREE AREA DIMENSIONS. ALL DUCTWORK SHALL BE
FABRICATED AND INSTALLED IN ACCORDANCE WITH SMACNA LOW PRESSURE DUCT
STANDARD, 2 INCH S.P.
4. EXTERNAL DUCT INSULATION AND FACTORY-INSULATED FLEXIBLE DUCT SHALL BE
LEGIBLY PRINTED OR IDENTIFIED AT INTERVALS NOT GREATER THAN 36 INCHES WITH
THE NAME OF THE MANUFACTURER, THE THERMAL RESISTANCE R-VALUE AT THE
SPECIFIED INSTALLED THICKNESS AND THE FLAME SPREAD AND SMOKE-DEVELOPED
INDEXES OF THE COMPOSITE MATERIALS. ALL DUCT INSULATION PRODUCT R-VALUES
SHALL BE BASED ON INSULATION ONLY, EXCLUDING AIR FILMS, VAPOR RETARDERS
OR OTHER DUCT COMPONENTS, AND SHALL BE BASED ON TESTED C-VALUES AT 75ºF
MEAN TEMPERATURE AT THE INSTALLED THICKNESS, IN ACCORDANCE WITH
RECOGNIZED INDUSTRY PROCEDURES. THE INSTALLED THICKNESS OF DUCT
INSULATION USED TO DETERMINE ITS R-VALUES SHALL BE DETERMINED AS FOLLOWS:
4.1. FOR DUCT BOARD, DUCT LINER AND FACTORY-MADE RIGID DUCTS NOT
NORMALLY SUBJECTED TO COMPRESSION, THE NOMINAL INSULATION THICKNESS
SHALL BE USED.
4.2. FOR DUCT WRAP, THE INSTALLED THICKNESS SHALL BE ASSUMED TO BE 75
PERCENT (25-PERCENT COMPRESSION) OF NOMINAL THICKNESS.
4.3. FOR FACTORY-MADE FLEXIBLE AIR DUCTS, THE INSTALLED THICKNESS SHALL
BE DETERMINED BY DIVIDING THE DIFFERENCE BETWEEN THE ACTUAL OUTSIDE
DIAMETER AND NOMINAL INSIDE DIAMETER BY TWO.
5. ALL INSULATION CONTAINING FIBROUS MATERIALS EXPOSED TO AIRFLOW SHALL BE
RATED FOR THAT EXPOSURE OR SHALL BE ENCAPSULATED. INSULATING PROPERTIES
FOR ALL MATERIALS SHALL MEET OR EXCEED INDUSTRY STANDARDS. POLYSTYRENE
PRODUCTS SHALL MEET ASTM C578. ALL INSULATION SHALL HAVE FORMALDEHYDE
EMISSIONS NOT GREATER THAN 0.05 PPM. THE MAXIMUM FLAME SPREAD AND SMOKE
DEVELOPED INDEX FOR INSULATION SHALL MEET THE REQUIREMENTS OF THE LOCAL
CODES AND ORDINANCES ADOPTED BY THE JURISDICTION IN WHICH THE BUILDING IS
LOCATED.
6. MASTIC USED TO SEAL DUCTWORK SHALL BE LISTED AND LABELED IN ACCORDANCE
WITH UL 181A OR UL 181B MAINTAIN AMBIENT TEMPERATURES AND CONDITIONS
REQUIRED BY MANUFACTURER OF ADHESIVES, MASTICS, AND INSULATION CEMENTS.
DO NOT INSTALL DUCT SEALANT WHEN TEMPERATURES ARE LESS THAT THOSE
RECOMMENDED BY THE SEALANT MANUFACTURER.
7. ALL ADHESIVES AND SEALANTS SHALL HAVE VOC CONTENT BELOW 20 GRAMS PER
LITER AND WHICH MEET THE REQUIREMENTS OF THE MANUFACTURER OF THE
PRODUCTS BEING ADHERED OR INVOLVED. ADHESIVES AND SEALANTS SHALL
CONTAIN NO HEAVY METALS OR FORMALDEHYDE.
8. FACTORY-MADE AIR DUCTS AND CONNECTORS SHALL COMPLY WITH UL 181.
9. FLEXIBLE DUCT SHALL BE UL LISTED CLASS 0 OR CLASS 1, INSULATED, AND COMPLY
WITH UL 181. FLEXIBLE DUCT SHALL BE FACTORY FORMED, COMPOSED OF SPIRAL
WOUND CORROSION RESISTANT WIRE BONDED TO AN INNER FABRIC LINER. DUCT
SHALL BE FACTORY INSULATED WITH A FOIL VAPOR BARRIER JACKET. CONNECT TO
RIGID DUCT WITH SPIN-IN FITTING AND DAMPER. FLEXIBLE DUCTS AND AIR
CONNECTORS SHALL NOT PASS THROUGH ANY FIRE RESISTANCE RATED ASSEMBLY.
10. THE MC SHALL PROVIDE ALL DIFFUSERS GRILLES, LOUVERS, AND OTHER AIR
DISTRIBUTION OUTLETS AND INLETS. LOUVERS, GRILLES, AND DIFFUSERS SHALL BE
INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FOR LAY-IN CEILINGS, INSTALL SUPPORT FROM THE STRUCTURE FOR
EACH DIFFUSER OR DAMPER. AIR DISTRIBUTION OUTLETS AND INLETS SHALL BE AS
SCHEDULE OR ALTERNATES LISTED.
11. AIR FILTERS SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 605 OF THE SMC
12. THE MC SHALL PROVIDE ALL REFRIGERATION PIPING. ALL PIPE AND FITTINGS SHALL
BE TYPE ACR HARD COPPER TUBING WITH SWEAT FITTINGS. REFRIGERATION LINES
SHALL BE RUN NEATLY. WHERE A GROUP OF LINES ARE RUN, TRAPEZE HANGERS MAY
BE USED. DO NOT USE CHAIN OR WIRE HANGERS. WRAP TUBING WITH RUBBER TAPE
AT EACH CLAMP OR HANGER. FOR COVERED PIPES, HANGERS SHALL FIT AROUND THE
OUTSIDE OF THE COVERING WITH 12 GAUGE GALVANIZED STEEL SHIELDS OF A
LENGTH EQUAL TO THE OUTSIDE DIAMETER OF THE INSULATION AND COVERING 3/4
OF THE CIRCUMFERENCE OF THE INSULATION. SAGS SHALL NOT BE PERMISSIBLE.
HORIZONTAL LINES SHALL PITCH DOWN NOT LESS THAN 1 INCH IN 40 FEET. INSULATE
WITH 1 INCH CLOSED CELL ARMAFLEX TYPE INSULATION WITH A FLAME DENSITY
RATING LESS THAN 25 AND A SMOKE DENSITY RATING LESS THAN 50. ALL JOINTS AND
SPLICES IN INSULATION SHALL BE TAPED AND AIRTIGHT. SOLDER REFRIGERATION
LINES USING 15 PERCENT SILVER SOLDER AND EVACUATE LINES TO 300 MICRONS.
PROVIDE MOISTURE INDICATING SIGHT GLASS AND FILTER DRYER IN LIQUID LINE.
PROVIDE OIL TRAPS AND DOUBLE RISERS IN REFRIGERANT SUCTION AND HOT GAS
LINES WHERE REQUIRED TO PREVENT OIL SLUGGING AT THE COMPRESSOR AND
INSURE PROPER LUBRICATION. MC SHALL BE RESPONSIBLE FOR SEALING LINE SET
PENETRATIONS OF ANY RATED ASSEMBLIES IN ACCORDANCE WITH A SYSTEM LISTED
IN THE UL DIRECTORY FOR THE SPECIFIC ASSEMBLY BEING PENETRATED. SEE
ARCHITECTURAL PLANS FOR A LIST OF ALL UL FIRE RATED ASSEMBLIES.
13. DUCT LINER MAY BE SUBSTITUTED FOR EXTERIOR DUCT WRAP. DUCT LINER
INSULATION MATERIALS SHALL MEET THE REQUIREMENTS OF ASTM C 1071, AND ASTM
G 21. EXTERIOR DUCT R-VALUE AND INTERIOR R-VALUE SHALL BE IN ACCORDANCE
WITH THE SECC. NOMINAL DUCT SIZES SHALL BE ADJUSTED AS NECESSARY SO THAT
FREE AREA DIMENSIONS ARE PRESERVED AS SHOWN ON THE PLANS. FABRICATION
AND INSTALLATION SHALL CONFORM TO THE MANUFACTURER'S INSTALLATION
RECOMMENDATIONS AND TO THE REQUIREMENTS OF THE LATEST EDITION OF THE
NORTH AMERICAN INSULATION MANUFACTURERS ASSOCIATION FIBROUS GLASS DUCT
LINER STANDARDS AND/OR SMACNA HVAC DUCT CONSTRUCTION STANDARDS. DUCT
LINER SHALL HAVE A BLACK PIGMENTED MAT ON THE AIRSTREAM SIDE TO RESIST
DAMAGE DURING INSTALLATION AND SERVICE. EDGES SHALL BE FACTORY COATED
WITH BLACK PIGMENTED COATING TO COMPLY WITH SMACNA DCS REQUIREMENTS.
ALL PORTIONS OF DUCT DESIGNATED TO RECEIVE DUCT LINER SHALL BE
COMPLETELY COVERED WITH DUCT LINER. TRANSVERSE JOINTS SHALL BE NEATLY
BUTTED AND THERE SHALL BE NO INTERRUPTIONS OR GAPS. THE BLACK PIGMENTED
OR MAT FACED SURFACES SHALL FACE THE AIRSTREAM. DUCT LINER SHALL BE
ADHERED TO THE SHEET METAL WITH 90 PERCENT COVERAGE OF ADHESIVE
COMPLYING WITH REQUIREMENTS OF ASTM C 916. ALL EXPOSED LEADING EDGES AND
TRANSVERSE JOINTS SHALL BE FACTORY COATED OR COATED WITH ADHESIVE
DURING FABRICATION. DUCT LINER SHALL BE ADDITIONALLY SECURED WITH
MECHANICAL FASTENERS, EITHER WELD-SECURED OR IMPACT DRIVEN, WHICH SHALL
COMPRESS THE DUCT LINER SUFFICIENTLY TO HOLD IT FIRMLY IN PLACE. ADHESIVE
BONDED PINS ARE NOT PERMITTED DUE TO LONG-TERM ADHESIVE AGING
CHARACTERISTICS. LININGS SHALL BE INTERRUPTED AT THE AREA OF OPERATION OF
A FIRE DAMPER AND AT A MINIMUM OF 6 INCHES UPSTREAM AND 6 INCHES
DOWNSTREAM OF ELECTRIC RESISTANCE AND FUEL-BURNING HEATERS IN A DUCT
SYSTEM. METAL NOSINGS OR SLEEVES SHALL BE INSTALLED OVER EXPOSED DUCT
LINER THAT FACE OPPOSITE THE DIRECTION OF AIRFLOW. UPON COMPLETION OF
INSTALLATION OF DUCT LINER AND BEFORE OPERATION IS TO COMMENCE, VISUALLY
INSPECT SYSTEM AND VERIFY THAT THE DUCT LINER IS PROPERLY INSTALLED. OPEN
ALL SYSTEM DAMPERS AND TURN ON FANS TO BLOW ALL SCRAPS AND OTHER LOOSE
PIECES OF MATERIAL OUT OF THE DUCT SYSTEM. ALLOW FOR A MEANS OF REMOVAL
OF SUCH MATERIAL.
E
54321
D
C
B
A
SO
LE
X
AR
C H
IT
EC
TU
R
E, IN
C
M
AI
N S
TR
EE
T D
AN
VI
LL
E, V
IR
G
IN
IA
4.
8.
P H
O N
E
4.
1.
F
AX
SHEET NUMBER
CHECKED BY
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SCALE
SHEET INFORMATION
SHEET NAME
NO. DESCRIPTION DATE
MWK
5 Y oun g S
t. S uit e C , H end ers on, NC ww w.k ilia nen gin eer ing
.co m |
(P ) 2
.43
8.8
CO
RP
OR
ATE
LIC
EN
SE
EC
A5
/REW
MECHANICAL
NOTES
2026-0769.0000
08/17/2026
JDD
M-001
N O
R
TH
U N
IO
N
P R
O
PE
R
TI
ES
, L
LC
C O
N
ST
R U
C
TI
O N
D O
C U
M
EN
TS
N O
R
TH
U N
IO
N
S
TR
EE
T
D
AN
VI
LL
E, V
IR
G
IN
IA
R
EN
O
VA
TI
O
N T
O
N
O R
TH
U
N
IO
N S
T.
8/17/26
UP
FE
C
BACKROOM
RETAIL 1 RETAIL 2
AHU-1
AHU-2
A
A
A
A
A
A
R1
R1
A
A
A
A
A
A
"Ø
S
PI
R
AL
"Ø
S
PI
R
AL
"Ø
S
PI
R
AL
"Ø
S
PI
R
AL
"Ø
S
PI
R
AL
"Ø
S
PI
R
AL
HP-1 HP-2
"Ø
S
PI
R
AL
16"Ø
T T
AHU-1 AHU-2
3 4
A
R2 10010
UP
UP
UP
UP
MECHANICAL PLAN HEX NOTES
1. AHU-1 TO BE VERTICALLY MOUNTED IN
CLOSET, MC TO INSTALL WITH
GALVANIZED STEEL DRAIN PAN PER
MANUFACTURER'S INSTRUCTIONS. ROUTE
CONDENSATE TO HUB DRAIN & PROVIDE
CONDENSATE PUMP.
2. AHU-2 TO BE LOCATED IN ATTIC SPACE
ABOVE BATHROOM AREA, INSTALL WITH
GALVANIZED STEEL DRAIN PAN PER
MANUFACTURER'S INSTRUCTIONS.ROUTE
CONDENSATE TO HUB DRAIN & PROVIDE
CONDENSATE PUMP.
3. RETURN GRILLE TO BE MOUNTED AT 18"
A.F.F. ROUTE TO UNIT USING 16"Ø DUCT.
4. RETURN GRILLE TO BE MOUNTED AT 108"
A.F.F. VERIFY MOUNTING HEIGHT ON SITE.
5. RETURN & SUPPLY DUCT TO BE DOUBLE
WALL SPIRAL DUCT, PAINT GRIP METAL
WHILE PASSING THROUGH BACKROOM.
6. DUCT IN RETAIL SPACE TO BE DOUBLE
WALL SPIRAL DUCT, PAINT GRIP METAL.
7. SUPPLY DUCT TO BE RUN OVERHEAD AT
12" BELOW CEILING HEIGHT.
8. DIFFUSER TO BE ANGLED AT 45° FACING
DOWNWARDS.
9. HP-1 & HP-2 TO BE LOCATED ON ROOF,
SHOWN HERE FOR CONVENIENCE.
REFRIGERANT LINE AND POWER FOR
ROOFTOP EQUIPMENT TO BE ROUTED
THROUGH UTILITY CLOSETS ON SECOND
FLOOR. SEAL ALL FLOOR PENETRATIONS
AND FLASH THE ROOF TO MAINTAIN
EXISTING WARRANTY
10. ROUTE AHU-1 & AHU-2 FRESH AIR DUCT
TO EXISTING 10" FRESH AIR DUCT IN
SPACE. MC TO INSTALL BACK DRAFT
DAMPER IN EACH UNITS INDIVIDUAL DUCT
PRIOR TO BRANCH CONNECTION.
E
54321
D
C
B
A
SO
LE
X
AR
C H
IT
EC
TU
R
E, IN
C
M
AI
N S
TR
EE
T D
AN
VI
LL
E, V
IR
G
IN
IA
4.
8.
P H
O N
E
4.
1.
F
AX
SHEET NUMBER
CHECKED BY
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SCALE
SHEET INFORMATION
SHEET NAME
NO. DESCRIPTION DATE
MWK
5 Y oun g S
t. S uit e C , H end ers on, NC ww w.k ilia nen gin eer ing
.co m |
(P ) 2
.43
8.8
CO
RP
OR
ATE
LIC
EN
SE
EC
A5
/REW
MECHANICAL
PLAN
2026-0769.0000
08/17/2026
JDD
M-101
N O
R
TH
U N
IO
N
P R
O
PE
R
TI
ES
, L
LC
C O
N
ST
R U
C
TI
O N
D O
C…