Text version
ATTACHMENT FOR ELECTRICAL CONNECTIONS
Pressure Tank at House on Hill Pressure tank to be located in the garage at the top of the hill. Homeowner will cut hole in concrete floor and install a conduit for the water service line coming into the tank and out to the home.
• Well-X-Trol Stand Tank (Any pressure tank meeting these specifications can be used)
• WX-251 (145S10), 62 Gal Well-X-Trol Well Tank (Stand)
• 62 Gallons
• 1 ¼” connection
• Max Pressure 150 PSI
• 46-3/4” height
• 22” Diameter
• Precharged PSI: 38 psi
Booster Pump (Operating at 230V) Grainger Multi-Stage Booster Pump: 8 Stages – Pumps, ½ hp-Pumps, 115/230V AC, Cast Iron Model 45MW67 (Any booster pump meeting these specifications can be used)
• ½ hp, 115/230V @ 60 Hz, 8 stages, single phase
• Pressure 120 PSI Max
• Max case pressure 300 PSI
• Connection inlet & outlets ¾” NPT (F)
• Flow 5.7 GPM at 60 PSI
• Length 22 5/8”
• Height 8 ¾”
Pressure Switch at Pressure Tank at House on Hill 40/60 (starts pumping at 40 psi and stops pumping at 60 psi) UF 14 gauge cable 2 conductor (Length 1300 LF) Direct burial Connects to Pump Control Box at Pump House
Breaker Box at House on Hill to Pump House 40 Amp Breaker
Options:
6 gauge AWG aluminum cable 3 conductors – Direct burial (Length 1300 LF) Or UF 8 gauge copper cable 3 conductors -- Direct burial (Length 1300 LF)
Pump House 40 Amp Breaker Box with Main Disconnect 8-12 circuits Connect the 6 gauge or 8 gauge cable from house on hill
• Two pole (230V) 20 Amp breaker for pump, 12 gauge cable to Pump Control Box
• Breaker for convenience outlet 15A 115V
• Overhead Light with switch by door
• Two Pole (230V) 30 Amp breaker for Heater (w/thermostat)
Pump Control Box 12 gauge cable from Pump House Breaker Box to Pump Control Box
• Contactor rated 230V/20 Amp or greater
• Provision for termination of incoming conductors including control from pressure switch
• 12 gauge cable to Pump Motor (230V)