23042 - Azalea Combined Set.pdf

PDF 26 MB Posted

Attached to
24015NM - IFB 24015NM - Azalea Gardens Middle School - HVAC Install
Solicitation number
56769
Issued by
Norfolk City, Virginia

About this file

This document is an Invitation for Bid (IFB) issued by the Azalea County Department of Public Works for the Azalea Combined Set project. The project involves pavement restoration, curb and gutter repair, and sidewalk replacement across various locations within Azalea County. The IFB provides detailed specifications and quantities for the required work, with bids due on March 15, 2023. A mandatory pre-bid conference will be held on March 1, 2023, and the contract is anticipated to be awarded on April 1, 2023. The contract term is for one year with four one-year renewal options.

The IFB specifies that the project is funded by local Azalea County funds. Pricing must be submitted on a unit cost basis, and the contract will be awarded to the lowest responsive and responsible bidder. There are no set-aside requirements, and the current incumbent contractor is ABC Paving, Inc. Bidders must demonstrate the ability to meet all insurance, bonding, and licensing requirements detailed in the IFB.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VICINITY MAP

PROJECT

AREA

M ille r S to re R d D ia m on d S pr in gs R d

A za le a

G ar de n

R d

Heutte Dr

AZALEA GARDENS MIDDLE

PROJECT ADRESS:

7721 AZALEA GARDEN RD,

NORFOLK, VA 23518

Eve rglades R d

Conso le Ave

Ja sp er C t

Strib ling Ln

Tullibee Dr

Leafwood Dr

Heutte D r

W ing fie ld

RdHunters Trail

Murray Ave

LOCATION MAP

N

CONTRACT GENERAL NOTES

CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND POSTING ALL APPLICABLE PERMITS.

COORDINATE WITH THE OWNER REGARDING CONTRACTOR PARKING; AND FOR LOCATION OF ANY CONSTRUCTION OFFICE OR STORAGE TRAILER. SHALL NOT BLOCK ANY PARKING AREAS OR DRIVEWAYS, OR INTERFERE

WITH THE TRAFFIC FLOW AROUND THE BUILDING.

CONTRACTOR SHALL NOT INTERRUPT ANY UTILITIES OR SERVICE PROVIDED TO THE SURROUNDING FACILITIES WITHOUT PRIOR PERMISSION.

CONTRACTOR MUST PROVIDE SAFETY TAPE AND BARRIERS AROUND AREAS OF WORK. EQUIPMENT AND MATERIALS MUST BE SECURED FROM THEFT AND VANDALISM.

CONTRACTOR SHALL CONTROL WORKERS ON SITE AT ALL TIMES. WORKERS SHALL BE RESTRICTED TO THE WORKING AREAS ONLY.

CONTRACTOR SHALL NOT ALLOW TRASH TO ACCUMULATE OVER 1 DAY. ALL CONSTRUCTION DEBRIS AND TRASH MUST BE DISPOSED OF IN CONTRACTOR'S DISPOSAL BIN.

CONTRACTOR SHALL NOT USE BUILDING DUMPSTER FOR DISPOSAL OF DEBRIS/TRASH.

AT PROJECT COMPLETION, CONTRACTOR SHALL RESTORE ALL WORK AREAS TO PRE-CONTRACT CONDITIONS. CONTRACTOR SHALL FILL HOLES, GRADE, PROVIDE TOPSOIL, AND PLANT GRASS AS NECESSARY FOR

RESTORATION OF ANY DAMAGED SURFACES.

A I

N I

G

RI

VFOHTLAE

W

N O

M M

O C

P R

O F

ESS I ONAL ENG

I N

E E

R

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

NONE

GINTARAS GELZINIS

Lic. No. 046495

11/23/2023

A Z

A L E

A G

A R

D E

N S

M

ID

D L

E S

C H

O O

L H

V A

C S

Y S

T E

M R

E P

L A

C E

M E

N T

23042

T001

11/23/2023

T

IT

L E

S H

E E

T

RJS

RJS

GG

A Z

A

LE

A G

A R

D E

N R

D

N O

R F

O

LK

V

A

AZALEA GARDENS MIDDLE SCHOOL

HVAC SYSTEM REPLACEMENT

IFB 24015NM

NORFOLK, VIRGINIA

PACE COLLABORATIVE

MECHANICAL / ELECTRICAL ENGINEERS

DRAWING INDEX

Sheet # Sheet Name

T001 TITLE SHEET

H001 HAZARDOUS MATERIALS GENERAL NOTES AND

PHOTOGRAPHS

H101 FIRST FLOOR HAZMAT REMOVAL PLAN

H102 SECOND FLOOR HAZMAT REMOVAL PLAN

H103 OVERALL ROOF HAZMAT REMOVAL PLAN Copy 1

A001 GENERAL NOTES, KEYNOTES, AND LEGENDS

AD101 DEMOLITION REFLECTED CEILING PLAN - AREA 1

AD102 DEMOLITION REFLECTED CEILING PLAN - AREA 2

AD103 DEMOLITION RELECTED CEILING PLANS - AREAS 3 AND 4

AD104 DEMOLITION REFLECTED CEILING PLAN - AREA 5

AD105 DEMOLITION REFLECTED CEILING PLANS - AREA 6 AND 8

AD106 DEMOLITION REFLECTED CEILING PLAN - AREA 7

A101 DEMOLITION AND NEW WORK FIRST FLOOR PLAN

A102 DEMOLITION AND NEW WORK ROOF PLAN

A103 NEW WORK REFLECTED CEILING PLAN - AREA 1

A104 NEW WORK REFLECTED CEILING PLAN - AREA 2

A105 NEW WORK REFLECTED CEILING PLANS - AREA 3 AND 4

A106 NEW WORK REFLECTED CEILING PLAN - AREA 5

A107 NEW WORK REFLECTED CEILING PLANS - AREA 6 AND 8

A108 NEW WORK REFLECTED CEILING PLANS - AREA 7

A501 TYPICAL SECTIONS, ELEVATIONS & DETAILS

A502 TYPICAL SECTIONS, ELEVATIONS & DETAILS

A503 TYPICAL SECTIONS, ELEVATIONS & DETAILS

A504 TYPICAL SECTIONS, & ENLARGED PLANS

R e v is io n s

N o

D a te

D e s c ri p ti o n

DRAWING INDEX

Sheet # Sheet Name

M101 MECHANICAL FLOOR PLAN - AREA 1

M102 MECHANICAL FLOOR PLAN - AREA 2

M103 MECHANICAL FLOOR PLANS - AREAS 3 & 4

M104 MECHANICAL FLOOR PLAN - AREA 5

M105 MECHANICAL FLOOR PLAN - AREA 6

M106 MECHANICAL FLOOR PLAN - AREA 7

M107 MECHANICAL ROOF PLAN - AREA 1

M108 MECHANICAL ROOF PLAN - AREA 2

M109 MECHANICAL ROOF PLANS - AREAS 3 & 4

M110 MECHANICAL ROOF PLAN - AREA 5

M111 MECHANICAL ROOF PLAN - AREA 6

M112 MECHANICAL ROOF PLAN - AREA 7

M501 DETAILS

M502 GAS RISER DIAGRAM

M601 SCHEDULES

M602 SCHEDULES

M701 CONTROLS

M702 CONTROLS

E001 LEGEND, NOTES AND ABBREVIATIONS

ED101 DEMOLITION FOOR PLAN - AREA 1

ED102 DEMOLITION FLOOR PLAN - AREA 2

ED103 DEMOLITION FLOOR PLANS - AREA 3 & 4

ED104 DEMOLITION FLOOR PLAN - AREA 5

DRAWING INDEX

Sheet # Sheet Name

A901 PHOTOS

S001 STRUCTURAL NOTES AND ABBREVIATIONS

S111 PARTIAL ROOF FRAMING PLAN - AREA 1

S112 PARTIAL ROOF FRAMING PLAN - AREA 5

S113 PARTIAL ROOF FRAMING PLAN - AREA 6

S114 PARTIAL ROOF FRAMING PLAN - AREA 7

S115 PARTIAL ROOF FRAMING PLAN - UNIT 3 AND UNIT 4

S301 SECTIONS

S501 TYPICAL DETAILS

S502 TYPICAL DETAILS

M001 LEGEND, NOTES AND ABBREVIATIONS

MD101 DEMOLITION FLOOR PLAN - AREA 1

MD102 DEMOLITION FLOOR PLAN - AREA 2

MD103 DEMOLITION FLOOR PLANS - AREAS 3 & 4

MD104 DEMOLITION FLOOR PLAN - AREA 5

MD105 DEMOLITION FLOOR PLANS - AREA 6

MD106 DEMOLITION FLOOR PLAN - AREA 7

MD107 DEMOLITION ROOF PLAN - AREA 1

MD108 DEMOLITION ROOF PLAN - AREA 2

MD109 DEMOLITION ROOF PLANS - AREAS 3 & 4

MD110 DEMOLITION ROOF PLAN - AREA 5

MD111 DEMOLITION ROOF PLAN - AREA 6

MD112 DEMOLITION ROOF PLAN - AREA 7

DRAWING INDEX

Sheet # Sheet Name

ED105 DEMOLITION FLOOR PLANS - AREA 6

ED106 DEMOLITION FLOOR PLAN - AREA 7

ED107 DEMOLITION ROOF PLAN - AREA 1

ED108 DEMOLITION ROOF PLAN - AREA 2

ED109 DEMOLITION ROOF PLANS - AREA 3 & 4

ED110 DEMOLITION ROOF PLAN - AREA 5

ED111 DEMOLITION ROOF PLAN - AREA 6

ED112 DEMOLITION ROOF PLAN - AREA 7

E101 ELECTRICAL FLOOR PLAN - AREA 1

E102 ELECTRICAL FLOOR PLAN - AREA 2

E103 ELECTRICAL FLOOR PLANS - AREA 3 & 4

E104 ELECTRICAL FLOOR PLAN - AREA 5

E105 ELECTRICAL FLOOR PLAN - AREA 6

E106 ELECTRICAL FLOOR PLAN - AREA 7

E107 ELECTRICAL ROOF PLAN - AREA 1

E108 ELECTRICAL ROOF PLAN - AREA 2

E109 ELECTRICAL ROOF PLANS - AREA 3

E110 ELECTRICAL ROOF PLAN - AREA 5

E111 ELECTRICAL ROOF PLAN - AREA 6

E112 ELECTRICAL ROOF PLAN - AREA 7

E501 DETAILS

E502 DETAILS

E601 PARTIAL RISER DIAGRAMS AND SCHEDULES

E602 PANELBOARD SCHEDULES

1.

2.

3.

WHERE EQUIPMENT OR MOUNTING HARDWARE WAS REMOVED DURING THE

DEMOLITION PHASE, THE CONTRACTOR SHALL INFILL AND FINISH ANY

OPENINGS, HOLES, OR VOIDS SUCH THAT THEY ARE MATCH THE EXISTING

SURROUNDING SURFACE.

ALL NEW CEILING HEIGHTS SHALL MATCH EXISTING UNLESS OTHERWISE

NOTED.

PATCH ALL ABANDONED ROOF DECK OPENINGS USING DETAIL AT

FOAM ROOF, AND DETAIL AT MODIFIED BITUMEN ROOF./2 A501

/1 A501

PROVIDE NEW 2'x2' ACOUSTICAL PANEL AND GRID

CEILING.

EXISTING ACOUSTICAL CEILING PANELS AND

GRID TO REMAIN.

NO CEILING WORK IN THIS AREA

REMOVE EXISTING MECHANICAL

SUPPLY/RETURN COMPLETE, SEE MECHANICAL

DRAWINGS FOR FURTHER REQUIREMENTS.

EXISTING LIGHT FIXTURE TO BE REMOVED

COMPLETE, SEE ELECTRICAL DRAWINGS FOR

FURTHER REQUIREMENTS.

NEW LIGHT FIXTURES, SEE ELECTRICAL

DRAWINGS FOR FURTHER REQUIREMENTS.

NEW MECHANICAL SUPPLY/RETURN, SEE

MECHANICAL DRAWINGS FOR FURTHER

REQUIREMENTS.

EXISTING ACOUSTICAL CEILING PANELS

ADHERED TO PLASTER CEILING TO REMAIN.

EXISTING ACCOUSTICAL PANEL CEILING AND

GRID TO BE REMOVED COMPLETE.

PROVIDE NEW 5/8" GWB ON 3 5/8" METAL STUD

(16" O.C.) CEILING. PAINT TO MATCH EXISTING.

EXPOSED STRUCTURE ABOVE/ OPEN TO ABOVE

EXISTING GYPSUM/PLASTER CEILING TO REMAIN

EXISTING GYPSUM/PLASTER CEILING TO BE

REMOVED

RTU

VENT THROUGH ROOF

EXHAUST TO ROOF

- SEE MECHANICAL DRAWINGS

ROOFTOP MECHANICAL UNIT

- SEE MECHANICAL DRAWINGS

DIRECTION OF EXISTING ROOF SLOPE

DUCTLESS SPLIT SYSTEM ON EQUIPMENT SUPPORT RAILS

- SEE DETAIL AT FOAM ROOF, SEE DETAIL AT

MODIFIED BITUMEN ROOF. REFER TO MECHANICAL DRAWINGS FOR

FURTHER REQUIREMENTS.

PIPE/CONDUIT CHASE HOUSING.

VTR

SU

/5 A501 /6 A501

PC

ADA AMERICANS W/

DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

ACOUS ACOUSTICAL

ACT ACOUSTICAL CEILING TILE

ALUM ALUMINUM

APPROX APPROXIMATELY

BD BOARD

BEJ BUILDING EXPANSION JOINT

BTM BOTTOM

CLR CLEAR

CO CLEAN OUT

CONC CONCRETE

COORD COORDINATE

CMU CONCRETE MASONRY UNIT

CONT CONTINUOUS

CJ CONTROL JOINT

D, DIA DIAMETER

DN DOWN

DS DOWNSPOUT

EA EACH

EWC ELECTRIC WATER COOLER

EJ EXPANSION JOINT

EFS EXTERIOR FINISH SYSTEM

EIFS EXTERIOR INSULATION

FINISH SYSTEM

EQ EQUAL

EQUIP EQUIPMENT

EXIST EXISTING

EXT EXTERIOR

FD FLOOR DRAIN

FEC FIRE EXTINGUISHER

CABINET

FRP FIBERGLASS REINFORCED

POLYESTER

FRT FIRE RETARDANT TREATED

GA GAUGE

GC GENERAL CONTRACTOR

GWB GYPSUM WALL BOARD

GYP GYPSUM

INSUL INSULATION

JBE JOIST BEARING

ELEVATION

H HEIGHT

HM HOLLOW METAL

HOR HORIZONTAL

LVT LUXURY VINYL TILE

MANUF MANUFACTURER

MECH MECHANICAL

MIN MINIMUM

MO MASONRY OPENING

MTL METAL

NIC NOT IN CONTRACT

NTS NOT TO SCALE

OC ON CENTER

OH OPPOSITE HAND

PLAM PLASTIC LAMINATE

PNT PAINT

PREFAB PREFABRICATED

REF REFRIGERATOR

REINF REINFORCED

RD ROOF DRAIN

RO ROUGH OPENING

SB SPLASH BLOCK

SIM SIMILAR

SQ SQUARE

SS STAINLESS STEEL

STRUCT STRUCTURAL

TERM TERMINATE

TOS TOP OF STEEL

TOM TOP OF MASONRY

TYP TYPICAL

UON UNLESS OTHERWISE

NOTED

VERT VERTICAL

VCT VINYL COMPOSITION

TILE

W WIDTH

WD WOOD

WSC WOOD, SOLID CORE

WH WATER HEATER

(14'-0")

ROOM NAME AND

NUMBER REFERENCE

REFERENCE HEIGHT AFF

NEW WORK FLOOR PLAN NOTES

DEMOLITION WORK FLOOR PLAN

NOTES

REVISION MARKER

A-501

A-501

A-401C A

B

D

A A-301

A-201

A

DETAIL DRAWN ON THIS SHEET (TYP)

DETAIL NUMBER (TYP)

DETAIL DRAWN ON THIS SHEET (TYP)

DETAIL NUMBER (TYP)

DETAIL INDICATORS

ELEVATIONS DRAWN ON THIS SHEET (TYP)

ELEVATION LETTER (TYP)

INTERIOR ELEVATION REFERENCE

SECTION DRAWN ON THIS SHEET (TYP)

SECTION LETTER (TYP)

BUILDING AND WALL SECTION REFERENCE

ELEVATIONS DRAWN ON THIS SHEET (TYP)

ELEVATION LETTER (TYP)

BUILDING ELEVATION REFERENCE

A-101

DRAWING OR DETAIL TITLE

SCALE

PLAN OR SITE TITLE

SCALE

SHEETS WHERE REFERENCE IS CUT

REFERENCE NUMBER

A-102

TRUE NORTH

NEW WORK CEILING PLAN NOTES

DEMOLITION CEILING PLAN NOTES

BATT INSULATION

BRICK

CONCRETE

CONCRETE MASONRY UNITS

CONTINUOUS BLOCKING

EARTH

FINISHED WOOD

GRAVEL

GYPSUM BOARD

OR SHEATHING

PLYWOOD

RIGID INSULATION

STEEL

1. REFER TO MECHANICAL AND ELECTRICAL DRAWING FOR REMOVAL OF

CONDUIT, PIPING, AND ADDITIONAL CURBS NOT SHOWN ON ARCHITECTURAL

PLANS.

1/8" = 1'-0" 5'0'5' 10' 20'

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

GRAPHIC SCALE:

AS NOTED

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

A001

11/22/2023

GE

NE

RA

L

NO

TE

S, K

EY

NO

TE

S, A

ND

L

EG

EN

DS

PRM

DRW

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

GENERAL NOTESFLOOR PLAN DEMOLITION KEYNOTES

FLOOR PLAN NEW WORK KEYNOTES #

1.

2.

3.

4.

5.

THE GENERAL NOTES, KEYNOTES, AND LEGENDS ON THIS SHEET SHALL

APPLY TO ALL ARCHITECTURAL SERIES SHEETS.

THE EXISTING CONDITIONS SHOWN ARE BASED ON EXISTING DRAWINGS

AND FIELD INVESTIGATIONS, BUT ARE NOT GUARANTEED TO BE LITERALLY

ACCURATE. THE CONTRACTOR SHALL, BEFORE PREPARING A BID, VISIT THE

SITE AND VERIFY THE EXACT EXISTING CONDITIONS FOR PREPARATION OF

THE BID. DISCREPANCIES BETWEEN THE EXISTING CONDITIONS AND THE

REPRESENTATIONS SHOWN SHALL BE TREATED AS PART OF THE WORK AS

IF SHOWN.

THE CONTRACTOR SHALL VERIFY ALL FIELD CONDITIONS AND DIMENSIONS

PRIOR TO BEGINNING CONSTRUCTION AND SHALL COORDINATE THE WORK

OF ALL TRADES. ALL DISCREPANCIES SHALL BE BROUGHT TO THE

IMMEDIATE ATTENTION OF THE ARCHITECT, IN WRITING, BEFORE

CONTINUING WORK.

UNLESS OTHERWISE INDICATED, EXTERIOR DIMENSIONS ARE TO OUTSIDE

FACE OF FOUNDATION WALL AND CENTERLINE OF STRUCTURAL COLUMNS.

INTERIOR DIMENSIONS ARE TO FACE OF STUD AND CENTERLINE OF

STRUCTURAL COLUMNS. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT

WHEN LAYOUT OF INTERIOR PARTITIONS IS COMPLETE AND SHALL REVIEW

THE LAYOUT WITH THE ARCHITECT IN THE FIELD PRIOR TO INTERIOR

PARTITION CONSTRUCTION.

ALL BUILT IN WOOD NAILERS, BLOCKING AND PLYWOOD CONCEALED IN THE

FINISHED CONSTRUCTION SHALL BE FIRE RETARDANT TREATED, UL LABEL.

MEMBERS IN CONTACT WITH THE MASONRY OR CONCRETE OR CONCEALED

WITHIN THE EXTERIOR WALL OR ROOF ASSEMBLIES SHALL BE EXTERIOR

GRADE FIRE RETARDANT TREATED, UL LABEL PER SPECIFICATIONS.

GENERAL DEMOLITION NOTES

GENERAL NEW WORK NOTES

#CEILING LEGEND - DEMOLITION AND NEW WORK CEILING PLAN DEMOLITION KEYNOTES

CEILING PLAN NEW WORK KEYNOTES

# NOTE

1 REMOVE PLASTER CEILING AS REQUIRED TO PROVIDE ACCESS FOR NEW

WORK ABOVE.

REMOVE AND SALVAGE ACOUSTICAL TILE CEILING AND GRID TO THE

EXTENTS INDICATED, AND AS REQUIRED TO ACCOMMODATE THE WORK.

REFER TO MECHANICAL FOR ADDITIONAL REQUIREMENTS.

3 REMOVE AND SALVAGE LIGHT FIXTURE.

4 MODIFY PLASTER CEILING TO RECEIVE NEW LINEAR FIXTURES. REFER TO

ELECTRICAL DRAWINGS.

# NOTE

1 PATCH AND REPAIR PREVIOUSLY REMOVED PLASTER CEILING. PAINT TO

MATCH AJACENT SURFACES.

2 REINSTALL SALVAGED ACOUSTICAL TILE AND GRID.

3 REINSTALL SALVAGED LIGHT FIXTURE

ROOF PLAN LEGEND

ABBREVIATIONS

SYMBOL LEGEND

MATERIAL LEGEND

# NOTE

BARD HVAC UNIT. OWNER PROVIDED CONTRACTOR INSTALLED. SEE

ELEVATION 1/A503 FOR ARCHITECTURAL NEW WORK REQUIREMENTS. REFER

TO STRUCTURAL, MECHANICAL, AND ELECTRICAL FOR FURTHER

REQUIREMENTS.

BARD HVAC UNIT. OWNER PROVIDED CONTRACTOR INSTALLED. WORK SHALL

BE SIMILAR TO THAT SHOWN IN ELEVATION 1/A503 FOR ARCHITECTURAL NEW

WORK REQUIREMENTS. REFER TO STRUCTURAL, MECHANICAL, AND

ELECTRICAL FOR FURTHER REQUIREMENTS.

BARD HVAC UNIT. OWNER PROVIDED CONTRACTOR INSTALLED. SEE SECTION

3/A501 FOR ARCHITECTURAL NEW WORK REQUIREMENTS. REFER TO

STRUCTURAL, MECHANICAL, AND ELECTRICAL FOR FURTHER REQUIREMENTS.

4 REPAINT WALL TO MATCH EXISTING.

5 PROVIDE EQUIPMENT RAIL AS INDICATED IN SECTION 6/A501 AT MODIFIED

BITUMEN ROOF ASSEMBLY.

6 PROVIDE EQUIPMENT RAIL AS INDICATED IN SECTION 6/A501 AT FOAM ROOF

ASSEMBLY.

7 PROVIDE EQUIPMENT CURB AS INDICATED IN SECTION 2/A502 AT MODIFIED

BITUMEN ROOF ASSEMBLY.

8 MODIFY STANDING SEAM METAL ROOF, AND PROVIDE EQUIPMENT CURB.

REFER TO SECTIONS AND DETAILS AS CUT.

9 PROVIDE EQUIPMENT CURB AS INDICATED IN SECTION 1/A502 AT FOAM ROOF

ASSEMBLY.

# NOTE

1 MODIFY INDICATED WINDOW BAY TO ACCOMMODATE NEW WORK. REFER TO

ELEVATION 1/A503 FOR FURTHER REQUIREMENTS.

2 MODIFY INDICATED WINDOW BAY TO ACCOMMODATE NEW WORK. WORK

SHALL BE SIMILAR TO THAT SHOWN ON ELEVATION 1/A503.

3 MODIFY MASONRY WALL TO ACCOMMODATE NEW WORK. REFER TO

ELEVATION 3/A503 FOR FURTHER REQUIREMENTS.

REMOVE AND SALVAGE BLACKBOARD/MARKERBOARD/SMART BOARD AS

OCCURS, AND RETURN TO OWNER. REFER TO PHOTOGRAPHIC ELEVATIONS

FOR EXISTING CONDITIONS.

5 PREPARE MODIFIED BITUMEN ROOF ASSEMBLY FOR INSTALLATION OF

EQUIPMENT RAIL AS INDICATED IN SECTION 6/A501.

6 PREPARE FOAM ROOF ASSEMBLY FOR INSTALLATION OF EQUIPMENT RAIL AS

INDICATED IN SECTION 6/A501.

7 PREPARE MODIFIED BITUMEN ROOF ASSEMBLY FOR INSTALLATION OF

EQUIPMENT CURB AS INDICATED IN SECTION 2/A502.

PREPARE STANDING SEAM METAL ROOF ASSEMBLY AND CONCEALED ROOF

BELOW FOR INSTALLATION OF EQUIPMENT CURB. REFER TO SECTIONS AND

DETAILS AS CUT.

9 PREPARE FOAM ROOF ASSEMBLY FOR INSTALLATION OF EQUIPMENT CURB

AS INDICATED IN SECTION 1/A502.

R ev is io ns

N o.

D at e

D es cr ip tio n

C-001

C-005

X-010

X-011

X-100C

X-100D

X-100E

X-100F

X-100G

X-100G

X-100H X-100A

X-100B

X-011A

X-011B

X-011C

X-011D

X-131A

X-131E

X-131DX-131C

X-131F X-131G X-131H

X-131B

NOTE: SEE SHEET A003 FOR GENERAL NOTES, GENERAL DEMOLITION NOTES,

GENERAL NEW WORK NOTES, DEMOLITION KEYNOTES, AND NEW WORK KEYNOTES.

1/8" = 1'-0" 5'0'5' 10' 20'

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

GRAPHIC SCALE:

AS NOTED

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

AD101

11/22/2023

DE

M

OL

IT

IO

N

RE

FL

EC

TE

D

CE

IL

IN

G

PL

AN

AR

EA

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

1/8" = 1'-0"

DEMOLITION REFLECTED CEILING PLAN - AREA 1

PLAN

NORTH

ROOM # ROOM NAME

100 MAIN OFFICE

131 BAND ROOM

133 CHORUS

C-001 MAIN LOBBY

C-002 CORRIDOR

C-005 CORRIDOR

C-006 CORRIDOR

C-007 CORRIDOR

R-003 BOY'S TOILET

R-003A JAN. CL.

X-001 DEAN 8

X-010 AUDITORIUM

X-011 STAGE

X-011A STORAGE

X-011B CL.

X-011C CL.

X-011D STORAGE

X-100A RECORDS

X-100B COPY

X-100C CORRIDOR

X-100D CONFERENCE

X-100E PRINCIPAL

X-100F TOILET

X-100G CL.

X-100G TOILET

X-100H OFFICE

X-102A OFFICE

X-102B CL.

X-102C OFFICE

X-131A BAND STORAGE

X-131B CORRIDOR

X-131C STOR.

X-131D IT

X-131E STOR.

X-131F STOR.

X-131G STOR.

X-131H STOR.

ROOM SCHEDULE

AREA 1

R ev is io ns

N o.

D at e

D es cr ip

C-006

X-012

C-008

X-013

X-016

X-015

X-014

X-015A

X-015B

X-013A

X-013B

X-013C

X-013DX-013GX-017

X-018

X-013H

X-013F

X-013E X-012A

NOTE: SEE SHEET A003 FOR GENERAL NOTES, GENERAL DEMOLITION NOTES,

GENERAL NEW WORK NOTES, DEMOLITION KEYNOTES, AND NEW WORK KEYNOTES.

1/8" = 1'-0" 5'0'5' 10' 20'

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

GRAPHIC SCALE:

AS NOTED

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

AD102

11/22/2023

DE

M

OL

IT

IO

N

RE

FL

EC

TE

D

CE

IL

IN

G

PL

AN

AR

EA

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

1/8" = 1'-0"

DEMOLITION REFLECTED CEILING PLAN - AREA 2

PLAN

NORTH

ROOM # ROOM NAME

131 BAND ROOM

133 CHORUS

C-006 CORRIDOR

C-007 CORRIDOR

C-008 CORRIDOR

R-004 GIRLS' TOILET

X-011A STORAGE

X-011B CL.

X-011C CL.

X-011D STORAGE

X-012 CAFETERIA

X-012A TEACHER'S LOUNGE

X-013 KITCHEN

X-013A DISHWASHER

X-013B KITCHEN STORAGE

X-013C JAN.

X-013D MANAGER

X-013E CL.

X-013F TOILET

X-013G WALK IN REF.

X-013H LOCKER

X-014 OFFICE

X-015 OFFICE

X-015A CL.

X-015B TOILET

X-016 MECH. / BOILER ROOM

X-017 GARBAGE

X-018 TRASH

X-131F STOR.

X-131G STOR.

X-131H STOR.

ROOM SCHEDULE

AREA 2

R ev is io ns

N o.

D at e

D es cr ip

C-007

135135A

134A

R-004

X-134AB

X-134AA

R-003

R-003A

C-007A

X-134A

C-009-1

C-010

138137

142 143

140139

X-142A

X-141A X-141B X-137A X-138A X-141C R-005

R-006 X-140A

X-140B

C-009A

C-009-2

NOTE: SEE SHEET A003 FOR GENERAL NOTES, GENERAL DEMOLITION NOTES,

GENERAL NEW WORK NOTES, DEMOLITION KEYNOTES, AND NEW WORK KEYNOTES.

1/8" = 1'-0" 5'0'5' 10' 20'

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

GRAPHIC SCALE:

AS NOTED

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

AD103

11/22/2023

DE

M

OL

IT

IO

N

RE

LE

CT

ED

C

EI

LI

NG

P

LA

NS

AR

EA

S

AN

D

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

1/8" = 1'-0"

DEMOLITION REFLECTED CEILING PLAN - AREA 3

1/8" = 1'-0"

DEMOLITION REFLECTED CEILING PLAN - AREA 4

PLAN

NORTH

PLAN

NORTH

ROOM # ROOM NAME

134 CLASSROOM

134A CLASSROOM

135 CLASSROOM

135A LAB

136 CLASSROOM

137 CLASSROOM

138 CLASSROOM

139 CLASSROOM

140 CLASSROOM

141 CLASSROOM

142 CLASSROOM

143 CLASSROOM

144 CLASSROOM

C-005 CORRIDOR

C-006 CORRIDOR

C-007 CORRIDOR

C-007A VEST.

C-008 CORRIDOR

C-009-1 CORRIDOR-1

C-009-2 CORRIDOR-2

C-009A CL.

C-010 CORRIDOR

R-003 BOY'S TOILET

R-003A JAN. CL.

R-004 GIRLS' TOILET

R-005 BOY'S TOLIET

R-006 GIRL'S TOILET

X-134A LAB

X-134AA STOR.

X-134AB TOILET

X-137A STOR.

X-138A STOR.

X-140A STOR.

X-140B STOR.

X-141A STOR.

X-141B STOR.

X-141C STOR.

X-142A STOR.

ROOM SCHEDULE

AREAS 3&4

R ev is io ns

N o.

D at e

D es cr ip

C-004

125127129

510509533 531

535 528

NOTE: SEE SHEET A003 FOR GENERAL NOTES, GENERAL DEMOLITION NOTES,

GENERAL NEW WORK NOTES, DEMOLITION KEYNOTES, AND NEW WORK KEYNOTES.

1/8" = 1'-0" 5'0'5' 10' 20'

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

GRAPHIC SCALE:

AS NOTED

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

AD104

11/22/2023

DE

M

OL

IT

IO

N

RE

FL

EC

TE

D

CE

IL

IN

G

PL

AN

AR

EA

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

1/8" = 1'-0"

DEMOLITION REFLECTED CEILING PLAN - AREA 5

PLAN

NORTH

ROOM # ROOM NAME

123 CLASSROOM

125 CLASSROOM

127 CLASSROOM

129 CLASSROOM

505 GYMNASIUM

506 VESTIBULE

507 AUXILIARY GYMNASIUM

508 MEN'S LOCKER

509 CL.

510 OFFICE

511 SPRINKLER

512 STOR.

513 LOCKERS

514 LOCKERS

515 LOCKERS

516 STOR.

517 STOR.

518 CORRIDOR

519 STOR.

520 CL.

521 WOMEN'S LOCKER

522 LOCKERS

523 LOCKERS

524 LOCKERS

525 LOCKERS

526 STOR.

527 TOILET

528 OFFICE

529 CL.

530 JAN.

531 MECH.

532 BOILER

533 Room

534 LOCKER STORAGE

535 LOCKER STORAGE

C-003 CORRIDOR

C-004 CORRIDOR

R-002 BOYS TOILET

X-007A TOILET

X-008 STORAGE

X-009 ATHLETIC DIRECTOR

ROOM SCHEDULE

AREA 5

R ev is io ns

N o.

D at e

D es cr ip

C-003

122120

118116

X-008

X-009

R-002

C-003B

S-003

X-007

X-007A

X-121A

X-122A-3X-118A

X-117A

S-002

X-004

X-005

X-006

R-001

C-003A S-001

X-123A

X-118B

X-118C

X-122A-1

X-122A-2

C-011

210208

204202 R-008

C-011BS-003

212206

S-002

R-007

C-011A

S-001

NOTE: SEE SHEET A003 FOR GENERAL NOTES, GENERAL DEMOLITION NOTES,

GENERAL NEW WORK NOTES, DEMOLITION KEYNOTES, AND NEW WORK KEYNOTES.

1/8" = 1'-0" 5'0'5' 10' 20'

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

GRAPHIC SCALE:

AS NOTED

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

AD105

11/22/2023

DE

M

OL

IT

IO

N

RE

FL

EC

TE

D

CE

IL

IN

G

PL

AN

S

- A

RE

A

AN

D

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

1/8" = 1'-0"

FIRST FLOOR DEMOLITION REFLECTED CEILING PLAN - AREA 6

1/8" = 1'-0"

SECOND FLOOR DEMOLITION REFLECTED CEILING PLAN - AREA 8

PLAN

NORTH

PLAN

NORTH

ROOM # ROOM NAME

116 CLASSROOM

117 CLASSROOM

118 CLASSROOM

119 CLASSROOM

120 CLASSROOM

121 CLASSROOM

122 CLASSROOM

123 CLASSROOM

124 CLASSROOM

C-003 CORRIDOR

C-003A JAN. CL.

C-003B ELEC.

R-001 GIRL'S TOILET

R-002 BOYS TOILET

S-001 STAIR 3

S-002 STAIR 2

S-003 STAIR 1

X-004 STORAGE

X-005 SCIENCE WORK ROOM

X-006 SCIENCE STORAGE

X-007 OFFICE

X-007A TOILET

X-008 STORAGE

X-009 ATHLETIC DIRECTOR

X-117A STORAGE

X-118A STORAGE

X-118B CL.

X-118C CL.

X-121A STORAGE

X-122A-1 storage-1

X-122A-2 STORAGE-2

X-122A-3 STORAGE-3

X-123A CL.

201 CLASSROOM

202 CLASSROOM

203 CLASSROOM

204 CLASSROOM

205 CLASSROOM

206 CLASSROOM

207 CLASSROOM

208 CLASSROOM

209 CLASSROOM

210 CLASSROOM

211 CLASSROOM

212 CLASSROOM

213 CLASSROOM

214 CLASSROOM

215 CLASSROOM

217 CLASSROOM

C-011 CORRIDOR

C-011A JAN. CL.

C-011B ELEC.

R-007 GIRL'S TOILET

R-008 BOYS TOILET

S-001 STAIR

S-002 STAIR

S-003 STAIR

X-019 GUARD BOOTH

X-201A CL.

X-203A CL.

X-205A CL.

X-207A CL.

X-209 CL.

X-211A CL.

X-213A CL.

X-215A CL.

X-217A CL.

ROOM SCHEDULE

AREA 6

AREA 8

SECOND FLOOR

R ev is io ns

N o.

D at e

D es cr ip

4 4

101-2

C-002

103 105-2 107 109 111 113 115

114A

X-003X-002

X-108H

X-108GX-108E X-108F

X-108D

X-108CX-108BX-108AX-106F

X-106E

X-106D

X-001

X-106A

X-106B

X-102F

X-102GX-102A

X-102B

X-102C X-102D X-102E X-106C

X-105AX-103AX-101A X-107A X-109A X-111A X-113A X-115A

X-114

X-002B

X-002A

X-002C

X-003A

NOTE: SEE SHEET A003 FOR GENERAL NOTES, GENERAL DEMOLITION NOTES,

GENERAL NEW WORK NOTES, DEMOLITION KEYNOTES, AND NEW WORK KEYNOTES.

1/8" = 1'-0" 5'0'5' 10' 20'

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

GRAPHIC SCALE:

AS NOTED

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

AD106

11/22/2023

DE

M

OL

IT

IO

N

RE

FL

EC

TE

D

CE

IL

IN

G

PL

AN

AR

EA

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

1/8" = 1'-0"

DEMOLITION REFLECTED CEILING PLAN - AREA 7

PLAN

NORTH

ROOM # ROOM NAME

101-2 CLASSROOM

102 GUIDANCE

103 CLASSROOM

105-2 CLASSROOM

106 CLINIC

107 CLASSROOM

108 MEDIA CENTER

109 CLASSROOM

111 CLASSROOM

113 CLASSROOM

114 CLASSROOM

114A CLASSROOM

115 CLASSROOM

117 CLASSROOM

C-001 MAIN LOBBY

C-002 CORRIDOR

C-003 CORRIDOR

C-005 CORRIDOR

R-001 GIRL'S TOILET

X-001 DEAN 8

X-002 ASSIST PRINCIPAL

X-002A CL.

X-002B BATHROOM

X-002C TOILET

X-003 TEACHER'S WORKROOM

X-003A TOILET

X-004 STORAGE

X-005 SCIENCE WORK ROOM

X-006 SCIENCE STORAGE

X-101A CL.

X-102A OFFICE

X-102B CL.

X-102C OFFICE

X-102D OFFICE

X-102E OFFICE

X-102F CL.

X-102G OFFICE

X-103A CL.

X-105A CL.

X-106A TOILET

X-106B TOILET

X-106C GIRL'S REST

X-106D BOY'S REST

X-106E NURSE'S OFFICE

X-106F WAITING

X-107A CL.

X-108A STUDY

X-108B STUDY

X-108C STUDY

X-108D CL.

X-108E STUDY

X-108F IT

X-108G CONFERENCE

X-108H STOR.

X-109A CL.

X-111A CL.

X-113A CL.

X-114 CL.

X-115A CL.

ROOM SCHEDULE

AREA 7

R ev is io ns

N o.

D at e

D es cr ip

C C

S

S

S S S

UP

101-2

C-001

C-005

X-010

X-011

C-006

X-012 C-008

X-013

X-016

C-007

135A

134A

C-009-1

C-010

138137

142 143

140139

C-004

125127129

C-003

C-002

103 105-2 107 109

114A

A901

A901

A901

A901

A901

A901

A901

A901

A901

A901

A901

A901

A901

A901

A901

A901

A901

A901

A901

A901

A901

A901

A901

3 3

3 3

3 3

4 4

4 4

4 4

X-100C

X-100D X-100E

X-100F

X-100G

X-100G

X-100H X-100A

X-100B

X-011A

X-011B

X-011C

X-011D

X-131A

X-131EX-131DX-131C

X-131F

X-131G X-131H

X-131B

X-015

X-014

X-015A

X-015B

X-013A

X-013B

X-013C

X-013D

X-013G

X-017

X-018 X-013H X-013F

X-013E X-012A

R-004

X-134AB

X-134AA

R-003

R-003A

C-007A

X-134A

X-142A

X-141A X-141B X-137A X-138A X-141C R-005 R-006 X-140A X-140B

C-009A

C-009-2

510509

X-008X-009 R-002

C-003B

S-003 X-007

X-007A

X-121A

X-122A-3

X-118A

X-117A

S-002

533 531

X-003X-002 X-108H

X-108G

X-004

X-005

X-006

R-001

C-003A

X-108E

X-108F

X-108D

X-108CX-108BX-108AX-106F

X-106E

X-106D

X-001

X-106A

X-106B

X-102F

X-102GX-102A

X-102B X-102C X-102D X-102E X-106C

S-001

X-123A

X-118B X-118C

X-122A-1 X-122A-2

X-105AX-103AX-101A X-107A X-109A X-111A X-113A X-115A

X-114 X-002B

X-002A

X-002C

X-003A

NOTE: SEE SHEET A003 FOR GENERAL NOTES, GENERAL DEMOLITION NOTES,

GENERAL NEW WORK NOTES, DEMOLITION KEYNOTES, AND NEW WORK KEYNOTES.

50'30'10'0' 5' 20'5' 1/16" = 1'-0"

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

GRAPHIC SCALE:

AS NOTED

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

A101

11/22/2023

DE

M

OL

IT

IO

N

AN

D

NE

W

W

OR

K

FI

RS

T

FL

OO

R

PL

AN

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

1/16" = 1'-0"

DEMOLITION AND NEW WORK FIRST FLOOR PLAN

ROOM # ROOM NAME

100 MAIN OFFICE

101-2 CLASSROOM

102 GUIDANCE

103 CLASSROOM

105-2 CLASSROOM

106 CLINIC

107 CLASSROOM

108 MEDIA CENTER

109 CLASSROOM

111 CLASSROOM

113 CLASSROOM

114 CLASSROOM

114A CLASSROOM

115 CLASSROOM

116 CLASSROOM

117 CLASSROOM

118 CLASSROOM

119 CLASSROOM

120 CLASSROOM

121 CLASSROOM

122 CLASSROOM

123 CLASSROOM

124 CLASSROOM

125 CLASSROOM

127 CLASSROOM

129 CLASSROOM

131 BAND ROOM

133 CHORUS

134 CLASSROOM

134A CLASSROOM

135 CLASSROOM

135A LAB

136 CLASSROOM

137 CLASSROOM

138 CLASSROOM

139 CLASSROOM

140 CLASSROOM

141 CLASSROOM

142 CLASSROOM

143 CLASSROOM

144 CLASSROOM

505 GYMNASIUM

506 VESTIBULE

507 AUXILIARY GYMNASIUM

508 MEN'S LOCKER

509 CL.

510 OFFICE

511 SPRINKLER

512 STOR.

513 LOCKERS

514 LOCKERS

515 LOCKERS

516 STOR.

517 STOR.

518 CORRIDOR

519 STOR.

520 CL.

521 WOMEN'S LOCKER

522 LOCKERS

523 LOCKERS

524 LOCKERS

525 LOCKERS

526 STOR.

527 TOILET

528 OFFICE

529 CL.

530 JAN.

531 MECH.

532 BOILER

533 Room

534 LOCKER STORAGE

535 LOCKER STORAGE

C-001 MAIN LOBBY

C-002 CORRIDOR

C-003 CORRIDOR

C-003A JAN. CL.

C-003B ELEC.

C-004 CORRIDOR

C-005 CORRIDOR

C-006 CORRIDOR

C-007 CORRIDOR

C-007A VEST.

C-008 CORRIDOR

C-009-1 CORRIDOR-1

C-009-2 CORRIDOR-2

C-009A CL.

C-010 CORRIDOR

R-001 GIRL'S TOILET

R-002 BOYS TOILET

R-003 BOY'S TOILET

R-003A JAN. CL.

R-004 GIRLS' TOILET

R-005 BOY'S TOLIET

R-006 GIRL'S TOILET

S-001 STAIR 3

S-002 STAIR 2

S-003 STAIR 1

X-001 DEAN 8

X-002 ASSIST PRINCIPAL

X-002A CL.

X-002B BATHROOM

X-002C TOILET

X-003 TEACHER'S WORKROOM

X-003A TOILET

X-004 STORAGE

X-005 SCIENCE WORK ROOM

X-006 SCIENCE STORAGE

X-007 OFFICE

X-007A TOILET

X-008 STORAGE

X-009 ATHLETIC DIRECTOR

X-010 AUDITORIUM

X-011 STAGE

X-011A STORAGE

X-011B CL.

X-011C CL.

X-011D STORAGE

X-012 CAFETERIA

X-012A TEACHER'S LOUNGE

X-013 KITCHEN

X-013A DISHWASHER

X-013B KITCHEN STORAGE

X-013C JAN.

X-013D MANAGER

X-013E CL.

X-013F TOILET

X-013G WALK IN REF.

X-013H LOCKER

X-014 OFFICE

ROOM # ROOM NAME

X-015 OFFICE

X-015A CL.

X-015B TOILET

X-016 MECH. / BOILER ROOM

X-017 GARBAGE

X-018 TRASH

X-100A RECORDS

X-100B COPY

X-100C CORRIDOR

X-100D CONFERENCE

X-100E PRINCIPAL

X-100F TOILET

X-100G CL.

X-100G TOILET

X-100H OFFICE

X-101A CL.

X-102A OFFICE

X-102B CL.

X-102C OFFICE

X-102D OFFICE

X-102E OFFICE

X-102F CL.

X-102G OFFICE

X-103A CL.

X-105A CL.

X-106A TOILET

X-106B TOILET

X-106C GIRL'S REST

X-106D BOY'S REST

X-106E NURSE'S OFFICE

X-106F WAITING

X-107A CL.

X-108A STUDY

X-108B STUDY

X-108C STUDY

X-108D CL.

X-108E STUDY

X-108F IT

X-108G CONFERENCE

X-108H STOR.

X-109A CL.

X-111A CL.

X-113A CL.

X-114 CL.

X-115A CL.

X-117A STORAGE

X-118A STORAGE

X-118B CL.

X-118C CL.

X-121A STORAGE

X-122A-1 storage-1

X-122A-2 STORAGE-2

X-122A-3 STORAGE-3

X-123A CL.

X-131A BAND STORAGE

X-131B CORRIDOR

X-131C STOR.

X-131D IT

X-131E STOR.

X-131F STOR.

X-131G STOR.

X-131H STOR.

X-134A LAB

X-134AA STOR.

X-134AB TOILET

X-137A STOR.

X-138A STOR.

X-140A STOR.

X-140B STOR.

X-141A STOR.

X-141B STOR.

X-141C STOR.

X-142A STOR.

ROOM SCHEDULE

PLAN

NORTH

R ev is io ns

N o.

D at e

D es cr ip

C C

J

J

JJJ

S S S

S

S

S S S SW

W

W

W

VTR

VTR

VTR

VTR

VTR

VTR

VTR

VTR

VTR

VTR

VTR

VTR

VTR VTR

VTR

VTR

VTRVTR

VTR

VTR VTR

VTR

VTR VTR

VTR

VTR

VTR

VTR

VTR

VTR VTR

VTR

VTR VTR

VTR

VTR

VTR

VTR

VTR

VTR

VTR

VTR

VTR

VTR

SUSU

VTR

VTR VTR

VTR

VTR

VTR

VTR

VTR

VTR

PC PC

AD

A504

A504

A504

A504

RD

RD

NOTE: MECHANICAL AND ELECTRICAL EQUIPMENT, PIPING

AND CONDUIT ARE SHOWN DIAGRAMMATICALLY. REFER

TO MECHANICAL AND ELECTRICAL DRAWINGS FOR

FURTHER REQUIREMENTS AND INFORMATION NOT

SHOWN.

NOTE: SEE SHEET A003 FOR GENERAL NOTES, GENERAL DEMOLITION NOTES,

GENERAL NEW WORK NOTES, DEMOLITION KEYNOTES, AND NEW WORK KEYNOTES.

1/8" = 1'-0" 5'0'5' 10' 20'

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

GRAPHIC SCALE:

AS NOTED

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

A102

11/22/2023

DE

M

OL

IT

IO

N

AN

D

NE

W

W

OR

K

RO

OF

P

LA

N

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

1/16" = 1'-0"

DEMOLITION AND NEW WORK ROOF PLAN

PLAN

NORTH

R ev is io ns

N o.

D at e

D es cr ip

PC

PC

NOTE: SEE SHEET A003 FOR GENERAL NOTES, GENERAL DEMOLITION NOTES,

GENERAL NEW WORK NOTES, DEMOLITION KEYNOTES, AND NEW WORK KEYNOTES.

C-001

C-005

X-010

X-011

X-100C

X-100D

X-100E

X-100F

X-100G

X-100G

X-100H X-100A

X-100B

X-011A

X-011B

X-011C

X-011D

X-131A

X-131E

X-131DX-131C

X-131F X-131G X-131H

X-131B

1/8" = 1'-0" 5'0'5' 10' 20'

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

GRAPHIC SCALE:

AS NOTED

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

A103

11/22/2023

NE

W

W

OR

K

RE

FL

EC

TE

D

CE

IL

IN

G

PL

AN

AR

EA

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

1/8" = 1'-0"

NEW WORK REFLECTED CEILING PLAN - AREA 1

PLAN

NORTH

ROOM # ROOM NAME

100 MAIN OFFICE

131 BAND ROOM

133 CHORUS

C-001 MAIN LOBBY

C-002 CORRIDOR

C-005 CORRIDOR

C-006 CORRIDOR

C-007 CORRIDOR

R-003 BOY'S TOILET

R-003A JAN. CL.

X-001 DEAN 8

X-010 AUDITORIUM

X-011 STAGE

X-011A STORAGE

X-011B CL.

X-011C CL.

X-011D STORAGE

X-100A RECORDS

X-100B COPY

X-100C CORRIDOR

X-100D CONFERENCE

X-100E PRINCIPAL

X-100F TOILET

X-100G CL.

X-100G TOILET

X-100H OFFICE

X-102A OFFICE

X-102B CL.

X-102C OFFICE

X-131A BAND STORAGE

X-131B CORRIDOR

X-131C STOR.

X-131D IT

X-131E STOR.

X-131F STOR.

X-131G STOR.

X-131H STOR.

ROOM SCHEDULE

AREA 1

R ev is io ns

N o.

D at e

D es cr ip

NOTE: SEE SHEET A003 FOR GENERAL NOTES, GENERAL DEMOLITION NOTES,

GENERAL NEW WORK NOTES, DEMOLITION KEYNOTES, AND NEW WORK KEYNOTES.

OPEN TO ABOVE

C-006

X-012

C-008

X-013

X-016

X-015

X-014

X-015A

X-015B

X-013A

X-013B

X-013C

X-013DX-013GX-017

X-018

X-013H

X-013F

X-013E X-012A

1/8" = 1'-0" 5'0'5' 10' 20'

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

GRAPHIC SCALE:

AS NOTED

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

A104

11/22/2023

NE

W

W

OR

K

RE

FL

EC

TE

D

CE

IL

IN

G

PL

AN

AR

EA

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

1/8" = 1'-0"

NEW WORK REFLECTED CEILING PLAN - AREA 2

PLAN

NORTH

ROOM # ROOM NAME

131 BAND ROOM

133 CHORUS

C-005 CORRIDOR

C-006 CORRIDOR

C-007 CORRIDOR

C-008 CORRIDOR

R-003 BOY'S TOILET

R-003A JAN. CL.

R-004 GIRLS' TOILET

X-011A STORAGE

X-011B CL.

X-011C CL.

X-011D STORAGE

X-012 CAFETERIA

X-012A TEACHER'S LOUNGE

X-013 KITCHEN

X-013A DISHWASHER

X-013B KITCHEN STORAGE

X-013C JAN.

X-013D MANAGER

X-013E CL.

X-013F TOILET

X-013G WALK IN REF.

X-013H LOCKER

X-014 OFFICE

X-015 OFFICE

X-015A CL.

X-015B TOILET

X-016 MECH. / BOILER ROOM

X-017 GARBAGE

X-018 TRASH

X-131F STOR.

X-131G STOR.

X-131H STOR.

ROOM SCHEDULE

AREA 2

R ev is io ns

N o.

D at e

D es cr ip

C-007

135135A

134A

R-004

X-134AB

X-134AA

R-003

R-003A

C-007A

X-134A

C-009-1

C-010

138137

142 143

140139

X-142A

X-141A X-141B X-137A X-138A X-141C R-005

R-006

X-140A

X-140B

C-009A

C-009-2

1/8" = 1'-0" 5'0'5' 10' 20'

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

GRAPHIC SCALE:

AS NOTED

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

A105

11/22/2023

NE

W

W

OR

K

RE

FL

EC

TE

D

CE

IL

IN

G

PL

AN

S

- A

RE

A

AN

D

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

N.T.S.

NEW WORK REFLECTED CEILING PLAN - AREA 3

N.T.S.

NEW WORK REFLECTED CEILING PLAN - AREA 4

PLAN

NORTH

PLAN

NORTH

ROOM # ROOM NAME

134 CLASSROOM

134A CLASSROOM

135 CLASSROOM

135A LAB

136 CLASSROOM

137 CLASSROOM

138 CLASSROOM

139 CLASSROOM

140 CLASSROOM

141 CLASSROOM

142 CLASSROOM

143 CLASSROOM

144 CLASSROOM

C-005 CORRIDOR

C-006 CORRIDOR

C-007 CORRIDOR

C-007A VEST.

C-008 CORRIDOR

C-009-1 CORRIDOR-1

C-009-2 CORRIDOR-2

C-009A CL.

C-010 CORRIDOR

R-003 BOY'S TOILET

R-003A JAN. CL.

R-004 GIRLS' TOILET

R-005 BOY'S TOLIET

R-006 GIRL'S TOILET

X-134A LAB

X-134AA STOR.

X-134AB TOILET

X-137A STOR.

X-138A STOR.

X-140A STOR.

X-140B STOR.

X-141A STOR.

X-141B STOR.

X-141C STOR.

X-142A STOR.

ROOM SCHEDULE

AREAS 3&4

R ev is io ns

N o.

D at e

D es cr ip

C-004

125127129

510509533 531

535 528

1/8" = 1'-0" 5'0'5' 10' 20'

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

GRAPHIC SCALE:

AS NOTED

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

A106

11/22/2023

NE

W

W

OR

K

RE

FL

EC

TE

D

CE

IL

IN

G

PL

AN

AR

EA

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

1/8" = 1'-0"

NEW WORK REFLECTED CEILING PLAN - AREA 5

PLAN

NORTH

ROOM # ROOM NAME

123 CLASSROOM

125 CLASSROOM

127 CLASSROOM

129 CLASSROOM

505 GYMNASIUM

506 VESTIBULE

507 AUXILIARY GYMNASIUM

508 MEN'S LOCKER

509 CL.

510 OFFICE

511 SPRINKLER

512 STOR.

513 LOCKERS

514 LOCKERS

515 LOCKERS

516 STOR.

517 STOR.

518 CORRIDOR

519 STOR.

520 CL.

521 WOMEN'S LOCKER

522 LOCKERS

523 LOCKERS

524 LOCKERS

525 LOCKERS

526 STOR.

527 TOILET

528 OFFICE

529 CL.

530 JAN.

531 MECH.

532 BOILER

533 Room

534 LOCKER STORAGE

535 LOCKER STORAGE

C-003 CORRIDOR

C-004 CORRIDOR

R-002 BOYS TOILET

X-007A TOILET

X-008 STORAGE

X-009 ATHLETIC DIRECTOR

ROOM SCHEDULE

AREA 5

R ev is io ns

N o.

D at e

D es cr ip

CL

EQEQ

4'- 6"

4'- 6"

EQ

EQ

EQ

EQ

EQ

EQ

EQEQ

AL

IG

N

CL

C L

EQEQ

EQ

EQ

CL

C-003

122120

118116

X-008

X-009

R-002

C-003B

S-003

X-007

X-007A

X-121A

X-122A-3X-118A

X-117A

S-002

X-004

X-005 X-006

R-001

C-003A S-001

X-123A

X-118B

X-118C

X-122A-1

X-122A-2

C-011

210208

204202 R-008

C-011BS-003

212206

S-002

R-007

C-011A

S-001 R-008

X-019

R-007

X-201A X-203A X-205A X-207A X-209 X-211A X-213A X-215A X-217A

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

NONE

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

A107

11/22/2023

NE

W

W

OR

K

RE

FL

EC

TE

D

CE

IL

IN

G

PL

AN

S

- A

RE

A

AN

D

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

N.T.S.

FIRST FLOOR NEW WORK REFLECTED CEILING PLAN - AREA 6

N.T.S.

SECOND FLOOR NEW WORK REFLECTED CEILING PLAN - AREA 8

PLAN

NORTH

PLAN

NORTH

ROOM # ROOM NAME

116 CLASSROOM

117 CLASSROOM

118 CLASSROOM

119 CLASSROOM

120 CLASSROOM

121 CLASSROOM

122 CLASSROOM

123 CLASSROOM

124 CLASSROOM

C-003 CORRIDOR

C-003A JAN. CL.

C-003B ELEC.

R-001 GIRL'S TOILET

R-002 BOYS TOILET

S-001 STAIR 3

S-002 STAIR 2

S-003 STAIR 1

X-004 STORAGE

X-005 SCIENCE WORK ROOM

X-006 SCIENCE STORAGE

X-007 OFFICE

X-007A TOILET

X-008 STORAGE

X-009 ATHLETIC DIRECTOR

X-117A STORAGE

X-118A STORAGE

X-118B CL.

X-118C CL.

X-121A STORAGE

X-122A-1 storage-1

X-122A-2 STORAGE-2

X-122A-3 STORAGE-3

X-123A CL.

201 CLASSROOM

202 CLASSROOM

203 CLASSROOM

204 CLASSROOM

205 CLASSROOM

206 CLASSROOM

207 CLASSROOM

208 CLASSROOM

209 CLASSROOM

210 CLASSROOM

211 CLASSROOM

212 CLASSROOM

213 CLASSROOM

214 CLASSROOM

215 CLASSROOM

217 CLASSROOM

C-011 CORRIDOR

C-011A JAN. CL.

C-011B ELEC.

R-007 GIRL'S TOILET

R-008 BOYS TOILET

S-001 STAIR

S-002 STAIR

S-003 STAIR

X-019 GUARD BOOTH

X-201A CL.

X-203A CL.

X-205A CL.

X-207A CL.

X-209 CL.

X-211A CL.

X-213A CL.

X-215A CL.

X-217A CL.

ROOM SCHEDULE

AREA 6

R ev is io ns

N o.

D at e

D es cr ip

CLEQ EQ

EQ

EQ

C L

CLEQ EQ

101-2

C-002

103 105-2 107 109 111 113 115

114A

X-003X-002

X-108H

X-108GX-108E X-108F

X-108D

X-108CX-108BX-108AX-106F

X-106E

X-106D

X-001

X-106A

X-106B

X-102F

X-102GX-102A

X-102B

X-102C X-102D X-102E X-106C

X-105AX-103AX-101A X-107A X-109A X-111A X-113A X-115A

X-114

X-002B

X-002A

X-002C

X-003A

1/8" = 1'-0" 5'0'5' 10' 20'

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

GRAPHIC SCALE:

AS NOTED

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

A108

11/22/2023

NE

W

W

OR

K

RE

FL

EC

TE

D

CE

IL

IN

G

PL

AN

S

- A

RE

A

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

1/8" = 1'-0"

NEW WORK REFLECTED CEILING PLAN - AREA 7

ROOM # ROOM NAME

101-2 CLASSROOM

102 GUIDANCE

103 CLASSROOM

105-2 CLASSROOM

106 CLINIC

107 CLASSROOM

108 MEDIA CENTER

109 CLASSROOM

111 CLASSROOM

113 CLASSROOM

114 CLASSROOM

114A CLASSROOM

115 CLASSROOM

117 CLASSROOM

C-001 MAIN LOBBY

C-002 CORRIDOR

C-003 CORRIDOR

C-005 CORRIDOR

R-001 GIRL'S TOILET

X-001 DEAN 8

X-002 ASSIST PRINCIPAL

X-002A CL.

X-002B BATHROOM

X-002C TOILET

X-003 TEACHER'S WORKROOM

X-003A TOILET

X-004 STORAGE

X-005 SCIENCE WORK ROOM

X-006 SCIENCE STORAGE

X-101A CL.

X-102A OFFICE

X-102B CL.

X-102C OFFICE

X-102D OFFICE

X-102E OFFICE

X-102F CL.

X-102G OFFICE

X-103A CL.

X-105A CL.

X-106A TOILET

X-106B TOILET

X-106C GIRL'S REST

X-106D BOY'S REST

X-106E NURSE'S OFFICE

X-106F WAITING

X-107A CL.

X-108A STUDY

X-108B STUDY

X-108C STUDY

X-108D CL.

X-108E STUDY

X-108F IT

X-108G CONFERENCE

X-108H STOR.

X-109A CL.

X-111A CL.

X-113A CL.

X-114 CL.

X-115A CL.

ROOM SCHEDULE

AREA 7

PLAN

NORTH

R ev is io ns

N o.

D at e

D es cr ip

EXISTING SPRAY FOAM

ROOFING.

6"

VARIES

OPENING WIDTH 6"

PATCH (SEE NOTE

BELOW)

EXISTING METAL DECK

NOTE:

PROVIDE AN 18 GAGE GALVANIZED TARGET PATCH OVER ALL ABANDONED DECK

OPENINGS LESS THAN 12” WIDE. OPENINGS EXCEEDING 12” WIDE BUT LESS THAN 30”

SHALL BE PATCHED WITH METAL DECK TO MATCH EXISTING OR ¼” PLATE WITH # 12

TEK SCREWS AT 6 INCHES O.C. COVER PATCH SHALL EXTEND 6” BEYOND EACH SIDE

OF OPENING.

INFILL OPENING WITH NEW

SPRAY FOAM ROOFING

COMPATIBLE WITH EXISTING

SYSTEM

EXISTING OPENING IN ROOF DECK

PREFABRICATED GALVANIZED

STEEL EQUIPMENT RAIL WITH

NAILER. TOP OF RAIL SHALL BE

LEVEL.

.040 ALUMINUM

COUNTER FLASHING

EXISTING ROOF DECK

SELF ADHERED MEMBRANE

SHEET METAL CAP FLASHING

EXISTING BUILT UP ROOF TO REMAIN

INSULATION FILLER

UN

LE

SS

O

TH

ER

W

IS

E

NO

TE

D

1'- 8"

T

YP

INFILL OPENING WITH SPRAY FOAM

ROOFING COMPATIBLE WITH

EXISTING SYSTEM.

TREATED WOOD BLOCKING AS

REQUIRED TO ACHIEVE INDICATED

HEIGHT.

EXISTING SPRAY FOAM ROOFING

TO REMAIN.

MECANICAL OR ELECTRICAL

EQUIPMENT. REFER TO

MECHAINCAL AND ELECTRICAL

DRAWINGS.

EXISTING ROOF DECK

EXISTING BUILT UP ROOF

TO REMAIN

EXISTING SPRAY FOAM

ROOFING TO REMAIN.

REMOVE EXISTING SPRAY

FOAM ROOFING AS REQUIRED

TO ACCOMADATE NEW WORK.

REMOVE BUILT UP ROOFING

AS REQUIRED TO

ACCOMADATE NEW WORK.

DEMOLITION NEW WORK

INSULATED LID W/ GASKET

PIPING - SEE MECHANICAL AND

ELECTRICAL DRAWINGS

CURB

GASKET

PIPE CHASE HOUSING AND CURB BASED

ON ALTA PRODUCTS MODEL AL-158C CURB

AND MODEL AL-161010 HOUSING OR EQUAL

CHASE HOUSING

EXISTING BUILT UP

ROOF TO REMAIN.

INFILL OPENING WITH SPRAY FOAM

ROOFING COMPATIBLE WITH

EXISTING SYSTEM.

EXISTING ROOF DECK

EXISTING SPRAY FOAM

ROOFING TO REMAIN.

EXISTING BUILT UP

ROOF TO REMAIN.

REMOVE SPRAY FOAM

ROOFING AS REQUIRED TO

ACCOMMODATE NEW

WORK.

EXISTING ROOF DECK

EXISTING SPRAY FOAM

ROOFING TO REMAIN.

REMOVE EXISTING BUILT UP

ROOFING AS REQUIRED TO

ACCOMMODATE NEW WORK

CUT HOLE IN ROOF DECK AS REQUIRED

TO ACCOMMODATE NEW PIPES/CONDUITS.

REFER TO PLUMBING, ELECTRICAL, AND

MECHANICAL FOR PIPE/CONDUIT SIZING

REQUIREMENTS.

DEMOLITION NEW WORK

EXISTING INSULATION

AND COVER BOARD.

6"

VARIES

OPENING WIDTH 6"

PATCH (SEE NOTE

BELOW)

EXISTING METAL DECK

NOTE:

PROVIDE AN 18 GAGE GALVANIZED TARGET PATCH OVER ALL ABANDONED DECK

OPENINGS LESS THAN 12” WIDE. OPENINGS EXCEEDING 12” WIDE BUT LESS THAN 30”

SHALL BE PATCHED WITH METAL DECK TO MATCH EXISTING OR ¼” PLATE WITH # 12

TEK SCREWS AT 6 INCHES O.C. COVER PATCH SHALL EXTEND 6” BEYOND EACH SIDE

OF OPENING.

EXISTING OPENING IN ROOF DECK

EXISTING MODIFIED

BITRUMENT ROOFING

SYSTEM

MODIFIED BITRUMENT

ROOFING SYSTEM TO

MATCH EXISTING. LAP

JOINTS AS SHOWN.

INSULATED LID W/ GASKET

PIPING - SEE MECHANICAL AND

ELECTRICAL DRAWINGS

CURB

GASKET

PIPE CHASE HOUSING AND CURB BASED

ON ALTA PRODUCTS MODEL AL-158C CURB

AND MODEL AL-161010 HOUSING OR EQUAL

CHASE HOUSING

EXISTING ROOF DECKEXISTING ROOF DECK

REMOVE EXISTING MODIFIED

BITRUMENT ROOF,

COVERBOARD, AND

INSULATION AS REQUIRED TO

ACCOMADATE NEW WORK.

CUT HOLE IN ROOF DECK AS REQUIRED

TO ACCOMMODATE NEW PIPES/CONDUITS.

REFER TO PLUMBING, ELECTRICAL, AND

MECHANICAL FOR PIPE/CONDUIT SIZING

REQUIREMENTS.

DEMOLITION NEW WORK

EXISTING MODIFIED BITRUMENT

ROOF, COVERBOARD, AND

INSULATION TO REMAIN.

EXISTING MODIFIED BITRUMENT

ROOF, COVERBOARD, AND

INSULATION TO REMAIN.

SELF ADHERED MEMBRANE

FLASHING

PRESSURE TREATED WOOD

BLOCKING

PREFABRICATED GALVANIZED

STEEL EQUIPMENT RAIL WITH

NAILER. TOP OF RAIL SHALL BE

LEVEL.

.040 ALUMINUM

COUNTER FLASHING

EXISTING ROOF DECK

SELF ADHERED MEMBRANE

SHEET METAL CAP FLASHING

INSULATION FILLER

UN

LE

SS

O

TH

ER

W

IS

E

NO

TE

D

1'- 8"

T

YP

INFILL OPENING WITH INSULATION,

AND COVERBOARD TO MATCH

EXISTING ROOF ASEMBELY.

TREATED WOOD BLOCKING AS

REQUIRED TO ACHIEVE INDICATED

HEIGHT.

MECANICAL OR ELECTRICAL

EQUIPMENT. REFER TO

MECHAINCAL AND ELECTRICAL

DRAWINGS.

EXISTING ROOF DECK

DEMOLITION NEW WORK

REMOVE EXISTING MODIFIED

BITRUMENT ROOF,

COVERBOARD, AND

INSULATION AS REQUIRED TO

ACCOMADATE NEW WORK.

EXISTING MODIFIED BITRUMENT

ROOF, COVERBOARD, AND

INSULATION TO REMAIN.

EXISTING MODIFIED BITRUMENT

ROOF, COVERBOARD, AND

INSULATION TO REMAIN.

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

NONE

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

A501

11/22/2023

TY

PI

CA

L

SE

CT

IO

NS

, E

LE

VA

TI

ON

S

DE

TA

IL

S

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

1 1/2" = 1'-0"A501

1 TYPICAL ROOF PATCH - FOAM ROOF

1 1/2" = 1'-0"A501

5 TYPICAL EQUIPMENT SUPPORT RAIL - FOAM ROOF

1 1/2" = 1'-0"A501

3 TYPICAL PIPE/CONDUIT CHASE HOUSING - FOAM ROOF

1 1/2" = 1'-0"A501

2 TYPICAL ROOF PATCH - MOD BIT ROOF

1 1/2" = 1'-0"A501

4 TYPICAL PIPE/CONDUIT CHASE HOUSING - MOD BIT ROOF

1 1/2" = 1'-0"A501

6 TYPICAL EQUIPMENT SUPPORT RAIL - MOD BIT ROOF

R ev is io ns

N o.

D at e

D es cr ip

EXISTING METAL

ROOF DECK

SELF ADHERED

MEMBRANE

2 PIECE .040 ALUMINUM

COUNTER FLASHING

PRE-MANUFACTURED ROOF CURB W/ NAILER.

PROVIDE CURB INSULATION OF TYPE, AND WITH

FACER AS REQUIRED FOR INSTALLATION OF

ROOFING

TOP OF CURB TO BE LEVEL

NEW MECHANICAL EQUIPMENT -

SEE MECHANICAL

CONTINUOUS COMPRESSIBLE ADHESIVE

BACKED SPONGE NEOPRENE GASKET

UN

LE

SS

O

TH

ER

W

IS

E

NO

TE

D

1'-

" T

YP

PROVIDE HORIZONTAL BRACING

@ 48" O.C.

INFILL OPENING WITH SPRAY FOAM

ROOFING COMPATIBLE WITH

EXISTING SYSTEM.

EXISTING BUILT UP ROOF TO

REMAIN

TREATED WOOD BLOCKING AS

REQUIRED TO ACHIEVE

INDICATED HEIGHT.

NEW OPENING IN ROOF DECK.

REFER TO STRUCTURAL FOR

REINFORCEMENT REQUIREMENTS

EXISTING SPRAY FOAM

ROOFING TO REMAIN.

EXISTING METAL

ROOF DECK

EXISTING BUILT UP ROOF TO

REMAIN

EXISTING SPRAY FOAM

ROOFING TO REMAIN.

DEMOLITION NEW WORK

REMOVE EXISTING SPRAY FOAM

ROOFING AS REQUIRED TO

ACCOMADATE NEW WORK.

REMOVE EXISTING BUILT UP

ROOFING AS REQUIRED TO

ACCOMADATE NEW WORK.

NEW ROOF PENETRATION. REFER TO

MECHANICAL DRAWINGS AND

SPECIFCIATIONS FOR SIZING.

EXISTING METAL

ROOF DECK

SELF ADHERED

MEMBRANE

2 PIECE .040 ALUMINUM

COUNTER FLASHING

PRE-MANUFACTURED ROOF CURB W/ NAILER.

PROVIDE CURB INSULATION OF TYPE, AND WITH

FACER AS REQUIRED FOR INSTALLATION OF

ROOFING

TOP OF CURB TO BE LEVEL

NEW MECHANICAL EQUIPMENT -

SEE MECHANICAL

CONTINUOUS COMPRESSIBLE ADHESIVE

BACKED SPONGE NEOPRENE GASKET

PROVIDE HORIZONTAL BRACING

@ 48" O.C.

EXISTING MODIFIED

BITRUMENT ROOF,

COVERBOARD, AND

INSULATION REMAIN

TREATED WOOD BLOCKING AS

REQUIRED TO ACHIEVE

INDICATED HEIGHT.

NEW OPENING IN ROOF DECK. REFER

TO STRUCTURAL FOR

REINFORCEMENT REQUIREMENTS

UN

LE

SS

O

TH

ER

W

IS

E

NO

TE

D

1'-

" T

YP

CUT NEW OPENING IN ROOF DECK.

REFER TO STRUCTURAL AND

MECHANICAL FOR SIZING

REQUIREMENTS.

EXISTING METAL

ROOF DECK

EXISTING MODIFIED

BITRUMENT ROOF,

COVERBOARD, AND

INSULATION REMAIN

REMOVE EXISTING

MODIFIED BITRUMENT

ROOF, COVERBOARD, AND

INSULATION AS REQUIRED

TO ACCOMADATE NEW

WORK.

DEMOLITION NEW WORK

PATCH WITH COVERBOARD,

AND INSULATION TO MATCH

EXISTING.

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

NONE

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

A502

11/22/2023

TY

PI

CA

L

SE

CT

IO

NS

, E

LE

VA

TI

ON

S

DE

TA

IL

S

Designer

Author

Checker

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

3" = 1'-0"A502

1 TYPICAL ROOF CURB - FOAM ROOF

3" = 1'-0"A502

2 TYPICAL ROOF CURB - MOD BIT ROOF

R ev is io ns

N o.

D at e

D es cr ip

DEMOLITION NEW WORK

EXISTING WINDOW

ASSEMBLY TO REMAIN. TYP.

REMOVE EXISTING WINDOW

ASSEMBLY TO THE EXTENTS

INDICATED.

FIELD VERIFY

+/- 3'-9 1/2"

DUCT PENETRATION

DUCT PENETRATION

.05 PREFINISHED ALUMINUM BREAK

METAL PANEL

STRUCTURAL SUPPORT. SEE

STRUCTURAL DRAWINGS.

EXTENTS OF PACKAGED HVAC UNIT.

REFER MECHANICAL DRAWING FOR

DIMENSIONS.

FI

EL

D W

OR

K

- 6

'-8

6"

EXISTING TO REMAIN LOUVER

WHERE OCCURS. FIELD VERIFY.

.05 PREFINISHED ALUMINUM BREAK

METAL PANEL WITH HEMMED

EDGES OVER EXISTING LOUVER

WHERE OCCURS. 1"

T

YP

A503

A503

PROVIDE CONTINUOUS BEAD OF

SEALANT BETWEEN METAL PANEL

AND MASONRY AS INDICATED.

EXTENTS OF EXISTING LOUVER.

A503

A503

O.H.

DEMOLITION NEW WORK

NO

TE

SE

E

SE

E

NO

TE

SE

E

NO

TE

6"

SE

E

NO

TE

.05 PREFINISHED ALUMINUM BREAK METAL PANEL

5/8" GLASS MAT SHEATHING

8" COLD FORMED FRAME

R-19 FIBERGLASS BATT INSULATION

5/8" GYPSUM BOARD. PAINT TO MATCH

ADJACENT WALL COLOR.

PACKAGE HVAC UNIT. SEE MECHANICAL DRAWINGS.

SELF-ADHERING MEMBRANE

NOTE 1:

DIMENSIONS SHALL BE DERIVED FROM

DIMENSIONS OF PACKAGED UNITS. REFER TO

MECHANICAL DRAWINGS, AND PRODUCT CUT

SHEET FOR REQUIREMENTS. DIMENSIONS OF

PACKAGED UNITS MAY VARY.

EXISTING HVAC

EQUIPMENT OCCURS.

ABANDON IN PLACE.

REMOVE EXISTING WINDOW

ASSEMBLY TO THE EXTENTS

INDICATED

STRUCTURAL STEEL ANGLE. SEE

STRUCTURAL DRAWINGS.

- 6

'-9

/4 " F

IE

LD

V

ER

IF

Y

SE

E

NO

TE

EXISTING WALL ASEMBLY

TO REMAIN.

DUCT. TYP.

MECHANICAL GRILLE. CAULK ALL

AROUND. SEE MECHANICAL FOR

FURTHER REQUIREMENTS. TYP.

FACE OF WALL BEYOND

NOTE 2:

TYPICAL SILL HEIGHT IS +/-3'-6" UON. IN ROOMS

137, 140, 141, AND 144 SILL HEIGHT IS +/- 4'-10

1/2". FIELD VERIFY ALL HEIGHTS PRIOR TO

WORK.

EXISTING STRUCTURAL

STEEL HEADER

A503

A503

EXTENTS OF PACKAGED HVAC UNIT.

REFER MECHANICAL DRAWING FOR

DIMENSIONS.

STRUCTURAL SUPPORT. SEE

STRUCTURAL DRAWINGS.

DUCT PENETRATION

SAWCUT MASONRY TO PROVIDE

OPENINGS FOR NEW WORK DUCT

PENETRATION. LOCATE CUTS ON

MORTAR JOINTS WHERE POSSIBLE.

TYP.

DUCT PENETRATION

DEMOLITION NEW WORK

PROVIDE MASONRY INFILL. BRICK TO

AND MORTAR COLOR TO MATCH

EXISTING. TYP.

REMOVE BRICK MASONRY TO THE

EXTENTS INDICATED INDICATED.

TYP.

MIN.

8" SEE NOTE 1

MIN.

�8"

NO

TE

SE

E

MIN.

8" SEE NOTE 1

MIN.

�8"

NOTE 1:

DIMENSIONS SHALL BE DERIVED FROM

DIMENSIONS OF PACKAGED UNITS. REFER TO

MECHANICAL DRAWINGS, AND PRODUCT CUT

SHEET FOR REQUIREMENTS. DIMENSIONS OF

PACKAGED UNITS MAY VARY.

CLASSROOM FINISH FLOOR HEIGHT

8"

NO

TE

SE

E

A503

A503

DEMOLITION NEW WORK

EXISTING MASONRY CONSTRUCTION

TO REMAIN. TYP.

NOTE 1:

DIMENSIONS SHALL BE DERIVED FROM

DIMENSIONS OF PACKAGED UNITS. REFER TO

MECHANICAL DRAWINGS, AND PRODUCT CUT

SHEET FOR REQUIREMENTS. DIMENSIONS OF

PACKAGED UNITS MAY VARY.

NO

TE

SE

E

SE

E

NO

TE

NO

TE

SE

E

SE

E

NO

TE

SAWCUT MASONRY TO PROVIDE

OPENINGS FOR NEW WORK DUCT

PENETRATION. LOCATE CUTS ON

MORTAR JOINTS WHERE POSSIBLE.

TYP.

REMOVE BRICK MASONRY TO THE

EXTENTS INDICATED.

REMOVE BRICK MASONRY TO THE

EXTENTS INDICATED.

FINISH FLOOR

8"

INFILL WITH BRICK MASONRY

TO MATCH EXISTING. TYP.

LINTEL. SEE STRUCTURAL. TYP.

0.50 PREFINISHED

THROUGH WALL FLASHING.

TYP.

DUCT

PACKAGED HVAC UNIT. SEE

MECHANICAL DRAWINGS AND

MANUFACTURER'S CUT SHEETS.

INSTALL PER MANUFACTURER'S

GUIDANCE.

MECHANICAL GRILLE. CAULK ALL

AROUND. SEE MECHANICAL FOR

FURTHER REQUIREMENTS.

MECHANICAL GRILLE. CAULK ALL

AROUND. SEE MECHANICAL FOR

FURTHER REQUIREMENTS.

STRUCTURAL SUPPORT. SEE

STRUCTURAL.

DUCT

CONTINOUS BEAD OF SEALANT

ALL AROUND.

PACKAGED HVAC UNIT. SEE

MECHANICAL.

EXISTING WINDOW

ASSEMBLY TO REMAIN.

8" COLD FORMED FRAME

.05 PREFINISHED ALUMINUM

BREAK METAL PANEL

5/8" GLASS MAT SHEATHING

R-19 FIBERGLASS

BATT INSULATION

5/8" GYPSUM BOARD. PAINT TO MATCH

ADJACENT WALL COLOR.

SELF-ADHERING

MEMBRANE FLASHING

SEALANT. TYP.

0.50 PREFINISHED THROUGH

WALL FLASHING

DUCT. SEE MECHANICAL.

VENT. SEE MECHANICAL.

J BEAD

INTERIOR

EXTERIOR

PACKAGED HVAC UNIT. SEE

MECHANICAL.

8" COLD FORMED FRAME

.05 PREFINISHED ALUMINUM

BREAK METAL PANEL

5/8" GLASS MAT SHEATHING

R-19 FIBERGLASS

BATT INSULATION

5/8" GYPSUM BOARD.

PAINT TO MATCH

ADJACENT WALL COLOR.

SELF-ADHERING

MEMBRANE FLASHING

SEALANT. TYP.0.50 PREFINISHED THROUGH

WALL FLASHING WITH DRIP

EDGE.

DUCT. SEE MECHANICAL.

VENT. SEE MECHANICAL.

J BEAD

0.50 PREFINISHED THROUGH

WALL FLASHING

STEEL PLATE AND

ANCHOR. SEE

STRUCTURAL

DRAWINGS.

INTERIOREXTERIOR

8" COLD FORMED

FRAMING AT 12" O.C.

.05 PREFINISHED ALUMINUM

BREAK METAL PANEL

5/8" GLASS MAT SHEATHING

R-19 FIBERGLASS

BATT INSULATION

5/8" GYPSUM BOARD.

PAINT TO MATCH

ADJACENT WALL COLOR.

SELF-ADHERED MEMBRANE

FLASHING

SEALANT. TYP.

0.50 PREFINISHED THROUGH

WALL FLASHING WITH DRIP

EDGE.

J BEAD

WOOD BLOCKING

INTERIOREXTERIOR

BACKER ROD AND SEALANT

Designed By:

1277 PERIMETER PARKWAY

VIRGINIA BEACH, VIRGINIA

23454

(757) 499-7223

Drawn By:

Checked By:

Scale:

Date:

PROJECT NUMBER:

SEAL

NONE

KEY PLAN:

'E'

'E'

'B'

'B'

'A' 'A'

'C'

'C'

'D'

'D'

4 5

AZ

AL

EA

G

AR

D

EN

S

M

ID

D

LE

S C

H O

O L

H

VA

C S

YS

TE

M R

EP

LA

C

EM

EN

T

23008

A503

11/22/2023

TY

PI

CA

L

SE

CT

IO

NS

, E

LE

VA

TI

ON

S

DE

TA

IL

S

LHS

LHS

RS

A

ZA

LE

A

GA

RD

EN

R

D, N

OR

FO

LK

, V

A

N.T.S.A503

1 TYPICAL WINDOW PENETRATION - ELEVATION

N.T.S.A503A503

2 TYPICAL WINDOW PENETRATION - SECTION

N.T.S.A503

3 TYPICAL MASONRY PENETRATION - ELEVATION

N.T.S.A503A503

4 TYPICAL MASONRY PENETRATION - SECTION

N.T.S.A503A503

7 TYPICAL WINDOW PENETRATION – SECTION - JAMB

N.T.S.A503A503

5 TYPICAL WINDOW PENETRATION – SECTION - SILL

N.T.S.A503A503

6 TYPICAL WINDOW PENETRATION – SECTION - HEAD

R ev is io ns

N o.

D at e

D es cr ip

NEW MECHANICAL EQUIPMENT - SEE MECHANICAL

CONTINUOUS COMPRESSIBLE ADHESIVE

BACKED SPONGE NEOPRENE GASKET. TYP.

DEMOLITION NEW WORK

EXISTING STANDING SEAM METAL ROOF TO REMAIN

EXISTING BATT INSULATION TO REMAIN

CUT AND PULL BACK EXISTING BATT INSULATION. SALVAGE FOR

LATER REINSTALLATION.

EXISTING CONCEALED ROOF ASSEMBLY TO REMAIN.

CREATE OPENING IN EXISTING CONCEALED ROOF ASSEMBLY. SIZE

OPENING TO ALLOW PASSAGE OF NEW DUCT. REFER TO

MECHANICAL FOR DUCT SIZE.

EXISTING BUILT UP ROOFING TO REMAIN.

REMOVE EXISTING BUILT UP ROOFING TO THE

EXTEND INDICATED AND AS REQUIRED TO

ACCOMMODATE THE NEW WORK.

REMOVE EXISTING STANDING SEAM METAL ROOFING

TO THE EXTEND INDICATED AND AS REQUIRED TO

ACCOMMODATE THE NEW WORK.

STRUCTURAL REINFORCING. REFER TO STRUCTURAL FOR REQUIREMENTS.

EXISTING CONCEALED ROOF ASSEMBLY TO REMAIN

EXISTING BATT INSULATION TO REMAIN.

REINSTALL SALVAGE BATT INSULATION. TYP.

TREATED WOOD BLOCKING.

PRE-MANUFACTURED ROOF CURB W/ NAILER COMPATIBLE

WITH METAL ROOFING SYSTEM.

PRE-MANUFACTURED ROOF CURB W/ NAILER. TYP.

MECHANICAL DUCT. SEE MECHANICAL.

FI

EL

D

VE

RI

FY

AND STRUCTURAL DRAWINGS

REFER TO MECHANICAL

STRUCTURAL REINFORCING. REFER TO STRUCTURAL FOR

REQUIREMENTS.

SELF ADHERED MEMBRANE FLASHING. TYP

2 PIECE .040 ALUMINUM COUNTER FLASHING. TYP.

.040 PREFINISHED BREAK METAL FLASHING WITH

HEMMED DRIP EDGE. TYP.

.040 BREAK METAL CRICKET. SLOPE SHALL BE 1/4" PER

FOOT OVER SURROUNDING SLOPE.

SELF ADHERED MEMBRANE FLASHING

.040 PREFINISHED BREAK METAL FLASHING SET IN

BED OF SEALANT.

2 PIECE .040 ALUMINUM COUNTER FLASHING

METAL END CLOSURES COMPATIBLE WITH METAL

ROOFING SYSTEM.

METAL END CLOSURES

COMPATIBLE WITH METAL

ROOFING SYSTEM.

8" M

IN

1'- 6"

M

IN

PROVIDE FLASHING PAN TO MATCH EXISTING ROOF

SYSTEM. INSERT FLASHING PAN UNDERNEATH EXISTING

ROOF SYSTEM, AND CAULK JOINT.

NOTES:

1) TOP OF ALL CURBS SHALL BE LEVEL.

2) PROVIDE HORIZONTAL BRACING INSIDE OF CURBS AT 48" O.C.

3) CURB SIZES ARE ATYPICAL. CUSTOM CURBS MAY BE

REQUIRED. VERIFY WITH MANUFACTURER PRIOR TO BID.

4) CURBS SHALL BE SIZED BASED OFF OF PACKAGE UNIT

DIMENSIONS. REFER TO MECHANICAL DRAWINGS AND

This is the start of the file's text. The full file is on GovTribe.