This document is Addendum One for Kenosha County's Request for Bid (RFB) #2520 for a Carwash Replacement project at the Public Safety Building, dated 8/20/2025. The addendum provides clarifications and answers to contractor questions regarding specific project details. Key points include approval of PVC wall panels as an acceptable alternative to FRP panels, and confirmation of precise measurements for pillars and electrical infrastructure within the carwash area. The project involves replacing an existing carwash system, with specifications noting a new Razor XR7 system that will allow vehicles up to 7'6" and featuring a drive-in backout configuration with no blowers.
The accompanying technical drawing provides additional spatial details, showing a ceiling height of approximately 11'8", a 15'1" wide space, and specific measurements for pillars and electrical components. The drawing indicates a pillar located 141" off the end wall that protrudes 13" into the bay and is 18" wide, with a continuous wall on the driver side. The electrical infrastructure includes an existing main disconnect with 125a 208v 3-phase power, and a pillar with a card reader and push button station. No floor heating is present in the concrete, and the project involves replacing an old Ryko inverted L system with a new WW system.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Vendor Responsibility Form Construction.pdf | ||
| 2520 Bid Documents.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFB #2520 Addendum One Page 1 of 1
Yes.
Questions and Answers:
Q. Could we have a product substation applicable to alternate 2 for the wall panels to be a PVC product instead of RFP. https://epiplastics.com/
A. Yes, a PVC panel would be acceptable. Either solution, FRP or PVC would be acceptable.
Q. Please confirm the location of the pillar that the existing push button station and card reader is on and it’s width/depth. Measuring from the other pillar would be great
A. The estimated distance from pillar to pillar is 23' 6", the pillar measures approximately 13" deep and 18" wide.
Q. Please confirm from that pillar how far away the current main disconnect is (the
208v transformer) on that same wall.
A. From edge of pillar to main disconnect is approximately 20' 4".
Q. Can you confirm there is no floor heat in the concrete?
A. There is no floor heat in the concrete.
Attachments:
Drawing confirming approximate measurements.
End Addendum 1
KENOSHA COUNTY
RFB #2520 ADDENDUM ONE DATED 8/20/2025
CARWASH REPLACEMENT AT THE PUBLIC SAFETY
BUILDING