23-34 New Greenhouse at Marion Senior High School - ADDENDUM NUMBER 2.pdf

PDF 56 KB Posted

Attached to
IFB MSHS New Greenhouse
Solicitation number
57158
Issued by
Smyth County, Virginia

About this file

This document is an Addendum Number 2 related to an Invitation for Bids (IFB) issued by Smyth County Public Schools in Virginia for the construction of a new greenhouse at Marion Senior High School. The addendum provides clarifications and revisions to the original bid documents, including specifying 20-inch high-velocity circulation fans in lieu of the previously specified 12-inch fans, as well as modifications to the electrical work required. Contractors are required to acknowledge receipt of this addendum on their bid form, and failure to do so may result in disqualification.

The related IFB opportunity is for the construction of a new pre-engineered greenhouse and associated site and concrete work at the Marion Senior High School in Smyth County, Virginia. No additional details regarding pricing, set-asides, incumbents, funding, or other salient information are provided in the given materials.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Comm. No. 23-34 Addendum Number 2

ADDENDUM NUMBER 2

Smyth County, VA Public Schools

New Greenhouse at Marion Senior High School

5 Design, LLC

5 Design Commission #23-34

January 23, 2024

This Addendum contains one (1) page. This addendum shall form part of the contract documents and supersedes previously published information. Contractors shall acknowledge receipt of this Addendum on the Bid Form. Failure to do so may result in disqualification of the

Contractor’s bid.

General:

1. Clarification: All glazing shall be ¼” thickness.

Drawings:

- Sheet M100, provide 20” HAF fans in lieu of 12” fans specified in Addendum #1. 20” fans shall be equal to Green Breeze HAF Fan model VBG20 by J&D Manufacturing. Provide mounting brackets and all associated hardware. Coordinate mounting locations with the

Owner.

- Sheet E100, Remove Fan Jets and replace disconnects indicated for Fan Jets with one

(1) 20 amp dedicated GFCI WP receptacle at each HAF fan indicated on the mechanical drawings issued in Addendum #1. Provide a 20-amp, single pole breaker with #12 wire and #12 ground for each receptacle. Mount receptacles to greenhouse roof structure.

Coordinate locations with fan locations.

End of Addendum Number 2

File details come from the government source that posted it. Updated .