26-048-ITB_-Vault_12_&_S._ARFF_Generator_Upgrades_-Drawings_-_Exhibit_E.pdf
PDF 8 MB Posted
- Attached to
- Vault 12 and South ARFF Generator Upgrades
- Solicitation number
- 26-048-ITB
- Issued by
- Kenton County, Kentucky
About this file
This is a set of technical drawings and exhibit documents for the Vault 12 and South ARFF Generator Upgrades project at Cincinnati/Northern Kentucky International Airport (CVG), a facility operated by the Kenton County Airport Board. The project consists of generator replacements at two locations on the CVG campus—Vault 12 and South ARFF Station—along with HVAC equipment upgrades in the Vault. The drawings include electrical schematics, site utility plans, demolition plans, power plans, panel schedules, and mechanical details prepared in accordance with the 2018 Kentucky Building Code, 2015 International Mechanical Code, 2012 International Energy Conservation Code, and 2023 National Electrical Code NFPA 70. A mandatory pre-proposal meeting and site visit is scheduled for Thursday, October 8, 2026, at 10:00 am at CVG Centre 77 Comair Blvd, Erlanger, KY 41018. Questions must be submitted by 11:59 pm on Thursday, October 15, 2026, with answers posted by Thursday, October 22, 2026. Proposals are due by Thursday, October 29, 2026, at 2:00 pm, with no proposals accepted after that time unless extended by addendum.
The drawings specify comprehensive electrical and mechanical work including demolition of existing generators, ATSs (Automatic Transfer Switches), and fuel tanks; installation of new diesel generators with integral belly tanks and weather-rated enclosures at both locations; installation of new ATSs; new transformers and panelboards; new conduit runs and cabling; concrete pads for generator placement; and associated controls integration with existing systems including the ALMCS (Airport Lighting Management and Control System) and Schneider Electric Power Monitoring and Control System. The Vault 12 location will receive a 625 kVA/500 kW diesel generator, while the South ARFF location will receive a 150 kW diesel generator. All work must comply with seismic restraint requirements, NEC standards, and applicable local, state, and federal regulations. The contractor is responsible for coordinating with utility companies, obtaining necessary permits, providing temporary generator support during phasing, and ensuring one-year warranties on all equipment and materials from substantial completion.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
THIS PROJECT CONSISTS OF GENERATOR REPLACEMENTS FOR 2 LOCATIONS ON THE
CVG CAMPUS. VAULT 12 AND SOUTH ARFF STATION. WITH THE REPLACEMENT OF
THE GENERATORS, THE UPGRADES OF HVAC EQUIPMENT IN THE VAULT WILL ALSO
BE COMPLETED AT THE SAME TIME.
KENTUCKY BUILDING CODE
GENERAL INFORMATION
GOVERNING REGULATIONS
PROJECT DESCRIPTION
BUILDING SCIENCE LEADERSHIP
INTERNATIONAL MECHANICAL CODE
INTERNATIONAL ENERGY CONSERVATION CODE
NATIONAL ELECTRICAL CODE NFPA 70
PROJECT LOCATION
VICINITY MAP: CITY
VICINITY MAP: LOCAL / CAMPUS
1100 SYCAMORE STREET
CINCINNATI, OH 45202
T: (513)429-4404
C
U se rs \M
S te a rn s\ D o cu m e n ts
\O C V G
-0
M
E P R m st e a rn sA S
JS
M .r v t
/9
/2
:0 :1
A
M
G-000
09/11/2026
D. JOHNSON
M. STEARNS
C V G
V A U
L T
A
N D
S O
U T H
A R F F G
E N
E R A T O
R U
P G
R A D
E S
C
IN
C
IN
N A T I
N
O R T H
E R N
K E N
T U
C K Y I
N T E R N
A T
IO
N A L A
IR
P O
R T
N
E W
P R
IC
E P
IK
E A
N D
T
O W
E R D
R
IV
E
E R L A N
G E R K Y
C O
V E R S
H E E T
OCVG25-05
CVG VAULT 12 AND SOUTH ARFF
GENERATOR UPGRADES
CINCINNATI / NORTHERN KENTUCKY INTERNATIONAL AIRPORT
171 NEW PRICE PIKE AND 2100 TOWER DRIVE
ERLANGER, KY 41018
BID AND PERMIT
09/11/2026
BID AND PERMIT
DRAWING INDEX
GENERAL
G-000 COVER SHEET
G-V-100 VAULT 12 ELEVATIONS
ELECTRICAL - GENERAL
E-000 ELECTRICAL LEGEND
E-001 OVERALL ELECTRICAL SITE PLAN
E-500 ELECTRICAL DETAILS
ELECTRICAL - SOUTH ARFF
E-A-001 SOUTH ARFF ELECTRICAL SITE UTILITY PLAN
E-A-100 SOUTH ARFF DEMOLITION PLAN
E-A-200 SOUTH ARFF POWER PLAN
E-A-600 SOUTH ARFF ELECTRICAL SINGLE LINE
E-A-601 SOUTH ARFF ELECTRICAL PANEL SCHEDULES
ELECTRICAL - VAULT 12
E-V-001 VAULT 12 ELECTRICAL SITE UTILITY PLAN
E-V-100 VAULT 12 DEMOLITION PLAN
E-V-200 VAULT 12 POWER AND CONDUIT PLAN
E-V-600 VAULT 12 ELECTRICAL SINGLE LINE
E-V-601 VAULT 12 ELECTRICAL PANEL SCHEDULES
MECHANICAL - VAULT 12
M-V-000 MECHANICAL LEGEND
M-V-100 VAULT 12 MECHANICAL PLANS
M-V-200 VAULT 12 MECHANICAL SCHEDULES, DETAILS & CONTROLS
REVISIONS
3' - 0"
4' - 2"
3' - 4" 3' - 4"
4' - 2"
3' - 4"
3' - 4" 3' - 6"
4' - 6"
3' - 6"
3' - 0"
3' - 4"
3' - 0" 3' - 4"
3' - 4"
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
1100 SYCAMORE STREET
CINCINNATI, OH 45202
T: (513)429-4404
C
U se rs \M
S te a rn s\ D o cu m e n ts
\O C V G
-0
M
E P R m st e a rn sA S
JS
M .r v t
/9
/2
:0 :1
A
M
G-V-100
09/11/2026
D. JOHNSON
M. STEARNS
C V G
V A U
L T
A
N D
S O
U T H
A R F F G
E N
E R A T O
R U
P G
R A D
E S
C
IN
C
IN
N A T I
N
O R T H
E R N
K E N
T U
C K Y I
N T E R N
A T
IO
N A L A
IR
P O
R T
N
E W
P R
IC
E P
IK
E A
N D
T
O W
E R D
R
IV
E
E R L A N
G E R K Y
V A U
L T
E
L E V A T
IO
N S
OCVG25-05
BID AND PERMIT
1/4" = 1'-0"G-V-100
EAST TO WEST ELEVATION - REGULATOR ROOM #25
1/4" = 1'-0"G-V-100
NORTH TO SOUTH ELEVATION - VAULT 121
1/4" = 1'-0"G-V-100
EAST TO WEST ELEVATION - VAULT 123
1/4" = 1'-0"G-V-100
SOUTH TO NORTH ELEVATION - VAULT 122
1/4" = 1'-0"G-V-100
WEST TO EAST ELEVATION - ATS ROOM (OLD GENERATOR ROOM)4
OPENINGS LESS THAN 24" IN HEIGHT:
INFILL EXISTING OPENING WITH CMU TO MATCH EXISTING WYTHE (8" +/- FIELD VERIFY) AND BRICK VENEER TO MATCH EXISTING. BRICK INFILL TO
BE FLUSH WITH EXISTING.
OPENINGS 32" OR GREATER IN HEIGHT:
INFILL EXISTING OPENING WITH CMU TO MATCH EXISTING WYTHE (8" +/- FIELD VERIFY) AND BRICK VENEER TO MATCH EXISTING. BRICK INFILL TO BE FLUSH WITH EXISTING. PROVIDE MASONRY TIES AT 16" O.C. VERTICALLY TYING NEW CMU TO EXISTING AT JAMBS. PROVIDE BRICK TIES AT 16"
O.C. HORIZONTALLY AND VERTICALLY.
OPENINGS MARKED WITH X:
OPENINGS MARKED WITH AN “X” ARE EXISTING TO REMAIN. DO NOT DEMOLISH OR REMOVE ANY EQUIPMENT WITHIN THESE OPENINGS. REFER
TO MECHANICAL AND ELECTRICAL DRAWINGS.
CONTRACTOR TO MAKE MEASUREMENTS PRIOR TO PRICING AND ORDERING OF MATERIALS, THESE DIMENSIONS ARE ALL ESTIMATIONS.
CONTRACTOR TO TRY AND REUSE EXISTING MATERIAL FROM NEW PENETRATIONS/OPENINGS TO INFILL OLD PENETRATIONS/OPENINGS.
MASONRY WALL PATCH NOTES
SD
UON
EM
CFOI
OFOI
CFCI
OFCI
J
DESCRIPTION
S
OS
GROUND FAULT PROTECTED DUPLEX WITH
WEATHER-PROOF "WHILE IN USE" TYPE DIE-CAST
METAL COVERPLATE WITH LOCKABLE
ENCLOSURE AT OUTLET - SEE SPECIFICATIONS
WP
DOOR RELEASE PUSH-PLATE / INFRA-RED OPERATOR
STATION. PROVIDE ANY ADDITIONAL ROUGH-IN FOR
''EMERGENCY RELEASE'' OPERATOR STATIONS AS
REQUIRED.
DOOR RELEASE CARD READER STATION. PROVIDE
ANY ADDITIONAL ROUGH-IN FOR ''EMERGENCY
RELEASE'' OPERATOR STATIONS AS REQUIRED.
SLASH THROUGH ANY DEVICE INDICATES MOUNTING
ABOVE COUNTERTOP 2" ABOVE BACKSPLASH, OR AT
48" WHERE NO COUNTER IS PRESENT
VS
FILLED CENTER BAR INDICATES INTEGRAL GROUND
FAULT PROTECTION (GFCI)
NON-REVERSING MOTOR STARTER SNAP SWITCH
CONTRACTOR FURNISHED OWNER INSTALLED
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
OWNER FURNISHED OWNER INSTALLED
OWNER FURNISHED CONTRACTOR INSTALLED
PHOTO-ELECTRIC SMOKE DETECTOR
MAIN CONTROL PANEL CENTRAL PROCESSING
UNIT (CPU)
DOOR POWER SUPPLY
LIGHT SWITCH:GENERAL PURPOSE
AS NOTED
6'-6'' TO
TOP
46" TO
LEVER
PULL STATION : DOUBLE ACTION
AUDIO/VISUAL NOTIFICATION APPLIANCE
HEAT DETECTOR
DUCT SMOKE DETECTOR
UNLESS OTHERWISE NOTED
INDICATES EMERGENCY POWER
HD
ABV CLG DD
ABBREVIATIONS
STRIP FIXTURE
PARALLEL-HATCHING INDICATES LIGHT IS
POWERED FROM THE EMERGENCY-LIFE SAFETY
BRANCH
POWER OUTLETS
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE
JUNCTION BOX, CEILING OR WALL
VOLTAGE/1PH RECEPTACLE, AS NOTED
VOLTAGE/3PH RECEPTACLE, AS NOTED
OCCUPANCY OR VACANCY SENSOR, CEILING MOUNT
EXIT LIGHT (CEILING, END, WALL MOUNT)
LIGHTING
SECURITY ACCESS CONTROL
DOOR RELEASE KEYPAD STATION
MOTION SENSOR DOOR CONTROL
WALL, CLG
CLG
CLG
46"
1'-6"
1'-6"
1'-6"
1'-6"
1'-6"
2'-2"
CLG
AS NOTED
46''
46''
46''
CEIL.
S M
M O
U N
T
IN
G H
E
IG
H T
(T O
C E
N T
E R
O F
B O
X
D R
A W
IN
G
S
Y M
B O
L
WALL MOUNT FIXTURE ,
F
F
ADDRESSABLE RELAY MODULE R
ABV CLG
ELECTRIC STRIKE AT LATCH
WP
WGWIREGUARD - PROVIDE MANUFACTURER'S
SPECIFIC GUARD FOR DEVICE NOTED
CONDUIT CONCEALED IN WALLS OR IN CEILING
SPACE: ARROW(S) INDICATE(S) HOME RUN & #
OF CIRCUITS: HASHMARKS INDICATE # OF
CONDUCTORS. DASHED LINE INDICATES
CONDUIT BELOW FLOOR.
PANELBOARD, SURFACE OR FLUSH MOUNTED,
HATCHING INDICATES EMERGENCY
EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE
MECHANICAL EQUIPMENT DESIGNATOR
(SEE MECH. SCHEDULES)
EQUIPMENT HARDWIRE CONNECTION (SEE DETAIL)
AS NOTED
AS SHOWN
MISCELLANEOUS
DISCONNECT SWITCH
MAGNETIC STARTER
MAGNETIC COMBINATION STARTER
ENCLOSED FLUSH MTD. CIRCUIT BREAKER
WEATHERPROOF - NEMA-3R, WET LOCATION LISTED.
PROVIDE COVERS, RATINGS, ETC, AS SUITABLE FOR
OUTDOORS.
PUSHBUTTON STATION
FLEXIBLE CONDUIT
TRANSFORMER
TAGGED NOTE
REVISION TAG
WIRE BASKET CABLE TRAY, SIZE AS NOTED
LOW VOLTAGE CABLE PATH
5'-0"
5'-0"
5'-0"
5'-0"
46"
6'-6'' TO TOP
GENERATOR ANNUNCIATOR PANEL - SEE
SPECIFICATIONS
46''
THERMOSTAT PROVIDED BY MECHANICAL
CONTRACTOR, ELECTRICAL CONTRACTOR SHALL
PROVIDE BACK-BOX CONDUIT STUB-UP, REFER TO
MECHANICAL DRAWINGS FOR LOCATIONS
SWITCHES
FIRE ALARM
E,EMINDICATES EMERGENCY POWER
PUSH-TO-EXIT BUTTON 46'' PE
GEN-A
J
ES
KP
MS
PP
CR
DS
FACP
T
AS SHOWNLADDER CABLE TRAY, SIZE AS NOTED
AS SHOWNSOLID BOTTOM CABLE TRAY, SIZE AS NOTED
EQUIP-1
GROUND
NEUTRAL
PHASE
F
, J
VARIABLE FREQUENCY DRIVE 5'-0"
MOTOR CONNECTION, REFER TO EQUIPMENT
CONNECTION SCHEDULE
CONDUIT UP
CONDUIT DOWN
GROUND BUS BAR ON INSULATED STANDOFFS 2'-0''
DESCRIPTION M
O
U N
T
IN
G H
E
IG
H T
(T O
C E
N T
E R
O F
B O
X
D R
A W
IN
G
S
Y M
B O
L
REFER TO LUMINAIRE SCHEDULE FOR EXACT FIXTURE
SPECIFICATIONS, MOUNTING HEIGHTS, ETC.
W H
IT
E
DEVICE
DEVICE COLOR
MATRIX
RECEPTACLE (NORMAL)
THERMOSTATS (COORDINATE WITH HVAC TYPICALLY NO
COLOR OPTIONS)
DEVICE COLOR GENERAL NOTES:
A. DEVICE PLATE TO MATCH DEVICE UNLESS NOTED OTHERWISE.
B. NOT ALL DEVICES MAYBE USED THAT ARE SHOWN.
C. IF DEVICE COLOR NOT DEFINED REFER TO SPECIFICATIONS.
DESCRIPTION
IV
O
R Y
R E
D
B L
A C
K
B L
U E
Y E
L L O
W
C U
S T
O M
S T
A
IN
L E
S S
S T
E E
L
LEGEND
INDICATES SELECTED COLOR
INDICATES COLOR NOT AVAILABLE
INDICATES COLOR NOT SELECTED
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
1100 SYCAMORE STREET
CINCINNATI, OH 45202
T: (513)429-4404
C
U se rs \M
S te a rn s\ D o cu m e n ts
\O C V G
-0
M
E P R m st e a rn sA S
JS
M .r v t
/9
/2
:0 :1
A
M
E-000
09/11/2026
D. JOHNSON
M. STEARNS
C V G
V A U
L T
A
N D
S O
U T H
A R F F G
E N
E R A T O
R U
P G
R A D
E S
C
IN
C
IN
N A T I
N
O R T H
E R N
K E N
T U
C K Y I
N T E R N
A T
IO
N A L A
IR
P O
R T
N
E W
P R
IC
E P
IK
E A
N D
T
O W
E R D
R
IV
E
E R L A N
G E R K Y
E L E C T R
IC
A L L
E G
E N
D
OCVG25-05
BID AND PERMIT
ELECTRICAL GENERAL NOTES:
A. EACH CONTRACTOR, PROPOSER, SUPPLIER AND/OR MANUFACTURER SHALL REFER TO ALL DOCUMENTS PERTAINING TO THIS PROJECT AND
COORDINATE ACCORDINGLY SO AS TO ENSURE ADEQUACY OF FIT, COMPLIANCE WITH SPECIFICATIONS, PROPER VOLTAGE AND CURRENT CHARACTERISTICS TO AVOID CONFLICT WITH ANY OTHER BUILDINGS SYSTEMS. VERIFY SAME WITH SHOP DRAWINGS.
B. ADDITIONAL ELECTRICAL REQUIREMENTS MAY BE SHOWN ON PLANS FROM OTHER DISCIPLINES IN THIS SET. IT IS THE CONTRACTOR’S RESPONSIBILITY TO REVIEW ALL PLANS AND SPECIFICATIONS FOR A COMPLETE UNDERSTANDING OF THE PROJECT REQUIREMENTS.
C. WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF ALL LOCAL, STATE, AND NATIONAL CODES. INCLUDING BUT NOT LIMITED TO NFPA 70
(NEC), NFPA 72, INTERNATIONAL BUILDING CODES, ETC.
D. CONTRACTOR SHALL FOLLOW SEISMIC RESTRAINT AND DESIGN REQUIREMENTS CONTAINED IN LATEST ADOPTED STATE AND INTERNATIONAL BUILDING CODES, WITH ALL AMENDMENTS AS ADOPTED BY THE CURRENT LEGISLATION. REFER TO ELECTRICAL AND STRUCTURAL SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
E. ALL OFFSETS, TURNS, FITTINGS, TRIM, DETAIL, ETC. MAY NOT BE INDICATED, BUT SHALL BE PROVIDED AS REQUIRED. ADDITIONAL ALLOWANCES SHALL
BE INCLUDED FOR SAME AT EACH PROPOSER’S DISCRETION.
F. INSTALL NO PIPING, CONDUIT, DUCTWORK, ETC. IN A LOCATION OR IN A MANNER WHICH WILL ALLOW FREEZING OR THE COLLECTION OF
CONDENSATION THEREON. IF IN DOUBT, CONTACT THE ENGINEER.
G. ADVISE THE ENGINEER OF ANY CONFLICTS, ERRORS, OMISSIONS, ETC. AT LEAST TEN DAYS PRIOR TO BID DATE, TO ALLOW CLARIFICATION BY WRITTEN
ADDENDUM.
H. WHERE CONFLICTS ARE FOUND BETWEEN DRAWINGS, DETAILS, OR SPECIFICATIONS, THE MORE STRINGENT REQUIREMENT SHALL APPLY. NOTIFY
ARCHITECT OF DISCREPANCY IN WRITING.
I. DEVIATION FROM SPECIFICATIONS OR PLANS REQUIRES PRIOR WRITTEN APPROVAL FROM THE ENGINEERS AND MUST BE SUBMITTED IN WRITING NO
LATER THAN TEN DAYS PRIOR TO THE BID DATE.
J. OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS THAT MAY APPLY TO THE WORK UNDER THIS CONTRACT. (CITY, COUNTY, LOCAL, STATE, FEDERAL, MUNICIPALITY, UTILITY COMPANY, OSHA, ETC.).
K. MOUNTING HEIGHTS FOR WALL MOUNTED DEVICES INDICATED ABOVE FINISHED FLOOR ARE TO CENTER OF DEVICE UNO. MOUNTING HEIGHTS TO
CEILING SUSPENDED DEVICES ARE TO BOTTOM OF DEVICE UNO.
L. INSTALL EQUIPMENT, MATERIALS, ETC. IN STRICT ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS AND DIRECTIONS. IF IN CONFLICT WITH THE DESIGN INDICATED IN CONTRACT DOCUMENTS, ADVISE THE ENGINEER PRIOR TO INSTALLATION FOR CLARIFICATION.
M. DO NOT RECESS PANELBOARD TUBS OR OTHER FLUSH-MOUNTED EQUIPMENT IN WALLS THAT HAVE A FIRE RATING. NO INSTALLATION SHALL DIMINISH
OR VOID FIRE RESISTIVE RATINGS IN ANYWAY.
N. THE PURPOSE AND INTENT OF ALL OF THE DOCUMENTS PERTAINING TO THIS PROJECT IS TO PROVIDE A COMPLETE, FUNCTIONAL, SAFE, LIKE-NEW
FACILITY. ANYTHING LESS SHALL BE UNACCEPTABLE.
O. ALL SYSTEMS, EQUIPMENT AND MATERIALS ARE TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. WORK NOT MEETING THIS CRITERION SHALL BE REMOVED AND REINSTALLED SATISFACTORILY. FINAL DETERMINATION OF THE ACCEPTABILITY OF THE QUALITY OF WORK RESIDES WITH THE
ENGINEER
P. ALL WORK, MATERIALS, EQUIPMENT, ETC. SHALL BE FULLY GUARANTEED FOR ONE FULL CALENDAR YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION AS DOCUMENTED BY THE ENGINEER, UNLESS LONGER WARRANTY PERIODS FOR EQUIPMENT ARE SPECIFIED.
Q. UNLESS OTHERWISE SPECIFIED OR INDICATED, ALL EQUIPMENT AND/OR MATERIALS WITHIN OCCUPIED SPACES OR EXPOSED TO VIEW ON THE BUILDING EXTERIOR SHALL BE PRIMED AND FINISHED SO AS TO COMPLEMENT ADJACENT SURFACE, UNLESS OTHERWISE NOTED. COORDINATE WORK
AND COLORS WITH ARCHITECT.
R. WHERE PENETRATING ROOFING MEMBRANE OR OTHER MATERIALS USED FOR WEATHERPROOFING THE BUILDING, MAKE SUCH PENETRATION IN A WAY THAT WILL NOT VOID OR DIMINISH THE ROOFING WARRANTY OR INTEGRITY IN ANYWAY. COORDINATE ALL SUCH PENETRATIONS WITH THE ROOFING
MANUFACTURER AND ARCHITECT.
S. THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY COMPANY FEES, CASH CONTRIBUTIONS OR OTHER COSTS THAT THE UTILITY COMPANY MAY
REQUIRE TO COMPLETE THEIR WORK. (ELECTRIC, TELEPHONE, TELEVISION, DATA, ETC.).
T. COORDINATE WITH ARCHITECTURAL FLOOR PLANS, ELEVATIONS AND CASEWORK DETAILS FOR LOCATION OF ADDITIONAL RECEPTACLES, UTILITY
OUTLETS, ELECTRICAL DEVICES, ETC.
U. CEILING-MOUNTED ELECTRICAL DEVICES SHALL BE CENTERED IN 2'X2' CEILING TILE AND INSTALLED CENTERED ON 2' DIMENSION OF 2'X4' TILE AND ON
CENTERLINE OR A QUARTER POINT ON 4' DIMENSION.
V. ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION PRODUCING EQUIPMENT SHALL BE ISOLATED FROM SURROUNDING SYSTEMS IN AN APPROVED MANNER. NOISY OR STRUCTURALLY DAMAGING INSTALLATIONS SHALL BE SATISFACTORILY REPLACED OR REPAIRED AT THE INSTALLING CONTRACTORS' EXPENSE. THE FINAL DECISION ON THE SUITABILITY OF A PARTICULAR INSTALLATION'S ACCEPTABILITY SHALL BE THAT OF THE
ENGINEER.
W. CHECK ALL THREE PHASE MOTORS WITH A PHASE ROTATION METER, PRIOR TO PLACING IN SERVICE.
X. PROVIDE DETAILED SHOP DRAWINGS TO ENGINEER PRIOR TO PURCHASING OR INSTALLING ANY EQUIPMENT Y. DEVIATIONS IN SIZES, CAPACITIES, FIT, FINISH, ETC. FOR EQUIPMENT FROM THAT PRIME SPECIFIED SHALL BE THE RESPONSIBILITY OF THE PURCHASER
OF THAT EQUIPMENT. ANY PROVISIONS REQUIRED TO ACCOMMODATE A DEVIATION, WHETHER APPROVED BY THE ENGINEER OR NOT, SHALL BE THE
RESPONSIBILITY OF THE PURCHASER.
Z. THE CONSTRUCTION MANAGER, GENERAL CONTRACTOR, OR WHOMEVER HOLDS THE PRIME CONTRACT(S) FOR THIS CONSTRUCTION IS RESPONSIBLE FOR THE COORDINATION, APPEARANCE, SCHEDULING AND TIMELINESS OF THE WORK OF ALL TRADES, CONTRACTORS, SUPPLIERS, INSTALLERS, ETC.
POOR OR UNTIMELY WORK ON THE PART OF ANY SUBCONTRACTOR SHALL BE RESOLVED BY THE PARTY WHO ENGAGED THEM ON THIS PROJECT.
AA. WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN CONFLICT WITH ANY OTHER BUILDING SYSTEM, CONTACT THE ENGINEER BEFORE AFFECTING INSTALLATION. REFER ALSO TO ARCHITECTURAL INTERIOR AND EXTERIOR ELEVATIONS, CEILING HEIGHTS AND OTHER DETAILS OF THESE
DOCUMENTS, AS APPLICABLE.
BB. WHERE FIRE-RATED CEILING ASSEMBLIES ARE NOTED, PROVIDE UL-LISTED FIRE-RATED GYPSUM BOARD OR PRE-MANUFACTURED ENCLOSURES ABOVE LUMINAIRES, CEILING DEVICES, ETC. IN OR ON CEILING, AS REQUIRED TO MAINTAIN CEILING RATINGS.
CC. COORDINATE THE LOCATION OF DRAINS, ELECTRICAL OUTLETS, GAS OUTLETS, ETC. WITH ALL CASEWORK, KITCHEN EQUIPMENT, MECHANICAL ROOM EQUIPMENT, ETC. PRIOR TO COMMENCING INSTALLATION. WORK NOT SO COORDINATED SHALL BE REMOVED AND PROPERLY INSTALLED AT THE
EXPENSE OF THE RESPONSIBLE CONTRACTOR(S).
DD. ALL ELECTRICAL COMPONENTS OR EQUIPMENT SHALL BE LISTED AND LABELED BY UNDERWRITER'S LABORATORIES OR OTHER APPROVED LISTING AGENCY. APPROVAL AND LABELING OF INDIVIDUAL COMPONENTS ON AN ASSEMBLY IS NOT ACCEPTABLE AS MEETING THIS REQUIREMENT, UNLESS
WAIVED BY THE ENGINEER IN WRITING.
EE. ALL WIRING SYSTEMS SHALL BE INSTALLED WITH A MINIMUM OF SPLICES. CONDUCTORS, WHETHER SINGLE OR MULTI-PAIR, SHALL BE INSTALLED
CONTINUOUS INSOFAR AS POSSIBLE FROM TERMINAL POINT TO TERMINAL POINT.
FF. NO CONDUIT, SUPPORTS, ETC. SHALL BE RUN THROUGH ACCESS CLEARANCES OF EQUIPMENT BY OTHER TRADES (I.E. VAV BOXES). COORDINATE WITH
ALL TRADES PRIOR TO CONSTRUCTION.
GG. ALL CONTRACTORS SHALL EXERCISE EXTREME CARE IN THE COURSE OF THEIR WORK SO AS TO ENSURE THAT THEY DO NOT INTERRUPT ANY EXISTING SERVICE OR SUB-SERVICE FOR SAFETY PURPOSES. PAY PARTICULAR ATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL GAS AND ELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC. OF EACH UNDERGROUND OR OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL FEDERAL, STATE AND/OR LOCAL RULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS. UTILITIES SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THE MOST STRINGENT
REQUIREMENT SHALL APPLY.
HH. ALL SUPPORTS FOR EQUIPMENT, DEVICES OR FIXTURES SHALL BE UNIQUE, DIRECTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT WORK FROM OTHER TRADES EQUIPMENT OR SUPPORTS WITHOUT WRITTEN PERMISSION FROM THE ENGINEER AND CONSENT OF THE OTHER TRADE, IN
WRITING.
II. WHERE INTERRUPTING AN EXISTING UTILITY OR SERVICE DELIBERATELY OR ACCIDENTALLY, THE RESPONSIBLE CONTRACTOR SHALL WORK
CONTINUOUSLY AS NEEDED TO RESTORE SAME, PROVIDING PREMIUM TIME AS NEEDED.
JJ. REFER TO ARCHITECTURAL WALL ELEVATIONS (WHERE GIVEN) FOR HEIGHTS AND MOUNTING RELATIONSHIP OF OUTLETS AND EQUIPMENT. IF IN
DOUBT, CONTACT ENGINEER FOR DIRECTION PRIOR TO ROUGH IN.
KK. FLUSH OR PEDESTAL TYPE FLOOR OUTLETS/BOXES, AS INDICATED ON PLAN, SHALL BE LOCATED BY DIMENSIONS PROVIDED BY THE ARCHITECT, UNLESS OTHERWISE SHOWN ON PLANS. IF IN DOUBT, CONTACT THE ENGINEER PRIOR TO ROUGHING-IN ANY WORK.
LL. AS APPLICABLE, REFER TO ARCHITECTURAL PHASING PLANS AND PHASING BOUNDARIES ON THESE DRAWINGS FOR SEQUENCING OF WORK, FULL EXTENT OF AREAS INVOLVED, EXTENT OF CEILING WORK, ETC. PROVIDE TEMPORARY CONNECTIONS FOR CIRCUITS AND WORK AS REQUIRED TO
MAINTAIN SEQUENCE OF THE WORK FROM PHASE TO PHASE.
MM. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR HIS WORK. ALL CUTTING AND PATCHING SHALL BE IN
ACCORDANCE WITH THE ARCHITECT'S STANDARDS FOR SUCH WORK.
NN. ALL WORK SHALL BE CONCEALED UNLESS SPECIFICALLY INDICATED TO BE EXPOSED, OR REQUIRED TO BE EXPOSED. IF IN DOUBT, CONTACT THE
ENGINEER FOR CLARIFICATIONS PRIOR TO INSTALLING ANY SUCH WORK.
OO. INTERRUPTION OF ANY EXISTING SERVICES SHALL BE COORDINATED WITH THE OWNER, GENERAL CONTRACTOR, UTILITY COMPANY AS NECESSARY, AND THE ARCHITECT, AT LEAST TWO WEEKS IN ADVANCE OF ANTICIPATED INTERRUPTION. A SCHEDULE FOR THESE OUTAGES SHALL BE DEVELOPED AND AGREED UPON BETWEEN THE PARTIES MENTIONED TO AVOID UNNECESSARY INCONVENIENCE TO THE OWNER OR ANY AFFECTED PARTY. NOTIFY THE UTILITY COMPANY OF ANY ANTICIPATED SERVICES REQUIRED TWO WEEKS IN ADVANCE, IN WRITING. IF UTILITY COMPANY REQUIRES A LONGER
NOTIFICATION PERIOD, SO PROVIDE.
PP. WHERE BACKBOXES ARE LOCATED IN THE SAME VERTICAL CHANNEL/STUD SPACE ON OPPOSITE SIDES OF THE SAME WALL, PROVIDE SOUND- INSULATING PUTTY AROUND BOXES AS REQUIRED TO ELIMINATE SOUND TRANSMISSION FROM ROOM TO ROOM.
QQ. JUNCTION BOXES LOCATED ABOVE ACCESSIBLE CEILINGS SHALL BE LOCATED NO MORE THAN 36” ABOVE CEILING LEVEL. LABEL EACH BOX IN AREA OF WORK WITH A PERMANENT MARKER OR IN ACCORDANCE WITH SPECIFICATIONS, WHICHEVER IS MORE STRINGENT.
RR. ALL MATERIALS FURNISHED AND ALL WORK INSTALLED SHALL COMPLY WITH THE CURRENT EDITION OF THE NATIONAL ELECTRICAL CODES, NATIONAL FIRE CODES OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE REQUIREMENTS OF LOCAL UTILITY COMPANIES, AND WITH THE REQUIREMENTS OF ALL GOVERNMENTAL AGENCIES OR DEPARTMENTS HAVING JURISDICTION. IF ANY CONFLICTS OR DISCREPANCIES OCCUR THE MOST STRINGENT SHALL
APPLY.
SS. DO NOT SCALE FROM DRAWINGS, AS PRINTING DISTORTS SCALE. WORK SHALL BE LAID OUT FROM DIMENSIONED DRAWINGS, OR DIMENSIONS
SUPPLIED TO THE CONTRACTOR.
TT. NOISY WORK, WORK OUTSIDE CONSTRUCTION BARRIERS, WORK IN OCCUPIED AREAS, ETC. SHALL BE PERFORMED AFTER HOURS OR ON WEEKENDS.
COORDINATE EXACT SCHEDULING WITH FACILITY PRIOR TO CONSTRUCTION.
UU. ALL ITEMS HAVING KEYED LOCKS/OPERATORS SHALL HAVE CORED LOCKS/OPERATORS. ALL KEYING SHALL MATCH THE OWNER'S EXISTING KEY-WAYS.
COORDINATE EXACT REQUIREMENTS WITH OWNER PRIOR TO CONSTRUCTION.
VV. REFER TO ARCHITECTURAL PLANS FOR PHASING REQUIREMENTS. WORK SHALL BE COMPLETED IN PHASES PER THE PHASING PLAN AND AS COORDINATED WITH OWNER AND GENERAL CONTRACTOR. PROVIDE ALL REQUIRED INCREMENTAL INSPECTIONS, CERTIFICATIONS, ETC. AND ALL
TEMPORARY SERVICES AS REQUIRED BY OWNER TO ACCOMPLISH THE PHASING PLAN.
ELECTRICAL DEMOLITION NOTES:
A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINES INDICATE EXISTING ITEMS TO
REMAIN.
B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR
EQUIPMENT THAT ARE TO REMAIN. WHEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAWINGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM" ON THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" WORKING ORDER. "LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR
PANELS. PROVIDE NEW TYPEWRITTEN DIRECTORIES FOR ALL PANELS AFFECTED.
C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING CONDITIONS.
CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT
THEY MAY COMPLETE ALL WORK REQUIRED FOR THE BID WHICH HE PROPOSES.
D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE), WHETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND REPAIR ANY EXISTING WALLS, FLOORS OR CEILINGS WHERE DEVICES ARE SHOWN TO BE REMOVED (PATCH AND
REPAIR TO RECEIVE NEW FINISHES - SEE ARCHITECTURAL PLANS).
E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION) WITH OWNER. TURN
OVER ITEMS REMOVED TO OWNER AT THEIR OPTION.
F. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/OR RELOCATION OF ELECTRICAL DEVICES AND
CONNECTIONS ASSOCIATED WITH THEIR EQUIPMENT.
G. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION BARRIERS AS REQUIRED.
H. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS / CEILINGS AS REQUIRED WHERE DEVICES ARE
BEING REMOVED OR INSTALLED.
I. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE CEILINGS SHALL BE REMOVED IN
ACCORDANCE WITH NEC REQUIREMENTS.
J. EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH CONSTRUCTION SHALL BE RELOCATED TO PERMIT
INSTALLATION OF DEVICES AND EQUIPMENT SHOWN ON PLANS.
K. CONTRACTOR SHALL SEAL ALL EXISTING AND NEW PENETRATIONS OF BUILDING ENVELOPE (EXTERIOR WALLS, ROOF, ETC.) WATER-TIGHT AND AS APPROVED BY ARCHITECT AND ENGINEER. ROOFING SHALL BE RESTORED BY A LICENSED ROOFING CONTRACTOR BASED ON WRITTEN INSTRUCTIONS AND DETAILS FROM ROOFING MANUFACTURER AS REQUIRED TO MAINTAIN ROOF WARRANTY. REFER TO ARCHITECTURAL AND ENGINEERING
PLANS AND SPECIFICATIONS FOR FURTHER REQUIREMENTS.
L. DEVICES INDICATED WITH AN ''R'' SHALL BE RELOCATED. REMOVE, PROTECT, AND REINSTALL IN NEW LOCATION INDICATED ON NEW WORK PLANS. INTERCEPT AND EXTEND ALL EXISTING CABLING TO NEW
LOCATION. CLEAN AND RE-LAMP RELOCATED LUMINAIRES.
M. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S WORK SHALL BE PROVIDED WITH NEW TYPE- WRITTEN PANEL DIRECTORIES AND INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES OR NUMBERS FROM THESE DRAWINGS. DIRECTORIES SHALL BE DETAILED AND COORDINATED WITH OWNER'S SUITE NUMBERS, FINAL ROOM NUMBERS, IT RACK NAMES, WORKSTATION DESIGNATIONS, ETC. UNUSED
BREAKERS SHALL BE IN OFF POSITION.
GENERAL NOTES (POWER):
A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS, AND CASEWORK DETAILS FOR EXACT
LOCATIONS OF ALL WALL AND CEILING MOUNTED ELECTRICAL DEVICES.
B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATED ON THE FLOOR PLANS, WITH A
MAXIMUM OF THREE (3) BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE PROVIDED WITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME CONDUIT WITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIWIRE BRANCH CIRCUITS AS DEFINED IN NEC 100 /
210.4 (CIRCUITS SHARING A COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.
C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES, SWITCHES, ETC. IN AREA OF
CONSTRUCTION. PROVIDE CLEAR ADHESIVE LABELS WITH BLACK LETTERING.
D. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS SHALL BE COORDINATED WITH MECHANICAL AND PLUMBING CONTRACTORS TO ENSURE ACCESS AND WORKING CLEARANCE IS MAINTAINED PER NEC. NOTIFY OTHER TRADES OF REQUIRED CLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS IN THESE AREAS. DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENT NAMEPLATES OR ACCESS PANELS
OR THROUGH ACCESS/MAINTENANCE CLEARANCES OF EQUIPMENT BY OTHER TRADES.
ACCESS CONTROL
ADD TRANSLUCENT FILM
PROJECT SCOPE
VAULT 12, DENOTED BY "-V"
IN THE SHEET SERIES NAMING
SOUTH ARFF, DENOTED BY "-A"
IN THE SHEET SERIES NAMING
THE CONTRACTOR AND ALL SUBCONTRACTORS SHALL
CONTACT ''KENTUCKY811" (BEFORE YOU DIG)'' AT
1-800-362-2764 OR 811 TO OBTAIN UNDERGROUND UTILITY
LOCATIONS PRIOR TO ANY CONSTRUCTION. ANY
CONTRACTOR OR SUBCONTRACTOR PERFORMING ANY
TYPE OF EXCAVATION ON THIS PROJECT TO OBTAIN AN
AUTHORIZATION NUMBER.
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
1100 SYCAMORE STREET
CINCINNATI, OH 45202
T: (513)429-4404
C
U se rs \M
S te a rn s\ D o cu m e n ts
\O C V G
-0
M
E P R m st e a rn sA S
JS
M .r v t
/9
/2
:0 :2
A
M
E-001
09/11/2026
D. JOHNSON
M. STEARNS
C V G
V A U
L T
A
N D
S O
U T H
A R F F G
E N
E R A T O
R U
P G
R A D
E S
C
IN
C
IN
N A T I
N
O R T H
E R N
K E N
T U
C K Y I
N T E R N
A T
IO
N A L A
IR
P O
R T
N
E W
P R
IC
E P
IK
E A
N D
T
O W
E R D
R
IV
E
E R L A N
G E R K Y
O V E R A L L E
L E C T R
IC
A L S
IT
E P
L A N
OCVG25-05
BID AND PERMIT
1" = 40'-0"E-001
EXISTING SITE PLAN1
GENERAL NOTES:
A. NORMAL POWER LABELS SHALL BE BLACK WITH WHITE LETTERS.
B. EMERGENCY POWER LABELS SHALL BE RED WITH WHITE LETTERS. LABEL SHOULD ALSO INCLUDE
THE WORD "EMERGENCY" IN 1/4" LETTERS.
C. EMERGENCY POWER LABELS IN HEALTHCARE APPLICATIONS SHOULD INCLUDE SYSTEM SEVERED
"LIFE SAFETY", "CRITICAL" OR "EQUIPMENT" .
D. UTILIZE SCREW-ON TYPE LAMACOID PLATES.
E. THIS DETAILS APPLIES TO ALL ELECTRICAL EQUIPMENT INCLUDING PANELS, SWITCHGEAR, DISCONNECTS, TRANSFORMERS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES (VDF'S), SPECIAL DEVICE PLATES, INVERTER, AND SIMILAR MATERIALS SHALL BE CLEARLY MARKED AS TO
THEIR FUNCTION AND USE.
TYPICAL POWER PANEL NAMEPLATE DETAIL
NO SCALE
1/2'' HIGH
LETTERS
1/4'' HIGH
LETTERS
PANEL LXW
120/208V/3PH/4W
FEED: 200 AMPS
(4) #3/0, #6 GND, 2" C.
FED FROM: MDP
NO SCALE
PUMP P-1
208V/3PH/4W
FEED: 600 AMPS
FED FROM: MDP
CKT # 6
TYPICAL EQUIPMENT NAMEPLATE
LAMACOID
NAME PLATE
1/2'' HIGH
LETTERS
1/4'' HIGH
LETTERS
LAMACOID
NAME PLATE
GENERAL FLOOR PENETRATION NOTES :
A. WHERE CONDUITS PENETRATE A FLOOR SLAB AND ARE EXPOSED, PROVIDE SQUARE 4'' HIGH CONCRETE
PAD AROUND CONDUIT SLEEVE AND EXTEND SLEEVE 4'' ABOVE PAD.
B. WHERE CONDUITS OR SLEEVES PENETRATE FLOORS IN GROUPS, THE CONCRETE PAD SHOULD BE
CONTINUOUS AROUND ALL CONDUITS OR SLEEVES.
2" EA. SIDE
CONDUIT SLEEVE 2'' LARGER IN DIAMETER
THAN CONDUIT(S) PASSING THROUGH SHALL
BE RIGID STEEL.
IF RATED FLOOR, PROVIDE CAULKING-STYLE
FIRESTOP BETWEEN SLEEVE AND WALL
MATERIAL TO ANCHOR SLEEVE AND
RESTORE RATING OF WALL PER LOCAL AUTH.
HAVING JURISDICTION.
TYPICAL CONDUIT PASSING
THROUGH A SUSPENDED FLOOR.
IF RATED FLOOR, PROVIDE REMOVABLE
FIRESTOP PILLOW (FSB OR EQUAL) IN
UL LISTED FIRESTOP ASSEMBLY TO
ALLOW FOR EASY REMOVAL AND
INSTALLATION OF NEW CABLES AND/OR
CONDUITS.
FLOOR
FIRE ALARM
AUDIO/VISUAL DEVICES
THERMOSTAT
CARBON DIOXIDE/
TEMPERATURE SENSOR
SWITCHES
FIRE ALARM
PULL STATION
TELEPHONE /
DATA OUTLET
RECEPTACLEFINISHED FLOOR
DEVICE MOUNTING DETAIL - GENERAL NOTES:
A. WHERE DEVICES OF ANY DISCIPLINE ARE LOCATED IN THE SAME GENERAL AREA ON THE PLANS AND ARE SHOWN TO BE MOUNTED AT A SIMILAR HEIGHT, ALIGN HORIZONTALLY ALONG TOP OF DEVICE BACKBOX (AS SHOWN IN DETAIL AND DESCRIBED IN KEY NOTE #2).
B. WHERE DEVICES OF ANY DISCIPLINE ARE LOCATED IN THE SAME GENERAL AREA ON THE PLANS AND ARE SHOWN MOUNTED AT DIFFERENT HEIGHTS, ALIGN VERTICALLY
ALONG THE CENTERLINE OF THE DEVICE BACKBOX (AS SHOWN IN DETAIL).
C. FOR ANY WALL OTHER THAN PAINTED GYPSUM BOARD OR CMU, DEVICE LOCATIONS MUST BE FIELD APPROVED BY ENGINEER OR ARCHITECT PRIOR TO INSTALLATION OF
FINISHES.
D. ADA REQUIRES 48" ABOVE FINISH FLOOR FOR FRONT ACCESS. SIDE REACH ACCESS ALLOWS A MAXIMUM OF 54" AND A LOW SIDE REACH OF NO LESS THAN 9" ABOVE FINISH FLOOR. ADA FRONT AND SIDE REACH ACCESS MUST BE MAINTAINED FOR NEW AND EXISTING CONSTRUCTION. NOTIFY ARCHITECT AND ENGINEER OF ANY
DISCREPANCIES.
8"
CARD READER / KEYPAD
DEVICE MOUNTING DETAIL - KEY NOTES:
1. MOUNT VISUAL NOTIFICATION APPLIANCES SO THAT ENTIRE LENS IS BETWEEN 80" AND 96" AFF. IF CEILING IS TOO LOW FOR DEVICE TO BE MOUNTED ABOVE 80", MOUNT
SO THAT THE LENS IS WITHIN 6" OF FINISHED CEILING.
2. ALIGN BACKBOXES OF DEVICES AT THE MOUNTING HEIGHT INDICATED. MEASURE TO THE CENTER OF THE BACKBOX FOR STANDARD OUTLET BOXES. NON-STANDARD BACKBOXES ARE TO BE INSTALLED SUCH THAT THE FINISHED DEVICES ARE ALIGNED ALONG THEIR RESPECTIVE CENTERLINES.
3. MOUNTING HEIGHTS SHOWN ILLUSTRATE DESIGN INTENT AND ARE TO BE FOLLOWED UNLESS CONTRADICTED BY APPLICABLE CODE. WHERE DEVICES ARE SHOWN ADJACENT TO DOOR FRAMES ON PLANS INSTALL 12" FROM FRAME TO AVOID SLUSHED SECTIONS OR BRACING. SPECIFIC DEVICES ARE SHOWN IN RELATIVE ORDER FROM DOOR FRAME; WHERE THESE DEVICES ARE NOT PRESENT AT A PARTICULAR LOCATION, ADJUST LOCATIONS CLOSER TO DOOR ACCORDINGLY.
4. THE CONTRACTOR IS TO COORDINATE ALL ROUGH-INS WITH ANY COUNTERTOPS/BACKSPLASHES/WALL PROTECTION TO AVOID CONFLICT. ALIGN DEVICE BACKBOXES IN THE BOTTOM OF THE NEXT FULL BLOCK ABOVE THE BACKSPLASH AS SHOWN. FOR NON-BLOCK WALLS ALIGN BOTTOM OF DEVICE BACKBOXES 2" ABOVE BACKSPLASH.
COORDINATE WORK WITH CASEWORK AND KITCHEN SHOP DRAWINGS ACCORDINGLY. IF CONFLICT STILL ARISES CONTACT THE ENGINEER FOR DIRECTION ON HOW TO
PROCEED.
X
COUNTERTOP (WHERE
APPLICABLE)
BACKSPLASH (WHERE
APPLICABLE)
CEILING
DOOR FRAME
(WHERE
APPLICABLE)
ADA PUSH PLATE
WALL TELEPHONES
INTERCOM CALL STATION
A/V TOUCH PANEL
F I R E
F I R E
FIRE
CASEWORK / FURNITURE
(WHERE APPLICABLE)
PP
(T O
C E
N T
E R
O F
B O
X
(T O
C E
N T
E R
O
F B
O X
PROVIDE REMOVABLE FIRESTOP PILLOW (FSB OR
EQUAL) IN UL LISTED FIRESTOP ASSEMBLY TO ALLOW
FOR EASY REMOVAL AND INSTALLATION OF NEW CABLES.
8"+, TO CLEAR
OBSTRUCTIONS
CL
2" EA. SIDE
CEILING
STRUCTURE
LOCATE SO THAT ACCESSIBLE CEILING IS AT EACH SIDE OF
SLEEVES OR PROVIDE ACCESS PANEL.
PROVIDE CAULKING-STYLE FIRESTOP BETWEEN
SLEEVE AND WALL MATERIAL TO ANCHOR SLEEVE AND
RESTORE RATING OF WALL PER LOCAL AUTH. HAVING
JURISDICTION.
SIZE CONDUIT SLEEVE (SIZE AS INDICATED) WITH
INSULATED THROAT CONDUIT TERMINATORS ON EACH
END. PROVIDE A THREADED CAP ON EACH END IF NOT
USED FOR WIRING . LINE-UP WITH "CABLE TRAY" OR ''HOOK
PATH'' WHERE APPLICABLE.
FIRE/SMOKE RATED OR UN-RATED PARTITION OF VARIOUS
CONSTRUCTIONS. REFER TO ARCHITECTURAL PLANS OR
FIELD VERIFY TYPE.
GENERAL NOTES:
A. PROVIDE ONE 2" SPARE CONDUIT SLEEVE THROUGH ALL FULL HEIGHT
PARTITIONS FOR FUTURE USE. LABEL AS SPARE FOR OWNER'S USE ONLY.
REFER TO ARCHITECTURAL PLANS FOR FULL HEIGHT PARTITION LOCATIONS.
B. USE AT ALL ''OPEN'' TYPE CABLING PENETRATIONS THROUGH WALLS, FLOORS,
ETC.
NOTE: IF THE SLEEVE SIZE AND NUMBER
INDICATED ON PLANS WILL NOT BE ADEQUATE TO
CONTAIN ALL CABLES AND STILL LEAVE 25%
SPARE CAPACITY, PROVIDE ADDLE SLEEVES AS
NEEDED TO PROVIDE THIS SPARE CAPACITY.
NOTE: BLOCK OUT
OPENINGS
IN PAD FOR CONDUITS PER
SHOP DRAWINGS.
FINISHED GRADE
PATCH EXISTING
PAVEMENT AS
NECESSARY.
GRADE BEAM AT
PERIMETER TO BE
12'' BELOW GRADE.
TURN REBAR DOWN.
3500 P.S.I CONCRETE
PAD CROWN TOP OF
PAD 1'' FOR DRAINAGE.
GENERATOR SET
WEATHERPROOF ENCLOSURE-
SEE SPECIFICATIONS.
#4 REBAR ON 12''
CENTERS EACH WAY
THROUGHOUT PAD.
3/4'' TOOLED RADIUS EDGE.
6'' AB. FIN.
GRADE.
18''
FORM GRADE BEAM ALL
AROUND PERIMETER.
SIZE GENERATOR SET PAD 6" - 36''
LARGER THAN UNIT ALL AROUND-
VERIFY EXACT DIMENSIONS WITH
SHOP DRAWINGS. AND NOTES ON
PLANS.
6'' CRUSHED STONE
6'' MIN.
6'' MIN.
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
1100 SYCAMORE STREET
CINCINNATI, OH 45202
T: (513)429-4404
C
U se rs \M
S te a rn s\ D o cu m e n ts
\O C V G
-0
M
E P R m st e a rn sA S
JS
M .r v t
/9
/2
:0 :2
A
M
E-500
09/11/2026
D. JOHNSON
M. STEARNS
C V G
V A U
L T
A
N D
S O
U T H
A R F F G
E N
E R A T O
R U
P G
R A D
E S
C
IN
C
IN
N A T I
N
O R T H
E R N
K E N
T U
C K Y I
N T E R N
A T
IO
N A L A
IR
P O
R T
N
E W
P R
IC
E P
IK
E A
N D
T
O W
E R D
R
IV
E
E R L A N
G E R K Y
E L E C T R
IC
A L D
E T A
IL
S
OCVG25-05
BID AND PERMIT
NOT TO SCALEE-500
ELECTRICAL EQUIPMENT NAMEPLATE2
NOT TO SCALEE-500
CONDUIT FLOOR PENETRATION SLEEVE INSTALLATION3
NOT TO SCALEE-500
TYPICAL WALL DEVICE MOUNTING DETAIL1
NOT TO SCALEE-500
CONDUIIT WALL SLEEVE INSTALLATION4
NOT TO SCALEE-500
GENERATOR CONCRETE PAD5
FACP
FS TS
ACCESS CONTROL
ADD TRANSLUCENT FILM
J
J
(E)TR-1
(E)LPA
(E)LPA1
UTILITY FEED
(E)SWBD
GDS
GENERATOR 1
U4
3 FEEDS
-NORMAL PRIMARY
-EMERGENCY PRIMARY
-SECONDARY FEEDER
ATS-1 NEW
THE CONTRACTOR AND ALL SUBCONTRACTORS SHALL
CONTACT ''KENTUCKY811" (BEFORE YOU DIG)'' AT
1-800-362-2764 OR 811 TO OBTAIN UNDERGROUND UTILITY
LOCATIONS PRIOR TO ANY CONSTRUCTION. ANY
CONTRACTOR OR SUBCONTRACTOR PERFORMING ANY
TYPE OF EXCAVATION ON THIS PROJECT TO OBTAIN AN
AUTHORIZATION NUMBER.
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
1100 SYCAMORE STREET
CINCINNATI, OH 45202
T: (513)429-4404
C
U se rs \M
S te a rn s\ D o cu m e n ts
\O C V G
-0
M
E P R m st e a rn sA S
JS
M .r v t
/9
/2
:0 :2
A
M
E-A-001
09/11/2026
D. JOHNSON
M. STEARNS
C V G
V A U
L T
A
N D
S O
U T H
A R F F G
E N
E R A T O
R U
P G
R A D
E S
C
IN
C
IN
N A T I
N
O R T H
E R N
K E N
T U
C K Y I
N T E R N
A T
IO
N A L A
IR
P O
R T
N
E W
P R
IC
E P
IK
E A
N D
T
O W
E R D
R
IV
E
E R L A N
G E R K Y
S O
U T H
A R F F E
L E C T R
IC
A L S
IT
E U
T
IL
IT
Y P
L A N
OCVG25-05
BID AND PERMIT
1" = 10'-0"E-A-001
SOUTH ARFF SITE UTILITY PLAN1
TAGGED NOTES
U4 GC SHALL PROVIDE SUFFICIENT EXPANSION JOINTS FOR THE
TRANSITION BETWEEN NEW AND EXISTING CONCRETE.
NEED 11"
ACCESS CONTROL
ACCESS CONTROL
900 SF
520 SF
ADD TRANSLUCENT FILM
(D) GENERATOR 1
(E)ATS-1
(E)SWBD
(E)LPA
(E)TR-1
(E)T-EMA
(E)EMB
(E)EMA
(E)DP-1
(E)EMA1
DE1
DE2
DE3
UTILITY
MEZZ A WING
UP TO WING B MEZZANINE
EXISTING MECH RM
(E)DP-1
2 SETS OF EXISTING 4" CONDUIT
E5
E5
(E)CD-XFMR
(E)CD
DE6
DE7
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
1100 SYCAMORE STREET
CINCINNATI, OH 45202
T: (513)429-4404
C
U se rs \M
S te a rn s\ D o cu m e n ts
\O C V G
-0
M
E P R m st e a rn sA S
JS
M .r v t
/9
/2
:0 :2
A
M
E-A-100
09/11/2026
D. JOHNSON
M. STEARNS
C V G
V A U
L T
A
N D
S O
U T H
A R F F G
E N
E R A T O
R U
P G
R A D
E S
C
IN
C
IN
N A T I
N
O R T H
E R N
K E N
T U
C K Y I
N T E R N
A T
IO
N A L A
IR
P O
R T
N
E W
P R
IC
E P
IK
E A
N D
T
O W
E R D
R
IV
E
E R L A N
G E R K Y
S O
U T H
A R F F D
E M
O L
IT
IO
N
P L A N
OCVG25-05
BID AND PERMIT
1" = 10'-0"E-A-100
SOUTH ARFF DEMO PLAN1
TAGGED NOTES
DE1 EXISTING ATS-1 & 2 SHALL BE REMOVED IN A MANNER THAT
ALLOWS IT TO BE RETURNED TO CVGI FOR STORAGE AND
POTENTIAL FUTURE USE.
DE2 CONTRACTOR TO DEMOLISH AND REMOVE EXISTING
UNDERGROUND GENERATOR FUEL TANK.
DE3 GENERAL CONTRACTOR TO DEMOLISH AND REMOVE EXISTING
GENERATOR IN ITS ENTIRETY ALONG WITH ALL EXISTING
EXTERIOR CONDUITS.
DE6 THE VIEW RANGE WITHIN THE ORANGE-HIGHLIGHTED BOX IS
ASSOCIATED WITH THE MEZZANINE LEVEL ABOVE. SEE NOTE E4
FOR CONTEXT ON THE OVERLAPPING OF THE FIRST FLOOR AND
MEZZANINE LEVEL.
DE7 CONTRACTOR TO DEMOLISH THE NECESSARY PORTION OF THE
EXISTING CONDUIT RUN TO INSTALL THE NEW JUNCTION BOX.
E5 DOOR TO FLOOR BELOW MEZZANINE.
FACP
FS TS
NEED 11"
ACCESS CONTROL
ACCESS CONTROL
900 SF
520 SF
ADD TRANSLUCENT FILM
J
J
(E)TR-1
(E)LPA
(E)SWBD
E3
3 FEEDS
-NORMAL PRIMARY
-EMERGENCY PRIMARY
-SECONDARY FEEDER
10' - 0"
UTILITY
GENERATOR BOD:
CUMMINS C150D6D 150kW
DIESEL WITH INTEGRAL BELLY-
TANK AND SOUND/WEATHER-
RATED (LEVEL 1) ENCLOSURE
WP
GDS
-41EMA
DINING
KITCHEN
2 SETS OF EXISTING 4" CONDUIT
UP TO WING B MEZZANINE
ATS-1 NEW E2
E5
E5
E4
E7
E6
(E)DP-1
(E)CD-XFMR
(E)CD
E1
EXISTING MECH RM
BLOCK HEATER
BATTERY CHARGER
-18EMA
-20EMA
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
1100 SYCAMORE STREET
CINCINNATI, OH 45202
T: (513)429-4404
C
U se rs \M
S te a rn s\ D o cu m e n ts
\O C V G
-0
M
E P R m st e a rn sA S
JS
M .r v t
/9
/2
:0 :2
A
M
E-A-200
09/11/2026
D. JOHNSON
M. STEARNS
C V G
V A U
L T
A
N D
S O
U T H
A R F F G
E N
E R A T O
R U
P G
R A D
E S
C
IN
C
IN
N A T I
N
O R T H
E R N
K E N
T U
C K Y I
N T E R N
A T
IO
N A L A
IR
P O
R T
N
E W
P R
IC
E P
IK
E A
N D
T
O W
E R D
R
IV
E
E R L A N
G E R K Y
S O
U T H
A R F F P
O W
E R P
L A N
OCVG25-05
BID AND PERMIT
1" = 10'-0"E-A-200
SOUTH ARFF POWER PLAN1
TAGGED NOTES
E1 NEW FEEDS ON THE EXTERIOR SIDE OF THE BUILDING ARE TO
DROP INTO THE GENERATOR DOCKING STATION (GDS), THEN
ROUTE BELOW GRADE AND RUN UNDERGROUND TO THE NEW
GENERATOR.
E2 CONTRACTOR TO FIELD-COORDINATE THE FINAL LOCATION OF THE
NEW ATS WITHIN MEZZANINE B ALONG WITH THE FINAL ROUTING
OF THE CONDUIT RUNS FROM THE SPECIFIED PENETRATION POINT
REFERENCED IN KEY NOTE E4. ENSURE ALL REQUIRED AND
APPLICABLE CODE CLEARANCES ARE MAINTAINED WITH EXISTING
EQUIPMENT PRESENT ON THE MEZZANINE.
E3 INSTALL NEW GENERATOR AND ASSOCIATED GENERATOR PAD IN
APPROXIMATE LOCATION SHOWN ON PLAN. CONTRACTOR TO
ENSURE GENERATOR IS POSITIONED A MINIMUM OF 10 FEET FROM
BUILDING STRUCTURE. REQUIRED MODIFICATIONS TO EXISTING
CONDUIT SHALL BE FIELD-COORDINATED AND COMPLETED BY
CONTRACTOR IN COORDINATION WITH ELECTRICAL CONTRACTOR.
E4 THE BOTTOM FEW FEET OF THE MEZZANINE LEVEL'S FLOOR TO
CEILING RANGE OVERLAP WITH THE UPPER FEW FEET OF THE
LEVEL 1 CEILING SPACE WHERE THE PROPOSED REWORKED
CONDUITS ARE ROUTED. THIS OVERLAP ALLOWS THE CONDUITS
TO RUN HORIZONTALLY THROUGH THE LEVEL 1 CEILING SPACE
AND EXIT THROUGH THE OTHER SIDE AT THE BASE OF THE
MEZZANINES WALL LOCATED IN THE EAST GARAGE.
E5 DOOR TO FLOOR BELOW MEZZANINE.
E6 THE VIEW RANGE WITHIN THE DASHED BOX IS ASSOCIATED WITH
THE MEZZANINE LEVEL ABOVE. SEE NOTE E4 FOR CONTEXT ON
THE OVERLAPPING OF THE FIRST FLOOR AND MEZZANINE LEVEL.
E7 PROVIDE A NEW JUNCTION BOX TO SERVE AS THE SPLIT POINT
WHERE THE TWO EXISTING CONDUIT RUNS ARE REWORKED INTO
THE NEW ATS FEEDING PLAN.
EG8
375KVA
EXISTING
DIESEL GEN
480Y/277V/3Φ/4W 600A
SWBD (MAIN ELECTRIC ROOM)
480Y/277V, 3-PHASE, 4-WIRE
600A BUSSING
DISTRIBUTION SECTION(S)
100AT/
100AF
N E
ATS-1
600A
ATS
RTU-1
480Y/277V,3Φ,4W
EMB
PANEL
225A
MCB
TX-2
TRANSFORMER
75 kVA
208Y/120V,3Φ,4W
EMA
PANEL
225A MCB
208Y/120V,3Φ,4W
KP
PANEL
100A
TR-1
TRANSFORMER
75 kVA
225AT/
400AF
208Y/120V,3Φ,4W
LPA
PANEL
225A MLO
8KVA UPS
120/240V,1Φ,3W
AOC
PANEL
80A MLO
A
A
A
A
A
A
A
A
A
A
600A600A
(2) SETS OF (4) #350MCM
(1) #1 GND
IN 4" C.
FROM UTILITY
TRANS.
(2) SETS OF (4) #350MCM
(1) #1 GND
IN 4" C.
(4) 4/0 &
(1) #6 GND IN
2-1/2" C.
(4) #1 &
GND IN
1-1/2" C.
(3) #2 &
(1) #8 GND IN
1-1/2" C.
(4) 4/0 &
(1) #6 GND IN
2-1/2" C.
(4) 4/0 &
(1) #6 GND IN
2-1/2" C.
(4) #2 &
(1) #8 GND IN
1-1/2" C.
DP-1
A
A
DP-2
A
SPARE
M
UTILITY METER
# 108 262 173
59.84KW PEAK DEMAND
(4) #1/0 THWN &
(1) #6 GND IN
2-1/2" C.
(3) #2 THWN &
(1) #8 GND IN
1-1/2" C.
SINGLE LINE TAGGED NOTES
1. DEMOLISH EXISTING ATS AND REPLACE WITH NEW ATS PER DRAWINGS.
2. DEMOLISH EXISTING GENERATOR AND REPLACE WITH NEW GENERATOR PER DRAWINGS.
3. NEW ATS-1 IS TO BE ADDED ON THE MEZZANINE LEVEL OF THE SOUTH ARFF BUILDING.
CONTRACTOR TO COORDINATE THE CONDUIT REWORK. ROUTE SHOWN ON DRAWINGS IS
PROPOSED LOCATION ONLY. SEE SHEET E-A-200 FOR FLOOR PLAN VIEW LAYOUT.
4. NEW GENERATOR IS TO BE ADDED IN THE LOCATION SHOWN ON SHEET E-A-200.
5. EXISTING FEEDS ARE TO BE RE WORKED PER SHEET E-A-200.
80AT/
100AF
T-AOC
TRANSFORMER
15 kVA
208Y/120V,3Φ,4W
EMA1
PANEL
100A
23.3KW
FROM DRAWINGS
54.72KW DEMAND FROM METER
(4) #3 &
GND IN
CU.
42.8KW FROM DRAWINGS
(3) #4 CU &
(1) #8 CU GND. IN
1-1/4" C.
(3) #4 CU &
(1) #8 CU GND. IN
1-1/4" C.
(3) #4 CU &
(1) #8 CU GND. IN
1-1/4" C.
(3) #8 CU &
(1) #10 CU GND. IN
3/4" C.
GEN
188kVA/150kW
NEW DIESEL
GENERATOR
480Y/277V/3Φ/4W 600A, LSIG
N E
ATS-1
600A
ATS
(2) SETS OF (4) #350MCM
(1) #1 GND
IN 4" C.
FEEDS TO EXISTING SWBD
IN MAIN ELECTRIC ROOM
FEED FROM EXISTING MCB
THAT IS FED OFF THE
EXISTING UTILITY FEED
EXISTING ATS-1 SHALL BE REMOVED
IN A MANNER THAT ALLOWS IT TO BE
RETURNED TO CVG FOR STORAGE
AND POTENTIAL FUTURE USE.
N E
GDS
600A
DOCKING
PLUG
CONNECTION
FOR ROLL UP
GEN SET
CONTROL WIRING
TO ATS(S) AND
ANNUNCIATOR(S)
SERVICE GROUND RODS
SERVICE GROUND UFER
PROVIDE CONCRETE PAD
AROUND GENERATOR
CONTRACTOR SHALL
CONFIRM THE
INSTALLATION OF ALL
CONTROL DEVICES WITH
THE OWNER.
CONTRACTOR SHALL
PROVIDE A TEMPORARY
GENERATOR AS REQUIRED
TO SUPPORT PROJECT
PHASING.
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
1100 SYCAMORE STREET
CINCINNATI, OH 45202
T: (513)429-4404
C
U se rs \M
S te a rn s\ D o cu m e n ts
\O C V G
-0
M
E P R m st e a rn sA S
JS
M .r v t
/9
/2
:0 :2
A
M
E-A-600
09/11/2026
D. JOHNSON
M. STEARNS
C V G
V A U
L T
A
N D
S O
U T H
A R F F G
E N
E R A T O
R U
P G
R A D
E S
C
IN
C
IN
N A T I
N
O R T H
E R N
K E N
T U
C K Y I
N T E R N
A T
IO
N A L A
IR
P O
R T
N
E W
P R
IC
E P
IK
E A
N D
T
O W
E R D
R
IV
E
E R L A N
G E R K Y
S O
U T H
A R F F E
L E C T R
IC
A L S
IN
G
L E L
IN
E
OCVG25-05
BID AND PERMIT
NOT TO SCALEE-A-600
SOUTH ARFF - ELECTRICAL SINGLE LINE - DEMO & NEW PLAN1
GENERAL NOTES (RISER):
A. PROVIDE ENGRAVED LAMACOID LABELS FOR ALL POWER DISTRIBUTION EQUIPMENT FURNISHED OR
MODIFIED IN THIS PROJECT, LABELS PER DETAILS AND SPECIFICATIONS.
B. SERVICE EQUIPMENT SHALL BE MARKED WITH THE MAXIMUM AVAILABLE FAULT-CURRENT AT THE
EQUIPMENT AND THE DATE THE CALCULATION WAS PERFORMED. APPLY A TYPE-WRITTEN
ADHESIVE LABEL WITH WHITE BACKGROUND, 1/2'' HIGH BLACK LETTERING.
C. CONTRACTOR SHALL INSTALL SEPARATE CONDUITS, PULL BOXES, ETC. FOR EACH EMERGENCY
POWER BRANCH & NORMAL POWER PER NEC FOR COMPLETE SEPARATION OF POWER SERVICES.
D. ALL CIRCUIT BREAKERS AND/OR DISCONNECTS SERVING THE PRIMARY SIDE OF A TRANSFORMER
WHICH ARE NOT WITHIN SITE OF THE TRANSFORMER SHALL BE PROVIDED WITH PERMANENTLY
INSTALLED MEANS TO LOCK THE BREAKER IN THE OFF POSITION. SUCH TRANSFORMERS SHALL
HAVE THE ROOM NAME AND NUMBER OF THE PRIMARY DISCONNECTING MEANS ENGRAVED ON THE
EQUIPMENT NAMEPLATE.
E. REFER TO SPECIFICATIONS FOR ARC FLASH AND RELATED POWER SYSTEM STUDY REQUIREMENTS.
F. REFER TO SPECIFICATIONS FOR CONDUCTOR REQUIREMENTS. ALL FEEDERS SHALL BE COPPER.
G. CURRENT CARRYING CONDUCTORS ARE SIZED FROM NEC-2023 TABLE 310.16 (75DEG C - FOR
THHW/THW/THWN INSULATION). REFER TO PROJECT SPECIFICATIONS FOR ALLOWABLE CONDUIT
AND WIRING METHODS.
H. GROUND WIRES ARE SIZED FROM NEC TABLE 250.122.
I. HVAC EQUIPMENT FEEDERS AND BRANCH CIRCUITS SHALL BE IN COPPER (UNLESS OTHERWISE
NOTED).
J. CONDUIT FILL RATES ARE BASED UPON TABLE C.10 (PVC-80 CONDUIT WITH THHN/THWN/THWN-2
WIRE). REFER TO PROJECT SPECIFICATIONS FOR ALLOWABLE CONDUIT AND WIRING METHODS.
K. CONTRACTOR SHALL CONFIRM THE INSTALLATION OF ALL CONTROL DEVICES WITH THE OWNER.
L. CONTRACTOR SHALL PROVIDE A TEMPORARY GENERATOR AS REQUIRED TO SUPPORT PROJECT
PHASING.
PROVIDE GROUND FAULT CIRCUIT INTERRUPTER TYPE CIRCUIT BREAKERGFI
A. ALL NEW PANELBOARDS SHALL BE ORDERED WITH ''DOOR-IN-DOOR'' OPTION.
B. PROVIDE LOCK-OUT TYPE CIRCUIT BREAKERS FOR ALL HARD-WIRED
EQUIPMENT. CIRCUIT BREAKERS SERVING HVAC EQUIPMENT SHALL BE HACR
TYPE.
C. PROVIDE TYPEWRITTEN SCHEDULES AT ALL PANELBOARDS. INDICATE ROOM
NUMBERS BEING SERVED BY CIRCUIT ON SCHEDULE.
D. PROVIDE SIX (4) SPARE 1'' CONDUITS STUBBED INTO ACCESSIBLE CEILING
SPACE FROM ALL NEW RECESSED PANELBOARDS.
E. PROVIDE SIX (4) SPARE 1'' CONDUITS STUBBED INTO ACCESSIBLE CEILING
SPACE OF FLOOR BELOW FROM ALL NEW RECESSED PANELBOARDS.
PANELBOARD SCHEDULE NOTES :
PANELBOARD SCHEDULE SYMBOLS :
MAIN LUG ONLYMLO
MAIN CIRCUIT BREAKERMCB
VARIABLE FREQUENCY DRIVEVFD
PROVIDE ARC-FAULT CIRCUIT INTERRUPTER TYPE CIRCUIT BREAKERAFCI
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
1100 SYCAMORE STREET
CINCINNATI, OH 45202
T: (513)429-4404
C
U se rs \M
S te a rn s\ D o cu m e n ts
\O C V G
-0
M
E P R m st e a rn sA S
JS
M .r v t
/9
/2
:0 :2
A
M
E-A-601
09/11/2026
D. JOHNSON
M. STEARNS
C V G
V A U
L T
A
N D
S O
U T H
A R F F G
E N
E R A T O
R U
P G
R A D
E S
C
IN
C
IN
N A T I
N
O R T H
E R N
K E N
T U
C K Y I
N T E R N
A T
IO
N A L A
IR
P O
R T
N
E W
P R
IC
E P
IK
E A
N D
T
O W
E R D
R
IV
E
E R L A N
G E R K Y
S O
U T H
A R F F E
L E C T R
IC
A L P
A N
E L S
C H
E D
U L E S
OCVG25-05
BID AND PERMIT
THIS IS AN EXISTING PANEL.
NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS.
TOTAL ESTIMATED DEMAND CURRENT: 0 A
TOTAL CONNECTED CURRENT: 0 A
TOTAL ESTIMATED DEMAND: 0 VA
TOTAL CONNECTED LOAD: 0 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
0 A 0 A 0 A
0.0 kVA 0.0 kVA 0.0 kVA
(E) AOC ACCESS CONTROL 20 1 41 0.0 0.0 42 1 20 (E) BACKUP AOC CPU QUAD
39 0.0 0.0 40 1 20 (E) BACKUP AOC CPU QUAD
(E) SPLIT SYSTEM 20 2
37 0.0 0.0 38 1 20 (E) BACKUP AOC CPU QUAD
(E) CORD DROP 20 1 35 0.0 0.0 36 1 20 (E) BACKUP AOC CPU QUAD
(E) BACKUP AOC CPU QUAD 20 1 33 0.0 0.0 34 1 20 (E) BACKUP AOC CPU QUAD
(E) BACKUP AOC HONEYWELL 20 1 31 0.0 0.0 32 1 20 (E) REC
(E) STORE ROOM 20 1 29 0.0 0.0 30 1 20 (E) REC
(E) ROOF TOP GFI 20 1 27 0.0 0.0 28 1 20 (E) REC
(E) MENS RR HEAT 20 1 25 0.0 0.0 26 1 20 (E) REC
(E) WOMENS RR HEAT 20 1 23 0.0 0.0 24 1 20 (E) REC
(E) BACKUP AOC RADIO CHRGERS 20 1 21 0.0 0.0 22 1 20 (E) REC
(E) BACKUP AOC WORKSTATION 20 1 19 0.0 0.0 20 1 20 (E) (L) FIRE ALARM DAMPERS
(E) HEATER IN MENS ROOM 20 1 17 0.0 0.0 18
(E) DATA RACK 20 1 15 0.0 0.0 16
2 20 (E) EQUIP (MINI SPLIT)
(E) DATA RACK 20 1 13 0.0 0.0 14 1 20 (E) REC
(E) REC 20 1 11 0.0 0.0 12 1 20 (E) REC
(E) AFCI REC 20 1 9 0.0 0.0 10 1 20 (E) AFCI REC
(E) AFCI REC 20 1 7 0.0 0.0 8 1 20 (E) AFCI REC
5 0.0 0.0 6 1 20 (E) AFCI REC
3 0.0 0.0 4 1 20 (E) REC(E) SPD 30 3
1 0.0 0.0 2 1 20 (E) REC
CIRCUIT DESCRIPTION CB... OCP P CKT A B C CKT P OCP CB... CIRCUIT DESCRIPTION
AMPERES: 100 A MOUNTING: SURFACE SUPPLY FROM: EMA
VOLTAGE: 208Y/120V,3P,4W SPD: No LOCATION: MEZZ A WING
PANEL: EMA1 MAINS TYPE: 100A MCB PANEL INTERRUPTING RATING: EXISTING PANEL
PANELBOARD AND WIRING SCHEDULE AVAILABLE FAULT CURRENT: EXISTING PANEL
THIS IS AN EXISTING PANEL. NEW ITEMS DENOTED AS BOLD.
NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS.
TOTAL ESTIMATED DEMAND CURRENT: 4 A
TOTAL CONNECTED CURRENT: 4 A
REC 180 VA 100.00% 180 VA TOTAL ESTIMATED DEMAND: 1280 VA
EQUIP 1100 VA 100.00% 1100 VA TOTAL CONNECTED LOAD: 1280 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
5 A 0 A 7 A
0.5 kVA 0.0 kVA 0.8 kVA
NEW GEN WP RECPT 20 1 41 0.2 0.0 42 1 20 (E) CORD DROP F5
(E) WATER HEATER RR/SHOWER 20 1 39 0.0 0.0 40 1 20 (E) BACKUP AOC TOWER LIGHTS
(E) F3 LADDER CORD DROP 20 1 37 0.0 0.0 38 1 20 (E) RADIO BATTERY CHARGERS
(E) CORD DROP WEST WALL 20 1 35 0.0 0.0 36
(E) CORD DROP WEST 20 1 33 0.0 0.0 34
(E) CORD DROP WEST 20 1 31 0.0 0.0 32
3 100 (E) EMA1
29 0.0 0.0 30 1 20 (E) DUPLEX WEST WALL + PIDs
27 0.0 0.0 28(E) KP 100 3
25 0.0 0.0 26
2 20 (E) SHORELINE DISASTER TRAILER
(E) CORD DROP DOOR F3 20 1 23 0.0 0.0 24
(E) RADIO 20 1 21 0.0 0.0 22
2 20 (E) AC-1
(E) RADIO 20 1 19 0.0 0.5 20 1 20 BATTERY CHARGER
(E) GATE CAMERA AND INTERCOM 20 1 17 0.0 0.6 18 1 20 BLOCK HEATER
(E) OPEN DOOR LIGHT 20 1 15 0.0 -- 16 1 -- (E) SPACE
(E) EF LOUVER 20 1 13 0.0 0.0 14 1 20 (E) F2 CORD DROP
(E) DUPLEX ALARM ROOM 20 1 11 0.0 0.0 12 1 20 (E) BAY HEATERS WEST
(E) BACKUP AOC CPU IG DUPLEX 20 1 9 0.0 0.0 10 1 20 (E) BAY HEATER WEST
(E) BACKUP AOC CPU IG DUPLEX 20 1 7 0.0 0.0 8 1 20 (E) CORD DROP BATALLION DOOR
(E) PAGING SYSTEM 20 1 5 0.0 0.0 6 1 20 (E) BACKUP AOC CPU IG DUPLEX
(E) FIRE ALARM PANEL 20 1 3 0.0 0.0 4 1 20 (E) DUPLEX AT CAPTAIN'S OFFICE
(E) DUPLEX AT TELEPHONE 20 1 1 0.0 0.0 2 1 20 (E) EX LOAD
CIRCUIT DESCRIPTION CB... OCP P CKT A B C CKT P OCP CB... CIRCUIT DESCRIPTION
AMPERES: 225 A MOUNTING: SURFACE SUPPLY FROM: T-EMA
VOLTAGE: 208Y/120V,3P,4W SPD: No LOCATION: MEZZ A WING
PANEL: EMA MAINS TYPE: 225A MCB PANEL INTERRUPTING RATING: EXISTING PANEL
PANELBOARD AND WIRING SCHEDULE AVAILABLE FAULT CURRENT: EXISTING PANEL
THIS IS AN EXISTING PANEL.
NOTES:
TOTAL EST. DEMAND CURRENT: 2 A
TOTAL CONN. CURRENT: 2 A
REC 180 VA 100.00% 180 VA TOTAL EST. DEMAND: 1 kVA
EQUIP 1100 VA 100.00% 1100 VA TOTAL CONN. LOAD: 1 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
8 (E) SPACE -- -- -- -- 3 -- -- --
7 (E) RTU-1 -- -- -- -- 3 100 A 100 A 0.0
6 (E) TR-1 -- -- -- -- 3 100 A 100 A 0.0
5 (E) SPARE -- -- -- -- 3 100 A 100 A 0.0
4 (E) T-AOC -- -- -- -- 2 100 A 40 A 0.0
3 (E) DP-2 -- -- -- -- 3 100 A 100 A 0.0
2 (E) DP-1 3 100 A 100 A 0.0
1 (E) EMB 3 200 A 125 A 1.3
CKT CIRCUIT DESCRIPTION SETS WIRE GND COND POLES FRAME TRIP LOAD (kVA) REMARKS
AMPERES: 600 A MOUNTING: FLOOR SUPPLY FROM: UTILITY
VOLTAGE: 480Y/277V,3P,4W SPD: No LOCATION: UTILITY 128
SWITCHBOARD: SWBD MAINS TYPE: 600A MCB kAIC RATING: EXISTING PANEL
SWITCHBOARD AND WIRING SCHEDULE kAIC VALUE: EXISTING PANEL
T
T
T
DD
DD
M
J
J
3W-1" #2 15 kV #6G 2W-5"
8W-5" - w/6
SETS 3 -
500 WITH A
GND.
JB1
JB2
5" 5"
IPA
(E) EXISTING 1500 kVA
OIL FILLED XFMR L-43
(PAD MTD)
(E) EXISTING 1500 kVA
OIL FILLED XFMR D-43
(PAD MTD)
TM M
(E) EXISTING 200A
MEDIUM VOLTAGE
(12,470V) SWITCH-2
L-43 (PAD MTD)
(E) EXISTING 200A
MEDIUM VOLTAGE
(12,470V)
SWITCH-1 D43
(PAD MTD)
(E) EXISTING DUKE
METERING CABINET
LIMABURG - 43 FEED
(E) EXISTING DUKE
METERING CABINET
DONALDSON - 43 FEED
3W-1" #2 15 kV #6G 2W-5"
2W-5", 3-1C #2 15 kV CABLE #6G
(E)GDSHVAC
UNIT
2W-5" CONDUITS
3 Spare 5" C3 Spare 5" C
1.5" PVC W/5 #12 LTG & RECPT
2 - 2" C 1 SPARE 1 FIRE
HVB FEEDER
FIBER / COMMUNICATION
DUCT
NAVAID DUCT BANK
HVB FEEDER
FIBER / COMMUNICATION
DUCT
NAVAID DUCT BANK
1.5" PVC W/5 #12 LTG & RECPT
NEW GENERATOR
E-V-001
INLET OUTLET
(E) CONCRETE
WALKWAY
NEW CONDUIT FROM
GENERATOR TO IPA
(E)PB12L1A
(E)TX-3
DUKE ENERGY
EQUIPMENT
U5
U6
NEW GENERATOR
BLOCK HEATER
WP
NEW FENCE
(E)GDS
HVAC
UNIT
-4PB12L1A
-6PB12L1A
-8PB12L1A
3' TYP.
U2
U1
EXISTING FENCE
EXISTING
FENCE
GENERATOR BOD:
CUMMINS DFEK 500kW DIESEL WITH
INTEGRAL BELLY-TANK (C207) AND
WEATHER-RATED ENCLOSURE
BATTERY CHARGER
THE CONTRACTOR AND ALL SUBCONTRACTORS SHALL
CONTACT ''KENTUCKY811" (BEFORE YOU DIG)'' AT
1-800-362-2764 OR 811 TO OBTAIN UNDERGROUND UTILITY
LOCATIONS PRIOR TO ANY CONSTRUCTION. ANY
CONTRACTOR OR SUBCONTRACTOR PERFORMING ANY
TYPE OF EXCAVATION ON THIS PROJECT TO OBTAIN AN
AUTHORIZATION NUMBER.
CHECKED:
DATE:
DRAWN:
F
IL
E N A M E
P L O T
T
IM
E
CLIENT/CMTA JOB #:
1100 SYCAMORE STREET
CINCINNATI, OH 45202
T: (513)429-4404
C
U se rs \M
S te a rn s\ D o cu m e n ts
\O C V G
-0
M
E P R m st e a rn sA S
JS
M .r v t
/9
/2
:0 :2
A
M
E-V-001
09/11/2026
D. JOHNSON
M. STEARNS
C V G
V A U
L T
A
N D
S O
U T H
A R F F G
E N
E R A T O
R U
P G
R A D
E S
C
IN
C
IN
N A T I
N
O R T H
E R N
K E N
T U
C K Y I
N T E R N
A T
IO
N A L A
IR
P O
R T
N
E W
P R
IC
E P
IK
E A
N D
T
O W
E R D
R
IV
E
E R L A N
G E R K Y
V A U
L T
E
L E C T R
IC
A L S
IT
E U
T
IL
IT
Y P
L A N
OCVG25-05
BID AND PERMIT
3/16" = 1'-0"E-V-001
VAULT 12 SITE UTILITY PLAN1
1/4" = 1'-0"E-V-001
ENLARGED VIEW 0F NEW GENERATOR2
TAGGED NOTES
U1 CONTRACTOR TO COORDINATE THE TWO CONCRETE REGIONS
SHOWN, WITH THE HALF-TONE AREA REPRESENTING EXISTING
CONCRETE AND THE SOLID BLACK AREA REPRESENTING THE NEW
GENERATOR PAD. REFER TO DETAIL 5 ON SHEET E-500.
U2 CONTRACTOR TO COORDINATE FENCE REWORK AS SHOWN ON
PLAN. THIS PLAN SERVES AS A GENERAL REPRESENTATION; FINAL
DIMENSIONS AND LAYOUT TO BE FIELD-COORDINATED WITH
OWNER PRIOR TO FENCE DEMO.
U5 NEW GENSET TO BE CONNECTED TO THE ALMCS SYSTEM TO
ALLOW THE TOWER TO START THE GENSET DURING ADVERSE
WEATHER CONDITIONS.
U6 CONTRACTOR SHALL COORDINATE WITH CVG, SCHNEIDER
ELECTRIC (SE), AND EATON TO PROVIDE, INSTALL, AND INTEGRATE
A NEW PM8000 (PM8214) POWER METER FOR MONITORING
GENERATOR OPERATING STATUS, POWER PARAMETERS, AND
FAULT CONDITIONS. THE PM8000 (PM8214) SHALL BE DIRECTLY
INTEGRATED WITH THE SCHNEIDER ELECTRIC POWER
MONITORING AND…