25-Garden City Elementary BDA Signal Survey 12-1-2025.pdf
PDF 5 MB Posted
- Solicitation number
- RFP C27-03 (ESPLOST)
- Issued by
- Chatham County, Georgia
About this file
This is a BDA (Bidders' Disadvantaged Affidavit) Signal Survey document for the Garden City Elementary School Renovation Project, prepared for the Savannah-Chatham County Public School System in Georgia. The survey serves as supporting documentation for the Construction Management at Risk (CMR) Services contract opportunity (ESPLOST RFP C27-03) for the renovation of Garden City Elementary School located at 4037 Kessler Ave, Savannah, GA 31408. The document is dated December 1, 2025, and functions as a preliminary assessment tool to gauge interested firms' qualifications and intentions regarding the CMR services contract. This survey precedes the formal sealed proposal submission process and assists the District in understanding the pool of potential bidders and their capability to deliver the required services.
The signal survey serves as a market research and outreach instrument to identify qualified construction management firms interested in participating in the competitive bidding process. By collecting preliminary information from prospective bidders regarding their disadvantaged business enterprise (DBE) status and general capability, the District can assess market interest and ensure adequate competition. The survey data informs the District's procurement strategy and helps facilitate an inclusive and competitive solicitation process for the CMR services, which will be procured under the AIA Document A133 - 2019 Agreement with payment structured as Cost of the Work Plus a Fee with a Guaranteed Maximum Price.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Provided by: Southeastern System Technologies
Emergency Responder Radio System Coverage Report Test Results
Date Prepared: Dec 1, 2025
Test File: 20251124 093731
Test Location: Garden City Elementary School 4037 Kessler Avenue
Garden City, GA, 31408 Technician: Kenneth Bragg
FCC#: 0031655897
The test results set forth in this report reflect conditions at the time of testing.
Building: Garden City Elementary Result: Fail
Test Report Summary
Channel/ Ch Group
Freq (MHz) Technology Band Result Area Points passed (%)
Critical Points passed (%)
1 772.53125 P25 Savannah Primay Channel Fail 239/356 (67%)
2/3 (66%)
1 772.53125 P25 Savannah Primay Channel Fail 121/356 (33%)
1/3 (33%)
Test Details
Number of Floors Tested: 5 Result Calculation: By area per floor Number of Areas Tested: 356 Area Pass Criteria: 95% Number of Critical Points Tested: 3 Critical Points Pass Criteria: 99% Apply Adjacent Area Rule: No
Equipment Report
Vendor Application Activation ID Maintenance Date
Device Calibration Expires
Antenna info
PCTEL SeeHawk Touch rel 5.3.0.0
9b5f-5f92- 3b4c-4f95-b6c5-3e37- 8d4a-6f63
11-30-2026 SeeGull IBflex Device rel 3.14.1.0
SN:
081810036
6-11-2027
Threshold Settings
Measurement DL Area
Point DL Critical
Point DL Use for grading UL Area
Point UL Critical
Point UL Use for grading
P25 Power (RSSI) -95.00 dBm -95.00 dBm Yes -95.00 dBm -95.00 dBm Yes
P25 S/N (SINR) 20.00 dB 22.00 dB Yes 20.00 dB 22.00 dB Yes
P25 FBER 2.00 % 1.50 % Yes 2.00 % 1.50 % Yes
DAQ 3.00 Yes
Sample collection method
Measurement Sample Collection Method
P25 Power (RSSI) Max
P25 Traffic Channels Power Max
P25 Control Channels Power Average
P25 Traffic Channels SINR Average
Floors Result
Floor Plan
1 772.53125
1 772.53125
200 Fail Fail
201 Fail Fail
202 Fail Fail
203 Fail Fail
204 Fail Fail
Floor: 200 Channel: 1
Freq (MHz) Tech Band Ant Gain
Cable Loss
Ph. Type Mod NAC Area Points passed (%)
Critical Points passed (%)
772.53125 P25 Savannah Primay
Channel
0.00 0.00 55/61 (90%) 1/2 (50%)
Grid # of Areas Area Size
(sq. ft) Area Width (ft)
Area Height (ft)
Ignore Area Color
Comments
1 20 308.80 14.22 21.71 Black 2 20 193.73 14.22 13.62 Black 3 20 344.74 14.18 24.31 Black 4 5 181.69 11.00 16.52 Black
Critical Points Critical Point
DL
Power (dBm)
DL
DAQ
UL
Power (dBm)
UL
DAQ
UL
Radio
ID
UL
Tested
Result DL Loss (dB)
Comment
1 -98.44 Fail 2 -94.85 Pass
Area Points Grid Area DL
Power (dBm)
DL
DAQ
UL
Power (dBm)
UL
DAQ
Radio
ID
UL
Tested
Result DL Loss (dB)
Comment
1 1 -92.09 Pass 1 2 -87.62 Pass 1 3 -90.96 Pass 1 4 -90.50 Pass 1 5 -92.13 Pass 1 6 -99.04 Fail 1 7 -90.92 Pass 1 8 -87.88 Pass 1 9 -91.15 Pass 1 10 -90.03 Pass 1 11 -96.09 Fail 1 12 -93.03 Pass 1 13 -97.72 Fail 1 14 -95.09 Fail 1 15 -91.51 Pass 1 16 -92.50 Pass 1 17 -89.22 Pass 1 18 -85.66 Pass 1 19 -90.04 Pass 1 20 -88.97 Pass 2 1 -95.94 Fail 2 2 -93.38 Pass 2 3 -91.03 Pass 2 4 -88.87 Pass 2 5 -94.24 Pass 2 6 -87.90 Pass 2 7 -86.04 Pass 2 8 -93.68 Pass 2 9 -86.69 Pass 2 10 -91.24 Pass 2 11 -93.27 Pass 2 12 -85.97 Pass 2 13 -93.49 Pass 2 14 -90.66 Pass 2 15 -94.57 Pass 2 16 -99.33 Fail 2 17 -90.56 Pass 2 18 -92.19 Pass 2 19 -82.22 Pass 2 20 -92.52 Pass 3 1 -86.45 Pass 3 2 -86.53 Pass 3 3 -86.86 Pass 3 4 -89.32 Pass
Power (dBm)
DL
DAQ
UL
Power (dBm)
ID
UL
Tested
Result DL Loss (dB)
Comment
3 5 NT NT NT NT NT
3 6 -88.84 Pass 3 7 -85.98 Pass 3 8 -89.72 Pass 3 9 -87.80 Pass
3 10 NT NT NT NT NT
3 11 -88.09 Pass 3 12 -86.25 Pass 3 13 -87.42 Pass 3 14 -81.45 Pass
3 15 NT NT NT NT NT
3 16 -86.90 Pass 3 17 -84.88 Pass 3 18 -88.44 Pass 3 19 -81.23 Pass
3 20 NT NT NT NT NT
4 1 -80.22 Pass 4 2 -87.24 Pass 4 3 -81.53 Pass 4 4 -84.48 Pass 4 5 -86.26 Pass
Cable Loss
Ph. Type Mod NAC Area Points passed (%)
Critical Points passed (%)
772.53125 P25 Savannah Primay
0.00 0.00 1 CC CQPSK 2C0 36/61 (59%) 0/2 (0%)
Area Width (ft)
Area Height (ft)
Ignore Area Color
Comments
1 20 308.80 14.22 21.71 Black 2 20 193.73 14.22 13.62 Black 3 20 344.74 14.18 24.31 Black 4 5 181.69 11.00 16.52 Black
Point
DL
Power (dBm)
DL
S/N (dB)
DL
FBER
DL
DAQ
UL
Power (dBm)
UL
S/N (dB)
UL
FBER
UL
DAQ
UL
Radio
ID
UL
Tested
Result DL Loss (dB)
Comment
1 -102.69 17.20 0.00 Fail 2 -95.78 24.88 0.00 Fail
Power (dBm)
DL
S/N (dB)
DL
FBER
DL
DAQ
UL
Power (dBm)
UL
S/N (dB)
UL
FBER
ID
UL
Tested
Result DL Loss (dB)
Comment
1 1 -96.39 26.37 0.00 Fail 1 2 -92.48 25.55 0.00 Pass 1 3 -98.29 22.96 0.00 Fail 1 4 -95.86 25.99 0.00 Fail 1 5 -97.17 25.65 0.00 Fail 1 6 -104.81 13.28 0.00 Fail 1 7 -94.22 26.99 0.00 Pass 1 8 -92.40 27.40 0.00 Pass 1 9 -92.42 27.03 0.00 Pass 1 10 -97.78 24.43 0.00 Fail 1 11 -98.79 23.97 0.00 Fail 1 12 -96.74 25.14 0.00 Fail 1 13 -103.18 21.24 0.00 Fail 1 14 -102.67 17.05 0.00 Fail 1 15 -97.03 26.02 0.00 Fail 1 16 -97.40 25.08 0.00 Fail 1 17 -92.43 28.74 0.00 Pass 1 18 -92.41 27.85 0.00 Pass 1 19 -93.53 28.13 0.00 Pass 1 20 -96.59 26.04 0.00 Fail 2 1 -96.94 25.92 0.00 Fail 2 2 -94.78 27.85 0.00 Pass 2 3 -93.28 29.11 0.00 Pass 2 4 -97.44 25.36 0.00 Fail 2 5 -94.13 27.35 0.00 Pass 2 6 -93.83 26.00 0.00 Pass 2 7 -90.87 27.54 0.00 Pass 2 8 -98.52 24.36 0.00 Fail 2 9 -93.03 27.24 0.00 Pass 2 10 -92.73 29.67 0.00 Pass 2 11 -96.98 24.24 0.00 Fail 2 12 -95.21 25.69 0.00 Fail 2 13 -97.32 25.37 0.00 Fail 2 14 -94.94 27.28 0.00 Pass 2 15 -99.70 23.01 0.00 Fail 2 16 -104.38 17.54 0.00 Fail 2 17 -97.66 25.14 0.00 Fail 2 18 -98.67 22.03 0.00 Fail 2 19 -90.02 28.36 0.00 Pass 2 20 -94.67 27.84 0.00 Pass 3 1 -94.15 26.26 0.00 Pass 3 2 -90.67 29.18 0.00 Pass 3 3 -95.88 16.03 0.00 Fail 3 4 -93.28 27.81 0.00 Pass
Power (dBm)
DL
S/N (dB)
DL
FBER
DL
DAQ
UL
Power (dBm)
UL
S/N (dB)
UL
FBER
ID
UL
Tested
Result DL Loss (dB)
Comment
3 5 NT NT NT NT NT NT NT NT NT
3 6 -95.90 26.11 0.00 Fail 3 7 -91.69 26.71 0.00 Pass 3 8 -91.54 28.75 0.00 Pass 3 9 -90.41 30.16 0.00 Pass
3 10 NT NT NT NT NT NT NT NT NT
3 11 -89.60 29.78 0.00 Pass 3 12 -92.58 29.18 0.00 Pass 3 13 -91.99 27.55 0.00 Pass 3 14 -88.97 28.65 0.00 Pass
3 15 NT NT NT NT NT NT NT NT NT
3 16 -89.86 29.34 0.00 Pass 3 17 -89.37 29.83 0.00 Pass 3 18 -90.55 28.40 0.00 Pass 3 19 -89.32 29.72 0.00 Pass
3 20 NT NT NT NT NT NT NT NT NT
4 1 -82.80 31.86 0.00 Pass 4 2 -91.45 29.98 0.00 Pass 4 3 -93.24 26.43 0.00 Pass 4 4 -91.78 27.67 0.00 Pass 4 5 -89.72 30.12 0.00 Pass
Floor: 201
Cable Loss
Ph. Type Mod NAC Area Points passed (%)
Critical Points passed (%)
772.53125 P25 Savannah Primay
0.00 0.00 52/72 (72%) 1/1 (100%)
Area Width (ft)
Area Height (ft)
Ignore Area Color
Comments
1 20 478.47 18.24 26.24 Black 2 5 100.71 8.70 11.58 Black 3 6 302.07 13.37 22.59 Black 4 20 171.78 7.33 23.44 Black 5 20 186.07 7.93 23.47 Black 6 1 89.53 8.08 11.08 Black
Point
DL
Power (dBm)
DL
DAQ
UL
Power (dBm)
UL
DAQ
UL
Radio
ID
UL
Tested
Result DL Loss (dB)
Comment
1 -87.32 Pass
Power (dBm)
DL
DAQ
UL
Power (dBm)
ID
UL
Tested
Result DL Loss (dB)
Comment
1 1 -84.08 Pass 1 2 -90.83 Pass 1 3 -92.04 Pass 1 4 -87.65 Pass 1 5 -88.01 Pass 1 6 -96.71 Fail 1 7 -95.94 Fail 1 8 -89.62 Pass 1 9 -90.93 Pass 1 10 -92.00 Pass 1 11 -91.94 Pass 1 12 -97.80 Fail 1 13 -88.45 Pass 1 14 -88.07 Pass 1 15 -86.11 Pass 1 16 -95.66 Fail 1 17 -89.02 Pass 1 18 -87.82 Pass 1 19 -86.23 Pass 1 20 -87.55 Pass 2 1 -85.61 Pass 2 2 -85.79 Pass 2 3 -80.26 Pass 2 4 -80.19 Pass 2 5 -82.57 Pass 3 1 -85.51 Pass 3 2 -87.83 Pass 3 3 -87.91 Pass 3 4 -88.96 Pass 3 5 -87.56 Pass 3 6 -90.38 Pass 4 1 -87.43 Pass 4 2 -87.50 Pass 4 3 -93.24 Pass 4 4 -92.26 Pass 4 5 -90.50 Pass 4 6 -100.04 Fail 4 7 -103.73 Fail 4 8 -101.42 Fail 4 9 -94.37 Pass 4 10 -97.89 Fail 4 11 -100.34 Fail 4 12 -95.49 Fail 4 13 -101.67 Fail 4 14 -99.36 Fail
Power (dBm)
DL
DAQ
UL
Power (dBm)
ID
UL
Tested
Result DL Loss (dB)
Comment
4 15 -95.97 Fail 4 16 -94.33 Pass 4 17 -93.92 Pass 4 18 -91.76 Pass 4 19 -90.37 Pass 4 20 -90.80 Pass 5 1 -91.80 Pass 5 2 -95.87 Fail 5 3 -94.48 Pass 5 4 -93.21 Pass 5 5 -89.38 Pass 5 6 -102.25 Fail 5 7 -101.48 Fail 5 8 -100.41 Fail 5 9 -100.16 Fail 5 10 -86.50 Pass 5 11 -96.44 Fail 5 12 -96.80 Fail 5 13 -91.46 Pass 5 14 -90.63 Pass 5 15 -89.84 Pass 5 16 -88.95 Pass 5 17 -91.03 Pass 5 18 -90.81 Pass 5 19 -90.08 Pass 5 20 -92.86 Pass 6 1 -87.61 Pass
Cable Loss
Ph. Type Mod NAC Area Points passed (%)
Critical Points passed (%)
772.53125 P25 Savannah Primay
0.00 0.00 1 CC CQPSK 2C0 38/72 (52%) 1/1 (100%)
Area Width (ft)
Area Height (ft)
Ignore Area Color
Comments
1 20 478.47 18.24 26.24 Black 2 5 100.71 8.70 11.58 Black 3 6 302.07 13.37 22.59 Black 4 20 171.78 7.33 23.44 Black 5 20 186.07 7.93 23.47 Black 6 1 89.53 8.08 11.08 Black
Point
DL
Power (dBm)
DL
S/N (dB)
DL
FBER
DL
DAQ
UL
Power (dBm)
UL
S/N (dB)
UL
FBER
UL
DAQ
UL
Radio
ID
UL
Tested
Result DL Loss (dB)
Comment
1 -92.78 26.81 0.00 Pass
Power (dBm)
DL
S/N (dB)
DL
FBER
DL
DAQ
UL
Power (dBm)
UL
S/N (dB)
UL
FBER
ID
UL
Tested
Result DL Loss (dB)
Comment
1 1 -91.23 28.42 0.00 Pass 1 2 -92.12 29.19 0.00 Pass 1 3 -97.12 25.74 0.00 Fail 1 4 -90.45 29.73 0.00 Pass 1 5 -93.08 27.46 0.00 Pass 1 6 -100.56 22.10 0.00 Fail 1 7 -99.75 23.79 0.00 Fail 1 8 -94.40 26.75 0.00 Pass 1 9 -93.06 27.66 0.00 Pass 1 10 -95.39 26.54 0.00 Fail 1 11 -97.29 25.54 0.00 Fail 1 12 -103.06 21.05 0.00 Fail 1 13 -94.85 25.30 0.00 Pass 1 14 -93.86 28.10 0.00 Pass 1 15 -93.61 24.90 0.00 Pass 1 16 -99.45 21.94 0.00 Fail 1 17 -92.83 28.51 0.00 Pass 1 18 -94.67 27.43 0.00 Pass 1 19 -94.58 27.92 0.00 Pass 1 20 -89.98 29.99 0.00 Pass 2 1 -94.83 27.74 0.00 Pass 2 2 -93.38 24.34 0.00 Pass 2 3 -84.54 25.19 0.00 Pass 2 4 -88.48 28.64 0.00 Pass 2 5 -92.70 27.23 0.00 Pass 3 1 -90.55 29.32 0.00 Pass 3 2 -91.49 28.45 0.00 Pass 3 3 -91.29 29.27 0.00 Pass 3 4 -92.49 28.44 0.00 Pass 3 5 -91.20 28.69 0.00 Pass 3 6 -92.20 29.05 0.00 Pass 4 1 -89.99 28.78 0.00 Pass 4 2 -93.26 27.54 0.00 Pass 4 3 -96.04 26.69 0.00 Fail 4 4 -94.28 27.43 0.00 Pass 4 5 -98.40 20.75 0.00 Fail 4 6 -105.24 18.83 0.00 Fail 4 7 -107.13 17.10 0.00 Fail 4 8 -99.57 18.64 0.00 Fail 4 9 -99.06 23.93 0.00 Fail 4 10 -101.75 22.48 0.00 Fail 4 11 -104.32 19.93 0.00 Fail 4 12 -101.53 22.43 0.00 Fail 4 13 -104.32 20.20 0.00 Fail 4 14 -106.46 17.70 0.00 Fail
Power (dBm)
DL
S/N (dB)
DL
FBER
DL
DAQ
UL
Power (dBm)
UL
S/N (dB)
UL
FBER
ID
UL
Tested
Result DL Loss (dB)
Comment
4 15 -101.79 21.53 0.00 Fail 4 16 -98.58 25.50 0.00 Fail 4 17 -94.97 27.04 0.00 Pass 4 18 -96.51 25.71 0.00 Fail 4 19 -94.92 27.06 0.00 Pass 4 20 -96.40 26.13 0.00 Fail 5 1 -98.31 23.65 0.00 Fail 5 2 -102.64 20.86 0.00 Fail 5 3 -97.02 25.94 0.00 Fail 5 4 -94.71 25.76 0.00 Pass 5 5 -94.52 26.92 0.00 Pass 5 6 -105.34 19.22 0.00 Fail 5 7 -105.17 19.40 0.00 Fail 5 8 -104.66 18.18 0.00 Fail 5 9 -103.84 21.80 0.00 Fail 5 10 -90.36 29.14 0.00 Pass 5 11 -104.24 18.43 0.00 Fail 5 12 -102.86 21.05 0.00 Fail 5 13 -98.05 24.66 0.00 Fail 5 14 -97.51 24.60 0.00 Fail 5 15 -94.41 26.29 0.00 Pass 5 16 -93.03 27.75 0.00 Pass 5 17 -97.07 25.12 0.00 Fail 5 18 -94.14 27.91 0.00 Pass 5 19 -93.29 28.51 0.00 Pass 5 20 -93.71 27.96 0.00 Pass 6 1 -90.46 28.76 0.00 Pass
Floor: 202
Cable Loss
Ph. Type Mod NAC Area Points passed (%)
Critical Points passed (%)
772.53125 P25 Savannah Primay
0.00 0.00 58/94 (61%) 0/0 (0%)
Area Width (ft)
Area Height (ft)
Ignore Area Color
Comments
1 35 235.95 10.82 21.80 Black 2 30 212.18 10.91 19.45 Black 3 30 165.06 13.70 12.05 Black 4 9 185.63 9.17 20.25 Black
Power (dBm)
DL
DAQ
UL
Power (dBm)
ID
UL
Tested
Result DL Loss (dB)
Comment
1 1 -85.95 Pass 1 2 -90.87 Pass 1 3 -88.86 Pass 1 4 -87.78 Pass 1 5 -93.94 Pass 1 6 -81.15 Pass 1 7 -89.31 Pass 1 8 -89.51 Pass 1 9 -92.15 Pass 1 10 -91.54 Pass 1 11 -92.49 Pass 1 13 -91.24 Pass 1 14 -97.65 Fail 1 15 -88.63 Pass 1 16 -91.85 Pass 1 17 -95.05 Fail 1 18 -94.65 Pass 1 19 -94.84 Pass 1 20 -96.04 Fail 1 21 -87.59 Pass 1 22 -88.61 Pass 1 23 -94.20 Pass 1 24 -94.34 Pass 1 25 -95.03 Fail 1 26 -88.45 Pass 1 27 -95.02 Fail 1 28 -96.34 Fail 1 29 -96.38 Fail 1 30 -89.00 Pass 1 31 -87.04 Pass 1 32 -93.78 Pass 1 33 -95.43 Fail 1 34 -93.78 Pass 1 35 -98.71 Fail 2 1 -97.13 Fail 2 2 -93.88 Pass 2 3 -97.63 Fail 2 4 -97.63 Fail 2 5 -94.16 Pass 2 6 -95.92 Fail 2 7 -101.24 Fail 2 8 -98.80 Fail 2 9 -94.68 Pass 2 10 -93.45 Pass 2 11 -96.10 Fail 2 12 -96.95 Fail 2 13 -96.21 Fail 2 14 -91.26 Pass 2 15 -92.33 Pass
Power (dBm)
DL
DAQ
UL
Power (dBm)
ID
UL
Tested
Result DL Loss (dB)
Comment
2 16 -98.87 Fail 2 17 -101.09 Fail 2 18 -104.86 Fail 2 19 -100.46 Fail 2 20 -91.80 Pass 2 21 -90.57 Pass 2 22 -104.31 Fail 2 23 -98.59 Fail 2 24 -92.23 Pass 2 25 -93.63 Pass 2 26 -93.39 Pass 2 27 -96.93 Fail 2 28 -96.56 Fail 2 29 -94.30 Pass 2 30 -95.78 Fail 3 1 -90.92 Pass 3 2 -83.51 Pass 3 3 -90.48 Pass 3 4 -90.35 Pass 3 5 -83.64 Pass 3 6 -91.21 Pass 3 7 -89.49 Pass 3 8 -85.90 Pass 3 9 -84.81 Pass 3 10 -93.15 Pass 3 11 -88.14 Pass 3 12 -89.31 Pass 3 13 -88.33 Pass 3 14 -100.78 Fail 3 15 -102.67 Fail 3 16 -99.77 Fail 3 17 -96.42 Fail 3 18 -93.72 Pass 3 19 -97.95 Fail 3 20 -103.47 Fail 3 22 -90.70 Pass 3 23 -93.59 Pass 3 24 -96.69 Fail 3 25 -91.76 Pass 3 27 -88.83 Pass 3 28 -88.99 Pass 3 29 -94.08 Pass 3 30 -95.99 Fail 4 5 -97.75 Fail 4 6 -93.47 Pass
Cable Loss
Ph. Type Mod NAC Area Points passed (%)
Critical Points passed (%)
772.53125 P25 Savannah Primay
0.00 0.00 1 CC CQPSK 2C0 13/94 (13%) 0/0 (0%)
Area Width (ft)
Area Height (ft)
Ignore Area Color
Comments
1 35 235.95 10.82 21.80 Black 2 30 212.18 10.91 19.45 Black 3 30 165.06 13.70 12.05 Black 4 9 185.63 9.17 20.25 Black
Power (dBm)
DL
S/N (dB)
DL
FBER
DL
DAQ
UL
Power (dBm)
UL
S/N (dB)
UL
FBER
ID
UL
Tested
Result DL Loss (dB)
Comment
1 1 -97.09 25.20 2.70 Fail 1 2 -95.75 24.01 0.00 Fail 1 3 -98.35 24.94 0.00 Fail 1 4 -95.11 27.09 0.00 Fail 1 5 -101.26 20.39 0.00 Fail 1 6 -89.83 28.34 0.00 Pass 1 7 -94.78 26.85 0.00 Pass 1 8 -99.77 22.82 0.00 Fail 1 9 -98.10 23.57 0.00 Fail 1 10 -98.08 25.44 0.00 Fail 1 11 -96.25 26.68 0.00 Fail 1 13 -98.23 24.03 0.00 Fail 1 14 -98.68 22.43 0.00 Fail 1 15 -93.99 27.96 0.00 Pass 1 16 -99.75 22.45 0.00 Fail 1 17 -99.82 23.45 0.00 Fail 1 18 -100.64 23.09 0.00 Fail 1 19 -102.12 20.70 0.00 Fail 1 20 -103.25 19.81 0.00 Fail 1 21 -93.64 26.28 0.00 Pass 1 22 -94.88 26.26 0.00 Pass 1 23 -99.10 22.65 0.00 Fail 1 24 -99.89 23.12 0.00 Fail 1 25 -101.31 22.10 0.00 Fail 1 26 -91.70 28.75 0.00 Pass 1 27 -101.21 21.65 0.00 Fail 1 28 -103.86 19.75 0.00 Fail 1 29 -102.87 20.82 0.00 Fail 1 30 -96.15 25.93 0.00 Fail 1 31 -95.08 26.69 0.00 Fail 1 32 -98.97 23.62 0.00 Fail 1 33 -101.27 21.72 0.00 Fail 1 34 -104.08 19.21 0.00 Fail 1 35 -102.26 21.08 0.00 Fail 2 1 -102.46 21.13 0.00 Fail 2 2 -103.81 20.29 0.00 Fail 2 3 -104.77 19.89 0.00 Fail 2 4 -103.12 19.67 0.00 Fail 2 5 -104.57 18.36 0.00 Fail 2 6 -103.07 18.91 0.00 Fail 2 7 -105.02 18.59 0.00 Fail 2 8 -105.89 17.19 0.00 Fail 2 9 -97.46 20.05 0.00 Fail 2 10 -102.19 18.22 0.00 Fail 2 11 -106.21 17.98 0.00 Fail 2 12 -105.36 18.63 0.00 Fail 2 13 -103.97 20.34 0.00 Fail 2 14 -97.94 24.85 0.00 Fail 2 15 -99.85 23.53 0.00 Fail
Power (dBm)
DL
S/N (dB)
DL
FBER
DL
DAQ
UL
Power (dBm)
UL
S/N (dB)
UL
FBER
ID
UL
Tested
Result DL Loss (dB)
Comment
2 16 -100.49 18.93 0.00 Fail 2 17 -102.31 15.74 0.00 Fail 2 18 -110.12 14.42 0.00 Fail 2 19 -105.81 18.62 0.00 Fail 2 20 -103.46 20.51 0.00 Fail 2 21 -99.74 21.51 0.00 Fail 2 22 -109.03 14.95 0.00 Fail 2 23 -105.64 18.56 0.00 Fail 2 24 -101.84 18.96 0.00 Fail 2 25 -98.60 22.24 0.00 Fail 2 26 -100.67 23.06 0.00 Fail 2 27 -103.83 19.68 0.00 Fail 2 28 -104.13 16.97 0.00 Fail 2 29 -103.17 20.63 0.00 Fail 2 30 -101.08 20.57 0.00 Fail 3 1 -96.17 26.76 0.00 Fail 3 2 -89.01 27.33 0.00 Pass 3 3 -94.00 26.20 0.00 Pass 3 4 -93.02 24.47 0.00 Pass 3 5 -90.18 26.05 0.00 Pass 3 6 -96.73 23.96 0.00 Fail 3 7 -98.42 25.39 0.00 Fail 3 8 -95.82 26.15 0.00 Fail 3 9 -94.49 26.49 0.00 Pass 3 10 -95.20 25.04 0.00 Fail 3 11 -93.97 25.43 0.00 Pass 3 12 -98.78 23.12 0.00 Fail 3 13 -95.88 26.36 0.00 Fail 3 14 -105.66 17.90 0.00 Fail 3 15 -108.67 15.81 0.00 Fail 3 16 -104.81 19.62 0.00 Fail 3 17 -99.83 23.13 0.00 Fail 3 18 -100.21 23.24 0.00 Fail 3 19 -104.77 18.39 0.00 Fail 3 20 -107.41 16.70 0.00 Fail 3 22 -97.18 25.31 0.00 Fail 3 23 -101.71 21.51 0.00 Fail 3 24 -103.17 20.78 0.00 Fail 3 25 -97.65 24.62 0.00 Fail 3 27 -93.48 27.22 0.00 Pass 3 28 -96.44 26.66 0.00 Fail 3 29 -99.21 23.71 0.00 Fail 3 30 -98.63 25.04 0.00 Fail 4 5 -102.41 22.28 0.00 Fail 4 6 -101.13 21.77 0.00 Fail
Floor: 203
Cable Loss
Ph. Type Mod NAC Area Points passed (%)
Critical Points passed (%)
772.53125 P25 Savannah Primay
0.00 0.00 32/66 (48%) 0/0 (0%)
Area Width (ft)
Area Height (ft)
Ignore Area Color
Comments
1 16 298.92 13.72 21.80 Black 2 20 302.00 16.86 17.91 Black 3 9 382.96 16.12 23.76 Black 4 25 261.68 11.18 23.41 Black
Power (dBm)
DL
DAQ
UL
Power (dBm)
ID
UL
Tested
Result DL Loss (dB)
Comment
1 1 -92.99 Pass 1 2 -101.71 Fail 1 3 -97.73 Fail 1 4 -95.35 Fail 1 5 -88.77 Pass 1 6 -92.10 Pass 1 7 -92.13 Pass 1 8 -95.99 Fail 1 9 -85.83 Pass 1 10 -85.85 Pass 1 11 -88.62 Pass 1 12 -89.23 Pass 1 13 -83.79 Pass 1 14 -85.15 Pass 1 15 -88.28 Pass 1 16 -88.78 Pass 2 1 -93.20 Pass 2 2 -90.30 Pass 2 4 -105.63 Fail 2 5 -98.89 Fail 2 6 -93.09 Pass 2 7 -92.32 Pass 2 9 -102.37 Fail 2 10 -105.16 Fail 2 11 -85.47 Pass 2 12 -96.66 Fail 2 13 -96.00 Fail 2 14 -105.01 Fail 2 15 -103.46 Fail 2 16 -85.72 Pass 2 17 -86.35 Pass 2 18 -95.66 Fail 2 19 -98.09 Fail 2 20 -101.99 Fail 3 1 -99.86 Fail 3 2 -90.51 Pass 3 3 -89.47 Pass 3 4 -99.55 Fail 3 5 -99.94 Fail 3 6 -96.27 Fail 3 7 -98.84 Fail 3 8 -94.85 Pass 3 9 -91.93 Pass 4 1 -88.36 Pass 4 2 -93.27 Pass 4 3 -100.31 Fail
4 4 NT NT NT NT NT
4 5 NT NT NT NT NT
4 6 -86.01 Pass
Power (dBm)
DL
DAQ
UL
Power (dBm)
ID
UL
Tested
Result DL Loss (dB)
Comment
4 7 -94.84 Pass 4 8 -104.06 Fail 4 9 -101.03 Fail 4 10 -93.72 Pass 4 11 -92.24 Pass 4 12 -95.87 Fail 4 13 -107.54 Fail 4 14 -102.76 Fail 4 15 -105.77 Fail 4 16 -88.02 Pass 4 17 -102.72 Fail 4 18 -96.13 Fail 4 19 -97.93 Fail 4 20 -96.13 Fail 4 21 -91.93 Pass 4 22 -93.30 Pass 4 23 -102.32 Fail 4 24 -100.43 Fail 4 25 -99.25 Fail
Cable Loss
Ph. Type Mod NAC Area Points passed (%)
Critical Points passed (%)
772.53125 P25 Savannah Primay
0.00 0.00 1 CC CQPSK 2C0 11/66 (16%) 0/0 (0%)
Area Width (ft)
Area Height (ft)
Ignore Area Color
Comments
1 16 298.92 13.72 21.80 Black 2 20 302.00 16.86 17.91 Black 3 9 382.96 16.12 23.76 Black 4 25 261.68 11.18 23.41 Black
Power (dBm)
DL
S/N (dB)
DL
FBER
DL
DAQ
UL
Power (dBm)
UL
S/N (dB)
UL
FBER
ID
UL
Tested
Result DL Loss (dB)
Comment
1 1 -99.74 20.09 0.00 Fail 1 2 -109.03 15.17 0.00 Fail 1 3 -103.47 20.70 0.00 Fail 1 4 -102.87 21.28 0.00 Fail 1 5 -98.02 24.08 0.00 Fail 1 6 -100.15 23.27 0.00 Fail 1 7 -100.58 22.13 0.00 Fail 1 8 -104.86 12.75 0.00 Fail 1 9 -94.31 23.38 0.00 Pass 1 10 -93.86 25.18 0.00 Pass 1 11 -95.26 25.24 0.00 Fail 1 12 -99.49 23.55 0.00 Fail 1 13 -89.76 28.97 0.00 Pass 1 14 -90.19 28.96 0.00 Pass 1 15 -96.12 23.44 0.00 Fail 1 16 -93.52 27.12 0.00 Pass 2 1 -99.66 22.61 0.00 Fail 2 2 -99.41 22.79 0.00 Fail 2 4 -110.43 8.63 0.00 Fail 2 5 -92.91 Fail 2 6 -99.59 24.38 0.00 Fail 2 7 -103.14 20.44 0.00 Fail 2 9 -106.19 16.41 0.00 Fail 2 10 -92.98 Fail 2 11 -97.32 17.09 0.00 Fail 2 12 -101.76 22.18 0.00 Fail 2 13 -100.72 17.27 0.00 Fail 2 14 -108.52 15.89 0.00 Fail 2 15 -92.93 Fail 2 16 -95.01 23.17 0.00 Fail 2 17 -92.85 27.62 0.00 Pass 2 18 -102.24 17.21 0.00 Fail 2 19 -104.00 21.33 0.00 Fail 2 20 -92.84 Fail 3 1 -92.69 Fail 3 2 -92.33 22.32 0.00 Pass 3 3 -91.44 19.24 0.00 Fail 3 4 -92.73 Fail 3 5 -92.85 Fail 3 6 -96.53 19.02 0.00 Fail 3 7 -92.56 Fail 3 8 -93.74 21.51 0.00 Pass 3 9 -92.69 26.52 0.00 Pass 4 1 -92.69 27.42 0.00 Pass 4 2 -97.76 22.02 0.00 Fail 4 3 -102.66 19.59 0.00 Fail
4 4 NT NT NT NT NT NT NT NT NT
4 5 NT NT NT NT NT NT NT NT NT
4 6 -95.61 25.53 0.00 Fail
Power (dBm)
DL
S/N (dB)
DL
FBER
DL
DAQ
UL
Power (dBm)
UL
S/N (dB)
UL
FBER
ID
UL
Tested
Result DL Loss (dB)
Comment
4 7 -98.61 24.22 0.00 Fail 4 8 -109.02 14.24 0.00 Fail 4 9 -107.68 13.16 0.00 Fail 4 10 -96.35 23.91 0.00 Fail 4 11 -99.13 22.29 0.00 Fail 4 12 -100.93 19.77 0.00 Fail 4 13 -108.14 14.03 0.00 Fail 4 14 -108.28 14.17 0.00 Fail 4 15 -109.73 13.86 0.00 Fail 4 16 -91.70 27.56 0.00 Pass 4 17 -105.93 17.31 0.00 Fail 4 18 -101.86 21.70 0.00 Fail 4 19 -101.95 21.85 0.00 Fail 4 20 -103.73 20.56 0.00 Fail 4 21 -98.53 23.51 0.00 Fail 4 22 -97.96 22.81 0.00 Fail 4 23 -102.39 13.96 0.00 Fail 4 24 -106.73 18.00 0.00 Fail 4 25 -92.39 Fail
Floor: 204
Cable Loss
Ph. Type Mod NAC Area Points passed (%)
Critical Points passed (%)
772.53125 P25 Savannah Primay
0.00 0.00 42/63 (66%) 0/0 (0%)
Area Width (ft)
Area Height (ft)
Ignore Area Color
Comments
1 10 236.76 15.72 15.07 Black 2 10 253.68 11.48 22.09 Black 3 25 171.87 11.36 15.12 Black 4 20 253.51 11.30 22.44 Black
Power (dBm)
DL
DAQ
UL
Power (dBm)
ID
UL
Tested
Result DL Loss (dB)
Comment
1 1 -89.61 Pass 1 2 -89.54 Pass 1 3 -87.99 Pass 1 4 -89.37 Pass 1 5 -88.29 Pass 1 6 -92.18 Pass 1 7 -87.04 Pass 1 8 -86.88 Pass 1 9 -88.88 Pass 1 10 -86.45 Pass 2 1 -87.93 Pass 2 2 -82.96 Pass 2 3 -88.48 Pass 2 4 -85.43 Pass 2 5 -86.45 Pass 2 6 -88.55 Pass 2 7 -90.13 Pass 2 8 -92.62 Pass 2 9 -93.61 Pass 2 10 -87.73 Pass 3 1 -94.49 Pass 3 2 -97.46 Fail 3 3 -109.98 Fail 3 4 -97.60 Fail 3 5 -85.93 Pass 3 6 -97.12 Fail 3 7 -101.12 Fail 3 8 -102.55 Fail 3 11 -94.64 Pass 3 12 -100.08 Fail 3 13 -97.47 Fail 3 14 -98.52 Fail 3 15 -94.34 Pass 3 16 -101.91 Fail 3 17 -100.49 Fail 3 18 -93.61 Pass 3 19 -95.62 Fail 3 20 -98.80 Fail 3 21 -98.55 Fail 3 22 -101.82 Fail 3 23 -100.78 Fail 3 24 -105.71 Fail 3 25 -98.01 Fail 4 1 -84.45 Pass 4 2 -90.62 Pass 4 3 -88.31 Pass 4 4 -95.73 Fail 4 5 -93.21 Pass 4 6 -84.90 Pass
Power (dBm)
DL
DAQ
UL
Power (dBm)
ID
UL
Tested
Result DL Loss (dB)
Comment
4 7 -82.36 Pass 4 8 -100.59 Fail 4 9 -96.72 Fail 4 10 -94.16 Pass 4 11 -82.72 Pass 4 12 -91.93 Pass 4 13 -92.85 Pass 4 14 -92.81 Pass 4 15 -88.47 Pass 4 16 -78.45 Pass 4 17 -88.17 Pass 4 18 -90.86 Pass 4 19 -85.83 Pass 4 20 -89.14 Pass
Cable Loss
Ph. Type Mod NAC Area Points passed (%)
Critical Points passed (%)
772.53125 P25 Savannah Primay
0.00 0.00 1 CC CQPSK 2C0 23/63 (36%) 0/0 (0%)
Area Width (ft)
Area Height (ft)
Ignore Area Color
Comments
1 10 236.76 15.72 15.07 Black 2 10 253.68 11.48 22.09 Black 3 25 171.87 11.36 15.12 Black 4 20 253.51 11.30 22.44 Black
Power (dBm)
DL
S/N (dB)
DL
FBER
DL
DAQ
UL
Power (dBm)
UL
S/N (dB)
UL
FBER
ID
UL
Tested
Result DL Loss (dB)
Comment
1 1 -94.97 27.33 0.00 Pass 1 2 -92.94 27.50 0.00 Pass 1 3 -92.12 28.24 0.00 Pass 1 4 -94.92 26.65 0.00 Pass 1 5 -94.17 27.64 0.00 Pass 1 6 -96.88 24.31 0.00 Fail 1 7 -90.66 26.59 0.00 Pass 1 8 -91.78 26.72 0.00 Pass 1 9 -90.16 27.89 0.00 Pass 1 10 -88.98 29.60 0.00 Pass 2 1 -94.82 24.24 0.00 Pass 2 2 -90.82 28.66 0.00 Pass 2 3 -97.38 25.58 0.00 Fail 2 4 -89.41 28.56 0.00 Pass 2 5 -91.19 28.12 0.00 Pass 2 6 -93.22 25.07 0.00 Pass 2 7 -91.44 29.31 0.00 Pass 2 8 -98.52 24.36 0.00 Fail 2 9 -98.07 24.12 0.00 Fail 2 10 -90.64 25.46 0.00 Pass 3 1 -96.90 25.23 0.00 Fail 3 2 -105.06 11.10 13.51 Fail 3 3 -112.67 7.51 0.00 Fail 3 4 -105.21 14.90 0.00 Fail 3 5 -102.51 19.08 0.00 Fail 3 6 -94.18 18.47 0.00 Fail 3 7 -103.10 12.24 0.00 Fail 3 8 -108.36 14.91 0.00 Fail 3 11 -99.63 24.31 0.00 Fail 3 12 -102.81 20.23 0.00 Fail 3 13 -102.99 20.82 0.00 Fail 3 14 -105.11 12.01 0.00 Fail 3 15 -102.41 16.62 0.00 Fail 3 16 -106.77 14.94 24.32 Fail 3 17 -105.44 18.41 0.00 Fail 3 18 -97.67 24.29 0.00 Fail 3 19 -101.83 21.59 0.00 Fail 3 20 -102.49 21.44 0.00 Fail 3 21 -103.09 22.21 0.00 Fail 3 22 -107.60 16.99 0.00 Fail 3 23 -103.60 17.82 0.00 Fail 3 24 -109.82 14.89 0.00 Fail 3 25 -104.58 17.05 0.00 Fail 4 1 -93.69 24.60 0.00 Pass 4 2 -96.15 19.40 0.00 Fail 4 3 -97.94 15.92 0.00 Fail 4 4 -104.25 16.47 0.00 Fail 4 5 -101.35 21.90 0.00 Fail 4 6 -91.39 23.33 0.00 Pass
Power (dBm)
DL
S/N (dB)
DL
FBER
DL
DAQ
UL
Power (dBm)
UL
S/N (dB)
UL
FBER
ID
UL
Tested
Result DL Loss (dB)
Comment
4 7 -90.49 26.06 0.00 Pass 4 8 -103.25 3.25 0.00 Fail 4 9 -101.55 21.37 0.00 Fail 4 10 -99.72 21.43 0.00 Fail 4 11 -87.54 26.01 0.00 Pass 4 12 -95.95 25.10 0.00 Fail 4 13 -98.91 20.10 0.00 Fail 4 14 -96.39 25.41 0.00 Fail 4 15 -95.27 26.48 0.00 Fail 4 16 -85.93 27.43 0.00 Pass 4 17 -93.04 26.49 0.00 Pass 4 18 -97.05 19.15 0.00 Fail 4 19 -91.50 29.61 0.00 Pass 4 20 -97.19 25.48 0.00 Fail
Additional Info
File details come from the government source that posted it. Updated .