22065 Milton-Freewater OMD 22-08-05.pdf

PDF 3 MB Posted

Attached to
39. 92 miles of chip seal along US730 & OR11
Solicitation number
S-73000-00005029
Issued by
Union County, Jacksonville City, Oregon

About this file

This document is a Request for Proposal (RFP) issued by the Oregon Military Department for mechanical and electrical system upgrades at the Milton-Freewater Armory located at 149 South Main Street, Milton-Freewater, Oregon 97862. The project involves design-build scope covering demolition of the existing Variable Refrigerant Flow (VRF) system and replacement with packaged rooftop equipment, condensing units, and furnaces. The RFP includes comprehensive mechanical and electrical drawings at 90% design completion dated August 5, 2022, showing Level 1 demolition and installation plans, roof plans, and equipment schedules. The project requires licensed Oregon engineers to prepare and seal all drawings, with contractors responsible for permitting and associated fees. Key deliverables include mechanical system modifications (RTU-1, RTU-2, RTU-3, and condensing units CU-1, CU-2, CU-3), natural gas piping installation with shut-off valves and pressure regulators, combustion air and vent provisions, condensate pump replacement, ductwork transitions, and electrical system upgrades including new disconnects and panel modifications. The mechanical schedule indicates basis of design performance specifications for equipment, with acceptable alternates required to perform within ±5% of scheduled values. Control systems will be contracted separately through the Oregon Military Department's control vendor, with packaged rooftop equipment required to include BACnet-compatible controllers.

The project involves structural engineering support for roof-mounted equipment with seismic connection calculations and attachment details, and requires coordination with the natural gas utility for meter replacement and regulator installation. Contractors must provide operation and maintenance manuals to the building owner within 90 days of system acceptance per ASHRAE Standard 90.1, including submittal data, service agency information, and controls system maintenance and calibration details. HVAC systems must be balanced in accordance with generally accepted engineering standards, with written balance reports provided for systems serving conditioned areas exceeding 5,000 square feet. All work shall comply with applicable local, county, state, and federal codes and regulations, including UL specifications for fire-safing and weather sealing at wall and floor penetrations, SMACNA standards for ductwork and piping support, and NFPA-13 for fire protection systems. The RFP emphasizes that drawings are diagrammatic in nature and indicate system concept rather than absolute precision, requiring contractors to provide all necessary components and materials for complete system operation and to verify locations, dimensions, and equipment placement prior to construction or material procurement.

View the file

Other files

File Type Posted
Invitation to Bid~8.pdf PDF
M21039_CON_SP_W_POR.pdf PDF
M21039_PSnEPlans_02.pdf PDF
GE_M21039_Memo_04.pdf PDF
Intent to Award Notice.pdf PDF
Bid Tabulation - Preliminary Results~1.pdf PDF
Addendum 1 - Special Provisions Modification.pdf PDF
Bid Pricing Form~13.xlsx XLSX spreadsheet

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

8 7 6 5 4 3 2 1

A

145 36 278

B

C

D

E

F

D

AT

E D

ES

C

R

IP

TI

O

N R

EV

Sheet Number:

Proj No:

Sheet Title:

AP

PR

C

LI

EN

T:

PR

O

JE

C

T:

M

IL

TO

N -F

R

EE

W

AT

ER

A

R M

O R

Y

ENGINEER STAMP

KEEP AREA CLEAR FOR AHJ

APPROVAL STAMP

M

IL

TO

N

-F R

EE

W

AT

ER

, O R

EG

O

N

SO

U

TH

M

AI

N

S

TR

EE

T

O R

EG

O

N M

IL

IT

AR

Y

D

EP

AR

TM

EN

T

R

EQ

U

ES

T

FO

R P

R O

PO

SA

L

VICINITY MAPOVERALL PLAN

NO

RT

H

N O

R

TH

OREGON MILITARY DEPARTMENT

MILTON-FREEWATER ARMORY REQUEST FOR PROPOSAL

149 South Main Street Milton-Freewater, Oregon 97862

SHEET NUMBER SHEET TITLE REV DATE

G-001 GENERAL TITLE SHEET B 08/05/22

M-001 MECHANICAL LEGEND, ABBREVIATIONS, & GENERAL NOTES B 08/05/22

E-001 ELECTRICAL LEGEND, ABBREVIATIONS, & GENERAL NOTES B 08/05/22

ME101 MECHANICAL/ELECTRICAL DEMOLITION LEVEL 1 PLAN B 08/05/22

ME102 MECHANICAL/ELECTRICAL DEMOLITION ROOF PLAN B 08/05/22

ME111 MECHANICAL/ELECTRICAL LEVEL 1 PLAN B 08/05/22

ME112 MECHANICAL/ELECTRICAL ROOF PLAN B 08/05/22

ME601 MECHANICAL/ELECTRICAL SCHEDULES B 08/05/22

ME602 MECHANICAL/ELECTRICAL SCHEDULES A 08/05/22

PROJECT

AREAS

PROJECT

SITE

S C

O

LU

M

BI

A

STS MAIN ST

S

EL

IZ

AB

ET

H

S T

D E

H

AV

EN

S

T

SW 2ND AVE

E BROADWAY AVE

SE 2ND AVE

SE 1ST AVE

SE 3RD AVE

CC22065

G-001

GENERAL

TITLE

SHEET

A

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 1/

JL

S

B

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 5/

JL

S

GENERAL NOTES

A OMD IS REQUESTING THAT THE EXISTING VRF SYSTEM TO BE DEMOLISH AND REPLACED

WITH PACKAGED ROOFTOP EQUIPMENT, CONDENSING UNITS, AND FURNACES.

B THESE DRAWINGS ARE TO PROVIDE DIRECTION AND PROJECT INTENT.

C THIS PROJECT WILL BE DESIGN/BUILD WITH MECHANICAL, ELECTRICAL, STRUCTURAL,

AND SLIGHT ARCHITECTURAL MODIFICATIONS. DRAWINGS ARE TO BE PREPARED AND

SEALED BY ENGINEERS LICENSED IN THE STATE OF OREGON.

D CONTRACTOR IS RESPONSIBLE FOR PERMITTING AND ALL ASSOCIATED FEES.

E MECHANICAL SCHEDULES SHOW BASIS OF DESIGN AND INCLUDE PERFORMANCE FOR

THAT SIZE MODEL. IF USING ALTERNATE APPROVED MANUFACTURERS, PERFORMANCE

SHOULD BE WITHIN +/-5% OF SCHEDULED VALUES.

F CONTROLS WILL BE CONTRACTED SEPARATELY THROUGH OMD'S CONTROL VENDOR.

UNIT CONTROLS FOR FURNACES AND CONDENSING UNITS WILL USE STANDARD

TERMINAL STRIPS. PACKAGED ROOFTOP EQUIPMENT IS TO INCLUDE BACNET

COMPATIBLE CONTROLLERS.

G AUTOCAD FILES OF THE EXISTING CONDITIONS ARE AVAILABLE FROM OMD.

H SEE WRITTEN REQUEST FOR PROPOSAL INSTRUCTIONS FOR OTHER DETAILS

NOT FOR CONSTRUCTION

AutoCAD SHX Text T

D

AT

E D

ES

C

R

IP

TI

O

N R

EV

Sheet Number:

Proj No:

Sheet Title:

AP

PR

C

LI

EN

T:

PR

O

JE

C

T:

M

IL

TO

N -F

R

EE

W

AT

ER

A

R M

O R

Y

ENGINEER STAMP

KEEP AREA CLEAR FOR AHJ

APPROVAL STAMP

M

IL

TO

N

-F R

EE

W

AT

ER

, O R

EG

O

N

SO

U

TH

M

AI

N

S

TR

EE

T

O R

EG

O

N M

IL

IT

AR

Y

D

EP

AR

TM

EN

T

R

EQ

U

ES

T

FO

R P

R O

PO

SA

L

CC22065

M-001

MECHANICAL

LEGEND,

ABBREVIATIONS,

& GENERAL NOTES

A

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 1/

JL

S

B

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 5/

JL

S

GENERAL NOTES

ABBREVIATIONS EQUIPMENT SYMBOLS

XX

XX

XX

XX

XX

GENERAL SYMBOLS

DUCTWORK SYMBOLS

GRILLE/REGISTER

S

BDD

FD

FSD

SD

12x9Ø

12Ø

12x9

SINGLE LINE

BDD

FSD

S

FIRE/SMOKE DAMPER

BACK DRAFT DAMPER

SMOKE DETECTOR

SD

FD

PHOTOHELIC

FIRE DAMPER

HAND/VOLUME DAMPER

BLAST GATE DAMPER

ACTUATED DAMPER

(UNIT CONTROLLED)

SIDEWALL SUPPLY REGISTER

ROOM THERMOSTAT, PENDENT MOUNT.

ROOM HUMIDISTAT

SMOKE DAMPER

SUPPLY DUCT

RADIUS ELBOW W/TURNING VANE

SQUARE ELBOW W/TURNING VANES

LONG RADIUS ELBOW

STANDARD RADIUS ELBOW

CROSS SECTION THRU ROUND DUCT

EXHAUST OR RETURN DUCT

12x9Ø

12x9

DOUBLE LINE

ROUND DUCT (INCHES)

DESCRIPTION

OVAL DUCT (INCHES)

FLEXIBLE CONNECTION

FLEXIBLE DUCT

RECTANGULAR DUCT, WIDTH x DEPTH (INCHES)

SIDEWALL EXHAUST REGISTER OR RETURN AIR

CEILING EXHAUST REGISTER OR RETURN AIR GRILLE

ASSUME 4-WAY THROW UNLESS OTHERWISE INDICATED

ROOM THERMOSTAT, PNEUMATIC OR ELECTRONIC

CEILING DIFFUSERS (ARROWS DENOTE THROW PATTERN)

SYMBOL DESCRIPTION

12Ø

= INTERNALLY LINED

SYMBOL DESCRIPTION

(UNIT CONTROLLED)

PIPE DESIGNATIONS

ACCEPTABLE METHOD

MULTI-LINE DESIGNATION

PREFERRED METHOD

2"-HWS

= INTERNALLY LINED

ANNOTATION SYMBOLS

FLOW ARROWS

NORTH ARROW

DETAIL SYMBOL

DETAIL NUMBER

ELEVATION SYMBOL

ELEVATION LETTER

XX KEYED NOTE

EQUIPMENT TAG

REVISION TRIANGLE

DRAWING NUMBER WHERE DETAIL APPEARS

DIFFERENTIAL PRESSURE SENSOR

NEW

STATIC PRESSURE SENSOR

EXISTING TO BE REMOVED

SHUT DOWN

CONNECT TO EXISTING

EXISTING TO REMAIN

FUTURE(F)

(E)

(N)

(D)

AIR OUTLET/INLET DESIGNATION

SPECIFICATIONS (TYP.)

(3-WAY SHOWN) RETURN OR EXHAUST

AIRFLOW, CFM (TYP.)

NECK SIZE, INCHES (TYP.)

FIXTURE IDENTIFICATION

EXAMPLE: SUPPLY (THROW DIRECTION)

FIXTURE IDENTIFICATION

ABBREVIATIONS TABLE

FIXTURE TYPE AS SHOWN IN

NO. IN SPECIFICATIONS

CD-1

EXAMPLE:

CFM

CD-1 18x18

800 CFM

RG-1 18x12

CFM

SG-3 24x18

X

XXX

XXX

DRAWING NUMBER WHERE ELEVATION APPEARS

XXX

XXX

XXX

XXX

SECTION CUT SYMBOL

SECTION LETTER

DRAWING NUMBER WHERE SECTION APPEARS

X

M M

(201)

(201)

T

H

T

S/D

DP

SP

FLOW STREAM DESIGNATION

XX

CENTRIFUGAL PUMP

SUBMERSIBLE PUMP

MULTISTAGE CENTRIFUGAL PUMP

VACUUM PUMP

LIQUID RING PUMP

SUMP PUMP

EXHAUST FAN

XX EQUALS:

AFD ADJUSTABLE FREQUENCY DRIVE

CS-1 CONSTANT SPEED - SINGLE SPEED MOTOR

CS-2 CONSTANT SPEED - TWO SPEED MOTOR

A THIS IS A GENERAL LEGEND PAGE, NOT ALL ITEMS ON THIS SHEET WILL BE USED.

B ALL WORK SHALL CONFORM TO ALL APPLICABLE LOCAL, COUNTY, STATE AND FEDERAL CODES AND

REGULATIONS AND OWNER'S STANDARDS.

C DRAWINGS ARE DIAGRAMMATIC. DRAWINGS ARE NOT INTENDED TO BE ABSOLUTELY PRECISE, AND DO NOT SPECIFY OR SHOW EVERY OFFSET, FITTING AND COMPONENT. THE PURPOSE OF THE DRAWINGS IS TO INDICATE A SYSTEM CONCEPT, THE MAIN COMPONENTS OF THE SYSTEMS, AND THE APPROXIMATE GEOMETRICAL RELATIONSHIPS. BASED ON THE SYSTEMS CONCEPT, THE MAIN COMPONENTS AND THE

GEOMETRICAL RELATIONSHIPS THE CONTRACTOR SHALL PROVIDE ALL OTHER COMPONENTS AND

MATERIALS NECESSARY TO MAKE THE SYSTEM FULLY COMPLETE AND OPERATIONS. CONTRACTOR

SHALL ROUTE PIPING OR PROVIDE OFFSETS TO AVOID INTERFERENCE WITH STRUCTURAL ELEMENTS, ELECTRICAL PANELS AND JUNCTION BOXES ETC. VERIFY LOCATIONS, DIMENSIONS, EXISTING FLOW DIRECTIONS, ETC. BEFORE CONSTRUCTION. FIELD VERIFY ALL SIZES, DIMENSIONS AND EQUIPMENT

LOCATIONS PRIOR TO CONSTRUCTION OR MATERIAL PROCUREMENT.

D REPAIR AND PATCH ALL (NEW AND EXISTING) WALL AND FLOOR PENETRATIONS TO MATCH EXISTING

FINISH. PROVIDE SLEEVES AND SEAL ALL PENETRATIONS OF FIRE RATED WALLS/ FLOORS IN

ACCORDANCE WITH UL SPECIFICATIONS, WITH 3M AND/ OR HILTI FIRE STOPPING MATERIALS APPROVED

FOR THE PURPOSE. PROVIDE FIRE DAMPERS WHERE DUCTS PENETRATE FIRE RATED WALLS OR

FLOORS.

E IN ADDITION TO FIRE-SAFING AND WEATHER SEALING REQUIREMENTS, PROVIDE CHROME ESCUTCHEON

RINGS WHERE DUCTS AND PIPES PENETRATE THE FINISHED SIDE OF WALLS AND CEILINGS.

F ALL EXTERIOR WALL PENETRATIONS SHALL BE FLASHED AND SEALED WEATHER-TIGHT AND TO A

STRUCTURALLY SOUND CONDITIONS.

G PROVIDE SUPPORT AND LATERAL BRACING FOR ALL DUCTWORK, PIPING AND EQUIPMENT IN

ACCORDANCE WITH SMACNA AND BUILDING CODES. CONTRACTOR SHALL DESIGN AND PROVIDE

CALCULATIONS AND SKETCHES AS REQUIRED BY THE LOCAL BUILDING DEPARTMENT.

H PROVIDE VOLUME DAMPERS AT NEW AND EXISTING SUPPLY AND EXHAUST DUCT BRANCHES.

J FIRE PROTECTION SCOPE IS A DESIGN-BUILD PROJECT BY THE FIRE PROTECTION CONTRACTOR.

SPRINKLER DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA-13 AND THE BUILDING

CODES.

K CONTRACTOR SHALL PROVIDE O&M MANUALS TO THE BUILDING OWNER FOR ALL PROVIDED EQUIPMENT WITHIN 90 DAYS OF SYSTEM ACCEPTANCE PER ASHRAE STANDARD 90.1 AND IN ACCORDANCE WITH

INDUSTRY ACCEPTED STANDARDS. MANUALS SHALL INCLUDE SUBMITTAL DATA, O&M MANUALS,

SERVICE AGENCY, CONTROLS SYSTEM MAINTENANCE AND CALIBRATION INFORMATION, AND A

NARRATIVE OF HOW EACH SYSTEM IS INTENDED TO OPERATE.

L HVAC SYSTEMS SHALL BE BALANCED IN ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING STANDARDS. CONTRACTOR SHALL PROVIDE A WRITTEN BALANCE REPORT TO THE BUILDING OWNER FOR HVAC SYSTEMS SERVING ZONES WITH A TOTAL CONDITIONED AREA EXCEEDING 5,000 SQFT PER ASHRAE

STANDARD 90.1.

XX

NORTH

EQUIPMENT TAGXXX-X

3"-HWS

3"-HWR

2"-CHWS

2"-CHWR

ACCEPTABLE METHOD

PIPING IDENTIFIED FROM

LEFT TO RIGHT OR TOP

TO BOTTOM

2"-HWS

CW

CHWR

CHWS

LPS

ICW

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CITY WATER

LOW PRESSURE STEAM

INDUSTRIAL COLD WATER

NON POTABLE WATERNPW

HEATING WATER RETURNHWR

HEATING WATER SUPPLYHWS

COND CONDENSATE DRAIN

ABV ABOVE

AC ACTIVATED CARBON FILTER OR

ALTERNATING CURRENT

ACC AIR COOLED CHILLER

ACFM ACTUAL CUBIC FEET/MINUTE

ACU AIR CONDITIONING UNIT

AD ACCESS DOOR

AFD ADJUSTABLE FREQUENCY DRIVE

AFF ABOVE FINISHED FLOOR

AH AIR HANDLER, GENERAL

AHU AIR HANDLING UNIT

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

AMP AMPERE (AMP,AMPS)

ARF ABOVE RAISED FLOOR

BDD BACK DRAFT DAMPER

BF BUTTERFLY VALVE

BHP BRAKE HORSEPOWER

BLO BLOWER

BLR BOILER

BOD BOTTOM OF DUCT

BOP BOTTOM OF PIPE

BOT BOTTOM OF TRAY

BOTT BOTTOM

BOM BILL OF MATERIAL

BTU BRITISH THERMAL UNIT

C CENTIGRADE OR COMPRESSOR

CA COMPRESSED AIR

CC COOLING COIL

CD CEILING DIFFUSER

CFM CUBIC FEET PER MINUTE

CH CHILLER

CKT CIRCUIT

CLP COIL PUMP

CO CLEANOUT

CONN CONNECTION

CPLG COUPLING

CRU CONDENSATE RETURN UNIT

CSST CORRUGATED STAINLESS STEEL TUBING

CT COOLING TOWER

CTG CLEANOUT TO GRADE

CU CONDENSATE UNIT

CV CONSTANT VOLUME TERMINAL UNIT

CVR ONSTANT VOLUME REHEAT TERMINAL UNIT

dB DECIBEL

(D) DEMOLISH

DB DRY BULB

DBT DRY BULB TEMPERATURE

DC DIRECT CURRENT

DDC DIRECT DIGITAL CONTROL

DEH DEHUMIDIFIER

DER DEAERATOR

DF DRINKING FOUNTAIN

DIA DIAMETER

DN DOWN

(E) EXISTING

EA EACH

EA EXHAUST AIR

EF EXHAUST FAN

EFF EFFICIENCY

ELEV ELEVATION

EPO EMERGENCY POWER OFF

ET EXPANSION TANK

EWC ELECTRIC WATER COOLER

EXH EXHAUST, GENERAL

(F) FUTURE

F FAHRENHEIT

FCU FAN COIL UNIT

FCO FLOOR CLEANOUT

FD FLOOR DRAIN

FF FINISHED FLOOR

FFE FINISHED FLOOR ELEV

FFU FAN FILTER UNIT

FL CARTRIDGE OR BAG FILTER

FLT FILTER

FN FAN

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

FP FAN POWERED TERMINAL UNIT

FPM FEET PER MINUTE

FPS FEET PER SECOND

FT FOOT OR FEET

GA GAGE OR GAUGE, OR GENERAL AIR

GAL GALLONS

GCO GRADE CLEANOUT

GEN GENERATOR

GD GROUND DIFFUSER

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

HC HEATING COIL

HD HEAD

HE HEAT EXHAUST

HG MERCURY

HOR HORIZONTAL

HP HORSEPOWER

HR HOUR(S)

HU HUMIDIFIER

HX HEAT EXCHANGER

HYD HYDRAULIC

HZ HERTZ (FREQUENCY)

ID INSIDE DIAMETERIE INVERT ELEVATION

KW KILOWATT

KWH KILOWATT HOUR

KVA KILOVOLT-AMPERE

LAV LAVATORY

LBS POUNDS

LD LEAK DETECTION

LPD LOW POINT DRAIN

(M) MECHANICAL

MAH MAKEUP AIR HANDLER

MAX MAXIMUM

MCC MOTOR CONTROL CENTER

MIN MINIMUM

MISC MISCELLANEOUS

MM MULTI-MEDIA FILTER

MOT MOTOR

MP METERING PUMP

MUA MAKEUP AIR

(N) NEW

N/A NOT APPLICABLE

NC NOISE CRITERIA OR NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OA OUTSIDE AIR

OBD OPPOSABLE BLADE DAMPER

OD OUTSIDE DIAMETER

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

OL OVERLOAD RELAY

OSA OUTSIDE SUPPLY AIR

OZ OUNCE

PD PRESSURE DROP

PH PHASE

PIV POST INDICATOR VALVE

PL PLUG VALVE

POC POINT OF CONNECTION

PPM PARTS PER MILLION

PSI POUNDS PER SQUARE INCH

PSIA PSI, ABSOLUTE

PSIG PSI, GAUGE

QT QUART

QTY QUANTITY

(R) RELOCATE

RA RETURN AIR

RAH RECIRC. AIR HANDLER

REQ REQUIRED

REV REVISION

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RM ROOM

RPM REVOLUTIONS PER MINUTE

RTU ROOF TOP UNIT

SA SUPPLY AIR

SC SCRUBBER

SCFM STANDARD CUBIC FEET/MINUTE

SD SUPPLY DIFFUSER

SEC SECOND

SG SUPPLY GRILLE

SLM STANDARD LITERS/MINUTE

SM SHEET METAL

SP STATIC PRESSURE

SPEC SPECIFICATION

SS STAINLESS STEEL

STD STANDARD

TB THRUST BLOCK

TD TEMPERATURE DIFFERENCE

TEMP TEMPERATURE

TF TRANSFER FAN

TK TANK

T.O. TOP OF

TOD TOP OF DUCT

TOP TOP OF PIPE

TOS TOP OF STEEL (SUPPORT)

TPU THERMAL PROCESSING UNIT

TSTAT THERMOSTAT

TU TERMINAL UNIT

TYP TYPICAL

UF ULTRA FILTRATION UNIT

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

UR URINAL

V VOLT

VAC VACUUM

VAR VARIABLE

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VEL VELOCITY

VERT VERTICAL

VP VACUUM PUMP

VV VARIABLE VOLUME TERMINAL UNIT

VVR VARIABLE VOLUME REHEAT TERMINAL UNIT

W/ WITH

W WATT

WB WET-BULB

WBT WET-BULB TEMPERATURE

WC WATER CLOSET

W.C. WATER COLUMN

WP WEATHERPROOF

WS WATER SOFTENER

WTR WATER TEMPERATURE RISE

WTD WATER TEMPERATURE DROP

WX WET EXHAUST

XFMR TRANSFORMER

YD YARD

YR YEAR

Z ZONE

NOT FOR CONSTRUCTION

E D

ES

C

R

IP

TI

O

N R

EV

Sheet Number:

Proj No:

Sheet Title:

AP

PR

C

LI

EN

T:

PR

O

JE

C

T:

M

IL

TO

N -F

R

EE

W

AT

ER

A

R M

O R

Y

ENGINEER STAMP

KEEP AREA CLEAR FOR AHJ

APPROVAL STAMP

M

IL

TO

N

-F R

EE

W

AT

ER

, O R

EG

O

N

SO

U

TH

M

AI

N

S

TR

EE

T

O R

EG

O

N M

IL

IT

AR

Y

D

EP

AR

TM

EN

T

R

EQ

U

ES

T

FO

R P

R O

PO

SA

L

CC22065

E-001

ELECTRICAL

LEGEND,

ABBREVIATIONS,

& GENERAL NOTES

A

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 1/

JL

S

B

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 5/

JL

S

ELECTRICAL LEGEND

SYMBOL DESCRIPTION

ABBREVIATIONS

BLACK

BLUE

ABOVE 600V208/120V, 240/120V

ISO GROUND

CONDUCTOR

NEUTRAL

GROUND

PHASE B

PHASE C

PHASE A

GREEN

WHITE

GN/YL

BLUE

RED

BLACK

GN/ YL

YELLOW

ORANGE

BROWN

480/277V

GREEN

GRAY

RED

CONDUCTOR COLOR CODES

T

HP

HP

NL

2'x4' RECESSED FIXTURE

2'x4' RECESSED FIXTURE, EMERGENCY

2'x4' FIXTURE

2'x4' FIXTURE, EMERGENCY

1'x4' RECESSED FIXTURE

1'x4' RECESSED FIXTURE, EMERGENCY

1'x4' FIXTURE

1'x4' FIXTURE, EMERGENCY

2'x2' RECESSED FIXTURE

2'x2' RECESSED FIXTURE, EMERGENCY

2'x2' FIXTURE

2'x2' FIXTURE, EMERGENCY

4' STRIP FIXTURE

4' WALL MOUNTED FIXTURE

SURFACE OR PENDANT MOUNTED FIXTURE

RECESSED DOWNLIGHT FIXTURE

NIGHT LIGHT

TELEPHONE JACK, 4SQ BOX WITH SINGLE GANG MUD RING

MOUNT @ +18" AFF (1-CAT6A) UNO

TELE/DATA JACK, 4SQ BOX WITH SINGLE GANG MUD RING

MOUNT @ +18" AFF UNO (2-CAT6A) UNO

DATA JACK, 4SQ BOX WITH SINGLE GANG MUD RING

MOUNT @ +18" AFF UNO (2-CAT6A) UNO

TELEPOWER POLE (T=TELEPHONE, P=POWER, C=COMPUTER)

1,3

T

FSD

S Z Y

EMERGENCY WALL PACK

WALL MOUNTED EXIT SIGN

CEILING MOUNTED EXIT SIGN

DARKENED SEGMENT INDICATES NUMBER OF AND DIRECTION OF

EXIT FACE(S)

DIRECTIONAL ARROWS AS SHOWN ON EXIT FIXTURES

POLE MOUNTED FIXTURE

SITE BOLLARD FIXTURE

NONFUSED DISCONNECT SWITCH, AMPERAGE INDICATED,

SEE NOTE F.

FUSED DISCONNECT SWITCH, AMPERAGE INDICATED,

SEE NOTE F.

ENCLOSED CONTACTOR, MAGNETIC, AMPERAGE INDICATED,

SEE NOTES F AND G.

ENCLOSED STARTER, MAGNETIC, NEMA SIZE INDICATED,

SEE NOTES F AND G.

ENCLOSED STARTER, COMBINATION MAGNETIC, NEMA SIZE

INDICATED, SEE NOTES F AND G.

CURRENT TRANSFORMERS (WITH POTENTIAL TRANSFORMERS

WHERE REQUIRED)

J

J

J

D

WP

GFCI

IG

SINGLE RECEPTACLE (120V)

DUPLEX RECEPTACLE (120V)

DEDICATED DUPLEX RECEPTACLE (120V)

WEATHERPROOF RECEPTACLE

GROUND FAULT RECEPTACLE

ISOLATED GROUND RECEPTACLE

RECEPTACLE ABOVE COUNTER

HALF SWITCHED RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

FLUSH FLOOR RECEPTACLE, DUPLEX

SPECIAL EQUIPMENT RECEPTACLE

LOCKING RECEPTACLE

JUNCTION BOX

PULL (JUNCTION) BOX

UNDER FLOOR JUNCTION BOX

SINGLE-POLE SWITCH

SINGLE-POLE SWITCH WITH SWITCH LEG

DOUBLE-POLE SWITCH

THREE-WAY SWITCH

FOUR-WAY SWITCH

SWITCH WITH PILOT LIGHT

COMBINATION SWITCH/DUPLEX RECEPTACLE

LOW-VOLTAGE SWITCH, NUMBER AS NOTED

LOCKING SWITCH

SINGLE-POLE DIMMER SWITCH

SINGLE-POLE FLUORESCENT DIMMER SWITCH

KEY SWITCH

WEATHERPROOF SWITCH

TIME SWITCH

OCCUPANCY SENSOR

SWITCH WITH OCCUPANCY SENSOR

60A

TL

THERMOSTAT

HUMIDISTAT

PHOTOCELL

TIME CLOCK

PUSHBUTTON STATION

FIRE ALARM PULL STATION

SMOKE DETECTOR

HEAT DETECTOR, RATE OF RISE

DUCT DETECTOR

HORN

STROBE ONLY, CANDELA AS NOTED

MAGNETIC DOOR HOLDER

FIREFIGHTER COMMUNICATION JACK

FLOW SWITCH

TAMPER SWITCH

FIRE SMOKE DAMPER

CEILING MOUNTED SPEAKER/STROBE, CANDELA AS NOTED

HORN STROBE, STROBE CANDELA AS NOTED

FIRE ALARM CONTROL PANEL

ANNUNCIATOR PANEL

CONTROL

FIRE ALARM

J

GENERAL NOTES

A THIS IS A STANDARD LEGEND SHEET. SOME SYMBOLS OR ABBREVIATIONS MAY APPEAR

ON THIS SHEET AND NOT ON THE PROJECT DRAWINGS.

B CONDUIT RUNS MARKED WITH CROSSHATCHES INDICATE NUMBER OF #12 AWG

CONDUCTORS. CROSSHATCH WITH DOT INDICATES GROUND WIRE. SIZE CONDUIT

ACCORDING TO SPECIFICATIONS AND APPLICABLE CODES UNLESS OTHERWISE NOTED.

C TAG NUMBER DENOTES DEVICES ADDRESS.

D CONDUCTORS AND CONDUIT ARE SIZED ON BASIS OF COPPER, THHN-2/THWN-2.

CIRCUITS THROUGH 100A SIZED ON BASIS OF 60°C. CIRCUITS GREATER THAN 100A SIZED

ON BASIS OF 75°C, UNLESS NOTED OTHERWISE. CONDUIT SHALL BE EMT, UNLESS

NOTED OTHERWISE.

E MOUNT ALL EQUIPMENT PER SPECIFICATIONS UNLESS INDICATED OTHERWISE. REFER

TO PLAN DRAWINGS AND SECTIONS FOR MOUNTING HEIGHTS.

F ALL ENCLOSURES ARE NEMA 1 UNLESS INDICATED OTHERWISE:

3R = NEMA 3R, X = EXPLOSION PROOF

4X = NEMA 4X, WP = WEATHER PROOF

G SEE CONTROL DIAGRAMS FOR OPERATIONAL SCHEMATIC.

H LUMINAIRE SYMBOLS SHOWN ARE GENERIC GRAPHIC REPRESENTATIONS. REFER TO

LUMINAIRE SCHEDULE FOR SPECIFIC SOURCE, TYPE AND MOUNTING.

J CONDUIT AND WIREWAY ROUTING IS SCHEMATIC. FIELD ROUTE.

K ELECTRICAL CONTRACTOR SHALL PROVIDE (FURNISH AND INSTALL) ALL ELECTRICAL

COMPONENTS, SUPPORT AND TERMINATIONS UNLESS NOTED OTHERWISE.

L ELECTRICAL CONTRACTOR SHALL MAINTAIN UPDATED PANEL SCHEDULES DURING

PROJECT AND PROVIDE FINAL TYPE WRITTEN SCHEDULES AT END OF PROJECT TO

ENGINEER AND PLACE COPY IN POWER PANEL.

M CONTRACTOR SHALL WALK PROJECT AREA PRIOR TO BID. TIME AND MATERIALS

REQUIRED DUE TO DIFFICULTY OF ROUTING AND IMPACTS TO BUILDING CONSTRUCTION

THAT ARE VISIBLE AT TIME OF WALK SHALL BE INCLUDED IN FINAL BID SUBMISSION.

AREAS THAT CAN NOT BE VIEWED AT TIME OF BID SHALL BE SPECIFICALLY NOTED AND

EXCLUDED IN BID FOR CONSTRUCTION IN AWARD PROCESS.

N COORDINATE EQUIPMENT/ DEVICE LOCATIONS WITH ARCHITECTURAL DRAWINGS.

P DEMOLITION SHALL INCLUDE REMOVAL OF CONDUIT, WIRE, BOXES AND HANGER

SUPPORT BACK TO SOURCE.

Q LIQUID LEAK DETECTION SYSTEM IS NOT PART OF THIS PROJECT. SYSTEM

INSTALLATION IS A DESIGN/ BUILD PROJECT DIRECTED BY THE OWNER.

R ALL BREAKERS INSTALLED SHALL BE RATED PER A.I.C RATING OF SYSTEM.

S ALL INTERCONNECTION CABLES WILL BE PROVIDED BY VENDOR, EXCEPT AS NOTED.

CONTRACTOR TO VERIFY INSTALLATION REQUIREMENTS.

T CONTRACTOR SHALL VERIFY ALL EQUIPMENT SUPPLIED FROM FACILITY POWER

SERVICE IS FED VIA A LOCKABLE BREAKER OR SWITCH, SIZED PER N.E.C. PROVIDE AS

REQUIRED.

U ROUTE GROUNDING CABLE TO NEAREST GROUND PAD.

V CONTRACTOR SHALL PROVIDE GROUNDING PER N.E.C. AND MANUFACTURER'S

REQUIREMENTS. REFER TO TOOL MANUAL AND VERIFY WITH EQUIPMENT SUPPLIER.

W REFERENCE FACILITY DATA MATRIX FOR POWER SOURCE DETAILS.

X CIRCUIT RACEWAYS MAY BE COMBINED. ADJUST CONDUCTOR SIZE AS NEEDED FOR

DERATING.

Y TRANSITION TO LIQUID-TITE FLEXIBLE CONDUIT AT TERMINATION TO EQUIPMENT TO

MINIMIZE VIBRATION TRANSMISSION.

Z CONTROLS SCOPE IS DESIGN-BUILD BY THE CONTROLS CONTRACTOR. DESIGN AND

INSTALLATION SHALL BE IN ACCORDANCE WITH DRAWINGS, SPECIFICATIONS AND

BUILDING CODES.

SPECIAL NOTE:

1 INTEGRATED EQUIPMENT RATING (IER) REFERS TO THE SHORT CIRCUIT RATING OF THE

ELECTRICAL COMPONENT THAT HAS THE LOWEST SHORT CIRCUIT RATING.

DH

FC

FS

TS

TC

F

CIRCUITRY AND RACEWAYS

OUTLETS

CONDUIT UP

CONDUIT DOWN

CONDUIT, CAP AND STAKE

HOME RUN (WITH CIRCUIT NUMBERS)

END OF CONDUIT RUN

"RUN CONTINUES" INDICATION

UNDERGROUND CONDUIT

1#12 GROUND

1#12 GROUND, ISOLATED

1#12 AWG HOT

1#12 AWG NEUTRAL

3#10 AWG CONDUCTORS (1 HOT, 1 NEUTRAL, 1 GROUND)

SWITCHED CONDUCTOR

WIREMOLD WITH RECEPTACLES AS NOTED

SERVICE AND EQUIPMENT

TRANSFORMER (KVA SHOWN)

PANELBOARD, FLUSH MOUNTED

PANELBOARD, SURFACE MOUNTED

UTILITY METER, AS REQUIRED

GROUND

CIRCUIT BREAKER, THERMAL MAGNETIC OR SOLID

TELEPHONE TERMINAL BOARD

CT

TTB

D

FACP

ANN

X

WALL MOUNTED STROBE ONLY, CANDELA AS NOTEDX

SYMBOL DESCRIPTION

SYMBOL DESCRIPTION

FIXTURES

MECHANICAL

SWITCHES

EBBH

MOTOR AND CONNECTION, HP AS NOTED

CEILING EXHAUST FAN

WALL TYPE EXHAUST FAN, HP AS NOTED

PIPE HEAT TRACE

ELECTRIC UNIT HEATER

ELECTRIC BASEBOARD HEATER

ELECTRIC TOEKICK HEATER

WATER HEATER

TELE/DATA

WH

PC

F a

P

LV

L

D

FD

K

WP

T

OC

WALL MOUNTED FIXTURE

VARIABLE FREQUENCY DRIVE WITH DISCONNECTVFD

M

T

H

H

#10

F

X

KVA?

#e

#l

EMERGENCY POWER OFF PUSHBUTTONEPO

S INTERCOM SPEAKER IN CEILING

SECURITY CAMERA (PAN, TILT, ZOOM)

SECURITY AND MISCELLANEOUS

SECURITY DEVICE:XX

GLASS BREAK MONITOR

CALL BUTTON

CARD READER

DOOR STATUS SWITCH

GB

CB

CR

DS

S INTERCOM SPEAKER, WALL MOUNTED

CCTV

P,T,Z

CEILING MOUNTED RECEPTACLES

120 SMOKE DETECTOR, 120V; P = PHOTOELECTRIC, PCM = COMBINATION

PHOTOELECTRIC CARBON MONOXIDE

WIRELESS ACCESS POINTWAP

ELECTRIC DOOR STRIKE

KEY PAD

LOG IN/LOG OUT

ES

KP

LILO

LOCAL DOOR ALARMLA

M MAG CONTACTOR, COIL OR CONTACT

MAX MAXIMUM

MBS MAINTENANCE BYPASS SWITCH

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCCB MOLDED CASE CIRCUIT BREAKER

MCP MOTOR CIRCUIT PROTECTOR

MDC MOTORIZED DAMPER CONTROL

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MLO MAIN LUGS ONLY MECHANICAL

MMP MECHANICAL MOUNTING PANEL

MO MOTOR OPERATOR

MS MOTOR STARTER

MSP MOTOR STARTER PANEL

MT,MTD MOUNTED

(N) NEW

N NEUTRAL

NA NON-AUTOMATIC

N.C. NORMALLY CLOSED

N.E. NORTH EAST

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

N.O. NORMALLY OPEN

NP NAMEPLATE

NTS NOT TO SCALE

N.W. NORTH WEST

OCB 115KV OIL CIRCUIT BREAKER

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

OL OVERLOAD RELAY

OO OVERLOAD

OOA ON-OFF-AUTO

OOR ON-OFF-REMOTE

OPD OPEN POLE DETECTOR

P POWER

PF POWER FACTOR

PL PILOT LIGHT

PB PUSHBUTTON SWITCH

PC PHOTOCELL

PCP PLANT CONTROL PANEL

PIN PERSONAL ID NUMBER

PIV POST INDICATOR VALVE

PNL PANEL

PQ POWER QUALITY

Ø, PH PHASE

PVC POLYVINYL CHLORIDE

QTY QUANTITY

R RATE OF RISE, RIGHT

(R) RELOCATE

RCPT RECEPTACLE

RCY RACEWAY

(RD) REDUNDANT

RF RADIO FREQUENCY

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RQD REQUIRED

RTM RUNNING TIME METER

RVNR REDUCED VOLTAGE NON-REVERSING

RVR REVERSING

S SPEAKER

S.C. SHORT CIRCUIT

SCP SECURITY CONTROL PANEL

S.E. SOUTH EAST

SEC SECONDS

SES SERVICE ENTRANCE SUBSTATION

SFEP SMOKE/FUME EXHAUST PANEL

SO SWITCH OPERATOR

SOL SLOW SPEED OL RELAY

SP SPARE

SS STAINLESS STEEL

ST SHUNT TRIP

STC SOURCE TRANSFER CONTROL

STD STANDARD

SUPP SUPPRESSOR

SUR SURFACE

SW SWITCH

S.W. SOUTH WEST

SWBD SWITCHBOARD

SWGR SWITCHGEAR

SYM SYMMETRICAL

SYNC SYNCHRONIZER

2S1W TWO SPEED, ONE WINDING

2S2W TWO SPEED, TWO WINDING

T TEMPORARY

TSTAT THERMOSTAT

TB TERMINAL BLOCK

TBD TO BE DETERMINED

TC TIME CLOCK

TDR TIME DELAY RELAY

TJB TERMINAL JUNCTION BOX

TS TAMPER SWITCH

TSP TWISTED SHIELDED PAIR

TYP TYPICAL

U UNDERGROUND

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLTMETER, VOLT

VA VOLT-AMPERE

VESDA VERY EARLY SMOKE DETECTION APPARATUS

VFD VARIABLE FREQUENCY DRIVE

VIB VERTICAL INSIDE BEND

VLF VERTICAL LAMINAR FLOW UNIT

VOB VERTICAL OUTSIDE BEND

VP VAPOR PROOF

VS VOLTMETER SWITCH

VT VOLTAGE TRANSFORMER

W WATT, WIRE

WHD WATTHOUR DEMAND

WP WEATHERPROOF

XFMR TRANSFORMER

Y WYE-CONNECTED

Z IMPEDANCE

ZSD UNBALANCED IMPEDANCE DETECTOR

A, AMP AMMETER, AMPERE

AB ABSOLUTE

AC ALTERNATING CURRENT

ACB AIR CIRCUIT BREAKER

AF AMPERE FRAME

AFD ADJUSTABLE FREQUENCY DRIVE

AFF ABOVE FINISHED FLOOR

AIC AMPS INTERRUPTING CURRENT

ANN ANNUNCIATOR

ARF ABOVE RAISED FLOOR

AS AMMETER SWITCH

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

ATX AUTO TRANSFORMER

AWG AMERICAN WIRE GAUGE

B BELL

BC BARE COPPER

BFF BELOW FINISHED FLOOR

BG BULK GAS

BKR BREAKER

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

BOC BOTTOM OF CONDUIT

BOD BOTTOM OF DUCT

BOP BOTTOM OF PIPE

BOT BOTTOM OF TRAY

BRN BUS REFERENCE NO. (ENGINEERING STUDY USE)

BT BASIC TRANSPONDER

C CONDUIT, COIL

CAP. CAPACITOR

CAT. # CATALOG NUMBER

CB CIRCUIT BREAKER

CC CONTROL CABLE

CCTV CLOSED CIRCUIT TELEVISION

CCT, CKT CIRCUIT

CLK CLOCK

CO CONDUIT ONLY

CONT CONTINUED

CPT CONTROL POWER TRANSFORMER

CR CORROSION RESISTANT

CRE CORROSION RESISTANT

CRS COATED RIGID STEEL CONDUIT

CRWP CLEANROOM WALL PANEL

CSFD COMBINATION SMOKE, FIRE DAMPER

CT CURRENT TRANSFORMER

(D) DEMOLISH

D DUCT

DB DUCT BANK

DC DIRECT CURRENT

DDC DIRECT DIGITAL CONTROL

DIA DIAMETER

DIV DIVISION

DWG DRAWING

Δ DELTA CONNECTED

E EMPTY

(E), EX EXISTING

ECS EMERGENCY COMMAND STATION

EDF ELECTRIC DRINKING FOUNTAIN

EEW ENERGIZED ELECTRICAL WORK

EG ENGINE GENERATOR

EL ELECTRICAL EMERGENCY

ELEC ELECTRICAL

EM, EMER EMERGENCY

EMH ELECTRICAL MANHOLE

EPO EMERGENCY POWER OFF

EMT ELECTRICAL METALLIC TUBING

ENT ELECTRICAL NON-METALLIC TUBING

EOL END-OF-LINE DEVICE

ERT EMERGENCY RESPONSE TEAM

ESD ELECTROSTATIC DISCHARGE

ESES EMERGENCY SERVICE ENTRANCE SUBSTATION

ET EXPANDED TRANSPONDER

ETM ELAPSED TIME METER

EWC ELECTRIC WATER COOLER

F FLUSH

(F) FUTURE

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FBO FURNISHED BY OTHERS

FCS FACILITY CONTROL SYSTEM

FDR FEEDER

FLR FLOOR

FOL FAST ACTING OL RELAY

FU FUSE

FWS FIRE WATER STORAGE

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

GND GROUND

GEN GENERAL

GFC GROUND FAULT CIRCUIT INTERRUPTER

GFR GROUND FAULT RELAY

GSM GAS SAFETY MONITOR

H HORN

HH HANDHOLE

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HVAC HEATING, VENTILATING & AIR CONDITIONING

HB HORIZONTAL BEND

HP HORSEPOWER

ICCB INSULATED CASE CIRCUIT BREAKER

I.D. IDENTIFICATION

IER INTEGRATED EQUIPMENT RATING

I&C INSTRUMENTATION AND CONTROL

IMC INTERMEDIATE METALLIC CONDUIT

I/O INPUT/OUTPUT

IS CURRENT SWITCH

J, JB JUNCTION BOX

K KEY INTERLOCK

KCMIL 1000 CIRCULAR MIL

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVAR

KW KILOWATT

KWH KILOWATT HOUR

L LEFT

LAN LOCAL AREA NETWORK

LC LIGHTING CONTACTOR

LTG LIGHTING

LV LOW VOLTAGE

LVR LOW VOLTAGE RELAY

COMM. KITCHEN

115A

CO

UNIT STORAGE

VAULT

CLASSROOM

MEN'S LOCKER

WOMEN'S LOCKER

VEST.

MEN'S

JANIT.

VEST.

WOMEN'S

MECH

RECRUITER

VESTIBULE

GEAR STORAGE

VEST

LACT.

FITNESS

AOT OFFICE

ASSEMBLY

FAMILY

1 SGT

IDF

VEST.

106B

ADMIN

102A

LOBBY

26x10

16x10

36x10

36x10

28x12 x1

"ø x1

14x12 12x10

12x6

12x6

12x6

6" ø

6" ø

"ø

"ø

8"ø

8"ø

"ø

6" ø

T

8" ø

TO FC-1

AND FC-2

TO FC-4

TO FC-5

16x10

10"ø

6x6

12x8

6x6 - S1

12x8

12x8

12x6

225 (TYP. 2)

12x6

12x6

12x6

12x6

32x12 x1

42x12

10"ø

24x12 26x14 x1

6x6

"ø

48x24

22"ø

14x10

38x38 x1

24x16

12x6

200 (TYP. 3)

24x10

12x8

18x10 x1

12x10 12x10

12x10

10"ø

12x6

22x10 - T1

12x6

250 (TYP. 5)

12x12

10x10

8x8

6x6

6x6

"ø

10x10

10x10

8x8

12x12

"ø

8" ø

26x10

8" ø

10"ø x1

10x6

130 (TYP. 3)

22x10

22x10

18x10

10"ø x6

16x16

22x10 - T1

RANGE HOOD

PROVIDED BY

OTHERS.

42x24

12x6

12x6

12x6

12x6

22x22

12x18

22x10

"ø

12x6 - E1

6x6

4" ø

18x12

4"ø

(TYP. 2)

x1

22x10

20x10 x1

38x16 14x10

18x30 x1

"ø

6" UP TO ROOF

A

145 36 278

B

C

D

E

F

22"ø

"ø

"ø

18x6 - S3

300 (TYP. 16)

22"ø

"ø

"ø

DUCT BLANK OFF AT

SHOWN LOCATION.

DUCT BLANK OFF AT

SHOWN LOCATION.

D

AT

E D

ES

C

R

IP

TI

O

N R

EV

Sheet Number:

Proj No:

Sheet Title:

AP

PR

C

LI

EN

T:

PR

O

JE

C

T:

M

IL

TO

N -F

R

EE

W

AT

ER

A

R M

O R

Y

ENGINEER STAMP

KEEP AREA CLEAR FOR AHJ

APPROVAL STAMP

M

IL

TO

N

-F R

EE

W

AT

ER

, O R

EG

O

N

SO

U

TH

M

AI

N

S

TR

EE

T

O R

EG

O

N M

IL

IT

AR

Y

D

EP

AR

TM

EN

T

R

EQ

U

ES

T

FO

R P

R O

PO

SA

L

CC22065

ME101

MECHANICAL/

ELECTRICAL

LEVEL 1

DEMOLITION PLAN

A

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 1/

JL

S

B

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 5/

JL

S

ME101

MECHANICA/ELECTRICAL LEVEL 1 DEMOLITION PLAN

NO

RT

H

0 16842

BAR SCALE

SCALE:

WHEN PRINTED ON SHEET

1/8" = 1'-0" 22"x34"

GENERAL NOTES

A SEE SHEET M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS,

AND GENERAL NOTES.

B SEE SHEET E-001 ELECTRICAL LEGEND, ABBREVIATIONS, &

GENERAL NOTES.

C PURGE ALL REFRIGERANT FROM VRF AND MINI-SPLIT SYSTEMS

AND DISPOSE IN ACCORDANCE WITH FEDERAL AND STATE LAWS.

D DEMOLISH EXISTING THERMOSTATS/SENSORS AND WIRING

BACK TO THE FAN COIL.

KEYED NOTES

1 REMOVE DISCONNECT AND CONDUIT BACK TO WALL. REMOVE

CONDUCTORS BACK TO THE PANEL.

2 DEMOLISH REFRIGERANT LINES BACK TO DISTRIBUTION BOXES.

DISCONNECT ELECTRICAL. MAINTAIN CONDENSATE PUMPS FOR

REUSE.

3 DEMOLISH DISTRIBUTION BOXES. DEMOLISH REFRIGERANT

PIPING TO VRF HEATPUMP UNITS ON THE ROOF. REMOVE

DISCONNECT, CONDUCTORS AND CONDUCTORS BACK TO THE

PANEL.

4 DEMOLISH EXHAUST FAN, DISCONNECT, CONDUIT AND

CONDUCTORS BACK TO THE PANEL.

5 DEMOLISH INDOOR DUCTLESS WALL UNIT. MAINTAIN CONDUIT

FOR POWER FEED TO THE ROOF. MAINTAIN REFRIGERANT

PIPING TO THE ROOF.

LEGEND

ITEMS TO BE DEMOLISHED

FC-5

5 3

FC-2

FC-1

DH-41

DH-21 DH-11

EF-3

FC-32

EF-1

FC-4

22'-5 5/8" 18'-11 5/8" 18'-0 1/4" 18'-0" 18'-0" 18'-4 1/2" 22'-10"

'-3

'-6

/2

'-3

'-4

'-1

DH-3 1

12x32 12x34 x1 x2

20x20

KITCHEN EXHAUST FAN

6" GOOSENECK

A

145 36 278

B

C

D

E

F

D

AT

E D

ES

C

R

IP

TI

O

N R

EV

Sheet Number:

Proj No:

Sheet Title:

AP

PR

C

LI

EN

T:

PR

O

JE

C

T:

M

IL

TO

N -F

R

EE

W

AT

ER

A

R M

O R

Y

ENGINEER STAMP

KEEP AREA CLEAR FOR AHJ

APPROVAL STAMP

M

IL

TO

N

-F R

EE

W

AT

ER

, O R

EG

O

N

SO

U

TH

M

AI

N

S

TR

EE

T

O R

EG

O

N M

IL

IT

AR

Y

D

EP

AR

TM

EN

T

R

EQ

U

ES

T

FO

R P

R O

PO

SA

L

CC22065

ME102

MECHANICAL/

ELECTRICAL

ROOF

DEMOLITION PLAN

A

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 1/

JL

S

B

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 5/

JL

S

ME102

MECHANICA/ELECTRICAL ROOF DEMOLITION PLAN

NO

RT

H

0 16842

BAR SCALE

SCALE:

WHEN PRINTED ON SHEET

1/8" = 1'-0" 22"x34"

GENERAL NOTES

A SEE SHEET M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS,

AND GENERAL NOTES.

B SEE SHEET E-001 ELECTRICAL LEGEND, ABBREVIATIONS, &

GENERAL NOTES.

KEYED NOTES

1 REMOVE DISCONNECT FROM UNIT AND LEAVE FOR NEW

EQUIPMENT.

2 REMOVE DISCONNECT AND CONDUIT TO BELOW ROOF. REMOVE

CONDUCTORS BACK TO THE PANEL.

LEGEND

ITEMS TO BE DEMOLISHED

RTU-1

RTU-1

2 ERV-1

HP-1

NOT FOR CONSTRUCTION

SOLAR AND

SATELLITE AREA

COMM. KITCHEN

115A

CO

UNIT STORAGE

VAULT

CLASSROOM

MEN'S LOCKER

WOMEN'S LOCKER

VEST.

MEN'S

JANIT.

VEST.

WOMEN'S

MECH

RECRUITER

VESTIBULE

GEAR STORAGE

VEST

LACT.

FITNESS

AOT OFFICE

ASSEMBLY

FAMILY

1 SGT

IDF

VEST.

106B

ADMIN

102A

LOBBY

26x10

16x10

36x10

36x10

28x12 x1

"ø x1

14x12 12x10

12x6

12x6

12x6

6" ø

6" ø

"ø

"ø

8"ø

8"ø

"ø

6" ø

8" ø

TO FC-1

AND FC-2

TO FC-4

TO FC-5

16x10

10"ø

6x6

12x8

6x6 - S1

12x8

12x8

12x6

225 (TYP. 2)

12x6

12x6

12x6

12x6

32x12 x1

24x12 26x14

6x6

"ø

48x24

22"ø

14x10

38x38

12x6

200 (TYP. 3)

24x10

12x8

18x10 x1

12x10 12x10

12x10

10"ø

12x6

22x10 - T1

12x6

250 (TYP. 5)

12x12

10x10

8x8

6x6

6x6

"ø

10x10

10x10

8x8

12x12

"ø

8" ø8" ø

10"ø x1

10x6

130 (TYP. 3)

22x10

22x10

18x10

10"ø x6

16x16

22x10 - T1

RANGE HOOD

PROVIDED BY

OTHERS.

42x24

12x6

12x6

12x6

12x6

22x22

12x18

22x10

"ø

12x6 - E1

6x6

4" ø

18x12

4"ø

(TYP. 2)

x1

22x10

14x10

18x30 x1

"ø

6" UP TO ROOF

A

145 36 278

B

C

D

E

F

22"ø

"ø

"ø

18x6 - S3

300 (TYP. 16)

22"ø

"ø

"ø

DUCT BLANK OFF AT

SHOWN LOCATION.

DUCT BLANK OFF AT

SHOWN LOCATION.

D

AT

E D

ES

C

R

IP

TI

O

N R

EV

Sheet Number:

Proj No:

Sheet Title:

AP

PR

C

LI

EN

T:

PR

O

JE

C

T:

M

IL

TO

N -F

R

EE

W

AT

ER

A

R M

O R

Y

ENGINEER STAMP

KEEP AREA CLEAR FOR AHJ

APPROVAL STAMP

M

IL

TO

N

-F R

EE

W

AT

ER

, O R

EG

O

N

SO

U

TH

M

AI

N

S

TR

EE

T

O R

EG

O

N M

IL

IT

AR

Y

D

EP

AR

TM

EN

T

R

EQ

U

ES

T

FO

R P

R O

PO

SA

L

CC22065

ME111

MECHANICAL/

ELECTRICAL

LEVEL 1 PLAN

A

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 1/

JL

S

B

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 5/

JL

S

ME111

MECHANICA/ELECTRICAL LEVEL 1 PLAN

NO

RT

H

0 16842

BAR SCALE

SCALE:

WHEN PRINTED ON SHEET

1/8" = 1'-0" 22"x34"

GENERAL NOTES

A SEE SHEET M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS,

AND GENERAL NOTES.

B SEE SHEET E-001 ELECTRICAL LEGEND, ABBREVIATIONS, &

GENERAL NOTES.

C PURGE ALL REFRIGERANT FROM VRF AND MINI-SPLIT SYSTEMS

AND DISPOSE IN ACCORDANCE WITH FEDERAL AND STATE LAWS.

D DEMOLISH EXISTING THERMOSTATS/SENSORS AND WIRING

BACK TO THE FAN COIL.

KEYED NOTES

1 PROVIDE DUCT TRANSITIONS AND CONNECT TO EXISTING

DUCTWORK.

2 PROVIDE NEW COMBUSTION AIR AND VENT PER

MANUFACTURER'S RECOMMENDATION. REPLACE EXISTING

CONDENSATE PUMP. CONNECT NATURAL GAS WITH SHUT-OFF

VALVE AND REGULATOR.

3 CONNECT NEW DUCTLESS UNIT TO EXISTING POWER,

REFRIGERANT PIPING AND CONDENSATE PIPING.

4 PATCH DUCT WHERE THE ELECTRIC DUCT HEATERS WERE

REMOVED.

5 THIS MECHANICAL CLOSET WILL NEED TO BE EXPANDED TO

HOUSE THE NEW FURNACE.

6 COORDINATE WITH NATURAL GAS SUPPLIER TO REPLACE THE

EXISTING METER WITH A 2-LBS METER. PROVIDE A REGULATOR

TO STANDARD PRESSURE ON THE BRANCH PIPING SERVING THE

KITCHEN AND MECHANICAL ROOM 116.

7 PATCH AND PAINT WALL TO MATCH EXISTING.

8 DUCTWORK EXTENDS THOUGH ROOF DECK.

(E) EF-3

22'-5 5/8" 18'-11 5/8" 18'-0 1/4" 18'-0" 18'-0" 18'-4 1/2" 22'-10"

'-2

'-7

/2

'-3

'-4

'-1

F-3

F-3

F-1

CAP DUCT

12"Ø-OSA

1 2

28"x14"-SA

CFM

RG-1 12"x12"

RTU-3

CFM

RG-1 36"x18" 1,475

14"x12"-RA

28"x10"-RA

CFM

EG-1 12"x12"

38"x20"-RA

24"x20"-SA

7 7

4 4

DS-1b

NOT FOR CONSTRUCTION

1 2

AutoCAD SHX Text T

KITCHEN EXHAUST FAN

6" GOOSENECK

A

145 36 278

B

C

D

E

F

D

AT

E D

ES

C

R

IP

TI

O

N R

EV

Sheet Number:

Proj No:

Sheet Title:

AP

PR

C

LI

EN

T:

PR

O

JE

C

T:

M

IL

TO

N -F

R

EE

W

AT

ER

A

R M

O R

Y

ENGINEER STAMP

KEEP AREA CLEAR FOR AHJ

APPROVAL STAMP

M

IL

TO

N

-F R

EE

W

AT

ER

, O R

EG

O

N

SO

U

TH

M

AI

N

S

TR

EE

T

O R

EG

O

N M

IL

IT

AR

Y

D

EP

AR

TM

EN

T

R

EQ

U

ES

T

FO

R P

R O

PO

SA

L

CC22065

ME112

MECHANICAL/

ELECTRICAL

ROOF PLAN

A

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 1/

JL

S

B

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 5/

JL

S

ME112

MECHANICA/ELECTRICAL ROOF PLAN

NO

RT

H

0 16842

BAR SCALE

SCALE:

WHEN PRINTED ON SHEET

1/8" = 1'-0" 22"x34"

GENERAL NOTES

A SEE SHEET M-001 FOR MECHANICAL LEGEND, ABBREVIATIONS,

AND GENERAL NOTES.

B SEE SHEET E-001 ELECTRICAL LEGEND, ABBREVIATIONS, &

GENERAL NOTES.

C STRUCTURAL ENGINEER TO PROVIDE ROOF FRAMING ANALYSIS

AND PROVIDE STRUCTURAL SUPPORT FOR THE NEW ROOF

MOUNTED UNITS. SEISMIC CONNECTION CALCULATIONS AND

ATTACHMENT DETAILS ARE ALSO TO BE PROVIDED.

KEYED NOTES

1 INSTALL UNIT AT EXISTING LOCATION. MOUNT EXISTING

DISCONNECT ON NEW EQUIPMENT.

2 EXTEND VTR TO 3' ABOVE THE NEW RTU OR RELOCATE 10' AWAY

FROM BOTH RTU INTAKES.

3 CONNECT NATURAL GAS TO UNITS WITH SHUT-OFF VALVES AND

PRESSURE REGULATORS.

4 NATURAL GAS PIPING DOWN THROUGH ROOF TO FURNACES

BELOW.

5 MOUNT CONDENSING UNITS ON 12" TALL ROOF CURBS.

6 PROVIDE NEW ELECTRICAL DISCONNECTS.

(E) RTU-1

22'-5 5/8" 18'-11 5/8" 18'-0 1/4" 18'-0" 18'-0" 18'-4 1/2" 22'-10"

'-2

'-7

/2

'-3

'-4

'-1

DS-1A

RTU-2

RTU-3

CU-1

CU-2

1"-NG

3/ 4"

-N G

CU-3

3/ 4"

-N G

1" -N

G

3/ 4"

-N G

1 1/2"-NG

HRV-1

10'-0"

'-9

VTR

EXISTING SOLAR

AND SATELLITE

AREA

NOT FOR CONSTRUCTION

4 5

6 6

E D

ES

C

R

IP

TI

O

N R

EV

Sheet Number:

Proj No:

Sheet Title:

AP

PR

C

LI

EN

T:

PR

O

JE

C

T:

M

IL

TO

N -F

R

EE

W

AT

ER

A

R M

O R

Y

ENGINEER STAMP

KEEP AREA CLEAR FOR AHJ

APPROVAL STAMP

M

IL

TO

N

-F R

EE

W

AT

ER

, O R

EG

O

N

SO

U

TH

M

AI

N

S

TR

EE

T

O R

EG

O

N M

IL

IT

AR

Y

D

EP

AR

TM

EN

T

R

EQ

U

ES

T

FO

R P

R O

PO

SA

L

CC22065

ME601

MECHANICAL/

ELECTRICAL

SCHEDULES

A

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 1/

JL

S

B

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 5/

JL

S

E D

ES

C

R

IP

TI

O

N R

EV

Sheet Number:

Proj No:

Sheet Title:

AP

PR

C

LI

EN

T:

PR

O

JE

C

T:

M

IL

TO

N -F

R

EE

W

AT

ER

A

R M

O R

Y

ENGINEER STAMP

KEEP AREA CLEAR FOR AHJ

APPROVAL STAMP

M

IL

TO

N

-F R

EE

W

AT

ER

, O R

EG

O

N

SO

U

TH

M

AI

N

S

TR

EE

T

O R

EG

O

N M

IL

IT

AR

Y

D

EP

AR

TM

EN

T

R

EQ

U

ES

T

FO

R P

R O

PO

SA

L

CC22065

ME602

MECHANICAL/

ELECTRICAL

SCHEDULES

A

R

FP

R

EV

IE

W D

R

AW

IN

G

S

/0 5/

JL

S

NOT FOR CONSTRUCTION

SERVICE ENTRANCE DISTRIBUTION BOARD 'MSB'

100A 3P

100A 3P

150A 3P

100A 3P

400A 3P

70A 3P

70A 3P

40A 3P

60A 3P

M

N E

L

ATS-EM1 (MER)

250A, 480Δ

G

100A

75 KW

BOND

MET.

C.W.

PIPE

GROUND

ROD

BOND

OTHER

METALLIC

PIPING

SUCH

AS

GAS

UTILITY

METER

UTILITY

TRANSFORMER

#3/0 CU

AVAILABLE FAULT CURRENT: 11,0004A

0A

SP

AC

E

0A

SP

AC

E

0A

SP

AC

E

0A

SP

AC

E

PANEL

L1

AFC:

9,889A

PANEL

P1

AFC:

9,889A

PANEL

P2

AFC:

10,117A

PANEL

P3

AFC:

3,200A

PANEL

M1

AFC:

10,508A

#8 CU

HP1-1 HP1-2 HP1-3

AFC: 293A AFC: 293A AFC: 293A

TVSS

LEAVE BREAKER

GENERAL NOTES

A SEE SHEET E-001 FOR LEGEND, ABBREVIATIONS, AND GENERAL

NOTES.

B

KEYED NOTES

1 REMOVE EXISTING BREAKER.

2 PROVIDE NEW BREAK. SIZE AS INDICATED.

REPLACE BREAKER, CONDUIT,

CONDUCTORS, AND

DISCONNECT FOR RTU-3

REPLACE BREAKER, CONDUIT,

CONDUCTORS, AND DISCONNECT

FOR RTU-2

ONE-LINE DIAGRAM

Sheets and Views
22065 G-001-Layout1
22065 M-001-Layout1
22065 E-001-Layout1
22065 ME101-Layout1
22065 ME102-Layout1
22065 ME111-Layout1
22065 ME112-Layout1
22065 ME601-Layout1
22065 ME602-Layout1

File details come from the government source that posted it. Updated .