24-11037-000_Addendum_1_Approved_Drawings.pdf
PDF 23 MB Posted
- Attached to
- 24-11037-000 Fuel Service Equipment Replacement
- Solicitation number
- 0000035341
- Issued by
- San Luis Obispo County, Anaheim City, San Luis Obispo City, California
About this file
The documents are construction drawings for a Fuel Service Equipment Replacement project for the Department of State Hospitals (DSH) at the Atascadero campus, located at 10333 El Camino Real, Atascadero, California. The project involves demolishing the existing fuel service equipment refill station and installing a new fuel management system for fleet vehicles, specifically for E-10 fuel. The scope includes mechanical and electrical work such as removing existing fuel service equipment, providing new fuel management system components, installing power and controls, and adding a convenience receptacle.
The project is designed with careful attention to fire safety and code compliance, utilizing 2022 California building, electrical, mechanical, and fire codes. The total project area is 425 square feet, with the work focused on Building S-17, a Type I-A construction building. The electrical and mechanical systems will be updated to support the new fuel service equipment, with specific requirements for conduit, wiring, and equipment installation. The project includes detailed specifications for equipment such as a Fuel Master Live Pedestal, tank gauging system, fuel dispenser, transfer pump, and associated electrical components.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 24-11037-000_Addendum_1.pdf | ||
| 24-11037-000_Fuel_Service_Equipment_Replacement_IFB.pdf | ||
| 24-11037-000_Addendum_1_Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T0.1
TITLE SHEET
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24791-8
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS - ATASCADERO
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
FUEL SERVICE
EQUIPMENT
REPLACEMENT
DSH
10/25/2024
100% SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E F e b ru a ry
:4
P
M
F
IL
E L \2
-8
F u e l S e rv ic e E q u ip m e n t R e p la c e m e n t, D
S H
-A \C
A D
\2 T
10333 EL CAMINO REAL, ATASCADERO, CALIFORNIA 93422
DEPARTMENT OF STATE HOSPITALS - ATASCADERO
DEPARTMENT OF STATE HOSPITALS
1. CONTRACTOR SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 33 -
FIRE SAFETY DURING CONSTRUCTION OF THE 2022 CALIFORNIA FIRE CODE.
FIRE SAFETY DURING CONSTRUCTION
REFERENCE: 2022 CALIFORNIA FIRE CODE
1. SEE OVERALL SITE PLAN FOR SITE ACCESS FOR BOTH PUBLIC RIGHT OF WAY
AND DSH FIRE DEPARTMENT.
FIRE APPARATUS ACCESS
FUEL SERVICE EQUIPMENT REPLACEMENT
OSFM PERMIT NUMBER: 24-N-4811
PROJECT INFORMATION
PREPARED BY:
J.C. CHANG & ASSOCIATES, INC.
ENGINEERS, ARCHITECTS AND PLANNERS
385 VAN NESS AVENUE, SUITE 208
TORRANCE, CALIFORNIA 90501
PHONE : (310) 212-7644
PROJECT ENGINEER
BEN STEFFES
385 VAN NESS AVE. #208
TORRANCE, CALIFORNIA 90501
ARCHITECT OF RECORD/
PRIMARY PROFESSIONAL
RICHARD DE LA FUENTE
LIC. NO. C-33965
385 VAN NESS AVE. #208
TORRANCE, CALIFORNIA 90501
MECHANICAL ENGINEER OF RECORD
ROBERT NOLAN
LIC. NO. 31684
385 VAN NESS AVE. #208
TORRANCE, CALIFORNIA 90501
ELECTRICAL ENGINEER OF RECORD
SEVAG AVANESSIAN
LIC. NO. E22793
385 VAN NESS AVE. #208
TORRANCE, CALIFORNIA 90501
DRAWING INDEX
STATE FIRE MARSHAL SPECIAL INSPECTIONS
A MINIMUM OF 72 HOURS NOTICE WILL BE PROVIDED TO THE STATE FIRE MARSHAL
WHEN SCHEDULING ANY TESTS OR INSPECTIONS.
1. DUCT, CONDUIT OR PIPE PENETRATIONS INSPECTIONS THRU FIRE RATED
ASSEMBLIES.
APPLICABLE CODES AND STANDARDS
1. 2022 BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R.
2. 2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R.
(2021 INTERNATIONAL BUILDING CODE & 2021 CALIFORNIA AMENDMENTS)
3. 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R.
(2021 NATIONAL ELECTRICAL CODE AND 2021 CALIFORNIA AMENDMENTS)
4. 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R.
(2022 UNIFORM MECHANICAL CODE AND 2022 CALIFORNIA AMENDMENTS)
5. 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R.
(2022 UNIFORM PLUMBING CODE AND 2022 CALIFORNIA AMENDMENTS)
6. 2022 CALIFORNIA ENERGY CODE (CEC), PART 6, TITLE 24 C.C.R.
7. 2022 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R.
(2022 INTERNATIONAL FIRE CODE AND 2022 CALIFORNIA AMENDMENTS)
8. 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), PART 11,
TITLE 24 C.C.R.
9. 2022 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R.
10. TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.
PARTIAL LIST OF APPLICABLE STANDARDS
1. NFPA 1 FIRE CODE, CHAPTER 42 - REFUELING 2022 EDITION
2. NFPA 13 AUTOMATIC SPRINKLER SYSTEMS (CA AMENDED) 2022 EDITION
3. NFPA 14 STANDPIPE SYSTEM (CA AMENDED) 2019 EDITION
4. NFPA 17a WET CHEMICAL SYSTEMS 2021 EDITION
5. NFPA 20 STATIONARY PUMPS 2019 EDITION
6. NFPA 24 PRIVATE FIRE MAINS (CA AMENDED) 2019 EDITION
7. NFPA 30A CODE FOR MOTOR FUEL DISPENSING FACILITIES 2022 EDITION
AND REPAIR GARAGES
8. NFPA 72 NATIONAL FIRE ALARM CODE (CA AMENDED) 2022 EDITION
9. NFPA 2001 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS 2018 EDITION
W/ CA AMENDMENTS
10. NFPA 101 LIFE SAFETY CODE 2021 EDITION
11. REFERENCE CODE SECTION FOR NFPA STANDARDS 2022 CBC (SFM)
CHAPTER 35
REFERENCE CODE SECTION FOR NFPA STANDARDS ARE IN 2022 CBC CHAPTER 35
OR 2022 CFC CHAPTER 80. SEE CHAPTER 35 FOR STATE OF CALIFORNIA
AMENDMENTS TO NFPA STANDARDS
MECHANICAL SCOPE:
1. DEMOLISH EXISTING FUEL SERVICE EQUIPMENT REFILL STATION.
2. PROVIDE NEW FUEL SERVICE EQUIPMENT FUEL MANAGEMENT SYSTEM FOR
FLEET VEHICLES ONLY, E-10 FUEL.
ELECTRICAL SCOPE:
1. DEMOLISH ELECTRICAL PROVISIONS FOR FUEL SERVICE EQUIPMENT.
2. PROVIDE POWER AND CONTROLS TO NEW FUEL SERVICE MANAGEMENT
SYSTEM.
3. PROVIDE CONVENIENCE RECEPTACLE.
1. NO DEFERRED APPROVAL ON THIS PROJECT
DEFERRED APPROVALS
N
N
SCOPE OF WORK (NOT LIMITED TO)VICINITY MAPSITE PLAN
PROJECT
LOCATION
MUSSELM
AN D
R.
SAN RAFAEL R
D
EL B
ORDO
SAN RAFAEL RD
H
AL
C O N R
D
LO
S P
UEBLO
S
HEILMANN
REGIONAL
PARK
LOS LOMAS VILLAGE
SAN RAFAEL RDS
A N R
A F A E L R
D
W F
R O N T R
D
E L C
A M
IN
O R
E A L
PREPARED FOR:
DEPARTMENT OF STATE HOSPITALS -
ATASCADERO
10333 EL CAMINO REAL
ATASCADERO, CALIFORNIA 93422
DEPARTMENT OF STATE HOSPITALS
1215 O ST., 2ND FLOOR
SACRAMENTO, CALIFORNIA 95814
RANDY DYE
CHIEF OF PLANT OPERATIONS III
10333 EL CAMINO REAL
ATASCADERO CA 93422
DESK: (805) 468-2206
CELL: (805) 712-6733
EMAIL: RANDY.DYE@DSH.CA.GOV
SHEET NUMBER SHEET TITLE
GENERAL
T0.1 TITLE SHEET
T0.2 FIRE ACCESS SITE PLAN
T0.3 STATE FIRE MARSHALL TRIAGE LIST
T0.4 BUILDING INFORMATION
MECHANICAL
M0.1 MECHANICAL COVER SHEET
M0.2 MECHANICAL SCHEDULES
M1.1 MECHANICAL DEMOLITION PLAN
M2.1 MECHANICAL NEW WORK PLAN
M3.1 MECHANICAL DETAILS
ELECTRICAL
E0.1 ELECTRICAL COVER SHEET
E0.2 ELECTRICAL PANEL SCHEDULE A
E1.1 ELECTRICAL DEMOLITION SITE PLAN
E2.1 ELECTRICAL NEW WORK SITE PLAN
E2.2
BUILDING 810 AND 850 ELECTRICAL POWER NEW WORK
FLOOR PLANS
E3.1 ELECTRICAL DETAILS
REFERENCE
R1.1 ENLARGED SITE PLAN
R1.2 REFERENCE SHEET
R1.3 REFERENCE SHEET
R2.1 REFERENCE SHEET
R3.1 REFERENCE PHOTOS
TOTAL NUMBER OF SHEETS = 20
BUILDING DATA
OCCUPANCY CLASSIFICATION AND USE U
(OUTDOOR
STORAGE AREA)
BUILDING CONSTRUCTION TYPE I-A
NUMBER OF STORIES 1
ACTUAL BUILDING HEIGHT 13 FT
BUILDING AREA IN SQUARE FEET 425 GSF
(TOTAL BUILDING, ALL FLOORS)
AREA OF PROJECT IN SQUARE FEET 425 SF
(TOTAL AREA)
SEPARATED OR NON-SEPARATED USE NON-SEPARATED
ALLOWABLE AREA PER C.B.C. UL
AREA INCREASE NO
HEIGHT INCREASE NO
FIRE SPRINKLERS NO
(YES,NO)
FIRE SPRINKLERS TYPE N/A
(WET, DRY, PRE-ACTION, OR DELUGE)
FIRE ALARM NO
(YES/NO)
FIRE ALARM TYPE N/A
(MANUAL, AUTOMATIC, EVAC, ETC.)
OTHER FIRE PROTECTION NO
(YES OR NO)
SMOKE CONTROL SYSTEM NO
(YES OR NO)
OCCUPANT LOAD FOR ENTIRE BUILDING N/A
(AND EACH FLOOR)
YEAR BUILDING WAS CONSTRUCTED 1969
IS BUILDING IN HIGH SEVERITY FIRE ZONE NO
(YES OR NO)
SEISMIC JOINTS NO
(YES OR NO)
SEISMIC JOINT LOCATION N/A
EMERGENCY RESPONDER RADIO COVERAGE YES
RISK CATEGORY PER 2022 CBC CHAPTER 16 II
BUILDING DATA - BLDG# S-17
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4811
Jeremy Willett. JCCA Thu Feb 20 12:02:49 2025: V2
503A
532 531
CS-40
546 542
510A
504A
505A
5B
5A
506A
508A
MB-104
MB-107
MB-103
MB-101
607 606
509B
508B
506B
B
305304
503B
502B
501B 510B
S-16
512A
(110A)
S-8
SB-2
SB-3
MB-102
CS-35 - CS-37
SB-1
CS-25
CS-38
SB-5
CS-39
S-18 S-19
S-7
CS
-23
CS
-24
SB-4
CS-17 CS-31
&CS-32
CS-1 - CS-16
CS-18 - CS-22
S-17
CS-33 & CS-34
S-1
S-3 S-2
S-4
S-5
S-15
509A
S-10
S-12
S-13
S-11
S-9 511A
CS-26
-CS-30
B
S-6
510C
502A
T0.2
FIRE ACCESS SITE PLAN
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24791-8
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS - ATASCADERO
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
FUEL SERVICE
EQUIPMENT
REPLACEMENT
DSH
10/25/2024
100% SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E M a rc h
:0
P
M
F
IL
E L \2
-8
F u e l S e rv ic e E q u ip m e n t R e p la c e m e n t, D
S H
-A \C
A D
\2 T
FIRE ACCESS SITE PLAN
NO TO SCALE
N
SITE ACCESS FROM PUBLIC
RIGHT OF WAY AND USING
EXISTING PAVED ROADS
BLDG 908
FIRE DEPARTMENT
BUILDING NAME
S-17 FUEL STATION
908 FIRE DEPARTMENT
810 MAINTENANCE SHOP
820 GARAGE
850 PAINT SHOP
EXISTING PAVED ROAD
IS MIN. 25' WIDE
EXISTING PAVED
ROAD IS MIN. 20' WIDE
TURNING RADIUS = 53'
SALLY PORT
LEGEND:
FIRE TRUCK ROUTE
FIRE HYDRANT
IDENTIFIED EXISTING
RED CURB MARKING
RED CURB/SIGNAGE WITHIN THE
AREA OF WORK , AS NOTED.
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
T0.3
STATE FIRE MARSHALL
TRIAGE LIST
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24791-8
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS - ATASCADERO
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
FUEL SERVICE
EQUIPMENT
REPLACEMENT
DSH
10/25/2024
100% SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E J a n u a ry
:3
P
M
F
IL
E L \2
-8
F u e l S e rv ic e E q u ip m e n t R e p la c e m e n t, D
S H
-A \C
A D
\2 T
ITEM SUBMITTAL REQUIREMENTS SUBMITTAL RESPONSE REFERENCE
GENERAL
SEE FOR SPECIFIC SECTION COMMENTS NOT APPLICABLE
PROVIDE A COMPLETE PLAN REVIEW APPLICATION
SUBMIT PLANS SUFFICIENT SIZE
PROVIDE SITE ADDRESS
PROVIDE NAME OF OWNER AND OCCUPANT
IDENTIFY IF NEW CONSTRUCTION OR T.I
IDENTIFY IF NEW OR EXISTING TENANT SPACE
IDENTIFY IF DEFERRED SUBMITTAL
ADD OSFM FILE NUMBER TO TITLE SHEET
PROJECT IS A PHASED SUBMITTAL
SLIP SHEETS SHALL BE BOUND TO SET
SHEET INDEX
WET STAMP AND SIGN SHEETS
SCOPE OF WORK
PROVIDED WITH SUBMITTAL
FLOOR PLANS ARE 1/8"=1' MINIMUM
10333 EL CAMINO REAL, ATASCADERO, CALIFORNIA 93422
OWNER: DEPARTMENT OF STATE HOSPITAL
T.I.
EXISTING
ALL RELEVANT
SHEETS
NOT APPLICABLE
T0.1
T0.1
OSFM NO IS NOTED ON THE TITLE SHEET T0.1
PROJECT IS NOT PHASED
NOT APPLICABLE
SHEET INDEX IS ON T0.1 T0.1
ELECTRONIC SIGNATURE PROVIDED ON DOCUMENT ALL SHEETS
SCOPE OF WORK IS INCLUDED ON TITLE SHEET T0.1
OCCUPANT: DEPARTMENT OF STATE HOSPITAL
PROVIDE A KEY PLAN COORDINATED TO EACH SHEET
PROVIDE A NORTH ORIENTED SITE MAP
ORIENTATE ALL SHEETS TO NORTH
PROVIDE ADOPTED CODE CYCLE LISTINGS AND STANDARDS
PROVIDE A LEGIBLE SCALE. TYPICALLY 1/8"
PROVIDE APPROVED REFERENCE PLANS/DOCUMENTATION
SITE KEY PLAN IS PROVIDED
NORTH ORIENTED SITE PLAN IS PROVIDED T0.3
SITE PLAN IS ORIENTED TO NORTH, INDIVIDUAL DRAWINGS HAVE KEYPLAN
ALL RELEVANT
SHEETS
ADOPTED CODE CYCLE LISTINGS ARE INCLUDED ON TITLE SHEET
ALL FLOOR PLANS ARE 1/8" SCALE MINIMUM. ALL SITE PLANS ARE 1"=30'
NOT APPLICABLE
T0.1
ALL RELEVANT
SHEETS
ALL RELEVANT
SHEETS
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
Jeremy Willett. JCCA Thu Feb 20 12:02:51 2025: V2
14'-6 5/8" 17'-5 9/16"
T0.4
BUILDING INFORMATION
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24791-8
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS - ATASCADERO
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
FUEL SERVICE
EQUIPMENT
REPLACEMENT
DSH
10/25/2024
100% SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E F e b ru a ry
:5
A
M
F
IL
E L \2
-8
F u e l S e rv ic e E q u ip m e n t R e p la c e m e n t, D
S H
-A \C
A D
\2 T
BUILDING INFORMATION
BUILDING
NAME
CONSTRUCTION
TYPE
ACTUAL NUMBER OF
STORIES / (STORIES
ALLOWED CBC 504.4)
ACTUAL
BUILDING AREA
(AREA ALLOWED
CBC 506.2 )
SEPARATED /
NON - SEPARATED
SPRINKLER
COVERAGE
FIRE
ALARM
OTHER
PROTECTION
SYSTEM
SMOKE
CONTROL
SYSTEM
OCCUPANT
LOAD
YEAR BUILDING
CONSTRUCTED
SEISMIC
JOINT
OCCUPANCY
CLASS
S-17 N/A N/A NONE NO
BUILDING
HEIGHT
NONE N/A NONE NO NO NOTYPE 1
U
OUTDOOR
STORAGE AREA
+/-13'-0"
(N/A)
EMERGENCY
RESPONDER
RADIO
COVERAGE
HIGH FIRE
HAZARD
SEVERITY
ZONE
(1)
SITE PLAN
SCALE: N
810 39 1954 NO NO YESII-B NON-SEPARATED YES
STANDPIPES AND
FIRE EXTINGUISHERS
NO
(3)
19,110 (70,000)
+/-20'-0"
S-1
(MANITENANCE
SHOPS)
AREA OF
PROJECT
AREA
INCREASE
NO
HEIGHT
INCREASE
NO
NO
HIGH-RISE
NO
NONO NO
(E) S-17 CANOPY
BLDG 810 (UPPER) &
BLDG 850 (LOWER)
0 81 FEET4
1/4" = 1'-0"
850 100 1989 NO NO YESII-B NON-SEPARATED YES
STANDPIPES AND
FIRE EXTINGUISHERS
NO
(3)
3,000 (N/A)
+/-20'-0"
S-1
(MAINTENANCE
SHOPS)
- NO NONO NO
(E) FUEL DISPENSING SYSTEM
(E) ABOVE GROUND FUEL STORAGE
TANK.
S-17 REFUELING - GENERAL REQUIREMENTS
FUEL
AREA
TYPE AND
DESIGN
FUEL DISPENSER:
LOCATION AND
DESIGN
DISTANCE:
DISPENSER TO
PROPERTY LINE
VEHICLE ACCESS
METHODS:
STORAGE AND
DISPENSING
OVERFILL
PREVENTION
VENTS
VAPOR
RECOVERY
PIPING, VALVES, AND
FITTINGS
SPECIFICATIONS
ELECTRICAL
EQUIPMENT
UNDERGROUND/
ABOVEGROUND
S-17 SEE M0.2 SEE E2.1 & E2.2
DISTANCE:
TANK TO
DISPENSER
SEE R1.1 SEE M0.2 & M2.1
SEE DISPENSER
SPECIFICATIONS
SEE VENTS ON M2.1
SEE LOCATION
ON M2.1
SEE M0.2 ABOVEGROUND +/- 1'-0" +/- 764'-9"
TANK MOUNTED
DISPENSER BEHIND
FENCE OF S-17
DISTANCE:
DISPENSER TO
ADJACENT
BUILDING
+/- 14'-6 5/8"
FIRE
APPLIANCES
SEE R1.1
VEHICLE
IMPACT
PROTECTION
SEE R1.1
(E) PEDESTRIAN GATE
(E) PEDESTRIAN GATE
(E) CHAIN-LINK FENCE
(E) S-17 CANOPY COLUMN, TYP.
(E) WALL
(E) STAIRS
CS-33 - NO NO NO YESNON-SEPARATED NO NO NO
(3) (N/A)
+/-9'-0" U
METAL STORAGE
SHED
- NO NONO NO
CS-34
II-B
II-B
U
METAL STORAGE
SHED
(3) +/-9'-0"
CS-34CS-33
(N/A)
- NON-SEPARATED NONO NO NO - NO NO NO YESNO NONO
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
M0.1
MECHANICAL COVER SHEET
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24791-8
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS - ATASCADERO
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
FUEL SERVICE
EQUIPMENT
REPLACEMENT
DSH
10/25/2024
100% SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E F e b ru a ry
:2
P
M
F
IL
E L \2
-8
F u e l S e rv ic e E q u ip m e n t R e p la c e m e n t, D
S H
-A \C
A D
\2 M
POINT OF DISCONNECTION
SHEET WHERE DETAIL IS DRAWN
ROOM THERMOSTATT
DETAIL NO.
NEW WORK KEY NOTE
DEMOLITION KEY NOTE
POINT OF CONNECTION
EXHAUST
CUBIC FEET PER
ABOVE FLOOR
ACCESS DOOR
GALLONS PER MINUTE
GAUGEGA.
GPM
EXH.
A.D.
A.F.
CFM
FIRE SPRINKLER LINE
FUEL OIL SUPPLY
FUEL OIL RETURN
VENT
F
FOS
FOR
V
SYMBOL DESCRIPTION
CONTROL VALVE
M MOTOR ACUATED MODULATING
SYMBOL
S
A
PUMP
P
PRESSURE RELIEF
AUTOMATIC AIR VENT
PETE'S PLUG
PRESSURE GAUGE
THERMOMETER
PNEUMATIC ACTUATED
SOLENOID ACTUATED
PRESSURE REGULATOR
ANGLE VALVE
CHECK VALVE
VENTURI FLOW METER
PLUG VALVE
GAS VALVE
STRAINER
GLOBE VALVE
BUTTERFLY VALVE
DESCRIPTION
GATE VALVE
BALL VALVE
MECHANICAL PIPING SYMBOLS
MINUTE
EXISTING TO REMAIN, PROTECT IN PLACE(E)
OPENING
PLATFORM
OPNG.
PLAT.
POINT OF DISCONNECTPOD
NEW, PROVIDE AND INSTALL(N)
MECHANICAL ABBREVIATIONS
POINT OF CONNECTIONPOC
CONDENSER WATER SUPPLYCWS
CONDENSER WATER RETURNCWR
CONDENSER WATERCW
BUILDING MANAGEMENT SYSTEMB.M.S.
DEMOLITION/ DEMOLISH(D)
GENERAL NOTES MECHANICAL SYMBOLS
1. THE CONTRACTOR SHALL FURNISH ALL LABOR, SUPERVISION, MATERIALS,
EQUIPMENT, TOOLS, TRANSPORTATION, WAREHOUSING, AND ANY OTHER
SERVICES REQUIRED TO COMPLETE THE WORK IN A TIMELY AND EFFICIENT
MANNER.
2. INDIVIDUAL ITEMS OF WORK ARE DETAILED IN THE VARIOUS SECTIONS OF THIS
SCOPE OF WORK, THE ATTACHED DRAWINGS, AND THE NOTES AND LEGENDS
ON THE DRAWINGS. THE CONTRACTOR IS RESPONSIBLE TO COMPLETE THE
REQUIREMENTS FOUND IN ANY OF THE ABOVE.
3. CONTRACTOR BIDS ARE TO BE BASED UPON COMPLETING THE WORK WITHIN
THE AMOUNT BID. ANY QUESTIONS PERTAINING TO UNKNOWN CONDITIONS,
CHANGES IN DESIGN, OMISSIONS IN THE DESIGN OR SCOPE OF WORK,
MATERIALS, AND INSTALLATION TECHNIQUE ARE TO BE DISCUSSED WITH THE
PROJECT MANAGER. THE PROJECT MANAGER WILL GET THE ANSWERS TO
QUESTIONS, AS SOON AS POSSIBLE, IF "ON-THE-SPOT" ANSWERS CAN NOT BE
PROVIDED. UNKNOWN CONDITIONS ENCOUNTERED DURING THE COURSE OF
WORK, WHICH MAY DELAY WORK OR ADD COST, WILL BE REPORTED TO THE
PROJECT MANAGER IMMEDIATELY-SO THAT PROPER ARRANGEMENTS CAN BE
MADE WITHOUT WORK STOPPAGE.
4. ALL WORK SHALL BE IN COMPLIANCE WITH THE EDITION OF THE OWNERS
STANDARDS AND REQUIREMENTS CURRENTLY IN FORCE AND ALL LOCAL
ORDINANCES AND REQUIREMENTS.
5. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL ALL
TEMPORARY BRACING AND SHORING OF EQUIPMENTS TO INSURE THE SAFETY
OF THE WORK UNTIL IT IS IN ITS COMPLETED FORM.
6. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE THAT ALL
APPLICABLE SAFETY LAWS ARE STRICTLY ENFORCED AND TO MAINTAIN A
SAFE CONSTRUCTION PROJECT.
7. THE CONTRACTOR SHALL REPAIR AND/OR REPAINT ALL AREAS DAMAGED BY
DEMOLITION OR CONSTRUCTION, AND FINISH TO MATCH EXISTING ADJACENT
SURFACES.
8. DAILY, AND UPON COMPLETION OF WORK, CONTRACTOR SHALL REMOVE
DEBRIS, RUBBISH, WASTE, AND SURPLUS MATERIAL FROM THE PREMISES.
9. THE CONTRACTOR SHALL PROTECT AND COVER ALL FIXTURES AND
EQUIPMENT IN AREAS AFFECTED BY WORK, AND UPON COMPLETION OF WORK,
SHALL THOROUGHLY CLEAN ALL FIXTURES, EQUIPMENT, WALLS, CEILING,
FLOOR, AND HARDWARE.
10. ALL PERMITS SHALL BE OBTAINED AS REQUIRED BY LOCAL CODES AND AHJ.
11. CONTRACTOR SHALL VERIFY ALL INDOOR/OUTDOOR DIMENSIONS AND
OUTDOOR JOB CONDITIONS AT THE JOB SITE PRIOR TO BID, DO NOT SCALE
DRAWINGS.
12. CONTRACTOR SHALL PROVIDE ALL PLAN CHECK SERVICES, WHERE
APPLICABLE.
13. CONTRACTOR SHALL OBTAIN A BURN PERMIT FOR ALL HOT WORK FROM FIRE
PREVENTION COORDINATOR.
14. FOR PURPOSES OF CLEARNESS AND LEGIBILITY, THE CONTRACT DRAWINGS
ARE ESSENTIALLY DIAGRAMMATIC AND, ALTHOUGH LOCATION OF THE
EQUIPMENT IS DRAWN TO SCALE, THE CONTRACTOR SHALL MAKE USE OF ALL
DATA IN ALL THE CONTRACT DOCUMENTS, TO ACCOMPLISH A COMPLETE,
OPERABLE AND MAINTAINABLE INSTALLATION.
15. ALL INSULATION AND COVERINGS INSTALLED ON PIPING AND TUBING SHALL
HAVE A FLAME-SPREAD RATING NOT TO EXCEED 25 AND A SMOKE DENSITY
NOT TO EXCEED 50 WHEN TESTED IN ACCORDANCE WITH NFPA 255. (PER
PARAGRAPH 1201.2.1.8 CMC 2022.
16. CONTRACTOR SHALL MEET OWNER'S CONSTRUCTION STANDARDS.
17. THE SYSTEM SHALL REMAIN OPERATIONAL EXCEPT FOR SCHEDULED
SHUT-DOWNS.
18. CONTRACTOR SHALL VERIFY LOCATION OF UTILITIES AND SCHEDULE WITH
FACILITY ENGINEER "OFF-HOURS" GENERAL SYSTEM SHUT-DOWN OF THE
UTILITIES.
19. ALL NEW PIPE AND EQUIPMENT SUPPORTS AND SEISMIC SHALL COMPLY WITH
OSHPD REQUIREMENTS AND ASCE/SEI 7.
20. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE A FULLY FUNCTIONAL
INSTALLATION AND TO INTEGRATE THE NEW WORK TO EXISTING SITE
CONDITIONS.
21. CONTRACTOR SHALL PROVIDE SHOP DRAWINGS OF PIPING, CONTROLS AND
PIPING SYSTEMS TO OWNER REPESENTATIVE FOR APPROVAL PRIOR TO
FABRICATION. CONTRACTOR SHALL PROVIDE EQUIPMENT SUBMITTALS OF ALL
HARDWARE TO BE INSTALLED ON THIS JOB PRIOR TO PURCHASE.
22. CONTRACTOR SHALL LABEL FINAL PIPING INSTALLATION SHOWING DIRECTION
OF FLOW ARROWS AND TYPE OF WATER (E.G. CONDENSER WATER SUPPLY,
AND RETURN, VENT, DRAIN, ETC).
23. CONTRACTOR SHALL PROVIDE ONE (1) HARD COPY AND ONE (1) SOFT COPY OF
EQUIPMENT SUBMITTALS OR SHOP DRAWINGS OF ALL EQUIPMENT SPECIFIED
IN THE MATERIAL LIST AND SCHEDULES ON DRAWINGS M0.2, TO OWNER
REPRESENTATIVE FOR APPROVAL PRIOR TO PURCHASE.
24. CONTRACTOR SHALL PROVIDE ONE (1) HARD COPY AND ONE (1) SOFT COPY OF
OPERATION & MAINTENANCE MANUALS OF ALL EQUIPMENT SPECIFIED.
25. CONTRACTOR SHALL INSTALL NEW PIPING WITH SPOOL SECTIONS TO ALLOW
MAINTENANCE ACCESS TO NEW EQUIPMENT PER EQUIPMENT
MANUFACTURER'S REQUIREMENT AND ALL CODE CLEARANCES.
MECHANICAL PIPING LEGEND
SYMBOL DESCRIPTION
FUEL SYSTEM NOTES
1. REFER TO SPECIFICATIONS AND SHEETS M0.1, M2.1, and M3.1 FOR FUEL
SYSTEM REQUIREMENTS.
2. CONTRACTOR SHALL USE A SINGLE SUPPLIER AND SHALL PROVIDE ALL
COMPONENTS OF FUEL SYSTEM FOR A COMPLETE WORKING SYSTEM.
3. COORDINATE WITH ELECTRICAL SHEETS FOR ELECTRICAL REQUIREMENTS.
4. CONTRACTOR SHALL PAINT ALL NEW FUEL PIPING PER SPECIFICATIONS.
MECHANICAL GENERAL NOTES
1. ALL WELDING ON PROJECT SHALL BE PER ASME B31.1 STANDARDS.
2. CONTRACTOR SHALL PROVIDE PIPING LABELS WHICH SHOW DIRECTION OF
FLOW AND TYPE OF SERVICE. ALL NEW LINES SHALL BE LABELED PER
SPECIFICATIONS.
3. ALL UTILITIES SHUTDOWNS SHALL BE REQUESTED 72 HOURS IN ADVANCE FOR
APPROVAL.
4. ALL JOB SITE WORK HOURS SHALL BE COORDINATED WITH THE INSTITUTION.
5. ALL EQUIPMENT CONNECTIONS SHALL NOT HAVE A DIAMETER LESS THAN
THAT OF THE INLET CONNECTIONS TO THE EQUIPMENT AS PROVIDED BY THE
MANUFACTURER AND EACH EQUIPMENT SHALL BE CONNECTED TO THE PIPING
WITH MATERIALS AS APPROVED IN 2022 CPC.
ADDITIVEADD
ENHANCED VAPOR RECOVERYEVR
DEMOLITION WORK
EXISTING
NEW WORK
DEMOLITION/ DEMOLISHDEMO
HOSE
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
M1.1
MECHANICAL DEMOLITION
PLAN
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24791-8
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS - ATASCADERO
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
FUEL SERVICE
EQUIPMENT
REPLACEMENT
DSH
10/25/2024
100% SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
BUILDING KEYPLAN
N
JCCA
D A T E T
IM
E F e b ru a ry
:2
P
M
F
IL
E L \2
-8
F u e l S e rv ic e E q u ip m e n t R e p la c e m e n t, D
S H
-A \C
A D
\2 M
DEMOLITION KEYNOTES:
(D) - DEMO AND REPLACE
(E) - EXISTING TO REMAIN, PROTECT IN PLACE
(D) FUEL DISPENSING UNIT. INCLUDING DISPENSING NOZZLE.
(E) FUEL TANK MOUNTING BRACKET.
(E) FUEL FILL PIPING.
(E) FILL POUR SYSTEM AND ASSOCIATED PIPING.
(D) FUEL OIL PIPING TO FUEL OIL TANK. (E) FUEL OIL TANK AND
FUEL OIL TANK WELDED PLUMBING COUPLING.
(D) FUEL SENSING LINE.
(D) FUEL OIL LEVEL SENSOR.
1"
1" 2"
(E) FIRE
EXTINGUISHER
AREA OF
WORK
1"
(E) FUEL FILL VAPOR
RECOVERY STATION
(E) EMERGENCY
VENT
(E) VENT
(E) 4000 GAL.
FUEL TANK
MECHANICAL DEMOLITION PLAN
SCALE: N0 41 FEET3
1/2" = 1'-0"
(E) CHAIN LINK
FENCE
(E) PEDESTRIAN
GATE
(E) PEDESTRIAN
GATE
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
M0.2
MECHANICAL SCHEDULES
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24791-8
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS - ATASCADERO
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
FUEL SERVICE
EQUIPMENT
REPLACEMENT
DSH
10/25/2024
100% SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E F e b ru a ry
:2
P
M
F
IL
E L \2
-8
F u e l S e rv ic e E q u ip m e n t R e p la c e m e n t, D
S H
-A \C
A D
\2 M
ITEM DESCRIPTION SPECIFICATION
EQUIPMENT SCHEDULE
FUEL MASTER LIVE PEDESTAL. AIRCRAFT QUALITY ALUMINUM. PROVIDE TMU EXPANSION CARD WITHIN UNIT. INCLUDE PROKEE READER
TO AUTHORIZE FUELING TRANSACTIONS BY USERS.
OMNTEC TANK GAUGING AND LEAK DETECTION SYSTEM, MODEL OEL8000IIIK OR APPROVED EQUAL. ACCEPTS UP TO 8
MAGNEOSTRICTIVE PROBES, UP TO 16 BRIGHT EYE SENSORS, COLOR 7-INCH GRAPHIC DISPLAY WITH CAPACITIVE TOUCH SCREEN.
BUILT IN WEB SERVER AND VPN CAPABILITY. ETHERNET / TCP / IP STANDARD WITH UP TO 5 BUILT IN PROGRAMMABLE RELAYS. 120VAC, 14LBS, 10" x 15.2" x 5.1" (H x W x D).
DRESSER WAYNE DIGITAL COMPACT DISPENSER, MODEL S1 COMPACT DISPENSER OR APPROVED EQUAL. POWDER-COATED METALLIC SILVER SIDES, TOP AND BASE. DOORS POWDER-COATED BLUE WITH CHARCOAL GRAY BEZEL WITH MATCHING DECAL WITH WHITE
LETTERING. EXTERIOR PANELS FABRICATED FROM HEAVY GAUGE GALVANNEALED STEEL WITH REMOVABLE DOORS. LIFT-TO-START ACTIVATION NOZZLE BOOT. SHELF-MOUNTED. WORKING PRESSURE UP TO 50 PSI, 30-1/4" x 22-5/8" x 18-1/8" (H x W x D). MOUNTING
PROVISIONS
FUEL OIL
DISPENSER
FUEL
MONITORING
SYSTEM
FUEL MASTER
LIVE PEDESTAL
FILL-RITE FUEL TRANSFER PUMP, MODEL FR700VN OR APPROVED EQUAL. HEAVY DUTY CAST IRON BODY, 20 GAL/MIN. 115V AC, 2" BUNG
INLET. THERMALLY PROTECTED, MESH STRAINER FILTER. 1/3 HP. 3/4" OUTLET
FUEL OIL
TRANSFER PUMP
OMNTECH BRIGHT EYE SENSOR, MODEL BX-LS OR APPROVED EQUAL. SHIELDED 22 AWG WITH DRAIN WIRE, MAXIMUM LENGTH 2,000
FEET. MOUNTING INTERFACE.
LEVEL SENSOR
OMNTECH REMOTE ANNUNCIATOR, MODEL RAS-1-NYS OR APPROVED EQUAL. LED INDICATORS RATED MTBF 11 YEARS. HIGH DECIBEL, HIGH INTENSITY AUDIBLE ALARM WITH VISUAL INDICATOR OF FLASHING STROBE BEACON. NEMA-4X RATING.OVERFILL ALARM
OMNTECH MAGNETOSTRICTIVE TANK GAUGING PROBE IN TANK LEAK DETECTION, MODEL MTG-RS-R5F1 OR APPROVED EQUAL.TANK PROBE
REMARKS
NOTES:
PROVIDE PROKEE ENCODER, CONNECTS TO COMPUTER TO ALLOW CODING OF KEYCARDS. PROKEE READER ACCEPTS PROKEE CARDS.
PROVIDE TMU INTERFACE WITHIN UNIT.
PROVIDE OMNTEC FIBERGLASS HINGE COVER, MODEL ENC-4X / ENC-4X-NW OR APPROVED EQUAL.
CONNECT TO FUEL MONITOR SYSTEM.
EQUIPMENT WETTED COMPONENTS TO BE COMPATIBLE WITH E-10 FUEL.
PIPE MATERIAL SCHEDULE
SERVICE/
PIPING
LOCATION
MATERIAL
OUTSIDE
BLACK STEEL,
TYPE E OR S
SCH 40, GRADE B
STAINLESS STEEL
TYPE 304
STAINLESS STEEL
TYPE 316
DRAWN TEMPER
COPPER
ANNEALED TEMPER
COPPER
FLEXIBLE,
NONMETALLIC,
REMARKS
OUTSIDE
OUTSIDEHOSE
FOR
FOS
FMU
FMS
FOD
FTP
LS
OA
TP
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
M2.1
MECHANICAL NEW WORK
PLAN
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24791-8
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS - ATASCADERO
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
FUEL SERVICE
EQUIPMENT
REPLACEMENT
DSH
10/25/2024
100% SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
BUILDING KEYPLAN
N
JCCA
D A T E T
IM
E F e b ru a ry
:2
P
M
F
IL
E L \2
-8
F u e l S e rv ic e E q u ip m e n t R e p la c e m e n t, D
S H
-A \C
A D
\2 M
NEW WORK KEYNOTES:
(N) - PROVIDE AND INSTALL,
(N) FUEL OIL DISPENSER. INSTALL ON (E) FUEL OIL TANK SIDE
BRACKET. ABIDE BY MANUFACTURER'S MOUNTING
REQUIREMENTS.
(N) VST EVR NOZZLE. PROVIDE WITH NEW HANGING HARDWARE.
(N) TANK MOUNTED FUELOIL TRANSFER PUMP.
(N) LEVEL SENSOR.
(N) TANK GAUGING PROBE FOR LEAK DETECTION. (N) EVR CAP.
(N) OMNTECH TANK GAUGING AND LEAK DETECTION MONITOR.
(N) TAMPERPROOF COVER.
(N) FUEL MASTER LIVE PEDESTAL WITH PROKEE READER AND
TMU INTERFACE. INSTALL PER MANUFACTURER REQUIREMENTS.
ABIDE BY EQUIPMENT CLEARANCE REQUIREMENTS. MAINTAIN
AT LEAST 18" OF CLEARANCE TO ANY SURROUNDING
EQUIPMENT.
(N) REMOTE ANNUNCIATOR.
(N) SPLITTER VALVE TO CONNECT VAPOR RETURN TO TANK AND
FUEL DISPENSING HOSE. MODEL: EMCO WHEATON A4041
SPLITTER OR APPROVED EQUAL.
FUEL SYSTEM NOTES:
1. CONTRACTOR SHALL INSTALL ALL PIPING, FUEL SERVICE
EQUIPMENT, ALL ELECTRICAL WIRING AND CONTROLS WIRING,
FOR A COMPLETE WORKING SYSTEM AND SHALL CONNECT TO
EXISTING WIRING FOR MAIN TANK.
2. EXISTING ABOVE GROUND STORAGE TANKS SHALL BE PER
NFPA 30 (NATIONAL FIRE PROTECTION ASSOCIATION). TANK
SHALL HAVE DOUBLE WALL CONTAINMENT AND SHALL BE
BUILT PER UL142 WITH UL508 COMPLIANT DAY TANK
CONTROLS AND REQUIREMENTS PER 2022 IFC
(INTERNATIONAL FIRE CODE).
3. SIGNAGE AND MARKINGS SHALL BE INSTALLED PER NFPA 704.
4. FUEL SYSTEM AND TANKS SHALL BE CONNECTED TO MASTER
CONTROLLER.
5. CONTRACTOR SHALL ROUTE PIPING TO AND FROM FUEL
SERVICE EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
6. PIPING SHALL BE PRESSURE TESTED PRIOR TO START UP.
7. FINAL INSTALLATION OF FUEL PIPING AND FUEL SERVICE
PIPING SHALL BE IN ACCORDANCE WITH AN APPROVED PIPING
FLOW DIAGRAM AND CONNECTION DETAILS PROVIDED BY
CONTRACTOR'S FUEL DESIGNER AND APPROVED BY
MECHANICAL ENGINEER OF RECORD (MEOR).
1-1/4" FOS
1" FOR
1"
F R
O N
T
(E) EMERGENCY
VENT
(E) VENT
(E) 4,000 GAL.
FUEL TANK
FMU
FMS
FOD
FTP
LS
OA 1
TP
MECHANICAL NEW WORK PLAN
SCALE: N0 41 FEET3
1/2" = 1'-0"
AREA OF
WORK
(E) FUEL FILL
VAPOR RECOVERY
STATION
(E) CHAIN LINK
FENCE
(E) PEDESTRIAN
GATE
(E) PEDESTRIAN
GATE
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
M3.1
MECHANICAL DETAILS
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24791-8
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS - ATASCADERO
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
FUEL SERVICE
EQUIPMENT
REPLACEMENT
DSH
10/25/2024
100% SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E F e b ru a ry
:2
P
M
F
IL
E L \2
-8
F u e l S e rv ic e E q u ip m e n t R e p la c e m e n t, D
S H
-A \C
A D
\2 M
VEHICLE FUELING TANK DETAIL
NO SCALEM3.1
COMPONENT DESCRIPTION:
FUEL MASTER LIVE PEDESTAL.
FUEL TRANSFER PUMP.
FUEL OIL DRESSER WAYNE DISPENSER.
OMNTECH LEAK SENSOR.
OMNTECH MAGNETOSTRICTIVE TANK GAUGING PROBE.
FUEL OIL RETURN. 1" DIA PIPE.
FUEL OIL SUPPLY. 1-1/4" DIA PIPE.
FUEL OIL RETURN. 1" DIA PIPE.
FUEL OIL HOSE.
(E) - EMERGENCY VENT.
(E) - FILL & VAPOR PIPING.
(E) - VENT.
(E) - ABOVEGROUND FUEL STORAGE TANK.
(E) - CONCRETE PAD.
LANE-ORIENTED NOZZLE BOOT.
TO FILL SYSTEM
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
-DRDR
E0.1
ELECTRICAL COVER SHEET
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24791-8
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS - ATASCADERO
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
FUEL SERVICE
EQUIPMENT
REPLACEMENT
DSH
10/25/2024
100% SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E N o v e m b e r :0
P
M
F
IL
E L \2
-8
F u e l S e rv ic e E q u ip m e n t R e p la c e m e n t, D
S H
-A \C
A D
\2 E
LIGHT, THIN LINES INDICATE EXISTING.
HEAVY, THICK LINES INDICATE NEW
HEAVY, SHORT DASHED LINES INDICATE
DEMOLITION OR REMOVAL
TYPICAL PLAN LEGEND
THIS SYMBOLOGY TO BE USED BY ELECTRICAL AND LAYOUT FOR ALL
FLOOR PLANS, EQUIPMENT, DEVICES, UTILITIES, ETC., SHOWN ON
DRAWINGS.
ABBREVIATIONS ELECTRICAL SYMBOL LIST
SWITCHBOARD 240D/120V, 3Ø, 4W
PANELBOARD 240D/120V, 3Ø, 4W
P4-10 BRANCH CIRCUIT DESTINATION (PANEL NAME-CIRCUIT
NUMBER)
HOMERUN INDICATES PROVIDING CONDUIT AND
CONDUCTORS
MINIMUM CONDUIT SIZE: 3/4"
MINIMUM CONDUCTOR SIZE: #12AWG
PROVIDE 3/4"C-2#12+1#12G WHERE NO CONDUIT/WIRE SIZE IS
STATED.
PROVIDE DEDICATED NEUTRAL FOR ALL BRANCH CIRCUIT
WIRING.
CONTRACTOR RESPONSIBLE FOR DE-RATING CONDUIT WITH
MORE THAN SIX CURRENT CARRYING CONDUCTORS PER CEC
310.
#12 AWG FOR CIRCUITS UP TO 100'
#10 AWG FOR CIRCUITS FROM 100' TO 200'
#8 AWG FOR CIRCUIT GREATER THAN 200'
UNFUSED DISCONNECT SIZED AS INDICATED ON DWGS.
CONTRACTOR TO CONFIRM FUSE SIZING BASED ON
EQUIPMENT MANUFACTURER RECOMMENDAITON
JUNCTION BOX
1. ALL WORK MUST BE PERFORMED IN COMPLIANCE WITH APPLICABLE CODES
AND STANDARDS. SEE T0.1 FOR A LIST OF APPLICABLE CODES AND
STANDARDS.
2. CEC 110.2 APPROVAL: ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED,
OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY
ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY HEALTH
ADMINISTRATION.
3. CEC 130.5(C): VOLTAGE DROP: THE MAXIMUM COMBINED VOLTAGE DROP ON
BOTH INSTALLED FEEDER CONDUCTORS AND BRANCH CIRCUIT CONDUCTORS
TO THE FARTHER CONNECTED LOAD OR OUTLET SHALL NOT EXCEED 5
PERCENT.
4. ALL CABLE/WIRE, CONDUIT RUNS ARE SHOWN DIAGRAMMATICALLY & THEY
SHALL BE ROUTED TO SUIT ACTUAL FIELD CONDITIONS, EXCEPT WHERE
LOCATIONS ARE EXPLICITLY DIMENSIONED ON THE DRAWINGS.
5. THE ELECTRICAL CONSTRUCTION DRAWINGS PROVIDED HEREIN ARE
DIAGRAMMATIC AND SYMBOLIC IN REPRESENTATION. LOCATIONS DEPICTED
ON THE DRAWINGS FOR ELECTRICAL EQUIPMENT/DEVICES (MOTORS,
STARTERS, DISCONNECT SWITCHES, RECEPTACLES, JUNCTION/OUTLET BOXES,
CONTROL SWITCHES, EQUIPMENT RACKS, SMALL TRANSFORMERS, ETC.) ARE
ONLY APPROXIMATE. FURTHERMORE, THE EQUIPMENT/DEVICE DEPICTIONS
ARE GENERALLY SYMBOLIC AND NOT DRAWN TO SCALE.
6. IN EVENT OF CONFLICT OR DISCREPANCY BETWEEN DRAWINGS,
SPECIFICATIONS, CONTRACT DOCUMENTS, SPECIFICATIONS, DRAWINGS AND
SITE CONDITIONS, THE CONTRACTOR SHALL PROVIDE THE MORE STRINGENT
OF THE DRAWINGS, SPECIFICATIONS, AND CONTRACT DOCUMENTS FOR THE
CONSTRUCTIONS AND BIDDING PURPOSES.
7. ELECTRICAL DRAWINGS INDICATE NEW WORK, UNLESS OTHERWISE NOTED.
EXISTING ELECTRICAL SYSTEMS ARE NOT SHOWN EXCEPT WHERE
INTERFACING IS REQUIRED.
8. ALL NEW BOXES, PANELS, OUTLET COVERS, ENCLOSURES, ETC. MOUNTED ON
THE EXTERIOR OF ANY STRUCTURE SHALL BE WEATHERPROOF (NEMA 3R
MINIMUM) & ALSO PAINTED TO MATCH THE EXISTING BUILDING/STRUCTURE.
9. ALL EXISTING SURFACES DAMAGED BY NEW CONSTRUCTION, SHALL BE
PATCHED, OR REPAINTED TO MATCH EXISTING CONDITIONS, PAINTED
SURFACE SHALL BE PAINTED FROM BREAK TO BREAK. IT SHALL BE THE
CONTRACTORS RESPONSIBILITY TO PATCH & REPAIR ALL DAMAGE TO EXISTING
SURFACES AND FINISHES. FURTHERMORE, THE AFFECTED AREA(S) OF WORK
SHALL BE REPAIRED TO MATCH THE FINISH THAT WAS PREVIOUSLY EXISTING,
PRIOR TO THE COMMENCEMENT OF WORK.
10. RUN CONDUITS CONCEALED IN WALLS AND CEILINGS UNLESS NOTED. CUT
EXISTING WALLS AS REQUIRED. PATCH AND PAINT TO MATCH EXISTING
SURFACE.
11. UPDATE ALL POWER PANEL DIRECTORIES AND ELECTRICAL OUTLET
IDENTIFICATION LABELS (KROYTAPE) TO REFLECT NEW CONSTRUCTION.
12. ALL FLEX AND SEALTIGHT CONDUIT SHALL HAVE A GROUND CONDUCTOR.
13. CONDUITS PENETRATING FIRE RATED AREAS SHALL BE SEALED, INSTALLED ON
OUTSIDE OF CONDUIT, WITH APPROVED FIRE STOP MATERIAL TO MAINTAIN THE
SAME FIRE RATING AS ORIGINAL.
14. ALL MATERIALS AND WORKS ARE NEW, UNLESS OTHERWISE NOTED. EXISTING
ELECTRICAL SYSTEMS ARE NOT SHOWN EXCEPT WHERE INTERFACING IS
REQUIRED.
15. MAINTAIN CONTINUITY OF ALL EXISTING CIRCUITS OR PORTIONS THEREOF
AFFECTED BY NEW WORK.
16. CONTRACTOR SHALL VISIT AND FAMILIARIZE AT THE SITE PRIOR TO START OF
PROJECT. COORDINATE WITH OWNER REPRESENTATIVE FOR EXACT LOCATION
OF ALL EQUIPMENT.
17. SEISMIC ANCHORAGE OF ALL NEW AND EXISTING PIPING, CONDUIT,
DUCTWORK, EQUIPMENT, PANELS, ETC. SHALL BE BY FOLLOWING THE
MANUFACTURERS SPECIFICATIONS IN ACCORDANCE WITH THE 2019 CBC AND
THE LATEST ISSUE OF "ENGINEERED SEISMIC BRACING OF SUSPENDED
UTILITIES" AS PUBLISHED BY THE INTERNATIONAL SEISMIC APPLICATION
TECHNOLOGY (ISAT) OPA-0485, MASON INDUSTRIES OPA-0349, TOLCO
OPA-0300, COOPER B-LINE OPA-0114, OR M.W. SAUSSE OPA-0029 OR EQUAL.
18. CONDUIT FITTINGS FOR USE IN EMT RUNS SHALL BE GALVANIZED STEEL
CONNECTORS AND COUPLINGS SHALL BE WATERTIGHT TYPE.
19. ALL SINGLE PHASE CIRCUITS SHALL HAVE A DEDICATED NEUTRAL.
20. ALL CONDUITS SHALL BE PROVIDED AN EQUIPMENT GROUNDING CONDUCTOR
SIZED PER CEC 250.
21. ALL NEW (ADDITIONAL) METALLIC STRUCTURES AND EQUIPMENT FABRICATED
WITH METALLIC MATERIALS SUCH AS GENERATORS, MOTOR FRAME,
ENCLOSURES, ETC, PANELS, RACEWAY SHALL BE PERMANENTLY &
EFFECTIVELY GROUNDED, WHETHER SHOWN ON DRAWING OR NOT. GROUND
CABLE SHALL BE CONNECTED TO COLD WATER PIPE PER CEC 250.52(A)(1), TO
BUILDING GROUNDING PER CEC 250.52(A)(2) OR CONNECTED TO GROUND ROD
PER CEC 250.52(A)(5).
22. OWNER RESERVES THE RIGHT TO REQUIRE MINOR CHANGES IN LOCATION OF
OUTLETS OR EQUIPMENT PRIOR TO ROUGHING-IN WITHOUT INCURRING ANY
ADDITIONAL COST OR CHARGES.
23. DURING CONSTRUCTION, DO NOT INTERRUPT OR IMPEDE OPERATION AND
WORK IN ADJACENT AREAS.
24. UPON COMPLETION OF ALL WORK, THOROUGHLY CLEAN ALL EQUIPMENT AND
DUCTS FROM INSIDE AND OUTSIDE OF EQUIPMENT. REMOVE ALL TRACES OF
SOIL, DUST, LABELS, GREASE, OIL, AND FOREIGN MATERIALS. CLEANUP AND
REMOVE FROM THE PREMISES ALL DEBRIS AND SURPLUS MATERIAL CAUSED
BY THIS WORK.
25. WHERE THERE IS A CONFLICT BETWEEN THE DRAWINGS & ANY RELEVANT
CODES, THE CODES SHALL GOVERN, EXCEPT WHERE THE DRAWINGS INDICATE
A QUALITY LEVEL SUPERIOR TO THAT SPECIFIED BY THE CODES.
26. THE WORD "PROVIDE" MEANS THAT THE CONTRACTOR SHALL FURNISH,
INSTALL, ADJUST, TEST, AND INTEGRATE INTO A COMPLETE SYSTEM THE ITEM
INDICATED INCLUDING ALL HARDWARE, WIRING AND MISCELLANEOUS ITEMS
AS NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM.
GENERAL NOTES
15A, 125V DUPLEX RECEPTACLE (NEMA 5-15R)
SUBSCRIPTS DENOTE THE FOLLOWING:
"WP" - WEATHERPROOFED
DISTANCE
DENOTES EXISTING
CIRCUIT BREAKER
EACH
COPPER
GROUND
MINIMUM
AMPERE
CIRCUIT
LOW VOLTAGE
AMPERE
INTERRUPTING
CAPACITY
ABOVE FINISHED
FLOOR
NOT TO SCALE
WEATHER PROOFWP
SWITCHBOARDSWBD
TYP. TYPICAL
UG UNDERGROUND
SWITCHSW
PULL BOXPB
SLD SINGLE LINE DIAGRAM
POLEP
PANELBOARDPNL
(R) RELOCATED
SUB SUBSTATION
NEW(N)
TIME DELAY
UNLESS
OTHERWISE
NOTED
UON
TRANSFORMERXFMR,
TRANSF.
VD VOLTAGE DROP
TD
DEMOLITION
D
(E)
CB
EA
CU
GND, G
MIN
A
CKT
LV
AIC
AFF
NTS
(D)
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
-DRDR
E0.2
ELECTRICAL PANEL
SCHEDULE A
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24791-8
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS - ATASCADERO
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
FUEL SERVICE
EQUIPMENT
REPLACEMENT
DSH
10/25/2024
100% SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E F e b ru a ry
:1
P
M
F
IL
E L \2
-8
F u e l S e rv ic e E q u ip m e n t R e p la c e m e n t, D
S H
-A \C
A D
\2 E
PANEL SCHEDULE A
NO SCALE
NEW WORK KEYNOTES:
PROVIDE 20A/1P CIRCUIT BREAKER, WITH KAIC TO MATCH
EXISTING (E.G. 10 KAIC).
DEMOLITION KEYNOTES:
DEMOLISH 40/3P CIRCUIT BREAKER PREVIOUSLY SERVING (D)
FUEL DISPENSER.
1 1
LOAD SUMMARY:
PANELBOARD A (208/120V, 3Ø, 4W):
LOAD REMOVED = 11.5 KVA
LOAD ADDED = 1.1 KVA
LOAD DELTA = -10.4 KVA
PER LOAD SUMMARY ABOVE, THE LOAD ON PANELBOARD A HAS
BEEN REDUCED. EXISTING PANELBOARD, INCLUDING
OVERCURRENT PROTECTION AND FEEDERS, IS ADEQUATE TO
SERVE THE CONNECTED LOAD.
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
E1.1
ELECTRICAL DEMOLITION
SITE PLAN
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24791-8
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS - ATASCADERO
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
FUEL SERVICE
EQUIPMENT
REPLACEMENT
DSH
10/25/2024
100% SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
BUILDING KEYPLAN
N
JCCA
D A T E T
IM
E F e b ru a ry
:1
P
M
F
IL
E L \2
-8
F u e l S e rv ic e E q u ip m e n t R e p la c e m e n t, D
S H
-A \C
A D
\2 E
DEMOLITION KEYNOTES:
DEMOLISH POWER AND CONTROLS SERVING (D) MECHANICAL.
PREPARE TO REPLACE IN NEW WORK.
DEMOLISH LEVEL SENSOR AND ASSOCIATED WIRING. PREPARE
TO REPLACE IN NEW WORK.
DEMOLISH DISCONNECT SWITCH AND ASSOCIATED CONDUIT AND
CONDUCTORS. DEMOLISH ASSOCIATED 40A/3P CIRCUIT BREAKER
IN SPACES 19,21,23 OF PANEL A AS SHOWN ON PANEL SCHEDULE
ON E0.3 AND PREPARE TO REPLACE IN NEW WORK.
(E) UNDERGROUND CONDUIT TO
REMAIN
(E) CONDUIT ABOVE GROUND(E) PULLBOX
ELECTRICAL NEW WORK PLAN
SCALE: N0 41 FEET3
1/2" = 1'-0"
BUILDING 810 ABOVE / BUILDING 850 BELOW
(SEE E2.2 FOR FLOOR PLANS)
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
19' (WITHIN 30')
F R
O N
T
A-19,21
A-23
-DRDR
E2.1
ELECTRICAL NEW WORK
SITE PLAN
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24791-8
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS - ATASCADERO
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
FUEL SERVICE
EQUIPMENT
REPLACEMENT
DSH
10/25/2024
100% SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
BUILDING KEYPLAN
N
JCCA
D A T E T
IM
E F e b ru a ry
:1
P
M
F
IL
E L \2
-8
F u e l S e rv ic e E q u ip m e n t R e p la c e m e n t, D
S H -A
\C A D
\2 E
NEW WORK KEYNOTES:
PROVIDE 3/4"C-2#12+1#12G TO (N) FUEL OIL DISPENSER "FOD".
PROVIDE VST EVR NOZZLE. POWER THROUGH "FOD".
PROVIDE TANK-MOUNTED FUEL OIL TRANSFER PUMP "FTP".
PROVIDE 3/4"C-2#12+1#12G BETWEEN "FTP" AND "FOD" IN
EXPLOSION-PROOF, SEALED RMC.
PROVIDE LEVEL SENSOR "LS".
PROVIDE TANK GAUGING PROBE "TP".
PROVIDE OMNTEC TANK GAUGING AND LEAK DETECTION
MONITOR "FMS" WITH WITH TAMPERPROOF COVER. PROVIDE
1"C-2#12 +1#12C IN WALL-MOUNTED EXPLOSION-PROOF, SEALED
RMC.
PROVIDE FUELMASTER LIVE PEDESTAL "FMU". PROVIDE 1"C-2#12
+ 1#12G IN UNDERGROUND EXPLOSION-PROOF, SEALED RMC.
PROVIDE REMOTE ANNUNCIATOR "OA". PROVIDE 1" CONTROL
CONDUIT BETWEEN "OA" AND "FMS" PER MANUFACTURER'S
INSTRUCTIONS.
PROVIDE 1"C CONTROL CONDUIT AND WIRING CONNECTING "FMS"
AND BOTH "LS" AND "TP" PER MANUFACTURER'S
RECOMMENDATIONS.
PROVIDE 1"C CONTROL CONDUIT AND WIRING CONNECTING "FMS"
AND "FMU" PER MANUFACTURER'S RECOMMENDATIONS.
PROVIDE 1"C CONTROL CONDUIT AND CAT6 CONNECTING "FMU"
AND "FOD" PER MANUFACTURER'S RECOMMENDATIONS.
PROVIDE 30A, 120V DISCONNECT SWITCH WITHIN 30' OF ALL FUEL
EQUIPMENT. LABEL DISCONNECT WITH BRANCH CIRCUITS
SERVING (N) "FOD" AND (N) "FMU" AND "FMS" (E.G. CIRCUITS A-19
AND A-21, RESPECTIVELY). SEE E2.2 FOR BUILDING 810 FLOOR
PLAN.
PROVIDE 125V, NEMA 5-15R CONVENIENCE RECEPTACLE WITH
WEATHERPROOF COVER.
(E) PULLBOX
(E) EXPLOSION PROOF
UNDERGROUND CONDUIT
TO REMAIN
(E) UNDERGROUND
CONDUIT FEEDING
CONEX TO REMAIN
ELECTRICAL NEW WORK SITE PLAN
SCALE: N0 41 FEET3
1/2" = 1'-0"
GENERAL NOTES:
1. WORK SHALL COMPLY WITH CLASS 1, DIVISION 2
REQUIREMENTS PER CEC, ESPECIALLY CHAPTERS 501 AND 514.
2. CONDUIT SHALL BE EXPLOSION-PROOF RMC AND SEALED
WITHIN 10' OF DIVISION 2 BOUNDARY AND ANY STUB-UP
LOCATION. FILL PERCENTAGE SHALL NOT EXCEED 25% WITHIN
SEALED PORTION OF CONDUIT. TERMINATIONS SHALL BE
SEALED AT THE POINT OF ENTRANCE PER DETAIL 1/E3.1.
3. WHERE LIQUID OR OTHER CONDENSED VAPOR MAY BE
TRAPPED WITHIN ENCLOSURES, AN APPROVED MEANS SHALL
BE PROVIDED TO PREVENT ACCUMULATION OR PERMIT
PERIODIC DRAINING.
4. COORDINATE WORK WITH MECHANICAL.
5. PROVIDE CONTROL WIRING PER MANUFACTURER'S
RECOMMENDATIONS.
6. PROVIDE TRENCHES PER DETAILS 2/E3.1 AND 3/E3.1 FOR SOIL
AND CONCRETE, RESPECTIVELY.
LS
TP
FMU
FOD
FMS
8OA
10 11
3FTP
(E) EMERGENCY
VENT
(E) VENT
(E) 4000 GAL.
FUEL TANK
BUILDING 810 ABOVE / BUILDING 850 BELOW
(E) ROLL-UP DOOR
(SEE E2.2 FOR FLOOR PLANS)
WP
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
P A
IN
T S
TO
R A G
E
(E) PNL B
STORAGE
(ABOVE BLDG 850,
SAND BLAST AREA)
STORAGE
PAINT SPRAY
BOOTH
PAINT PARLOR
STORAGE
CURING OVEN
PAINT SHOP
(E) PNL A
SAND BLAST AREA
(LOWER LEVEL,
BELOW BLDG 810,
STORAGE 21)
NEW WORK KEYNOTES:
PROVIDE 3/4"C-6#12 + 3#12G.
PROVIDE TWO (2) 20A, 1P CIRCUIT BREAKERS IN PANEL A PER PANEL
SCHEDULE ON E0.2.
PROVIDE ONE (1) 15A, 1P CIRCUIT BREAKER IN PANEL A PER PANEL
SCHEDULE ON E0.2.
PROVIDE CONCRETE FIRESTOP FOR CONDUIT PENETRATION AT
CONCRETE DECK ABOVE PER DETAIL 4/E3.1. LABEL FIRE RATED
PENETRATION PER SPECIFICATIONS.
PROVIDE CONCRETE FIRESTOP AND SLEEVE CP 653, OR APPROVED
EQUAL, FOR CONDUIT PENETRATION AT CMU WALL PER DETAIL 5/E3.1.
LABEL FIRE RATED PENETRATION PER SPECIFICATIONS.
PROVIDE 30A, 120V DISCONNECT SWITCH.
BUILDING 810 ELECTRICAL NEW WORK FLOOR PLAN
SCALE: 0 81 FEET4
1/4" = 1'-0"
GENERAL NOTES:
1. FIRESTOP PENETRATIONS PER DETAILS 4/E3.1 AND
5/E3.1 FOR MINIMUM 2-1/2" AND 4-1/2" CONCRETE
CONDUIT PENETRATIONS RESPECTIVELY.
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24791-8
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS - ATASCADERO
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
FUEL SERVICE
EQUIPMENT
REPLACEMENT
DSH
10/25/2024
100% SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
BUILDING KEYPLAN
N
JCCA
D A T E T
IM
E F e b ru a ry
:1
P
M
F
IL
E L \2
-8
F u e l S e rv ic e E q u ip m e n t R e p la c e m e n t, D
S H
-A \C
A D
\2 E
N
BUILDING 850 ELECTRICAL NEW WORK FLOOR PLAN
SCALE: 0 81 FEET4
1/4" = 1'-0"
N
(E) PULLBOX
OA
FMS
ROUTE CONDUIT TO
BUILDING 810 ABOVE
(E) ROLL-UP DOOR(E) DISCONNECT
PENETRATION FROM
BUILDING 850 BELOW
-DRDR
E2.2
BUILDING 810 AND 850
ELECTRICAL POWER NEW
WORK FLOOR PLANS
BLDG 810
BLDG
BLDG 810
FDN
KEY ELEVATION
NOT TO SCALE
6 (N) DISCONNECT
V2
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
E3.1
ELECTRICAL DETAILS
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24791-8
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS - ATASCADERO
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
FUEL SERVICE
EQUIPMENT
REPLACEMENT
DSH
10/25/2024
100% SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E F e b ru a ry
:2
P
M
F
IL
E L \2
-8
F u e l S e rv ic e E q u ip m e n t R e p la c e m e n t, D
S H
-A \C
A D
\2 E
CONDUIT SEAL FITTINGS DETAIL
NO SCALEE3.1
FILL THICKNESS EQUAL TO CONDUIT
DIAMETER NOT LESS THAN 5/8"
FIBER FILLER
EYS VERTICAL
SEALING COMPOUND
CONDUIT
WYE
SEAL
VERTICAL CONDUIT SEAL
SEALING COMPOUND
FIBER FILLER
SEALING COMPOUND
FIBER FILLER
HORIZONTAL CONDUIT SEAL
WARNING TAPE
M
IN
ADDITIONAL OR LESS CONDUIT REQUIRE SAME SPACING
NOTE:
BACKFILL MATERIAL
SHALL BE 90%
COMPACTION
M
IN
RMC (TYP.)
CONCRETE ASPHALT
OR LANDSCAPE
CONDUITS IN SOIL DETAIL
NO SCALE E3.1
NOTES:
12" MIN SEPARATION BETWEEN DUCT BANK AND ALL OTHER UNDERGROUND
UTILITIES.
PROVIDE TEMPORARY CONDUIT SUPPORTS EVERY 4' FOR CONCRETE
POUR.
"M
IN
"M
IN
"M
IN
3"MIN. 2"MIN. 3"MIN.
REFILL WITH
NATIVE SOIL
COMPACTED
TO 90%
RMC (TYP.)
CAUTION TAPE
12" ABOVE CONCRETE
CAST IN PLACE
CONCRETE
ENCASEMENT (3000
PSI)
PAVE TO MATCH EXISTING CONDITIONS,
INCLUDING BUT NOT LIMITED TO, AC PAVING,
CONCRETE PAVING, CURBS, GUTTERS,
DRIVEWAYS, ETC. PER CIVIL DETAILS.
2 TYP.
System No. C-AJ-1575
SECTION A-A
1. FLOOR OR WALL ASSEMBLY — MIN 2-1/2 IN. (64 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL
CLASSIFIED CONCRETE BLOCKS*. FLOOR MAY ALSO BE CONSTRUCTED OF ANY MIN 6 IN. (152 MM) THICK UL CLASSIFIED HOLLOW CORE PRECAST CONCRETE UNITS*. MAX DIAM OF OPENING IS 30-7/8 IN. (784 MM) WHEN CONCRETE FLOOR OR WALL IS USED AND MAX 7 IN. (178 MM) WHEN PRECAST CONCRETE UNITS ARE USED.
SEE CONCRETE BLOCKS (CAZT) AND PRECAST CONCRETE UNITS (CFTV) CATEGORIES IN THE FIRE
RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
1A. FLOOR ASSEMBLY - (OPTIONAL - NOT SHOWN) — THE FIRE RATED UNPROTECTED CONCRETE AND
STEEL FLOOR ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL D900 SERIES DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND AS SUMMARIZED
BELOW:
A. CONCRETE — MIN 2-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT
(100-150 PCF OR 1600-2400 KG/M3) CONCRETE.
B. STEEL FLOOR AND FORM UNITS* — COMPOSITE OR NON-COMPOSITE MAX 3 IN. (76 MM) DEEP
GALV STEEL FLUTED UNITS AS SPECIFIED IN THE INDIVIDUAL FLOOR-CEILING DESIGN.
2. STEEL SLEEVE — SEE TABLE IN ITEM 4B FOR WHEN SLEEVE IS REQUIRED. ALSO NOT REQUIRED FOR HOLLOW CORE PRECAST CONCRETE FLOORS. SCHEDULE 10 (OR HEAVIER) STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY. SLEEVE MAY EXTEND A MAX OF 8 IN. (203 MM) ABOVE TOP OF FLOOR OR BEYOND EITHER SURFACE OF WALL. AS AN ALTERNATE, IN FLOORS ONLY, MIN 26 GAUGE
GALVANIZED SHEET STEEL SLEEVE PROVIDED WITH A MIN. 26 GAUGE GALVANIZED STEEL SQUARE FLANGE SPOT WELDED TO THE BOTTOM OF THE SLEEVE AND SIZED TO BE A MIN OF 2 IN. (51 MM) LARGER THAN THE
SLEEVE DIAM. THE SHEET METAL SLEEVE IS TO BE CAST IN PLACE AND MAY EXTEND A MAX OF 2 IN. (51 MM) ABOVE THE TOP SURFACE OF THE CONCRETE FLOOR, EXCEPT THAT WHEN SLEEVE IS GREATER THAN NOM 13 IN. (330 MM) DIAM, SLEEVE SHALL BE INSTALLED FLUSH WITH BOTH SURFACES OF FLOOR.
3. THROUGH-PENETRANTS — ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING OR SLEEVE SHALL BE MIN 0 IN. (POINT CONTACT).
SEE TABLE IN ITEM 4B FOR MAX ANNULAR SPACE. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE — NOM 30 IN. (762 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE — NOM 30 IN. (762 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. CONDUIT — NOM 6 IN. (152 MM) DIAM (OR SMALLER) RIGID STEEL CONDUIT.
D. CONDUIT — NOM 4 IN. (102 MM) DIAM (OR SMALLER) ELECTRICAL METALLIC TUBING (EMT).
E. COPPER TUBING — NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER
TUBING.
F. COPPER PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
4. FIRESTOP SYSTEM — THE FIRESTOP SYSTEM SHALL…