23388 Colonial Michilimackinac Powder Magazine Redesign - Construction Drawings-2.pdf

PDF 5 MB Posted

Attached to
751/23388. ABG; MISP -Michilimackinac Powder Mag Redesign
Solicitation number
RFQ - 171 - 240000000264
Issued by
Emmet County, Mackinac Island City, Michigan

About this file

This document contains construction drawings and specifications for the Colonial Michilimackinac Powder Magazine Redesign project in Mackinac Island, Michigan. The project is being managed by the State of Michigan Department of Technology, Management and Budget, State Facilities Administration, Design and Construction Division. The work includes installing new HVAC equipment, ductwork, piping, and controls, as well as electrical system upgrades, in the Powder Magazine Room, Observation Room, and surrounding support spaces. Key mechanical and electrical components are detailed, including new heat pumps, dehumidifiers, supply and return air ductwork, and power panels. General notes emphasize the need to protect the historic site and buildings during construction.

The solicitation for this project is listed as 751/23388.ABG and titled "MISP -Michilimackinac Powder Mag Redesign". Bids must be submitted electronically through the SIGMA VSS system. Bidders are instructed to submit questions via email to the designated point of contact. The contract will be awarded by the State of Michigan and will be specific to the Mackinac Island location in Emmet County.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AC-2AC-1

SD-1 600

24x8 ---

RG-1 600

24x8 ---

CO

CO DEH-1

DX

DX

DX

3/4"

CD

3/4"

CD

1" CD

1-1/4" CD

1" CD

3/4" CD

3/4" CD

3/4" CD

DEH-2

AC-3

CO

8" RA

8" RA

HT

DEH-2

AC-3

12x10 RA

16x8 SA

1 1

TG-1 ----

8x8 ---

TG-1 ----

8x8 ---

8x8 TD 8x8 TD

H

TAC-2

DEH-1

4 4

5 5

DX

CDP-1

8 8

CO

POWDER

MAGAZINE ROOM

OBSERVATION

ROOM

STAIRS

STAIRS

LOBBY

CLOSET

FIREARMS ROOM

STAIRS

TG-2 ----

8x8 ---

T1 AC-110

MECHANICAL KEY NOTES

INSTALL NEW AC UNIT, CONTROLS, THERMOSTAT, AND ALL

ASSOCIATED ACCESSORIES PER THE MANUFACTURER'S

INSTALLATION INSTRUCTIONS IN THE LOCATION SHOWN.

INSTALL NEW DEHUMIDIFIER, CONTROLS, HUMIDISTAT, AND

ALL ASSOCIATED ACCESSORIES PER THE MANUFACTURER'S

INSTALLATION INSTRUCTIONS IN THE LOCATION SHOWN.

FASTEN NEW DEHUMIDIFIER TO UNISTRUT AND SET ON

EXISTING GRADE IN THE DISPLAY AREA/ EXISTING FLOOR IN

THE STORAGE SPACE.

INSTALL NEW SUPPLY AIR DUCTWORK, SUPPLY DIFFUSERS,

RETURN AIR DUCTWORK, RETURN GRILLES, AND ALL

ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN.

CONTRACTOR TO PRIME AND PAINT SUPPLY DIFFUSERS AND

RETURN GRILLES. CONTRACTOR TO COORDINATE THE COLOR

FOR THE NEW DIFFUSERS AND GRILLES WITH THE OWNER.

INSTALL NEW TRANSFER AIR DUCTWORK, TRANSFER GRILLES,

AND ALL ASSOCIATED ACCESSORIES IN THE LOCATION

SHOWN. INSTALL NEW TRANSFER GRILLES BELOW DISPLAY

LEDGE APPROXIMATELY 4" AFF. CONTRACTOR TO PAINT AND

PRIME TRANSFER GRILLES FACING THE PUBLIC SPACE.

COORDINATE COLOR OF NEW TRANSFER GRILLES WITH

OWNER.

INSTALL NEW CONDENSATE PIPING AND ALL ASSOCIATED

ACCESSORIES IN THE LOCATION SHOWN. MODIFY THE

EXISTING CONDENSATE EXTERIOR WALL PENETRATION AS

REQUIRED TO BE REUSED FOR THE ROUTING OF THE NEW

CONDENSATE OUT OF THE BUILDING. PATCH EXISTING WALL

PENETRATION TO MATCH EXISTING AND SEAL WATER TIGHT.

INSTALL NEW DX PIPING AND ALL ASSOCIATED ACCESSORIES

IN THE LOCATION SHOWN.

ROUTE PIPING TIGHT TO WALL TO BE OUT OF VIEW INSIDE THE

DISPLAY. PIPING SHOWN AWAY FROM THE WALL FOR CLARITY.

INSTALL NEW AC UNIT, PIPING, AND ALL ASSOCIATED

ACCESSORIES AS LOW AS POSSIBLE BEHIND THE DISPLAY

LEDGE TO HAVE THE UNIT OUT OF VIEW INSIDE THE DISPLAY.

INSTALL NEW CONDENSATE PUMP, CONDENSATE PIPING, AND

ALL ASSOCIATED ACCESSORIES PER THE MANUFACTURER'S

INSTALLATION INSTRUCTIONS IN THE LOCATION SHOWN.

INSTALL NEW THERMOSTATS AND HUMIDISTAT LOW BEHIND

THE DISPLAY LEDGE TO BE OUT OF VIEW INSIDE THE DISPLAY.

MOUNT NEW THERMOSTATS AND HUMIDISTAT IN LOCATION SO

THEY CAN BE EASILY ACCESSED BY THE HINGED DISPLAY

WINDOWS.

INSTALL NEW RETURN GRILLE APPROXIMATELY 6" AFF.

INSTALL NEW SUPPLY DIFFUSER APPROXIMATELY 6" BELOW

CLOSET CEILING SPACE.

ROUTE NEW DX PIPING UP TO ATTIC THROUGH FIRST FLOOR

STAIR CLOSET.

INSTALL AC-3 ON MANUFACTURER PROVIDED STAND.

INSTALL NEW LOCK BOX AROUND NEW THERMOSTAT AND

HUMIDISTAT.

GENERAL MECHANICAL NOTES

1. AFTER ALL NEW WORK HAS BEEN COMPLETED, CONTRACTOR TO

PATCH, PRIME, AND PAINT CEILING AND WALLS AS REQUIRED TO

MATCH EXISTING.

2. CONTRACTOR TO REMOVE AND REINSTALL WOOD CEILING AS

REQUIRED TO COMPLETE THEIR WORK.

3. ALL NEW EQUIPMENT, DUCTWORK, PIPING, AND ALL ASSOCIATED

ACCESSORIES IS TO BE INSTALLED IN CLOSET SPACES, CEILING,

SPACES, BULKHEADS, ETC. TO BE CONCEALED FROM VIEW.

4. CONTRACTOR TO TAKE ALL APPROPRIATE MEASURES TO

PROTECT/PRESERVE THE EXISTING HISTORICAL SITE,

HISTORICAL ARTIFACTS, HISTORICAL DISPLAYS, AND ALL

HISTORICAL BUILDINGS DURING ALL ASPECTS OF

CONSTRUCTION. CONTRACTOR TO USE TEMPORARY WALLS,

PROTECTIVE COVERINGS, AND OTHER ASSOCIATED MEASURES

TO ENSURE FULL PROTECTION OF HISTORICAL ITEMS DURING

ALL ASPECTS OF CONSTRUCTION. CONTRACTOR TO PROVIDE A

DETAILED PLAN OF PROCEDURES AND ACTIONS THAT WILL BE

USED FOR PROTECTIVE EFFORTS TO THE MACKINAC STATE

HISTORIC PARKS TEAM FOR THEIR APPROVAL PRIOR TO

STARTING CONSTRUCTION.

AC-2AC-1

SD-1 600

24x8 ---

RG-1 600

24x8 ---

CO

CO DEH-1

DX

DX

DX

3/4"

CD

3/4"

CD

1" CD

1-1/4" CD

1" CD

3/4" CD

3/4" CD

3/4" CD

DEH-2

AC-3

CO

8" RA

8" RA

HT

DEH-2

AC-3

12x10 RA

16x8 SA

1 1

TG-1 ----

8x8 ---

TG-1 ----

8x8 ---

8x8 TD 8x8 TD

H

TAC-2

DEH-1

4 4

5 5

DX

CDP-1

8 8

CO

POWDER

MAGAZINE ROOM

OBSERVATION

ROOM

STAIRS

STAIRS

LOBBY

CLOSET

FIREARMS ROOM

STAIRS

TG-2 ----

8x8 ---

T1 AC-110

TG-1

FILTER SECTION

TG-2

8x8 TD

X-DISPLAY

LEDGE

TG-2

X-DISPLAY

LEDGE

TG-2

BOTTOM OF TG-2

APPROX. 4" AFF (TYP.)

X-DISPLAY

VIEWING FLOOR

1 TRANSFER GRILLE INSTALLATION DETAIL

SCALE: NTS

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

23436.00

M a t r ix

751/23388.ABG

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P

L A

C H

R

A

D

IR

E C

T O

R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

2/9/2024 CD SET

M-400

DBP

CAT

SOUTH-SOUTHEAST

ROWHOUSE BELOW GRADE

FLOOR PLAN - MECHANICAL

NEW

N SOUTH-SOUTHEAST ROWHOUSE BELOW GRADE FLOOR PLAN - MECHANICAL NEW

SCALE: 1/4" = 1'-0"

0 1 5 10

L-1

DX

DX

DX

HP-3

HP-1

HP-2

WINDOW FRAME. CONTRACTOR TO MODIFY WINDOW OPENING

DX DN

34 HVAC KEY NOTES

INSTALL NEW HEAT PUMP, CONTROLS, DX PIPING, AND ALL

ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN PER

THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. HEAT

PUMP TO BE MOUNTED ON A MANUFACTURER PROVIDED

STAND THAT IS SECURED TO THE ATTIC FLOOR.

INSTALL NEW DX PIPING AND ALL ASSOCIATED ACCESSORIES

IN THE LOCATION SHOWN. ROUTE NEW DX PIPING DOWN TO

BELOW GRADE FLOOR PLAN THOUGH FIRST FLOOR STAIR

CLOSET. SUPPORT DX PIPING WITH MIRO PIPE SUPPORTS

ALONG THE FLOOR.

INSTALL NEW LOUVER AND ALL ASSOCIATED ACCESSORIES

PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS IN

THE EXISTING WINDOW OPENING BEHIND THE SALVAGED

WINDOW FRAME. CONTRACTOR TO MODIFY WINDOW OPENING

AS REQUIRED TO INSTALL NEW LOUVER. LOUVER TO BE

BLACK. LOUVER TO BE INSTALLED TO HAVE THE EXISTING

WINDOW OPENING SEALED WATER TIGHT.

CONTRACTOR TO REINSTALL THE SALVAGED WINDOW FRAME

TO THE OUTSIDE OF THE LOUVER IN THE EXISTING LOCATION

TO HIDE THE NEW LOUVER AND TO MATCH OTHER BUILDINGS

AT THE FACILITY.

GENERAL HVAC NOTES

1. CONTRACTOR TO TAKE ALL APPROPRIATE MEASURES TO

PROTECT/PRESERVE THE EXISTING HISTORICAL SITE,

HISTORICAL ARTIFACTS, HISTORICAL DISPLAYS, AND ALL

HISTORICAL BUILDINGS DURING ALL ASPECTS OF

CONSTRUCTION. CONTRACTOR TO USE TEMPORARY WALLS,

PROTECTIVE COVERINGS, AND OTHER ASSOCIATED

MEASURES TO ENSURE FULL PROTECTION OF HISTORICAL

ITEMS DURING ALL ASPECTS OF CONSTRUCTION.

CONTRACTOR TO PROVIDE A DETAILED PLAN OF

PROCEDURES AND ACTIONS THAT WILL BE USED FOR

PROTECTIVE EFFORTS TO THE MACKINAC STATE HISTORIC

PARKS TEAM FOR THEIR APPROVAL PRIOR TO STARTING

CONSTRUCTION.

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

23436.00

M a t r ix

751/23388.ABG

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P

L A

C H

R

A

D

IR

E C

T O

R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

2/9/2024 CD SET

M-401

DBP

CAT

SOUTH-SOUTHEAST

ROWHOUSE ATTIC FLOOR PLAN

- MECHANICAL NEW

N SOUTH-SOUTHEAST ROWHOUSE ATTIC FLOOR PLAN - MECHANICAL NEW

DEH-3 SD-2 150

8x8 ---

RG-2 150

8x8 ---

3/4" CD

DEH-4

SD-2 150

8x8 ---

RG-2 150

8x8 ---

3/4" CD

CO

CO

8" RA 8" SA

8" RA 8" SA

H

H

2 2

3/4" CD

3/4" CD3

41" CD DN 3

1" CD3

MECHANICAL KEY NOTES

INSTALL NEW DEHUMIDIFIER (IN ATTIC), CONTROLS,

HUMIDISTAT, AND ALL ASSOCIATED ACCESSORIES PER THE

MANUFACTURER'S INSTALLATION INSTRUCTIONS IN THE

LOCATION SHOWN. INSTALL NEW HUMIDISTAT AS HIGH AS

POSSIBLE INSIDE THE DISPLAY ENCLOSURE BEHIND

ENCLOSURE TOP WOODEN FRAME OUT OF VIEW. MOUNT NEW

DEHUMIDIFIER ON UNISTRUT FRAME AND FASTEN TO FLOOR.

INSTALL NEW SUPPLY AIR DUCTWORK, SUPPLY DIFFUSERS,

RETURN AIR DUCTWORK, RETURN GRILLES, AND ALL

ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN.

CONTRACTOR TO PRIME AND PAINT DIFFUSERS AND GRILLES.

CONTRACTOR TO COORDINATE THE COLOR FOR THE NEW

DIFFUSERS AND GRILLES WITH THE OWNER.

CONTRACTOR TO REINFORCE NEW CEILING PENETRATIONS IN

THE ATTIC SPACE AS REQUIRED.

INSTALL NEW CONDENSATE PIPING AND ALL ASSOCIATED

ACCESSORIES IN THE ATTIC IN THE LOCATION SHOWN.

CONTRACTOR TO REINFORCE NEW CEILING PENETRATION IN

THE ATTIC SPACE AS REQUIRED.

ROUTE NEW CONDENSATE PIPING DOWN ON THE EAST SIDE OF

THE EXISTING SCREEN FENCE. COORDINATE EXACT LOCATION

OF THE CONDENSATE PIPE DROP WITH THE OWNER.

CONTRACTOR TO INSULATE AND PROVIDE COLORED PVC

JACKET ON THE CONDENSATE PIPE DROP TO BLEND IN THE

EXISTING BUILDING. COORDINATE PVC JACKET COLOR WITH

OWNER. SEAL NEW PIPE PENETRATION TO SEAL WATER TIGHT

AND MATCH EXISTING.

GENERAL MECHANICAL NOTES

1. AFTER ALL NEW WORK HAS BEEN COMPLETED, CONTRACTOR TO PATCH,

PRIME, AND PAINT CEILING AND WALLS AS REQUIRED TO MATCH EXISTING.

2. ALL NEW EQUIPMENT, DUCTWORK AND PIPING TO BE INSTALLED IN THE ATTIC

SPACE TO BE CONCEALED FROM VIEW.

3. CONTRACTOR TO PAINT NEW DIFFUSERS AND GRILLES. CONTRACTOR TO

COORDINATE NEW SUPPLY DIFFUSER AND RETURN GRILLE COLORS WITH

OWNER PRIOR TO ORDERING.

4. CONTRACTOR TO TAKE ALL APPROPRIATE MEASURES TO PROTECT/PRESERVE

THE EXISTING HISTORICAL SITE, HISTORICAL ARTIFACTS, HISTORICAL

DISPLAYS, AND ALL HISTORICAL BUILDINGS DURING ALL ASPECTS OF

CONSTRUCTION. CONTRACTOR TO USE TEMPORARY WALLS, PROTECTIVE

COVERINGS, AND OTHER ASSOCIATED MEASURES TO ENSURE FULL

PROTECTION OF HISTORICAL ITEMS DURING ALL ASPECTS OF CONSTRUCTION.

CONTRACTOR TO PROVIDE A DETAILED PLAN OF PROCEDURES AND ACTIONS

THAT WILL BE USED FOR PROTECTIVE EFFORTS TO THE MACKINAC STATE

HISTORIC PARKS TEAM FOR THEIR APPROVAL PRIOR TO STARTING

CONSTRUCTION.

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

23436.00

M a t r ix

751/23388.ABG

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P

L A

C H

R

A

D

IR

E C

T O

R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

2/9/2024 CD SET

M-402

DBP

CAT

SOUTHEAST ROWHOUSE FLOOR

PLAN - MECHANICAL NEW

N SOUTHEAST ROWHOUSE FLOOR PLAN - MECHANICAL NEW

SCALE: 1/2" = 1'-0"

0 1 5

FCPS

V

M C

VI

AV

B

C

DC

M

B

KP

SSCP

CR

SS

AS

TS

G

NCC

M P

E

A L B1 B2

S

SRS

X

X

X

CB

EMERGENCY PUSH STATION

CODE BLUE STATION

TVSS

VFD

TRANSIENT VOLTAGE SURGE SUPPRESSION

VARIABLE FREQUENCY DRIVE

GLASS BREAK

DS

DUPLEX RECEPTACLE

TEACHER STATION

ADMINISTRATION STATION

STUDENT STATION

CARD READER

CARBON MONOXIDE DETECTOR

H

DOCK LIGHT FIXTURE

CONTROL MODULE

S

TELEPHONE / DATA OUTLET

DUTY STATION

STAFF STATION

STAFF REGISTER STATION

DOME LIGHT

DUAL BED STATION

SINGLE BED STATION

BED / LIGHT INTERFACE

PENDENT INTERFACE

EMERGENCY PULL STATION

MASTER STATION

NURSE CALL CONTROLLER

NURSE CALL

ADDENDUM NOTE

PLAN NOTE

DEMOLITION NOTE

THREE PHASE MOTOR

BELL

AUDIO / VIDEO INPUT

VIDEO INPUT

WALL MOUNTED SPEAKER / CLOCK COMBO

WALL MOUNTED SPEAKERS

DUAL FACE CLOCK

CCTV CONTROL PANELCCTV

SECURITY SYSTEM CONTROL PANEL

KEY PAD

BEAM DETECTOR

MOTION DETECTOR

DOOR CONTACT

CAMERA

MONITOR MODULE

FIRE CONTROL POWER SUPPLY

VISUAL ONLY UNIT

ELECTRICAL SYMBOLS LEGEND

DH

V

S

C

M

I

J

SINGLE RECEPTACLE (120 VOLT)

EMERGENCY RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

SINGLE FACE CLOCK

FLUSH FLOOR BOX

SURFACE FLOOR BOX

SPECIAL EQUIPMENT RECEPTACLE

TELEPHONE OUTLET

DATA OUTLET

POWER POLE

JUNCTION BOX

WALL JUNCTION BOX

PULL (JUNCTION) BOX

UNDERFLOOR JUNCTION BOX

OUTLETS

LIGHT FIXTURE

STRIP FIXTURE

IN-GRADE LIGHT FIXTURE

SPOTLIGHT (number of heads shown) EXIT SIGN (face & direction as shown)

WALL MOUNT LIGHT FIXTURE

CEILING LIGHT FIXTURE

TRACK & FIXTURE

STREET TYPE POLE FIXTURE

POLE MOUNTED LIGHT FIXTURE

EXTERIOR WALL MOUNT LIGHT FIXTURE

WALLPACK LIGHT FIXTURE

SPECIAL PURPOSE LIGHT FIXTURE

HIGH BAY LIGHT FIXTURE

EMERGENCY EGRESS LIGHT FIXTURE

(number of heads shown)

EMERGENCY LIGHT FIXTURE

FIXTURES

SWITCHES

SINGLE-POLE SWITCH

DIMMER SWITCH

TIME SWITCH

KEY SWITCH

MANUAL MOTOR SWITCH

THERMAL OVERLOAD SWITCH

SWITCH WITH PILOT LIGHT

FOUR-WAY SWITCH

THREE-WAY SWITCH

CIRCUITRY and RACEWAYS

UNDERFLOOR DUCT

BUS DUCT

PLUGMOLD AS SPECIFIED

WIREMOLD AS SPECIFIED

FLEXIBLE PIGTAILS/CONNECTIONS

"CONDUIT RUN CONTINUES" INDICATION

END OF CONDUIT RUN, CAP AND STAKE

END OF CONDUIT RUN

HOME RUN (with circuit numbers)

CONDUIT STUB DOWN

CONDUIT STUB UP

CONDUIT INSTALLED

CONDUIT INSTALLED

MECHANICAL

ELECTRIC WATER HEATER

ELECTRIC UNIT HEATER

PIPE TRACE HEATER

RESISTANCE HEATER, KW SHOWN

SINGLE PHASE MOTOR

SOUND and SIGNAL

INTERCOM OUTLET

MICROPHONE OUTLET

TELEVISION OUTLET

CHIME

BUZZER

VOLUME CONTROL

SPEAKER

SERVICE and EQUIPMENT

THERMOSTAT

CAPACITOR

ENCLOSED CIRCUIT BREAKER

TRANSFER SWITCH

WIREWAY

GROUND CONNECTION PER N.E.C.

TELEPHONE TERMINAL BOARD

GENERATOR, KW SHOWN

CURRENT TRANSFORMERS

UTILITY METER, AS REQUIRED

WEATHERHEAD

PANELBOARD, FLUSH MOUNTED

PANELBOARD, SURFACE MOUNTED

COMB. STARTER

MAGNETIC STARTER

DISCONNECT SWITCH

TRANSFORMER

CONTROL

xxVA connection by x/C) IRRIGATION CONTROLLER (120 volt

LIGHTING CONTACTOR

CONTROL TRANSFORMER

buttons indicated) PUSHBUTTON STATION (number of TIME CLOCK (24 hour U.O.N.)

PHOTOCELL (voltage as required)

HUMIDISTAT

FIRE ALARM

TAMPER SWITCH (furnished by FP/C) FLOW SWITCH (furnished by FP/C)

FIREFIGHTER COMMUNICATION JACK

MAGNETIC DOOR HOLDER

REMOTE INDICATING LIGHT, CLG. MTD.

REMOTE INDICATING LIGHT, WALL MTD.

END OF LINE DEVICE

ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

PULL STATION

SPEAKER & LIGHT

SPEAKER

HORN

DUCT SMOKE DETECTOR

HEAT DETECTOR

SMOKE DETECTOR

HORN & LIGHT

DESIGNATIONS

(by E.C.)

(by others)

TT

FACP

ANN

EOL

G

WW

PC

CT

TS

T

H

TC

IC

F

FC

F

T

1,3

OR

PM

WM

BD

UFD

B

F S

J

J

D

WH

PP

J

SWITCH STYLE OCCUPANCY SENSOROC

DIGITAL TIME SWITCH

POWER PACK

DUAL TECHNOLOGY SENSOR - 360° - 500 SQ FT

DUAL TECHNOLOGY SENSOR - 360° - 1000 SQ FT

ULTRASONIC SENSOR - 360° - 2 CIRCUIT

OCCUPANCY SENSOR / PHOTOCELL

WALL MOUNT DUAL TECHNOLOGY SENSOR

OS5

OS4

T

OS2

OS3

OS1

PP

DUCT SMOKE DETECTORF/S

CEILING MOUNTED WIFI

DIGITAL EQUIPMENT METER, AS REQUIRED

M

POLE

PUMP

PANEL

P

PNL

PVC

PRV-

P-

PB

POLY VINYL CLORIDE

POWER ROOF VENTILATOR

PULL BOX

GENERAL CONTRACTOR

GROUND

HUMIDIFIERH-

GND

GFI

GC

GROUND FAULT INTERUPTER

ABBREVIATIONS LEGEND

POWER

SWITCH

RECEPT

SF-

SWBD

TCC

SPEC

SW

RGC

RTU-

PWR

VOLTS

WATTS

UF

V

W

UL

VL

UNO

UH-

TS

TYP

TR

ROOF TOP UNIT

RECEPTACLE

SWITCHBOARD

UNDER FLOOR

SPECIFICATIONS

RIGID GALVANIZED STEEL CONDUIT

UNLESS NOTED OTHERWISE

UNDERWRITERS' LABORATORIES, INC.

TAMPER PROOF RECEPTACLE

TAMPER PROOF SWITCH

TEMPERATURE CONTROL CONTRACTOR

VERIFY LOCATION WITH OWNER

TYPICAL

UNIT HEATER

SUPPLY FAN

WITH

WITHOUT

W/

XFMR

W/O

WP

TRANSFORMER

WEATHER PROOF

HOUR

LIGHT

JUNCTION BOX

LIGHT CONTROL

ISOLATED GROUND

HORSEPOWER

MINIMUM

MOUNT

MAKE-UP AIR UNIT

MOTOR CONTROL CENTER

MAIN LUG ONLY

MOUNTED

MOUNTING

MAXIMUM

LIGHTING

LT FLEX

MTD

MUAU-

MTG

MLO

MIN

MT

MC

MAX

MCC

LTG

IG

LC

LT

IMC

JB

HR

HVAC

HOA

HP

NORMALLY CLOSED

NOT IN CONTRACT

NORMALLY OPEN

NOT TO SCALE

NIGHT LIGHTNL

NTS

NO

NIC

NC

HAND-OFF-AUTO SELECTOR SWITCH

HEATING/VENTILATING/AIR CONDITIONING

INTERMEDIATE METAL CONDUIT

LIQUID TIGHT FLEXIBLE METAL CONDUIT

MECHANICAL CONTRACTOR

HID HIGH INTENSITY DISCHARGE

A

AC

AFF

ACU-

AHJ

AHU-

AS

B-

BC

AIC

ATS

BLDG

CHLR-

CND (C)

CKT BKR

CKT

CUH-

CU-

DISC

DFU-

EF-

EC

DWH-

EBB-

DWG

CT-

EXIST (E)

EWC

FLEX

FLA

FLR

FSES

FLUOR

EMT

ABOVE FINISHED FLOOR

AIR CONDITIONING UNIT

AMPS

ABOVE COUNTER

AIR HANDLING UNIT

AUTOMATIC TRANSFER SWITCH

AMPS INTERUPTING CAPACITY

AUTHORITY HAVING JURISDICTION

ABOVE SHELF

BOILER

BUILDING

BELOW COUNTER

CHILLER

DOMESTIC WATER HEATER

CABINET UNIT HEATER

CIRCUIT

CIRCUIT BREAKER

CONDUIT

CONDENSING UNIT

COOLING TOWER

DUCT FURNACE

DRAWING

DISCONNECT

FOOD SERVICE EQUIP. SUPPLIER

ELECTRIC WATER COOLER

ELECTRICAL CONTRACTOR

ELECTRIC BASEBOARD

ELECTRICAL METALLIC TUBING

EXISTING

EXHAUST FAN

FLOOR

FLUORESCENT

FLEXIBLE CONDUIT

FULL LOAD AMPS

EM EMERGENCY

F/S FIRE/SMOKE

FU- FURNACE

1. ALL WALL AND FLOOR PENETRATIONS ARE TO BE SEALED TO MAINTAIN ORIGINAL

RATING.

2. ALL CONDUITS TO BE FIELD ROUTED ALONG EXISTING PIPING AND STRUCTURAL

STEEL.

3. THE DIVISION 26 CONTRACTORS SHALL VISIT THE PROJECT AND DETERMINE THE

EXACT EXTENT OF THE DEMOLITION WORK REQUIRED BEFORE BIDDING THE PROJECT.

4. REMOVE ALL EXISTING OBSOLETE EXPOSED CONDUIT, WIRE AND UNUSED EQUIPMENT

WHERE WORK IS BEING DONE EXCEPT ITEMS NOTED OTHERWISE.

5. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF OLD WORK,

SURFACES SHALL BE PATCHED TO MATCH ADJACENT.

6. EXISTING WORK WHICH IS PRESENTLY CONCEALED AND WHICH WILL REMAIN

CONCEALED AND DOES NOT INTERFERE WITH ANY NEW WORK OF ANY TRADE NEED

NOT BE REMOVED. HOWEVER, ALL CONDUIT SHALL BE CAPPED BELOW FINISH

SURFACE AND THEN PATCHED TO MATCH, OR AS NOTED.

7. EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED OR ENLARGED

TO SUIT THE NEW SYSTEMS AS REQUIRED. PROVIDE ALL REQUIRED CUTTING AND

PATCHING.

8. IF ASBESTOS IS PRESENT, IT WILL BE REMOVED OR RENDERED HARMLESS UNDER

SEPARATE CONTRACT BY THE OWNER.

9. THE DIVISION 26 CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING

WALLS TO MATCH THE ADJACENT SURFACES BEHIND ALL SURFACE MOUNTED

EQUIPMENT.

10. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT VOLTAGES AND LOADS PRIOR TO

INSTALLING SERVICE TO EQUIPMENT.

11. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENT AND CASUAL FIELD

OBSERVATION. REPORT ANY DISCREPANCIES TO ENGINEER FOR CLARIFICATION.

12. CONTRACTOR TO TAKE ALL APPROPRIATE MEASURES TO PROTECT/PRESERVE THE

EXISTING HISTORICAL SITE, HISTORICAL ARTIFACTS, HISTORICAL DISPLAYS, AND

HISTORICAL BUILDINGS DURING ALL ASPECTS OF CONSTRUCTION. CONTRACTOR TO

USE TEMPORARY WALLS, PROTECTIVE COVERINGS, AND OTHER ASSOCIATED

MEASURES TO ENSURE FULL PROTECTION OF HISTORICAL ITEMS DURING ALL

ASPECTS OF CONSTRUCTION. CONTRACTOR TO PROVIDE A DETAILED PLAN OF

PROCEDURES AND ACTION THAT WILL BE USED FOR PROTECTIVE EFFORTS TO THE

MACKINAC STATE HISTORIC PARK TEAM FOR THEIR APPROVAL PRIOR TO STARTING

CONSTRUCTION.

GENERAL ELECTRICAL NOTES

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

23436.00

M a t r ix

751/23388.ABG

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

2/9/2024 CD SET

E-100

MJTC

JFS

ELECTRICAL

SYMBOLS,

ABBREV,

+ NOTES

UNDER STAIRS

1 1

1 1 1 1

1 1

1 1

CONDENSATE

PUMP

DEHUMIDIFIER

DEHUMIDIFIER

PANEL 3

POWDER

MAGAZINE ROOM

OBSERVATION

ROOM

STAIRS

STAIRS

LOBBY

CLOSET

FIREARMS ROOM

STAIRS

EXISTING LIGHT FIXTURE TO REMAIN.

EXISTING DEVICE TO REMAIN.

EXISTING EQUIPMENT TO REMAIN.

DISCONNECT & REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED

CONDUIT & WIRE.

DISCONNECT & REMOVE EXISTING PANEL FOR INSTALLATION OF NEW 30

CIRCUIT PANEL. EXISTING ASSOCIATED CONDUIT & WIRE TO REMAIN.

DISCONNECT & RELOCATE EXISTING LIGHT FIXTURE. EXTEND CONDUIT &

WIRE TO NEW LOCATION.

DEMOLITION NOTES

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

23436.00

M a t r ix

751/23388.ABG

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

2/9/2024 CD SET

E-300

MJTC

JFS

ELECTRICAL

DEMOLITION

FLOOR PLAN

N ELECTRICAL - FLOOR PLAN - LIGHTING

1 1

1EX

EX EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX EX EX EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EXEX

EX

EX

EX

EX

POWDER

MAGAZINE ROOM

OBSERVATION

ROOM

STAIRS

STAIRS

LOBBY

CLOSET

FIREARMS ROOM

STAIRS

ELECTRICAL KEY NOTES

RELOCATED LIGHT FIXTURE.1

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

23436.00

M a t r ix

751/23388.ABG

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

2/9/2024 CD SET

E-400

MJTC

JFS

ELECTRICAL

FLOOR PLAN

NEW LIGHTING

N ELECTRICAL - FLOOR PLAN - LIGHTING

EX EX

DEH-1

120V-1Ø, 5.1A

AC-1

DEH-2

120V-1Ø, 5.1A

AC-3

AC-2

FED FROM

HP-1

FED FROM

HP-2

FED FROM

HP-3

PNL3-26

PNL3-28

NEW PANEL 3

CDP-1

120V-1Ø, 1.5FLA

PNL3-17

POWDER

MAGAZINE ROOM

OBSERVATION

ROOM

STAIRS

STAIRS

LOBBY

CLOSET

FIREARMS ROOM

STAIRS

HP-1

240V-1Ø, 10FLA

HP-2

240V-1Ø, 10FLA

HP-3

240V-1Ø, 16.1FLA

PNL3-22,24

PNL3-25,27

PNL3-21,23

DEH-3

120V-1Ø, 5.1A

DEH-4

120V-1Ø, 5.1A

PNL4-11

PNL4-13

ELECTRICAL KEY NOTES

CONTRACTOR SHALL PROVIDE A NEW 100A ,120/240V-1Ø, 3W PANEL.

CONTRACTOR SHALL RECONNECT ALL EXISTING FEEDERS AND BRANCH

CIRCUITS.

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

23436.00

M a t r ix

751/23388.ABG

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

2/9/2024 CD SET

E-500

MJTC

JFS

ELECTRICAL

FLOOR PLAN

NEW POWER

N ELECTRICAL - SOUTH-SOUTHEAST ROWHOUSE BELOW GRADE FLOOR PLAN - POWER

SCALE: 1/4" = 1'-0"

0 1 5 10

N ELECTRICAL - SOUTH-SOUTHEAST ROWHOUSE ATTIC FLOOR PLAN - POWER

SCALE: 1/4" = 1'-0"

0 1 5 10

N ELECTRICAL - SOUTHEAST ROWHOUSE DISPLAY CASES - POWER

PANEL

EXISTING

MDP

240/120V 1Ø, 3W

400 MCB

M PANEL

EXISTING

120/240V 1Ø, 3W

200 MCB

PANEL

NEW

120/240V 1Ø, 3W

100 MCB

PANEL

EXISTING

120/240V 1Ø, 3W

100 MCB

UTILITY

PANEL

EXISTING

PRIEST HOUSE

120/240V 1Ø, 3W

200 MCB

P

ELECTRICAL KEY NOTES

CONTRACTOR TO INSTALL NEW 20A-1P BREAKER AS INDICATED. BREAKER

SHALL MATCH EXISTING TYPE.

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

23436.00

M a t r ix

751/23388.ABG

acct. template sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

2/9/2024 CD SET

E-600

MJTC

JFS

ELECTRICAL

RISER DIAGRAM

+ PANEL SCHEDULES

NTS

ELECTRICAL - RISER DIAGRAM

Mech
Sheets and Views
M400-2343600-M-400
M401-2343600-M-400
M402-2343600-M-402
Electrical set 100% CD
E100-2343600-24x36

File details come from the government source that posted it. Updated .