25-Garden City Elementary BDA Signal Survey 12-1-2025.pdf

PDF 5 MB Posted

Attached to
CMR Services for Garden City Elementary School Renovation Project
Solicitation number
RFP C27-03 (ESPLOST)
Issued by
Chatham County, Georgia

About this file

This is a BDA (Bidders' Disadvantaged Affidavit) Signal Survey document for the Garden City Elementary School Renovation Project, prepared for the Savannah-Chatham County Public School System in Georgia. The survey serves as supporting documentation for the Construction Management at Risk (CMR) Services contract opportunity (ESPLOST RFP C27-03) for the renovation of Garden City Elementary School located at 4037 Kessler Ave, Savannah, GA 31408. The document is dated December 1, 2025, and functions as a preliminary assessment tool to gauge interested firms' qualifications and intentions regarding the CMR services contract. This survey precedes the formal sealed proposal submission process and assists the District in understanding the pool of potential bidders and their capability to deliver the required services.

The signal survey serves as a market research and outreach instrument to identify qualified construction management firms interested in participating in the competitive bidding process. By collecting preliminary information from prospective bidders regarding their disadvantaged business enterprise (DBE) status and general capability, the District can assess market interest and ensure adequate competition. The survey data informs the District's procurement strategy and helps facilitate an inclusive and competitive solicitation process for the CMR services, which will be procured under the AIA Document A133 - 2019 Agreement with payment structured as Cost of the Work Plus a Fee with a Guaranteed Maximum Price.

View the file

Other files

File Type Posted
9-RFP C27-03 - Solicitation Form 2 - Contractor Affidavit.pdf PDF
13-RFP C27-03 - Solicitation Form 6 - Performance Bond Form.pdf PDF
27-RFP C27-03 - Addendum 4.pdf PDF
5-RFP C27-03 - Phasing Option 4.1 reduced 2026-07-30.pdf PDF
6-RFP C27-03 - Project Manual 082826.pdf PDF
4-RFP C27-03 - DRAWINGS 100 CD R2 Add-0.pdf PDF
14-RFP C27-03 - Solicitation Form 7 - Payment Bond Form.pdf PDF
17-SECTION 012200 - UNIT PRICES.pdf PDF
18-SECTION 012100 - ALLOWANCES.pdf PDF
3-RFP C27-03 - A201-2017 Sample Contract.pdf PDF
7-RFP C27-03 - Solicitation Document.pdf PDF
12-RFP C27-03 - Solicitation Form 5 - Bid Security Form.pdf PDF
8-RFP C27-03 - Solicitation Form 1 - Offeror Information Form.pdf PDF
11-RFP C27-03 - Solicitation Form 4 - Lobbying.pdf PDF
21-RFP C27-03 - Pre-Proposal Register.pdf PDF
26-Garden City Elementary Parking Lot Geotech Report - WSP.pdf PDF
23-RFP C27-03 - Solicitation Document - Pages 25-27.pdf PDF
20-RFP C27-03 - Addendum 2.pdf PDF
10-RFP C27-03 - Solicitation Form 3 - Debarment.pdf PDF
19-SECTION 012300 - ALTERNATES.pdf PDF
16-RFP C27-03 - Addendum 1.pdf PDF
1-RFP C27-03 - A133-2019 Sample Contract.pdf PDF
24-Garden City Updated Spec Sections Addendum 4.pdf PDF
2-RFP C27-03 - A133-2019 Sample Exhibit A - GMP Amendment.pdf PDF
15-RFP C27-03 - Solicitation Form 8 - GMP Proposal Form.pdf PDF
22-RFP C27-03 - Addendum 3.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Provided by: Southeastern System Technologies

Emergency Responder Radio System Coverage Report Test Results

Date Prepared: Dec 1, 2025

Test File: 20251124 093731

Test Location: Garden City Elementary School 4037 Kessler Avenue

Garden City, GA, 31408 Technician: Kenneth Bragg

FCC#: 0031655897

The test results set forth in this report reflect conditions at the time of testing.

Building: Garden City Elementary Result: Fail

Test Report Summary

Channel/ Ch Group

Freq (MHz) Technology Band Result Area Points passed (%)

Critical Points passed (%)

1 772.53125 P25 Savannah Primay Channel Fail 239/356 (67%)

2/3 (66%)

1 772.53125 P25 Savannah Primay Channel Fail 121/356 (33%)

1/3 (33%)

Test Details

Number of Floors Tested: 5 Result Calculation: By area per floor Number of Areas Tested: 356 Area Pass Criteria: 95% Number of Critical Points Tested: 3 Critical Points Pass Criteria: 99% Apply Adjacent Area Rule: No

Equipment Report

Vendor Application Activation ID Maintenance Date

Device Calibration Expires

Antenna info

PCTEL SeeHawk Touch rel 5.3.0.0

9b5f-5f92- 3b4c-4f95-b6c5-3e37- 8d4a-6f63

11-30-2026 SeeGull IBflex Device rel 3.14.1.0

SN:

081810036

6-11-2027

Threshold Settings

Measurement DL Area

Point DL Critical

Point DL Use for grading UL Area

Point UL Critical

Point UL Use for grading

P25 Power (RSSI) -95.00 dBm -95.00 dBm Yes -95.00 dBm -95.00 dBm Yes

P25 S/N (SINR) 20.00 dB 22.00 dB Yes 20.00 dB 22.00 dB Yes

P25 FBER 2.00 % 1.50 % Yes 2.00 % 1.50 % Yes

DAQ 3.00 Yes

Sample collection method

Measurement Sample Collection Method

P25 Power (RSSI) Max

P25 Traffic Channels Power Max

P25 Control Channels Power Average

P25 Traffic Channels SINR Average

Floors Result

Floor Plan

1 772.53125

1 772.53125

200 Fail Fail

201 Fail Fail

202 Fail Fail

203 Fail Fail

204 Fail Fail

Floor: 200 Channel: 1

Freq (MHz) Tech Band Ant Gain

Cable Loss

Ph. Type Mod NAC Area Points passed (%)

Critical Points passed (%)

772.53125 P25 Savannah Primay

Channel

0.00 0.00 55/61 (90%) 1/2 (50%)

Grid # of Areas Area Size

(sq. ft) Area Width (ft)

Area Height (ft)

Ignore Area Color

Comments

1 20 308.80 14.22 21.71 Black 2 20 193.73 14.22 13.62 Black 3 20 344.74 14.18 24.31 Black 4 5 181.69 11.00 16.52 Black

Critical Points Critical Point

DL

Power (dBm)

DL

DAQ

UL

Power (dBm)

UL

DAQ

UL

Radio

ID

UL

Tested

Result DL Loss (dB)

Comment

1 -98.44 Fail 2 -94.85 Pass

Area Points Grid Area DL

Power (dBm)

DL

DAQ

UL

Power (dBm)

UL

DAQ

Radio

ID

UL

Tested

Result DL Loss (dB)

Comment

1 1 -92.09 Pass 1 2 -87.62 Pass 1 3 -90.96 Pass 1 4 -90.50 Pass 1 5 -92.13 Pass 1 6 -99.04 Fail 1 7 -90.92 Pass 1 8 -87.88 Pass 1 9 -91.15 Pass 1 10 -90.03 Pass 1 11 -96.09 Fail 1 12 -93.03 Pass 1 13 -97.72 Fail 1 14 -95.09 Fail 1 15 -91.51 Pass 1 16 -92.50 Pass 1 17 -89.22 Pass 1 18 -85.66 Pass 1 19 -90.04 Pass 1 20 -88.97 Pass 2 1 -95.94 Fail 2 2 -93.38 Pass 2 3 -91.03 Pass 2 4 -88.87 Pass 2 5 -94.24 Pass 2 6 -87.90 Pass 2 7 -86.04 Pass 2 8 -93.68 Pass 2 9 -86.69 Pass 2 10 -91.24 Pass 2 11 -93.27 Pass 2 12 -85.97 Pass 2 13 -93.49 Pass 2 14 -90.66 Pass 2 15 -94.57 Pass 2 16 -99.33 Fail 2 17 -90.56 Pass 2 18 -92.19 Pass 2 19 -82.22 Pass 2 20 -92.52 Pass 3 1 -86.45 Pass 3 2 -86.53 Pass 3 3 -86.86 Pass 3 4 -89.32 Pass

Power (dBm)

DL

DAQ

UL

Power (dBm)

ID

UL

Tested

Result DL Loss (dB)

Comment

3 5 NT NT NT NT NT

3 6 -88.84 Pass 3 7 -85.98 Pass 3 8 -89.72 Pass 3 9 -87.80 Pass

3 10 NT NT NT NT NT

3 11 -88.09 Pass 3 12 -86.25 Pass 3 13 -87.42 Pass 3 14 -81.45 Pass

3 15 NT NT NT NT NT

3 16 -86.90 Pass 3 17 -84.88 Pass 3 18 -88.44 Pass 3 19 -81.23 Pass

3 20 NT NT NT NT NT

4 1 -80.22 Pass 4 2 -87.24 Pass 4 3 -81.53 Pass 4 4 -84.48 Pass 4 5 -86.26 Pass

Cable Loss

Ph. Type Mod NAC Area Points passed (%)

Critical Points passed (%)

772.53125 P25 Savannah Primay

0.00 0.00 1 CC CQPSK 2C0 36/61 (59%) 0/2 (0%)

Area Width (ft)

Area Height (ft)

Ignore Area Color

Comments

1 20 308.80 14.22 21.71 Black 2 20 193.73 14.22 13.62 Black 3 20 344.74 14.18 24.31 Black 4 5 181.69 11.00 16.52 Black

Point

DL

Power (dBm)

DL

S/N (dB)

DL

FBER

DL

DAQ

UL

Power (dBm)

UL

S/N (dB)

UL

FBER

UL

DAQ

UL

Radio

ID

UL

Tested

Result DL Loss (dB)

Comment

1 -102.69 17.20 0.00 Fail 2 -95.78 24.88 0.00 Fail

Power (dBm)

DL

S/N (dB)

DL

FBER

DL

DAQ

UL

Power (dBm)

UL

S/N (dB)

UL

FBER

ID

UL

Tested

Result DL Loss (dB)

Comment

1 1 -96.39 26.37 0.00 Fail 1 2 -92.48 25.55 0.00 Pass 1 3 -98.29 22.96 0.00 Fail 1 4 -95.86 25.99 0.00 Fail 1 5 -97.17 25.65 0.00 Fail 1 6 -104.81 13.28 0.00 Fail 1 7 -94.22 26.99 0.00 Pass 1 8 -92.40 27.40 0.00 Pass 1 9 -92.42 27.03 0.00 Pass 1 10 -97.78 24.43 0.00 Fail 1 11 -98.79 23.97 0.00 Fail 1 12 -96.74 25.14 0.00 Fail 1 13 -103.18 21.24 0.00 Fail 1 14 -102.67 17.05 0.00 Fail 1 15 -97.03 26.02 0.00 Fail 1 16 -97.40 25.08 0.00 Fail 1 17 -92.43 28.74 0.00 Pass 1 18 -92.41 27.85 0.00 Pass 1 19 -93.53 28.13 0.00 Pass 1 20 -96.59 26.04 0.00 Fail 2 1 -96.94 25.92 0.00 Fail 2 2 -94.78 27.85 0.00 Pass 2 3 -93.28 29.11 0.00 Pass 2 4 -97.44 25.36 0.00 Fail 2 5 -94.13 27.35 0.00 Pass 2 6 -93.83 26.00 0.00 Pass 2 7 -90.87 27.54 0.00 Pass 2 8 -98.52 24.36 0.00 Fail 2 9 -93.03 27.24 0.00 Pass 2 10 -92.73 29.67 0.00 Pass 2 11 -96.98 24.24 0.00 Fail 2 12 -95.21 25.69 0.00 Fail 2 13 -97.32 25.37 0.00 Fail 2 14 -94.94 27.28 0.00 Pass 2 15 -99.70 23.01 0.00 Fail 2 16 -104.38 17.54 0.00 Fail 2 17 -97.66 25.14 0.00 Fail 2 18 -98.67 22.03 0.00 Fail 2 19 -90.02 28.36 0.00 Pass 2 20 -94.67 27.84 0.00 Pass 3 1 -94.15 26.26 0.00 Pass 3 2 -90.67 29.18 0.00 Pass 3 3 -95.88 16.03 0.00 Fail 3 4 -93.28 27.81 0.00 Pass

Power (dBm)

DL

S/N (dB)

DL

FBER

DL

DAQ

UL

Power (dBm)

UL

S/N (dB)

UL

FBER

ID

UL

Tested

Result DL Loss (dB)

Comment

3 5 NT NT NT NT NT NT NT NT NT

3 6 -95.90 26.11 0.00 Fail 3 7 -91.69 26.71 0.00 Pass 3 8 -91.54 28.75 0.00 Pass 3 9 -90.41 30.16 0.00 Pass

3 10 NT NT NT NT NT NT NT NT NT

3 11 -89.60 29.78 0.00 Pass 3 12 -92.58 29.18 0.00 Pass 3 13 -91.99 27.55 0.00 Pass 3 14 -88.97 28.65 0.00 Pass

3 15 NT NT NT NT NT NT NT NT NT

3 16 -89.86 29.34 0.00 Pass 3 17 -89.37 29.83 0.00 Pass 3 18 -90.55 28.40 0.00 Pass 3 19 -89.32 29.72 0.00 Pass

3 20 NT NT NT NT NT NT NT NT NT

4 1 -82.80 31.86 0.00 Pass 4 2 -91.45 29.98 0.00 Pass 4 3 -93.24 26.43 0.00 Pass 4 4 -91.78 27.67 0.00 Pass 4 5 -89.72 30.12 0.00 Pass

Floor: 201

Cable Loss

Ph. Type Mod NAC Area Points passed (%)

Critical Points passed (%)

772.53125 P25 Savannah Primay

0.00 0.00 52/72 (72%) 1/1 (100%)

Area Width (ft)

Area Height (ft)

Ignore Area Color

Comments

1 20 478.47 18.24 26.24 Black 2 5 100.71 8.70 11.58 Black 3 6 302.07 13.37 22.59 Black 4 20 171.78 7.33 23.44 Black 5 20 186.07 7.93 23.47 Black 6 1 89.53 8.08 11.08 Black

Point

DL

Power (dBm)

DL

DAQ

UL

Power (dBm)

UL

DAQ

UL

Radio

ID

UL

Tested

Result DL Loss (dB)

Comment

1 -87.32 Pass

Power (dBm)

DL

DAQ

UL

Power (dBm)

ID

UL

Tested

Result DL Loss (dB)

Comment

1 1 -84.08 Pass 1 2 -90.83 Pass 1 3 -92.04 Pass 1 4 -87.65 Pass 1 5 -88.01 Pass 1 6 -96.71 Fail 1 7 -95.94 Fail 1 8 -89.62 Pass 1 9 -90.93 Pass 1 10 -92.00 Pass 1 11 -91.94 Pass 1 12 -97.80 Fail 1 13 -88.45 Pass 1 14 -88.07 Pass 1 15 -86.11 Pass 1 16 -95.66 Fail 1 17 -89.02 Pass 1 18 -87.82 Pass 1 19 -86.23 Pass 1 20 -87.55 Pass 2 1 -85.61 Pass 2 2 -85.79 Pass 2 3 -80.26 Pass 2 4 -80.19 Pass 2 5 -82.57 Pass 3 1 -85.51 Pass 3 2 -87.83 Pass 3 3 -87.91 Pass 3 4 -88.96 Pass 3 5 -87.56 Pass 3 6 -90.38 Pass 4 1 -87.43 Pass 4 2 -87.50 Pass 4 3 -93.24 Pass 4 4 -92.26 Pass 4 5 -90.50 Pass 4 6 -100.04 Fail 4 7 -103.73 Fail 4 8 -101.42 Fail 4 9 -94.37 Pass 4 10 -97.89 Fail 4 11 -100.34 Fail 4 12 -95.49 Fail 4 13 -101.67 Fail 4 14 -99.36 Fail

Power (dBm)

DL

DAQ

UL

Power (dBm)

ID

UL

Tested

Result DL Loss (dB)

Comment

4 15 -95.97 Fail 4 16 -94.33 Pass 4 17 -93.92 Pass 4 18 -91.76 Pass 4 19 -90.37 Pass 4 20 -90.80 Pass 5 1 -91.80 Pass 5 2 -95.87 Fail 5 3 -94.48 Pass 5 4 -93.21 Pass 5 5 -89.38 Pass 5 6 -102.25 Fail 5 7 -101.48 Fail 5 8 -100.41 Fail 5 9 -100.16 Fail 5 10 -86.50 Pass 5 11 -96.44 Fail 5 12 -96.80 Fail 5 13 -91.46 Pass 5 14 -90.63 Pass 5 15 -89.84 Pass 5 16 -88.95 Pass 5 17 -91.03 Pass 5 18 -90.81 Pass 5 19 -90.08 Pass 5 20 -92.86 Pass 6 1 -87.61 Pass

Cable Loss

Ph. Type Mod NAC Area Points passed (%)

Critical Points passed (%)

772.53125 P25 Savannah Primay

0.00 0.00 1 CC CQPSK 2C0 38/72 (52%) 1/1 (100%)

Area Width (ft)

Area Height (ft)

Ignore Area Color

Comments

1 20 478.47 18.24 26.24 Black 2 5 100.71 8.70 11.58 Black 3 6 302.07 13.37 22.59 Black 4 20 171.78 7.33 23.44 Black 5 20 186.07 7.93 23.47 Black 6 1 89.53 8.08 11.08 Black

Point

DL

Power (dBm)

DL

S/N (dB)

DL

FBER

DL

DAQ

UL

Power (dBm)

UL

S/N (dB)

UL

FBER

UL

DAQ

UL

Radio

ID

UL

Tested

Result DL Loss (dB)

Comment

1 -92.78 26.81 0.00 Pass

Power (dBm)

DL

S/N (dB)

DL

FBER

DL

DAQ

UL

Power (dBm)

UL

S/N (dB)

UL

FBER

ID

UL

Tested

Result DL Loss (dB)

Comment

1 1 -91.23 28.42 0.00 Pass 1 2 -92.12 29.19 0.00 Pass 1 3 -97.12 25.74 0.00 Fail 1 4 -90.45 29.73 0.00 Pass 1 5 -93.08 27.46 0.00 Pass 1 6 -100.56 22.10 0.00 Fail 1 7 -99.75 23.79 0.00 Fail 1 8 -94.40 26.75 0.00 Pass 1 9 -93.06 27.66 0.00 Pass 1 10 -95.39 26.54 0.00 Fail 1 11 -97.29 25.54 0.00 Fail 1 12 -103.06 21.05 0.00 Fail 1 13 -94.85 25.30 0.00 Pass 1 14 -93.86 28.10 0.00 Pass 1 15 -93.61 24.90 0.00 Pass 1 16 -99.45 21.94 0.00 Fail 1 17 -92.83 28.51 0.00 Pass 1 18 -94.67 27.43 0.00 Pass 1 19 -94.58 27.92 0.00 Pass 1 20 -89.98 29.99 0.00 Pass 2 1 -94.83 27.74 0.00 Pass 2 2 -93.38 24.34 0.00 Pass 2 3 -84.54 25.19 0.00 Pass 2 4 -88.48 28.64 0.00 Pass 2 5 -92.70 27.23 0.00 Pass 3 1 -90.55 29.32 0.00 Pass 3 2 -91.49 28.45 0.00 Pass 3 3 -91.29 29.27 0.00 Pass 3 4 -92.49 28.44 0.00 Pass 3 5 -91.20 28.69 0.00 Pass 3 6 -92.20 29.05 0.00 Pass 4 1 -89.99 28.78 0.00 Pass 4 2 -93.26 27.54 0.00 Pass 4 3 -96.04 26.69 0.00 Fail 4 4 -94.28 27.43 0.00 Pass 4 5 -98.40 20.75 0.00 Fail 4 6 -105.24 18.83 0.00 Fail 4 7 -107.13 17.10 0.00 Fail 4 8 -99.57 18.64 0.00 Fail 4 9 -99.06 23.93 0.00 Fail 4 10 -101.75 22.48 0.00 Fail 4 11 -104.32 19.93 0.00 Fail 4 12 -101.53 22.43 0.00 Fail 4 13 -104.32 20.20 0.00 Fail 4 14 -106.46 17.70 0.00 Fail

Power (dBm)

DL

S/N (dB)

DL

FBER

DL

DAQ

UL

Power (dBm)

UL

S/N (dB)

UL

FBER

ID

UL

Tested

Result DL Loss (dB)

Comment

4 15 -101.79 21.53 0.00 Fail 4 16 -98.58 25.50 0.00 Fail 4 17 -94.97 27.04 0.00 Pass 4 18 -96.51 25.71 0.00 Fail 4 19 -94.92 27.06 0.00 Pass 4 20 -96.40 26.13 0.00 Fail 5 1 -98.31 23.65 0.00 Fail 5 2 -102.64 20.86 0.00 Fail 5 3 -97.02 25.94 0.00 Fail 5 4 -94.71 25.76 0.00 Pass 5 5 -94.52 26.92 0.00 Pass 5 6 -105.34 19.22 0.00 Fail 5 7 -105.17 19.40 0.00 Fail 5 8 -104.66 18.18 0.00 Fail 5 9 -103.84 21.80 0.00 Fail 5 10 -90.36 29.14 0.00 Pass 5 11 -104.24 18.43 0.00 Fail 5 12 -102.86 21.05 0.00 Fail 5 13 -98.05 24.66 0.00 Fail 5 14 -97.51 24.60 0.00 Fail 5 15 -94.41 26.29 0.00 Pass 5 16 -93.03 27.75 0.00 Pass 5 17 -97.07 25.12 0.00 Fail 5 18 -94.14 27.91 0.00 Pass 5 19 -93.29 28.51 0.00 Pass 5 20 -93.71 27.96 0.00 Pass 6 1 -90.46 28.76 0.00 Pass

Floor: 202

Cable Loss

Ph. Type Mod NAC Area Points passed (%)

Critical Points passed (%)

772.53125 P25 Savannah Primay

0.00 0.00 58/94 (61%) 0/0 (0%)

Area Width (ft)

Area Height (ft)

Ignore Area Color

Comments

1 35 235.95 10.82 21.80 Black 2 30 212.18 10.91 19.45 Black 3 30 165.06 13.70 12.05 Black 4 9 185.63 9.17 20.25 Black

Power (dBm)

DL

DAQ

UL

Power (dBm)

ID

UL

Tested

Result DL Loss (dB)

Comment

1 1 -85.95 Pass 1 2 -90.87 Pass 1 3 -88.86 Pass 1 4 -87.78 Pass 1 5 -93.94 Pass 1 6 -81.15 Pass 1 7 -89.31 Pass 1 8 -89.51 Pass 1 9 -92.15 Pass 1 10 -91.54 Pass 1 11 -92.49 Pass 1 13 -91.24 Pass 1 14 -97.65 Fail 1 15 -88.63 Pass 1 16 -91.85 Pass 1 17 -95.05 Fail 1 18 -94.65 Pass 1 19 -94.84 Pass 1 20 -96.04 Fail 1 21 -87.59 Pass 1 22 -88.61 Pass 1 23 -94.20 Pass 1 24 -94.34 Pass 1 25 -95.03 Fail 1 26 -88.45 Pass 1 27 -95.02 Fail 1 28 -96.34 Fail 1 29 -96.38 Fail 1 30 -89.00 Pass 1 31 -87.04 Pass 1 32 -93.78 Pass 1 33 -95.43 Fail 1 34 -93.78 Pass 1 35 -98.71 Fail 2 1 -97.13 Fail 2 2 -93.88 Pass 2 3 -97.63 Fail 2 4 -97.63 Fail 2 5 -94.16 Pass 2 6 -95.92 Fail 2 7 -101.24 Fail 2 8 -98.80 Fail 2 9 -94.68 Pass 2 10 -93.45 Pass 2 11 -96.10 Fail 2 12 -96.95 Fail 2 13 -96.21 Fail 2 14 -91.26 Pass 2 15 -92.33 Pass

Power (dBm)

DL

DAQ

UL

Power (dBm)

ID

UL

Tested

Result DL Loss (dB)

Comment

2 16 -98.87 Fail 2 17 -101.09 Fail 2 18 -104.86 Fail 2 19 -100.46 Fail 2 20 -91.80 Pass 2 21 -90.57 Pass 2 22 -104.31 Fail 2 23 -98.59 Fail 2 24 -92.23 Pass 2 25 -93.63 Pass 2 26 -93.39 Pass 2 27 -96.93 Fail 2 28 -96.56 Fail 2 29 -94.30 Pass 2 30 -95.78 Fail 3 1 -90.92 Pass 3 2 -83.51 Pass 3 3 -90.48 Pass 3 4 -90.35 Pass 3 5 -83.64 Pass 3 6 -91.21 Pass 3 7 -89.49 Pass 3 8 -85.90 Pass 3 9 -84.81 Pass 3 10 -93.15 Pass 3 11 -88.14 Pass 3 12 -89.31 Pass 3 13 -88.33 Pass 3 14 -100.78 Fail 3 15 -102.67 Fail 3 16 -99.77 Fail 3 17 -96.42 Fail 3 18 -93.72 Pass 3 19 -97.95 Fail 3 20 -103.47 Fail 3 22 -90.70 Pass 3 23 -93.59 Pass 3 24 -96.69 Fail 3 25 -91.76 Pass 3 27 -88.83 Pass 3 28 -88.99 Pass 3 29 -94.08 Pass 3 30 -95.99 Fail 4 5 -97.75 Fail 4 6 -93.47 Pass

Cable Loss

Ph. Type Mod NAC Area Points passed (%)

Critical Points passed (%)

772.53125 P25 Savannah Primay

0.00 0.00 1 CC CQPSK 2C0 13/94 (13%) 0/0 (0%)

Area Width (ft)

Area Height (ft)

Ignore Area Color

Comments

1 35 235.95 10.82 21.80 Black 2 30 212.18 10.91 19.45 Black 3 30 165.06 13.70 12.05 Black 4 9 185.63 9.17 20.25 Black

Power (dBm)

DL

S/N (dB)

DL

FBER

DL

DAQ

UL

Power (dBm)

UL

S/N (dB)

UL

FBER

ID

UL

Tested

Result DL Loss (dB)

Comment

1 1 -97.09 25.20 2.70 Fail 1 2 -95.75 24.01 0.00 Fail 1 3 -98.35 24.94 0.00 Fail 1 4 -95.11 27.09 0.00 Fail 1 5 -101.26 20.39 0.00 Fail 1 6 -89.83 28.34 0.00 Pass 1 7 -94.78 26.85 0.00 Pass 1 8 -99.77 22.82 0.00 Fail 1 9 -98.10 23.57 0.00 Fail 1 10 -98.08 25.44 0.00 Fail 1 11 -96.25 26.68 0.00 Fail 1 13 -98.23 24.03 0.00 Fail 1 14 -98.68 22.43 0.00 Fail 1 15 -93.99 27.96 0.00 Pass 1 16 -99.75 22.45 0.00 Fail 1 17 -99.82 23.45 0.00 Fail 1 18 -100.64 23.09 0.00 Fail 1 19 -102.12 20.70 0.00 Fail 1 20 -103.25 19.81 0.00 Fail 1 21 -93.64 26.28 0.00 Pass 1 22 -94.88 26.26 0.00 Pass 1 23 -99.10 22.65 0.00 Fail 1 24 -99.89 23.12 0.00 Fail 1 25 -101.31 22.10 0.00 Fail 1 26 -91.70 28.75 0.00 Pass 1 27 -101.21 21.65 0.00 Fail 1 28 -103.86 19.75 0.00 Fail 1 29 -102.87 20.82 0.00 Fail 1 30 -96.15 25.93 0.00 Fail 1 31 -95.08 26.69 0.00 Fail 1 32 -98.97 23.62 0.00 Fail 1 33 -101.27 21.72 0.00 Fail 1 34 -104.08 19.21 0.00 Fail 1 35 -102.26 21.08 0.00 Fail 2 1 -102.46 21.13 0.00 Fail 2 2 -103.81 20.29 0.00 Fail 2 3 -104.77 19.89 0.00 Fail 2 4 -103.12 19.67 0.00 Fail 2 5 -104.57 18.36 0.00 Fail 2 6 -103.07 18.91 0.00 Fail 2 7 -105.02 18.59 0.00 Fail 2 8 -105.89 17.19 0.00 Fail 2 9 -97.46 20.05 0.00 Fail 2 10 -102.19 18.22 0.00 Fail 2 11 -106.21 17.98 0.00 Fail 2 12 -105.36 18.63 0.00 Fail 2 13 -103.97 20.34 0.00 Fail 2 14 -97.94 24.85 0.00 Fail 2 15 -99.85 23.53 0.00 Fail

Power (dBm)

DL

S/N (dB)

DL

FBER

DL

DAQ

UL

Power (dBm)

UL

S/N (dB)

UL

FBER

ID

UL

Tested

Result DL Loss (dB)

Comment

2 16 -100.49 18.93 0.00 Fail 2 17 -102.31 15.74 0.00 Fail 2 18 -110.12 14.42 0.00 Fail 2 19 -105.81 18.62 0.00 Fail 2 20 -103.46 20.51 0.00 Fail 2 21 -99.74 21.51 0.00 Fail 2 22 -109.03 14.95 0.00 Fail 2 23 -105.64 18.56 0.00 Fail 2 24 -101.84 18.96 0.00 Fail 2 25 -98.60 22.24 0.00 Fail 2 26 -100.67 23.06 0.00 Fail 2 27 -103.83 19.68 0.00 Fail 2 28 -104.13 16.97 0.00 Fail 2 29 -103.17 20.63 0.00 Fail 2 30 -101.08 20.57 0.00 Fail 3 1 -96.17 26.76 0.00 Fail 3 2 -89.01 27.33 0.00 Pass 3 3 -94.00 26.20 0.00 Pass 3 4 -93.02 24.47 0.00 Pass 3 5 -90.18 26.05 0.00 Pass 3 6 -96.73 23.96 0.00 Fail 3 7 -98.42 25.39 0.00 Fail 3 8 -95.82 26.15 0.00 Fail 3 9 -94.49 26.49 0.00 Pass 3 10 -95.20 25.04 0.00 Fail 3 11 -93.97 25.43 0.00 Pass 3 12 -98.78 23.12 0.00 Fail 3 13 -95.88 26.36 0.00 Fail 3 14 -105.66 17.90 0.00 Fail 3 15 -108.67 15.81 0.00 Fail 3 16 -104.81 19.62 0.00 Fail 3 17 -99.83 23.13 0.00 Fail 3 18 -100.21 23.24 0.00 Fail 3 19 -104.77 18.39 0.00 Fail 3 20 -107.41 16.70 0.00 Fail 3 22 -97.18 25.31 0.00 Fail 3 23 -101.71 21.51 0.00 Fail 3 24 -103.17 20.78 0.00 Fail 3 25 -97.65 24.62 0.00 Fail 3 27 -93.48 27.22 0.00 Pass 3 28 -96.44 26.66 0.00 Fail 3 29 -99.21 23.71 0.00 Fail 3 30 -98.63 25.04 0.00 Fail 4 5 -102.41 22.28 0.00 Fail 4 6 -101.13 21.77 0.00 Fail

Floor: 203

Cable Loss

Ph. Type Mod NAC Area Points passed (%)

Critical Points passed (%)

772.53125 P25 Savannah Primay

0.00 0.00 32/66 (48%) 0/0 (0%)

Area Width (ft)

Area Height (ft)

Ignore Area Color

Comments

1 16 298.92 13.72 21.80 Black 2 20 302.00 16.86 17.91 Black 3 9 382.96 16.12 23.76 Black 4 25 261.68 11.18 23.41 Black

Power (dBm)

DL

DAQ

UL

Power (dBm)

ID

UL

Tested

Result DL Loss (dB)

Comment

1 1 -92.99 Pass 1 2 -101.71 Fail 1 3 -97.73 Fail 1 4 -95.35 Fail 1 5 -88.77 Pass 1 6 -92.10 Pass 1 7 -92.13 Pass 1 8 -95.99 Fail 1 9 -85.83 Pass 1 10 -85.85 Pass 1 11 -88.62 Pass 1 12 -89.23 Pass 1 13 -83.79 Pass 1 14 -85.15 Pass 1 15 -88.28 Pass 1 16 -88.78 Pass 2 1 -93.20 Pass 2 2 -90.30 Pass 2 4 -105.63 Fail 2 5 -98.89 Fail 2 6 -93.09 Pass 2 7 -92.32 Pass 2 9 -102.37 Fail 2 10 -105.16 Fail 2 11 -85.47 Pass 2 12 -96.66 Fail 2 13 -96.00 Fail 2 14 -105.01 Fail 2 15 -103.46 Fail 2 16 -85.72 Pass 2 17 -86.35 Pass 2 18 -95.66 Fail 2 19 -98.09 Fail 2 20 -101.99 Fail 3 1 -99.86 Fail 3 2 -90.51 Pass 3 3 -89.47 Pass 3 4 -99.55 Fail 3 5 -99.94 Fail 3 6 -96.27 Fail 3 7 -98.84 Fail 3 8 -94.85 Pass 3 9 -91.93 Pass 4 1 -88.36 Pass 4 2 -93.27 Pass 4 3 -100.31 Fail

4 4 NT NT NT NT NT

4 5 NT NT NT NT NT

4 6 -86.01 Pass

Power (dBm)

DL

DAQ

UL

Power (dBm)

ID

UL

Tested

Result DL Loss (dB)

Comment

4 7 -94.84 Pass 4 8 -104.06 Fail 4 9 -101.03 Fail 4 10 -93.72 Pass 4 11 -92.24 Pass 4 12 -95.87 Fail 4 13 -107.54 Fail 4 14 -102.76 Fail 4 15 -105.77 Fail 4 16 -88.02 Pass 4 17 -102.72 Fail 4 18 -96.13 Fail 4 19 -97.93 Fail 4 20 -96.13 Fail 4 21 -91.93 Pass 4 22 -93.30 Pass 4 23 -102.32 Fail 4 24 -100.43 Fail 4 25 -99.25 Fail

Cable Loss

Ph. Type Mod NAC Area Points passed (%)

Critical Points passed (%)

772.53125 P25 Savannah Primay

0.00 0.00 1 CC CQPSK 2C0 11/66 (16%) 0/0 (0%)

Area Width (ft)

Area Height (ft)

Ignore Area Color

Comments

1 16 298.92 13.72 21.80 Black 2 20 302.00 16.86 17.91 Black 3 9 382.96 16.12 23.76 Black 4 25 261.68 11.18 23.41 Black

Power (dBm)

DL

S/N (dB)

DL

FBER

DL

DAQ

UL

Power (dBm)

UL

S/N (dB)

UL

FBER

ID

UL

Tested

Result DL Loss (dB)

Comment

1 1 -99.74 20.09 0.00 Fail 1 2 -109.03 15.17 0.00 Fail 1 3 -103.47 20.70 0.00 Fail 1 4 -102.87 21.28 0.00 Fail 1 5 -98.02 24.08 0.00 Fail 1 6 -100.15 23.27 0.00 Fail 1 7 -100.58 22.13 0.00 Fail 1 8 -104.86 12.75 0.00 Fail 1 9 -94.31 23.38 0.00 Pass 1 10 -93.86 25.18 0.00 Pass 1 11 -95.26 25.24 0.00 Fail 1 12 -99.49 23.55 0.00 Fail 1 13 -89.76 28.97 0.00 Pass 1 14 -90.19 28.96 0.00 Pass 1 15 -96.12 23.44 0.00 Fail 1 16 -93.52 27.12 0.00 Pass 2 1 -99.66 22.61 0.00 Fail 2 2 -99.41 22.79 0.00 Fail 2 4 -110.43 8.63 0.00 Fail 2 5 -92.91 Fail 2 6 -99.59 24.38 0.00 Fail 2 7 -103.14 20.44 0.00 Fail 2 9 -106.19 16.41 0.00 Fail 2 10 -92.98 Fail 2 11 -97.32 17.09 0.00 Fail 2 12 -101.76 22.18 0.00 Fail 2 13 -100.72 17.27 0.00 Fail 2 14 -108.52 15.89 0.00 Fail 2 15 -92.93 Fail 2 16 -95.01 23.17 0.00 Fail 2 17 -92.85 27.62 0.00 Pass 2 18 -102.24 17.21 0.00 Fail 2 19 -104.00 21.33 0.00 Fail 2 20 -92.84 Fail 3 1 -92.69 Fail 3 2 -92.33 22.32 0.00 Pass 3 3 -91.44 19.24 0.00 Fail 3 4 -92.73 Fail 3 5 -92.85 Fail 3 6 -96.53 19.02 0.00 Fail 3 7 -92.56 Fail 3 8 -93.74 21.51 0.00 Pass 3 9 -92.69 26.52 0.00 Pass 4 1 -92.69 27.42 0.00 Pass 4 2 -97.76 22.02 0.00 Fail 4 3 -102.66 19.59 0.00 Fail

4 4 NT NT NT NT NT NT NT NT NT

4 5 NT NT NT NT NT NT NT NT NT

4 6 -95.61 25.53 0.00 Fail

Power (dBm)

DL

S/N (dB)

DL

FBER

DL

DAQ

UL

Power (dBm)

UL

S/N (dB)

UL

FBER

ID

UL

Tested

Result DL Loss (dB)

Comment

4 7 -98.61 24.22 0.00 Fail 4 8 -109.02 14.24 0.00 Fail 4 9 -107.68 13.16 0.00 Fail 4 10 -96.35 23.91 0.00 Fail 4 11 -99.13 22.29 0.00 Fail 4 12 -100.93 19.77 0.00 Fail 4 13 -108.14 14.03 0.00 Fail 4 14 -108.28 14.17 0.00 Fail 4 15 -109.73 13.86 0.00 Fail 4 16 -91.70 27.56 0.00 Pass 4 17 -105.93 17.31 0.00 Fail 4 18 -101.86 21.70 0.00 Fail 4 19 -101.95 21.85 0.00 Fail 4 20 -103.73 20.56 0.00 Fail 4 21 -98.53 23.51 0.00 Fail 4 22 -97.96 22.81 0.00 Fail 4 23 -102.39 13.96 0.00 Fail 4 24 -106.73 18.00 0.00 Fail 4 25 -92.39 Fail

Floor: 204

Cable Loss

Ph. Type Mod NAC Area Points passed (%)

Critical Points passed (%)

772.53125 P25 Savannah Primay

0.00 0.00 42/63 (66%) 0/0 (0%)

Area Width (ft)

Area Height (ft)

Ignore Area Color

Comments

1 10 236.76 15.72 15.07 Black 2 10 253.68 11.48 22.09 Black 3 25 171.87 11.36 15.12 Black 4 20 253.51 11.30 22.44 Black

Power (dBm)

DL

DAQ

UL

Power (dBm)

ID

UL

Tested

Result DL Loss (dB)

Comment

1 1 -89.61 Pass 1 2 -89.54 Pass 1 3 -87.99 Pass 1 4 -89.37 Pass 1 5 -88.29 Pass 1 6 -92.18 Pass 1 7 -87.04 Pass 1 8 -86.88 Pass 1 9 -88.88 Pass 1 10 -86.45 Pass 2 1 -87.93 Pass 2 2 -82.96 Pass 2 3 -88.48 Pass 2 4 -85.43 Pass 2 5 -86.45 Pass 2 6 -88.55 Pass 2 7 -90.13 Pass 2 8 -92.62 Pass 2 9 -93.61 Pass 2 10 -87.73 Pass 3 1 -94.49 Pass 3 2 -97.46 Fail 3 3 -109.98 Fail 3 4 -97.60 Fail 3 5 -85.93 Pass 3 6 -97.12 Fail 3 7 -101.12 Fail 3 8 -102.55 Fail 3 11 -94.64 Pass 3 12 -100.08 Fail 3 13 -97.47 Fail 3 14 -98.52 Fail 3 15 -94.34 Pass 3 16 -101.91 Fail 3 17 -100.49 Fail 3 18 -93.61 Pass 3 19 -95.62 Fail 3 20 -98.80 Fail 3 21 -98.55 Fail 3 22 -101.82 Fail 3 23 -100.78 Fail 3 24 -105.71 Fail 3 25 -98.01 Fail 4 1 -84.45 Pass 4 2 -90.62 Pass 4 3 -88.31 Pass 4 4 -95.73 Fail 4 5 -93.21 Pass 4 6 -84.90 Pass

Power (dBm)

DL

DAQ

UL

Power (dBm)

ID

UL

Tested

Result DL Loss (dB)

Comment

4 7 -82.36 Pass 4 8 -100.59 Fail 4 9 -96.72 Fail 4 10 -94.16 Pass 4 11 -82.72 Pass 4 12 -91.93 Pass 4 13 -92.85 Pass 4 14 -92.81 Pass 4 15 -88.47 Pass 4 16 -78.45 Pass 4 17 -88.17 Pass 4 18 -90.86 Pass 4 19 -85.83 Pass 4 20 -89.14 Pass

Cable Loss

Ph. Type Mod NAC Area Points passed (%)

Critical Points passed (%)

772.53125 P25 Savannah Primay

0.00 0.00 1 CC CQPSK 2C0 23/63 (36%) 0/0 (0%)

Area Width (ft)

Area Height (ft)

Ignore Area Color

Comments

1 10 236.76 15.72 15.07 Black 2 10 253.68 11.48 22.09 Black 3 25 171.87 11.36 15.12 Black 4 20 253.51 11.30 22.44 Black

Power (dBm)

DL

S/N (dB)

DL

FBER

DL

DAQ

UL

Power (dBm)

UL

S/N (dB)

UL

FBER

ID

UL

Tested

Result DL Loss (dB)

Comment

1 1 -94.97 27.33 0.00 Pass 1 2 -92.94 27.50 0.00 Pass 1 3 -92.12 28.24 0.00 Pass 1 4 -94.92 26.65 0.00 Pass 1 5 -94.17 27.64 0.00 Pass 1 6 -96.88 24.31 0.00 Fail 1 7 -90.66 26.59 0.00 Pass 1 8 -91.78 26.72 0.00 Pass 1 9 -90.16 27.89 0.00 Pass 1 10 -88.98 29.60 0.00 Pass 2 1 -94.82 24.24 0.00 Pass 2 2 -90.82 28.66 0.00 Pass 2 3 -97.38 25.58 0.00 Fail 2 4 -89.41 28.56 0.00 Pass 2 5 -91.19 28.12 0.00 Pass 2 6 -93.22 25.07 0.00 Pass 2 7 -91.44 29.31 0.00 Pass 2 8 -98.52 24.36 0.00 Fail 2 9 -98.07 24.12 0.00 Fail 2 10 -90.64 25.46 0.00 Pass 3 1 -96.90 25.23 0.00 Fail 3 2 -105.06 11.10 13.51 Fail 3 3 -112.67 7.51 0.00 Fail 3 4 -105.21 14.90 0.00 Fail 3 5 -102.51 19.08 0.00 Fail 3 6 -94.18 18.47 0.00 Fail 3 7 -103.10 12.24 0.00 Fail 3 8 -108.36 14.91 0.00 Fail 3 11 -99.63 24.31 0.00 Fail 3 12 -102.81 20.23 0.00 Fail 3 13 -102.99 20.82 0.00 Fail 3 14 -105.11 12.01 0.00 Fail 3 15 -102.41 16.62 0.00 Fail 3 16 -106.77 14.94 24.32 Fail 3 17 -105.44 18.41 0.00 Fail 3 18 -97.67 24.29 0.00 Fail 3 19 -101.83 21.59 0.00 Fail 3 20 -102.49 21.44 0.00 Fail 3 21 -103.09 22.21 0.00 Fail 3 22 -107.60 16.99 0.00 Fail 3 23 -103.60 17.82 0.00 Fail 3 24 -109.82 14.89 0.00 Fail 3 25 -104.58 17.05 0.00 Fail 4 1 -93.69 24.60 0.00 Pass 4 2 -96.15 19.40 0.00 Fail 4 3 -97.94 15.92 0.00 Fail 4 4 -104.25 16.47 0.00 Fail 4 5 -101.35 21.90 0.00 Fail 4 6 -91.39 23.33 0.00 Pass

Power (dBm)

DL

S/N (dB)

DL

FBER

DL

DAQ

UL

Power (dBm)

UL

S/N (dB)

UL

FBER

ID

UL

Tested

Result DL Loss (dB)

Comment

4 7 -90.49 26.06 0.00 Pass 4 8 -103.25 3.25 0.00 Fail 4 9 -101.55 21.37 0.00 Fail 4 10 -99.72 21.43 0.00 Fail 4 11 -87.54 26.01 0.00 Pass 4 12 -95.95 25.10 0.00 Fail 4 13 -98.91 20.10 0.00 Fail 4 14 -96.39 25.41 0.00 Fail 4 15 -95.27 26.48 0.00 Fail 4 16 -85.93 27.43 0.00 Pass 4 17 -93.04 26.49 0.00 Pass 4 18 -97.05 19.15 0.00 Fail 4 19 -91.50 29.61 0.00 Pass 4 20 -97.19 25.48 0.00 Fail