25.041_JCS_STORAGE BUILDING 3-10-2025.pdf
PDF 1 MB Posted
- Attached to
- COLD STORAGE SHED
- Solicitation number
- RFP-JCS-250000002133-1
- Issued by
- Gratiot County, Michigan
About this file
The documents represent construction plans for a storage building project for Jonesville Community Schools, located in Jonesville, Michigan. The project involves constructing a new 30' x 40' storage building at 460 Adrian St, with detailed architectural, electrical, and site plans prepared by Ignyte Design and dated March 10, 2025. The plans include comprehensive specifications for electrical systems, site layout, grading, and structural details, with the project designed to meet 2015-2023 Michigan and National building, mechanical, electrical, and energy codes.
The electrical system for the storage building will be a 120/240-volt, single-phase, 100-amp service connected to the existing utility infrastructure. The building will feature surface-mounted lighting fixtures, wall-mounted fixtures with battery backup, an electric unit heater, an exhaust fan, and a louver for ventilation. The electrical plan includes a detailed panel schedule, lighting fixture specifications, and grounding requirements. The estimated connected load is approximately 6 kVA, with a demand load of 7 kVA. The site plan shows the building's location relative to existing structures, with provisions for underground electrical conduits and a ground mat system.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ConcreteFFA.pdf | ||
| ConstructionFFA.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
THE FOLLOWING DIMENSION
EQUALS ONE INCH WHEN PRINTED
TO SCALE.
1"
Project No:
Drawing Title:
© 2025 IGNYTE DESIGN
SCALE
STAMP
Issued For: Date
Engineer:
Applicable Codes:
G000
COVER SHEET
JONESVILLE
COMMUNITY
SCHOOLS
24.150
MARCH 10, 2025CONSTRUCTION
JONESVILLE COMMUNITY SCHOOLS
STORAGE BUILDING
460 Adrian St, Jonesville, MI 49250
IGNYTE DESIGN
123 DEVISSER ALLEY
KALAMAZOO, MI 49007
(269) 203-5058
WWW.IGNYTE.DESIGN
2015 MICHIGAN BUILDING CODE
2021 MICHIGAN MECHANICAL CODE
2021 MICHIGAN PLUMBING CODE
2015 MICHIGAN ENERGY CODE
2023 NATIONAL ELECTRIC CODE
Drawing Index:
SHEET NO SHEET NAME
G000 COVER SHEET
C1.0 EXISTING CONDITIONS & DEMO PLAN
C2.0 SITE LAYOUT
C3.0 GRADING & SESC PLAN
A101 ARCHITECTURAL
E000 ELECTRICAL SYMBOLS AND SPECIFICATION
E010 ELECTRICAL SITE PLAN
E110 FIRST FLOOR ELECTRICAL AND MECHANICAL PLAN
6' CHAINLINK FENCE
4' WIRE FENCE
32.3'
.2
32.4'
.1
ADRIAN ST
M
AU
N M
EE S
T
EAST ST
K E
IT
H
S T
G
LE
N D
A
LE
S T
C1.0
E X
IS
IT
N G
C O
N D
IT
IO
N S
D
E M
O P
LA
N
PLANS PREPARED BY:
MICHIGAN | INDIANA | ILLINOIS | OHIO
TC
PLANS PREPARED BY:
www.arengineeringllc.com
269.250.5991 PHONE | 866.569.0604 FAX
CHECKED:
DRAWN: LM
SHEET NUMBER
D
AT
E
IS
SU
ED
F O
R
BY
JOB NUMBER
R
EP
R O
D U
C
TI
O N
, C O
PY
IN
G O
R O
TH
ER
U
SE
O F
TH
IS
D R
AW
IN
G W
IT
H
O U
T W
R
IT
TE
N
C O
N
SE
N T
IS
P
R O
H
IB
IT
ED
A
R E
N G
IN
EE
R
IN
G
DATE
N o.
24191003
12/27/2024
43210
PR
O
JE
C
T:
SH
EE
T
TI
TL
E:
C
LI
EN
T:
JO
N
ES
VI
LL
E
SC
H
O O
LS
S
TO
R
AG
E
BL
D
G
IG
N
YT
E
SI
TE
A
D D
R
ES
S:
SI
TE
S
EC
TI
O
N
AD
R
IA
N
S T
SE
C
TI
O
N
4, T
S, R
W
ST
ATE OF MICHIGAN
L I C E N S E D P R O F E S S I O N A L E N G
I N E E
R
SPENCER O'DELL, P.E.
No. 6201309325
ALL UTILITIES AS SHOWN ARE APPROXIMATE LOCATIONS DERIVED
FROM ACTUAL MEASUREMENTS AND AVAILABLE RECORDS. THEY
SHOULD NOT BE INTERPRETED TO BE EXACT LOCATION NOR
SHOULD IT BE ASSUMED THAT THEY ARE THE ONLY UTILITIES IN THE
AREA. FIELD WORK PERFORMED BY: AR ENGINEERING
1. ALL WORK SHALL CONFORM TO ALL LOCAL, STATE AND FEDERAL LAWS, RULES AND
REGULATIONS IN FORCE AT TIME OF CONSTRUCTION.
2. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS,
PERMIT COSTS, TAP FEES, METER DEPOSITS, PERMANENT UTILITY APPLICATIONS,
BONDS, AND OTHER FEES REQUIRED FOR PROPOSED WORK. THIS SHALL INCLUDE,
BUT SHALL NOT BE LIMITED TO THOSE REQUIRED BY THE CITY OF JONESVILLE,
MDOT AND HILLSDALE COUNTY.
3. CONTACT "MISS DIG 811" AT 1-800-482-7171 FOR LOCATION OF UNDERGROUND
UTILITIES A MINIMUM OF 48 HOURS BEFORE COMMENCING EXCAVATION WORK.
THIS DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY OF NOTIFYING
UTILITY OWNERS WHO ARE NOT PART OF THE "811" ALERT SYSTEM. THE
CONTRACTOR SHALL CONDUCT HIS OPERATIONS IN A MANNER AS TO ENSURE
THAT THOSE UTILITIES NOT REQUIRING RELOCATION WILL NOT BE DISTURBED.
4. DEMOLISH & REMOVE ALL EXISTING SITE FEATURES AS REQUIRED.
5. ALL SOIL EROSION CONTROL MEASURES SHALL BE IN PLACE PRIOR TO DEMOLITION.
6. ALL EXCAVATION SHALL BE IN ACCORDANCE WITH THE TECHNICAL SPECIFICATIONS
AND GEOTECHNICAL REPORT.
7. ALL EXISTING ELEVATIONS ARE TO BE VERIFIED AND ACCEPTED AS SHOWN PRIOR
TO COMMENCEMENT OF WORK.
8. CONTRACTOR SHALL TAKE PRECAUTIONS TO AVOID TRACKING SOIL ONTO
ADJACENT ROADWAYS. CONTRACTOR SHALL SWEEP IMMEDIATELY IF OCCURS.
9. ANY DISTURBED AREA WHICH WILL BE LEFT UNWORKED 15 DAYS OR LONGER MUST
BE SEEDED TO ESTABLISH VEGETATION FOR TEMPORARY STABILIZATION. BASINS
TO BE SEEDED AND MULCH BLANKETS APPLIED IMMEDIATELY TO PROVIDE A
STABLE BASE AND AVOID EXCESSIVE EROSION.
10. REVIEW ALL THE REMOVALS AND PROTECTION WITH OWNER PRIOR TO
COMMENCING CONSTRUCTION. INSTALL TEMPORARY SNOW FENCE AROUND ALL
TREES REQUIRING PROTECTION. SNOW FENCE SHALL BE PLACED AT EDGE OF DRIP
LINE.
11. SAWCUT ALL CURB, SIDEWALK, AND PAVEMENTS PRIOR TO REMOVAL. ADDITIONAL
SAWCUT MAY BE NECESSARY PRIOR TO REPLACEMENT TO ENSURE CLEAN EDGE.
12. ALL REMOVALS SHALL BE TAKEN OFF-SITE AND DISPOSED OF PROPERLY. NO
STOCKPILE OR BURNING OF DEBRIS IS ALLOWED.
13. ALL REMOVALS SHALL BE TO THE LIMITS INDICATED ABOVE UNLESS OTHERWISE
DIRECTED BY THE ENGINEER. UNAUTHORIZED REMOVALS AND SUBSEQUENT
REPLACEMENT SHALL BE AT THE CONTRACTOR'S EXPENSE.
14. REMOVE, STORE, AND RESET ANY EXISTING SIGNS AS DIRECTED BY THE
ENGINEER/OWNER.
15. REMOVE ALL TREES TO THE CLEARING LIMITS AS SHOWN. REMOVE ALL EXISTING
TREES, STUMPS AND BRUSH FROM THE SITE AS NECESSARY TO CONSTRUCT THE
IMPROVEMENTS.
16. THE CONTRACTOR SHALL DEMOLISH AND REMOVE ANY ITEMS REMAINING FROM
THE EXISTING BUILDING, IN ITS ENTIRETY, INCLUDING WALLS, FOUNDATIONS AND
FOOTINGS. ALL BUILDING DRAINS AND UTILITY LEADS SHALL BE LOCATED AND
PROPERLY PLUGGED. UTILITY LEAD WORK SHALL BE COORDINATED WITH THE
APPROPRIATE UTILITY COMPANY.
17. BACKFILL EXCAVATED AREAS WITH CLEAN GRANULAR FILL COMPACTED TO 95% OF
THE MATERIAL UNIT WEIGHT BY MODIFIED PROCTOR.
18. CONTROL SHALL BE MAINTAINED OVER THE SITE AND OPERATION TO ELIMINATE
HAZARDS TO THE PUBLIC. NAILS OR OTHER TIRE PUNCTURING ITEMS SHALL NOT
BE DROPPED ON STREETS, ALLEYS AND ADJACENT PROPERTY. PUBLIC STREETS,
CURBS AND SIDEWALKS SHALL BE PROTECTED FROM DAMAGE. THE PERSON
ENGAGED IN THE DEMOLITION WORK SHALL BE LIABLE FOR ANY AND ALL DAMAGE
TO CURBS, STREETS, SIDEWALKS AND OTHER PUBLIC OR PRIVATE PROPERTY AND
FOR ANY BODILY INJURY OCCURRING AS A RESULT OF THE DEMOLITION WORK.
DEMOLITION NOTES N
1 inch = ft.
20 4030
EXISTING
BUILDING
EXISITING LIGHT POLE
EXISTING LIGHT POLE
EXISITNG CONCRETE DRIVE
EXISITNG BRICK SIDEWALK
21' ASPHALT ROAD
LOCATION MAP
NOT TO SCALE
N
41°58'35.1"N 84°39'08.9"W
EXISTING ASPHALT
LEGEND
EXISTING CONCRETE
EXISTING BRICK
EXISTING CONIFEROUS TREE
SAWCUT
SAWCUT EDGE OF ASPHALT
FOR CLEAN CONNECTION
AutoCAD SHX Text SPENCER ANDREW O'DELL ENGINEER No. 6201309325
AutoCAD SHX Text
SITE LOCATION
32.3'
.2
32.4'
.1
C2.0
S
IT
E L
A Y
O U
T
PLANS PREPARED BY:
MICHIGAN | INDIANA | ILLINOIS | OHIO
TC
PLANS PREPARED BY:
www.arengineeringllc.com
269.250.5991 PHONE | 866.569.0604 FAX
CHECKED:
DRAWN: LM
SHEET NUMBER
D
AT
E
IS
SU
ED
F O
R
BY
JOB NUMBER
R
EP
R O
D U
C
TI
O N
, C O
PY
IN
G O
R O
TH
ER
U
SE
O F
TH
IS
D R
AW
IN
G W
IT
H
O U
T W
R
IT
TE
N
C O
N
SE
N T
IS
P
R O
H
IB
IT
ED
A
R E
N G
IN
EE
R
IN
G
DATE
N o.
24191003
12/27/2024
43210
PR
O
JE
C
T:
SH
EE
T
TI
TL
E:
C
LI
EN
T:
JO
N
ES
VI
LL
E
SC
H
O O
LS
S
TO
R
AG
E
BL
D
G
IG
N
YT
E
SI
TE
A
D D
R
ES
S:
SI
TE
S
EC
TI
O
N
AD
R
IA
N
S T
SE
C
TI
O
N
4, T
S, R
W
ST
ATE OF MICHIGAN
L I C E N S E D P R O F E S S I O N A L E N G
I N E E
R
SPENCER O'DELL, P.E.
No. 6201309325
1. DIMENSIONS TAKE PRECEDENCE OVER SCALE. CONTRACTOR
TO VERIFY ALL DIMENSIONS IN FIELD.
2. IF ANY ERRORS, DISCREPANCIES, OR OMISSIONS BECOME
APPARENT, THESE SHALL BE BROUGHT TO THE ATTENTION
OF THE ARCHITECT/ ENGINEER PRIOR TO CONSTRUCTION OF
ANYTHING AFFECTED SO THAT CLARIFICATION OR REDESIGN
MAY OCCUR.
3. ALL CURB RADII AND DIMENSIONS ARE TO FACE OF CURB.
CURB TO BE PROVIDED WHERE SHOWN AND INTEGRAL WITH
SIDEWALK AT PAVING EDGE.
4. SLOPE GRADES UNIFORMLY BETWEEN ELEVATIONS SHOWN.
NOMINAL GRADING, SLOPE SIDEWALKS AWAY FROM BUILDING
AT 1/4" PER FOOT ON ENTRY WALK.
1. PROPERTY INFORMATION:
PARCEL #: 21-004-400-004-04-6-3
SITE AREA: 1,948,874 SF (44.74 AC)
OWNER: JONESVILLE COMMUNITY SCHOOLS
ALL UTILITIES AS SHOWN ARE APPROXIMATE LOCATIONS DERIVED
FROM ACTUAL MEASUREMENTS AND AVAILABLE RECORDS. THEY
SHOULD NOT BE INTERPRETED TO BE EXACT LOCATION NOR SHOULD
IT BE ASSUMED THAT THEY ARE THE ONLY UTILITIES IN THE AREA.
FIELD WORK PERFORMED BY: AR ENGINEERING
GENERAL NOTES
SITE DATA N
1 inch = ft.
20 4030
PROPOSED
STORAGE
BLDG
40'
10'
40'
EXISTING
BUILDING
EXISITNG LIGHPOLE
EXISITNG LIGHPOLE
EXISITNG CONCRETE DRIVE
EXISITNG BRICK SIDEWALK
21' ASPHALT ROAD
PROPOSED CONCRETE
SIDEWALK
PROPOSED CONCRETE
DRIVE
PROPOSED CONCRETE PAVEMENT
AND SIDEWALK
LEGEND
EXISTING CONCRETE
EXISTING BRICK
*2% MAX
*TRANSVERSE SIDEWALK SLOPES ARE TYPICALLY 1.5% OR 2% MAXIMUM.
IN ORDER TO MEET SITE CONDITIONS, IF THE TRANSVERSE SLOPE IS
REQUIRED TO BE LESS THAN 1.5%, LONGITUDINAL DRAINAGE MUST BE
PROVIDED.
REFER TO MDOT STANDARD PLAN R-29-I
(DRIVEWAY OPENINGS & APPROACHES, AND CONCRETE SIDEWALK)
4" MIN. COMPACTED (95% DENSITY)
MDOT CLASS II SAND BASE
4" CONC. SIDEWALK (GRADE P1 MIX
DESIGN 6.0 SACK CONCRETE MIX)
4" TOPSOIL, MDOT ROADSIDE SEED
AND MULCH (TYP.)
4" R
(TYP.)
5' WIDE
6"
TYP.
CONCRETE & SIDEWALK
SECTION
C2.0 - 030301 NOT TO SCALE
EXISTING CONIFEROUS TREE
R10 ' R10'
OVERHEAD DOOR
MAN DOOR
5'
SPENCER ANDREW O'DELL ENGINEER No. 6201309325
32.3'
.2
32.4'
.1
1113.32
1113.05
1113.63
1113.60
1113.50 1113.50
1113.50
1113.50
1113.50
1113.501113.421113.42 1113.42
1113.30
1113.42
1113.42
1112.98
1112.91
1112.80
1112.69
1112.61
1113.25
1113.25
1113.50
1113.50
1112.55
1113.42
C3.0
G R
A D
IN
G
S
E S
C P
LA
N
PLANS PREPARED BY:
MICHIGAN | INDIANA | ILLINOIS | OHIO
TC
PLANS PREPARED BY:
www.arengineeringllc.com
269.250.5991 PHONE | 866.569.0604 FAX
CHECKED:
DRAWN: LM
SHEET NUMBER
D
AT
E
IS
SU
ED
F O
R
BY
JOB NUMBER
R
EP
R O
D U
C
TI
O N
, C O
PY
IN
G O
R O
TH
ER
U
SE
O F
TH
IS
D R
AW
IN
G W
IT
H
O U
T W
R
IT
TE
N
C O
N
SE
N T
IS
P
R O
H
IB
IT
ED
A
R E
N G
IN
EE
R
IN
G
DATE
N o.
24191003
12/27/2024
43210
PR
O
JE
C
T:
SH
EE
T
TI
TL
E:
C
LI
EN
T:
JO
N
ES
VI
LL
E
SC
H
O O
LS
S
TO
R
AG
E
BL
D
G
IG
N
YT
E
SI
TE
A
D D
R
ES
S:
SI
TE
S
EC
TI
O
N
AD
R
IA
N
S T
SE
C
TI
O
N
4, T
S, R
W
ST
ATE OF MICHIGAN
L I C E N S E D P R O F E S S I O N A L E N G
I N E E
R
SPENCER O'DELL, P.E.
No. 6201309325
1. ALL WORK SHALL CONFORM TO ALL LOCAL, STATE AND FEDERAL LAWS, RULES AND REGULATIONS IN
FORCE AT TIME OF CONSTRUCTION.
2. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS, PERMIT COSTS, TAP FEES, METER DEPOSITS, PERMANENT UTILITY APPLICATIONS, BONDS, AND OTHER FEES REQUIRED FOR PROPOSED WORK. THIS SHALL INCLUDE, BUT SHALL NOT BE LIMITED TO THOSE REQUIRED BY THE
MICHIGAN DEPARTMENT OF TRANSPORTATION.
3. CONTACT "MISS DIG 811" AT 1-800-482-7171 FOR LOCATION OF UNDERGROUND UTILITIES A MINIMUM OF 48 HOURS BEFORE COMMENCING EXCAVATION WORK. THIS DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY OF NOTIFYING UTILITY OWNERS WHO ARE NOT PART OF THE "811" ALERT SYSTEM. THE CONTRACTOR SHALL CONDUCT HIS OPERATIONS IN A MANNER AS TO ENSURE THAT THOSE UTILITIES
NOT REQUIRING RELOCATION WILL NOT BE DISTURBED.
4. DEMOLISH & REMOVE ALL EXISTING SITE FEATURES AS REQUIRED.
5. MATCH EXISTING GRADES AROUND PERIMETER WITH SLOPES AS SHOWN.
6. ALL SPOT ELEVATIONS ARE TOP OF PAVEMENT GRADES AT EDGE OF METAL (EOM) UNLESS OTHERWISE
NOTED.
7. ALL SOIL EROSION CONTROL MEASURES SHALL BE IN PLACE PRIOR TO MASS GRADING.
8. ALL EXCAVATION SHALL BE IN ACCORDANCE WITH THE TECHNICAL SPECIFICATIONS AND GEOTECHNICAL
REPORT.
9. ALL EXISTING ELEVATIONS ARE TO BE VERIFIED AND ACCEPTED AS SHOWN PRIOR TO COMMENCEMENT
OF WORK.
10. CONTRACTOR SHALL TAKE PRECAUTIONS TO AVOID TRACKING SOIL ONTO ADJACENT ROADWAYS.
CONTRACTOR SHALL SWEEP IMMEDIATELY IF OCCURS.
11. ANY DISTURBED AREA WHICH WILL BE LEFT UNWORKED 15 DAYS OR LONGER MUST BE SEEDED TO ESTABLISH VEGETATION FOR TEMPORARY STABILIZATION. BASINS TO BE SEEDED AND MULCH BLANKETS
APPLIED IMMEDIATELY TO PROVIDE A STABLE BASE AND AVOID EXCESSIVE EROSION.
LIMITS OF CONSTRUCTION
SILT FENCE
1 ALL CONSTRUCTION METHODS SHALL BE DONE IN COMPLIANCE WITH MDOT-MDEQ. THE OWNER SHALL BE RESPONSIBLE FOR OBTAINING A "SOIL EROSION PERMIT" FROM THE COUNTY AND A "PERMIT BY RULE/NOTICE OF COVERAGE" FROM MDEQ, IF APPLICABLE, PRIOR TO START OF CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ALL REQUIREMENTS OF THE COUNTY "SOIL EROSION PERMIT" AND FOR ALL CERTIFIED STORM WATER INSPECTION SERVICE REQUIRED BY THE "PERMIT BY RULE." EROSION CONTROL MEASURES SHOWN ON THE PLANS ARE THE MINIMUM REQUIREMENTS AND SHALL NOT RELIEVE THE CONTRACTOR'S RESPONSIBILITY FOR PROVIDING ALL
REQUIRED EROSION CONTROL MEASURES.
2. AVOID UNNECESSARY DISTURBING OR REMOVING OF EXISTING VEGETATED TOPSOIL OR EARTH COVER, THESE COVER AREAS ACT AS SEDIMENT FILTERS.
3. ALL TEMPORARY SOIL EROSION PROTECTION SHALL REMAIN IN PLACE UNTIL REMOVAL IS REQUIRED
FOR FINAL CLEAN UP AND APPROVAL.
4. GEOTEXTILE SILT FENCE SHALL BE INSTALLED AS REQUIRED WHEN CROSSING CREEKS OR WHEN ADJACENT TO WETLANDS OR SURFACE WATER BODIES TO PREVENT SILTATION AND ELSEWHERE AS DIRECTED BY THE ENGINEER. SEEDING AND/OR SODDING SHALL BE INSTALLED ON CREEK BANKS
IMMEDIATELY AFTER CONSTRUCTION TO PREVENT EROSION.
5. MAINTENANCE, CLEANING, AND REMOVAL OF THE VARIOUS SEDIMENT CONTROL MEASURES SHALL BE
INCLUDED IN THE VARIOUS EROSION CONTROL ITEMS.
DENOTES AGGREGATE COVER/PERMANENT PAVEMENT RESTORATION
DENOTES GRAVEL ACCESS APPROACH. APPROACH SHALL BE INSTALLED TO PROVIDE STABLE ACCESS
TO ROADWAYS AND MINIMIZE DUST AND TRACKING OF MATERIALS ONTO PUBLIC STREETS AND
HIGHWAYS. THE APPROACH SHALL BE A MINIMUM OF 12' WIDE, 6" DEEP, AND CONSIST OF 2"-4"
AGGREGATE
DENOTES INLET PROTECTION FABRIC DROP. SHALL BE INSTALLED AT EXISTING AND PROPOSED STORM SEWER INLETS TO PROVIDE SETTLING AND FILTERING OF SILT LADEN WATER PRIOR TO ENTRY INTO THE
DRAINAGE SYSTEM.
4T
8P
26T
ALL UTILITIES AS SHOWN ARE APPROXIMATE LOCATIONS DERIVED
FROM ACTUAL MEASUREMENTS AND AVAILABLE RECORDS. THEY
SHOULD NOT BE INTERPRETED TO BE EXACT LOCATION NOR
SHOULD IT BE ASSUMED THAT THEY ARE THE ONLY UTILITIES IN THE
AREA. FIELD WORK PERFORMED BY: AR ENGINEERING
SOIL EROSION & SEDIMENTATION CONTROL NOTES
GRADING NOTES
LEGEND
SILT FENCE B
SILT FENCE A
1' MIN.
SHEET FLOW
ROLL JOINTS
SPACING 6-10' MAX.
FENCE POSTS DRIVEN
INTO GROUND 1' MIN.
ROLL JOINT
1' M
IN
.6" ANCHOR TRENCH
FABRIC TO BE
WRAPPED AROUND
FENCE POST
GEOTEXTILE FILTER
FABRIC FASTENED ON
UPHILL SIDE, TOWARDS
EARTH DISRUPTION
RIDGE OF COMPACTED
EARTH ON UPHILL SIDE OF
FILTER FABRIC
UNDISTURBED
VEGETATION
6"x6" ANCHOR TRENCH
36" SILT FENCE DETAIL
C3.0 - 130104 NOT TO SCALE
N 1 inch = ft.
20 4030
4T
8P
4T
8P
PROPOSED
STORAGE BLDG
F.F. 1113.50
26T
EXISTING
BUILDING
EXISITNG LIGHPOLE
EXISITNG CONCRETE DRIVE
EXISITNG BRICK SIDEWALK
3" EXPOSED
FOUNDATION
SPENCER ANDREW O'DELL ENGINEER No. 6201309325
LINE OF LOFT ABOVE
LIN
E
OF
L
OF
T
AB
OV
E
WI
RE
S
TA
LL
P
AR
TIT
IO
NS
WI
RE
S
TA
LL
P
AR
TIT
IO
NS
WIRE STALL PARTITIONS
' 3
-1/ 4"
2 X
L
OF
T
JO
IST
S
" O
C
2 X
L
OF
T
JO
IST
S
" O
C
2 X
L
OF
T
JO
IST
S
" O
C
(2) 2 x 10 carriers
(2) 2 x 10 carriers
(1) 11 7/8" lvl ledger to support loft joists
(1) 11 7/8" lvl ledger to support loft joists
10' x 8' sliding door
5' 3-
1/1 6"
3' 4-
9/
6'
-3 /4
30' 0"
10' 9-3/4"3' 5-1/2"8' 5-1/2"8' 5-1/2"8' 9-3/4"
' 0
' 0
' 0
8' 9-3/4" 8' 5-1/2" 8' 5-1/2" 8' 5-1/2" 5' 9-3/4"
' 0
' 0
' 0
12' exterior wall 6 x 6 .060 trtd post
2 x 10 trtd skirt board
(2) 2 x 12 #1 syp carriers
2 x 4 horiz. purlins 24" oc 29 ga painted steel
40' 0"
' 0
20" x 10" ftg 20" x 10" ftg 20" x 10" ftg20" x 10" ftg20" x 10" ftg
20" x 10" ftg 20" x 10" ftg 20" x 10" ftg 20" x 10" ftg
30" x 15" ftg 30" x 15" ftg 30" x 15" ftg 30" x 15" ftg 30" x 15" ftg 30" x 15" ftg
30" x 15" ftg 30" x 15" ftg 30" x 15" ftg 30" x 15" ftg 30" x 15" ftg 30" x 15" ftg
14" x 8" ftg
14" x 8" ftg eave column load (@ 8'-9" oc) roof: 140 sf @ 40 psf LOFT: 44 SF @ 90 psf column weight: 160# ea Wall weight 105 Sf @ 10 PSF footer weight: 6.13 cf @ 150#
5600# 3960#
160# 1050# 920#
11,690# footer area reqd @ 2500 psf = 11,690 / 2500 = 4.68 sf 30" dia. footing = 4.91 sf gable column load (@ 10'-0" oc) column weight: 160# ea LOFT weight 6.67SF @ 90 PSF Wall weight 120 Sf @ 10 PSF footer weight: 0.71 cf @ 150#
160# 601#
1200# 107#
2068# footer area reqd @ 2500 psf = 2,068 / 2,500 = 0.83 sf 14" dia. footing = 1.07 sf
LOFT column load (@ 8'-9" oc) FLOOR: 52.5 sf @ 90 psf column weight: 120# ea
CARRIER WEIGHT: 8.75 LF @ 7 PLF
footer weight: 1.82 cf @ 150#
4,725# 120# 62# 273#
5,180# footer area reqd @ 2500 psf = 5,180 / 2,500 = 2.07 sf 20" dia. footing = 2.18 sf
FOOTING CALCULATIONS
' 0
' 0
8' 9-3/4"
11 7/8" LVL LEDGER
SECURE W/(4) 5/16" X 6"
GRK RSS SCREW EA. POST
3/4" OSB T/G SUBFLOOR
2 X 8 #1 SYP JOIST @ 16" OC
(2) 2 X 10
#1 SYP CARRIERS
0' 7-1/2"
9' 0-3/4"
(2) 2 X 12 CARRIERS
SECURE TRUSS TO
CARRIER W/16", 2X VERTICAL
BLOCK AT EACH TRUSS
& SIMPSON H2.5 TIE-DOWN AT
EACH TRUSS TO OUTSIDE CARRIER
30" X 15" CONC. FOOTING
20" X 10" CONC. FOOTING 20" X 10" CONC. FOOTING
30" X 15" CONC. FOOTING
BOTTOM OF ALL FOOTINGS MINIMUM 42" BELOW FINISH GRADE
SCISSOR TRUSS @ 4'-0" OC
4/12 TOP CHORD, 2/12 BTM CHORD
30+5+5 LOADING
29 GA STEEL ROOFING
ON 2X4 PURLINS 24" OC.
1' 0"
7' 6" 8'
2"10' X 10' SLIDING DOOR
4030 SLIDER
4030 SLIDER
4030 SLIDER
4030 SLIDER
revisions
JO
NE
SV
ILL
E
SC
HO
OL
S
FF
A
BA
RN
page
PL
AN
A
ND
D
ET
AI
LS
01 05/15/24
FRONT ELEVATION
REAR ELEVATION
RIGHT ELEVATION
LEFT ELEVATION
SECTION VIEW
FLOOR PLAN
12'
1' 0"
1' 0"
1' 0"
12'
12'
30' 0"
30' 0"
40' 0"
40' 0"
2X4 UPLIFT BLOCKS
EACH EXT POST
2' 2-1/4"
TO
P
OF
C
AR
RI
ER
TO
P
OF
C
AR
RI
ER
DESIGN LOADS
ROOF
30# GROUND SNOW LOAD
5# TOP CHORD DEAD LOAD
5# BOTTOM CHORD DEAD LOAD
STORAGE LOFT
40# LIVE LOAD
10# DEAD LOAD
LOFT SPACE FOR LIGHT
STORAGE ONLY. NOT FOR
HABITATION OR DAILY USE
TRUSS MANUFACTURER TO PROVIDE
STAMPED TRUSS DRAWINGS PRIOR
TO ORDER, SHOWING ALL DIMENSIONS,
DESIGN LOADS, AND BRACING
REQUIREMENTS (TEMPORARY AND
PERMANENT)
17'
-7 /16
17'
-7 /16
1' 0"
1' 0"
1' 0"
12'
1' 0" 1' 0"
MUST MEET
REQUIREMENTS
FOR HANDICAP
ACCESSIBILITY
4/
X 3/
SL
ID
ER
4/
X 3/
SL
ID
ER
4/0 X 3/0 SLIDER
4/0 X 3/0 SLIDER
02 03/05/24
3' 11-1/2"
INTERIOR WALL
1/2" TRTD PLY TO 48" A.F.F.
1/2" OSB TO BTM OF LOFT JOIST
R-21 FIBERGLASS BATT INSUL.
CEILING
7/16" OSB
2X4 PURLINS 24" OC
R-30 FIBERGLASS FACED INSUL.
03 03/07/25
ELECTRICAL SYMBOL LIST
SYMBOL DESCRIPTION
LIGHTING FIXTURE - ARCHITECTURAL TROFFER
EMERGENCY LIGHTING FIXTURE
LIGHTING FIXTURE - PENDANT
WALL MOUNTED LIGHTING FIXTURE
LIGHTING FIXTURE
LIGHTING TRACK OR ROPE LIGHT
TRACK LIGHTING FIXTURE
EMERGENCY LIGHTING UNIT
POLE MOUNTED LIGHTING FIXTURE
POLE MOUNTED LIGHTING FIXTURE - POST TOP
BOLLARD LIGHTING FIXTURE
EXIT LIGHTING FIXTURE WITH DIRECTIONAL
ARROWS (SHADED AREA INDICATES FACE)
EXIT LIGHTING FIXTURE WITH DIRECTIONAL
ARROWS (SHADED AREA INDICATES FACE)
EXIT LIGHTING FIXTURE - WALL MOUNTED
SINGLE POLE TOGGLE SWITCH
TWO POLE TOGGLE SWITCH
3 WAY TOGGLE SWITCH
4 WAY TOGGLE SWITCH
KEY OPERATED SWITCH
DIMMER SWITCH
PILOT SWITCH
OCCUPANCY SENSOR DEVICE - CEILING
SIMPLEX / DUPLEX RECEPTACLE
SIMPLEX / DUPLEX RECEPTACLE CONTROLLED BY
AUTOMATIC CONTROL DEVICE / SYSTEM
QUAD RECEPTACLE
ABOVE COUNTER DUPLEX RECEPTACLE (SIMILAR FOR
TAMPER RESISTANT, QUADS, EMERGENCY AND GFI
RECEPTACLES)
DUPLEX RECEPTACLE-GROUND FAULT CIRCUIT
INTERRUPTER
DUPLEX EMERGENCY RECEPTACLE
CEILING MOUNTED
DUPLEX RECEPTACLE
SPECIAL RECEPTACLE - REFER TO ELECTRICAL
STANDARD SCHEDULES
MULTI-OUTLET RACEWAY - LEGRAND AL3300 OR EQUAL
POKE-THROUGH ASSEMBLY - LEGRAND
EVOLUTION SERIES OR EQUAL
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
CONTROL PANEL
VARIABLE FREQUENCY DRIVE
MOTOR
MANUAL CONTROLLER
MAGNETIC CONTROLLER
COMBINATION MAGNETIC CONTROLLER
NON-FUSIBLE DISCONNECT SWITCH
FUSIBLE DISCONNECT SWITCH
ENCLOSED CIRCUIT BREAKER
PUSH BUTTON STATION
AUTOMATIC DOOR CONTROLLER
AUTOMATIC DOOR PUSH PAD OPERATOR
GROUND ROD
GROUND CONNECTION
CONDUIT SLEEVE WITH BUSHINGS
LENGTH AS REQUIRED
"X" INDICATES CONDUIT SIZE
CONDUIT STUB - UP/DOWN
EMPTY BOX FOR FUTURE
TELECOMMUNICATION OUTLET
EMPTY BOX FOR FUTURE TELECOMMUNICATION
OUTLET MOUNTED 4" ABOVE COUNTERTOP
EMPTY BOX FOR FUTURE CEILING MOUNTED
TELECOMMUNICATION OUTLET
TELECOMMUNICATION OUTLET
"X" INDICATES TYPE
SPEAKER
SPEAKER - WALL MOUNTED
MICROPHONE
VOLUME CONTROL
SIGNALING BELL
SINGLE FACE CLOCK - CEILING MOUNTED
SINGLE FACE CLOCK - WALL MOUNTED
DOUBLE FACE CLOCK - CEILING MOUNTED
DOUBLE FACE CLOCK - WALL MOUNTED
P
PT
FB
CP
VFD
CB
DP
PP
X
X
S
S
MIC
VC
B
USB RECEPTACLE
GENERATOR TRANSFER DEVICEGTD
REMOTE GENERATOR ANNUNCIATOR PANELRGP
AUTOMATIC TRANSFER SWITCHATS
SWITCHBOARD
BRANCH CIRCUIT PANEL BOARD - 208/120V
TRANSFORMER
DISTRIBUTION PANEL - 208/120V
SECURITY CAMERA
MOTION DETECTOR
SECURITY KEY SWITCH
DOOR CONTACT
KEY PAD
CARD READER
CIRCUIT BREAKER
DRAWOUT CIRCUIT BREAKER
MANUALLY/ OPERATED
SWITCH
AUTOMATIC OR MANUAL TRANSFER
SWITCH
FUSE
TRANSFORMER
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
LIGHTNING ARRESTOR
PANELBOARD
"X" INDICATES PANELBOARD NAME
GROUND
SECURITY KEY INTERLOCK
ENGINE GENERATOR
UTILITY METER
AMMETER
VOLTMETER
AMMETER SWITCH
VOLTMETER SWITCH
SURGE PROTECTIVE DEVICE
TIME DELAY RELAY
THERMAL OVERLOAD RELAY
NORMALLY OPEN CONTACTS
NORMALLY CLOSED CONTACTS
N.O. PUSH BUTTON SINGLE CIRCUIT
N.C. PUSH BUTTON SINGLE CIRCUIT
GROUND BUS
MD
K
DC
KP
CR
X
K
G
M
A
V
AS
VS
SPD
TDR
GB
DURESS PUSH BUTTON STATION
DELAYED EGRESS
DB
DE
REQUEST TO EXIT STATIONREX
MANUAL FIRE ALARM PULL STATION
SMOKE DETECTOR
DUCT SMOKE DETECTOR
REMOTE TEST STATION (FOR DUCT DETECTOR)
THERMAL DETECTOR
FIRE ALARM BELL
FIRE ALARM AUDIBLE NOTIFICATION - WALL MOUNT
SPEAKER/STROBE
FIREFIGHTERS PHONE JACK
TAMPER SWITCH
FLOW SWITCH
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
F
SD
DD
RT
TD
F
F
F
TS
FS
FACP
FAA
NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANELNAC
R E
F E
R T
O E
L E
C T
R
IC
A L
S T
A N
D A
R D
S C
H E
D U
L E
S
DIMMER OCCUPANCY SENSOR SWITCH
LOW VOLTAGE DIMMER SWITCH
POWER POLE - WIREMOLD TYPE
F FIRE ALARM AUDIBLE NOTIFICATION - CEILING MOUNT
SPEAKER/STROBE
CARBON MONOXIDE DETECTORCO
LIGHTING CONTROL DEVICE - REFER TO LIGHTING
CONTROL SCHEDULE
LC
K
D
OS
LV
GFI
USB
CLG
FLOOR BOX ASSEMBLY - LEGRAND
EVOLUTION SERIES OR EQUAL
TOUCH SCREEN SWITCHTS
OS
OCCUPANCY SENSOR DEVICE - WALLOS
PC PHOTOCELL DEVICE - REFER TO ZONES SHOWN ON
PLANS
EQ
EQUIPMENT CONNECTION - REFER TO ELECTRICAL
FEEDER AND PANEL SCHEDULE FOR BREAKER AND
CONDUCTOR SIZE/QUANTITY
J JUNCTION BOX
EMERGENCY POWER OFF BUTTON
V FIRE ALARM VISUAL NOTIFICATION - CEILING MOUNT
STROBE
FIRE ALARM VISUAL NOTIFICATION - WALL MOUNT
SPEAKER/STROBE
F
BRANCH CIRCUIT PANEL BOARD - 480/277V
DISTRIBUTION PANEL - 480/277V
EXIT FIXTURE-BACK
MOUNTED BOTTOM OF EXIT
SIGN TO BE 4" ABOVE TOP OF
DOOR FRAME
EXIT
EXIT
1' -6
EXIT
A/C SUPPLY
DIFFUSER
90" MAX (IBC)
4' -0
5"
8' -6
EXIT-CEILING MOUNTED
EXIT-FIXTURE END
MOUNTED
NFPA 72 AUDIBLE APPLIANCE 6" MIN
BELOW FINISHED CEILING
EMERGENCY
BATTERY
FIXTURE
ABOVE FINISHED FLOOR
AUDIBLE 80" MIN (IBC)
CEILING HEIGHTS LESS THEN 86" VISUAL
LENS MOUNTING HEIGHT WILL BE WITHIN 6"
OF THE CEILING
FINISHED CEILING
AUDIO/VISUAL &
VISUAL ONLY
DEVICES
SYNCHRONIZE MORE THAN
TWO APPLIANCES IN ANY
FIELD OF VIEW
MANUAL PULL STATION
AUDIBLE
ONLY
'-8
DOOR WIDTH LESS THEN 3'-0"
(MODIFY FOR DIFFERENT
DOOR WIDTHS)
FINISHED FLOOR
O R
A P
P R
O V
E D
F R
O M
A H
J
M
IN
A B
O V
E F
IN
IS
H E
D F
L O
O R
CEILING MOUNTED SMOKE/HEAT
DETECTOR
3'-0" MIN 4"
NOTES:
1. INSTALL ELECTRICAL DEVICES AT MOUNTING HEIGHTS NOTED ABOVE UNLESS OTHERWISE NOTED ON PLANS. COORDINATE WITH ALL OTHER DISCIPLINES PRIOR TO INSTALL.
2. VISUAL MOUNTING APPLIANCE MOUNTING HEIGHT IN SLEEPING ROOMS:
A. MINIMUM DISTANCE IN SLEEPING ROOMS IS 24" FROM CEILING TO THE TOP OF LENS FOR 110cd STROBES WITHIN 16' OF PILLOW
B. 177cd STROBES, USED IN SLEEPING ROOMS, CAN BE WITHIN THE 24" MINIMUM DISTANCE FROM THE CEILING, THE HIGHER INTENSITY IS TO COMPENSATE FOR A POSSIBLE SMOKE LAYER
7' -6
(M
IN
(M
A X
1' -0
"4"
M A
X
DO NOT INSTALL HEAT DETECTOR IN
SHADED AREA
WALL MOUNTED
SMOKE/HEAT
DETECTOR
MAGNETIC
DOOR
HOLDER
FINISHED WALL
SWITCHBANK
AUTOMATIC DOOR OPERATOR PUSH
BUTTON
RECEPTACLE, DATA JACK OR
TELEPHONE JACK
3'-0"
5' MAX TO EXIT DOOR
4' -0
4"
7' -6
ELECTRICAL DEVICE TYPICAL MOUNTING HEIGHTS
6' -6
BRANCH CIRCUIT PANELBOARDS
DISCONNECT SWITCH
5' -0
AREA
TYPICAL ELECTRICAL RECEPTACLES
DESCRIPTION MANUFACTURER
GENERAL 20A DUPLEX, EXTRA HEAVY DUTY, TAMPER-RESISTANT, WHITE
OUTDOOR 20A DUPLEX, EXTRA HEAVY DUTY, TAMPER-RESISTANT, WEATHER-RESISTANT, GFCI, WHITE
NOTES:
1. COLORS AS LISTED IN TABLE ABOVE, UNLESS NOTED OTHERWISE
2. MANUFACTURER EQUALS BY LEVITON, PASS & SEYMOUR
HUBBELL #HBL5362STWTR
HUBBELL #GFSG5362W
SCHEDULE 40 PVC CONDUIT
PVC TO RIGID ADAPTOR
PROVIDE RGC WITH SWEEP TO
TRANSITION FROM
UNDERFLOOR PVC CONDUIT.
CONCRETE SLAB
COMPACTED BACKFILL
3" MIN. BELOW SLAB
OR AS REQUIRED
FOR SWEEPS
REFER TO SPECS FOR CONDUIT REQUIREMENTS
EXOTHERMIC WELD
CONNECTION (TYP.)
POLYESTER/FIBERGLASS
INSULATOR. 45mm (1-3/4") DIA. x
50mm (2") LONG. RED IN COLOR
SECTION "A-A"
COPPER GROUND BUS
10mm (3/8") MOUNTING BOLT
M
IN
m m
50mm (2") 6mm (1/4")
FRONT ELEVATION
INSULATED COPPER
GROUNDING CONDUCTOR
BARE COPPER GROUNDING
CONDUCTOR
6mm x 50mm (1/4" x 2") LONG
COPPER GROUND BUS MOUNTED
TO WALL WITH INSULATORS
BONDING CONDUCTOR SIZED
TO THE LARGEST GROUND
CONDUCTOR IN GROUP (TYP.)GROUNDING BUSHING (TYP.)
INSULATED GROUNDING IN
CONDUIT. SEE BUILDING
GROUNDING DETAIL FOR
ADDITIONAL INFORMATION.
A
A
NOTES:
1. REFER TO BUILDING GROUNDING
ELECTRODE SYSTEM DETAIL FOR EXACT
CONFIGURATION.
4 AWG OR LARGER BAR COPPER
CONDUCTOR OR STEE REINFORCING
BAR OR ROD NOT LESS THAN 1/2" DIAMETER
AND AT LEAST 20 FT LONG
2" MIN
STEEL TIE WIRE
FOUNDATION IN DIRECT
CONTACT WITH EARTH
LISTED CONNECTOR
NONMETALLIC PROTECTIVE
SLEEVE
GROUNDING ELECTRODE
CONDUCTOR
18''
COPPER GROUND
BUS 24''Lx2''Wx 1/4'' THICK
FLOOR
ANCHOR BUS
TO WALL AS
REQUIRED
ISOLATED
ANCHORS
1''
THE FOLLOWING DIMENSION
EQUALS ONE INCH WHEN PRINTED
TO SCALE.
1"
Project No:
Drawing Title:
© 2025 IGNYTE DESIGN
SCALE
STAMP
NOT FOR
CONSTRUCTION
Issued For: Date
E000
ELECTRICAL SYMBOLS
AND SPECIFICATION
JONESVILLE
COMMUNITY
SCHOOLS
24.150
MARCH 10, 2025CONSTRUCTION
NOTE: SOME SYMBOLS AND ABBREVIATIONS SHOWN
MAY NOT APPLY TO THIS PROJECT.
ELECTRICAL SPECIFICATION
1. CONTRACTOR TO PROCURE ALL REQUIRED BUILDING PERMITS AND INSPECTIONS TO COMPLETE PROJECT.
2. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE MICHIGAN ELECTRICAL CODE.
3. PROVIDE NEW ELECTRICAL SERVICES FROM CONSUMERS ENERGY AS INDICATED. COORDINATE SCOPE OF WORK AND PROVIDE ALL WORK TO PROVIDE A FULLY FUNCTIONAL ELECTRICAL SERVICE.
4. REMOVE ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, ETC ASSOCIATED WITH DEMOLISHED EQUIPMENT.
5. REMOVE ALL ABANDONDED ELECTRICAL CONDUIT AND WIRE BACK TO SOURCE.
6. PROVIDE SHOP DRAWINGS FOR THE FOLLOWING:
A. CONDUIT.
B. CONDUCTORS.
C. WIRING DEVICES INCLUDING COVERPLATES.
D. DISCONNECT SWITCHES, ENCLOSED CIRCUIT BREAKERS AND FUSED SWITCHES.
E. PANELBOARDS. AND SWITCHBOARDS
F. SURGE PROTECTION DEVICES
G. INTERIOR LIGHT FIXTURES.
H. EXTERIOR LIGHT FIXTURES INCLUDING SITE POLES.
I. LIGHTING CONTROL SYSTEM AND DEVICES.
7. PATCH, REPAIR, AND PAINT ANY OPENINGS THROUGH ROOF, CEILINGS, WALLS, OR FLOORS TO MATCH EXISTING CONDITION.
8. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL OF ALL DEMOLISHED EQUIPMENT.
9. PROVIDE LAMACOID LABELS FOR:
A. PANELBOARDS AND SWITCHBOARDS.
B. DISCONNECT SWITCHES.
10. MINIMUM CONDUIT SIZE SHALL BE 1/2" TRADE SIZE.
11. USE THE CONDUIT TYPE SUITABLE FOR THE ENVIRONMENT IN WHICH IS IS LOCATED:
A. INDOORS: EMT WITH SET SCREW FITTINGS. MC CABLE IS ACCEPTABLE FOR BRANCH CIRCUITS WHERE CONCEALED.
B. OUTDOORS: RIGID GALVANIZED STEEL.
C. UNDERGROUND: RIGID NON METALLIC SCHEDULE 80 PVC.
D. CONDUIT EXITING FROM UNDERGROUND SHALL TRANSITION TO EMT/RGS PRIOR TO BEING EXPOSED.
12. PROVIDE CONDUIT SLEEVES FOR LOW VOLTAGE DATA CABLING.
13. ALL CABLING SHALL BE IN CONDUIT UNLESS ABOVE AN ACCESSIBLE CEILING WHERE "J" HOOKS ARE ACCEPTABLE.
14. USE CONDUIT SWEEPS FOR ALL DATA CABLING CONDUITS.
15. DATA BOXES SHALL BE DOUBLE GANG, 3 1/2" DEEP WITH SINGLE GANG MUD RING WITH 1" CONDUIT TO ABOVE ACCESSIBLE CEILING.
16. ALL BOXES SHALL BE RECESSED IN WALLS AND CONDUIT CONCEALED WHERE POSSIBLE.
17. MINIMUM CONDUCTOR SIZE FOR POWER SHALL BE #12 AWG. ANY BRANCH CIRCUITS OVER 100' IN LENGTH SHALL BE #10 AWG MINIMUM FOR VOLTAGE DROP.
18. PROVIDE THHN-2 COPPER INDOORS AND THWN-2 COPPER OUTDOORS, UNLESS NOTED OTHERWISE OR DICTATED OTHERWISE BY THE NEC.
19. PROVIDE GROUNDING ELECTRODE SYSTEM AND EQUIPMENT GROUNDING PER THE NATIONAL ELECTRIC CODE.
20. PANELBOARDS SHALL BE FULLY RATED, SERIES RATED PANELS ARE NOT ACCEPTABLE. HAVE HINGED SWING DOOR-IN-DOOR. LOAD CENTERS ARE NOT ACCEPTABLE. SQUARE D NQOD OR EQUAL FOR
208/120V BRANCH PANELBOARDS. SQUARE D NF OR EQUAL FOR 480/277V PANELBOARDS. PROVIDE TYPED PANELBOARD CIRCUIT LABEL CARDS. UPDATE ALL EXISTING LABEL CARDS AS REQUIRED.
21. SURGE PROTECTION DEVICES SHALL BE MOUNTED AS CLOSE TO MAIN BUS AS POSSIBLE TO LIMIT FEEDER LENGTH.
22. RECEPTACLES SHALL BE TAMPER-RESISTANT EXTRA HEAVY DUTY GRADE, 20AMP MINIMUM. WHITE IN COLOR UNLESS NOTED OTHERWISE.
23. ALL DEVICE COVERS SHALL MATCH DEVICE COLOR UNLESS STAINLESS STEEL COVERS ARE SPECIFIED.
24. WEATHERPROOF RECEPTACLE COVERS SHALL BE METAL, WHILE-IN-USE TYPE.
25. SWITCHES SHALL BE HEAVY DUTY GRADE, 20 AMP, QUIET TYPE, WHITE UNLESS NOTED OTHERWISE.
26. LIGHTING CONTROL DEVICES SHALL BE MANUFACTURED BY N-LIGHT, UNLESS NOTED OTHERWISE.
27. ALL LIGHTING CONTROLS SHALL MEET ASHRAE 90.1 - 2013 WITH MICHIGAN AMENDMENTS.
28. IT IS UNDERSTOOD AND AGREED BY THE INSTALLER THAT WORK HEREIN DESCRIBED SHALL BE COMPLETE IN EVERY DETAIL, EVEN THOUGH EVERY ITEM INVOLVED IS NOT PARTICULARLY MENTIONED.
INSTALLER SHALL BE HELD TO PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR THE WORK INTENDED AND DESCRIBED FOR A COMPLETE AND OPERATIONAL SYSTEM. SUCH MATERIALS SHALL
INCLUDE, BUT ARE NOT LIMITED TO, CONDUIT, FITTINGS, COVERPLATES, WIRING, BREAKERS, CONTROL DEVICES, LIGHTING ACCESSORIES, ETC. THIS ALSO INCLUDES EQUIPMENT REQUIRED BY STATE AND
LOCAL CODES.
NOT TO SCALEE000
3 UNDERFLOOR CONDUITS IN SLAB ON GRADE INSTALLATION
NOT TO SCALEE000
4 BUILDING ELECTRICAL SYSTEM GROUND BUS
NOT TO SCALEE000
6 BUILDING GROUNDING ELECTRODE SYSTEM
NOT TO SCALEE000
7 GROUND BUS MOUNTING DETAIL
CB
CB
CB
CB
UTILITY FEED
M
PANEL
STORAGE
PANEL
P1
3 #3, 2" C.
3 #3, 2" C.
NEW BUILDING
GROUND BAR
NEW GROUND
MAT
#3/0 GND
(TYPICAL FOR ALL
GROUND WIRE)
SPD
SERVICE
120/240-V0LT, 1-PHASE, 3-WIRE, 100-AMP
EXISTING 12-MONTH MAXIMUIM DEMAND = 6A
CONNECTED LOAD 6 x 1.25 + 28 = 36A
STORAGE
P1
NEW UNDERGROUND
FEEDER A MINIMUM OF
30" BELOW GRADE
THE FOLLOWING DIMENSION
EQUALS ONE INCH WHEN PRINTED
TO SCALE.
1"
Project No:
Drawing Title:
© 2025 IGNYTE DESIGN
SCALE
STAMP
Issued For: Date
E010
ELECTRICAL SITE PLAN
JONESVILLE
COMMUNITY
SCHOOLS
24.150
MARCH 10, 2025CONSTRUCTION
EXISTING 12-MONTH MAXIMUM DEMAND = 6A
Notes:
Demand Current: 27 A
POWER 5250 VA 100.00% 5250 VA Demand Load: 7 kVA
RECEPTACLE 720 VA 100.00% 720 VA Connected Current: 27 A
LIGHTING - INTERIOR 491 VA 125.00% 614 VA Connected Load: 6 kVA
Other 0 VA 0.00% 0 VA Panel Totals
Load Classification Connected Factor Demand
Connected Current: 29 A 25 A
Connected Load: 3 kVA 3 kVA
23 SPACE -- 1 -- -- 1 -- SPACE 24
21 SPACE -- 1 -- -- 1 -- SPACE 22
19 SPACE -- 1 -- -- 1 -- SPACE 20
17 SPACE -- 1 -- -- 1 -- SPACE 18
15 SPACE -- 1 -- -- 1 -- SPACE 16
13 SPACE -- 1 -- -- 1 -- SPACE 14
11 SPACE -- 1 -- 0 1 20 RECEPTS STORAGE BARN 12
9 SPACE -- 1 -- 0 10
7 3040 0
2 30 SPARE
PANEL P1 60 2
3421 0 1 20 RECEPTS STORAGE BARN 6
3 0 0 1 20 RECEPTS STORAGE BARN 4
MAIN BREAKER 100 2
0 0 1 20 LIGHTS STORAGE BARN 2
Ckt Description Trip (A) Poles FN/Note Phase A
Load (VA) Phase B
Load (VA) FN/Note Poles Trip (A) Description Ckt
Enclosure: NEMA 1
Mounting: SURFACE Features & Modifications: -
Supply: Feed-Thru Lugs: No SCCR: 10,000
Location: Neutral: 100% Mains FN/Note: MCB
Bus Rating: 100 A Mains Rating: 100 A
Panelboard: STORAGE Voltage: 240 V, 1Ø, 3W Mains Type: MCB
PROVIDE NEW BREAKER IN
EXISTING EATON PANEL
NOT TO SCALEE010
1 ELECTRICAL ONE LINE DIAGRAM
1" = 20'-0"E010
2 SITE PLAN
T
LINE OF LOFT ABOVE
L
IN
E O
F L
O F
T A
B O
V E
FRONT ELEVATION
REAR ELEVATION
LEFT ELEVATION
SECTION VIEW
RIGHT ELEVATION
o s
EQ
EQ EQ
M
P1
BUILDING
GROUND BAR
P1-1
WP
P1-4
P1-4
P1-4
GFI
10' GROUND ROD
TYPICAL
AE
A
BE
P1-2
A A
A A A AE
A
A A
AE
WALL MOUNTED, 120-VOLT VACANCY
SENSOR SHALL TURN LIGHTS OFF
AFTER 30 MINUTES OF NO MOTION.
TYPE A FIXTURE TYPE A FIXTURE
TYPE A FIXTURE
TYPE BE
FIXTURE
WEATHER
PROOF OUTLET
P1-2
UH-1
P1-3,5
#10 WIRE
EF-01
CONNECT EF-1 AND LOUVER TO
OCCUPANCY SENSOR. LOUVER AND
EF SHALL BE INTERLOCKED.
EUH-01
30"x24"
LOUVER
30"x24"
LV-1 250
EF-01
THE FOLLOWING DIMENSION
EQUALS ONE INCH WHEN PRINTED
TO SCALE.
1"
Project No:
Drawing Title:
© 2025 IGNYTE DESIGN
SCALE
STAMP
Issued For: Date
E110
FIRST FLOOR ELECTRICAL
AND MECHANICAL PLAN
JONESVILLE
COMMUNITY
SCHOOLS
24.150
MARCH 10, 2025CONSTRUCTION
1/4" = 1'-0"E110
1 FIRST FLOOR ELECTRICAL AND MECHANICAL PLAN
FULLY RATED AND SERVICE RATED
Notes:
Demand Current: 27 A
POWER 5250 VA 100.00% 5250 VA Demand Load: 7 kVA
RECEPTACLE 720 VA 100.00% 720 VA Connected Current: 27 A
LIGHTING - INTERIOR 491 VA 125.00% 614 VA Connected Load: 6 kVA
Other 0 VA 0.00% 0 VA Panel Totals
Load Classification Connected Factor Demand
Connected Current: 29 A 25 A
Connected Load: 3 kVA 3 kVA
17 0 0 1 20 SPARE 18
SPD 30 2
0 0 1 20 SPARE 16
13 SPARE 20 1 0 0 1 20 SPARE 14
11 SPARE 20 1 0 0 1 20 SPARE 12
9 SPARE 20 1 0 0 1 20 SPARE 10
7 SPARE 20 1 0 0 1 20 SPARE 8
5 2500 250 1 20 EF-1 STORAGE BARN 6
UNIT HEATER STORAGE BARN 30 2
2500 540 1 20 RECEPTACLES STORAGE BARN 4
1 RECEPTACLE EXTERIOR STORAGE... 20 1 180 491 1 20 INTERIOR LIGHTING STORAGE BARN 2
Ckt Description Trip (A) Poles FN/Note Phase A
Load (VA) Phase B
Load (VA) FN/Note Poles Trip (A) Description Ckt
Enclosure: NEMA 1
Mounting: SURFACE Features & Modifications: -
Supply: STORAGE Feed-Thru Lugs: No SCCR: 10,000
Location: Neutral: 100% Mains FN/Note: MCB
Bus Rating: 100 A Mains Rating: 60 A
Panelboard: P1 Voltage: 240 V, 1Ø, 3W Mains Type: MCB
LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION MOUNTING DRIVER LOAD MANUFACTURER NOTES
A SURFACE WRAP SURFACE 0-10V 39 VA LITHONIA: #BLWP4-48L-ADP-EZ1-LP840-NESPDT7
AE SURFACE WRAP WITH BATTERY SURFACE 0-10V 39 VA LITHONIA: #BLWP4-48L-ADP-EZ1-LP840NESPDT7--E10WLCP 1
BE WALL PACK WITH BATTERY SURFACE NA 23 VA LITHONIA: #WDGE2-P3-40K-80CRI-VW-MVOLT-PE-E10WH-DBLXD 1
LIGHT FIXTURE NOTES:
1. PROVIDE FIXTURE WITH SELF CONTAINED BATTERY PACK. BATTERY SHALL COME ON WHEN NORMAL POWER FAILS AND OPPERATE A MINUMUM OF 90 MINUTES.
NOTES:
1. PROVIDE WITH RECESSED MOUNT ENCLOSURE MODEL CDFRE
2. PROVIDE WITH RECESED MOUNT POWER DISCONNECT
3. PROVIDE WITH ONE 7-DAY PROGRAMMABLE THERMOSTAT PER BULDING.
4. SPACE IS VENTILATED BY NATURAL VENTILATION (OPERABLAE WINDOWS) EXCEEDING 4% OF FLOOR AREA PER MMC 402.1 AND 402.2.
ELECTRIC UNIT HEATER SCHEDULE
IDENTITY MANUFACTURER MODEL PRODUCT TYPE
BOTTOM
ELEVATION
FAN
CAPACITY
FAN OUTLET
VELOCTIY
FAN MOTOR
FAN SPEC
HEATING AIRFLOW DESIGN HEATING
TEMP. RISE
ELECTRIC HEAT ELECTRICAL
SPECIFICATION NOTESQTY SIZE RPM OUTPUT AIRFLOW EAT LAT RATING LOAD ELEMENT(S) VOLTAGE PHASE
EUH-01 Berko HUH-524SA Unit 9'-0" 270 CFM 0 FPM 1 0.01 hp 1350 Motor: PSC/ECM 17,496 Btu/h 270 CFM 60 °F 120 °F 60 °F 5.0 kW 20.8 A 1 240 V 1
EXHAUST FAN SCHEDULE
INSTALLED
LOCATION
MANUFACTURER MODEL
DESIGN
AIRFLOW RATE
FAN DESIGN DRIVE
TYPE
MOTOR ELECTRICAL
SONES
REMARKS
CAPACITY ESP BHP RPM HP RPM FLA VOLTAGE PHASE
EF-01 SIDEWALL GREENHECK SE1-10-428-PX
-QD
250 CFM 250 CFM 0.13 in-wg 0.02 hp 1550 DIRECT 0.1 hp 1550 1.3 A 120 V 1 0
LOUVER SCHEDULE
MARK MANUFACTURER MODEL QTY DESCRIPTION TYPE
DIMENSIONS FREE AREA DESIGN
AIRFLOW RATE MATERIAL FINISH NOTESWIDTH HEIGHT DEPTH AREA VELOCITY
LV-1 GREENHECK ESJ-602 1 OUTDOOR AIR LOUVER STATIONARY LOUVER 30" 24" 6" 2 SF 590 FPM 250 CFM ALLUMINUM MILL
| Sheets |
| A101 - ARCHITECTURAL |
| E000 - ELECTRICAL SYMBOLS AND SPECIFICATION |
| E010 - ELECTRICAL SITE PLAN |
| E110 - FIRST FLOOR ELECTRICAL AND MECHANICAL PLAN |
| G000 - COVER SHEET |
File details come from the government source that posted it. Updated .