25-29532-01A - Gaston College RCB - BID SET Drawings.pdf
PDF 13 MB Posted
- Attached to
- Robinson Classroom Building Boiler Replacement
- Solicitation number
- 98-25-29532-01A
- Issued by
- Gaston County, North Carolina
About this file
This is a bid set of architectural and engineering drawings for Gaston College's Robinson Classroom Building Heating and Hot Water Upgrades project located at 250 Library Lane, Dallas, North Carolina. The project involves upgrades to the heating and hot water systems serving the 17,571-square-foot building, classified as a Level 1 Alteration affecting 2,562 square feet (14.6% of the building). The scope includes demolition of existing combustion air intake and flue vent for the boiler, replacement of the existing gas-fired boiler system with two new condensing boilers (Lochinvar FCB1500 models rated at 1,500 MBH input each), installation of new hydronic piping and controls, addition of UV lighting upstream of cooling coils in air handling units with MERV-13 filter upgrades, and associated mechanical and electrical work. The design team consists of Morris Berg Architects and AME Consulting Engineers, with the final review bid set dated November 7, 2025. The project includes comprehensive mechanical plans showing HVAC demolition and new construction, piping demolition and new construction, controls and schedules, details, and piping diagrams, along with electrical demolition and power plans.
Key technical specifications include two new primary heating hot water pumps (Armstrong Series Design Envelope model rated at 53 GPM), an air separator (Bell & Gossett CRSN-2F rated at 53 GPM), and an expansion tank (Bell & Gossett B130 with 13.4-gallon volume). Three UV lighting systems (UV Resources RLM XTREME models) are specified for the air handling units. The project requires seismic restraint design per NSCE 2018/ASCE 7-10 standards for mechanical components and equipment. Electrical work includes connection to existing panels (MSB main switchboard at 480/277V and R1A panel at 208/120V), with total added load of 6.42 kVA at the switchboard and 4.62 kVA at the panel. The mechanical contractor must verify existing conditions prior to bidding, coordinate demolition with all trades, maintain continuity of existing systems, and include all labor for after-hours, weekend, and shutdown work in the bid price without additional charges for difficulties encountered.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Addendum 1.pdf | ||
| 25-29532-01A - Gaston College RCB - BID SET Project Manual (Specifications).pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C O N S U L T I N G E N G I N E E R S
413 DALTON AVENUE, SUITE A
CHARLOTTE, NC 28206 • 704-295-4263
NC LICENSE NO.: F-1533
AME PROJECT NO.:
Y S T A N D A R D
A C A D
B L O C K S T
IT
L E
B L O C K
IN
F O N e w
T B x .d w g
:2 :1
A M
B ri a n
E lb e rt s o n
Drawing No.
Drawing Title
Issues / Revisions
Checked by
Seals
Drawn by
Scale
Job No.
Drawing Info
AS SHOWN
24064
Project
24064
Issue Date
KEYPLAN
MECH &
ELEC
ROOM
FINAL REVIEW
SET
GENERAL
Morris Berg Architects 1018 Jay St., Suite 130 Charlotte, NC 28208 P (704) 552-5800
MECHANICAL ENGINEER
DESIGN TEAM
GENERAL MECHANICAL ELECTRICAL
ELECTRICAL ENGINEER
AME Consulting Engineers 413 Dalton Avenue, Suite A Charlotte, NC 28206 P (704) 295-4263
ARCHITECT
Morris Berg Architects 1018 Jay St., Suite 130 Charlotte, NC 28208 P (704) 552-5800
ARCHITECTURAL
INDEX OF DRAWINGS
AME Consulting Engineers 413 Dalton Avenue, Suite A Charlotte, NC 28206 P (704) 295-4263
SCO #25-29532-01A
NOT FOR
CONSTRUCTION
COVER SHEET
GASTON COLLEGE
ROBINSON CLASSROOM
BUILDING HEATING HOT
WATER UPGRADES
250 LIBRARY LANE, DALLAS, NC 28034
CS100
LA
ZH
11/07/2025
FINAL REVIEW SET
GASTON COLLEGE
GASTON COLLEGE ROBINSON CLASSROOM
BUILDING HEATING HOT WATER UPGRADES
250 LIBRARY LANE, DALLAS, NC 28034
AS100 ARCHITECTURAL SITE PLAN
A201 CLASSIFICATION OF WORK
CS100 COVER SHEET
LS100 APPENDIX B
LS200 LIFE SAFETY PLANS
VICINITY MAP
MECHANICAL – GENERAL NOTES AND LEGENDS
MECHANICAL HVAC – DEMOLITION PLAN
MECHANICAL PIPING – DEMOLITION PLAN
MECHANICAL HVAC – NEW CONSTRUCTION PLAN
MECHANICAL PIPING – NEW CONSTRUCTION PLAN
MECHANICAL – CONTROLS & SCHEDULES
MECHANICAL – DETAILS
MECHANICAL – PIPING DIAGRAMS
M0.1
M1.1
M1.2
M2.1
M3.1
M6.1
M7.1
M7.2
ELECTRICAL – GENERAL NOTES, LEGENDS, AND DETAILS
ELECTRICAL – DEMOLITION PLAN
ELECTRICAL – POWER PLAN
ELECTRICAL – RISER AND SCHEDULES
E0.1
E1.1
E2.1
E5.1
Rev. No. Date Description
BID
BID SET
C O N S U L T I N G E N G I N E E R S
413 DALTON AVENUE, SUITE A
CHARLOTTE, NC 28206 • 704-295-4263
NC LICENSE NO.: F-1533
AME PROJECT NO.:
Y S T A N D A R D
A C A D
B L O C K S T
IT
L E
B L O C K
IN
F O N e w
T B x .d w g
:2 :1
A M
B ri a n
E lb e rt s o n
Drawing No.
Drawing Title
Issues / Revisions
Checked by
Seals
Drawn by
Scale
Job No.
Drawing Info
AS SHOWN
24064
Project
24064
Issue Date
KEYPLAN
MECH &
ELEC
ROOM
FINAL REVIEW
SET
SCO #25-29532-01A
NOT FOR
CONSTRUCTION
APPENDIX B
GASTON COLLEGE
ROBINSON CLASSROOM
BUILDING HEATING HOT
WATER UPGRADES
250 LIBRARY LANE, DALLAS, NC 28034
LS100
MH
LA
11/07/2025
Rev. No. Date Description
LEGEND
CLASSROOM
995 SF
ROOM NUMBER
ROOM SQUARE
FOOTAGE
1 HOUR FIRE - RESISTANCE RATING
1-A
2 HOUR FIRE - RESISTANCE RATING
TRAVEL DISTANCE LINE & PATH ID -
SEE TABLE FOR DISTANCES
ACCESSIBLE ENTRANCE/EXITHC
ROOM NAME
LECTURE
HALL
COMPUTER
CLASSROOM
SMALL
CLASSROOM
SMALL
CLASSROOM
SMALL
CLASSROOM
STAIR #1
ELEV #1
CORRIDOR
COMM
STORAGE
133A
SPRINKLER
ROOM
ELEC
MECHANICAL
CHAIR/TABLE
STORAGE
126A
STAIR #2
OFFICE
OFFICE
DEPT
CHAIR
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
SMALL
CLASSROOM
SMALL
CLASSROOM
CORR
CHILD
DEVELOPMENT
CLASSROOM
ELEV #1
EQUIP
FAC TLT
FAC TLT
JANITOR
MEN
FACULTY
BREAK
ROOM
ELEV #2
EQUIP
ELEC
WOMEN
ELEV #2
STORAGE
126B
STORAGE
126C
STORAGE
102D STORAGE
102E
STORAGE
102E
STORAGE
102A
STORAGE
102B
CORR
A B C
D
C O
M M
O N
P A
T H
O F
T R
A V
E L
C O N S U L T I N G E N G I N E E R S
413 DALTON AVENUE, SUITE A
CHARLOTTE, NC 28206 • 704-295-4263
NC LICENSE NO.: F-1533
AME PROJECT NO.:
Y S T A N D A R D
A C A D
B L O C K S T
IT
L E
B L O C K
IN
F O N e w
T B x .d w g
:2 :1
A M
B ri a n
E lb e rt s o n
Drawing No.
Drawing Title
Issues / Revisions
Checked by
Seals
Drawn by
Scale
Job No.
Drawing Info
AS SHOWN
24064
Project
24064
Issue Date
KEYPLAN
MECH &
ELEC
ROOM
FINAL REVIEW
SET
SCO #25-29532-01A
NOT FOR
CONSTRUCTION
LIFE SAFETY PLANS
GASTON COLLEGE
ROBINSON CLASSROOM
BUILDING HEATING HOT
WATER UPGRADES
250 LIBRARY LANE, DALLAS, NC 28034
LS200
LA
ZH
11/07/2025
TRAVEL DISTANCE
PATH ID DISTANCE (FT)
A 98' - 4"
B 120' - 0"
C 106' - 3"
D 78' - 11"
P L A
N
O
R T
H
TRUE
NORTH
1/8" = 1'-0"1
FIRST FLOOR - LIFE SAFETY
NO CHANGES TO
OCCUPANCY OR EGRESS
U S
R O
U T
E
S O
U T
H
U S
R O
U T
E
N O
R T
H
ROBINSON CLASSROOM
BUILDLING
AREA OF WORK
T O
W E
R B
O U
L E
V A
R D
R H
O D
E S
P E
R
IM
E T
E R
D R
IV
E
LI
B
R A
R Y
L A
N E
R H
O D
E S
P E
R
IM
E T
E R
D R
IV
E
K
K
M J
J
A
B
O
N
F
T
V
H
I
I
C O N S U L T I N G E N G I N E E R S
413 DALTON AVENUE, SUITE A
CHARLOTTE, NC 28206 • 704-295-4263
NC LICENSE NO.: F-1533
AME PROJECT NO.:
Y S T A N D A R D
A C A D
B L O C K S T
IT
L E
B L O C K
IN
F O N e w
T B x .d w g
:2 :1
A M
B ri a n
E lb e rt s o n
Drawing No.
Drawing Title
Issues / Revisions
Checked by
Seals
Drawn by
Scale
Job No.
Drawing Info
AS SHOWN
24064
Project
24064
Issue Date
KEYPLAN
MECH &
ELEC
ROOM
FINAL REVIEW
SET
SCO #25-29532-01A
NOT FOR
CONSTRUCTION
ARCHITECTURAL SITE
PLAN
GASTON COLLEGE
ROBINSON CLASSROOM
BUILDING HEATING HOT
WATER UPGRADES
250 LIBRARY LANE, DALLAS, NC 28034
AS100
LA
ZH
11/07/2025
P L
R T
H
TRUE
NORTH
1" = 50'-0"1
ARCHITECTURAL SITE PLAN
SYMBOL LEGEND
GENERAL NOTES
A. DO NOT SCALE DRAWING. CONTRACTOR SHALL RELY ON
WRITTEN DIMENSIONS AS SHOWN. THE CONTRACTOR
SHALL NOTIFY THE ARCHITECT FOR CLARIFICATION. ALL
DIMENSIONS SHALL BE FIELD VERIFIED BY THE
CONTRACTOR AND COORDINATED WITH ALL OF THE WORK
OF ALL TRADES. IF DISCREPANCIES ARE FOUND, THE
GENERAL CONTRACTOR SHALL NOTIFY THE ARCHITECT IN
WRITING FOR CLARIFICATION BEFORE STARTING THE
WORK.
1 HOUR RATED
WALL/PARTITION
14 15 15.3 16 171312
H
G
F
E
E.3
D
C
C.7
LECTURE
HALL 127
COMPUTER
CLASSROOM
SMALL
CLASSROOM
SMALL
CLASSROOM
SMALL
CLASSROOM
STAIR #1
141 ELEV
#1
CORRIDOR
COMM
133A
STORAGE
SPRINKLER
ROOM
136 ELEC
MECHANICAL
126A
CHAIR/TABLE
STORAGE
STAIR #2
OFFICE
OFFICE
105 DEPT
CHAIR
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
SMALL
CLASSROOM
SMALL
CLASSROOM
CORR
CHILD
DEVELOPMENT
CLASSROOM
140 ELEV
#1 EQUIP
118 FAC
TLT
119 FAC
TLT
JANITOR
115 MEN
FACULTY
BREAK
ROOM
122 ELEV
#2 EQUIP
123 ELEC
WOMEN
116 ELEV
#2
126B
STORAGE
126C
STORAGE
102D
STORAGE
STORAGE
102E
102E
STORAGE
102A
STORAGE
102B
STORAGE
CORR
CLASSIFICATION OF WORK LEGEND
LEVEL 1 ALTERATION
NO WORK
GROSS BUILDING AREA: 17,571 SF
CLASSIFICATION OF WORK TOTALS
LEVEL 1 ALTERATION: 2,562 SF (14.6%)
BASED ON TOTAL AREA OF WORK @ <50% OF GROSS BUILDING AREA
PROJECT DOES NOT NEED TO COMPLY WITH LEVEL 3 ALTERATION OF
THE NC EXISTING BUILDING CODE
EXISTING OVERHEAD COILING DOOR -
FIELD VERIFY LOCATION AND
CLEARANCE
EXISTING STEEL BEAM - FIELD VERIFY
LOCATION AND CLEARANCE
BOILER EXHAUST/INTAKE PIPING -
SEE MECHANICAL DRAWINGS FOR
MORE INFO. AND SPEC SECTION
230517 FOR SEALING REQUIREMENTS
CAST IRON THRU WALL PENETRATION
SLEEVE (WALL THIMBLE) FOR BOILER
EXHAUST/INTAKE PIPING (TYP. OF 4) -
SEE SPEC SECTION 230517 (SPACE
SLEEVES TO AVOID CUTTING OF
METAL STUDS). CONTINUOUS HEAT-
RESISTANT SILICONE SEALANT
AROUND PENETRATION
EXISTING BRICK VENEER GROUT AT
SLEEVE OPENING PER SPEC SECTION
230517
STAINLESS STEEL DRIP EDGE OVER
PENETRATION TO SHED WATER.
CONTINUOUS SILICONE SEALANT AT
TOP OF DRIP EDGE. DRIP EDGE TO
EXTEND 12" PAST OUTER EDGE OF
PENETRATION
C O N S U L T I N G E N G I N E E R S
413 DALTON AVENUE, SUITE A
CHARLOTTE, NC 28206 • 704-295-4263
NC LICENSE NO.: F-1533
AME PROJECT NO.:
Y S T A N D A R D
A C A D
B L O C K S T
IT
L E
B L O C K
IN
F O N e w
T B x .d w g
:2 :1
A M
B ri a n
E lb e rt s o n
Drawing No.
Drawing Title
Issues / Revisions
Checked by
Seals
Drawn by
Scale
Job No.
Drawing Info
AS SHOWN
24064
Project
24064
Issue Date
KEYPLAN
MECH &
ELEC
ROOM
FINAL REVIEW
SET
SCO #25-29532-01A
NOT FOR
CONSTRUCTION
CLASSIFICATION OF
WORK
GASTON COLLEGE
ROBINSON CLASSROOM
BUILDING HEATING HOT
WATER UPGRADES
250 LIBRARY LANE, DALLAS, NC 28034
A201
LA
ZH
11/07/2025
P L
R T
H
TRUE
NORTH
1/8" = 1'-0"1
FIRST FLOOR - CLASSIFICATION OF WORK
1 1/2" = 1'-0"2
BOILER EXHAUST/INTAKE @ EXTERIOR WALL
PIPE TURN UP (UP)
PIPE TURN DOWN (DN)
MECHANICAL PIPING LEGEND
MEDIUM PRESSURE STEAM PIPING
CONDENSATE DRAIN PIPINGCD
NAME OF PROJECT: GASTON COLLEGE RCB HEATING HOT WATER
UPGRADE
ADDRESS: 250 LIBRARY LN,
DALLAS, NC, 28034
PROPOSED USE: EDUCATION
OWNER/CONTACT PERSON: GASTON COLLEGE
CODE ENFORCEMENT JURISDICTION: GASTON COUNTY
BUILDING OCCUPANCY: BUSINESS
GROSS BUILDING AREA: 1,708 SF (IN SCOPE)
METHOD OF COMPLIANCE: PRESCRIPTIVE
THERMAL ZONE: 3A
MECHANICAL SYSTEMS, SERVICE SYSTEMS AND EQUIPMENT.
EXTERIOR DESIGN CONDITIONS:
WINTER DRY BULB: 23°F
SUMMER DRY BULB: 95°F
RELATIVE HUMIDITY: MCWB 74 F
INTERIOR DESIGN CONDITIONS:
WINTER DRY BULB: 72°F
SUMMER DRY BULB: 74°F
RELATIVE HUMIDITY: 50% R.H.
BUILDING HEATING LOAD: 1,065 MBH
BUILDING COOLING LOAD: 1,320 MBH
MECHANICAL SPACING CONDITIONING SYSTEM
DESCRIPTION OF UNIT: EXISTING TO REMAIN
HEATING EFFICIENCY: SEE SCHEDULES
COOLING EFFICIENCY: SEE SCHEDULES
HEAT OUTPUT OF SYSTEMS: SEE SCHEDULES
COOLING OUTPUT OF SYSTEMS: SEE SCHEDULES
MECHANICAL CODE SUMMARY
DESIGNATION DESCRIPTION
EXISTING TO REMAIN
(EQUIPMENT, DUCTWORK, PIPING, ETC.)
EXISTING/DEMOLITION/NEW
LEGEND
EXISTING TO BE DEMO'D OR RELOCATED -
REFER TO PLAN NOTES PRIOR TO DEMOLITION
(EQUIPMENT, DUCTWORK, PIPING, ETC.)
NEW
(EQUIPMENT, DUCTWORK, PIPING, ETC.)
BEGINNING OR END OF NEW WORK -OR-
CONNECT TO EXISTING
MECHANICAL GENERAL NOTES
DUCT PRESSURE CLASS REQUIREMENTS
PRESSURE CLASSDUCT SYSTEM
LOW PRESSURE EXHAUST
GENERAL ITEMS
A. GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH HVAC
DRAWING OF THIS SET. SEE EACH DRAWING FOR SPECIFIC NOTES
APPLICABLE TO THAT DRAWING.
B. THE USE OF BRAND NAMES, INCLUDING MANUFACTURERS AND MODEL
NUMBERS, IS NOT INTENDED TO RESTRICT BIDDERS TO A SPECIFIC
MANUFACTURER OR LIST OF MANUFACTURERS. THE MANUFACTURERS AND
MODEL NUMBERS LISTED ON THESE MECHANICAL DRAWINGS ARE
INTENDED TO CONVEY THE GENERAL QUALITY AND CONFIGURATION OF A
PRODUCT. EQUIVALENT PRODUTS WILL BE CONSIDERED ACCEPTABLE
PROVIDED THAT APPROVAL OF THE SPECIFIC PRODUCT HAS BEEN GIVEN IN
WRITING BY THE ARCHITECT AND OWNER.
C. ARRANGE PIPING AND DUCTWORK AS REQUIRED TO CLEAR STRUCTURE,
DUCTS, CONDUITS, ETC. ALLOWING SPACE FOR PIPE HANGERS, ACCESS TO
VALVES, FILTERS, AND MAINTENANCE OF EQUIPMENT.
D. COORDINATE LOCATION AND INSTALLATION OF EQUIPMENT WITH OTHER
TRADES.
E. PIPING, DUCTWORK, VENTS, ETC., EXTENDING THROUGH EXTERIOR WALLS
AND ROOF MUST BE FLASHED AND COUNTER FLASHED IN A
WEATHERPROOF MANNER.
F. EXTEND DRAIN LINES AS INDICATED. ROUTING MUST NOT INTERFERE WITH
PASSAGEWAYS AND MAINTENANCE. SLOPE CONDENSATE DRAIN PIPING AT
1/8" PER FOOT.
G. PIPING AND DUCTWORK INSULATION MUST RUN CONTINUOUSLY THROUGH
NON-RATED FLOORS, WALLS, ROOF AND PARTITIONS, UNLESS OTHERWISE
INDICATED.
H. FOR LOCATION OF MOTOR STARTERS, SEE ELECTRICAL DRAWINGS.
I. NO PIPING SHALL BE SMALLER THAN 3/4" UNLESS OTHERWISE NOTED.
J. PROVIDE UNION OR FLANGED CONNECTIONS AT EACH PIECE OF EQUIPMENT
AND ON BOTH SIDES OF CONTROL VALVES AND PRESSURE REGULATING
VALVES. PROVIDE SHUT-OFF VALVES ON BOTH SIDES OF AUTOMATIC
VALVES.
K. PIPING MUST BE SUPPORTED IN ACCORDANCE WITH THE SPECIFICATIONS.
ADDITIONAL SUPPORTS OR HANGERS MUST BE ADJACENT TO ELBOWS TO
PREVENT WEIGHT OF PIPING BEING PLACED ON EQUIPMENT.
L. FILL IN ANY EXISTING PENETRATIONS THROUGH THE EXTERIOR WALL THAT
ARE NOT BEING UTILIZED FOR NEW BOILER VENT OR INTAKE DUCTWORK.
M. GENERAL CONTRACTOR MUST COORDINATE CONSTRUCTION SCHEDULE
WITH OWNER. CONTRACTOR MUST COORDINATE THE SCHEDULE OF THE
DOMESTIC HOT WATER SHUT DOWN WITH THE OWNER.
SHEET METAL
A. ALL DUCTWORK MUST BE FABRICATED AND INSTALLED IN ACCORDANCE
WITH THE LATEST EDITION OF SMACNA'S "HVAC DUCT CONSTRUCTION
STANDARDS - METAL AND FLEXIBLE."
B. PROVIDE BEARING PLATES AND OTHER NECESSARY REINFORCEMENTS AT
DUCTWORK SUPPORTS TO ENSURE THAT DUCT INSULATION MAINTAINS
REQUIRED "R" VALUES.
DESIGNATION DESCRIPTION
MPS
HOT WATER RETURN (HEATING)HWR
HOT WATER SUPPLY (HEATING)HWS
BUTTERFLY VALVE
UNION
DIRECTION OF FLOW
FULL PORT BALL VALVE
CHECK VALVE
Y-STRAINER
2.0" PRESSURE CLASS
LOW PRESSURE OUTDOOR AIR 2.0" PRESSURE CLASS
RELATIVE HUMIDITYRH
PHASEPH
PRESSURE DROPPD
OUTDOOR AIROA
MINIMUM CIRCUIT AMPACITYMCA
MECHANICAL CONTRACTORM.C.
1000 BTU PER HOURMBH
MAXIMUMMAX
LEAVING AIR TEMPERATURELAT
DEGREES FAHRENHEIT°F
EXHAUST AIREA
DIGITAL OUTPUTDO
BUILDING AUTOMATION SYSTEMBAS
AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASHRAE
ANALOG OUTPUTAO
MAXIMUM OVER CURRENT PROTECTION
INCHES WATER GAUGE (PRESSURE)
FULL LOAD AMPS
MOCP
ALARM
AIR HANDLING UNIT
ABOVE FINISHED FLOOR
IN. WG.
FLA
AL
AHU
AFF
AMERICAN SOCIETY OF HEATING,
REFRIGERATING, AND AIR CONDITIONING
ENGINEERS
ASME
MECHANICAL ABBREVIATIONS
DESCRIPTIONDESIGNATION
ENTERING AIR TEMPERATUREEAT
ELECTRICAL CONTRACTORE.C.
UNIT HEATERUH
CONTROLS CONTRACTORC.C.
AIR SEPARATORAS
DIFFERENTIAL PRESSUREDP
VARIABLE FREQUENCY DRIVEVFD
EXPANSION TANKET
HEAT PUMP OR HORSEPOWERHP
LOW PRESSURE STEAM PIPINGLPS
NATURAL GAS METERGM
NATURAL GAS PIPINGNG
GAS PRESSURE REDUCING REGULATOR
TEMPERATURE SENSORTS
AUTOMATIC FLOW LIMITING VALVE
AF
FLOW SWITCHFS
2-WAY CONTROL VALVE
CONDENSATE RETURN PUMPCR
BOILER SHUTOFFBS
SOLENOID VALVE
S
SUSPENDED PIPE ON TRAPEZE NOT REQUIRED 13.1.4.5
DUCTWORK NOT REQUIRED
NOT REQUIREDMULTIPLE DUCTS ON TRAPEZE
NOT REQUIRED
REQUIRED
(SEE NOTE 4)
13.2.2
13.1.4.5NOT REQUIRED
NOT REQUIRED 13.1.4.5
13.1.4.5RESTRAIN ALL13.1.4.5NOT REQUIRED
NOT REQUIRED 13.1.4.5
13.6.5
13.1.4.5
13.1.4.5
13.1.4.5RESTRAIN ALL
RESTRAIN ALL
RESTRAIN ALL
RESTRAIN ALL13.1.4.5
13.1.4.5
13.1.4.5
13.1.4.5NOT REQUIRED
NOT REQUIRED
NOT REQUIRED
NOT REQUIREDCOMPONENT SUPPORTS
WALL MOUNTED
FLOOR MOUNTED
ROOF MOUNTED
COMPONENT IDENTIFICATION
COMPONENT IMPORTANCE FACTOR (Ip)
SEISMIC DESIGN CATEGORY: C
RISK CATEGORY: III
SEISMIC AND WIND REQUIREMENTS
FOR MECHANICAL SYSTEMS
RESTRAIN IF ANY PIPE
ON TRAPEZE >2"
RESTRAIN IF TOTAL
WEIGHT OF PIPES ON
TRAPEZE >10 LB/FT
(SEE NOTE 2)
RESTRAIN IF TOTAL
WEIGHT OF DUCTS ON
TRAPEZE >10 LB/FT
(SEE NOTE 2,3)
COMPONENT CERTIFICATION
RESTRAIN ALL
(SEE NOTE 2)
SUSPENDED NON DUCTILE PIPING
(CAST IRON, PLASTIC, CERAMIC)
SUSPENDED DUCTILE PIPING
(STEEL, AL, CU, ETC.)
RESTRAIN IF>2"
(SEE NOTE 2)
NOT INLINE W/
DUCT/PIPE
SUSPENDED
EQUIPMENT
RESTRAIN IF >75 LB
PROVIDE FLEX. CONN.
(SEE NOTE 1)
INLINE W/
DUCT/PIPE
13.1.4.5
13.1.4.5
13.2.2
TABLE NOTES:
1. FLEXIBLE CONNECTIONS REQUIRED FOR PIPE CONNECTIONS ONLY.
2. RESTRAINT IS NOT REQUIRED IF THE PIPING OR DUCTWORK IS SUPPORTED BY HANGERS WHERE EACH HANGER IS 12 INCHES OR LESS IN LENGTH FROM THE TOP OF THE PIPE OR DUCT TO THE SUPPORTING STRUCTURE. WHERE PIPES OR DUCTS ARE SUPPORTED ON A TRAPEZE, THE TRAPEZE MUST BE SUPPORTED BY HANGERS HAVING A LENGTH OF 12 INCHES OR LESS. WHERE ROD HANGERS ARE USED, THEY MUST BE EQUIPPED WITH SWIVELS, EYES NUTS OR OTHER
DEVICES TO PREVENT BENDING IN THE ROD.
3. ALL PIPING AND DUCTWORK, REGARDLESS OF SIZE, DESIGNED TO CARRY TOXIC, HIGHLY TOXIC, OR EXPLOSIVE GASES OR
USED FOR SMOKE CONTROL MUST BE RESTRAINED.
4. COMPONENT CERTIFICATION MUST BE SUPPLIED BY THE EQUIPMENT MANUFACTURER AT THE TIME OF SUBMITTAL FOR
REVIEW BY ENGINEER OF RECORD.
5. ALL COMPONENTS HAVE LP=1.0 EXCEPT GAS PIPING AND GAS FIRED EQUIPMENT WHICH HAVE AN LP=1.5.
13.6.7
13.6.8.3.3.a
13.6.8.3.3
13.6.8.3.1
13.6.7
RESTRAIN IF >6 SQ.
FT. OR >17 LB/FT
(SEE NOTE 2, 3)
13.6.7
INFORMATION FOR NCSBC 2018 / ASCE 7-10
A. PER 2018 NORTH CAROLINA BUILDING CODE, MECHANICAL EQUIPMENT AND COMPONENTS, INCLUDING THEIR SUPPORTS AND ATTACHMENTS, MUST BE DESIGNED FOR SEISMIC FORCES IN ACCORDANCE WITH CHAPTER 13 OF ASCE 7-10.
B. EXTERIOR EQUIPMENT (INCLUDING ROOF CURBS AND ROOF RAILS) EXPOSED TO WIND MUST BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH CHAPTERS 26 THROUGH 29 OF ASCE 7-10.
C. WHERE DESIGN FOR SEISMIC AND WIND LOADS IS REQUIRED, THE MORE DEMANDING FORCE MUST BE USED.
D. USE TABLE BELOW TO DETERMINE SEISMIC RESTRAINT REQUIREMENTS FOR EACH COMPONENT.
E. FOR ALL COMPONENTS REQUIRING SEISMIC RESTRAINT, THE COMPONENT SUPPORTS AND ATTACHMENTS MUST BE
DESIGNED BY A REGISTERED DESIGN PROFESSIONAL.
F. WHERE SEISMIC RESTRAINT IS REQUIRED, HOUSEKEEPING PADS NEEDED FOR THE INSTALLATION OF EQUIPMENT UNDER THIS CONTRACT MUST BE DESIGNED BY THE SEISMIC ENGINEER. DO NOT POUR ANY HOUSEKEEPING PADS PRIOR TO THE
RECEIPT OF APPROVED SEISMIC SUBMITTAL.
G. SEISMIC RESTRAINTS FOR DUCTWORK, PIPING AND CONDUIT MUST BE SHOWN ON SEISMIC SUBMITTAL LAYOUT DRAWINGS SHOWING SPECIFIC RESTRAINT LOCATIONS ALONG WITH ACCOMPANYING DETAILS AND CALCULATIONS.
SEISMIC RESTRAINT
REQUIREMENT
ASCE 7-10
REFERENCE
SEISMIC RESTRAINT
REQUIREMENT
ASCE 7-10
REFERENCE
1.0 1.5
C O N S U L T I N G E N G I N E E R S
413 DALTON AVENUE, SUITE A
CHARLOTTE, NC 28206 • 704-295-4263
NC LICENSE NO.: F-1533
AME PROJECT NO.:
Y S T A N D A R D
A C A D
B L O C K S T
IT
L E
B L O C K
IN
F O N e w
T B x .d w g
:2 :1
A M
B ri a n
E lb e rt s o n
Drawing No.
Drawing Title
Issues / Revisions
Checked by
Seals
Drawn by
Scale
Job No.
Drawing Info
AS SHOWN
24064
Project
24064
Issue Date
FINAL REVIEW
SET
SCO #25-29532-01A
MECHANICAL -
GENERAL NOTES AND
LEGENDS
GASTON COLLEGE
ROBINSON CLASSROOM
BUILDING HEATING HOT
WATER UPGRADES
250 LIBRARY LN, DALLAS, NC 28035
M0.1
FFR
NJH
11/07/2025
MECHANICAL SHEET INDEX
M0.1 MECHANICAL - GENERAL NOTES AND LEGENDS
M1.1 MECHANICAL HVAC - DEMOLITION PLAN
M1.2 MECHANICAL PIPING - DEMOLITION PLAN
M2.1 MECHANICAL HVAC - NEW CONSTRUCTION PLAN
M3.1 MECHANICAL PIPING - NEW CONSTRUCTION PLAN
M6.1 MECHANICAL - CONTROLS & SCHEDULES
M7.1 MECHANICAL - DETAILS
M7.2 MECHANICAL - PIPING DIAGRAMS
14 15 15.3 16 17
H
G
F
E
E.3
D
C
C.7
H
G
F
E.3
E
D
C.7
C
14 15.3 16 17
(ETR)
AHU-2
(ETR)
AHU-3
(ETR)
AHU-1
(ETR)
P-6
(ETR)
P-5
(ETR)
P-4
(ETR)
P-3
(ETR)
WCC-1
(ETBD)
B-1
(ETR)
WH-1
(ETBD)
HX-1
(ETBD)
CR-1
8ø-OA
60x24-RA
32x22-SA
32x22-SA32x32-SA
36x24-SA
36x24-SA
UP TO 3RD
FLOOR
44x24-RA
24x24-OA
36x20-RA
44x24-SA
24x24-OA
32x32-OA
32x32-OA
24x24-OA
26x22-RA
60x24-RA 32x22-SA
44x24-RA
24x24-OA
UP TO 3RD FLOOR
UP TO 2ND FLOOR
UP TO 2ND
FLOOR
44x24-SA
UP
UP
(ETR)
EF-6
16x16-EA
16x16-EA
UP
C O N S U L T I N G E N G I N E E R S
413 DALTON AVENUE, SUITE A
CHARLOTTE, NC 28206 • 704-295-4263
NC LICENSE NO.: F-1533
AME PROJECT NO.:
Y S T A N D A R D
A C A D
B L O C K S T
IT
L E
B L O C K
IN
F O N e w
T B x .d w g
:2 :1
A M
B ri a n
E lb e rt s o n
Drawing No.
Drawing Title
Issues / Revisions
Checked by
Seals
Drawn by
Scale
Job No.
Drawing Info
AS SHOWN
24064
Project
24064
Issue Date
KEYPLAN
MECH &
ELEC
ROOM
FINAL REVIEW
SET
SCO #25-29532-01A
MECHANICAL HVAC -
DEMOLITION PLAN
GASTON COLLEGE
ROBINSON CLASSROOM
BUILDING HEATING HOT
WATER UPGRADES
250 LIBRARY LN, DALLAS, NC 28035
M1.1
FFR
NJH
11/07/2025
1. M.C. MUST VISIT THE SITE TO CAREFULLY EXAMINE AND BECOME FAMILIARIZED WITH
THE DEMOLITION DOCUMENTS AND EXISTING CONDITIONS PRIOR TO BIDDING.
SUBMISSION OF A PROPOSAL WILL BE CONSIDERED AS EVIDENCE THAT SUCH AN
EXAMINATION HAS BEEN PERFORMED. M.C MUST INCLUDE IN HIS BID ALL WORK
NEEDING TO BE DONE AFTER HOURS, ON WEEKENDS, AND ANY WORK REQUIRING
SHUTDOWNS OR ANY TIME THAT MAY REQUIRE OVERTIME. LATER CLAIMS FOR EXTRA
LABOR OR MATERIALS REQUIRED DUE TO DIFFICULTIES ENCOUNTERED WILL NOT BE
RECOGNIZED.
2. DEMO EQUIPMENT SHOWN DASHED. RELOCATE EQUIPMENT SHOWN DASHED AND
NOTED. REFER TO KEY NOTES FOR ADDITIONAL DEMOLITION INFORMATION.
3. DEMOLITION WORK MUST BE COORDINATED WITH THE OWNERS REPRESENTATIVE
AND ALSO BE COORDINATED WITH ALL EXISTING ARCHITECTURAL, MECHANICAL,
ELECTRICAL, AND STRUCTURAL SYSTEMS.
4. EXISTING CONDITIONS, EQUIPMENT, MATERIALS, AND SIZES ARE SHOWN FOR
REFERENCE ONLY. M.C. IS RESPONSIBLE TO VERIFY EXISTING CONDITIONS AND
BRING ANY DISCREPANCIES TO THE ENGINEER'S ATTENTION IN WRITING PRIOR TO
DEMOLITION AND STARTING NEW WORK.
5. ANY REMAINING SYSTEMS DAMAGED DURING THE DEMOLITION PHASE OF WORK
MUST BE RESTORED TO ORIGINAL CONDITION AT NO ADDITIONAL COST.
6. G.C. MUST REPAIR AND PATCH ALL EXISTING CONSTRUCTION ITEMS. ANY EXISTING
HVAC SYSTEM ITEMS THAT ARE TO REMAIN ARE SHOWN ON THE NEW WORK HVAC
FLOOR PLAN. IT IS THE RESPONSIBILITY OF THE M.C. TO MAINTAIN THE CONTINUITY
OF THE EXISTING HVAC SYSTEMS TO REMAIN.
GENERAL NOTES - MECHANICAL
1. DEMOLISH EXISTING COMBUSTION AIR INTAKE FOR BOILER. INFILL ANY EXSITING
OPENINGS NOT TO BE RE-USED. MATCH EXISTING BUILDING CONSTRUCTION WHEN
INFILLING UNUSED OPENINGS IN THE BUILDING EXTERIOR WALLS.
2. REFER TO SHEET M1.2 FOR ADDITIONAL INFORMATION CONCERNING DEMOLITION OF
THE EXISTING GAS FIRED BOILER.
3. EXISTING AIR HANDLERS ARE TO REMAIN AND BE UPFIT WITH NEW AIR CLEANING
DEVICES. REFER TO SHEET M2.1 FOR ADDITIONAL INFORMATION.
4. DEMOLISH EXISTING FLUE VENT FOR BOILER. IF POSSIBLE REUSE THIS OPENING FOR
A NEW BOILER FLUE VENT. IF THIS OPENING CANNOT BE REUSED, INFILL EXISTING
OPEINING TO MATCH EXISTING BUILDING CONSTRUCTION.
KEYED NOTES#
GRAPHICS SCALE
8' 12' 16'4'
SCALE: 1/4" = 1'-0"
TRUE
NORTH
SCALE 1/4" = 1'-0"
MECHANICAL - HVAC PLAN - DEMOLITION
14 15 15.3 16 1713
G
F
E
E.3
D
C
C.7
H
G
F
E.3
E
D
C.7
C
13 14 15 15.3 16 17
(ETR)
AHU-3
(ETR)
AHU-2
(ETR)
AHU-1
(ETR)
WCC-1
(ETR)
P-3
(ETR)
P-4
(ETR)
P-5
(ETR)
P-6
B-1
B-2
(ETR)
WH-1
8ø-EA
8ø-OA
MECHANICAL
UV-14
UV-24
UV-3
8ø-EA
8ø-OA
M2.1
(ETR)
EF-6
EXISTING RETAINING WALL
H G
8ø-EA
16x16-EA
BOILER
INTAKE
BOILER
COMBUSTION AIR
EXHAUST ABOVE
RETAINING WALL
AND INTAKE
EXISTING EXHAUST LOUVER
RETAINING
WALL
C O N S U L T I N G E N G I N E E R S
413 DALTON AVENUE, SUITE A
CHARLOTTE, NC 28206 • 704-295-4263
NC LICENSE NO.: F-1533
AME PROJECT NO.:
Y S T A N D A R D
A C A D
B L O C K S T
IT
L E
B L O C K
IN
F O N e w
T B x .d w g
:2 :1
A M
B ri a n
E lb e rt s o n
Drawing No.
Drawing Title
Issues / Revisions
Checked by
Seals
Drawn by
Scale
Job No.
Drawing Info
AS SHOWN
24064
Project
24064
Issue Date
KEYPLAN
MECH &
ELEC
ROOM
FINAL REVIEW
SET
SCO #25-29532-01A
MECHANICAL HVAC -
NEW CONSTRUCTION
PLAN
GASTON COLLEGE
ROBINSON CLASSROOM
BUILDING HEATING HOT
WATER UPGRADES
250 LIBRARY LN, DALLAS, NC 28035
M2.1
FFR
NJH
11/07/2025
1. EXISTING CONDITIONS, EQUIPMENT, MATERIALS, LOCATIONS, AND SIZES ARE
SHOWN FOR REFERENCE ONLY. M.C. IS RESPONSIBLE TO VERIFY ALL
EXISTING CONDITIONS/SIZES AND NOTIFY ENGINEER OF ANY DISCREPANCIES
IN WRITING PRIOR TO STARTING WORK.
2. CAP AND REPAIR EXISTING PIPING FROM DEMOLITION NOT USED. SEAL AIR
TIGHT AND PATCH INSULATION. M.C. MUST MATCH EXISTING PIPE AND
INSULATION SYSTEMS.
3. CLEAN AND REPAIR EXISTING DUCTWORK & INSULATION WITHIN THE SCOPE
OF PROJECT TO LIKE-NEW CONDITION.
GENERAL NOTES
SCALE 1/4" = 1'-0"
MECHANICAL - HVAC PLAN - NEW CONSTRUCTION
1. PROVIDE FACTORY FRESH AIR INTAKE KIT FROM BOILER MANUFACTURER. ROUTE
INTAKE TO BUILDING EXTERIOR IN A NEW OPENING IN THE EXTERIOR WALL.
CONTRACTOR TO PROVIDE NEW WALL OPENINGS FOR INTAKE DUCT.
2. PROVIDE FACTORY FLUE KIT FROM BOILER MANUFACTURER. ROUTE VENT TO
BUILDING EXTERIOR. CONTRACTOR TO UTILIZE EXISTING BOILER VENT OPENING IF
POSSIBLE. REFER TO DETAIL 12/M7.1 FOR EXHAUST FLUE DUCT ROUTING ON THE
EXTERIOR OF THE BUILDING. MAINTAIN ALL CLEARANCES NOTED IN THE BOILER
MANUFACTURERS INSTALLATION MANUAL.
3. REPLACE EXISTING MERV-8 FILTERS IN THE AIR HANDLING UNIT WITH 2" MERV-13
FILTERS. CAMFIL AQ13 2" FILTERS ARE THE BASIS OF DESIGN. THE DIFFERENTIAL
PRESSURE ALARM ACROSS SETPOINT SHOULD REMAIN UNCHANGED.
4. PROVIDE UV LIGHTING UPSTREAM OF THE COOLING COIL. INSTALL UV LIGHTING
BASED ON UV MANUFACTURER INSTALLATION INSTRUCTIONS. MOUNT UV LIGHTING
CONTROL BOX ON A NEW UNISTRUT RACK NEXT TO THE ASSOCIATED AIR HANDLING
UNIT. INTERLOCK UV LIGHTS WITH THE CORRESPONDING AHU DOORS. THE LIGHTS
SHOULD SHUT OFF WHEN THE DOORS OPEN.
5. DUCTWORK SHOWN ON PLANS NEXT TO EACH OTHER FOR REFERENCE. STACK
BOILER INTAKE AND VENT DUCTWORK ALONG THE EXTERIOR WALL AS SHOWN IN
DETAIL 9/M7.1.
6. ACCESS DOOR MARKS THE END OF PUBLIC WALKWAY FOR EGRESS. THE SPACE
BETWEEN THIS DOOR AND THE RETAINING WALL AT THE END OF THE ALLEY IS FOR
SERVICE ACCESS TO THE MECHANICAL ROOM ONLY.
KEYED NOTES#
GRAPHICS SCALE
8' 12' 16'4'
SCALE: 1/4" = 1'-0" TRUE
NORTH
SCALE 3/4" = 1'-0"
EXTERIOR WALL BOILER COMBUSTION AIR AND INTAKE
SCALE: 3/4" = 1'-0"GRAPHICS SCALE
4' 6'2'
G
F
E
E.3
D
C
C.7
H
G
F
E.3
E
D
C.7
C
14 15 15.3 16 17
(ETR)
AHU-3
(ETR)
AHU-2
(ETR)
AHU-1
(ETR)
WCC-1
(ETR)
P-3
(ETR)
P-4
(ETR)
P-5
(ETR)
P-6
B-1 B-2
(ETR)
WH-1
8ø-EA
8ø-OA
MECHANICAL
UV-14
UV-24
UV-3
8ø-EA 8ø-OA
M2.1
(ETR)
EF-6
H G
8ø-EA
8ø-OA
16x16-EA
BOILER
INTAKE
BOILER
COMBUSTION
AIR EXHAUST
ABOVE
RETAINING WALL
AND INTAKE
EXHAUST LOUVER
RETAINING
WALL
C O N S U L T I N G E N G I N E E R S
413 DALTON AVENUE, SUITE A
CHARLOTTE, NC 28206 • 704-295-4263
NC LICENSE NO.: F-1533
AME PROJECT NO.:
Y S T A N D A R D
A C A D
B L O C K S T
IT
L E
B L O C K
IN
F O N e w
T B x .d w g
:2 :1
A M
B ri a n
E lb e rt s o n
Drawing No.
Drawing Title
Issues / Revisions
Checked by
Seals
Drawn by
Scale
Job No.
Drawing Info
AS SHOWN
24064
Project
24064
Issue Date
KEYPLAN
MECH &
ELEC
ROOM
FINAL REVIEW
SET
SCO #25-29532-01A
MECHANICAL HVAC -
NEW CONSTRUCTION
PLAN
GASTON COLLEGE
ROBINSON CLASSROOM
BUILDING HEATING HOT
WATER UPGRADES
250 LIBRARY LN, DALLAS, NC 28035
M2.1
FFR
NJH
11/07/2025
1. EXISTING CONDITIONS, EQUIPMENT, MATERIALS, LOCATIONS, AND SIZES ARE
SHOWN FOR REFERENCE ONLY. M.C. IS RESPONSIBLE TO VERIFY ALL
EXISTING CONDITIONS/SIZES AND NOTIFY ENGINEER OF ANY DISCREPANCIES
IN WRITING PRIOR TO STARTING WORK.
2. CAP AND REPAIR EXISTING PIPING FROM DEMOLITION NOT USED. SEAL AIR
TIGHT AND PATCH INSULATION. M.C. MUST MATCH EXISTING PIPE AND
INSULATION SYSTEMS.
3. CLEAN AND REPAIR EXISTING DUCTWORK & INSULATION WITHIN THE SCOPE
OF PROJECT TO LIKE-NEW CONDITION.
GENERAL NOTES
SCALE 1/4" = 1'-0"
MECHANICAL - HVAC PLAN - NEW CONSTRUCTION
1. PROVIDE FACTORY FRESH AIR INTAKE KIT FROM BOILER MANUFACTURER. ROUTE
INTAKE TO BUILDING EXTERIOR IN A NEW OPENING IN THE EXTERIOR WALL.
CONTRACTOR TO PROVIDE NEW WALL OPENINGS FOR INTAKE DUCT.
2. PROVIDE FACTORY FLUE KIT FROM BOILER MANUFACTURER. ROUTE VENT TO
BUILDING EXTERIOR. CONTRACTOR TO UTILIZE EXISTING BOILER VENT OPENING IF
POSSIBLE. REFER TO DETAIL 12/M7.1 FOR EXHAUST FLUE DUCT ROUTING ON THE
EXTERIOR OF THE BUILDING.
3. REPLACE EXISTING MERV-8 FILTERS IN THE AIR HANDLING UNIT WITH 2" MERV-13
FILTERS. CAMFIL AQ13 2" FILTERS ARE THE BASIS OF DESIGN. THE DIFFERENTIAL
PRESSURE ALARM ACROSS SETPOINT SHOULD REMAIN UNCHANGED.
4. PROVIDE UV LIGHTING UPSTREAM OF THE COOLING COIL. INSTALL UV LIGHTING
BASED ON UV MANUFACTURER INSTALLATION INSTRUCTIONS. MOUNT UV LIGHTING
CONTROL BOX ON A NEW UNISTRUT RACK NEXT TO THE ASSOCIATED AIR HANDLING
UNIT. INTERLOCK UV LIGHTS WITH THE CORRESPONDING AHU DOORS. THE LIGHTS
SHOULD SHUT OFF WHEN THE DOORS OPEN.
5. DUCTWORK SHOWN ON PLANS NEXT TO EACH OTHER FOR REFERENCE. STACK
BOILER INTAKE AND VENT DUCTWORK ALONG THE EXTERIOR WALL AS SHOWN IN
DETAIL 9/M7.1.
KEYED NOTES#
GRAPHICS SCALE
8' 12' 16'4'
SCALE: 1/4" = 1'-0" TRUE
NORTH
SCALE 3/4" = 1'-0"
EXTERIOR WALL BOILER COMBUSTION AIR AND INTAKE
SCALE: 3/4" = 1'-0"GRAPHICS SCALE
4' 6'2'
G
F
E.3
E
D
C.7
C
(ETR)
AHU-3
(ETR)
AHU-2
(ETR)
AHU-1
(ETR)
WCC-1
(ETR)
P-3
(ETR)
P-4
(ETR)
P-5
(ETR)
P-6
B-1 B-2
(ETR)
WH-1
CONTINUES TO REST
OF CAMPUS
HHWP-1
2 1/2" MPS
2" CD
(ETR)
P-1
(ETR)
P-2
AS-1
2 1/2" HWS
2 1/2" HWR
2 1/2" HWS
2 1/2" HWR
2 1/2" HWS
2 1/2" HWR
2 1/2" HWS
2 1/2" HWR
2 1/2" HWR
2 1/2" HWS
(ETR)2 1/2" HWS
(ETR)2 1/2" HWR
(ETR)1" NG
1" NG
1" NG
1" NG
(ETR)2" HWS
(ETR)2" HWR
(ETR)2" HWS
(ETR)2" HWR
(ETR)2" HWS
(ETR)2" HWR
(ETR)2" HWS
(ETR)2" HWR2 1/2" HWS
BUILDING MAX NG
CAPACITY:
1,500 CFH
(ETR)1" NG
(ETR)2" HWS
(ETR)2" HWR
(ETR)2" HWR
(ETR)2" HWS
CONTINUES TO
REST OF BUILDING
MECHANICAL
BS
ET-1
BS
1" CD
1" CD
10 10
1" CD
C O N S U L T I N G E N G I N E E R S
413 DALTON AVENUE, SUITE A
CHARLOTTE, NC 28206 • 704-295-4263
NC LICENSE NO.: F-1533
AME PROJECT NO.:
Y S T A N D A R D
A C A D
B L O C K S T
IT
L E
B L O C K
IN
F O N e w
T B x .d w g
:2 :1
A M
B ri a n
E lb e rt s o n
Drawing No.
Drawing Title
Issues / Revisions
Checked by
Seals
Drawn by
Scale
Job No.
Drawing Info
AS SHOWN
24064
Project
24064
Issue Date
KEYPLAN
MECH &
ELEC
ROOM
FINAL REVIEW
SET
SCO #25-29532-01A
MECHANICAL PIPING -
NEW CONSTRUCTION
PLAN
GASTON COLLEGE
ROBINSON CLASSROOM
BUILDING HEATING HOT
WATER UPGRADES
250 LIBRARY LN, DALLAS, NC 28035
M3.1
FFR
NJH
11/07/2025
1. EXISTING CONDITIONS, EQUIPMENT, MATERIALS, LOCATIONS, AND SIZES ARE
SHOWN FOR REFERENCE ONLY. M.C. IS RESPONSIBLE TO VERIFY ALL
EXISTING CONDITIONS/SIZES AND NOTIFY ENGINEER OF ANY DISCREPANCIES
IN WRITING PRIOR TO STARTING WORK.
2. CAP AND REPAIR EXISTING PIPING FROM DEMOLITION NOT USED. SEAL AIR
TIGHT AND PATCH INSULATION. M.C. MUST MATCH EXISTING PIPE AND
INSULATION SYSTEMS.
GENERAL NOTES
1. CAP EXISTING MEDIUM PRESSURE STEAM AND CONDENSATE PIPES ENTERING THE
BUILDING AT THE POINT THEY ENTER THE MECHANICAL ROOM. PROVIDE END OF LINE
DRIP LEG AND TRAP. SEE DETAIL 7/M7.1.
2. PROVIDE A NEW 4" HOUSE KEEPING PAD UNDERNEATH THE TWO NEW BOILERS, B-1
AND B-2. REFER TO DETAIL ON M7.1 FOR DIMENSIONS OF THE HOUSEKEEPING PAD.
3. MAINTAIN 3' OF CLEARANCE FROM ELECTRICAL PANELS AND BAS PANELS LOCATED
ON THE WALL TO THE BOILER.
4. THE EXISTING NATURAL GAS METER LOCATED ON THE EXTERIOR OF THE BUILDING
ABOVE GRADE SHALL REMAIN TO SERVE THE NEW BOILERS.
5. REFER TO NATURAL GAS EQUIPMENT CONNECTION DETAIL ON SHEET M7.1 TO SEE
CONNECTION REQUIREMENTS.
6. PROVIDE BOILER EMERGENCY STOP SWITCH (ESS) NEXT TO THE ENTRY DOOR INTO
THE MECHANICAL ROOM. TIE THE BOILER SHUT OFF SWITCH INTO THE NATURAL GAS
SOLENOID VALVE.
7. TIE GAS SOLENOID SHUT-OFF VALVE INTO EMERGENCY STOP SWITCHES (ESS).
8. EXISTING VALVE SCHEDULE IS LOCATED ON THIS WALL. PROVIDE THE OWNER WITH A
NEW VALVE SCHEDULE BASED ON THE NEW HYDRONIC PIPING.
9. PUMP MOTOR TO BE MOUNTED VERTICALLY. DO NOT INSTALL PUMP WITH
HORIZONTAL MOUNT MOTOR.
10. PIPE ALL RELIEF AND/OR DRAIN PIPING OVERHEAD AND DOWN TO NEAREST FLOOR
DRAIN. LOCATE ALL VALVES IN ACCESSIBLE LOCATIONS. REFER TO PIPING DIAGRAMS
AND DETAILS FOR REQUIRED VALVING.
11. TERMINATE ALL NEW DRAIN PIPING WITH AIR GAP ABOVE EXISTING FLOOR DRAIN.
12. ROUTE NEW BOILER CONDENSATE DRAIN PIPING TIGHT TO OUTSIDE EDGE OF NEW
BOILER EQUIPMENT PAD. CROSS THE OPEN FLOOR IN THE MOST DIRECT PATH
POSSIBLE TO THE NOTED FLOOR DRAIN.
KEYED NOTES#
GRAPHICS SCALE
8' 12' 16'4'
SCALE: 1/4" = 1'-0" TRUE
NORTH
SCALE 1/4" = 1'-0"
MECHANICAL - PIPING PLAN - NEW CONSTRUCTION
POINT DESCRIPTION UNITS
HEATING HOT WATER SYSTEM
CONTROL DIAGRAM AND SEQUENCE OF OPERATIONS
OA-T
B-1-HWS-T
S-HWS-T*
S-HWR-T*
P-1-O*
P-1-C*
DP-SP*
OUTSIDE AIR TEMPERATURE
SECONDARY HOT WATER SUPPLY TEMPERATURE
SECONDARY HOT WATER RETURN TEMPERATURE
SECONDARY HOT WATER PUMP 1 VFD OUTPUT
SECONDARY HOT WATER PUMP 1 COMMAND
DIFFERENTIAL PRESSURE SETPOINT
DEG F
DEG F
DEG F
OFF ON
PSI
%P-2-O* SECONDARY HOT WATER PUMP 2 VFD OUTPUT
P-2-C* SECONDARY HOT WATER PUMP 2 COMMAND OFF ON
HEATING HOT WATER SYSTEM CONTROL POINTS LIST
B-2-HWS-T
DEG F
DEG F
PSIS-HW-DP* SECONDARY HOT WATER DIFFERENTIAL PRESSURE
BOILER 1 HOT WATER SUPPLY TEMPERATURE
BOILER 2 HOT WATER SUPPLY TEMPERATURE
B-1-HWR-T
B-2-HWR-T
DEG F
DEG F
BOILER 1 HOT WATER RETURN TEMPERATURE
BOILER 2 HOT WATER RETURN TEMPERATURE
HHWP-1-S PRIMARY HOT WATER PUMP 1 STATUS OFF ON
P-1-S* SECONDARY HOT WATER PUMP 1 STATUS OFF ON
P-2-S* SECONDARY HOT WATER PUMP 2 STATUS OFF ON
HHWP-1-C PRIMARY HOT WATER PUMP 1 COMMAND OFF ON
HWS
HWR
S-HWR-F
B-1-EN
B-1-A
BOILER B-1
CONTROL
CABINET
HHWP-1-C
HHWP-1-S
HHWP-1
B-1-HWS-T
B-1-HWR-T
S-HWS-T
P-2 (LAG)
P-1 (LEAD)
P-1 VFD
P-2 VFD
P-2-S P-2-C
P-2-O
P-1-S P-1-C
P-1-O
B-1
S-HWR-T
B-2-EN
B-2-A
B-2-HWS-T
B-2-HWR-T
S-HW-DP
B-2
PRIMARY HOT WATER PUMP CONTROL (HHWP-1): THE PRIMARY HOT WATER PUMP IS STARTED/STOPPED BY A SIGNAL FROM THE BOILER. THE PUMP MUST RUN FOR AN ADJUSTABLE TIME DELAY AFTER THE BOILER STOPS. THIS FUNCTION IS CONTROLLED BY THE BOILER CONTROLLER. IF IT'S STATUS DOES NOT MATCH IT'S COMMANDED VALUE, AN ALARM MUST BE GENERATED.
SECONDARY HOT WATER PUMP CONTROL (P-1 & P2): EXISTING CONTROLS AND SEQUENCE TO REMAIN FOR SECONDARY HOT
WATER PUMPS.
BOILER CONTROL (B-1 & B-2): WHEN THERE IS A CALL FOR HEATING BY THE BAS ENABLE THE LEAD BOILER. IF THE HEATING HOT WATER TEMPERATURE FAILS TO INCREASE TO SETPOINT DISABLE THE LEAD BOILER AND ENABLE THE LAG BOILER. PROVIDE AN ALARM AT THE BAS IF THE STATUS OF THE BOILER DOES NOT MATCH IT'S COMMAND VALUE. FACTORY MOUNTED CONTROLS MUST
BE USED TO MAINTAIN THE SUPPLY WATER TEMPERATURE SETPOINT OF 180°F (ADJ).
THE FOLLOWING POINTS MUST BE DISPLAYED ON THE CONTROL GRAPHICS:
BOILER B-2
CONTROL
CABINET
GPMS-HWR-F* SECONDARY HOT WATER RETURN FLOW
B-1-EN OFF ONBOILER 1 ENABLE
B-1-A BOILER 1 ALARM DESCRIPTION
B-2-EN OFF ONBOILER 2 ENABLE
B-2-A BOILER 2 ALARM DESCRIPTION
P-HWS-F
P-HWS-F GPMPRIMARY HOT WATER SUPPLY FLOW
CONTROL POINT NOTES:
1. CONTROL POINTS SHOWN ABOVE IN GREY AND WITH * ARE EXISTING AND MUST REMAIN.
HTG-2-O
NC
HTG-1-O
NO
%HTG-1-O HEATING OUTPUT - VALVE POSITION 1
%HTG-2-O HEATING OUTPUT - VALVE POSITION 2
THE EXISTING DDC SYSTEM MUST BE EXTENDED TO CONTROL NEW EQUIPMENT. TIE THE NEW EQUIPMENT INTO THE BAS VIA BACNET. UPDATE
SYSTEM GRAPHICS TO REFLECT THE SYSTEM MODIFICATIONS.
NOTES:
1. BASIS OF DESIGN IS BELL & GOSSETT. REFER TO SPECIFICATIONS FOR APPROVED EQUALS.
2. PROVIDE WITH ASME CONSTRUCTION.
3. PROVIDE WITH HIGH CAPACITY AIR VENT, AUTOMATIC AIR VENT, PRV, RELIEF VALVE, AND BLOW
DOWN CONNECTION WITH STRAINER.
NOTES:
1. BASIS OF DESIGN IS LOCHINVAR. REFER TO SPECIFICATIONS FOR APPROVED EQUALS.
2. PROVIDE FULL-COLOR 8" TOUCHSCREEN LCD DISPLAY.
3. PROVIDE MODULATING BURNER WITH MINIMUM TURNDOWN OF 10:1
4. PROVIDE ASME STAINLESS STEEL HEAT EXCHANGER.
5. PROVIDE FACTORY STAINLESS STEEL SIDEWALL VENT TERMINATION KIT.
6. PROVIDE WITH CONDENSATE NEUTRALIZATION KIT, LOW WATER CUTOFF W/ MANUAL RESET & TEST.
7. PROVIDE BMS GATEWAY.
8. E.C. TO PROVIDE DISCONNECT.
NOTES:
1. BASIS OF DESIGN IS BELL & GOSSETT. REFER TO SPECIFICATIONS FOR APPROVED
EQUALS.
2. PROVIDE WITH ASME CONSTRUCTION AND HEAVY DUTY BUTYL RUBBER BLADDER.
3. PROVIDE WITH LIFTING RINGS AND CHARGING VALVE CONNECTION.
NOTES:
1. BASIS OF DESIGN IS ARMSTRONG. REFER TO SPECIFICATIONS FOR APPROVED EQUALS.
2. E.C. TO PROVIDE AND INSTALL COMBINATION STARTER/DISCONNECT WITH THERMAL OVERLOAD PROTECTION.
3. PROVIDE WITH SUCTION DIFFUSER.
4. PROVIDE WITH RELIEF VALVE, AUTOMATIC AIR VENT, HIGH CAPACITY AIR VENT, PRESSURE REDUCING VALVE.
NOTES:
1. BASIS OF DESIGN IS UV RESOURCES. THE FOLLOWING ARE APPROVED EQUALS: STERILE-AIRE, AMERICAN ULTRAVIOLET
2. ENABLE THE UV-LIGHTS WHEN THE SUPPLY FANS IN THEIR RESPECTIVE AHU ARE ENABLED.
NOTE:
THE EMERGENCY STOP SWITCH (ESS) IS PROVIDED AND INSTALLED BY THE CONTROLS CONTRACTOR.
SEQUENCE: IF AN ESS IS ACTIVATED, THE BOILERS MUST SHUT DOWN AND AN ALARM MUST BE
GENERATED TO THE BAS.
EMERGENCY STOP SWITCH SEQUENCE OF OPERATIONS
C O N S U L T I N G E N G I N E E R S
413 DALTON AVENUE, SUITE A
CHARLOTTE, NC 28206 • 704-295-4263
NC LICENSE NO.: F-1533
AME PROJECT NO.:
Y S T A N D A R D
A C A D
B L O C K S T
IT
L E
B L O C K
IN
F O N e w
T B x .d w g
:2 :1
A M
B ri a n
E lb e rt s o n
Drawing No.
Drawing Title
Issues / Revisions
Checked by
Seals
Drawn by
Scale
Job No.
Drawing Info
AS SHOWN
24064
Project
24064
Issue Date
FINAL REVIEW
SET
SCO #25-29532-01A
MECHANICAL -
CONTROLS &
SCHEDULES
GASTON COLLEGE
ROBINSON CLASSROOM
BUILDING HEATING HOT
WATER UPGRADES
250 LIBRARY LN, DALLAS, NC 28035
M6.1
FFR
NJH
11/07/2025
BOILER SCHEDULE
MARK MANUFACTURER MODEL TYPE FUEL TYPE
INPUT
(MBH)
OUTPUT
(MBH)
EFFICIENCY
MIN. FLOW
(GPM)
MAX FLOW
(GPM)
DESIGN FLOW
(GPM)
PD
(FT. W.G.)
EWT
(°F)
LWT
(°F)
VOLUME
(GAL.)
GAS
(IN.)
COMBUSTION AIR
INLET (IN.)
FLUE GAS VENT
(IN.)
VOLT/
PHASE
APPROX.
WEIGHT (LB)
NOTES
B-1 LOCHINVAR FCB1500 CONDENSING FIRE TUBE NATURAL GAS 1,500 1,443 96.2 25 350 53 7.3 140 180 94 4-14 8 8 120 / 1 2,345 ALL
B-2 LOCHINVAR FCB1500 CONDENSING FIRE TUBE NATURAL GAS 1,500 1,443 96.2 25 350 53 7.3 140 180 94 4-14 8 8 120 / 1 2,345 ALL
PUMP SCHEDULE
MARK MANUFACTURER MODEL TYPE
FLOW
(GPM)
FRICTION HEAD
(FT. W.G.)
MOTOR
(HP)
VOLT / PHASE
APPROX.
WEIGHT (LB)
NOTES
HHWP-1 ARMSTRONG
SERIES DESIGN ENVELOPE
SENSORLESS 4380 1503
INLINE 53 31 1 460 / 3 54 ALL
AIR SEPARATOR SCHEDULE
MARK MANUFACTURER MODEL SYSTEM
FLOW
(GPM)
PD
(FT. W.G.)
NOTES
AS-1 BELL & GOSSETT CRSN-2F
HEATING HOT
WATER
53 1.2 ALL
EXPANSION TANK SCHEDULE
MARK MANUFACTURER MODEL
DIAMETER
(IN)
ACCEPTABLE
VOLUME (GAL)
NOTES
ET-1 BELL & GOSSETT B130 20 13.4 ALL
UV LIGHTING SCHEDULE
MARK
ASSOCIATED
EQUIPMENT
MANUFACTURER MODEL
PLENUM
DIMENSIONS
COIL
DIMENSIONS
LAMPS PER
ROW
NUMBER OF
ROWS
ELECTRICAL DATA
NOTES
VOLTAGE
WATTS PER
LAMP
TOTAL
POWER (W)
UV-1 AHU-1 UV RESOURCES RLM XTREME 56" X 78" 55" X 77" 2 2 120 145 740 ALL
UV-2 AHU-2 UV RESOURCES RLM XTREME 56" X 78" 55" X 77" 2 2 120 145 740 ALL
UV-3 AHU-3 UV RESOURCES RLM XTREME 56" X 91" 55" X 90" 2 2 120 145 740 ALL
NOTE: FOR ANGLE SIZE AND HANGER STRAP GAUGE, SEE
SMACNA LOW PRESSURE DUCT CONSTRUCTION STANDARDS.
SECURE TO BOTTOM
AND SIDES OF DUCT
WITH SHEET METAL
SCREWS
NUT WITH WASHER
(TYPICAL)
METAL HANGER STRAP
STEEL ANGLE
TO STRUCTURE
THREADED ROD
(TYPICAL)
HANGER
LOAD
RATED
FASTENERS
<=24" <=36"
SECURE
WIRE
<=10"
HANGERS,
RODS, WIRES,
OR STRAPSTO STRUCTURE
BAND
4" CONCRETE
HOUSEKEEPING PAD
6X6 WOVEN
WIRE MESH
DOWEL INTO
BUILDING SLAB
(TYPICAL)
CONCRETE FLOOR SLAB
NOTES:
1. ALL CONCRETE PADS MUST BE THE SIZE OF THE EQUIPMENT FOOTPRINT PLUS 6"
ON ALL SIDES.
2. SEISMIC RESTRAINT REQUIREMENTS MAY ALTER - REFER TO SPECIFICATIONS.
45° CHAMFER
GAUGE ISOLATION
VALVE (BALL VALVE)
BALL
VALVE
STRAINER WITH BLOWDOWN
VALVE AND HOSE ADAPTER
NOTES:
1. INSTALL DIFFERENT PRESSURE SWITCH ON EACH PUMP CONNECTED TO THE DDC
SYSTEM TO ALLOW PUMP OPERATION TO BE MONITORED.
2. PROVIDE DIELECTRIC FITTINGS BETWEEN DISSIMILAR METALS.
3. DO NOT LOCATE PUMPS OVER BOILERS OR BURNERS.
INLINE
PUMP
TRIPLE
DUTY
VALVE
PRESSURE GAUGE - SELECT
RANGE TO SUIT PUMP HEAD
(TYPICAL)
FLEXIBLE
CONNTECTOR
(TYP.)
INLINE PUMP MOTOR TO BE
INSTALLED VERTICALLY
CLAMP MUST BE LOCATED
MAXIMUM OF 3" FROM JOIST PANEL
POINT. IF NOT PROVIDE VERTICAL
ANGLE IRON SUPPORT FRONT AND
BACK TO STRENGTHEN.
B-LINE OR EQUAL TOP BEAM
CLAMP (USE ONLY ON LEVEL
JOIST MEMBERS).
B-LINE B3100 OR EQUAL
CLEVIS HANGER.
PIPE INSULATION. REFER TO
SPECIFICATIONS FOR DETAILS.
PIPING REFER TO
SPECIFICATION
FOR DETAILS
B-LINE B3151 OR EQUAL
SHEET METAL
INSULATION SHIELD
NOTES:
1. PIPE HANGER SPACING MUST BE IN ACCORDANCE WITH THE LATEST ADOPTED VERSION OF
THE NORTH CAROLINA MECHANICAL CODE.
2. PROVIDE UNISTRUT OR ANGLE IRON BRIDGING SPANNING MULTIPLE BAR JOIST AS REQUIRED.
3. PRIME OR PAINT ALL HANGERS, PIPE WELDS, AND OTHER ITEMS SUBJECT TO RUSTING.
TYPICAL WATER
PIPING
REDUCER, IF
REQUIRED
3/4" GATE VALVE
ADAPTER TO 3/4" HOSE
THREAD - PROVIDE
HOSE CAP NUT
ELEVATION
THREADED PIPING
ELEVATION
WELDED PIPING
NOTE:
DRAIN ALL LOW POINTS AS INDICATED ABOVE.
6" DIRT LEG
(FULL SIZE)
AGA
APPROVED
FLEXIBLE
CONNECTOR
GAS
COCK
GAS
EQUIPMENT
GAS MAIN
(SEE SIZE
ON PLANS)
SIZE TO EQUIPMENT
CONNECTION
PRESSURE
REGULATOR
FLOOR
MANUFACTURER
PROVIDED
GAS TRAIN
PRESSURE RELIEF
VALVE
(30 P.S.I.)
GAS VENT
HOT
WATER
RETURN
DRAIN VALVE
REFER TO CONDENSATE DRAIN DETAIL
GAS
SUPPLY
RELIEF PIPE TO FLOOR DRAIN
ANY ANGLE
THERMOMETER
(0-250 RANGE)
(TYP)
4" HIGH CONCRETE PAD
(VERIFY WITH EQUIPMENT
PROVIDE)
CHECK VALVEY-STRAINER (TYP)
HOT WATER
SUPPLY
2-WAY CONTROL VALVE
EXISTING
FLOOR
DRAIN.
VACUUM BREAK
NEUTRALIZER KIT,
3" MIN. BELOW
CONDENSATE
TRAP.
CONDENSATE
TRAP, SAME
LEVEL OR
BELOW BOILER
BASE.
BOILER
EQUIPMENT
PAD
6"
DIRT LEG
STEAM SUPPLY
THERMOSTATIC
AIR VENT
CONDENSATE RETURN
STRAINER
1/2" BLOWDOWN VALVE
GATE
VALVE
(TYPICAL)
CHECK VALVE REQUIRED ONLY
IF RETURN IS ABOVE TRAP
UNION (TYPICAL)
1/2" BUCKET TRAP
12"
(MINIMUM)
CONDENSATE RETURN
15"
NOTES:
1. REFER TO DUCT HANGER DETAIL FOR HANGER REQUIREMENTS.
MECHANICAL ROOM WALL
TO STRUCTUREB-1 INTAKE DUCT
B-2 INTAKE DUCT
B-1 VENT DUCT
B-2 VENT DUCT
STRUT CLAMP
(TYP.)
2' 0"
NOTES:
1. INSTALL EMERGENCY STOP SWITCH IN A LISTED, METALLIC SINGLE GANG JUNCTION
BOX IMMEDIATELY ADJACENT TO THE THERMOSTAT. THE CLEARANCE BETWEEN
THE BOX AND SHEETROCK MUST NOTEXCEED 1/8".
2. PROVIDE UL 'WALL OPENING PROTECTIVE MATERIALS" SYSTEM CLIV IN EACH NEW
JUNCTION BOX. USE METACAULK BOX GUARD INSERT. INSTALL IN ACCORDANCE
WITH THE UL LISTING.
3. MOUNT SWITCH 48" ABOVE FINISHED FLOOR.
DURABLE LABEL
ON WALL ABOVE
STOP SWITCH
STI MODEL STI-13000
NC (OR EQUAL)
POLYCARBONATE
COVER
SWITCH PLATE WITH
ONE 30MM
DIAMETER HOLE.
EATON PUSH BUTTON
STOP SWITCH MODEL
10250T (OR EQUAL).
LIFT HERE
EMERGENCY GAS SHUTOFF
COMBUSTION
AIR DISCHARGE
DUCT INTO
BUILDING
EXISTING EGRESS
DOOR
EXISTING ROLL-UIP DOOR TO MECHANICAL ROOM
BOILER INTAKE
DUCT INTO
BUIDLING
OFFSET COMBUSTION AIR DUCTWORK
FROM WINDOW ABOVE AND INSTALL THE
DUCT WORK ABOVE THE INTAKE DUCTS
PROVIDE INTAKE FITTING
PER MANUFACTURER'S
REQUIREMENTS
PROVIDE COMBUSTION AIR
DISCHARGE FITTING PER
MANUFACTURER'S
REQUIREMENTS
DUCT INTO
BUILDING
LIBRARY LANE DRIVE GRADE
SERVICE ALLEY
EXISTING
RETAINING WALL
4FT7FT
C O N S U L T I N G E N G I N E E R S
413 DALTON AVENUE, SUITE A
CHARLOTTE, NC 28206 • 704-295-4263
NC LICENSE NO.: F-1533
AME PROJECT NO.:
Y S T A N D A R D
A C A D
B L O C K S T
IT
L E
B L O C K
IN
F O N e w
T B x .d w g
:2 :1
A M
B ri a n
E lb e rt s o n
Drawing No.
Drawing Title
Issues / Revisions
Checked by
Seals
Drawn by
Scale
Job No.
Drawing Info
AS SHOWN
24064
Project
24064
Issue Date
FINAL REVIEW
SET
SCO #25-29532-01A
MECHANICAL -
DETAILS
GASTON COLLEGE
ROBINSON CLASSROOM
BUILDING HEATING HOT
WATER UPGRADES
250 LIBRARY LN, DALLAS, NC 28035
M7.1
FFR
NJH
11/07/2025
NTS
DUCT SUPPORT DETAIL
NTS
INDOOR EQUIPMENT PAD DETAIL
NTS
INLINE PUMP INSTALLATION DETAIL
NTS
PIPE HANGER DETAIL - INDIVIDUAL
NTS
PIPING DRAIN VALVE CONNECTION DETAIL
NTS
EQUIPMENT GAS PIPING CONNECTION DETAIL
NTS
GAS FIRED BOILER PIPING DETAIL
NTS
BOILER CONDENSATE DRAIN DETAIL
NTS
END OF MAIN STEAM TRAP DETAIL
NTS
BOILER INTAKE AND VENT DUCTWORK SUPPORT DETAIL
NTS
HVAC EMERGENCY STOP SWITCH DETAIL
NTS
BOILER EXHAUST EXTERIOR DUCT ROUTING DETAIL
MAXIMUM LENGTH FROM METER TO EQUIPMENT: 125'
2018 NORTH CAROLINA FUEL GAS CODE
TABLE 402.4(5) SCH 40 METALLIC PIPE
INLET PRESSURE 2 P.S.I.
FIRST FLOOR
B-1
1,500 MBTU
1" NG
GAS METER LOCATED ON
THE EXTRIOR OF THE
BUILDING NEXT TO THE
ENTRY WAY STAIRWELL.
1" @ 2 P.S.I.
79 FT EPL - 1,500 MBTU
GAS PRESSURE
REDUCING
REGULATOR
(2 P.S.I. TO 0.5 P.S.I.)
(TYPICAL)
B-2
1,500 MBTU
1" NG
EXTERIOR - ON GRADE
NOTE:
PROVIDE DIELECTRIC FITTINGS BETWEEN DISSIMILAR METALS
SYSTEM CONNECTION
(CONNECT TO SIDE OR
BOTTOM OF MAIN
HEADER)
REDUCER
TO DRAIN
HIGH
CAPACITY
VENT
AIR SEPARATOR
PRESSURE REDUCING VALVE
GLOBE VALVE
AS-1
AIR CHARGING VALVE
(PRESSURIZE DRY TANK
EQUAL TO FILL VALVE
PRESSURE)
ET-1
DRAIN VALVE W/
HOSE CONNECTION
PROVIDE VALVE IN
ACCESIBLE
LOCATION FROM THE
FLOOR
LOW CAPACITY AIR
VENT B&G NO. 87
EXPANSION TANK
PRESSURE GAUGE W/
NEEDLE VALVE
H W
S
2 1/2" HWS2 1/2" HWS2 1/2" HWS
2 1/2" HWS
1" DOMESTIC COLD WATER
MAKE-UP LINE BY P.C. TIE INTO
EXISTING MAKE-UP WATER LINE
TS
TS TS
FSFS
AFAF
BOILER
B-1
BOILER
B-2
H W
S
/2
H W
S
T&P RELIEF VALVE
BY BOILER MFGR.
RUN FULL SIZE LINE
TO FLOOR
(TYPICAL)
2 1/2" HWS
2 1/2" HWR
/2
2 1/2" HWR
2 1/2" HWR
TO EXISTING HEATING
HOT WATER
SECONDARY PUMPS:
P-1 & P-2
2 1/2" HWS
2 1/2" HWR
HEATING HOT
WATER PRIMARY
PUMP: HHWP-1
REFER TO DETAIL ON
SHEET M7.1 FOR INLINE
PUMP DETAIL
/2
H W
R
MECH ROOM FLOOR
/2
H W
R
EXISTING TO REMAIN NEW CONSTRUCTION SCOPE
PROVIDE VALVE
IN ACCESIBLE
LOCATION FROM
FLOOR
NTS
NATURAL GAS RISER DIAGRAM
C O N S U L T I N G E N G I N E E R S
413 DALTON AVENUE, SUITE A
CHARLOTTE, NC 28206 • 704-295-4263
NC LICENSE NO.: F-1533
AME PROJECT NO.:
Y S T A N D A R D
A C A D
B L O C K S T
IT
L E
B L O C K
IN
F O N e w
T B x .d w g
:2 :1
A M
B ri a n
E lb e rt s o n
Drawing No.
Drawing Title
Issues / Revisions
Checked by
Seals
Drawn by
Scale
Job No.
Drawing Info
AS SHOWN
24064
Project
24064
Issue Date
FINAL REVIEW
SET
SCO #25-29532-01A
MECHANICAL - PIPING
DIAGRAMS
GASTON COLLEGE
ROBINSON CLASSROOM
BUILDING HEATING HOT
WATER UPGRADES
250 LIBRARY LN, DALLAS, NC 28035
M7.2
FFR
NJH
11/07/2025
NTS
HEATING HOT WATER PIPING DIAGRAM
ABBREVIATIONS
DESCRIPTIONTYPE
A
AC
AF
AFC
AFF
AFG
BFC
C
EF
EC
ETBD
ETR
ETBR
EWC
FA
FAAP
FACP
AMPERE
ALTERNATING CURRENT
AMPERE FRAME
ABOVE FINISHED COUNTER
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
BELOW FINISHED CEILING
CONDUIT
EXHAUST FAN
ELECTRICAL CONTRACTOR
G OR GND
GF OR GFI
KVA
KW
EXISTING TO BE DEMOLISHED
EXISTING TO REMAIN
EXISTING TO BE RELOCATED
ELECTRIC WATER COOLER
FIRE ALARM
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
GROUND
GROUND FAULT INTERRUPTER
KILOVOLT AMPERES
KILOWATTS
AIC AMPERE INTERRUPTING CURRENT
AMP AMPERE
ARA AREA OF RESCUE ASSISTANCE
AT AMPERE TRIP
AWG AMERICAN WIRE GAUGE
CCT CIRCUIT
CCT BRKR CIRCUIT BREAKER
CR CARD READER
CT CURRENT TRANSFORMER
FPN FUSE/TRIP PER NAMEPLATE
FVNR FULL VOLTAGE NON-REVERSING
HID HIGH INTENSITY DISCHARGE
HOA HAND OFF AUTO
IG ISOLATED GROUND
INTERCOM INTERCOMMUNICATION
J-BOX JUNCTION BOX
GC GENERAL CONTRACTOR
CLG CEILING
GEN GENERATOR
ATS AUTOMATIC TRANSFER SWITCH
BET BUILDING ENTRANCE TERMINAL
MCB
MLO
NEC
Ø OR PH
R
REF
RTU
UON
V
W
WP
MAIN CIRCUIT BREAKER
MAIN LUG ONLY
PHASE
RELOCATED DEVICE
REFRIGERATOR
ROOFTOP UNIT
UNLESS OTHERWISE NOTED
VOLT(S)
WATTS OR WIRE
WEATHERPROOF
P POLE
MCC MOTOR CONTROL CENTER
MD MOTION DETECTOR
MIC MICROPHONE
MOCP MAXIMUM OVERCURRENT PROTECTION
NATIONAL ELECTRICAL CODE
N OR NEUT NEUTRAL
NTS NOT TO SCALE
OC ON CENTER
OL OVERLOAD
PA PUBLIC ADDRESS
PB PUSHBUTTON SWITCH
PNL PANELBOARD
RVNR REDUCED VOLTAGE NON-REVERSING
SPD SURGE PROTECTION DEVICE
SWBD SWITCHBOARD
TTB TELEPHONE TERMINAL BOARD
TC TIME CLOCK
TS TIME SWITCH
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VFD VARIABLE FREQUENCY DRIVE
VSD VARIABLE SPEED DRIVE
XFMR TRANSFORMER
Z IMPEDANCE
WG WIRE GUARD
PC PLUMBING CONTRACTOR
SPKR SPEAKER
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPACITY
SOG SLAB ON GRADE
LV LOW VOLTAGE
MSB MAIN SWITCH BOARD
NIC NOT IN CONTRACT
ABBREVIATIONS
DESCRIPTIONTYPE
IM ICE MAKER
MW MICROWAVE
A. ALL WORK MUST CONFORM TO THE LATEST NFPA, 2020 NATIONAL ELECTRICAL CODE,
THE LATEST STATE CODE, & THE LATEST LOCAL AUTHORITY REQUIREMENTS.
B. THE CONTRACTOR MUST VISIT THE PREMISES AND THOROUGHLY FAMILIARIZE
THEMSELVES WITH ALL DETAILS OF THE WORK AND WORKING CONDITIONS. VERIFY ALL
FIELD CONDITIONS INCLUDING LOCATION OF UTILITY LINES, STRUCTURES, AND ADVISE
THE ENGINEER OF ANY DISCREPANCY THAT MAY PREVENT OR HINDER THE SPECIFIED
WORK FROM BEING COMPLETED.
C. THE CONTRACTOR MUST STUDY THE STRUCTURE AND FINISH CONDITIONS AFFECTING
THEIR WORK AND MUST COORDINATE THEIR WORK ACCORDINGLY. THE CONTRACTOR
MUST PROVIDE ALL ACCESSORIES, HANGERS, AND ANCHORS AS NECESSARY TO MEET
SUCH CONDITIONS WITHOUT ANY ADDITIONAL COST TO THE OWNER.
D. PRIOR TO ACCOMPLISHING ANY WORK IN ANY AREA, ALL WORK MUST BE PLANNED AND
COORDINATED WITH OTHER TRADES AND THE OWNER. THE CONDUIT ROUTING MUST
BE COORDINATED WITH DUCT WORK, AND OTHER OBSTACLES SO AS TO PROVIDE THE
MOST EFFICIENT AND AESTHETICALLY PLEASING INSTALLATION.
E. PROPERLY SUPPORT ALL WORK AND EQUIPMENT INSTALLED UNDER THIS CONTRACT.
STUDY ALL DRAWINGS, MANUFACTURER'S INSTRUCTIONS, UL LISTINGS, AND CATALOG
DATA TO DETERMINE HOW EQUIPMENT, ACCESSORIES, AND RELATED ITEMS ARE TO BE
SUPPORTED, MOUNTED, OR SUSPENDED. PROVIDE ALL BOLTS, INSERTS, BRACKETS,
SPACERS, STRUCTURAL SUPPORTS, AND ACCESSORIES FOR PROPER SUPPORT OF
EQUIPMENT FURNISHED UNDER THIS CONTRACT.
F. PROVIDE GREEN EQUIPMENT GROUNDING CONDUCTOR WITH ALL FEEDER AND BRANCH
CIRCUITS.
G. MOUNTING HEIGHTS INDICATED ARE TO THE CENTER OF THE DEVICE, OR EQUIPMENT
UNLESS NOTED OTHERWISE. CONTRACTOR MUST NOT INSTALL J-BOXES, OUTLETS,
DEVICES, ETC. BACK TO BACK FOR NEW OR RENOVATION WORK.
H. DO NOT SCALE THESE PLANS.
I. COORDINATE MOUNTING HEIGHT AND LOCATION OF ALL WALL MOUNTED EQUIPMENT
WITH ARCHITECTURAL ELEVATIONS.
J. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. THE ELECTRICAL INSTALLATION MUST
BE FULLY COORDINATED WITH ALL OTHER TRADES PRIOR TO ROUGH-IN BETWEEN THE
ELECTRICAL WIRING AND DEVICES AND MECHANICAL WORK.
K. RECEPTACLES LOCATED WITHIN 6'-0" OF A WATER SOURCE MUST BE GFI TYPE.
L. INSPECTION MUST BE COMPLETED BY THE SCO ELECTRICAL INSPECTOR. CONTRACTOR
MUST COORDINATE ALL INSPECTIONS WITH THE SCO INSPECTOR. INSPECTIONS MUST
BE COMPLETED MONDAY THROUGH FRIDAY BETWEEN 8AM AND 5PM.
GENERAL NOTES
ELECTRICAL ENERGY CODE SUMMARY
(2018 NC ENERGY CODE)
ELECTRICAL SYSTEM AND EQUIPMENT:
METHOD OF COMPLIANCE: N/A
STATE ENERGY CODE: (X) PRESCRIPTIVE ( ) PERFORMANCE
LUMINAIRE SCHEDULE:
LAMP TYPE REQUIRED IN LUMINAIRE
NUMBER OF LAMPS IN LUMINAIRE
BALLAST TYPE USED IN THE LUMINAIRE
NUMBER OF BALLASTS IN LUMINAIRE
TOTAL WATTAGE PER LUMINAIRE
TOTAL INTERIOR WATTAGE ALLOWED VS. SPECIFIED
EXTERIOR LIGHTING ZONE
TOTAL EXTERIOR WATTAGE ALLOWED VS. SPECIFIED
EXTERIOR LUMINAIRES >100 WATTS MUST HAVE A
MINIMUM EFFICACY OF 60 LUMENS/WATT
PROJECT TOTAL SQUARE FOOTAGE:
STATE ENERGY CODE ADDITIONAL PRESCRIPTIVE COMPLIANCE SUMMARY:
MUST COMPLY WITH ONE OF THE FOLLOWING SECTIONS:
( ) 506.2.1 MORE EFFICIENT MECHANICAL EQUIPMENT
( ) 506.2.2 REDUCED LIGHTING POWER DENSITY
( ) 506.2.3 ENERGY RECOVERY VENTILATION SYSTEMS
( ) 506.2.4 HIGHER EFFICIENCY SERVICE WATER HEATING
( ) 506.2.5 ON-SITE SUPPLY OF RENEWABLE ENERGY
( ) 506.2.6 AUTOMATIC DAYLIGHTING CONTROL SYSTEM
CALCULATION ABOVE INCLUDES REDUCED LIGHTING POWER DENSITY
**NO NEW LIGHTING IS PROVIDED IN THIS PROJECT. **
N/A N/A N/A N/A N/A
N/A VS N/A
N/A
N/A VS N/A
1936.99 SQFT
TYPE DESCRIPTION
DUPLEX CONVENIENCE RECEPTACLE, 20A, 120V, MOUNT 18" AFF, UON. SUBSCRIPT 'GFI' DENOTES GROUND FAULT
INTERRUPTING TYPE RECEPTACLE.
EXISTING JUNCTION BOX
SWITCH, 20A, 120/277V, REFERENCE NEW WORK PLAN FOR LOCATION.
NO SUBSCRIPT DENOTES SINGLE POLE SWITCH.
JJ
EQUIPMENT CONNECTION, AS NOTED. REFER TO EQUIPMENT CONNECTION SCHEDULE.
XXX
EXISTING SURFACE MOUNTED PANELBOARD
DESIGNATION AS NOTED. REFER TO PANEL
SCHEDULES FOR ADDITIONAL INFORMATION.
T EXISTING PAD MOUNTED TRANSFORMER. REFER TO RISER DIAGRAM FOR ADDITIONAL
INFORMATION.
SPD EXISTING SURGE PROTECTION DEVICE WALL MOUNTED ADJACENT TO EQUIPMENT BEING
PROTECTED. 'TVSS' DENOTES TRANSIENT VOLTAGE SURGE SUPPRESSION DEVICE AND CAN
BE USED INTERCHANGEABLY WITH 'SPD.'
SYMBOL LEGEND
(NOTE: NOT ALL SYMBOLS ARE NECESSARILY USED ON PLANS)
EXISTING FIRE ALARM CONTROL PANEL
FACP
EXISTING FIRE ALARM MANUAL PULL STATION
EXISTING FIRE ALARM SYSTEM CEILING MOUNTED SMOKE DETECTORSD
F
EQ
GFI
EXISTING FIRE ALARM AUDIO/VISUAL APPLIANCE, WALL MOUNTEDF
LIGHTING CONTROL SYSTEM, LOCAL DUAL TECHNOLOGY OCCUPANCY SENSOR, CEILING MOUNTED AT 96" AFF TO UNISTRUT SUSPENDED FROM EXISTING STRUCTURE. PROVIDE POWER PACK AND WIRING AS REQUIRED. PROVIDE AND INSTALL PER
MANUFACTURER'S RECOMMENDATIONS.
OS
TWO SWITCHES IN COMMON BOX AND COMMON FACEPLATE. REFERENCE NEW WORK PLAN FOR LOCATION.
SEISMIC AND WIND REQUIREMENTS
FOR ELECTRICAL SYSTEMS
INFORMATION FOR NCSBC 2018/ASCE 7-10
A. SEE EQUIPMENT SCHEDULES AND DETAILS FOR SPECIFIC COMPONENT IMPORTANCE FACTOR
DESIGNATIONS.
A. USE APPLICABLE TABLE BELOW TO DETERMINE SEISMIC RESTRAINT REQUIREMENTS FOR EACH
ELECTRICAL COMPONENT.
B. FOR ALL COMPONENTS REQUIRING SEISMIC RESTRAINT, THE COMPONENT SUPPORTS AND
ATTACHMENTS MUST BE DESIGNED BY A REGISTERED DESIGN PROFESSIONAL.
C. WHERE SEISMIC RESTRAINT IS REQUIRED, HOUSEKEEPING PADS NEEDED FOR THE INSTALLATION OF EQUIPMENT UNDER THIS CONTRACT MUST BE DESIGNED BY THE SEISMIC ENGINEER. DO NOT
POUR ANY HOUSEKEEPING PADS PRIOR TO THE RECEIPT OF THE SEISMIC SUBMITTAL.
D. SEISMIC RESTRAINT FOR CONDUIT MUST BE SHOWN ON LAYOUT DRAWINGS SHOWING SPECIFIC
RESTRAINT LOCATIONS ALONG WITH ACCOMPANYING DETAILS AND CALCULATIONS.
COMPONENT
CERTIFICATION
NOT REQUIRED
NOT REQUIRED
NOT REQUIREDCOMPONENT SUPPORTS
WALL MOUNTED
COMPONENT
IDENTIFICATION
SEISMIC
RESTRAINT
REQUIREMENT
ASCE 7-10
REFERENCE
1.0
COMPONENT IMPORTANCE FACTOR (Ip)
SEISMIC DESIGN CATEGORIES C
NOT REQUIREDSUSPENDED EQUIPMENT
TRAPEZED CONDUIT NOT REQUIRED
SINGLE CONDUIT NOT REQUIRED
REQUIRED
SEISMIC
RESTRAINT
REQUIREMENT
ASCE 7-10
REFERENCE
>2"
(SEE NOTE 1)
1.5
13.1.4.3
13.1.4.3
13.1.4.3
13.1.4.3
13.1.4.3
13.2.2
13.6.5
13.1.4.3
13.1.4.3
13.6.8.2b
13.2.2
GENERAL NOTES:
A. RESTRAINT IS NOT REQUIRED IF SUSPENDED 12 IN. OR LESS FROM THE STRUCTURE, IF THE
HANGERS ARE DETAILED TO AVOID SIGNIFICANT BENDING OF THE HANGERS AND THEIR
ATTACHMENTS, AND IF PROVISIONS ARE MADE FOR CONDUIT TO ACCOMMODATE EXPECTED
DEFLECTIONS.
B. COMPONENT CERTIFICATION MUST BE SUPPLIED BY THE EQUIPMENT MANUFACTURERS AT TIME OF
SUBMITTAL FOR REVIEW BY ENGINEER OF RECORD.
TC-8-CH13-48-R8
13.6.8.3.1
RESTRAIN IF ANY
CONDUIT ON TRAPEZE
>2" RESTRAIN IF
TOTAL WEIGHT OF
CONDUIT ON TRAPEZE
> 10 LBS/FT
(SEE NOTE 1)
RESTRAIN ALL
RESTRAIN ALL
RESTRAIN ALL
480V, 3Ø
FED FROM
AHU-X
AHU-X
1/2" HIGH LETTERING FOR
EQUIPMENT NAME
1/4" HIGH LETTERING FOR
REMAINING TEXT
EQUIPMENT NAME
1/8" THICK WHITE PLASTIC WITH BLACK
LETTERS PER SPECIFICATIONS
480V, 3Ø
FED FROM
EQUIPMENT VOLTAGE
FASTEN WITH BRASS SCREWS
EQUIPMENT SOURCE
(PANEL & CIRCUIT)
SYSTEM NO. C-AJ-1001
MAX…