4269 M-80, KINCHELOE, MI 49788

FILE NUMBER: 472/22138.ABG

MATRIX PROJECT NUMBER: 22295.01

MECHANICAL/ELECTRICAL ENGINEER

STATE OF MICHIGAN

DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET

FOR DEPARTMENT OF CORRECTIONS

CHIPPEWA CORRECTIONAL FACILITY (URF) - ERT BUILDING HVAC UPGRADES PROJECT

N SITE MAP

MECHANICAL DRAWING INDEX

ERT BUILDING

ELECTRICAL DRAWING INDEX

M-000

TITLE SHEET

DBP

CAT

22295.01

472/22138.ABG

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

M a t r ix funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P

L A

C H

R

A

D

IR

E C

T O

R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

2/14/2025 CD SET

GENERAL HVAC NOTES

1. INSTALL ALL EQUIPMENT, MATERIALS, AND ACCESSORIES PER

MANUFACTURERS WRITTEN INSTRUCTIONS.

2. ALL EXISTING SYSTEMS (PUMPS) THAT SERVES AREAS BEING

RENOVATED SHALL BE REBALANCED AS REQUIRED.

3. FIELD VERIFY LOCATIONS OF EXISTING PIPING THAT MAY

CONFLICT WITH NEW CONSTRUCTION AND RELOCATE AS

NEEDED.

4. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER

DISCIPLINES PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.

5. PROVIDE MANUAL AIR VENTS WITH 3/4" HOSE CONNECTION AT

ALL HIGH POINTS.

6. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION,

ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS THAT

MAY AFFECT THE WORK.

7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING

THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW"

CONDITION DURING CONSTRUCTION.

8. ALL WORK SHALL BE PERFORMED BY LICENSED

CONTRACTORS AND SUBCONTRACTORS AS REQUIRED BY LAW.

9. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE,

LATEST APPLICABLE EDITION.

10. ALL CONDENSATE DRAIN PIPING SET @ MIN. 1% SLOPE.

11. ALL CONDENSATE DRAIN PIPING TO TERMINATE TO DRAIN VIA

AIR GAP.

12. IF THERE IS CONFLICTING INFORMATION IN THE PLANS OR

SPECIFICATIONS THE MORE STRINGENT AND GREATER COST

ITEM SHALL BE USED.

13. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF

TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES.

IT IS NOT INTENTION OF DRAWINGS TO INDICATE ALL

NECESSARY OFFSETS. INSTALL WORK IN MANNER TO

CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE

HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.

DO NOT SCALE FROM DRAWINGS.

14. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS,

REVISIONS, AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE

STATUTES, ORDINANCES, CODES OR REGULATIONS OF

FEDERAL, STATE, AND LOCAL AUTHORITIES HAVING

JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.

15. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY

OSHA, UNDERWRITERS, LABORATORIES, AMERICAN CODES,

ASA, ASHRAE, ARI, NEC, STATE FIRE INSURANCE REGULATION

BODY, NFPA OR OTHERS, THESE STANDARDS SHALL BE

FOLLOWED WHETHER OR NOT INDICATED ON THE DRAWING

AND SPECIFICATIONS.

16. PIPING LAYOUT IS SCHEMATIC. EXACT LOCATION OF PIPING

AND EQUIPMENT SHALL BE COORDINATED WITH BUILDING

STRUCTURE, EQUIPMENT FURNISHED, EXISTING CONDITIONS

AND ALL OTHER TRADES PRIOR TO INSTALLATION. ANY

CONTRACTOR INSTALLING WORK WITHOUT PRIOR

COORDINATION SHALL RELOCATE HIS WORK AT HIS EXPENSE

TO ALLOW PROPER INSTALLATION OF ANY AND ALL TRADES

WORK.

17. PIPING SHALL NOT BE RUN ABOVE ELECTRICAL GEAR IN THE

SERVICE SPACE REQUIRED BY THE NATIONAL ELECTRICAL

CODE.

18. ANY ADDITIONAL LOW VOLTAGE CONTROL WIRING THAT IS

REQUIRED SHALL BE PROVIDED BY THE HVAC CONTRACTOR.

CONTROL WIRING SHALL BE RUN IN CONDUIT IF REQUIRED BY

LOCAL CODES. POWER SHALL BE PROVIDED BY THE

ELECTRICAL CONTRACTOR.

19. PROVIDE VIBRATION ISOLATION AT EACH CONNECTION TO A

MOTORIZED PIECE OF EQUIPMENT BY THE HVAC

CONTRACTOR.

20. CONTRACTOR TO ATTEND A 6 MONTH AND AN 11 MONTH POST

CONSTRUCTION MEETING WITH THE ENGINEER AND OWNER

TO REVIEW AND FIX ISSUES DURING THE WARRANTY PERIOD.

21. CONTRACTOR TO TRACK AND PROVIDE PAPERWORK TO

OWNER OF THE AMOUNT OF MATERIAL BEING RECYCLED

THROUGHOUT THE PROJECT.

22. CONTRACTOR WILL HAVE 1 ESCORT TO WORK WITH THROUGH

AT THE PROJECT.

23. CONTRACTOR TO PATCH, PRIME, AND PAINT EXISTING

WALLS/CEILINGS AS NEEDED TO MATCH EXISTING WHERE

DEMOLITION AND/OR NEW WORK IS COMPLETED.

24. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING

HEAT/DOMESTIC HOT WATER IN BUILDINGS THROUGHOUT THE

PROJECT.

25. FIELD VERIFY EXISTING SIZE OF ALL CONTROL VALVES AND

EQUIPMENT PRIOR TO ORDERING.

26. CONTRACTOR TO NOTIFY THE FACILITY AT LEAST 1 DAY IN

ADVANCE FOR ANY HOT WORK TO ALLOW THE OWNER TO

DISABLE THE FIRE ALARM.

27. ALL FASTENERS USED IN AREAS EXPOSED TO INMATES SHALL

USE TAMPERPROOF SCREWS.

28. ROOF PENETRATIONS TO INCLUDE A CURB AND ROOF CURB

BOOT. PATCH AND SEAL ROOF PENETRATIONS TO BE WATER

TIGHT. ALL ROOF PENETRATIONS SHALL BE SEALED WATER

TIGHT AND SHALL MAINTAIN ALL EXISTING WARRANTIES.

29. CONTRACTOR TO PROVIDED ALL CONTROLS

EQUIPMENT/ACCESSORIES REQUIRED TO CONNECT

NEW/EXISTING EQUIPMENT TO NEW DDC CONTROL PANEL AS

IN THE CONSTRUCTION DOCUEMENTS.

30. CONNECT NEW DDC CONTROL PANEL TO SECURITY IT RACK

WITH PURPLE CAT-6 CABLES(S) AS REQUIRED TO CONNECT TO

STARNET 2 SYSTEM. CONTRACTOR TO HIRE AND COORDINATE

CONNECTION TO SECURITY IT RACK WITH BRETT EMERSON

FROM COMMTECH DESIGN (PHONE 616-433-7210).

MECHANICAL SYMBOLS LEGEND

HVAC PIPING SYMBOLSHVAC PIPING

HVAC DUCTWORK

F/S

F/S s s

TEMPERATURE CONTROL SYMBOLS

MISCELLANEOUS NOTES

HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS HVAC PIPING VALVES

MECHANICAL ABBREVIATIONS

AFF ABOVE FINISH FLOOR

AC AIR COMPRESSOR

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

A.T.C. ARCHITECTURAL TRADES CONTRACTOR

B BOILER

B.A.S. BUILDING AUTOMATION SYSTEM

CAF COMBUSTION AIR FAN

CC COOLING COIL

CFM CUBIC FEET PER MINUTE

CHLR CHILLER

CHP CONSOLE HEAT PUMP

CONV CONVECTOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONTROL VALVE

CWP CHILLED WATER PUMP

DB DRY BULB

DFU DUCT FURNACE

DIA DIAMETER

DN DOWN

DPR DAMPER

DS DUCT SILENCER

EAT ENTERING AIR TEMPERATURE

EF EXHAUST FAN

EG EXHAUST GRILLE

E.T.C. ELECTRICAL TRADES CONTRACTOR

EVR EVAPORATOR

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

EXIST EXISTING

FF FINISH FLOOR

FPM FEET PER MINUTE

FT FEET

FTR FINNED TUBE RADIATION

FU FURNACE

GAL GALLON

GFRH GAS FIRED RADIANT HEATER

GR GRILLE

H HUMIDIFIER

HC HEATING COIL

HD HEAD (FT)

HP HORSE POWER

HHP HORIZONTAL HEAT PUMP

HTG HEATING

HVAC HEATING, VENTILATION, & AIR CONDITIONING

HWP HEATING WATER PUMP

HX HEAT EXCHANGER

ID INSIDE DIAMETER

I.E. INVERT ELEVATION

IAH INTAKE HOOD

LAT LEAVING AIR TEMPERATURE

LH LATENT HEAT (MBH)

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH BTU PER HOUR (THOUSAND)

MIN MINIMUM

M.T.C. MECHANICAL TRADES CONTRACTOR

N.C. NOISE CRITERIA

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NTS NOT TO SCALE

P PUMP

PCR PUMPED CONDENSATE RETURN

PD PRESSURE DROP

RCP RADIANT CEILING PANEL

REQ'D REQUIRED

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RLH RELIEF HOOD

RTU ROOF TOP UNIT

SD SUPPLY DIFFUSER

SF SUPPLY FAN

SG SUPPLY GRILLE

SH SENSIBLE HEAT (MBH)

SM SHEET METAL

SQ. FT. SQUARE FEET

SST SATURATED SUCTION TEMPERATURE

STR STRAINER

TC TOTAL COOLING (MBH)

TCL TEMPERATURE CONTROL

T&P TEMPERATURE & PRESSURE RELIEF VALVE

TYP TYPICAL

UH UNIT HEATER

VAV VARIABLE AIR VOLUME BOX

VRH VARIABLE AIR VOLUME REHEAT BOX

FPVAV FAN POWERED VARIABLE AIR VOLUME BOX

V.F.D VARIABLE FREQUENCY DRIVE

ZD ZONE DAMPER

X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)

ITEM

EXISTING

CHILLED WATER SUPPLY

CHILLED WATER RETURN

CONDENSATE DRAIN

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

COOLING TOWER WATER SUPPLY

COOLING TOWER WATER RETURN

DIRECT EXPANSION

HEAT PUMP WATER SUPPLY

HEAT PUMP WATER RETURN

HEATING WATER SUPPLY

HEATING WATER RETURN

SUCTION (REFRIGERANT)

LIQUID (REFRIGERANT)

SUCTION (DIRECT EXPANSION)

LIQUID (DIRECT EXPANSION)

LOW PRESSURE STEAM (0-20 LBS.)

MEDIUM PRESSURE STEAM (21-75 LBS.)

HIGH PRESSURE STEAM (76 LBS. & ABV.)

STEAM CONDENSATE (GRAVITY)

PUMPED STEAM CONDENSATE

STEAM CONDENSATE BOILER FEED

GATE VALVE

GAS COCK

CHECK VALVE

BALANCE COCK

CIRCUIT SETTER

TWO-WAY CONTROL VALVE

THREE-WAY CONTROL VALVE

GLOBE VALVE

BALL VALVE

SOLENOID VALVE

EXPANSION VALVE WITH

THERMOSTATIC BULB

PLUG VALVE

BUTTERFLY VALVE

RELIEF VALVE

HOSE & DRAIN END VALVE

PRESSURE RELIEF VALVE

PRESSURE REDUCING VALVE

TRIPLE DUTY VALVE

GAS PRESSURE REGULATOR

STRAINER (BLOW-OFF)

FLOW DIRECTION

PIPING DROP

PIPING RISE

INLINE PIPING DROP

INLINE PIPING RISE

PIPING TEE

PIPING ELBOW

THERMOMETER

PUMP

UNION

PIPE ANCHOR

PIPE GUIDE

BACK FLOW PREVENTER

PIPE CAP

PIPE BREAK

THERMOMETER WELL

EXPANSION LOOP

EXPANSION COMPENSATOR

FLOAT & THERMOSTATIC STEAM TRAP

INVERTED BUCKET STEAM TRAP

THERMOSTAT

PROGRAMMABLE THERMOSTAT

THERMOSTAT (W/ NIGHT SETBACK)

ROOM SENSOR

HUMIDISTAT

PRESSURE GAUGE

DAMPER (ELECTRIC OPERATION)

DAMPER (PNEUMATIC OPERATION)

DAMPER BLADES

SUPPLY AIR DUCT

EXIST SUPPLY AIR DUCT

RETURN AIR DUCT

EXIST RETURN AIR DUCT

OUTSIDE AIR DUCT

EXIST OUTSIDE AIR DUCT

EXHAUST AIR DUCT

EXIST EXHAUST AIR DUCT

SUPPLY AIR DUCT RISER

RETURN AIR DUCT RISER

OUTSIDE AIR DUCT RISER (AS NOTED)

EXHAUST AIR DUCT

INSULATED DUCTWORK (AS NOTED)

SUPPLY AIR DIFFUSER (SQUARE)

SUPPLY AIR DIFFUSER (INLINE)

TURNING VANES

SURFACE MTD. GRILLE

SUPPLY AIR DIFFUSER (ROUND)

90° TEE W/45° APPROACH

CONICAL TAKE-OFF

CONICAL TAKE-OFF W/ DAMPER

BALANCE DAMPER

RETURN AIR DUCT BOOT

ECCENTRIC REDUCER

CONCENTRIC REDUCER

VERTICAL FIRE DAMPER

EXISTING VERTICAL FIRE DAMPER

HORIZONTAL FIRE DAMPER

EXISTING HORIZONTAL FIRE DAMPER

VERTICAL SMOKE DAMPER

HORIZONTAL SMOKE DAMPER

VERTICAL FIRE / SMOKE DAMPER

HORIZONTAL FIRE / SMOKE DAMPER

DUCT SMOKE DETECTOR, INSTALLED BY M.T.C.,

PROVIDED & WIRED BY E.T.C.

UNIT HEATER

CEILING EXHAUST FAN

ROOF MOUNTED EXHAUST FAN

DEMOLITION

POINT OF CONNECTION BETWEEN NEW AND

EXISTING

POINT OF EXISTING TO REMAIN AND EXISTING

TO BE REMOVED

INDICATES PLAN NOTE

INDICATES DEMOLITION NOTE

DETAIL BUBBLE

DETAIL NUMBER

PAGE LOCATION INDICATES

DIRECTION OF DETAIL SECTION

X

X

XX

XXXX

XX

XXXX

SA

OA

X-OA

X-EA

EA

X-SA

X-RA

RA

SCP

SC

DXS

DXL

HR

CR

CD

CS

DX

CTR

HPR

HS

HPS

CTS

CWR

CWS

S

L

LPS

MPS

HPS

SC (BF)

TAG CFM

NECK REMARKS

SIZE

BT

FT

SD-1 250

8"ø ---

P

H

S

T

T P

T N

M

M

SD

1. EXISTING EQUIPMENT LAYOUT IS SCHEMATIC. EXACT LOCATION OF EXISTING

PIPING AND EQUIPMENT SHALL BE COORDINATED WITH BUILDING STRUCTURE,

EQUIPMENT FURNISHED, ARCHITECTURAL DRAWINGS AND ALL OTHER

TRADES PRIOR TO DEMOLITION.

2. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS,

AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES,

CODES OR REGULATIONS OF FEDERAL, STATE, AND LOCAL AUTHORITIES

HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.

3. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA,

UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI, NEC,

STATE FIRE INSURANCE REGULATION BODY, NFPA OR OTHERS. THESE

STANDARDS SHALL BE FOLLOWED WHETHER OR NOT INDICATED ON THE

DRAWING AND SPECIFICATIONS.

4. COORDINATE CUTTING AND PATCHING WITH GENERAL CONTRACTOR.

5. ALL BOLD DASHED LINES INDICATE ITEMS TO BE REMOVED UNLESS NOTED BY

KEYNOTE. ALL OTHER EXISTING SYSTEMS SHOWN FOR REFERENCE ONLY.

6. PATCH AND REPAIR ALL FLOOR AND WALL SURFACES LEFT DAMAGED OR

INCOMPLETE FROM REMOVAL OF EXISTING HVAC EQUIPMENT OR OTHER

FIXED ACCESSORIES AND EQUIPMENT WITH MATERIALS TO MATCH EXISTING.

7. NOTATIONS ARE MADE IN VARIOUS PLACES ON THE DRAWINGS TO CALL

ATTENTION TO DEMOLITION WHICH IS REQUIRED. HOWEVER, THESE

DRAWINGS ARE NOT INTENDED TO SHOW EACH AND EVERY ITEM TO BE

REMOVED. CONTRACTOR SHALL REMOVE ALL MATERIALS RELATED TO THEIR

RESPECTIVE TRADES AS REQUIRED TO PERMIT THE CONSTRUCTION OF THE

NEW WORK AS SHOWN.

8. THE GENERAL CONTRACTOR SHALL COORDINATE THE EXTENT OF THE

REQUIRED DEMOLITION OF THE EXISTING BUILDING AS REQUIRED TO

FACILITATE THE CONSTRUCTION OF THE PROJECT AS SHOWN AS PART OF

THIS WORK.

9. ALL DEMOLITION SHALL BE APPROVED BY THE OWNER PRIOR TO

COMMENCEMENT AND SHALL BE PERFORMED UNDER REQUIREMENTS AND

APPROVAL OF THE LOCAL CODE JURISDICTIONS.

10. ASBESTOS ABATEMENT: CONTRACTOR SHALL NOTIFY BUILDING

REPRESENTATIVE IMMEDIATELY WHEN AND IF ANY ITEMS ARE ENCOUNTERED

THAT IN ANY WAY, SHAPE, OR FORM APPEAR TO BE HAZARDOUS OF NATURE.

ASBESTOS ABATEMENT IS NOT PART OF THE SCOPE OF THE DESIGN

PROFESSIONALS DOCUMENTATION OR RESPONSIBILITY TO SURVEY, IDENTIFY,

OR FOR CONSULTATION OF PROPER DISPOSAL.

11. PROTECT ALL EXISTING WORK WHICH IS TO REMAIN AND RESTORE IN AN

APPROVED MANNER ANY SUCH WORK WHICH BECOMES DAMAGED.

12. RUBBISH AND DEBRIS RESULTING FROM THE WORK SHALL BE REMOVED

IMMEDIATELY FROM THE SITE IN A SAFE AND LEGAL MANNER BY THE

CONTRACTOR.

13. DEMOLITION CONTRACTOR SHALL BE RESPONSIBLE TO CONTACT BUILDING

REPRESENTATIVE TO CLARIFY ANY ITEMS NOT SHOWN ON THESE

DOCUMENTS OR SHOWN NOT MATCHING FIELD CONDITIONS.

GENERAL DEMOLITION NOTES

1. THE EXISTING ERT BUILDING (WEST CONVERSION ROOM) HEATING HOT WATER SYSTEM

MUST REMAIN FULLY ACTIVE UNTIL JUNE 1, 2025.

2. CONTRACTOR CAN BEGIN WORK ON THE TEMPORARY HEATING HOT WATER SYSTEM PRIOR

TO JUNE 1, 2025, AS REQUIRED HAVE THE TEMPORARY SYSTEM RUN CONTINUOUSLY FOR 5

DAYS WITH NO ISSUES AND TO BE READY TO DEMOLISH THE EXISTING SYSTEM JUNE 1,

2025. ALL NEW EQUIPMENT MUST BE RECEIVED AND READY TO INSTALL BEFORE

DEMOLITION CAN OCCUR.

2.1. CONTRACTOR TO CONSTRUCT A TEMPORARY HEATING HOT WATER SYSTEM TO FEED

THE EXISTING HEATING HOT WATER SUPPLY AND HEATING HOT WATER RETURN

PIPING DURING CONSTRUCTION.

2.2. THE TEMPORARY HEATING HOT WATER SYSTEM IS TO BE CONSTRUCTED FROM (1)

TEMPORARY BASE MOUNTED PUMP (P-3), (1) SALVAGED HEAT EXCHANGER AND ALL

ASSOCIATED CONTROLS, (1) SALVAGED AIR SEPARATOR, (1) TEMPORARY

CONDENSATE PUMP (CRP-2), AND TEMPORARY PIPING (HEATING SUPPLY, HEATING

RETURN, STEAM, AND STEAM CONDENSATE) AND VALVES AS REQUIRED TO TIE IN THE

EXISTING SYSTEM. THE TEMPORARY HEATING HOT WATER SYSTEM IS TO BE TIED INTO

THE EXISTING SYSTEM DURING A SMALL SHUTDOWN COORDINATED WITH OWNER.

2.3. THE NEW AIR SEPARATOR (AS-2) IS TO BE INSTALLED IN THE LOCATION OF THE

EXISTING AIR SEPARATOR IN THE EXISTING SYSTEM SO THE EXISTING AIR SEPARATOR

CAN BE SALVAGED AND RE-USED FOR THE TEMPORARY HEATING HOT WATER

SYSTEM. THE NEW AIR SEPARATOR (AS-2) IS TO BE INSTALLED IN LOCATION OF

EXISTING SALVAGED AIR SEPARATOR DURING SMALL SHUTDOWN COORDINATED WITH

OWNER.

2.4. CONTRACTOR TO CONSTRUCT TEMPORARY HEATING HOT WATER SYSTEM IN A

CONTRACTOR SUPPLIED STORAGE TRAILER ON THE OUTSIDE OF THE ERT BUILDING.

THE STORAGE TRAILER IS TO BE INSTALLED AS CLOSE AS POSSIBLE TO THE ERT

BUILDING TO ENCLOSE ALL THE TEMPORARY HEATING EQUIPMENT AND TEMPORARY

PIPING TO PROTECT THEM FROM THE WEATHER.

2.5. THE TEMPORARY HEATING HOT WATER SYSTEM MUST RUN CONTINUOUSLY FOR

5-DAYS WITH NO ISSUES BEFORE ANY OF THE EXISTING SYSTEM CAN BEGIN TO BE

DEMOLISHED.

3. SUBSTANTIAL COMPLETION FOR ALL WORK IS TO BE OCTOBER 1, 2025.

4. FINAL COMPLETION FOR ALL WORK IS TO BE OCTOBER 15, 2025

5. ALL NEW EQUIPMENT IS TO HAVE SUBMITTALS PROVIDED/APPROVED AS SOON AS POSSIBLE

ONCE THE CONTRACT CHANGE ORDERED IS ISSUED. ONCE EQUIPMENT SUBMITTALS ARE

PROVIDED/APPROVED EQUIPMENT IS TO BE ORDERED AS SOON AS POSSIBLE.

CONSTRUCTION PHASING SCHEDULE

M-100

DBP

CAT

22295.01

472/22138.ABG

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

M a t r ix funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P

L A

C H

R

A

D

IR

E C

T O

R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

2/14/2025 CD SET

MECHANICAL SYMBOLS,

NOTES, ABBREVIATIONS,

AND SCHEDULES

M-300

X-CW

X-HS

X-HR

X-4" CW

X-8" HS

X-8" HR

X-STM

X-PSC

X-6" STM &

X-2-1/2"

PSC IN TUNNEL

X-

HS

X-

HR

X-

PS

C

X-STM

X-P-1

X-P-2

X-XT-1

X-AS

X-HE-2

BT

BT

X-HE-1

BT

X-

HS

X-

HR

X-

PS

C X-

PS

C

X-

ST

M X-

ST

M

X-CW

X-CRP-1

X-2-1/2"

X-2-1/2"

X-6"

X-6"

X-6"

X-2-1/2"

X-8"

X-3"

X-3"

X-

SCX-3/4"

X-8"

X-8"

X-2-1/2"

X-

CW

X-2"

X-6"

X-1-1/2"

X-CONCRETE

PAD (TYP. 2)

CONCRETE

PAD

X-CONTROL

PANEL X-CONTROL

PANEL

X-EF 10

X-4" VTR

DEMOLITION NOTES

CONTRACTOR TO PATCH, PRIME, AND PAINT THE EXISTING DAMAGED

DRYWALL WALL BEHIND THE HEAT EXCHANGERS ONCE THE HEAT

EXCHANGERS ARE REMOVED TO MATCH EXISTING. CONTRACTOR TO

PAINT PATCH AND ENTIRE NORTH WALL WHITE.

DISCONNECT, REMOVE, AND DEMO EXISTING SKID PACKAGE

CONDENSATE RECEIVER TANK/PUMPS, CONTROL PANEL, CONTROLS,

METAL FRAME, CONDENSATE PIPING, VALVES, FITTINGS, CONCRETE

PAD, VENT, AND ALL ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.

CONTRACTOR TO REUSE EXISTING VENT ROOF PENETRATION FOR

NEW VENT SHOWN ON NEW DRAWINGS. MODIFY EXISTING ROOF

PENETRATION AS REQUIRED TO BE REUSED.

DISCONNECT, REMOVE, AND SALVAGE EXISTING HEAT EXCHANGER

AND STEAM CONTROL VALVE. DISCONNECT, REMOVE, AND DEMO

EXISTING STEAM PIPING, CONDENSATE PIPING, HEATING SUPPLY

PIPING, HEATING RETURN PIPING, CONTROLS, VALVES, FITTINGS, AND

ALL ASSOCIATED ACCESSORIES IN THEIR ENTIRETY. EXISTING METAL

SUPPORT FRAME TO REMAIN AND BE RE-USED. CONTRACTOR TO SAND

BLAST AND PAINT EXISTING METAL SUPPORT FRAMES PRIOR TO

INSTALL OF NEW HEAT EXCHANGERS.

DISCONNECT, REMOVE, AND SALVAGE EXISTING AIR SEPARATOR.

DISCONNECT, REMOVE, AND DEMO EXISTING, HEATING SUPPLY PIPING,

VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES IN THEIR

ENTIRETY. DISCONNECT, REMOVE, AND DEMO EXISTING COLD WATER

PIPING AND ALL ASSOCIATED ACCESSORIES TO THE LOCATION

SHOWN.

DISCONNECT, REMOVE, AND DEMO EXISTING STEAM PIPING, HEATING

SUPPLY PIPING, HEATING RETURN PIPING, STEAM CONDENSATE

PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES TO

THE EXTENTS SHOWN.

EXISTING PUMPS AND CONCRETE PAD TO REMAIN. DISCONNECT,

REMOVE AND DEMO EXISTING HEATING SUPPLY PIPING, CONTROLS,

VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES IN THEIR

ENTIRETY.

DISCONNECT, REMOVE, AND DEMO EXISTING WEST CONVERSION

ROOM CONTROL PANEL, CONTROLS, PNEUMATIC TUBING, CONTROL

WIRING, AND ALL ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.

EXISTING MAINTENANCE BUILDING CONTROL PANEL, AIR DRYER, AIR

COMPRESSOR, CONTROLS, PNEUMATIC TUBING, CONTROL WIRING,

AND ALL ASSOCIATED ACCESSORIES TO REMAIN.

EXISTING EXPANSION TANK, CHEMICAL POT FEEDER, SIDE STREAM

FILTER, AND ALL ASSOCIATED ACCESSORIES TO REMAIN.

EXISTING EXHAUST FAN AND ALL ASSOCIATED ACCESSORIES TO

REMAIN.

EXISTING MAINTENANCE BUILDING INLINE HEATING SUPPLY PUMP,

3-WAY CONTROL VALVE, CONTROLS, PIPING, VALVES, FITTINGS, AND

ALL ASSOCIATED ACCESSORIES TO REMAIN. EXISTING MAINTENANCE

BUILDING INLINE HEATING SUPPLY PUMP, 3-WAY CONTROL VALVE, AND

ALL ASSOCIATED ACCESSORIES ARE NOT SHOWN ON MECHANICAL

ROOM PLAN FOR CLARITY.

DISCONNECT, REMOVE, AND DEMO EXISTING STEAM PRESSURE

REDUCING VALVE, PRESSURE RELIEF VALVE, STEAM PIPING, VENT

PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES IN

THEIR ENTIRETY. CONTRACTOR TO REUSE EXISTING VENT ROOF

PENETRATION FOR NEW VENT SHOWN ON NEW DRAWINGS. MODIFY

EXISTING ROOF PENETRATION AS REQUIRED TO BE REUSED.

DISCONNECT, REMOVE, AND SALVAGE EXISTING METAL FENCING

ENCLOSURE AND ALL ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.

CONTRACTOR TO PATCH EXISTING FLOOR AS REQUIRED TO MATCH

EXISTING WHERE SUPPORTS WERE INSTALLED. THE SALVAGED METAL

FENCING ENCLOSURE AND ALL ASSOCIATED ACCESSORIES ARE TO BE

TURNED OVER TO THE OWNER.

GENERAL DEMOLITION NOTES

1. BEFORE ROUTING TEMPORARY STEAM PIPING, TEMPORARY STEAM

CONDENSATE PIPING, TEMPORARY HEATING SUPPLY PIPING, TEMPORARY

HEATING RETURN PIPING, CONTRACTOR TO DISCONNECT, REMOVE, AND

SALVAGE STEEL PANELING CONSTRUCTION OF EXTERIOR WALL. TEMPORARY

BOARDING SHALL BE USED TO RE-ENCLOSE THE BUILDING. PENETRATIONS

FOR THE TEMPORARY PIPING SHALL BE MADE IN THE TEMPORARY BOARDING.

TEMPORARY PIPING WILL BE USED TO KEEP THE EXISTING SYSTEM ACTIVE

DURING CONSTRUCTION.

2. CONTRACTOR TO USE SALVAGED HEAT EXCHANGER, NEW BASE MOUNTED

PUMP (P-3), SALVAGED STEAM CONTROL VALVE, SALVAGED AIR SEPARATOR,

NEW TEMPORARY CONDENSATE PUMP (CRP-2), EXISTING EXPANSION TANK,

NEW DDC CONTROL PANEL, AND ALL ASSOCIATED ACCESSORIES AS

REQUIRED TO CREATE TEMPORARY HEATING TO FEED THE EXISTING

HEATING HOT WATER WATER SUPPLY IN THE ERT BUILDING DURING

CONSTRUCTION. CONTRACTOR TO INSTALL NEW TEMPORARY HEATING HOT

WATER SUPPLY PIPING, HEATING HOT WATER RETURN PIPING, AND ALL

ASSOCIATED ACCESSORIES AS REQUIRED TO CONNECT THE TEMPORARY

SALVAGED HEAT EXCHANGER, NEW PUMP PUMP, AND SALVAGED AIR

SEPARATOR TO THE EXISTING HEATING HOT SUPPLY AND HEATING HOT

WATER RETURN RISERS. CONTRACTOR TO INSTALL NEW TEMPORARY STEAM

PIPING, STEAM CONDENSATE PIPING, AND ALL ASSOCIATED ACCESSORIES AS

REQUIRED TO CONNECT THE TEMPORARY SALVAGED HEAT EXCHANGER AND

TEMPORARY CONDENSATE PUMP TO THE EXISTING STEAM AND STEAM

CONDENSATE RISERS. CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT

THE TEMPORARY HEATING SYSTEM IS OPERATIONAL AND ONLINE FOR THE

DURATION OF CONSTRUCTION. NEW TEMPORARY HEATING SYSTEM IS TO BE

INSTALLED OUTSIDE THE ERT BUILDING IN A STORAGE CONTAINER WITH

DOORS ON BOTH ENDS. STORAGE CONTAINER IS TO BE INSTALLED TIGHT TO

THE ERT BUILDING. CONNECT NEW TEMPORARY HEATING SYSTEM DDC

CONTROL PANEL TO DARK NETWORK IT RACK WITH PURPLE CAT-6 CABLE(S)

AS REQUIRED TO CONNECT TO THE EXISTING STARNET 2.0 SYSTEM.

CONTRACTOR TO HIRE AND COORDINATE CONNECTION TO DARK NETWORK

IT RACK WITH BRET EMERSON FROM COMMTECH DESIGN ( PHONE

616-446-4545).

3. CONTRACTOR IS RESPONSIBLE FOR PROVIDING TEMPORARY HEAT AND

DOMESTIC HOT WATER THROUGHOUT THE CONSTRUCTION DURATION

BESIDES SMALL CHANGEOVER SHUTDOWNS.

4. DISCONNECT, REMOVE, AND DEMO EXISTING LAY-IN CEILING, CEILING GRID,

CEILING TILES, AND ALL ASSOCIATED ACCESSORIES TO THE EXTENTS SHOWN

ON DRAWING M-800. TEMPORARY SUPPORT ALL CONDUIT AND OTHER

EQUIPMENT THAT IS SECURED TO THE EXISTING CEILING GRID/CEILING TILES

AS REQUIRED.

X-4" VTR

X-HE-1

X-CRP-1

X-CONCRETE

PAD

X-HE-2

X-AS

X-PSC

X-XT

X-PSC X-PSC

X-

PS

C

X-2-1/2"

X-2-1/2" X-2-1/2" X-2-1/2"

X- V

X- V

X-4"

BT

X-STMX-STMX-STM

BT

X-

SC

X-SC

X-SC

X-3"

X-3"

X-3"

BT

X-

SC

X-3/4"

X-

ST

M

X-

ST

M

P

P

P

P

X-HR X-HR X-HR

X-HS

X-

HSX-

HR

X-

HSX-

HR

X-P-1 X-P-2

X-SSF X-CHEMICAL

POT FEEDER

X-

HS

X-

HS X-

HS

X-

HS

X-

HR

X-

HR

X-HS

X-

HS

X-

HS

X-

HS

X-

HS

X-4" VTR

X-HS

X-P X-

SCX-

SC

X-2-WAY CV (TYP.)

X-PRV

X-PRESSURE

RELIEF VALVE

(TYP.)

X-1/2"

X-8"

X-8" X-8"

X-8"

X-8" X-8" X-8"

X-PSC

X-STM

X-STEAM TRAP

(TYP.)

X-STRAINER

(TYP.)

X-CHECK

VALVE (TYP.) X-DRIP LEG

(TYP.)

X-UNION

(TYP.)

X-CONCRETE

PAD

X-6" X-6"

X-6" X-6" X-6"

X-6" X-6"

X-2-1/2"

X-PRESSURE

GAUGE (TYP.)

X-SHUTOFF

VALVE (TYP.)

P P

X-8" X-8"

P P

X-1/2"

P X-1-1/2"

X-

CW

X-2"

X-2" X-BVPX-PRV

X-2" CW

X-8" X-8" HR

X-8" HS

X-6"

X-3-WAY CVX-P

X-1-1/2"

HS & HR

METAL FRAME2

X-METAL

FRAME (TYP.)

3 3

6 6

12 12

3 3 3

X-PSC

X-STM

M-300

ERT BUILDING FIRST FLOOR

PLAN - MECHANICAL

DEMOLITION

DBP

CAT

N ERT BUILDING FIRST FLOOR PLAN - MECHANICAL DEMOLITION

1 ERT BUILDING MECHANICAL ROOM - MECHANICAL DEMOLITION

SCALE: 1/4" = 1'-0"

22295.01

472/22138.ABG

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

M a t r ix funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P

L A

C H

R

A

D

IR

E C

T O

R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

2/14/2025 CD SET

SCALE: 1/8" = 1'-0"

0 1 5 10 20

2 ERT BUILDING MECHANICAL ROOM - PIPING DEMOLITION DIAGRAM

SCALE: NTS

M-600

X-CW

X-HS

X-HR

X-4" CW

X-8" HS

X-8" HR

X-STM

X-PSC

X-6" STM &

X-2-1/2"

PSC IN TUNNEL

X-P-1

X-P-2

X-XT-1

X-CW

X-

CW

X-2"

X-CONCRETE

PAD (TYP. 2)

X-CONTROL

PANEL

X-EF

HSHR

PS

C

STM

X-P-1

X-P-2

AS-2

BT

BT

BT

HS

HR

PS

C

ST

M

ST

M

CRP-1

SC

CONCRETE

PAD

SC

HX-1

HX-2

PRV-2

DDC CONTROL

PANEL

2-1/2"

6"

6"

6"

2-1/2"

8"

3"

3"

3/4"

8"

8"

2-1/2"

6"

1-1/2"

4" VTR

PRV-112

STORAGE TRAILER

LOCATION

MECHANICAL KEY NOTES

INSTALL NEW 2-WAY MODULATING STEAM CONTROL VALVE (6,770 LB/HR). AND ALL ASSOCIATED ACCESSORIES IN

THE LOCATION SHOWN PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.

INSTALL NEW 2-WAY MODULATING STEAM CONTROL VALVE (3,385 LB/HR) AND ALL ASSOCIATED ACCESSORIES IN

THE LOCATION SHOWN PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.

INSTALL NEW 2-WAY, 2-POSITION CONTROL VALVE AND ALL ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN

PER THE MANUFACTURERS INSTALLATION INSTRUCTIONS.

INSTALL NEW SIDE STREAM FILTER MEDIA IN THE EXISTING SIDE STREAM FILTER (FLOW-MAX FILTER MODEL #:

MJCH170) PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.

INSTALL NEW DDC TOUCHSCREEN CONTROL PANEL IN LOCATION SHOWN. CONNECT NEW DDC CONTROL PANEL TO DARK NETWORK IT RACK WITH PURPLE CAT-6 CABLE(S) AS REQUIRED TO CONNECT TO THE EXISTING STARNET

2.0 SYSTEM. CONTRACTOR TO HIRE AND COORDINATE CONNECTION TO DARK NETWORK IT RACK WITH BRET

EMERSON FROM COMMTECH DESIGN ( PHONE 616-446-4545).

CONNECT NEW HEATING SUPPLY PIPING, HEATING RETURN PIPING, STEAM PIPING, STEAM CONDENSATE PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES TO EXISTING PIPING. MODIFY EXISTING PIPING AS

REQUIRED FOR NEW CONNECTION.

INSTALL NEW CONDENSATE RECEIVER TANK/PUMP SKID, STEAM CONDENSATE PIPING, VENT PIPING, CONTROLS, CONTROL WIRING, VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. INSTALL NEW CONDENSATE RECEIVER TANK/PUMP SKID ON 4" INCH THICK CONCRETE PAD WITH 4" OVERLAP IN ALL DIRECTIONS. MODIFY EXISTING VENT ROOF PENETRATION TO BE REUSED FOR NEW VENT. PATCH ROOF TO MATCH EXISTING, SEAL WATER TIGHT, AND MAINTAIN ALL EXISTING ROOF WARRANTIES. CONNECT CONDENSATE RECEIVER TANK/PUMP SKID TO NEW DDC CONTROL PANEL.

INSTALL NEW HEAT EXCHANGER, STEAM PIPING, STEAM CONDENSATE PIPING, HEATING SUPPLY PIPING, HEATING RETURN PIPING, CONTROLS, CONTROL WIRING, VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. INSTALL NEW HEAT EXCHANGER ON EXISTING METAL SUPPORT FRAME. MODIFY METAL SUPPORT FRAME AS REQUIRED. CONNECT NEW HEAT

EXCHANGER CONTROLS AND CONTROL VALVES TO NEW DDC CONTROL PANEL.

INSTALL NEW AIR SEPARATOR, HEATING SUPPLY PIPING, COLD WATER PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.

INSTALL NEW AIR SEPARATOR ON 4" THICK CONCRETE PAD WITH 4" OVERLAP IN ALL DIRECTIONS.

CONNECT NEW HEATING SUPPLY PIPING AND ALL ASSOCIATED ACCESSORIES TO EXISTING PUMPS AND EXISTING

EXPANSION TANK IN THE LOCATION SHOWN.

INSTALL NEW VFD, CONTROLS, CONTROL WIRING, AND ALL ASSOCIATED ACCESSORIES PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS TO CONNECT THE EXISTING PUMPS TO THE NEW DDC CONTROL

PANEL.

INSTALL NEW PRESSURE REDUCING VALVE, PRESSURE RELIEF VALVE, AND ALL ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. MODIFY EXISTING VENT ROOF PENETRATION TO BE REUSED FOR NEW VENT. PATCH ROOF TO MATCH EXISTING, SEAL WATER TIGHT, AND

MAINTAIN ALL EXISTING ROOF WARRANTIES.

INSTALL NEW MAKE UP WATER METER AND ALL ASSOCIATED IN NEW MAKE UP COLD WATER PIPING. CONNECT

NEW MAKE UP WATER METER TO BAS.

GENERAL MECHANICAL NOTES

1. BEFORE ROUTING TEMPORARY STEAM PIPING, TEMPORARY STEAM CONDENSATE PIPING, TEMPORARY

HEATING SUPPLY PIPING, TEMPORARY HEATING RETURN PIPING, CONTRACTOR TO DISCONNECT, REMOVE, AND SALVAGE STEEL PANELING CONSTRUCTION OF EXTERIOR WALL. TEMPORARY BOARDING SHALL BE USED TO RE-ENCLOSE THE BUILDING. PENETRATIONS FOR THE TEMPORARY PIPING SHALL BE MADE IN THE TEMPORARY BOARDING. TEMPORARY PIPING WILL BE USED TO KEEP THE EXISTING SYSTEM ACTIVE DURING

CONSTRUCTION.

2. CONTRACTOR TO USE SALVAGED HEAT EXCHANGER, NEW BASE MOUNTED PUMP (P-3), SALVAGED STEAM CONTROL VALVE, SALVAGED AIR SEPARATOR, NEW TEMPORARY CONDENSATE PUMP (CRP-2), EXISTING EXPANSION TANK, NEW DDC CONTROL PANEL, AND ALL ASSOCIATED ACCESSORIES AS REQUIRED TO CREATE TEMPORARY HEATING TO FEED THE EXISTING HEATING HOT WATER WATER SUPPLY IN THE ERT BUILDING DURING CONSTRUCTION. CONTRACTOR TO INSTALL NEW TEMPORARY HEATING HOT WATER SUPPLY PIPING, HEATING HOT WATER RETURN PIPING, AND ALL ASSOCIATED ACCESSORIES AS REQUIRED TO

CONNECT THE TEMPORARY SALVAGED HEAT EXCHANGER, NEW PUMP PUMP, AND SALVAGED AIR

SEPARATOR TO THE EXISTING HEATING HOT SUPPLY AND HEATING HOT WATER RETURN RISERS.

CONTRACTOR TO INSTALL NEW TEMPORARY STEAM PIPING, STEAM CONDENSATE PIPING, AND ALL ASSOCIATED ACCESSORIES AS REQUIRED TO CONNECT THE TEMPORARY SALVAGED HEAT EXCHANGER AND TEMPORARY CONDENSATE PUMP TO THE EXISTING STEAM AND STEAM CONDENSATE RISERS. CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT THE TEMPORARY HEATING SYSTEM IS OPERATIONAL AND ONLINE FOR THE DURATION OF CONSTRUCTION. NEW TEMPORARY HEATING SYSTEM IS TO BE INSTALLED OUTSIDE THE ERT BUILDING IN A STORAGE CONTAINER WITH DOORS ON BOTH ENDS. STORAGE CONTAINER IS TO BE INSTALLED TIGHT TO THE ERT BUILDING. CONNECT NEW TEMPORARY HEATING SYSTEM DDC CONTROL PANEL TO DARK NETWORK IT RACK WITH PURPLE CAT-6 CABLE(S) AS REQUIRED TO CONNECT TO THE EXISTING STARNET 2.0 SYSTEM. CONTRACTOR TO HIRE AND COORDINATE CONNECTION TO DARK NETWORK

IT RACK WITH BRET EMERSON FROM COMMTECH DESIGN ( PHONE 616-446-4545).

3. CONTRACTOR IS RESPONSIBLE FOR PROVIDING TEMPORARY HEAT AND DOMESTIC HOT WATER

THROUGHOUT THE CONSTRUCTION DURATION BESIDES SMALL CHANGEOVER SHUTDOWNS.

4. ONCE NEW SYSTEM IS COMPLETE AND READY TO BE ACTIVATED, REMOVE TEMPORARY HEATING HOT WATER SUPPLY PIPING, HEATING HOT WATER RETURN PIPING, STEAM PIPING, STEAM CONDENSATE PIPING, AND ALL ASSOCIATED ACCESSORIES. CONTRACTOR TO REMOVE TEMPORARY BOARDING AND REINSTALL SALVAGE STEEL PANELING CONSTRUCTION OF WALL. CONTRACTOR IS RESPONSIBLE FOR THE REPLACEMENT OF ANY

DAMAGED STEEL PANELING.

5. INSTALL NEW STEAM PIPING, STEAM CONDENSATE PIPING, HEATING SUPPLY PIPING, HEATING RETURN PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN. CONNECT NEW PIPING TO EXISTING PIPING WHERE SHOWN. MODIFY EXISTING PIPING AS REQUIRED FOR NEW CONNECTION.

6. INSTALL NEW LAY-IN CEILING, CEILING, GRID, CEILING TILES, AND ALL ASSOCIATED ACCESSORIES PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS TO THE EXTENTS SHOW ON THE M-800 DRAWING.

RE-INSTALL ALL TEMPORARY MOUNTED CONDUIT AND ACCESSORIES AS REQUIRED.

7. ALL NEW SHUTOFF VALVES ARE TO BE GATE VALVES.

8. AFTER TEMPORARY HEAT IS NOT LONGER REQUIRED, DISCONNECT, REMOVE AND SALVAGE PUMP (P-3) AND

CONDENSATE RECEIVER PUMP (CRP-2) AND HAND OVER TO OVER.

9. ANY ROOF PENETRATIONS/MODIFICATIONS REQUIRED FOR NEW THROUGH ROOF VENTS ARE TO BE PATCHED TO MATCH EXISTING, SEALED WATER TIGHT, AND MAINTAIN ALL EXISTING ROOF WARRANTIES.

HX-1

CRP-1

HX-2

AS-2

BT

P

P

P P

PP

P

4" VTR

CONCRETE

PAD

PSC PSC PSC

PS

C

2-1/2"

2-1/2" 2-1/2" 2-1/2"

V V

4"

STMSTMSTM

SC

SC

SC

3"

3" 3"

SC

3/4"

ST

M

ST

M

HR HR HR

HS

HSHRHSHR HS

HS

HS

HS

4" VTR

HS

SCSC

PRV-1

PRESSURE

RELIEF VALVE

(TYP.)

8"

8"

8"

8"

8" 8" 8"

PSC

STM

STEAM TRAP

(TYP.)

STRAINER

(TYP.)

CHECK VALVE

(TYP.) DRIP LEG

(TYP.)

UNION

(TYP.)

6" 6"

6" 6" 6"

2-1/2"

PRESSURE

GAUGE (TYP.)

CIRCUIT

SETTER

(TYP.)

8" 8"

CW

2"

8"

6"

METAL SKID

FRAME

THERMOMETER

(TYP.)

P/T SENSOR

PORT (TYP.)

SHUTOFF

VALVE (TYP.)

X-XT

X-P-1 X-P-2

X-SSF X-CHEMICAL

POT FEEDER

X-

HS

X-

HS

X-

HR

X-

HR

X-1/2"

X-CONCRETE

PAD

X-1/2"

X-2" X-BVPX-PRV

X-2" CW

X-8" HR

X-8" HS

X-3-WAY CVX-P

X-1-1/2"

HS & HR

X-METAL

FRAME (TYP.)

X-PSC

X-STM

PUMP

FLEX CONNECTOR (TYP.)

1-1/2"

TO FLOOR

DRAIN (TYP.)

CONCRETE

PAD

11 11

6" (TYP.)

BT

3/4"

3/4"

P P

8 8 8

3"

BT

3"

3"3"

3"

HOSE END

DRAIN VALVE

8" HS & HR

TEMP.

HEATING

SYSTEM

CONNECTIONS

6" (TYP.)

HS

PP

HS

HS

SUCTION DIFFUSER WITH

STRAINER (TYP.)

2 3

NCNC

NC PRV-2

3"3"

FT FT

13 M

2 STEAM PRESSURE REDUCING VALVE DETAIL - NEW

SCALE: NTS

PRV-2

P

4" VTR

SHUTOFF

VALVE (TYP.)

STRAINER

(TYP.)

PRESSURE

GAUGE (TYP.)REDUCER (TYP.)

PIPING KEY NOTES

INSTALL NEW PRESSURE RELIEF VALVE IN THE

LOCATION SHOWN.

PRESSURE RELIEF VALVE SPECS:

MANUFACTURER: SPIRAX SARCO

MODEL: SV74

SIZE: 4"

SET PRESSURE: 100 PSI

INSTALL NEW PRV-1 IN THE LOCATION SHOWN.

PRESSURE REDUCING VALVE SPECS:

MANUFACTURER: SPIRAX SARCO

MODEL: 25P

INLET PRESSURE: 165 PSIG

OUTLET PRESSURE: 90 PSIG

CAPACITY: 20,310 LB/HR

INSTALL NEW PRV-2 IN THE LOCATION SHOWN.

PRESSURE REDUCING VALVE SPECS:

MANUFACTURER: SPIRAX SARCO

MODEL: 25P

INLET PRESSURE: 165 PSIG

OUTLET PRESSURE: 90 PSIG

CAPACITY: 20,310 LB/HR

STEAM PRV NOTES:

1. ALLOW AT LEAST 10 PIPE DIAMETERS OF

STRAIGHT PIPE BEFORE AND AFTER PRV.

2. ALL PIPING VALVING ETC. ON HIGH PRESSURE

SIDE OF PRV'S SHALL BE WELDED OR FLANGED.

3. ALL ACCESSORY PIPING ON HIGH PRESSURE

SIDE OF PRV'S SHALL BE SCREWED AND BACK

WELDED.

4. TOTAL PRV CAPACITY 20,310# FOR INLET

PRESSURE OF 165 PSI AND OUTLET PRESSURE

OF 90 PSI.

6" STM

6" STM

PRESSURE

RELIEF VALVE 6" STM NC PRV-1

P

P

STEAM PIPING ACCESSORIS SPECIFICATION

1.1 Y-PATTERN STRAINERS:

A. BODY: ASTM A 126, CLASS B CAST IRON, WITH BOLTED COVER AND BOTTOM DRAIN CONNECTION.

B. END CONNECTIONS: THREADED ENDS FOR STRAINERS NPS 2 AND SMALLER; FLANGED ENDS FOR STRAINERS NPS 2-1/2 AND LARGER.

C. STRAINER SCREEN: STAINLESS-STEEL, 20 MESH STRAINER, AND PERFORATED STAINLESS-STEEL BASKET WITH 50 PERCENT FREE AREA.

D. TAPPED BLOWOFF PLUG.

E. CWP RATING: 250-PSIG WORKING STEAM PRESSURE.

1.2 PRESSURE-REDUCING VALVES

A. SIZE, CAPACITY, AND PRESSURE RATING: FACTORY SET FOR INLET AND OUTLET PRESSURES INDICATED.

B. DESCRIPTION: PILOT-ACTUATED, DIAPHRAGM TYPE, WITH ADJUSTABLE PRESSURE RANGE AND POSITIVE SHUTOFF.

C. BODY: CAST IRON.

D. END CONNECTIONS: FLANGED CONNECTIONS FOR VALVES NPS 2-1/2 AND LARGER.

E. TRIM: HARDENED STAINLESS STEEL.

F. HEAD AND SEAT: REPLACEABLE, MAIN HEAD STEM GUIDE FITTED WITH FLUSHING AND PRESSURE-ARRESTING DEVICE COVER OVER PILOT

DIAPHRAGM.

G. GASKETS: NON-ASBESTOS MATERIALS.

1.3 PRESSURE GAGES

A. DIRECT-MOUNTED, METAL-CASE, DIAL-TYPE PRESSURE GAGES:

1. STANDARD: ASME B40.100.

2. CASE: LIQUID-FILLED TYPE; CAST ALUMINUM OR DRAWN STEEL 4-1/2-INCH NOMINAL DIAMETER.

3. PRESSURE-ELEMENT ASSEMBLY: BOURDON TUBE UNLESS OTHERWISE INDICATED.

4. PRESSURE CONNECTION: BRASS, WITH NPS 1/4, ASME B1.20.1 PIPE THREADS AND BOTTOM-OUTLET TYPE UNLESS BACK-OUTLET TYPE IS

INDICATED.

5. MOVEMENT: MECHANICAL, WITH LINK TO PRESSURE ELEMENT AND CONNECTION TO POINTER.

6. DIAL: NONREFLECTIVE ALUMINUM WITH PERMANENTLY ETCHED SCALE MARKINGS GRADUATED IN PSI.

7. POINTER: DARK-COLORED METAL.

8. WINDOW: PLASTIC.

9. RING: STAINLESS STEEL.

10. ACCURACY: GRADE A, PLUS OR MINUS 1 PERCENT OF MIDDLE HALF OF SCALE RANGE.

1.4 PRESSURE GAGE ATTACHMENTS

A. SNUBBERS: ASME B40.100, BRASS; WITH NPS 1/4, ASME B1.20.1 PIPE THREADS AND POROUS-METAL-TYPE SURGE-DAMPENING DEVICE. INCLUDE

EXTENSION FOR USE ON INSULATED PIPING.

B. SIPHONS: LOOP-SHAPED SECTION OF BRASS PIPE WITH NPS 1/4 PIPE THREADS.

C. VALVES: BRASS BALL, WITH NPS 1/4, ASME B1.20.1 PIPE THREADS.

M-600

ERT BUILDING FIRST FLOOR

PLAN - MECHANICAL NEW

DBP

CAT

N ERT BUILDING FIRST FLOOR PLAN - MECHANICAL NEW

1 ERT BUILDING MECHANICAL ROOM - MECHANICAL NEW

SCALE: 1/4" = 1'-0"

22295.01

472/22138.ABG

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

M a t r ix funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P

L A

C H

R

A

D

IR

E C

T O

R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

2/14/2025 CD SET

SCALE: 1/8" = 1'-0"

0 1 5 10 20

3 ERT BUILDING MECHANICAL ROOM - PIPING NEW DIAGRAM

SCALE: NTS

DEMOLITION NOTES

DISCONNECT, REMOVE, AND DEMO EXISTING LAY-IN CEILING, CEILING

GRID, CEILING TILES, SUPPORTS, AND ALL ASSOCIATED ACCESSORIES

IN THEIR ENTIRETY. EXISTING HIGHLIGHTED SPACE CONTAINING LAY-IN

CEILING THAT IS TO BE DEMOLISHED IS ROUGHLY 1700 SQUARE FEET.

CONRACTOR TO REMOVE AND SALVATE EXISTING LIGHTING, WIRE,

CONDUIT, AND ALL ASSOCIATED ACCESORIES AS REQUIRED TO

REMOVE EXISTING LAY-IN CEILING AND BE RE-INSTALLED AFTER NEW

LAY-IN CEILING IS IN PLACE.

MECHANICAL KEY NOTES

INSTALL NEW LAY-IN CEILING, CEILING GRID, CEILING TILES,

SUPPORTS, AND ALL ASSOCIATED ACCESSORIES IN THE

HIGHLIGHTED AREA SHOWN.HIGHLIGHTED SPACE SHOWN FOR

INSTALLATION OF NEW LAY-IN CEILING THAT IS IS ROUGHLY 1700

SQUARE FEET. NEW LAY IN CEILING GRID AND CEILING TILES

ARE TO BE 2' x 4'. NEW CEILING TILES ARE BE BASED ON

ARMSTRONG GRENOBLE OR APPROVED EQUAL. INSTALL NEW

CEILING AT EXISTING CEILING HEIGHT. RE-INSTALL ALL

SALVAGED LIGHTING, CONDUIT, WIRE, AND ALL ASSOCAITED

ACCESSORIES TO MATCH THE LIGHTING ORIENTATION PRIOR TO

CONSTRUCTION.

WALLS ARE NOT FULL LENGTH UP TO LAY-IN CEILING.

1 1

1 1

1. ACOUSTICAL CEILING UNITS - GENERAL

1.1.STANDARD FOR ACOUSTICAL CEILING UNITS: PROVIDE UNITS

CONFORMING TO APPLICABLE REQUIREMENTS OF ASTM E 1264

FOR CLASS A MATERIALS.

2. CEILING SUSPENSION SYSTEMS - GENERAL

2.1.ATTACHMENT DEVICES FOR SUSPENSION SYSTEM:

2.1.1. ANCHORS AND INTERMEDIATE SUPPORT MEMBERS:

PROVIDE SIZES CAPABLE OF SUSTAINING 5 TIMES THE

LOAD-CARRYING CAPABILITIES SHOWN IN ASTM C 635,TABLE

1, “DIRECT HUNG” COLUMN.

2.1.2. DECK INSERTS AND HANGER CLIPS: FABRICATE FROM

STAINLESS STEEL.

2.1.3. HANGER WIRE: STAINLESS STEEL WIRE, ASTM A 641,

SOFT-TEMPER, WITH CLASS 1 COATING, MINIMUM 12 GA.

(0.106 INCH DIAMETER)

3. EDGE MOLDINGS AND TRIM:

3.1.METAL: PROVIDE INDICATED PROFILES. WHERE PROFILES ARE

NOT INDICATED, PROVIDE MOLDING WITH PROFILES SUITED TO

EDGE PROFILES OF ACOUSTICAL UNITS AND SUSPENSION

MEMBERS.

4. LAY-IN ACOUSTICAL CEILING SYSTEM

4.1.ACOUSTICAL PANELS: ARMSTRONG GRENOBLE, WHITE

4.1.1. SUBSTITUTIONS: EQUIVALENT PRODUCTS BY OTHER

MANUFACTURERS WILL BE CONSIDERED. THE ENGINEER

WILL BE THE SOLE JUDGE OF EQUIVALENCE.

4.1.2. SIZE: 24 X 48

4.1.3. EDGE PROFILE: SQUARE

4.1.4. COLOR: WHITE

4.1.5. PROVIDE 4 CASES FOR ATTIC STOCK.

4.2.EXPOSED GRID: PAINTED ALUMINUM WITH SPECIAL STAINLESS

STEEL LOCKING CLIPS

4.2.1. PROFILE: SINGLE-WEB TEE, 15/16”

4.2.2. STRUCTURAL CLASSIFICATION (ASTM C 635): INTERMEDIATE

DUTY SYSTEM

5. INSTALLATION

5.1. SUSPENSION SYSTEM INSTALLATION

5.1.1. GENERAL:

5.1.1.1. CONFORM TO THE REQUIREMENTS OF ASTM C 636,

MANUFACTURER'S INSTALLATION INSTRUCTIONS AND

GOVERNING REGULATIONS.

5.1.1.2. INSTALL HANGERS PLUMB AND SUPPORTED SOLELY

BY BUILDING STRUCTURE OR CARRYING CHANNELS.

DO NOT ALLOW HANGERS TO CONTACT ANY OBJECTS

OR MATERIALS IN CEILING PLENUM WHICH ARE NOT

ACTUAL COMPONENTS OF CEILING SYSTEM.

5.1.1.3. DO NOT ATTACH HANGERS TO PIPING, CONDUIT, OR

DUCT. PROVIDE CARRYING CHANNEL TRAPEZE

SUPPORT WHERE OBSTRUCTION CANNOT BE AVOIDED

BY SPLAYING HANGER 45 DEGREES FROM VERTICAL

OR LESS.

5.1.1.4. LEVEL CEILING SUSPENSION SYSTEM TO TOLERANCE

OF 1/8 INCH IN 12 FEET. BENDING OR KINKING OF

HANGERS IS NOT ALLOWED.

5.1.2. INDIRECT HUNG SUSPENSION: INSTALL CARRYING

CHANNELS AT 48 INCHES ON CENTER UNLESS INDICATED

OTHERWISE. USE CHANNELS LARGER THAN MINIMUM SIZE (1

½ INCH) OR DOUBLE CHANNELS TO MAINTAIN DEFLECTION

LIMITATION OF 1/360 OF SPAN OR LESS FOR LOADING

INDICATED.

5.2. TRIM INSTALLATION

5.2.1. INSTALL EDGE MOLDINGS AND TRIM UNITS AT ACOUSTICAL

CEILING BORDERS, AT LOCATIONS INDICATED, AND WHERE

REQUIRED TO COVER ACOUSTICAL UNIT EDGES.

FACE-RIVETING OF TRIM AND MOLDINGS IS NOT ALLOWED.

5.3. LAY-IN PANEL INSTALLATION

5.3.1. PANEL INSTALLATIONS: INSTALL ACOUSTICAL PANELS FOR

ACCURATE FIT WITH SUSPENSION SYSTEM AND TRIM

MEMBERS. SCRIBE AND CUT PANELS AT CEILING PERIMETER

AND AT OBSTRUCTIONS TO PROVIDE NEAT, PRECISE-FIT,

SQUARE EDGE PANEL INSTALLATION. PROVIDE

INSTALLATION WITH PANEL EDGES THAT ARE HIDDEN FROM

VIEW BY SUSPENSION MEMBERS OR TRIM.

GENERAL CEILING NOTES

M-800

DBP

CAT

22295.01

472/22138.ABG

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

M a t r ix funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P

L A

C H

R

A

D

IR

E C

T O

R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

2/14/2025 CD SET

MECHANICAL DETAILS

N ERT BUILDING MECHANICAL ROOM - CEILING REPLACMENT

SCALE: 1/8" = 1'-0"

0 1 5 10 20

J

PP

WH

D

J

J

EBBH

ECH

S

F

B

UNO

UFD

BD

WM

PM

OR

1,3

NUMBER

T

NF

F

FC

F

IC

TC

H

T

TS

CT

PC

WW

G EOL

ANN

FACP

TTDESIGNATIONS

FIRE ALARM

CONTROL

SERVICE and EQUIPMENT

SOUND and SIGNAL

MECHANICAL

CIRCUITRY and RACEWAYS

SWITCHES

FIXTURES

OUTLETS

MD

J

I

M

C

S

V

DH

ELECTRICAL SYMBOLS LEGEND

V

FCPS

M

C

DC

M

B

KP

SSCP

CCTV

S

VI

AV

B

X

X

X

NURSE CALL

NCC

M

P A

L

B1

B2

SRS

S D

S

C

H

CR

SS

AS

TS

OS1

OS3

PP

OS2

OS4

OS5

OC

SINGLE RECEPTACLE (120 VOLT)

DUPLEX RECEPTACLE

SWITCHED RECEPTACLE

HALF SWITCHED RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

FLUSH FLOOR BOX

SURFACE FLOOR BOX

SPECIAL EQUIPMENT RECEPTACLE

TELEPHONE OUTLET

DATA OUTLET

TELEPHONE / DATA OUTLET

POWER POLE

JUNCTION BOX

WALL JUNCTION BOX

PULL (JUNCTION) BOX

UNDERFLOOR JUNCTION BOX

FIXTURE

STRIP FIXTURE

FIXTURE ON EMERGENCY CIRCUIT

INGRADE FIXTURE

SPOTLIGHT (number of heads shown)

EXIT FIXTURE (face & direction as shown)

WALL MOUNT FIXTURE

DOWN LIGHT

TRACK & FIXTURE

STREET TYPE POLE FIXTURE

POLE MOUNTED FIXTURE

EXTERIOR WALL MOUNTED FIXTURE

WALLPACK FIXTURE

SPECIAL PURPOSE FIXTURE

HIGH BAY

EMERGENCY EGRESS LIGHT

(number of heads shown)

DOCK LIGHT

SINGLE-POLE SWITCH

THREE-WAY SWITCH

FOUR-WAY SWITCH

SWITCH WITH PILOT LIGHT

THERMAL OVERLOAD SWITCH

MANUAL MOTOR SWITCH

KEY SWITCH

DIMMER SWITCH

SINGLE PHASE MOTOR

THREE PHASE MOTOR

RESISTANCE HEATER, KW SHOWN

PIPE TRACE HEATER

ELECTRIC UNIT HEATER

ELECTRIC BASEBOARD HEATER

ELECTRIC CABINET HEATER

ELECTRIC WATER HEATER

NURSE CALL CONTROLLER

MASTER STATION

EMERGENCY PULL STATION

PENDENT INTERFACE

BED / LIGHT INTERFACE

SINGLE BED STATION

DUAL BED STATION

DOME LIGHT

STAFF REGISTER STATION

STAFF STATION

DUTY STATION

DEMOLITION NOTE

PLAN NOTE

ADDENDUM NOTE

EQUIPMENT DESIGNATION

UNLESS NOTED OTHERWISE

CONDUIT INSTALLED (specify method)

CONDUIT INSTALLED (specify method)

CONDUIT INSTALLED (specify method)

CIRCUIT UP

CIRCUIT DOWN

HOME RUN (with circuit numbers)

CONDUCTORS (ground, neutral, phase, switch leg, two travelers)

END OF CONDUIT RUN

END OF RUN, CAP AND STAKE

"RUN CONTINUES" INDICATION

FLEXIBLE PIGTAILS/CONNECTIONS

WIREMOLD AS SPECIFIED

PLUGMOLD AS SPECIFIED

BUS DUCT

UNDERFLOOR DUCT

SPEAKER

WALL MOUNTED SPEAKER

WALL MOUNTED SPEAKER / CLOCK COMBO

CLOCK RECEPTACLE

DUAL CLOCK RECEPTACLE

VIDEO INPUT

AUDIO / VIDEO INPUT

BELL

VOLUME CONTROL

BUZZER

CHIME

TELEVISION OUTLET

MICROPHONE OUTLET

INTERCOM OUTLET

CAMERA

DOOR CONTACT

MOTION DETECTOR

BEAM DETECTOR

KEY PAD

SECURITY SYSTEM CONTROL PANEL

CCTV CONTROL PANEL

CARD READER

STUDENT STATION

ADMINISTRATION STATION

TEACHER STATION

SMOKE DETECTOR

DETECTOR, RATE OF RISE

DUCT DETECTOR

HORN

HORN & LIGHT

SPEAKER

SPEAKER & LIGHT

PULL STATION

FIRE ALARM CONTROL PANEL

ANNUNCIATOR PANEL

END OF LINE DEVICE

REMOTE INDICATING LIGHT, WALL MTD.

REMOTE INDICATING LIGHT, CLG. MTD.

MAGNETIC DOOR HOLDER

FIREFIGHTER COMMUNICATION JACK

FLOW SWITCH (furnished by x/C)

TAMPER SWITCH (furnished by x/C)

VISUAL ONLY UNIT

FIRE CONTROL POWER SUPPLY

MONITOR MODULE

CONTROL MODULE

CARBON DIOXIDE DETECTOR

TRANSFORMER

DISCONNECT SWITCH (fuse size shown)

NON-FUSED DISC. (switch size shown)

MAGNETIC STARTER (BY x/C U.O.N.)

COMB. STARTER (BY x/C U.O.N.)

PANELBOARD, SURFACE MOUNTED

PANELBOARD, FLUSH MOUNTED

WEATHERHEAD

UTILITY METER, AS REQUIRED

CURRENT TRANSFORMERS

GENERATOR, KW SHOWN

TELEPHONE TERMINAL BOARD

GROUND CONNECTION PER N.E.C.

WIREWAY

TRANSFER SWITCH

CIRCUIT BREAKER

CIRCUIT BREAKER

CAPACITOR

THERMOSTAT

HUMIDISTAT

PHOTOCELL (voltage as required)

TIME CLOCK (24 hour U.O.N.)

PUSHBUTTON STATION (number of buttons indicated)

CONTROL TRANSFORMER

LIGHTING CONTACTOR

IRRIGATION CONTROLLER (120 volt xxVA connection by x/C)

MOTION DETECTOR

WALL MOUNT DUAL TECHNOLOGY SENSOR

SENSOR SWITCH WV-PDT-16 SERIES

OCCUPANCY SENSOR / PHOTOCELL SENSOR

SWITCH CMR-PC-ADC SERIES

ULTRASONIC SENSOR - 360° - 2 CIRCUIT SENSOR

SWITCH CMR-PDT-10-2P

ULTRASONIC SENSOR - 360° - 1000 SQ FT

SENSOR SWITCH CMR-PDT-10

ULTRASONIC SENSOR - 360° - 500 SQ FT SENSOR

SWITCH MCR-PDT SERIES

SWITCH STYLE OCCUPANCY SENSOR SENSOR

SWITCH WSD-PDT SERIES

POWER PACK SENSOR SWITCH MP20 SERIES

DIGITAL TIME SWITCH WATT STOPPER TS-400

M

ELECTRICAL ABBREVIATIONS

1P 1 POLE (2P, 3P, 4P, ETC.)

A AMPERE

AC ABOVE COUNTER

AC- AIR CONDITIONER

ACU- AIR CONDITIONING UNIT

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

AF AMP FRAME

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHJ AUTHORITY HAVING JURISDICTION

AHU- AIR HANDLING UNIT

AIC AMPS INTERUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

AMPL AMPLIFIER

ANNUN ANNUNCIATOR

APPROX APPROXIMATELY

AQ-STAT AQUASTAT

ARCH ARCHITECT, ARCHITECTURAL

AS AMP SWITCH OR ABOVE SHELF

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

B- BOILER

BATT BATTERY

BC BELOW COUNTER

BD BOARD

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

C CONDUIT

CAB CABINET

CAT CATALOG

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CHLR- CHILLER

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLG CEILING

COMB COMBINATION

CMPR COMPRESSOR

CND(C) CONDUIT

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

CONV CONVECTOR

CP CIRCULATING PUMP

CRT CATHODE-RAY TUBE

CT CURRENT TRANSFORMER

CT- COOLING TOWER

CTR CENTER

CU COPPER

CU- CONDENSING UNIT

CUH- CABINET UNIT HEATER

DCP DOMESTIC WATER CIRCULATING PUMP

DEPT DEPARTMENT

DET DETAIL

DFU- DUCT FURNACE

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DPR DAMPER

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

DWH- DOMESTIC WATER HEATER

EBB- ELECTRIC BASEBOARD

EC ELECTRICAL CONTRACTOR

EF- EXHAUST FAN

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EP ELECTRIC PNEUMATIC

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXH EXHAUST

EXIST (E) EXISTING

EXP EXPLOSION PROOF

FA FIRE ALARM

FABP FIRE ALARM BOOSTER POWER

SUPPLY PANEL

FACP FIRE ALARM CONTROL PANEL

FCU FAN COIL UNIT

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE CONDUIT

FLR FLOOR

FLUOR FLUORESCENT

FU FUSE

FU- FURNACE

FUDS FUSED SAFETY DISCONNECT SWITCH

GA GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTOR

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BD GYPSUM BOARD

H- HUMIDIFIER

HID HIGH INTENSITY DISCHARGE

HOA HANDS-OFF-AUTOMATIC SWITCH

HORIZ HORIZONTAL

HP HORSEPOWER

HPF HIGH POWER FACTOR

HR HOUR

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

HWP HYDRONIC WATER PUMP

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

I/W INTERLOCK WITH

JB JUNCTION BOX

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LC LIGHT CONTROL

LOC LOCATE OR LOCATION

LT LIGHT

LT FLEX LIQUID TIGHT FLEXIBLE METAL CONDUIT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MAX MAXIMUM

MAG.S MAGNETIC STARTER

M/C MOMENTARY CONTACT

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDC MAIN DISTRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOA MULTIOUTLET ASSEMBLY

MSP MOTOR STARTER PANELBOARD

MSBD MAIN SWITCHBOARD

MT MOUNT

MT.C EMPTY CONDUIT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MTR MOTOR, MOTORIZED

MUA- MAKE-UP AIR UNIT

N.C. NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURER'S

ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

N.O. NORMALLY OPEN

NPF NORMAL POWER FACTOR

NTS NOT TO SCALE

OH OVERHEAD

OL OVERLOADS

P POLE

P- PUMP

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PE PNEUMATIC ELECTRIC

PED PEDESTAL

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

PP POWER POLE

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV- POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QUAN QUANTITY

RCPT RECEPTACLE

RECEPT RECEPTACLE

REQD REQUIRED

RGC RIGID GALVANIZED STEEL CONDUIT

RM ROOM

RSC RIGID STEEL CONDUIT

RTU- ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SF- SUPPLY FAN

SHT SHEET

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

S/S STOP/START PUSHBUTTONS

STA STATION

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TCC TEMPERATURE CONTROL CONTRACTOR

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TL TWIST LOCK

TR TAMPER RESISTANT

TS TAMPER PROOF SWITCH

T-STAT THERMOSTAT

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TVTC TELEVISION TERMINAL CABINET

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UF UNDER FLOOR

UG UNDERGROUND

UH- UNIT HEATER

UL UNDERWRITERS' LABORATORIES, INC.

UNO UNLESS NOTED OTHERWISE

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UV UNIT VENTILATOR OR ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VDT VIDEO DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VL VERIFY LOCATION WITH OWNER

VOL VOLUME

W WATT

W/ WITH

WG WIRE GUARD

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Ø PHASE

C CENTER LINE

P PLATE

L L

GENERAL ELECTRICAL NOTES

1. ALL NON-FIRE RATED SURFACES ARE TO BE PATCHED WITH LIKE MATERIAL TO

MAINTAIN ORIGINAL RATING.

2. ALL PENETRATIONS THROUGH FIRE RATED SURFACES ARE TO BE SEALED WITH FIRE

CAULK TO MAINTAIN ORIGINAL RATING.

3. CONTRACTORS SHALL VISIT THE PROJECT SITE DURING PRE-BID WALK THROUGH TO

DETERMINE THE EXACT EXTENT OF THE WORK REQUIRED BEFORE BIDDING THE

PROJECT.

4. REMOVE ALL EXISTING EXPOSED CONDUIT, WIRE, AND EQUIPMENT NOT TO BE

RE-USED WHERE WORK IS BEING DONE EXCEPT ITEMS NOTED OTHERWISE.

5. EXISTING WORK WHICH IS PRESENTLY CONCEALED AND WHICH WILL REMAIN

CONCEALED AND DOES NOT INTERFERE WITH ANY NEW WORK OF ANY TRADE NEED

NOT BE REMOVED. HOWEVER, ALL CONDUIT SHALL BE CAPPED BELOW FINISH

SURFACE AND THEN PATCHED AND PAINTED TO MATCH, OR AS NOTED.

6. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF OLD WORK,

SURFACES SHALL BE PATCHED AND PAINTED TO MATCH ADJACENT.

7. EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED OR ENLARGED

TO SUIT THE NEW SYSTEMS AS REQUIRED. PROVIDE ALL REQUIRED CUTTING AND

PATCHING.

8. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING WALLS TO

MATCH THE ADJACENT SURFACES BEHIND ALL SURFACE MOUNTED EQUIPMENT.

9. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENTS AND CASUAL FIELD

OBSERVATION. REPORT ANY DISCREPANCIES TO ENGINEER FOR CLARIFICATION.

10. MINIMUM RACEWAY SIZE; 3/4" TRADE SIZE. ALL FLEXIBLE CONDUIT RACEWAYS SHALL

BE LIQUID TITE, MAXIMUM 36" LENGTH. REFER TO SPECIFICATION 260533 - RACEWAY

AND BOXES FOR ELECTRICAL SYSTEMS.

11. ALL CONDUIT ABOVE 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:

11.1. STRAP DISTANCE: 5 FEET.

11.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.

11.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED- GRC.

11.4. FITTINGS: COMPRESSION.

11.5. BELL BOXES: FS TYPE.

11.6. NO KNOCKOUTS.

11.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES.

12. ALL CONDUIT BELOW 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:

12.1. STRAP DISTANCE: 3 FEET.

12.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.

12.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED - GRC.

12.4. FITTINGS: COMPRESSION.

12.5. BELL BOXES: FS TYPE.

12.6. NO KNOCKOUTS.

12.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES

13. ALL EXPOSED WIRING SHALL BE IN CONDUIT. OPEN LOW VOLTAGE WIRING ABOVE

CEILINGS IS ACCEPTABLE.

14. ALL NEW CONDUITS AND WIRES SHALL BE INSTALLED STRAIGHT AND LEVEL AND

SHALL BE PARALLEL OR PERPENDICULAR TO THE BUILDING LINES.

15. ALL NEW CONDUITS SHALL BE FIELD ROUTED ALONG EXISTING PIPING AND

STRUCTURAL STEEL.

16. ALL LOCATIONS WHERE THE WALLS CAN'T BE FISHED SHALL BE SURFACE MOUNTED

CONDUIT FOLLOWING NOTES 10 THROUGH 12 ABOVE.

17. ALL WALLS THAT ARE ACCESSIBLE SHALL BE FISHED AND DEVICE CUT INTO WALL.

18. ALL EXTERIOR CONCEALED CONDUIT UNDERGROUND SHALL BE RNC, TYPE

EPC-40-PVC

19. ALL ELECTRICAL OUTAGES SHALL NOT LAST OVER 2-HOURS. PORTABLE GENERATORS

SHALL BE USED TO REPLACE ANY ELECTRICAL SERVICE EXCEEDING THAT DURATION.

20. IN RELATION TO RELOCATING ANY ELECTRICAL DEVICE, CONTRACTOR SHALL

COMPLETE THE RELOCATION IN ONE DAY AND VERIFY THAT ALL DEVICES RELOCATED

ARE WORKING PROPERLY PRIOR TO LEAVING THE SITE.

21. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED COMPONENTS,

RACEWAYS, WIRE, AND HARDWARE AS INDICATED ON DRAWINGS.

22. ALL WORK DONE WITHOUT APPROVED SHOP DRAWINGS IS AT CONTRACTORS RISK.

23. CONTRACTOR SHALL CONTACT COMMTECH FOR SPECIFICATIONS FOR CAT6 AND

OTHER…