24-119_E-2-R2.pdf
PDF 1 MB Posted
- Attached to
- Lift Station # 64 Rehabilitation
- Solicitation number
- PSUT-25-09
- Issued by
- Broward County, Florida
About this file
This document is an electrical engineering drawing set for the Existing Lift Station 64 Restoration project located at 120 NW 108 Terrace in Pembroke Pines, Florida, prepared for the City of Pembroke Pines. The technical drawing (Sheet E-2) details electrical riser diagrams for existing and new electrical infrastructure, including specifications for relocating an FPL meter, replacing lighting fixtures, installing new lift station pumps, and reconfiguring electrical control panels. The drawing includes detailed electrical key notes outlining specific requirements for electrical contractors, such as coordination with FPL and city project managers, grounding systems, and installation of new water level sensors.
The electrical design includes specific technical specifications like a double throw panel (DTP) with 150A, 240V-high leg, 3-phase configuration, and a lift station control panel with a 100A, 240V-3PH, 22KAIC rating. The project involves two pumps (15HP and 17HP) with immersible motors, new electrical power and control wiring, and compliance with National Electrical Code (NEC) standards for grounding, bonding, and classified area requirements. The drawing is sealed by a Florida-registered Professional Engineer and includes revisions for permit submission and owner's review, with the most recent revision dated 09-25-24.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DOUBLE THROW PANELDTP
NEW
DEMOLITION
LEVEL 3.55'
FPL
METER
CP
DTP
150A
240V-HIGH LEG
3PH
NEMA 3R
15HPPUMP #1
CP-2
15HP PUMP #2
L
NE
FROM FPL
TRANSFORMER
LEVEL (-) 15.85'
FPL
METER
17HPPUMP #1 17HP PUMP #2
FROM FPL
TRANSFORMER
CP
LIFT STATION
CONTROL PANEL
MCB
100A
240V-3PH
22KAIC
NEMA 3R-SS
LEVEL 7.00'
LEVEL 9.23'
9 9
ELECTRICAL KEY NOTES
1 EXISTING FPL METER TO BE RELOCATED.
2 ELECTRICAL CONTRACTOR SHALL COORDINATE ALL FPL SERVICE WORK WITH
FPL PROJECT MANAGER:
DANIEL ROBLES
Daniel.Robles@fpl.com (941)202-9019
3 EXISTING LIGHTING FIXTURE AND LIGHT SWITCH TO BE REPLACED.
4 NEW LIGHTING FIXTURE. LIGHTING FIXTURE SHALL BE PROTECTED BY A 20AMPS
FUSE. ELECTRICAL CONTRACTOR SHALL INSTALL AN IN-LINE FUSE ON PHASE-A
TO FEED THE EXISTING SERVICE LIGHT FIXTURE. USE POLARIS TAP INSIDE THE
DISCONNECT SWITCH.
5 NEW LIFT STATION PUMP PROVIDED AND INSTALLED BY CONTRACTOR.
6 ELECTRICAL POWER WIRING AND CONTROL WRING BETWEEN LIFT STATION
CONTROL PANEL AND LIFT STATION PUMPS TO BE PROVIDED AND COMPLETED
BY CONTRACTOR.
7 FINAL CONNECTIONS BETWEEN LIFT STATION CONTROL PANEL AND LIFT
STATION PUMPS AND START-UP BY CONTRACTOR.
8 ELECTRICAL POWERCORD - 3#8AWG + 1#10 - TYPE SOOW - EPDM INSULATION -
CPE JACKET. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH CITY OF
PEMBROKE PINES PROJECT MANAGER. NO JUNCTION BOXES ALLOWED
BETWEEN WET WELL AND CONTROL PANEL.
9 17HP IMMERSIBLE MOTOR. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH
CITY OF PEMBROKE PINES PROJECT MANAGER.
10 EXISTING CONDUIT AND WIRE FROM FPL TRANSFORMER TO BE REUSED.
ELECTRICAL CONTRACTOR SHALL EXTEND AND RECONNECT EXISTING WIRE AS
REQUIRED IF THEY ARE IN GOOD CONDITION AND MATCH NEW REQUIREMENTS.
11 EYS EXPLOSION PROOF SEALING FITTING AS PER NEC ART 501.10.
12 NEW WATER LEVEL SENSORS TO BE PROVIDED AND COMPLETED
BY CONTRACTOR.
5 6 7
2"C 2"C
EXISTING GROUNDING SYSTEM
AS PER NEC ART 250.50
#8
PROVIDE AN INTERSYSTEM BONDING
TERMINATION AS PER NEC ART. 250.94
CONNECT TO TWO 5/8" x 10Ft LONG
COPPERCLAD STEEL GROUND DRIVEN RODS.
SPACE RODS MIN. 6Ft O.C.
NEC ART 250.66
GROUNDING SYSTEM
AS PER NEC ART 250.50
LS
2"C
CLASSIFIED AREA
CLASS 1, DIVISION 1, GROUP D
UNISTRUT CHANNEL
8'
SWITCH
CONCRETE SLAB
NEW FIXTURE (ES)
N.T.S.
LIGHT UNISTRUT MOUNTING DETAIL
MDS
240V-3PH
HIGH-LEG
22KAIC
NEMA 3R-SS
UNISTRUT P2072A OR
P2072A SQ - POST BASE
1/2" UNISTRUT CHANNEL NUT AND CAP
SCREW TORQUED TO 50 Ft-lbs
UNISTRUT P1000SL
PRE-DRILLED 3/4" HOLES
5/8" WEDGE ANCHOR
1/2" EMT CONDUIT
SYMBOL LABEL
ES
DESCRIPTION
LIGHTING SCHEDULE
ESXF1 ALO SWW2 KY DDB, YOKE MOUNTING PLATE,
120V.
MANUFACTURER
LITHONIA
LIGHTING
APPROVED:
DRAWN:
SCALE :
OF:
PROJECT NO.:
DWG FILE:
DATE:
DATEREV No. DESCRIPTION
This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.
LEGENDS:
SHEET:
SHEET No.:
CONTENTS:
PROJECT ADDRESS:
PROJECT:
P.E. SEAL
TO THE BEST OF OUR KNOWLEDGE THE
PLANS AND SPECIFICATIONS COMPLY WITH
THE APPLICABLE MINIMUM BUILDING CODE
EXISTING
LIFT STATION 64
RESTORATION
120 NW 108 TERRACE
PEMBROKE PINES, FL, 33026
INDICATED 09-25-24
J.MEDINA
P.ARIAS 24-119
07-21-250 ISSUED FOR PERMIT
ELECTRICAL RISER
EXISTING-DEMOLITION
NEW
24-119-E2
E - 2
2 14
1 08-20-25 CONDUIT SEAL REV
2 09-12-25 OWNER'S REVIEW
Pedro Arias, P.E.
Florida Registration. No. 63813
ELECTRICAL RISER- NEW
N.T.S.
ELECTRICAL RISER / EXISTING - DEMOLITION
N.T.S.
AutoCAD SHX Text S
AutoCAD SHX Text S
| Sheets and Views |
| E-2 |