26-048-ITB_-Vault_12_&_S._ARFF_Generator_Upgrades_-Drawings_-_Exhibit_E.pdf

PDF 8 MB Posted

Attached to
Vault 12 and South ARFF Generator Upgrades
Solicitation number
26-048-ITB
Issued by
Kenton County, Kentucky

About this file

This is a set of technical drawings and exhibit documents for the Vault 12 and South ARFF Generator Upgrades project at Cincinnati/Northern Kentucky International Airport (CVG), a facility operated by the Kenton County Airport Board. The project consists of generator replacements at two locations on the CVG campus—Vault 12 and South ARFF Station—along with HVAC equipment upgrades in the Vault. The drawings include electrical schematics, site utility plans, demolition plans, power plans, panel schedules, and mechanical details prepared in accordance with the 2018 Kentucky Building Code, 2015 International Mechanical Code, 2012 International Energy Conservation Code, and 2023 National Electrical Code NFPA 70. A mandatory pre-proposal meeting and site visit is scheduled for Thursday, October 8, 2026, at 10:00 am at CVG Centre 77 Comair Blvd, Erlanger, KY 41018. Questions must be submitted by 11:59 pm on Thursday, October 15, 2026, with answers posted by Thursday, October 22, 2026. Proposals are due by Thursday, October 29, 2026, at 2:00 pm, with no proposals accepted after that time unless extended by addendum.

The drawings specify comprehensive electrical and mechanical work including demolition of existing generators, ATSs (Automatic Transfer Switches), and fuel tanks; installation of new diesel generators with integral belly tanks and weather-rated enclosures at both locations; installation of new ATSs; new transformers and panelboards; new conduit runs and cabling; concrete pads for generator placement; and associated controls integration with existing systems including the ALMCS (Airport Lighting Management and Control System) and Schneider Electric Power Monitoring and Control System. The Vault 12 location will receive a 625 kVA/500 kW diesel generator, while the South ARFF location will receive a 150 kW diesel generator. All work must comply with seismic restraint requirements, NEC standards, and applicable local, state, and federal regulations. The contractor is responsible for coordinating with utility companies, obtaining necessary permits, providing temporary generator support during phasing, and ensuring one-year warranties on all equipment and materials from substantial completion.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

THIS PROJECT CONSISTS OF GENERATOR REPLACEMENTS FOR 2 LOCATIONS ON THE

CVG CAMPUS. VAULT 12 AND SOUTH ARFF STATION. WITH THE REPLACEMENT OF

THE GENERATORS, THE UPGRADES OF HVAC EQUIPMENT IN THE VAULT WILL ALSO

BE COMPLETED AT THE SAME TIME.

KENTUCKY BUILDING CODE

GENERAL INFORMATION

GOVERNING REGULATIONS

PROJECT DESCRIPTION

BUILDING SCIENCE LEADERSHIP

INTERNATIONAL MECHANICAL CODE

INTERNATIONAL ENERGY CONSERVATION CODE

NATIONAL ELECTRICAL CODE NFPA 70

PROJECT LOCATION

VICINITY MAP: CITY

VICINITY MAP: LOCAL / CAMPUS

1100 SYCAMORE STREET

CINCINNATI, OH 45202

T: (513)429-4404

C

U se rs \M

S te a rn s\ D o cu m e n ts

\O C V G

-0

M

E P R m st e a rn sA S

JS

M .r v t

/9

/2

:0 :1

A

M

G-000

09/11/2026

D. JOHNSON

M. STEARNS

C V G

V A U

L T

A

N D

S O

U T H

A R F F G

E N

E R A T O

R U

P G

R A D

E S

C

IN

C

IN

N A T I

N

O R T H

E R N

K E N

T U

C K Y I

N T E R N

A T

IO

N A L A

IR

P O

R T

N

E W

P R

IC

E P

IK

E A

N D

T

O W

E R D

R

IV

E

E R L A N

G E R K Y

C O

V E R S

H E E T

OCVG25-05

CVG VAULT 12 AND SOUTH ARFF

GENERATOR UPGRADES

CINCINNATI / NORTHERN KENTUCKY INTERNATIONAL AIRPORT

171 NEW PRICE PIKE AND 2100 TOWER DRIVE

ERLANGER, KY 41018

BID AND PERMIT

09/11/2026

BID AND PERMIT

DRAWING INDEX

GENERAL

G-000 COVER SHEET

G-V-100 VAULT 12 ELEVATIONS

ELECTRICAL - GENERAL

E-000 ELECTRICAL LEGEND

E-001 OVERALL ELECTRICAL SITE PLAN

E-500 ELECTRICAL DETAILS

ELECTRICAL - SOUTH ARFF

E-A-001 SOUTH ARFF ELECTRICAL SITE UTILITY PLAN

E-A-100 SOUTH ARFF DEMOLITION PLAN

E-A-200 SOUTH ARFF POWER PLAN

E-A-600 SOUTH ARFF ELECTRICAL SINGLE LINE

E-A-601 SOUTH ARFF ELECTRICAL PANEL SCHEDULES

ELECTRICAL - VAULT 12

E-V-001 VAULT 12 ELECTRICAL SITE UTILITY PLAN

E-V-100 VAULT 12 DEMOLITION PLAN

E-V-200 VAULT 12 POWER AND CONDUIT PLAN

E-V-600 VAULT 12 ELECTRICAL SINGLE LINE

E-V-601 VAULT 12 ELECTRICAL PANEL SCHEDULES

MECHANICAL - VAULT 12

M-V-000 MECHANICAL LEGEND

M-V-100 VAULT 12 MECHANICAL PLANS

M-V-200 VAULT 12 MECHANICAL SCHEDULES, DETAILS & CONTROLS

REVISIONS

3' - 0"

4' - 2"

3' - 4" 3' - 4"

4' - 2"

3' - 4"

3' - 4" 3' - 6"

4' - 6"

3' - 6"

3' - 0"

3' - 4"

3' - 0" 3' - 4"

3' - 4"

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

1100 SYCAMORE STREET

CINCINNATI, OH 45202

T: (513)429-4404

C

U se rs \M

S te a rn s\ D o cu m e n ts

\O C V G

-0

M

E P R m st e a rn sA S

JS

M .r v t

/9

/2

:0 :1

A

M

G-V-100

09/11/2026

D. JOHNSON

M. STEARNS

C V G

V A U

L T

A

N D

S O

U T H

A R F F G

E N

E R A T O

R U

P G

R A D

E S

C

IN

C

IN

N A T I

N

O R T H

E R N

K E N

T U

C K Y I

N T E R N

A T

IO

N A L A

IR

P O

R T

N

E W

P R

IC

E P

IK

E A

N D

T

O W

E R D

R

IV

E

E R L A N

G E R K Y

V A U

L T

E

L E V A T

IO

N S

OCVG25-05

BID AND PERMIT

1/4" = 1'-0"G-V-100

EAST TO WEST ELEVATION - REGULATOR ROOM #25

1/4" = 1'-0"G-V-100

NORTH TO SOUTH ELEVATION - VAULT 121

1/4" = 1'-0"G-V-100

EAST TO WEST ELEVATION - VAULT 123

1/4" = 1'-0"G-V-100

SOUTH TO NORTH ELEVATION - VAULT 122

1/4" = 1'-0"G-V-100

WEST TO EAST ELEVATION - ATS ROOM (OLD GENERATOR ROOM)4

OPENINGS LESS THAN 24" IN HEIGHT:

INFILL EXISTING OPENING WITH CMU TO MATCH EXISTING WYTHE (8" +/- FIELD VERIFY) AND BRICK VENEER TO MATCH EXISTING. BRICK INFILL TO

BE FLUSH WITH EXISTING.

OPENINGS 32" OR GREATER IN HEIGHT:

INFILL EXISTING OPENING WITH CMU TO MATCH EXISTING WYTHE (8" +/- FIELD VERIFY) AND BRICK VENEER TO MATCH EXISTING. BRICK INFILL TO BE FLUSH WITH EXISTING. PROVIDE MASONRY TIES AT 16" O.C. VERTICALLY TYING NEW CMU TO EXISTING AT JAMBS. PROVIDE BRICK TIES AT 16"

O.C. HORIZONTALLY AND VERTICALLY.

OPENINGS MARKED WITH X:

OPENINGS MARKED WITH AN “X” ARE EXISTING TO REMAIN. DO NOT DEMOLISH OR REMOVE ANY EQUIPMENT WITHIN THESE OPENINGS. REFER

TO MECHANICAL AND ELECTRICAL DRAWINGS.

CONTRACTOR TO MAKE MEASUREMENTS PRIOR TO PRICING AND ORDERING OF MATERIALS, THESE DIMENSIONS ARE ALL ESTIMATIONS.

CONTRACTOR TO TRY AND REUSE EXISTING MATERIAL FROM NEW PENETRATIONS/OPENINGS TO INFILL OLD PENETRATIONS/OPENINGS.

MASONRY WALL PATCH NOTES

SD

UON

EM

CFOI

OFOI

CFCI

OFCI

J

DESCRIPTION

S

OS

GROUND FAULT PROTECTED DUPLEX WITH

WEATHER-PROOF "WHILE IN USE" TYPE DIE-CAST

METAL COVERPLATE WITH LOCKABLE

ENCLOSURE AT OUTLET - SEE SPECIFICATIONS

WP

DOOR RELEASE PUSH-PLATE / INFRA-RED OPERATOR

STATION. PROVIDE ANY ADDITIONAL ROUGH-IN FOR

''EMERGENCY RELEASE'' OPERATOR STATIONS AS

REQUIRED.

DOOR RELEASE CARD READER STATION. PROVIDE

ANY ADDITIONAL ROUGH-IN FOR ''EMERGENCY

RELEASE'' OPERATOR STATIONS AS REQUIRED.

SLASH THROUGH ANY DEVICE INDICATES MOUNTING

ABOVE COUNTERTOP 2" ABOVE BACKSPLASH, OR AT

48" WHERE NO COUNTER IS PRESENT

VS

FILLED CENTER BAR INDICATES INTEGRAL GROUND

FAULT PROTECTION (GFCI)

NON-REVERSING MOTOR STARTER SNAP SWITCH

CONTRACTOR FURNISHED OWNER INSTALLED

CONTRACTOR FURNISHED CONTRACTOR INSTALLED

OWNER FURNISHED OWNER INSTALLED

OWNER FURNISHED CONTRACTOR INSTALLED

PHOTO-ELECTRIC SMOKE DETECTOR

MAIN CONTROL PANEL CENTRAL PROCESSING

UNIT (CPU)

DOOR POWER SUPPLY

LIGHT SWITCH:GENERAL PURPOSE

AS NOTED

6'-6'' TO

TOP

46" TO

LEVER

PULL STATION : DOUBLE ACTION

AUDIO/VISUAL NOTIFICATION APPLIANCE

HEAT DETECTOR

DUCT SMOKE DETECTOR

UNLESS OTHERWISE NOTED

INDICATES EMERGENCY POWER

HD

ABV CLG DD

ABBREVIATIONS

STRIP FIXTURE

PARALLEL-HATCHING INDICATES LIGHT IS

POWERED FROM THE EMERGENCY-LIFE SAFETY

BRANCH

POWER OUTLETS

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE

QUADRUPLEX RECEPTACLE

JUNCTION BOX, CEILING OR WALL

VOLTAGE/1PH RECEPTACLE, AS NOTED

VOLTAGE/3PH RECEPTACLE, AS NOTED

OCCUPANCY OR VACANCY SENSOR, CEILING MOUNT

EXIT LIGHT (CEILING, END, WALL MOUNT)

LIGHTING

SECURITY ACCESS CONTROL

DOOR RELEASE KEYPAD STATION

MOTION SENSOR DOOR CONTROL

WALL, CLG

CLG

CLG

46"

1'-6"

1'-6"

1'-6"

1'-6"

1'-6"

2'-2"

CLG

AS NOTED

46''

46''

46''

CEIL.

S M

M O

U N

T

IN

G H

E

IG

H T

(T O

C E

N T

E R

O F

B O

X

D R

A W

IN

G

S

Y M

B O

L

WALL MOUNT FIXTURE ,

F

F

ADDRESSABLE RELAY MODULE R

ABV CLG

ELECTRIC STRIKE AT LATCH

WP

WGWIREGUARD - PROVIDE MANUFACTURER'S

SPECIFIC GUARD FOR DEVICE NOTED

CONDUIT CONCEALED IN WALLS OR IN CEILING

SPACE: ARROW(S) INDICATE(S) HOME RUN & #

OF CIRCUITS: HASHMARKS INDICATE # OF

CONDUCTORS. DASHED LINE INDICATES

CONDUIT BELOW FLOOR.

PANELBOARD, SURFACE OR FLUSH MOUNTED,

HATCHING INDICATES EMERGENCY

EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE

MECHANICAL EQUIPMENT DESIGNATOR

(SEE MECH. SCHEDULES)

EQUIPMENT HARDWIRE CONNECTION (SEE DETAIL)

AS NOTED

AS SHOWN

MISCELLANEOUS

DISCONNECT SWITCH

MAGNETIC STARTER

MAGNETIC COMBINATION STARTER

ENCLOSED FLUSH MTD. CIRCUIT BREAKER

WEATHERPROOF - NEMA-3R, WET LOCATION LISTED.

PROVIDE COVERS, RATINGS, ETC, AS SUITABLE FOR

OUTDOORS.

PUSHBUTTON STATION

FLEXIBLE CONDUIT

TRANSFORMER

TAGGED NOTE

REVISION TAG

WIRE BASKET CABLE TRAY, SIZE AS NOTED

LOW VOLTAGE CABLE PATH

5'-0"

5'-0"

5'-0"

5'-0"

46"

6'-6'' TO TOP

GENERATOR ANNUNCIATOR PANEL - SEE

SPECIFICATIONS

46''

THERMOSTAT PROVIDED BY MECHANICAL

CONTRACTOR, ELECTRICAL CONTRACTOR SHALL

PROVIDE BACK-BOX CONDUIT STUB-UP, REFER TO

MECHANICAL DRAWINGS FOR LOCATIONS

SWITCHES

FIRE ALARM

E,EMINDICATES EMERGENCY POWER

PUSH-TO-EXIT BUTTON 46'' PE

GEN-A

J

ES

KP

MS

PP

CR

DS

FACP

T

AS SHOWNLADDER CABLE TRAY, SIZE AS NOTED

AS SHOWNSOLID BOTTOM CABLE TRAY, SIZE AS NOTED

EQUIP-1

GROUND

NEUTRAL

PHASE

F

, J

VARIABLE FREQUENCY DRIVE 5'-0"

MOTOR CONNECTION, REFER TO EQUIPMENT

CONNECTION SCHEDULE

CONDUIT UP

CONDUIT DOWN

GROUND BUS BAR ON INSULATED STANDOFFS 2'-0''

DESCRIPTION M

O

U N

T

IN

G H

E

IG

H T

(T O

C E

N T

E R

O F

B O

X

D R

A W

IN

G

S

Y M

B O

L

REFER TO LUMINAIRE SCHEDULE FOR EXACT FIXTURE

SPECIFICATIONS, MOUNTING HEIGHTS, ETC.

W H

IT

E

DEVICE

DEVICE COLOR

MATRIX

RECEPTACLE (NORMAL)

THERMOSTATS (COORDINATE WITH HVAC TYPICALLY NO

COLOR OPTIONS)

DEVICE COLOR GENERAL NOTES:

A. DEVICE PLATE TO MATCH DEVICE UNLESS NOTED OTHERWISE.

B. NOT ALL DEVICES MAYBE USED THAT ARE SHOWN.

C. IF DEVICE COLOR NOT DEFINED REFER TO SPECIFICATIONS.

DESCRIPTION

IV

O

R Y

R E

D

B L

A C

K

B L

U E

Y E

L L O

W

C U

S T

O M

S T

A

IN

L E

S S

S T

E E

L

LEGEND

INDICATES SELECTED COLOR

INDICATES COLOR NOT AVAILABLE

INDICATES COLOR NOT SELECTED

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

1100 SYCAMORE STREET

CINCINNATI, OH 45202

T: (513)429-4404

C

U se rs \M

S te a rn s\ D o cu m e n ts

\O C V G

-0

M

E P R m st e a rn sA S

JS

M .r v t

/9

/2

:0 :1

A

M

E-000

09/11/2026

D. JOHNSON

M. STEARNS

C V G

V A U

L T

A

N D

S O

U T H

A R F F G

E N

E R A T O

R U

P G

R A D

E S

C

IN

C

IN

N A T I

N

O R T H

E R N

K E N

T U

C K Y I

N T E R N

A T

IO

N A L A

IR

P O

R T

N

E W

P R

IC

E P

IK

E A

N D

T

O W

E R D

R

IV

E

E R L A N

G E R K Y

E L E C T R

IC

A L L

E G

E N

D

OCVG25-05

BID AND PERMIT

ELECTRICAL GENERAL NOTES:

A. EACH CONTRACTOR, PROPOSER, SUPPLIER AND/OR MANUFACTURER SHALL REFER TO ALL DOCUMENTS PERTAINING TO THIS PROJECT AND

COORDINATE ACCORDINGLY SO AS TO ENSURE ADEQUACY OF FIT, COMPLIANCE WITH SPECIFICATIONS, PROPER VOLTAGE AND CURRENT CHARACTERISTICS TO AVOID CONFLICT WITH ANY OTHER BUILDINGS SYSTEMS. VERIFY SAME WITH SHOP DRAWINGS.

B. ADDITIONAL ELECTRICAL REQUIREMENTS MAY BE SHOWN ON PLANS FROM OTHER DISCIPLINES IN THIS SET. IT IS THE CONTRACTOR’S RESPONSIBILITY TO REVIEW ALL PLANS AND SPECIFICATIONS FOR A COMPLETE UNDERSTANDING OF THE PROJECT REQUIREMENTS.

C. WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF ALL LOCAL, STATE, AND NATIONAL CODES. INCLUDING BUT NOT LIMITED TO NFPA 70

(NEC), NFPA 72, INTERNATIONAL BUILDING CODES, ETC.

D. CONTRACTOR SHALL FOLLOW SEISMIC RESTRAINT AND DESIGN REQUIREMENTS CONTAINED IN LATEST ADOPTED STATE AND INTERNATIONAL BUILDING CODES, WITH ALL AMENDMENTS AS ADOPTED BY THE CURRENT LEGISLATION. REFER TO ELECTRICAL AND STRUCTURAL SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

E. ALL OFFSETS, TURNS, FITTINGS, TRIM, DETAIL, ETC. MAY NOT BE INDICATED, BUT SHALL BE PROVIDED AS REQUIRED. ADDITIONAL ALLOWANCES SHALL

BE INCLUDED FOR SAME AT EACH PROPOSER’S DISCRETION.

F. INSTALL NO PIPING, CONDUIT, DUCTWORK, ETC. IN A LOCATION OR IN A MANNER WHICH WILL ALLOW FREEZING OR THE COLLECTION OF

CONDENSATION THEREON. IF IN DOUBT, CONTACT THE ENGINEER.

G. ADVISE THE ENGINEER OF ANY CONFLICTS, ERRORS, OMISSIONS, ETC. AT LEAST TEN DAYS PRIOR TO BID DATE, TO ALLOW CLARIFICATION BY WRITTEN

ADDENDUM.

H. WHERE CONFLICTS ARE FOUND BETWEEN DRAWINGS, DETAILS, OR SPECIFICATIONS, THE MORE STRINGENT REQUIREMENT SHALL APPLY. NOTIFY

ARCHITECT OF DISCREPANCY IN WRITING.

I. DEVIATION FROM SPECIFICATIONS OR PLANS REQUIRES PRIOR WRITTEN APPROVAL FROM THE ENGINEERS AND MUST BE SUBMITTED IN WRITING NO

LATER THAN TEN DAYS PRIOR TO THE BID DATE.

J. OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS THAT MAY APPLY TO THE WORK UNDER THIS CONTRACT. (CITY, COUNTY, LOCAL, STATE, FEDERAL, MUNICIPALITY, UTILITY COMPANY, OSHA, ETC.).

K. MOUNTING HEIGHTS FOR WALL MOUNTED DEVICES INDICATED ABOVE FINISHED FLOOR ARE TO CENTER OF DEVICE UNO. MOUNTING HEIGHTS TO

CEILING SUSPENDED DEVICES ARE TO BOTTOM OF DEVICE UNO.

L. INSTALL EQUIPMENT, MATERIALS, ETC. IN STRICT ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS AND DIRECTIONS. IF IN CONFLICT WITH THE DESIGN INDICATED IN CONTRACT DOCUMENTS, ADVISE THE ENGINEER PRIOR TO INSTALLATION FOR CLARIFICATION.

M. DO NOT RECESS PANELBOARD TUBS OR OTHER FLUSH-MOUNTED EQUIPMENT IN WALLS THAT HAVE A FIRE RATING. NO INSTALLATION SHALL DIMINISH

OR VOID FIRE RESISTIVE RATINGS IN ANYWAY.

N. THE PURPOSE AND INTENT OF ALL OF THE DOCUMENTS PERTAINING TO THIS PROJECT IS TO PROVIDE A COMPLETE, FUNCTIONAL, SAFE, LIKE-NEW

FACILITY. ANYTHING LESS SHALL BE UNACCEPTABLE.

O. ALL SYSTEMS, EQUIPMENT AND MATERIALS ARE TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. WORK NOT MEETING THIS CRITERION SHALL BE REMOVED AND REINSTALLED SATISFACTORILY. FINAL DETERMINATION OF THE ACCEPTABILITY OF THE QUALITY OF WORK RESIDES WITH THE

ENGINEER

P. ALL WORK, MATERIALS, EQUIPMENT, ETC. SHALL BE FULLY GUARANTEED FOR ONE FULL CALENDAR YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION AS DOCUMENTED BY THE ENGINEER, UNLESS LONGER WARRANTY PERIODS FOR EQUIPMENT ARE SPECIFIED.

Q. UNLESS OTHERWISE SPECIFIED OR INDICATED, ALL EQUIPMENT AND/OR MATERIALS WITHIN OCCUPIED SPACES OR EXPOSED TO VIEW ON THE BUILDING EXTERIOR SHALL BE PRIMED AND FINISHED SO AS TO COMPLEMENT ADJACENT SURFACE, UNLESS OTHERWISE NOTED. COORDINATE WORK

AND COLORS WITH ARCHITECT.

R. WHERE PENETRATING ROOFING MEMBRANE OR OTHER MATERIALS USED FOR WEATHERPROOFING THE BUILDING, MAKE SUCH PENETRATION IN A WAY THAT WILL NOT VOID OR DIMINISH THE ROOFING WARRANTY OR INTEGRITY IN ANYWAY. COORDINATE ALL SUCH PENETRATIONS WITH THE ROOFING

MANUFACTURER AND ARCHITECT.

S. THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY COMPANY FEES, CASH CONTRIBUTIONS OR OTHER COSTS THAT THE UTILITY COMPANY MAY

REQUIRE TO COMPLETE THEIR WORK. (ELECTRIC, TELEPHONE, TELEVISION, DATA, ETC.).

T. COORDINATE WITH ARCHITECTURAL FLOOR PLANS, ELEVATIONS AND CASEWORK DETAILS FOR LOCATION OF ADDITIONAL RECEPTACLES, UTILITY

OUTLETS, ELECTRICAL DEVICES, ETC.

U. CEILING-MOUNTED ELECTRICAL DEVICES SHALL BE CENTERED IN 2'X2' CEILING TILE AND INSTALLED CENTERED ON 2' DIMENSION OF 2'X4' TILE AND ON

CENTERLINE OR A QUARTER POINT ON 4' DIMENSION.

V. ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION PRODUCING EQUIPMENT SHALL BE ISOLATED FROM SURROUNDING SYSTEMS IN AN APPROVED MANNER. NOISY OR STRUCTURALLY DAMAGING INSTALLATIONS SHALL BE SATISFACTORILY REPLACED OR REPAIRED AT THE INSTALLING CONTRACTORS' EXPENSE. THE FINAL DECISION ON THE SUITABILITY OF A PARTICULAR INSTALLATION'S ACCEPTABILITY SHALL BE THAT OF THE

ENGINEER.

W. CHECK ALL THREE PHASE MOTORS WITH A PHASE ROTATION METER, PRIOR TO PLACING IN SERVICE.

X. PROVIDE DETAILED SHOP DRAWINGS TO ENGINEER PRIOR TO PURCHASING OR INSTALLING ANY EQUIPMENT Y. DEVIATIONS IN SIZES, CAPACITIES, FIT, FINISH, ETC. FOR EQUIPMENT FROM THAT PRIME SPECIFIED SHALL BE THE RESPONSIBILITY OF THE PURCHASER

OF THAT EQUIPMENT. ANY PROVISIONS REQUIRED TO ACCOMMODATE A DEVIATION, WHETHER APPROVED BY THE ENGINEER OR NOT, SHALL BE THE

RESPONSIBILITY OF THE PURCHASER.

Z. THE CONSTRUCTION MANAGER, GENERAL CONTRACTOR, OR WHOMEVER HOLDS THE PRIME CONTRACT(S) FOR THIS CONSTRUCTION IS RESPONSIBLE FOR THE COORDINATION, APPEARANCE, SCHEDULING AND TIMELINESS OF THE WORK OF ALL TRADES, CONTRACTORS, SUPPLIERS, INSTALLERS, ETC.

POOR OR UNTIMELY WORK ON THE PART OF ANY SUBCONTRACTOR SHALL BE RESOLVED BY THE PARTY WHO ENGAGED THEM ON THIS PROJECT.

AA. WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN CONFLICT WITH ANY OTHER BUILDING SYSTEM, CONTACT THE ENGINEER BEFORE AFFECTING INSTALLATION. REFER ALSO TO ARCHITECTURAL INTERIOR AND EXTERIOR ELEVATIONS, CEILING HEIGHTS AND OTHER DETAILS OF THESE

DOCUMENTS, AS APPLICABLE.

BB. WHERE FIRE-RATED CEILING ASSEMBLIES ARE NOTED, PROVIDE UL-LISTED FIRE-RATED GYPSUM BOARD OR PRE-MANUFACTURED ENCLOSURES ABOVE LUMINAIRES, CEILING DEVICES, ETC. IN OR ON CEILING, AS REQUIRED TO MAINTAIN CEILING RATINGS.

CC. COORDINATE THE LOCATION OF DRAINS, ELECTRICAL OUTLETS, GAS OUTLETS, ETC. WITH ALL CASEWORK, KITCHEN EQUIPMENT, MECHANICAL ROOM EQUIPMENT, ETC. PRIOR TO COMMENCING INSTALLATION. WORK NOT SO COORDINATED SHALL BE REMOVED AND PROPERLY INSTALLED AT THE

EXPENSE OF THE RESPONSIBLE CONTRACTOR(S).

DD. ALL ELECTRICAL COMPONENTS OR EQUIPMENT SHALL BE LISTED AND LABELED BY UNDERWRITER'S LABORATORIES OR OTHER APPROVED LISTING AGENCY. APPROVAL AND LABELING OF INDIVIDUAL COMPONENTS ON AN ASSEMBLY IS NOT ACCEPTABLE AS MEETING THIS REQUIREMENT, UNLESS

WAIVED BY THE ENGINEER IN WRITING.

EE. ALL WIRING SYSTEMS SHALL BE INSTALLED WITH A MINIMUM OF SPLICES. CONDUCTORS, WHETHER SINGLE OR MULTI-PAIR, SHALL BE INSTALLED

CONTINUOUS INSOFAR AS POSSIBLE FROM TERMINAL POINT TO TERMINAL POINT.

FF. NO CONDUIT, SUPPORTS, ETC. SHALL BE RUN THROUGH ACCESS CLEARANCES OF EQUIPMENT BY OTHER TRADES (I.E. VAV BOXES). COORDINATE WITH

ALL TRADES PRIOR TO CONSTRUCTION.

GG. ALL CONTRACTORS SHALL EXERCISE EXTREME CARE IN THE COURSE OF THEIR WORK SO AS TO ENSURE THAT THEY DO NOT INTERRUPT ANY EXISTING SERVICE OR SUB-SERVICE FOR SAFETY PURPOSES. PAY PARTICULAR ATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL GAS AND ELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC. OF EACH UNDERGROUND OR OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL FEDERAL, STATE AND/OR LOCAL RULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS. UTILITIES SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THE MOST STRINGENT

REQUIREMENT SHALL APPLY.

HH. ALL SUPPORTS FOR EQUIPMENT, DEVICES OR FIXTURES SHALL BE UNIQUE, DIRECTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT WORK FROM OTHER TRADES EQUIPMENT OR SUPPORTS WITHOUT WRITTEN PERMISSION FROM THE ENGINEER AND CONSENT OF THE OTHER TRADE, IN

WRITING.

II. WHERE INTERRUPTING AN EXISTING UTILITY OR SERVICE DELIBERATELY OR ACCIDENTALLY, THE RESPONSIBLE CONTRACTOR SHALL WORK

CONTINUOUSLY AS NEEDED TO RESTORE SAME, PROVIDING PREMIUM TIME AS NEEDED.

JJ. REFER TO ARCHITECTURAL WALL ELEVATIONS (WHERE GIVEN) FOR HEIGHTS AND MOUNTING RELATIONSHIP OF OUTLETS AND EQUIPMENT. IF IN

DOUBT, CONTACT ENGINEER FOR DIRECTION PRIOR TO ROUGH IN.

KK. FLUSH OR PEDESTAL TYPE FLOOR OUTLETS/BOXES, AS INDICATED ON PLAN, SHALL BE LOCATED BY DIMENSIONS PROVIDED BY THE ARCHITECT, UNLESS OTHERWISE SHOWN ON PLANS. IF IN DOUBT, CONTACT THE ENGINEER PRIOR TO ROUGHING-IN ANY WORK.

LL. AS APPLICABLE, REFER TO ARCHITECTURAL PHASING PLANS AND PHASING BOUNDARIES ON THESE DRAWINGS FOR SEQUENCING OF WORK, FULL EXTENT OF AREAS INVOLVED, EXTENT OF CEILING WORK, ETC. PROVIDE TEMPORARY CONNECTIONS FOR CIRCUITS AND WORK AS REQUIRED TO

MAINTAIN SEQUENCE OF THE WORK FROM PHASE TO PHASE.

MM. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR HIS WORK. ALL CUTTING AND PATCHING SHALL BE IN

ACCORDANCE WITH THE ARCHITECT'S STANDARDS FOR SUCH WORK.

NN. ALL WORK SHALL BE CONCEALED UNLESS SPECIFICALLY INDICATED TO BE EXPOSED, OR REQUIRED TO BE EXPOSED. IF IN DOUBT, CONTACT THE

ENGINEER FOR CLARIFICATIONS PRIOR TO INSTALLING ANY SUCH WORK.

OO. INTERRUPTION OF ANY EXISTING SERVICES SHALL BE COORDINATED WITH THE OWNER, GENERAL CONTRACTOR, UTILITY COMPANY AS NECESSARY, AND THE ARCHITECT, AT LEAST TWO WEEKS IN ADVANCE OF ANTICIPATED INTERRUPTION. A SCHEDULE FOR THESE OUTAGES SHALL BE DEVELOPED AND AGREED UPON BETWEEN THE PARTIES MENTIONED TO AVOID UNNECESSARY INCONVENIENCE TO THE OWNER OR ANY AFFECTED PARTY. NOTIFY THE UTILITY COMPANY OF ANY ANTICIPATED SERVICES REQUIRED TWO WEEKS IN ADVANCE, IN WRITING. IF UTILITY COMPANY REQUIRES A LONGER

NOTIFICATION PERIOD, SO PROVIDE.

PP. WHERE BACKBOXES ARE LOCATED IN THE SAME VERTICAL CHANNEL/STUD SPACE ON OPPOSITE SIDES OF THE SAME WALL, PROVIDE SOUND- INSULATING PUTTY AROUND BOXES AS REQUIRED TO ELIMINATE SOUND TRANSMISSION FROM ROOM TO ROOM.

QQ. JUNCTION BOXES LOCATED ABOVE ACCESSIBLE CEILINGS SHALL BE LOCATED NO MORE THAN 36” ABOVE CEILING LEVEL. LABEL EACH BOX IN AREA OF WORK WITH A PERMANENT MARKER OR IN ACCORDANCE WITH SPECIFICATIONS, WHICHEVER IS MORE STRINGENT.

RR. ALL MATERIALS FURNISHED AND ALL WORK INSTALLED SHALL COMPLY WITH THE CURRENT EDITION OF THE NATIONAL ELECTRICAL CODES, NATIONAL FIRE CODES OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE REQUIREMENTS OF LOCAL UTILITY COMPANIES, AND WITH THE REQUIREMENTS OF ALL GOVERNMENTAL AGENCIES OR DEPARTMENTS HAVING JURISDICTION. IF ANY CONFLICTS OR DISCREPANCIES OCCUR THE MOST STRINGENT SHALL

APPLY.

SS. DO NOT SCALE FROM DRAWINGS, AS PRINTING DISTORTS SCALE. WORK SHALL BE LAID OUT FROM DIMENSIONED DRAWINGS, OR DIMENSIONS

SUPPLIED TO THE CONTRACTOR.

TT. NOISY WORK, WORK OUTSIDE CONSTRUCTION BARRIERS, WORK IN OCCUPIED AREAS, ETC. SHALL BE PERFORMED AFTER HOURS OR ON WEEKENDS.

COORDINATE EXACT SCHEDULING WITH FACILITY PRIOR TO CONSTRUCTION.

UU. ALL ITEMS HAVING KEYED LOCKS/OPERATORS SHALL HAVE CORED LOCKS/OPERATORS. ALL KEYING SHALL MATCH THE OWNER'S EXISTING KEY-WAYS.

COORDINATE EXACT REQUIREMENTS WITH OWNER PRIOR TO CONSTRUCTION.

VV. REFER TO ARCHITECTURAL PLANS FOR PHASING REQUIREMENTS. WORK SHALL BE COMPLETED IN PHASES PER THE PHASING PLAN AND AS COORDINATED WITH OWNER AND GENERAL CONTRACTOR. PROVIDE ALL REQUIRED INCREMENTAL INSPECTIONS, CERTIFICATIONS, ETC. AND ALL

TEMPORARY SERVICES AS REQUIRED BY OWNER TO ACCOMPLISH THE PHASING PLAN.

ELECTRICAL DEMOLITION NOTES:

A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINES INDICATE EXISTING ITEMS TO

REMAIN.

B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR

EQUIPMENT THAT ARE TO REMAIN. WHEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAWINGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM" ON THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" WORKING ORDER. "LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR

PANELS. PROVIDE NEW TYPEWRITTEN DIRECTORIES FOR ALL PANELS AFFECTED.

C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING CONDITIONS.

CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT

THEY MAY COMPLETE ALL WORK REQUIRED FOR THE BID WHICH HE PROPOSES.

D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE), WHETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND REPAIR ANY EXISTING WALLS, FLOORS OR CEILINGS WHERE DEVICES ARE SHOWN TO BE REMOVED (PATCH AND

REPAIR TO RECEIVE NEW FINISHES - SEE ARCHITECTURAL PLANS).

E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION) WITH OWNER. TURN

OVER ITEMS REMOVED TO OWNER AT THEIR OPTION.

F. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/OR RELOCATION OF ELECTRICAL DEVICES AND

CONNECTIONS ASSOCIATED WITH THEIR EQUIPMENT.

G. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION BARRIERS AS REQUIRED.

H. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS / CEILINGS AS REQUIRED WHERE DEVICES ARE

BEING REMOVED OR INSTALLED.

I. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE CEILINGS SHALL BE REMOVED IN

ACCORDANCE WITH NEC REQUIREMENTS.

J. EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH CONSTRUCTION SHALL BE RELOCATED TO PERMIT

INSTALLATION OF DEVICES AND EQUIPMENT SHOWN ON PLANS.

K. CONTRACTOR SHALL SEAL ALL EXISTING AND NEW PENETRATIONS OF BUILDING ENVELOPE (EXTERIOR WALLS, ROOF, ETC.) WATER-TIGHT AND AS APPROVED BY ARCHITECT AND ENGINEER. ROOFING SHALL BE RESTORED BY A LICENSED ROOFING CONTRACTOR BASED ON WRITTEN INSTRUCTIONS AND DETAILS FROM ROOFING MANUFACTURER AS REQUIRED TO MAINTAIN ROOF WARRANTY. REFER TO ARCHITECTURAL AND ENGINEERING

PLANS AND SPECIFICATIONS FOR FURTHER REQUIREMENTS.

L. DEVICES INDICATED WITH AN ''R'' SHALL BE RELOCATED. REMOVE, PROTECT, AND REINSTALL IN NEW LOCATION INDICATED ON NEW WORK PLANS. INTERCEPT AND EXTEND ALL EXISTING CABLING TO NEW

LOCATION. CLEAN AND RE-LAMP RELOCATED LUMINAIRES.

M. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S WORK SHALL BE PROVIDED WITH NEW TYPE- WRITTEN PANEL DIRECTORIES AND INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES OR NUMBERS FROM THESE DRAWINGS. DIRECTORIES SHALL BE DETAILED AND COORDINATED WITH OWNER'S SUITE NUMBERS, FINAL ROOM NUMBERS, IT RACK NAMES, WORKSTATION DESIGNATIONS, ETC. UNUSED

BREAKERS SHALL BE IN OFF POSITION.

GENERAL NOTES (POWER):

A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS, AND CASEWORK DETAILS FOR EXACT

LOCATIONS OF ALL WALL AND CEILING MOUNTED ELECTRICAL DEVICES.

B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATED ON THE FLOOR PLANS, WITH A

MAXIMUM OF THREE (3) BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE PROVIDED WITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME CONDUIT WITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIWIRE BRANCH CIRCUITS AS DEFINED IN NEC 100 /

210.4 (CIRCUITS SHARING A COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.

C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES, SWITCHES, ETC. IN AREA OF

CONSTRUCTION. PROVIDE CLEAR ADHESIVE LABELS WITH BLACK LETTERING.

D. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS SHALL BE COORDINATED WITH MECHANICAL AND PLUMBING CONTRACTORS TO ENSURE ACCESS AND WORKING CLEARANCE IS MAINTAINED PER NEC. NOTIFY OTHER TRADES OF REQUIRED CLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS IN THESE AREAS. DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENT NAMEPLATES OR ACCESS PANELS

OR THROUGH ACCESS/MAINTENANCE CLEARANCES OF EQUIPMENT BY OTHER TRADES.

ACCESS CONTROL

ADD TRANSLUCENT FILM

PROJECT SCOPE

VAULT 12, DENOTED BY "-V"

IN THE SHEET SERIES NAMING

SOUTH ARFF, DENOTED BY "-A"

IN THE SHEET SERIES NAMING

THE CONTRACTOR AND ALL SUBCONTRACTORS SHALL

CONTACT ''KENTUCKY811" (BEFORE YOU DIG)'' AT

1-800-362-2764 OR 811 TO OBTAIN UNDERGROUND UTILITY

LOCATIONS PRIOR TO ANY CONSTRUCTION. ANY

CONTRACTOR OR SUBCONTRACTOR PERFORMING ANY

TYPE OF EXCAVATION ON THIS PROJECT TO OBTAIN AN

AUTHORIZATION NUMBER.

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

1100 SYCAMORE STREET

CINCINNATI, OH 45202

T: (513)429-4404

C

U se rs \M

S te a rn s\ D o cu m e n ts

\O C V G

-0

M

E P R m st e a rn sA S

JS

M .r v t

/9

/2

:0 :2

A

M

E-001

09/11/2026

D. JOHNSON

M. STEARNS

C V G

V A U

L T

A

N D

S O

U T H

A R F F G

E N

E R A T O

R U

P G

R A D

E S

C

IN

C

IN

N A T I

N

O R T H

E R N

K E N

T U

C K Y I

N T E R N

A T

IO

N A L A

IR

P O

R T

N

E W

P R

IC

E P

IK

E A

N D

T

O W

E R D

R

IV

E

E R L A N

G E R K Y

O V E R A L L E

L E C T R

IC

A L S

IT

E P

L A N

OCVG25-05

BID AND PERMIT

1" = 40'-0"E-001

EXISTING SITE PLAN1

GENERAL NOTES:

A. NORMAL POWER LABELS SHALL BE BLACK WITH WHITE LETTERS.

B. EMERGENCY POWER LABELS SHALL BE RED WITH WHITE LETTERS. LABEL SHOULD ALSO INCLUDE

THE WORD "EMERGENCY" IN 1/4" LETTERS.

C. EMERGENCY POWER LABELS IN HEALTHCARE APPLICATIONS SHOULD INCLUDE SYSTEM SEVERED

"LIFE SAFETY", "CRITICAL" OR "EQUIPMENT" .

D. UTILIZE SCREW-ON TYPE LAMACOID PLATES.

E. THIS DETAILS APPLIES TO ALL ELECTRICAL EQUIPMENT INCLUDING PANELS, SWITCHGEAR, DISCONNECTS, TRANSFORMERS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES (VDF'S), SPECIAL DEVICE PLATES, INVERTER, AND SIMILAR MATERIALS SHALL BE CLEARLY MARKED AS TO

THEIR FUNCTION AND USE.

TYPICAL POWER PANEL NAMEPLATE DETAIL

NO SCALE

1/2'' HIGH

LETTERS

1/4'' HIGH

LETTERS

PANEL LXW

120/208V/3PH/4W

FEED: 200 AMPS

(4) #3/0, #6 GND, 2" C.

FED FROM: MDP

NO SCALE

PUMP P-1

208V/3PH/4W

FEED: 600 AMPS

FED FROM: MDP

CKT # 6

TYPICAL EQUIPMENT NAMEPLATE

LAMACOID

NAME PLATE

1/2'' HIGH

LETTERS

1/4'' HIGH

LETTERS

LAMACOID

NAME PLATE

GENERAL FLOOR PENETRATION NOTES :

A. WHERE CONDUITS PENETRATE A FLOOR SLAB AND ARE EXPOSED, PROVIDE SQUARE 4'' HIGH CONCRETE

PAD AROUND CONDUIT SLEEVE AND EXTEND SLEEVE 4'' ABOVE PAD.

B. WHERE CONDUITS OR SLEEVES PENETRATE FLOORS IN GROUPS, THE CONCRETE PAD SHOULD BE

CONTINUOUS AROUND ALL CONDUITS OR SLEEVES.

2" EA. SIDE

CONDUIT SLEEVE 2'' LARGER IN DIAMETER

THAN CONDUIT(S) PASSING THROUGH SHALL

BE RIGID STEEL.

IF RATED FLOOR, PROVIDE CAULKING-STYLE

FIRESTOP BETWEEN SLEEVE AND WALL

MATERIAL TO ANCHOR SLEEVE AND

RESTORE RATING OF WALL PER LOCAL AUTH.

HAVING JURISDICTION.

TYPICAL CONDUIT PASSING

THROUGH A SUSPENDED FLOOR.

IF RATED FLOOR, PROVIDE REMOVABLE

FIRESTOP PILLOW (FSB OR EQUAL) IN

UL LISTED FIRESTOP ASSEMBLY TO

ALLOW FOR EASY REMOVAL AND

INSTALLATION OF NEW CABLES AND/OR

CONDUITS.

FLOOR

FIRE ALARM

AUDIO/VISUAL DEVICES

THERMOSTAT

CARBON DIOXIDE/

TEMPERATURE SENSOR

SWITCHES

FIRE ALARM

PULL STATION

TELEPHONE /

DATA OUTLET

RECEPTACLEFINISHED FLOOR

DEVICE MOUNTING DETAIL - GENERAL NOTES:

A. WHERE DEVICES OF ANY DISCIPLINE ARE LOCATED IN THE SAME GENERAL AREA ON THE PLANS AND ARE SHOWN TO BE MOUNTED AT A SIMILAR HEIGHT, ALIGN HORIZONTALLY ALONG TOP OF DEVICE BACKBOX (AS SHOWN IN DETAIL AND DESCRIBED IN KEY NOTE #2).

B. WHERE DEVICES OF ANY DISCIPLINE ARE LOCATED IN THE SAME GENERAL AREA ON THE PLANS AND ARE SHOWN MOUNTED AT DIFFERENT HEIGHTS, ALIGN VERTICALLY

ALONG THE CENTERLINE OF THE DEVICE BACKBOX (AS SHOWN IN DETAIL).

C. FOR ANY WALL OTHER THAN PAINTED GYPSUM BOARD OR CMU, DEVICE LOCATIONS MUST BE FIELD APPROVED BY ENGINEER OR ARCHITECT PRIOR TO INSTALLATION OF

FINISHES.

D. ADA REQUIRES 48" ABOVE FINISH FLOOR FOR FRONT ACCESS. SIDE REACH ACCESS ALLOWS A MAXIMUM OF 54" AND A LOW SIDE REACH OF NO LESS THAN 9" ABOVE FINISH FLOOR. ADA FRONT AND SIDE REACH ACCESS MUST BE MAINTAINED FOR NEW AND EXISTING CONSTRUCTION. NOTIFY ARCHITECT AND ENGINEER OF ANY

DISCREPANCIES.

8"

CARD READER / KEYPAD

DEVICE MOUNTING DETAIL - KEY NOTES:

1. MOUNT VISUAL NOTIFICATION APPLIANCES SO THAT ENTIRE LENS IS BETWEEN 80" AND 96" AFF. IF CEILING IS TOO LOW FOR DEVICE TO BE MOUNTED ABOVE 80", MOUNT

SO THAT THE LENS IS WITHIN 6" OF FINISHED CEILING.

2. ALIGN BACKBOXES OF DEVICES AT THE MOUNTING HEIGHT INDICATED. MEASURE TO THE CENTER OF THE BACKBOX FOR STANDARD OUTLET BOXES. NON-STANDARD BACKBOXES ARE TO BE INSTALLED SUCH THAT THE FINISHED DEVICES ARE ALIGNED ALONG THEIR RESPECTIVE CENTERLINES.

3. MOUNTING HEIGHTS SHOWN ILLUSTRATE DESIGN INTENT AND ARE TO BE FOLLOWED UNLESS CONTRADICTED BY APPLICABLE CODE. WHERE DEVICES ARE SHOWN ADJACENT TO DOOR FRAMES ON PLANS INSTALL 12" FROM FRAME TO AVOID SLUSHED SECTIONS OR BRACING. SPECIFIC DEVICES ARE SHOWN IN RELATIVE ORDER FROM DOOR FRAME; WHERE THESE DEVICES ARE NOT PRESENT AT A PARTICULAR LOCATION, ADJUST LOCATIONS CLOSER TO DOOR ACCORDINGLY.

4. THE CONTRACTOR IS TO COORDINATE ALL ROUGH-INS WITH ANY COUNTERTOPS/BACKSPLASHES/WALL PROTECTION TO AVOID CONFLICT. ALIGN DEVICE BACKBOXES IN THE BOTTOM OF THE NEXT FULL BLOCK ABOVE THE BACKSPLASH AS SHOWN. FOR NON-BLOCK WALLS ALIGN BOTTOM OF DEVICE BACKBOXES 2" ABOVE BACKSPLASH.

COORDINATE WORK WITH CASEWORK AND KITCHEN SHOP DRAWINGS ACCORDINGLY. IF CONFLICT STILL ARISES CONTACT THE ENGINEER FOR DIRECTION ON HOW TO

PROCEED.

X

COUNTERTOP (WHERE

APPLICABLE)

BACKSPLASH (WHERE

APPLICABLE)

CEILING

DOOR FRAME

(WHERE

APPLICABLE)

ADA PUSH PLATE

WALL TELEPHONES

INTERCOM CALL STATION

A/V TOUCH PANEL

F I R E

F I R E

FIRE

CASEWORK / FURNITURE

(WHERE APPLICABLE)

PP

(T O

C E

N T

E R

O F

B O

X

(T O

C E

N T

E R

O

F B

O X

PROVIDE REMOVABLE FIRESTOP PILLOW (FSB OR

EQUAL) IN UL LISTED FIRESTOP ASSEMBLY TO ALLOW

FOR EASY REMOVAL AND INSTALLATION OF NEW CABLES.

8"+, TO CLEAR

OBSTRUCTIONS

CL

2" EA. SIDE

CEILING

STRUCTURE

LOCATE SO THAT ACCESSIBLE CEILING IS AT EACH SIDE OF

SLEEVES OR PROVIDE ACCESS PANEL.

PROVIDE CAULKING-STYLE FIRESTOP BETWEEN

SLEEVE AND WALL MATERIAL TO ANCHOR SLEEVE AND

RESTORE RATING OF WALL PER LOCAL AUTH. HAVING

JURISDICTION.

SIZE CONDUIT SLEEVE (SIZE AS INDICATED) WITH

INSULATED THROAT CONDUIT TERMINATORS ON EACH

END. PROVIDE A THREADED CAP ON EACH END IF NOT

USED FOR WIRING . LINE-UP WITH "CABLE TRAY" OR ''HOOK

PATH'' WHERE APPLICABLE.

FIRE/SMOKE RATED OR UN-RATED PARTITION OF VARIOUS

CONSTRUCTIONS. REFER TO ARCHITECTURAL PLANS OR

FIELD VERIFY TYPE.

GENERAL NOTES:

A. PROVIDE ONE 2" SPARE CONDUIT SLEEVE THROUGH ALL FULL HEIGHT

PARTITIONS FOR FUTURE USE. LABEL AS SPARE FOR OWNER'S USE ONLY.

REFER TO ARCHITECTURAL PLANS FOR FULL HEIGHT PARTITION LOCATIONS.

B. USE AT ALL ''OPEN'' TYPE CABLING PENETRATIONS THROUGH WALLS, FLOORS,

ETC.

NOTE: IF THE SLEEVE SIZE AND NUMBER

INDICATED ON PLANS WILL NOT BE ADEQUATE TO

CONTAIN ALL CABLES AND STILL LEAVE 25%

SPARE CAPACITY, PROVIDE ADDLE SLEEVES AS

NEEDED TO PROVIDE THIS SPARE CAPACITY.

NOTE: BLOCK OUT

OPENINGS

IN PAD FOR CONDUITS PER

SHOP DRAWINGS.

FINISHED GRADE

PATCH EXISTING

PAVEMENT AS

NECESSARY.

GRADE BEAM AT

PERIMETER TO BE

12'' BELOW GRADE.

TURN REBAR DOWN.

3500 P.S.I CONCRETE

PAD CROWN TOP OF

PAD 1'' FOR DRAINAGE.

GENERATOR SET

WEATHERPROOF ENCLOSURE-

SEE SPECIFICATIONS.

#4 REBAR ON 12''

CENTERS EACH WAY

THROUGHOUT PAD.

3/4'' TOOLED RADIUS EDGE.

6'' AB. FIN.

GRADE.

18''

FORM GRADE BEAM ALL

AROUND PERIMETER.

SIZE GENERATOR SET PAD 6" - 36''

LARGER THAN UNIT ALL AROUND-

VERIFY EXACT DIMENSIONS WITH

SHOP DRAWINGS. AND NOTES ON

PLANS.

6'' CRUSHED STONE

6'' MIN.

6'' MIN.

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

1100 SYCAMORE STREET

CINCINNATI, OH 45202

T: (513)429-4404

C

U se rs \M

S te a rn s\ D o cu m e n ts

\O C V G

-0

M

E P R m st e a rn sA S

JS

M .r v t

/9

/2

:0 :2

A

M

E-500

09/11/2026

D. JOHNSON

M. STEARNS

C V G

V A U

L T

A

N D

S O

U T H

A R F F G

E N

E R A T O

R U

P G

R A D

E S

C

IN

C

IN

N A T I

N

O R T H

E R N

K E N

T U

C K Y I

N T E R N

A T

IO

N A L A

IR

P O

R T

N

E W

P R

IC

E P

IK

E A

N D

T

O W

E R D

R

IV

E

E R L A N

G E R K Y

E L E C T R

IC

A L D

E T A

IL

S

OCVG25-05

BID AND PERMIT

NOT TO SCALEE-500

ELECTRICAL EQUIPMENT NAMEPLATE2

NOT TO SCALEE-500

CONDUIT FLOOR PENETRATION SLEEVE INSTALLATION3

NOT TO SCALEE-500

TYPICAL WALL DEVICE MOUNTING DETAIL1

NOT TO SCALEE-500

CONDUIIT WALL SLEEVE INSTALLATION4

NOT TO SCALEE-500

GENERATOR CONCRETE PAD5

FACP

FS TS

ACCESS CONTROL

ADD TRANSLUCENT FILM

J

J

(E)TR-1

(E)LPA

(E)LPA1

UTILITY FEED

(E)SWBD

GDS

GENERATOR 1

U4

3 FEEDS

-NORMAL PRIMARY

-EMERGENCY PRIMARY

-SECONDARY FEEDER

ATS-1 NEW

THE CONTRACTOR AND ALL SUBCONTRACTORS SHALL

CONTACT ''KENTUCKY811" (BEFORE YOU DIG)'' AT

1-800-362-2764 OR 811 TO OBTAIN UNDERGROUND UTILITY

LOCATIONS PRIOR TO ANY CONSTRUCTION. ANY

CONTRACTOR OR SUBCONTRACTOR PERFORMING ANY

TYPE OF EXCAVATION ON THIS PROJECT TO OBTAIN AN

AUTHORIZATION NUMBER.

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

1100 SYCAMORE STREET

CINCINNATI, OH 45202

T: (513)429-4404

C

U se rs \M

S te a rn s\ D o cu m e n ts

\O C V G

-0

M

E P R m st e a rn sA S

JS

M .r v t

/9

/2

:0 :2

A

M

E-A-001

09/11/2026

D. JOHNSON

M. STEARNS

C V G

V A U

L T

A

N D

S O

U T H

A R F F G

E N

E R A T O

R U

P G

R A D

E S

C

IN

C

IN

N A T I

N

O R T H

E R N

K E N

T U

C K Y I

N T E R N

A T

IO

N A L A

IR

P O

R T

N

E W

P R

IC

E P

IK

E A

N D

T

O W

E R D

R

IV

E

E R L A N

G E R K Y

S O

U T H

A R F F E

L E C T R

IC

A L S

IT

E U

T

IL

IT

Y P

L A N

OCVG25-05

BID AND PERMIT

1" = 10'-0"E-A-001

SOUTH ARFF SITE UTILITY PLAN1

TAGGED NOTES

U4 GC SHALL PROVIDE SUFFICIENT EXPANSION JOINTS FOR THE

TRANSITION BETWEEN NEW AND EXISTING CONCRETE.

NEED 11"

ACCESS CONTROL

ACCESS CONTROL

900 SF

520 SF

ADD TRANSLUCENT FILM

(D) GENERATOR 1

(E)ATS-1

(E)SWBD

(E)LPA

(E)TR-1

(E)T-EMA

(E)EMB

(E)EMA

(E)DP-1

(E)EMA1

DE1

DE2

DE3

UTILITY

MEZZ A WING

UP TO WING B MEZZANINE

EXISTING MECH RM

(E)DP-1

2 SETS OF EXISTING 4" CONDUIT

E5

E5

(E)CD-XFMR

(E)CD

DE6

DE7

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

1100 SYCAMORE STREET

CINCINNATI, OH 45202

T: (513)429-4404

C

U se rs \M

S te a rn s\ D o cu m e n ts

\O C V G

-0

M

E P R m st e a rn sA S

JS

M .r v t

/9

/2

:0 :2

A

M

E-A-100

09/11/2026

D. JOHNSON

M. STEARNS

C V G

V A U

L T

A

N D

S O

U T H

A R F F G

E N

E R A T O

R U

P G

R A D

E S

C

IN

C

IN

N A T I

N

O R T H

E R N

K E N

T U

C K Y I

N T E R N

A T

IO

N A L A

IR

P O

R T

N

E W

P R

IC

E P

IK

E A

N D

T

O W

E R D

R

IV

E

E R L A N

G E R K Y

S O

U T H

A R F F D

E M

O L

IT

IO

N

P L A N

OCVG25-05

BID AND PERMIT

1" = 10'-0"E-A-100

SOUTH ARFF DEMO PLAN1

TAGGED NOTES

DE1 EXISTING ATS-1 & 2 SHALL BE REMOVED IN A MANNER THAT

ALLOWS IT TO BE RETURNED TO CVGI FOR STORAGE AND

POTENTIAL FUTURE USE.

DE2 CONTRACTOR TO DEMOLISH AND REMOVE EXISTING

UNDERGROUND GENERATOR FUEL TANK.

DE3 GENERAL CONTRACTOR TO DEMOLISH AND REMOVE EXISTING

GENERATOR IN ITS ENTIRETY ALONG WITH ALL EXISTING

EXTERIOR CONDUITS.

DE6 THE VIEW RANGE WITHIN THE ORANGE-HIGHLIGHTED BOX IS

ASSOCIATED WITH THE MEZZANINE LEVEL ABOVE. SEE NOTE E4

FOR CONTEXT ON THE OVERLAPPING OF THE FIRST FLOOR AND

MEZZANINE LEVEL.

DE7 CONTRACTOR TO DEMOLISH THE NECESSARY PORTION OF THE

EXISTING CONDUIT RUN TO INSTALL THE NEW JUNCTION BOX.

E5 DOOR TO FLOOR BELOW MEZZANINE.

FACP

FS TS

NEED 11"

ACCESS CONTROL

ACCESS CONTROL

900 SF

520 SF

ADD TRANSLUCENT FILM

J

J

(E)TR-1

(E)LPA

(E)SWBD

E3

3 FEEDS

-NORMAL PRIMARY

-EMERGENCY PRIMARY

-SECONDARY FEEDER

10' - 0"

UTILITY

GENERATOR BOD:

CUMMINS C150D6D 150kW

DIESEL WITH INTEGRAL BELLY-

TANK AND SOUND/WEATHER-

RATED (LEVEL 1) ENCLOSURE

WP

GDS

-41EMA

DINING

KITCHEN

2 SETS OF EXISTING 4" CONDUIT

UP TO WING B MEZZANINE

ATS-1 NEW E2

E5

E5

E4

E7

E6

(E)DP-1

(E)CD-XFMR

(E)CD

E1

EXISTING MECH RM

BLOCK HEATER

BATTERY CHARGER

-18EMA

-20EMA

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

1100 SYCAMORE STREET

CINCINNATI, OH 45202

T: (513)429-4404

C

U se rs \M

S te a rn s\ D o cu m e n ts

\O C V G

-0

M

E P R m st e a rn sA S

JS

M .r v t

/9

/2

:0 :2

A

M

E-A-200

09/11/2026

D. JOHNSON

M. STEARNS

C V G

V A U

L T

A

N D

S O

U T H

A R F F G

E N

E R A T O

R U

P G

R A D

E S

C

IN

C

IN

N A T I

N

O R T H

E R N

K E N

T U

C K Y I

N T E R N

A T

IO

N A L A

IR

P O

R T

N

E W

P R

IC

E P

IK

E A

N D

T

O W

E R D

R

IV

E

E R L A N

G E R K Y

S O

U T H

A R F F P

O W

E R P

L A N

OCVG25-05

BID AND PERMIT

1" = 10'-0"E-A-200

SOUTH ARFF POWER PLAN1

TAGGED NOTES

E1 NEW FEEDS ON THE EXTERIOR SIDE OF THE BUILDING ARE TO

DROP INTO THE GENERATOR DOCKING STATION (GDS), THEN

ROUTE BELOW GRADE AND RUN UNDERGROUND TO THE NEW

GENERATOR.

E2 CONTRACTOR TO FIELD-COORDINATE THE FINAL LOCATION OF THE

NEW ATS WITHIN MEZZANINE B ALONG WITH THE FINAL ROUTING

OF THE CONDUIT RUNS FROM THE SPECIFIED PENETRATION POINT

REFERENCED IN KEY NOTE E4. ENSURE ALL REQUIRED AND

APPLICABLE CODE CLEARANCES ARE MAINTAINED WITH EXISTING

EQUIPMENT PRESENT ON THE MEZZANINE.

E3 INSTALL NEW GENERATOR AND ASSOCIATED GENERATOR PAD IN

APPROXIMATE LOCATION SHOWN ON PLAN. CONTRACTOR TO

ENSURE GENERATOR IS POSITIONED A MINIMUM OF 10 FEET FROM

BUILDING STRUCTURE. REQUIRED MODIFICATIONS TO EXISTING

CONDUIT SHALL BE FIELD-COORDINATED AND COMPLETED BY

CONTRACTOR IN COORDINATION WITH ELECTRICAL CONTRACTOR.

E4 THE BOTTOM FEW FEET OF THE MEZZANINE LEVEL'S FLOOR TO

CEILING RANGE OVERLAP WITH THE UPPER FEW FEET OF THE

LEVEL 1 CEILING SPACE WHERE THE PROPOSED REWORKED

CONDUITS ARE ROUTED. THIS OVERLAP ALLOWS THE CONDUITS

TO RUN HORIZONTALLY THROUGH THE LEVEL 1 CEILING SPACE

AND EXIT THROUGH THE OTHER SIDE AT THE BASE OF THE

MEZZANINES WALL LOCATED IN THE EAST GARAGE.

E5 DOOR TO FLOOR BELOW MEZZANINE.

E6 THE VIEW RANGE WITHIN THE DASHED BOX IS ASSOCIATED WITH

THE MEZZANINE LEVEL ABOVE. SEE NOTE E4 FOR CONTEXT ON

THE OVERLAPPING OF THE FIRST FLOOR AND MEZZANINE LEVEL.

E7 PROVIDE A NEW JUNCTION BOX TO SERVE AS THE SPLIT POINT

WHERE THE TWO EXISTING CONDUIT RUNS ARE REWORKED INTO

THE NEW ATS FEEDING PLAN.

EG8

375KVA

EXISTING

DIESEL GEN

480Y/277V/3Φ/4W 600A

SWBD (MAIN ELECTRIC ROOM)

480Y/277V, 3-PHASE, 4-WIRE

600A BUSSING

DISTRIBUTION SECTION(S)

100AT/

100AF

N E

ATS-1

600A

ATS

RTU-1

480Y/277V,3Φ,4W

EMB

PANEL

225A

MCB

TX-2

TRANSFORMER

75 kVA

208Y/120V,3Φ,4W

EMA

PANEL

225A MCB

208Y/120V,3Φ,4W

KP

PANEL

100A

TR-1

TRANSFORMER

75 kVA

225AT/

400AF

208Y/120V,3Φ,4W

LPA

PANEL

225A MLO

8KVA UPS

120/240V,1Φ,3W

AOC

PANEL

80A MLO

A

A

A

A

A

A

A

A

A

A

600A600A

(2) SETS OF (4) #350MCM

(1) #1 GND

IN 4" C.

FROM UTILITY

TRANS.

(2) SETS OF (4) #350MCM

(1) #1 GND

IN 4" C.

(4) 4/0 &

(1) #6 GND IN

2-1/2" C.

(4) #1 &

GND IN

1-1/2" C.

(3) #2 &

(1) #8 GND IN

1-1/2" C.

(4) 4/0 &

(1) #6 GND IN

2-1/2" C.

(4) 4/0 &

(1) #6 GND IN

2-1/2" C.

(4) #2 &

(1) #8 GND IN

1-1/2" C.

DP-1

A

A

DP-2

A

SPARE

M

UTILITY METER

# 108 262 173

59.84KW PEAK DEMAND

(4) #1/0 THWN &

(1) #6 GND IN

2-1/2" C.

(3) #2 THWN &

(1) #8 GND IN

1-1/2" C.

SINGLE LINE TAGGED NOTES

1. DEMOLISH EXISTING ATS AND REPLACE WITH NEW ATS PER DRAWINGS.

2. DEMOLISH EXISTING GENERATOR AND REPLACE WITH NEW GENERATOR PER DRAWINGS.

3. NEW ATS-1 IS TO BE ADDED ON THE MEZZANINE LEVEL OF THE SOUTH ARFF BUILDING.

CONTRACTOR TO COORDINATE THE CONDUIT REWORK. ROUTE SHOWN ON DRAWINGS IS

PROPOSED LOCATION ONLY. SEE SHEET E-A-200 FOR FLOOR PLAN VIEW LAYOUT.

4. NEW GENERATOR IS TO BE ADDED IN THE LOCATION SHOWN ON SHEET E-A-200.

5. EXISTING FEEDS ARE TO BE RE WORKED PER SHEET E-A-200.

80AT/

100AF

T-AOC

TRANSFORMER

15 kVA

208Y/120V,3Φ,4W

EMA1

PANEL

100A

23.3KW

FROM DRAWINGS

54.72KW DEMAND FROM METER

(4) #3 &

GND IN

CU.

42.8KW FROM DRAWINGS

(3) #4 CU &

(1) #8 CU GND. IN

1-1/4" C.

(3) #4 CU &

(1) #8 CU GND. IN

1-1/4" C.

(3) #4 CU &

(1) #8 CU GND. IN

1-1/4" C.

(3) #8 CU &

(1) #10 CU GND. IN

3/4" C.

GEN

188kVA/150kW

NEW DIESEL

GENERATOR

480Y/277V/3Φ/4W 600A, LSIG

N E

ATS-1

600A

ATS

(2) SETS OF (4) #350MCM

(1) #1 GND

IN 4" C.

FEEDS TO EXISTING SWBD

IN MAIN ELECTRIC ROOM

FEED FROM EXISTING MCB

THAT IS FED OFF THE

EXISTING UTILITY FEED

EXISTING ATS-1 SHALL BE REMOVED

IN A MANNER THAT ALLOWS IT TO BE

RETURNED TO CVG FOR STORAGE

AND POTENTIAL FUTURE USE.

N E

GDS

600A

DOCKING

PLUG

CONNECTION

FOR ROLL UP

GEN SET

CONTROL WIRING

TO ATS(S) AND

ANNUNCIATOR(S)

SERVICE GROUND RODS

SERVICE GROUND UFER

PROVIDE CONCRETE PAD

AROUND GENERATOR

CONTRACTOR SHALL

CONFIRM THE

INSTALLATION OF ALL

CONTROL DEVICES WITH

THE OWNER.

CONTRACTOR SHALL

PROVIDE A TEMPORARY

GENERATOR AS REQUIRED

TO SUPPORT PROJECT

PHASING.

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

1100 SYCAMORE STREET

CINCINNATI, OH 45202

T: (513)429-4404

C

U se rs \M

S te a rn s\ D o cu m e n ts

\O C V G

-0

M

E P R m st e a rn sA S

JS

M .r v t

/9

/2

:0 :2

A

M

E-A-600

09/11/2026

D. JOHNSON

M. STEARNS

C V G

V A U

L T

A

N D

S O

U T H

A R F F G

E N

E R A T O

R U

P G

R A D

E S

C

IN

C

IN

N A T I

N

O R T H

E R N

K E N

T U

C K Y I

N T E R N

A T

IO

N A L A

IR

P O

R T

N

E W

P R

IC

E P

IK

E A

N D

T

O W

E R D

R

IV

E

E R L A N

G E R K Y

S O

U T H

A R F F E

L E C T R

IC

A L S

IN

G

L E L

IN

E

OCVG25-05

BID AND PERMIT

NOT TO SCALEE-A-600

SOUTH ARFF - ELECTRICAL SINGLE LINE - DEMO & NEW PLAN1

GENERAL NOTES (RISER):

A. PROVIDE ENGRAVED LAMACOID LABELS FOR ALL POWER DISTRIBUTION EQUIPMENT FURNISHED OR

MODIFIED IN THIS PROJECT, LABELS PER DETAILS AND SPECIFICATIONS.

B. SERVICE EQUIPMENT SHALL BE MARKED WITH THE MAXIMUM AVAILABLE FAULT-CURRENT AT THE

EQUIPMENT AND THE DATE THE CALCULATION WAS PERFORMED. APPLY A TYPE-WRITTEN

ADHESIVE LABEL WITH WHITE BACKGROUND, 1/2'' HIGH BLACK LETTERING.

C. CONTRACTOR SHALL INSTALL SEPARATE CONDUITS, PULL BOXES, ETC. FOR EACH EMERGENCY

POWER BRANCH & NORMAL POWER PER NEC FOR COMPLETE SEPARATION OF POWER SERVICES.

D. ALL CIRCUIT BREAKERS AND/OR DISCONNECTS SERVING THE PRIMARY SIDE OF A TRANSFORMER

WHICH ARE NOT WITHIN SITE OF THE TRANSFORMER SHALL BE PROVIDED WITH PERMANENTLY

INSTALLED MEANS TO LOCK THE BREAKER IN THE OFF POSITION. SUCH TRANSFORMERS SHALL

HAVE THE ROOM NAME AND NUMBER OF THE PRIMARY DISCONNECTING MEANS ENGRAVED ON THE

EQUIPMENT NAMEPLATE.

E. REFER TO SPECIFICATIONS FOR ARC FLASH AND RELATED POWER SYSTEM STUDY REQUIREMENTS.

F. REFER TO SPECIFICATIONS FOR CONDUCTOR REQUIREMENTS. ALL FEEDERS SHALL BE COPPER.

G. CURRENT CARRYING CONDUCTORS ARE SIZED FROM NEC-2023 TABLE 310.16 (75DEG C - FOR

THHW/THW/THWN INSULATION). REFER TO PROJECT SPECIFICATIONS FOR ALLOWABLE CONDUIT

AND WIRING METHODS.

H. GROUND WIRES ARE SIZED FROM NEC TABLE 250.122.

I. HVAC EQUIPMENT FEEDERS AND BRANCH CIRCUITS SHALL BE IN COPPER (UNLESS OTHERWISE

NOTED).

J. CONDUIT FILL RATES ARE BASED UPON TABLE C.10 (PVC-80 CONDUIT WITH THHN/THWN/THWN-2

WIRE). REFER TO PROJECT SPECIFICATIONS FOR ALLOWABLE CONDUIT AND WIRING METHODS.

K. CONTRACTOR SHALL CONFIRM THE INSTALLATION OF ALL CONTROL DEVICES WITH THE OWNER.

L. CONTRACTOR SHALL PROVIDE A TEMPORARY GENERATOR AS REQUIRED TO SUPPORT PROJECT

PHASING.

PROVIDE GROUND FAULT CIRCUIT INTERRUPTER TYPE CIRCUIT BREAKERGFI

A. ALL NEW PANELBOARDS SHALL BE ORDERED WITH ''DOOR-IN-DOOR'' OPTION.

B. PROVIDE LOCK-OUT TYPE CIRCUIT BREAKERS FOR ALL HARD-WIRED

EQUIPMENT. CIRCUIT BREAKERS SERVING HVAC EQUIPMENT SHALL BE HACR

TYPE.

C. PROVIDE TYPEWRITTEN SCHEDULES AT ALL PANELBOARDS. INDICATE ROOM

NUMBERS BEING SERVED BY CIRCUIT ON SCHEDULE.

D. PROVIDE SIX (4) SPARE 1'' CONDUITS STUBBED INTO ACCESSIBLE CEILING

SPACE FROM ALL NEW RECESSED PANELBOARDS.

E. PROVIDE SIX (4) SPARE 1'' CONDUITS STUBBED INTO ACCESSIBLE CEILING

SPACE OF FLOOR BELOW FROM ALL NEW RECESSED PANELBOARDS.

PANELBOARD SCHEDULE NOTES :

PANELBOARD SCHEDULE SYMBOLS :

MAIN LUG ONLYMLO

MAIN CIRCUIT BREAKERMCB

VARIABLE FREQUENCY DRIVEVFD

PROVIDE ARC-FAULT CIRCUIT INTERRUPTER TYPE CIRCUIT BREAKERAFCI

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

1100 SYCAMORE STREET

CINCINNATI, OH 45202

T: (513)429-4404

C

U se rs \M

S te a rn s\ D o cu m e n ts

\O C V G

-0

M

E P R m st e a rn sA S

JS

M .r v t

/9

/2

:0 :2

A

M

E-A-601

09/11/2026

D. JOHNSON

M. STEARNS

C V G

V A U

L T

A

N D

S O

U T H

A R F F G

E N

E R A T O

R U

P G

R A D

E S

C

IN

C

IN

N A T I

N

O R T H

E R N

K E N

T U

C K Y I

N T E R N

A T

IO

N A L A

IR

P O

R T

N

E W

P R

IC

E P

IK

E A

N D

T

O W

E R D

R

IV

E

E R L A N

G E R K Y

S O

U T H

A R F F E

L E C T R

IC

A L P

A N

E L S

C H

E D

U L E S

OCVG25-05

BID AND PERMIT

THIS IS AN EXISTING PANEL.

NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS.

TOTAL ESTIMATED DEMAND CURRENT: 0 A

TOTAL CONNECTED CURRENT: 0 A

TOTAL ESTIMATED DEMAND: 0 VA

TOTAL CONNECTED LOAD: 0 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

0 A 0 A 0 A

0.0 kVA 0.0 kVA 0.0 kVA

(E) AOC ACCESS CONTROL 20 1 41 0.0 0.0 42 1 20 (E) BACKUP AOC CPU QUAD

39 0.0 0.0 40 1 20 (E) BACKUP AOC CPU QUAD

(E) SPLIT SYSTEM 20 2

37 0.0 0.0 38 1 20 (E) BACKUP AOC CPU QUAD

(E) CORD DROP 20 1 35 0.0 0.0 36 1 20 (E) BACKUP AOC CPU QUAD

(E) BACKUP AOC CPU QUAD 20 1 33 0.0 0.0 34 1 20 (E) BACKUP AOC CPU QUAD

(E) BACKUP AOC HONEYWELL 20 1 31 0.0 0.0 32 1 20 (E) REC

(E) STORE ROOM 20 1 29 0.0 0.0 30 1 20 (E) REC

(E) ROOF TOP GFI 20 1 27 0.0 0.0 28 1 20 (E) REC

(E) MENS RR HEAT 20 1 25 0.0 0.0 26 1 20 (E) REC

(E) WOMENS RR HEAT 20 1 23 0.0 0.0 24 1 20 (E) REC

(E) BACKUP AOC RADIO CHRGERS 20 1 21 0.0 0.0 22 1 20 (E) REC

(E) BACKUP AOC WORKSTATION 20 1 19 0.0 0.0 20 1 20 (E) (L) FIRE ALARM DAMPERS

(E) HEATER IN MENS ROOM 20 1 17 0.0 0.0 18

(E) DATA RACK 20 1 15 0.0 0.0 16

2 20 (E) EQUIP (MINI SPLIT)

(E) DATA RACK 20 1 13 0.0 0.0 14 1 20 (E) REC

(E) REC 20 1 11 0.0 0.0 12 1 20 (E) REC

(E) AFCI REC 20 1 9 0.0 0.0 10 1 20 (E) AFCI REC

(E) AFCI REC 20 1 7 0.0 0.0 8 1 20 (E) AFCI REC

5 0.0 0.0 6 1 20 (E) AFCI REC

3 0.0 0.0 4 1 20 (E) REC(E) SPD 30 3

1 0.0 0.0 2 1 20 (E) REC

CIRCUIT DESCRIPTION CB... OCP P CKT A B C CKT P OCP CB... CIRCUIT DESCRIPTION

AMPERES: 100 A MOUNTING: SURFACE SUPPLY FROM: EMA

VOLTAGE: 208Y/120V,3P,4W SPD: No LOCATION: MEZZ A WING

PANEL: EMA1 MAINS TYPE: 100A MCB PANEL INTERRUPTING RATING: EXISTING PANEL

PANELBOARD AND WIRING SCHEDULE AVAILABLE FAULT CURRENT: EXISTING PANEL

THIS IS AN EXISTING PANEL. NEW ITEMS DENOTED AS BOLD.

NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS.

TOTAL ESTIMATED DEMAND CURRENT: 4 A

TOTAL CONNECTED CURRENT: 4 A

REC 180 VA 100.00% 180 VA TOTAL ESTIMATED DEMAND: 1280 VA

EQUIP 1100 VA 100.00% 1100 VA TOTAL CONNECTED LOAD: 1280 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

5 A 0 A 7 A

0.5 kVA 0.0 kVA 0.8 kVA

NEW GEN WP RECPT 20 1 41 0.2 0.0 42 1 20 (E) CORD DROP F5

(E) WATER HEATER RR/SHOWER 20 1 39 0.0 0.0 40 1 20 (E) BACKUP AOC TOWER LIGHTS

(E) F3 LADDER CORD DROP 20 1 37 0.0 0.0 38 1 20 (E) RADIO BATTERY CHARGERS

(E) CORD DROP WEST WALL 20 1 35 0.0 0.0 36

(E) CORD DROP WEST 20 1 33 0.0 0.0 34

(E) CORD DROP WEST 20 1 31 0.0 0.0 32

3 100 (E) EMA1

29 0.0 0.0 30 1 20 (E) DUPLEX WEST WALL + PIDs

27 0.0 0.0 28(E) KP 100 3

25 0.0 0.0 26

2 20 (E) SHORELINE DISASTER TRAILER

(E) CORD DROP DOOR F3 20 1 23 0.0 0.0 24

(E) RADIO 20 1 21 0.0 0.0 22

2 20 (E) AC-1

(E) RADIO 20 1 19 0.0 0.5 20 1 20 BATTERY CHARGER

(E) GATE CAMERA AND INTERCOM 20 1 17 0.0 0.6 18 1 20 BLOCK HEATER

(E) OPEN DOOR LIGHT 20 1 15 0.0 -- 16 1 -- (E) SPACE

(E) EF LOUVER 20 1 13 0.0 0.0 14 1 20 (E) F2 CORD DROP

(E) DUPLEX ALARM ROOM 20 1 11 0.0 0.0 12 1 20 (E) BAY HEATERS WEST

(E) BACKUP AOC CPU IG DUPLEX 20 1 9 0.0 0.0 10 1 20 (E) BAY HEATER WEST

(E) BACKUP AOC CPU IG DUPLEX 20 1 7 0.0 0.0 8 1 20 (E) CORD DROP BATALLION DOOR

(E) PAGING SYSTEM 20 1 5 0.0 0.0 6 1 20 (E) BACKUP AOC CPU IG DUPLEX

(E) FIRE ALARM PANEL 20 1 3 0.0 0.0 4 1 20 (E) DUPLEX AT CAPTAIN'S OFFICE

(E) DUPLEX AT TELEPHONE 20 1 1 0.0 0.0 2 1 20 (E) EX LOAD

CIRCUIT DESCRIPTION CB... OCP P CKT A B C CKT P OCP CB... CIRCUIT DESCRIPTION

AMPERES: 225 A MOUNTING: SURFACE SUPPLY FROM: T-EMA

VOLTAGE: 208Y/120V,3P,4W SPD: No LOCATION: MEZZ A WING

PANEL: EMA MAINS TYPE: 225A MCB PANEL INTERRUPTING RATING: EXISTING PANEL

PANELBOARD AND WIRING SCHEDULE AVAILABLE FAULT CURRENT: EXISTING PANEL

THIS IS AN EXISTING PANEL.

NOTES:

TOTAL EST. DEMAND CURRENT: 2 A

TOTAL CONN. CURRENT: 2 A

REC 180 VA 100.00% 180 VA TOTAL EST. DEMAND: 1 kVA

EQUIP 1100 VA 100.00% 1100 VA TOTAL CONN. LOAD: 1 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

8 (E) SPACE -- -- -- -- 3 -- -- --

7 (E) RTU-1 -- -- -- -- 3 100 A 100 A 0.0

6 (E) TR-1 -- -- -- -- 3 100 A 100 A 0.0

5 (E) SPARE -- -- -- -- 3 100 A 100 A 0.0

4 (E) T-AOC -- -- -- -- 2 100 A 40 A 0.0

3 (E) DP-2 -- -- -- -- 3 100 A 100 A 0.0

2 (E) DP-1 3 100 A 100 A 0.0

1 (E) EMB 3 200 A 125 A 1.3

CKT CIRCUIT DESCRIPTION SETS WIRE GND COND POLES FRAME TRIP LOAD (kVA) REMARKS

AMPERES: 600 A MOUNTING: FLOOR SUPPLY FROM: UTILITY

VOLTAGE: 480Y/277V,3P,4W SPD: No LOCATION: UTILITY 128

SWITCHBOARD: SWBD MAINS TYPE: 600A MCB kAIC RATING: EXISTING PANEL

SWITCHBOARD AND WIRING SCHEDULE kAIC VALUE: EXISTING PANEL

T

T

T

DD

DD

M

J

J

3W-1" #2 15 kV #6G 2W-5"

8W-5" - w/6

SETS 3 -

500 WITH A

GND.

JB1

JB2

5" 5"

IPA

(E) EXISTING 1500 kVA

OIL FILLED XFMR L-43

(PAD MTD)

(E) EXISTING 1500 kVA

OIL FILLED XFMR D-43

(PAD MTD)

TM M

(E) EXISTING 200A

MEDIUM VOLTAGE

(12,470V) SWITCH-2

L-43 (PAD MTD)

(E) EXISTING 200A

MEDIUM VOLTAGE

(12,470V)

SWITCH-1 D43

(PAD MTD)

(E) EXISTING DUKE

METERING CABINET

LIMABURG - 43 FEED

(E) EXISTING DUKE

METERING CABINET

DONALDSON - 43 FEED

3W-1" #2 15 kV #6G 2W-5"

2W-5", 3-1C #2 15 kV CABLE #6G

(E)GDSHVAC

UNIT

2W-5" CONDUITS

3 Spare 5" C3 Spare 5" C

1.5" PVC W/5 #12 LTG & RECPT

2 - 2" C 1 SPARE 1 FIRE

HVB FEEDER

FIBER / COMMUNICATION

DUCT

NAVAID DUCT BANK

HVB FEEDER

FIBER / COMMUNICATION

DUCT

NAVAID DUCT BANK

1.5" PVC W/5 #12 LTG & RECPT

NEW GENERATOR

E-V-001

INLET OUTLET

(E) CONCRETE

WALKWAY

NEW CONDUIT FROM

GENERATOR TO IPA

(E)PB12L1A

(E)TX-3

DUKE ENERGY

EQUIPMENT

U5

U6

NEW GENERATOR

BLOCK HEATER

WP

NEW FENCE

(E)GDS

HVAC

UNIT

-4PB12L1A

-6PB12L1A

-8PB12L1A

3' TYP.

U2

U1

EXISTING FENCE

EXISTING

FENCE

GENERATOR BOD:

CUMMINS DFEK 500kW DIESEL WITH

INTEGRAL BELLY-TANK (C207) AND

WEATHER-RATED ENCLOSURE

BATTERY CHARGER

THE CONTRACTOR AND ALL SUBCONTRACTORS SHALL

CONTACT ''KENTUCKY811" (BEFORE YOU DIG)'' AT

1-800-362-2764 OR 811 TO OBTAIN UNDERGROUND UTILITY

LOCATIONS PRIOR TO ANY CONSTRUCTION. ANY

CONTRACTOR OR SUBCONTRACTOR PERFORMING ANY

TYPE OF EXCAVATION ON THIS PROJECT TO OBTAIN AN

AUTHORIZATION NUMBER.

CHECKED:

DATE:

DRAWN:

F

IL

E N A M E

P L O T

T

IM

E

CLIENT/CMTA JOB #:

1100 SYCAMORE STREET

CINCINNATI, OH 45202

T: (513)429-4404

C

U se rs \M

S te a rn s\ D o cu m e n ts

\O C V G

-0

M

E P R m st e a rn sA S

JS

M .r v t

/9

/2

:0 :2

A

M

E-V-001

09/11/2026

D. JOHNSON

M. STEARNS

C V G

V A U

L T

A

N D

S O

U T H

A R F F G

E N

E R A T O

R U

P G

R A D

E S

C

IN

C

IN

N A T I

N

O R T H

E R N

K E N

T U

C K Y I

N T E R N

A T

IO

N A L A

IR

P O

R T

N

E W

P R

IC

E P

IK

E A

N D

T

O W

E R D

R

IV

E

E R L A N

G E R K Y

V A U

L T

E

L E C T R

IC

A L S

IT

E U

T

IL

IT

Y P

L A N

OCVG25-05

BID AND PERMIT

3/16" = 1'-0"E-V-001

VAULT 12 SITE UTILITY PLAN1

1/4" = 1'-0"E-V-001

ENLARGED VIEW 0F NEW GENERATOR2

TAGGED NOTES

U1 CONTRACTOR TO COORDINATE THE TWO CONCRETE REGIONS

SHOWN, WITH THE HALF-TONE AREA REPRESENTING EXISTING

CONCRETE AND THE SOLID BLACK AREA REPRESENTING THE NEW

GENERATOR PAD. REFER TO DETAIL 5 ON SHEET E-500.

U2 CONTRACTOR TO COORDINATE FENCE REWORK AS SHOWN ON

PLAN. THIS PLAN SERVES AS A GENERAL REPRESENTATION; FINAL

DIMENSIONS AND LAYOUT TO BE FIELD-COORDINATED WITH

OWNER PRIOR TO FENCE DEMO.

U5 NEW GENSET TO BE CONNECTED TO THE ALMCS SYSTEM TO

ALLOW THE TOWER TO START THE GENSET DURING ADVERSE

WEATHER CONDITIONS.

U6 CONTRACTOR SHALL COORDINATE WITH CVG, SCHNEIDER

ELECTRIC (SE), AND EATON TO PROVIDE, INSTALL, AND INTEGRATE

A NEW PM8000 (PM8214) POWER METER FOR MONITORING

GENERATOR OPERATING STATUS, POWER PARAMETERS, AND

FAULT CONDITIONS. THE PM8000 (PM8214) SHALL BE DIRECTLY

INTEGRATED WITH THE SCHNEIDER ELECTRIC POWER

MONITORING AND…