24-119_E-2-R2.pdf

PDF 1 MB Posted

Attached to
Lift Station # 64 Rehabilitation
Solicitation number
PSUT-25-09
Issued by
Broward County, Florida

About this file

This document is an electrical engineering drawing set for the Existing Lift Station 64 Restoration project located at 120 NW 108 Terrace in Pembroke Pines, Florida, prepared for the City of Pembroke Pines. The technical drawing (Sheet E-2) details electrical riser diagrams for existing and new electrical infrastructure, including specifications for relocating an FPL meter, replacing lighting fixtures, installing new lift station pumps, and reconfiguring electrical control panels. The drawing includes detailed electrical key notes outlining specific requirements for electrical contractors, such as coordination with FPL and city project managers, grounding systems, and installation of new water level sensors.

The electrical design includes specific technical specifications like a double throw panel (DTP) with 150A, 240V-high leg, 3-phase configuration, and a lift station control panel with a 100A, 240V-3PH, 22KAIC rating. The project involves two pumps (15HP and 17HP) with immersible motors, new electrical power and control wiring, and compliance with National Electrical Code (NEC) standards for grounding, bonding, and classified area requirements. The drawing is sealed by a Florida-registered Professional Engineer and includes revisions for permit submission and owner's review, with the most recent revision dated 09-25-24.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DOUBLE THROW PANELDTP

NEW

DEMOLITION

LEVEL 3.55'

FPL

METER

CP

DTP

150A

240V-HIGH LEG

3PH

NEMA 3R

15HPPUMP #1

CP-2

15HP PUMP #2

L

NE

FROM FPL

TRANSFORMER

LEVEL (-) 15.85'

FPL

METER

17HPPUMP #1 17HP PUMP #2

FROM FPL

TRANSFORMER

CP

LIFT STATION

CONTROL PANEL

MCB

100A

240V-3PH

22KAIC

NEMA 3R-SS

LEVEL 7.00'

LEVEL 9.23'

9 9

ELECTRICAL KEY NOTES

1 EXISTING FPL METER TO BE RELOCATED.

2 ELECTRICAL CONTRACTOR SHALL COORDINATE ALL FPL SERVICE WORK WITH

FPL PROJECT MANAGER:

DANIEL ROBLES

Daniel.Robles@fpl.com (941)202-9019

3 EXISTING LIGHTING FIXTURE AND LIGHT SWITCH TO BE REPLACED.

4 NEW LIGHTING FIXTURE. LIGHTING FIXTURE SHALL BE PROTECTED BY A 20AMPS

FUSE. ELECTRICAL CONTRACTOR SHALL INSTALL AN IN-LINE FUSE ON PHASE-A

TO FEED THE EXISTING SERVICE LIGHT FIXTURE. USE POLARIS TAP INSIDE THE

DISCONNECT SWITCH.

5 NEW LIFT STATION PUMP PROVIDED AND INSTALLED BY CONTRACTOR.

6 ELECTRICAL POWER WIRING AND CONTROL WRING BETWEEN LIFT STATION

CONTROL PANEL AND LIFT STATION PUMPS TO BE PROVIDED AND COMPLETED

BY CONTRACTOR.

7 FINAL CONNECTIONS BETWEEN LIFT STATION CONTROL PANEL AND LIFT

STATION PUMPS AND START-UP BY CONTRACTOR.

8 ELECTRICAL POWERCORD - 3#8AWG + 1#10 - TYPE SOOW - EPDM INSULATION -

CPE JACKET. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH CITY OF

PEMBROKE PINES PROJECT MANAGER. NO JUNCTION BOXES ALLOWED

BETWEEN WET WELL AND CONTROL PANEL.

9 17HP IMMERSIBLE MOTOR. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH

CITY OF PEMBROKE PINES PROJECT MANAGER.

10 EXISTING CONDUIT AND WIRE FROM FPL TRANSFORMER TO BE REUSED.

ELECTRICAL CONTRACTOR SHALL EXTEND AND RECONNECT EXISTING WIRE AS

REQUIRED IF THEY ARE IN GOOD CONDITION AND MATCH NEW REQUIREMENTS.

11 EYS EXPLOSION PROOF SEALING FITTING AS PER NEC ART 501.10.

12 NEW WATER LEVEL SENSORS TO BE PROVIDED AND COMPLETED

BY CONTRACTOR.

5 6 7

2"C 2"C

EXISTING GROUNDING SYSTEM

AS PER NEC ART 250.50

#8

PROVIDE AN INTERSYSTEM BONDING

TERMINATION AS PER NEC ART. 250.94

CONNECT TO TWO 5/8" x 10Ft LONG

COPPERCLAD STEEL GROUND DRIVEN RODS.

SPACE RODS MIN. 6Ft O.C.

NEC ART 250.66

GROUNDING SYSTEM

AS PER NEC ART 250.50

LS

2"C

CLASSIFIED AREA

CLASS 1, DIVISION 1, GROUP D

UNISTRUT CHANNEL

8'

SWITCH

CONCRETE SLAB

NEW FIXTURE (ES)

N.T.S.

LIGHT UNISTRUT MOUNTING DETAIL

MDS

240V-3PH

HIGH-LEG

22KAIC

NEMA 3R-SS

UNISTRUT P2072A OR

P2072A SQ - POST BASE

1/2" UNISTRUT CHANNEL NUT AND CAP

SCREW TORQUED TO 50 Ft-lbs

UNISTRUT P1000SL

PRE-DRILLED 3/4" HOLES

5/8" WEDGE ANCHOR

1/2" EMT CONDUIT

SYMBOL LABEL

ES

DESCRIPTION

LIGHTING SCHEDULE

ESXF1 ALO SWW2 KY DDB, YOKE MOUNTING PLATE,

120V.

MANUFACTURER

LITHONIA

LIGHTING

APPROVED:

DRAWN:

SCALE :

OF:

PROJECT NO.:

DWG FILE:

DATE:

DATEREV No. DESCRIPTION

This drawing and the information and design application herein contained is property of INGEMEL S.A. The information contained herein may not be used or reproduced in any manner without written permission of INGEMEL S.A.

LEGENDS:

SHEET:

SHEET No.:

CONTENTS:

PROJECT ADDRESS:

PROJECT:

P.E. SEAL

TO THE BEST OF OUR KNOWLEDGE THE

PLANS AND SPECIFICATIONS COMPLY WITH

THE APPLICABLE MINIMUM BUILDING CODE

EXISTING

LIFT STATION 64

RESTORATION

120 NW 108 TERRACE

PEMBROKE PINES, FL, 33026

INDICATED 09-25-24

J.MEDINA

P.ARIAS 24-119

07-21-250 ISSUED FOR PERMIT

ELECTRICAL RISER

EXISTING-DEMOLITION

NEW

24-119-E2

E - 2

2 14

1 08-20-25 CONDUIT SEAL REV

2 09-12-25 OWNER'S REVIEW

Pedro Arias, P.E.

Florida Registration. No. 63813

ELECTRICAL RISER- NEW

N.T.S.

ELECTRICAL RISER / EXISTING - DEMOLITION

N.T.S.

AutoCAD SHX Text S

AutoCAD SHX Text S

Sheets and Views
E-2

File details come from the government source that posted it. Updated .