22065 Milton-Freewater OMD 22-08-05.pdf
PDF 3 MB Posted
- Attached to
- 39. 92 miles of chip seal along US730 & OR11
- Solicitation number
- S-73000-00005029
- Issued by
- Union County, Jacksonville City, Oregon
About this file
This document is a Request for Proposal (RFP) issued by the Oregon Military Department for mechanical and electrical system upgrades at the Milton-Freewater Armory located at 149 South Main Street, Milton-Freewater, Oregon 97862. The project involves design-build scope covering demolition of the existing Variable Refrigerant Flow (VRF) system and replacement with packaged rooftop equipment, condensing units, and furnaces. The RFP includes comprehensive mechanical and electrical drawings at 90% design completion dated August 5, 2022, showing Level 1 demolition and installation plans, roof plans, and equipment schedules. The project requires licensed Oregon engineers to prepare and seal all drawings, with contractors responsible for permitting and associated fees. Key deliverables include mechanical system modifications (RTU-1, RTU-2, RTU-3, and condensing units CU-1, CU-2, CU-3), natural gas piping installation with shut-off valves and pressure regulators, combustion air and vent provisions, condensate pump replacement, ductwork transitions, and electrical system upgrades including new disconnects and panel modifications. The mechanical schedule indicates basis of design performance specifications for equipment, with acceptable alternates required to perform within ±5% of scheduled values. Control systems will be contracted separately through the Oregon Military Department's control vendor, with packaged rooftop equipment required to include BACnet-compatible controllers.
The project involves structural engineering support for roof-mounted equipment with seismic connection calculations and attachment details, and requires coordination with the natural gas utility for meter replacement and regulator installation. Contractors must provide operation and maintenance manuals to the building owner within 90 days of system acceptance per ASHRAE Standard 90.1, including submittal data, service agency information, and controls system maintenance and calibration details. HVAC systems must be balanced in accordance with generally accepted engineering standards, with written balance reports provided for systems serving conditioned areas exceeding 5,000 square feet. All work shall comply with applicable local, county, state, and federal codes and regulations, including UL specifications for fire-safing and weather sealing at wall and floor penetrations, SMACNA standards for ductwork and piping support, and NFPA-13 for fire protection systems. The RFP emphasizes that drawings are diagrammatic in nature and indicate system concept rather than absolute precision, requiring contractors to provide all necessary components and materials for complete system operation and to verify locations, dimensions, and equipment placement prior to construction or material procurement.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Invitation to Bid~8.pdf | ||
| M21039_CON_SP_W_POR.pdf | ||
| M21039_PSnEPlans_02.pdf | ||
| GE_M21039_Memo_04.pdf | ||
| Intent to Award Notice.pdf | ||
| Bid Tabulation - Preliminary Results~1.pdf | ||
| Addendum 1 - Special Provisions Modification.pdf | ||
| Bid Pricing Form~13.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
8 7 6 5 4 3 2 1
A
145 36 278
B
C
D
E
F
D
AT
E D
ES
C
R
IP
TI
O
N R
EV
Sheet Number:
Proj No:
Sheet Title:
AP
PR
C
LI
EN
T:
PR
O
JE
C
T:
M
IL
TO
N -F
R
EE
W
AT
ER
A
R M
O R
Y
ENGINEER STAMP
KEEP AREA CLEAR FOR AHJ
APPROVAL STAMP
M
IL
TO
N
-F R
EE
W
AT
ER
, O R
EG
O
N
SO
U
TH
M
AI
N
S
TR
EE
T
O R
EG
O
N M
IL
IT
AR
Y
D
EP
AR
TM
EN
T
R
EQ
U
ES
T
FO
R P
R O
PO
SA
L
VICINITY MAPOVERALL PLAN
NO
RT
H
N O
R
TH
OREGON MILITARY DEPARTMENT
MILTON-FREEWATER ARMORY REQUEST FOR PROPOSAL
149 South Main Street Milton-Freewater, Oregon 97862
SHEET NUMBER SHEET TITLE REV DATE
G-001 GENERAL TITLE SHEET B 08/05/22
M-001 MECHANICAL LEGEND, ABBREVIATIONS, & GENERAL NOTES B 08/05/22
E-001 ELECTRICAL LEGEND, ABBREVIATIONS, & GENERAL NOTES B 08/05/22
ME101 MECHANICAL/ELECTRICAL DEMOLITION LEVEL 1 PLAN B 08/05/22
ME102 MECHANICAL/ELECTRICAL DEMOLITION ROOF PLAN B 08/05/22
ME111 MECHANICAL/ELECTRICAL LEVEL 1 PLAN B 08/05/22
ME112 MECHANICAL/ELECTRICAL ROOF PLAN B 08/05/22
ME601 MECHANICAL/ELECTRICAL SCHEDULES B 08/05/22
ME602 MECHANICAL/ELECTRICAL SCHEDULES A 08/05/22
PROJECT
AREAS
PROJECT
SITE
S C
O
LU
M
BI
A
STS MAIN ST
S
EL
IZ
AB
ET
H
S T
D E
H
AV
EN
S
T
SW 2ND AVE
E BROADWAY AVE
SE 2ND AVE
SE 1ST AVE
SE 3RD AVE
CC22065
G-001
GENERAL
TITLE
SHEET
A
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 1/
JL
S
B
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 5/
JL
S
GENERAL NOTES
A OMD IS REQUESTING THAT THE EXISTING VRF SYSTEM TO BE DEMOLISH AND REPLACED
WITH PACKAGED ROOFTOP EQUIPMENT, CONDENSING UNITS, AND FURNACES.
B THESE DRAWINGS ARE TO PROVIDE DIRECTION AND PROJECT INTENT.
C THIS PROJECT WILL BE DESIGN/BUILD WITH MECHANICAL, ELECTRICAL, STRUCTURAL,
AND SLIGHT ARCHITECTURAL MODIFICATIONS. DRAWINGS ARE TO BE PREPARED AND
SEALED BY ENGINEERS LICENSED IN THE STATE OF OREGON.
D CONTRACTOR IS RESPONSIBLE FOR PERMITTING AND ALL ASSOCIATED FEES.
E MECHANICAL SCHEDULES SHOW BASIS OF DESIGN AND INCLUDE PERFORMANCE FOR
THAT SIZE MODEL. IF USING ALTERNATE APPROVED MANUFACTURERS, PERFORMANCE
SHOULD BE WITHIN +/-5% OF SCHEDULED VALUES.
F CONTROLS WILL BE CONTRACTED SEPARATELY THROUGH OMD'S CONTROL VENDOR.
UNIT CONTROLS FOR FURNACES AND CONDENSING UNITS WILL USE STANDARD
TERMINAL STRIPS. PACKAGED ROOFTOP EQUIPMENT IS TO INCLUDE BACNET
COMPATIBLE CONTROLLERS.
G AUTOCAD FILES OF THE EXISTING CONDITIONS ARE AVAILABLE FROM OMD.
H SEE WRITTEN REQUEST FOR PROPOSAL INSTRUCTIONS FOR OTHER DETAILS
NOT FOR CONSTRUCTION
AutoCAD SHX Text T
D
AT
E D
ES
C
R
IP
TI
O
N R
EV
Sheet Number:
Proj No:
Sheet Title:
AP
PR
C
LI
EN
T:
PR
O
JE
C
T:
M
IL
TO
N -F
R
EE
W
AT
ER
A
R M
O R
Y
ENGINEER STAMP
KEEP AREA CLEAR FOR AHJ
APPROVAL STAMP
M
IL
TO
N
-F R
EE
W
AT
ER
, O R
EG
O
N
SO
U
TH
M
AI
N
S
TR
EE
T
O R
EG
O
N M
IL
IT
AR
Y
D
EP
AR
TM
EN
T
R
EQ
U
ES
T
FO
R P
R O
PO
SA
L
CC22065
M-001
MECHANICAL
LEGEND,
ABBREVIATIONS,
& GENERAL NOTES
A
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 1/
JL
S
B
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 5/
JL
S
GENERAL NOTES
ABBREVIATIONS EQUIPMENT SYMBOLS
XX
XX
XX
XX
XX
GENERAL SYMBOLS
DUCTWORK SYMBOLS
GRILLE/REGISTER
S
BDD
FD
FSD
SD
12x9Ø
12Ø
12x9
SINGLE LINE
BDD
FSD
S
FIRE/SMOKE DAMPER
BACK DRAFT DAMPER
SMOKE DETECTOR
SD
FD
PHOTOHELIC
FIRE DAMPER
HAND/VOLUME DAMPER
BLAST GATE DAMPER
ACTUATED DAMPER
(UNIT CONTROLLED)
SIDEWALL SUPPLY REGISTER
ROOM THERMOSTAT, PENDENT MOUNT.
ROOM HUMIDISTAT
SMOKE DAMPER
SUPPLY DUCT
RADIUS ELBOW W/TURNING VANE
SQUARE ELBOW W/TURNING VANES
LONG RADIUS ELBOW
STANDARD RADIUS ELBOW
CROSS SECTION THRU ROUND DUCT
EXHAUST OR RETURN DUCT
12x9Ø
12x9
DOUBLE LINE
ROUND DUCT (INCHES)
DESCRIPTION
OVAL DUCT (INCHES)
FLEXIBLE CONNECTION
FLEXIBLE DUCT
RECTANGULAR DUCT, WIDTH x DEPTH (INCHES)
SIDEWALL EXHAUST REGISTER OR RETURN AIR
CEILING EXHAUST REGISTER OR RETURN AIR GRILLE
ASSUME 4-WAY THROW UNLESS OTHERWISE INDICATED
ROOM THERMOSTAT, PNEUMATIC OR ELECTRONIC
CEILING DIFFUSERS (ARROWS DENOTE THROW PATTERN)
SYMBOL DESCRIPTION
12Ø
= INTERNALLY LINED
SYMBOL DESCRIPTION
(UNIT CONTROLLED)
PIPE DESIGNATIONS
ACCEPTABLE METHOD
MULTI-LINE DESIGNATION
PREFERRED METHOD
2"-HWS
= INTERNALLY LINED
ANNOTATION SYMBOLS
FLOW ARROWS
NORTH ARROW
DETAIL SYMBOL
DETAIL NUMBER
ELEVATION SYMBOL
ELEVATION LETTER
XX KEYED NOTE
EQUIPMENT TAG
REVISION TRIANGLE
DRAWING NUMBER WHERE DETAIL APPEARS
DIFFERENTIAL PRESSURE SENSOR
NEW
STATIC PRESSURE SENSOR
EXISTING TO BE REMOVED
SHUT DOWN
CONNECT TO EXISTING
EXISTING TO REMAIN
FUTURE(F)
(E)
(N)
(D)
AIR OUTLET/INLET DESIGNATION
SPECIFICATIONS (TYP.)
(3-WAY SHOWN) RETURN OR EXHAUST
AIRFLOW, CFM (TYP.)
NECK SIZE, INCHES (TYP.)
FIXTURE IDENTIFICATION
EXAMPLE: SUPPLY (THROW DIRECTION)
FIXTURE IDENTIFICATION
ABBREVIATIONS TABLE
FIXTURE TYPE AS SHOWN IN
NO. IN SPECIFICATIONS
CD-1
EXAMPLE:
CFM
CD-1 18x18
800 CFM
RG-1 18x12
CFM
SG-3 24x18
X
XXX
XXX
DRAWING NUMBER WHERE ELEVATION APPEARS
XXX
XXX
XXX
XXX
SECTION CUT SYMBOL
SECTION LETTER
DRAWING NUMBER WHERE SECTION APPEARS
X
M M
(201)
(201)
T
H
T
S/D
DP
SP
FLOW STREAM DESIGNATION
XX
CENTRIFUGAL PUMP
SUBMERSIBLE PUMP
MULTISTAGE CENTRIFUGAL PUMP
VACUUM PUMP
LIQUID RING PUMP
SUMP PUMP
EXHAUST FAN
XX EQUALS:
AFD ADJUSTABLE FREQUENCY DRIVE
CS-1 CONSTANT SPEED - SINGLE SPEED MOTOR
CS-2 CONSTANT SPEED - TWO SPEED MOTOR
A THIS IS A GENERAL LEGEND PAGE, NOT ALL ITEMS ON THIS SHEET WILL BE USED.
B ALL WORK SHALL CONFORM TO ALL APPLICABLE LOCAL, COUNTY, STATE AND FEDERAL CODES AND
REGULATIONS AND OWNER'S STANDARDS.
C DRAWINGS ARE DIAGRAMMATIC. DRAWINGS ARE NOT INTENDED TO BE ABSOLUTELY PRECISE, AND DO NOT SPECIFY OR SHOW EVERY OFFSET, FITTING AND COMPONENT. THE PURPOSE OF THE DRAWINGS IS TO INDICATE A SYSTEM CONCEPT, THE MAIN COMPONENTS OF THE SYSTEMS, AND THE APPROXIMATE GEOMETRICAL RELATIONSHIPS. BASED ON THE SYSTEMS CONCEPT, THE MAIN COMPONENTS AND THE
GEOMETRICAL RELATIONSHIPS THE CONTRACTOR SHALL PROVIDE ALL OTHER COMPONENTS AND
MATERIALS NECESSARY TO MAKE THE SYSTEM FULLY COMPLETE AND OPERATIONS. CONTRACTOR
SHALL ROUTE PIPING OR PROVIDE OFFSETS TO AVOID INTERFERENCE WITH STRUCTURAL ELEMENTS, ELECTRICAL PANELS AND JUNCTION BOXES ETC. VERIFY LOCATIONS, DIMENSIONS, EXISTING FLOW DIRECTIONS, ETC. BEFORE CONSTRUCTION. FIELD VERIFY ALL SIZES, DIMENSIONS AND EQUIPMENT
LOCATIONS PRIOR TO CONSTRUCTION OR MATERIAL PROCUREMENT.
D REPAIR AND PATCH ALL (NEW AND EXISTING) WALL AND FLOOR PENETRATIONS TO MATCH EXISTING
FINISH. PROVIDE SLEEVES AND SEAL ALL PENETRATIONS OF FIRE RATED WALLS/ FLOORS IN
ACCORDANCE WITH UL SPECIFICATIONS, WITH 3M AND/ OR HILTI FIRE STOPPING MATERIALS APPROVED
FOR THE PURPOSE. PROVIDE FIRE DAMPERS WHERE DUCTS PENETRATE FIRE RATED WALLS OR
FLOORS.
E IN ADDITION TO FIRE-SAFING AND WEATHER SEALING REQUIREMENTS, PROVIDE CHROME ESCUTCHEON
RINGS WHERE DUCTS AND PIPES PENETRATE THE FINISHED SIDE OF WALLS AND CEILINGS.
F ALL EXTERIOR WALL PENETRATIONS SHALL BE FLASHED AND SEALED WEATHER-TIGHT AND TO A
STRUCTURALLY SOUND CONDITIONS.
G PROVIDE SUPPORT AND LATERAL BRACING FOR ALL DUCTWORK, PIPING AND EQUIPMENT IN
ACCORDANCE WITH SMACNA AND BUILDING CODES. CONTRACTOR SHALL DESIGN AND PROVIDE
CALCULATIONS AND SKETCHES AS REQUIRED BY THE LOCAL BUILDING DEPARTMENT.
H PROVIDE VOLUME DAMPERS AT NEW AND EXISTING SUPPLY AND EXHAUST DUCT BRANCHES.
J FIRE PROTECTION SCOPE IS A DESIGN-BUILD PROJECT BY THE FIRE PROTECTION CONTRACTOR.
SPRINKLER DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA-13 AND THE BUILDING
CODES.
K CONTRACTOR SHALL PROVIDE O&M MANUALS TO THE BUILDING OWNER FOR ALL PROVIDED EQUIPMENT WITHIN 90 DAYS OF SYSTEM ACCEPTANCE PER ASHRAE STANDARD 90.1 AND IN ACCORDANCE WITH
INDUSTRY ACCEPTED STANDARDS. MANUALS SHALL INCLUDE SUBMITTAL DATA, O&M MANUALS,
SERVICE AGENCY, CONTROLS SYSTEM MAINTENANCE AND CALIBRATION INFORMATION, AND A
NARRATIVE OF HOW EACH SYSTEM IS INTENDED TO OPERATE.
L HVAC SYSTEMS SHALL BE BALANCED IN ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING STANDARDS. CONTRACTOR SHALL PROVIDE A WRITTEN BALANCE REPORT TO THE BUILDING OWNER FOR HVAC SYSTEMS SERVING ZONES WITH A TOTAL CONDITIONED AREA EXCEEDING 5,000 SQFT PER ASHRAE
STANDARD 90.1.
XX
NORTH
EQUIPMENT TAGXXX-X
3"-HWS
3"-HWR
2"-CHWS
2"-CHWR
ACCEPTABLE METHOD
PIPING IDENTIFIED FROM
LEFT TO RIGHT OR TOP
TO BOTTOM
2"-HWS
CW
CHWR
CHWS
LPS
ICW
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CITY WATER
LOW PRESSURE STEAM
INDUSTRIAL COLD WATER
NON POTABLE WATERNPW
HEATING WATER RETURNHWR
HEATING WATER SUPPLYHWS
COND CONDENSATE DRAIN
ABV ABOVE
AC ACTIVATED CARBON FILTER OR
ALTERNATING CURRENT
ACC AIR COOLED CHILLER
ACFM ACTUAL CUBIC FEET/MINUTE
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
AFD ADJUSTABLE FREQUENCY DRIVE
AFF ABOVE FINISHED FLOOR
AH AIR HANDLER, GENERAL
AHU AIR HANDLING UNIT
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
AMP AMPERE (AMP,AMPS)
ARF ABOVE RAISED FLOOR
BDD BACK DRAFT DAMPER
BF BUTTERFLY VALVE
BHP BRAKE HORSEPOWER
BLO BLOWER
BLR BOILER
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BOT BOTTOM OF TRAY
BOTT BOTTOM
BOM BILL OF MATERIAL
BTU BRITISH THERMAL UNIT
C CENTIGRADE OR COMPRESSOR
CA COMPRESSED AIR
CC COOLING COIL
CD CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE
CH CHILLER
CKT CIRCUIT
CLP COIL PUMP
CO CLEANOUT
CONN CONNECTION
CPLG COUPLING
CRU CONDENSATE RETURN UNIT
CSST CORRUGATED STAINLESS STEEL TUBING
CT COOLING TOWER
CTG CLEANOUT TO GRADE
CU CONDENSATE UNIT
CV CONSTANT VOLUME TERMINAL UNIT
CVR ONSTANT VOLUME REHEAT TERMINAL UNIT
dB DECIBEL
(D) DEMOLISH
DB DRY BULB
DBT DRY BULB TEMPERATURE
DC DIRECT CURRENT
DDC DIRECT DIGITAL CONTROL
DEH DEHUMIDIFIER
DER DEAERATOR
DF DRINKING FOUNTAIN
DIA DIAMETER
DN DOWN
(E) EXISTING
EA EACH
EA EXHAUST AIR
EF EXHAUST FAN
EFF EFFICIENCY
ELEV ELEVATION
EPO EMERGENCY POWER OFF
ET EXPANSION TANK
EWC ELECTRIC WATER COOLER
EXH EXHAUST, GENERAL
(F) FUTURE
F FAHRENHEIT
FCU FAN COIL UNIT
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FF FINISHED FLOOR
FFE FINISHED FLOOR ELEV
FFU FAN FILTER UNIT
FL CARTRIDGE OR BAG FILTER
FLT FILTER
FN FAN
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FP FAN POWERED TERMINAL UNIT
FPM FEET PER MINUTE
FPS FEET PER SECOND
FT FOOT OR FEET
GA GAGE OR GAUGE, OR GENERAL AIR
GAL GALLONS
GCO GRADE CLEANOUT
GEN GENERATOR
GD GROUND DIFFUSER
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HC HEATING COIL
HD HEAD
HE HEAT EXHAUST
HG MERCURY
HOR HORIZONTAL
HP HORSEPOWER
HR HOUR(S)
HU HUMIDIFIER
HX HEAT EXCHANGER
HYD HYDRAULIC
HZ HERTZ (FREQUENCY)
ID INSIDE DIAMETERIE INVERT ELEVATION
KW KILOWATT
KWH KILOWATT HOUR
KVA KILOVOLT-AMPERE
LAV LAVATORY
LBS POUNDS
LD LEAK DETECTION
LPD LOW POINT DRAIN
(M) MECHANICAL
MAH MAKEUP AIR HANDLER
MAX MAXIMUM
MCC MOTOR CONTROL CENTER
MIN MINIMUM
MISC MISCELLANEOUS
MM MULTI-MEDIA FILTER
MOT MOTOR
MP METERING PUMP
MUA MAKEUP AIR
(N) NEW
N/A NOT APPLICABLE
NC NOISE CRITERIA OR NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OBD OPPOSABLE BLADE DAMPER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OL OVERLOAD RELAY
OSA OUTSIDE SUPPLY AIR
OZ OUNCE
PD PRESSURE DROP
PH PHASE
PIV POST INDICATOR VALVE
PL PLUG VALVE
POC POINT OF CONNECTION
PPM PARTS PER MILLION
PSI POUNDS PER SQUARE INCH
PSIA PSI, ABSOLUTE
PSIG PSI, GAUGE
QT QUART
QTY QUANTITY
(R) RELOCATE
RA RETURN AIR
RAH RECIRC. AIR HANDLER
REQ REQUIRED
REV REVISION
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RM ROOM
RPM REVOLUTIONS PER MINUTE
RTU ROOF TOP UNIT
SA SUPPLY AIR
SC SCRUBBER
SCFM STANDARD CUBIC FEET/MINUTE
SD SUPPLY DIFFUSER
SEC SECOND
SG SUPPLY GRILLE
SLM STANDARD LITERS/MINUTE
SM SHEET METAL
SP STATIC PRESSURE
SPEC SPECIFICATION
SS STAINLESS STEEL
STD STANDARD
TB THRUST BLOCK
TD TEMPERATURE DIFFERENCE
TEMP TEMPERATURE
TF TRANSFER FAN
TK TANK
T.O. TOP OF
TOD TOP OF DUCT
TOP TOP OF PIPE
TOS TOP OF STEEL (SUPPORT)
TPU THERMAL PROCESSING UNIT
TSTAT THERMOSTAT
TU TERMINAL UNIT
TYP TYPICAL
UF ULTRA FILTRATION UNIT
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UR URINAL
V VOLT
VAC VACUUM
VAR VARIABLE
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VERT VERTICAL
VP VACUUM PUMP
VV VARIABLE VOLUME TERMINAL UNIT
VVR VARIABLE VOLUME REHEAT TERMINAL UNIT
W/ WITH
W WATT
WB WET-BULB
WBT WET-BULB TEMPERATURE
WC WATER CLOSET
W.C. WATER COLUMN
WP WEATHERPROOF
WS WATER SOFTENER
WTR WATER TEMPERATURE RISE
WTD WATER TEMPERATURE DROP
WX WET EXHAUST
XFMR TRANSFORMER
YD YARD
YR YEAR
Z ZONE
NOT FOR CONSTRUCTION
E D
ES
C
R
IP
TI
O
N R
EV
Sheet Number:
Proj No:
Sheet Title:
AP
PR
C
LI
EN
T:
PR
O
JE
C
T:
M
IL
TO
N -F
R
EE
W
AT
ER
A
R M
O R
Y
ENGINEER STAMP
KEEP AREA CLEAR FOR AHJ
APPROVAL STAMP
M
IL
TO
N
-F R
EE
W
AT
ER
, O R
EG
O
N
SO
U
TH
M
AI
N
S
TR
EE
T
O R
EG
O
N M
IL
IT
AR
Y
D
EP
AR
TM
EN
T
R
EQ
U
ES
T
FO
R P
R O
PO
SA
L
CC22065
E-001
ELECTRICAL
LEGEND,
ABBREVIATIONS,
& GENERAL NOTES
A
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 1/
JL
S
B
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 5/
JL
S
ELECTRICAL LEGEND
SYMBOL DESCRIPTION
ABBREVIATIONS
BLACK
BLUE
ABOVE 600V208/120V, 240/120V
ISO GROUND
CONDUCTOR
NEUTRAL
GROUND
PHASE B
PHASE C
PHASE A
GREEN
WHITE
GN/YL
BLUE
RED
BLACK
GN/ YL
YELLOW
ORANGE
BROWN
480/277V
GREEN
GRAY
RED
CONDUCTOR COLOR CODES
T
HP
HP
NL
2'x4' RECESSED FIXTURE
2'x4' RECESSED FIXTURE, EMERGENCY
2'x4' FIXTURE
2'x4' FIXTURE, EMERGENCY
1'x4' RECESSED FIXTURE
1'x4' RECESSED FIXTURE, EMERGENCY
1'x4' FIXTURE
1'x4' FIXTURE, EMERGENCY
2'x2' RECESSED FIXTURE
2'x2' RECESSED FIXTURE, EMERGENCY
2'x2' FIXTURE
2'x2' FIXTURE, EMERGENCY
4' STRIP FIXTURE
4' WALL MOUNTED FIXTURE
SURFACE OR PENDANT MOUNTED FIXTURE
RECESSED DOWNLIGHT FIXTURE
NIGHT LIGHT
TELEPHONE JACK, 4SQ BOX WITH SINGLE GANG MUD RING
MOUNT @ +18" AFF (1-CAT6A) UNO
TELE/DATA JACK, 4SQ BOX WITH SINGLE GANG MUD RING
MOUNT @ +18" AFF UNO (2-CAT6A) UNO
DATA JACK, 4SQ BOX WITH SINGLE GANG MUD RING
MOUNT @ +18" AFF UNO (2-CAT6A) UNO
TELEPOWER POLE (T=TELEPHONE, P=POWER, C=COMPUTER)
1,3
T
FSD
S Z Y
EMERGENCY WALL PACK
WALL MOUNTED EXIT SIGN
CEILING MOUNTED EXIT SIGN
DARKENED SEGMENT INDICATES NUMBER OF AND DIRECTION OF
EXIT FACE(S)
DIRECTIONAL ARROWS AS SHOWN ON EXIT FIXTURES
POLE MOUNTED FIXTURE
SITE BOLLARD FIXTURE
NONFUSED DISCONNECT SWITCH, AMPERAGE INDICATED,
SEE NOTE F.
FUSED DISCONNECT SWITCH, AMPERAGE INDICATED,
SEE NOTE F.
ENCLOSED CONTACTOR, MAGNETIC, AMPERAGE INDICATED,
SEE NOTES F AND G.
ENCLOSED STARTER, MAGNETIC, NEMA SIZE INDICATED,
SEE NOTES F AND G.
ENCLOSED STARTER, COMBINATION MAGNETIC, NEMA SIZE
INDICATED, SEE NOTES F AND G.
CURRENT TRANSFORMERS (WITH POTENTIAL TRANSFORMERS
WHERE REQUIRED)
J
J
J
D
WP
GFCI
IG
SINGLE RECEPTACLE (120V)
DUPLEX RECEPTACLE (120V)
DEDICATED DUPLEX RECEPTACLE (120V)
WEATHERPROOF RECEPTACLE
GROUND FAULT RECEPTACLE
ISOLATED GROUND RECEPTACLE
RECEPTACLE ABOVE COUNTER
HALF SWITCHED RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
FLUSH FLOOR RECEPTACLE, DUPLEX
SPECIAL EQUIPMENT RECEPTACLE
LOCKING RECEPTACLE
JUNCTION BOX
PULL (JUNCTION) BOX
UNDER FLOOR JUNCTION BOX
SINGLE-POLE SWITCH
SINGLE-POLE SWITCH WITH SWITCH LEG
DOUBLE-POLE SWITCH
THREE-WAY SWITCH
FOUR-WAY SWITCH
SWITCH WITH PILOT LIGHT
COMBINATION SWITCH/DUPLEX RECEPTACLE
LOW-VOLTAGE SWITCH, NUMBER AS NOTED
LOCKING SWITCH
SINGLE-POLE DIMMER SWITCH
SINGLE-POLE FLUORESCENT DIMMER SWITCH
KEY SWITCH
WEATHERPROOF SWITCH
TIME SWITCH
OCCUPANCY SENSOR
SWITCH WITH OCCUPANCY SENSOR
60A
TL
THERMOSTAT
HUMIDISTAT
PHOTOCELL
TIME CLOCK
PUSHBUTTON STATION
FIRE ALARM PULL STATION
SMOKE DETECTOR
HEAT DETECTOR, RATE OF RISE
DUCT DETECTOR
HORN
STROBE ONLY, CANDELA AS NOTED
MAGNETIC DOOR HOLDER
FIREFIGHTER COMMUNICATION JACK
FLOW SWITCH
TAMPER SWITCH
FIRE SMOKE DAMPER
CEILING MOUNTED SPEAKER/STROBE, CANDELA AS NOTED
HORN STROBE, STROBE CANDELA AS NOTED
FIRE ALARM CONTROL PANEL
ANNUNCIATOR PANEL
CONTROL
FIRE ALARM
J
GENERAL NOTES
A THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS OR ABBREVIATIONS MAY APPEAR
ON THIS SHEET AND NOT ON THE PROJECT DRAWINGS.
B CONDUIT RUNS MARKED WITH CROSSHATCHES INDICATE NUMBER OF #12 AWG
CONDUCTORS. CROSSHATCH WITH DOT INDICATES GROUND WIRE. SIZE CONDUIT
ACCORDING TO SPECIFICATIONS AND APPLICABLE CODES UNLESS OTHERWISE NOTED.
C TAG NUMBER DENOTES DEVICES ADDRESS.
D CONDUCTORS AND CONDUIT ARE SIZED ON BASIS OF COPPER, THHN-2/THWN-2.
CIRCUITS THROUGH 100A SIZED ON BASIS OF 60°C. CIRCUITS GREATER THAN 100A SIZED
ON BASIS OF 75°C, UNLESS NOTED OTHERWISE. CONDUIT SHALL BE EMT, UNLESS
NOTED OTHERWISE.
E MOUNT ALL EQUIPMENT PER SPECIFICATIONS UNLESS INDICATED OTHERWISE. REFER
TO PLAN DRAWINGS AND SECTIONS FOR MOUNTING HEIGHTS.
F ALL ENCLOSURES ARE NEMA 1 UNLESS INDICATED OTHERWISE:
3R = NEMA 3R, X = EXPLOSION PROOF
4X = NEMA 4X, WP = WEATHER PROOF
G SEE CONTROL DIAGRAMS FOR OPERATIONAL SCHEMATIC.
H LUMINAIRE SYMBOLS SHOWN ARE GENERIC GRAPHIC REPRESENTATIONS. REFER TO
LUMINAIRE SCHEDULE FOR SPECIFIC SOURCE, TYPE AND MOUNTING.
J CONDUIT AND WIREWAY ROUTING IS SCHEMATIC. FIELD ROUTE.
K ELECTRICAL CONTRACTOR SHALL PROVIDE (FURNISH AND INSTALL) ALL ELECTRICAL
COMPONENTS, SUPPORT AND TERMINATIONS UNLESS NOTED OTHERWISE.
L ELECTRICAL CONTRACTOR SHALL MAINTAIN UPDATED PANEL SCHEDULES DURING
PROJECT AND PROVIDE FINAL TYPE WRITTEN SCHEDULES AT END OF PROJECT TO
ENGINEER AND PLACE COPY IN POWER PANEL.
M CONTRACTOR SHALL WALK PROJECT AREA PRIOR TO BID. TIME AND MATERIALS
REQUIRED DUE TO DIFFICULTY OF ROUTING AND IMPACTS TO BUILDING CONSTRUCTION
THAT ARE VISIBLE AT TIME OF WALK SHALL BE INCLUDED IN FINAL BID SUBMISSION.
AREAS THAT CAN NOT BE VIEWED AT TIME OF BID SHALL BE SPECIFICALLY NOTED AND
EXCLUDED IN BID FOR CONSTRUCTION IN AWARD PROCESS.
N COORDINATE EQUIPMENT/ DEVICE LOCATIONS WITH ARCHITECTURAL DRAWINGS.
P DEMOLITION SHALL INCLUDE REMOVAL OF CONDUIT, WIRE, BOXES AND HANGER
SUPPORT BACK TO SOURCE.
Q LIQUID LEAK DETECTION SYSTEM IS NOT PART OF THIS PROJECT. SYSTEM
INSTALLATION IS A DESIGN/ BUILD PROJECT DIRECTED BY THE OWNER.
R ALL BREAKERS INSTALLED SHALL BE RATED PER A.I.C RATING OF SYSTEM.
S ALL INTERCONNECTION CABLES WILL BE PROVIDED BY VENDOR, EXCEPT AS NOTED.
CONTRACTOR TO VERIFY INSTALLATION REQUIREMENTS.
T CONTRACTOR SHALL VERIFY ALL EQUIPMENT SUPPLIED FROM FACILITY POWER
SERVICE IS FED VIA A LOCKABLE BREAKER OR SWITCH, SIZED PER N.E.C. PROVIDE AS
REQUIRED.
U ROUTE GROUNDING CABLE TO NEAREST GROUND PAD.
V CONTRACTOR SHALL PROVIDE GROUNDING PER N.E.C. AND MANUFACTURER'S
REQUIREMENTS. REFER TO TOOL MANUAL AND VERIFY WITH EQUIPMENT SUPPLIER.
W REFERENCE FACILITY DATA MATRIX FOR POWER SOURCE DETAILS.
X CIRCUIT RACEWAYS MAY BE COMBINED. ADJUST CONDUCTOR SIZE AS NEEDED FOR
DERATING.
Y TRANSITION TO LIQUID-TITE FLEXIBLE CONDUIT AT TERMINATION TO EQUIPMENT TO
MINIMIZE VIBRATION TRANSMISSION.
Z CONTROLS SCOPE IS DESIGN-BUILD BY THE CONTROLS CONTRACTOR. DESIGN AND
INSTALLATION SHALL BE IN ACCORDANCE WITH DRAWINGS, SPECIFICATIONS AND
BUILDING CODES.
SPECIAL NOTE:
1 INTEGRATED EQUIPMENT RATING (IER) REFERS TO THE SHORT CIRCUIT RATING OF THE
ELECTRICAL COMPONENT THAT HAS THE LOWEST SHORT CIRCUIT RATING.
DH
FC
FS
TS
TC
F
CIRCUITRY AND RACEWAYS
OUTLETS
CONDUIT UP
CONDUIT DOWN
CONDUIT, CAP AND STAKE
HOME RUN (WITH CIRCUIT NUMBERS)
END OF CONDUIT RUN
"RUN CONTINUES" INDICATION
UNDERGROUND CONDUIT
1#12 GROUND
1#12 GROUND, ISOLATED
1#12 AWG HOT
1#12 AWG NEUTRAL
3#10 AWG CONDUCTORS (1 HOT, 1 NEUTRAL, 1 GROUND)
SWITCHED CONDUCTOR
WIREMOLD WITH RECEPTACLES AS NOTED
SERVICE AND EQUIPMENT
TRANSFORMER (KVA SHOWN)
PANELBOARD, FLUSH MOUNTED
PANELBOARD, SURFACE MOUNTED
UTILITY METER, AS REQUIRED
GROUND
CIRCUIT BREAKER, THERMAL MAGNETIC OR SOLID
TELEPHONE TERMINAL BOARD
CT
TTB
D
FACP
ANN
X
WALL MOUNTED STROBE ONLY, CANDELA AS NOTEDX
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
FIXTURES
MECHANICAL
SWITCHES
EBBH
MOTOR AND CONNECTION, HP AS NOTED
CEILING EXHAUST FAN
WALL TYPE EXHAUST FAN, HP AS NOTED
PIPE HEAT TRACE
ELECTRIC UNIT HEATER
ELECTRIC BASEBOARD HEATER
ELECTRIC TOEKICK HEATER
WATER HEATER
TELE/DATA
WH
PC
F a
P
LV
L
D
FD
K
WP
T
OC
WALL MOUNTED FIXTURE
VARIABLE FREQUENCY DRIVE WITH DISCONNECTVFD
M
T
H
H
#10
F
X
KVA?
#e
#l
EMERGENCY POWER OFF PUSHBUTTONEPO
S INTERCOM SPEAKER IN CEILING
SECURITY CAMERA (PAN, TILT, ZOOM)
SECURITY AND MISCELLANEOUS
SECURITY DEVICE:XX
GLASS BREAK MONITOR
CALL BUTTON
CARD READER
DOOR STATUS SWITCH
GB
CB
CR
DS
S INTERCOM SPEAKER, WALL MOUNTED
CCTV
P,T,Z
CEILING MOUNTED RECEPTACLES
120 SMOKE DETECTOR, 120V; P = PHOTOELECTRIC, PCM = COMBINATION
PHOTOELECTRIC CARBON MONOXIDE
WIRELESS ACCESS POINTWAP
ELECTRIC DOOR STRIKE
KEY PAD
LOG IN/LOG OUT
ES
KP
LILO
LOCAL DOOR ALARMLA
M MAG CONTACTOR, COIL OR CONTACT
MAX MAXIMUM
MBS MAINTENANCE BYPASS SWITCH
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCCB MOLDED CASE CIRCUIT BREAKER
MCP MOTOR CIRCUIT PROTECTOR
MDC MOTORIZED DAMPER CONTROL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY MECHANICAL
MMP MECHANICAL MOUNTING PANEL
MO MOTOR OPERATOR
MS MOTOR STARTER
MSP MOTOR STARTER PANEL
MT,MTD MOUNTED
(N) NEW
N NEUTRAL
NA NON-AUTOMATIC
N.C. NORMALLY CLOSED
N.E. NORTH EAST
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
N.O. NORMALLY OPEN
NP NAMEPLATE
NTS NOT TO SCALE
N.W. NORTH WEST
OCB 115KV OIL CIRCUIT BREAKER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OL OVERLOAD RELAY
OO OVERLOAD
OOA ON-OFF-AUTO
OOR ON-OFF-REMOTE
OPD OPEN POLE DETECTOR
P POWER
PF POWER FACTOR
PL PILOT LIGHT
PB PUSHBUTTON SWITCH
PC PHOTOCELL
PCP PLANT CONTROL PANEL
PIN PERSONAL ID NUMBER
PIV POST INDICATOR VALVE
PNL PANEL
PQ POWER QUALITY
Ø, PH PHASE
PVC POLYVINYL CHLORIDE
QTY QUANTITY
R RATE OF RISE, RIGHT
(R) RELOCATE
RCPT RECEPTACLE
RCY RACEWAY
(RD) REDUNDANT
RF RADIO FREQUENCY
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RQD REQUIRED
RTM RUNNING TIME METER
RVNR REDUCED VOLTAGE NON-REVERSING
RVR REVERSING
S SPEAKER
S.C. SHORT CIRCUIT
SCP SECURITY CONTROL PANEL
S.E. SOUTH EAST
SEC SECONDS
SES SERVICE ENTRANCE SUBSTATION
SFEP SMOKE/FUME EXHAUST PANEL
SO SWITCH OPERATOR
SOL SLOW SPEED OL RELAY
SP SPARE
SS STAINLESS STEEL
ST SHUNT TRIP
STC SOURCE TRANSFER CONTROL
STD STANDARD
SUPP SUPPRESSOR
SUR SURFACE
SW SWITCH
S.W. SOUTH WEST
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMMETRICAL
SYNC SYNCHRONIZER
2S1W TWO SPEED, ONE WINDING
2S2W TWO SPEED, TWO WINDING
T TEMPORARY
TSTAT THERMOSTAT
TB TERMINAL BLOCK
TBD TO BE DETERMINED
TC TIME CLOCK
TDR TIME DELAY RELAY
TJB TERMINAL JUNCTION BOX
TS TAMPER SWITCH
TSP TWISTED SHIELDED PAIR
TYP TYPICAL
U UNDERGROUND
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTMETER, VOLT
VA VOLT-AMPERE
VESDA VERY EARLY SMOKE DETECTION APPARATUS
VFD VARIABLE FREQUENCY DRIVE
VIB VERTICAL INSIDE BEND
VLF VERTICAL LAMINAR FLOW UNIT
VOB VERTICAL OUTSIDE BEND
VP VAPOR PROOF
VS VOLTMETER SWITCH
VT VOLTAGE TRANSFORMER
W WATT, WIRE
WHD WATTHOUR DEMAND
WP WEATHERPROOF
XFMR TRANSFORMER
Y WYE-CONNECTED
Z IMPEDANCE
ZSD UNBALANCED IMPEDANCE DETECTOR
A, AMP AMMETER, AMPERE
AB ABSOLUTE
AC ALTERNATING CURRENT
ACB AIR CIRCUIT BREAKER
AF AMPERE FRAME
AFD ADJUSTABLE FREQUENCY DRIVE
AFF ABOVE FINISHED FLOOR
AIC AMPS INTERRUPTING CURRENT
ANN ANNUNCIATOR
ARF ABOVE RAISED FLOOR
AS AMMETER SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
ATX AUTO TRANSFORMER
AWG AMERICAN WIRE GAUGE
B BELL
BC BARE COPPER
BFF BELOW FINISHED FLOOR
BG BULK GAS
BKR BREAKER
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BOC BOTTOM OF CONDUIT
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BOT BOTTOM OF TRAY
BRN BUS REFERENCE NO. (ENGINEERING STUDY USE)
BT BASIC TRANSPONDER
C CONDUIT, COIL
CAP. CAPACITOR
CAT. # CATALOG NUMBER
CB CIRCUIT BREAKER
CC CONTROL CABLE
CCTV CLOSED CIRCUIT TELEVISION
CCT, CKT CIRCUIT
CLK CLOCK
CO CONDUIT ONLY
CONT CONTINUED
CPT CONTROL POWER TRANSFORMER
CR CORROSION RESISTANT
CRE CORROSION RESISTANT
CRS COATED RIGID STEEL CONDUIT
CRWP CLEANROOM WALL PANEL
CSFD COMBINATION SMOKE, FIRE DAMPER
CT CURRENT TRANSFORMER
(D) DEMOLISH
D DUCT
DB DUCT BANK
DC DIRECT CURRENT
DDC DIRECT DIGITAL CONTROL
DIA DIAMETER
DIV DIVISION
DWG DRAWING
Δ DELTA CONNECTED
E EMPTY
(E), EX EXISTING
ECS EMERGENCY COMMAND STATION
EDF ELECTRIC DRINKING FOUNTAIN
EEW ENERGIZED ELECTRICAL WORK
EG ENGINE GENERATOR
EL ELECTRICAL EMERGENCY
ELEC ELECTRICAL
EM, EMER EMERGENCY
EMH ELECTRICAL MANHOLE
EPO EMERGENCY POWER OFF
EMT ELECTRICAL METALLIC TUBING
ENT ELECTRICAL NON-METALLIC TUBING
EOL END-OF-LINE DEVICE
ERT EMERGENCY RESPONSE TEAM
ESD ELECTROSTATIC DISCHARGE
ESES EMERGENCY SERVICE ENTRANCE SUBSTATION
ET EXPANDED TRANSPONDER
ETM ELAPSED TIME METER
EWC ELECTRIC WATER COOLER
F FLUSH
(F) FUTURE
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FBO FURNISHED BY OTHERS
FCS FACILITY CONTROL SYSTEM
FDR FEEDER
FLR FLOOR
FOL FAST ACTING OL RELAY
FU FUSE
FWS FIRE WATER STORAGE
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
GND GROUND
GEN GENERAL
GFC GROUND FAULT CIRCUIT INTERRUPTER
GFR GROUND FAULT RELAY
GSM GAS SAFETY MONITOR
H HORN
HH HANDHOLE
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HVAC HEATING, VENTILATING & AIR CONDITIONING
HB HORIZONTAL BEND
HP HORSEPOWER
ICCB INSULATED CASE CIRCUIT BREAKER
I.D. IDENTIFICATION
IER INTEGRATED EQUIPMENT RATING
I&C INSTRUMENTATION AND CONTROL
IMC INTERMEDIATE METALLIC CONDUIT
I/O INPUT/OUTPUT
IS CURRENT SWITCH
J, JB JUNCTION BOX
K KEY INTERLOCK
KCMIL 1000 CIRCULAR MIL
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVAR
KW KILOWATT
KWH KILOWATT HOUR
L LEFT
LAN LOCAL AREA NETWORK
LC LIGHTING CONTACTOR
LTG LIGHTING
LV LOW VOLTAGE
LVR LOW VOLTAGE RELAY
COMM. KITCHEN
115A
CO
UNIT STORAGE
VAULT
CLASSROOM
MEN'S LOCKER
WOMEN'S LOCKER
VEST.
MEN'S
JANIT.
VEST.
WOMEN'S
MECH
RECRUITER
VESTIBULE
GEAR STORAGE
VEST
LACT.
FITNESS
AOT OFFICE
ASSEMBLY
FAMILY
1 SGT
IDF
VEST.
106B
ADMIN
102A
LOBBY
26x10
16x10
36x10
36x10
28x12 x1
"ø x1
14x12 12x10
12x6
12x6
12x6
6" ø
6" ø
"ø
"ø
8"ø
8"ø
"ø
6" ø
T
8" ø
TO FC-1
AND FC-2
TO FC-4
TO FC-5
16x10
10"ø
6x6
12x8
6x6 - S1
12x8
12x8
12x6
225 (TYP. 2)
12x6
12x6
12x6
12x6
32x12 x1
42x12
10"ø
24x12 26x14 x1
6x6
"ø
48x24
22"ø
14x10
38x38 x1
24x16
12x6
200 (TYP. 3)
24x10
12x8
18x10 x1
12x10 12x10
12x10
10"ø
12x6
22x10 - T1
12x6
250 (TYP. 5)
12x12
10x10
8x8
6x6
6x6
"ø
10x10
10x10
8x8
12x12
"ø
8" ø
26x10
8" ø
10"ø x1
10x6
130 (TYP. 3)
22x10
22x10
18x10
10"ø x6
16x16
22x10 - T1
RANGE HOOD
PROVIDED BY
OTHERS.
42x24
12x6
12x6
12x6
12x6
22x22
12x18
22x10
"ø
12x6 - E1
6x6
4" ø
18x12
4"ø
(TYP. 2)
x1
22x10
20x10 x1
38x16 14x10
18x30 x1
"ø
6" UP TO ROOF
A
145 36 278
B
C
D
E
F
22"ø
"ø
"ø
18x6 - S3
300 (TYP. 16)
22"ø
"ø
"ø
DUCT BLANK OFF AT
SHOWN LOCATION.
DUCT BLANK OFF AT
SHOWN LOCATION.
D
AT
E D
ES
C
R
IP
TI
O
N R
EV
Sheet Number:
Proj No:
Sheet Title:
AP
PR
C
LI
EN
T:
PR
O
JE
C
T:
M
IL
TO
N -F
R
EE
W
AT
ER
A
R M
O R
Y
ENGINEER STAMP
KEEP AREA CLEAR FOR AHJ
APPROVAL STAMP
M
IL
TO
N
-F R
EE
W
AT
ER
, O R
EG
O
N
SO
U
TH
M
AI
N
S
TR
EE
T
O R
EG
O
N M
IL
IT
AR
Y
D
EP
AR
TM
EN
T
R
EQ
U
ES
T
FO
R P
R O
PO
SA
L
CC22065
ME101
MECHANICAL/
ELECTRICAL
LEVEL 1
DEMOLITION PLAN
A
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 1/
JL
S
B
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 5/
JL
S
ME101
MECHANICA/ELECTRICAL LEVEL 1 DEMOLITION PLAN
NO
RT
H
0 16842
BAR SCALE
SCALE:
WHEN PRINTED ON SHEET
1/8" = 1'-0" 22"x34"
GENERAL NOTES
A SEE SHEET M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS,
AND GENERAL NOTES.
B SEE SHEET E-001 ELECTRICAL LEGEND, ABBREVIATIONS, &
GENERAL NOTES.
C PURGE ALL REFRIGERANT FROM VRF AND MINI-SPLIT SYSTEMS
AND DISPOSE IN ACCORDANCE WITH FEDERAL AND STATE LAWS.
D DEMOLISH EXISTING THERMOSTATS/SENSORS AND WIRING
BACK TO THE FAN COIL.
KEYED NOTES
1 REMOVE DISCONNECT AND CONDUIT BACK TO WALL. REMOVE
CONDUCTORS BACK TO THE PANEL.
2 DEMOLISH REFRIGERANT LINES BACK TO DISTRIBUTION BOXES.
DISCONNECT ELECTRICAL. MAINTAIN CONDENSATE PUMPS FOR
REUSE.
3 DEMOLISH DISTRIBUTION BOXES. DEMOLISH REFRIGERANT
PIPING TO VRF HEATPUMP UNITS ON THE ROOF. REMOVE
DISCONNECT, CONDUCTORS AND CONDUCTORS BACK TO THE
PANEL.
4 DEMOLISH EXHAUST FAN, DISCONNECT, CONDUIT AND
CONDUCTORS BACK TO THE PANEL.
5 DEMOLISH INDOOR DUCTLESS WALL UNIT. MAINTAIN CONDUIT
FOR POWER FEED TO THE ROOF. MAINTAIN REFRIGERANT
PIPING TO THE ROOF.
LEGEND
ITEMS TO BE DEMOLISHED
FC-5
5 3
FC-2
FC-1
DH-41
DH-21 DH-11
EF-3
FC-32
EF-1
FC-4
22'-5 5/8" 18'-11 5/8" 18'-0 1/4" 18'-0" 18'-0" 18'-4 1/2" 22'-10"
'-3
'-6
/2
'-3
'-4
'-1
DH-3 1
12x32 12x34 x1 x2
20x20
KITCHEN EXHAUST FAN
6" GOOSENECK
A
145 36 278
B
C
D
E
F
D
AT
E D
ES
C
R
IP
TI
O
N R
EV
Sheet Number:
Proj No:
Sheet Title:
AP
PR
C
LI
EN
T:
PR
O
JE
C
T:
M
IL
TO
N -F
R
EE
W
AT
ER
A
R M
O R
Y
ENGINEER STAMP
KEEP AREA CLEAR FOR AHJ
APPROVAL STAMP
M
IL
TO
N
-F R
EE
W
AT
ER
, O R
EG
O
N
SO
U
TH
M
AI
N
S
TR
EE
T
O R
EG
O
N M
IL
IT
AR
Y
D
EP
AR
TM
EN
T
R
EQ
U
ES
T
FO
R P
R O
PO
SA
L
CC22065
ME102
MECHANICAL/
ELECTRICAL
ROOF
DEMOLITION PLAN
A
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 1/
JL
S
B
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 5/
JL
S
ME102
MECHANICA/ELECTRICAL ROOF DEMOLITION PLAN
NO
RT
H
0 16842
BAR SCALE
SCALE:
WHEN PRINTED ON SHEET
1/8" = 1'-0" 22"x34"
GENERAL NOTES
A SEE SHEET M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS,
AND GENERAL NOTES.
B SEE SHEET E-001 ELECTRICAL LEGEND, ABBREVIATIONS, &
GENERAL NOTES.
KEYED NOTES
1 REMOVE DISCONNECT FROM UNIT AND LEAVE FOR NEW
EQUIPMENT.
2 REMOVE DISCONNECT AND CONDUIT TO BELOW ROOF. REMOVE
CONDUCTORS BACK TO THE PANEL.
LEGEND
ITEMS TO BE DEMOLISHED
RTU-1
RTU-1
2 ERV-1
HP-1
NOT FOR CONSTRUCTION
SOLAR AND
SATELLITE AREA
COMM. KITCHEN
115A
CO
UNIT STORAGE
VAULT
CLASSROOM
MEN'S LOCKER
WOMEN'S LOCKER
VEST.
MEN'S
JANIT.
VEST.
WOMEN'S
MECH
RECRUITER
VESTIBULE
GEAR STORAGE
VEST
LACT.
FITNESS
AOT OFFICE
ASSEMBLY
FAMILY
1 SGT
IDF
VEST.
106B
ADMIN
102A
LOBBY
26x10
16x10
36x10
36x10
28x12 x1
"ø x1
14x12 12x10
12x6
12x6
12x6
6" ø
6" ø
"ø
"ø
8"ø
8"ø
"ø
6" ø
8" ø
TO FC-1
AND FC-2
TO FC-4
TO FC-5
16x10
10"ø
6x6
12x8
6x6 - S1
12x8
12x8
12x6
225 (TYP. 2)
12x6
12x6
12x6
12x6
32x12 x1
24x12 26x14
6x6
"ø
48x24
22"ø
14x10
38x38
12x6
200 (TYP. 3)
24x10
12x8
18x10 x1
12x10 12x10
12x10
10"ø
12x6
22x10 - T1
12x6
250 (TYP. 5)
12x12
10x10
8x8
6x6
6x6
"ø
10x10
10x10
8x8
12x12
"ø
8" ø8" ø
10"ø x1
10x6
130 (TYP. 3)
22x10
22x10
18x10
10"ø x6
16x16
22x10 - T1
RANGE HOOD
PROVIDED BY
OTHERS.
42x24
12x6
12x6
12x6
12x6
22x22
12x18
22x10
"ø
12x6 - E1
6x6
4" ø
18x12
4"ø
(TYP. 2)
x1
22x10
14x10
18x30 x1
"ø
6" UP TO ROOF
A
145 36 278
B
C
D
E
F
22"ø
"ø
"ø
18x6 - S3
300 (TYP. 16)
22"ø
"ø
"ø
DUCT BLANK OFF AT
SHOWN LOCATION.
DUCT BLANK OFF AT
SHOWN LOCATION.
D
AT
E D
ES
C
R
IP
TI
O
N R
EV
Sheet Number:
Proj No:
Sheet Title:
AP
PR
C
LI
EN
T:
PR
O
JE
C
T:
M
IL
TO
N -F
R
EE
W
AT
ER
A
R M
O R
Y
ENGINEER STAMP
KEEP AREA CLEAR FOR AHJ
APPROVAL STAMP
M
IL
TO
N
-F R
EE
W
AT
ER
, O R
EG
O
N
SO
U
TH
M
AI
N
S
TR
EE
T
O R
EG
O
N M
IL
IT
AR
Y
D
EP
AR
TM
EN
T
R
EQ
U
ES
T
FO
R P
R O
PO
SA
L
CC22065
ME111
MECHANICAL/
ELECTRICAL
LEVEL 1 PLAN
A
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 1/
JL
S
B
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 5/
JL
S
ME111
MECHANICA/ELECTRICAL LEVEL 1 PLAN
NO
RT
H
0 16842
BAR SCALE
SCALE:
WHEN PRINTED ON SHEET
1/8" = 1'-0" 22"x34"
GENERAL NOTES
A SEE SHEET M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS,
AND GENERAL NOTES.
B SEE SHEET E-001 ELECTRICAL LEGEND, ABBREVIATIONS, &
GENERAL NOTES.
C PURGE ALL REFRIGERANT FROM VRF AND MINI-SPLIT SYSTEMS
AND DISPOSE IN ACCORDANCE WITH FEDERAL AND STATE LAWS.
D DEMOLISH EXISTING THERMOSTATS/SENSORS AND WIRING
BACK TO THE FAN COIL.
KEYED NOTES
1 PROVIDE DUCT TRANSITIONS AND CONNECT TO EXISTING
DUCTWORK.
2 PROVIDE NEW COMBUSTION AIR AND VENT PER
MANUFACTURER'S RECOMMENDATION. REPLACE EXISTING
CONDENSATE PUMP. CONNECT NATURAL GAS WITH SHUT-OFF
VALVE AND REGULATOR.
3 CONNECT NEW DUCTLESS UNIT TO EXISTING POWER,
REFRIGERANT PIPING AND CONDENSATE PIPING.
4 PATCH DUCT WHERE THE ELECTRIC DUCT HEATERS WERE
REMOVED.
5 THIS MECHANICAL CLOSET WILL NEED TO BE EXPANDED TO
HOUSE THE NEW FURNACE.
6 COORDINATE WITH NATURAL GAS SUPPLIER TO REPLACE THE
EXISTING METER WITH A 2-LBS METER. PROVIDE A REGULATOR
TO STANDARD PRESSURE ON THE BRANCH PIPING SERVING THE
KITCHEN AND MECHANICAL ROOM 116.
7 PATCH AND PAINT WALL TO MATCH EXISTING.
8 DUCTWORK EXTENDS THOUGH ROOF DECK.
(E) EF-3
22'-5 5/8" 18'-11 5/8" 18'-0 1/4" 18'-0" 18'-0" 18'-4 1/2" 22'-10"
'-2
'-7
/2
'-3
'-4
'-1
F-3
F-3
F-1
CAP DUCT
12"Ø-OSA
1 2
28"x14"-SA
CFM
RG-1 12"x12"
RTU-3
CFM
RG-1 36"x18" 1,475
14"x12"-RA
28"x10"-RA
CFM
EG-1 12"x12"
38"x20"-RA
24"x20"-SA
7 7
4 4
DS-1b
NOT FOR CONSTRUCTION
1 2
AutoCAD SHX Text T
KITCHEN EXHAUST FAN
6" GOOSENECK
A
145 36 278
B
C
D
E
F
D
AT
E D
ES
C
R
IP
TI
O
N R
EV
Sheet Number:
Proj No:
Sheet Title:
AP
PR
C
LI
EN
T:
PR
O
JE
C
T:
M
IL
TO
N -F
R
EE
W
AT
ER
A
R M
O R
Y
ENGINEER STAMP
KEEP AREA CLEAR FOR AHJ
APPROVAL STAMP
M
IL
TO
N
-F R
EE
W
AT
ER
, O R
EG
O
N
SO
U
TH
M
AI
N
S
TR
EE
T
O R
EG
O
N M
IL
IT
AR
Y
D
EP
AR
TM
EN
T
R
EQ
U
ES
T
FO
R P
R O
PO
SA
L
CC22065
ME112
MECHANICAL/
ELECTRICAL
ROOF PLAN
A
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 1/
JL
S
B
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 5/
JL
S
ME112
MECHANICA/ELECTRICAL ROOF PLAN
NO
RT
H
0 16842
BAR SCALE
SCALE:
WHEN PRINTED ON SHEET
1/8" = 1'-0" 22"x34"
GENERAL NOTES
A SEE SHEET M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS,
AND GENERAL NOTES.
B SEE SHEET E-001 ELECTRICAL LEGEND, ABBREVIATIONS, &
GENERAL NOTES.
C STRUCTURAL ENGINEER TO PROVIDE ROOF FRAMING ANALYSIS
AND PROVIDE STRUCTURAL SUPPORT FOR THE NEW ROOF
MOUNTED UNITS. SEISMIC CONNECTION CALCULATIONS AND
ATTACHMENT DETAILS ARE ALSO TO BE PROVIDED.
KEYED NOTES
1 INSTALL UNIT AT EXISTING LOCATION. MOUNT EXISTING
DISCONNECT ON NEW EQUIPMENT.
2 EXTEND VTR TO 3' ABOVE THE NEW RTU OR RELOCATE 10' AWAY
FROM BOTH RTU INTAKES.
3 CONNECT NATURAL GAS TO UNITS WITH SHUT-OFF VALVES AND
PRESSURE REGULATORS.
4 NATURAL GAS PIPING DOWN THROUGH ROOF TO FURNACES
BELOW.
5 MOUNT CONDENSING UNITS ON 12" TALL ROOF CURBS.
6 PROVIDE NEW ELECTRICAL DISCONNECTS.
(E) RTU-1
22'-5 5/8" 18'-11 5/8" 18'-0 1/4" 18'-0" 18'-0" 18'-4 1/2" 22'-10"
'-2
'-7
/2
'-3
'-4
'-1
DS-1A
RTU-2
RTU-3
CU-1
CU-2
1"-NG
3/ 4"
-N G
CU-3
3/ 4"
-N G
1" -N
G
3/ 4"
-N G
1 1/2"-NG
HRV-1
10'-0"
'-9
VTR
EXISTING SOLAR
AND SATELLITE
AREA
NOT FOR CONSTRUCTION
4 5
6 6
E D
ES
C
R
IP
TI
O
N R
EV
Sheet Number:
Proj No:
Sheet Title:
AP
PR
C
LI
EN
T:
PR
O
JE
C
T:
M
IL
TO
N -F
R
EE
W
AT
ER
A
R M
O R
Y
ENGINEER STAMP
KEEP AREA CLEAR FOR AHJ
APPROVAL STAMP
M
IL
TO
N
-F R
EE
W
AT
ER
, O R
EG
O
N
SO
U
TH
M
AI
N
S
TR
EE
T
O R
EG
O
N M
IL
IT
AR
Y
D
EP
AR
TM
EN
T
R
EQ
U
ES
T
FO
R P
R O
PO
SA
L
CC22065
ME601
MECHANICAL/
ELECTRICAL
SCHEDULES
A
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 1/
JL
S
B
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 5/
JL
S
E D
ES
C
R
IP
TI
O
N R
EV
Sheet Number:
Proj No:
Sheet Title:
AP
PR
C
LI
EN
T:
PR
O
JE
C
T:
M
IL
TO
N -F
R
EE
W
AT
ER
A
R M
O R
Y
ENGINEER STAMP
KEEP AREA CLEAR FOR AHJ
APPROVAL STAMP
M
IL
TO
N
-F R
EE
W
AT
ER
, O R
EG
O
N
SO
U
TH
M
AI
N
S
TR
EE
T
O R
EG
O
N M
IL
IT
AR
Y
D
EP
AR
TM
EN
T
R
EQ
U
ES
T
FO
R P
R O
PO
SA
L
CC22065
ME602
MECHANICAL/
ELECTRICAL
SCHEDULES
A
R
FP
R
EV
IE
W D
R
AW
IN
G
S
/0 5/
JL
S
NOT FOR CONSTRUCTION
SERVICE ENTRANCE DISTRIBUTION BOARD 'MSB'
100A 3P
100A 3P
150A 3P
100A 3P
400A 3P
70A 3P
70A 3P
40A 3P
60A 3P
M
N E
L
ATS-EM1 (MER)
250A, 480Δ
G
100A
75 KW
BOND
MET.
C.W.
PIPE
GROUND
ROD
BOND
OTHER
METALLIC
PIPING
SUCH
AS
GAS
UTILITY
METER
UTILITY
TRANSFORMER
#3/0 CU
AVAILABLE FAULT CURRENT: 11,0004A
0A
SP
AC
E
0A
SP
AC
E
0A
SP
AC
E
0A
SP
AC
E
PANEL
L1
AFC:
9,889A
PANEL
P1
AFC:
9,889A
PANEL
P2
AFC:
10,117A
PANEL
P3
AFC:
3,200A
PANEL
M1
AFC:
10,508A
#8 CU
HP1-1 HP1-2 HP1-3
AFC: 293A AFC: 293A AFC: 293A
TVSS
LEAVE BREAKER
GENERAL NOTES
A SEE SHEET E-001 FOR LEGEND, ABBREVIATIONS, AND GENERAL
NOTES.
B
KEYED NOTES
1 REMOVE EXISTING BREAKER.
2 PROVIDE NEW BREAK. SIZE AS INDICATED.
REPLACE BREAKER, CONDUIT,
CONDUCTORS, AND
DISCONNECT FOR RTU-3
REPLACE BREAKER, CONDUIT,
CONDUCTORS, AND DISCONNECT
FOR RTU-2
ONE-LINE DIAGRAM
| Sheets and Views |
| 22065 G-001-Layout1 |
| 22065 M-001-Layout1 |
| 22065 E-001-Layout1 |
| 22065 ME101-Layout1 |
| 22065 ME102-Layout1 |
| 22065 ME111-Layout1 |
| 22065 ME112-Layout1 |
| 22065 ME601-Layout1 |
| 22065 ME602-Layout1 |
File details come from the government source that posted it. Updated .