24-119_E-2-R2.pdf
PDF 1 MB Posted
- Attached to
- Lift Station # 64 Rehabilitation
- Solicitation number
- PSUT-25-09
- Issued by
- Broward County, Florida
About this file
This is an electrical riser diagram and specification sheet for the City of Pembroke Pines' Lift Station #64 Rehabilitation project located at 120 NW 108th Terrace, Pembroke Pines, Florida. The document outlines the electrical infrastructure requirements for the lift station renovation, including the installation of a new double throw panel with 150-amp, 240-volt, three-phase service at NEMA 3R rating, relocation of the existing Florida Power & Light (FPL) meter, replacement of lighting fixtures, and installation of electrical power and control wiring between the lift station control panel and two submersible pumps rated at 15 horsepower and 17 horsepower respectively. The electrical contractor is responsible for coordinating all FPL service work with FPL Project Manager Daniel Robles, providing new water level sensors, completing final connections and pump startup, and ensuring compliance with National Electrical Code (NEC) standards including proper grounding systems with two 5/8-inch by 10-foot copper-clad steel ground-driven rods spaced minimum 6 feet on center. The classified area designation is Class 1, Division 1, Group D, requiring explosion-proof sealing fittings in accordance with NEC Article 501.10.
The electrical specifications detail the use of 3#8 AWG plus 1#10 type SOOW electrical power cord with EPDM insulation and CPE jacket, prohibition of junction boxes between the wet well and control panel, reuse and extension of existing conduit and wire from the FPL transformer if in good condition, and installation of Lithonia Lighting fixtures with 20-amp fuse protection. The lift station control panel is specified as an MDS 200 model with 100-amp, 240-volt, three-phase capacity rated at 22KAIC with NEMA 3R stainless steel construction. Coordination with the City of Pembroke Pines Project Manager is required throughout the installation process. The drawing was issued for permit on September 25, 2024, with the second revision dated September 12, 2025, and prepared by engineer Pedro Arias, P.E., Florida Registration No. 63813.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DOUBLE THROW PANELDTP
NEW
DEMOLITION
LEVEL 3.55'
FPL
METER
CP
DTP
150A
240V-HIGH LEG
3PH
NEMA 3R
15HPPUMP #1
CP-2
15HP PUMP #2
L
NE
FROM FPL
TRANSFORMER
LEVEL (-) 15.85'
FPL
METER
17HPPUMP #1 17HP PUMP #2
FROM FPL
TRANSFORMER
CP
LIFT STATION
CONTROL PANEL
MCB
100A
240V-3PH
22KAIC
NEMA 3R-SS
LEVEL 7.00'
LEVEL 9.23'
9 9
ELECTRICAL KEY NOTES
1 EXISTING FPL METER TO BE RELOCATED.
2 ELECTRICAL CONTRACTOR SHALL COORDINATE ALL FPL SERVICE WORK WITH
FPL PROJECT MANAGER:
DANIEL ROBLES
Daniel.Robles@fpl.com (941)202-9019
3 EXISTING LIGHTING FIXTURE AND LIGHT SWITCH TO BE REPLACED.
4 NEW LIGHTING FIXTURE. LIGHTING FIXTURE SHALL BE PROTECTED BY A 20AMPS
FUSE. ELECTRICAL CONTRACTOR SHALL INSTALL AN IN-LINE FUSE ON PHASE-A
TO FEED THE EXISTING SERVICE LIGHT FIXTURE. USE POLARIS TAP INSIDE THE
DISCONNECT SWITCH.
5 NEW LIFT STATION PUMP PROVIDED AND INSTALLED BY CONTRACTOR.
6 ELECTRICAL POWER WIRING AND CONTROL WRING BETWEEN LIFT STATION
CONTROL PANEL AND LIFT STATION PUMPS TO BE PROVIDED AND COMPLETED
BY CONTRACTOR.
7 FINAL CONNECTIONS BETWEEN LIFT STATION CONTROL PANEL AND LIFT
STATION PUMPS AND START-UP BY CONTRACTOR.
8 ELECTRICAL POWERCORD - 3#8AWG + 1#10 - TYPE SOOW - EPDM INSULATION -
CPE JACKET. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH CITY OF
PEMBROKE PINES PROJECT MANAGER. NO JUNCTION BOXES ALLOWED
BETWEEN WET WELL AND CONTROL PANEL.
9 17HP IMMERSIBLE MOTOR. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH
CITY OF PEMBROKE PINES PROJECT MANAGER.
10 EXISTING CONDUIT AND WIRE FROM FPL TRANSFORMER TO BE REUSED.
ELECTRICAL CONTRACTOR SHALL EXTEND AND RECONNECT EXISTING WIRE AS
REQUIRED IF THEY ARE IN GOOD CONDITION AND MATCH NEW REQUIREMENTS.
11 EYS EXPLOSION PROOF SEALING FITTING AS PER NEC ART 501.10.
12 NEW WATER LEVEL SENSORS TO BE PROVIDED AND COMPLETED
BY CONTRACTOR.
5 6 7
2"C 2"C
EXISTING GROUNDING SYSTEM
AS PER NEC ART 250.50
#8
PROVIDE AN INTERSYSTEM BONDING
TERMINATION AS PER NEC ART. 250.94
CONNECT TO TWO 5/8" x 10Ft LONG
COPPERCLAD STEEL GROUND DRIVEN RODS.
SPACE RODS MIN. 6Ft O.C.
NEC ART 250.66
GROUNDING SYSTEM
AS PER NEC ART 250.50
LS
2"C
CLASSIFIED AREA
CLASS 1, DIVISION 1, GROUP D
UNISTRUT CHANNEL
8'
SWITCH
CONCRETE SLAB
NEW FIXTURE (ES)
N.T.S.
LIGHT UNISTRUT MOUNTING DETAIL
MDS
240V-3PH
HIGH-LEG
22KAIC
NEMA 3R-SS
UNISTRUT P2072A OR
P2072A SQ - POST BASE
1/2" UNISTRUT CHANNEL NUT AND CAP
SCREW TORQUED TO 50 Ft-lbs
UNISTRUT P1000SL
PRE-DRILLED 3/4" HOLES
5/8" WEDGE ANCHOR
1/2" EMT CONDUIT
SYMBOL LABEL
ES
DESCRIPTION
LIGHTING SCHEDULE
ESXF1 ALO SWW2 KY DDB, YOKE MOUNTING PLATE,
120V.
MANUFACTURER
LITHONIA
LIGHTING
APPROVED:
DRAWN:
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
07-21-250 ISSUED FOR PERMIT
ELECTRICAL RISER
EXISTING-DEMOLITION
NEW
24-119-E2
E - 2
2 14
1 08-20-25 CONDUIT SEAL REV
2 09-12-25 OWNER'S REVIEW
Pedro Arias, P.E.
Florida Registration. No. 63813
ELECTRICAL RISER- NEW
N.T.S.
ELECTRICAL RISER / EXISTING - DEMOLITION
N.T.S.
AutoCAD SHX Text S
AutoCAD SHX Text S
| Sheets and Views |
| E-2 |