241216_Combined_CHCF_Skid_Schematic.pdf

PDF 1 MB Posted

Attached to
CHCF WATER TREATMENT SKID SYSTEMS
Solicitation number
0000034843
Issued by
San Joaquin County, Stockton City, California

About this file

This draft engineering document depicts detailed mechanical room modifications and skid schematics for the California Department of Corrections and Rehabilitation (CDCR) at the California Health Care Facility located in Stockton, CA. The project involves implementing supplemental chlorination and hyperchlorination systems, which includes installing new equipment such as chemical metering pumps, chlorine analyzers, controllers, and associated piping modifications. The proposed modifications include new injection points, monitoring points, bypass configurations, and portable skid-mounted equipment designed to be wheeled in and out of mechanical rooms.

The technical drawings outline specific requirements for two primary skid systems: a Supplemental Chlorination Skid and a Hyperchlorination Skid, each approximately 49 inches wide and 30 inches maximum height. Both skids are specified to be portable with locking, tamper-proof, and splash-proof enclosures, and include features like calibration columns, pressure relief valves, ball valves, strainers, and power distribution components. The design emphasizes flexibility, with connection points for additional external pumps and the ability to be easily moved within institutional equipment rooms. The draft documents are marked with "DRAFT" watermarks and appear to be part of a detailed engineering design phase for infrastructure improvements at the correctional healthcare facility.

View the file

Other files

File Type Posted
FPCM-CHCF-SKID_SYSTEMS-RS.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRAFT

HYPERCHLORINATION MIXING VALVE BYPASS AND SUPPLEMENTAL

CHLORINATION INJECTION & MONITORING MODIFICATIONS

SEE DETAIL A ON EXHIBIT A PAGE 2

HYPERCHLORINATION MODIFICATIONS

SEE DETAIL B ON EXHIBIT A PAGE 2

MIXING VALVE

ASSEMBLY

PROPOSED SUPPLEMENTAL

CHLORINATION INJECTION POINT

PROPOSED SUPPLEMENTAL CHLORINATION MONITORING POINT

DOMESTIC WATER HEATER DOMESTIC WATER HEATER

(N) NORMALLY OPEN

2" FLOOD SWITCH

(N) CHEMICAL METERING PUMP

(N) CHLORINE

ANALYZER &

CONTROLLER

5' MIN

CL

(N) SUPPLEMENTAL

CHLORINATION SKID

EXHIBIT NO.DRAWING SCALE

www.ksninc.com

711 N. Pershing Avenue Stockton, CA 95203

209-946-0268

916-403-5900

1550 Harbor Blvd., Suite 212 West Sacramento, CA 95691 1"½"0

ORIGINAL DRAWING SCALE PAGE NO.

A

CDCR

TYPICAL MECHANICAL ROOM PLAN VIEW

CALIFORNIA HEALTH CARE FACILITY

STOCKTON, CA

NTS

(E )H

OT

W

AT

ER

RE

TU

RN

(E) MIXING VALVE

(E) BALL VALVE

(TYP)

(E) MIXING VALVE

BYPASS

(E )D

OM

ES

TI

C

HO

TW

AT

ER

LIN

E

(E )D

OM

ES

TI

C

HO

TW

AT

ER

LIN

E

(E) TEE

(TYP)

(N) BALL VALVE

(TYP)

(N) TEE

(TYP)

(N) 90° ELBOW

(E) PRESSURE GAUGE

(E )D

OM

ES

TI

C

CO

LD

W

AT

ER

DETAIL A

5'

MI

N

(E) CHECK VALVE

(TYP)

PROPOSED CHLORINATION

MONITORING POINT

(SEE SUPPLEMENTAL CHLORINATION SKID IN EXHIBIT B)

PROPOSED SUPPLEMENTAL CHLORINATION

INJECTION POINT

(N) 2" TEE W/ FEMALE BUSHING (3/8") W/ 3/8"

COMPRESSION FITTING CONNECTOR

(N )C

HE

MI

CA

L

ME

TE

RI

NG

PU

MP

(N )C

HL

OR

IN

E

AN

AL

YZ

ER

CL

2 (N) BALL VALVE

(TYP OF 3)

(N) REDUCE PRESSURE DEVICE OR

REDUCE PRESSURE BACKFLOW PREVENTER

(N) TEE

(TYP OF 2)

(N) REMOVAL PIPE SPOOL

(E )D

OM

ES

TI

C

CO

LD

W

AT

ER

DETAIL A

DETAIL B

PROPOSED HYPERCHLORINATION INJECTION POINT

(N) 4" BYPASS

(N) 1/2" INJECTION QUILL W/ BALL VALVE

(SEE HYPERCHLORINATION SKID ASSEMBLY IN EXHIBIT C)

EXHIBIT NO.DRAWING SCALE

www.ksninc.com

711 N. Pershing Avenue Stockton, CA 95203

209-946-0268

916-403-5900

1550 Harbor Blvd., Suite 212 West Sacramento, CA 95691 1"½"0

ORIGINAL DRAWING SCALE PAGE NO.

A

CDCR

TYP MECHANICAL ROOM MODIFICATIONS DETAILS

CALIFORNIA HEALTH CARE FACILITY

STOCKTON, CA

PLAN VIEW

A

PROFILE VIEW

SECTIONA-A

CONTROLLER

CHLORINE

ANALYZER

BALL VALVE

(TYP)

PRESSURE GAUGE

BACK PRESSURE

VALVE

CALIBRATION COLUMN VENT

CALIBRATION COLUMN

TEE

(TYP) PRESSURE RELIEF VALVE

LOCKING

CASTER WHEELS

METERING PUMP

CONTAINMENT WALL

PLUG

SKID INLET

TO CHEMICAL TANK

STRAINER

A

"M

AX

SKID DRAIN

SKID DISCHARGE

TO INJECTION POINT

SAMPLE MONITORING

DRAIN W/

3/4" MALE HOSE FITTING

NO SWITCH SIGNAL

NOTES:

1.SKID TO BE PROVIDED WITH A LOCKING, TAMPER AND SPLASH PROOF ENCLOSURE

2.SKID TO BE PORTABLE WITH CAPABILITY TO BE WHEELED IN AND OUT OF

INSTITUTION EQUIPMENT ROOMS.

SKID CONTAINMENT DRAIN

VALVE W/ BARB

2" NORMALLY OPEN

FLOOD SWITCH

CHLORINATION

MONITORING POINTFR

OM

CH

EM

IC

AL

IN

JE

CT

IO

N

SK

ID

DI

SC

HA

RG

E

PO

W

ER

DI

ST

RI

BU

TI

ON

BO

X

TYPICAL MECHANICAL ROOM

FLOOD SWITCH AND SUPPLEMENTARY CHLORINATION SECTIONS

49"±

TEE WITH BUSHING TO 3/8"

COMPRESSION FITTING

CONNECTOR

CL2

TO FLOOR DRAIN

TO (E) 120V EQUIPMENT

OUTLET

2" TEE WITH FEMALE BUSHING (3/8") W/

3/8" COMPRESSION FITTING CONNECTOR

2" TEE WITH FEMALE BUSHING (3/8") W/

3/8" COMPRESSION FITTING CONNECTOR

SUPPLEMENTARY CHLORINATION

INJECTION POINT

EXHIBIT NO.DRAWING SCALE

www.ksninc.com

711 N. Pershing Avenue Stockton, CA 95203

209-946-0268

916-403-5900

1550 Harbor Blvd., Suite 212 West Sacramento, CA 95691 1"½"0

ORIGINAL DRAWING SCALE PAGE NO.

B

CDCR

SUPPLEMENTAL CHLORINATION SKID SCHEMATIC

CALIFORNIA HEALTH CARE FACILITY

STOCKTON, CA

PLAN VIEW

A

PROFILE VIEW

SECTIONA-A

BALL VALVE

(TYP)

PRESSURE GAUGE

(TYP)

TEE

(TYP)

PRESSURE

RELIEF VALVE

(TYP OF 2)

LOCKING

CASTER WHEELS

CONTAINMENT WALL

SKID INLET

TO CHEMICAL TANK

(TYP OF 2)

A

"M

AX

NOTES:

SKID TO BE PORTABLE WITH CAPABILITY TO BE WHEELED IN AND OUT

OF INSTITUTION EQUIPMENT ROOMS.

SKID CONTAINMENT DRAIN

PO

W

ER

DI

ST

RI

BU

TIO

N

BO

X

TYPICAL MECHANICAL ROOM

HYPERCHLORINATION SECTION

49"±

METERING PUMP

(TYP OF 2)

CALIBRATION COLUMN VENT

(TYP OF 2)

CALIBRATION COLUMN

(TYP OF 2)

(N) BALL VALVE

(TYP OF 3)

(N) REDUCE PRESSURE PRINCIPAL

BACKFLOW PREVENTER

(N) TEE

(TYP OF 2)

(N) REMOVAL PIPE SPOOL

(E )D

OM

ES

TI

C

CO

LD

W

AT

ER

PROPOSED HYPERCHLORINATION INJECTION POINT

(N) 4" BYPASS

(N) 1/2" INJECTION QUILL W/ BALL VALVE

PLUG

(TYP OF 2)

STRAINER

(TYP OF 2)

COMPRESSION FITTING

(TYP OF 2)

CHECK VALVE

(TYP OF 2)

ALLOW FOR CALIBRATION COLUMN AND

VENT TO BE REMOVED VIA THREADED CONNECTION

(TYP OF 2)

CONNECTION POINT TO ALLOW FOR

CONNECTION OF ADDITIONAL

PUMP EXTERNAL TO SKID

TO (E) 120V EQUIPM

OUTLET

EXHIBIT NO.DRAWING SCALE

www.ksninc.com

711 N. Pershing Avenue Stockton, CA 95203

209-946-0268

916-403-5900

1550 Harbor Blvd., Suite 212 West Sacramento, CA 95691 1"½"0

ORIGINAL DRAWING SCALE PAGE NO.

C

CDCR

HYPERCHLORINATION SKID SCHEMATIC

CALIFORNIA HEALTH CARE FACILITY

STOCKTON, CA

File details come from the government source that posted it. Updated .