2311 Drawings.pdf

PDF 3 MB Posted

Attached to
Brookside Care Center Fire Protection Piping Modifications
Solicitation number
2311
Issued by
Kenosha County, Kellnersville Village, Wisconsin

About this file

File Summary

This document set comprises technical drawings for fire protection piping modifications at Brookside Care Center in Kenosha, Wisconsin, prepared by Clark Dietz, a licensed design firm in Wisconsin. The project involves the replacement and modification of fire suppression system piping throughout the facility located at 3506 Washington Road, Kenosha, Wisconsin 53144. The work includes demolition of existing fire protection piping in seven residential wings (Wings 100-700) and an administrative area, followed by installation of new piping systems. The new construction specifies 1-1/2" and 4" fire protection piping routed above ceilings and through attic spaces to serve existing sprinkler heads. The project encompasses comprehensive coordination with existing building systems, including HVAC, electrical, structural elements, and recessed lighting. Design compliance is required with Wisconsin SPS 362 and NFPA 13 standards as adopted by Kenosha County. The drawings were issued for bid on March 31, 2023, and include detailed demolition plans (sheets FP1.01-FP1.08) and new installation plans (sheets FP2.01-FP2.08) for each facility section.

The contractor is required to provide complete design and shop drawings prepared by licensed professionals in Wisconsin, along with all calculations and documentation necessary for engineer and authority having jurisdiction approval. General notes specify that contractors must maintain fire sprinkler and fire alarm systems in operation at the end of each workday with no overnight shutdowns permitted. The facility operates as a Class 2 medical facility requiring fire watch for any system shutdowns exceeding four hours. Contractors must coordinate all work to minimize interference with facility operations, manage ceiling tile removal carefully due to return air plenum concerns (maximum three tiles at any given time), and handle all cutting, patching, fire stopping, and supporting infrastructure. The project includes removal of existing 1-1/4" and 3" piping with connections to remaining branch piping and associated sprinkler heads.

View the file

Other files

File Type Posted
2311 Addendum 1.pdf PDF
2311 Addendum 2.pdf PDF
2311 Bid Documents.pdf PDF
Vendor Responsibility Form Construction.pdf PDF
2311 Project Manual - Specifications.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DATE REVISION

PROJECT No.

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

TI

TL

E S

H E

E T

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

G0.01

DWG #### OF #### DWGS

PROJECT LOCATION

KENOSHA COUNTY

GENERAL LOCATION MAP PROJECT LOCATION MAPPROJECT AREA MAP

BROOKSIDE

CARE CENTER

BROOKSIDE

CARE CENTER

Sheet List Table Sheet

Number Sheet Title

G0.01 TITLE SHEET

FP0.01 FIRE PROTECTION GENERAL NOTES, SYMBOLS AND

DETAILS

FP0.02 OVERALL FIRST FLOOR PLAN

FP1.01 ATTIC FIRE PROTECTION DEMOLITION - WING 100

FP1.02 ATTIC FIRE PROTECTION DEMOLITION - WING 200

FP1.03 ATTIC FIRE PROTECTION DEMOLITION - WING 300

FP1.04 ATTIC FIRE PROTECTION DEMOLITION - WING 400

FP1.05 ATTIC FIRE PROTECTION DEMOLITON - WING 500

FP1.06 ATTIC FIRE PROTECTION DEMOLITION - WING 600

FP1.07 ATTIC FIRE PROTECTION DEMOLITION - WING 700

FP1.08 ATTIC FIRE PROTECTION DEMOLITION - ADMIN AREA

FP2.01 ATTIC FIRE PROTECTION PLAN - WING 100

FP2.02 ATTIC FIRE PROTECTION PLAN - WING 200

FP2.03 ATTIC FIRE PROTECTION PLAN - WING 300

FP2.04 ATTIC FIRE PROTECTION PLAN - WING 400

FP2.05 ATTIC FIRE PROTECTION PLAN - WING 500

FP2.06 ATTIC FIRE PROTECTION PLAN - WING 600

FP2.07 ATTIC FIRE PROTECTION PLAN - WING 700

FP2.08 ATTIC FIRE PROTECTION PLAN - ADMIN AREA

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

FI

R

E P

R O

TE

C

TI

O

N G

E N

E R

A L

N O

TE

S

, S Y

M B

O

LS

A N

D D

E

TA

IL

S

FP0.01

DWG #### OF #### DWGS

SYMBOL DESCRIPTION

FIRE PROTECTION LEGENDFIRE PROTECTION GENERAL NOTES

1. THE CONTRACTOR SHALL PROVIDE COMPLETE DESIGN AND DESIGN DRAWINGS FOR THE INSTALLATION OF

THE FIRE SUPPRESSION SYSTEMS IN ACCORDANCE WITH NFPA STANDARDS. THESE DRAWINGS SHALL BE

PREPARED BY A LICENSED PROFESSIONALS IN THE STATE OF WISCONSIN.

1.1. THE DESIGN OF THE FIRE SUPPRESSION SYSTEM SHALL BE IN ACCORDANCE WITH THE FOLLOWING

CODES

1.1.1. WISCONSIN SPS 362 -CURRENT EDITION

1.1.2. NFPA 13 -EDITION ADOPTED BY KENOSHA COUNTY

1.2. THE CONTRACTOR SHALL PROVIDE ALL DRAWINGS, CALCULATIONS, AND ADDITIONAL

DOCUMENTATION AS REQUIRED TO ENGINEER AND AUTHORITY HAVING JURISDICTION FOR

APPROVAL.

2. CONTRACTOR SHALL VERIFY LOCATION OF ALL EXISTING SPRINKLER HEADS AND PIPING INCLUDING, SIZE, FITTINGS AND COUPLINGS. CONTRACTOR SHALL INCLUDE COST ASSOCIATED WITH SHORTER PIPE SECTIONS THAT MAY HAVE TO BE INSTALLED DUE TO LACK OF ACCESS. OWNER MAY ALLOW NEW OPENINGS

TO BE ADDED TO THE EXISTING CEILING.

3. ALL SPRINKLER PIPING SHALL BE ROUTED TO CONSERVE BUILDING SPACE AND ABOVE THE CEILING UNLESS OTHERWISE NOTED. ALL PIPING TO BE EXPOSED SHALL BE CLEARLY DISPLAYED AND LABELED ON CONTRACTOR SUPPLIED SHOP DRAWINGS. WHERE EXPOSED, ALL PIPING SHALL BE RUN BETWEEN OR ADJACENT TO THE STRUCTURE. PIPING SHALL BE INSTALLED ABOVE THE BOTTOM CHORD OF ALL TRUSSES.

4. CONTRACTOR SHALL COORDINATE LOCATION AND ELEVATION OF NEW FIRE PROTECTION PIPING AND SYSTEM WITH EXISTING AND NEW RECESSED AND SURFACE MOUNTED LIGHTS, SMOKE DETECTORS, ALL EXISTING AND NEW CONDUITS, PIPING, DUCTWORK AND OTHER UTILITIES PRIOR TO INSTALLATION.

5. REMOVAL AND REPLACEMENT OF ANY SPRINKLER PIPING AND OR SPRINKLER HEADS REQUIRED TO INSTALL

NEW MAINS SHALL BE INCLUDED IN BIDS SUBMITTED.

6. ALL CUTTING AND PATCHING AS REQUIRED TO INSTALL THE FIRE SUPPRESSION SYSTEM SHALL BE BY THE

CONTRACTOR.

7. NO SPRINKLER PIPING AND/OR SPRINKLER HEADS SHALL BE LOCATED DIRECTLY ABOVE ELECTRICAL

EQUIPMENT.

8. PIPING IS SHOWN IN SCHEMATIC FORM ONLY, CHANGES IN ELEVATION ARE NOT NECESSARILY SHOWN.

ROUTE PIPING IN AN ORDERLY MANNER AS REQUIRED FOR CLEARANCE WITH STRUCTURAL CONDITIONS.

COORDINATE LOCATION OF PIPING WITH OTHER TRADES PRIOR TO INSTALLATION.

9. PROVIDE AND INSTALL SLEEVES FOR ALL PIPING PASSING THROUGH WALLS, AND FLOORS.

10. PROVIDE FIRE STOPPING OR FIRE CAULK AT ALL PENETRATIONS OF FIRE AND/OR SMOKE RATED WALLS, CEILINGS, AND FLOORS. FIELD VERIFY LOCATIONS OF FIRE AND/OR SMOKE RATED WALLS, CEILINGS, AND

FLOORS. ALL EXISTING CORRIDOR WALLS ARE TREATED AS FIRE RATED WALLS.

11. PROVIDE ADEQUATE SUPPORTING SYSTEMS FOR PIPING, EQUIPMENT, AND ACCESSORIES PER NFPA

REQUIREMENTS.

12. ALL CONNECTIONS TO, OR SHUTDOWNS OF EXISTING SYSTEMS SHALL BE COORDINATED WITH THE OWNER

TO PROVIDE MINIMUM INTERFERENCE WITH THEIR OPERATION AND DOWNTIME OF THE SYSTEM.

13. EXISTING FACILITY IS PROVIDED WITH RETURN AIR PLENUM. CONTRACTOR MUST MAKE SURE NO MORE THAN THREE CEILING TILES ARE ALLOWED TO BE REMOVED TO INSTALL NEW PIPING AT ANY GIVEN TIME.

14. EXISTING FACILITY IS A CLASS 2 MEDICAL FACILITY AND FIRE WATCH IS REQUIRED FOR ANY FIRE SPRINKLER OR FIRE ALARM SHUT DOWNS THAT EXTEND OVER FOUR HOURS. CONTRACTOR MUST VERIFY THIS

REQUIREMENT WITH THE STATE OF WISCONSIN.

WALL

FROM END OF

INTERIOR WALL

FIN. FLR.

TEST VALVE

BRANCH LINE

SMOOTH BORE CORROSION

RESISTANT OUTLET.

DISCHARGE OPEN-SITE

ABOVE SUMP.

45° ELBOWM

AX

IM

U

M

'0

PROVIDE WALL

SUPPORT SUPPORT

REQUIRED

12"

D

N.O.

N.C.

MIN.

Ø

AFF

SIDE WALL TYPE SPRINKLER HEAD

DRY PENDENT TYPE SPRINKLER HEAD

UPRIGHT TYPE SPRINKLER HEAD

RECESSED PENDENT TYPE SPRINKLER HEAD

PENDENT TYPE SPRINKLER HEAD

WALL MOUNTED FIRE DEPT CONNECTION

CAP OR BLIND FLANGE

TEE UP

TEE DOWN

RISE OR DROP

ELBOW DOWN

ELBOW UP

DRAIN PIPING

DOMESTIC COLD WATER

FIRE PROTECTION LINEF

EXISTING FIRE PROTECTION LINE(F)

NORMALLY OPEN

NORMALLY CLOSED

MINIMUM

MAXIMUMMAX.

FLOOR DRAINFD-X

DIAMETER

ABOVE FINISHED FLOOR

EXISTING TO BE REMOVED

CONCEALED PIPING PIPING EXPOSED TO VIEW

TERMINATE SLEEVE FLUSH WITH

FINISHED WALL SURFACES

SEAL OR CAULK SLEEVES

THRU FIRE WALLS WITH

RATED MATERIAL

PIPE TO BE CENTERED IN

SLEEVE - DO NOT SUPPORT

FROM SLEEVE

SLEEVE MATERIAL PER SPECIFICATIONS

SIZE SLEEVE TO PASS PIPE

FINISHED ESCUTCHEON PLATE FLUSH

AGAINST WALL AND OF SIZE TO

COMPLETELY COVER OPENING IN

FINISHED WALL SURFACE

NEW CONNECTION TO EXISTING

FIRE ALARM GENERAL NOTES

1. CONTRACTORS WILL BE REQUIRED TO HAVE FIRE SPRINKLER AND FIRE ALARM SYSTEMS IN OPERATION AT

THE END OF EACH WORK DAY. OVER NIGHT SHUT DOWNS WILL NOT BE ALLOWED.

2. SHUTDOWNS OF FIRE SPRINKLER OR FIRE ALARM SYSTEM WILL NEED TO BE COORDINATED AND CALLED INTO DISPATCH AT THE START OF WORK DAY. CONTRACTOR MUST HAVE STAFF THAT CAN OPERATE THE

SYSTEM WITHOUT THE ASSISTANCE OF THE OWNER.

3. SEE BASEMENT PLAN ON THIS SHEET FOR EXISTING TAMPER SWITCH LOCATION AT ZONE ISOLATION VALVES.

4. CONTRACTOR SHALL COORDINATE WITH AHJ FIRE REQUIREMENTS DURING ANY FIRE ALARM SHUTDOWNS

DUE TO CONSTRUCTION.

KEYPLAN

BASEMENT FIRE PROTECTION PLAN3

EXISTING DRY VALVE AND TAMPER SWITCH LOCATION. ONE DRY

SYSTEM BRANCH SERVES WING 100, 200, AND 300. THE OTHER

DRY BRANCH SERVES WINGS 400 THRU 700.

INSPECTORS TEST DRAIN - INTERIOR DRAIN2

INTERIOR WALL SLEEVE DETAIL1

NOT TO SCALE

NOT TO SCALE

0 4' 8' 16' 32'

SCALE 1/16" = 1'

DN

DN

DN

DN

DN

STORAGE

511 MED ROOM

508-A

CHARTING

BATHING

JANITOR

KITCHEN

COUNTRY KITCHEN

103-A

DINING

STAFF CONFERENCE

KITCHEN

DINING

STORAGE

CO

UN

TR

Y

KI

T.

C1

TV ROOM

STORAGE

STORAGE

801-A

PRIVATE DINING

MECH

ACTIVITY

ACTIVITY

SEATING

BISTRO

RN

OFFICE

TV ROOM

STORAGE (EXST)

CONFERENCE

CONFERENCE

DINING

C165

STORAGE

PT/OT OFFICE

CONFERENCE

DINING

C163

JANITOR

KITCHEN

C161

RN

C156

STAFF TLT

SPEECH

SPEECH

ENTRY

CORRIDOR

DINING JC

C160

OXYGEN STORAGE

C159

PT GYM

302-A

UNIT DIRECTOR

DINING

CORRIDOR

CORRIDOR

DINING

COUNTRY KITCHEN

202-A

KITCHEN

CO

UN

TR

Y

KI

T.

C1

IT ROOM

C157

ME

D

RO

OM

C1

ME

D

SU

PP

LY

C1

ELECTRICAL

C154

ST

AF

F

TO

ILE

T

C1

LIQ

UI

D

OX

YG

EN

C1

CORRIDOR

C135

LIVING ROOM

C150

LAUNDRY

C148

TOILET

C147

ACTIVITY

C130

TOILET

C130-B

SOILED LINEN

C129

JANITOR

C128

STORAGE

C167

STORAGE

C166

ACTIVITY

C127

TOILET

C127-B

SOILED LINEN

C126

JANITOR

C125

CORRIDOR

C133

CORRIDOR

C132

LIVING

C144

LAUNDRY

C146

HOUSEKEEPING

STORAGE

C143

TOILET

C142

BATHER SPA

C151

CORRIDOR

C131

MEDITATION

C139

DIRECTOR

C140

VESTIBULE

C100

OFFICE

C138

OFFICE

C137

OFFICE

C136

ACT STORAGE

C130-A

CONFERENCE

C141

ACT STORAGE

C127-A

STAIR 1

ELEVATOR

ENCLOSED ACTIVITY

R134

ACTIVITY STORAGE

R136

TOILET

R135

LIVING

R137

CORRIDOR

R126

COUNTRY KITCHEN

R156

DINING JC

R152

DINING

R157

STORAGE

R159

STAIR 2 SOILED LINEN

R160

SEATING

R128

KITCHEN

R153

RN

R148

MED ROOM

R150

MED SUPPLY

R144

IT ROOM

R145

STAFF TOILET

R146

JANITOR

R147

BATHER SPA

R143

OXYGEN STORAGE

R151

CORRIDOR

R129

CORRIDOR

R130

DINING

R155

LIVING

R140

JAN & HK STORAGE

R139

TOILET

R138

ACTIVITY

STORAGE/OFFICE

R142

VESTIBULE

COUNTRY KITCHEN

R154

SEATING

R131

SOILED LINEN

R162

STAIR 3

CORRIDOR

R125

STORAGE

R158

STORAGE

TOILET (EXST)

DINING JC

TOILET

NAMASTE

TOILET

STORAGE

OFFICE

STORAGE

848-A

STORAGE

850-A

STORAGE

849-A

OFFICE

OFFICE

TRAINING

STORAGE (EXST)

STAFF TLT

OFFICE

PUBLIC TOILET

PUBLIC TOILET

JANITOR

STAFF

CORRIDOR

TV ROOM

MASSAGE

BEAUTY / BARBER

STORAGE

MEDICAL RECORDS

OFFICE

827CONFERENCE

826STAFF

RECEPTION

BANKING

OFFICE

825 WORK ROOM

823 FAMILY ROOM

MED ROOM

204-A

CHARTING

CHARTING

105MED ROOM

105-A

OFFICE

OFFICE

OFFICE

RESIDENT ROOM 1

C124

RESIDENT ROOM 1

C123

RESIDENT ROOM 2

C122

RESIDENT ROOM 2

C121

RESIDENT ROOM 1

C120

RESIDENT ROOM 1

C119 RESIDENT ROOM 2

C118

RESIDENT ROOM 2

C117

RESIDENT ROOM 1

C115 RESIDENT ROOM 1

C113

RESIDENT ROOM 2

C116

RESIDENT ROOM 2

C114

RESIDENT ROOM 1

C112

RESIDENT ROOM 1

C111

RESIDENT ROOM 2

C110

RESIDENT ROOM 2

C109

RESIDENT ROOM 1

C108

RESIDENT ROOM 1

C107

RESIDENT ROOM 2

C106

RESIDENT ROOM 2

C105

RESIDENT ROOM 1

C103

RESIDENT ROOM 1

C101

RESIDENT ROOM

C104

RESIDENT ROOM

C102

RESIDENT ROOM 1

R111

RESIDENT ROOM 1

R109

RESIDENT ROOM 1

R107

RESIDENT ROOM 1

R105

RESIDENT ROOM 1

R103

RESIDENT ROOM 1

R101

RESIDENT ROOM 1

R102

RESIDENT ROOM 1

R104

RESIDENT ROOM 1

R106

RESIDENT ROOM 1

R108

RESIDENT ROOM 1

R110

RESIDENT ROOM 1

R112

RESIDENT ROOM 1

R124

RESIDENT ROOM 1

R122

RESIDENT ROOM 1

R120

RESIDENT ROOM 1

R118

RESIDENT ROOM 1

R116

RESIDENT ROOM 1

R114

RESIDENT ROOM 1

R113

RESIDENT ROOM 1

R115

RESIDENT ROOM 1

R117

RESIDENT ROOM 1

R119

RESIDENT ROOM 1

R121

RESIDENT ROOM 1

R123

WORK ROOM

WAITING

832 STAFF TOILET

CORRIDOR

MAIN ENTRY

MED ROOM

728-A CHARTING

STORAGE

BATHING

JANITOR

MED ROOM

611-A

CHARTING

BATHING

JANITOR

STORAGE

CHARTING

MED ROOM

404-A

BATHING

JANITOR

BEVERAGE

STATION

BEVERAGESTATION

BE

VE

RA

GE

ST

AT

IO

N

BEVERAGE

STATION

SEATING

202-B

SEATING

103A

BOOTH

SEATING

ELECTRICAL

R142-A

TRASH

R132

LIFT STORAGE

R127-B

LIFT STORAGE

R127-A

LIFT STORAGE

R130-B

LIFT STORAGE

R130-A

ADL TOILET

DIRTY LINEN

ACTIVITY

EXAM

ACTIVITY STORAGE

C149

CLOSET

C134-A

LIFT STORAGE

C135-C

LIFT STORAGE

C135-A

ACTIVITY STORAGE

C145

LIFT STORAGE

C133-C

LIFT STORAGE

C133-A

CLEAN LINEN

OT STORAGE

OT GYM

302-B

PASSAGE

SEATING

R133

TOILET

TLT ROOM

TLT ROOM

UNIT CLERK

CLOSET

R134-A

STORAGE

OFFICE

840-A

COLLABORATION

837-A

FA

A

FC

P

DATE REVISION

PROJECT No.

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

O V

E R

A

LL

F

IR

S T

FL

O

O R

P

LA

N

FP0.02

DWG #### OF #### DWGS

0 8' 16' 32' 64'

SCALE 1/32" = 1'

OVERALL FIRST FLOOR PLAN1

EXISTING FIRE ALARM

CONTROL PANEL

EXISTING FIRE ALARM

ANNUNCIATOR PANEL

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

D E

M O

LI

TI

O N

W

IN

G t h

S t t h

F l o o r

K e n o s h a

W I

P H O N E w c l a r k d i e t z c o m

FP1.01

DWG #### OF #### DWGS

NOTES (THIS SHEET)

KEYPLAN

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION DEMOLITION PLAN - WING 1001

KEYNOTES (THIS SHEET)#

DEMO NOTES#

1. REMOVE EXISTING 1-1/4" DRY FIRE PROTECTION PIPING TAKEOFF. EXISTING SPRINKLER HEADS TO

REMAIN PER CONTRACTOR DISCRETION. SEE SHEET FP2.01 FOR NEW WORK.

1. DRY SYSTEM BRANCH TAKEOFFS AND ASSOCIATED SPRINKLER HEADS TO REMAIN UNLESS

OTHERWISE NOTED (TYPICAL).

2. EXISTING SPRINKLER HEADS IN ATTIC TO REMAIN (TYPICAL).

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. REMOVAL OF FP PIPING SHALL INCLUDE OF ALL HANGERS, SUPPORTS, AND ACCESSORIES.

3. PATCH AND PAINT ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

GRID REQUIRED TO INSTALL THEIR WORK. PROVIDE NEW CEILING TILES OR GRID WHERE EXISTING

CEILING TILES OR GRID ARE DAMAGED DURING WORK.

5. CONTRACTOR MAY CHOOSE TO REPLACE EXISTING SPRINKLER HEADS IN THE BRANCH PIPING

WITH NEW FOR EASE OF INSTALLATION.

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

D E

M O

LI

TI

O N

W

IN

G t h

S t t h

F l o o r

K e n o s h a

W I

P H O N E w c l a r k d i e t z c o m

FP1.02

DWG #### OF #### DWGS

NOTES (THIS SHEET)

KEYPLAN

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION DEMOLITION PLAN - WING 2001

KEYNOTES (THIS SHEET)#

DEMO NOTES#

1. REMOVE EXISTING 1-1/4" DRY FIRE PROTECTION PIPING TAKEOFF. EXISTING SPRINKLER HEADS TO

REMAIN PER CONTRACTOR DISCRETION. SEE SHEET FP2.02 FOR NEW WORK.

1. DRY SYSTEM BRANCH TAKEOFFS AND ASSOCIATED SPRINKLER HEADS TO REMAIN UNLESS

OTHERWISE NOTED (TYPICAL).

2. EXISTING SPRINKLER HEADS IN ATTIC TO REMAIN (TYPICAL).

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. REMOVAL OF FP PIPING SHALL INCLUDE OF ALL HANGERS, SUPPORTS, AND ACCESSORIES.

3. PATCH AND PAINT ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

GRID REQUIRED TO INSTALL THEIR WORK. PROVIDE NEW CEILING TILES OR GRID WHERE EXISTING

CEILING TILES OR GRID ARE DAMAGED DURING WORK.

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

D E

M O

LI

TI

O N

W

IN

G t h

S t t h

F l o o r

K e n o s h a

W I

P H O N E w c l a r k d i e t z c o m

FP1.03

DWG #### OF #### DWGS

NOTES (THIS SHEET)

KEYPLAN

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION DEMOLITION PLAN - WING 3001

KEYNOTES (THIS SHEET)#

DEMO NOTES#

1. REMOVE 1-1/4" DRY FIRE PROTECTION PIPING TAKEOFF. EXISTING SPRINKLER HEADS TO REMAIN

PER CONTRACTOR DISCRETION. SEE SHEET FP2.03 FOR NEW WORK.

1. DRY SYSTEM BRANCH TAKEOFFS AND ASSOCIATED SPRINKLER HEADS TO REMAIN UNLESS

OTHERWISE NOTED (TYPICAL).

2. EXISTING 1-1/2" DRY FIRE PROTECTION BRANCH PIPING AND ASSOCIATED SPRINKLER HEADS TO

REMAIN.

3. EXISTING SPRINKLER HEADS IN ATTIC TO REMAIN (TYPICAL).

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. REMOVAL OF FP PIPING SHALL INCLUDE OF ALL HANGERS, SUPPORTS, AND ACCESSORIES.

3. PATCH AND PAINT ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

GRID REQUIRED TO INSTALL THEIR WORK. PROVIDE NEW CEILING TILES OR GRID WHERE EXISTING

CEILING TILES OR GRID ARE DAMAGED DURING WORK.

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

D E

M O

LI

TI

O N

W

IN

G t h

S t t h

F l o o r

K e n o s h a

W I

P H O N E w c l a r k d i e t z c o m

FP1.04

DWG #### OF #### DWGS

NOTES (THIS SHEET)

KEYPLAN

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION DEMOLITION PLAN - WING 4001

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. REMOVAL OF FP PIPING SHALL INCLUDE OF ALL HANGERS, SUPPORTS, AND ACCESSORIES.

3. PATCH AND PAINT ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

GRID REQUIRED TO INSTALL THEIR WORK. PROVIDE NEW CEILING TILES OR GRID WHERE EXISTING

CEILING TILES OR GRID ARE DAMAGED DURING WORK.

KEYNOTES (THIS SHEET)#

DEMO NOTES#

1. REMOVE EXISTING 3" FIRE PROTECTION MAIN TO LIMITS SHOWN. ALLOW FOR CONNECTION TO

EXISTING PIPING.

2. SEE SHEET 1/FP1.08 FOR PIPING CONTINUATION.

1. SPRINKLER BRANCH PIPING TO REMAIN (TYPICAL).

2. EXISTING SPRINKLER HEADS IN ATTIC TO REMAIN (TYPICAL).

1/FP1.08

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

D E

M O

LI

TO

N

W

IN

G t h

S t t h

F l o o r

K e n o s h a

W I

P H O N E w c l a r k d i e t z c o m

FP1.05

DWG #### OF #### DWGS

NOTES (THIS SHEET)

KEYPLAN

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION DEMOLITION PLAN - WING 5001

KEYNOTES (THIS SHEET)#

DEMO NOTES#

1. REMOVE EXISTING 3" FIRE PROTECTION MAIN TO LIMITS SHOWN. ALLOW FOR CONNECTION TO

EXISTING PIPING.

2. SEE SHEET 1/FP1.08 FOR PIPING CONTINUATION.

1. SPRINKLER BRANCH PIPING TO REMAIN (TYPICAL).

2. EXISTING SPRINKLER HEADS IN ATTIC TO REMAIN (TYPICAL).

1/FP1.08

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. REMOVAL OF FP PIPING SHALL INCLUDE OF ALL HANGERS, SUPPORTS, AND ACCESSORIES.

3. PATCH AND PAINT ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

GRID REQUIRED TO INSTALL THEIR WORK. PROVIDE NEW CEILING TILES OR GRID WHERE EXISTING

CEILING TILES OR GRID ARE DAMAGED DURING WORK.

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

D E

M O

LI

TI

O N

W

IN

G t h

S t t h

F l o o r

K e n o s h a

W I

P H O N E w c l a r k d i e t z c o m

FP1.06

DWG #### OF #### DWGS

NOTES (THIS SHEET)

KEYNOTES (THIS SHEET)#

KEYPLAN

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION DEMOLITION PLAN - WING 6001

DEMO NOTES#

1. REMOVE EXISTING 3" FIRE PROTECTION MAIN TO LIMITS SHOWN. ALLOW FOR CONNECTION TO

EXISTING PIPING.

2. SEE SHEET 1/FP1.08 FOR PIPING CONTINUATION.

1. SPRINKLER BRANCH PIPING TO REMAIN (TYPICAL).

2. EXISTING SPRINKLER HEADS IN ATTIC TO REMAIN (TYPICAL).

1/FP1.08

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. REMOVAL OF FP PIPING SHALL INCLUDE OF ALL HANGERS, SUPPORTS, AND ACCESSORIES.

3. PATCH AND PAINT ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

D E

M O

LI

TI

O N

W

IN

G t h

S t t h

F l o o r

K e n o s h a

W I

P H O N E w c l a r k d i e t z c o m

FP1.07

DWG #### OF #### DWGS

NOTES (THIS SHEET)

KEYPLAN

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION DEMOLITION PLAN - WING 7001

KEYNOTES (THIS SHEET)#

DEMO NOTES#

1. REMOVE EXISTING 3" FIRE PROTECTION MAIN TO LIMITS SHOWN. ALLOW FOR CONNECTION TO

EXISTING PIPING.

2. SEE SHEET 1/FP1.08 FOR PIPING CONTINUATION.

1. SPRINKLER BRANCH PIPING TO REMAIN (TYPICAL).

2. EXISTING SPRINKLER HEADS IN ATTIC TO REMAIN (TYPICAL).

1/FP1.08

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. REMOVAL OF FP PIPING SHALL INCLUDE OF ALL HANGERS, SUPPORTS, AND ACCESSORIES.

3. PATCH AND PAINT ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

D E

M O

LI

TI

O N

A

D M

IN

A

R E

A

FP1.08

DWG #### OF #### DWGS

NOTES (THIS SHEET)

KEYNOTES (THIS SHEET)#

KEYPLAN

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. REMOVAL OF FP PIPING SHALL INCLUDE OF ALL HANGERS, SUPPORTS, AND ACCESSORIES.

3. PATCH AND PAINT ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

GRID REQUIRED TO INSTALL THEIR WORK. PROVIDE NEW CEILING TILES OR GRID WHERE EXISTING

CEILING TILES OR GRID ARE DAMAGED DURING WORK.

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION DEMOLITION PLAN - ADMIN AREA1

1. SPRINKLER BRANCH TO REMAIN (TYPICAL).

2. EXISTING SPRINKLER HEADS IN ATTIC TO REMAIN (TYPICAL).

1/FP1.04

1/FP1.05

1/FP1.06

1/FP1.07

(TYP.)1

1(TYP.)

DEMO NOTES#

1. REMOVE EXISTING 3" FIRE PROTECTION MAIN TO LIMITS SHOWN. ALLOW FOR CONNECTION TO

EXISTING PIPING.

2. REMOVE EXISTING PIPING TEE TO COORDINATE INSTALLATION OF NEW PIPING.

COUNTRY KITCHEN

103-A

DINING

CORRIDOR

DINING JC

TOILET

CHARTING

105MED ROOM

105-A

SEATING

103A

DATE REVISION

PROJECT No.

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

P

LA

N

- W

IN

G

FP2.01

DWG #### OF #### DWGS

NOTES (THIS SHEET)

KEYNOTES (THIS SHEET)#

KEYPLAN

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION PLAN - WING 1002

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. PATCH ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

GRID REQUIRED TO INSTALL THEIR WORK. PROVIDE NEW CEILING TILES OR GRID WHERE EXISTING

CEILING TILES OR GRID ARE DAMAGED DURING WORK.

1. SPRINKLER BRANCH TAKEOFFS AND ASSOCIATED SPRINKLER HEADS TO REMAIN UNLESS

OTHERWISE NOTED (TYPICAL).

2. NEW 1-1/2" FIRE PROTECTION PIPING TO SERVE EXISTING SPRINKLER HEADS.

3. CONNECT EXISTING SPRINKLER HEAD TO NEW 1-1/2" FIRE PROTECTION PIPING (TYPICAL).

4. POTENTIAL LOCATION FOR TEMPORARY ACCESS HATCH TO ATTIC. CONTRACTOR TO COORDINATE

WITH OWNER FOR FINAL ACCESS LOCATIONS REQUIRED FOR WORK. REPAIR ANY DRYWALL

CEILING/INSULATION TO MATCH PRE-CONSTRUCTION CONDITION.

1-1/2" F

1-1/2" F

1-1/2" F

1-1/2" F

1-1/2" (F)

1-1/2" (F)

0 2' 4' 8' 16'

SCALE 1/8" = 1'

FIRST FLOOR FIRST FIRE PROTECTION PLAN - WING 1001

CORRIDOR

DINING

COUNTRY KITCHEN

202-A

TOILET (EXST)

MED ROOM

204-A

CHARTING

SEATING

202-B

DATE REVISION

PROJECT No.

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

P

LA

N

- W

IN

G

FP2.02

DWG #### OF #### DWGS

NOTES (THIS SHEET)

KEYNOTES (THIS SHEET)#

KEYPLAN

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION PLAN - WING 2002

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. PATCH ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

GRID REQUIRED TO INSTALL THEIR WORK. PROVIDE NEW CEILING TILES OR GRID WHERE EXISTING

CEILING TILES OR GRID ARE DAMAGED DURING WORK.

3" (F)

1. SPRINKLER BRANCH TAKEOFFS AND ASSOCIATED SPRINKLER HEADS TO REMAIN UNLESS

OTHERWISE NOTED (TYPICAL).

2. NEW FIRE PROTECTION BRANCH OF MAIN PIPING TO SERVE (4) EXISTING SPRINKLER HEADS AT SIZE

SHOWN ON PLAN.

3. CAP EXISTING TEE.

4. POTENTIAL LOCATION FOR TEMPORARY ACCESS HATCH TO ATTIC. CONTRACTOR TO COORDINATE

WITH OWNER FOR FINAL ACCESS LOCATIONS REQUIRED FOR WORK. REPAIR ANY DRYWALL

CEILING/INSULATION TO MATCH PRE-CONSTRUCTION CONDITION.

1-1/2" F1" F1" F

1-1/4" F

0 2' 4' 8' 16'

SCALE 1/8" = 1'

FIRST FLOOR FIRE PROTECTION PLAN - WING 200

STORAGE

PT/OT OFFICE

CONFERENCE

JANITOR

STAFF TLT

SPEECH

SPEECH

ENTRY

CORRIDOR

PT GYM

302-A

UNIT DIRECTOR

MED SUPPLY

R144

IT ROOM

R145

STAFF TOILET

R146

JANITOR

BATHER SPA

R143

JAN & HK STORAGE

R139

TOILET

R138

ACTIVITY

STORAGE/OFFICE

R142

VESTIBULE

CORRIDOR

R125

ELECTRICAL

R142-A

TRASH

R132

ADL TOILET

DIRTY LINEN

CLEAN LINEN

OT STORAGE

OT GYM

302-B

PASSAGE

SEATING

R133

UNIT CLERK

DATE REVISION

PROJECT No.

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

P

LA

N

- W

IN

G

FP2.03

DWG #### OF #### DWGS

NOTES (THIS SHEET)

KEYNOTES (THIS SHEET)#

KEYPLAN

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. PATCH ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

GRID REQUIRED TO INSTALL THEIR WORK. PROVIDE NEW CEILING TILES OR GRID WHERE EXISTING

CEILING TILES OR GRID ARE DAMAGED DURING WORK.

1. SPRINKLER BRANCH TAKEOFFS AND ASSOCIATED SPRINKLER HEADS TO REMAIN UNLESS

OTHERWISE NOTED (TYPICAL).

2. EXISTING 1-1/2" FIRE PROTECTION PIPING BRANCH AND ASSOCIATED SPRINKLER HEADS TO

REMAIN.

3. NEW 1-1/2" FIRE PROTECTION PIPING TO SERVE (3) EXISTING SPRINKLER HEADS.

4. POTENTIAL LOCATION FOR TEMPORARY ACCESS HATCH TO ATTIC. CONTRACTOR TO COORDINATE

WITH OWNER FOR FINAL ACCESS LOCATIONS REQUIRED FOR WORK. REPAIR ANY DRYWALL

CEILING/INSULATION TO MATCH PRE-CONSTRUCTION CONDITION.

1-1/2" (F)

1-1/2" (F)

3 1-1/2" F

3 1-1/2" F

3 1-1/2" F 3 1-1/2" F

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION PLAN - WING 30020 2' 4' 8' 16'

SCALE 1/8" = 1'

FIRST FLOOR FIRE PROTECTION PLAN - WING 300

DINING

CONFERENCE

STORAGE

CHARTING

MED ROOM

404-A

BATHING

JANITOR

DATE REVISION

PROJECT No.

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

P

LA

N

- W

IN

G

FP2.04

DWG #### OF #### DWGS

NOTES (THIS SHEET)

KEYNOTES (THIS SHEET)#

KEYPLAN

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION PLAN - WING 4002

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. PATCH ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

GRID REQUIRED TO INSTALL THEIR WORK. PROVIDE NEW CEILING TILES OR GRID WHERE EXISTING

CEILING TILES OR GRID ARE DAMAGED DURING WORK.

1. FIRE PROTECTION BRANCH TAKEOFFS TO REMAIN. MAKE NEW CONNECTION TO EXISTING FIRE

PROTECTION BRANCH PIPING (TYPICAL).

2. NEW 4" FIRE PROTECTION MAIN IN ATTIC. ROUTE NEW PIPING IN EXISTING LOCATION. MAKE

CONNECTIONS TO EXISTING BRANCH PIPING TO REMAIN.

3. POTENTIAL LOCATION FOR TEMPORARY ACCESS HATCH TO ATTIC. CONTRACTOR TO COORDINATE

WITH OWNER FOR FINAL ACCESS LOCATIONS REQUIRED FOR WORK. REPAIR ANY DRYWALL

CEILING/INSULATION TO MATCH PRE-CONSTRUCTION CONDITION.

4. SEE SHEET 1/FP2.08 FOR PIPING CONTINUATION.

4" F

1-1/2" (F)

1-1/2" (F)

1-1/2" (F)

1-1/2" (F)

4" F

0 2' 4' 8' 16'

SCALE 1/8" = 1'

FIRST FLOOR FIRE PROTECTION PLAN - WING 4001

1/FP2.08

511 MED ROOM

508-A

CHARTING

BATHING

JANITOR

KITCHEN

DINING

STAFF CONFERENCE

RN

CHARTING

MED ROOM

404-A

BATHING

TLT ROOM

DATE REVISION

PROJECT No.

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

P

LA

N

- W

IN

G

FP2.05

DWG #### OF #### DWGS

NOTES (THIS SHEET)

KEYNOTES (THIS SHEET)#

KEYPLAN

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION PLAN - WING 5002

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. PATCH ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

GRID REQUIRED TO INSTALL THEIR WORK. PROVIDE NEW CEILING TILES OR GRID WHERE EXISTING

CEILING TILES OR GRID ARE DAMAGED DURING WORK.

1. FIRE PROTECTION BRANCH TAKEOFFS TO REMAIN. MAKE NEW CONNECTION TO EXISTING FIRE

PROTECTION BRANCH PIPING (TYPICAL).

2. NEW 4" FIRE PROTECTION MAIN IN ATTIC. ROUTE NEW PIPING IN EXISTING LOCATION. MAKE

CONNECTIONS TO EXISTING BRANCH PIPING TO REMAIN.

3. POTENTIAL LOCATION FOR TEMPORARY ACCESS HATCH TO ATTIC. CONTRACTOR TO COORDINATE

WITH OWNER FOR FINAL ACCESS LOCATIONS REQUIRED FOR WORK. REPAIR ANY DRYWALL

CEILING/INSULATION TO MATCH PRE-CONSTRUCTION CONDITION.

4. SEE SHEET 1/FP2.08 FOR PIPING CONTINUATION.

4" F

1-1/2" (F)

1-1/2" (F)

4" F

1-1/2" (F)

1-1/2" (F)

0 2' 4' 8' 16'

SCALE 1/8" = 1'

FIRST FLOOR FIRE PROTECTION PLAN - WING 5001

KITCHEN

DINING

STORAGE

OFFICE

TV ROOM

MED ROOM

611-A

CHARTING

BATHING

JANITOR

TLT ROOM

DATE REVISION

PROJECT No.

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

P

LA

N

- W

IN

G

FP2.06

DWG #### OF #### DWGS

NOTES (THIS SHEET)

KEYNOTES (THIS SHEET)#

KEYPLAN

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION PLAN - WING 6002

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. PATCH ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

GRID REQUIRED TO INSTALL THEIR WORK. PROVIDE NEW CEILING TILES OR GRID WHERE EXISTING

CEILING TILES OR GRID ARE DAMAGED DURING WORK.

1. FIRE PROTECTION BRANCH TAKEOFFS TO REMAIN. MAKE NEW CONNECTION TO EXISTING FIRE

PROTECTION BRANCH PIPING (TYPICAL).

2. NEW 4" FIRE PROTECTION MAIN IN ATTIC. ROUTE NEW PIPING IN EXISTING LOCATION. MAKE

CONNECTIONS TO EXISTING BRANCH PIPING TO REMAIN.

3. POTENTIAL LOCATION FOR TEMPORARY ACCESS HATCH TO ATTIC. CONTRACTOR TO COORDINATE

WITH OWNER FOR FINAL ACCESS LOCATIONS REQUIRED FOR WORK. REPAIR ANY DRYWALL

CEILING/INSULATION TO MATCH PRE-CONSTRUCTION CONDITION.

4. SEE SHEET 1/FP2.08 FOR PIPING CONTINUATION.

4" F

1-1/2" (F)

1-1/2" (F)

4" F

1-1/2" (F)

1-1/2" (F)

0 2' 4' 8' 16'

SCALE 1/8" = 1'

FIRST FLOOR FIRE PROTECTION PLAN - WING 6001

MECH

TV ROOM

STORAGE (EXST)

CONFERENCE

MED ROOM

728-A CHARTING

STORAGE

BATHING

JANITOR

MED ROOM

611-A

CHARTING

TOILET

DATE REVISION

PROJECT No.

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

P

LA

N

- W

IN

G

FP2.07

DWG #### OF #### DWGS

NOTES (THIS SHEET)

KEYNOTES (THIS SHEET)#

KEYPLAN

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION PLAN - WING 7002

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. PATCH ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

GRID REQUIRED TO INSTALL THEIR WORK. PROVIDE NEW CEILING TILES OR GRID WHERE EXISTING

CEILING TILES OR GRID ARE DAMAGED DURING WORK.

1. FIRE PROTECTION BRANCH TAKEOFFS TO REMAIN. MAKE NEW CONNECTION TO EXISTING FIRE

PROTECTION BRANCH PIPING (TYPICAL).

2. NEW 4" FIRE PROTECTION MAIN IN ATTIC. ROUTE NEW PIPING IN EXISTING LOCATION. MAKE

CONNECTIONS TO EXISTING BRANCH PIPING TO REMAIN.

3. POTENTIAL LOCATION FOR TEMPORARY ACCESS HATCH TO ATTIC. CONTRACTOR TO COORDINATE

WITH OWNER FOR FINAL ACCESS LOCATIONS REQUIRED FOR WORK. REPAIR ANY DRYWALL

CEILING/INSULATION TO MATCH PRE-CONSTRUCTION CONDITION.

4. SEE SHEET 1/FP2.08 FOR PIPING CONTINUATION.

4" F

1-1/2" (F)

4" F

1-1/2" (F)

1-1/2" (F)

1-1/2" (F)

0 2' 4' 8' 16'

SCALE 1/8" = 1'

FIRST FLOOR FIRE PROTECTION PLAN - WING 7001

DRAWING No.

P R O J E C T

T I T L E

D R A W I N G

T I T L E

K E

N O

S H

A C

O U

N

TY

B R

O O

K S

ID

E

C A

R E

C E

N

TE

R

FI

R E

P R

O

TE

C

TI

O N

P

IP

IN

G

M O

D

IF

IC

A

TI

O

N S

K0450160

NOTE: DIMENSIONAL DATA IS NOT TO BE OBTAINED BY SCALING ANY PORTION OF THIS DRAWING.

D E S I G N

F I R M

R E G I S T R A T I O N

N O

T H

S T R E E T

T H

F L O O R

K E N O S H A

W I

P H O N E w c l a r k d i e t z c o m

DESIGNED BY: MCB

DRAWN BY: MCB

CHECKED BY: NTP

DATE CHECKED: 03/29/23

03/31/23 ISSUED FOR BID

A

TT

IC

F

IR

E

P R

O

TE

C

TI

O N

P

LA

N

- A

D M

IN

A

R E

A

FP2.08

DWG #### OF #### DWGS

KEYNOTES (THIS SHEET)#

KEYPLAN

1. NEW 4" FIRE PROTECTION MAIN IN ATTIC. ROUTE NEW PIPING IN EXISTING LOCATION. MAKE

CONNECTIONS TO EXISTING PIPING WITH NEW TEE.

2. SEE DESIGNATED SHEET FOR PIPING CONTINUATION.

0 2' 4' 8' 16'

SCALE 1/8" = 1'

ATTIC FIRE PROTECTION PLAN - ADMIN AREA

1/FP2.04

1/FP2.05

1/FP2.06

1/FP2.07

2 NOTES (THIS SHEET)

1. SEE SHEET FP0.01 FOR FIRE PROTECTION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

2. PATCH ALL EXISTING OPENINGS LEFT FROM REMOVAL TO MATCH ADJACENT SURFACES.

3. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND REPLACING ALL CEILING TILES OR

GRID REQUIRED TO INSTALL THEIR WORK. PROVIDE NEW CEILING TILES OR GRID WHERE EXISTING

CEILING TILES OR GRID ARE DAMAGED DURING WORK.

4" (F)

4" (F)

4" (F)

4" (F)

Sheets and Views
G0.01 TITLE SHEET
FP0.01 FIRE PROTECTION GENERAL NOTES, SYMBOLS AND DETAILS
FP0.02 OVERALL FIRST FLOOR PLAN
FP1.01 ATTIC FIRE PROTECTION DEMOLITION - WING 100
FP1.02 ATTIC FIRE PROTECTION DEMOLITION - WING 200
FP1.03 ATTIC FIRE PROTECTION DEMOLITION - WING 300
FP1.04 ATTIC FIRE PROTECTION DEMOLITION - WING 400
FP1.05 ATTIC FIRE PROTECTION DEMOLITON - WING 500
FP1.06 ATTIC FIRE PROTECTION DEMOLITION - WING 600
FP1.07 ATTIC FIRE PROTECTION DEMOLITION - WING 700
FP1.08 ATTIC FIRE PROTECTION DEMOLITION - ADMIN AREA
FP2.01 ATTIC FIRE PROTECTION PLAN - WING 100
FP2.02 ATTIC FIRE PROTECTION PLAN - WING 200
FP2.03 ATTIC FIRE PROTECTION PLAN - WING 300
FP2.04 ATTIC FIRE PROTECTION PLAN - WING 400
FP2.05 ATTIC FIRE PROTECTION PLAN - WING 500
FP2.06 ATTIC FIRE PROTECTION PLAN - WING 600
FP2.07 ATTIC FIRE PROTECTION PLAN - WING 700
FP2.08 ATTIC FIRE PROTECTION PLAN - ADMIN AREA

File details come from the government source that posted it. Updated .